University of Pennsylvania Perelman School of Medicine ISSUE TO BID Richards Medical Research Laboratory - Additional Scope, Towers C&D 08.05.2016 3700 Hamilton Walk, Philadelphia, PA 19104 PROJECT TEAM CLIENT ARCHITECT MEPFP ENGINEER University of Pennsylvania 3451 Walnut Street Philadelphia, PA 19104 Tel: 215.898.5000 Atkin Olshin Schade Architects 125 S. 9th Street, Suite 900 Philadelphia, PA 19107 215.925.7812 Bruce E. Brooks & Associates 2209 Chestnut Street, Philadelphia, PA 19103 215.569.0400 SHEET INDEX CS Cover Sheet ARCHITECTURAL A001 General Notes & Typical Mounting Heights A100 Basement Floor Plan A101 First Floor Plan A102 Second Floor Plan A103 Third Floor Plan A104 Fourth Floor Plan A105 Fifth Floor Plan A106 Sixth Floor Plan A107 Seventh Floor Plan A116 Goddard - Sixth Floor Plan A600 C Tower Basement Shower Rooms A601 C Tower Stair Cleaning A602 C Tower Lounges A603 C & D Towers Miscellaneous Millwork A604 Goddard Knee Panels & Glazing Film A700 Millwork Details A900 C Tower Entry Doors A901 Entry Door Details A902 Loading Dock Door Details A903 Door Schedule & Details A910 Finish Schedule & Key HVAC H000 H100 H200 H201 H300 H301 H800 HVACCover Sheet HVAC Key Plans HVAC Levels B, 1, & 2 Demolition Plans HVAC levcels 3, 4, 6, 7, & 8 Demolition Plans HVAC Levels B, 1, & 2 New Work Plans HVAC Levels 3, 4, 7, & 8 New Work Plans Mechanical Schedules & Details PLUMBING/FIRE PROTECTION PF000 Plumbing/FP Cover Sheet PF300 Plumbing/FP Basement Demolition & New Work Plans PF800 Plumbing/FP Schedules & Details ELECTRICAL E000 Electrical Cover Sheet E400 Electrical Basement Plans E401 Electrical Level 1 New Work Plan - Power E402 Electrical Level 7, 8 New Work Plan - Power E700 Electrical Schedules RICHARDS GODDARD C D EAST WEST B A ABBREVIATIONS N PROJECT SITE ABV ADJ AFF ALUM ANOD AP ARCH above adjacent above finished floor aluminum anodized access panel architect(ural) BD BITUM BLDG BM BOT BSMT BTW board bituminous building beam bottom basement between CAB CEM CIPC CLG CLR CMU COL CONC CONST CONT CORR CPT CT CTR cabinet cement cast-in-place concrete ceiling clear(ance) concrete masonry unit column concrete construction continuous corridor carpet ceramic tile counter DIAM DIFF DIM DN DR DS DTL DWG diameter diffuser dimension down door downspout detail drawing EL ELEC ELEV EMER EQ EQUIP EXG EXIST EXP EXPN EXT elevation electric(al) elevator emergency equal equipment existing existing exposed expansion exterior FD FE FEC FF FIN FLR FLUR FND FOC FOM FTG FUR floor drain fire extinguisher fire extinguisher cabinet finished floor finish(ed) floor(ing) fluorescent foundation face of concrete face of masonry footing furred, furring GA GALV GL GLBLK GT GPSHTH GWB gauge galvanized glass, glazing glass block grout gypsum sheathing gypsum wall board MULL mullion NAT NIC NOM NRC NTS natural not in contract nominal noise reduction coefficient not to scale HC HDR HDW HM HT HVAC hollow core header hardware hollow metal height heating/ventilating/ air conditioning OC OPG OPP on center(s) opening opposite INS INT insulated interior PLAM PNT PTD PTN PVC PWD plastic laminate paint(ed) painted partition polyvinyl chloride plywood JAN/JC JT janitor (closet) joint LAM LH LT laminated left hand light MAS MAX MATL MECH MEM MIN MISC MLDG MTL MO masonry maximum material(s) mechanic(al) membrane minimum miscellaneous moulding metal masonry opening R'S RA RAD RD REC REF REQ REV RM RO RTN RWC risers return air radius roof drain recommendation reference required revision(s), revised room rough opening return air rainwater conductcor SAB SCHED SD SECT SF SHT SIM SPEC SPKLS SQ FT SST STL SOG STD STN STR SURF SYS sound absorbing batts schedule storm drain section square feet sheet similar specifications sprinklers square foot stainless steel steel slab on grade standard stone structural surface system T'S TEL T&G THK TOS TOSTL TYP treads telephone tongue and groove thick(ness) top of slab top of steel typical UNO, UON unless noted otherwise VERT VIF vertical verify in field WD WGL WPT WPM wood wire glass working point waterproofing membrane REVISIONS ISSUE DATE SANITARY NAP DISPOSAL, BELOW GRAB BAR, WITHIN REACH FROM TOILET TP DISPENS. 60" MIN 3'-0" MIN 16" - 27" MIRROR 1'-6" 33" - 36" 48" MAX 38" MIN 17"-19" 2'-5" MIN WALL OR OBSTRUCTION 33" - 36" LAVATORY 40" MAX 33" - 36" MIRROR 34" MAX 18" MAX 24" 12" MIN MIN 39" - 41" 33" - 39" 15" MIN SPOUT OUTLET 3'-0" 2'-10" 42" MIN 3'-3" 3'-5" SPOUT OUTLET 60" 3'-10" A.F.F. 12" MAX 18" CLR 1 36" MIN ACCESSIBLE SHOWER REVERSIBLE FOLDING SHOWER SEAT 27" MIN 54" MIN 3" MAX 44"-48" TO OPERABLE PARTS 39" - 41" LAVATORY AND MIRROR CLEAR FLOOR SPACE 30" CLR 7"-9" 6'-6" 3'-0" RESTROOM ACCESSORIES 6'-0" ACCESIBLE TOILETS 15"-48" DRINKING FOUNTAINS DI SP PA EN DI PE S. SP R EN TO S. WE L SA DI NI SP TA EN RY S NA TO . PK CO ILE IN VE T S R EA DI T SP OD ENS C O . DI ONT R SP R EN OL S. FIRE EXTINGUISHER SO AP DOOR SIGNAGE DESCRIPTION ALLOWED LAVATORY ANSI STANDARD MOUNTING HEIGHTS A001 SCALE: 1/4" = 1'-0" GENERAL NOTES 1. EXISTING CONDITIONS SHOWN ARE PER AS BUILT DRAWINGS PROVIDED BY OWNER. THE CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS PRIOR TO BEGINNING WORK. ANY DISCREPANCY BETWEEN CONSTRUCTION DOCUMENTS AND ACTUAL CONDITIONS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO COORDINATE AND RESOLVE. 2. DO NOT SCALE THE DRAWINGS. DIMENSIONAL DISCREPANCIES AND QUESTIONS SHALL BE DIRECTED TO THE CONTRACTOR. 3. THE CONTRACTOR SHALL INSTALL ALL EQUIPMENT IDENTIFIED AS OFCI ACCORDING TO MANUFACTURERS' INSTRUCTIONS. 4. THE CONTRACTOR SHALL FULLY COORDINATE ALL ARCHITECTURAL, MECHANICAL, PLUMBING, ELECTRICAL AND STRUCTURAL WORK. THE CONTRACTOR SHALL NOTIFY OWNER AND ARCHITECT OF ANY DISCREPANCIES. 5. THE CONTRACTOR SHALL LOCATE ALL EXISTING UTILITIES AND SERVICES PRIOR TO START OF WORK. 6. THE CONTRACTOR SHALL PROTECT FROM DAMAGE ALL ADJACENT AREAS AND PROPERTIES, SUCH AS LANDSCAPING AND EXTERIOR OR INTERIOR BUILDING SURFACES. LOSS OR DAMAGE SHALL BE REPLACED/REPAIRED AT THE CONTRACTOR’S EXPENSE. MEPFP ENGINEER BRUCE E. BROOKS & ASSOC. 2209 Chestnut Street Philadelphia, PA 19103 215.569.0400 7. ALL EXISTING WORK AFFECTED BY THESE CONTRACT DOCUMENTS SHALL BE RESTORED TO MATCH EXISTING CONDITIONS. 8. ALL DIMENSIONS SHOWN ARE FROM FACE OF FINISH UNLESS OTHERWISE NOTED. CONTRACTOR SHALL VERIFY IN THE FIELD ALL DIMENSIONS. DIMENSIONS NOTED "CLEAR" ARE NOT TO BE ADJUSTED WITHOUT APPROVAL OF ARCHITECT. 9. THESE DRAWINGS ARE PREPARED AND COORDINATED WITH THE PROJECT MANUAL WHICH INCLUDES TECHNICAL SPECIFICATIONS. TOGETHER THESE FORM THE CONSTRUCTION DOCUMENTS. 10. ITEMS OF SALVAGEABLE VALUE SHALL REMAIN THE PROPERTY OF THE OWNER. 11. THE CONTRACTOR SHALL CHALK LINE ALL PARTITIONS FOR REVIEW AND APPROVAL BY OWNER PRIOR TO COMMENCEMENT OF MASONRY AND STUD INTERIOR PARTITIONS. ANY EXISTING FIELD CONDITIONS SHALL IMMEDIATELY BE COORDINATED W/ THE CONTR. C:\Users\pjune\Desktop\revit models\135300 Richards\add'l scope\135302 Richards Add'l 8/5/2016 4:15:50 PM Scope_Central_PJ.rvt CITY OF PHILADELPHIA BUSINESS PRIVILIEGE LICENSE #63180 3700 Hamilton Walk, Philadelphia, PA 19104 Richards Medical Research Laboratory - Additional Scope, Towers C&D University of Pennsylvania Perelman School of Medicine 125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107 ATKIN OLSHIN SCHADE ARCHITECTS 12. CONTRACTOR TO VERIFY LEVEL OF ALL SUB-FLOORS PRIOR TO INSTALLATION OF FINISH FLOOR MATERIALS. General Notes & Typical Mounting Heights DATE 08.05.2016 SCALE 1/4" = 1'-0" DRAWN BY PQJ A001 C:\Users\pjune\Desktop\revit models\135300 Richards\add'l scope\135302 Richards Add'l 8/5/2016 4:15:52 PM Scope_Central_PJ.rvt A6 01 D-6 CLEAN STAIR 3 4 2 ST-C0 C003 D-7 1 A600 ACCESSIBLE GENDER NEUTRAL RESTROOM C003B C003B 1 STAIR C VESTIBULE C003 EXG PARTITION NEW PARTITION C003A WOOD PARTITION GENDER NEUTRAL RESTROOM C003A RICHARDS C RICHARDS D N RICHARDS A GODDARD EAST SCALE 1/4" = 1'-0" DRAWN BY PQJ CITY OF PHILADELPHIA BUSINESS PRIVILIEGE LICENSE #63180 D-5 Basement Floor Plan GODDARD WEST RICHARDS B DATE 08.05.2016 A100 3700 Hamilton Walk, Philadelphia, PA 19104 D-8 MEPFP ENGINEER BRUCE E. BROOKS & ASSOC. 2209 Chestnut Street Philadelphia, PA 19103 215.569.0400 ISSUE DATE Richards Medical Research Laboratory - Additional Scope, Towers C&D University of Pennsylvania Perelman School of Medicine 125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107 D-3 ATKIN OLSHIN SCHADE ARCHITECTS DN REF. REVISIONS DESCRIPTION UP D-2 D006 D-4 D-1 REVISIONS ISSUE DATE DESCRIPTION DN UP SHARED KITCHENETTE C109 D-3 DN D-2 1 03 A6 48 1/2" 1 A700 EXTENDED SOLID SURFACE COUNTERTOP WITH (1) GROMMET C109 20" 18" VIF INFILL TRANSFER GRILL OPENING W/ LIKE (GWB) CONSTRUCTION. PNT TO MATCH. REMOVE TEMP PLYWOOD THRESHOLD. INSTALL NEW ALUM ADA THRESHOLD W/ WEATHERSEAL D-4 C110 C114 D-1 DN 2 A902 BACK-PAINTED GLASS MARKERBOARD WALL LOUNGE C114 1 FE D-8 D-5 CLEAN STAIR 2 STAIR C 1 ST-C1 A6 01 3 4 BOLLARD CX04 CX03 1 A900 CITY OF PHILADELPHIA BUSINESS PRIVILIEGE LICENSE #63180 First Floor Plan VESTIBULE C:\Users\pjune\Desktop\revit models\135300 Richards\add'l scope\135302 Richards Add'l 8/5/2016 4:15:54 PM Scope_Central_PJ.rvt University of Pennsylvania Perelman School of Medicine D-7 125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107 D-6 ATKIN OLSHIN SCHADE ARCHITECTS LOUNGE IMPROVEMENTS RICHARDS C C110 RICHARDS D GODDARD EAST GODDARD WEST RICHARDS B DATE N RICHARDS A CX01 CX02 BOLLARD 08.05.2016 SCALE 1/4" = 1'-0" DRAWN BY Author A101 3700 Hamilton Walk, Philadelphia, PA 19104 CX03 Richards Medical Research Laboratory - Additional Scope, Towers C&D REPAIR GWB, PNT AT ENLARGED TRANSFER DUCT MEPFP ENGINEER BRUCE E. BROOKS & ASSOC. 2209 Chestnut Street Philadelphia, PA 19103 215.569.0400 02 A6 C:\Users\pjune\Desktop\revit models\135300 Richards\add'l scope\135302 Richards Add'l 8/5/2016 4:15:56 PM Scope_Central_PJ.rvt A6 01 02 A6 LOUNGE IMPROVEMENTS D-6 3 4 2 D-7 CLEAN STAIR EXG PARTITION NEW PARTITION 1 WOOD PARTITION STAIR C ST-C2 RICHARDS C N RICHARDS D RICHARDS A GODDARD EAST CITY OF PHILADELPHIA BUSINESS PRIVILIEGE LICENSE #63180 2 C214 REPAIR GWB, PNT AT ENLARGED TRANSFER DUCT D-8 D-5 Second Floor Plan GODDARD WEST RICHARDS B DATE 08.05.2016 SCALE 1/4" = 1'-0" DRAWN BY PQJ A102 3700 Hamilton Walk, Philadelphia, PA 19104 WHITEBOARD PANEL / CONT CHANNEL FRAME MEPFP ENGINEER BRUCE E. BROOKS & ASSOC. 2209 Chestnut Street Philadelphia, PA 19103 215.569.0400 ISSUE DATE Richards Medical Research Laboratory - Additional Scope, Towers C&D 1 A700 University of Pennsylvania Perelman School of Medicine D-3 125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107 UP ATKIN OLSHIN SCHADE ARCHITECTS 24" REVISIONS DESCRIPTION DN D-2 EXTENDED SOLID SURFACE COUNTERTOP W/ (2) GROMMETS 55" SIM 2 03 A6 REF. D-4 D-1 FE LOUNGE C:\Users\pjune\Desktop\revit models\135300 Richards\add'l scope\135302 Richards Add'l 8/5/2016 4:15:57 PM Scope_Central_PJ.rvt A6 01 02 A6 D-5 LOUNGE IMPROVEMENTS D-6 3 4 2 D-7 CLEAN STAIR EXG PARTITION NEW PARTITION 1 WOOD PARTITION STAIR C ST-C3 RICHARDS C RICHARDS D N RICHARDS A GODDARD EAST CITY OF PHILADELPHIA BUSINESS PRIVILIEGE LICENSE #63180 2 C314 REPAIR GWB, PNT AT ENLARGED TRANSFER DUCT D-8 Third Floor Plan GODDARD WEST RICHARDS B DATE 08.05.2016 SCALE 1/4" = 1'-0" DRAWN BY PQJ A103 3700 Hamilton Walk, Philadelphia, PA 19104 WHITEBOARD PANEL / CONT CHANNEL FRAME MEPFP ENGINEER BRUCE E. BROOKS & ASSOC. 2209 Chestnut Street Philadelphia, PA 19103 215.569.0400 ISSUE DATE Richards Medical Research Laboratory - Additional Scope, Towers C&D C316 University of Pennsylvania Perelman School of Medicine D-3 125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107 UP ATKIN OLSHIN SCHADE ARCHITECTS REVISIONS DESCRIPTION DN D-2 C310C C310D C310A C310B REPLACE HDW FUNCTION (TYP OF 4) REPLACE HDW FUNCTION REF. D-4 D-1 FE LOUNGE C:\Users\pjune\Desktop\revit models\135300 Richards\add'l scope\135302 Richards Add'l 8/5/2016 4:15:58 PM Scope_Central_PJ.rvt A6 01 C425 C416 WHITEBOARD PANEL / CONT CHANNEL FRAME 3 4 2 2 02 A6 LOUNGE IMPROVEMENTS D-6 D-7 CLEAN STAIR EXG PARTITION NEW PARTITION 1 WOOD PARTITION STAIR C ST-C4 RICHARDS C RICHARDS D N RICHARDS A GODDARD EAST CITY OF PHILADELPHIA BUSINESS PRIVILIEGE LICENSE #63180 C424 C414 REPAIR GWB, PNT AT ENLARGED TRANSFER DUCT D-8 D-5 Fourth Floor Plan GODDARD WEST RICHARDS B DATE 08.05.2016 SCALE 1/4" = 1'-0" DRAWN BY PQJ A104 3700 Hamilton Walk, Philadelphia, PA 19104 C425 MEPFP ENGINEER BRUCE E. BROOKS & ASSOC. 2209 Chestnut Street Philadelphia, PA 19103 215.569.0400 ISSUE DATE Richards Medical Research Laboratory - Additional Scope, Towers C&D TESTING ROOM University of Pennsylvania Perelman School of Medicine C426 TESTING ROOM D-3 125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107 TESTING ROOM ATKIN OLSHIN SCHADE ARCHITECTS REF. REVISIONS DESCRIPTION DN C422 D-2 C422 C421 C420 C424 C423 REPLACE HDW FUNCTION (TYP OF 8) D-4 D-1 FE Lounge C:\Users\pjune\Desktop\revit models\135300 Richards\add'l scope\135302 Richards Add'l 8/5/2016 4:16:04 PM Scope_Central_PJ.rvt A6 01 3 4 2 D-5 LOUNGE IMPROVEMENTS D-6 D-7 CLEAN STAIR 1 STAIR C ST-C5 RICHARDS C RICHARDS D N RICHARDS A GODDARD EAST CITY OF PHILADELPHIA BUSINESS PRIVILIEGE LICENSE #63180 C514 D-8 Fifth Floor Plan GODDARD WEST RICHARDS B DATE 08.05.2016 SCALE 1/4" = 1'-0" DRAWN BY PJ A105 3700 Hamilton Walk, Philadelphia, PA 19104 02 A6 MEPFP ENGINEER BRUCE E. BROOKS & ASSOC. 2209 Chestnut Street Philadelphia, PA 19103 215.569.0400 ISSUE DATE Richards Medical Research Laboratory - Additional Scope, Towers C&D 2 University of Pennsylvania Perelman School of Medicine C510A 125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107 D-3 ATKIN OLSHIN SCHADE ARCHITECTS REF. REVISIONS DESCRIPTION D-2 C509A C510AA C509AA REPLACE HDW FUNCTION (TYP OF 5) C508AA D-4 D-1 WHITEBOARD PANEL / CONT CHANNEL FRAME Lounge C:\Users\pjune\Desktop\revit models\135300 Richards\add'l scope\135302 Richards Add'l 8/5/2016 4:16:08 PM Scope_Central_PJ.rvt A6 01 3 4 2 UP LOUNGE IMPROVEMENTS - INSTALL 3'-0" WIDE WHITE BOARD. PROVIDED BY OWNER. D-6 D-7 CLEAN STAIR 1 STAIR C ST-C6 RICHARDS C RICHARDS D N RICHARDS A GODDARD EAST CITY OF PHILADELPHIA BUSINESS PRIVILIEGE LICENSE #63180 D-8 D-5 Sixth Floor Plan GODDARD WEST RICHARDS B DATE 08.05.2016 SCALE 1/4" = 1'-0" DRAWN BY PJ A106 3700 Hamilton Walk, Philadelphia, PA 19104 C614 MEPFP ENGINEER BRUCE E. BROOKS & ASSOC. 2209 Chestnut Street Philadelphia, PA 19103 215.569.0400 ISSUE DATE Richards Medical Research Laboratory - Additional Scope, Towers C&D 02 A6 University of Pennsylvania Perelman School of Medicine 2 125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107 D-3 ATKIN OLSHIN SCHADE ARCHITECTS - C609A REF. REVISIONS DESCRIPTION D-2 REPLACE HDW FUNCTION D-4 D-1 WHITEBOARD PANEL / CONT CHANNEL FRAME LOUNGE C:\Users\pjune\Desktop\revit models\135300 Richards\add'l scope\135302 Richards Add'l 8/5/2016 4:16:11 PM Scope_Central_PJ.rvt A6 01 3 4 2 COMPUTER ROOM D-6 3 D708 03 A6 LOUNGE IMPROVEMENTS UP D-7 CLEAN STAIR DN EXG PARTITION NEW PARTITION 1 WOOD PARTITION ST-C7 RICHARDS C RICHARDS D N RICHARDS A GODDARD EAST CITY OF PHILADELPHIA BUSINESS PRIVILIEGE LICENSE #63180 1'-0" 2 A700 REPAIR GWB, PNT AT ENLARGED TRANSFER DUCT D-8 D-5 STAIR C Seventh Floor Plan GODDARD WEST RICHARDS B DATE 08.05.2016 SCALE 1/4" = 1'-0" DRAWN BY PQJ A107 3700 Hamilton Walk, Philadelphia, PA 19104 C714 MEPFP ENGINEER BRUCE E. BROOKS & ASSOC. 2209 Chestnut Street Philadelphia, PA 19103 215.569.0400 ISSUE DATE Richards Medical Research Laboratory - Additional Scope, Towers C&D LOUNGE University of Pennsylvania Perelman School of Medicine 02 A6 125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107 2 ATKIN OLSHIN SCHADE ARCHITECTS D-3 6'-9" REVISIONS DESCRIPTION D-2 REF. D-4 D-1 20" & 18" HEAVY DUTY ADJ SHELVES WHITEBOARD PANEL / CONT CHANNEL FRAME 12'-2" C:\Users\pjune\Desktop\revit models\135300 Richards\add'l scope\135302 Richards Add'l 8/5/2016 4:16:12 PM Scope_Central_PJ.rvt REMOVE FILTER (TYP OF 32) SEE M201 FOR MECH WORK IN THIS ROOM RICHARDS C RICHARDS D N RICHARDS A GODDARD EAST GODDARD WEST Goddard - Sixth Floor Plan RICHARDS B DATE 08.05.2016 SCALE 1/4" = 1'-0" DRAWN BY PQJ A116 3700 Hamilton Walk, Philadelphia, PA 19104 CITY OF PHILADELPHIA BUSINESS PRIVILIEGE LICENSE #63180 MEPFP ENGINEER BRUCE E. BROOKS & ASSOC. 2209 Chestnut Street Philadelphia, PA 19103 215.569.0400 ISSUE DATE Richards Medical Research Laboratory - Additional Scope, Towers C&D 1 A604 University of Pennsylvania Perelman School of Medicine 2 125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107 3 ATKIN OLSHIN SCHADE ARCHITECTS REF. A6 04 REVISIONS DESCRIPTION GLAZING FILM AT CLERESTORY WINDOWS (TYP FOR 6) TYP ALTERNATE 3 INSULATED KNEE PANEL (TYP FOR 32) TYP OF 8 REVISIONS TOILET ACCESSORY LEGEND ISSUE DATE EXG UTILITY SPACE TRANSLUCENT GLAZING FILM -TYPE 2 EXG UTILITY SPACE EXG UTILITY SPACE WALL-MNTD VANITY LIGHT PNTD GWB ON 1 5/8" MTL STUD ODOR CONTROL DISPENSER LIQUID SOAP DISPENSER 4 TA-1 GRAB BAR TA-1 5 FOLDING SHOWER SEAT TA-1 6 FEMININE NAPKIN DISPOSAL TA-1 7 SEAT COVER DISPENSER 8 TA-1 MIRROR TA-9 ODOR CONTROL DISPENSER EQ TA-12 SHOWER BASKET EQ 1. 2. 3. CT-1 REFER TO SHEET A003 FOR MOUNTING HEIGHT INFORMATION PROVIDE (1) TOILET TISSUE DISPENSER PER (1) WC PROVIDE (1) FEMININE NAPKIN DISPOSAL PER (1) WOMEN'S WC FINISH KEY 3'-4" 2'-10" 3 TA-1 CT-1 CERAMIC TILE #1 CT-2 CERAMIC TILE #2 SHOWER STALL INSERT CT-2 CT-2 CT-2 CT-2 4" 8" PAPER TOWEL DISPENSER CT-1 WALL-MNTD LAVATORY 3" TA-1 2 DESCRIPTION TA-11 SHOWER CURTAIN & HOOKS PARABOLIC ALUMINUM BAFFLE WITH TRANSLUCENT LENS WALL-MNTD FRAMELESS MIRROR TOILET TISSUE DISPENSER TA-10 SHOWER CURTAIN ROD CT-1 SHOWER CURTAIN ROD 3'-4" CT-1 6" PTD GWB TA-1 FLR-MNTD WATER CLOSET 7 6 C003A - EAST A600 SCALE: 1/2" = 1'-0" 5 C003A - SOUTH A600 SCALE: 1/2" = 1'-0" C003A - WEST A600 4 SCALE: 1/2" = 1'-0" C003A - NORTH A600 SCALE: 1/2" = 1'-0" REMOVE EXG CONC FLOOR IN SHOWER. USE THICKSET BED FOR FLUSH TILE FLOOR. SLOPE FLOOR TO DRAIN. TA-12 WINDOW OPENING ABV EQ N2 TA-4 ROLL-IN SHOWER INSERT 5' - 3" 2' - 10" EQ EQ EQ 1'-0" ACCESSIBLE LAVATORY WINDOW OPENING ABOVE CLEAR TA-3 FD TA-8 TA-1 CT-1 7" ACCESSIBLE FLR-MNTD WATER CLOSET FOLD-DOWN SHOWER SEAT F1 TA-9 7/8" HAT CHANNEL W/ (1) LAYER 5/8" OF GWB TA-4 C003B 4" EXISTING CMU WALL REMOVE CT FLOOR FINISHES 7' - 6" MIN CT-2 CT-2 C003B - NORTH A600 F1 SCALE: 1/2" = 1'-0" MIN EQ 8 SCALE: 1/2" = 1'-0" 3-5/8" STUD WALLS W/ (1) LAYER 5/8" OF GWB EACH SIDE W/2" SOUND ABSORBING BATTS VESTIBULE 5'-0" A600 EQ 9 C003B - WEST C003 C003 7' - 10" REMOVE DOOR & FRAME 1'-2" 1'-0" C003A F1 TA-9 WALL-MNTD VANITY LIGHT 7" 7' - 10" 7' - 6" MIN EQ 8" 00 A6 EQ EQ 6' - 8" MIN 7" FD 3'-0" EQ TA-6 TA-7 1'-1" TA-4 5 N2 FLR-MNTD WATER CLOSET LOCATE WALL TO CLEAR EXG PIPE FOLD-DOWN SHOWER SEAT 3'-6" 2'-10" 3'-4" F1 EQ 4 3'-0" EQ TA-1 6 REMOVE CT WALL FINISHES EQ 3'-4" 6' - 8" MIN TA-4 C:\Users\pjune\Desktop\revit models\135300 Richards\add'l scope\135302 Richards Add'l 8/5/2016 4:27:14 PM Scope_Central_PJ.rvt 7 TA-2 TA-11 GRAB BARS WINDOW OPENING ABOVE 1'-3" C003A 1'-10" SHOWER STALL INSERT SEE A001 WALL-MNTD LAVATORY LAVATORY TA-10 SHOWER STALL INSERT 3" TA-8 TA-3 GENDER NEUTRAL RESTROOM CT-1 WALL TILE CT-1 WINDOW OPENING ABV EQ 1' - 3" 1'-3" TA-12 VIF EXG UTILITY SPACE EXG UTILITY SPACE CITY OF PHILADELPHIA BUSINESS PRIVILIEGE LICENSE #63180 EQ University of Pennsylvania Perelman School of Medicine EQ TILE DIRECTLY ON CIPC WALLS 125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107 6'-8" ODOR CONTROL DISPENSER MIN 5' - 0" TA-6 CT-1 10 11 9 8 0 0 A6 TA-7 ATKIN OLSHIN SCHADE ARCHITECTS SHOWER CURTAIN ROD C Tower Basement Shower Rooms SHOWER INSERT FLR-MNTD WATER CLOSET CT-2 CT-2 TILE BASE DATE 08.05.2016 11 C003B - EAST A600 SCALE: 1/2" = 1'-0" 10 C003B - SOUTH A600 SCALE: 1/2" = 1'-0" 3 SHOWER ROOM - RCP A600 SCALE: 1/2" = 1'-0" 2 SHOWER ROOM - NEW WORK A600 SCALE: 1/2" = 1'-0" 1 SHOWER ROOM - DEMOLITION A600 SCALE: 1/2" = 1'-0" SCALE 1/2" = 1'-0" DRAWN BY PQJ A600 3700 Hamilton Walk, Philadelphia, PA 19104 7' - 10" TA-2 MEPFP ENGINEER BRUCE E. BROOKS & ASSOC. 2209 Chestnut Street Philadelphia, PA 19103 215.569.0400 F1 TA-5 10'-5" EQ TRANSLUCENT GLAZING FILM - TYPE 2 PARABOLIC ALUMINUM BAFFLE WITH 1/8" THK TRANSLUCENT LENS C003B Richards Medical Research Laboratory - Additional Scope, Towers C&D EQ TA-10 1'-3" ACCESSIBLE GENDER NEUTRAL RESTROOM TA-11 2' - 2 3/4" EXG UTILITY SPACE REVISIONS GENERAL STAIR NOTES - CLEAN ALL CIPC SURFACE ISSUE DATE DESCRIPTION - ALL NEW STAIR SIGNAGE; REMOVE EXG PAINTED SIGNS CLEAN ALL CIPC CEILING SURFACES TYP 7th Floor 84' - 0" 7th Floor 84' - 0" CLEAN ALL CIPC WALL SURFACES TYP 6th Floor 72' - 0" 6th Floor 72' - 0" NEW 8"x6" FLOOR IDENTIFICATION SIGN, TYP. BY OWNER TYP. CLEAN BRASS HANDRAIL END CAPS 5th Floor 60' - 0" 5th Floor 60' - 0" 4th Floor 48' - 0" REMOVE PNTD & ADHESIVE SIGNS, TYP 2nd Floor 24' - 0" 2nd Floor 24' - 0" REMOVE SIGN REMOVE PNTD SIGN, TYP 1st Floor 12' - 0" 1st Floor 12' - 0" REMOVE PNTD SIGN, TYP C:\Users\pjune\Desktop\revit models\135300 Richards\add'l scope\135302 Richards Add'l 8/5/2016 4:16:18 PM Scope_Central_PJ.rvt REMOVE PANEL SIGN Basement 0' - 0" Basement 0' - 0" 4 TOWER C - STAIR, FACING SOUTH A601 SCALE: 3/16" = 1'-0" 3 TOWER C - STAIR, FACING EAST A601 SCALE: 3/16" = 1'-0" 2 TOWER C - STAIR, FACING NORTH A601 SCALE: 3/16" = 1'-0" 1 TOWER C - STAIR, FACING WEST A601 SCALE: 3/16" = 1'-0" CITY OF PHILADELPHIA BUSINESS PRIVILIEGE LICENSE #63180 NEW 18"x24" STAIR IDENTIFICATION SIGN, TYP. BY OWNER TYP. University of Pennsylvania Perelman School of Medicine 3rd Floor 36' - 0" 125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107 3rd Floor 36' - 0" ATKIN OLSHIN SCHADE ARCHITECTS PAINT ALL EXISTING UTILITIES IN STAIR 3700 Hamilton Walk, Philadelphia, PA 19104 ALTERNATE NO.1 Richards Medical Research Laboratory - Additional Scope, Towers C&D 4th Floor 48' - 0" MEPFP ENGINEER BRUCE E. BROOKS & ASSOC. 2209 Chestnut Street Philadelphia, PA 19103 215.569.0400 CLEAN ALL CIPC STAIR SURFACES INCLUDING RISERS C Tower Stair Cleaning DATE 08.05.2016 SCALE 3/16" = 1'-0" DRAWN BY PQJ A601 REVISIONS DESCRIPTION GL-1 3 A700 EXG FA DEVICE ALIGNED W/ B.O. TRUSS ALIGN ALIGN EXG SSTL CORNER GUARD BACK-PAINTED GLASS IN ALUMINUM BRACKET -TYPE GL-2 GL-1 1 A902 WHITEBOARD 5'-0" 1 1/4" 3'-8" 6'-10" CONT 1/2"x1/2"x1/16" ALUM ANGLE TRIM 3'-8" 7'-3" BUTT JOINT 2'-0" RELOCATE EXG THERMOSTAT & CONDUIT TO WALL OPPOSITE 3'-8" STEEL DOOR, TRANSOM, & FRAME CITY OF PHILADELPHIA BUSINESS PRIVILIEGE LICENSE #63180 4" [VERIFY HT] 5/8" TYP C:\Users\pjune\Desktop\revit models\135300 Richards\add'l scope\135302 Richards Add'l 8/5/2016 4:16:19 PM Scope_Central_PJ.rvt C Tower Lounges 2 Interior Elevation - C Tower Lounge Floors 2-7, Facing East A602 SCALE: 1/2" = 1'-0" 1 Interior Elevation - Lounge C114, Facing South A602 SCALE: 1/2" = 1'-0" DATE 08.05.2016 SCALE 1/2" = 1'-0" DRAWN BY PQJ A602 3700 Hamilton Walk, Philadelphia, PA 19104 REMOVE EXG COVER PLATE AND PATCH CONCRETE TO MATCH ADJACENT AREA (TYP OF 3) Richards Medical Research Laboratory - Additional Scope, Towers C&D PROVIDE CUT-OUT FOR CARD READER University of Pennsylvania Perelman School of Medicine PROVIDE CUTOUT IN GLASS FOR MONITOR BACK BOX. COORD. REMOVAL AND REPLACEMENT OF MONITOR BY OWNER. 125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107 REMOVE AND REPLACE EXISTING CMU INFILL AROUND EXG UTILITIES TO PROVIDE MINIMUM CLEARANCES AND NEAT JOINTS. SEAL JOINTS ATKIN OLSHIN SCHADE ARCHITECTS MEPFP ENGINEER BRUCE E. BROOKS & ASSOC. 2209 Chestnut Street Philadelphia, PA 19103 215.569.0400 ISSUE DATE REVISIONS ISSUE DATE DESCRIPTION 2 A700 SHELF STANDARDS, 16" O.C. PNTD PLYWOOD BLOCKING (1) 18" ADJ SHELF (1) 20" ADJ SHELF EXG RACEWAY & CONDUIT 1 A700 SIM PLAM APRON PLAM APRON 1 A700 SS SPLASH RETURN 4" SS SPLASH RETURN EXG COUNTER AND CABINETS C:\Users\pjune\Desktop\revit models\135300 Richards\add'l scope\135302 Richards Add'l 8/5/2016 4:16:20 PM Scope_Central_PJ.rvt (2) SURFACE-MNTD SUPPORT ANGLES EXG COUNTER AND CABINETS CITY OF PHILADELPHIA BUSINESS PRIVILIEGE LICENSE #63180 3700 Hamilton Walk, Philadelphia, PA 19104 EXTENDED SOLID SURFACE COUNTERTOP & BACKSPLASH Richards Medical Research Laboratory - Additional Scope, Towers C&D EXTENDED SOLID SURFACE COUNTERTOP & BACKSPLASH SCALE: 3/4" = 1'-0" University of Pennsylvania Perelman School of Medicine RELOCATE WHITEBOARD TO CLEAR COUNTER A603 125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107 OWNER'S APPLIANCES South Elevation - Computer Room D708 ATKIN OLSHIN SCHADE ARCHITECTS 3 MEPFP ENGINEER BRUCE E. BROOKS & ASSOC. 2209 Chestnut Street Philadelphia, PA 19103 215.569.0400 EXG FURNITURE WORKBENCHES C & D Towers Miscellaneous Millwork 2 South Elevation - Kitchen C208A A603 SCALE: 3/4" = 1'-0" 1 East Elevation - Kitchen C109 A603 DATE 08.05.2016 SCALE: 3/4" = 1'-0" SCALE 3/4" = 1'-0" DRAWN BY PQJ A603 REVISIONS ISSUE DATE DESCRIPTION ALIGN MTL BRACKET ON DOUBLE-STICK TAPE MTL CLEAT ON DOUBLESTICK TAPE VIF 2'-8 1/4" PNTD 1/4" MASONITE ON DOUBLE-STICK TAPE 2 A6 04 3 ALTERNATE 3: INSULATED KNEE PANEL, TYP 4 A604 2 1/2" FABRIC WRAPPED INSULATED PANEL HARDENED EDGE REMOVE FILTER, TYP GENERAL NOTE - TYP OF (8) BUILDING CORNERS 4 A604 4 A604 TYP 4 A604 TYP 3700 Hamilton Walk, Philadelphia, PA 19104 10'-1" 10'-1" University of Pennsylvania Perelman School of Medicine GLAZING FILM (TYPE-1) AT SOUTH SIDE ONLY. TYP. OF (8) WINDOWS CITY OF PHILADELPHIA BUSINESS PRIVILIEGE LICENSE #63180 SCALE: 1/2" = 1'-0" 125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107 A604 ATKIN OLSHIN SCHADE ARCHITECTS GLAZING FILM (TYPE-1) AT SOUTH SIDE ONLY. TYP. OF (8) WINDOWS C:\Users\pjune\Desktop\revit models\135300 Richards\add'l scope\135302 Richards Add'l 8/5/2016 4:16:20 PM Scope_Central_PJ.rvt 1 SCALE: 3" = 1'-0" 2'-3" A604 Enlarged Plan - Goddard Bays 2'-3" ALTERNATE No. 3 Insulated Knee Panel at Goddard Bays Richards Medical Research Laboratory - Additional Scope, Towers C&D 3 1/4" 4 MEPFP ENGINEER BRUCE E. BROOKS & ASSOC. 2209 Chestnut Street Philadelphia, PA 19103 215.569.0400 REMOVE FABRIC FILTERS FROM SUPPLY DUCTS AND VACCUUM FIRST 12" OF DUCT Goddard Knee Panels & Glazing Film 3 Interior Elevation - Goddard Bays A604 SCALE: 1/2" = 1'-0" 2 Interior Elevation, Goddard Bays 2 A604 SCALE: 1/2" = 1'-0" DATE 08.05.2016 SCALE As indicated DRAWN BY PQJ A604 REVISIONS ISSUE DATE DESCRIPTION 8' - 0" MEPFP ENGINEER BRUCE E. BROOKS & ASSOC. 2209 Chestnut Street Philadelphia, PA 19103 215.569.0400 F.O. EXG WALL 2'-0" (1) 18" ADJ. SHELF: KV 183 BRACKET (1) 20" PNTD 3/4" PLYWOOD SHELF W/ SOLID EDGE 2" x 1-1/2" x 1/4" ALUM STRUC ANGLE 1 1/2" 2" x 1" x 1/8" ALUM ANGLE 3/4" x 3/4" x 1/8" ALUM CHANNEL FRAME SEE PLANS (1) 20" ADJ. SHELF: KV 183 BRACKET 3" 1 1/2" EXG RACEWAY 4'-6" 4" SEALANT AND SETTING BLOCK 1" 2 3/8" 5 1/2" 2" 1/8" 1" 2" GROMMET 3/4" SOLID SURFACE COUNTERTOP & BACKSPLASH ON 3/4" PLYWOOD EXG WORK BENCH 1/2" EPOXY ANCHOR & SHIM WASHERS. TYP BACK PAINTED GLASS (GL-2) PLAM APRON TO MATCH EXG DRAWER FRONT 2'-10" 1/8" 2" x 2 1/2" x 1/4" ALUM STRUC ANGLE 3/4" x 3/4" x 1/8" ALUM CHANNEL FRAME NOTE: VERIFY DIMENSIONS OF EXG CASEWORK BEFORE FABRICATOIN 2" x 1 3/4" x 1/8" ALUM ANGLE 2 3/4" COUNTERSUNK ALUM SCREWS Millwork Details C:\Users\pjune\Desktop\revit models\135300 Richards\add'l scope\135302 Richards Add'l 8/5/2016 4:25:54 PM Scope_Central_PJ.rvt EXG CONCRETE WALL 3 WHITEBOARD MOUNTING DETAIL A700 SCALE: 6" = 1'-0" CITY OF PHILADELPHIA BUSINESS PRIVILIEGE LICENSE #63180 1/8" 2 Adjustable Shelves - D1 A700 SCALE: 1 1/2" = 1'-0" 1 Infill Counter at Kitchenettes A700 SCALE: 1 1/2" = 1'-0" DATE 08.05.2016 SCALE As indicated DRAWN BY PQJ A700 3700 Hamilton Walk, Philadelphia, PA 19104 COUNTERSUNK ALUM SCREWS University of Pennsylvania Perelman School of Medicine 2 3/4" 125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107 PNTD PLYWOOD BLOCKING ATKIN OLSHIN SCHADE ARCHITECTS PROVIDE (1) 2" GROMMET PER SHELF SECTION Richards Medical Research Laboratory - Additional Scope, Towers C&D 48" SHELF STANDARDS: KV 83 REVISIONS EXISTING SSTL DOOR FRAMES, REPLACE HORIZONTAL HEAD. VERTICAL JAMBS TO REMAIN, TYP ISSUE DATE EXISTING MOTION DETECTOR LOCATION DESCRIPTION REMOVE AND REPLACE MAGNETIC LOCKS GL-1 REPLACE EXISTING GLASS W/ GL-1 GLAZING LOBBY GL-1 APPROX LOCATION OF EXIST DOOR PIVOT. NEW AUTO DOOR OPERATOR REQUIRES 2-3/4" WEATHER STRIPPING TYP GL-1 REPLACE EXISTING GLASS W/ GL-1 GLAZING 10 1/2" REPLACE SETTING BLOCK W/ SIMILIAR EXISTING STEEL PLATE 3" 3 VESTIBULE - INTERIOR ELEVATION A900 SCALE: 1/2" = 1'-0" EXISTING ALUM PLATE EXISTING REFURBISH BRONZE DOOR FRAME. REPLACE BOTTOM AND TOP RAILS GL-1 REMOVE HORZ DIVIDE & EXTEND GLAZING TO CEILING REPLACE STL FLANGE AROUND ENTIRE PERIMETER OF GLASS EXISTING EXTERIOR GLAZING ASSEMBLY GL-1 BRONZE DOOR PULLS TO MATCH EXISTING SCALE: 6" = 1'-0" 3" 2' - 8 3/4" 1 A903 INTERIOR VESTIBULE 2 A900 SCALE: 1/2" = 1'-0" 5 A900 SIM 1 3/4" REFURBISH BRONZE DOOR FRAME. REPLACE BOTTOM AND TOP RAILS 3 REPLACE EXISTING GLASS W/ GL-1 GLAZING A901 3/4" 3 A903 REPLACE EXISTING GLASS W/ GL-1 GLAZING C:\Users\pjune\Desktop\revit models\135300 Richards\add'l scope\135302 Richards Add'l 8/5/2016 4:16:22 PM Scope_Central_PJ.rvt A900 REPLACE EXISTING FLOOR DIFFUSER PLATES W/ NON-PERFORATED BRONZE PLATES AT WIN WALL ONLY EXISTING DIFFUSER PLATES AT COLUMNS TO REMAIN, TYP REPLACE SETTING BLOCK W/ SIMILIAR, TYP ALTERNATE 2A WORK 4 00 A9 CX01 DC DC REPLACE ALL BRONZE DOOR THRESHOLDS TYP 4 A900 EXISTING CARD READER TO REMAIN PER ALTERNATE CX02 EXTERIOR SCALE: 6" = 1'-0" 4 A900 SIM ALTERNATE 2A: RECESSED DOOR OPERATOR EXISTING GRANITE THRESHOLD NOTE: ALL WORK ON THIS DRAWING PERTAINS TO ALTERNATES 2 & 2A 1'-6" 2 EXISTING BRONZE GUARD TO REMAIN 5 A900 2 1 3/8" APPOX OPENING IN SLAB BELOW 6" 7" EXISTING TERRAZZO FLOOR 1" GROUT JOINT BETWEEN WINDOW AND OUTSIDE EDGE OF DOOR THRESHOLDS EXTERIOR VESTIBULE DOORS - PLAN DETAIL 1'-0" 7" 1 1/2" 1" A901 ALTERNATE 2A: BOLLARD W/ ADA PUSHPLATE FOR DOOR OPERATOR 2 A903 CX04 CX03 EXISTING ALUM EXPANSION JOINT SEALANT & BACKER ROD 1 ALTERNATE SCOPE: RECESSED DOOR OPERATOR. DOOR TO SWING OUTWARD ONLY. PROVIDE BRONZE PULL TO MATCH EXISTING, (SEE 1/A903 FOR PULL DETAILS) ALTERNATE 2A: BOLLARD W/ ADA PUSHPLATE FOR DOOR OPERATOR 13'-4" CITY OF PHILADELPHIA BUSINESS PRIVILIEGE LICENSE #63180 REPLACE PERFORATED BRONZE VENT PLATES LOCATED IN WIN WALL W/ NON-PERFORATED BRONZE PLATES 3" 3 1/2" 7/8" 7/8" University of Pennsylvania Perelman School of Medicine REPLACE SSTL DOOR STRIKE & STOP W/ SIMILIAR VESTIBULE - INTERIOR ELEVATION 125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107 APPROX LOCATION OF EXIST DOOR PIVOT. NEW AUTO DR OPERATOR REQUIRES 2-3/4" REFURBISHED BRONZE DOORS. REPLACE TOP AND BOTTOM RAILS, TYP. REPLACE METAL FLANGE AROUND PERIMETER OF GLASS. VERIFY GAUGE, MATERIAL, AND REPLACE IF REQUIRED ATKIN OLSHIN SCHADE ARCHITECTS EXISTING STAINLESS STEEL DOOR FRAME TO REMAIN. REPLACE HEAD ONLY 4 1/2" INSERT BENT SSTL PLATE INTO EXISTING FRAME TO CONCEAL VERTICAL CONDUIT. MATCH FINISH W/ ADJACENT FRAME. PTE EXTERIOR GRANITE THRESHOLD C Tower Entry Doors CR 2 A903 DATE 08.05.2016 1 VESTIBULE - ENLARGED PLAN A900 SCALE As indicated SCALE: 1/2" = 1'-0" DRAWN BY GR A900 3700 Hamilton Walk, Philadelphia, PA 19104 A901 1' - 0" 5 A900 REMOVE THERMOSTAT 4 A901 INTERIOR VESTIBULE DOORS - PLAN DETAIL 4' - 0 1/4" REPLACE ALL EXISTING SIDELIGHT, DOOR & TRANSOM GL W/ GL-1 GLAZING 3 GL-1 MEPFP ENGINEER BRUCE E. BROOKS & ASSOC. 2209 Chestnut Street Philadelphia, PA 19103 215.569.0400 ALUM EXPANSION JOINT THRESHOLD GL-1 Richards Medical Research Laboratory - Additional Scope, Towers C&D REPLACE EXISTING GLASS W/ GL-1 GLAZING EXISTING SSTL DOOR FRAMES: REPLACE HORIZONTAL DOOR HEADS. VERTICAL JAMBS TO REMAIN, TYP 3 1/4" BRONZE PULLS ON SWING SIDE OF DOORS REFURBISHED BRONZE DOORS. REPLACE TOP AND BOTTOM RAILS, TYP. 3' - 0 3/8" THRESHOLD WDITH 6 3/4" 3/8" EXG GROUT JOINT NEOPRENE SPACER EXISTING TERRAZZO 8' - 3 1/2" NEW VERT SSTL DOOR STOP EXISTING SSTL LOCK ENCLOSURE 3/4" 6" EXISTING TERRAZZO 3 A903 ALTERNATE WORK EXISTING STAINLESS STEEL DOOR FRAME TO REMAIN SSTL PLATE FLUSH WITH FLOOR AND WELDED AT EDGES TO CHANNEL, TYP 8' - 6" 7/8" 3/8" 3' - 0" GL-1 EXISTING SSTL CROSS BRACING REPLACE BRONZE DOOR PANIC BAR W/ SIMILAR. EXTERIOR DR PULLS TO BE REPLACED W/ PULLS MATCHING ORIGINAL, SEE DETAIL 1/A90-2 3/4"1/4" NEOPRENE SPACER ISSUE DATE 1/8" REVISIONS 1/4" 1" 1 1/2" GL-1 GLAZING 2" 2' - 10 3/4" 5/8" 1" 3 1/2" EMBEDDED METAL PLATE DESCRIPTION 6" 2' - 9 1/2" NOTE: ALL WORK ON THIS DRAWING PERTAINS TO ALTERNATES 2 & 2A 1/2" VIF MTL FRAME 6" 6" 1/8" SSTL DOOR FRAME 1 7/8" WEATHERSTRIPPING REPLACE BRONZE TOP DOOR RAIL REPLACE EXISTING GLASS W/ GL-1 GLAZING REPLACE BRONZE TOP DOOR RAIL 6" 8' - 6" 8' - 4" EDGE OF SSTL DOOR FRAME BEYOND 8' - 0 3/4" WEATHER STRIPPING GL-1 GLAZING REFURBSH BRONZE MIDDLE DOOR 'PUSH' RAIL GL-1 GLAZING 7/8" 8' - 3 1/2" 4' - 0 1/4" GL-1 GLAZING REFURBISH BRONZE MIDDLE DOOR 'PUSH' RAIL MEPFP ENGINEER BRUCE E. BROOKS & ASSOC. 2209 Chestnut Street Philadelphia, PA 19103 215.569.0400 1' - 0" 10" REFURBISH OR REPLACE BRONZE PANIC PUSH BARS W/ SIMILIAR 11 3/4" EXTERIOR DOOR PULLS TO BE REPLACED W/ PULLS MATCHING ORIGINAL, SEE DETAIL 1/A903. VERIFY DIMENSIONS 7/8" EDGES OF FRAME BEYOND DOOR STRIKE PATCH TERRRAZO SAWCUT EXISTING SLAB FOR INSTALLATION OF DOOR OPERATOR AS REQ'D 4 1/2" 3 A903 7" 1 1/4" 1 1/8" 4 1/2" 8" 6 7/8" INGROUND DOOR OPERATOR EXISTING CONC SLAB DEPTH SLOTTED HOLE FOR EXPANSION EXISTING CONC SLAB DEPTH 6 3/4" 8" 8" STL PLATE BOLTED TO UNDERSIDE OF CONCRETE SLAB. 1 1/8" C:\Users\pjune\Desktop\revit models\135300 Richards\add'l scope\135302 Richards Add'l 8/5/2016 4:16:23 PM Scope_Central_PJ.rvt 7" INGROUND DOOR OPERATOR EXISTING CONC SLAB DEPTH EXPANSION JOINT. VERIFY LOCATION GROUT JOINT EXISTING OPENING IN SLAB GROUT EXISTING CONC SLAB DEPTH 8" EXPANSION JOINT PLATE COVER 1" PATCH TERRRAZO AS REQ'D 6 7/8" 1/4" EXISTING TERRAZZO FINISH 3" 3/4" EXIST MTL EXPANSION PLATE NEW BRONZE THRESHOLD TO MATCH EXISTING 3" NEW BRONZE THRESHOLD TO MATCH EXISTING NEOPRENE SPACER EXISTING STEEL SUPPORTS. VERIFY SIZE AND LOCATIONS IN THE FIELD EXISTING OPENING IN SLAB 1 1/4" CITY OF PHILADELPHIA BUSINESS PRIVILIEGE LICENSE #63180 Entry Door Details DATE 08.05.2016 4 INTERIOR VESTIBULE WINDOW WALL SECTION DETAIL A901 SCALE: 6" = 1'-0" 3 INTERIOR VESTIBULE DOOR SECTION DETAIL A901 SCALE: 6" = 1'-0" 3 A903 ALTERNATE WORK 2 EXTERIOR VESTIBULE DOOR SECTION DETAIL A901 SCALE: 6" = 1'-0" 1 EXTERIOR VESTIBULE WIN WALL SECTION DETAIL A901 SCALE: 6" = 1'-0" SCALE 6" = 1'-0" DRAWN BY GR A901 3700 Hamilton Walk, Philadelphia, PA 19104 6" EXISTING PERFORATED BRONZE PANEL TO BE REPLACED W/ NEW SOLID BRONZE PLATE REPLACE BRONZE BOTTOM DOOR RAIL REPLACE BRONZE BOTTOM DOOR RAIL University of Pennsylvania Perelman School of Medicine INFLOOR RECESSED ACTUATOR OUTPUT SHAFT 125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107 2' - 8 3/4" 1/2" ATKIN OLSHIN SCHADE ARCHITECTS STAINLESS STEEL CROSS FRAME Richards Medical Research Laboratory - Additional Scope, Towers C&D 1/2" REVISIONS ISSUE DATE SEALANT & BACKER ROD DESCRIPTION 3/8" 1 3/4" 1 1/2" EXISTING CONCRETE WALL 1 3/4" SPACER EXISTING BRICK WALL SEALANT & BACKER ROD SSTL DOOR 1' - 3 3/4" 1' - 3" SSTL ATTACHMENT FLANGE, TO MATCH DOOR AND FRAME 1 1/2" 1 1/2" 1 5/8" 4 3/4" 1 1/2" 3/8" 1 1/2" CLEAN EXISTING VERT SOLDIER COURSE 1 1/2" GL-1 GLASS 1 1/2" 2 1/4" 1 1/2" 1/2" SSTL DOOR FRAME GL-1 GLASS 3 SSTL ATTACHMENT FLANGE, TO MATCH DOOR AND FRAME LOADING DOCK DOOR - PLAN A902 SCALE: 6" = 1'-0" SEALANT SSTL ATTACHMENT FLANGE. EXTEND FROM FLOOR TO CEILING 1/2" 4'-2" SSTL WATER DIVERTER SSTL DOOR FRAME 1 1/4" FRICTION HINGE SSTL DOOR 4 A902 A902 SCALE: 1/2" = 1'-0" SSTL KICK PANEL 8 5/8" SSTL ATTACHEMENT FLANGE GL-1 8' - 6" 4" CONTINUOUS WEATHERSEAL 1/2" SILL 3' - 6" 3/8" EXTERIOR SILL STL SPREADER PLATE BELOW SILL [VERIFY HT REQ'D] WEATHERSEAL C:\Users\pjune\Desktop\revit models\135300 Richards\add'l scope\135302 Richards Add'l 8/5/2016 4:16:24 PM Scope_Central_PJ.rvt BENCH OVERLAPS VERT DOOR FLANGE 4 LOADING DOCK DOOR SECTION DETAIL A902 SCALE: 6" = 1'-0" 1 LOADING DOCK DOOR INTERIOR ELEVATION A902 SCALE: 1/2" = 1'-0" SSTL KICK PLATE CITY OF PHILADELPHIA BUSINESS PRIVILIEGE LICENSE #63180 CLEAN EXISTING VERTICAL BRICK COURSE University of Pennsylvania Perelman School of Medicine GL-1 125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107 SSTL ATTACHEMENT FLANGE BEYOND 3' - 3" T-BAR ATKIN OLSHIN SCHADE ARCHITECTS EXTERIOR Loading Dock Door Details DATE 08.05.2016 SCALE As indicated DRAWN BY GR A902 3700 Hamilton Walk, Philadelphia, PA 19104 2 LOADING DOCK ENTRY DOOR PLAN Richards Medical Research Laboratory - Additional Scope, Towers C&D 3 A902 GL-1 GLASS MEPFP ENGINEER BRUCE E. BROOKS & ASSOC. 2209 Chestnut Street Philadelphia, PA 19103 215.569.0400 C114 1 5/8" REVISIONS VARIES VARIES 2" CERAMIC TILE 6" TOP OF CASE STONE SADDLE EXG FLOOR S2 ADA SILL AT EXG DOOR 3 3/4" FLOOR AS SCHEDULED INTERIOR SILL DETAILS A903 NEW BRONZE SILL TO MATCH EXISTING TOP OF OPERATOR CASE BELOW THRESHOLD [2] INLINE DOORS TO OPERATE TOGETHER S1 STONE SADDLE REFURBISHED DOOR MODIFY TO RECEIVE OPERATOR STEM 4" HORIZONTAL SECTION B-B REFURBISHED FRAME LIQUID TIGHT CONDUIT SCALE: 3" = 1'-0" EXISTING GRANITE (EXTERIOR DOORS ONLY) 1" OUTPUT SHAFT 8" 4 ADA THRESHOLD EXISTING TERRAZZO PATCH AS REQUIRED 6" TOP OF CASE S3 NO SADDLE DOOR DESCRIPTION 7" FLOOR AS SCHEDULED EXG DOOR & FRAME ISSUE DATE EXISTING SSTL DOOR FRAME 6 1/2" PIT DOOR 1 1/4" 1/4" LIQUID TIGHT CONDUIT RAPID SET POUR FILL 2" 4 7/8" 9 3/4" 7 5/8" OPERATOR CASE (2) MTL STUDS @ HEADS AND JAMBS B B A FLOOR GWB PARTITION AS SCHEDULED EXG CMU MASONRY ANCHOR VERTICAL SECTION A-A 1" GROUT SOLID, TYP 1 1/4" JAMB ANCHOR, UL RATED @ RATED FRAMES 1'-9 1/2" CASE 1 1/4" 2'-0" PIT 1" CONT SEALANT A ADJ WALL WHERE OCCURS HM FRAME 3 GROUT SOLID ELEVATION ALTERNATE No. 2A AUTOMATIC DOOR OPERATOR DETAILS A903 SCALE: 3" = 1'-0" 1.5" HOLE THROUGH BOLLARD MOUNTING BRACKET FOR CONDUIT PLAN SCHEDULED DOOR SCHEDULED DOOR MOUNTING HOLES (4 LOCATIONS) H/J-2 JAMB SIM HOLLOW METAL FRAME @ CMU WALL 6" SCALE: 3" = 1'-0" 1/2" THICK MORTISED BOLLARD CAP, R.F. TRANSPARENT (BLACK) Hardware Revisions 2. 3. 4. Replace all existing door hardware (floor closers, top pivots, and pull (where missing.) Refurbish all door components including reinforcing or replacing top and bottom rails to accommodate new closer hardware. Replace all door and sidelight glass with tempered, GL-1 glass.Remove miscellaneous abandoned devices in and on vestibule surfaces. Reuse existing black key security devices. ALTERNATE 2A: EQ 1. 2. EQ 6" 3. F FLUSH L1 4. LOUVERED 5. DOOR TYPES (NEW) A903 SCALE: 1/4" = 1'-0" Classroom Classroom Classroom Classroom Privacy w/ Occupied Indicator 10 10 10 10 11 Storeroom Storeroom Storeroom Storeroom Storeroom Storeroom Storeroom Storeroom Passage Classroom Classroom Classroom Classroom Classroom Classroom Classroom 09 10 10 10 10 10 10 10 Storeroom Storeroom Storeroom Storeroom Storeroom Classroom Classroom Classroom Classroom Classroom 10 10 10 10 10 Storeroom Passage 09 6" 1" CARD READER AT EXTERIOR BOLLARD EXISTING BRONZE PLATE 1/8" FORMED AND BRAZED BRONZE BAR STOCK, MATCH EXISTING BRONZE TUBE, MATCH EXISTING 1'-0" 7 Items 1 through 4 above. Remove existing black key security devices and patch surfaces. Install power operated door openers (in-floor device) for west leaves. Inner door to swing out only. Add new bronze pulls on both interior doors to match existing. Install (2) new custom bollards for ADA actuator and new black-key devices. Remove existing floor grills and infill with st steel plate (or threshold as part of floor closer cover.) Storeroom Storeroom Storeroom Storeroom Storeroom C:\Users\pjune\Desktop\revit models\135300 Richards\add'l scope\135302 Richards Add'l 8/5/2016 4:16:24 PM Scope_Central_PJ.rvt Door # Basement C003 C003A C003B 1st Floor C110 C114 CX01 CX02 CX03 CX04 Status NEW NEW NEW Hardware Type Material 01 02 03 L1 F F HM HM HM Door Finish PNT PNT PNT Door Schedule Frame Type Material Width Height Status 3' - 0" 3' - 0" 3' - 0" 7' - 0" 7' - 0" 7' - 0" NEW NEW NEW F1 F1 F1 HM HM HM 1/2" HEAVY DUTY MASONRY ANCHORS, MIN. ENGAGEMENT 1-1/4" DEEP Finish P-6 P-1 P-1 Head H2 H1 H1 Jamb J2 J1 J1 Sill S1 S3 S3 Comments PROVIDE 18"x6" LOUVER 1" UNDERCUT 1" UNDERCUT BOLLARD MOUNTING BRACKET Door Schedule & Details 1/4-20 STAINLESS STEEL F.H.M.S. EXG NEW EXG EXG EXG EXG 12 08 04 05 06 07 F FG FG FG FG FG HM SSTL/GL BR/GL BR/GL BR/GL BR/GL EXG MFR EXG EXG EXG EXG 6' - 0" 4' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 0" 7' - 0" 8' - 6" 8' - 3" 8' - 3" 8' - 3" 8' - 3" EXG NEW EXG EXG EXG EXG F1 1/A902 1&2/A600 1&2/A600 1&2/A600 SIM 1&2/A600 SIM HM SSTL BR BR BR BR EXG MFR EXG EXG EXG EXG EXG 4/A902 4/A900 4/A900 5/A900 5/A900 EXG 3/A902 4/A900 4/A900 5/A900 5/A900 S2 4/A902 2/A901 2/A901 4/A901 4/A901 CITY OF PHILADELPHIA BUSINESS PRIVILIEGE LICENSE #63180 1. SCALE: 1/4" = 1'-0" 4" University of Pennsylvania Perelman School of Medicine A903 THRU BOLT TO MATCH EXISTING 125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107 ALTERNATE 2: INTERIOR FRAME TYPES SWITCH MOUNT PREP FOR CURVED SWITCHES OR ADAPTER CUFF FOR MOUNTING FLAT 4-1/2" X 4-1/2" CARD READER 1 1/2" 6 HOLLOW MTL 09 12 1/4" F1 Passage N/A Hardware Group 6" VESTIBULE DOORS SCOPE OF WORK Storeroom N/A New Function 3'-6" 1st Floor C109 C110 3rd Floor C310A C310B C310C C310D C316 4th Floor C416 C420 C421 C422 C423 C424 C425 C426 5th Floor C508AA C509A C509AA C510A C510AA 6th Floor C609A Current Function STRAP FOR OPTIONAL TRANSMITTER CONNECT WIRES TO SWITCH ATKIN OLSHIN SCHADE ARCHITECTS Door # MEPFP ENGINEER BRUCE E. BROOKS & ASSOC. 2209 Chestnut Street Philadelphia, PA 19103 215.569.0400 #4-40 SET SCREWS GRANITE OR TERRAZO MOUNTING SURFACE DATE 08.05.2016 ALTERNATE #2 - AUTOMATIC DOOR OPERATOR ALTERNATE #2 - AUTOMATIC DOOR OPERATOR 3700 Hamilton Walk, Philadelphia, PA 19104 A903 Richards Medical Research Laboratory - Additional Scope, Towers C&D HEAD AND JAMB TYPES 1/8" 5 H/J-1 JAMB SIM HOLLOW METAL FRAME @ GYPSUM BOARD PARTITION 2 ALTERNATE No. 2A DOOR ACTUATOR BOLLARD A903 SCALE: 3" = 1'-0" 1 NEW DOOR PULL@ EXISTING ENTRY DOOR A903 SCALE: 6" = 1'-0" SCALE As indicated DRAWN BY GR A903 REVISIONS Basement C003 VESTIBULE C003A GENDER NEUTRAL RESTROOM C003B ACCESSIBLE GENDER NEUTRAL RESTROOM ST-C0 STAIR C CT-1 CT-1 CT-1 XT-1 CT-1 CT-1 CT-1 N/A GWB+P-1 CT-2 CT-2 XCW-1 GWB+P-1 CT-2 CT-2 XCW-1 GWB+P-1 CT-2 CT-2 XCW-1 GWB+P-1 CT-2 CT-2 XCW-1 ACT-3 ACT-3//GWB+P-7 FULL-HEIGHT WALL TILE ACT-3/GWB+P-7 FULL-HEIGHT WALL-TILE XCC-1 SEE PLANS & STAIR ELEVATIONS, USE P-4 TO PNT UTILITIES 1st Floor ST-C1 STAIR C XT-1 N/A XCW-1 XCW-1 XCW-1 XCW-1 XCC-1 SEE PLANS & STAIR ELEVATIONS, USE P-4 TO PNT UTILITIES 2nd Floor ST-C2 STAIR C XT-1 N/A XCW-1 XCW-1 XCW-1 XCW-1 XCC-1 SEE PLANS & STAIR ELEVATIONS, USE P-4 TO PNT UTILITIES 3rd Floor ST-C3 STAIR C XT-1 N/A XCW-1 XCW-1 XCW-1 XCW-1 XCC-1 SEE PLANS & STAIR ELEVATIONS, USE P-4 TO PNT UTILITIES 4th Floor ST-C4 STAIR C XT-1 N/A XCW-1 XCW-1 XCW-1 XCW-1 XCC-1 SEE PLANS & STAIR ELEVATIONS, USE P-4 TO PNT UTILITIES 5th Floor ST-C5 STAIR C XT-1 N/A XCW-1 XCW-1 XCW-1 XCW-1 XCC-1 SEE PLANS & STAIR ELEVATIONS, USE P-4 TO PNT UTILITIES 6th Floor ST-C6 STAIR C XT-1 N/A XCW-1 XCW-1 XCW-1 XCW-1 XCC-1 SEE PLANS & STAIR ELEVATIONS, USE P-4 TO PNT UTILITIES 7th Floor ST-C7 STAIR C XT-1 N/A XCW-1 XCW-1 XCW-1 XCW-1 XCC-1 SEE PLANS & STAIR ELEVATIONS, USE P-4 TO PNT UTILITIES MATERIAL FLOOR CT-1 XT-1 CERAMIC TILE FLOOR EXG TERRAZZO BASE CT-1 CERAMIC BASE TILE PAINT P-1 P-3 P-4 P-5 P-6 P-7 EGGSHELL LATEX SEMI-GLOSS LATEX EGGSHELL LATEX EGGSHELL LATEX FLAT LATEX FLAT LATEX WALL CT-2 XCW-1 CERAMIC WALL TILE EXG CONC/CMU WALL CEILING ACT-3 GWB XCC-1 ACOUSTICAL CEILING PANEL GYPSUM BOARD, PNTD EXG CONC CEILING FINISH KEY SCHEDULE COLOR APPRVD MFR SIZE REMARKS DESERT GRAY SPC EXG 1"x1" SQUARE DESERT GREAT SPC 1'x1" SQUARE PROVIDE COVE, BULLNOSE, AND CORNER SHAPES SHERWIN WILLIAMS SHERWIN WILLIAMS SHERWIN WILLIAMS SHERWIN WILLIAMS SHERWIN WILLIAMS SHERWIN WILLIAMS SW 7551 GREEK VILLA SW 7551 GREEK VILLA GRAY MATCH SW7017 DORIAN GRAY SW7030 ANEW GRAY SW 7007 CEILING BRIGHT WHITE N/A N/A N/A N/A N/A N/A HM IN GWB WALLS PNTD WITH P-1 EXPOSED OVERHEAD UTILITIES IN FINISHED AREAS; TRUSS INFILL PTNS CMU SUBSTRATES CONCRETE SUBSTRATES; D TOWER BASEMENT CLG GWB CEILINGS PEPPER WHITE SPC EXG 1"x1" SQUARE N/A PROVIDE COVE, BULLNOSE, AND CORNER SHAPES N/A WHITE TBD EXG 24"x24" N/A N/A SEE RCP'S FOR ACCESSORIES N/A ARMSTRONG N/A CITY OF PHILADELPHIA BUSINESS PRIVILIEGE LICENSE #63180 NOTES Finish Schedule & Key DATE 08.05.2016 SCALE DRAWN BY PQJ A910 3700 Hamilton Walk, Philadelphia, PA 19104 CLG FINISH Richards Medical Research Laboratory - Additional Scope, Towers C&D WEST University of Pennsylvania Perelman School of Medicine NORTH FINISH SCHEDULE WALL FIINISH SOUTH EAST 125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107 ROOM NAME KEY NAME C:\Users\pjune\Desktop\revit models\135300 Richards\add'l scope\135302 Richards Add'l 8/5/2016 4:16:25 PM Scope_Central_PJ.rvt FLOOR BASE FINISH FINISH ATKIN OLSHIN SCHADE ARCHITECTS ROOM # DESCRIPTION MEPFP ENGINEER BRUCE E. BROOKS & ASSOC. 2209 Chestnut Street Philadelphia, PA 19103 215.569.0400 ISSUE DATE REVISIONS HVAC LEGEND DESCRIPTION STRAINER EXISTING TO REMAIN PIPE DROP THERMOMETER EXISTING TO BE REMOVED (DEMO PLANS) PIPE TAKE-OFF UP NEW WORK PRESSURE GAGE W/ BALL VALVE PIPE ANCHOR RETURN PIPING (NEW WORK PLANS) PIPE GUIDE STEAM PRESSURE GAGE W/ BALL VALVE CAP RETURN, EXHAUST, MAKEUP, OR OUTSIDE AIR INTAKE D STEAM DRIP POCKET SIDEWALL GRILLE M MOTORIZED DAMPER PIPE UP PIPE DOWN FD FIRE DAMPER W/ ACCESS PANEL FD FS FIRE AND SMOKE DAMPER WITH DUCT SMOKE DETECTOR AND ACCESS PANEL RETURN AIR GRILLE SUPPLY AIR DIFFUSER STEAM TRAP F/S CONNECT NEW TO EXISTING SUPPLY AIR DIFFUSER 2-WAY TWO-WAY CONTROL VALVE CUT AND CAP FLEX DUCT THREE-WAY CONTROL VALVE (E) EXISTING TO REMAIN VOLUME DAMPER BALL VALVE (R) EXISTING TO BE REMOVED X BUTTERFLY VALVE (RL) UNDERCUT DOOR OR LOUVERED DOOR EXISTING TO BE RELOCATED MEPFP ENGINEER BRUCE E. BROOKS & ASSOC. 2209 Chestnut Street Philadelphia, PA 19103 215.569.0400 UNION PRESSURE RELIEF VALVE DIAMETER HUMIDISTAT S SMOKE DETECTOR CALIBRATED BALANCING VALVE CO2 CARBON DIOXIDE SENSOR XX GATE VALVE S XX EQUIPMENT TAG EQUIPMENT TYPE DESIGNATOR EQUIPMENT NUMBER SENSOR X XX CHECK VALVE HVAC WATER RISER LOCATION RISER TYPE RISER NUMBER T THERMOSTAT X DOUBLE CHECK VALVE W XX BAS WATER DETECTOR ZS ZONE SUPPY VALVE ASSEMBLY. SEE H800 ZR ZONE RETURN VALVE ASSEMBLY. SEE H800 SECTION MARKER SECTION NUMBER SHEET NUMBER VAV BOX REDUCED PRESSURE BACKFLOW PREVENTION BFP HVAC DRAWING SCHEDULE SHEET NUMBER H000 H100 H200 H201 H300 H301 H800 SHEET NAME HVAC COVER SHEET HVAC KEY PLANS HVAC LEVELS B, 1, & 2 DEMOLITION PLANS HVAC LEVELS 3, 4, 6, 7, & 8 DEMOLITION PLANS HVAC LEVELS B, 1, & 2 NEW WORK PLANS HVAC LEVELS 3, 4, 7, & 8 NEW WORK PLANS HVAC SCHEDULES AND DETAILS 100% CONSTRUCTION DOCUMENTS 07/15/16 ● ● ● ● ● ● ● 3700 Hamilton Walk, Philadelphia, PA 19104 H Richards Medical Research Laboratory - Additional Work Towers C&D HEAT PUMP/HORSE POWER HIGH PRESSURE STEAM RETURN HIGH PRESSURE STEAM SUPPLY DOMESTIC HOT WATER RECIRCULATION/HOUR HEAT RECOVERY WHEEL HOT WATER HEATING HOT WATER PUMP HEATING HOT WATER RETURN HEATING HOT WATER SUPPLY HEAT EXCHANGER REFRIGERANT LIQUID LINE/LOUVER LEAVING AIR TEMPERATURE LINEAR DIFFUSER - RETURN LINEAR BAR GRILLE LINEAR DIFFUSER LOW PRESSURE STEAM RETURN LOW PRESSURE STEAM SUPPLY LINEAR SUPPLY REGISTER LINEAR RETURN GRILLE LEAVING WATER TEMPERATURE MAXIMUM 1000 BTUH MECHANICAL CONTRACTOR MINIMUM FUSE AMPACITY MOTORIZED DAMPER MAXIMUM FUSE SIZE MINIMUM MAXIMUM OVER-CURRENT PROTECTION SIZE MEDIUM PRESSURE STEAM RETURN MEDIUM PRESSURE STEAM SUPPLY MAKE-UP AIR NEW WORK NOT APPLICABLE NORMALLY CLOSED NOT IN CONTRACT NORMALLY OPEN NOT TO SCALE OUTSIDE AIR OUTSIDE AIR INTAKE OPPOSED BLADE DAMPER OFFICE OF PHYSICAL PLANT PUMP PARALLEL BLADE DAMPER PLUMBING CONTRACTOR PUMPED CONDENSATE DRAIN PIPING PRESSURE REDUCING VALVE POUNDS PER SQUARE INCH PACKAGED TERMINAL AIR CONDITIONER EXISTING TO BE REMOVED REFRIGERANT GAS RETURN LINE RETURN AIR RELATIVE HUMIDITY EXISTING TO BE RELOCATED REVOLUTIONS PER MINUTE ROOF TOP UNIT SLOPE SANITARY/SLOPE SUPPLY AIR SECONDARY CHILLED WATER SUPPLY OR RETURN SPLITTER DAMPER SQUARE FEET SOUND TRAP/SILENCER TESTING, ADJUSTING & BALANCING TRANSFER AIR GRILLE TERTIARY CHILLED WATER SUPPLY OR RETURN TOTAL DEVELOPED HEAD(DYNAMIC) TRANSFER FAN TOP OF DUCT TRANSITION TOTAL STATIC PRESSURE TYPICAL UNIT HEATER UNLESS NOTED OTHERWISE UNIT VENTILATOR VARIABLE AIR VOLUME VOLUME DAMPER VARIABLE FREQUENCY DRIVE VERIFY IN FIELD WET BULB WALL EXHAUST GRILLE WALL EXHAUST REGISTER WATER PRESSURE DROP WALL RETURN GRILLE WALL RETURN REGISTER WALL SUPPLY GRILLE WATER SOURCE HEAT PUMP WALL SUPPLY REGISTER WIRE MESH SCREEN University of Pennsylvania Perelman School of Medicine HP HPR HPS HR HRC DHW DHWP DHWR HWS HTX L LAT LDR LBG LD LPR LPS LSR LRG LWT MAX MBH MC MCA MD MFS MIN MOCP MPR MPS MUA (N) N/A NC NIC NO NTS OA OAI OBD OPP P PBD PC PD PRV PSI PTAC (R) R RA RH (RL) RPM RTU s=02' S SA SCHWS/R SD SF ST TAB TAG TCHWS/R TDH TF TOD TR TSP TYP UH U.N.O. UV VAV VD VFD VIF WB WEG WER WPD WRG WRR WSG WSHP WSR WMS 125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107 COMPRESSED AIR PIPING AUTOMATIC AIR VENT AIR COMPRESSOR AIR CONDITIONING FAN (AIR HANDLING UNIT) DUCT ACCESS DOOR ABOVE FINISHED FLOOR ACCESS PANEL AIR PRESSURE DROP AIR SEPARATOR AUTOMATIC TEMPERATURE CONTROLS BOILER BOTTOM OF DUCT BOTTOM OF PIPE BRITISH THERMAL UNIT BTU PER HOUR CEILING DIFFUSER CEILING EXHAUST GRILLE CEILING EXHAUST REGISTER CUBIC FEET PER HOUR CUBIC FEET PER MINUTE CHILLER CHILLED WATER RETURN CHILLED WATER SUPPLY CONSTRUCTION MANAGER CLEAN OUT CONTINUED CONDENSATE PUMP CEILING RETURN GRILLE CEILING RETURN REGISTER COOLING TOWER CONDENSING UNIT CABINET UNIT HEATER CONSTANT VOLUME CHILLED WATER PUMP CONDENSER WATER RETURN CONDENSER WATER SUPPLY CONDENSATE DRAIN PIPING DRY BULB/DECIBEL A-WEIGHTED DECIBEL DIRECT DIGITAL CONTROLS DOMESTIC HOT WATER DOMESTIC HOT WATER RETURN DIAMETER DOWN DUCT MOUNTED SUPPLY GRILLE DUAL TEMPERATURE WATER RETURN DUAL TEMPERATURE WATER SUPPLY DIRECT EXPANSION EXISTING TO REMAIN EXHAUST AIR EACH ENTERING AIR TEMPERATURE ELECTRIC BASEBOARD CONVECTOR ELECTRICAL CONTRACTOR ELECTRIC DUCT HEATER EXHAUST FAN ENERGY RECOVERY WHEEL EXTERNAL STATIC PRESSURE EXPANSION TANK ELECTRIC WATER COOLER ELECTRIC WATER HEATER ENTERING WATER TEMPERATURE EXISTING FURNACE/FAHRENHEIT FREE AREA/FRESH AIR FRESH AIR INLET FLEX CONNECTION/FAN COIL/FORCED CONDENSATE FLOOR DRAIN FLEXIBLE FUEL OIL RETURN FUEL OIL SUPPLY SPRINKLER/FIRE PROTECTION CONTRACTOR FEET PER MINUTE FLOOR RETURN GRILLE FLOOR RETURN REGISTER FLOOR SUPPLY GRILLE FLOOR SUPPLY REGISTER FOOT/FEET FIN-TUBE CONVECTOR GAS GENERAL CONTRACTOR/GRAVITY CONDENSATE GROUND COUPLED RETURN GROUND COUPLED SUPPLY GALLONS PER MINUTE ATKIN OLSHIN SCHADE ARCHITECTS A AAV AC ACF AD AFF AP APD AS ATC B BOD BOP BTU BTUH CD CEG CER CFH CFM CH CHWR CHWS CM CO CONT CP CRG CRR CT CU CUH CV CWP CWR CWS D DB DBA DDC DHW DHWR DIA DN DSG DTR DTS DX (E) E EA EAT EBBC EC EDH EFN ERW ESP ET EWC EWH EWT EX F FA FAI FC FD FLEX FOR FOS FPC FPM FRG FRR FSG FSR FT FTC G GC GCR GCS GPM ISSUE DATE HVAC PLAN SYMBOLS ABBREVIATIONS C:\Users\sas\Documents\13-129 Richards Add'l Scope_SAS.rvt 8/5/2016 12:35:08 PM HVAC COVER SHEET DATE 08.05.2016 SCALE 1/8" = 1'-0" DRAWN BY AG H000 REVISIONS ISSUE DATE DN UP 2 H201 REF. 2 H301 DN UP REF. DN DESCRIPTION 1 H200 1 H300 UP DN 1 HVAC BASEMENT KEY PLAN H100 1" = 40'-0" 5 HVAC LEVEL 4 KEY PLAN H100 1" = 40'-0" DN UP REF. 2 H300 REF. DN UP 2 H200 5 H201 5 H301 UP UP 8 2 MEPFP ENGINEER BRUCE E. BROOKS & ASSOC. 2209 Chestnut Street Philadelphia, PA 19103 215.569.0400 HVAC LEVEL 6 KEY PLAN H100 1" = 40'-0" HVAC LEVEL 1 KEY PLAN H100 1" = 40'-0" DN UP 3 H201 3 H200 REF. 3 H300 DN D N UP REF. 3 H301 1 H201 1 H301 DN UP REF. 4 H201 4 H301 HVAC KEY PLANS C:\Users\sas\Documents\13-129 Richards Add'l Scope_SAS.rvt 8/5/2016 12:35:49 PM UP DN 4 HVAC LEVEL 3 KEY PLAN H100 1" = 40'-0" 7 HVAC LEVEL 8 KEY PLAN H100 1" = 40'-0" DATE 08.05.2016 SCALE 1" = 40'-0" DRAWN BY AG H100 3700 Hamilton Walk, Philadelphia, PA 19104 DN UP Richards Medical Research Laboratory - Additional Work Towers C&D HVAC LEVEL 7 KEY PLAN H100 1" = 40'-0" HVAC LEVEL 2 KEY PLAN H100 1" = 40'-0" University of Pennsylvania Perelman School of Medicine 6 3 125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107 UP ATKIN OLSHIN SCHADE ARCHITECTS DN REVISIONS ISSUE DATE DESCRIPTION (E)6ø SA REF. (E)14x10 SA (R) TRANSFER GRILLES. SEE ARCH DRAWINGS FOR WALL PATCHING. (E)6ø SA (RL) TEMP/HUMIDITY SENSOR. SEE NEW WORK PLANS FOR NEW LOCATION T T H H F/S REMOVE TWO EXISTING RADIATORS AND ASSOCIATED PIPING AND CONTROLS. (E)16x8 SA (E)20x10 SA (E)12x6 SA (E)16x8 SA REMOVE CHILLED BEAM FOR REINSTALLATION BELOW RETURN DUCT. (R) 14x8 WRR AND DUCT BRANCH (R) TRANSFER ASSEMBLY. SEE ARCH DRAWINGS FOR WALL PATCHING SCOPE. (R) TRANSFER ASSEMBLY 20x10 (E) 14x12 SA F/S F/S (E)14x12 SA(E) BRANCH PIPE TAPS OFF BOTTOM OF MAIN. RELOCATE TO TOP TO MAKE WAY FOR RA DUCT. REMOVE DUCT AND PIPING CONNECTION TO CHILLED BEAM SA 6ø C:\Users\sas\Documents\13-129 Richards Add'l Scope_SAS.rvt 8/5/2016 12:36:02 PM HVAC BASEMENT DEMOLITION PLAN H200 1/8" = 1'-0" HVAC LEVEL 2 DEMOLITION PLAN H200 1/4" = 1'-0" 3700 Hamilton Walk, Philadelphia, PA 19104 1 3 University of Pennsylvania Perelman School of Medicine HVAC LEVEL 1 DEMOLITION PLAN H200 1/4" = 1'-0" 125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107 2 ATKIN OLSHIN SCHADE ARCHITECTS UP Richards Medical Research Laboratory - Additional Work Towers C&D MEPFP ENGINEER BRUCE E. BROOKS & ASSOC. 2209 Chestnut Street Philadelphia, PA 19103 215.569.0400 F/S SA 5ø (R) 20x10 WRR AND DUCT BRANCH (E)24x10 RA (E) 16x14 SA (E) 12x8 SA (E) 22x12 SA REMOVE PIPING BACK TO MAINS RECENTLY INSTALLED IN PHASE 2. (E) 22x16 SA (E) 16x8 SA (E)16x8 SA (E)26x12 SA (R) 8x16 GRILLE. SEE NEW WORK PLAN FOR RELOCATION. (E)16x12 RA F/S F/S REF. (RL) TEMP/HUMIDITY SENSOR. SEE NEW WORK PLANS FOR NEW LOCATION HVAC LEVELS B, 1, & 2 DEMOLITION PLANS DATE 08.05.2016 SCALE As indicated DRAWN BY AG H200 REVISIONS ISSUE DATE DESCRIPTION (RL) TEMP/HUMIDITY SENSOR. SEE NEW WORK PLANS FOR NEW LOCATION (RL) TEMP/HUMIDITY SENSOR. SEE NEW WORK PLANS FOR NEW LOCATION REF. WRR 14X10 585 CFM H T REMOVE CHILLED BEAM FOR RE-INSTALLATION BELOW RETURN DUCT. RELOCATE CHW PIPING ABOVE WIRE TROUGH/SOLID CABLE TRAY TO ALLOW ROOM BELOW FOR RETURN AIR DUCT. (R) TRANSFER ASSEMBLY (E)10x6 SA (R) 16x12 WRR AND DUCT BRANCH (E)24x12 RA (E)24x14 SA (R) TRANSFER ASSEMBLY (E)16x8 SA (E)18x12 SA (E)22x12 SA (E)16x8 SA (R) 16x12 WRR AND DUCT BRANCH (E)14x12 SA (E)14x12 SA (E)24x14 SA F/S F/S F/S H (E)16x8 SA REMOVE CHILLED BEAM FOR REINSTALLATION BELOW RETURN DUCT. (E)12x6 SA (E)24x12 RA (E)16x8 SA (E)14x12 RA (E)16x8 SA (E)14x10 RA F/S REMOVE DUCT AND PIPING CONNECTION TO CHILLED BEAM F/S 1 REMOVE DUCT AND PIPING CONNECTION TO CHILLED BEAM 2 HVAC LEVEL 3 DEMOLITION PLAN H201 1/4" = 1'-0" HVAC LEVEL 4 DEMOLITION PLAN H201 1/4" = 1'-0" MEPFP ENGINEER BRUCE E. BROOKS & ASSOC. 2209 Chestnut Street Philadelphia, PA 19103 215.569.0400 T (E) EA DN (RL) TEMP/HUMIDITY SENSOR. SEE NEW WORK PLANS FOR NEW LOCATION T PI OFFICE 602W (E) EA UP (E)24x12 RA (E)12x6 SA (R) TRANSFER ASSEMBLY (R) 16x12 WRR AND DUCT BRANCH (E)24x14 SA 5 F/S F/S (E)20x18 EA (E)5ø SA (E)14x12 SA HVAC LEVEL 6 DEMOLITION PLAN H201 1/4" = 1'-0" PREP EXISTING DUCTWORK FOR NEW CONNECTIONS REMOVE DUCT AND PIPING CONNECTION TO CHILLED BEAM (R) EXHAUST FAN (R)6x6 (E)6x10 SA (R) OPENENDED DUCT 3 C:\Users\sas\Documents\13-129 Richards Add'l Scope_SAS.rvt 8/5/2016 12:36:12 PM HVAC LEVEL 7 DEMOLITION PLAN H201 1/4" = 1'-0" 3700 Hamilton Walk, Philadelphia, PA 19104 H201 Richards Medical Research Laboratory - Additional Work Towers C&D REMOVE CHILLED BEAM FOR REINSTALLATION BELOW RETURN DUCT. 6 University of Pennsylvania Perelman School of Medicine (E)10x14 SA 125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107 (E)16x8 SA ATKIN OLSHIN SCHADE ARCHITECTS (E)22x12 SA H (E)16x12 RA T (E)10x30 EA (E)16x8 SA HVAC LEVELS 3, 4, 6, 7, & 8 DEMOLITION PLANS 4 HVAC LEVEL 8 DEMOLITION PLAN H201 1/4" = 1'-0" DATE 08.05.2016 6 G602W DEMO SECTION H201 1/4" = 1'-0" SCALE 1/4" = 1'-0" DRAWN BY AG H201 REVISIONS ISSUE DATE DESCRIPTION (E)6ø SA (E)14x10 SA 16x6 WRR ABOVE CEILING - BALANCE TO 330 CFM (E)6ø SA H T T R PROVIDE ACOUSTIC LINING ON THIS SECTION OF NEW DUCTWORK - JOHNS MANVILLE PERMACOTE LINACOUSTIC R300 OR EQUIVALENT RA 16x6 1 8x8 RA BELOW PIPING - VERIFY OPENING SIZE IN FIELD AND PROVIDE LARGEST POSSIBLE DUCT THROUGH (E) OPENING. TRANSITION TO 8x16 IMMEDIATELY AFTER OPENING RA 8x16 WEG 120 CFM (E)16x8 SA H T R WEG 120 CFM EA 16x4 1 (RL) TEMP/HUMIDITY SENSOR. PENETRATE ELECTRICAL ROOM WALL WEST OF EXISTING SPRINKLER PIPE. RELOCATED CONDUIT AS REQUIRED. PROVIDE 1.5 HRRATED FIRE DAMPER AT WALL PENETRATION REBALANCE (E) WSR TO 225 CFM (E)14x12 SA F/S EF EA 10x6 (E) HW PUMPS WRR 34X14 1350 CFM RA 36x10 F/S FD VOLUME DAMPER (E)16x14 RA (E) B-TOWER HW ISOLATION VALVES (E)22x12 SA (E)12x8 SA (E)22x16 SA EA 10x4 3/4" HWR (E)16x8 RA 3/4" HWS 1 UP 2 HVAC LEVEL 1 NEW WORK PLAN H300 1/4" = 1'-0" WEG 12x8 240 CFM ROUTE IN FIELD TO COORDINATE WITH EXISTING DUCTWORK AND PIPING SHOWER ROOM EXHAUST DUCTWORK UPSTREAM OF EF1 SHALL BE ALUMINUM EA 12x12 REF. CONNECT TO (E) 42x12 EA RISER ABANDONED IN PHASE 1 (E)16x12 RA (E)20x10 SA (E)16x8 SA PROVIDE NEW A-TOWER HW ISOLATION VALVE (E) HWR RISER TO A TOWER (E)16x8 SA RE-INSTALL CHILLED BEAM AT LOWER ELEVATION, COORDINATED WITH NEW RETURN DUCT VOLUME DAMPER RA 44x10 VOLUME DAMPER RA 36x9 H T 5ø F/S C:\Users\sas\Documents\13-129 Richards Add'l Scope_SAS.rvt 8/5/2016 12:36:16 PM F/S (E)14x12 SA RELOCATED 1/2" CHW BRANCH TAPPED OFF TOP OF MAIN RE-INSTALL CHILLED BEAM BRANCH DUCT, PIPING, AND CONTROL, BALANCING AND SHUT-OFF VALVES HVAC LEVELS B, 1, & 2 NEW WORK PLANS 1 HVAC BASEMENT NEW WORK PLAN H300 1/4" = 1'-0" (E)26x12 SA (E)12x6 SA (RL) TEMP/HUMIDITY SENSOR. WRR 36X9 1350 CFM (E)24x10 RA REBALANCE (E) WSR TO 225 CFM University of Pennsylvania Perelman School of Medicine PROVIDE NEW A-TOWER HW ISOLATION VALVE 125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107 (E) HWS RISER TO A TOWER ATKIN OLSHIN SCHADE ARCHITECTS (E) EA DUCT CONTINUES TO FAN ON. CONFIRM ROUTING AT THE START OF CONSTRUCTION. REMOVE FAN WHEEL AND INTERNAL COMPONENTS AND REUSE FAN HOUSING AS RAIN CAP. 3700 Hamilton Walk, Philadelphia, PA 19104 MEPFP ENGINEER BRUCE E. BROOKS & ASSOC. 2209 Chestnut Street Philadelphia, PA 19103 215.569.0400 RUN DUCT IN FRONT OF EXISTING SPRINKLER PIPE, IN SOFFIT EA 12x12 Richards Medical Research Laboratory - Additional Work Towers C&D EA 12x12 3 HVAC LEVEL 2 NEW WORK PLAN H300 1/4" = 1'-0" DATE 08.05.2016 SCALE 1/4" = 1'-0" DRAWN BY AG H300 REVISIONS ISSUE DATE DESCRIPTION (E)16x8 SA (E)16x8 SA VOLUME DAMPER (E)10x6 SA H T REBALANCE (E) WSR TO 225 CFM WRR 34X14 1350 CFM (RL) TEMP/HUMIDITY SENSOR. (RL) TEMP/HUMIDITY SENSOR. (E)24x14 SA 5ø F/S (E)14x12 SA RA 36 X12 F/S RE-INSTALL CHILLED BEAM BRANCH DUCT, PIPING, AND CONTROL, BALANCING AND SHUT-OFF VALVES F/S F/S 1 VOLUME DAMPER RA 40x8 (E)14x12 SA F/S RE-INSTALL CHILLED BEAM BRANCH DUCT, PIPING, AND CONTROL, BALANCING AND SHUT-OFF VALVES 2 HVAC LEVEL 3 NEW WORK PLAN H301 1/4" = 1'-0" HVAC LEVEL 4 NEW WORK PLAN H301 1/4" = 1'-0" MEPFP ENGINEER BRUCE E. BROOKS & ASSOC. 2209 Chestnut Street Philadelphia, PA 19103 215.569.0400 REBALANCE (E) WSR TO 225 CFM VOLUME DAMPER RA 28x18 5ø T (E)24x12 RA H VOLUME DAMPER WRR 40x8 1350 CFM RELOCATE CHW PIPING ABOVE ELECTRICAL WIRE TROUGH/SOLID CABLE TRAY. RUN RA DUCT BELOW WIRE TROUGH. (E)24x12 RA (E)12x6 SA (E)16x8 SA RE-INSTALL CHILLED BEAM AT LOWER ELEVATION, COORDINATED WITH NEW RETURN DUCT (E)18x12 SA (E)14x12 RA RE-INSTALL CHILLED BEAM AT LOWER ELEVATION, COORDINATED WITH NEW RETURN DUCT (E)24x14 SA (E)16x8 SA REF. T (E)16x8 SA (E)22x12 SA (E)14x10 RA REF. (E) EA DN PI OFFICE 602W 5 REBALANCE (E) WSR TO 225 CFM T VOLUME DAMPER RA 40x10 2 WRR 40x10 1350 CFM SA 5ø (E)20x18 EA CONNECT TO EXISTING DUCTWORK (E)14x12 SA F/S F/S (E)24x14 SA (RL) TEMP/HUMIDITY SENSOR. (E)24x12 RA EF HVAC LEVEL 6 NEW WORK PLAN H301 1/4" = 1'-0" RA 40x10 RE-INSTALL CHILLED BEAM BRANCH DUCT, PIPING, AND CONTROL, BALANCING AND SHUT-OFF VALVES (N) CD 3 C:\Users\sas\Documents\13-129 Richards Add'l Scope_SAS.rvt 8/5/2016 12:36:26 PM HVAC LEVEL 7 NEW WORK PLAN H301 1/4" = 1'-0" 3700 Hamilton Walk, Philadelphia, PA 19104 H VOLUME DAMPER Richards Medical Research Laboratory - Additional Work Towers C&D (E)12x6 SA (E) EA UP University of Pennsylvania Perelman School of Medicine RE-INSTALL CHILLED BEAM AT LOWER ELEVATION, COORDINATED WITH NEW RETURN DUCT H301 125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107 (E)16x12 RA (E)22x12 SA (E)10x14 SA 6 (N) CD ATKIN OLSHIN SCHADE ARCHITECTS (E)10x30 EA (E)16x8 SA HVAC LEVELS 3, 4, 7, & 8 NEW WORK PLANS 4 HVAC LEVEL 8 NEW WORK PLAN H301 1/4" = 1'-0" 6 G602W NEW WORK SECTION H301 1/4" = 1'-0" DATE 08.05.2016 SCALE 1/4" = 1'-0" DRAWN BY AG H301 REVISIONS ISSUE DATE DESCRIPTION 1 01 AUG 2014 ISSUE FOR BID 2 08 AUG 2014 ADDENDUM #3/ ISSUE FOR PERMITS AIR DEVICE SCHEDULE FACE/ SLOTS/ SPACING BORDER BASIS WHITE BAKED ENAMEL 35 FIXED DEGREE BARS, VERTICAL BARS, 3/4" SPACING 1-1/4" BORDER WITH CONCEALED SCREWS PRICE 530 OPPOSED BLADE DAMPER. PLASTER FRAME FOR DRYWALL INSTALLATIONS. ALUMINUM WHITE BAKED ENAMEL 35 FIXED DEGREE HORIZONTAL BARS 1-1/4" BORDER PRICE 630 OPPOSED BLADE DAMPER. PLASTER FRAME WHERE REQ'D. STEEL WHITE BAKED ENAMEL ADJUSTABLE BLADES SURFACE MOUNT PRICE SMDA DESIGNATION MATERIAL WRR STEEL CEG CD FINISH REMARKS 9"x6" WITH OPPOSED BLADE DAMPER AND ADJUSTABLE BLADES. NOTES: 1. REFER TO FLOOR PLANS FOR BALANCING CFM. 2. ARCHITECT TO SELECT COLOR EXHAUST FAN SCHEDULE SYMBOL TAG NO. EF 1 EF 2 SERVICE BASEMENT SHOWER ROOMS C TOWER CORE BATHROOMS LOCATION BASEMENT MECH ROOM LEVEL 8 MECH ROOM CFM 720 4120 ESP (IN WC) 0.5 1 RPM 1209 1328 HP 1/4 1-1/2 SONES 6.1 19.7 V/PH/HZ 120/1/60 460/3/60 FLA 1 3 BASIS MANUFACTURER NAME MODEL NO GREENHECK SQ-100-VG GREENHECK SWB-118 NOTES: 1. EF-2 SHALL BE PROVIDED WITH A VFD FOR BALANCING. 2. EF-1 AND EF-2 SHALL TIE INTO THE EXISTING BAS. RADIATOR SCHEDULE DEPTH 2" HEIGHT 8-5/8" EWT 180 RUNOUT SIZES 3/4" BASIS OF DESIGN RUNTAL RF-3 1. ALL DIMENSIONS ARE NET FREE AREA. WHERE ACOUSTIC LINER IS USED, INCREASE SHEET METAL DIMENSIONS TO ALLOW FOR INSTALLATION OF LINER. VAPOR SEAL BUTT JOINT PLAN VIEW - CLAMP INSTALLATION AIR FLOW * CONCRETE STRUCTURE MAIN SUPPLY AIR DUCT HANGER ROD 45° VIBRATION ISOLATOR (WHERE APPLICABLE. REFER TO SPECIFICATIONS) 5 DUCT DIAMETERS LOCK NUT EXPANSION SHIELD STANDARD ADJUSTABLE CLEVIS SUPPORT NUT BRANCH DUCT VOLUME DAMPER (WHERE REQUIRED) SEE FLOOR PLAN FOR PIPE SIZE PRE INSULATED CLAMP INSERT C:\Users\sas\Documents\13-129 Richards Add'l Scope_SAS.rvt 8/5/2016 12:36:27 PM * EQUALS 1/4 WIDTH OF BRANCH DUCT MINIMUM 4". SINGLE PIPE HANGER SECTION VIEW 1 H - DUCT - RECTANGULAR DUCT TAKE-OFF DETAIL H800 N.T.S. 2. LEADING EDGE OF ACOUSTIC DUCT LINER SHALL BE PROTECTED WITH A SHEET METAL NOSING, MINIMUM 3/4" LONG. 3. ALL DUCTWORK SHALL BE CONSTRUCTED WITH A "SMOOTH" EXTERIOR APPEARANCE. OBTAIN APPROVAL FROM OWNER FOR PROPOSED DUCT CONSTRUCTION, JOINTS AND JOINING METHODS. 4. PREPARE SURFACES OF DUCTWORK FOR PAINTING. REMOVE ALL STICKERS, OIL, AND OTHER RESIDUE. University of Pennsylvania Perelman School of Medicine DUCTWORK CONSTRUCTION NOTES: 125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107 PRE-INSULATED RIGID CLAMP INSERT WITH VAPOR BARRIER (KLO-SHURE OR EQUAL) ATKIN OLSHIN SCHADE ARCHITECTS UNISTRUT STRAP AND LOCKING NUT HVAC SCHEDULES AND DETAILS 5 PIPE HANGER DETAIL H800 N.T.S. 3700 Hamilton Walk, Philadelphia, PA 19104 BTUH/LF 699 WATER LWT EAT GPM 160 65 SEE RISER MEPFP ENGINEER BRUCE E. BROOKS & ASSOC. 2209 Chestnut Street Philadelphia, PA 19103 215.569.0400 TUBE MATERIAL STEEL ELEMENT LENGTH 2 FT Richards Medical Research Laboratory - Additional Work Towers C&D ENCLOSURE STYLE EXPOSED STRUCTURAL ENGINEER KEAST & HOOD CO. 400 Market Street Suite 1250 Philadelphia, PA 19106 215.625.0099 SYMBOL TAG NO. R 1 DATE 08.05.2016 SCALE As indicated DRAWN BY AG H800 REVISIONS ISSUE DATE DESCRIPTION PLUMBING LEGEND ABBREVIATIONS EXISTING TO REMAIN PIPE GUIDE TRAP EXISTING VENT TO REMAIN CAP FUNNEL DRAIN AND/OR FLOOR SINK EXISTING TO BE REMOVED BALL-TYPE SHUTOFF VALVE EXISTING VENT TO BE REMOVED BUTTERFLY VALVE NEW WORK GATE VALVE G NATURAL GAS CONNECTION REDUCER XX XX PLUMBING FIXTURE TAG FIXTURE TYPE FIXTURE NUMBER NEW VENT PIPE DRAIN VALVE X XX SANITARY/VENT RISER LOCATION RISER TYPE RISER NUMBER DIAMETER BALANCING VALVE X XX PRESSURE RELIEF VALVE CUT AND CAP CHECK VALVE EXISTING TO REMAIN EXISTING TO BE REMOVED NATURAL GAS COCK (RL) EXISTING TO BE RELOCATED VERTICAL VALVE METER SHOCK ABSORBER W/ ACCESS PANEL GAS METER ANTI-SIPHONAGE VACUUM BREAKER GAS PRESSURE REGULATOR THERMOMETER PIPE UP PRESSURE GAGE W/ BALL VALVE PIPE DOWN HOSE BIBB PIPE DROP WALL CLEAN OUT UNION FLOOR DRAIN/TRAP PLUMBING/ FIRE PROTECTION DRAWING SCHEDULE SHEET NUMBER PF000 PF300 C:\Users\sas\Documents\13-129 Richards Add'l Scope_SAS.rvt 8/5/2016 12:36:27 PM PF800 SHEET NAME PLUMBING/FIRE PROTECTION COVER SHEET PLUMBING/FIRE PROTECTION BASEMENT DEMOLITION AND NEW WORK PLANS PLUMBING/FIRE PROTECTION SCHEDULES AND DETAILS 100% CONSTRUCTION DOCUMENTS 07/15/16 ● ● ● 3700 Hamilton Walk, Philadelphia, PA 19104 PIPE ANCHOR Richards Medical Research Laboratory - Additional Work Towers C&D MEPFP ENGINEER BRUCE E. BROOKS & ASSOC. 2209 Chestnut Street Philadelphia, PA 19103 215.569.0400 (R) R RISER NUMBER REDUCED PRESSURE BACKFLOW PREVENTION BFP M RISER TYPE University of Pennsylvania Perelman School of Medicine (E) CONNECT NEW TO EXISTING DOMESTIC WATER RISER LOCATION 125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107 ABOVE AREA DRAIN ACCESS PANEL BATH TUB CUBIC FEET PER HOUR CEILING CLEAN OUT CONTINUED CLEAN OUT TO GRADE DOMESTIC COLD WATER DRAINAGE FIXTURE UNITS DOMESTIC HOT WATER DOMESTIC HOT WATER RETURN DOWN DIONIZED DISHWASHER EXISTING TO REMAIN EACH ELECTRICAL CONTRACTOR EMERGENCY SHOWER EMERGENCY EYEWASH ELECTRIC WATER COOLER ELECTRIC WATER HEATER ELEVATION EXISTING FRESH AIR INLET FORCED CONDENSATE FLOOR CLEAN OUT FLOOR DRAIN FIRE PROTECTION PIPING SPRINKLER/FIRE PROTECTION CONTRACTOR FLOOR SINK FOOT/FEET GAS GRAVITY CONDENSATE GENERAL CONTRACTOR GAS WATER HEATER HORSE POWER DOMESTIC HOT WATER RECIRCULATION/HOUR WALL HYDRANT INDIRECT WASTE INVERT JANITOR SINK LAVATORY LAUNDRY TUB MAXIMUM MECHANICAL CONTRACTOR MAN HOLE MINIMUM MOP RECEPTOR MIXING VALVE(THERMOSTATIC) NEW WORK NOT APPLICABLE NORMALLY CLOSED NOT IN CONTRACT NORMALLY OPEN NOT TO SCALE PUMP PLUMBING CONTRACTOR PRESSURE REDUCING VALVE POUNDS PER SQUARE INCH EXISTING TO BE REMOVED ROOF DRAIN EXISTING TO BE RELOCATED REVOLUTIONS PER MINUTE REDUCED PRESSURE BACKFLOW PREVENTER RAIN WATER CONDUCTOR SLOPE SINK / SOUTH SHOCK ABSORBER W/ ACCESS PANEL SANITARY SEWAGE EJECTOR SUPPLY FIXTURE UNITS SHOWER SUMP PUMP SOIL STACK STORM DRAINAGE PIPING STACK VENT SAFEWASTE TUB TRAP PRIMER TYPICAL URINAL UNLESS NOTED OTHERWISE VENT PIPING VACUUM BREAKER VARIABLE FREQUENCY DRIVE VERIFY IN FIELD VENT THRU ROOF WASTE RISER WASHER BOX WATER CLOSET WALL CLEAN OUT WATER FOUNTAIN ATKIN OLSHIN SCHADE ARCHITECTS ABV AD AP BT CFH CLG CO CONT COTG DCW DFU DHW DHWR DN DI DW (E) EA EC ES EW EWC EWH ELEV EX FAI FC FCO FD FP FPC FS FT G GC GC GWH HP HR HY IW INV JS L LT MAX MC MH MIN MR MV (N) N/A NC NIC NO NTS P PC PRV PSI (R) RD (RL) RPM RPZ RWC s=02' S SA SAN SE SFU SH SP SS ST SV SW T TP TYP U U.N.O. V VB VFD VIF VTR W WB WC WCO WF SYMBOLS PLUMBING/FIRE PROTECTION COVER SHEET DATE 08.05.2016 SCALE 1/8" = 1'-0" DRAWN BY AG PF000 REVISIONS ISSUE DATE DESCRIPTION (E) 4" V UP CONNECT NEW 2" V TO (E) 4" RISER 1" DHWR 2" DHW 3" DCW (E) 4" GAS 1/2" DCW 1/2" DHW 1/2" DHW DN TO SH-1 1/2" DCW DN TO SH-1 (E) CLEAN-OUT TO REMAIN SH (E) 6" SAN 2 L 1 FD 1 (E) 6" SAN TP 1 SH 1/2" DCW 1/2" DHW 2 WC L 2" SAN 1 1 (E )4 "S AN 1-1/2" DCW (E) 1-1/2" DHWR (E) 3" DCW (E) 2" DHW (E) 2" A (E) 2" VAC (E) 6" G FD 1 (R) 6" SAN 1 1/2" SAN FD 3" SAN 1 L DEMO 6" SANITARY MAIN BETWEEN NEW PLUMBING FIXTURES. 1 WC 1 TP 1 SH 1/2" DCW WCO 1 1/2" DHW FD 1/2" DCW 1/2" DHW 1 WC (E) BELOW SLAB SANITARY PIPING TO BE REPLACED. PIPING CONTINUES TO SEWAGE EJECTOR PUMP IN MECH ROOM. L 1 1 3" SAN 1-1/2" DCW 2" SAN 1 1/2" SAN UP SH 1 3 WC MEPFP ENGINEER BRUCE E. BROOKS & ASSOC. 2209 Chestnut Street Philadelphia, PA 19103 215.569.0400 PLUMBING BASEMENT NEW WORK PLAN - DOMESTIC PF300 1/4" = 1'-0" 1 UP WCO (E) 6" SAN 1 PLUMBING BASEMENT DEMOLITION PLAN - SANITARY PF300 1/4" = 1'-0" 2 PLUMBING BASEMENT NEW WORK PLAN - SANITARY PF300 1/4" = 1'-0" University of Pennsylvania Perelman School of Medicine 125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107 PROVIDE LIGHT HAZARD COVERAGE PER NFPA-13. ATKIN OLSHIN SCHADE ARCHITECTS NOTE: 1. REMOVE EXISTING SPRINKLERS AND BRANCH LINES AS REQUIRED TO FACILITATE INSTALLATION OF NEW WORK. REUSE MAINS. 3700 Hamilton Walk, Philadelphia, PA 19104 2" V Richards Medical Research Laboratory - Additional Work Towers C&D (E) 6" SAN C:\Users\sas\Documents\13-129 Richards Add'l Scope_SAS.rvt 8/5/2016 12:36:35 PM UP 4 FIRE PROTECTION BASEMENT NEW WORK PLAN PF300 1/4" = 1'-0" PLUMBING/FIRE PROTECTION BASEMENT DATE DEMOLITION AND NEW 08.05.2016 WORK PLANS SCALE 1/4" = 1'-0" DRAWN BY AG PF300 REVISIONS ISSUE DATE DESCRIPTION PLUMBING FIXTURE SCHEDULE FIXTURE TAG WC-1 FLOOR-MOUNTED ELONGATED WATER CLOSET AUTO FLUSH LAVATORY SENSOR OPERATED L-1 SHOWER (NON-ADA) SH-1 SH-2 SHOWER (ADA-ROLL IN TYPE) BASIS OF DESIGN MANUFACTURER AND MODEL APPLICABLE STANDARD AMERICAN STANDARD "FLOWISE" (3641.001) ASME A112.19.2M ADA SIZE CONNECTION MOUNTING AND OUTLET MATERIAL VITREOUS CHINA DIMENSIONS FAUCETS, FITTINGS AND ACCESSORIES RIM HEIGHT TRAP FLOOR-MOUNTED 15" ADA 17"-19" 28-1/4"x17"x17-1/8" CW 4" 1-1/2" - ASME A112.19.2M DURAVIT "VERO" FAUCET ASME A112.18.1M CENTER FAUCET (045460..00) ANSI 117.1 ANSI Z 124.2 ASSE 1016 ASTM F 445 AQUARIUS MODEL STN 3679 SH 3P ANSI 117.1 ANSI Z 124.2 ASSE 1016 ASTM F 445 AQUARIUS MODEL S6430BF VITREOUS CHINA 23-5/8"x18-1/2" WALL MOUNTED THERMOFORMED FROM CONTINUOUS CAST ACRYLIC SHEET INTO ONE PIECE, SEAMLESS UNIT THERMOFORMED FROM CONTINUOUS CAST ACRYLIC SHEET INTO ONE PIECE, SEAMLESS UNIT 32" ADA 34" FLOOR MOUNTED - 36"x36"x77.75" FLOOR MOUNTED - 60"x30"x84" 1-1/4" 1/2" - - - - BASIS HW 1/2" - - 1. AUTO FLUSH VALVE: "SLOAN ROYAL" (TOP SPUD) MODEL 111-1.28.SMO, BATTERY POWERED, WITH OVER-RIDE BUTTON. 2. SEATS: "OLSONITE" , "BEMIS" OR "CHURCH" OPEN FRONT, LESS COVER, COMMERCIAL GRADE W/CHECK HINGE. 3. TRAP PRIMER: CONNECTION AS REQUIRED. 4. SUPPLY: CHROME PLATED BRASS, 1-1/2"TOP INLET SPUD. DESIGN CONSUMPTION: 1.28 GPF PRESSURE RANGE 30 PSI, FLUSHING-80 PSI STATIC DIRECT-FED SIPHON JET FLUSH ACTION. COLOR: WHITE BOLT CAPS 1. SENSOR OPERATED FAUCET: CHICAGO FAUCETS MODEL 116.850.AB.1 2. TERMOSTATIC MIXING VALVE (LEAD-FREE): WATTS MODEL LFUSG-B 3. DRAIN: GRID TYPE, POLISHED CHROME, VANDAL RESISTANT. 4. TRAP TYPE: "MCGUIRE" P-TRAP CHROME PLATED CAST BRASS BODY WITH CLEANOUT AND 17" GAUGE TUBULAR WALL BEND. 5. SUPPLY: "MCGUIRE" MODEL 2165CC 1/2"x3/8" COMPRESSION TEE 6. CARRIER: J.R. SMITH WALL MOUNTED CONCEALED ARM SUPPORT 7. UNDER-SINK PIPING COVERS: LAVGUARD2 OR EQUAL FRONT OVERFLOW BACK AND SIDE SPLASH SHIELDS 0.5 GPM FLOW RATE COLOR: WHITE CONTROL: LOW TEMPERATURE THERMOSTATIC SHOWER VALVE WITH ROUGH BRASS BODY, LEVER HANDLE, SCREWDRIVER SWEAT END CHECK STOPS, "POWERS" E 425 SHOWER HEAD: FLEXIBLE STAINLESS STEEL HOSE WITH IN-LINE VACUUM BREAKER, WITH ADJUSTABLE SPRAY SWIVEL JOINT, 60"LONG FLEXIBLE HOSE, 24" SLIDE BAR WITH ADJUSTABLE SHOWER MOUNT, "POWERS" NO. 141-918 DRAIN: 2" CAST BRASS CHROME PLATED SHOWER DRAIN CURTAIN ROD: 1" DIAMETER STAINLESS STEEL SHOWER RIGHT -OR LEFT HAND AS REQUIRED WITH SEAT AND SHELF WITH SOAP DISH, WITH RECESSED ROUND SHOWER LIGHT. SHOWER SHALL BE REINFORCED IN THE BACK WITH FIBERGLASS POLYESTER RESIN WHICH HAS BEEN TREATED WITH FLAME RETARDANT ADDITIVE. SHOWER SHALL BE PREDRILLED FOR ANY FIELD INSTALLATION REQUIREMENTS, UNIT SHALL HAVE ANTISKID FLOOR TREATMENT CONTROL: LOW TEMPERATURE THERMOSTATIC SHOWER VALVE WITH ROUGH BRASS BODY, LEVER HANDLE, SCREWDRIVER SWEAT END CHECK STOPS, "POWERS" E 425 SHOWER HEAD: FLEXIBLE STAINLESS STEEL HOSE WITH IN-LINE VACUUM BREAKER, WITH ADJUSTABLE SPRAY SWIVEL JOINT, 60"LONG FLEXIBLE HOSE, 24" SLIDE BAR WITH ADJUSTABLE SHOWER MOUNT, "POWERS" NO. 141-918 GRAB BAR: 1-1/4" TO 1-1/2" O.D. STAINLESS STEEL DRAIN: 2" CAST BRASS CHROME PLATED SHOWER DRAIN CURTAIN ROD: 1" DIAMETER STAINLESS STEEL NO THRESHOLD SHOWER RIGHT -OR LEFT HAND AS REQUIRED WITH SEAT AND SHELF WITH SOAP DISH, WITH RECESSED ROUND SHOWER LIGHT. SHOWER SHALL BE REINFORCED IN THE BACK WITH FIBERGLASS POLYESTER RESIN WHICH HAS BEEN TREATED WITH FLAME RETARDANT ADDITIVE. SHOWER SHALL BE PREDRILLED FOR ANY FIELD INSTALLATION REQUIREMENTS, UNIT SHALL HAVE ANTISKID FLOOR TREATMENT MIXED HW OUTLET THERMOMETER FINISHED FLOOR TAMPER RESISTANT TEMPERATURE CONTROL STRAINER HEAD WATERPROOFING MEMBRANE (WHERE PROVIDED FOR BY ARCHITECT) UNION LIQUID FILLED THERMOSTATIC MIXING VALVE (FULL LINE SIZE) VIBRATION ISOLATOR (WHERE APPLICABLE, REFER TO SPECIFICATIONS) FLASHING COLLAR SEEPAGE OPENINGS HANGER ROD UNISTRUT STRAP AND LOCKING NUT PRE-INSULATED RIGID CLAMP INSERT WITH VAPOR BARRIER (KLO-SHURE OR EQUAL) LOCK NUT EXPANSION SHIELD SUPPORT NUT STANDARD ADJUSTABLE CLEVIS HANGER PER SPECIFICATIONS THERMOMETER STRAINER HW INLET SHUT OFF CW INLET PRE INSULATED CLAMP INSERT SEE FLOOR PLAN FOR PIPE SIZE VAPOR SEAL BUTT JOINT FLOOR SLAB MEPFP ENGINEER BRUCE E. BROOKS & ASSOC. 2209 Chestnut Street Philadelphia, PA 19103 215.569.0400 BALL VALVE CONCRETE STRUCTURE ABOVE. SEE ARCH DWGS DRAIN BODY PLAN VIEW - CLAMP INSTALLATION OUTLET CONNECTION PIPE HANGER DETAIL PF800 1" = 1'-0" CONNECT DOMESTIC COLD WATER, DOMESTIC HOT WATER, AND DOMESTIC HOT WATER RETURN LINES TO EXISTING MAINS AT MECHANICAL ROOM WALL 2" V LAVATORY 1/2" DCW 1/2" DCW 1/2" DHW 1/2" DHW 1/2" DCW 1/2" DHW 1/2" DCW 1-1/2" DCW 1/2" DHW CONNECT NEW 2" V TO (E) 4" V RISER 1-1/2" DCW 1" DHWR 2" DHW WC L WC L 1 1 1 1 3" DCW 4" SAN DOWN IN WALL WCO FLOOR DRAIN C:\Users\sas\Documents\13-129 Richards Add'l Scope_SAS.rvt 8/5/2016 12:36:37 PM FLOOR 1/2" TYPE "L" COPPER PRIMER, SAFEWASTE TO TRAP SH L WC L SH WC SH FD 1 1 1 1 1 1 1 1 TP TP 1 1 FD FD 1 1 (E) 4" SAN, 60 DFU'S, TO EXISTING SEWAGE EJECTOR IN MECH ROOM 2" SAN 3" SAN BASEMENT DEEP SEAL TRAP 6 5 P-TRAP PRIMER LAV PF800 12" = 1'-0" BASEMENT DOMESTIC PLUMBING SCHEMATIC PF800 N.T.S. 7 WCO 4" SAN BASEMENT SANITARY PLUMBING RISER DIAGRAM PF800 N.T.S. FD SH 1 2 BASEMENT 3" SAN 1-1/2" SAN 2" SAN (E) 6" SAN 3700 Hamilton Walk, Philadelphia, PA 19104 4 Richards Medical Research Laboratory - Additional Work Towers C&D FLOOR DRAIN DETAIL PF800 12" = 1'-0" University of Pennsylvania Perelman School of Medicine 3 P-MIXING VALVE PF800 12" = 1'-0" 125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107 2 ATKIN OLSHIN SCHADE ARCHITECTS SINGLE PIPE HANGER SECTION VIEW PLUMBING/FIRE PROTECTION SCHEDULES AND DATE DETAILS 08.05.2016 SCALE As indicated DRAWN BY AG PF800 REVISIONS ISSUE DATE ABBREVIATIONS ELECTRICAL SYMBOL LIST POWER EWC ELECTRIC WATER COOLER - MOUNT RECEPTACLE WITHIN COOLER ENCLOSURE. LIGHTING (NOTE: UPPER CASE LETTER INDICATES TYPE, LOWER CASE LETTER INDICATES SWITCHING ARRANGEMENT) C2 c A2 c LINEAR STRIP FIXTURE DUPLEX RECEPTACLE M1 B1 d d DOWNLIGHT f WALL BRACKET FIXTURE QUADRAPLEX RECEPTACLE F F DUPLEX GROUND FAULT RECEPTACLE DUPLEX GROUND FAULT RECEPTACLE - MOUNTED ABOVE COUNTER HEIGHT, BACKSPLASH, OR AS INDICATED ON DRAWINGS DUPLEX RECEPTACLE - MOUNTED ABOVE COUNTER HEIGHT, BACKSPLASH, OR AS INDICATED ON DRAWINGS EM X F X B EMERGENCY BATTERY PACK X EXIT SIGN A LIGHTING FIXTURE ON EMERGENCY SINGLE RECEPTACLE - SPECIAL PURPOSE (AS NOTED ON DRAWINGS) SWITCHING FLOOR MOUNTED DUPLEX RECEPTACLE FLOOR MOUNTED QUADRAPLEX RECEPTACLE AV S S3 COMBINATION POWER, DATA & AV FLOOR BOX CEILING MOUNTED DUPLEX RECEPTACLE SURFACE MOUNTED MULTI OUTLET RACEWAY ASSEMBLY J J J PB SINGLE POLE SWITCH S4 THREE WAY AND FOUR WAY SWITCHES SD SINGLE POLE DIMMING SWITCH SOS WALL MOUNTED OCCUPANCY SENSOR WITH OVERRIDE SWITCH SVS WALL MOUNTED VACANCY SENSOR WITH OVERRIDE SWITCH JUNCTION BOX (FLOOR, CEILING, WALL) OS OS OCCUPANCY SENSOR (CEILING, WALL) PULL BOX VS VS VACANCY SENSOR (CEILING, WALL) DS DS VACANCY SENSOR (CEILING, WALL) MOTOR T TRANSFORMER GROUND ROD SYSTEMS FURNITURE P = POWER, D = DATA J J P D CIRCUIT PROTECTION SM FLOOR MOUNTED JUNCTION BOX CONNECTION POINTS, JUNCTION BOXES PROVIDED BY ELECTRICAL CONTRACTOR MANUAL MOTOR STARTER DESCRIPTION 1P 2P 3P 4P A AB AC AFCI AFF AIC AFG ARCH ATS BLDG C CATV CB CD CKT CMT C.T. DISC DO DWG (E) EC (ER) EWC FA FAAP FACP FLA GC GFCI GND HP HV Hz IG JB KCMIL KVA KW ONE POLE TWO POLE THREE POLE FOUR POLE AMPERE ABOVE CEILING ABOVE COUNTER ARC FAULT CURRENT INTERRUPTER ABOVE FINISHED FLOOR AMPS INTERRUPTING CURRENT ABOVE FINISHED GRADE ARCHITECT AUTOMATIC TRANSFER SWITCH BUILDING CONDUIT CABLE TELEVISION CIRCUIT BREAKER CANDELA CIRCUIT EMPTY CONDUIT CURRENT TRANSFORMER DISCONNECT DISCONNECT DRAWING EXISTING TO REMAIN ELECTRICAL CONTRACTOR EXISTING TO BE RELOCATED ELECTRIC WATER COOLER FIRE ALARM FIRE ALARM ANNUNCIATOR PANEL FIRE ALARM CONTROL PANEL FULL LOAD AMPS GENERAL CONTRACTOR GROUND FAULT CIRCUIT INTERRUPTER GROUNDED HORSEPOWER HIGH VOLTAGE HERTZ (CYCLE) PER SECOND ISOLATED GROUND JUNCTION BOX THOUSAND CIRCULAR MILS KILOVOLT AMPERE KILOWATT DISCONNECT SWITCH, UNFUSED TYPE LP LTG MCB NDO (ME) MISC MLO MOA MOD MTD MTG MTS (N) N/A NEC NIC NL # NTS P PB PH PNL PVC PWR (R) (RE) REC SCP SWBD SYS TC TEL/DATA TEL TTB TVSS TYP UON V W WP XFMR + #1/E300 LIGHTING PANEL LIGHTING MAIN CIRCUIT BREAKER MAIN DISTRIBUTION PANEL MODIFY EXISITNG MISCELLANEOUS MAIN LUGS ONLY MULTI-OUTLET ASSEMBLY MOTOR OPERATED DISCONNECT SWITCH MOUNTED MOUNTING MANUAL TRANSFER SWITCH NEW NOT APPLICABLE NATIONAL ELECTRICAL CODE NOT IN CONTRACT NIGHT LIGHT NUMBER NOT TO SCALE POLE PULL BOX PHASE PANEL POLYVINYL CHLORIDE CONDUIT POWER REMOVE EXISTING RELOCATE EXISTING RECESSED SECURITY CONTROL PANEL SWITCHBOARD CONNECTION TO SYSTEMS FURNITURE TIME CLOCK TELEPHONE/DATA TELEPHONE TELEPHONE TERMINAL BOARD TRANSIENT VOLTAGE SURGE SUPPRESSION TYPICAL UNLESS OTHERWISE NOTED VOLT WATT WEATHERPROOF TRANSFORMER INDICATES MOUNTED ABOVE CENTER OR AS NOTED ON DWG. DETAIL NUMBER/DRAWING NUMBER DISCONNECT SWITCH, FUSED TYPE DATA # = NUMBER OF DROPS # DATA COMMUNICATION OUTLET PANELBOARDS # FLOOR MOUNTED COMBINATION DATA OUTLET SURFACE MOUNTED ELECTRICAL PANELBOARD RECESSED MOUNTED ELECTRICAL PANELBOARD AUDIO VISUAL SECURITY SYSTEM FIRE ALARM BLACK KEY ACCESS DC DOOR STRIKE FIRE ALARM STROBE LIGHT CR CARD ACCESS READER DUCT MOUNTED SMOKE DETECTOR PB PANIC BUTTON FOR ADA BATHROOMS FIRE ALARM MANUAL PULL STATION F FIRE ALARM STROBE LIGHT & HORN COMBINATION F D C:\Users\prd\Documents\13-129 Richards Add'l Scope_prd.rvt 8/5/2016 12:37:29 PM BK F FACP FIRE ALARM CONTROL PANEL FAAP FIRE ALARM ANNUNCIATOR PANEL NAC NOTIFICATION APPLIANCE CIRCUIT EXTENDER PANEL FMM FIRE ALARM MONITOR MODULE FRM FIRE ALARM RELAY MODULE FS SPRINKLER FLOW SWITCH TS SPRINKLER TAMPER SWITCH SD SMOKE DAMPER PTD POWER TRANSFER DEVICE ELECTRICAL DRAWING SCHEDULE SHEET NUMBER E000 E400 E401 E402 E700 SHEET NAME ELECTRICAL COVER SHEET ELECTRICAL BASEMENT PLANS ELECTRICAL LEVEL 1 NEW WORK PLAN - POWER ELECTRICAL LEVEL 7, 8 NEW WORK PLAN - POWER ELECTRICAL SCHEDULES 100% CONSTRUCTION DOCUMENTS 07/15/2016 ● ● ● ● ● NOT IN CONTRACT ELECTRICAL COVER SHEET DATE 08.05.2016 SCALE 12" = 1'-0" DRAWN BY PRD E000 3700 Hamilton Walk, Philadelphia, PA 19104 CEILING MOUNTED AV BOX MEPFP ENGINEER BRUCE E. BROOKS & ASSOC. 2209 Chestnut Street Philadelphia, PA 19103 215.569.0400 AV DISTRIBUTION PANEL Richards Medical Research Laboratory - Additional Work Towers C&D WALL MOUNTED AV BOX University of Pennsylvania Perelman School of Medicine AV SYSTEMS PANEL OR TERMINAL CABINET (AS INDICATED ON DRAWING) 125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107 AV FLOOR BOX ATKIN OLSHIN SCHADE ARCHITECTS AV REVISIONS GENERAL NOTES: ISSUE DATE 1. ALL EQUIPMENT & DEVICES ARE NEW UNLESS OTHERWISE NOTED. 2. ALL EQUIPMENT & DEVICES SHALL BE CIRCUITED TO PANEL CBRP SEC. 2 UNLESS OTHERWISE NOTED. 3. REFER TO ELECTRICAL CONNECTION SCHEDULE ON DRAWING E700 FOR CIRCUITING OF MECHANICAL EQUIPMENT. 4. COORDINATE ALL ROUTING OF NEW BRANCH CIRCUITS WITH ARCHITECT PRIOR TO ROUGH-IN. DESCRIPTION D-4 (E)SECURITY/ ACCESS PANEL (E)PANEL CBRP-SEC. 1 (E)PANEL CBRP-SEC. 2 (E)PANEL CBLP F ACCESSIBLE GENDER NEUTRAL RESTROOM (15) CONNECT TO EXISTING FIRE ALARM NOTIFICATION LOOP IN ADJACENT CORRIDOR. (TYPICAL FOR 2) 1 C003B D-5 PB C003B VESTIBULE C003 (E) F F C003 C003A GENDER NEUTRAL RESTROOM DEMOLISH ALL EXISTING LIGHTING FIXTURES, WIRING DEVICES & ASSOCIATED IN THIS AREA BACK TO SOURCE. REFER TO DETAIL 1/E400 AND 3/E400 FOR POWER AND LIGHTING PLAN IN THIS AREA 1 C003A F (15) PB 1 MEPFP ENGINEER BRUCE E. BROOKS & ASSOC. 2209 Chestnut Street Philadelphia, PA 19103 215.569.0400 ELECTRICAL BASEMENT BATHROOM NEW WORK PLAN - POWER & SYSTEMS E400 1/4" = 1'-0" FOR ALL NEW NORMAL LIGHTING FIXTURES: EXTEND EXISTING NORMAL LIGHTING BRANCH CIRCUIT IN CORRIDOR FROM PANEL CBLP, CIRCUIT 2 TO NEW NORMAL LIGHTING FIXTURES IN BATHROOMS & VESTIBULE. a F1 a b os SS F1 a CONDUIT ROUTING FROM 1ST FLOOR DOOR/BOLLARDS. TO ELECTRICAL ROOM. A-4 (E) (E)DISCONNECT SWITCH. CONDUIT PENETRATING WALL TO BE RELOCATED/RAISED DUE TO NEW MECHANICAL DUCT PENETRATION. COORDINATE WORK WITH MECHANICAL CONTRACTOR. os F1 FOR NEW EMERGENCY LIGHTING FIXTURE: EXTEND EXISTING EMERGENCY LIGHTING BRANCH CIRCUIT IN ADJACENT CORRIDOR FROM PANEL ELB, CIRCUIT 1 TO NEW EMERGENCY LIGHTING FIXTURE IN VESTIBULE. EM/NL SS UP(E)480/277V, 3-PHASE PANEL F1 a b os a A-1 b F1 a 3 ELECTRICAL BASEMENT BATHROOM NEW WORK PLAN - LIGHTING E400 1/4" = 1'-0" C:\Users\prd\Documents\13-129 Richards Add'l Scope_prd.rvt 8/5/2016 12:37:33 PM 2 ELECTRICAL BASEMENT NEW WORK PLAN - POWER E400 1/4" = 1'-0" N2 ELECTRICAL BASEMENT PLANS DATE 08.05.2016 SCALE 1/4" = 1'-0" DRAWN BY Author E400 3700 Hamilton Walk, Philadelphia, PA 19104 (E) Richards Medical Research Laboratory - Additional Work Towers C&D (E) b University of Pennsylvania Perelman School of Medicine A-2 125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107 A-3 ATKIN OLSHIN SCHADE ARCHITECTS N2 REVISIONS ISSUE DATE DESCRIPTION D-4 GENERAL NOTES: 1. ALL EQUIPMENT & DEVICES ARE EXISTING UNLESS OTHERWISE NOTED. KEYED NOTES: 3 D-5 PROVIDE CONDUIT TO SECURITY/ACCESS CONTROL PANEL IN THE BASEMENT LEVEL TELE/DATA ROOM. DROP TO BASEMENT LEVEL AT BOLLARD. REFER TO BASEMENT POWER PLAN 2/E400 FOR DIAGRAMMATIC CONDUIT ROUTE AND PANEL LOCATION. REFER TO ARCHITECTURAL DETAILS FOR CONDUIT ROUTING AT BOLLARDS. PROVIDE NEW BRANCH CIRCUIT FROM BASEMENT PANEL CBRP, SECTION 2, CIRCUIT NUMBER 3. PROVIDE CONDUIT DOWN TO BASEMENT LEVEL AT DOOR FRAME LOCATION. REFER TO BASEMENT POWER PLAN 2/E400 FOR DIAGRAMMATIC CONDUIT ROUTE. COORDINATE CONDUIT ROUTING WITH ARCHITECT PRIOR TO ROUGH-IN. PROVIDE CONTROL CONDUIT TO PTE CONTROLLER AT BOLLARD, ROUTED AT BASEMENT LEVEL. MEPFP ENGINEER BRUCE E. BROOKS & ASSOC. 2209 Chestnut Street Philadelphia, PA 19103 215.569.0400 ALTERNATE NO. 2: ADA OPERATORS AT BOLLARD (TYPICAL FOR 2) BASE BID: ELECTRIC STRIKES ARE RELEASED BY BLACK KEY/CARD READER. CR PTE 2 3 J ES ES 1 2 REMOVE ALL EXISTING ACCESS CONTROL SYSTEMS & ASSOCIATED DEVICES BACK TO SOURCE. 1 C:\Users\prd\Documents\13-129 Richards Add'l Scope_prd.rvt 8/5/2016 12:37:35 PM ELECTRICAL LEVEL 1 NEW WORK PLAN - POWER E401 1/4" = 1'-0" PTE CR 1 University of Pennsylvania Perelman School of Medicine A-2 MOUNT DEVICES ON PEDESTAL 125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107 A-3 ATKIN OLSHIN SCHADE ARCHITECTS J ELECTRICAL LEVEL 1 NEW WORK PLAN POWER DATE 08.05.2016 SCALE 1/4" = 1'-0" DRAWN BY PRD E401 3700 Hamilton Walk, Philadelphia, PA 19104 2 PROVIDE CONDUIT FROM SECURITY/ACCESS CONTROL PANEL LOCATED IN BASEMENT LEVEL TELE/DATA ROOM TO BACK BOX FOR DOOR CONTROL DEVICE. PROVIDE SPARE CONDUIT PARALLEL FOR ADDITIONAL DOOR CONTROL EQUIPMENT. REFER TO BASEMENT POWER PLAN 2/E400 FOR DIAGRAMMATIC CONDUIT ROUTE AND PANEL LOCATION. Richards Medical Research Laboratory - Additional Work Towers C&D 1 REVISIONS ISSUE DATE DESCRIPTION GENERAL NOTES: 1. ALL EQUIPMENT & DEVICES ARE EXISTING UNLESS OTHERWISE NOTED. KEYED NOTES: 1 2 DISCONNECT, EXTEND AND RECONNECT EXISTING BRANCH CIRCUIT WIRING FROM REMOVED EXHAUST FAN TO NEW EXHAUST FAN FROM PANEL PNH8, CIRCUIT (38,40,42) - 15A, 3P. NEW VFD LOCATION IN PLACE OF REMOVED MOTOR STARTER DISCONNECT FOR EXISTING TOILET ROOM EXHAUST FAN. B-1 (E)PANEL EL7 EF (E)PANEL C7LP 2 (E)FOR MECH. RM. EF (E)PANEL 'PNH8' (E)PANEL 'SB8' B-8 2 ELECTRICAL LEVEL 8 NEW WORK PLAN - POWER E402 1/4" = 1'-0" EXHAUST FAN LOCATION ON 8TH FLOOR ABOVE C:\Users\prd\Documents\13-129 Richards Add'l Scope_prd.rvt 8/5/2016 12:37:38 PM DN University of Pennsylvania Perelman School of Medicine 2 125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107 VFD FOR EF-2. CONFIRM INSTALLED BY DIV. 26 ATKIN OLSHIN SCHADE ARCHITECTS 1 3700 Hamilton Walk, Philadelphia, PA 19104 (E) 45kVA 480V 208Y/120V Richards Medical Research Laboratory - Additional Work Towers C&D MEPFP ENGINEER BRUCE E. BROOKS & ASSOC. 2209 Chestnut Street Philadelphia, PA 19103 215.569.0400 (E)PANEL C7RP ELECTRICAL LEVEL 7, 8 NEW WORK PLAN POWER 1 ELECTRICAL LEVEL 7 NEW WORK PLAN - POWER E402 1/4" = 1'-0" DATE 08.05.2016 SCALE 1/4" = 1'-0" DRAWN BY PRD E402 REVISIONS ISSUE DATE SYMBOL TAG EF EF NO. 1 2 ELECTRICAL CONNECTION SCHEDULE LOCAL LOCAL LOCAL LOCAL LOCAL DISCONNECT DISCONNECT DISCONNECT DISCONNECT DISCONNECT ELECTRICAL ELECTRICAL ELECTRICAL ELECTRICAL DEVICE DEVICE DEVICE DEVICE DEVICE CHARACTERISTICS CHARACTERISTICS CHARACTERISTICS CHARACTERISTICS STARTER STARTER STARTER STARTER STARTER STARTER STARTER STARTER MAN MOTOR MAN MOTOR SW SW COMBINATION COMBINATION COMBINATION ACCESSORIES ACCESSORIES FUSED UNFUSED FUSED UNFUSED SWITCH SWITCH SWITCH SWITCH MCP HOA PILOT V/PH/HZ MCA MOCP HP OL PILOT DIV TYPE SIZE DIV 120/1/60 460/3/60 1.25 3.75 15 15 1/4 1-1/2 X 26 23 WIRE 2#12 + 1#12 GND 3#12 + 1#12 GND VFD Panel Circuit Number CBRP-SEC. 2 PNH8 2 38,40,42 DESCRIPTION NOTES: 1. VFD FOR EF-2 PROVIDED/FURNISHED BY DIV. 23 AND INSTALLED BY DIV. 26. 2. EF-1 AND EF-2 TO BE CONNECTED TO EXISTING BAS PANEL SYSTEMS. 3. FOR EF-2: UTILIZE EXISTING 480V, 3-PHASE, 20A-3P CB MADE AVAILABLE BY THE DEMOLITION OF THE EXISTING EF. CONFIRM ALL CONNECTIONS PRIOR TO ROUGH-IN. NOTES: LIGHTING FIXTURE SCHEDULE DESCRIPTION NO. TYPE WATTS T8 17 VOLTS MOUNTING REMARKS 2. SUBSTITUTIONS FOR THE SPECIFIED LIGHTING PRODUCTS ARE ACCEPTABLE FOR PART OF THE SPECIFIED PRODUCTS AND WILL BE CONSIDERED. THE SPECIFIED PRODUCTS ARE PART OF THE BASIS OF DESIGN. SUBSTITUTIONS ARE AT THE DISCRETION OF THE ARCHITECT. THE PROPOSED SUBSTITUTION LIGHTING PRODUCT MUST BE EQUAL IN EVERY ASPECT OF THE SPECIFIED FIXTURE. 3. ALL COLORS & FINISHES WILL BE SELECTED BY THE ARCHITECT FROM MANUFACTURER'S COMPLETE AND CUSTOM LINE. 2-5/8"W X 3.75"H X 2' L SLIM, LOW PROFILE SURFACE MOUNTED. FROSTED, ACRYLIC EXTRUDED LENS, SLIM END PLATES. INTEGRAL ELECTRONIC BALLAST. WALL MOUNTED H.E. WILLIAMS LLMS-2-1-17-E-SQ 1 RECESSED 6" APERTURE CFL LENSED DOWNLIGHT. WITH SHOWER TRIM PRESCOLITE LF6CV-26-EB-X-6CFV-X-DL-WT 1 20 277V WALL 4. ALL BALLASTS SHALL BE ELECTRONIC. 277V RECESSED ELECTRICAL PANEL SCHEDULE 3 PHASE, 4 WIRE 208/120V 10 KAIC SURFACE MOUNTED LOCATION: TR P CKT 1 20 A 1 3 20 A 1 5 --7 --9 --11 --13 --15 --17 --19 --21 --23 --25 --27 --29 --31 --33 --35 --37 --39 --41 --- (EXISTING) MAIN BUS RATING: MAINS: NEUT. BUS: GRD. BUS: ISOL GRD. BUS: DESCRIPTION RCPTL-BATHROOMS (N) DOOR MOTORS (N) Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space A 0.36 B NOTES: 1. (N) DENOTES NEW CIRCUIT BREAKER C A 0.06 0.72 B C 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 TOTAL KVA A: TOTAL KVA B: TOTAL KVA C: C:\Users\prd\Documents\13-129 Richards Add'l Scope_prd.rvt 8/5/2016 12:37:40 PM PANEL CBRP-SEC. 2 0.00 0.42 0.72 0.00 150 A MCB X X DESCRIPTION EF-1 (N) Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space TOTAL CONNECTED KVA: TOTAL CONNECTED AMPS: P 1 --------------------- TR CKT 20 A 2 -4 -6 -8 -10 -12 -14 -16 -18 -20 -22 -24 -26 -28 -30 -32 -34 -36 -38 -40 -42 1.14 kVA 3.17 A ELECTRICAL SCHEDULES DATE 08.05.2016 SCALE 12" = 1'-0" DRAWN BY PRD E700 3700 Hamilton Walk, Philadelphia, PA 19104 30 MEPFP ENGINEER BRUCE E. BROOKS & ASSOC. 2209 Chestnut Street Philadelphia, PA 19103 215.569.0400 26 Richards Medical Research Laboratory - Additional Work Towers C&D CF26 University of Pennsylvania Perelman School of Medicine N2 VA/ FIXTURE MANUFACTURER & CATALOG NUMBER 125 S 9TH STREET SUITE 900 PHILADELPHIA PA 19107 F1 DESCRIPTION ATKIN OLSHIN SCHADE ARCHITECTS TYPE 1. ELECTRICAL CONTRACTOR SHALL REFER TO ARCHITECTURAL DRAWINGS FOR SECTIONS, ELEVATIONS & ROOM FINISH SCHEDULES, FOR CEILING TYPES AND PROVIDE APPROPRIATE MOUNTING HARDWARE, PLASTER FRAMES, PENDANTS, ETC. USE THE LIGHTING FIXTURE SCHEDULE AS A GUIDE ONLY.