MCCB Automatic Transfer Switches Legrand can supply Automatic Transfer Switches (ATS) for Moulded Case Circuit Breakers to suit your requirements. DISCOVER THE RANGES Available from 16 to 630A, Legrand Automatic Transfer switches accommodate DPX3 or DPX Moulded Case Circuit Breakers (3 Pole versions). They consist of two circuit breakers (motor-operated and fitted with 230V AC/DC shunt release) on a mechanical interlock plate, one control panel and one controller. Common loadside busbar can be ordered as an option. Automatic transfer switches are factory-assembled, pre-wired and tested by Legrand. They are to be ordered as one catalogue no. see opposite page. umain: present usec: absent Q1: closed Q2: open Q1: closed Temporisation S1: 0,5 to 120s umain: absent Q2: open Temporisation SC: 0,1 to 10s Automatic Transfer Switches (ATS) enable an automatic changeover from the main source of supply to a standby power supply in the event of power failure. yes umain: present? umain: absent? no no Applications: Hospitals yes Temporisation SC1: 3 to 120s Q1: open Airports Tunnels / infrastructures Back to normal umain: present Temporisation S: 0,5 to 120s Data centres Manufacturing plants no usec present? yes Q2: closed umain : absent usec : present Q1: open Q2: closed Example of algorithm for the functioning of an automatic transfer switch Key benefits: Automatic Transfer Switches are designed and developed by our R&D team. They are assembled and tested in our factory to guarantee the Legrand reknown quality. Pre-wired and fitted with connectors (plug-in type), they will enable quick installation and ensure a professional work for end-users. 102 Automatic transfer switches DPX3 / DPX MCCBs How to order 1 Basic transfer Switch 1 Control Panel Mechanical interlock between two MCCBs (BTS) Prewired and mounted on metal plate 1 2 1 Controller 3 Catalogue No. ATS 160 3P 25kA 25 = 1+2+3 MCCB frame size MCCB kA rating 3 pole Pack 1 1 1 1 1 1 1 Cat. No. ATS for DPX3 160 3P TM MCCBs with DPX3 160 25 kA breaking capacity ATS1603P25kA25 ATS for DPX3 160 3P/3P 25 kA 25A ATS1603P25kA40 ATS for DPX3 160 3P/3P 25 kA 40A ATS1603P25kA63 ATS for DPX3 160 3P/3P 25 kA 63A ATS1603P25kA80 ATS for DPX3 160 3P/3P 25 kA 80A ATS1603P25kA100 ATS for DPX3 160 3P/3P 25 kA 100A ATS1603P25kA125 ATS for DPX3 160 3P/3P 25 kA 125A ATS1603P25kA160 ATS for DPX3 160 3P/3P 25 kA 160A with DPX3 160 36 kA breaking capacity 1 1 1 1 1 ATS1603P36kA63 ATS1603P36kA80 ATS1603P36kA100 ATS1603P36kA125 ATS1603P36kA160 ATS ATS ATS ATS ATS for for for for for DPX3 DPX3 DPX3 DPX3 DPX3 160 160 160 160 160 3P/3P 3P/3P 3P/3P 3P/3P 3P/3P 36 36 36 36 36 kA kA kA kA kA 63A 80A 100A 125A 160A with DPX3 160 50 kA breaking capacity 1 1 1 1 1 ATS1603P50kA63 ATS1603P50kA80 ATS1603P50kA100 ATS1603P50kA125 ATS1603P50kA160 ATS ATS ATS ATS ATS for for for for for DPX3 DPX3 DPX3 DPX3 DPX3 160 160 160 160 160 3P/3P 3P/3P 3P/3P 3P/3P 3P/3P 50 50 50 50 50 kA kA kA kA kA 63A 80A 100A 125A 160A MCCB nominal current Pack Cat. No. 1 1 1 1 ATS2503P36kA100 ATS2503P36kA160 ATS2503P36kA200 ATS2503P36kA250 1 1 1 1 ATS2503P50kA100 ATS2503P50kA160 ATS2503P50kA200 ATS2503P50kA250 1 1 1 1 ATS2503P70kA100 ATS2503P70kA160 ATS2503P70kA200 ATS2503P70kA250 with DPX3 250 36 kA breaking capacity ATS for DPX3 250 3P/3P 36 kA 100A ATS for DPX3 250 3P/3P 36 kA 160A ATS for DPX3 250 3P/3P 36 kA 200A ATS for DPX3 250 3P/3P 36 kA 250A with DPX3 250 50 kA breaking capacity ATS for DPX3 250 3P/3P 50 kA 100A ATS for DPX3 250 3P/3P 50 kA 160A ATS for DPX3 250 3P/3P 50 kA 200A ATS for DPX3 250 3P/3P 50 kA 250A with DPX3 250 70 kA breaking capacity ATS for DPX3 250 3P/3P 70 kA 100A ATS for DPX3 250 3P/3P 70 kA 160A ATS for DPX3 250 3P/3P 70 kA 200A ATS for DPX3 250 3P/3P 70 kA 250A ATS for DPX 630 3P MCCBs 1 1 1 1 1 1 TM = Thermal Magnetic Note: 1. MCCBs fitted with 230V AC/DC Shunt release 2. Control Panel supplied with wire looms for quick plug-in connections with controller & BTS 3. Common loadside busbar available on request ATS for DPX3 250 3P TM MCCBs 1 1 with DPX 630 36 kA breaking capacity (TM) ATS6303P36kA400 ATS for DPX630 3P/3P 36 kA 400A ATS6303P36kA630 ATS for DPX630 3P/3P 36 kA 630A with DPX 630 70 kA breaking capacity (TM) ATS6303P70kA400 ATS for DPX630 3P/3P 70 kA 400A ATS6303P70kA630 ATS for DPX630 3P/3P 70 kA 630A with DPX 630 Electronic 36 kA breaking capacity ATS6303P36K400E ATS for DPX630 3P/3P 36 kA 400A Electronic ATS6303P36K630E ATS for DPX630 3P/3P 36 kA 630A Electronic with DPX 630 Electronic 70 kA breaking capacity ATS6303P70K400E ATS for DPX630 3P/3P 70 kA 400A Electronic ATS6303P70K630E ATS for DPX630 3P/3P 70 kA 630A Electronic 103