ISSUE TO BID
Richards Medical Research Laboratory - Additional Scope, Towers C&D
08.05.2016
3700 Hamilton Walk, Philadelphia, PA 19104
PROJECT TEAM
CLIENT
ARCHITECT
MEPFP ENGINEER
University of Pennsylvania
3451 Walnut Street
Philadelphia, PA 19104
Tel: 215.898.5000
Atkin Olshin Schade Architects
125 S. 9th Street, Suite 900
Philadelphia, PA 19107
215.925.7812
Bruce E. Brooks & Associates
2209 Chestnut Street,
Philadelphia, PA 19103
215.569.0400
SHEET INDEX
CS
Cover Sheet
ARCHITECTURAL
A001 General Notes & Typical Mounting Heights
A100 Basement Floor Plan
A101 First Floor Plan
A102 Second Floor Plan
A103 Third Floor Plan
A104 Fourth Floor Plan
A105 Fifth Floor Plan
A106 Sixth Floor Plan
A107 Seventh Floor Plan
A116 Goddard - Sixth Floor Plan
A600 C Tower Basement Shower Rooms
A601 C Tower Stair Cleaning
A602 C Tower Lounges
A603 C & D Towers Miscellaneous Millwork
A604 Goddard Knee Panels & Glazing Film
A700 Millwork Details
A900 C Tower Entry Doors
A901 Entry Door Details
A902 Loading Dock Door Details
A903 Door Schedule & Details
A910 Finish Schedule & Key
HVAC
H000
H100
H200
H201
H300
H301
H800
HVACCover Sheet
HVAC Key Plans
HVAC Levels B, 1, & 2 Demolition Plans
HVAC levcels 3, 4, 6, 7, & 8 Demolition Plans
HVAC Levels B, 1, & 2 New Work Plans
HVAC Levels 3, 4, 7, & 8 New Work Plans
Mechanical Schedules & Details
PLUMBING/FIRE PROTECTION
PF000 Plumbing/FP Cover Sheet
PF300 Plumbing/FP Basement Demolition & New Work Plans
PF800 Plumbing/FP Schedules & Details
ELECTRICAL
E000 Electrical Cover Sheet
E400 Electrical Basement Plans
E401 Electrical Level 1 New Work Plan - Power
E402 Electrical Level 7, 8 New Work Plan - Power
E700 Electrical Schedules
RICHARDS
GODDARD
C
D
EAST
WEST
B
A
ABBREVIATIONS
N
PROJECT SITE
ABV
ADJ
AFF
ALUM
ANOD
AP
ARCH
above
adjacent
above finished floor
aluminum
anodized
access panel
architect(ural)
BD
BITUM
BLDG
BM
BOT
BSMT
BTW
board
bituminous
building
beam
bottom
basement
between
CAB
CEM
CIPC
CLG
CLR
CMU
COL
CONC
CONST
CONT
CORR
CPT
CT
CTR
cabinet
cement
cast-in-place concrete
ceiling
clear(ance)
concrete masonry unit
column
concrete
construction
continuous
corridor
carpet
ceramic tile
counter
DIAM
DIFF
DIM
DN
DR
DS
DTL
DWG
diameter
diffuser
dimension
down
door
downspout
detail
drawing
EL
ELEC
ELEV
EMER
EQ
EQUIP
EXG
EXIST
EXP
EXPN
EXT
elevation
electric(al)
elevator
emergency
equal
equipment
existing
existing
exposed
expansion
exterior
FD
FE
FEC
FF
FIN
FLR
FLUR
FND
FOC
FOM
FTG
FUR
floor drain
fire extinguisher
fire extinguisher cabinet
finished floor
finish(ed)
floor(ing)
fluorescent
foundation
face of concrete
face of masonry
footing
furred, furring
GA
GALV
GL
GLBLK
GT
GPSHTH
GWB
gauge
galvanized
glass, glazing
glass block
grout
gypsum sheathing
gypsum wall board
MULL
mullion
NAT
NIC
NOM
NRC
NTS
natural
not in contract
nominal
noise reduction coefficient
not to scale
HC
HDR
HDW
HM
HT
HVAC
hollow core
header
hardware
hollow metal
height
heating/ventilating/
air conditioning
OC
OPG
OPP
on center(s)
opening
opposite
INS
INT
insulated
interior
PLAM
PNT
PTD
PTN
PVC
PWD
plastic laminate
paint(ed)
painted
partition
polyvinyl chloride
plywood
JAN/JC
JT
janitor (closet)
joint
LAM
LH
LT
laminated
left hand
light
MAS
MAX
MATL
MECH
MEM
MIN
MISC
MLDG
MTL
MO
masonry
maximum
material(s)
mechanic(al)
membrane
minimum
miscellaneous
moulding
metal
masonry opening
R'S
RA
RAD
RD
REC
REF
REQ
REV
RM
RO
RTN
RWC
risers
return air
radius
roof drain
recommendation
reference
required
revision(s), revised
room
rough opening
return air
rainwater conductcor
SAB
SCHED
SD
SECT
SF
SHT
SIM
SPEC
SPKLS
SQ FT
SST
STL
SOG
STD
STN
STR
SURF
SYS
sound absorbing batts
schedule
storm drain
section
square feet
sheet
similar
specifications
sprinklers
square foot
stainless steel
steel
slab on grade
standard
stone
structural
surface
system
T'S
TEL
T&G
THK
TOS
TOSTL
TYP
treads
telephone
tongue and groove
thick(ness)
top of slab
top of steel
typical
UNO, UON
unless noted otherwise
VERT
VIF
vertical
verify in field
WD
WGL
WPT
WPM
wood
wire glass
working point
waterproofing membrane
REVISIONS
ISSUE DATE
SANITARY NAP DISPOSAL,
BELOW GRAB BAR, WITHIN
REACH FROM TOILET
TP DISPENS.
60" MIN
3'-0" MIN
16" - 27"
MIRROR
1'-6"
33" - 36"
48" MAX
38" MIN
17"-19"
2'-5" MIN
WALL OR
OBSTRUCTION
33" - 36"
LAVATORY
40" MAX
33" - 36"
MIRROR
34" MAX
18"
MAX
24" 12"
MIN MIN
39" - 41"
33" - 39"
15"
MIN
SPOUT OUTLET
3'-0"
2'-10"
42" MIN
3'-3"
3'-5" SPOUT OUTLET
60"
3'-10" A.F.F.
12"
MAX
18"
CLR
1
36" MIN
ACCESSIBLE SHOWER
REVERSIBLE FOLDING SHOWER SEAT
27" MIN
54" MIN
3"
MAX 44"-48" TO OPERABLE PARTS
39" - 41"
LAVATORY AND MIRROR
CLEAR FLOOR
SPACE
30" CLR
7"-9"
6'-6"
3'-0"
RESTROOM ACCESSORIES
6'-0"
ACCESIBLE TOILETS
15"-48"
DRINKING FOUNTAINS
DI
SP
PA
EN
DI PE
S.
SP R
EN TO
S. WE
L
SA
DI NI
SP TA
EN RY
S NA
TO .
PK
CO ILE
IN
VE T S
R EA
DI T
SP
OD ENS
C O
.
DI ONT R
SP R
EN OL
S.
FIRE EXTINGUISHER
SO
AP
DOOR SIGNAGE
DESCRIPTION
ALLOWED
LAVATORY
ANSI STANDARD MOUNTING HEIGHTS
A001
SCALE: 1/4" = 1'-0"
GENERAL NOTES
1. EXISTING CONDITIONS SHOWN ARE PER AS BUILT DRAWINGS PROVIDED BY OWNER. THE CONTRACTOR SHALL VERIFY ALL
EXISTING CONDITIONS PRIOR TO BEGINNING WORK. ANY DISCREPANCY BETWEEN CONSTRUCTION DOCUMENTS AND ACTUAL
CONDITIONS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO COORDINATE AND RESOLVE.
2. DO NOT SCALE THE DRAWINGS. DIMENSIONAL DISCREPANCIES AND QUESTIONS SHALL BE DIRECTED TO THE CONTRACTOR.
3.
THE CONTRACTOR SHALL INSTALL ALL EQUIPMENT IDENTIFIED AS OFCI ACCORDING TO MANUFACTURERS' INSTRUCTIONS.
4. THE CONTRACTOR SHALL FULLY COORDINATE ALL ARCHITECTURAL, MECHANICAL, PLUMBING, ELECTRICAL AND STRUCTURAL
WORK. THE CONTRACTOR SHALL NOTIFY OWNER AND ARCHITECT OF ANY DISCREPANCIES.
5. THE CONTRACTOR SHALL LOCATE ALL EXISTING UTILITIES AND SERVICES PRIOR TO START OF WORK.
6. THE CONTRACTOR SHALL PROTECT FROM DAMAGE ALL ADJACENT AREAS AND PROPERTIES, SUCH AS LANDSCAPING AND
EXTERIOR OR INTERIOR BUILDING SURFACES. LOSS OR DAMAGE SHALL BE REPLACED/REPAIRED AT THE CONTRACTOR’S EXPENSE.
MEPFP ENGINEER
BRUCE E. BROOKS & ASSOC.
2209 Chestnut Street
Philadelphia, PA 19103
215.569.0400
7. ALL EXISTING WORK AFFECTED BY THESE CONTRACT DOCUMENTS SHALL BE RESTORED TO MATCH EXISTING CONDITIONS.
8. ALL DIMENSIONS SHOWN ARE FROM FACE OF FINISH UNLESS OTHERWISE NOTED. CONTRACTOR SHALL VERIFY IN THE FIELD ALL
DIMENSIONS. DIMENSIONS NOTED "CLEAR" ARE NOT TO BE ADJUSTED WITHOUT APPROVAL OF ARCHITECT.
9. THESE DRAWINGS ARE PREPARED AND COORDINATED WITH THE PROJECT MANUAL WHICH INCLUDES TECHNICAL
SPECIFICATIONS. TOGETHER THESE FORM THE CONSTRUCTION DOCUMENTS.
10. ITEMS OF SALVAGEABLE VALUE SHALL REMAIN THE PROPERTY OF THE OWNER.
11. THE CONTRACTOR SHALL CHALK LINE ALL PARTITIONS FOR REVIEW AND APPROVAL BY OWNER PRIOR TO COMMENCEMENT OF
MASONRY AND STUD INTERIOR PARTITIONS. ANY EXISTING FIELD CONDITIONS SHALL IMMEDIATELY BE COORDINATED W/ THE CONTR.
C:\Users\pjune\Desktop\revit models\135300
Richards\add'l scope\135302 Richards Add'l
8/5/2016 4:15:50 PM
Scope_Central_PJ.rvt
CITY OF PHILADELPHIA BUSINESS
PRIVILIEGE LICENSE #63180
3700 Hamilton Walk, Philadelphia, PA 19104
Richards Medical Research
Laboratory - Additional Scope,
Towers C&D
University of Pennsylvania
Perelman School of Medicine
125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107
ATKIN OLSHIN SCHADE ARCHITECTS
12. CONTRACTOR TO VERIFY LEVEL OF ALL SUB-FLOORS PRIOR TO INSTALLATION OF FINISH FLOOR MATERIALS.
General Notes & Typical
Mounting Heights
DATE
08.05.2016
SCALE
1/4" = 1'-0"
DRAWN BY
PQJ
A001
C:\Users\pjune\Desktop\revit models\135300
Richards\add'l scope\135302 Richards Add'l
8/5/2016 4:15:52 PM
Scope_Central_PJ.rvt
A6
01
D-6
CLEAN STAIR
3
4
2
ST-C0
C003
D-7
1
A600
ACCESSIBLE GENDER
NEUTRAL RESTROOM
C003B
C003B
1
STAIR C
VESTIBULE
C003
EXG PARTITION
NEW PARTITION
C003A
WOOD PARTITION
GENDER NEUTRAL
RESTROOM
C003A
RICHARDS
C
RICHARDS
D
N
RICHARDS
A
GODDARD
EAST
SCALE
1/4" = 1'-0"
DRAWN BY
PQJ
CITY OF PHILADELPHIA BUSINESS
PRIVILIEGE LICENSE #63180
D-5
Basement Floor Plan
GODDARD
WEST
RICHARDS
B
DATE
08.05.2016
A100
3700 Hamilton Walk, Philadelphia, PA 19104
D-8
MEPFP ENGINEER
BRUCE E. BROOKS & ASSOC.
2209 Chestnut Street
Philadelphia, PA 19103
215.569.0400
ISSUE DATE
Richards Medical Research
Laboratory - Additional Scope,
Towers C&D
University of Pennsylvania
Perelman School of Medicine
125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107
D-3
ATKIN OLSHIN SCHADE ARCHITECTS
DN
REF.
REVISIONS
DESCRIPTION
UP
D-2
D006
D-4
D-1
REVISIONS
ISSUE DATE
DESCRIPTION
DN
UP
SHARED KITCHENETTE
C109
D-3
DN
D-2
1
03
A6
48 1/2"
1
A700
EXTENDED SOLID
SURFACE COUNTERTOP
WITH (1) GROMMET
C109
20"
18"
VIF
INFILL TRANSFER GRILL
OPENING W/ LIKE (GWB)
CONSTRUCTION.
PNT TO MATCH.
REMOVE TEMP PLYWOOD
THRESHOLD. INSTALL NEW
ALUM ADA THRESHOLD W/
WEATHERSEAL
D-4
C110
C114
D-1
DN
2
A902
BACK-PAINTED GLASS
MARKERBOARD WALL
LOUNGE
C114
1
FE
D-8
D-5
CLEAN STAIR
2
STAIR C
1
ST-C1
A6
01
3
4
BOLLARD
CX04
CX03
1
A900
CITY OF PHILADELPHIA BUSINESS
PRIVILIEGE LICENSE #63180
First Floor Plan
VESTIBULE
C:\Users\pjune\Desktop\revit models\135300
Richards\add'l scope\135302 Richards Add'l
8/5/2016 4:15:54 PM
Scope_Central_PJ.rvt
University of Pennsylvania
Perelman School of Medicine
D-7
125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107
D-6
ATKIN OLSHIN SCHADE ARCHITECTS
LOUNGE
IMPROVEMENTS
RICHARDS
C
C110
RICHARDS
D
GODDARD
EAST
GODDARD
WEST
RICHARDS
B
DATE
N
RICHARDS
A
CX01
CX02
BOLLARD
08.05.2016
SCALE
1/4" = 1'-0"
DRAWN BY
Author
A101
3700 Hamilton Walk, Philadelphia, PA 19104
CX03
Richards Medical Research
Laboratory - Additional Scope,
Towers C&D
REPAIR GWB, PNT AT ENLARGED
TRANSFER DUCT
MEPFP ENGINEER
BRUCE E. BROOKS & ASSOC.
2209 Chestnut Street
Philadelphia, PA 19103
215.569.0400
02
A6
C:\Users\pjune\Desktop\revit models\135300
Richards\add'l scope\135302 Richards Add'l
8/5/2016 4:15:56 PM
Scope_Central_PJ.rvt
A6
01
02
A6
LOUNGE
IMPROVEMENTS
D-6
3
4
2
D-7
CLEAN STAIR
EXG PARTITION
NEW PARTITION
1
WOOD PARTITION
STAIR C
ST-C2
RICHARDS
C
N
RICHARDS
D
RICHARDS
A
GODDARD
EAST
CITY OF PHILADELPHIA BUSINESS
PRIVILIEGE LICENSE #63180
2
C214
REPAIR GWB, PNT AT ENLARGED
TRANSFER DUCT
D-8
D-5
Second Floor Plan
GODDARD
WEST
RICHARDS
B
DATE
08.05.2016
SCALE
1/4" = 1'-0"
DRAWN BY
PQJ
A102
3700 Hamilton Walk, Philadelphia, PA 19104
WHITEBOARD PANEL / CONT
CHANNEL FRAME
MEPFP ENGINEER
BRUCE E. BROOKS & ASSOC.
2209 Chestnut Street
Philadelphia, PA 19103
215.569.0400
ISSUE DATE
Richards Medical Research
Laboratory - Additional Scope,
Towers C&D
1
A700
University of Pennsylvania
Perelman School of Medicine
D-3
125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107
UP
ATKIN OLSHIN SCHADE ARCHITECTS
24"
REVISIONS
DESCRIPTION
DN
D-2
EXTENDED SOLID
SURFACE
COUNTERTOP W/
(2) GROMMETS
55"
SIM 2
03
A6
REF.
D-4
D-1
FE
LOUNGE
C:\Users\pjune\Desktop\revit models\135300
Richards\add'l scope\135302 Richards Add'l
8/5/2016 4:15:57 PM
Scope_Central_PJ.rvt
A6
01
02
A6
D-5
LOUNGE
IMPROVEMENTS
D-6
3
4
2
D-7
CLEAN STAIR
EXG PARTITION
NEW PARTITION
1
WOOD PARTITION
STAIR C
ST-C3
RICHARDS
C
RICHARDS
D
N
RICHARDS
A
GODDARD
EAST
CITY OF PHILADELPHIA BUSINESS
PRIVILIEGE LICENSE #63180
2
C314
REPAIR GWB, PNT AT ENLARGED
TRANSFER DUCT
D-8
Third Floor Plan
GODDARD
WEST
RICHARDS
B
DATE
08.05.2016
SCALE
1/4" = 1'-0"
DRAWN BY
PQJ
A103
3700 Hamilton Walk, Philadelphia, PA 19104
WHITEBOARD PANEL / CONT
CHANNEL FRAME
MEPFP ENGINEER
BRUCE E. BROOKS & ASSOC.
2209 Chestnut Street
Philadelphia, PA 19103
215.569.0400
ISSUE DATE
Richards Medical Research
Laboratory - Additional Scope,
Towers C&D
C316
University of Pennsylvania
Perelman School of Medicine
D-3
125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107
UP
ATKIN OLSHIN SCHADE ARCHITECTS
REVISIONS
DESCRIPTION
DN
D-2
C310C
C310D
C310A
C310B
REPLACE HDW
FUNCTION
(TYP OF 4)
REPLACE HDW
FUNCTION
REF.
D-4
D-1
FE
LOUNGE
C:\Users\pjune\Desktop\revit models\135300
Richards\add'l scope\135302 Richards Add'l
8/5/2016 4:15:58 PM
Scope_Central_PJ.rvt
A6
01
C425
C416
WHITEBOARD PANEL / CONT
CHANNEL FRAME
3
4
2
2
02
A6
LOUNGE
IMPROVEMENTS
D-6
D-7
CLEAN STAIR
EXG PARTITION
NEW PARTITION
1
WOOD PARTITION
STAIR C
ST-C4
RICHARDS
C
RICHARDS
D
N
RICHARDS
A
GODDARD
EAST
CITY OF PHILADELPHIA BUSINESS
PRIVILIEGE LICENSE #63180
C424
C414
REPAIR GWB, PNT AT ENLARGED
TRANSFER DUCT
D-8
D-5
Fourth Floor Plan
GODDARD
WEST
RICHARDS
B
DATE
08.05.2016
SCALE
1/4" = 1'-0"
DRAWN BY
PQJ
A104
3700 Hamilton Walk, Philadelphia, PA 19104
C425
MEPFP ENGINEER
BRUCE E. BROOKS & ASSOC.
2209 Chestnut Street
Philadelphia, PA 19103
215.569.0400
ISSUE DATE
Richards Medical Research
Laboratory - Additional Scope,
Towers C&D
TESTING ROOM
University of Pennsylvania
Perelman School of Medicine
C426
TESTING ROOM
D-3
125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107
TESTING ROOM
ATKIN OLSHIN SCHADE ARCHITECTS
REF.
REVISIONS
DESCRIPTION
DN
C422
D-2
C422
C421
C420
C424
C423
REPLACE HDW FUNCTION
(TYP OF 8)
D-4
D-1
FE
Lounge
C:\Users\pjune\Desktop\revit models\135300
Richards\add'l scope\135302 Richards Add'l
8/5/2016 4:16:04 PM
Scope_Central_PJ.rvt
A6
01
3
4
2
D-5
LOUNGE
IMPROVEMENTS
D-6
D-7
CLEAN STAIR
1
STAIR C
ST-C5
RICHARDS
C
RICHARDS
D
N
RICHARDS
A
GODDARD
EAST
CITY OF PHILADELPHIA BUSINESS
PRIVILIEGE LICENSE #63180
C514
D-8
Fifth Floor Plan
GODDARD
WEST
RICHARDS
B
DATE
08.05.2016
SCALE
1/4" = 1'-0"
DRAWN BY
PJ
A105
3700 Hamilton Walk, Philadelphia, PA 19104
02
A6
MEPFP ENGINEER
BRUCE E. BROOKS & ASSOC.
2209 Chestnut Street
Philadelphia, PA 19103
215.569.0400
ISSUE DATE
Richards Medical Research
Laboratory - Additional Scope,
Towers C&D
2
University of Pennsylvania
Perelman School of Medicine
C510A
125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107
D-3
ATKIN OLSHIN SCHADE ARCHITECTS
REF.
REVISIONS
DESCRIPTION
D-2
C509A
C510AA
C509AA
REPLACE HDW
FUNCTION (TYP
OF 5)
C508AA
D-4
D-1
WHITEBOARD PANEL / CONT
CHANNEL FRAME
Lounge
C:\Users\pjune\Desktop\revit models\135300
Richards\add'l scope\135302 Richards Add'l
8/5/2016 4:16:08 PM
Scope_Central_PJ.rvt
A6
01
3
4
2
UP
LOUNGE
IMPROVEMENTS
-
INSTALL 3'-0" WIDE
WHITE BOARD.
PROVIDED BY
OWNER.
D-6
D-7
CLEAN STAIR
1
STAIR C
ST-C6
RICHARDS
C
RICHARDS
D
N
RICHARDS
A
GODDARD
EAST
CITY OF PHILADELPHIA BUSINESS
PRIVILIEGE LICENSE #63180
D-8
D-5
Sixth Floor Plan
GODDARD
WEST
RICHARDS
B
DATE
08.05.2016
SCALE
1/4" = 1'-0"
DRAWN BY
PJ
A106
3700 Hamilton Walk, Philadelphia, PA 19104
C614
MEPFP ENGINEER
BRUCE E. BROOKS & ASSOC.
2209 Chestnut Street
Philadelphia, PA 19103
215.569.0400
ISSUE DATE
Richards Medical Research
Laboratory - Additional Scope,
Towers C&D
02
A6
University of Pennsylvania
Perelman School of Medicine
2
125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107
D-3
ATKIN OLSHIN SCHADE ARCHITECTS
-
C609A
REF.
REVISIONS
DESCRIPTION
D-2
REPLACE HDW
FUNCTION
D-4
D-1
WHITEBOARD PANEL / CONT
CHANNEL FRAME
LOUNGE
C:\Users\pjune\Desktop\revit models\135300
Richards\add'l scope\135302 Richards Add'l
8/5/2016 4:16:11 PM
Scope_Central_PJ.rvt
A6
01
3
4
2
COMPUTER ROOM
D-6
3
D708
03
A6
LOUNGE
IMPROVEMENTS
UP
D-7
CLEAN STAIR
DN
EXG PARTITION
NEW PARTITION
1
WOOD PARTITION
ST-C7
RICHARDS
C
RICHARDS
D
N
RICHARDS
A
GODDARD
EAST
CITY OF PHILADELPHIA BUSINESS
PRIVILIEGE LICENSE #63180
1'-0"
2
A700
REPAIR GWB, PNT AT ENLARGED
TRANSFER DUCT
D-8
D-5
STAIR C
Seventh Floor Plan
GODDARD
WEST
RICHARDS
B
DATE
08.05.2016
SCALE
1/4" = 1'-0"
DRAWN BY
PQJ
A107
3700 Hamilton Walk, Philadelphia, PA 19104
C714
MEPFP ENGINEER
BRUCE E. BROOKS & ASSOC.
2209 Chestnut Street
Philadelphia, PA 19103
215.569.0400
ISSUE DATE
Richards Medical Research
Laboratory - Additional Scope,
Towers C&D
LOUNGE
University of Pennsylvania
Perelman School of Medicine
02
A6
125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107
2
ATKIN OLSHIN SCHADE ARCHITECTS
D-3
6'-9"
REVISIONS
DESCRIPTION
D-2
REF.
D-4
D-1
20" & 18" HEAVY DUTY ADJ
SHELVES
WHITEBOARD PANEL / CONT
CHANNEL FRAME
12'-2"
C:\Users\pjune\Desktop\revit models\135300
Richards\add'l scope\135302 Richards Add'l
8/5/2016 4:16:12 PM
Scope_Central_PJ.rvt
REMOVE FILTER
(TYP OF 32)
SEE M201
FOR MECH
WORK IN
THIS ROOM
RICHARDS
C
RICHARDS
D
N
RICHARDS
A
GODDARD
EAST
GODDARD
WEST
Goddard - Sixth Floor
Plan
RICHARDS
B
DATE
08.05.2016
SCALE
1/4" = 1'-0"
DRAWN BY
PQJ
A116
3700 Hamilton Walk, Philadelphia, PA 19104
CITY OF PHILADELPHIA BUSINESS
PRIVILIEGE LICENSE #63180
MEPFP ENGINEER
BRUCE E. BROOKS & ASSOC.
2209 Chestnut Street
Philadelphia, PA 19103
215.569.0400
ISSUE DATE
Richards Medical Research
Laboratory - Additional Scope,
Towers C&D
1
A604
University of Pennsylvania
Perelman School of Medicine
2
125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107
3
ATKIN OLSHIN SCHADE ARCHITECTS
REF.
A6
04
REVISIONS
DESCRIPTION
GLAZING FILM AT
CLERESTORY
WINDOWS
(TYP FOR 6)
TYP
ALTERNATE 3
INSULATED KNEE
PANEL (TYP FOR
32)
TYP OF 8
REVISIONS
TOILET ACCESSORY LEGEND
ISSUE DATE
EXG UTILITY SPACE
TRANSLUCENT
GLAZING FILM -TYPE 2
EXG UTILITY SPACE
EXG UTILITY SPACE
WALL-MNTD
VANITY LIGHT
PNTD GWB ON 1 5/8"
MTL STUD
ODOR CONTROL
DISPENSER
LIQUID SOAP DISPENSER
4
TA-1
GRAB BAR
TA-1
5
FOLDING SHOWER SEAT
TA-1
6
FEMININE NAPKIN DISPOSAL
TA-1
7
SEAT COVER DISPENSER
8
TA-1
MIRROR
TA-9
ODOR CONTROL DISPENSER
EQ
TA-12 SHOWER BASKET
EQ
1.
2.
3.
CT-1
REFER TO SHEET A003 FOR MOUNTING HEIGHT INFORMATION
PROVIDE (1) TOILET TISSUE DISPENSER PER (1) WC
PROVIDE (1) FEMININE NAPKIN DISPOSAL PER (1) WOMEN'S WC
FINISH KEY
3'-4"
2'-10"
3
TA-1
CT-1 CERAMIC TILE #1
CT-2 CERAMIC TILE #2
SHOWER STALL
INSERT
CT-2
CT-2
CT-2
CT-2
4"
8"
PAPER TOWEL DISPENSER
CT-1
WALL-MNTD
LAVATORY
3"
TA-1
2
DESCRIPTION
TA-11 SHOWER CURTAIN & HOOKS
PARABOLIC
ALUMINUM BAFFLE
WITH TRANSLUCENT
LENS
WALL-MNTD
FRAMELESS
MIRROR
TOILET TISSUE DISPENSER
TA-10 SHOWER CURTAIN ROD
CT-1
SHOWER CURTAIN ROD
3'-4"
CT-1
6"
PTD GWB
TA-1
FLR-MNTD WATER
CLOSET
7
6
C003A - EAST
A600
SCALE: 1/2" = 1'-0"
5
C003A - SOUTH
A600
SCALE: 1/2" = 1'-0"
C003A - WEST
A600
4
SCALE: 1/2" = 1'-0"
C003A - NORTH
A600
SCALE: 1/2" = 1'-0"
REMOVE EXG CONC
FLOOR IN SHOWER.
USE THICKSET BED
FOR FLUSH TILE FLOOR.
SLOPE FLOOR TO DRAIN.
TA-12
WINDOW
OPENING
ABV
EQ
N2
TA-4
ROLL-IN SHOWER
INSERT
5' - 3"
2' - 10"
EQ
EQ
EQ
1'-0"
ACCESSIBLE
LAVATORY
WINDOW
OPENING
ABOVE
CLEAR
TA-3
FD
TA-8
TA-1
CT-1
7"
ACCESSIBLE
FLR-MNTD
WATER CLOSET
FOLD-DOWN
SHOWER SEAT
F1
TA-9
7/8" HAT CHANNEL
W/ (1) LAYER 5/8"
OF GWB
TA-4
C003B
4"
EXISTING CMU WALL
REMOVE CT FLOOR
FINISHES
7' - 6"
MIN
CT-2
CT-2
C003B - NORTH
A600
F1
SCALE: 1/2" = 1'-0"
MIN
EQ
8
SCALE: 1/2" = 1'-0"
3-5/8" STUD
WALLS W/
(1) LAYER 5/8"
OF GWB
EACH SIDE
W/2" SOUND
ABSORBING
BATTS
VESTIBULE
5'-0"
A600
EQ
9
C003B - WEST
C003
C003
7' - 10"
REMOVE DOOR & FRAME
1'-2"
1'-0"
C003A
F1
TA-9
WALL-MNTD
VANITY LIGHT
7"
7' - 10"
7' - 6"
MIN
EQ
8"
00
A6
EQ
EQ
6' - 8"
MIN
7"
FD
3'-0"
EQ
TA-6
TA-7
1'-1"
TA-4
5
N2
FLR-MNTD
WATER CLOSET
LOCATE WALL TO
CLEAR EXG PIPE
FOLD-DOWN
SHOWER SEAT
3'-6"
2'-10"
3'-4"
F1
EQ
4
3'-0"
EQ
TA-1
6
REMOVE CT WALL
FINISHES
EQ
3'-4"
6' - 8"
MIN
TA-4
C:\Users\pjune\Desktop\revit models\135300
Richards\add'l scope\135302 Richards Add'l
8/5/2016 4:27:14 PM
Scope_Central_PJ.rvt
7
TA-2
TA-11
GRAB BARS
WINDOW
OPENING
ABOVE
1'-3"
C003A
1'-10"
SHOWER
STALL
INSERT
SEE A001
WALL-MNTD
LAVATORY
LAVATORY
TA-10
SHOWER STALL
INSERT
3"
TA-8
TA-3
GENDER NEUTRAL
RESTROOM
CT-1
WALL TILE
CT-1
WINDOW
OPENING
ABV
EQ
1' - 3"
1'-3"
TA-12
VIF
EXG UTILITY SPACE
EXG UTILITY SPACE
CITY OF PHILADELPHIA BUSINESS
PRIVILIEGE LICENSE #63180
EQ
University of Pennsylvania
Perelman School of Medicine
EQ
TILE DIRECTLY
ON CIPC WALLS
125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107
6'-8"
ODOR CONTROL
DISPENSER
MIN
5' - 0"
TA-6
CT-1
10
11 9
8 0
0
A6
TA-7
ATKIN OLSHIN SCHADE ARCHITECTS
SHOWER
CURTAIN ROD
C Tower Basement
Shower Rooms
SHOWER INSERT
FLR-MNTD
WATER CLOSET
CT-2
CT-2 TILE BASE
DATE
08.05.2016
11
C003B - EAST
A600
SCALE: 1/2" = 1'-0"
10
C003B - SOUTH
A600
SCALE: 1/2" = 1'-0"
3
SHOWER ROOM - RCP
A600
SCALE: 1/2" = 1'-0"
2
SHOWER ROOM - NEW WORK
A600
SCALE: 1/2" = 1'-0"
1
SHOWER ROOM - DEMOLITION
A600
SCALE: 1/2" = 1'-0"
SCALE
1/2" = 1'-0"
DRAWN BY
PQJ
A600
3700 Hamilton Walk, Philadelphia, PA 19104
7' - 10"
TA-2
MEPFP ENGINEER
BRUCE E. BROOKS & ASSOC.
2209 Chestnut Street
Philadelphia, PA 19103
215.569.0400
F1
TA-5
10'-5"
EQ
TRANSLUCENT
GLAZING FILM
- TYPE 2
PARABOLIC
ALUMINUM BAFFLE
WITH 1/8" THK
TRANSLUCENT LENS
C003B
Richards Medical Research
Laboratory - Additional Scope,
Towers C&D
EQ
TA-10
1'-3"
ACCESSIBLE GENDER
NEUTRAL RESTROOM
TA-11
2' - 2 3/4"
EXG UTILITY SPACE
REVISIONS
GENERAL STAIR NOTES
- CLEAN ALL CIPC SURFACE
ISSUE DATE
DESCRIPTION
- ALL NEW STAIR SIGNAGE; REMOVE EXG
PAINTED SIGNS
CLEAN ALL CIPC
CEILING SURFACES
TYP
7th Floor
84' - 0"
7th Floor
84' - 0"
CLEAN ALL CIPC
WALL SURFACES
TYP
6th Floor
72' - 0"
6th Floor
72' - 0"
NEW 8"x6" FLOOR
IDENTIFICATION
SIGN, TYP.
BY OWNER TYP.
CLEAN BRASS
HANDRAIL END CAPS
5th Floor
60' - 0"
5th Floor
60' - 0"
4th Floor
48' - 0"
REMOVE PNTD &
ADHESIVE SIGNS,
TYP
2nd Floor
24' - 0"
2nd Floor
24' - 0"
REMOVE SIGN
REMOVE PNTD
SIGN, TYP
1st Floor
12' - 0"
1st Floor
12' - 0"
REMOVE PNTD
SIGN, TYP
C:\Users\pjune\Desktop\revit models\135300
Richards\add'l scope\135302 Richards Add'l
8/5/2016 4:16:18 PM
Scope_Central_PJ.rvt
REMOVE PANEL SIGN
Basement
0' - 0"
Basement
0' - 0"
4
TOWER C - STAIR, FACING SOUTH
A601
SCALE: 3/16" = 1'-0"
3
TOWER C - STAIR, FACING EAST
A601
SCALE: 3/16" = 1'-0"
2
TOWER C - STAIR, FACING NORTH
A601
SCALE: 3/16" = 1'-0"
1
TOWER C - STAIR, FACING WEST
A601
SCALE: 3/16" = 1'-0"
CITY OF PHILADELPHIA BUSINESS
PRIVILIEGE LICENSE #63180
NEW 18"x24" STAIR
IDENTIFICATION
SIGN, TYP. BY
OWNER TYP.
University of Pennsylvania
Perelman School of Medicine
3rd Floor
36' - 0"
125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107
3rd Floor
36' - 0"
ATKIN OLSHIN SCHADE ARCHITECTS
PAINT ALL EXISTING
UTILITIES IN STAIR
3700 Hamilton Walk, Philadelphia, PA 19104
ALTERNATE NO.1
Richards Medical Research
Laboratory - Additional Scope,
Towers C&D
4th Floor
48' - 0"
MEPFP ENGINEER
BRUCE E. BROOKS & ASSOC.
2209 Chestnut Street
Philadelphia, PA 19103
215.569.0400
CLEAN ALL CIPC STAIR
SURFACES INCLUDING
RISERS
C Tower Stair Cleaning
DATE
08.05.2016
SCALE
3/16" = 1'-0"
DRAWN BY
PQJ
A601
REVISIONS
DESCRIPTION
GL-1
3
A700
EXG FA DEVICE
ALIGNED W/ B.O. TRUSS
ALIGN
ALIGN
EXG SSTL CORNER GUARD
BACK-PAINTED GLASS IN ALUMINUM
BRACKET -TYPE GL-2
GL-1
1
A902
WHITEBOARD
5'-0"
1 1/4"
3'-8"
6'-10"
CONT 1/2"x1/2"x1/16"
ALUM ANGLE TRIM
3'-8"
7'-3"
BUTT JOINT
2'-0"
RELOCATE EXG
THERMOSTAT & CONDUIT
TO WALL OPPOSITE
3'-8"
STEEL DOOR, TRANSOM,
& FRAME
CITY OF PHILADELPHIA BUSINESS
PRIVILIEGE LICENSE #63180
4"
[VERIFY HT]
5/8"
TYP
C:\Users\pjune\Desktop\revit models\135300
Richards\add'l scope\135302 Richards Add'l
8/5/2016 4:16:19 PM
Scope_Central_PJ.rvt
C Tower Lounges
2
Interior Elevation - C Tower Lounge Floors 2-7, Facing East
A602
SCALE: 1/2" = 1'-0"
1
Interior Elevation - Lounge C114, Facing South
A602
SCALE: 1/2" = 1'-0"
DATE
08.05.2016
SCALE
1/2" = 1'-0"
DRAWN BY
PQJ
A602
3700 Hamilton Walk, Philadelphia, PA 19104
REMOVE EXG COVER PLATE AND
PATCH CONCRETE TO MATCH
ADJACENT AREA (TYP OF 3)
Richards Medical Research
Laboratory - Additional Scope,
Towers C&D
PROVIDE CUT-OUT FOR CARD
READER
University of Pennsylvania
Perelman School of Medicine
PROVIDE CUTOUT IN
GLASS FOR MONITOR BACK BOX.
COORD. REMOVAL AND REPLACEMENT
OF MONITOR BY OWNER.
125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107
REMOVE AND REPLACE
EXISTING CMU INFILL
AROUND EXG UTILITIES TO
PROVIDE MINIMUM
CLEARANCES AND NEAT
JOINTS. SEAL JOINTS
ATKIN OLSHIN SCHADE ARCHITECTS
MEPFP ENGINEER
BRUCE E. BROOKS & ASSOC.
2209 Chestnut Street
Philadelphia, PA 19103
215.569.0400
ISSUE DATE
REVISIONS
ISSUE DATE
DESCRIPTION
2
A700
SHELF STANDARDS, 16" O.C.
PNTD PLYWOOD BLOCKING
(1) 18" ADJ SHELF
(1) 20" ADJ SHELF
EXG RACEWAY & CONDUIT
1
A700
SIM
PLAM APRON
PLAM APRON
1
A700
SS SPLASH RETURN
4"
SS SPLASH RETURN
EXG COUNTER
AND CABINETS
C:\Users\pjune\Desktop\revit models\135300
Richards\add'l scope\135302 Richards Add'l
8/5/2016 4:16:20 PM
Scope_Central_PJ.rvt
(2) SURFACE-MNTD
SUPPORT ANGLES
EXG COUNTER
AND CABINETS
CITY OF PHILADELPHIA BUSINESS
PRIVILIEGE LICENSE #63180
3700 Hamilton Walk, Philadelphia, PA 19104
EXTENDED SOLID
SURFACE COUNTERTOP &
BACKSPLASH
Richards Medical Research
Laboratory - Additional Scope,
Towers C&D
EXTENDED SOLID
SURFACE COUNTERTOP
& BACKSPLASH
SCALE: 3/4" = 1'-0"
University of Pennsylvania
Perelman School of Medicine
RELOCATE
WHITEBOARD TO
CLEAR COUNTER
A603
125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107
OWNER'S APPLIANCES
South Elevation - Computer Room D708
ATKIN OLSHIN SCHADE ARCHITECTS
3
MEPFP ENGINEER
BRUCE E. BROOKS & ASSOC.
2209 Chestnut Street
Philadelphia, PA 19103
215.569.0400
EXG FURNITURE WORKBENCHES
C & D Towers
Miscellaneous Millwork
2
South Elevation - Kitchen C208A
A603
SCALE: 3/4" = 1'-0"
1
East Elevation - Kitchen C109
A603
DATE
08.05.2016
SCALE: 3/4" = 1'-0"
SCALE
3/4" = 1'-0"
DRAWN BY
PQJ
A603
REVISIONS
ISSUE DATE
DESCRIPTION
ALIGN
MTL BRACKET ON
DOUBLE-STICK TAPE
MTL CLEAT ON DOUBLESTICK TAPE
VIF
2'-8 1/4"
PNTD 1/4" MASONITE ON
DOUBLE-STICK TAPE
2
A6
04
3
ALTERNATE 3:
INSULATED KNEE PANEL, TYP
4
A604
2 1/2" FABRIC WRAPPED
INSULATED PANEL
HARDENED EDGE
REMOVE FILTER, TYP
GENERAL NOTE - TYP OF (8) BUILDING CORNERS
4
A604
4
A604
TYP
4
A604
TYP
3700 Hamilton Walk, Philadelphia, PA 19104
10'-1"
10'-1"
University of Pennsylvania
Perelman School of Medicine
GLAZING FILM (TYPE-1) AT SOUTH
SIDE ONLY. TYP. OF (8) WINDOWS
CITY OF PHILADELPHIA BUSINESS
PRIVILIEGE LICENSE #63180
SCALE: 1/2" = 1'-0"
125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107
A604
ATKIN OLSHIN SCHADE ARCHITECTS
GLAZING FILM (TYPE-1) AT SOUTH
SIDE ONLY. TYP. OF (8) WINDOWS
C:\Users\pjune\Desktop\revit models\135300
Richards\add'l scope\135302 Richards Add'l
8/5/2016 4:16:20 PM
Scope_Central_PJ.rvt
1
SCALE: 3" = 1'-0"
2'-3"
A604
Enlarged Plan - Goddard Bays
2'-3"
ALTERNATE No. 3
Insulated Knee Panel at Goddard Bays
Richards Medical Research
Laboratory - Additional Scope,
Towers C&D
3 1/4"
4
MEPFP ENGINEER
BRUCE E. BROOKS & ASSOC.
2209 Chestnut Street
Philadelphia, PA 19103
215.569.0400
REMOVE FABRIC FILTERS FROM
SUPPLY DUCTS AND VACCUUM
FIRST 12" OF DUCT
Goddard Knee Panels &
Glazing Film
3
Interior Elevation - Goddard Bays
A604
SCALE: 1/2" = 1'-0"
2
Interior Elevation, Goddard Bays 2
A604
SCALE: 1/2" = 1'-0"
DATE
08.05.2016
SCALE
As indicated
DRAWN BY
PQJ
A604
REVISIONS
ISSUE DATE
DESCRIPTION
8' - 0"
MEPFP ENGINEER
BRUCE E. BROOKS & ASSOC.
2209 Chestnut Street
Philadelphia, PA 19103
215.569.0400
F.O. EXG WALL
2'-0"
(1) 18" ADJ. SHELF:
KV 183 BRACKET
(1) 20" PNTD 3/4" PLYWOOD
SHELF W/ SOLID EDGE
2" x 1-1/2" x 1/4" ALUM STRUC ANGLE
1 1/2"
2" x 1" x 1/8" ALUM ANGLE
3/4" x 3/4" x 1/8" ALUM CHANNEL FRAME
SEE PLANS
(1) 20" ADJ. SHELF:
KV 183 BRACKET
3"
1 1/2"
EXG RACEWAY
4'-6"
4"
SEALANT AND SETTING BLOCK
1"
2 3/8"
5 1/2"
2"
1/8"
1"
2" GROMMET
3/4" SOLID SURFACE
COUNTERTOP
& BACKSPLASH ON
3/4" PLYWOOD
EXG WORK BENCH
1/2" EPOXY ANCHOR & SHIM WASHERS. TYP
BACK PAINTED GLASS (GL-2)
PLAM APRON TO MATCH
EXG DRAWER FRONT
2'-10"
1/8"
2" x 2 1/2" x 1/4" ALUM STRUC ANGLE
3/4" x 3/4" x 1/8" ALUM CHANNEL FRAME
NOTE: VERIFY
DIMENSIONS OF EXG
CASEWORK BEFORE
FABRICATOIN
2" x 1 3/4" x 1/8" ALUM ANGLE
2 3/4"
COUNTERSUNK ALUM SCREWS
Millwork Details
C:\Users\pjune\Desktop\revit models\135300
Richards\add'l scope\135302 Richards Add'l
8/5/2016 4:25:54 PM
Scope_Central_PJ.rvt
EXG CONCRETE WALL
3
WHITEBOARD MOUNTING DETAIL
A700
SCALE: 6" = 1'-0"
CITY OF PHILADELPHIA BUSINESS
PRIVILIEGE LICENSE #63180
1/8"
2
Adjustable Shelves - D1
A700
SCALE: 1 1/2" = 1'-0"
1
Infill Counter at Kitchenettes
A700
SCALE: 1 1/2" = 1'-0"
DATE
08.05.2016
SCALE
As indicated
DRAWN BY
PQJ
A700
3700 Hamilton Walk, Philadelphia, PA 19104
COUNTERSUNK ALUM SCREWS
University of Pennsylvania
Perelman School of Medicine
2 3/4"
125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107
PNTD PLYWOOD BLOCKING
ATKIN OLSHIN SCHADE ARCHITECTS
PROVIDE (1) 2" GROMMET
PER SHELF SECTION
Richards Medical Research
Laboratory - Additional Scope,
Towers C&D
48" SHELF STANDARDS:
KV 83
REVISIONS
EXISTING SSTL DOOR
FRAMES, REPLACE
HORIZONTAL HEAD.
VERTICAL JAMBS TO
REMAIN, TYP
ISSUE DATE
EXISTING MOTION
DETECTOR LOCATION
DESCRIPTION
REMOVE AND REPLACE
MAGNETIC LOCKS
GL-1
REPLACE
EXISTING
GLASS W/
GL-1 GLAZING
LOBBY
GL-1
APPROX LOCATION
OF EXIST DOOR
PIVOT. NEW AUTO
DOOR OPERATOR
REQUIRES 2-3/4"
WEATHER
STRIPPING
TYP
GL-1
REPLACE EXISTING
GLASS W/ GL-1
GLAZING
10 1/2"
REPLACE SETTING
BLOCK W/ SIMILIAR
EXISTING
STEEL
PLATE
3"
3
VESTIBULE - INTERIOR ELEVATION
A900
SCALE: 1/2" = 1'-0"
EXISTING
ALUM PLATE
EXISTING
REFURBISH BRONZE
DOOR FRAME. REPLACE
BOTTOM AND TOP RAILS
GL-1
REMOVE HORZ DIVIDE &
EXTEND GLAZING TO CEILING
REPLACE STL FLANGE
AROUND ENTIRE
PERIMETER OF GLASS
EXISTING
EXTERIOR
GLAZING
ASSEMBLY
GL-1
BRONZE DOOR PULLS
TO MATCH EXISTING
SCALE: 6" = 1'-0"
3"
2' - 8 3/4"
1
A903
INTERIOR
VESTIBULE
2
A900
SCALE: 1/2" = 1'-0"
5
A900
SIM
1 3/4"
REFURBISH BRONZE
DOOR FRAME. REPLACE
BOTTOM AND TOP RAILS
3
REPLACE EXISTING
GLASS W/ GL-1 GLAZING
A901
3/4"
3
A903
REPLACE EXISTING
GLASS W/ GL-1
GLAZING
C:\Users\pjune\Desktop\revit models\135300
Richards\add'l scope\135302 Richards Add'l
8/5/2016 4:16:22 PM
Scope_Central_PJ.rvt
A900
REPLACE EXISTING FLOOR
DIFFUSER PLATES
W/ NON-PERFORATED BRONZE
PLATES AT WIN WALL ONLY
EXISTING DIFFUSER PLATES
AT COLUMNS TO REMAIN, TYP
REPLACE
SETTING BLOCK
W/ SIMILIAR, TYP
ALTERNATE 2A
WORK
4
00
A9
CX01
DC
DC
REPLACE ALL
BRONZE DOOR
THRESHOLDS
TYP
4
A900
EXISTING CARD
READER TO REMAIN
PER ALTERNATE
CX02
EXTERIOR
SCALE: 6" = 1'-0"
4
A900
SIM
ALTERNATE 2A:
RECESSED DOOR
OPERATOR
EXISTING
GRANITE
THRESHOLD
NOTE: ALL WORK ON THIS DRAWING
PERTAINS TO ALTERNATES 2 & 2A
1'-6"
2
EXISTING
BRONZE GUARD
TO REMAIN
5
A900
2
1 3/8"
APPOX OPENING IN SLAB BELOW
6"
7"
EXISTING
TERRAZZO FLOOR
1"
GROUT JOINT
BETWEEN WINDOW AND
OUTSIDE EDGE OF DOOR
THRESHOLDS
EXTERIOR VESTIBULE DOORS - PLAN DETAIL
1'-0"
7"
1 1/2"
1"
A901
ALTERNATE 2A:
BOLLARD W/
ADA PUSHPLATE
FOR DOOR OPERATOR
2
A903
CX04
CX03
EXISTING ALUM
EXPANSION JOINT
SEALANT &
BACKER ROD
1
ALTERNATE SCOPE: RECESSED
DOOR OPERATOR. DOOR TO SWING
OUTWARD ONLY. PROVIDE BRONZE
PULL TO MATCH EXISTING,
(SEE 1/A903 FOR PULL DETAILS)
ALTERNATE 2A:
BOLLARD W/
ADA PUSHPLATE FOR
DOOR OPERATOR
13'-4"
CITY OF PHILADELPHIA BUSINESS
PRIVILIEGE LICENSE #63180
REPLACE PERFORATED
BRONZE VENT PLATES
LOCATED IN WIN WALL W/
NON-PERFORATED BRONZE
PLATES
3"
3 1/2"
7/8"
7/8"
University of Pennsylvania
Perelman School of Medicine
REPLACE SSTL
DOOR STRIKE & STOP
W/ SIMILIAR
VESTIBULE - INTERIOR ELEVATION
125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107
APPROX LOCATION
OF EXIST DOOR
PIVOT. NEW AUTO DR
OPERATOR REQUIRES
2-3/4"
REFURBISHED BRONZE DOORS.
REPLACE TOP AND BOTTOM RAILS, TYP.
REPLACE METAL FLANGE AROUND
PERIMETER OF GLASS.
VERIFY GAUGE, MATERIAL, AND
REPLACE IF REQUIRED
ATKIN OLSHIN SCHADE ARCHITECTS
EXISTING STAINLESS
STEEL DOOR FRAME
TO REMAIN. REPLACE
HEAD ONLY
4 1/2"
INSERT BENT SSTL
PLATE INTO EXISTING
FRAME TO CONCEAL
VERTICAL CONDUIT.
MATCH FINISH W/
ADJACENT FRAME.
PTE
EXTERIOR
GRANITE
THRESHOLD
C Tower Entry Doors
CR
2
A903
DATE
08.05.2016
1
VESTIBULE - ENLARGED PLAN
A900
SCALE
As indicated
SCALE: 1/2" = 1'-0"
DRAWN BY
GR
A900
3700 Hamilton Walk, Philadelphia, PA 19104
A901
1' - 0"
5
A900
REMOVE
THERMOSTAT
4
A901
INTERIOR VESTIBULE DOORS - PLAN DETAIL
4' - 0 1/4"
REPLACE ALL
EXISTING
SIDELIGHT, DOOR
& TRANSOM GL W/
GL-1 GLAZING
3
GL-1
MEPFP ENGINEER
BRUCE E. BROOKS & ASSOC.
2209 Chestnut Street
Philadelphia, PA 19103
215.569.0400
ALUM EXPANSION
JOINT THRESHOLD
GL-1
Richards Medical Research
Laboratory - Additional Scope,
Towers C&D
REPLACE EXISTING
GLASS W/ GL-1 GLAZING
EXISTING SSTL
DOOR FRAMES: REPLACE
HORIZONTAL DOOR HEADS.
VERTICAL JAMBS
TO REMAIN, TYP
3 1/4"
BRONZE PULLS ON
SWING SIDE OF DOORS
REFURBISHED BRONZE DOORS.
REPLACE TOP AND BOTTOM RAILS, TYP.
3' - 0 3/8"
THRESHOLD WDITH
6 3/4"
3/8"
EXG GROUT JOINT
NEOPRENE
SPACER
EXISTING
TERRAZZO
8' - 3 1/2"
NEW VERT SSTL
DOOR STOP
EXISTING SSTL
LOCK ENCLOSURE
3/4"
6"
EXISTING
TERRAZZO
3
A903
ALTERNATE
WORK
EXISTING STAINLESS
STEEL DOOR FRAME TO REMAIN
SSTL PLATE FLUSH
WITH FLOOR AND WELDED
AT EDGES TO CHANNEL, TYP
8' - 6"
7/8"
3/8"
3' - 0"
GL-1
EXISTING
SSTL CROSS
BRACING
REPLACE BRONZE
DOOR PANIC BAR W/
SIMILAR. EXTERIOR DR
PULLS TO BE REPLACED
W/ PULLS MATCHING
ORIGINAL, SEE
DETAIL 1/A90-2
3/4"1/4"
NEOPRENE
SPACER
ISSUE DATE
1/8"
REVISIONS
1/4"
1"
1 1/2"
GL-1 GLAZING
2"
2' - 10 3/4"
5/8"
1"
3 1/2"
EMBEDDED
METAL PLATE
DESCRIPTION
6"
2' - 9 1/2"
NOTE: ALL WORK ON THIS DRAWING
PERTAINS TO ALTERNATES 2 & 2A
1/2"
VIF
MTL FRAME
6"
6"
1/8"
SSTL DOOR FRAME
1 7/8"
WEATHERSTRIPPING
REPLACE BRONZE
TOP DOOR RAIL
REPLACE EXISTING
GLASS W/ GL-1 GLAZING
REPLACE
BRONZE
TOP DOOR
RAIL
6"
8' - 6"
8' - 4"
EDGE OF SSTL
DOOR
FRAME BEYOND
8' - 0 3/4"
WEATHER
STRIPPING
GL-1 GLAZING
REFURBSH
BRONZE
MIDDLE DOOR
'PUSH' RAIL
GL-1 GLAZING
7/8"
8' - 3 1/2"
4' - 0 1/4"
GL-1 GLAZING
REFURBISH
BRONZE
MIDDLE
DOOR
'PUSH' RAIL
MEPFP ENGINEER
BRUCE E. BROOKS & ASSOC.
2209 Chestnut Street
Philadelphia, PA 19103
215.569.0400
1' - 0"
10"
REFURBISH OR REPLACE
BRONZE PANIC PUSH BARS W/
SIMILIAR
11 3/4"
EXTERIOR DOOR
PULLS TO BE REPLACED
W/ PULLS MATCHING
ORIGINAL, SEE
DETAIL 1/A903. VERIFY
DIMENSIONS
7/8"
EDGES OF
FRAME BEYOND
DOOR STRIKE
PATCH
TERRRAZO
SAWCUT EXISTING SLAB FOR
INSTALLATION OF DOOR
OPERATOR AS REQ'D
4 1/2"
3
A903
7"
1 1/4"
1 1/8"
4 1/2"
8"
6 7/8"
INGROUND DOOR
OPERATOR
EXISTING CONC SLAB DEPTH
SLOTTED HOLE
FOR EXPANSION
EXISTING CONC SLAB DEPTH
6 3/4"
8"
8"
STL PLATE BOLTED
TO UNDERSIDE OF
CONCRETE SLAB.
1 1/8"
C:\Users\pjune\Desktop\revit models\135300
Richards\add'l scope\135302 Richards Add'l
8/5/2016 4:16:23 PM
Scope_Central_PJ.rvt
7"
INGROUND DOOR
OPERATOR
EXISTING CONC SLAB DEPTH
EXPANSION JOINT.
VERIFY LOCATION
GROUT
JOINT
EXISTING
OPENING
IN SLAB
GROUT
EXISTING CONC SLAB DEPTH
8"
EXPANSION JOINT
PLATE COVER
1"
PATCH
TERRRAZO
AS REQ'D
6 7/8"
1/4"
EXISTING
TERRAZZO
FINISH
3"
3/4"
EXIST MTL
EXPANSION
PLATE
NEW BRONZE
THRESHOLD
TO MATCH
EXISTING
3"
NEW
BRONZE
THRESHOLD
TO MATCH
EXISTING
NEOPRENE
SPACER
EXISTING STEEL
SUPPORTS.
VERIFY SIZE
AND LOCATIONS
IN THE FIELD
EXISTING
OPENING
IN SLAB
1 1/4"
CITY OF PHILADELPHIA BUSINESS
PRIVILIEGE LICENSE #63180
Entry Door Details
DATE
08.05.2016
4
INTERIOR VESTIBULE WINDOW WALL SECTION DETAIL
A901
SCALE: 6" = 1'-0"
3
INTERIOR VESTIBULE DOOR SECTION DETAIL
A901
SCALE: 6" = 1'-0"
3
A903
ALTERNATE
WORK
2
EXTERIOR VESTIBULE DOOR SECTION DETAIL
A901
SCALE: 6" = 1'-0"
1
EXTERIOR VESTIBULE WIN WALL SECTION DETAIL
A901
SCALE: 6" = 1'-0"
SCALE
6" = 1'-0"
DRAWN BY
GR
A901
3700 Hamilton Walk, Philadelphia, PA 19104
6"
EXISTING
PERFORATED
BRONZE PANEL
TO BE REPLACED
W/ NEW SOLID
BRONZE PLATE
REPLACE
BRONZE
BOTTOM
DOOR RAIL
REPLACE
BRONZE
BOTTOM
DOOR RAIL
University of Pennsylvania
Perelman School of Medicine
INFLOOR RECESSED
ACTUATOR
OUTPUT SHAFT
125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107
2' - 8 3/4"
1/2"
ATKIN OLSHIN SCHADE ARCHITECTS
STAINLESS STEEL
CROSS FRAME
Richards Medical Research
Laboratory - Additional Scope,
Towers C&D
1/2"
REVISIONS
ISSUE DATE
SEALANT & BACKER ROD
DESCRIPTION
3/8"
1 3/4"
1 1/2"
EXISTING CONCRETE WALL
1 3/4"
SPACER
EXISTING BRICK WALL
SEALANT & BACKER ROD
SSTL DOOR
1' - 3 3/4"
1' - 3"
SSTL ATTACHMENT FLANGE,
TO MATCH DOOR AND FRAME
1 1/2"
1 1/2"
1 5/8"
4 3/4"
1 1/2"
3/8"
1 1/2"
CLEAN
EXISTING
VERT
SOLDIER
COURSE
1 1/2"
GL-1 GLASS
1 1/2"
2 1/4"
1 1/2"
1/2"
SSTL DOOR FRAME
GL-1 GLASS
3
SSTL ATTACHMENT FLANGE,
TO MATCH DOOR AND FRAME
LOADING DOCK DOOR - PLAN
A902
SCALE: 6" = 1'-0"
SEALANT
SSTL ATTACHMENT
FLANGE. EXTEND
FROM FLOOR TO CEILING
1/2"
4'-2"
SSTL WATER DIVERTER
SSTL DOOR FRAME
1 1/4"
FRICTION HINGE
SSTL DOOR
4
A902
A902
SCALE: 1/2" = 1'-0"
SSTL KICK PANEL
8 5/8"
SSTL
ATTACHEMENT
FLANGE
GL-1
8' - 6"
4"
CONTINUOUS
WEATHERSEAL
1/2" SILL
3' - 6"
3/8"
EXTERIOR
SILL
STL SPREADER
PLATE BELOW SILL
[VERIFY HT REQ'D]
WEATHERSEAL
C:\Users\pjune\Desktop\revit models\135300
Richards\add'l scope\135302 Richards Add'l
8/5/2016 4:16:24 PM
Scope_Central_PJ.rvt
BENCH OVERLAPS
VERT DOOR FLANGE
4
LOADING DOCK DOOR SECTION DETAIL
A902
SCALE: 6" = 1'-0"
1
LOADING DOCK DOOR INTERIOR ELEVATION
A902
SCALE: 1/2" = 1'-0"
SSTL
KICK
PLATE
CITY OF PHILADELPHIA BUSINESS
PRIVILIEGE LICENSE #63180
CLEAN EXISTING
VERTICAL BRICK
COURSE
University of Pennsylvania
Perelman School of Medicine
GL-1
125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107
SSTL ATTACHEMENT
FLANGE BEYOND
3' - 3"
T-BAR
ATKIN OLSHIN SCHADE ARCHITECTS
EXTERIOR
Loading Dock Door
Details
DATE
08.05.2016
SCALE
As indicated
DRAWN BY
GR
A902
3700 Hamilton Walk, Philadelphia, PA 19104
2
LOADING DOCK ENTRY DOOR PLAN
Richards Medical Research
Laboratory - Additional Scope,
Towers C&D
3
A902
GL-1 GLASS
MEPFP ENGINEER
BRUCE E. BROOKS & ASSOC.
2209 Chestnut Street
Philadelphia, PA 19103
215.569.0400
C114
1 5/8"
REVISIONS
VARIES
VARIES
2"
CERAMIC TILE
6"
TOP OF CASE
STONE SADDLE
EXG FLOOR
S2
ADA SILL AT EXG DOOR
3 3/4"
FLOOR AS
SCHEDULED
INTERIOR SILL DETAILS
A903
NEW BRONZE SILL TO
MATCH EXISTING
TOP OF OPERATOR CASE
BELOW THRESHOLD
[2] INLINE DOORS
TO OPERATE
TOGETHER
S1
STONE SADDLE
REFURBISHED DOOR
MODIFY TO RECEIVE
OPERATOR STEM
4"
HORIZONTAL SECTION B-B
REFURBISHED
FRAME
LIQUID TIGHT
CONDUIT
SCALE: 3" = 1'-0"
EXISTING GRANITE
(EXTERIOR DOORS ONLY)
1" OUTPUT SHAFT
8"
4
ADA THRESHOLD
EXISTING TERRAZZO
PATCH AS REQUIRED
6" TOP OF CASE
S3
NO SADDLE
DOOR
DESCRIPTION
7"
FLOOR AS
SCHEDULED
EXG DOOR & FRAME
ISSUE DATE
EXISTING SSTL
DOOR FRAME
6 1/2" PIT
DOOR
1 1/4"
1/4"
LIQUID TIGHT
CONDUIT
RAPID SET POUR FILL
2"
4 7/8"
9 3/4"
7 5/8"
OPERATOR CASE
(2) MTL STUDS @ HEADS
AND JAMBS
B
B
A
FLOOR
GWB PARTITION AS
SCHEDULED
EXG CMU
MASONRY ANCHOR
VERTICAL SECTION A-A
1"
GROUT SOLID, TYP
1 1/4"
JAMB ANCHOR, UL RATED
@ RATED FRAMES
1'-9 1/2" CASE
1 1/4"
2'-0" PIT
1"
CONT SEALANT
A
ADJ WALL WHERE
OCCURS
HM FRAME
3
GROUT SOLID
ELEVATION
ALTERNATE No. 2A
AUTOMATIC DOOR OPERATOR DETAILS
A903
SCALE: 3" = 1'-0"
1.5" HOLE THROUGH BOLLARD
MOUNTING BRACKET FOR CONDUIT
PLAN
SCHEDULED DOOR
SCHEDULED DOOR
MOUNTING HOLES (4 LOCATIONS)
H/J-2
JAMB SIM
HOLLOW METAL FRAME @ CMU WALL
6"
SCALE: 3" = 1'-0"
1/2" THICK MORTISED BOLLARD CAP,
R.F. TRANSPARENT (BLACK)
Hardware Revisions
2.
3.
4.
Replace all existing door hardware (floor closers,
top pivots, and pull (where missing.)
Refurbish all door components including
reinforcing or replacing top and bottom rails to
accommodate new closer hardware.
Replace all door and sidelight glass with
tempered, GL-1 glass.Remove miscellaneous
abandoned devices in and on vestibule surfaces.
Reuse existing black key security devices.
ALTERNATE 2A:
EQ
1.
2.
EQ
6"
3.
F
FLUSH
L1
4.
LOUVERED
5.
DOOR TYPES (NEW)
A903
SCALE: 1/4" = 1'-0"
Classroom
Classroom
Classroom
Classroom
Privacy w/ Occupied Indicator
10
10
10
10
11
Storeroom
Storeroom
Storeroom
Storeroom
Storeroom
Storeroom
Storeroom
Storeroom
Passage
Classroom
Classroom
Classroom
Classroom
Classroom
Classroom
Classroom
09
10
10
10
10
10
10
10
Storeroom
Storeroom
Storeroom
Storeroom
Storeroom
Classroom
Classroom
Classroom
Classroom
Classroom
10
10
10
10
10
Storeroom
Passage
09
6"
1"
CARD READER AT EXTERIOR BOLLARD
EXISTING BRONZE
PLATE
1/8"
FORMED AND BRAZED
BRONZE BAR STOCK,
MATCH EXISTING
BRONZE TUBE,
MATCH EXISTING
1'-0"
7
Items 1 through 4 above.
Remove existing black key security devices and
patch surfaces.
Install power operated door openers (in-floor
device) for west leaves. Inner door to swing out
only. Add new bronze pulls on both interior doors
to match existing.
Install (2) new custom bollards for ADA actuator
and new black-key devices.
Remove existing floor grills and infill with st steel
plate (or threshold as part of floor closer cover.)
Storeroom
Storeroom
Storeroom
Storeroom
Storeroom
C:\Users\pjune\Desktop\revit models\135300
Richards\add'l scope\135302 Richards Add'l
8/5/2016 4:16:24 PM
Scope_Central_PJ.rvt
Door #
Basement
C003
C003A
C003B
1st Floor
C110
C114
CX01
CX02
CX03
CX04
Status
NEW
NEW
NEW
Hardware Type Material
01
02
03
L1
F
F
HM
HM
HM
Door
Finish
PNT
PNT
PNT
Door Schedule
Frame
Type
Material
Width Height Status
3' - 0"
3' - 0"
3' - 0"
7' - 0"
7' - 0"
7' - 0"
NEW
NEW
NEW
F1
F1
F1
HM
HM
HM
1/2" HEAVY DUTY MASONRY ANCHORS,
MIN. ENGAGEMENT 1-1/4" DEEP
Finish
P-6
P-1
P-1
Head
H2
H1
H1
Jamb
J2
J1
J1
Sill
S1
S3
S3
Comments
PROVIDE 18"x6" LOUVER
1" UNDERCUT
1" UNDERCUT
BOLLARD MOUNTING BRACKET
Door Schedule & Details
1/4-20 STAINLESS STEEL F.H.M.S.
EXG
NEW
EXG
EXG
EXG
EXG
12
08
04
05
06
07
F
FG
FG
FG
FG
FG
HM
SSTL/GL
BR/GL
BR/GL
BR/GL
BR/GL
EXG
MFR
EXG
EXG
EXG
EXG
6' - 0"
4' - 0"
3' - 0"
3' - 0"
3' - 0"
3' - 0"
7' - 0"
8' - 6"
8' - 3"
8' - 3"
8' - 3"
8' - 3"
EXG
NEW
EXG
EXG
EXG
EXG
F1
1/A902
1&2/A600
1&2/A600
1&2/A600 SIM
1&2/A600 SIM
HM
SSTL
BR
BR
BR
BR
EXG
MFR
EXG
EXG
EXG
EXG
EXG
4/A902
4/A900
4/A900
5/A900
5/A900
EXG
3/A902
4/A900
4/A900
5/A900
5/A900
S2
4/A902
2/A901
2/A901
4/A901
4/A901
CITY OF PHILADELPHIA BUSINESS
PRIVILIEGE LICENSE #63180
1.
SCALE: 1/4" = 1'-0"
4"
University of Pennsylvania
Perelman School of Medicine
A903
THRU BOLT TO
MATCH EXISTING
125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107
ALTERNATE 2:
INTERIOR FRAME TYPES
SWITCH MOUNT PREP FOR CURVED
SWITCHES OR ADAPTER CUFF FOR
MOUNTING FLAT 4-1/2" X 4-1/2" CARD READER
1 1/2"
6
HOLLOW MTL
09
12
1/4"
F1
Passage
N/A
Hardware
Group
6"
VESTIBULE DOORS
SCOPE OF WORK
Storeroom
N/A
New Function
3'-6"
1st Floor
C109
C110
3rd Floor
C310A
C310B
C310C
C310D
C316
4th Floor
C416
C420
C421
C422
C423
C424
C425
C426
5th Floor
C508AA
C509A
C509AA
C510A
C510AA
6th Floor
C609A
Current Function
STRAP FOR OPTIONAL TRANSMITTER
CONNECT WIRES TO SWITCH
ATKIN OLSHIN SCHADE ARCHITECTS
Door #
MEPFP ENGINEER
BRUCE E. BROOKS & ASSOC.
2209 Chestnut Street
Philadelphia, PA 19103
215.569.0400
#4-40 SET SCREWS
GRANITE OR TERRAZO MOUNTING SURFACE
DATE
08.05.2016
ALTERNATE #2 - AUTOMATIC DOOR OPERATOR
ALTERNATE #2 - AUTOMATIC DOOR OPERATOR
3700 Hamilton Walk, Philadelphia, PA 19104
A903
Richards Medical Research
Laboratory - Additional Scope,
Towers C&D
HEAD AND JAMB TYPES
1/8"
5
H/J-1
JAMB SIM
HOLLOW METAL FRAME @ GYPSUM BOARD PARTITION
2
ALTERNATE No. 2A
DOOR ACTUATOR BOLLARD
A903
SCALE: 3" = 1'-0"
1
NEW DOOR PULL@ EXISTING ENTRY DOOR
A903
SCALE: 6" = 1'-0"
SCALE
As indicated
DRAWN BY
GR
A903
REVISIONS
Basement
C003
VESTIBULE
C003A GENDER NEUTRAL RESTROOM
C003B ACCESSIBLE GENDER NEUTRAL RESTROOM
ST-C0 STAIR C
CT-1
CT-1
CT-1
XT-1
CT-1
CT-1
CT-1
N/A
GWB+P-1
CT-2
CT-2
XCW-1
GWB+P-1
CT-2
CT-2
XCW-1
GWB+P-1
CT-2
CT-2
XCW-1
GWB+P-1
CT-2
CT-2
XCW-1
ACT-3
ACT-3//GWB+P-7 FULL-HEIGHT WALL TILE
ACT-3/GWB+P-7 FULL-HEIGHT WALL-TILE
XCC-1
SEE PLANS & STAIR ELEVATIONS, USE P-4 TO PNT UTILITIES
1st Floor
ST-C1 STAIR C
XT-1
N/A
XCW-1
XCW-1
XCW-1
XCW-1
XCC-1
SEE PLANS & STAIR ELEVATIONS, USE P-4 TO PNT UTILITIES
2nd Floor
ST-C2 STAIR C
XT-1
N/A
XCW-1
XCW-1
XCW-1
XCW-1
XCC-1
SEE PLANS & STAIR ELEVATIONS, USE P-4 TO PNT UTILITIES
3rd Floor
ST-C3 STAIR C
XT-1
N/A
XCW-1
XCW-1
XCW-1
XCW-1
XCC-1
SEE PLANS & STAIR ELEVATIONS, USE P-4 TO PNT UTILITIES
4th Floor
ST-C4 STAIR C
XT-1
N/A
XCW-1
XCW-1
XCW-1
XCW-1
XCC-1
SEE PLANS & STAIR ELEVATIONS, USE P-4 TO PNT UTILITIES
5th Floor
ST-C5 STAIR C
XT-1
N/A
XCW-1
XCW-1
XCW-1
XCW-1
XCC-1
SEE PLANS & STAIR ELEVATIONS, USE P-4 TO PNT UTILITIES
6th Floor
ST-C6 STAIR C
XT-1
N/A
XCW-1
XCW-1
XCW-1
XCW-1
XCC-1
SEE PLANS & STAIR ELEVATIONS, USE P-4 TO PNT UTILITIES
7th Floor
ST-C7 STAIR C
XT-1
N/A
XCW-1
XCW-1
XCW-1
XCW-1
XCC-1
SEE PLANS & STAIR ELEVATIONS, USE P-4 TO PNT UTILITIES
MATERIAL
FLOOR
CT-1
XT-1
CERAMIC TILE FLOOR
EXG TERRAZZO
BASE
CT-1
CERAMIC BASE TILE
PAINT
P-1
P-3
P-4
P-5
P-6
P-7
EGGSHELL LATEX
SEMI-GLOSS LATEX
EGGSHELL LATEX
EGGSHELL LATEX
FLAT LATEX
FLAT LATEX
WALL
CT-2
XCW-1
CERAMIC WALL TILE
EXG CONC/CMU WALL
CEILING
ACT-3
GWB
XCC-1
ACOUSTICAL CEILING PANEL
GYPSUM BOARD, PNTD
EXG CONC CEILING
FINISH KEY SCHEDULE
COLOR
APPRVD MFR
SIZE
REMARKS
DESERT GRAY SPC
EXG
1"x1" SQUARE
DESERT GREAT SPC
1'x1" SQUARE
PROVIDE COVE, BULLNOSE, AND CORNER SHAPES
SHERWIN WILLIAMS
SHERWIN WILLIAMS
SHERWIN WILLIAMS
SHERWIN WILLIAMS
SHERWIN WILLIAMS
SHERWIN WILLIAMS
SW 7551 GREEK VILLA
SW 7551 GREEK VILLA
GRAY MATCH
SW7017 DORIAN GRAY
SW7030 ANEW GRAY
SW 7007 CEILING BRIGHT WHITE
N/A
N/A
N/A
N/A
N/A
N/A
HM IN GWB WALLS PNTD WITH P-1
EXPOSED OVERHEAD UTILITIES IN FINISHED AREAS; TRUSS INFILL PTNS
CMU SUBSTRATES
CONCRETE SUBSTRATES; D TOWER BASEMENT CLG
GWB CEILINGS
PEPPER WHITE SPC
EXG
1"x1" SQUARE
N/A
PROVIDE COVE, BULLNOSE, AND CORNER SHAPES
N/A
WHITE
TBD
EXG
24"x24"
N/A
N/A
SEE RCP'S FOR ACCESSORIES
N/A
ARMSTRONG
N/A
CITY OF PHILADELPHIA BUSINESS
PRIVILIEGE LICENSE #63180
NOTES
Finish Schedule & Key
DATE
08.05.2016
SCALE
DRAWN BY
PQJ
A910
3700 Hamilton Walk, Philadelphia, PA 19104
CLG FINISH
Richards Medical Research
Laboratory - Additional Scope,
Towers C&D
WEST
University of Pennsylvania
Perelman School of Medicine
NORTH
FINISH SCHEDULE
WALL FIINISH
SOUTH
EAST
125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107
ROOM NAME
KEY NAME
C:\Users\pjune\Desktop\revit models\135300
Richards\add'l scope\135302 Richards Add'l
8/5/2016 4:16:25 PM
Scope_Central_PJ.rvt
FLOOR BASE
FINISH FINISH
ATKIN OLSHIN SCHADE ARCHITECTS
ROOM
#
DESCRIPTION
MEPFP ENGINEER
BRUCE E. BROOKS & ASSOC.
2209 Chestnut Street
Philadelphia, PA 19103
215.569.0400
ISSUE DATE
REVISIONS
HVAC LEGEND
DESCRIPTION
STRAINER
EXISTING TO REMAIN
PIPE DROP
THERMOMETER
EXISTING TO BE REMOVED (DEMO PLANS)
PIPE TAKE-OFF UP
NEW WORK
PRESSURE GAGE W/ BALL VALVE
PIPE ANCHOR
RETURN PIPING (NEW WORK PLANS)
PIPE GUIDE
STEAM PRESSURE GAGE W/ BALL VALVE
CAP
RETURN, EXHAUST, MAKEUP, OR OUTSIDE AIR INTAKE
D
STEAM DRIP POCKET
SIDEWALL GRILLE
M
MOTORIZED DAMPER
PIPE UP
PIPE DOWN
FD
FIRE DAMPER W/ ACCESS PANEL
FD
FS
FIRE AND SMOKE DAMPER WITH DUCT
SMOKE DETECTOR AND ACCESS PANEL
RETURN AIR GRILLE
SUPPLY AIR DIFFUSER
STEAM TRAP
F/S
CONNECT NEW TO EXISTING
SUPPLY AIR DIFFUSER 2-WAY
TWO-WAY CONTROL VALVE
CUT AND CAP
FLEX DUCT
THREE-WAY CONTROL VALVE
(E)
EXISTING TO REMAIN
VOLUME DAMPER
BALL VALVE
(R)
EXISTING TO BE REMOVED
X
BUTTERFLY VALVE
(RL)
UNDERCUT DOOR OR LOUVERED DOOR
EXISTING TO BE RELOCATED
MEPFP ENGINEER
BRUCE E. BROOKS & ASSOC.
2209 Chestnut Street
Philadelphia, PA 19103
215.569.0400
UNION
PRESSURE RELIEF VALVE
DIAMETER
HUMIDISTAT
S
SMOKE DETECTOR
CALIBRATED BALANCING VALVE
CO2
CARBON DIOXIDE SENSOR
XX
GATE VALVE
S
XX
EQUIPMENT TAG
EQUIPMENT TYPE DESIGNATOR
EQUIPMENT NUMBER
SENSOR
X
XX
CHECK VALVE
HVAC WATER RISER LOCATION
RISER TYPE
RISER NUMBER
T
THERMOSTAT
X
DOUBLE CHECK VALVE
W
XX
BAS WATER DETECTOR
ZS
ZONE SUPPY VALVE ASSEMBLY. SEE H800
ZR
ZONE RETURN VALVE ASSEMBLY. SEE H800
SECTION MARKER
SECTION NUMBER
SHEET NUMBER
VAV BOX
REDUCED PRESSURE BACKFLOW PREVENTION
BFP
HVAC DRAWING SCHEDULE
SHEET NUMBER
H000
H100
H200
H201
H300
H301
H800
SHEET NAME
HVAC COVER SHEET
HVAC KEY PLANS
HVAC LEVELS B, 1, & 2 DEMOLITION PLANS
HVAC LEVELS 3, 4, 6, 7, & 8 DEMOLITION PLANS
HVAC LEVELS B, 1, & 2 NEW WORK PLANS
HVAC LEVELS 3, 4, 7, & 8 NEW WORK PLANS
HVAC SCHEDULES AND DETAILS
100% CONSTRUCTION DOCUMENTS
07/15/16
●
●
●
●
●
●
●
3700 Hamilton Walk, Philadelphia, PA 19104
H
Richards Medical Research
Laboratory - Additional Work
Towers C&D
HEAT PUMP/HORSE POWER
HIGH PRESSURE STEAM RETURN
HIGH PRESSURE STEAM SUPPLY
DOMESTIC HOT WATER RECIRCULATION/HOUR
HEAT RECOVERY WHEEL
HOT WATER
HEATING HOT WATER PUMP
HEATING HOT WATER RETURN
HEATING HOT WATER SUPPLY
HEAT EXCHANGER
REFRIGERANT LIQUID LINE/LOUVER
LEAVING AIR TEMPERATURE
LINEAR DIFFUSER - RETURN
LINEAR BAR GRILLE
LINEAR DIFFUSER
LOW PRESSURE STEAM RETURN
LOW PRESSURE STEAM SUPPLY
LINEAR SUPPLY REGISTER
LINEAR RETURN GRILLE
LEAVING WATER TEMPERATURE
MAXIMUM
1000 BTUH
MECHANICAL CONTRACTOR
MINIMUM FUSE AMPACITY
MOTORIZED DAMPER
MAXIMUM FUSE SIZE
MINIMUM
MAXIMUM OVER-CURRENT PROTECTION SIZE
MEDIUM PRESSURE STEAM RETURN
MEDIUM PRESSURE STEAM SUPPLY
MAKE-UP AIR
NEW WORK
NOT APPLICABLE
NORMALLY CLOSED
NOT IN CONTRACT
NORMALLY OPEN
NOT TO SCALE
OUTSIDE AIR
OUTSIDE AIR INTAKE
OPPOSED BLADE DAMPER
OFFICE OF PHYSICAL PLANT
PUMP
PARALLEL BLADE DAMPER
PLUMBING CONTRACTOR
PUMPED CONDENSATE DRAIN PIPING
PRESSURE REDUCING VALVE
POUNDS PER SQUARE INCH
PACKAGED TERMINAL AIR CONDITIONER
EXISTING TO BE REMOVED
REFRIGERANT GAS RETURN LINE
RETURN AIR
RELATIVE HUMIDITY
EXISTING TO BE RELOCATED
REVOLUTIONS PER MINUTE
ROOF TOP UNIT
SLOPE
SANITARY/SLOPE
SUPPLY AIR
SECONDARY CHILLED WATER SUPPLY OR RETURN
SPLITTER DAMPER
SQUARE FEET
SOUND TRAP/SILENCER
TESTING, ADJUSTING & BALANCING
TRANSFER AIR GRILLE
TERTIARY CHILLED WATER SUPPLY OR RETURN
TOTAL DEVELOPED HEAD(DYNAMIC)
TRANSFER FAN
TOP OF DUCT
TRANSITION
TOTAL STATIC PRESSURE
TYPICAL
UNIT HEATER
UNLESS NOTED OTHERWISE
UNIT VENTILATOR
VARIABLE AIR VOLUME
VOLUME DAMPER
VARIABLE FREQUENCY DRIVE
VERIFY IN FIELD
WET BULB
WALL EXHAUST GRILLE
WALL EXHAUST REGISTER
WATER PRESSURE DROP
WALL RETURN GRILLE
WALL RETURN REGISTER
WALL SUPPLY GRILLE
WATER SOURCE HEAT PUMP
WALL SUPPLY REGISTER
WIRE MESH SCREEN
University of Pennsylvania
Perelman School of Medicine
HP
HPR
HPS
HR
HRC
DHW
DHWP
DHWR
HWS
HTX
L
LAT
LDR
LBG
LD
LPR
LPS
LSR
LRG
LWT
MAX
MBH
MC
MCA
MD
MFS
MIN
MOCP
MPR
MPS
MUA
(N)
N/A
NC
NIC
NO
NTS
OA
OAI
OBD
OPP
P
PBD
PC
PD
PRV
PSI
PTAC
(R)
R
RA
RH
(RL)
RPM
RTU
s=02'
S
SA
SCHWS/R
SD
SF
ST
TAB
TAG
TCHWS/R
TDH
TF
TOD
TR
TSP
TYP
UH
U.N.O.
UV
VAV
VD
VFD
VIF
WB
WEG
WER
WPD
WRG
WRR
WSG
WSHP
WSR
WMS
125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107
COMPRESSED AIR PIPING
AUTOMATIC AIR VENT
AIR COMPRESSOR
AIR CONDITIONING FAN (AIR HANDLING UNIT)
DUCT ACCESS DOOR
ABOVE FINISHED FLOOR
ACCESS PANEL
AIR PRESSURE DROP
AIR SEPARATOR
AUTOMATIC TEMPERATURE CONTROLS
BOILER
BOTTOM OF DUCT
BOTTOM OF PIPE
BRITISH THERMAL UNIT
BTU PER HOUR
CEILING DIFFUSER
CEILING EXHAUST GRILLE
CEILING EXHAUST REGISTER
CUBIC FEET PER HOUR
CUBIC FEET PER MINUTE
CHILLER
CHILLED WATER RETURN
CHILLED WATER SUPPLY
CONSTRUCTION MANAGER
CLEAN OUT
CONTINUED
CONDENSATE PUMP
CEILING RETURN GRILLE
CEILING RETURN REGISTER
COOLING TOWER
CONDENSING UNIT
CABINET UNIT HEATER
CONSTANT VOLUME
CHILLED WATER PUMP
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
CONDENSATE DRAIN PIPING
DRY BULB/DECIBEL
A-WEIGHTED DECIBEL
DIRECT DIGITAL CONTROLS
DOMESTIC HOT WATER
DOMESTIC HOT WATER RETURN
DIAMETER
DOWN
DUCT MOUNTED SUPPLY GRILLE
DUAL TEMPERATURE WATER RETURN
DUAL TEMPERATURE WATER SUPPLY
DIRECT EXPANSION
EXISTING TO REMAIN
EXHAUST AIR
EACH
ENTERING AIR TEMPERATURE
ELECTRIC BASEBOARD CONVECTOR
ELECTRICAL CONTRACTOR
ELECTRIC DUCT HEATER
EXHAUST FAN
ENERGY RECOVERY WHEEL
EXTERNAL STATIC PRESSURE
EXPANSION TANK
ELECTRIC WATER COOLER
ELECTRIC WATER HEATER
ENTERING WATER TEMPERATURE
EXISTING
FURNACE/FAHRENHEIT
FREE AREA/FRESH AIR
FRESH AIR INLET
FLEX CONNECTION/FAN COIL/FORCED CONDENSATE
FLOOR DRAIN
FLEXIBLE
FUEL OIL RETURN
FUEL OIL SUPPLY
SPRINKLER/FIRE PROTECTION CONTRACTOR
FEET PER MINUTE
FLOOR RETURN GRILLE
FLOOR RETURN REGISTER
FLOOR SUPPLY GRILLE
FLOOR SUPPLY REGISTER
FOOT/FEET
FIN-TUBE CONVECTOR
GAS
GENERAL CONTRACTOR/GRAVITY CONDENSATE
GROUND COUPLED RETURN
GROUND COUPLED SUPPLY
GALLONS PER MINUTE
ATKIN OLSHIN SCHADE ARCHITECTS
A
AAV
AC
ACF
AD
AFF
AP
APD
AS
ATC
B
BOD
BOP
BTU
BTUH
CD
CEG
CER
CFH
CFM
CH
CHWR
CHWS
CM
CO
CONT
CP
CRG
CRR
CT
CU
CUH
CV
CWP
CWR
CWS
D
DB
DBA
DDC
DHW
DHWR
DIA
DN
DSG
DTR
DTS
DX
(E)
E
EA
EAT
EBBC
EC
EDH
EFN
ERW
ESP
ET
EWC
EWH
EWT
EX
F
FA
FAI
FC
FD
FLEX
FOR
FOS
FPC
FPM
FRG
FRR
FSG
FSR
FT
FTC
G
GC
GCR
GCS
GPM
ISSUE DATE
HVAC PLAN SYMBOLS
ABBREVIATIONS
C:\Users\sas\Documents\13-129 Richards Add'l
Scope_SAS.rvt
8/5/2016 12:35:08 PM
HVAC COVER SHEET
DATE
08.05.2016
SCALE
1/8" = 1'-0"
DRAWN BY
AG
H000
REVISIONS
ISSUE DATE
DN
UP
2
H201
REF.
2
H301
DN
UP
REF.
DN
DESCRIPTION
1
H200
1
H300
UP
DN
1
HVAC BASEMENT KEY PLAN
H100 1" = 40'-0"
5
HVAC LEVEL 4 KEY PLAN
H100 1" = 40'-0"
DN
UP
REF.
2
H300
REF.
DN
UP
2
H200
5
H201
5
H301
UP
UP
8
2
MEPFP ENGINEER
BRUCE E. BROOKS & ASSOC.
2209 Chestnut Street
Philadelphia, PA 19103
215.569.0400
HVAC LEVEL 6 KEY PLAN
H100 1" = 40'-0"
HVAC LEVEL 1 KEY PLAN
H100 1" = 40'-0"
DN
UP
3
H201
3
H200
REF.
3
H300
DN
D
N
UP
REF.
3
H301
1
H201
1
H301
DN
UP
REF.
4
H201
4
H301
HVAC KEY PLANS
C:\Users\sas\Documents\13-129 Richards Add'l
Scope_SAS.rvt
8/5/2016 12:35:49 PM
UP
DN
4
HVAC LEVEL 3 KEY PLAN
H100 1" = 40'-0"
7
HVAC LEVEL 8 KEY PLAN
H100 1" = 40'-0"
DATE
08.05.2016
SCALE
1" = 40'-0"
DRAWN BY
AG
H100
3700 Hamilton Walk, Philadelphia, PA 19104
DN
UP
Richards Medical Research
Laboratory - Additional Work
Towers C&D
HVAC LEVEL 7 KEY PLAN
H100 1" = 40'-0"
HVAC LEVEL 2 KEY PLAN
H100 1" = 40'-0"
University of Pennsylvania
Perelman School of Medicine
6
3
125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107
UP
ATKIN OLSHIN SCHADE ARCHITECTS
DN
REVISIONS
ISSUE DATE
DESCRIPTION
(E)6ø SA
REF.
(E)14x10 SA
(R) TRANSFER
GRILLES. SEE ARCH
DRAWINGS FOR
WALL PATCHING.
(E)6ø SA
(RL) TEMP/HUMIDITY
SENSOR. SEE NEW WORK
PLANS FOR NEW LOCATION
T
T H
H
F/S
REMOVE TWO EXISTING RADIATORS AND
ASSOCIATED PIPING AND CONTROLS.
(E)16x8 SA
(E)20x10 SA
(E)12x6 SA
(E)16x8 SA
REMOVE CHILLED
BEAM FOR REINSTALLATION
BELOW RETURN
DUCT.
(R) 14x8 WRR AND
DUCT BRANCH
(R) TRANSFER ASSEMBLY. SEE ARCH
DRAWINGS FOR WALL PATCHING SCOPE.
(R) TRANSFER
ASSEMBLY
20x10
(E) 14x12 SA
F/S
F/S
(E)14x12 SA(E) BRANCH PIPE TAPS OFF
BOTTOM OF MAIN.
RELOCATE TO TOP TO
MAKE WAY FOR RA DUCT.
REMOVE DUCT AND
PIPING CONNECTION TO
CHILLED BEAM
SA 6ø
C:\Users\sas\Documents\13-129 Richards Add'l
Scope_SAS.rvt
8/5/2016 12:36:02 PM
HVAC BASEMENT DEMOLITION PLAN
H200 1/8" = 1'-0"
HVAC LEVEL 2 DEMOLITION PLAN
H200 1/4" = 1'-0"
3700 Hamilton Walk, Philadelphia, PA 19104
1
3
University of Pennsylvania
Perelman School of Medicine
HVAC LEVEL 1 DEMOLITION PLAN
H200 1/4" = 1'-0"
125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107
2
ATKIN OLSHIN SCHADE ARCHITECTS
UP
Richards Medical Research
Laboratory - Additional Work
Towers C&D
MEPFP ENGINEER
BRUCE E. BROOKS & ASSOC.
2209 Chestnut Street
Philadelphia, PA 19103
215.569.0400
F/S
SA 5ø
(R) 20x10 WRR AND
DUCT BRANCH
(E)24x10 RA
(E) 16x14 SA
(E) 12x8 SA
(E) 22x12 SA
REMOVE PIPING BACK TO MAINS
RECENTLY INSTALLED IN PHASE 2.
(E) 22x16 SA
(E) 16x8 SA
(E)16x8 SA
(E)26x12 SA
(R) 8x16 GRILLE. SEE
NEW WORK PLAN
FOR RELOCATION.
(E)16x12 RA
F/S F/S
REF.
(RL) TEMP/HUMIDITY
SENSOR. SEE NEW WORK
PLANS FOR NEW LOCATION
HVAC LEVELS B, 1, & 2
DEMOLITION PLANS
DATE
08.05.2016
SCALE
As indicated
DRAWN BY
AG
H200
REVISIONS
ISSUE DATE
DESCRIPTION
(RL) TEMP/HUMIDITY
SENSOR. SEE NEW WORK
PLANS FOR NEW LOCATION
(RL) TEMP/HUMIDITY
SENSOR. SEE NEW WORK
PLANS FOR NEW LOCATION
REF.
WRR 14X10
585 CFM
H
T
REMOVE CHILLED BEAM FOR
RE-INSTALLATION BELOW
RETURN DUCT.
RELOCATE CHW PIPING ABOVE
WIRE TROUGH/SOLID CABLE
TRAY TO ALLOW ROOM BELOW
FOR RETURN AIR DUCT.
(R) TRANSFER
ASSEMBLY
(E)10x6 SA
(R) 16x12 WRR AND
DUCT BRANCH
(E)24x12 RA
(E)24x14 SA
(R) TRANSFER
ASSEMBLY
(E)16x8 SA
(E)18x12 SA
(E)22x12 SA
(E)16x8 SA
(R) 16x12 WRR AND
DUCT BRANCH
(E)14x12 SA
(E)14x12 SA
(E)24x14 SA
F/S
F/S
F/S
H
(E)16x8 SA
REMOVE CHILLED
BEAM FOR REINSTALLATION
BELOW RETURN
DUCT.
(E)12x6 SA
(E)24x12 RA
(E)16x8 SA
(E)14x12 RA
(E)16x8 SA
(E)14x10 RA
F/S
REMOVE DUCT AND
PIPING CONNECTION TO
CHILLED BEAM
F/S
1
REMOVE DUCT AND
PIPING CONNECTION TO
CHILLED BEAM
2
HVAC LEVEL 3 DEMOLITION PLAN
H201 1/4" = 1'-0"
HVAC LEVEL 4 DEMOLITION PLAN
H201 1/4" = 1'-0"
MEPFP ENGINEER
BRUCE E. BROOKS & ASSOC.
2209 Chestnut Street
Philadelphia, PA 19103
215.569.0400
T
(E) EA DN
(RL) TEMP/HUMIDITY
SENSOR. SEE NEW WORK
PLANS FOR NEW LOCATION
T
PI OFFICE
602W
(E) EA UP
(E)24x12 RA
(E)12x6 SA
(R) TRANSFER
ASSEMBLY
(R) 16x12 WRR AND
DUCT BRANCH
(E)24x14 SA
5
F/S
F/S
(E)20x18 EA
(E)5ø SA
(E)14x12 SA
HVAC LEVEL 6 DEMOLITION PLAN
H201 1/4" = 1'-0"
PREP EXISTING
DUCTWORK FOR NEW
CONNECTIONS
REMOVE DUCT AND
PIPING CONNECTION TO
CHILLED BEAM
(R) EXHAUST FAN
(R)6x6
(E)6x10 SA
(R) OPENENDED DUCT
3
C:\Users\sas\Documents\13-129 Richards Add'l
Scope_SAS.rvt
8/5/2016 12:36:12 PM
HVAC LEVEL 7 DEMOLITION PLAN
H201 1/4" = 1'-0"
3700 Hamilton Walk, Philadelphia, PA 19104
H201
Richards Medical Research
Laboratory - Additional Work
Towers C&D
REMOVE CHILLED
BEAM FOR REINSTALLATION
BELOW RETURN
DUCT.
6
University of Pennsylvania
Perelman School of Medicine
(E)10x14 SA
125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107
(E)16x8 SA
ATKIN OLSHIN SCHADE ARCHITECTS
(E)22x12 SA
H
(E)16x12 RA
T
(E)10x30 EA
(E)16x8 SA
HVAC LEVELS 3, 4, 6, 7,
& 8 DEMOLITION PLANS
4
HVAC LEVEL 8 DEMOLITION PLAN
H201 1/4" = 1'-0"
DATE
08.05.2016
6
G602W DEMO SECTION
H201 1/4" = 1'-0"
SCALE
1/4" = 1'-0"
DRAWN BY
AG
H201
REVISIONS
ISSUE DATE
DESCRIPTION
(E)6ø SA
(E)14x10 SA
16x6 WRR ABOVE
CEILING - BALANCE
TO 330 CFM
(E)6ø SA
H
T
T
R
PROVIDE ACOUSTIC LINING ON
THIS SECTION OF NEW
DUCTWORK - JOHNS MANVILLE
PERMACOTE LINACOUSTIC R300 OR EQUIVALENT
RA 16x6
1
8x8 RA BELOW PIPING - VERIFY
OPENING SIZE IN FIELD AND
PROVIDE LARGEST POSSIBLE
DUCT THROUGH (E) OPENING.
TRANSITION TO 8x16 IMMEDIATELY
AFTER OPENING
RA 8x16
WEG
120 CFM
(E)16x8 SA
H
T
R
WEG
120 CFM
EA 16x4
1
(RL) TEMP/HUMIDITY
SENSOR.
PENETRATE ELECTRICAL ROOM WALL WEST
OF EXISTING SPRINKLER PIPE. RELOCATED
CONDUIT AS REQUIRED. PROVIDE 1.5 HRRATED FIRE DAMPER AT WALL PENETRATION
REBALANCE (E)
WSR TO 225 CFM
(E)14x12 SA
F/S
EF
EA 10x6
(E) HW PUMPS
WRR 34X14
1350 CFM
RA 36x10
F/S
FD
VOLUME DAMPER
(E)16x14 RA
(E) B-TOWER HW
ISOLATION VALVES
(E)22x12 SA
(E)12x8 SA
(E)22x16 SA
EA 10x4
3/4" HWR
(E)16x8 RA
3/4" HWS
1
UP
2
HVAC LEVEL 1 NEW WORK PLAN
H300 1/4" = 1'-0"
WEG 12x8
240 CFM
ROUTE IN FIELD TO
COORDINATE WITH EXISTING
DUCTWORK AND PIPING
SHOWER ROOM EXHAUST
DUCTWORK UPSTREAM OF EF1 SHALL BE ALUMINUM
EA 12x12
REF.
CONNECT TO (E)
42x12 EA RISER
ABANDONED IN
PHASE 1
(E)16x12 RA
(E)20x10 SA
(E)16x8 SA
PROVIDE NEW A-TOWER
HW ISOLATION VALVE
(E) HWR RISER
TO A TOWER
(E)16x8 SA
RE-INSTALL CHILLED
BEAM AT LOWER
ELEVATION,
COORDINATED WITH
NEW RETURN DUCT
VOLUME DAMPER
RA 44x10
VOLUME DAMPER
RA 36x9
H
T
5ø
F/S
C:\Users\sas\Documents\13-129 Richards Add'l
Scope_SAS.rvt
8/5/2016 12:36:16 PM
F/S
(E)14x12 SA
RELOCATED 1/2" CHW BRANCH
TAPPED OFF TOP OF MAIN
RE-INSTALL CHILLED BEAM BRANCH
DUCT, PIPING, AND CONTROL,
BALANCING AND SHUT-OFF VALVES
HVAC LEVELS B, 1, & 2
NEW WORK PLANS
1
HVAC BASEMENT NEW WORK PLAN
H300 1/4" = 1'-0"
(E)26x12 SA
(E)12x6 SA
(RL) TEMP/HUMIDITY
SENSOR.
WRR 36X9
1350 CFM
(E)24x10 RA
REBALANCE (E)
WSR TO 225 CFM
University of Pennsylvania
Perelman School of Medicine
PROVIDE NEW A-TOWER
HW ISOLATION VALVE
125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107
(E) HWS RISER
TO A TOWER
ATKIN OLSHIN SCHADE ARCHITECTS
(E) EA DUCT CONTINUES TO FAN ON.
CONFIRM ROUTING AT THE START OF
CONSTRUCTION. REMOVE FAN WHEEL
AND INTERNAL COMPONENTS AND REUSE FAN HOUSING AS RAIN CAP.
3700 Hamilton Walk, Philadelphia, PA 19104
MEPFP ENGINEER
BRUCE E. BROOKS & ASSOC.
2209 Chestnut Street
Philadelphia, PA 19103
215.569.0400
RUN DUCT IN FRONT
OF EXISTING
SPRINKLER PIPE, IN
SOFFIT
EA 12x12
Richards Medical Research
Laboratory - Additional Work
Towers C&D
EA 12x12
3
HVAC LEVEL 2 NEW WORK PLAN
H300 1/4" = 1'-0"
DATE
08.05.2016
SCALE
1/4" = 1'-0"
DRAWN BY
AG
H300
REVISIONS
ISSUE DATE
DESCRIPTION
(E)16x8 SA
(E)16x8 SA
VOLUME DAMPER
(E)10x6 SA
H
T
REBALANCE (E)
WSR TO 225 CFM
WRR 34X14
1350 CFM
(RL) TEMP/HUMIDITY
SENSOR.
(RL) TEMP/HUMIDITY
SENSOR.
(E)24x14 SA
5ø
F/S
(E)14x12 SA
RA 36 X12
F/S
RE-INSTALL CHILLED BEAM BRANCH
DUCT, PIPING, AND CONTROL,
BALANCING AND SHUT-OFF VALVES
F/S
F/S
1
VOLUME DAMPER
RA 40x8
(E)14x12 SA
F/S
RE-INSTALL CHILLED BEAM BRANCH
DUCT, PIPING, AND CONTROL,
BALANCING AND SHUT-OFF VALVES
2
HVAC LEVEL 3 NEW WORK PLAN
H301 1/4" = 1'-0"
HVAC LEVEL 4 NEW WORK PLAN
H301 1/4" = 1'-0"
MEPFP ENGINEER
BRUCE E. BROOKS & ASSOC.
2209 Chestnut Street
Philadelphia, PA 19103
215.569.0400
REBALANCE (E)
WSR TO 225 CFM
VOLUME DAMPER
RA 28x18
5ø
T
(E)24x12 RA
H
VOLUME DAMPER
WRR 40x8
1350 CFM
RELOCATE CHW PIPING
ABOVE ELECTRICAL WIRE
TROUGH/SOLID CABLE
TRAY. RUN RA DUCT
BELOW WIRE TROUGH.
(E)24x12 RA
(E)12x6 SA
(E)16x8 SA
RE-INSTALL CHILLED BEAM AT
LOWER ELEVATION, COORDINATED
WITH NEW RETURN DUCT
(E)18x12 SA
(E)14x12 RA
RE-INSTALL CHILLED BEAM AT
LOWER ELEVATION, COORDINATED
WITH NEW RETURN DUCT
(E)24x14 SA
(E)16x8 SA
REF.
T
(E)16x8 SA
(E)22x12 SA
(E)14x10 RA
REF.
(E) EA DN
PI OFFICE
602W
5
REBALANCE (E)
WSR TO 225 CFM
T
VOLUME DAMPER
RA 40x10
2
WRR 40x10
1350 CFM
SA 5ø
(E)20x18 EA
CONNECT TO
EXISTING DUCTWORK
(E)14x12 SA
F/S
F/S
(E)24x14 SA
(RL) TEMP/HUMIDITY
SENSOR.
(E)24x12 RA
EF
HVAC LEVEL 6 NEW WORK PLAN
H301 1/4" = 1'-0"
RA 40x10
RE-INSTALL CHILLED BEAM BRANCH
DUCT, PIPING, AND CONTROL,
BALANCING AND SHUT-OFF VALVES
(N) CD
3
C:\Users\sas\Documents\13-129 Richards Add'l
Scope_SAS.rvt
8/5/2016 12:36:26 PM
HVAC LEVEL 7 NEW WORK PLAN
H301 1/4" = 1'-0"
3700 Hamilton Walk, Philadelphia, PA 19104
H
VOLUME DAMPER
Richards Medical Research
Laboratory - Additional Work
Towers C&D
(E)12x6 SA
(E) EA UP
University of Pennsylvania
Perelman School of Medicine
RE-INSTALL CHILLED BEAM AT
LOWER ELEVATION, COORDINATED
WITH NEW RETURN DUCT
H301
125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107
(E)16x12 RA
(E)22x12 SA
(E)10x14 SA
6
(N) CD
ATKIN OLSHIN SCHADE ARCHITECTS
(E)10x30 EA
(E)16x8 SA
HVAC LEVELS 3, 4, 7, &
8 NEW WORK PLANS
4
HVAC LEVEL 8 NEW WORK PLAN
H301 1/4" = 1'-0"
6
G602W NEW WORK SECTION
H301 1/4" = 1'-0"
DATE
08.05.2016
SCALE
1/4" = 1'-0"
DRAWN BY
AG
H301
REVISIONS
ISSUE DATE
DESCRIPTION
1
01 AUG 2014
ISSUE FOR BID
2
08 AUG 2014
ADDENDUM #3/ ISSUE FOR PERMITS
AIR DEVICE SCHEDULE
FACE/
SLOTS/
SPACING
BORDER
BASIS
WHITE BAKED
ENAMEL
35 FIXED DEGREE
BARS, VERTICAL BARS,
3/4" SPACING
1-1/4" BORDER WITH
CONCEALED SCREWS
PRICE 530
OPPOSED BLADE DAMPER. PLASTER FRAME FOR DRYWALL
INSTALLATIONS.
ALUMINUM
WHITE BAKED
ENAMEL
35 FIXED DEGREE
HORIZONTAL BARS
1-1/4" BORDER
PRICE 630
OPPOSED BLADE DAMPER. PLASTER FRAME WHERE REQ'D.
STEEL
WHITE BAKED
ENAMEL
ADJUSTABLE BLADES
SURFACE MOUNT
PRICE SMDA
DESIGNATION
MATERIAL
WRR
STEEL
CEG
CD
FINISH
REMARKS
9"x6" WITH OPPOSED BLADE DAMPER AND ADJUSTABLE BLADES.
NOTES:
1. REFER TO FLOOR PLANS FOR BALANCING CFM.
2. ARCHITECT TO SELECT COLOR
EXHAUST FAN SCHEDULE
SYMBOL
TAG
NO.
EF
1
EF
2
SERVICE
BASEMENT SHOWER ROOMS
C TOWER CORE BATHROOMS
LOCATION
BASEMENT MECH ROOM
LEVEL 8 MECH ROOM
CFM
720
4120
ESP (IN
WC)
0.5
1
RPM
1209
1328
HP
1/4
1-1/2
SONES
6.1
19.7
V/PH/HZ
120/1/60
460/3/60
FLA
1
3
BASIS MANUFACTURER
NAME
MODEL NO
GREENHECK SQ-100-VG
GREENHECK
SWB-118
NOTES:
1. EF-2 SHALL BE PROVIDED WITH A VFD FOR BALANCING.
2. EF-1 AND EF-2 SHALL TIE INTO THE EXISTING BAS.
RADIATOR SCHEDULE
DEPTH
2"
HEIGHT
8-5/8"
EWT
180
RUNOUT
SIZES
3/4"
BASIS OF DESIGN
RUNTAL RF-3
1. ALL DIMENSIONS ARE NET FREE AREA. WHERE
ACOUSTIC LINER IS USED, INCREASE SHEET
METAL DIMENSIONS TO ALLOW FOR
INSTALLATION OF LINER.
VAPOR SEAL BUTT JOINT
PLAN VIEW - CLAMP INSTALLATION
AIR FLOW
*
CONCRETE STRUCTURE
MAIN SUPPLY
AIR DUCT
HANGER ROD
45°
VIBRATION ISOLATOR
(WHERE APPLICABLE. REFER
TO SPECIFICATIONS)
5 DUCT
DIAMETERS
LOCK NUT
EXPANSION SHIELD
STANDARD ADJUSTABLE
CLEVIS
SUPPORT NUT
BRANCH DUCT
VOLUME DAMPER
(WHERE REQUIRED)
SEE FLOOR PLAN
FOR PIPE SIZE
PRE INSULATED
CLAMP INSERT
C:\Users\sas\Documents\13-129 Richards Add'l
Scope_SAS.rvt
8/5/2016 12:36:27 PM
* EQUALS 1/4 WIDTH OF BRANCH DUCT MINIMUM 4".
SINGLE PIPE HANGER SECTION VIEW
1
H - DUCT - RECTANGULAR DUCT TAKE-OFF DETAIL
H800 N.T.S.
2. LEADING EDGE OF ACOUSTIC DUCT LINER
SHALL BE PROTECTED WITH A SHEET METAL
NOSING, MINIMUM 3/4" LONG.
3. ALL DUCTWORK SHALL BE CONSTRUCTED
WITH A "SMOOTH" EXTERIOR APPEARANCE.
OBTAIN APPROVAL FROM OWNER FOR
PROPOSED DUCT CONSTRUCTION, JOINTS AND
JOINING METHODS.
4. PREPARE SURFACES OF DUCTWORK FOR
PAINTING. REMOVE ALL STICKERS, OIL, AND
OTHER RESIDUE.
University of Pennsylvania
Perelman School of Medicine
DUCTWORK CONSTRUCTION NOTES:
125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107
PRE-INSULATED RIGID
CLAMP INSERT WITH
VAPOR BARRIER
(KLO-SHURE OR EQUAL)
ATKIN OLSHIN SCHADE ARCHITECTS
UNISTRUT STRAP AND
LOCKING NUT
HVAC SCHEDULES AND
DETAILS
5
PIPE HANGER DETAIL
H800 N.T.S.
3700 Hamilton Walk, Philadelphia, PA 19104
BTUH/LF
699
WATER
LWT
EAT
GPM
160
65
SEE RISER
MEPFP ENGINEER
BRUCE E. BROOKS & ASSOC.
2209 Chestnut Street
Philadelphia, PA 19103
215.569.0400
TUBE MATERIAL
STEEL
ELEMENT
LENGTH
2 FT
Richards Medical Research
Laboratory - Additional Work
Towers C&D
ENCLOSURE
STYLE
EXPOSED
STRUCTURAL ENGINEER
KEAST & HOOD CO.
400 Market Street Suite 1250
Philadelphia, PA 19106
215.625.0099
SYMBOL
TAG
NO.
R
1
DATE
08.05.2016
SCALE
As indicated
DRAWN BY
AG
H800
REVISIONS
ISSUE DATE
DESCRIPTION
PLUMBING LEGEND
ABBREVIATIONS
EXISTING TO REMAIN
PIPE GUIDE
TRAP
EXISTING VENT TO REMAIN
CAP
FUNNEL DRAIN AND/OR FLOOR SINK
EXISTING TO BE REMOVED
BALL-TYPE SHUTOFF VALVE
EXISTING VENT TO BE REMOVED
BUTTERFLY VALVE
NEW WORK
GATE VALVE
G
NATURAL GAS CONNECTION
REDUCER
XX
XX
PLUMBING FIXTURE TAG
FIXTURE TYPE
FIXTURE NUMBER
NEW VENT PIPE
DRAIN VALVE
X
XX
SANITARY/VENT RISER LOCATION
RISER TYPE
RISER NUMBER
DIAMETER
BALANCING VALVE
X
XX
PRESSURE RELIEF VALVE
CUT AND CAP
CHECK VALVE
EXISTING TO REMAIN
EXISTING TO BE REMOVED
NATURAL GAS COCK
(RL)
EXISTING TO BE RELOCATED
VERTICAL VALVE
METER
SHOCK ABSORBER W/ ACCESS PANEL
GAS METER
ANTI-SIPHONAGE VACUUM BREAKER
GAS PRESSURE REGULATOR
THERMOMETER
PIPE UP
PRESSURE GAGE W/ BALL VALVE
PIPE DOWN
HOSE BIBB
PIPE DROP
WALL CLEAN OUT
UNION
FLOOR DRAIN/TRAP
PLUMBING/ FIRE PROTECTION DRAWING SCHEDULE
SHEET NUMBER
PF000
PF300
C:\Users\sas\Documents\13-129 Richards Add'l
Scope_SAS.rvt
8/5/2016 12:36:27 PM
PF800
SHEET NAME
PLUMBING/FIRE PROTECTION COVER SHEET
PLUMBING/FIRE PROTECTION BASEMENT DEMOLITION AND
NEW WORK PLANS
PLUMBING/FIRE PROTECTION SCHEDULES AND DETAILS
100% CONSTRUCTION
DOCUMENTS 07/15/16
●
●
●
3700 Hamilton Walk, Philadelphia, PA 19104
PIPE ANCHOR
Richards Medical Research
Laboratory - Additional Work
Towers C&D
MEPFP ENGINEER
BRUCE E. BROOKS & ASSOC.
2209 Chestnut Street
Philadelphia, PA 19103
215.569.0400
(R)
R
RISER NUMBER
REDUCED PRESSURE BACKFLOW PREVENTION
BFP
M
RISER TYPE
University of Pennsylvania
Perelman School of Medicine
(E)
CONNECT NEW TO EXISTING
DOMESTIC WATER RISER LOCATION
125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107
ABOVE
AREA DRAIN
ACCESS PANEL
BATH TUB
CUBIC FEET PER HOUR
CEILING
CLEAN OUT
CONTINUED
CLEAN OUT TO GRADE
DOMESTIC COLD WATER
DRAINAGE FIXTURE UNITS
DOMESTIC HOT WATER
DOMESTIC HOT WATER RETURN
DOWN
DIONIZED
DISHWASHER
EXISTING TO REMAIN
EACH
ELECTRICAL CONTRACTOR
EMERGENCY SHOWER
EMERGENCY EYEWASH
ELECTRIC WATER COOLER
ELECTRIC WATER HEATER
ELEVATION
EXISTING
FRESH AIR INLET
FORCED CONDENSATE
FLOOR CLEAN OUT
FLOOR DRAIN
FIRE PROTECTION PIPING
SPRINKLER/FIRE PROTECTION CONTRACTOR
FLOOR SINK
FOOT/FEET
GAS
GRAVITY CONDENSATE
GENERAL CONTRACTOR
GAS WATER HEATER
HORSE POWER
DOMESTIC HOT WATER RECIRCULATION/HOUR
WALL HYDRANT
INDIRECT WASTE
INVERT
JANITOR SINK
LAVATORY
LAUNDRY TUB
MAXIMUM
MECHANICAL CONTRACTOR
MAN HOLE
MINIMUM
MOP RECEPTOR
MIXING VALVE(THERMOSTATIC)
NEW WORK
NOT APPLICABLE
NORMALLY CLOSED
NOT IN CONTRACT
NORMALLY OPEN
NOT TO SCALE
PUMP
PLUMBING CONTRACTOR
PRESSURE REDUCING VALVE
POUNDS PER SQUARE INCH
EXISTING TO BE REMOVED
ROOF DRAIN
EXISTING TO BE RELOCATED
REVOLUTIONS PER MINUTE
REDUCED PRESSURE BACKFLOW PREVENTER
RAIN WATER CONDUCTOR
SLOPE
SINK / SOUTH
SHOCK ABSORBER W/ ACCESS PANEL
SANITARY
SEWAGE EJECTOR
SUPPLY FIXTURE UNITS
SHOWER
SUMP PUMP
SOIL STACK
STORM DRAINAGE PIPING
STACK VENT
SAFEWASTE
TUB
TRAP PRIMER
TYPICAL
URINAL
UNLESS NOTED OTHERWISE
VENT PIPING
VACUUM BREAKER
VARIABLE FREQUENCY DRIVE
VERIFY IN FIELD
VENT THRU ROOF
WASTE RISER
WASHER BOX
WATER CLOSET
WALL CLEAN OUT
WATER FOUNTAIN
ATKIN OLSHIN SCHADE ARCHITECTS
ABV
AD
AP
BT
CFH
CLG
CO
CONT
COTG
DCW
DFU
DHW
DHWR
DN
DI
DW
(E)
EA
EC
ES
EW
EWC
EWH
ELEV
EX
FAI
FC
FCO
FD
FP
FPC
FS
FT
G
GC
GC
GWH
HP
HR
HY
IW
INV
JS
L
LT
MAX
MC
MH
MIN
MR
MV
(N)
N/A
NC
NIC
NO
NTS
P
PC
PRV
PSI
(R)
RD
(RL)
RPM
RPZ
RWC
s=02'
S
SA
SAN
SE
SFU
SH
SP
SS
ST
SV
SW
T
TP
TYP
U
U.N.O.
V
VB
VFD
VIF
VTR
W
WB
WC
WCO
WF
SYMBOLS
PLUMBING/FIRE
PROTECTION COVER
SHEET
DATE
08.05.2016
SCALE
1/8" = 1'-0"
DRAWN BY
AG
PF000
REVISIONS
ISSUE DATE
DESCRIPTION
(E) 4" V UP
CONNECT NEW 2"
V TO (E) 4" RISER
1" DHWR
2" DHW
3" DCW
(E) 4" GAS
1/2" DCW
1/2" DHW
1/2" DHW DN TO SH-1
1/2" DCW DN TO SH-1
(E) CLEAN-OUT
TO REMAIN
SH
(E) 6" SAN
2
L
1
FD
1
(E) 6" SAN
TP
1
SH
1/2" DCW
1/2" DHW
2
WC
L
2" SAN
1
1
(E
)4
"S
AN
1-1/2" DCW
(E) 1-1/2" DHWR
(E) 3" DCW
(E) 2" DHW
(E) 2" A
(E) 2" VAC
(E) 6" G
FD
1
(R) 6" SAN
1 1/2" SAN
FD
3" SAN
1
L
DEMO 6" SANITARY MAIN
BETWEEN NEW
PLUMBING FIXTURES.
1
WC
1
TP
1
SH
1/2" DCW
WCO
1
1/2" DHW
FD
1/2" DCW
1/2" DHW
1
WC
(E) BELOW SLAB SANITARY PIPING TO BE
REPLACED. PIPING CONTINUES TO
SEWAGE EJECTOR PUMP IN MECH ROOM.
L
1
1
3" SAN
1-1/2" DCW
2" SAN
1 1/2" SAN
UP
SH
1
3
WC
MEPFP ENGINEER
BRUCE E. BROOKS & ASSOC.
2209 Chestnut Street
Philadelphia, PA 19103
215.569.0400
PLUMBING BASEMENT NEW WORK PLAN - DOMESTIC
PF300 1/4" = 1'-0"
1
UP
WCO
(E) 6" SAN
1
PLUMBING BASEMENT DEMOLITION PLAN - SANITARY
PF300 1/4" = 1'-0"
2
PLUMBING BASEMENT NEW WORK PLAN - SANITARY
PF300 1/4" = 1'-0"
University of Pennsylvania
Perelman School of Medicine
125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107
PROVIDE LIGHT HAZARD
COVERAGE PER NFPA-13.
ATKIN OLSHIN SCHADE ARCHITECTS
NOTE:
1. REMOVE EXISTING SPRINKLERS AND BRANCH LINES AS REQUIRED TO FACILITATE INSTALLATION OF NEW WORK. REUSE MAINS.
3700 Hamilton Walk, Philadelphia, PA 19104
2" V
Richards Medical Research
Laboratory - Additional Work
Towers C&D
(E) 6" SAN
C:\Users\sas\Documents\13-129 Richards Add'l
Scope_SAS.rvt
8/5/2016 12:36:35 PM
UP
4
FIRE PROTECTION BASEMENT NEW WORK PLAN
PF300 1/4" = 1'-0"
PLUMBING/FIRE
PROTECTION
BASEMENT
DATE
DEMOLITION AND NEW
08.05.2016
WORK PLANS
SCALE
1/4" = 1'-0"
DRAWN BY
AG
PF300
REVISIONS
ISSUE DATE
DESCRIPTION
PLUMBING FIXTURE SCHEDULE
FIXTURE
TAG
WC-1
FLOOR-MOUNTED
ELONGATED
WATER CLOSET
AUTO FLUSH
LAVATORY
SENSOR
OPERATED
L-1
SHOWER (NON-ADA)
SH-1
SH-2
SHOWER (ADA-ROLL IN
TYPE)
BASIS OF DESIGN
MANUFACTURER AND
MODEL
APPLICABLE
STANDARD
AMERICAN
STANDARD
"FLOWISE"
(3641.001)
ASME
A112.19.2M
ADA
SIZE CONNECTION
MOUNTING AND
OUTLET
MATERIAL
VITREOUS CHINA
DIMENSIONS
FAUCETS, FITTINGS AND ACCESSORIES
RIM HEIGHT
TRAP
FLOOR-MOUNTED
15"
ADA 17"-19"
28-1/4"x17"x17-1/8"
CW
4"
1-1/2"
-
ASME
A112.19.2M
DURAVIT
"VERO"
FAUCET
ASME
A112.18.1M
CENTER FAUCET
(045460..00)
ANSI 117.1
ANSI Z 124.2
ASSE 1016
ASTM F 445
AQUARIUS MODEL
STN 3679 SH 3P
ANSI 117.1
ANSI Z 124.2
ASSE 1016
ASTM F 445
AQUARIUS MODEL
S6430BF
VITREOUS CHINA
23-5/8"x18-1/2"
WALL MOUNTED
THERMOFORMED FROM
CONTINUOUS CAST
ACRYLIC SHEET INTO
ONE PIECE,
SEAMLESS UNIT
THERMOFORMED FROM
CONTINUOUS CAST
ACRYLIC SHEET INTO
ONE PIECE,
SEAMLESS UNIT
32"
ADA 34"
FLOOR
MOUNTED
-
36"x36"x77.75"
FLOOR
MOUNTED
-
60"x30"x84"
1-1/4"
1/2"
-
-
-
-
BASIS
HW
1/2"
-
-
1. AUTO FLUSH VALVE: "SLOAN ROYAL" (TOP SPUD) MODEL 111-1.28.SMO, BATTERY
POWERED, WITH OVER-RIDE BUTTON.
2. SEATS: "OLSONITE" , "BEMIS" OR "CHURCH" OPEN FRONT,
LESS COVER, COMMERCIAL GRADE W/CHECK HINGE.
3. TRAP PRIMER: CONNECTION AS REQUIRED.
4. SUPPLY: CHROME PLATED BRASS, 1-1/2"TOP INLET SPUD.
DESIGN CONSUMPTION: 1.28 GPF
PRESSURE RANGE 30 PSI, FLUSHING-80 PSI
STATIC DIRECT-FED SIPHON JET FLUSH
ACTION.
COLOR: WHITE
BOLT CAPS
1. SENSOR OPERATED FAUCET: CHICAGO FAUCETS MODEL 116.850.AB.1
2. TERMOSTATIC MIXING VALVE (LEAD-FREE): WATTS MODEL LFUSG-B
3. DRAIN:
GRID TYPE, POLISHED CHROME, VANDAL RESISTANT.
4. TRAP TYPE: "MCGUIRE" P-TRAP CHROME PLATED CAST BRASS BODY
WITH CLEANOUT AND 17" GAUGE TUBULAR WALL BEND.
5. SUPPLY:
"MCGUIRE" MODEL 2165CC 1/2"x3/8" COMPRESSION TEE
6. CARRIER: J.R. SMITH WALL MOUNTED CONCEALED ARM SUPPORT
7. UNDER-SINK PIPING COVERS: LAVGUARD2 OR EQUAL
FRONT OVERFLOW
BACK AND SIDE SPLASH SHIELDS
0.5 GPM FLOW RATE
COLOR: WHITE
CONTROL: LOW TEMPERATURE THERMOSTATIC SHOWER VALVE WITH ROUGH BRASS BODY,
LEVER HANDLE, SCREWDRIVER SWEAT END CHECK STOPS, "POWERS" E 425
SHOWER HEAD: FLEXIBLE STAINLESS STEEL HOSE WITH IN-LINE VACUUM BREAKER, WITH
ADJUSTABLE SPRAY SWIVEL JOINT, 60"LONG FLEXIBLE HOSE, 24" SLIDE BAR WITH ADJUSTABLE
SHOWER MOUNT, "POWERS" NO. 141-918
DRAIN: 2" CAST BRASS CHROME PLATED SHOWER DRAIN
CURTAIN ROD: 1" DIAMETER STAINLESS STEEL
SHOWER RIGHT -OR LEFT HAND AS REQUIRED WITH SEAT
AND SHELF WITH SOAP DISH, WITH RECESSED ROUND
SHOWER LIGHT. SHOWER SHALL BE REINFORCED IN THE
BACK WITH FIBERGLASS POLYESTER RESIN WHICH HAS
BEEN TREATED WITH FLAME RETARDANT ADDITIVE.
SHOWER SHALL BE PREDRILLED FOR ANY FIELD
INSTALLATION REQUIREMENTS, UNIT SHALL HAVE
ANTISKID FLOOR TREATMENT
CONTROL: LOW TEMPERATURE THERMOSTATIC SHOWER VALVE WITH ROUGH BRASS BODY,
LEVER HANDLE, SCREWDRIVER SWEAT END CHECK STOPS, "POWERS" E 425
SHOWER HEAD: FLEXIBLE STAINLESS STEEL HOSE WITH IN-LINE VACUUM BREAKER, WITH
ADJUSTABLE SPRAY SWIVEL JOINT, 60"LONG FLEXIBLE HOSE, 24" SLIDE BAR WITH ADJUSTABLE
SHOWER MOUNT, "POWERS" NO. 141-918
GRAB BAR: 1-1/4" TO 1-1/2" O.D. STAINLESS STEEL
DRAIN: 2" CAST BRASS CHROME PLATED SHOWER DRAIN
CURTAIN ROD: 1" DIAMETER STAINLESS STEEL
NO THRESHOLD
SHOWER RIGHT -OR LEFT HAND AS REQUIRED WITH SEAT
AND SHELF WITH SOAP DISH, WITH RECESSED ROUND
SHOWER LIGHT. SHOWER SHALL BE REINFORCED IN THE
BACK WITH FIBERGLASS POLYESTER RESIN WHICH HAS
BEEN TREATED WITH FLAME RETARDANT ADDITIVE.
SHOWER SHALL BE PREDRILLED FOR ANY FIELD
INSTALLATION REQUIREMENTS, UNIT SHALL HAVE ANTISKID
FLOOR TREATMENT
MIXED HW
OUTLET
THERMOMETER
FINISHED FLOOR
TAMPER RESISTANT
TEMPERATURE CONTROL
STRAINER HEAD
WATERPROOFING
MEMBRANE
(WHERE PROVIDED
FOR BY
ARCHITECT)
UNION
LIQUID FILLED THERMOSTATIC
MIXING VALVE (FULL LINE SIZE)
VIBRATION ISOLATOR
(WHERE APPLICABLE,
REFER TO SPECIFICATIONS)
FLASHING COLLAR
SEEPAGE OPENINGS
HANGER ROD
UNISTRUT STRAP AND
LOCKING NUT
PRE-INSULATED RIGID
CLAMP INSERT WITH
VAPOR BARRIER
(KLO-SHURE OR EQUAL)
LOCK NUT
EXPANSION SHIELD
SUPPORT NUT
STANDARD ADJUSTABLE
CLEVIS HANGER PER
SPECIFICATIONS
THERMOMETER
STRAINER
HW
INLET
SHUT OFF
CW
INLET
PRE INSULATED
CLAMP INSERT
SEE FLOOR PLAN
FOR PIPE SIZE
VAPOR SEAL BUTT JOINT
FLOOR SLAB
MEPFP ENGINEER
BRUCE E. BROOKS & ASSOC.
2209 Chestnut Street
Philadelphia, PA 19103
215.569.0400
BALL
VALVE
CONCRETE STRUCTURE ABOVE.
SEE ARCH DWGS
DRAIN
BODY
PLAN VIEW - CLAMP INSTALLATION
OUTLET
CONNECTION
PIPE HANGER DETAIL
PF800 1" = 1'-0"
CONNECT DOMESTIC COLD WATER, DOMESTIC HOT
WATER, AND DOMESTIC HOT WATER RETURN LINES TO
EXISTING MAINS AT MECHANICAL ROOM WALL
2" V
LAVATORY
1/2" DCW
1/2" DCW
1/2" DHW
1/2" DHW
1/2" DCW
1/2" DHW
1/2" DCW
1-1/2" DCW
1/2" DHW
CONNECT NEW 2" V
TO (E) 4" V RISER
1-1/2" DCW
1" DHWR
2" DHW
WC
L
WC
L
1
1
1
1
3" DCW
4" SAN
DOWN IN WALL
WCO
FLOOR DRAIN
C:\Users\sas\Documents\13-129 Richards Add'l
Scope_SAS.rvt
8/5/2016 12:36:37 PM
FLOOR
1/2" TYPE "L"
COPPER PRIMER,
SAFEWASTE TO TRAP
SH
L
WC
L
SH
WC
SH
FD
1
1
1
1
1
1
1
1
TP
TP
1
1
FD
FD
1
1
(E) 4" SAN, 60 DFU'S,
TO EXISTING
SEWAGE EJECTOR
IN MECH ROOM
2" SAN
3" SAN
BASEMENT
DEEP SEAL TRAP
6
5
P-TRAP PRIMER LAV
PF800 12" = 1'-0"
BASEMENT DOMESTIC PLUMBING SCHEMATIC
PF800 N.T.S.
7
WCO
4"
SAN
BASEMENT SANITARY PLUMBING RISER DIAGRAM
PF800 N.T.S.
FD
SH
1
2
BASEMENT
3" SAN
1-1/2" SAN
2" SAN
(E) 6" SAN
3700 Hamilton Walk, Philadelphia, PA 19104
4
Richards Medical Research
Laboratory - Additional Work
Towers C&D
FLOOR DRAIN DETAIL
PF800 12" = 1'-0"
University of Pennsylvania
Perelman School of Medicine
3
P-MIXING VALVE
PF800 12" = 1'-0"
125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107
2
ATKIN OLSHIN SCHADE ARCHITECTS
SINGLE PIPE HANGER SECTION VIEW
PLUMBING/FIRE
PROTECTION
SCHEDULES AND
DATE
DETAILS
08.05.2016
SCALE
As indicated
DRAWN BY
AG
PF800
REVISIONS
ISSUE DATE
ABBREVIATIONS
ELECTRICAL SYMBOL LIST
POWER
EWC
ELECTRIC WATER COOLER - MOUNT RECEPTACLE WITHIN COOLER ENCLOSURE.
LIGHTING (NOTE: UPPER CASE LETTER INDICATES TYPE,
LOWER CASE LETTER INDICATES SWITCHING ARRANGEMENT)
C2
c
A2
c
LINEAR STRIP FIXTURE
DUPLEX RECEPTACLE
M1
B1
d
d
DOWNLIGHT
f
WALL BRACKET FIXTURE
QUADRAPLEX RECEPTACLE
F
F
DUPLEX GROUND FAULT RECEPTACLE
DUPLEX GROUND FAULT RECEPTACLE - MOUNTED ABOVE COUNTER HEIGHT,
BACKSPLASH, OR AS INDICATED ON DRAWINGS
DUPLEX RECEPTACLE - MOUNTED ABOVE COUNTER HEIGHT, BACKSPLASH,
OR AS INDICATED ON DRAWINGS
EM
X
F
X
B
EMERGENCY BATTERY PACK
X
EXIT SIGN
A
LIGHTING FIXTURE ON EMERGENCY
SINGLE RECEPTACLE - SPECIAL PURPOSE (AS NOTED ON DRAWINGS)
SWITCHING
FLOOR MOUNTED DUPLEX RECEPTACLE
FLOOR MOUNTED QUADRAPLEX RECEPTACLE
AV
S
S3
COMBINATION POWER, DATA & AV FLOOR BOX
CEILING MOUNTED DUPLEX RECEPTACLE
SURFACE MOUNTED MULTI OUTLET RACEWAY ASSEMBLY
J
J
J
PB
SINGLE POLE SWITCH
S4
THREE WAY AND FOUR WAY SWITCHES
SD
SINGLE POLE DIMMING SWITCH
SOS
WALL MOUNTED OCCUPANCY SENSOR WITH OVERRIDE SWITCH
SVS
WALL MOUNTED VACANCY SENSOR WITH OVERRIDE SWITCH
JUNCTION BOX (FLOOR, CEILING, WALL)
OS
OS
OCCUPANCY SENSOR (CEILING, WALL)
PULL BOX
VS
VS
VACANCY SENSOR (CEILING, WALL)
DS
DS
VACANCY SENSOR (CEILING, WALL)
MOTOR
T
TRANSFORMER
GROUND ROD
SYSTEMS FURNITURE P = POWER, D = DATA
J J
P D
CIRCUIT PROTECTION
SM
FLOOR MOUNTED JUNCTION BOX CONNECTION POINTS, JUNCTION BOXES PROVIDED
BY ELECTRICAL CONTRACTOR
MANUAL MOTOR STARTER
DESCRIPTION
1P
2P
3P
4P
A
AB
AC
AFCI
AFF
AIC
AFG
ARCH
ATS
BLDG
C
CATV
CB
CD
CKT
CMT
C.T.
DISC
DO
DWG
(E)
EC
(ER)
EWC
FA
FAAP
FACP
FLA
GC
GFCI
GND
HP
HV
Hz
IG
JB
KCMIL
KVA
KW
ONE POLE
TWO POLE
THREE POLE
FOUR POLE
AMPERE
ABOVE CEILING
ABOVE COUNTER
ARC FAULT CURRENT INTERRUPTER
ABOVE FINISHED FLOOR
AMPS INTERRUPTING CURRENT
ABOVE FINISHED GRADE
ARCHITECT
AUTOMATIC TRANSFER SWITCH
BUILDING
CONDUIT
CABLE TELEVISION
CIRCUIT BREAKER
CANDELA
CIRCUIT
EMPTY CONDUIT
CURRENT TRANSFORMER
DISCONNECT
DISCONNECT
DRAWING
EXISTING TO REMAIN
ELECTRICAL CONTRACTOR
EXISTING TO BE RELOCATED
ELECTRIC WATER COOLER
FIRE ALARM
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM CONTROL PANEL
FULL LOAD AMPS
GENERAL CONTRACTOR
GROUND FAULT CIRCUIT INTERRUPTER
GROUNDED
HORSEPOWER
HIGH VOLTAGE
HERTZ (CYCLE) PER SECOND
ISOLATED GROUND
JUNCTION BOX
THOUSAND CIRCULAR MILS
KILOVOLT AMPERE
KILOWATT
DISCONNECT SWITCH, UNFUSED TYPE
LP
LTG
MCB
NDO
(ME)
MISC
MLO
MOA
MOD
MTD
MTG
MTS
(N)
N/A
NEC
NIC
NL
#
NTS
P
PB
PH
PNL
PVC
PWR
(R)
(RE)
REC
SCP
SWBD
SYS
TC
TEL/DATA
TEL
TTB
TVSS
TYP
UON
V
W
WP
XFMR
+
#1/E300
LIGHTING PANEL
LIGHTING
MAIN CIRCUIT BREAKER
MAIN DISTRIBUTION PANEL
MODIFY EXISITNG
MISCELLANEOUS
MAIN LUGS ONLY
MULTI-OUTLET ASSEMBLY
MOTOR OPERATED DISCONNECT SWITCH
MOUNTED
MOUNTING
MANUAL TRANSFER SWITCH
NEW
NOT APPLICABLE
NATIONAL ELECTRICAL CODE
NOT IN CONTRACT
NIGHT LIGHT
NUMBER
NOT TO SCALE
POLE
PULL BOX
PHASE
PANEL
POLYVINYL CHLORIDE CONDUIT
POWER
REMOVE EXISTING
RELOCATE EXISTING
RECESSED
SECURITY CONTROL PANEL
SWITCHBOARD
CONNECTION TO SYSTEMS FURNITURE
TIME CLOCK
TELEPHONE/DATA
TELEPHONE
TELEPHONE TERMINAL BOARD
TRANSIENT VOLTAGE SURGE SUPPRESSION
TYPICAL
UNLESS OTHERWISE NOTED
VOLT
WATT
WEATHERPROOF
TRANSFORMER
INDICATES MOUNTED ABOVE CENTER
OR AS NOTED ON DWG.
DETAIL NUMBER/DRAWING NUMBER
DISCONNECT SWITCH, FUSED TYPE
DATA # = NUMBER OF DROPS
#
DATA COMMUNICATION OUTLET
PANELBOARDS
#
FLOOR MOUNTED COMBINATION DATA OUTLET
SURFACE MOUNTED ELECTRICAL PANELBOARD
RECESSED MOUNTED ELECTRICAL PANELBOARD
AUDIO VISUAL
SECURITY SYSTEM
FIRE ALARM
BLACK KEY ACCESS
DC
DOOR STRIKE
FIRE ALARM STROBE LIGHT
CR
CARD ACCESS READER
DUCT MOUNTED SMOKE DETECTOR
PB
PANIC BUTTON FOR ADA BATHROOMS
FIRE ALARM MANUAL PULL STATION
F
FIRE ALARM STROBE LIGHT & HORN COMBINATION
F
D
C:\Users\prd\Documents\13-129 Richards Add'l
Scope_prd.rvt
8/5/2016 12:37:29 PM
BK
F
FACP
FIRE ALARM CONTROL PANEL
FAAP
FIRE ALARM ANNUNCIATOR PANEL
NAC
NOTIFICATION APPLIANCE CIRCUIT EXTENDER PANEL
FMM
FIRE ALARM MONITOR MODULE
FRM
FIRE ALARM RELAY MODULE
FS
SPRINKLER FLOW SWITCH
TS
SPRINKLER TAMPER SWITCH
SD
SMOKE DAMPER
PTD
POWER TRANSFER DEVICE
ELECTRICAL DRAWING SCHEDULE
SHEET NUMBER
E000
E400
E401
E402
E700
SHEET NAME
ELECTRICAL COVER SHEET
ELECTRICAL BASEMENT PLANS
ELECTRICAL LEVEL 1 NEW WORK PLAN - POWER
ELECTRICAL LEVEL 7, 8 NEW WORK PLAN - POWER
ELECTRICAL SCHEDULES
100% CONSTRUCTION
DOCUMENTS
07/15/2016
●
●
●
●
●
NOT IN CONTRACT
ELECTRICAL COVER
SHEET
DATE
08.05.2016
SCALE
12" = 1'-0"
DRAWN BY
PRD
E000
3700 Hamilton Walk, Philadelphia, PA 19104
CEILING MOUNTED AV BOX
MEPFP ENGINEER
BRUCE E. BROOKS & ASSOC.
2209 Chestnut Street
Philadelphia, PA 19103
215.569.0400
AV
DISTRIBUTION PANEL
Richards Medical Research
Laboratory - Additional Work
Towers C&D
WALL MOUNTED AV BOX
University of Pennsylvania
Perelman School of Medicine
AV
SYSTEMS PANEL OR TERMINAL CABINET (AS INDICATED ON DRAWING)
125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107
AV FLOOR BOX
ATKIN OLSHIN SCHADE ARCHITECTS
AV
REVISIONS
GENERAL NOTES:
ISSUE DATE
1.
ALL EQUIPMENT & DEVICES ARE NEW UNLESS OTHERWISE NOTED.
2.
ALL EQUIPMENT & DEVICES SHALL BE CIRCUITED TO PANEL CBRP SEC. 2 UNLESS OTHERWISE NOTED.
3.
REFER TO ELECTRICAL CONNECTION SCHEDULE ON DRAWING E700 FOR CIRCUITING OF MECHANICAL EQUIPMENT.
4.
COORDINATE ALL ROUTING OF NEW BRANCH CIRCUITS WITH ARCHITECT PRIOR TO ROUGH-IN.
DESCRIPTION
D-4
(E)SECURITY/
ACCESS PANEL
(E)PANEL CBRP-SEC. 1
(E)PANEL CBRP-SEC. 2
(E)PANEL CBLP
F
ACCESSIBLE GENDER
NEUTRAL RESTROOM
(15)
CONNECT TO EXISTING
FIRE ALARM NOTIFICATION
LOOP IN ADJACENT
CORRIDOR.
(TYPICAL FOR 2)
1
C003B
D-5
PB
C003B
VESTIBULE
C003
(E)
F F
C003
C003A
GENDER NEUTRAL
RESTROOM
DEMOLISH ALL EXISTING
LIGHTING FIXTURES,
WIRING DEVICES &
ASSOCIATED IN THIS AREA
BACK TO SOURCE.
REFER TO DETAIL 1/E400
AND 3/E400 FOR POWER
AND LIGHTING PLAN IN
THIS AREA
1
C003A
F (15)
PB
1
MEPFP ENGINEER
BRUCE E. BROOKS & ASSOC.
2209 Chestnut Street
Philadelphia, PA 19103
215.569.0400
ELECTRICAL BASEMENT BATHROOM NEW WORK PLAN - POWER & SYSTEMS
E400 1/4" = 1'-0"
FOR ALL NEW NORMAL
LIGHTING FIXTURES:
EXTEND EXISTING NORMAL
LIGHTING BRANCH CIRCUIT IN
CORRIDOR FROM PANEL
CBLP, CIRCUIT 2 TO NEW
NORMAL LIGHTING FIXTURES
IN BATHROOMS & VESTIBULE.
a
F1
a
b os
SS
F1 a
CONDUIT ROUTING FROM 1ST
FLOOR DOOR/BOLLARDS. TO
ELECTRICAL ROOM.
A-4
(E)
(E)DISCONNECT SWITCH.
CONDUIT PENETRATING
WALL TO BE
RELOCATED/RAISED DUE
TO NEW MECHANICAL
DUCT PENETRATION.
COORDINATE WORK
WITH MECHANICAL
CONTRACTOR.
os
F1
FOR NEW EMERGENCY
LIGHTING FIXTURE:
EXTEND EXISTING
EMERGENCY LIGHTING
BRANCH CIRCUIT IN
ADJACENT CORRIDOR FROM
PANEL ELB, CIRCUIT 1 TO
NEW EMERGENCY LIGHTING
FIXTURE IN VESTIBULE.
EM/NL
SS
UP(E)480/277V, 3-PHASE PANEL
F1 a
b os
a
A-1
b
F1 a
3
ELECTRICAL BASEMENT BATHROOM NEW WORK PLAN - LIGHTING
E400 1/4" = 1'-0"
C:\Users\prd\Documents\13-129 Richards Add'l
Scope_prd.rvt
8/5/2016 12:37:33 PM
2
ELECTRICAL BASEMENT NEW WORK PLAN - POWER
E400 1/4" = 1'-0"
N2
ELECTRICAL
BASEMENT PLANS
DATE
08.05.2016
SCALE
1/4" = 1'-0"
DRAWN BY
Author
E400
3700 Hamilton Walk, Philadelphia, PA 19104
(E)
Richards Medical Research
Laboratory - Additional Work
Towers C&D
(E)
b
University of Pennsylvania
Perelman School of Medicine
A-2
125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107
A-3
ATKIN OLSHIN SCHADE ARCHITECTS
N2
REVISIONS
ISSUE DATE
DESCRIPTION
D-4
GENERAL NOTES:
1. ALL EQUIPMENT & DEVICES ARE EXISTING UNLESS OTHERWISE NOTED.
KEYED NOTES:
3
D-5
PROVIDE CONDUIT TO SECURITY/ACCESS CONTROL PANEL IN THE BASEMENT LEVEL TELE/DATA
ROOM. DROP TO BASEMENT LEVEL AT BOLLARD. REFER TO BASEMENT POWER PLAN 2/E400 FOR
DIAGRAMMATIC CONDUIT ROUTE AND PANEL LOCATION. REFER TO ARCHITECTURAL DETAILS
FOR CONDUIT ROUTING AT BOLLARDS.
PROVIDE NEW BRANCH CIRCUIT FROM BASEMENT PANEL CBRP, SECTION 2, CIRCUIT NUMBER 3.
PROVIDE CONDUIT DOWN TO BASEMENT LEVEL AT DOOR FRAME LOCATION. REFER TO
BASEMENT POWER PLAN 2/E400 FOR DIAGRAMMATIC CONDUIT ROUTE. COORDINATE CONDUIT
ROUTING WITH ARCHITECT PRIOR TO ROUGH-IN. PROVIDE CONTROL CONDUIT TO PTE
CONTROLLER AT BOLLARD, ROUTED AT BASEMENT LEVEL.
MEPFP ENGINEER
BRUCE E. BROOKS & ASSOC.
2209 Chestnut Street
Philadelphia, PA 19103
215.569.0400
ALTERNATE NO. 2:
ADA OPERATORS AT
BOLLARD (TYPICAL FOR 2)
BASE BID:
ELECTRIC STRIKES ARE
RELEASED BY BLACK
KEY/CARD READER.
CR
PTE
2
3
J ES
ES
1
2
REMOVE ALL EXISTING ACCESS
CONTROL SYSTEMS & ASSOCIATED
DEVICES BACK TO SOURCE.
1
C:\Users\prd\Documents\13-129 Richards Add'l
Scope_prd.rvt
8/5/2016 12:37:35 PM
ELECTRICAL LEVEL 1 NEW WORK PLAN - POWER
E401 1/4" = 1'-0"
PTE
CR
1
University of Pennsylvania
Perelman School of Medicine
A-2
MOUNT DEVICES
ON PEDESTAL
125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107
A-3
ATKIN OLSHIN SCHADE ARCHITECTS
J
ELECTRICAL LEVEL 1
NEW WORK PLAN POWER
DATE
08.05.2016
SCALE
1/4" = 1'-0"
DRAWN BY
PRD
E401
3700 Hamilton Walk, Philadelphia, PA 19104
2
PROVIDE CONDUIT FROM SECURITY/ACCESS CONTROL PANEL LOCATED IN BASEMENT LEVEL
TELE/DATA ROOM TO BACK BOX FOR DOOR CONTROL DEVICE. PROVIDE SPARE CONDUIT
PARALLEL FOR ADDITIONAL DOOR CONTROL EQUIPMENT. REFER TO BASEMENT POWER PLAN
2/E400 FOR DIAGRAMMATIC CONDUIT ROUTE AND PANEL LOCATION.
Richards Medical Research
Laboratory - Additional Work
Towers C&D
1
REVISIONS
ISSUE DATE
DESCRIPTION
GENERAL NOTES:
1. ALL EQUIPMENT & DEVICES ARE EXISTING UNLESS OTHERWISE NOTED.
KEYED NOTES:
1
2
DISCONNECT, EXTEND AND RECONNECT EXISTING BRANCH CIRCUIT WIRING FROM REMOVED EXHAUST
FAN TO NEW EXHAUST FAN FROM PANEL PNH8, CIRCUIT (38,40,42) - 15A, 3P.
NEW VFD LOCATION IN PLACE OF REMOVED MOTOR STARTER DISCONNECT FOR EXISTING TOILET ROOM
EXHAUST FAN.
B-1
(E)PANEL EL7
EF
(E)PANEL C7LP
2
(E)FOR MECH. RM. EF
(E)PANEL 'PNH8'
(E)PANEL 'SB8'
B-8
2
ELECTRICAL LEVEL 8 NEW WORK PLAN - POWER
E402 1/4" = 1'-0"
EXHAUST FAN
LOCATION ON 8TH
FLOOR ABOVE
C:\Users\prd\Documents\13-129 Richards Add'l
Scope_prd.rvt
8/5/2016 12:37:38 PM
DN
University of Pennsylvania
Perelman School of Medicine
2
125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107
VFD FOR EF-2. CONFIRM
INSTALLED BY DIV. 26
ATKIN OLSHIN SCHADE ARCHITECTS
1
3700 Hamilton Walk, Philadelphia, PA 19104
(E)
45kVA
480V
208Y/120V
Richards Medical Research
Laboratory - Additional Work
Towers C&D
MEPFP ENGINEER
BRUCE E. BROOKS & ASSOC.
2209 Chestnut Street
Philadelphia, PA 19103
215.569.0400
(E)PANEL C7RP
ELECTRICAL LEVEL 7, 8
NEW WORK PLAN POWER
1
ELECTRICAL LEVEL 7 NEW WORK PLAN - POWER
E402 1/4" = 1'-0"
DATE
08.05.2016
SCALE
1/4" = 1'-0"
DRAWN BY
PRD
E402
REVISIONS
ISSUE DATE
SYMBOL
TAG
EF
EF
NO.
1
2
ELECTRICAL CONNECTION SCHEDULE
LOCAL
LOCAL
LOCAL
LOCAL
LOCAL
DISCONNECT DISCONNECT DISCONNECT DISCONNECT DISCONNECT
ELECTRICAL
ELECTRICAL
ELECTRICAL
ELECTRICAL
DEVICE
DEVICE
DEVICE
DEVICE
DEVICE
CHARACTERISTICS CHARACTERISTICS CHARACTERISTICS CHARACTERISTICS
STARTER STARTER
STARTER
STARTER
STARTER
STARTER
STARTER
STARTER
MAN MOTOR MAN MOTOR
SW
SW
COMBINATION COMBINATION COMBINATION ACCESSORIES ACCESSORIES
FUSED
UNFUSED
FUSED
UNFUSED
SWITCH
SWITCH
SWITCH
SWITCH
MCP
HOA
PILOT
V/PH/HZ
MCA
MOCP
HP
OL
PILOT
DIV
TYPE
SIZE
DIV
120/1/60
460/3/60
1.25
3.75
15
15
1/4
1-1/2
X
26
23
WIRE
2#12 + 1#12 GND
3#12 + 1#12 GND
VFD
Panel
Circuit
Number
CBRP-SEC. 2
PNH8
2
38,40,42
DESCRIPTION
NOTES:
1. VFD FOR EF-2 PROVIDED/FURNISHED BY DIV. 23 AND INSTALLED BY DIV. 26.
2. EF-1 AND EF-2 TO BE CONNECTED TO EXISTING BAS PANEL SYSTEMS.
3. FOR EF-2: UTILIZE EXISTING 480V, 3-PHASE, 20A-3P CB MADE AVAILABLE BY THE DEMOLITION OF THE EXISTING EF. CONFIRM ALL CONNECTIONS PRIOR TO ROUGH-IN.
NOTES:
LIGHTING FIXTURE SCHEDULE
DESCRIPTION
NO.
TYPE
WATTS
T8
17
VOLTS
MOUNTING
REMARKS
2. SUBSTITUTIONS FOR THE SPECIFIED LIGHTING PRODUCTS ARE ACCEPTABLE FOR PART OF THE SPECIFIED PRODUCTS AND WILL BE CONSIDERED. THE SPECIFIED PRODUCTS
ARE PART OF THE BASIS OF DESIGN. SUBSTITUTIONS ARE AT THE DISCRETION OF THE ARCHITECT. THE PROPOSED SUBSTITUTION LIGHTING PRODUCT MUST BE EQUAL IN EVERY
ASPECT OF THE SPECIFIED FIXTURE.
3. ALL COLORS & FINISHES WILL BE SELECTED BY THE ARCHITECT FROM MANUFACTURER'S COMPLETE AND CUSTOM LINE.
2-5/8"W X 3.75"H X 2' L SLIM, LOW PROFILE
SURFACE MOUNTED. FROSTED, ACRYLIC
EXTRUDED LENS, SLIM END PLATES. INTEGRAL
ELECTRONIC BALLAST. WALL MOUNTED
H.E. WILLIAMS
LLMS-2-1-17-E-SQ
1
RECESSED 6" APERTURE CFL LENSED
DOWNLIGHT. WITH SHOWER TRIM
PRESCOLITE
LF6CV-26-EB-X-6CFV-X-DL-WT
1
20
277V
WALL
4. ALL BALLASTS SHALL BE ELECTRONIC.
277V
RECESSED
ELECTRICAL PANEL SCHEDULE
3 PHASE, 4 WIRE
208/120V
10 KAIC
SURFACE MOUNTED
LOCATION:
TR
P
CKT
1
20 A
1
3
20 A
1
5
--7
--9
--11
--13
--15
--17
--19
--21
--23
--25
--27
--29
--31
--33
--35
--37
--39
--41
---
(EXISTING)
MAIN BUS RATING:
MAINS:
NEUT. BUS:
GRD. BUS:
ISOL GRD. BUS:
DESCRIPTION
RCPTL-BATHROOMS (N)
DOOR MOTORS (N)
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
A
0.36
B
NOTES:
1. (N) DENOTES NEW CIRCUIT BREAKER
C
A
0.06
0.72
B
C
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
TOTAL KVA A:
TOTAL KVA B:
TOTAL KVA C:
C:\Users\prd\Documents\13-129 Richards Add'l
Scope_prd.rvt
8/5/2016 12:37:40 PM
PANEL CBRP-SEC. 2
0.00
0.42
0.72
0.00
150 A
MCB
X
X
DESCRIPTION
EF-1 (N)
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
TOTAL CONNECTED KVA:
TOTAL CONNECTED AMPS:
P
1
---------------------
TR
CKT
20 A
2
-4
-6
-8
-10
-12
-14
-16
-18
-20
-22
-24
-26
-28
-30
-32
-34
-36
-38
-40
-42
1.14 kVA
3.17 A
ELECTRICAL
SCHEDULES
DATE
08.05.2016
SCALE
12" = 1'-0"
DRAWN BY
PRD
E700
3700 Hamilton Walk, Philadelphia, PA 19104
30
MEPFP ENGINEER
BRUCE E. BROOKS & ASSOC.
2209 Chestnut Street
Philadelphia, PA 19103
215.569.0400
26
Richards Medical Research
Laboratory - Additional Work
Towers C&D
CF26
University of Pennsylvania
Perelman School of Medicine
N2
VA/
FIXTURE
MANUFACTURER & CATALOG NUMBER
125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107
F1
DESCRIPTION
ATKIN OLSHIN SCHADE ARCHITECTS
TYPE
1. ELECTRICAL CONTRACTOR SHALL REFER TO ARCHITECTURAL DRAWINGS FOR SECTIONS, ELEVATIONS & ROOM FINISH SCHEDULES, FOR CEILING TYPES AND PROVIDE
APPROPRIATE MOUNTING HARDWARE, PLASTER FRAMES, PENDANTS, ETC. USE THE LIGHTING FIXTURE SCHEDULE AS A GUIDE ONLY.
Download