Catalog Information

advertisement
Multi-I/O Units — Introduction — 900 MHz
Wireless I/O
WI-I/O 9 Multi I/O Units
Atransceiverisawirelessdevicemade
upofatransmitterandreceiver.Since
eachmodulecanmanagebothinputand
outputsignals,itcanbeusedtomonitor
transducers and control industrial
processes.Thismodulecanalsobeused
as a repeater to relay another wireless
device’stransmission,thusincreasing
theoverallrangeofthesystem.
Typical Applications
•Wirelessjunctionboxinaprocessplanttoconnecta
largenumberofsignalstootherpartsoftheplantandto
the plant control center
•SimpleRemoteTerminalUnit(RTU)inaSCADAsystem,
connecting sensors/instrumentation/process signals
inpumpstations,sub-stations,pipelineregulator
stations,etc.
•Machine-to-Machinewirelessconnectivityinfactories
• Short distance and long distance applications with
license-freeandlicensedproducts
•Multi-hoprepeaterfunctions–upto5intermediate
unitscanbeconfiguredinanyinput/outputlink
•Fourversionsavailable
•Anyinputonanyunitcanbewirelesslylinkedto
anyoutputonanotherunit.Inputscanbelinkedto
multiple outputs.
•Inputsandoutputscanbeaddedviaadditional
serial units
•Theunitscanbepre-programmedtoconsideranalog
set-points,pulserateandpulsetotal,powersupply
voltage,powersupplyalarm
•Set-pointstatusgeneratedbycomparinganaloginputs
tohighandlowset-points.AvailableonAI1of-1units,
andAI1-4of-2units.
•Pulseinputsgenerateaseparatepulsecountvalueand
apulseratevalue.Pulseratesaretreatedasinternal
analogregisterswithaconfigurablemaximumvalue.
•Widevoltagepowersupply,withintegralUPSbattery
charger and solar regulator
•Powersupplygeneratesinternalsignalvalueswhich
canbetransmitted,lownormalsupplyvoltagestatus,
lowbatteryvoltagestatusandbatteryvoltage(analog)
•Multiplecommunicationfailurediagnosticswithoutput
status.Fail-to-transmitalarmandfail-to-receivealarm
status.
•RadioreceivessignalandbackgroundRFnoise
measurement / logging diagnostics
•Inputmeasurementdisplayandoutput“forcing”
diagnostics
• Communication logging diagnostics
•Easy-to-useE-SeriesWindowsconfigurationavailable
at www.weidmuller.ca or www.weidmuller.com
Features
•ClassI,Division2hazardousareasapproved
(USA/Canada);(CSAcertified)
•Multipleinputs/outputchannelsformonitoring
andcontrolfunctions
•Upto95wirelessunitspernetwork
• Each wireless unit can connect to input/output
expansion modules via RS485 multi-drop with up
to31expansionmodulesperwirelessunit
•Sensorsignalsconnectedatonemodule;input
signals are transmitted to another module where
the signals are re-created as output signals or
passedviaserialtoahostdevicesuchasaPLC
orSCADAsystem
28
Gas Analyzer
Metering
ALARM
PLC
Alarms
Plant
Control
Gauges
Multi-I/O Units — Introduction — 900 MHz
WI-I/O 9
-1
-2
-3
-4
Digitalinputs
Digitaloutputs
Analoginputs
Analogoutputs
Pulseinputs
Pulseoutputs
4
Voltage-freecontacts
1+3
Relay+FET
2
4-20mA
2
4-20mA
1
100Hz
1
100Hz
4
Voltage-freecontacts
1
FET
6
0-20mA/0-10V
0
4
1x1KHz,3x100Hz
0
0
Voltage-freecontacts
8
FET
0
4–16
Voltage-freecontacts
4-16
FET
0
8
0-20mA/0-10V
0
4
1x1KHz,3x100Hz
0
Note:Pulseanddigitalinputsaresameconnectionpoint. Wireless I/O
Multi-I/O Unit Ordering Information
4
1x1KHz,3x100Hz
4
1x1KHz,3x100Hz
FET=FieldEffectTransistor
Dimensions
6.57"
(167 mm)
• Regulatory Approvals: EMCFCCPart15,AS3548,
89/336/EEC,EN301489
• Certifications: CSAClassI,Division2hazardousareas
(USA/Canada)
• Housing:extrudedaluminumcase,5.1"x7.4"x2.4"
(130x188x60mm)withDIN-railmounting
• Removable terminals up to 2.5 mm2 (12 gauge) wires
• LED indication forpowersupply,modulestatus,
digital I/O
7.4"
(188 mm)
Inputs and Outputs*
Digital Inputs
2.16"
(55 mm)
2.4"
(60 mm)
5.1"
•Opto-isolated(5000V)inputssuitableforvoltage-free
contactsorNPNtransistor,contactwettingcurrent5mA
• Type-1 & -2 -fourinputs
• Type-4 - upto16inputs(4inputs+12selectableI/O).
The12selectableinputsaresurgeprotected,but
not isolated.
(130mm)
General
• Frequency:frequencyhoppingspreadspectrum
902-908MHz,sub-bandsconfigurable
• Power:transmitpower1W,approvedtoFCC
Part15.247,RSS210
• Sensitivity:receiverdatasensitivity–108dBm
• Max. Range (line-of-sight):USA/Canada-4W
ERP,20+miles.Othercountries-1WERP,15+km
depending on local conditions
• Data Rate: 19.2Kb/swithforward-errorcorrection
• Antenna Connector:SMAfemalecoaxial
• Temperature:-40to60°C/-40to140°F
• Humidity: 0-99%RH
Digital Outputs
• Type-1 - fourrelay,contacts,FormA,AC50V5A/DC
30V2A
• Type-2 - 1FEToutput30VDC500mA
• Type-3 - 8FEToutput30VDC500mA
• Type-4 - upto16FEToutput(4outputs+
12selectableI/O)
Analog Inputs
•“Floating”differentialinputs,commonmodevoltage
27V.24VDCforpoweringexternalloopsprovided.
Digitalfiltering1sec.
• Type-1 - two4-20mAresolution15-bit,accuracy0.1%
(overrangeindication2-25mA)
• Type-2 - six0-20mAresolution12-bit,accuracy0.1%
(overrangeindication0-25mA)
*SeetableaboveforInput/Outputsummary
29
Multi-I/O Units — Introduction — 900 MHz
Wireless I/O
Analog Outputs
•Currentsinktocommon,max.loopvoltage27V,max.
loop resistance 1000 ohms
• Type-1 - two4-20mAresolution15-bit,accuracy0.1%
(overrangeindication0.5-25mA)
• Type-3 - eight0-20mAresolution12-bit,accuracy
0.1%(overrangeindication0-20.5mA)
Pulse Inputs
•Specificationsasperdigitalinputs,max.pulserate
100Hz,pulsewidthmin.5ms
• Type-1 - oneinput(DI1)
• Type-2 - fourinputs(DI1-4)-firstpulseinput(DI1)max.
1000Hz,pulsewidthmin.0.5ms
• Type-4 - fourinputs(DI1-4)-firstpulseinput(DI1)max.
1000Hz,pulsewidthmin.0.5ms
Pulse Outputs
•FET30VDC500mAmax.100Hz
• Type-1 - one
• Type-3 & -4 -four
Power Supply
• Battery Supply: 11.5-15.0VDC
• Normal Supply: 12-24VACor15-30VDC,overvoltage and reverse power protected
•Internalmonitoringofpowerfail,solarchargestatus
andbatteryvoltage.Thesevaluesmaybetransmittedto
remotemodulesformonitoring.
•InternalDC/DCconverterprovides24VDC150mAfor
analog loop supply
•Batterychargingcircuitincludedfor1.2-12AHrsealed
battery
•Solarregulatorfordirectconnectionofsolarpanel
(upto30W)andsolarbattery(100AHr)
Serial Port
•Aserialportcanbeusedtoconfiguretransceiversand
to hard wire one transceiver to another when desired.
This connection avoids the need to add wireless nodes
tocircumventimpenetrableobstructionsandprovidesa
redundantpathforcriticalapplications.
•RS232/RS485serialport9600baud,8bits,noparity,
1stopbit
•RS2329pinDB9femaleconnector
•RS485terminalconnections(max.cabledistance
2000m)
30
Muti-I/O Units — 900 MHz
C
WI-I/O 9-2
Wireless I/O
WI-I/O 9-1
C1D2
US
Technical Data
Inputs
Digital:opto-isolated(5000V)inputssuitablefor
voltagefreecontactsorNPNtransistor,contact
wettingcurrent5mA
Analog:“floating”differentialinputs,commonmode
voltage27V,24VDCforpoweringexternalloops
provided,digitalfiltering1sec.
Pulse:asperdigitalinputs,
Maxpulserate100Hz,pulsewidthmin5ms
fourinputs
fourinputs
two4-20mAresolution15bit,
accuracy 0.1%
six0-20mA/0-10Vresolution12bit,
accuracy 0.1%
oneinput(DI1)
fourinput(DI1-4)-firstpulseinput(DI1)max1000Hz,
pulse width min 0.5ms
4(1RelayFormA,AC,50V5A/DC30V2A;3FET)
two4-20mAresolution15bit,accuracy0.1%
oneFEToutput30VDC500mA
Outputs
Digital
Analog:currentsinktocommon,maxloopvoltage
27V,maxloopresistance1000ohms
Pulse:FET30VDC500mAmax100Hz
one
Power Supply
Batterysupply
Normalsupply
Batterychargingcircuit
Solar regulator
Internal monitoring
Notes
11.5-15.0VDC
12-24VACor15-30VDC,over-voltageand
reverse power protected
includedfor1.2-12AHrsealedbattery
fordirectconnectionofsolarpanel(upto30W)
andsolarbattery(100AHr)
powerfail,solarchargestatus,andbatteryvoltage
AninternalDC/DCconverterprovides24VDC150mA
foranalogloopsupply.
11.5-15.0VDC
12-24VACor15-30VDC,over-voltageand
reverse power protected
includedfor1.2-12AHrsealedbattery
fordirectconnectionofsolarpanel(upto30W)
andsolarbattery(100AHr)
powerfail,solarchargestatus,andbatteryvoltage
AninternalDC/DCconverterprovides24VDC150mA
foranalogloopsupply.
serialport9600baud,8bits,noparity,1stopbit
9pinDB9femaleconnector
maxcabledistance2000mterminalconnections
serialport9600baud,8bits,noparity,1stopbit
9pinDB9femaleconnector
maxcabledistance2000mterminalconnections
-40to60°C(-40to140°F)
0-99%RH
FCCPart15,AS3548,89/336/EEC,EN301489
Class1Div2
DIN-railmounting
Forpowersupply,WDT,digitalI/O
SMAfemalecoaxial
130x188x60(5.1x7.4x2.4)
-40to60°C(-40to140°F)
0-99%RH
FCCPart15,AS3548,89/336/EEC,EN301489
Class1Div2
DIN-railmounting
Forpowersupply,WDT,digitalI/O
SMAfemalecoaxial
130x188x60(5.1x7.4x2.4)
Type
Type
Serial Port
RS232/RS485
RS232connection
RS485 connection
General Data
Operating Temperature
Humidity
EMC Standards
Approvals
Mounting
LEDindication
Antennaconnector
Dimensions mm (in)
C
US
C
US
Ordering Data
Accessories:DB9Male-DB9FemaleSerialconfig.cable
WI-I/O 9-1
WI-CSER-905-9
Part No.
6720005000
6720005105
WI-I/O 9-2
WI-CSER-905-9
Part No.
6720005001
6720005105
31
Muti-I/O Units — 900 MHz
Wireless I/O
WI-I/O 9-3
C
WI-I/O 9-4
C1D2
US
Technical Data
Inputs
Digital:opto-isolated(5000V)inputssuitablefor
voltagefreecontactsorNPNtransistor,contact
wettingcurrent5mA
Analog:“floating”differentialinputs,commonmode
voltage27V,24VDCforpoweringexternalloops
provided,digitalfiltering1sec.
Pulse:asperdigitalinputs,
Maxpulserate100Hz,pulsewidthmin5ms
upto16inputs(4inputs+12selectableI/O)the12
selectableinputsaresurgeprotectedbutnotisolated
fourinput(DI1-4)-firstpulseinput(DI1)max1000Hz,
pulse width min 0.5ms
Outputs
Digital
Analog:currentsinktocommon,maxloopvoltage
27V,maxloopresistance1000ohms
Pulse:FET30VDC500mAmax100Hz
eightFEToutput30VDC500mA
eight0-20mAresolution12bit,accuracy0.1%
upto16FEToutput(4outputs+12selectableI/O)
four(DO1-4)
four(DO1-4)
11.5-15.0VDC
12-24VACor15-30VDC,over-voltage
and reverse power protected
includedfor1.2-12AHrsealedbattery
fordirectconnectionofsolarpanel(upto30W)
andsolarbattery(100AHr)
powerfail,solarchargestatus,andbatteryvoltage
AninternalDC/DCconverterprovides24VDC150mA
foranalogloopsupply.
11.5-15.0VDC
12-24VACor15-30VDC,over-voltage
and reverse power protected
includedfor1.2-12AHrsealedbattery
fordirectconnectionofsolarpanel(upto30W)
andsolarbattery(100AHr)
powerfail,solarchargestatus,andbatteryvoltage
AninternalDC/DCconverterprovides24VDC150mA
foranalogloopsupply.
serialport9600baud,8bits,noparity,1stopbit
9pinDB9femaleconnector
maxcabledistance2000mterminalconnections
serialport9600baud,8bits,noparity,1stopbit
9pinDB9femaleconnector
maxcabledistance2000mterminalconnections
-40to60°C(-40to140°F)
0-99%RH
FCCPart15,AS3548,89/336/EEC,EN301489
Class1Div2
DIN-railmounting
Forpowersupply,WDT,digitalI/O
SMAfemalecoaxial
130x188x60(5.1x7.4x2.4)
-40to60°C(-40to140°F)
0-99%RH
FCCPart15,AS3548,89/336/EEC,EN301489
Class1Div2
DIN-railmounting
Forpowersupply,WDT,digitalI/O
SMAfemalecoaxial
130x188x60(5.1x7.4x2.4)
Type
Type
Power Supply
Batterysupply
Normalsupply
Batterychargingcircuit
Solar regulator
Internal monitoring
Notes
Serial Port
RS232/RS485
RS232connector
RS485 connector
General Data
Operating Temperature
Humidity
EMC Standards
Approvals
Mounting
LEDindication
AntennaConnector
Dimensions mm (in)
C
US
C
US
Ordering Data
Accessories:DB9Male-DB9FemaleSerialconfig.cable
32
WI-I/O9-3
WI-CSER-905-9
Part No.
6720005002
6720005105
WI-I/O 9-4
WI-CSER-905-9
Part No.
6720005003
6720005105
Download