MO325-16 Manual Motor Starter Magnetic Only
The MO325-16 manual motor starter magnetic only is a 54 mm width device with a rated
operational current of Ie = 16.0 A. This device is used to manually switch on and off motors
and to protect them reliably and without the need for a fuse from short-circuits. The manual
motor starter magnetic only offers a rated service short-circuit breaking capacity Ics = 60 kA
at 400 VAC. Further features are the build-in disconnect function, trip-free mechanism and a
rotary handle with a clear switch position indication. The manual motor starter magnetic only
is suitable for three- and single-phase applications. Auxiliary contacts, signalling contacts,
undervoltage releases, shunt trips, 3-phase bus bars, power in-feed blocks are available as
accessory.
Categories
Products » Low Voltage Products and Systems » Circuit Breakers » Manual Motor Starters
Products » Low Voltage Products and Systems » Control Products » Manual Motor Starters » Manual Motor Starters
Ordering
Minimum Order Quantity:
Customs Tariff Number:
Replacement Product ID (NEW):
EAN:
1 piece
85362010
1SAM360000R1011
4013614302084
Container Information
Package Level 1 Width:
Package Level 1 Length:
Package Level 1 Height:
Package Level 1 Gross Weight:
Package Level 2 Units:
Package Level 2 Width:
Package Level 2 Length:
Package Level 2 Height:
Package Level 2 Gross Weight:
Package Level 2 EAN:
Package Level 1 Units:
92 mm
58 mm
78 mm
0.37 kg
24 piece
280 mm
395 mm
210 mm
0.61 kg
4013614495045
1 piece
Dimensions
Product Net Height:
Product Net Depth:
Product Net Weight:
Product Net Width:
87.5 mm
75.5 mm
0.34 kg
54 mm
Technical
Rated Ultimate Short-Circuit
Breaking Capacity (Icu):
Rated Instantaneous Short-Circuit
Current Setting (Ii):
Setting Range:
Rated Operational Voltage:
(230 V AC) 100 kA
(400 V AC) 60 kA
(440 V AC) 40 kA
(500 V AC) 25 kA
(690 V AC) 4 kA
240 A
None
Main Circuit 690 V AC
Main Circuit 440 V DC
Rated Operational Current (Ie):
16 A
Rated Operational Current AC-3 (Ie): 16 A
Rated Frequency (f):
Main Circuit 50 Hz
Main Circuit 60 Hz
Rated Impulse Withstand Voltage Main Circuit 6 kV
(Uimp):
Rated Insulation Voltage (Ui):
690 V
Power Loss:
at Rated Operating Conditions per Pole 1.7 W
Number of Poles:
3
Conventional Free-air Thermal
Current (Ith):
Degree of Protection:
Pollution Degree:
Electrical Durability:
Mechanical Durability:
Connecting Capacity Main Circuit:
Tightening Torque:
Wire Stripping Length:
Recommended Screw Driver:
Mounting Position:
Actuator Type:
Contact Position Indication:
Mounting on DIN Rail:
Standards:
Remarks:
Rated Service Short-Circuit
Breaking Capacity (Ics):
Main Circuit 16 A
IP20
3
50000 cycle
100000 cycle
Flexible with Ferrule 1/2x 0.75 ... 4 mm²
Flexible with Insulated Ferrule 1/2x 0.75 ... 4 mm²
Flexible 1/2x 1 ... 6 mm²
Rigid 1/2x 1 ... 6 mm²
Main Circuit 1.4 N·m
Main Circuit 10 mm
M3.5
Pozidriv 2
Position 1 to 6
Rotary Handle
ON / OFF
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
IEC/EN 60947-1
IEC/EN 60947-2
IEC/EN 60947-4-1
UL 508
CSA 22.2 No. 14
For overload protection of the motors, an appropriate thermal or electronic overload relays
must be used
(230 V AC) 100 kA
(400 V AC) 60 kA
(440 V AC) 40 kA
(500 V AC) 25 kA
(690 V AC) 4 kA
Environmental
Ambient Air Temperature
Compensation:
Maximum Operating Altitude
Permissible:
Resistance to Shock acc. to IEC
60068-2-27:
Resistance to Vibrations acc. to IEC
60068-2-6:
RoHS Status:
Ambient Air Temperature:
No
2000 m
11 ms Pulse 15g
5g / 10 ... 150 Hz
Following EU Directive 2002/95/EC August 18, 2005 and amendment
Around the Enclosure 0 ... +40 °C
Operation -25 ... +50 °C
Storage -50 ... +80 °C
Technical UL/CSA
Horsepower Rating UL/CSA:
Ampere Rating UL/CSA:
Connecting Capacity Main Circuit
UL/CSA:
Tightening Torque UL/CSA:
Maximum Operating Voltage
UL/CSA:
(220 ... 240 V AC) Three Phase 5 Hp
(440 ... 480 V AC) Three Phase 10 Hp
(550 ... 600 V AC) Three Phase 10 Hp
16 A
Flexible 1/2x 14-8 AWG
Stranded 1/2x 14-8 AWG
Main Circuit 14 in·lb
Main Circuit 600 V AC
Certificates and Declarations (Document Number)
Instructions and Manuals:
CB Certificate:
CCC Certificate:
cUL Certificate:
cULus Certificate:
Data Sheet, Technical Information:
Declaration of Conformity - CE:
DNV Certificate:
GL Certificate:
GOST Certificate:
LR Certificate:
RINA Certificate:
1SAM107011P0003
1SAA918000-2002
1SAA918000-3806
cUL_E137861
E137861
2CDC130002C0206
1SAD938506-0037
1SAA918000-0305
1SAA918000-0403
1SAA918000-2703
1SAA918000-0503
1SAA918000-0803
RMRS Certificate:
RoHS Information:
UL Certificate:
1SAA918000-0703
1SAA918001-4401
UL_E137861
Classifications
ETIM 4:
ETIM 5:
ETIM 6:
eClass:
UNSPSC:
Object Classification Code:
EC000074 - Motor protective circuit-breaker
EC000074 - Motor protective circuit-breaker
EC000074 - Motor protection circuit-breaker