SERIES DS-3 11.2 K-FACTOR DRY TYPE SPRINKLERS (TY5339) The FIRST Extended Coverage Ordinary Hazard (ECOH) Dry Sidewall F EATURES & B ENEFITS N Largest Throw Pattern (20 ft.) Dry Sidewall for Ordinary Hazard N Protect Loading Dock Overhangs, with a Roof Pitch up to 4 inches per foot (4:12) N Reduce Pipe, Fittings, Hangers and Labor Because of Fewer Branch Lines N Eliminate Dry Systems and Costly Anti-Freeze Loops MAXIMUM THROW N Maximum 12" Deflector Distance from the Ceiling 6" (150 mm) TO 12" (300 mm) CEILING TO TOP OF SPRINKLER DEFLECTOR DISTANCE GENERAL DESCRIPTION The DS-3 provides protection of areas up to 16 ft. x 20 ft. (320 ft.2), as compared to standard coverage horizontal sidewall sprinklers having a maximum coverage of 10 ft. x 10 ft. (100 ft. 2) for ordinary hazard occupancies. Sprinkler Placement Under Slope Ceilings in Loading Docks TECHNICAL DATA Approvals: UL and C-UL Listed. . Series DS-3 Dry Type Sprinkler Coverage MAXIMUM COVERAGE AREA The Tyco® Series DS-3 Dry Type Extended Coverage Ordinary Hazard (ECOH) Horizontal Sidewall Sprinklers are intended for use in applications where the sprinklers and/or a portion of the connecting piping may be exposed to freezing temperatures (e.g., horizontal piping extensions through a wall to protect an unheated area of a building). The DS-3 is designed for extended coverage use in ordinary hazard (ECOH) occupancies per NFPA 13. 4/12 SLOPE MAXIMUM Maximum Working Pressure: 175 psi (12,1 bar) Inlet Thread Connection: 1" NPT (Standard) or ISO 7-R1 20 ft. Standard Sprinkler Coverage Temperature Ratings: 155°F/68°C – Red Bulb 200°F/93°C – Green Bulb Discharge Coefficient: K-factor is determined by the length of the DS-3 Dry Type Sprinkler. 10 ft. 10 ft.. 16 ft. MAXIMUM WIDTH Sidewall Sprinkler Discharge Pattern Comparison Finishes: Sprinkler – Natural Brass, Chrome Plated, White Polyester Escutcheon – Brass Plated, RChrome Plated, White Coated Always refer to the Technical Data Sheet TFP550 for complete description of all Listing & Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty. TYCO is a registered trademark of Tyco International Services GmbH, and is used under license by Tyco Fire & Building Products and its affiliates in the United States and other countries. S ERIES DS-3 O RDERING P ROCEDURE & S PECIFICATIONS Purchase Number to Indicate Horizontal Sidewall Dry Type Sprinkler Matrix P/N: 6 1 - X X X - X - X X X No. 161 163 171 173 151 153 SERIES DS-3 SELECTION Description Temp. Rating Flush Escutcheon (1"NPT) Flush Escutcheon (1"NPT) Extended Escutcheon (1"NPT) Extended Escutcheon (1"NPT) Without Escutcheon (1"NPT) Without Escutcheon (1"NPT) 155°F/68°C 200°F/93°C 155°F/68°C 200°F/93°C 155°F/68°C 200°F/93°C ORDERING PROCEDURE No. FINISH COMBINATIONS Sprinkler Escutcheon 1 4 9 0 Natural Brass Brass Plated White Polyester White Coated Chrome Plated Chrome Plated Chrome Plated White Coated (1). Dry Type Sprinklers are furnished based upon “Order Length” as measured per below diagrams. The measurement should be rounded to the nearest 1/4" increment. ORDER LENGTH (1) Example No. / Length 055 5.50" 082 8.25" 180 18.00" 187 18.75" 372 37.25" 480 48.00" DS-3 (TY5339) ECOH Dry Horizontal Sidewall with Flush Escutcheon Contact your local distributor for availability, and please specify the following: ORDER LENGTHS 2-1/4" to 45-1/4" (57,2 to 1149,4 mm) IN 1/4" (6,4 mm) INCREMENTS Model: DS-3/TY5339 2-3/4" DIA. (69,9 mm) 1" NPT, NOMINAL MAKE-IN 9/16" (14,3 mm) Sprinkler: ECOH Horizontal Sidewall Dry Type Sprinkler 2-3/4" ± 1/8" (69,9 ± 3,2 mm) 9/16" (14,3 mm) 3-11/16" DIA. (93,7 mm) K-factor: 11.2 Order Length: Order Length is determined by measuring the distance from the face of the wall to the face of the sprinkler fitting and the measurement is then rounded to the nearest 1/4" increment. SPRINKLER FITTING CENTERLINE OF WATERWAY FACE OF SPRINKLER FITTING FACE OF MOUNTING SURFACE DS-3 (TY5339) ECOH Dry Horizontal Sidewall with Extended Escutcheon Inlet Connection: 1" NPT or ISO 7-R1 ORDER LENGTHS 1" to 44" (25,4 to 1117,6 mm) IN 1/4" (6,4 mm) INCREMENTS Temperature Ratings: 155F°/68°C Red Bulb 200F°/93°C Green Bulb Use the above chart to determine the specific Part Number when ordering the DS-3 Series Dry Type Sprinklers. 9/16" (14,3 mm) 3-1/2" DIA. (88,9 mm) SPRINKLER FITTING CENTERLINE OF WATERWAY FACE OF SPRINKLER FITTING FACE OF MOUNTING SURFACE DS-3 (TY5339) ECOH Dry Horizontal Sidewall with no Escutcheon ORDER LENGTHS 5" to 48" (63,5 to 1219,2 mm) IN 1/4" (6,4 mm) INCREMENTS Refer to the D-3 Series price list for a complete listing of part numbers for sprinkler, parts and accessories. Note: A W-Type 8 wrench or its equivalent must be used when installing the DS-3 Series sprinklers. 2-3/4" DIA. (69,9 mm) 1" NPT, NOMINAL MAKE-IN 9/16" (14,3 mm) Sprinkler and/or Escutcheon Finish: Listed in the above part number ordering chart. Escutcheon Type: Flush and Extended and Plain Barrel 4" ± 1/8" (101,6 ± 3,2 mm) MINIMUM 2-1/4" (57,2 mm) DEFLECTOR TO MOUNTING SURFACE 1" NPT, NOMINAL MAKE-IN 9/16" (14,3 mm) SPRINKLER FITTING FACE OF SPRINKLER FITTING CENTERLINE OF WATERWAY 9/16" (14,3 mm) Tyco Fire & Building Products Technical Services Phone: 800-381-9312 Fax: 800-791-5500 www.Tyco-Fire.com Always refer to the Technical Data Sheet TFP550 for complete description of all Listing & Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty. All brand names, product names or trademarks belong to their respective owners. Tyco Fire & Building Products reserves the right to change product design and specifications without notice. Copyright © 2007 Tyco Fire Products LP. All rights reserved. Printed in USA / VIG / 5M / TF-2007036 07-07