City And County of San Francisco Office Of Contract Administration Purchasing Division Bid Proposal No. ITSF11000455/CD Attachment E Switchgear and Transformers for Calaveras Dam Replacement Project TECHNICAL SPECIFICATION FOR SHORT-CIRCUIT/ COORDINATION STUDY/ ARC FLASH HAZARD ANALYSIS PART 1 - GENERAL 1.01 DESCRIPTIONS A. The Contractor shall engage the services of an electrical engineer with qualifications specified in this attachment to conduct the short circuit/ coordination/arc flash hazard analysis study. The Contractor shall coordinate the scope of work specified under this attachment with other trades and other work. All equipment, materials, labor, and testing, which are not included in the services of the electrical engineer conducting the short circuit/ coordination/arc flash hazard analysis study shall be the responsibility of the Contractor and shall be included in the Contractor’s base bid. B. The objective of the study is to determine the optimal overcurrent protective device settings to ensure equipment will withstand fault current, to protect electrical equipment from damage, to size and set overcurrent protection devices such that in response to an electrical disturbance (short circuit, ground fault, overvoltage, etc.), the minimum amount of branches of the distribution system is removed from service, and to determine arc flash hazard, appropriate PPE and code compliant labeling. C. Short circuit ratings of all equipment shall not be less than 115% of calculated short circuit available. D. For purposes of clarity in this attachment, the term overcurrent protective devices refer to relays, circuit breakers, and fuses. The short circuit/ coordination/arc flash hazard analysis study is herein referred as the Study in this attachment. The party conducting the Study, is herein referred to as the Study Engineer. The Study shall include a system one-line diagram of the power system modeled with the utility and the existing portable generator power sources. The entire study package shall include: 1) short circuit calculation; 2) relay, circuit breaker and fuse coordination; 3) load flow; 4) equipment evaluation; and 5) arc flash analysis. Potential problem areas shall be identified and specific recommendations to mitigate these problematic areas shall be included. E. The short circuit calculation, load flow, equipment evaluation, and arc flash analysis studies shall include all portions of the electrical distribution system from the normal power source and the existing portable generator power source down to 120/208V and 120/240V panelboard and control panel level. The switching ITSF11000455/CD Attachment E – 1/17/2011 1 of 14 City And County of San Francisco Office Of Contract Administration Purchasing Division Bid Proposal No. ITSF11000455/CD Attachment E Switchgear and Transformers for Calaveras Dam Replacement Project transient analysis, motor starting analysis, and coordination study shall include all portions of the electrical distribution system from the normal and the existing portable generator power sources down to the 480V power distribution equipment level. The coordination study shall include coordination between the upper tiers of overcurrent protective devices and the smallest adjustable trip circuit breaker in the power distribution equipment such as switchgear, panelboard, control panel, etc. Normal system connections and those which result in maximum fault conditions shall be adequately covered in the five studies referenced in Article 1.01.D above. F. The Contractor shall perform field investigation to document as-built electrical distribution conditions and profile. The Study Engineer shall be responsible for all necessary research in existing drawings and specifications with respect to existing and new electrical equipment for a complete power system analysis. G. The Contractor shall coordinate a minimum of two meetings between the Study Engineer and the City Electrical Engineer through the City Representative for purposes of conducting the preliminary short circuit, load flow, and equipment evaluation studies. These meetings shall take place within 45 days after NTP or award of contract. H. After all the electrical distribution equipment and inter-equipment conduit and wiring runs have been installed in place, the Contractor shall refine the preliminary short circuit, load flow, and equipment evaluation studies referenced in Article 1.04.B of this attachment based on actual distance measure of conduit and wiring runs and electrical distribution equipment loading, and shall submit a final short circuit, load flow, and equipment evaluation studies for City’s review and approval. Around this time, the two other studies referenced in Article 1.01.D shall also be completed and submitted for City’s review and approval. After the Study Engineer has incorporated all the City comments on the five studies referenced in Article 1.01.D, he/she shall submit the final version of the five studies to the City for approval. The final and City approved version of these five studies is herein referred to as the Final Study. I. After the overcurrent protective device settings have been set in the field per the Final Study, and the overall electrical distribution system has been tested and certified by the NETA testing company, the Study Engineer shall submit a copy of the Final Study to PG&E for review and approval through the City Representative. This is intended for protective device coordination between utility and City owned distribution equipment. J. SKM Power Tools, latest version, is the only acceptable software for the power ITSF11000455/CD Attachment E – 1/17/2011 2 of 14 City And County of San Francisco Office Of Contract Administration Purchasing Division Bid Proposal No. ITSF11000455/CD Attachment E Switchgear and Transformers for Calaveras Dam Replacement Project system studies. K. 1.02 RELATED DOCUMENTS A. 1.03 Overcurrent protective device setting sheets for all protective devices shall be submitted with recommended settings documented by the Study Engineer based on the Study. The cover sheet for this set shall be stamped and signed by a California professional electrical engineer with current registration. Electronic file of the settings shall also be submitted. See attachments and appendices. REFERENCES A. Institute of Electrical and Electronics Engineers, Inc. (IEEE): 1. IEEE 141 – Recommended Practice for Electric Power Distribution and Coordination of Industrial and Commercial Power Systems 2. IEEE 242 – Recommended Practice for Protection and Coordination of Industrial and Commercial Power Systems IEEE 399 – Recommended Practice for Industrial and Commercial Power System Analysis 3. B. 4. IEEE 241 – Recommended Practice for Electric Power Systems in Commercial Buildings 5. IEEE 1015 – Recommended Practice for Applying Low-Voltage Circuit Breakers Used in Industrial and Commercial Power Systems 6. IEEE 1584 – Guide for Performing Arc-Flash Hazard Calculations American National Standards Institute (ANSI): 1. ANSI C57.12.00 – Standard General Requirements for Liquid-Immersed Distribution, Power, and Regulating Transformers 2. ANSI C37.13 – Standard for Low Voltage AC Power Circuit Breakers Used in Enclosures 3. ANSI C37.010 – Standard Application Guide for AC High Voltage Circuit Breakers Rated on a Symmetrical Current Basis ITSF11000455/CD Attachment E – 1/17/2011 3 of 14 City And County of San Francisco Office Of Contract Administration Purchasing Division Bid Proposal No. ITSF11000455/CD Attachment E Switchgear and Transformers for Calaveras Dam Replacement Project C. 1.04 4. ANSI C 37.41 – Standard Design Tests for High Voltage Fuses, Distribution Enclosed Single-Pole Air Switches, Fuse Disconnecting Switches and Accessories 5. ANSI C37.5 – Methods for Determining the RMS Value of a Sinusoidal Current Wave and Normal-Frequency Recovery Voltage, and for Simplified Calculation of Fault Currents The National Fire Protection Association (NFPA): 1. NFPA 70 - National Electrical Code, latest edition 2. NFPA 70E - Standard for Electrical Safety in the Workplace SUBMITTALS A. Provide Study Engineer’s credentials, resume, sample reports and three references. The three references shall confirm the equivalent system study competency of the Study Engineer, and his/her past experience in preparing short circuit/coordination/arc flash hazard analysis study in projects related to the water/wastewater industry. Current contact information for the references is required. For the reasons stated above this submittal is required within 30 days of NTP or award of contract. B. Since the short-circuit study is required to confirm the ratings of the proposed electrical distribution equipment, preliminary short circuit, load flow, and equipment evaluation studies are required within 60 days of NTP or award of contract. The Preliminary Report, which shall include a formal available fault duty letter from PG & E dated after NTP, shall contain sufficient study data based on which selection of devices and equipment is possible. The preliminary short circuit, load flow, and equipment evaluation studies shall be prepared with completeness and accuracy to allow the reviewer to use this Study to verify ratings of all electrical equipment submittals. C. The preliminary short circuit, load flow, and equipment evaluation studies shall go through two study report iterations. Each submittal iteration report shall be subject to review for minimum standards and completeness, and shall include all the sections described in Article 2.04. Additional iterations may be necessitated by incomplete single line diagram data or use of unacceptable assumptions. 1. ITSF11000455/CD Attachment E – 1/17/2011 Study #1 shall include short circuit analysis, load flow, and equipment 4 of 14 City And County of San Francisco Office Of Contract Administration Purchasing Division Bid Proposal No. ITSF11000455/CD Attachment E Switchgear and Transformers for Calaveras Dam Replacement Project evaluation. 1.05 Study #2 shall update Study #1 to address all City review comments. 3. See Article 1.06 for meetings held between the Study Engineer and the City Electrical Engineer in the course of preparing Study #1 and #2. D. Pursuant to Article 1.01.K, the Study shall provide complete overcurrent protective device setting sheets. Sheets shall include study recommended overcurrent protective device settings. E. Pursuant to Article 1.01.H, the Study Engineer shall submit the Final Study to the City Representative. The Final Study shall reflect not only all the changes and revisions made to the studies by the Study Engineer, but also all the settings implemented in the field on the circuit breakers and fuses by the Contractor, and all the relay settings and programming performed on the relays by the representative from the relay company. F. Two CD’s containing all the study work including all libraries used. QUALIFICATIONS A. 1.06 2. The Study Engineer performing the coordination study shall be currently involved in medium-and low-voltage power system analysis. The Study Engineer shall be an electrical engineer licensed in the State of California with current registration. He/she shall have a minimum of ten (10) years experience working in power system analysis, and shall provide a resume, a list of projects performed, references and three sample project reports. The Study Engineer shall have experience conducting short circuit/coordination/arc flash hazard analysis study in the water/wastewater industry. He/she shall be very experienced in SKM program modeling and shall have experience working with SEL relays. Each of the sample projects shall be presented in SKM format and shall include settings for at least three different models of SEL relays. The Final Study referenced in Article 1.01.H shall be stamped and signed by the Study Engineer. MEETINGS A. City representatives and Study Engineer shall meet two times to plan study details and evaluate progress for purposes of developing the preliminary short circuit, load flow, and equipment evaluation studies. ITSF11000455/CD Attachment E – 1/17/2011 5 of 14 City And County of San Francisco Office Of Contract Administration Purchasing Division Bid Proposal No. ITSF11000455/CD Attachment E Switchgear and Transformers for Calaveras Dam Replacement Project 1. 2. Initial Meeting a. After the Study Engineer has completed Study #1 referenced in Article 1.04.C.1, a meeting shall be held between the Study Engineer and the City Electrical Engineer through the arrangement by the City Representatives to discuss the completed Study #1. The City Electrical Engineer shall be given four weeks advanced time frame to review Study #1 before this initial meeting is held. b. Discuss City Electrical Engineer’s review comments on Study #1. Second Meeting a. After the Study Engineer has completed Study #2 referenced in Article 1.04.C.2 and incorporated the City Electrical Engineer’s review comments on Study #1, a meeting shall be held between the Study Engineer and the City Electrical Engineer to discuss the completed Study #2. The City Electrical Engineer shall be given four weeks advanced time frame to review Study #2 before this second meeting is held. b. The purpose of this meeting between the Study Engineer and the City Electrical Engineer is to finalize Study #2 so that it can be released to the Contractor for ordering electrical distribution equipment based on the short circuit rating recommended in the Study. B. Meetings will be held at 1155 Market Street, San Francisco, CA 94103, unless otherwise noted by the City Representative. Give three-weeks advanced notice to the City Representative before each proposed meeting date. C. It is the responsibility of the Contractor to pay for all their own travel expenses. PART 2 - PRODUCTS 2.01 DAPPER STUDIES A. The Study Engineer shall model the complete electrical distribution system per single line diagrams shown in the appendices. ITSF11000455/CD Attachment E – 1/17/2011 6 of 14 City And County of San Francisco Office Of Contract Administration Purchasing Division Bid Proposal No. ITSF11000455/CD Attachment E Switchgear and Transformers for Calaveras Dam Replacement Project 2.02 B. Load flow shall be run and results presented. C. Calculate short circuit interrupting and momentary (asymmetrical) duties for 3phase bolted fault, line to line fault, single line to ground fault at each medium voltage switchgear lineup, branch circuit panelboard, and other significant locations throughout the system. For ground fault current study include the associated zero sequence impedance data. Include in tabulations fault impedance, X to R ratios, asymmetrical values or factors from the manufacturer, motor contribution, short circuit KVA, and symmetrical and asymmetrical fault currents. D. Include complete fault calculations as specified herein for each proposed source combination. E. Use existing and proposed equipment characteristics to verify equipment ratings required. The Contractor shall quickly gather this information for timely approval of electrical equipment. Make all additions or changes as required by the City’s reviewer and prepare Study #1 and #2. F. Include fault contribution of all motors 1 hp and larger. Smaller size motors may be grouped. G. Notify the City Representative in writing of circuit protective devices and electrical equipment not properly rated for fault conditions. H. Perform Equipment Evaluation studies for equipment evaluation based on marginal/fail criteria required by the SKM Power Tools software as agreed with the City Representative. I. Use actual conductor impedances and lengths. If impedances are unknown, use typical conductor impedances from SKM for preliminary studies. J. Transformer design impedances and standard X/R ratios shall be used when nameplate values are not available. Final report shall show actual impedances. CAPTOR STUDIES A. In order to select proper relay, circuit breaker and fuse characteristics as required for optimal coordination, the coordination study shall be performed for the electrical distribution equipment described in the project. All overcurrent protective device settings shall be based on the recommendations of the approved ITSF11000455/CD Attachment E – 1/17/2011 7 of 14 City And County of San Francisco Office Of Contract Administration Purchasing Division Bid Proposal No. ITSF11000455/CD Attachment E Switchgear and Transformers for Calaveras Dam Replacement Project Study #2. See Article 1.04.C for details. B. Coordination study shall include coordination between negative sequence overcurrent elements with phase overcurrent elements. Negative sequence relay settings shall be determined based on unbalanced fault study. C. Include on the curve sheets utility company short circuit contribution, mediumvoltage equipment relay characteristics, low-voltage equipment circuit breaker trip device and fuse characteristics, pertinent transformer characteristics, pertinent motor and existing portable generator characteristics, and characteristics of other system components. Include all overcurrent protective devices down to those in the 480V distribution level. D. Include all adjustable settings for ground fault protective devices. Include manufacturing tolerance and damage bands in plotted fuse characteristics. Show transformer full load and 150, 400, or 600 percent currents, transformer magnetizing inrush, ANSI transformer withstand parameters, and significant symmetrical and asymmetrical fault currents. Terminate device characteristic curves at a point reflecting the maximum symmetrical or asymmetrical fault current to which the device is exposed. E. Select each primary protective device required for a delta-wye connected transformer so that its characteristic or operating band is within the transformer characteristics, including a point equal to 58 percent of the ANSI withstand point to provide secondary line-to-ground fault protection. Where the primary device characteristic is not within the transformer characteristics, show a transformer damage curve. F. The coordination study shall address relay setting requirements with respect to utility company’s protection for the respective incoming service. G. Provide adequate time margins between device characteristics such that selective operation is provided, while providing proper protection. 1. Separate transformer primary protective device characteristic curves from associated secondary device characteristics by a 16 percent current margin to provide proper coordination and protection in the event of secondary line-to-line faults. 2. Separate medium-voltage relay characteristic curves from curves for other devices by at least a 0.4-second time margin. ITSF11000455/CD Attachment E – 1/17/2011 8 of 14 City And County of San Francisco Office Of Contract Administration Purchasing Division Bid Proposal No. ITSF11000455/CD Attachment E Switchgear and Transformers for Calaveras Dam Replacement Project 2.03 2.04 ARC FLASH HAZARD ANALYSIS A. The arc flash hazard analysis shall be performed according to the IEEE 1584 equations that are presented in NFPA70E-2009, Annex D. B. The flash protection boundary and the incident energy shall be calculated at all significant locations in the electrical distribution system (switchgears, panelboards) where work could be performed on energized parts. C. The Arc Flash Hazard Analysis shall include all medium voltage, 480V locations and locations in 240 volt and 208 volt systems fed from transformers equal to or greater than 125 kVA. D. Safe working distances shall be specified for calculated fault locations based on the calculated arc flash boundary with an incident energy of 1.2 cal/cm2. E. The Arc Flash Hazard analysis shall include calculations for maximum and minimum contributions of fault current magnitude. The minimum calculation shall assume that the utility contribution is at a minimum and shall assume a minimum motor load. Conversely, the maximum calculation shall assume a maximum contribution from the utility and shall assume motors to be operating under full-load conditions. F. Arc flash computation shall include both line and load side of main circuit breaker calculations, where necessary. G. Arc Flash calculations shall be based on actual overcurrent protective device clearing time. Maximum clearing time will be capped at 2 seconds based on IEEE 1584-2002, Section B.1.2. PRELIMINARY STUDY REPORT A. Provide the following: 1. 2. 3. 4. ITSF11000455/CD Attachment E – 1/17/2011 Calculation methods and assumptions. Selected base per unit quantities. Input data report. One-line diagram of the system being evaluated with available fault at each bus, and interrupting rating of devices noted. 9 of 14 City And County of San Francisco Office Of Contract Administration Purchasing Division Bid Proposal No. ITSF11000455/CD Attachment E Switchgear and Transformers for Calaveras Dam Replacement Project 5. 6. 7. 8. B. Calculate short-circuit momentary and interrupting duties for a three-phase bolted fault at each: 1. 2. 3. 4. 5. Electric utility’s supply termination point. Medium voltage switchgear. Existing portable generator. Branch circuit panelboards. At all locations where electrical equipment will be provided in the system, including all new control panel locations. C. For grounded systems, provide a bolted line-to-ground fault current study for areas as defined for the three-phase bolted fault short-circuit study. D. Protective Device Evaluation: 1. 2. 3. 4. 5. 2.05 Source impedance data, including electric utility system and motor fault contribution characteristics. Typical calculations. Tabulations of calculated quantities. Results, conclusions, and recommendations. Evaluate equipment and protective devices and compare to short circuit ratings. Adequacy of switchgear and panelboard bus bracing to withstand shortcircuit stresses. Adequacy of transformer windings to withstand short-circuit stresses. Cable sizes for ability to withstand short-circuit heating. CT sizing is appropriate for fault current and trip functions. COMPLETE STUDY REPORT A. The results of the power system study shall be summarized in a complete report. Three (3) bound copies each of Study #1 and Study #2 are required. Six (6) bound copies of the Final Study shall be submitted. B. SKM crystal reports shall be used. C. The Studies shall include all information specified in NETA Acceptance Testing Specifications for Electrical Power Distribution Equipment and Systems. D. The report shall include the following sections: ITSF11000455/CD Attachment E – 1/17/2011 10 of 14 City And County of San Francisco Office Of Contract Administration Purchasing Division Bid Proposal No. ITSF11000455/CD Attachment E Switchgear and Transformers for Calaveras Dam Replacement Project 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. E. Descriptions, purpose, basis and scope of the study. Executive Summary. Recommendations for system improvements, where needed. Load flow showing voltage drop at each bus, among other data. Equipment evaluation. Short circuit study. Coordination Study. Arc Flash Evaluation. Input data Two full size system complete single line diagrams in ANSI Size E drawings. Single line diagram shall show protective device ampere ratings and associated designations, cable size and length, transformer kVA and voltage ratings, motor and existing portable generator kVA and voltage ratings, and switchgear, and panel board voltage ratings and designations. Completed relay setting sheets. In the protective device coordination study section, provide time-current curves graphically indicating the coordination proposed for the system, centered on conventional, full-size, log-log forms. Include with each curve sheet a complete title and one-line diagram with legend identifying the specific portion of the system covered by that particular curve sheet. Utilize 11” X 17” sized paper to present the information on one sheet for each coordination thread. 1. Terminate device characteristic curves at a point reflecting maximum symmetrical or asymmetrical fault current to which device is exposed. 2. Include a detailed description of each protective device identifying its type, function, manufacturer, and time-current characteristics. Tabulate recommended device tap, time dial, pickup, instantaneous, and time delay settings. 3. Plot the following characteristics on the curve sheets, where applicable: a. b. c. d. e. ITSF11000455/CD Attachment E – 1/17/2011 Electric utility’s protective device. Medium voltage equipment relays. Medium and low voltage fuses including manufacturer’s minimum melt, total clearing, tolerance, and damage bands. Low voltage equipment circuit breaker trip devices, including manufacturer’s tolerance bands. Transformer full-load current, magnetizing inrush current, and ANSI transformer withstand parameters. 11 of 14 City And County of San Francisco Office Of Contract Administration Purchasing Division Bid Proposal No. ITSF11000455/CD Attachment E Switchgear and Transformers for Calaveras Dam Replacement Project f. g. h. i. j. Conductor damage curves. Ground fault protective devices. Pertinent motor starting characteristics and motor damage points. Pertinent existing portable generator short-circuit decrement curve and existing portable generator damage point. Other system load protective devices for the largest branch circuit and the largest feeder circuit breaker in each electrical distribution equipment such as panelboard. F. Arc Flash Section shall describe the calculation method used, flash protection boundary, hazard risk category and incident energy. Also, replicas of Arc Flash Labels for all electrical distribution gear in this project shall be included. G. Input Data: 1. 2. 3. 4. 5. Utility three-phase and line-to-ground available contribution with associated X/R ratios. Short-circuit reactance of rotating machines with associated X/R ratios. Cable type, construction, size, number per phase, length, impedance and conduit type. Transformer primary and secondary voltages, winding configurations, kVA rating, impedance, and X/R ratio. Reactor inductance and continuous ampere rating. PART 3 - EXECUTION 3.01 DATA COLLECTION A. Contractor shall solely be responsible for providing all the information needed to perform the power system analysis as described in this attachment to the Study Engineer. Contractor shall coordinate with Study Engineer to provide all the information needed by him/her. B. Contractor shall provide a complete set of data collection documents in the field. C. Contractor shall provide all data from the equipment manufacturer and confirm/correct all pertinent data, including cable type, length and configuration. The Contractor shall expedite collection of the data to eliminate unnecessary delays and assure completion of the studies as required for final approval of the distribution equipment shop drawings before release of the equipment from the factory. ITSF11000455/CD Attachment E – 1/17/2011 12 of 14 City And County of San Francisco Office Of Contract Administration Purchasing Division Bid Proposal No. ITSF11000455/CD Attachment E Switchgear and Transformers for Calaveras Dam Replacement Project D. 3.02 For existing equipment data the Contractor shall coordinate site visit(s) and investigate and obtain all pertinent field data to prepare the Study. Contractor shall engage the services of electricians, as needed, to investigate existing field conditions. ARC FLASH WARNING LABELS A. Provide a 3.5 inch x 5 inch thermal transfer type label of high adhesion polyester for each work location analyzed. B. The label shall have an orange header with the wording, “WARNING, ARC FLASH HAZARD”, or any other “DANGEROUS” sign required and shall include the following information: 1. 2. 3. 4. 5. 6. 7. 8. 9. Location designation. Nominal voltage. Flash protection boundary. Hazard risk category. Incident energy. Working distance. Engineering report number, revision number and issue date. Labels shall be machine printed, with no field markings. Arc flash labels shall be provided in the following manner and all labels shall be based on recommended over current device settings. C. Labels shall be field installed by the Contractor under the supervision of the Study Engineer. D. For the work locations not analyzed within the arc flash study such as landscape irrigation controller panels, auxiliary relay panels and any other panels that are powered by 120 volts, provide labels as shown below. Labels shall be a 3.5 inch x 2 inch thermal transfer type label of high adhesion polyester. Provide a minimum of 100 spare arc flash labels as shown below. ITSF11000455/CD Attachment E – 1/17/2011 13 of 14 City And County of San Francisco Office Of Contract Administration Purchasing Division Bid Proposal No. ITSF11000455/CD Attachment E Switchgear and Transformers for Calaveras Dam Replacement Project 3.03 DEVICE SETTING A. The Contractor shall be responsible for setting all overcurrent protective devices except relays per the recommended settings from the Study, and the representative from the relay manufacturer shall be responsible for programming/settings of all relays. The Study Engineer is required to supervise the on site settings of all overcurrent protective devices including the programming/ settings of all relays. The Study Engineer shall certify that all overcurrent protective devices are set per the Study. After the certification by the Study Engineer, the NETA testing company in the Electrical Equipment Commissioning and Technical Support attachment shall perform overall electrical distribution system testing and certify the passing of the NETA test before the plant is ready for energization. B. Pickup and time delays for overcurrent protective devices shall not be tested at minimum values. Test overcurrent protective devices at the final settings per the coordination study. END OF ATTACHMENT ITSF11000455/CD Attachment E – 1/17/2011 14 of 14