45521 LaMarche P_25_C A P fix for web.qxd 12/4/2003 11:54 AM Page 1 DIGITAL C.A.P. SYSTEMS DIGITAL C.A.P. SYSTEMS (COMBINED ACCESSORY PACKAGE) (COMBINED ACCESSORY PACKAGE) Option Codes ISO 9001 CERTIFIED Standard Features Selectable Digital LED Display for DC Voltage, DC Amps (Current), Timer Mode and Equalize Time Remaining (hrs) • Multi-Mode Equalize Timer & Light; adjustable from 1-144 hrs with five selectable modes: Standard, 7-day, 14-day, 30-day and Equalize after Low DC Voltage • AC Pilot Light • AC Power Failure Alarm (except 16H) Adjustable Time Delay (0-255 sec) (De-Energizes during alarm condition) • Low DC Current Alarm Adjustable Time Delay (0-255 sec) (De-Energizes during alarm condition) • Low DC Voltage Alarm Adjustable Time Delay (0-255 sec) (De-Energizes during alarm condition) • Low DC Voltage 2 Alarm Adjustable Time Delay (0-255 sec) (De-Energizes during alarm condition) • High DC Voltage Alarm Adjustable Time Delay (0-255 sec) (Energizes during alarm condition) • High DC Voltage Shutdown Alarm Adjustable Time Delay (0-255 sec) (Energizes during alarm condition) THE ULTIMATE ACCESSORY FOR YOUR LAMARCHE BATTERY CHARGER The Digital C.A.P. (Combined Accessory Package) Systems feature a microprocessor-based design that incorporates the most popular alarms combined with a Multi-Mode Equalize Timer and a Digital LED Display in one convenient factory installed package. The Alarm relay contacts and LED indicators allow the user to report faulty conditions remotely and locally. Alarm conditions are reported via Form “C” contacts to alert the operator of a faulty condition of the DC Power System and take corrective actions. Individual Alarm LED indicators and the Digital Display are provided for local supervision. You are not limited to a one size fits all either - several Digital C.A.P. System configurations are offered to meet your specific needs. Whether Ground Detection, Low Voltage Battery Disconnect, Low Voltage Load Disconnect or an Audible Alarm is required, LaMarche offers a wide variety of solutions for every application. Completely user-friendly, the Digital C.A.P. System alarm settings can be adjusted and calibrated in the field without the need of special tools or equipment. Best of all, adjustments can be made when the battery is online without affecting the load thus reducing costly downtime. • Positive & Negative Ground Alarm (16J, 16Q, 16T & 16U only) (Energizes during alarm condition) • Summary Alarm Adjustable Time Delay (0-255 sec) (De-Energizes during alarm condition) All alarm contacts are rated for 0.5A @ 120VAC, 2A @ 30VDC and 0.25A @ 125VDC 16E 16G 16H 16J 16L 16P 16Q 16T 16U Features Available on Charger Models Digital Selectable LED Display for: DC Voltage, DC Current (Amps), Timer Mode, Equalize Time Remaining (hrs) Multi-Mode Digital Equalize Timer; adjustable from 1-144 hrs w/ five selectable modes: Standard, 7-day, 14-day, 30-day, Equalize after Low DC Voltage Equalize Light (Amber LED) AC Pilot Light (Green LED) AC Power Failure Relay w/ (2) sets Form "C" Low DC Current Alarm Light (Red LED) w/ (2) sets Form "C" Low DC Voltage Alarm Light (Red LED) w/ (2) sets Form "C" Low DC Voltage Alarm Light (Red LED) only - no contacts Low DC Voltage 2 Alarm Light (Red LED) w/ (2) sets Form "C" Low DC Voltage 2 Alarm Light (Red LED) w/ (1) set Form "C" – utilized for Low Voltage Battery Disconnect Low DC Voltage 2 Alarm Light (Red LED) w/ (1) set Form “C” – utilized for Low Voltage Load Disconnect Low DC Voltage 2 Alarm Light (Red LED) only - no contacts High DC Voltage Alarm Light (Red LED) w/ (2) sets Form "C" High DC Voltage Alarm Light (Red LED) only - no contacts High DC Voltage Shutdown Alarm Light (Red LED) w/ (1) set Form "C" Positive Ground Alarm Light (Green LED) w/ (1) set Form "C" Negative Ground Alarm Light (Green LED) w/ (1) set Form "C" Summary Alarm w/ (2) sets Form "C" includes: AC Power Failure (except 16H), Low DC Current (can be de-selected), Low DC Voltage, Low DC Voltage 2, High DC Voltage, High DC Voltage Shutdown (except 16H). Adds Positive & Negative Ground on 16J, 16Q, 16T & 16U. Summary Alarm w/ (1) set Form “C” includes: AC Power Failure, Low DC Current (can be de-selected), Low DC Voltage, Low DC Voltage 2, High DC Voltage, High DC Voltage Shutdown. Adds Positive & Negative Ground on 16T. Audible Alarm w/ Silence Switch A12B A12B A46 A12B PPC --- ----- --- --- ----- ----- --- --- --- ----- ----- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ----- ----- ------- --- --- --- --- --- --- ----- ----- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- DIGITAL C.A.P. DESCRIPTIONS Digital C.A.P. Systems common features EXCEPT 16H : Selectable LED Display, Multi-Mode Equalize Timer, Equalize Light, AC Pilot Light , AC Power Failure Relay w/ (2) sets Form "C", Low DC Current Alarm Light w/ (2) sets Form "C", & Low DC Voltage Alarm Light w/ (2) sets Form "C". 16E (for LaMarche Chargers models A12B & A46 only): Low DC Voltage 2 Alarm Light w/ (2) sets Form "C", High DC Voltage Alarm Light w/ (2) sets Form "C", High DC Voltage Shutdown Alarm Light w/ (1) set Form "C", Summary Alarm (all alarms listed above) w/ (2) sets Form "C" (Low DC Current can be de-selected). 16G (for LaMarche Charger model A12B only): Low DC Voltage 2 Alarm Light utilized for Low Voltage Battery Disconnect w/ (1) set Form "C", High DC Voltage Alarm Light With its uncomplicated interface, operating these Digital C.A.P. Systems is easy; Meter readings, Equalize and Calibration modes are accessed via the multi-functional Eq/Select switch. All alarm settings are stored in memory - the last becomes the new default setting even if an extended power failure occurs. The LED indicators are instantaneously alarmed and the alarm relays have an adjustable time delay of 0-255 seconds with the exception of the Ground Detection Alarms (16J, 16Q, 16T & 16U only) which have no time delay. The Multi-Mode Equalize Timer is field programmable and has Equalize settings that are adjustable from 1-144 hrs in five different modes; Standard, 7-day, 14-day, 30day and Equalize after Low DC Voltage, allowing you to select the right mode for your application. An Equalize LED is displayed on the front panel when the timer is in operation and an Equalize Time Remaining feature can be viewed through the selectable Digital Display. w/ (2) sets Form "C", High DC Voltage Shutdown Alarm Light w/ (1) set Form "C", Summary Alarm (all alarms listed above) w/ (2) sets Form "C" (Low DC Current can be deselected). 16H (for LaMarche Charger model PPC only): Low DC Voltage Alarm Light only (no contacts), Low DC Voltage 2 Alarm Light only (no contacts), High DC Voltage Alarm Light only (no contacts), Summary Alarm (all alarms listed above) w/ (2) sets Form "C" (Low DC Current can be de-selected). 16J (for LaMarche Charger model A12B only): Low DC Voltage 2 Alarm Light only (no contacts), High DC Voltage Alarm Light w/ (2) sets Form "C", High DC Voltage Shutdown Alarm Light w/ (1) set Form "C", Positive Ground Alarm Light w/ (1) set of Form "C", Negative Ground Alarm Light w/ (1) set Form "C", Summary Alarm (all alarms listed above) w/ (2) sets Form "C" (Low DC Current can be de-selected). 16L (for LaMarche Charger model A12B only): Low DC Voltage 2 Alarm Light utilized for Low Voltage Load Disconnect w/ (1) set Form "C", High DC Voltage Alarm Light w/ (2) sets Form "C", High DC Voltage Shutdown Alarm Light w/ (1) set Form "C", Summary Alarm (all alarms listed above) w/ (2) sets Form "C" (Low DC Current can be deselected). 16P (for LaMarche Charger model A12B only): Low DC Voltage 2 Alarm Light w/ (2) sets Form "C", High DC Voltage Alarm Light w/ (2) sets Form "C", High DC Voltage Shutdown Alarm Light w/ (1) set Form "C", Summary Alarm (all alarms listed above) w/ (1) set Form "C" (Low DC Current can be de-selected), Audible Alarm w/ Silence Switch. 16Q (for LaMarche Charger model A12B only): Low DC Voltage 2 Alarm Light with (1) set of form "C" contacts utilized for Low Voltage Load Disconnect, High DC Voltage Alarm Light w/ (2) sets Form "C", High DC Voltage Shutdown Alarm Light w/ (1) set Form "C", Positive Ground Alarm Light w/ (1) set of Form "C", Negative Ground Alarm Light w/ (1) set Form "C", Summary Alarm (all alarms listed above) w/ (2) sets Form "C" (Low DC Current can be de-selected). 16T (for LaMarche Charger model A12B only): Low DC Voltage 2 Alarm Light only (no contacts), High DC Voltage Alarm Light w/ (2) sets Form "C", High DC Voltage Shutdown Alarm Light w/ (1) set Form "C", Positive Ground Alarm Light w/ (1) set of Form "C", Negative Ground Alarm Light w/ (1) set Form "C", Summary Alarm (all alarms listed above) w/ (1) set Form "C" (Low DC Current can be de-selected), Audible Alarm w/ Silence Switch. 16U (for LaMarche Charger model A12B only): Low DC Voltage 2 Alarm Light utilized for Low Voltage Battery Disconnect w/ (1) set Form "C", High DC Voltage Alarm Light w/ (2) sets Form "C", High DC Voltage Shutdown Alarm Light w/ (1) set Form "C", Positive Ground Alarm Light w/ (1) set of Form "C", Negative Ground Alarm Light w/ (1) set Form "C", Summary Alarm (all alarms listed above) w/ (2) sets Form "C" (Low DC Current can be de-selected). Specifications subject to change without notice LaMarche Manufacturing Company 106 Bradrock Drive, Des Plaines, IL 60018-1967 Tel: 847-299-1188 Toll Free Fax: 1-888-232-9562 sales@lamarchemfg.com www.lamarchemfg.com ISO 9001 CERTIFIED P25-DSDIGITAL_CAP_SYSTEMS-1 ECN 16210 10-03 106 Bradrock Drive, Des Plaines, IL 60018-1967 Tel: 847-299-1188 Toll Free Fax: 1-888-232-9562 sales@lamarchemfg.com www.lamarchemfg.com 45521 LaMarche P_25_C A P fix for web.qxd 12/4/2003 11:54 AM Page 1 DIGITAL C.A.P. SYSTEMS DIGITAL C.A.P. SYSTEMS (COMBINED ACCESSORY PACKAGE) (COMBINED ACCESSORY PACKAGE) Option Codes ISO 9001 CERTIFIED Standard Features Selectable Digital LED Display for DC Voltage, DC Amps (Current), Timer Mode and Equalize Time Remaining (hrs) • Multi-Mode Equalize Timer & Light; adjustable from 1-144 hrs with five selectable modes: Standard, 7-day, 14-day, 30-day and Equalize after Low DC Voltage • AC Pilot Light • AC Power Failure Alarm (except 16H) Adjustable Time Delay (0-255 sec) (De-Energizes during alarm condition) • Low DC Current Alarm Adjustable Time Delay (0-255 sec) (De-Energizes during alarm condition) • Low DC Voltage Alarm Adjustable Time Delay (0-255 sec) (De-Energizes during alarm condition) • Low DC Voltage 2 Alarm Adjustable Time Delay (0-255 sec) (De-Energizes during alarm condition) • High DC Voltage Alarm Adjustable Time Delay (0-255 sec) (Energizes during alarm condition) • High DC Voltage Shutdown Alarm Adjustable Time Delay (0-255 sec) (Energizes during alarm condition) THE ULTIMATE ACCESSORY FOR YOUR LAMARCHE BATTERY CHARGER The Digital C.A.P. (Combined Accessory Package) Systems feature a microprocessor-based design that incorporates the most popular alarms combined with a Multi-Mode Equalize Timer and a Digital LED Display in one convenient factory installed package. The Alarm relay contacts and LED indicators allow the user to report faulty conditions remotely and locally. Alarm conditions are reported via Form “C” contacts to alert the operator of a faulty condition of the DC Power System and take corrective actions. Individual Alarm LED indicators and the Digital Display are provided for local supervision. You are not limited to a one size fits all either - several Digital C.A.P. System configurations are offered to meet your specific needs. Whether Ground Detection, Low Voltage Battery Disconnect, Low Voltage Load Disconnect or an Audible Alarm is required, LaMarche offers a wide variety of solutions for every application. Completely user-friendly, the Digital C.A.P. System alarm settings can be adjusted and calibrated in the field without the need of special tools or equipment. Best of all, adjustments can be made when the battery is online without affecting the load thus reducing costly downtime. • Positive & Negative Ground Alarm (16J, 16Q, 16T & 16U only) (Energizes during alarm condition) • Summary Alarm Adjustable Time Delay (0-255 sec) (De-Energizes during alarm condition) All alarm contacts are rated for 0.5A @ 120VAC, 2A @ 30VDC and 0.25A @ 125VDC 16E 16G 16H 16J 16L 16P 16Q 16T 16U Features Available on Charger Models Digital Selectable LED Display for: DC Voltage, DC Current (Amps), Timer Mode, Equalize Time Remaining (hrs) Multi-Mode Digital Equalize Timer; adjustable from 1-144 hrs w/ five selectable modes: Standard, 7-day, 14-day, 30-day, Equalize after Low DC Voltage Equalize Light (Amber LED) AC Pilot Light (Green LED) AC Power Failure Relay w/ (2) sets Form "C" Low DC Current Alarm Light (Red LED) w/ (2) sets Form "C" Low DC Voltage Alarm Light (Red LED) w/ (2) sets Form "C" Low DC Voltage Alarm Light (Red LED) only - no contacts Low DC Voltage 2 Alarm Light (Red LED) w/ (2) sets Form "C" Low DC Voltage 2 Alarm Light (Red LED) w/ (1) set Form "C" – utilized for Low Voltage Battery Disconnect Low DC Voltage 2 Alarm Light (Red LED) w/ (1) set Form “C” – utilized for Low Voltage Load Disconnect Low DC Voltage 2 Alarm Light (Red LED) only - no contacts High DC Voltage Alarm Light (Red LED) w/ (2) sets Form "C" High DC Voltage Alarm Light (Red LED) only - no contacts High DC Voltage Shutdown Alarm Light (Red LED) w/ (1) set Form "C" Positive Ground Alarm Light (Green LED) w/ (1) set Form "C" Negative Ground Alarm Light (Green LED) w/ (1) set Form "C" Summary Alarm w/ (2) sets Form "C" includes: AC Power Failure (except 16H), Low DC Current (can be de-selected), Low DC Voltage, Low DC Voltage 2, High DC Voltage, High DC Voltage Shutdown (except 16H). Adds Positive & Negative Ground on 16J, 16Q, 16T & 16U. Summary Alarm w/ (1) set Form “C” includes: AC Power Failure, Low DC Current (can be de-selected), Low DC Voltage, Low DC Voltage 2, High DC Voltage, High DC Voltage Shutdown. Adds Positive & Negative Ground on 16T. Audible Alarm w/ Silence Switch A12B A12B A46 A12B PPC --- ----- --- --- ----- ----- --- --- --- ----- ----- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ----- ----- ------- --- --- --- --- --- --- ----- ----- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- DIGITAL C.A.P. DESCRIPTIONS Digital C.A.P. Systems common features EXCEPT 16H : Selectable LED Display, Multi-Mode Equalize Timer, Equalize Light, AC Pilot Light , AC Power Failure Relay w/ (2) sets Form "C", Low DC Current Alarm Light w/ (2) sets Form "C", & Low DC Voltage Alarm Light w/ (2) sets Form "C". 16E (for LaMarche Chargers models A12B & A46 only): Low DC Voltage 2 Alarm Light w/ (2) sets Form "C", High DC Voltage Alarm Light w/ (2) sets Form "C", High DC Voltage Shutdown Alarm Light w/ (1) set Form "C", Summary Alarm (all alarms listed above) w/ (2) sets Form "C" (Low DC Current can be de-selected). 16G (for LaMarche Charger model A12B only): Low DC Voltage 2 Alarm Light utilized for Low Voltage Battery Disconnect w/ (1) set Form "C", High DC Voltage Alarm Light With its uncomplicated interface, operating these Digital C.A.P. Systems is easy; Meter readings, Equalize and Calibration modes are accessed via the multi-functional Eq/Select switch. All alarm settings are stored in memory - the last becomes the new default setting even if an extended power failure occurs. The LED indicators are instantaneously alarmed and the alarm relays have an adjustable time delay of 0-255 seconds with the exception of the Ground Detection Alarms (16J, 16Q, 16T & 16U only) which have no time delay. The Multi-Mode Equalize Timer is field programmable and has Equalize settings that are adjustable from 1-144 hrs in five different modes; Standard, 7-day, 14-day, 30day and Equalize after Low DC Voltage, allowing you to select the right mode for your application. An Equalize LED is displayed on the front panel when the timer is in operation and an Equalize Time Remaining feature can be viewed through the selectable Digital Display. w/ (2) sets Form "C", High DC Voltage Shutdown Alarm Light w/ (1) set Form "C", Summary Alarm (all alarms listed above) w/ (2) sets Form "C" (Low DC Current can be deselected). 16H (for LaMarche Charger model PPC only): Low DC Voltage Alarm Light only (no contacts), Low DC Voltage 2 Alarm Light only (no contacts), High DC Voltage Alarm Light only (no contacts), Summary Alarm (all alarms listed above) w/ (2) sets Form "C" (Low DC Current can be de-selected). 16J (for LaMarche Charger model A12B only): Low DC Voltage 2 Alarm Light only (no contacts), High DC Voltage Alarm Light w/ (2) sets Form "C", High DC Voltage Shutdown Alarm Light w/ (1) set Form "C", Positive Ground Alarm Light w/ (1) set of Form "C", Negative Ground Alarm Light w/ (1) set Form "C", Summary Alarm (all alarms listed above) w/ (2) sets Form "C" (Low DC Current can be de-selected). 16L (for LaMarche Charger model A12B only): Low DC Voltage 2 Alarm Light utilized for Low Voltage Load Disconnect w/ (1) set Form "C", High DC Voltage Alarm Light w/ (2) sets Form "C", High DC Voltage Shutdown Alarm Light w/ (1) set Form "C", Summary Alarm (all alarms listed above) w/ (2) sets Form "C" (Low DC Current can be deselected). 16P (for LaMarche Charger model A12B only): Low DC Voltage 2 Alarm Light w/ (2) sets Form "C", High DC Voltage Alarm Light w/ (2) sets Form "C", High DC Voltage Shutdown Alarm Light w/ (1) set Form "C", Summary Alarm (all alarms listed above) w/ (1) set Form "C" (Low DC Current can be de-selected), Audible Alarm w/ Silence Switch. 16Q (for LaMarche Charger model A12B only): Low DC Voltage 2 Alarm Light with (1) set of form "C" contacts utilized for Low Voltage Load Disconnect, High DC Voltage Alarm Light w/ (2) sets Form "C", High DC Voltage Shutdown Alarm Light w/ (1) set Form "C", Positive Ground Alarm Light w/ (1) set of Form "C", Negative Ground Alarm Light w/ (1) set Form "C", Summary Alarm (all alarms listed above) w/ (2) sets Form "C" (Low DC Current can be de-selected). 16T (for LaMarche Charger model A12B only): Low DC Voltage 2 Alarm Light only (no contacts), High DC Voltage Alarm Light w/ (2) sets Form "C", High DC Voltage Shutdown Alarm Light w/ (1) set Form "C", Positive Ground Alarm Light w/ (1) set of Form "C", Negative Ground Alarm Light w/ (1) set Form "C", Summary Alarm (all alarms listed above) w/ (1) set Form "C" (Low DC Current can be de-selected), Audible Alarm w/ Silence Switch. 16U (for LaMarche Charger model A12B only): Low DC Voltage 2 Alarm Light utilized for Low Voltage Battery Disconnect w/ (1) set Form "C", High DC Voltage Alarm Light w/ (2) sets Form "C", High DC Voltage Shutdown Alarm Light w/ (1) set Form "C", Positive Ground Alarm Light w/ (1) set of Form "C", Negative Ground Alarm Light w/ (1) set Form "C", Summary Alarm (all alarms listed above) w/ (2) sets Form "C" (Low DC Current can be de-selected). Specifications subject to change without notice LaMarche Manufacturing Company 106 Bradrock Drive, Des Plaines, IL 60018-1967 Tel: 847-299-1188 Toll Free Fax: 1-888-232-9562 sales@lamarchemfg.com www.lamarchemfg.com ISO 9001 CERTIFIED P25-DSDIGITAL_CAP_SYSTEMS-1 ECN 16210 10-03 106 Bradrock Drive, Des Plaines, IL 60018-1967 Tel: 847-299-1188 Toll Free Fax: 1-888-232-9562 sales@lamarchemfg.com www.lamarchemfg.com