Datasheet - Amplicon

advertisement
Datasheet
Amplicon.com
IT and Instrumentation for industry
Sales: +44 (0) 1273 570 220 Website: www.amplicon.com Email: sales@amplicon.com
Datasheet
Online UPS : Zero Transfer Time
Absolutely no interruption of application when current is transferred to and from battery. Typically
UPS have a minimum of 4 milliseconds to transfer power but online UPS has no transfer time
allowing constant power to your system and equipment.
DS-B series offer the highest performance protection for servers, networking equipment,
telecommunication systems and other critical equipment. The double conversion online
topology protects against all brownouts, blackouts, voltage fluctuations and surges. True sinewave
output and zero transfer time ensures perfect protection.
Sinewave:
Represents energy entirely concentrated at a single frequency. The more
concentrated the energy is the
cleaner and safer the current will be.
There are four tower models and four
rackmount models from DS1000B to
DS3000RM to serve your every need.
Amplicon.com
IT and Instrumentation for industry
Sales: +44 (0) 1273 570 220 Website: www.amplicon.com Email: sales@amplicon.com
Datasheet
* Zero transfer time (online)
* Input voltage regulator = 80-144 VAC
for 100 / 110 / 120 VAC or 120-276 VAC for 220 / 230 / 240 VAC
* Smart fan speed control = saves more
power and minimizes noise
* 4 hours recharge time
* Cold start : Allows unit to be powered
without input power being available
* EPO port ready : emergency power off
switch
* SNMP card slot available
* Hot swappable / replaceable battery:
continuous operation even when
battery is being replaced
* Extended battery pack (optional)
* RS232 and USB port
* Full version of OPTI-Xtreme software
DS1000B
1PC+1LCD
DS1500B
1PC+1LCD
DS2000B
1PC+1LCD
DS3000B
1PC+1LCD
Amplicon.com
80 mins
90 mins
120 mins
140 mins
DS1000B-RM
1PC+1LCD
DS1500B-RM
1PC+1LCD
DS2000B-RM
1PC+1LCD
DS3000B-RM
1PC+1LCD
IT and Instrumentation for industry
Sales: +44 (0) 1273 570 220 Website: www.amplicon.com Email: sales@amplicon.com
80 mins
90 mins
120 mins
140 mins
Datasheet
DS1000B / DS1500B
DS2000B / DS3000B
DS-B
ON
120V
230V
120V
230V
DS2000B / DS3000B & battery pack
5-20A
* DS2000B
* DS2000B-RM
5-30A
FUNC
ENTER
ON/OFF
A
B
C
DS-B RM
ON
ON-BAT
ON-LINE
230V
A) Func
B) Enter
C) On / Off
DS2000B / DS3000B-RM
Amplicon.com
FAULT
A) Func
B) Enter
C) On / Off
DS1000B-RM / DS1500B-RM
120V
ON-BAT BYPASS
* DS3000B
* DS3000B-RM
120V
120V
ON-LINE
230V
IT and Instrumentation for industry
Sales: +44 (0) 1273 570 220 Website: www.amplicon.com Email: sales@amplicon.com
FAULT
FUNC
ENTER
ON/OFF
A
B
C
BYPASS
Datasheet
Model Name
DS1000B
Topology
On-battery Output Waveform
Number of Phase
INPUT
Maximum Capacity
Nominal Input Voltage
Input Voltage Regulation
Nominal Input Frequency
Input PFC
Input Short Protection
OUTPUT
Nominal Output Voltage
Output Voltage Regulation
Output T.H.D
High Efficiency Mode (AC to AC)
Crest Factor
Start on Battery
Auto Restart
Number of Outlets
DS1500B
DS2000B
DS3000B
True On-Line, Double Conversion
Sine Wave
Single Phase (2W+G)
1000VA / 700W
1500VA / 1050W
2000VA / 1400W
100/110/120Vac or 220/230/240Vac
80-144Vac or 160-276Vac
50Hz / 60Hz Auto Sensing
> 0.97@Full load
Circuit Breaker
3000VA / 2100W
100/110/115/120/127Vac or 208/220/230/240Vac (selectable)
Rated Voltage +/- 2%
< 3% T.H.D at Linear Load
92%
3:1
Yes
Yes
6 Battery backup (US)
12 Battery backup (US)
4 Battery backup (IEC)
9 Battery backup (IEC320 10A×8, IEC320 16A×1)
PROTECTION
Data Line Surge Protection
BATTERY
User Replaceable Battery
Typical Backup Time (Full / Half load) *
Recharge Time to 90%
Extended Battery Pack
ADVANCED WARNINGS / DIAGNOSTICS
Front Panel LEDs
Audible Alarms
COMMUNICATIONS INTERFACE
Communication Port
SNMP Manageable
ENVIRONMENTAL
Operation Temperature
Storage Temperature
Relative Humidity
Audible Noise
PHYSICAL
Dimensions (Physical / Packing)
(in)
(mm)
(L x W x H)
Weight (Net / Gross)
(lbs)
(kg)
RJ11 / RJ45
36V / 12V7.2AH x 3
72V / 12V34W x 3
6 / 18 min
72V / 12V7.2AH x 6
72V / 12V34W x 6
5 / 15 min
< 4 Hours
BP1000
BP1500
BP2000
BP3000
AC mode / On line / On battery / Bypass / Fault / Overload and 15 UPS Parameters
Battery mode / UPS fault / Overload
RS232 and USB
Yes
0o ~40o C / 32 o~104 oF
-20o~60 oC / -4o~140 oF
0~95% humidity, non-condensing
< 40 dBA (at 1 meter from surface of unit)
16.5 x 6 x 9.4 / 21.5 x 11 x 14
420 x 152 x 238 / 545 x 280 x 355
39 / 42.9
37.7 / 41.6
17.1 / 19
16.5 / 18.4
CONFORMANCE
Approvals
16.5 x 8.9 x 14.1 / 20.7 x 13.8 x 19.1
420 x 225 x 358 / 526 x 350 x 485
68.4 / 73.9
72.6 / 78.1
31.1 / 33.6
33 / 35.5
CE ; UL / cUL ; C-Tick, A-Tick ; GOST-R
Specifications are subject to change without notice.
* Backup time depends on power consumption of equipment attached and on UPS battery capacity. Numbers here are for reference only.
Win
Win
windows
windows
95/98
ME/NT
Amplicon.com
2000
XP/2003
IBM
IBM OS/2
IBM AIX
Novell Netware
Linux
FreeBSD
SUN Solaris
HP-UX
SGI Irix
IT and Instrumentation for industry
Sales: +44 (0) 1273 570 220 Website: www.amplicon.com Email: sales@amplicon.com
Datasheet
DS1000B-RM
Model Name
Topology
On-battery Output Waveform
Number of Phase
INPUT
Maximum Capacity
Nominal Input Voltage
Input Voltage Regulation
Nominal Input Frequency
Input PFC
Input Short Protection
OUTPUT
Nominal Output Voltage
Output Voltage Regulation
Output T.H.D
High Efficiency Mode (AC to AC)
Crest Factor
Start on Battery
Auto Restart
Number of Outlets
DS2000B-RM
DS3000B-RM
True On-Line, Double Conversion
Sine Wave
Single Phase (2W+G)
1000VA / 700W
1500VA / 1050W
2000VA / 1400W
100/110/120Vac or 220/230/240Vac
80-144Vac or 160-276Vac
50Hz / 60Hz Auto Sensing
> 0.97@Full load
Circuit Breaker
(kg)
RJ11 / RJ45
36V / 12V7.2AH x 3
36V / 12V34W x 3
6 / 18 min
72V / 12V7.2AH x 6
72V / 12V34W x 6
5 / 15 min
< 4 Hours
BP1000-RM
BP1500-RM
BP2000-RM
BP3000-RM
AC mode / On line / On battery / Bypass / Fault / Overload and 15 UPS Parameters
Battery mode / UPS fault / Overload
RS232 and USB
Yes
0o~40o C / 32 o~104oF
-20o~60oC / -4o ~140oF
0~95% humidity , non-condensing
< 40 dBA (at 1 meter from surface of unit)
16.9 x 16.7 x 3.3 / 21.7 x 21.5 x 8.1
425 x 428 x 84 / 552 x 546 x 206
41.5 / 48
40.9 / 47.4
18.4 / 21.7
18.2 / 21.5
25 x 16.8 x 3.3 / 29.5 x 21.6 x 8.6
635 x 428 x 84 / 750 x 550 x 220
69 / 74.3
71.5 / 78.5
31.6 / 33.8
32.5 / 35.7
CE ; UL / cUL ; C-Tick, A-Tick ; GOST-R
Specifications are subject to change without notice.
* Backup time depends on power consumption of equipment attached and on UPS battery capacity. Numbers here are for reference only.
Amplicon.com
3000VA / 2100W
100/110/115/120/127Vac or 208/220/230/240Vac (selectable)
Rated Voltage +/- 2%
< 3% T.H.D at Linear Load
92%
3:1
Yes
Yes
6 Battery backup (US)
4 Battery backup (US)
4 Battery backup (IEC)
5 Battery backup (IEC320 10A*4, IEC320 16A*1)
PROTECTION
Data Line Surge Protection
BATTERY
User Replaceable Battery
Typical Backup Time (Full / Half load) *
Recharge Time to 90%
Extended Battery Pack
ADVANCED WARNINGS / DIAGNOSTICS
Front Panel LEDs
Audible Alarms
COMMUNICATIONS INTERFACE
Communication Port
SNMP Manageable
ENVIRONMENTAL
Operation Temperature
Storage Temperature
Relative Humidity
Audible Noise
PHYSICAL
Dimensions (Physical / Packing)
(in)
(mm)
(L x W x H)
Weight (Net / Gross)
(lbs)
CONFORMANCE
Approvals
DS1500B-RM
IT and Instrumentation for industry
Sales: +44 (0) 1273 570 220 Website: www.amplicon.com Email: sales@amplicon.com
Download