C120N circuit-breakers B, C and D curves EN 60898/EN 61009: 10000 IEC 60947-2: 10 kA protect circuit protection function # protection of cables against overloads and short-circuits in final distribution # manual control and isolation # earth leakage protection when combined with a Vigi C120 module without temperature derating: compliance with standard: EN 61009 (refer to pages 90265/2) # remote tripping, indication, by adding auxiliaries common to the entire C60/C120 range (refer to pages 90142/2). description Technical data # current rating: 63 to 125 A # voltage rating Ue max.: 440 V AC # insulation voltage Ui: 500 V # impulse withstand voltage Uimp: 6 kV # compliance with standard EN 60898: devices accessible by unexperienced persons # breaking capacity: 5 as in EN 60898 # approval: IMQ # connection: 5 flexible cables: 1.5 to 35 mm2 5 rigid cables: 1 to 50 mm2 5 terminals ensure: type voltage (V) 230…400 1, 2, 3, 4P breaking cap. Icn (A) 10000 5 as in IEC 60947.2 (Icu) type voltage breaking cap. (V) Icu (kA) 1P 130 20 230…240 10 400…415 3 (1) 2, 3, 4P 230…240 20 400…415 10 440 6 (1) breaking capacity under 1 pole with IT isolated neutral system (case of double fault) # service breaking capacity Ics =75 % Icu # positive break indication # fast closing ensures simultaneous closing of poles # electrical durability: 5 63 A: 10000 cycles (O-C) 5 80…125 A: 5000 cycles (O-C) # limitation class: 3 # mechanical durability: 20000 cycles (O-C) # bistable fixing pawl: simplifies disassembly # weight (g): 1P 205 90260E.fm/2 2P 410 3P 615 4P 820 - degree of protection IP2 - tightening of wide cross-section cables - pull-out withstand of cables - automatic guiding of cable into the correct position # markers: 5 4 marker clips next to the upstream terminal 5 label holder on handle (2P, 3P, 4P) # degree of pollution: 3 (for use in an industrial environment) # degree of protection: 5 open or surface mounted device: IP2 5 in a Pragma or Prisma enclosure: IP4 (IPxxD) B curve # magnetic trip units operate between 3 and 5 In # protection of very long cables # protection of networks supplied by generators C curve # magnetic trip units operate between 5 and 10 In # protection of standard networks D curve # magnetic trip units operate between 10 and 14 In # protection of circuits that supply high inrush current loads: transformers, motors, etc. Updated: 5/07/01 Schneider Electric C120N circuit-breakers B curve EN 60898/EN 61009: 10000 IEC 60947-2: 10 kA protect circuit protection catalogue numbers type rating (A) catalogue number width in mod. of 9 mm 63 80 100 125 18340 18341 18342 18343 3 3 3 3 63 80 100 125 18344 18345 18346 18347 6 6 6 6 63 80 100 125 18348 18349 18350 18351 9 9 9 9 63 80 100 125 18352 18353 18354 18355 12 12 12 12 B curve C120N 1P 1 2 18340 2P 1 3 2 4 18344 3P 1 3 5 2 4 6 18349 4P 1 3 5 7 2 4 6 8 18355 Schneider Electric Updated: 5/07/01 90260E.fm/3 C120N circuit-breakers C curve EN 60898/EN 61009: 10000 IEC 60947-2: 10 kA protect circuit protection catalogue numbers type rating (A) catalogue number width in mod. of 9 mm 63 80 100 125 18356 18357 18358 18359 3 3 3 3 63 80 100 125 18360 18361 18362 18363 6 6 6 6 63 80 100 125 18364 18365 18367 18369 9 9 9 9 63 80 100 125 18371 18372 18374 18376 12 12 12 12 C curve C120N 1P 1 2 18356 2P 1 3 2 4 18360 3P 1 3 5 2 4 6 18365 4P 1 3 5 7 2 4 6 8 18377 90260E.fm/4 Updated: 5/07/01 Schneider Electric C120N circuit-breakers D curve EN 60898/EN 61009: 10000 IEC 60947-2: 10 kA protect circuit protection catalogue numbers type rating (A) catalogue number width in mod. of 9 mm 63 80 100 125 18378 18379 18380 18381 3 3 3 3 63 80 100 125 18382 18383 18384 18385 6 6 6 6 63 80 100 125 18386 18387 18388 18389 9 9 9 9 63 80 100 125 18390 18391 18392 18393 12 12 12 12 D curve C120N 1P 1 2 18378 2P 1 3 2 4 18385 3P 1 3 5 2 4 6 18389 4P 1 3 5 7 2 4 6 8 18393 additional information Schneider Electric auxiliaries: page 92142/2 accessories: page 91903/2 Vigi module: page 90265/2 discrimination table: page 92511/2 dimensions: page 90148/2 derating: page 92515/2 tripping curves: page 90180/2 Updated: 5/07/01 90260E.fm/5 C120 circuit-breaker choice tables services practical advice type current rating (A) maximum voltage rating Ue (V) AC DC minimum voltage rating Ue min (V AC-DC) insulation voltage Ui (V) impulse voltage Uimp (kV) number of poles breaking capacity AC EN 60898 (kA) Icn 230/400 V Ics IEC 60947.2 (kA) Icu 130 V 230…240 V 400…415 V 440 V Ics breaking capacity DC IEC 60947-2 Icu 24/48 V (1P) 125 V (1P) (kA)(2) 250 V (2P) fast closing isolation with positive break indication adaptable Vigi module auxiliaries OF-SD, OF+SD/OF MN, MX-OF Tm connection screwdriver Ø (mm) tightening torque(N.m) inlet dimension (mm) utilisation temperature (°C) storage temperature (°C) insulating material (1) (2) C120N C120H 63…125 440 125 V/pole 12 500 6 1 10…125 234 10 7.5 20 10 3(1) 1 10 234 15 7.5 30 15 4.5(1) 20 10 6 75 % Icu 50 % Icu 10 10 15 15 15 30 15 10 10 b b b b b b b b b b b b b b 6.5 mm maximum blade (POSIDRIV No. 2) 3.5 H x L: 10 x 10 -30 to + 60 -40 to + 70 self-extinguishing 960 °C 15 b b b b b b b b 1-pole breaking capacity in the unearthed neutral IT system (double fault) the number of poles participating in breaking is given between brackets type thermal magnetic trip units magnetic Im thermal In (A) setting current at 30 °C C120N C120H not interchangeable and not adjustable B C D curve 10 16 20 25 32 40 50 63 80 100 125 b b b b b b b b b b b b B b b b b b b b b b b b C b b b b b b b b b b b D b b b b b b b b b b b additional information 92603E_Ver2.1.fm/2 Updated: 14/12/04 Schneider Electric