Matthew Caie ERICO Co-ordinated earthing for protection of railway signalling and communication systems CO-ORDINATED EARTHING FOR PROTECTION OF RAILWAY SIGNALLING AND COMMUNICATION SYSTEMS Matthew Caie B.E. Hons (Elect), M.B.A ERICO SUMMARY High-energy over-current and over-voltage transients induced by direct lightning strikes or conducted into a site via power, signalling or communication lines cause millions of dollars damage each year. No single technology or action can prevent damage for all possible mechanisms, therefore a coordinated protection approach is required. Commencing with, for sites exposed to direct lightning, an effective means to capture, conduct and then safely dissipate the energy in direct lightning strikes to earth. For sites with incoming power, communication or signalling services, a means of diverting transients arriving at the site via co-ordinated surge protection and isolation. In addition to surge protection, the need to provide a low impedance earth plane throughout the site is required. The required features of such configurations for Rail Facility applications are discussed. This paper will concentrate on addressing co-ordinated earthing with effective techniques for protection against the effects of lightning for rail facilities, focusing on the elements of the earthing system from the ground up to the equipment being protected. It is acknowledged that damage to electrical equipment may be derived from sources other than lightning, the principles discussed however may also be applicable as a design foundation in protection with additional consideration. INTRODUCTION Lightning and over-voltage transients cause millions of dollars damage to low voltage installations each year. Damage to equipment in the US for example is estimated to be at least US$1.2 billion annually, before including the loss of productivity from industrial and business downtime [1]. High-energy over-voltage transients may be derived from direct lightning strikes to structures or they may be conducted on power, signalling or communication cables entering facilities. Induced transient over-voltages may also originate from near strikes due to capacitive or inductive coupling. Some of the characteristics of the dangers include: • Peak currents can exceed 200kA with 10/350µs wave-shapes (IEC 62305-1 [2] standard). • Current rise times vary from 0.1 to 100 µs. • Multiple pulse surges are experienced in over 70% of lightning strike cases. This is a naturally occurring phenomenon where up to 20 restrikes may follow the path of the main discharge. • Continuing currents of 200-500A lasting 12 seconds may also occur. There is no single technology that can eliminate the risk of lightning and subsequent transients that occur. A holistic co-ordinated systems approach is required, and can be applied to the majority of applications. This systems approach is documented in a number of national and international standards, notably the IEC62305 [2] series of standards for protection against the effects of lightning, and can be broken down into a co-ordinated approach as referenced by ERICO as the Six Point Protection Plan. The ERICO Six Point Plan recommends: 1. Capture the direct lightning strike at a preferred point, creating a zone of protection for the structure to be protected; 2. Conduct the lightning current to ground safely, minimising the dangers of side-flash to people, equipment or structures; 3. Dissipate the energy into the ground with minimal rise in earth potential through a low impedance earthing system; 4. Eliminate earth loops and differentials by creating an equipotential earth plane under transient conditions; 5. Protect equipment from surges and transients on power lines; and 6. Protect equipment from surges and transients on communications and signal lines to prevent equipment damage and costly operational downtime. AusRAIL 2015 24 – 26 November, Melbourne Matthew Caie ERICO This paper will focus only on the points 3 to 6 of the Six Point Plan. Co-ordinated earthing for protection of railway signalling and communication systems The IEC 62561-7 set out the test and performance requirements for such materials which include: 1.0 EARTHING Regardless of the path of the lightning energy, either a direct strike, conducted surge, induced transients or through earth potential rise, once the energy is conducted to ground level, a low impedance earth is essential to dissipate the lightning energy into the earth mass as effectively as possible. The earthing systems for dedicated lightning protection terminals, tower or mast footings and electronic equipment rooms or control centres are critical design elements. 1.1 ACHIEVING A LOW IMPEDANCE EARTH Attributes of an ideal earthing arrangement: • Each earthing system (lightning, electrical, communications, and equipment room) must be individually of high integrity, as well as being considered a component of an overall earthing network. Where separate earths exist, they should be bonded together (especially under transient conditions). Bonding of all earthing systems is also typically required by code, with some exceptions not covered in the scope of this paper. • Because lightning is a multiple frequency event, it is the high frequency “impedance” that is the critical design element, not the D.C. resistance. • An earth loop conductor should surround sensitive electronic equipment rooms or facilities. This will reduce the risk of potential gradients across the facility. • There should be a “single” point connection to the ground network from all equipment within a facility. The use of earth enhancing materials to improve soil conditions and therefore achieve a lower resistance connection to ground is becoming more common practice around the world. Until a few years ago, there was no single standard that addressed the requirements of such materials. Now into its second committee cycle, the relatively new IEC62561-7 (Requirements for Earth Enhancing Compounds) [3] standard sets out to define the product testing and marking requirements for such products. 1. Leaching tests – important to consider the longevity of the material in the ground over time. 2. Sulfur content tests – lower quality materials can include bi-products or additives that act to corrode the earthing conductors. 3. Determination of resistivity – an important measure to determine the impact on the earth system resistance the material will have. 4. Corrosion tests – to determine the corrosion rate on copper or other conductors by the material, used to predict the life of the earthing system when the material is used. 5. Marking and indications – to ensure that users of the material can contrast and compare different standardised materials. This standard illustrates the key factors important to consider when considering the use of an earth enhancing compound. The earthing conductor and interconnection of earthing conductors are also important factors in the longevity of the earthing system. In this section a review of the basic metals used for earthing conductors are reviewed. A set of basic requirements (desirable features) is defined for earthing conductors. These basic requirements are detailed below: Conductive (reduce voltage differences). The more conductive the conductor the more beneficial it will be to the application. In addition to being conductive, it is important for the conductor to exhibit a low contact resistance, meaning good electrical connection either with the soil (ground) or with other conductors through connectors. Certain materials may have good conductivity, however exhibit poor contact resistance, especially following oxidization. AusRAIL 2015 24 – 26 November, Melbourne Matthew Caie ERICO Co-ordinated earthing for protection of railway signalling and communication systems Resist fusing and remain mechanically sound when exposed to electrical fault current. The ability of a conductor to conduct high electrical fault currents is a function of the materials conductivity and thermal properties. Electrical fault currents place high thermal and mechanical stress on conductors. Specifically in electrical substation or transformer grounding applications this requirement is an overriding factor, however it is not relevant for lightning protection application due to the relatively low energy of the lightning phenomenon. Mechanical application reliability based on the Practically all earthing applications require mechanical strength of the conductor to resist damage, sources of potential damage range from driving the conductor into the ground, scratching coating layers to fatigue from traffic, earthwork or installation. Various standards such as UL and IEC define clearly the mechanical strength requirements for various applications. Resist corrosion over design life Corrosion is one of the largest concerns relating to the selection of the appropriate earthing conductor. Corrosion can occur in many ways from galvanic, to interaction with corrosive soils, to oxidization. An ideal conductor would be compatible with other buried metals in the ground, compatible with other metals in contact with, resist the corrosive nature of the soil it is buried within and resist oxidation when exposed to open air over time. It is important to state that various technologies perform better in certain environments and conditions than others, and therefore no one technology is suited for all applications and environments. Cost effective installation the installation does not have influence or knowledge of the lifetime cost benefits, however, when the this is not the case the cost per year installed is more likely to be taken into account. Additionally the increase in metal prices, specifically copper, has driven a trend away from the amount of copper used in applications in an effort to curb grounding costs. The labour or equipment required to install certain technologies may also make them less attractive for certain applications, therefore the ability of the conductor to be formed (flexible), and its ease of handling contribute greatly to a cost effective installation. Resisting theft Over the past decade concern over the value to thieves of the conductor before, during and after installation has risen. This is driven by the increased cost of metals, predominantly copper, and has resulted in a clear trend in many applications to reducing the level of copper content used. An ideal conductor would be one that either is difficult to steal, has little re-sale value or at least deters or cloaks its value to potential thieves. Ease and termination reliability of connection / A conductor is only as good as its connection method within the electrical system. Certain conductors may be costly or difficult to interconnect with the electrical system. This may range from galvanic concerns requiring special termination procedures, to the flexibility of the conductor, or the cost and availability of the connectors designed or approved to be compatible with the conductor. Copper is a versatile material to terminate, is easily formed and compressed compared to steel which is ideally required to be welded or bolted. Exothermic welding methods, especially in below grade applications over time have proven to be reliable and permanent. The cost of the conductor, for the life of the installation is critical in practically every application. Initial purchase cost is the dominant factor specifically when the owner of AusRAIL 2015 24 – 26 November, Melbourne Matthew Caie ERICO Basic Choice of Metals There are a handful of basic metals to choose. There is a clear trend and history in combining these metals together to achieve the advantages of each, which is a reflection on the fact that no one metal is perfect for all aspects on the application. Each of these material properties as it relates to the application is summarized below. Copper, Aluminium, Steel. Copper High conductivity, easy to form and terminate, resistant to most underground corrosion. The reasons not to use copper would be the high value of the metal, compatibility with other metals or corrosion concerns. Copper is a noble metal and is almost totally impervious to corrosion in many types of soils. Co-ordinated earthing for protection of railway signalling and communication systems bonded or clad coatings do not increase the current carrying capability of the steel conductor. Stainless Steel clad or solid stainless steel used in the application of grounding termination is well documented to provide an excellent corrosion resistance below grade. The overall below grade performance of stainless steel in both resisting soil corrosion and galvanic corrosion is well documented. Stainless steel however is currently a relatively more expensive technology, and also has a characteristic higher resistance and contact resistance with the soil over time than copper based or copper bi-metallic conductors. 1.2 IMPORTANCE OF EARTHING LAYOUT As stated in point 4 of the Six Point protection plan, it is critical to provide an earthing layout that eliminates earth loops and differentials by creating an equipotential earth plane under transient conditions. Aluminum Good conductivity, easy to form, subject to corrosion in soils and is anodic compared to most other metals. A suitable metal to be used in above grade grounding applications or insulated below grade. Special attention is required for connection methods to other conductors due to bi-metallic concerns and oxidation that may develop resulting in poor conductivity. Steel (including Bi-metals) Relative compared to copper or aluminium, steel has a low conductivity, difficult to form during application, subject to corrosion above and below grade, requires a coatings or treatment to resist corrosion rate. In the grounding application, steel is typically used with a copper bonded layer or copper cladding, zinc plating or a stainless treatment or plating. It is well documented that copper bonding of steel will provide “some” of the corrosive and conductivity of copper in the find product, at a lower cost/value and higher strength when compared to using solid copper alone. Likewise plating steel with zinc provides excellent cost effective corrosion protection above grade. Below grade the zinc coating provides a limited lifespan when compared to other more noble and “thicker” coatings, a fact that is well documented and accepted for the application. Zinc coatings, unlike copper Figure 1 shows an example of an earthing system with a “single” point connection of mains power and communications equipment earth wires to the ground ring. If a surge arrives at the facility via the mains power supply, the surge protection equipment will divert excessive energy to earth, and the telecommunications and lightning protection grounds will rise equipotentially with all other grounding / ground points as they are closely bonded together. There is therefore little opportunity for potential differences between ground points creating earth loops, or causing sparking or side flashing. Figure 1: Single point earthing arrangement Figure 2 shows a “non-ideal” system with multiple connection points to the earth-ring. Although adequate surge and lightning protection equipment on both the power and AusRAIL 2015 24 – 26 November, Melbourne Matthew Caie ERICO communications interfaces is provided, the separated electrical and communications earth are located some distance apart (as shown by the parameter ‘d’ in figure 2). Regardless of the impedance of each individual earth, for a very short time the potential of the electrical ground will be higher than the communications ground. As a result the excess energy has two potential paths to follow to reach the lower potential communications earth, thus creating a dangerous ‘earth loop’ that will damage sensitive electronic equipment in the equipment room. Co-ordinated earthing for protection of railway signalling and communication systems • Special materials or compounds can be used to reduce earth impedances at locations where the earth resistivity is high such as in rocky, sandy or mountainous areas with large particle soil sizes. A relatively new international standard now exists for such materials or compounds. • Interconnections of conductors are a weak point in any earthing system, more-so below grade, the use of Exothermic a molecular bonding processes (copper-tocopper or alloys and copper-to-steel or alloys) for earthing and lightning protection systems provide connections that are • permanent; • low impedance; Finally, regular testing of the earthing system is recommended across various seasons to determine and change in performance over time, and to trigger the need for maintenance. A number of indicative tests are available to diagnose grounding problems and to evaluate the true transient performance of a grounding system prior to a real lightning event. Figure 2: non-ideal earthing arrangement 1.3 EARTHING SYSTEM SUMMARY The following key points to consider for an effective co-ordinated earthing system for the mitigation of the direct and secondary effects from lightning. • A single point earthing system arrangement is preferred, when this is not possible or practical, a multiple path bonding (or mesh system) system is a compromise. • A low-impedance earthing system ensures a more reliable flow of energy to ground, minimising earth potential rise. The use of a radial earthing technique allows energy to diverge as each conductor takes a share of the current. This acts to lower voltage gradients leading away from the injection point reducing voltage “step potentials” affecting equipment or people. • The selection of below grade earthing conductors will affect the life and performance of the earthing system. Electrolytic copper-bonded steel conductors provide a cost-effective means of earthing for most standard applications. An effective earthing system is the foundation of the overall facility protection system, and provides the means for the effective operation of other elements such as surge protection and lightning protection. 2.0 SURGE PROTECTION DESIGN Surge protection, when used as part of a coordinated earth system, is an effective means to protect electrical equipment from surges and transients originating from lightning or other means. In the simplest terms it provides a bond to earth for service conductors, either power, signal or communication, a diversion of excessive energy from those conductors to earth instead of electrical equipment, limiting the voltage from those conductors with reference to earth potential. This paper looks at surge protection from to main aspects, the desired performance of the device itself, and then from how the device should be effectively applied while forming part of the co-ordinated earth system. AusRAIL 2015 24 – 26 November, Melbourne Matthew Caie ERICO 2.1 IMPORTANT PERFORMANCE FACTORS FOR SURGE PROTECTION There are three critical performance aspects of the device itself. SURGE RATING Two issues need to be considered when determining the surge rating of a Surge Protection Device (SPD) for a specific location: • • What is the largest surge impulse the site is likely to require protection against; and Will this rating provide sufficient operational life under the more frequent smaller impulses? Competition between SPD manufactures has seen ever-increasing surge ratings being offered to the market, to the point where surges of this magnitude are unlikely to ever occur in nature. A number of sources provide information on the statistical distribution of the current discharge of the direct lightning strike. Many studies have shown that peak lightning discharges above 100kA are likely to occur less than 5% of the time. Combined with the fact that most discharges do not strike the service conductor directly but are magnetically or capacitive coupled to it, and that even under a direct lightning discharge the energy will split in either direction and be attenuated by the distribution arrestors and line losses it is not difficult to determine that a smaller fraction of the initial lightning energy typically enters the facility in question. It’s important to note however that some Rail Locations are very isolated and are often the only building in a particular area. The NFPA80 [6] Lightning Protection standard has classified the “point of entry” environment for power conductors as 40kA 8/20us or 20kA 8/20us for signal or communication conductors. In contrast to the above IEC62305 [2] standard defines some differing guidelines, describing protection zone concepts. A “zone” is where the lighting electromagnetic environment can be defined/controlled. The zones are characterised by significant changes of electromagnetic conditions at their boundaries. These will typically be building Co-ordinated earthing for protection of railway signalling and communication systems boundaries, or the point where protection is installed. As it can be shown, protection equipment for power supply systems are classified as follows according to its task. • Class I SPD - Lightning Arrestors • Class II SPD - Overvoltage Arrestor Lightning current arrestors must be capable of conducting lightning currents or major components of them without being destroyed. Overvoltage arrestors are only used for limiting over-voltages at relatively smaller surge currents. The different “protection zones” assume the division of the initial lightning current from zone 0 or external exposed conductors to subsequent zones within the facility. For zone 0, it is required for the user to select the lightning protection class, from I – IV: (i.e. these refer to max energy within a direct lightning strike) Protection Level I: 200kA (10/350us) Protection Level II: 150kA (10/350us) Protection Level III - IV: 100kA (10/350us) The above levels can be selected based on statistical level of protection required. A lightning current of 200kA (10/350us) can be expected for the Protection Level I. This lightning current is divided as follows in the most exposed sites: 50% (100kA, 10/350us) discharges via the earth system. 50% (100kA, 10/350us) flows into the supply systems connected to it. (i.e. power supply system, signal or communications system, metal pipes etc) In the worst case the power supply system is present only with two conductors (L;PEN), then this is loaded with 50% of the lightning current, or 50kA (10/350us) per conductor. In summary, if the IEC standard were selected, the highest surge current expected at Zone 0, with Protection Level I, for single phase two conductor is 50kA (10/350us) or 25kA (10/350us) for three phase 4-wire systems. In contrast, the lowest required surge current expected at Zone 0, with Protection Level IIIIV, for single phase two conductor is 25kA (10/350us) or 12.5kA (10/350us) for three phase 4-wire systems. AusRAIL 2015 24 – 26 November, Melbourne Matthew Caie ERICO Co-ordinated earthing for protection of railway signalling and communication systems It is a matter of selecting the product with the required surge rating for the exposure application, and the standards mentioned are a good guide in making this selection. such as disconnected neutrals in unbalanced three phase WYE systems, or by missinstallation of SPDs. UL1449 now specifies the following over voltage requirements: LET-THROUGH VOLTAGE Firstly when an over voltage of 110% of nominal voltage is applied, the device must remain functional and safe. Secondly when an abnormal over voltage of 125% is applied, the device is allowed to permanently stop functioning, but must not become unsafe. Finally when the full phase voltage according to Table 2 is applied, the device is allowed to permanently stop functioning, but must not become a fire or safety hazard. The role of the SPD is to limit the transient voltage due to lightning or the more common switching transient from reaching the equipment, thereby preventing possible transient voltage damage to the equipment. No SPD device is perfect, and some resulting letthrough voltage above the nominal service conductor voltage will still reach the equipment. This is acceptable provided that the let-through voltage is within the range that the ‘protected’ equipment can withstand. Note over time a lower let-through product will increase the equipment reliability, as the equipment would be less stressed, and multiple stresses over a period of time may cause ageing and eventual failure. Electronic equipment is sensitive not only to the magnitude of the let-through, but also to the rate of the pre-clamped voltage rise, i.e. the slope of the leading edge. This is known as the dV/dt, change in voltage over time. SAFE OPERATION UNDER END OF LIFE CONDITIONS This issue generally relates to the construction of the product, i.e. strength, accessibility of live parts and equally important to the maximum voltage the SPD can withstand without becoming a fire or safety hazard. The latter is a very important safety issue. Traditionally SPDs could not differentiate between slower overvoltages and the faster transient voltages. For power connected SPDs a maximum continuous operating voltage of 20% above the normal voltage was selected; as to make this much higher would also increase the letthrough voltage (under transient impulses) to a point where the equipment may not have been sufficiently protected. There are however many known cases where the nominal voltage has exceeded this 20%, causing the SPD to clamp on each half cycle and build up sufficient heat to become a hazard. Underwriters Laboratory with industry developed the UL1449 [5] standard, to address this growing problem. Over voltages can be caused by poor power regulation, wiring faults Although this Full Phase Voltage test is an extreme over-voltage, it is recommended that even with sites with known good power regulation that UL1449 compliant products, or those with equivalent MCOV ratings, are selected, as wiring faults and accidents can occur. test or the full phase voltage test. The International (or European version) safety and testing standard for surge protection devices is IEC61643. This standard is similar to the UL1449 standard in regards to product requirements under over voltage conditions. However both the UL1449 [5] and IEC61643 [3] standard as extremely important in specifying the safety requirements for surge protection devices. To a user of SPDs, devices marked with a UL and CE mark reassure compliant to both these safety and performance standards. It means the markings of the products are standardised and able to be compared by users and that products meet basic safety in operation requirements. To state that compliance with the above two standards, in some countries mandatory standards, is of little importance is under-estimating the need for product safety under the most testing conditions. Many different types of SPDs and technology are available on the market. To enable the selection of effective protection at the best value for money, one needs to make a selection based on the most important technical performance specifications. In addition to the above-mentioned critical factors, the following selection parameters should be considered: AusRAIL 2015 24 – 26 November, Melbourne Matthew Caie ERICO 1. 2. 3. Co-ordinated earthing for protection of railway signalling and communication systems Maximum Continuous Over Voltage (MCOV) withstand Indication & Life Physical & Environmental issues 2.2 SPECIFIC PERFORMANCE FACTORS FOR COMMUNICATIONS, SIGNAL AND DATA SURGE PROTECTION Protection of land-based communications, signal and data lines into the facility are an issue for comprehensive protection. Transients up to 20 kA 8/20µs injected onto telecommunications and signal lines can damage and destroy sensitive terminal equipment and lead to facility down time. Protecting data and communications equipment necessitates the same concepts as used in Point 5, however due to the differing exposure levels, much lower operating currents and voltages and increased sensitivity of equipment, the parameters of each surge protector need to be carefully selected. Knowing where to install surge protection can be difficult. To ensure cost-effective protection is provided for data, signalling and control circuits, two issues need to be considered: • Where should the SPDs be installed? • What type of SPD is appropriate for each circuit type and location? Communications devices are at risk from transients being induced onto the interconnecting signal lines. The use of surge protection barriers, installed at either end of the lines, provides cost effective mitigation. The highest risk is posed by communication or signal lines that enter or exit the building. In such circumstances, protection devices should be installed at the point of entry or at the equipment termination itself. Internal wiring which extends more than 10 – 15m should also be protected. Twisting or shielding of cables provides a level of protection, however this should not be regarded as sufficient for the sensitive interfaces that characterize todays communication devices. Five parameters must be considered to ensure that surge protection devices for use on data, signalling or control circuits are effective and do not adversely affect operation of the circuit. sustainable by the equipment, yet should not interfere with the normal signalling voltages. As a guide, the SPD clamping voltage should be selected to be approximately 20% higher than peak working voltage of the circuit. 2. The line current rating of the SPD should be sufficient to handle the maximum expected signalling current. 3. The SPD bandwidth should be sufficient to allow correct operation of the system without adverse attenuation. This ensures that the attenuation of the SPD at the nominal operating frequency of the system does not exceed the stated limit. For most SPDs, frequency attenuation data or a maximum recommended baud rate is generally specified. 4. The connection termination, mounting method, number of lines to be protected and other physical aspects must be considered. 5. The SPD surge rating should be appropriate for the intended location. For circuits internal to the location, surge ratings of 1-5kA 8/20us are generally sufficient. For the protection of circuits that connect to exposed lines entering or exiting the location, 10-20kA 8/20us is recommended. It is vital to consider, as per Point 5 of the Six Point Plan, the surge rating and let-through voltages are considered when selecting appropriate protection for communications and/or data lines. The optimum level of protection is provided using multistage (or series) connected products. Single-stage, “gas arrester only” circuits provide cost-effective protection for less sensitive electro-mechanical or discrete component-type terminals and supplement circuits with “built-in” protection. Multistage stage protectors employing gas arrester primary and decoupled semi-conductor secondary protection stages can provide lower clamp (let-through) voltages than the singlestage protectors. 1. SPDs are designed to clamp the excess transient voltage to safe levels AusRAIL 2015 24 – 26 November, Melbourne Matthew Caie ERICO Co-ordinated earthing for protection of railway signalling and communication systems 2.3 CO-ORDINATION OF PROTECTION WITH EARTHING SURGE The correct application of surge protection is equally as important at the features of the surge protection device itself. In addition to the importance of the actual below grade earthing system quality and layout is the following three points. INSTALLED LEAD-LENGTH OF THE SPD The lead-length is defined as the conductor length from the active conductor to which the surge protection device is connected to earth point itself. The actual “earth point” also needs to be defined in the application also, however Figure 3 defines two basis connection means of an SPD, one being defined as a “T” connection (non-preferred) and the other as a series connection (preferred). As the surge current is diverted from one conductor to the other through the SPD, the resultant voltage is the sum of the SPD letthrough at that surge current, and the voltage drop along the connecting leads. This voltage drop is determined by the equation: Equation 1: V = R.i x L.dV/dt where: R L dV/dt i - resistance of the leads - inductance of the leads - rate voltage rise of the surge - peak surge current. Due to the inherent sharp rise time of surges, the inductance of the connection leads can lead to voltage drops of approximately 1V/mm of standard 4-6mm2 wire, for typical magnitude surges. Clearly a surge protection arrangement that allows for a series line/load through connection will allow for optimal performance of the SPD as it acts to drastically reduce the let-through voltage protected equipment will be exposed to under surge conditions. Figure 3 – SPD Connection methods SEPARATION WIRING OF CLEAN AND DIRTY From an electrical perspective, the term clean and dirty wiring refers to the zone or position of the wiring with reference to surge protection or filtering devices. Dirty wiring from the aspect of the design, refers to wiring that is upstream of the surge protection and therefore considered to be exposed to surges or transients. From earlier sections of this paper, it could also be described as wiring within zone 0 or zone 1, and accepted within the design to potentially carry high levels of surge energy. Clean wiring is considered to be downstream of the surge protection. It is critically important in the design of the protection system to provide a physical or electrical means of separation of the dirty and clean wiring otherwise it is possible for unwanted energy from the dirty wiring to be transferred or induced onto the clean wiring, AusRAIL 2015 24 – 26 November, Melbourne Matthew Caie ERICO effectively bypassing or negating effectiveness of the surge protection. Co-ordinated earthing for protection of railway signalling and communication systems the Separation can be achieved by physical means such and not installed them both in the same cable tray or conduit, or shielding them magnetically from each other when physical separation is not practical. These principles are not new, shown in figure 4 is a typical wiring layout within a trackside signalling bungalow in North America which shows traditional surge protected terminal blocks inherently designed to separate the field “dirty” signal wires from the “clean” equipment connected wiring through providing a termination system that allows for a series connection with a low-impedance earth plane perpendicular to the wiring to provide a transition from dirty to clean. CONNECTION ARRANGEMENT. The IEC62305 [2] standard defines these two basic earth system layouts as described in Figure 5, defining the layout from the equipment down to the bonding network, being either an external earthing system or structural bonding system that forms part of the earthing system itself. The star configuration, or single point earthing system is ideal in creating an environment that eliminates earth potential. Star Configuration • • • • All metal components (e.g. cabinets, enclosures, racks) of the internal systems shall be isolated from the earthing system Shall be integrated into the earthing system only by a single bonding bar acting as the earth reference point (ERP) Can be used where internal systems are located in relatively small zones and all lines enter the zone at one point only (at the ERP) Achieves Equipotential by keeping surge currents out of the equipment earthing lines Mesh Bonding Network • • • All metal components (e.g. cabinets, enclosures, racks) of the internal systems are not to be isolated from the earthing system, but shall be integrated into it by multiple bonding points Is preferred for internal systems extended over relatively wide zones or over a whole structure, where many lines run between the individual pieces of equipment, and where the lines enter the structure at several points Achieves Equipotential by having many parallel low-impedance paths, Figure 4 – Typical field wire termination system within a trackside bungalow. AusRAIL 2015 24 – 26 November, Melbourne Matthew Caie ERICO Co-ordinated earthing for protection of railway signalling and communication systems Figure 6: Multi zonal earth system layout. 2.3 SURGE PROTECTION SUMMARY There are two key aspects to consider when selecting and applying surge protection for power, signalling and communication systems. That is the important performance features of the surge protection device itself, and the installation of the surge protection device including the correct connection means and the co-ordination with the earthing system design and layout. The key performance features to select for the application of the SPD are: Figure 5: Star and Meshing Bonding configurations For larger sites, or for more distributed facilities or equipment it is possible to apply the star configuration method more effectively by defining separate zones. The concept is to define zones as illustrated by the dotted line box in figure 6 where all cabling crossing the zone boundary requires a local SPD referenced to one single earth bar within that zone. An example of a multi zonal star earth system layout is shown in figure 6. This design method is effective especially when considering the earthing upgrade on existing locations as it is often practical to apply. - Surge protection for the environment - Let-through voltage compatible with the tolerance of the equipment being protected. - Safe operation, defined by standards compliance, testing and marking. The key installation parameters of the SPD are: - Wiring lead length and means to reduce it within the application. - Separation of clean and dirty wiring to ensure. - A co-ordinated connection arrangement to earth through either a star point earthing arrangement within a single zone or a mesh bonding network. It is acknowledged that in certain or special applications there are other secondary parameters to consider that those stated above. AusRAIL 2015 24 – 26 November, Melbourne Matthew Caie ERICO Co-ordinated earthing for protection of railway signalling and communication systems CONCLUSIONS Direct lightning strikes and over-voltage transients create major equipment failures and cause downtime. Analysis of damage has shown that no single protection device can provide lightning immunity. Comprehensive protection is provided only by employing an integrated Six Point Plan approach to lightning protection of facilities and assets. REFENRENCES [1] Insurance Information Institute, NY, (NY Press Release 11 August 1989 [2] IEC62305-1, Protection of structures against lightning, Part 1: General principles [3] IEC62561-7, Requirements for Earth Enhancing Compounds [4] IEC61643-1 Surge Protective Devices connected to low-voltage power distribution systems. Part 1: Performance requirements and testing methods. [5] UL1449 Edition 4, Standard for Surge Protection Devices, 2016 [6] NFPA780, Installation Guide for Lightning Protection Systems, 2014 AusRAIL 2015 24 – 26 November, Melbourne