INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s) 452763 FD, DFD, SSFD & KFD Models 453946 FD & DFD 150X Models 10–17 462721 DFDR-XXX, SSDFDR-XXX, FDR-XXX, and SSFDR-XXX Models 18–22 461337 OFSD-XXX, ODFD-XXX, OFD-XXX and OSSFD-XXX Series 23–34 474015 Single Side Retaining Angle 35-37 2–9 KIT # 826251 CURTAIN FIRE DAMPERS DFD/FD/OFD/ODFD/DFDR/FDR Return to Table of Contents Document Number 452763 FD, DFD, SSFD, SSDFD, & KFD Models 11/2 and 3 Hour Curtain Fire Dampers Vertical and Horizontal Mount ® Installation, Operation and Maintenance Instructions FD, DFD, SSFD, & KFD models are intended for installation in accordance with fire damper requirements established by: National Fire Protection Association NFPA Standard 80, 90A, & 101 IBC International Building Code CSFM California State Fire Marshal Fire Damper Listing (#3225-0981:102) New York City (BSA/MEA listing #260-91-M) “UL CLASSIFIED (see complete marking on product)” “UL CLASSIFIED to Canadian safety standards (see complete marking on product)” UL Standard 555 (Listing #R13317) SAFETY WARNING: Installation Supplements Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating, and maintenance instructions thoroughly before installing or servicing this equipment. Refer to the appropriate Greenheck installation supplements for special requirements: • Close Indicator Switch • Concrete Floor with Steel Deck • Drive Slip Breakaway Connection • Fire Resistant Ventilated Duct Assembly • Firestop Material • Greenheck Test Switch • Grille Installation • Metal Stud in Shaftwall • Quick Connect Breakaway Connections • Sealant Supplement • Single Side Retaining Angle • Single 3-Sided Retaining Angle - Vertical Mount • Sleeve Extension • Support Mullions Note: Refer to Greenheck IOM, Part #461335, for CFSD models to be installed in corridor ceiling applications. WARRANTY Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the shipment date. Any units or parts which prove to be defective during the warranty period will be repaired or replaced at our option. Greenheck shall not be liable for damages resulting from misapplication or misuse of its products. Greenheck will not be responsible for any installation or removal costs. Greenheck will not be responsible for any service work or backcharges without prior written authorization. These instructions apply to 11/2 and 3 hour rated fire dampers mounted (blades must be horizontal) in masonry, block or stud walls and concrete floors. Specific requirements in these instructions are mandatory. These instructions meet the requirements of UL 555. Installation shall comply with the requirements of NFPA 90A Standard for the Installation of Air Conditioning and Ventilating Systems. UL listing R13317, California State Fire Marshal listings 3225-0981:102, and New York City BSA/MEA listing 260-91-M apply to these dampers. Note: Fire dampers are manufactured and labelled for either vertical or horizontal installation. The dampers must be installed in accordance with the labelling. RECEIVING AND HANDLING Upon receiving dampers, check for both obvious and hidden damage. If damage is found, record all necessary information on the bill of lading and file a claim with the final carrier. Check to be sure that all parts of the shipment, including accessories, are accounted for. Dampers must be kept dry and clean. Indoor storage and protection from dirt, dust and the weather is highly recommended. Do not store at temperatures in excess of 100°F (38°C). Due to continuing research, Greenheck reserves the right to change specifications without notice. This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the job is complete. 2 Table of Contents Pre-Installation Guidelines..............................................................................................................................................................3 Installation....................................................................................................................................................................................3-9 • Clearances Required Between Fire Damper Sleeves and Wall/Floor Openings............................................................3 • Sleeve Length and Wall Thickness............................................................... ..............................................................4-5 • Duct to Sleeve Connections.......................................................................... .................................................................6 • Securing the Damper/Sleeve Assembly to Wall and Floor Openings........................................................ .....................6 • Installing Multiple Damper Section Assemblies.............................................................................................................7 • Recommended Preparation of Openings in Wood and Metal Stud Walls............................................................ ...........9 • Breakaway Connections..................................................................... .........................................................................7-8 Pre-Installation Guidelines The basic intent of a proper installation is to secure the fire damper in, not to, the opening in such a manner as to prevent distortion and disruption of damper operation. This is accomplished by allowing the fire damper in rated separation openings to expand and for the connecting duct to separate in the event of the collapse of the hanging system. The following items will aid in completing the damper installation in a timely and effective manner. 1)Check the schedules for proper damper locations within the building. Visually inspect the damper for damage and verify that the fusible link is in place or has not activated. Never install a fire damper without the proper UL approved fusible link in place. If damper is furnished with fusible link, visually inspect the link to verify its not missing or broken. Replace link as necessary. 2)Lift or handle damper using sleeve or frame. Do not lift damper using blades. 3)Damper has label on outside of sleeve indicating a ‘No Screw’ area. Do not install screws into this area as screws may interfere with unexposed blade linkage and prevent damper blades from opening and/or closing. 4)Damper has label indicating position of damper and sleeve assembly in the wall. Install accordingly to comply with manufacturer’s appropriate UL Classification file number. 5)Damper must be installed into duct or opening square and free of twist or other misalignment. Damper must not be squeezed or stretched into duct or opening. Out of square, racked, twisted or misaligned 1.CLEARANCES REQUIRED BETWEEN FIRE DAMPER SLEEVES AND WALL/FLOOR OPENINGS Fire damper and sleeve assemblies expand during periods of intense heat. Therefore it is essential that openings in walls or floors be larger than the fire damper and sleeve assembly to allow for this expansion. Minimum clearances required between the outside of fire damper sleeve assemblies and wall/floor openings are: • Galvanized steel fire dampers and sleeves: 1/8 in. (3mm) per foot of damper width and 1/8 in. (3mm) per foot height with a minimum clearance of 1/4 in. (6mm) Recommended clearances, for width and/or height dimensions of: 1) 48 in. (1219mm) or less: 1/2 in. (13mm) clearance 2) More than 48 in. (1219mm) and 96 in. (2438mm) or less: 1 in. (25mm) clearance installations can cause excessive leakage and/or torque requirements to exceed damper/actuator design. 6)Damper must be kept clean and protected from dirt, dust and other foreign materials prior to and after installation. Examples of such foreign materials include but are not limited to: a) Mortar dust b) Drywall dust c) Firesafing materials d) Wall texture e) Paint overspray 7)Damper should be sufficiently covered as to prevent overspray if wall texturing or spray painting will be performed within 5 feet of the damper. Excessive dirt or foreign material deposits on damper can cause excessive leakage and/or torque requirements to exceed damper/actuator design. 8)Caulking is not necessary, nor is it allowed, between the damper sleeve and the wall or floor opening (annular space). However, caulking may be applied to the retaining angles. 9)ACCESS: Suitable access (such that fusible links can be maintained, etc.) must be provided for damper inspection and servicing. Where it is not possible to achieve sufficient size access, it will be necessary to install a removable section of duct. (Refer to NFPA 90A). 10)The Code Authority Having Jurisdiction (AHJ) must evaluate and provide approval of final installation where variations to these instructions are necessary. 3) More than 96 in. (2438mm): 11/2 in. (38mm) clearance • Stainless steel fire dampers and stainless steel or galvanized sleeves: 3/16 in. (4.8mm) per foot of damper width and height with a minimum clearance of 1/4 in. (6mm), maximum of 2 in. (51mm). Recommended clearances, for width and/or height dimensions of: 1) 48 in. (1219mm) or less: 3/4 in. (19mm) clearance 2) More than 48 in. (1219mm) and 96 in. (2438mm) or less: 1 1/2 in. (38mm) clearance 3) More than 96 in. (2438mm): 2 in. (51mm) clearance These are total clearances (ignoring fastener heads) and do not need to be equally spaced around the damper. Refer to Section 4 and Figure 6 for additional installation considerations. 3 Vertical mount without factory mounted sleeve Example: A 12 in. x 12 in. (305mm x 305mm) damper would require a minimum clearance of 1/4 in. (6mm) on width and 1/4 in. (6mm) on height A 48 in. x 12 in. (1219mm x 305mm) damper would require a minimum clearance of 1/2 in. (13mm) on width and 1/4 in. (6mm) on height. 1/4 in. minimum total clearance (See Section 1) 2.GAUGES AND LENGTHS OF FIRE DAMPER SLEEVES Wall or floor All fire dampers must be installed in a steel sleeve of the required gauge and length. See Table 1 for required minimum sleeve gauges. Maximum sleeve thickness is 10 gauge (3.5mm). Sleeve inside dimensions must equal damper outside dimensions. Sleeves shall extend a maximum of 6 in. (152mm) beyond the wall or floor opening on each side (see Figure 1). When an access door is incorporated as a part of sleeve, the sleeve may extend a maximum of 16 in. (406mm) beyond the wall or floor opening on the access door side. See Section 2 See Section 2 Mounting (See Para Damper 1 t (S Duct Sleeve (See Sections 2 & 3) Retaining Angles (See Section 4) Type A Sleeve Gauge Duct Dimension Type of Duct to Sleeve Connection Permitted 14 ga. (0.075 in.) - 10 ga. (0.138 in.) [2mm - 3.5mm] All duct sizes Rigid or Breakaway 16 ga. (0.060 in.) [1.5mm] 36 in. (914mm) max. width 24 in. (610mm) max. width 24 in. (610mm) diameter Rigid or Breakaway 16 ga. (0.060 in.) [1.5mm] All duct sizes 18 ga. (0.048 in.) [1.2mm] 85 in. (2159mm) wide and over 20 ga. (0.036 in.) [0.9mm] 55 in. - 84 in. wide (1397mm - 2134mm) 22 ga. (.030 in.) [0.76mm] 31 in. - 54 in. wide (787mm - 1372mm) 24 ga. (0.024) [0.6mm] 13 in. - 30 in. wide (330mm - 762mm) 26 ga. (0.018 in.) [0.46mm] 12 in. wide and under (305mm) Wall or floor Retaining angle leg shall not exceed 7 in. (178mm) Sleeve Damper Duct Type B Breakaway only Wall or floor On types R & CR factory furnished duct collar qualifies as breakaway conneciton (See Section 5) Damper Sleeve thickness must not be less than the gauge of the connecting duct. UL Standard 555 requires all ducts to terminate at fire damper sleeves. Table 1: Minimum sleeve thickness for fire dampers. Duct Sleeve Type C, CO, CR & R When dampers installed vertically, the blade stack must be on the top.. 4 Figure 1 Horizontal mount without factory mounted sleeve 1/4mount in. minimum Vertical with factory total clearance mounted sleeve Horizontal mount with factory mounted sleeve 1/4 in. minimum total clearance Wall or Floor Maximum 6 in. Retaining Angles (See Section 4) Maximum 6 in. See Section 2 “K” side See Section 2 Maximum in.Floor Wall6or Retaining Angles (See Section 4) Maximum 6 in. See Section 2 “K” side Wall or Floor Sleeve (see sections 2 & 3) Damper Duct Duct See Section 2 1/4 in. minimum total clearance Wall or Floor Sleeve (see sections 2 & 3) Damper Duct Damper Duct Damper Retaining Angles Retaining Angles (See (See Section 3) 3) Section Type A Type AA Type Type A Wall or Floor Wall or Floor Wall or Floor Maximum 6 in. Retaining Angles (See Section 4) Maximum 6 in. Damper Damper See Section 2 “K” side Wall or Floor Retaining angles (See Section 4) See Section 2 “K” side Sleeve (see sections 2 & 3) Wall or Floor See Section 2 Damper Duct Duct Duct Sleeve (See Sections 2 & 3) See Section 2 Damper Damper Type B Retaining Angles Duct (See Section 3) Type B Type A Duct On types R, CO & CR factory Type furnished duct collar qualifies as breakaway connection. Type B Damper B Wall or Floor Wall or Floor Damper On types R, CO & CR factory furnished duct collar qualifies as breakaway connection. Damper Duct Type B Type B2 Wall or floor Wall or floor Type B2 Sleeve Type C, CO, CR, & R “K” side Damper Wall or Floor Duct Duct Damper Damper Type B2 Sleeve Wall or floor Sleeve Sleeve Wall or floor Wall or floor Duct Type B2 Damper Duct On types R, CO & CR factory furnished duct collar qualifies as breakaway Wall or Floor connection. Type C, CO, CR, & R Sleeve “K” side On types R & CR factory furnished duct collar qualifies as breakaway connection, see Section 5 Sleeve Type C, CO, CR, & R On types R & CR factory furnished duct collar qualifies as breakaway connection, see Section 5 Damper Duct When dampers installed horizontally, the ramp must be positioned up as shown in above drawings. Figure 1 Wall or floor Type C, CO, CR, & R Type C, CO, CR, & R When dampers installed vertically, the blade stack must be on the top. 5 When dampers installed horizontally, the ramp must be positioned up as shown in above drawings. 3.ATTACHING FIRE DAMPERS TO SLEEVES Fire dampers must be attached to sleeves as shown in Figure 3. All four sides of the damper frame must be attached to the sleeve with one row of attachments on each side of the blade channel. Attachments must be spaced a maximum of 6 in. (152mm) on centers and a maximum of 2 in. (51mm) from corners. A minimum of 4 attachments (2 on each side of the blade channel ) per side ( 16 per damper ) are required. One of the methods of attachment shown below must be used. • tack or spot welds • #10 sheet metal screws • 1/4 in. (6mm) bolts and nuts • 3/16 in. (4.7mm) steel pop rivets 4.SECURING FIRE DAMPER AND SLEEVES TO WALL AND FLOOR OPENINGS. The fire damper must be installed such that the centerline of the blades are mounted in the plane of the wall or floor. Figure 2 Transfer opening or no connecting duct Fire damper and sleeve assemblies must be installed in wall and floor openings using retaining angles on each side of the wall or floor as described below: •Retaining angles for 11/2 hour rated dampers with a width and height 48 in. (1219mm) or less must be a minimum of 20 ga. (1mm). Retaining angles for all 3 hour rated dampers and all dampers with a width or height greater than 48 in. (1219mm) must be a minimum of 16 gauge (1.5mm). The leg of the retaining angle on the damper sleeve shall be a minimum of 11/4 in. (32mm). The leg of the retaining angle on the wall/floor shall be long enough to cover the annular space and overlap the wall/floor by a minimum of 1 in. (25mm). (See Figure 4). Retaining angle legs may be reversed with leg of retaining angle with annular space of opening so angle and sleeve is flush against barrier. • Retaining angles must be attached to the sleeve using the procedures and methods described in Section 3. The angles must be attached to all 4 sides of the sleeve with butt joints at each corner. A minimum of two attachments are required on each side, top and bottom. The angles need not be attached to each other at the corners. • Retaining angles should not be fastened to the wall / floor material. The angles should only sandwich the wall /floor and allow for damper/sleeve expansion during periods of intense heat. For single retaining angle applications, see Single Side Retaining Angle Supplement (#474015). Attachments--Do not place attachments between blade channels Blade Channel NOTE: Attachments must not enter blade channel or they may cause interference with blade closure. Narrow Line and Ultra Thin dampers do not have flange for attachments and must be welded to sleeve. 2 in. Max. 6 in. Max. Attachments can be staggered or evenly spaced. Figure 3: Field attachment of fire dampers to sleeves. Wall or Floor Min. 1 in. overlay* Retaining Angle Retaining angle Sleeve No Connecting Duct or Transfer Opening Openings where duct does not attach on either side will not require a breakaway connection. Transfer openings are typical of a non-ducted installation (see Figure 2). 2 in. • Sleeve may end flush with the rated wall/floor on both sides Duct Max . 6 in. M ax. • Refer to Section 4 for securing retaining angles to sleeves. 5. CONNECTING DUCTS TO FIRE DAMPER SLEEVE Any duct connection other than breakaway is considered rigid. The connections shown on this page are considered breakaway. Factory furnished duct collars on type R and CR fire dampers are also considered breakaway (see Figure 1). 6 6 in. M ax. 2 in. Max . Figure 4: Retaining angle installation. Damper 6. MULTIPLE SECTION FIRE DAMPERS When multiple sections are shipped unassembled, installer shall fasten dampers together as described in Section 3. Table 2 shows maximum sizes for multiple section dampers. Dampers that are two or more sections tall must be factory assembled. Damper Model Mounting Maximum Single Section Damper Sizes* Maximum Multi-Section Damper Sizes* FD-100 , FD-300, FD-310, SSFD-350 Vertical 48 X 48 (1219mm x 1219mm) 96 x 48 (2438mm x 1219mm) or 120 x 40 (3048mm x 1016mm) FD-150 Vertical or Horizontal 48 X 48 (1219mm x 1219mm) FD-110 Vertical or Horizontal 48 x 48 (1219mm x 1219mm) 96 x 48 (2438mm x 1219mm) Vertical 48 X 48 (1219mm x 1219mm) 96 X 48 (2438mm x 1219mm) or 120 X 40 (3048mm x 1016mm) Horizontal 36 x 36 (914mm x 914mm) - Vertical 48 x 48 (1219mm x 1219mm) - Horizontal 40 x 40 (1016mm x 1016mm) 80 x 40 (2032mm x 1016mm) 96 x 48 (2438mm x 1219mm) or 120 x 40 (3048mm x 1016mm) SSFD-150 FD-350 KFD-150 Vertical or Horizontal 36 x 16 (914mm x 406mm) KFD-110 Vertical or Horizontal 36 x 16 (914mm x 406mm) 96 x 48 (2438mm x 1219mm) 36 x 16 (914mm x 406mm) 96 X 48 (2438mm x 1219mm) or 120 X 40 (3048mm x 1016mm) SSKFD-150 Vertical KFD-350 SSKFD-350 Vertical 36 x 16 (914mm x 406mm) - Horizontal 36 x 16 (914mm x 406mm) 80 x 40 (2032mm x 1016mm) Vertical 36 x 16 (914mm x 406mm) - 36 x 36 (914mm x 914mm) 72 x 48 (1828mm x 1219mm) or 60 x 60 (1524mm x 1524mm) or 120 x 30 (3048mm x 762mm) 24 x 18 (610mm x 457mm) 48 x 36 (1217mm x 914mm) 30 x 30 (762mm x 762mm) - Vertical DFD-150, DFD-110 Horizontal Vertical DFD-350 Horizontal DFD-310 SSDFD-110, SSDFD-150. SSDFD-350 36 x 36 (914mm x 914mm) - 24 x 18 (610mm x 457mm) 48 x 36 (1217mm x 914mm) 30 x 30 (762mm x 762mm) Vertical 36 x 36 (914mm x 914mm) - Horizontal 30 x 30 (762mm x 762mm) - Vertical 30 x 30 (762mm x 762mm) - Note: All dimensions shown are in inches (W x H). * Sizes listed is the damper size not transition size. Table 2: Maximum section sizes and overall sizes for multiple section dampers (W x H). DUCT-SLEEVE CONNECTIONS Traditional Breakaway Style Transverse Joints Transverse joints illustrated in Figure 5 have always been approved as breakaway connections. SMACNA testing has also approved the following variations as breakaway connections. •The breakaway connections shown to the right can be applied with maximum of (2) #10 sheet metal screws on each side and on the bottom located in the center of the slip pocket and penetrating both sides of the slip pocket. •Transverse joints illustrated can be applied as top and bottom joints with Drive Slip - side joints in duct heights up to 20 inches Drive Slip Joint (508mm). Plain “S” Slip Inside Slip Joint Standing “S” (Alt.) Hemmed “S” Slip Double “S” Slip Standing “S” Standing “S” (Alt.) Standing “S” (Bar Reinforced) Standing “S” (Angle Reinforced) Figure 5: Traditional breakaway style transverse joints. 7 DUCT-SLEEVE CONNECTIONS cont... Round and Oval Duct Breakaway Connections Round ducts connected to factory supplied Type R or CR damper collars may use #10 sheet metal screws as follows: • Ducts 22 in. (559mm) wide (or dia.) and smaller may use 3 screws. • Ducts larger than 22 in. (559mm) wide (or dia.) may use 5 screws. NOTE: All breakaway connections described may have duct sealant applied, PA2084T duct sealant adhesive manufactured by Precision or DP1010 water base duct sealant by Design Polymetrics, Grey Pookie, or Ductmate PROseal®, or CL Ward S Seal in accordance with SMACNA recommendations. Fire Damper Sleeve 6 in. long 1/16 in. max. thickness plastic cleats; 12 in. c-c (min. 1 per side) Flanged system angles (Attach per manufacturer's instructions) Do not bolt corners Neoprene gasket between all angles Manufactured Flanged System Breakaway Connections Duct Figure 6: Detail of manufactured flanged system breakaway connections. Flanged connection systems manufactured by Ductmate, Ward, and Nexus are approved as breakaway connections when installed as illustrated in Figure 6. Proprietary Flange System Breakaway Connections Clip Spacing (TDC by Lockformer, TDF by Engle) Std. Clip Length 6 in. 60 in. Duct 4 Req’d. TDC and TDF systems are approved as breakaway connections when installed as described in the SMACNA Duct Construction Standards. Standard 6 in. (152mm) metal clip may be used with spacing as shown in Figure 7. ThreeSleeve eighths in. (9.5mm) metal bolts and nuts may be used to fasten together corner pieces. 60 in. Duct 4 Req’d. Typical TDC/TDF joint Sleeve Std. Clip Length 36 6in.in.Duct 3 Req’d. Duct6 in. 7 in. 48 in. Duct 3 Req’d. 24 in. Duct 2 Req’d. 5 in. 36 in. Duct 3 Req’d. Duct 6 in. 7 in. 48 in. Duct 3 Req’d. Clip Spacing 9 in. 6 in. 7 in. 5 in. 5 in. 9 in. 6 in. 5 in. 5 in. 7 in. 5 in. 18 in. DuctMetal & Stud Construction Smaller CL 5 in. 1 Req’d. Duct Gypsum Wallboard 5 in. 24 in. Duct 2 Req’d. Figure 7: Detail of proprietary flanged system 18 in. Duct & breakaway connections. Typical TDC/TDF joint Smaller 1 Req’d. CL Duct Stud or Runner Recommended Preparation of Openings in Wood and Metal Stud Walls Retaining • Frame wall openings as shown in Figure 8 & 8A. Angle (25mm) minimum • Gypsum wall board must be fastened 12 in. (305mm) on center to all stud and runner flanges surrounding 1in. opening (see Figure 8 & 8A). In metal stud construction, • Prepare opening between studs and sleeve assembly as shown (see. Figure 9). Damper exposed steel surfaces need Sleeve not be covered with gypsum • All construction and fasteners must meet the requirements of the appropriate wall design. wallboard. (See UL Fire Resistance Directory) Metal Stud Construction Wooden Stud Construction Gypsum Wallboard Gypsum Wallboard Stud or Runner Stud or Runner Retaining Angle Retaining Angle 1in. (25mm) minimum 1in. (25mm) minimum Damper Sleeve In metal stud construction, exposed steel surfaces need not be covered with gypsum wallboard. Damper Sleeve In wood stud construction, gypsum wallboard must cover all wood stud surfaces. Figure 9: Detail of retaining angles and gypsum board application for metal and wooden stud construction. Wooden Stud Construction Gypsum Wallboard 8 Stud or Runner Second set of studs are not required on openings 36 in. x 36 in. (914mm x 914mm) or smaller. 24 in. o.c. Maximum (metal studs) 24 in. o.c. Maximum (metal studs) Ceiling Runner 12 in. 24 in. o.c. Maximum 2 in. (51mm) 2 Panhead Screws 16 in. o.c. Maximum (wood studs) 2 in. (51mm) 16 in. o.c. Maximum (wood studs) Metal stud only Floor Runner Figure 8A Figure 8: Preparation detail for opening in stud wall. Damper Maintenance Dampers shall be maintained, cycled, and tested in intervals as stated in the latest editions of NFPA 90A, 92A, and UL 864 unless local codes require more frequent inspections. Dampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, use mild detergents or solvents. If lubrication is desired, do not use oil-based lubricants or any other lubricants that attract contaminant’s such as dust. Damper Trouble Shooting The following is a cause and correction list for common concerns with the dampers. Symptom Damper does not fully open and/or fully close Link separated Possible Cause Corrective Action Frame is 'racked' causing blades to bind on jamb Adjust frame such that it is square and plumb Screws in damper linkage Locate screws and remove Contaminant's on damper Clean with a non-oil based solvent (see Damper Maintenance) Heat Replace link Our Commitment As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice. Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the Library under Warranties. ® Phone: (715) 359-6171 • Fax: (715) 355-2399 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com 452763• DFD, FD, SSDFD Series Rev. 17, August 2013 9 Copyright 2013 © Greenheck Fan Corporation Return to Table of Contents Document Number 453946 FD & DFD 150X MODELS ® 1 1⁄2 Hour Curtain Fire Dampers Vertical or Horizontal Mount Installation, Operation and Maintenance Instructions S TAT CALIFOR OF RE AL E L S TAT FI NIA E FD and DFD 150X Series models are intended for installation in accordance with fire damper requirements established by: S T ING LI National Fire Protection Association NFPA Standard 80, 90A, & 101 SE IBC International Building Codes R VIC E CSFM California State Fire Marshal Fire Damper Listing (#3225-0981:102) New York City (BSA/MEA listing #260-91-M) M AR S H “UL CLASSIFIED (see complete marking on product)” “UL CLASSIFIED to Canadian safety standards (see complete marking on product)” UL Standard 555 (Listing #R13317) INSTALLATION SUPPLEMENTS Refer to the appropriate Greenheck installation supplements for special requirements: • Support Mullions • Shaftwall Supplement • Drywall Supplement • Grille Installation Supplement • Drive Slip Supplement • Sealant Supplement • Sleeve Extension Supplement • Single side Retaining Angles Supplement Note: Refer to Greenheck IOM, Part #461335, for CFSD models to be installed in corridor ceiling applications. Refer to Greenheck IOM, Part # 452763 for standard DFD and FD models. SAFETY WARNING: Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating, and maintenance instructions thoroughly before installing or servicing this equipment. RECEIVING AND HANDLING WARRANTY Upon receiving dampers, check for both obvious and hidden damage. If damage is found, record all necessary information on the bill of lading and file a claim with the final carrier. Check to be sure that all parts of the shipment, including accessories, are accounted for. Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the shipment date. Any units or parts which prove to be defective during the warranty period will be repaired or replaced at our option. Greenheck shall not be liable for damages resulting from misapplication or misuse of its products. Greenheck will not be responsible for any installation or removal costs. Greenheck will not be responsible for any service work or backcharges without prior written authorization. Dampers must be kept dry and clean. Indoor storage and protection from dirt, dust and the weather is highly recommended. Do not store at temperatures in excess of 100°F. This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the job is complete. Due to continuing research, Greenheck reserves the right to change specifications without notice. 10 Table of Contents Pre-Installation Guidelines..........................................................................................................................................11 Installation.............................................................................................................................................................12-14 Breakaway Connections.............................................................................................................................................15 Installation for Steel Stud Connection Option...........................................................................................................16 Damper Maintenance..................................................................................................................................................17 Damper Troubleshooting.............................................................................................................................................17 Pre-Installation Guidelines The basic intent of a proper installation is to secure the fire damper in, not to, the opening in such a manner as to prevent distortion and disruption of damper operation. This is accomplished by allowing the fire damper in rated separation openings to expand and for the connecting duct to separate in the event of the collapse of the hanging system. The following items will aid in completing the damper installation in a timely and effective manner. 1. Check the schedules for proper damper locations within the building. Visually inspect the damper for damage and verify that the fusible link is in place or has not separated. If fusible link is not present or has separated, replace link. Never install a fire damper without the proper UL approved fusible link in place. (Fusible link is standard control option. An electric link may have been provided.) 2. Lift or handle damper using sleeve or frame. 3. Install damper accordingly to comply with manufacturer’s appropriate UL procedure file number. 4. Damper must be installed into duct or opening square and free of twist or other misalignment. Damper must not be squeezed or stretched into duct or opening. 5. Damper must be kept clean and protected from dirt, dust and other foreign materials prior to and after installation. Examples of such foreign materials include, but are not limited to: a. Mortar dust b. Drywall dust c. Firesafing materials d. Wall texture e. Paint overspray 6. Damper should be sufficiently covered as to prevent overspray of spray-on insulating, wall texturing, or spray painting when performed within 5 feet of the damper. Excessive dirt or foreign material deposits can cause damper to bind and not operate properly. 7. Caulking is not necessary, nor is it allowed, between the damper sleeve and the wall or floor opening (annular space). However, caulking may be applied to the retaining angles. 8. ACCESS: Suitable access (such that fusible links can be changed) must be provided for damper inspection and servicing. Where it is not possible to achieve sufficient size access, it will be necessary to install a removable section of duct. (Refer to NFPA 90A). 9. The Code Authority Having Jurisdiction (AHJ) must evaluate and provide approval of final installation where variations to these instructions are necessary. 11 Installation - Failure to follow these instructions will void all warranties. These instructions apply to 11/2 hour rated fire dampers mounted in masonry, block or stud walls and concrete floors. Specific requirements in these instructions are mandatory. These instructions meet the requirements of UL 555. Installation shall comply with the requirements of NFPA 90A Standard for the Installation of Air Conditioning and Ventilating Systems. U.L. listing R13317, California State Fire Marshal listings 3225981:102, and New York City BSA/MEA listing 260-91-M as they apply to these dampers. Min. 1 in. Overlap* Retaining Angle Wall or Floor Retaining Angle Sleeve Duct 2 in . M ax . Note: Fire dampers are manufactured and labelled for either vertical or horizontal installation. The dampers must be installed in accordance with the labelling. 6 in . M ax . Damper 6 in . M ax. 1.NO ADDITIONAL SLEEVES ARE REQUIRED The fire damper extended frame is an approved sleeve and can be properly installed without the need for a supplemental field installed sleeve. Damper frame shall extend a maximum of 6 in. (152mm) beyond the wall or floor opening on each side. 2.CLEARANCES REQUIRED BETWEEN FIRE DAMPER SLEEVES AND WALL/FLOOR OPENINGS Fire damper assemblies expand during periods of intense heat. Therefore, it is essential that openings in walls or floors be larger than the fire damper assembly to allow for this expansion. Minimum clearances required between the outside of fire damper sleeve assemblies and wall/floor openings are: • Galvanized steel fire dampers and sleeves: 1/8 in. (3mm) per linear foot of damper width and height with a minimum clearance of 1/4 in. (6mm) .Recommended clearances, for width and/or height dimensions of: 1) 48 in. (1219mm) or less: 1/2 in. (13mm) clearance 2) More than 48 in. (1219mm) and 96 in. (2438mm) or less: 1 in. (25mm) clearance 3) More than 96 in. (2438mm): 11/2 in. (38mm) clearance These are total clearances (ignoring fastener heads) and do not need to be equally spaced around the damper. Refer to Section 3 and Figure 1 for additional installation considerations. Example: A 12 in. x 12 in. (305mm x 305mm) damper would require a minimum clearance of 1/4 in. (6mm). A 48 in. x 12 in. (1219mm x 305mm) damper would require a minimum clearance of 1/2 in. (13mm) on width and 1/4 in. (6mm) on height. 2 in . M ax. *only applicable for damper sizes above 36 in. x 36 in. Figure 1: Retaining angle installation. 3.SECURING THE FIRE DAMPER TO WALL AND FLOOR OPENINGS Fire damper assemblies must be installed in wall and floor openings using retaining angles on each side of the wall or floor as described below: • Retaining angles for 11/2 hour rated dampers with a width and height 48 in. (1219mm) or less must be a minimum of 20 ga. (1mm). Retaining angles for all 3 hour rated dampers and all dampers with a width or height greater than 48 in. (1219mm) must be a minimum of 16 gauge (1.5mm). The leg of the retaining angle on the damper sleeve shall be a minimum of 11/4 in. (32mm). The leg of the retaining angle on the wall/floor shall be long enough to cover the annular space and overlap the wall/floor by a minimum of 1 in. (25mm). •Retaining angles must be attached to the damper using one or more of the following methods of attachment: • tack or spot welds • #10 sheetmetal screws • 1/4 in. (6mm) bolts and nuts • 3/16 in. (4.7mm) steel pop rivets Attachments must be spaced a maximum of 6 in. (152mm) on center and a maximum of 2 in. (51mm) from corners. The angles must be attached to all 4 sides of the sleeve with butt joints at each corner. A minimum of two attachments are required on each side, top and bottom. The angles need not be attached to each other at the corners. 12 • Retaining angles should not be fastened to the wall/ floor material. The angles should only sandwich the wall/floor and allow for damper expansion during periods of intense heat. 4. CONNECTING DUCTS TO THE FIRE DAMPER All duct connections to FD & DFD 150X series extended frame dampers must be “breakaway” type connections. All 1/4are in. minimum connections shown considered breakaway. Factory furnished duct collars on types R & CR fire total clearance dampers are also considered breakaway(see Figure 2 & 3). 1/4 in. minimum total clearance Retaining Angles (See Section 4) 1/4 in. minimum total clearance Wall or Floor Maximum 6 in. See Section 2 e Maximum Wall or Floor 6 in. “K” side Wall or Floor Maximum 6 in. Maximum 6 in. Maximum 6 in. Wall or Floor W Maximum 6 in. Sleeve (see sections 2 & 3) See Section 2 Damper Dampe Duct Duct Type A Damper Duct Duct Damper Damper Retaining Angles Retaining Angles (See SectionAngles 3) Retaining (See Section 3) (See Section 3) Type Type AA Retaining Angles (See Section 4) Type A Wall Wall or Floor or Floor Wall or Floor See Section 2 Damper Damper “K” side Damper Wall or Floor Sleeve (see sections 2 & 3) See Section 2 Damper Duct Duct Duct Duct Type B Wall or Floor On types R & CR factory furnished duct collar qualifies as breakaway connection. On types R & CR factory Type B Type B Type B Duct Wall or Floor Wall or Floor On types R &duct CR factory furnished collar qualifies as breakaway furnished duct collar connection. qualifies as breakaway connection. “K” side Wall or floor Damper Duct Sleeve Type C, CO, CR, & R Damper Duct On types R & CR factory furnished duct collar qualifies as breakaway connection, see Section 5 Damper Duct Type C, CO, CR, & R Type C, CO, CR, & R Figure 2: Vertical Mount Type A, Type B, and Type C, CO, CR, R damper installation diagrams. Type C, CO, CR, & R Figure 3: Horizontal Mount Type A, Type B, and Type C, CO, CR, R damper installation diagrams. When dampers installed horizontally, the ramp must be positioned up as shown in above drawings. Damper Model Maximum Sizes for Single Section Dampers* in. (mm) FD-150X (H or V) 48 x 48 (1219 x 1219) DFD-150X (V) 36 x 36 (914 x 914) DFD-150X (H) 30 x 30 (762 x 762) Note: V = Vertical mount & H = Horizontal * Sizes are based on damper with no transitions. Table 1 13 Recommended Preparation of Openings in Wood and Metal Stud Walls • Frame wall openings as shown in Figure 4 and 4A. •Gypsum wall board must be fastened 12 in. on center to all stud and runner flanges surrounding opening (see Figure 4 and 4A). • Prepare opening between studs and sleeve assembly as shown below (see Figure 5). •All construction and fasteners must meet then requirements of the appropriate wall design. (See UL Fire Resistance Directory) 24 in. o.c. Maximum (metal studs) 24 in. o.c. Maximum (metal studs) Ceiling Runner 12 in. 24 in. o.c. Maximum 2 Panhead Screws 16 in. o.c. Maximum (wood studs) 2 in. (51mm) 2 in. (51mm) 16 in. o.c. Maximum (wood studs) Floor Runner Figure 4: Preparation detail for opening in stud wall. Second set of studs are not required on openings 36 in. x 36 in. (914mm x 914mm) or smaller. Metal Stud Construction Gypsum Wallboard Stud or Runner Retaining Angle 1 in. Min. Damper Sleeve In metal stud construction, exposed steel surfaces need not be covered with gypsum wallboard. Metal stud only Figure 4A Wooden Stud Construction Metal Stud Construction Gypsum Wallboard Gypsum Wa llboard Stud or Runner Stud or Runner Retaining Angl e Retaining Angle 1 in. Min. Damper Sleeve 1 in. Min. In metal stud construction, exposed steel surfaces need not be covered with gypsum wallboard. Damper Sleeve In wood stud construction, gypsum wallboard must cover all wood stud surfaces. Figure 5: Detail of retaining angles and gypsum board application for metal and wooden stud construction. 14 Wooden Stud Construction Duct-Sleeve Connections Traditional Breakaway Style Transverse Joints Transverse joints illustrated in Figure 6 have always been approved as breakaway connections. SMACNA testing has also approved the following variations as breakaway connections. Plain “S” Slip •The breakaway connections shown to the right can be applied with maximum of (2) #10 sheet metal screws on each side and on the bottom located in the center of the slip pocket and penetrating both sides of the slip pocket. •Transverse joints illustrated can be applied as top and bottom joints with Drive Slip - side Drive Slip Joint joints in duct heights up to 20 in. (508mm). Round and Oval Duct Breakaway Connections Round or flat oval ducts connected to factory supplied Type R, CR, or CO damper collars may use #10 sheet metal screws as follows: • Ducts 22 in. (559mm) wide (or dia.) and smaller may use 3 screws. • Ducts larger than 22 in. (559mm) wide (or dia.) may use 5 screws. Hemmed “S” Slip Inside Slip Joint Standing “S” (Alt.) Double “S” Slip Standing “S” Standing “S” (Alt.) Standing “S” (Bar Reinforced) Standing “S” (Angle Reinforced) Figure 6: Traditional breakaway style transverse joints. NOTE: All breakaway connections described may have duct sealant, PA2084T duct sealant adhesive manufactured by Precision, DP1010 water base duct sealant by Design Polymetrics, Grey Pookie, Ductmate PROseal®, or CL Ward S Seal applied in accordance with SMACNA recommendations. Proprietary Flange System Breakaway Connections (Ductmate, Ward, Nexus) Flanged connection systems manufactured by Ductmate, Ward, and Nexus are approved as breakaway connections when installed as illustrated in Figure 7. Fire Damper Sleeve 6 in. long 1/16 in. max. thickness plastic cleats; 12 in. c-c (min. 1 per side) Flanged system angles (TDC by Lockformer, TDF by Engle) TDC and TDF systems are approved as breakaway connections when installed as described in the SMACNA Duct Construction Standards. Standard 6 in. metal clips may be used with spacing (see Figure 8). Three-eighth in. metal bolts and nuts may be used to fasten together corner pieces (see Figure 9). (Attach per manufacturer’s instructions) Do not bolt corners Neoprene gasket between all angles Duct Figure 7: Detail of manufactured flanged system breakaway connections. Clip Spacing Std. Clip Length 6 in. 60 in. Duct 4 Req’d. 6 in. Duct Typical TDC/TDF joint 6 in. Corner Piece 7 in. 48 in. Duct 3 Req’d. Sleeve Duct End Flange 9 in. 36 in. Duct 3 Req’d. 7 in. 5 in. 5 in. 5 in. 5 in. 3/8 in. bolt (optional) 24 in. Duct 2 Req’d. 18 in. Duct & Smaller 1 Req’d. CL Duct Figure 8: Detail of proprietary flanged system breakaway connections. Figure 9: Detail of bolted corner. 15 Installation for Steel Stud Connection (SSC) Option These instructions apply to 11/2 hour rated fire dampers mounted in steel stud walls. Specific requirements in these instructions are mandatory. These instructions meet the requirements of UL555. Installation shall comply with the requirements of NFPA 90A Standard for the Installation of Air Conditioning and Ventilating Systems. U.L. listings R13317 and R13743, California State Fire Marshal listings 3225-981:102 and 3225-1241:101, and New York City BSA/ MEA listing 260-91-M as they apply to these dampers. 1. NO ADDITIONAL SLEEVES OR ANGLES ARE REQUIRED 3. FRAMING OF WALL OPENING Form a wall opening 1/8 in. (3mm) to 1/4 in. (6mm) larger than the OD of the fire damper's extended frame (sleeve) using the same metal studs and techniques required by the wall design per the UL Fire Resistance Directory. Open side of the steel stud channels shall face the fire damper and encompass the damper's retaining bar. The fire damper extended frame is an approved sleeve and the Steel Stud Connection (SSC) Option allows fastening of the fire damper sleeve directly to the wall's steel stud framing. Damper frame shall extend a maximum of 6 in. (152mm) beyond the wall opening on either side. Maximum size fire damper that may be installed using this SSC option is 36 in. W x 36 in. H (914mm x 914mm). 4.APPLY WALLBOARD AFTER DAMPER INSTALLATION 2.INSTALLATION After damper is installed, wallboard shall be applied to steel stud framework in the manner required by the wall design per the UL Fire Resistance Directory listing. Around the damper perimeter use a minimum of 2 connections per side, spaced 12 in. (305mm) maximum and located a maximum of 2 in. (51mm) from each corner. No additional retaining angles are required to complete the installation. Fire damper with SSC option must be in place before the wall is constructed or it can be installed as the wall is being constructed. Wall opening is framed around the fire damper before sheet rock or other wall board material is applied to the steel studs. This installation provides appropriate protection for duct penetrations in fire resistant wall construction using steel studs with a fire resistance rating less than 3 3 hours. The following wall design numbers (as detailed in the UL Fire Resistance Directory) are appropriate for fire damper installations using this SSC option: 5. CONNECTING DUCTS TO THE FIRE DAMPER 3 All duct connections to FD & DFD 150X series extended frame dampers must be “breakaway” type connections. All connections shown on page 5 & 6 are considered breakaway. Factory furnished duct collars on types R, CR, & CO fire dampers are also considered breakaway. 1 Hour Design: U405, U406, U422, U434, U448, U451, U456, U457, U465, U468, U469, U485, U494 11/2 Hour Design: U449, U452, U470, U471 2 2 2 Hour Design: U403, U411, U412, U421, U425, U428, U429, U443, U453, U474, U475, U477, U484, U491, U495 Item Description 3 3 1 FD150X fire damper with SSC option 2 Steel stud wall (see UL Fire Resistance Directory for specific details) 3 Steel stud frame around opening in wall 4 Duct connection (see section 6) 5 Wallboard (see UL Fire Resistance Directory for specific details) 6 Fasteners (see UL Fire Resistance Directory and Section 5) 3 2 3 3 Retaining Bar 1 5 3 4 Retaining Bar 4 1 4 Top Cross-section View 6 1 5 1 3 6 3 3 2 4 Side Cross-Section View Top Cross-section View of Damper in Wall 16 3 Retaining 5 1 2 Side Cross-Section View of Damper in Wall 6 1 4 Damper Maintenance Dampers shall be maintained, cycled, and tested in intervals as stated in the latest editions of NFPA 90A, 92A, and UL 864 unless local codes require more frequent inspections. Dampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, use mild detergents or solvents. If lubrication is desired, do not use oil-based lubricants or any other lubricants that attract contaminant’s such as dust. Damper Trouble Shooting The following is a cause and correction list for common concerns with the dampers. Symptom Damper does not fully open and/or fully close Link separated Possible Cause Corrective Action Frame is 'racked' causing blades to bind on jamb Adjust frame such that it is square and plumb Screws in damper linkage Locate screws and remove Contaminant's on damper Clean with a non-oil based solvent (see Damper Maintenance) Heat Replace link Our Commitment As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice. Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the Library under Warranties. ® Phone: (715) 359-6171 • Fax: (715) 355-2399 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com 453946• DFD & FD 150X Series Rev. 15, August 2013 17 Copyright 2013 © Greenheck Fan Corporation Return to Table of Contents DOCUMENT NUMBER 462721 DFDR-XXX, SEDFDR-XXX, SSDFDR-XXX, FDR-XXX, and SSFDR-XXX MODELS ® 1 1⁄2 Hour Round Fire Dampers Vertical and Horizontal Mount Installation, Operation and Maintenance Instructions DFDR-XXX, SSDFDR-XXX, FDR-XXX, and SSFDRXXX Model Dampers are intended for installation in accordance with fire damper requirements established by: National Fire Protection Association NFPA Standards 80, 90A, 101 and 105 IBC International Building Codes New York City (MEA listing #260-91-M) California State Fire Marshal (CSFM) Fire Listing (3225-0981:0112) “UL CLASSIFIED (see complete marking on product)” “UL CLASSIFIED to Canadian safety standards (see complete marking on product)” UL Standard 555 (Classification #R13317) RECEIVING AND HANDLING SAFETY WARNING: Upon receiving dampers, check for both obvious and hidden damage. If damage is found, record all necessary information on the bill of lading and file a claim with the final carrier. Check to be sure that all parts of the shipment, including accessories, are accounted for. Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating, and maintenance instructions thoroughly before installing or servicing this equipment. Dampers must be kept dry and clean. Indoor storage and protection from dirt, dust and the weather is highly recommended. Do not store at temperatures in excess of 100°F (37°C). WARRANTY Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the shipment date. Any units or parts which prove to be defective during the warranty period will be repaired or replaced at our option. Greenheck shall not be liable for damages resulting from misapplication or misuse of its products. Greenheck will not be responsible for any installation or removal costs. Greenheck will not be responsible for any service work or backcharges without prior written authorization. INSTALLATION SUPPLEMENTS Refer to the appropriate Greenheck installation supplements for special requirements: • Steel Deck Supplement Due to continuing research, Greenheck reserves the right to change specifications without notice. This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the job is complete. 18 Table of Contents Pre-Installation Guidelines........................................................................................................19 Installation............................................................................................................................19-22 Maintenance..............................................................................................................................19 Troubleshooting.........................................................................................................................19 Pre-Installation Guidelines The basic intent of a proper installation is to secure the fire damper in the opening in such a manner as to prevent distortion and disruption of damper operation. This is accomplished by allowing the fire damper in rated separation openings to expand and for the connecting duct to separate in the event of the collapse of the hanging system. The following items will aid in completing the damper installation in a timely and effective manner. 1) Check the schedules for proper damper locations within the building. Visually inspect the damper for damage and verify that the fusible link is in place or has not separated. Dampers will be supplied with a temperature responsive fusible link device. If fusible link is not present or has separated, replace link. Never install a fire damper without the proper UL approved fusible link in place. 2) Lift or handle damper using the frame. Do not lift damper using blades. 3) Do not install screws into the main body area of the damper frame as screws may interfere with and prevent damper blade from opening and/or closing. 4) Damper must be installed into duct or opening free of distortion or other misalignment. Damper must not be squeezed or stretched into duct or opening. Out of round, racked, twisted or misaligned installations can cause torque requirements to exceed damper design. 5) Damper must be kept clean and protected from dirt, dust and other foreign materials prior to and after installation. Examples of such foreign materials include but are not limited to: 1) Mortar dust 2) Drywall dust 3) Firesafing materials 4) Wall texture and 5) Paint overspray. Installation - 6) Damper should be sufficiently covered to prevent overspray if wall texturing or spray painting will be performed within 5 feet of the damper. Excessive dirt or foreign material deposits on damper can cause torque requirements to exceed damper design. 7) Caulking is not allowed between the damper sleeve and the wall or floor opening (annular space). However, caulking may be applied to the retaining plates and a field-applied sealant may be required for the damper sleeve and transitions to meet certain duct leakage standards. 8) ACCESS: Suitable access (such that fusible links can be maintained) must be provided for damper inspection and servicing. Where it is not possible to achieve sufficient size access, it will be necessary to install a removable section of duct. (Refer to NFPA 90A). 9) The Code Authority Having Jurisdiction (AHJ) must evaluate and provide approval of final installation where variations to these instructions are necessary. Failure to follow these instructions will void all warranties. These instructions apply to 1 1/2 hour rated fire dampers mounted (blades must be horizontal) in: 1) masonry, block or stud walls and 2) concrete floors or ceilings. Specific requirements in these instructions are mandatory. Dampers must be installed in accordance with these instructions to meet the requirements of UL 555. The installation of the damper and all duct connections to the damper sleeve shall conform to the latest editions of NFPA 90A, Standard for the Installation of Air Conditioning and Ventilating Systems, and the SMACNA Fire, Smoke and Radiation Damper Installation Guide, and UL Classifications R13317. 19 Installation - Continued 1. C LEARANCES REQUIRED BETWEEN FIRE DAMPER SLEEVES AND WALL/FLOOR OPENINGS Fire damper assemblies expand during periods of intense heat. Therefore, it is essential that openings in walls or floors be larger than the fire damper assembly to allow for this expansion. The wall/floor opening must be a minimum of 7/8 in. (22mm) larger than the outside diameter of the damper. Refer to Section 4 for additional installation considerations. and can be installed without the need for additional field installed sleeves. Gauge of factory furnished sleeve determines the type of duct to sleeve connections required (see table below). Any duct connection other than the breakaway connections are considered rigid. Sleeve Gauge (mm) Duct Dimension Maximum Inches (mm) Type of Duct to Sleeve Connection Permitted 24 (610) Rigid or Breakaway 24 (610) Breakaway only 10 ga. (3.5) RETAINER PLATE (OPTIONAL) CLEARANCE FOR EXPANSION 14 ga. (2) RETAINER PLATE 16 ga. (1.5) BLADE LATCH DUCT CONNECTION AREA ACCESS DOOR TO BE ON SAME SIDE AS BLADE LATCH 2 in. 20 ga. (1mm) Sleeve thickness must not be less than the gauge of the connecting duct. AIRFLOW 2 in. DUCT CONNECTION AREA DO NOT PLACE RETAINER PLATE IN THIS GROOVE 6 in. max. Fig. 1 6 in. max. TW SLEEVE LENGTH 2. S LEEVE LENGTH AND WALL/FLOOR THICKNESS Insert the damper assembly into the prepared opening, to appropriate depth (see Fig. 1). Recommended maximum and minimum insertion depth can be exceeded as long as the CL of the damper blade remains within the plane of the wall/ floor. IMPORTANT SAFETY DANGER! To avoid causing death or serious bodily harm to building occupants, do not insert screws into the damper frame unless used for duct connection within 2 in. (51mm) of the frame end. The sleeve may extend a maximum of 6 in. (152mm) beyond both sides of the wall or floor. Recommended standard sleeve lengths for various wall/floor thicknesses are: UL Standard 555 requires all ducts to terminate at fire damper sleeves. 4. S ECURING THE DAMPER/SLEEVE ASSEMBLY TO WALL AND FLOOR OPENINGS Damper assemblies must be installed in wall/ floor openings using a single retaining plate on either side of the wall/floor or by using a retaining plate on both sides of the wall/floor. The use of a second retaining plate is allowed, but is not necessary. A single retaining plate is provided with the dampers. A second retaining plate can be ordered as an option. •T he retaining plate(s) will open up for easy installation when the clamping screw is loosened. If necessary, remove the clamping screw and nut (see Fig. 2). (IMPORTANT: The clamping mechanism should face away from the wall/floor). Retainer plate(s) are designed to mount flush to the wall/floor and hold the damper in the wall/floor opening. •P lace the damper and attached retainer plate into the wall/floor opening. • If a second retaining plate is being used, secure it on the opposite side of the wall/floor DO NOT POSITION RETAINER PLATE(S) IN FRAME GROOVE Wall/Floor Thickness Dimension (Tw) Inches (mm) Sleeve Length Dimension (L) Inches (mm) Up to 61/2 (165) 13 5/8 (346) 61/2 - 81/2 (165 - 216) 15 5/8 (397) 81/2 - 101/2 (216 - 267) 17 5/8 (448) 3.DUCT TO SLEEVE CONNECTIONS Dampers are supplied with sleeves from the factory 20 •Verify position, blade orientation, and actuator clearance then tighten the retainer plate clamping screws. The retainer plate(s) must overlap the wall/floor opening a minimum of 1 inch (25mm). Secure the retainer plate(s) to the wall using appropriate fasteners (minimum #8 sheet metal screws) at the four corners of each retainer plate when two retainer plates are used and also within 3/4 in. (19mm) of the center of each plate when one retainer plate is used. Opening +2 Opening + in. 2 in.Min. Min. 24 in. o.c. Maximum (metal studs) 24 in. o.c. Maximum (metal studs) Ceiling Runner 12 in. Wall/Floor Opening Wall/Floor Opening = Nominal Size + 7/8 in.in. Min. = Nominal Size + 7/8 Min. Clamping Clamping Screw Screw 1.00 in.in. Typ. 1.00 Typ. 24 in. o.c. Maximum Fasteners Fasteners Nut Nut 2 in . 2 Panhead Screws 16 in. o.c. Maximum (wood studs) Retaining Retaining Plate Assembly Plate Assembly Fig. 2 Second set of studs are not required on openings 36 in. x 36 in. (914mm x 914mm) or smaller. Fig. 4 2 in . 16 in. o.c. Maximum (wood studs) Floor Runner Clamping Screw Clamping Screw 5. R ecommended Preparation of Openings in Wood and Metal Stud Walls • Frame wall openings as shown below. (see Fig. 4 & 4A). • Gypsum wall board must be fastened 12 in. (305mm) on center to all stud and runner flanges surrounding opening. (see Fig. 4 & 4A). • Prepare opening between studs and sleeve assembly as shown below (see Fig. 3). • All construction and fasteners must meet the requirements of the appropriate wall design (See UL Fire Resistance Directory) and/or local codes. Second set of studs are not required on openings 36 in. x 36 in. (914mm x 914mm) or smaller. Metal stud only DAMPER FRAME METAL STUD 1.00 MIN Fig. 4A 6. Round Duct Connections DO NOT PLACE RETAINER PLATE Round duct connections shall be attached with #8 sheet metal screws as follows: • Ducts 22 in. (559mm) dia. and smaller shall have three screws. IN THIS GROOVE. DAMPER FRAME WOOD STUD 1.00 MIN DO NOT PLACE RETAINER PLATE IN THIS GROOVE. Fig. 3 Metal stud only •D ucts larger than 22 in. (559mm) dia. and up to including 24 in. dia. shall have five screws. NOTE: All breakaway connections described may have duct sealant, PA2084T Duct Sealant Adhesive manufactured by Precision or DP1010 Water Base Duct Sealant manufactured by Design Polymetrics, Grey Pookie, Ductmate PROseal® , or CL Ward S Seal applied in accordance with SMACNA recommendations. 21 DFDR-XXX Blade Orientation 30° Axle Axle 30° Axle Normal 30° Off Horizontal (Maximum) 30° Off Horizontal (Maximum) Damper Maintenance Dampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, use mild detergents or solvents. If lubrication is desired for components such as axle bearings, do not use oilbased lubricants or any other lubricants that attract contaminants such as dust. Dampers and their actuator(s) must be maintained, cycled, and tested a minimum in accordance with: • The latest editions of NFPA 80, 90A, 92A, 92B, 101, 105, UL864, AMCA 503-03 and local codes. • Actuator manufacturer recommendations. Damper Troubleshooting The following is a possible cause and correction list for common concerns with the dampers. Symptom Damper does not fully open and/or fully close Possible Cause Corrective Action Frame is out of round causing blades to interfere with frame Adjust frame such that it is round Screws interfere with blade Locate screws and remove Contaminants on damper Clean with a non-oil based solvent (see Damper Maintenance) Heat Replace link Link separated Our Commitment As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice. Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the Library under Warranties. ® Phone: (715) 359-6171 • Fax: (715) 355-2399 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com 462721• DFDR, FDR Series Rev. 9, August 2013 22 Copyright 2013 © Greenheck Fan Corporation Return to Table of Contents Document Number 461337 ® OFSD-XXX, ODFD-XXX, OFD-XXX, and OSSFD-XXX Series 11/2 Hour Combination Fire Smoke or Curtain Fire Dampers Out of Wall or Out of Floor Vertical or Horizontal Mount Installation, Operation, and Maintenance Instructions OFSD-XXX, ODFD-XXX, OFD-XXX, and OSSFD-XXX series dampers are intended for installation in accordance with combination fire smoke dampers requirements established by: NFPA National Fire Protection Association NFPA Standards 80, 90A, 92A, 92B, 101, & 105 IBC International Building Codes New York City (MEA listing # 260-91-M) California State Fire Marshal Listing #3225-0981:103 & 3230-0981:104 “UL Classified (see complete marking on product)” “UL Classified to Canadian safety standards (see complete marking on product)” UL Standard 555 & 555S (Classification R13317) Receiving and Handling Upon receiving dampers, check for both obvious and hidden damage. If damage is found, record all necessary information on the bill of lading and file a claim with the final carrier. Check to be sure that all parts of the shipment, including accessories, are accounted for. Electrical Guidelines All wiring shall be done in accordance with the National Electrical Code ANSI/NFPA-70 latest edition, any local codes that may apply, and wiring diagrams developed in compliance with the job or project design and specifications. Dampers must be kept dry and clean. Indoor storage and protection from dirt, dust and the weather is highly recommended. Do not store at temperatures in excess of 100°F (38°C). Safety Warning: Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating, and maintenance instructions thoroughly before installing or servicing this equipment. Warranty Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the purchase date. Any units or parts which prove to be defective during the warranty period will be repaired or replaced at our option. Greenheck shall not be liable for damages resulting from misapplication or misuse of its products. Greenheck will not be responsible for any installation or removal costs. Greenheck will not be responsible for any service work or backcharges without prior written authorization. Safety Caution! Electrical input may be needed for this equipment. This work should be performed by a qualified electrician. Verify power before wiring actuator. Greenheck is not responsible for any damage to, or failure of the unit caused by incorrect field wiring. To avoid causing death or serious bodily harm to building occupants, follow all instructions carefully. Dampers must close completely to preserve the integrity of the fire smoke separation. Due to continuing research, Greenheck reserves the right to change specifications without notice. This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the job is complete. 23 Table of Contents Pre-Installation Guidelines................................................................................................................................. 24 Installation...................................................................................................................................................... 24-34 • Clearances Requirements..............................................................................................................25-30 • Duct to Sleeve Connections....................................... .........................................................................31 • Securing the Damper/Sleeve Assembly to Wall and Floor Openings.................... ......................31-32 • Actuator Connections.................................... ......................................................................................32 • Recommended Preparation of Openings in Wood and Metal Stud Walls....................................32-33 • Breakaway Connections....................................... .........................................................................33-34 Maintenance.........................................................................................................................................................34 Troubleshooting....................................................................................................................................................34 Pre-Installation Guidelines The basic intent of a proper installation is to secure the fire or fire smoke damper in, not to, the opening in such a manner as to prevent distortion and disruption of damper operation. This is accomplished by allowing the fire or fire smoke damper in rated separation openings to expand and for the connecting duct to separate in the event of the collapse of the hanging system. The following items will aid in completing the damper installation in a timely and effective manner. 1)Check the schedules for proper damper locations within the building. Visually inspect the damper for damage and verify that the Reusable Resettable Link (RRL) is in place or has not activated. Never install a fire damper without the proper UL approved RRL in place. (RRL is standard control option. These electric links have a button for resetting.) If damper is furnished with fusible link, visually inspect the link to verify its not missing or broken. Replace link as necessary. 2)Lift or handle damper using sleeve or frame. Do not lift damper using blades or actuators. 3)Damper has label on outside of sleeve indicating a ‘No Screw’ area. Do not install screws into this area as screws may interfere with unexposed blade linkage and prevent damper blades from opening and/or closing. 4)Damper has label indicating position of damper and sleeve assembly in the wall. Install accordingly to comply with manufacturer’s appropriate UL Classification file number. 5)Damper must be installed into duct or opening square and free of twist or other misalignment. Damper must not be squeezed or stretched into duct or opening. Out of square, racked, twisted or misaligned installations can cause excessive leakage and/or torque requirements to exceed damper/actuator design. 6)Damper and actuator must be kept clean and protected from dirt, dust and other foreign materials prior to and after installation. Examples of such foreign materials include but are not limited to: a) Mortar dust b) Drywall dust c) Firesafing materials d) Wall texture e) Paint overspray 7)Damper should be sufficiently covered as to prevent overspray if wall texturing or spray painting will be performed within 5 feet of the damper. Excessive dirt or foreign material deposits on damper can cause excessive leakage and/or torque requirements to exceed damper/actuator design. 8)Caulking is not necessary, nor is it allowed, between the damper sleeve and the wall or floor opening (annular space). However, caulking may be applied to the retaining angles. 9)ACCESS: Suitable access (such that RRL’s and actuators can be maintained, etc.) must be provided for damper inspection and servicing. Where it is not possible to achieve sufficient size access, it will be necessary to install a removable section of duct. (Refer to NFPA 90A). 10)The Code Authority Having Jurisdiction (AHJ) must evaluate and provide approval of final installation where variations to these instructions are necessary. Installation - Failure to follow these instructions will void all warranties. These instructions apply to 11/2 hour rated combination fire smoke dampers and curtain fire dampers mounted in masonry, block, wood or metal stud walls, or concrete floors. Specific requirements in these instructions are mandatory. These instructions meet the requirements of UL555. Installation shall comply with the requirements of NFPA 90A (Installation of Air Conditioning and Ventilating Systems) and UL listing R13317. 24 the header, sill and jamb framing members. Screw into rear portion of the studs so as to avoid space conflicts with the grille assembly. Factory Supplied Thermal Blanket 1. D AMPER IS INSTALLED OUTSIDE OF WALL PLANE Grille OFSD-XXX (Supplied Factory Supplied Thermal Blanket by others) Figure 1 shows two approved installations for combination fire smoke dampers: 1) “Through the grille access” and 2) installation in continuing duct. To provide “through the grille” access to the damper actuator, the damper is located toward the back of the sleeve and the actuator is installed between the damper and grille. Actuator and damper can be accessed and serviced by removing the grille. To provide access to the damper actuator for continuing ductwork, refer to the 7 1/2 in. Max. requirements of NFPA 90A. 7 1/2 in. Max. Masonry floor Damper Damper “Duct Continues” Horizontal or Vertical Mount Steel stud Gypsum Wallboard Stud or Runner In wood stud construction, gypsum wallboard must cover all wood stud surfaces. Wooden Stud Construction #10 2 1/2 in. long sheet metal screws spaced 6 in. on center and maximum of 2 in. from the corners (minimum of 2 screws per side) through the sleeve into the header, sill and jamb framing members. Screw into rear portion of the studs so as to avoid space conflicts with the grille assembly. Flange Retaining Angle (Refer to section 4) Factory Supplied Thermal Blanket Factory Supplied Thermal Blanket Grille (Supplied by others) #10 sheet metal screws, 2 1/2 inches long, spaced 6 in. on center and maximum of 2 in. from corners (minimum of 2 screws per side). Screw into rear portion of the studs so as to avoid space conflicts with the grille assembly. Factory Supplied Thermal Blanket Grille (Supplied by others) 7 1/2 in. Max. Masonry floor Damper 7 1/2 in. Max. Damper 6 1/2 in. Max. “Duct Terminates” Metal Stud Fire damper or combination fire smoke damper “Duct Terminates” Wood Stud (Duct Terminates) Note: Both installations for vertical mount. Figure 1: Installation configurations for ‘Out of Wall’ combination fire smoke dampers. ODFD-XXX, OFD-XXX, and OSSFD-XXX: Figure 2 shows installations that are also approved for curtain fire dampers. For access to inspect the damper and fusible link, refer to the requirements of NFPA 90A. 25 2. CLEARANCE REQUIREMENTS There is no minimum clearance requirement between the wall/floor opening and the sleeve exterior (with thermal blanket attached). However, to facilitate installation, clearances between the wall/floor opening and the damper sleeve are recommended. although there is no maximum allowable clearance, the minimum overlap requirements between the wall/floor and the flange/retaining angle must be met. On grill mount installations the flange must overlap the wall/floor by 1⁄2 in. (13mm). On continuous duct installations, the retaining angles must overlap the wall/floor by 1 in. (25mm). Because no clearances are required between the wall/floor opening and the sleeve, dampers may not be installed in the plane of the wall using this installation method. Figure 2 Concrete or Masonry Wall Concrete or Masonry Wall Wood Stud Flange 7 1/2 in. (191mm) maximum 7 1/2 in. (191mm) max. Damper Wood Stud Steel Stud Flange Steel Stud Damper Factory Supplied Thermal Blanket Flange Retaining Angle Alternate Retaining Angle Location Type A- Vertical Mount, Duct Terminates Single Angle Method Factory Supplied Thermal Blanket Type A- Vertical Mount, Duct Terminates Flange Method Damper Factory Supplied Thermal Blanket Retaining Angle 7 1/2 in. (191mm) max. Concrete or Masonry Floor Flange Masonry or Concrete Floor Type A - Horizontal Mount Above Floor/Wall, Duct Terminates Single Angle Method Factory Supplied Thermal Blanket 7 1/2 in. (191mm) max. Retaining Angle Damper Concrete or Masonry Floor Type A - Horizontal Mount Below Floor/Wall, Duct Terminates Flange Method 7 1/2 in. (191mm) max. Factory Supplied Thermal Blanket Damper Type A - Horizontal Mount Below Floor/Wall, Duct Terminates Single Angle Method 26 Figure 2 cont... Masonry or Concrete Wall Wood Stud 7 1/2 in. (191mm) max. Damper Factory Supplied Thermal Blanket Retaining Angle Concrete or Masonry Wall Metal Stud Damper 7 1/2 in. (191mm) maximum Factory Supplied Thermal Blanket Retaining Angle Retaining Angle Alternate Retaining Angle Location Type A- Vertical Mount, Thru Duct with Single Retaining Angle Type A- Vertical Mount, Thru Duct with Two Retaining Angles Damper Retaining Angle Wood Stud Damper Retaining Angle 7 1/2 in. (191mm) max. Masonry or Concrete Floor 7 1/2 in. (191mm) maximum Concrete or Masonry Floor Factory Supplied Thermal Blanket Retaining Angle Factory Supplied Thermal Blanket Type A - Horizontal Mount Above Floor/Wall, Thru Duct with Single Retaining Angle Type A - Horizontal Mount Above Floor/Wall, Thru Duct with Two Retaining Angles Retaining Angle Retaining Angle Concrete or Masonry Floor Masonry or Concrete Floor Retaining Angle Factory Supplied Thermal Blanket 7 1/2 in. (191mm) max. 7 1/2 in. (191mm) maximum Factory Supplied Thermal Blanket Damper Type A - Horizontal Mount Below Floor/Wall, Thru Duct with Single Retaining Angle Type A - Horizontal Mount Below Floor/Wall, Thru Duct with Two Retaining Angles 27 Figure 2 cont.... Wood Stud 7 1/2 in.(191mm) Maximum Damper Metal Stud Masonry or Concrete Damper 7 1/2 in. (191mm) maximum Wood Stud Factory Supplied Thermal Blanket Steel Stud Retaining Angle Retaining Angle Flange Type B2- Vertical Mount, Thru Duct with Two Retaining Angles Factory Supplied Thermal Blanket Masonry or Concrete Damper Type B2- Vertical Mount, Duct Terminates Flange Method Factory Supplied Thermal Blanket Retaining Angle 7 1/2 in. (191mm) maximum Flange Masonry or Concrete Masonry or Concrete Retaining Angle Factory Supplied Thermal Blanket Type B2 - Horizontal Mount Above Floor/Wall, Thru Duct with Two Retaining Angles 7 1/2 in. (191mm) maximum Damper Factory Supplied Thermal Blanket Retaining Angle Masonry or Concrete Type B2 - Horizontal Mount Below Floor/Wall, Duct Terminates Flange Method 7 1/2 in. (191mm) maximum Retaining Angle Damper Type B2 - Horizontal Mount Below Floor/Wall, Thru Duct with Two Retaining Angles 28 Figure 2 cont.... 7 1/2 in. (191mm) maximum Damper Wood Stud Concrete or Masonry Damper 7 1/2 in. (191mm) maximum Metal Stud Concrete or Masonry Factory Supplied Thermal Blanket Retaining Angle Factory Supplied Thermal Blanket Retaining Angle Alternate Retaining Angle Location Alternate Retaining Angle Location Type B2- Vertical Mount, Thru Duct with Single Retaining Angle Type B2- Vertical Mount, Duct Terminates Single Angle Method Damper Damper Factory Supplied Thermal Blanket Retaining Angle Retaining Angle 7 1/2 in. (191mm) maximum Concrete or Masonry 7 1/2 in. (191mm) maximum Concrete or Masonry Type B2 - Horizontal Mount Above Floor/Wall, Duct Terminates Single Angle Method Factory Supplied Thermal Blanket Type B2 - Horizontal Mount Above Floor/Wall, Thru Duct with Single Retaining Angle Retaining Angle Factory Supplied Thermal Blanket Concrete or Masonry Retaining Angle Concrete or Masonry 7 1/2 in. (191mm) maximum Factory Supplied Thermal Blanket 7 1/2 in. (191mm) maximum Damper Damper Type B2 - Horizontal Mount Below Floor/Wall, Duct Terminates Single Angle Method Type B2 - Horizontal Mount Below Floor/Wall, Thru Duct with Single Retaining Angle 29 Figure 2 cont.... Damper Wood Stud 7 1/2 in. (191mm) maximum Wood Stud 7 1/2 in. (191mm) maximum Metal Stud Flange Concrete or Masonry Concrete or Masonry Factory Supplied Thermal Blanket Retaining Angle Metal Stud Retaining Angle Factory Supplied Thermal Blanket Type C2- Vertical Mount, Thru Duct with Two Retaining Angles Type C2- Vertical Mount, Duct Terminates Flange Method Damper Factory Supplied Thermal Blanket Retaining Angle Factory Supplied Thermal Blanket 7 1/2 in. (191mm) maximum Damper 7 1/2 in. (191mm) maximum Concrete or Masonry Concrete or Masonry Retaining Angle Flange Type C2 - Horizontal Mount Above Floor/ Wall, Duct Terminates Flange Method Type C2 - Horizontal Mount Above Floor/Wall, Thru Duct with Two Retaining Angles Flange Retaining Angle Concrete or Masonry Concrete or Masonry 7 1/2 in. (191mm) maximum Factory Supplied Thermal Blanket Retaining Angle Damper 7 1/2 in. (191mm) maximum Factory Supplied Thermal Blanket Damper Type C2 - Horizontal Mount Below Floor/Wall, Thru Duct with Two Retaining Angles Type C2 - Horizontal Mount Below Floor/Wall, Duct Terminates Flange Method 30 Figure 2 cont.... Wood Stud 3. DUCT TO SLEEVE CONNECTIONS Dampers are supplied with actuators (on applicable models) and sleeves from the factory and can be installed without the need for additional field installed sleeves. Metal Stud 7 1/2 in. (191mm) maximum Sleeve gauges of 20-14 (.9mm - 2mm) are to be used. UL Standard 555 requires all ducts to terminate at fire damper sleeves. Sleeve thickness must not be less than the gauge of the connecting duct. Concrete or Masonry Duct to sleeve breakaway connections must be of the type described on page 33. Factory furnished round duct collars on type R and CR dampers are also considered to be breakaway connections and may be used. Factory Supplied Thermal Blanket Alternate Retaining Angle Location Type C2- Vertical Mount, Thru Duct with Single Retaining Angle Flange Thermal Blanket (installed around entire outside surface of sleeve) Damper Factory Supplied Thermal Blanket Retaining Angle 7 1/2 in. (191mm) maximum Wall Concrete or Masonry Figure 3: Sleeved damper with Thermal Blanket (duct termination). 4. S ECURING THE DAMPER/SLEEVE ASSEMBLY TO WALL OPENINGS. Damper/sleeve assemblies must be installed in wall openings using flanges and sheet metal screws as illustrated and described below. Type C2 - Horizontal Mount Above Floor/Wall, Thru Duct with Single Retaining Angle • Flange on front (grille end) of sleeve must be a minimum of 16 gauge (1.5mm) steel and have a 5⁄8 in. (16mm) minimum flange leg (refer to Figure 3). Using #10 (19mm) sheet metal screws, screw from inside of sleeve through the rear portion of the studs (as shown in Figure 1). Space screws a maximum of 6 in. (152mm) on center and a maximum of 2 in. (51mm) from the corners (minimum of 2 screws per side). No retaining angles are required on the side of wall opposite from the grille. Retaining Angle Concrete or Masonry 7 1/2 in. (191mm) maximum • Retaining angles for 11/2 hour rated dampers with a width and height 48 in. (1219mm) or less must be a minimum of 20 ga. (1mm). Retaining angles for all 3 hour rated dampers and all dampers with a width or height greater than 48 in. (1219mm) must be a minimum of 16 gauge (1.5mm). The leg of the retaining angle on the damper sleeve shall be a minimum of 11/4 in. (32mm). The leg of the retaining angle on the wall/floor shall be long enough to cover the annular space and overlap the wall/floor by a minimum of 1 in. (25mm)(see Figure 4). Factory Supplied Thermal Blanket Damper Type C2 - Horizontal Mount Below Floor/Wall, Thru Duct with Single Retaining Angle 31 4. S ECURING THE DAMPER/SLEEVE ASSEMBLY TO WALL OPENINGS continued.... Retaining Angle • Retaining angles must be attached to the sleeve using one or more of the following methods of attachment: • Tack or spot welds • #10 (19mm) sheet metal screws • 1⁄4 in. (6mm) bolts and nuts • 3⁄16 in. (4.7mm) steel pop rivets Thermal Blanket (installed around entire outside surface of sleeve) 2i n. 6i n. Attachments must be spaced a minimum of 6 in. (152mm) on center and a maximum of 2 in. (51mm) from corners. The angles must be attached to all 4 sides of the sleeve. A minimum of two attachments are required on each side, top and bottom. The angles need not be attached to each other at the corners. 6i n. 2i n. Ma x. Ma x. Ma x. Ma x. Wall Caution! Do not tear the thermal blanket during Figure 4: Sleeved damper with Thermal Blanket (duct continuation). installation. Dampers are tested for correct operation and are square and straight before shipment from the factory. Dampers must be installed square and straight and must not be twisted or racked. Failure to install the damper square and straight may prevent the damper blades from operating open and closed. Note: Thermal blanket is riveted to the damper sleeve and the seam is taped with acrylic adhesive tape, FSK facing tape 152 5CWnt, manufactured by Venture Tape Company. 5. ACTUATOR CONNECTIONS Electrical and/or pneumatic connections to damper actuators should be made in accordance with wiring and piping diagrams developed in compliance with applicable codes, ordinances and regulations (see Electrical Guidelines). 24 in. o.c. Maximum (metal studs) 24 in. o.c. Maximum (metal studs) Ceiling Runner 12 in. 6R ecommended Preparation of Openings in Wood and Metal Stud Walls • Frame wall openings as shown (see Figure 5 & 5A) 24 in. o.c. Maximum • Gypsum wall board must be fastened 12 in. (305mm) on center to all stud and runner flanges surrounding opening (see Figure 5 & 5A). • Prepare opening between studs and sleeve assembly as shown (Figure 6 & 7). 2 Panhead Screws • All construction and fasteners must meet the requirements of the appropriate wall design (See UL Fire Resistance Directory) and/or local codes. 16 in. o.c. Maximum (wood studs) 16 in. o.c. Maximum (wood studs) Floor Runner Figure 5 Second set of studs are not required on openings 36 in. x 36 in. (914mm x 914mm) or smaller. Figure 5A Metal stud only 32 2 in. (51mm) 2 in. (51mm) Damper Sleeve Metal Stud Construction exposed steel surfaces need not be covered with gypsum wallboard. Wooden Stud Construction Gypsum Wallboard Gypsum Wallboard Stud or Runner Stud or Runner Retaining Angle Retaining Angle 1 in. Min. 1 in. Min. Damper Sleeve In metal stud construction, exposed steel surfaces need not be covered with gypsum wallboard. Damper Sleeve Figure 6 In wood stud construction, gypsum wallboard must cover all wood stud surfaces. Figure 7 Wooden Stud Construction Breakaway Connections Gypsum Wallboard Traditional Breakaway Style Transverse Joints Stud or Runner Transverse joints illustrated at right have always been approved as breakaway connections. SMACNA testing has also approved the following variations as breakaway Retaining Angle connections. Plain “S” Slip Hemmed “S” Slip Double “S” Slip 1 in. Min. • The breakaway connections shown (Figure 8) can be applied with maximum of In wood stud construction, Damper (19mm) two #10 sheet metal Sleeve gypsum wallboard must cover screws on each side on all wood studand surfaces. Drive Slip Joint the bottom located in the Figure 7 center of the slip pocket and penetrating both sides of the slip pocket. Inside Slip Joint Standing “S” (Alt.) • Transverse joints illustrated can be applied as top and bottom joints with Drive Slip - side joints in duct heights up to 20 inches (508mm) See Figure 7. • Ducts to 22 in. (558mm) wide (or dia.) and smaller shall have three screws. • Ducts larger than 22 in. (558mm) wide (or dia.) up to and including 36 in. (914mm) wide (or dia.) shall have five screws. Standing “S” (Bar Reinforced) Standing “S” (Alt.) Standing “S” (Angle Reinforced) Figure 8 Fire Damper Sleeve 6 in. long 1/16 in. max. thickness plastic cleats; 12 in. c-c (min. 1 per side) Round and Oval Duct Breakaway Connections Round or flat oval ducts connected to Type R or O damper collars shall be attached with #10 (19mm) sheet metal screws as follows: Standing “S” Flanged system angles (Attach per manufacturer's instructions) Do not bolt corners Neoprene gasket between all angles NOTE: All breakaway connections described may have duct sealant applied, PA2084T duct sealant adhesive manufactured by Precision, DP1010 water base duct sealant manufactured by Design Polymetrics, Grey Pookie, Ductmate PROseal®, or CL Ward S Seal in accordance with SMACNA recommendations. Duct Figure 9 Proprietary Flange System Breakaway Connections (TDC by Lockformer, TDF by Engle) TDC and TDF systems are approved as breakaway connections when installed as described in the TDC or TDF addendum to the SMACNA Duct Construction Standards except the corners may not be bolted. Standard 6 in. (152mm) metal clip may be used with spacing as shown in Figure 10. 3/8 in. (9.5mm) metal bolts and nuts may be used to fasten Sleeve Duct together corner pieces (see Figure 11). Manufactured Flanged System Breakaway Connections Flanged connection systems manufactured by Ductmate, Ward, and Nexus are approved as breakaway connections when installed as illustrated (Figure 9). Clip Spac 6 in 60 in. Duct 4 Req’d. 48 in. Duct 3 Req’d. 36 in. Duct 3 Req’d. 24 in. Du 2 Req’d Typical TDC/TDF joint 33 18 in S 1 Clip Spacing Duct End Flange Std. Clip Length 9 in. 6 in. 6 in. Corner Piece 6 in. 60 in. Duct 4 Req’d. 7 in. 48 in. Duct 3 Req’d. 7 in. 5 in. 3/8 in. bolt (optional) 5 in. 36 in. Duct 3 Req’d. Duct 5 in. 5 in. 24 in. Duct 2 Req’d. C/TDF joint 18 in. Duct Smaller 1 Req’d. & Figure 11 CL Duct Figure 10: Detail of proprietary flanged system breakaway connections. Damper Maintenance Dampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, use mild detergents or solvents. If lubrication is desired for components such as axle bearings, jackshaft bearings and jamb seals, do not use oil-based lubricants or any other lubricants that attract contaminants such as dust. Dampers and their actuator(s) must be maintained, cycled, and tested a minimum in accordance with: • The latest editions of NFPA 80, 90A, 92A, 92B, 101, 105, UL864, AMCA 503-03 and local codes. • Actuator manufacturer recommendations. Damper Troubleshooting The following is a possible cause and correction list for common concerns with the dampers. Symptom Possible Cause Corrective Action Frame is 'racked' causing blades to bind on jamb seals Adjust frame such that it is square and plumb Actuator linkage loose Close damper, disconnect power, adjust and tighten linkage Defective motor Replace Screws in damper linkage Damper installed too far into wall. Move out to line as designated on damper label Contaminants on damper Clean with a non-oil based solvent (see Damper Maintenance) RRL or TOR sensor tripped Heat Push reset button located on backside of RRL or TOR Damper does not operate No power supplied to the actuator Add power supply Damper does not fully open and/or close Our Commitment As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice. Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the Library under Warranties. ® Phone: (715) 359-6171 • Fax: (715) 355-2399 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com 461337• ODFD OFD Rev. 14, August 2013 34 Copyright 2013 © Greenheck Fan Corporation Return to Table of Contents Document number 474015 Single Side Retaining Angle ® Installation Instructions Supplement FD & DFD Series Refer to: ‘Installation Instructions for FD, DFD, SSFD, & KFD Models’ (Part #452763) or ‘Installation Instructions for FSD-XXX, DFD-XXX, SSFSDXXX & CFSD-XXX Series Fire & Combination Fire Smoke Dampers’ (Part #461336) or ‘Installation Instructions for FD & DFD 150X Series Curtain Fire Dampers’ (Part #453946) for additional details. 11/2 Hour Fire Dampers and FSD Series 11/2 Hour Combination Fire Smoke Dampers “UL CLASSIFIED (see complete marking on product)” “UL CLASSIFIED to Canadian safety standards (see complete marking on product)” Standards UL 555 & 555S Classifications Filed at UL under Listing #R13317 Single side retaining angle These instructions apply to 11/2 hour rated combination fire smoke dampers and curtain fire dampers mounted in masonry or block walls, metal stud walls, wood stud walls or concrete floors. Specific requirement in these instructions are mandatory. These instructions meet the requirements of NFPA 90A (Standard for the Installation of Air Conditioning and Ventilating Systems). Vertical mount dampers up to a maximum size of 80 in. W x 50 in. H (2032mm x 1270mm), 50 in. W x 80 in. H (1270mm x 2032mm), or 40 in. W x 100 in. H (1016mm x 2540mm) or horizontal mount dampers up to a maximum size of 144 in. W x 96 in. H (3658mm x 2438mm) may be installed as illustrated below. Larger damper assemblies require retaining angles on both sides of the partition. Note: Model specific size limits can be found in the base installation instruction documents noted above. dampers with a width or height greater than 48 in. (1219mm) must be a minimum of 16 ga. (1.5mm). The leg of the retaining angle on the damper sleeve shall be a minimum of 1 1/4 in. (32mm). The leg of the retaining angle on the wall/floor shall be long enough to cover the annular space and overlap the wall/floor by at least 1 in. (25mm). For metal stud partitions only, the single-side mounting angle may be directly attached to the metal stud prior to the installation of the drywall. • Retaining angles must be attached to the sleeve using one of the methods shown below: • tack or spot welds • #10 sheet metal screws • 1/4 in. (6mm) nuts and bolts • Retaining angles must be attached to the partition using one of the methods shown below: • Drywall screws of a length such that the screw engages the steel stud/track by 1/2 in. (13mm) (steel framing). 1. Clearance Requirements On vertical mount single side angle installations there are no minimum clearance requirements between the wall opening and the damper sleeve. However, to facilitate installation, clearances between the wall opening and the damper sleeve are recommended. On horizontal mount single side angle installations a minimum clearance is required between the outside of the damper sleeve and the floor opening of 1/8 in. per foot (3mm per .3m) of damper width and 1/8 in. per foot (3mm per .3m) height with a minimum clearance of 1/4 in. (6mm). The maximum overall clearance is 1 1/2 in. (38mm), 2. Securing the Damper/Sleeve Assembly to Wall/ Floor Opening Retaining angles must be attached to both the sleeve and the partition (see figures 1-8). •R etaining angles for dampers with a width and height of 48 in. (1219mm) or less must be a minimum of 20 ga. (1mm). Retaining angles for 35 2. Securing the Damper/Sleeve Assembly to the Wall/Floor opening cont....... • Drywall screws of a length such that the screw engages the wood stud by 13/4 in. (44mm) (wood framing). • Steel anchors or self tapping concrete screws penetrating masonry or block 11/4 in. (31mm). • A minimum of two connections per side are required. Additional connections must be made at a maximum of 12 in. (305mm) O.C. (on center) maximum for openings of 48 in. W x 36 in. H (1219mm x 914mm) and less, and 6 in. (152mm) O.C. (on center) for openings 80 in. W x 50 in. H (2032mm x 1270mm), 50 in. W x 80 in. H (1270mm x 2032mm), and 40 in. W x 100 in. H (1016mm x 2540mm) or less. Damper Sleeve Damper Sleeve 2 1/2 in. Min. Stud or Runner 2 1/2 in. min. Stud or Runner 1/2 in. UL Classified Gypsum Wallboard (see UL Rated Wall Design for Additional Details) Angle Fastener (see Section 2) Two layers of 1/2 in. UL Classified Gypsum Wallboard (see UL Rated Wall Design for Additional Details) Angle Fastener (See Section 2) Figure 1: 1 Hour Wall Rating Figure 2: 2 Hour Wall Rating Two layers of 1/2 in. UL Classified Gypsum Wallboard (see UL Rated Wall Design for Additional Details) 1/ 2 2 1/2 in. Min. Metal Stud or Runner Damper Sleeve in. UL Classified Gypsum Wallboard (see UL Rated Wall Design for Additional Details) 2 1/2 in. min. Metal Stud or Runner Damper Sleeve Angle Fastener (see Section 2) Angle Fastener (See Section 2) Figure 3: 1 Hour Wall Rating Figure 4: 2 Hour Wall Rating Damper Sleeve Damper Sleeve 2 1/2 in. Min. Stud or Runner 2 1/2 in. Min. Stud or Runner 1/ 2 in. UL Classified Gypsum Wallboard (see UL Rated Wall Design for Additional Details) 1/ 2 in. UL Classified Gypsum Wallboard (see UL Rated Wall Design for Additional Details) Angle Fastener (see Section 2) Angle Fastener (see Section 2) Figure 6: 2 Hour Wall Rating Figure 5: 1 Hour Wall Rating 36 2. Securing the Damper/Sleeve Assembly to the Wall/Floor opening cont....... Top Side Damper Sleeve Angle Fastener (see Section 2) Damper Sleeve Masonry or Concrete Wall Masonry or Concrete Floor Angle Fastener (see Section 2) Figure 7: Masonry or Concrete Wall Figure 8: Concrete Floor Note: For horizontal installations, retaining angles must be mounted on top side of partition. Space screws a maximum of 6 in. (152mm) on center and a maximum of 2 in. (51mm) from the corners (minimum of 2 screws per side). See Figure 9 and Figure 10. Grille Installations (Dampers up to 36 in. x 36 in. [914mm x 914mm] maximum) • Angle legs may be reversed and one leg inserted into the wall/floor opening. Retaining angles used in conjunction with grille installations must be a minimum of 20 gauge (1mm) steel and have a minimum of 5/8 in. x 1 in. (15mm x 25mm) 20 gauge (1mm) steel. Note: Screws used to attach grille are allowed to penetrate reversed angle leg. Damper Sleeve Damper Sleeve #10 sheet metal screws spaced 6 in. on center and a maximum of 2 in. from the corners (minimum of 2 screws per side). Screw into studs so as to avoid space conflicts with the grille #10 sheet metal screws spaced 6 in. on center and a maximum of 2 in. from the corners (minimum of 2 screws per side). Screw into studs so as to avoid space conflicts with the grille 2 1/2 in. Min. Stud or Runner Angle Fastener (see Note 2) Grille (supplied by others) 1 /2 in. UL Classified Gypsum Wallboard (see UL Rated Wall Design for Additional Details) 2 1/2 in. Min. Stud or Runner Angle Fastener (see Note 2) Retaining Angle (See Section 2) Grille (supplied by others) Figure 9: 1 Hour Wall Rating Two layers of 1/2 in. UL Classified Gypsum Wallboard (see UL Rated Wall Design for Additional Details) Retaining Angle (See Section 2) Figure 10: 2 Hour Wall Rating Copyright © 2013 Greenheck Corporation 474015 Single Side Retaining Angle Suppl Rev. 3 Jan 2013 37 DATE NOTES 38 DATE NOTES 39 Copyright ©2013 Greenheck Fan Corporation 826251 Curtain Packet August 2013