Overhead Lines
Bare Soft Draw Stranded Copper Conductors
Application : Soft drawn copper conductors are used for earthing electrical
systems and equipment, where high conductivity , flexibility and easy handing
during installation are required.
Specifications
Type : bare copper
standerd: IEC 60228.
conductor: soft annealed copper wires stranded
in succesive layers, in opposite direction, to form
the copper stranded conductor.
Packing: The soft drawn conductors are delivered
in coils of 100 m. or in non returnable wood drums
as stated in technical information.
Cable
Code
01c004C0000
01c006C0000
01c010C0000
01c016C0000
01c025C0000
01c035C0000
01c050C0000
01c070C0000
01c095C0000
01c120C0000
01c150C0000
01c185C0000
01c240C0000
01c300C0000
01c400C0000
01c500C0000
01c630C0000
Nominal Number & Approx.
Cross
Section
mm2
NR x mm
mm
4
7 x 0.84
2.5
6
7 x 1.03
3.1
10
7 x 1.33
4.0
16
7 x 1.68
5.0
25
7 x 2.11
6.3
35
7 x 2.48
7.5
50
19 x 1.76
8.8
70
19 x 2.12
10.6
95
19 x 2.48
12.5
120
37 x 2.00
14
150
37 x 2.22
15.6
185
37 x 2.48
17.5
240
61 x 2.22
20
300
61 x 2.48
22.4
400
61 x 2.82
25.4
500
61 x 3.17
28.6
630
91 x 3.00
31.95
DC Resistance: the d.c resistance
of soft annealed copper conductors
are based on 100 % conductivity at
20 0C with corresponding volume resistivity
0.17241 ohm.mm2/m. and temperature coefficient
of resistance at 20 0C per 0C equal 0.00393
Approx.
Max D.C
kg/km
35
53
88
140
221
306
419
607
831
1053
1298
1620
2141
2672
3455
4365
5475
ohm/km
4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.047
0.0366
0.0283
The above data is approximate and subject to manufacturing tolerance.
Delivery length tolerance is + 5 %
Other sizes and mutiple conductor cables are available upon request.
Overhead Lines
Bare Hard Draw Stranded Copper Conductors
Application : Hard drawn copper conductors are used for overhead lines
in transmission and distribution electrical networks.
Specifications
Type : bare Hard copper
standerd: DIN - 48201, Part 1.
conductor: Hard drawn copper wires stranded
in succesive layers, in opposite direction, to form
the copper stranded conductor.
Packing: The Hard drawn conductors are delivered
in non returnable wood drums
as stated in technical information.
Cable
Code
01c010C0000
01c016C0000
01c025C0000
01c035C0000
01c050C0000
01c050C0000
01c070C0000
01c095C0000
01c120C0000
01c150C0000
01c185C0000
01c240C0000
01c300C0000
01c400C0000
01c500C0000
01c630C0000
DC Resistance: the d.c resistance
of Hard drawn copper conductors
are based on 97 % conductivity at
20 0C with corresponding volume resistivity
0.1771 ohm.mm2/m. and temperature coefficient
of resistance at 20 0C per 0C equal 0.00381.
Nominal Number & Approx. Approx. Max D.C Calculated
Cross nominal wire overall conductor Resistance Breaking
Section
diameter diameter weight
at 20 0C
Load
mm2
NR x mm
mm
kg/km
ohm/km
KN
10
7 x 1.35
4.1
90
1.806
4.1
16
7 x 1.7
5.1
142
1.1385
6.5
25
7 x 2.1
6.3
217
0.7461
9.9
35
7 x 2.5
7.5
308
0.5264
14
50
7 x 2.11
9
444
0.3656
20.2
50
19 x 1.8
9
436
0.3759
19.8
70
19 x 2.1
10.5
593
0.2762
26.9
95
19 x 2.5
12.5
840
0.1949
38.1
120
19 x 2.8
14
1054
0.1554
47.8
150
37 x 2.25
16
1326
0.1238
60.1
185
37 x 2.5
17.5
1640
0.1003
74.2
240
61 x 2.25
20.2
2208
0.0753
99
300
61 x 2.5
22.5
2726
0.061
122.3
400
61 x 2.89
26
3643
0.0456
163.4
500
61 x 3.23
29.1
4550
0.0365
204.2
630
91 x 3.00
33.1
5475
0.0283
260
The above data is approximate and subject to manufacturing tolerance.
Delivery length tolerance is + 5 %
Other sizes and mutiple conductor cables are available upon request.
Overhead Lines
Bare Hard Draw Stranded All Aluminum Conductors (AAC)
Application : All aluminum conductors are used for overhead
lines in distribution electrical networks of relatively short spans.
Specifications
Type : (AAC).
standerd: DIN - 48201, Part 5. & BS
conductor: Hard drawn aluminum wires stranded
in succesive layers, in opposite direction, to form
the aluminum stranded conductor.
Packing: The AAC conductors are delivered
in non returnable wood drums
as stated in technical information.
Cable
Code
01c016A0000
01c025C0000
01c035A0000
01c050A0000
01c050A0000
01c070A0000
01c095A0000
01c120A0000
01c150A0000
01c185A0000
01c240A0000
01c300A0000
01c400A0000
01c500A0000
01c630A0000
DC Resistance: The D.C resistance
of Hard drawn aluminum conductors
are based o volume resistivity of
0.028264 ohm.mm2/m. and temperature coefficient
of resistance at 20 0C per 0C equal 0.00403
Density: Density at 20 0C is 2.7 kg/m3
Nominal Number & Approx. Approx.
Cross nominal wire overall conductor
Section
diameter diameter weight
mm2
NR x mm
mm
kg/km
A - Acording To DIN 48201 Part 5
16
7 x 1.7
5.1
44
25
7 x 2.1
6.3
67
35
7 x 2.5
7.5
94
50
7 x 3.0
9
135
50
19 x 1.8
9
133
70
19 x 2.1
10.5
181
95
19 x 2.5
12.5
256
120
19 x 2.8
14
322
150
37 x 2.25
15.7
406
185
37 x 2.5
17.5
501
240
61 x 2.25
20.2
670
300
61 x 2.5
22.5
827
400
61 x 2.89
26
1105
500
61 x 3.23
29.1
1381
630
61 x 2.96
32.6
1733
The above data is approximate and subject to manufacturing tolerance.
Delivery length tolerance is + 5 %
Other sizes and mutiple conductor cables are available upon request.
Max D.C Calculated
Resistance Breaking
at 20 0C
Load
ohm/km
KN
1.8017
1.1807
0.8331
0.5786
0.5949
0.4371
0.3084
0.2459
0.196
0.1587
0.1191
0.09649
0.0722
0.05781
0.04625
2.84
4.17
5.78
7.94
8.45
11.32
15.68
18.78
25.3
30.54
39.51
47.7
60.86
74.67
95.25
Overhead Lines
PVC Insulated Hard Draw Stranded Copper Conductors Type 8 & Type 16
For Overhead Lines
Application : used for overhead power lines when crossing
telecommunication lines. Type 8 is used for operating voltages that do not
exceed 650 volt between phases and type 16 where operating voltages
do not exceed 11 kv.
Specifications
Type : type 8 , type 16.
standerd: BS - 6485.
conductor: Hard drawn copper wires stranded
in succesive layers, in opposite direction, to form
the copper stranded conductor.
Insulation: stranded conductor are insulated
with alayer of extruded PVC compound type 1 as per
BS 6746, to form the insulated conductor.
Insulation colour: The color of the insulation
shall be black for type 8 and green for type 16.
Packing: The insulation conductors are delivered
in non returnable wood drums
as stated in technical information.
Cable
Code
01c010CP000
01c016CP000
01c025CP000
01c035CP000
01c050CP000
01c050CP000
01c070CP000
01c095CP000
01c120CP000
01c150CP000
01c185CP000
01c010CP000
01c016CP000
01c025CP000
01c035CP000
01c050CP000
01c050CP000
01c070CP000
01c095CP000
01c120CP000
01c150CP000
01c185CP000
DC Resistance: The D.C resistance
of hard drawn copper conductors
are based on 97 % conductivity at
20 0C with corresponding volume resistivity
0.1771 ohm.mm2/m. and temperature coefficient
of resistance at 20 0C per 0C equal 0.00381
Type 8
Nominal Number & Minimum Approx. Approx. Max D.C
Cross nominal wireInsulation overall conductor Resistance
Section
diameter Thickness diameter
weight
at 20 0C
mm2
NR x mm
mm
mm
kg/km
ohm/km
10
7 x 1.5
0.8
6.5
141
1.89
16
7 x 1.7
0.8
7.1
178
1.19
25
7 x 2.1
0.8
8.3
268
0.749
35
7 x 2.5
0.8
9.5
368
0.54
50
7 x 3.1
0.8
11.3
548
0.399
50
19 x 1.8
0.8
11
503
0.399
70
19 x 2.1
0.8
12.5
685
0.276
95
19 x 2.5
0.8
14.5
951
0.199
120
19 x 2.8
0.8
16.0
1180
0.158
150
37 x 2.25
0.8
17.8
1462
0.128
185
37 x 2.5
0.8
19.5
1790
0.102
Type 16
10
7 x 1.5
1.6
8.3
172
1.89
16
7 x 1.7
1.6
8.9
210.0
1.19
25
7 x 2.1
1.6
10.1
600.0
0.749
35
7 x 2.5
1.6
11.3
405
0.54
50
7 x 3.1
1.6
13.1
595
0.399
50
19 x 1.8
1.6
12.8
541
0.399
70
19 x 2.1
1.6
14.3
716
0.276
95
19 x 2.5
1.6
16.3
995
0.199
120
19 x 2.8
1.6
17.8
1228
0.158
150
37 x 2.25
1.6
19.5
1515
0.128
185
37 x 2.5
1.6
21.3
1845
0.102
The above data is approximate and subject to manufacturing tolerance.
Delivery length tolerance is + 5 %
Other sizes and mutiple conductor cables are available upon request.
Overhead Lines
PVC Insulated Hard Draw Stranded Aluminum Conductors Type 8 & Type 16
For Overhead Lines
Application : used for overhead power lines when crossing
telecommunication lines. Type 8 is used for operating voltages that do not
exceed 650 volt between phases and type 16 where operating voltages
do not exceed 11 kv.
Specifications
Type : type 8 , type 16.
standerd: BS - 6485.
conductor: Hard drawn aluminum wires stranded
in succesive layers, in opposite direction, to form
the copper stranded conductor.
Insulation: stranded conductors are insulated
with alayer of extruded PVC compound type 1 as per
BS 6746, to form the insulated conductor.
Insulation colour: The color of the insulation
shall be black for type 8 and green for type 16.
Packing: The insulation conductors are delivered
in non returnable wood drums
as stated in technical information.
Cable
Code
01c016AP000
01c025AP000
01c035AP000
01c050AP000
01c050AP000
01c070AP000
01c095AP000
01c120AP000
01c150AP000
01c185AP000
01c016AP000
01c025AP000
01c035AP000
01c050AP000
01c050AP000
01c070AP000
01c095AP000
01c120AP000
01c150AP000
01c185AP000
DC Resistance: The D.C resistance
of hard drawn aluminum conductors
are based on volume resistivity of
0.028264 ohm.mm2/m. and temperature coefficient
of resistance at 20 0C per 0C equal 0.00403
Density: Density at 20 0C is 2.7 kg/m3
Type 8
Nominal Number & Minimum Approx. Approx. Max D.C
Cross nominal wireInsulation overall conductor Resistance
Section
diameter Thickness diameter
weight
at 20 0C
mm2
NR x mm
mm
mm
kg/km
ohm/km
16
7 x 1.7
0.8
7.1
77
1.8017
25
7 x 2.1
0.8
8.3
116
1.1807
35
7 x 2.5
0.8
9.5
154
0.8331
50
7 x 3.1
0.8
11
209
0.5786
50
19 x 1.8
0.8
11
200
0.5949
70
19 x 2.1
0.8
12.5
271
0.4371
95
19 x 2.5
0.8
14.5
365
0.3084
120
19 x 2.8
0.8
16.0
445
0.2459
150
37 x 2.25
0.8
17.8
536
0.196
185
37 x 2.5
0.8
19.5
648
0.1587
Type 16
16
7 x 1.7
0.8
8.9
111.0
1.8017
25
7 x 2.1
0.8
10.1
148.0
1.1807
35
7 x 2.5
0.8
11.3
190
0.8331
50
7 x 3.1
0.8
12.8
254
0.5786
50
19 x 1.8
0.8
12.8
243
0.5949
70
19 x 2.1
0.8
14.3
305
0.4371
95
19 x 2.5
0.8
16.3
405
0.3084
120
19 x 2.8
0.8
17.8
485
0.2459
150
37 x 2.25
0.8
19.5
585
0.196
185
37 x 2.5
0.8
21.3
710
0.1587
The above data is approximate and subject to manufacturing tolerance.
Delivery length tolerance is + 5 %
Other sizes and mutiple conductor cables are available upon request.
Overhead Lines
Stranded Aluminum Conductors Steel Reinforced (A.C.S.R)
Application : Used as bare overhead transmission lines and as primary an
secondary overhead electrical cable. They are also used for transporting electrical
power over long distances. ( Ideal for long overhead lines spans. )
Specifications
Type : (ACSR)
Grease: ACSR conductors may also
standerd: BS 215 Part 2, BS EN 50182:2001& DIN 48204:1984
be greased if required for anti-corrosive
conductor: ACSR is a concentrically stranded
purposes.
conductor composed of one or more layers of hard
Packing : The ACSR conductors are delivered in
drawn aluminum wire stranded with agalvanized
non returnable wood drums as stated in technical
steel core. The core may be single wire or
informations.
stranded dependingon the size.
According to : BS 215 Part 2
Nominal
Area
Gopher
weasel
Ferret
Rabbit
Horse
Dog
Wolf
Dingo
Lynx
Caracal
Panther
Jaguar
Zebra
mm2
25
30
40
50
70
100
150
150
175
175
200
200
400
Stranding & Wire
Diameter
Aluminium
Steel
mm
mm
6/2.36
1/2.36
6/2.59
1/2.59
6/3.00
1/3.00
6/3.35
1/3.35
12/2.79
7/2.79
6/4.72
7/4.72
30/2.59
7/2.59
18/3.35
1/3.35
30/2.79
7/2.79
18/3.61
1/3.61
30/3.00
7/3.00
18/3.86
1/3.86
54/3.18
7/3.18
Approx.
Sectional Area
overall
diameter Aluminium Steel
mm
mm2
mm2
7.08
26.24
4.38
7.77
31.61
5.27
9.00
42.41
7.07
10.05
52.88
8.82
13.95
73.37
42.83
14.15
105.00
13.50
18.13
158.10
36.80
16.75
158.70
8.80
19.53
183.40
42.80
18.05
184.30
10.20
21.00
212.10
49.20
19.30
210.60
11.70
28.62
428.90
55.60
Approx.
Weight
DC
Resistance
Breaking
Load
Total
mm2
30.62
36.88
49.48
61.70
116.20
118.50
194.90
167.50
226.20
194.50
261.30
222.30
484.50
kg/km
106
128
172
214
538
394
726
506
842
587
974
671
1621
ohm/km
1.093
0.9077
0.6766
0.5426
0.3936
0.2733
0.1828
0.1815
0.1576
0.1563
0.1363
0.1367
0.0674
Kn
9.61
11.45
15.2
18.35
61.2
32.7
69.2
35.7
79.8
41.1
92.25
46.55
131.9
Approx.
Weight
Breaking
Load
DC
Resistance
Current
Rating
kg/km
42.8
84.7
148.1
254.9
463
302.9
318.3
338.8
385.3
423.8
520.7
418.8
602.2
1093.4
1213.4
1488.2
1721.3
1413.8
1442.5
1971.4
2189.5
1798.8
1997.3
Kn
4.14
7.87
13.21
21.67
52.79
25.76
27.06
28.81
32.76
36.04
45.86
29.74
57.87
100.47
111.5
135.13
156.3
118.88
121.3
179
198.8
146.4
159.92
ohm/km
2.7027
1.3659
0.7812
0.454
0.4568
0.382
0.3635
0.3415
0.3003
0.273
0.2192
0.2188
0.2202
0.1213
0.1093
0.0891
0.0771
0.0773
0.0758
0.0673
0.0606
0.0608
0.0547
A
67
109
147
174
146
193
231
240
248
273
311
314
323
448
481
542
592
588
595
639
679
677
763
According to BS EN 50182:2001
Code
name
Mole
Squirrel
Fox
Mink
Skunk
Beaver
Racoon
Otter
Cat
Hare
Coyote
Cougar
Tiger
Lion
Bear
Goat
Sheep
Antelope
Bison
Deer
Elk
Camel
Moose
Stranding & Wire
Diameter
Aluminium
Steel
mm
mm
6/1.5
1/1.5
6/2.11
1/2.11
6/2.79
1/2.79
6/3.66
1/3.66
12/2.59
7/2.59
6/3.99
1/3.99
6/4.1
1/4.1
6/4.22
1/4.22
6/4.5
1/4.5
6/4.72
1/4.72
26/2.54
7/1.91
18/3.05
1/3.05
30/2.36
7/2.36
30/3.18
7/3.18
30/3.35
7/3.35
30/3.71
7/3.71
30/3.99
7/3.99
54/2.97
7/2.97
54/3.00
7/3.00
30/4.27
7/4.27
30/4.5
7/4.5
54/3.35
7/3.35
54/3.53
7/3.53
Approx.
Sectional Area
overall
diameter Aluminium Steel
mm
mm2
mm2
4.5
10.6
1.77
6.33
21
3.5
8.37
36.7
6.11
11.0
63.1
10.5
13
63.2
36.9
12
75
12.5
12.3
78.8
13.1
12.7
83.9
14
13.50
95.4
15.9
14.20
105
17.5
15.9
131.7
20.1
15.3
131.5
7.31
16.5
131.2
30.6
22.3
238.3
55.6
23.5
264.4
61.7
26
324.3
75.7
27.9
375.1
87.5
26.7
374.1
48.5
27
381.7
49.5
29.9
429.6
100.2
31.5
477.1
111.3
30.2
476
61.7
31.8
528.5
68.5
Total
mm2
12.4
24.5
42.8
73.6
100.1
87.5
92.4
97.9
111.3
122.5
151.8
138.8
161.8
293.9
326.1
400
462.6
422.6
431.2
529.8
588.4
537.7
597
According to DIN 48204:1984
Nominal
Area
mm2
16/2.5
25/4.0
35/6
44/32
50/8
50/30
70/112
95/15
95/55
105/75
120/20
120/70
125/30
150/25
170/40
185/30
210/35
210/50
230/30
240/40
265/35
300/50
305/40
340/30
380/50
385/35
435/55
450/40
490/65
495/35
510/45
550/70
560/50
570/40
650/45
680/85
1045/45
Stranding & Wire
Diameter
Aluminium
Steel
mm
mm
6/1.8
1/1.8
6/2.25
1/2.25
6/2.7
1/2.7
14/2.0
7/2.4
6/3.2
1/3.2
12/2.33
7/2.33
26/1.85
7/1.44
26/2.15
7/1.67
12/3.2
7/3.2
14/3.1
19/2.25
26/2.44
7/1.9
12/3.6
7/3.6
30/2.33
7/2.33
26/2.7
7/2.1
30/2.7
7/2.7
26/3.0
7/2.33
26/3.2
7/2.49
30/3.0
7/3.0
24/3.5
7/2.33
26/3.45
7/2.68
24/3.74
7/2.49
26/3.86
7/3.0
54/2.68
7/2.68
48/3.0
7/2.33
54/3.0
7/3.0
48/3.2
7/2.49
54/3.2
7/3.2
48/3.45
7/2.68
54/3.4
7/3.4
45/3.74
7/2.49
48/3.68
7/2.87
54/3.6
7/3.6
48/3.86
7/3.0
45/4.02
7/2.68
45/4.3
7/2.87
54/4.0
19/2.4
72/4.3
7/2.87
Approx.
Approx. Calculated Breaking
overall
DC Resistance Load
Actual area
Weight
diameter Aluminium Steel
Total
at 20 0C
mm2
mm2
mm2
mm
kg/km
ohm/km
Kn
5.4
15.27
2.54
17.81
20.0
1.879
5.81
6.75
23.86
3.98
27.84
31.00
1.203
9.02
8.10
34.35
5.73
40.08
45.00
0.8353
12.7
11.2
43.98
31.67
75.65
248.0
0.6573
45.46
9.6
48.25
8.04
56.29
63
0.5946
17.18
11.65
51.17
29.85
81.02
234
0.5644
44.28
11.72
69.89
11.4
81.29
89
0.413
26.31
13.61
94.39
15.33
109.72
120
0.3058
35.17
16.00
96.51
56.3
152.81
441.00
0.2992
80.2
17.45
105.67
75.55
181.22
594.00
0.2736
106.69
15.46
121.57
19.85
141.42
156.00
0.2374
44.94
18
122.15
71.25
193.4
558
0.2364
98.16
16.31
127.92
29.85
157.77
234
0.2259
57.86
17.1
148.86
24.25
173.11
190
0.1939
54.37
18.9
171.77
40.08
211.85
314
0.1682
77.01
18.99
183.78
29.85
213.63
234
0.1571
66.28
20.27
209.1
34.09
243.19
267
0.138
74.94
21
212.06
49.48
261.54
388
0.1363
92.25
20.99
230.91
29.85
260.76
234
0.1249
73.09
21.84
243.05
39.49
282.54
309
0.1188
86.46
22.43
263.66
34.09
297.75
267
0.1094
82.94
24.44
304.26
49.48
353.74
388
0.09487
105.09
24.12
304.62
39.49
344.11
309
0.0949
99.3
24.99
339.29
29.85
369.14
234
0.08513
92.56
27
381.7
49.48
431.18
388
0.07573
120.91
26.67
386.04
34.09
420.13
267
0.07482
104.31
28.8
434.29
56.3
490.59
441
0.06656
136.27
28.74
448.71
39.49
488.2
309
0.06437
120.19
30.6
490.28
63.55
553.83
498
0.05896
152.85
29.91
494.36
34.09
528.45
267
0.05843
120.31
30.69
510.54
45.28
555.82
355
0.05657
134.33
32.4
549.65
71.25
620.9
558
0.05259
167.42
32.16
561.7
49.48
611.18
388
0.05142
146.28
32.16
571.16
39.49
610.65
309
0.05057
137.98
34.41
653.49
45.28
698.77
355
0.0442
155.52
36
678.58
85.95
764.53
676
0.0426
209.99
43.01
1045.58
45.28
1090.86
355
0.02766
217.87