PRECISE Load Break Switch Type SF6 Standard Feature Performance • The puffer interrupter has designed for more 400 operations a rated normal current interruption and 2000 operations at on-load. • 24 VDC Battery is capable to sustain operation in the event of loss of AC power source. • Toggle mechanism could sectionalize the feeder line in short time. (Close/ Open within 1 sec.) • The switch has been tested in accordance with IEC requirement. Electrical Remote (SCADA) • Different control packages are available permitting either onsite operation only or remote (SCADA) operation from a central control station. Switch Control Equipment The control equipment shall be contained in a control cabinet. The cabinet shall be suitable for outdoor installation on a pole approximately 1.5-3 meters above ground level. The control cabinet will be supplied with : 1. Miniature circuit breaker and fuse for the control circuit 2. Surge protection equipment 3. SCADA interface (control, status and alarm) 4. Two (2) 12 V DC batteries and charger 5. Selector switch for LOCAL/REMOTE 6. Indicating lamps (LOCAL/REMOTE, ON/ OFF and etc.) 7. Alarm lamps and interlocking component (Low gas pressure and Power supply monitoring) 8. Operation counter 9. Weatherproof fitting for control cable Certificate Sale Office: PRECISE INTERNATIONAL CORPORATION LTD. Address : 1842 Krungthep-Nonthaburi Rd., Bangsue, Bangkok, 10800 Thailand Telephone :(662) 910 9700-12 Telefax: (662) 910 9713-4 http://www.precise.co.th 06/07 : Rev.0 PRECISE Load Break Switch Type SF6 Performance Data Descriptions 22 kV Manufacturer 33 kV Precise Electro Mechanical Works Co., Ltd. Model / Type or Catalogue No. ORAP21-396-20MT Rated voltage (kV) 24 kV 33 kV Rated frequency (Hz) 50 Rated normal Current (A) (max.) 630 400 Rated symmetrical interrupting current 630 Rated short-time withstand current, 1 sec (kA r.m.s.) 12.5 Rated short-time making current (kA peak) 31.5 Rated impulse withstand voltage (kV peak) 125 170 Rated mainly active load breaking capacity (A) 630 Rated transformer off-load breaking capacity (A) 21 Rated cable charging breaking capacity (A) 10 Maximum temperature of (K) - Contacts - Current Carrying Parts - Mechanical Parts 30 30 5 Number of operations at rated normal current Interruption 400 Mechanical endurance, in number of operations 2,000 2 Rated pressure range of SF6 gas (kgf/cm ) 1.2 2 Pressure of SF6 when locking device operates (kgf/cm ) 0.7 Protection degree of assembled enclosure IP 67 (SF6 tank) Operation force of handle (kgf) 35 max Conductor material of main circuit lead Copper 200 mm 120 mm2 Creepage distance of porcelain bushing (mm) 600 900 Net weight (kg) 240 230 Cross section of main circuit lead 2 Factsheet No. : PMW-OSW20-0001 Factsheet State 3 Issued On : 20/07/2007 Revision No. 0 Date : 20/07/2007