B7 Gas Insulated Load Break Switch C O N T E N T S For Underground Features B7-2 Rated Specification / Controller B7-4 Dimension B7-6 Control Circuit Diagram B7-9 For Pole Mounted Features B7-10 Rating & Performance / Controller B7-12 Dimension B7-14 Control Circuit Diagram & Controller Connection Diagram B7-16 Certification B7-17 Gas Insulated Load Break Switch _ Feature For Underground(GLBS) VITZRO TECH Gas Insulated Load Break Switch is a SF6 gas-insulated multi-circuit switch that is installed on ground or underground at 22.9kV-Y or 22kV-△ underground distribution line. It is an optimal product that uses SF6 gas as the insulating medium superior for its arc extinguishing capability and the operating mechanism is a single-operation method with 3-ground circuit for distinguishing the lines and branch lines. B7-2 VITZROTECH Switch Body It is a 3-phase integrated operating, single-tank type that consists of switch, auxiliaries based on the operation method, cabinet based on the installation type and so on. It is equipped with a ground switch for each circuit and it is designed so that the operating state of the ground switch can be easily checked outside. B7 Bolts are not used in order to prevent gas leak and it is completely enclosed by TIG welding. The insulating material used in the inner part is the bisphenol, epoxy resin with excellent resistance to electrical and mechanical characteristics and SF6 gas. ▶ Operating Device The operating device of the switch is divided into a main circuit part and earth part. It is designed to require no special skills and all 3-phase contacts are opened / closed simultaneously and the switching speed is always consistent regardless of the operation method. An automatic switch enables the mechanical closing/opening, electrical closing/opening and remote operation (after installing a separate terminal and communication device) of the main circuit part. However, the closing (earth)/opening of ground switch part can be manually operated on site. An interlock device is applied so that the closing (earth) operation of the ground switch is not done unless the main circuit is opened and the closing operation of the main circuit is impossible at closing (earth) state of the ground switch. ▶ Bushing Part It is structured to connect to the 600A deadbreak-type connector that is regulated in IEEE386 and it is installed in the body part using bolts and it is in an O-ring enclosed structure for full enclosure. A flange is made up of epoxy material and the flange surface that is connected to the body is connected based on IEEE386. ▶ Cabinet The cabinet and the base are made up of stainless steel plate [KSD 3705 3(Type & Mark), STS304L] with size of 2.0mm or bigger and 3.0mm or bigger respectively. It is structured so that water does not form a pool in the cabinet. The cabinet is designed and manufactured so that it is easy to connect and disconnect cables, detect current, check earth and phase and so forth by opening the cabinet door easily. In addition, automatic voltage transformer (PT) for power control is installed in the lower part of the body and a door is installed in the lower-side part of the cabinet for easy replacements. The cabinet is coated in Munsell NO. 7.5GY 3.5/2 (green color) when installed in green belt and in Munsell NO. 5Y 7/1 (gray color) when installed in sidewalk and other areas. Product Standards •ES - 5925 - 0002(2008. 12. 30) •IEC 60265-1(1998) •IEC 60694(2002) •IEEE C37.71(2001) •IEEE C37.90.1(2002) ▶ Gas Insulated Load Break Switch B7-3 Gas Insulated Load Break Switch The body cabinet is 3mm or bigger and the front part where the bushing is mounted is 5mm or bigger and both are manufactured using a stainless steel plate [KSD 3705 3 (Type & Mark), STS304L] that can endure the inner gas pressure. It is designed to have a stable structure with strong electrical and mechanical characteristics and durability. Ratings Type 33-D-M-125 (Manual Type) 44-D-M-125 (Manual Type) Rated Voltage 25.8kV Rated Current 600A Rated Frequency 60Hz Rated Short Time Withstand Current 2.5 kA / 1s Rated Closing Current 32.5 kAp Load Current (100%) Switching Capability 600A Load Current(5%) 30A LOOP Current 600A Exciting Current 21A Cable Charging Current(100%) 25A Cable Charging Current(30%) 7.5A Line Charging Current 1.5A 5000 times Voltage Switching Closing - Opening Capability Opening - Contact 1000 times Power Frequency Withstand Voltage Switching Capability 60kV /1min Lightning Impulse Withstand Voltage (1.2×50 μs) 125kV DC 78kV/15min DC Withstand Voltage Minimum Discharge Extinction Voltage 19kV - Rated Operating Voltage SF6 Gas-Filled Pressure Weight Function & Performance 44-D-A-125 (Automatic Type) About 230kg 0.07 MPa・G(at 20℃) About 300kg AC220V, DC24V About 580kg Gas Pressure Gauge It is installed with a gas pressure gauge with diameter of 65mm or above in order to easily check the inner gas pressure and a scale mark is divided into colors for the normal operating pressure range with MPa unit marked. Counter A mechanical counter for switching operation of each circuit is mounted and reset of it is impossible. Earth Terminal A clamp-type earth terminal is installed in the switch body and more than 1 terminal is installed for each circuit at Bus Bar so that it can be connected to the cable earth line that connects to the switch and the switch earth line (22~205㎟) Body Fixing Bracket A bracket with holes of 14mm in diameter (for fixed bolts) is welded and mounted in the lower part of the body to fix the switch and it should be strong enough to support the weight of the body regardless of the installation direction. Towing Hook In case of the switch body or for on-ground installation type, a towing hook is installed at the cabinet for lifting. Gas-Injecting Valve The body consists of a valve to inject gas and it is located in a place where it cannot be easily damaged due to the delivery, installation and operation. Hot-line Display Lamp A switch installed on ground is equipped with a hot-line display lamp to distinguish whether there is a hot-line or not for each circuit. B7-4 VITZROTECH Gas Insulated Load Break Switch Controller Structure B7 •Modem Installing Tool •Plug Socket •Voltage Supply Unit : AC220V/DC24V Functions Our control box is equipped with the following functions. 1) Control Function : It can control the switch. - Operation Switch“Close/Open” 2) Status Information Display: It displays the switch state. - Operation Switch“Close/Open” - Operation Lock“Control Box/Body” - Storage Battery Test “Charging Part/Storage Battery” 3) Selection Switch: It sets the control conditions. - Control Power“ON/OFF (Toggle)” - Selection of Operation“Site/Remote (Toggle)” - Operation Lock“Lock/Unlock (Momentary)” 4) Others - Connector to connect to FRTU (Located at the upper part of control part) - 220V plug socket Gas Insulated Load Break Switch B7-5 Gas Insulated Load Break Switch •Control Part •Battery : DC 24V(12V, 2EA) For Underground 44-D-A-125(4-Circuit Automatic Type) No. Name of parts 8 9 10 11 12 13 14 P.T Actuator Earth Bushing Earth Terminal Storage Battery Rating Plate Gas Pressure Gauge No. Name of parts Q’ ty No. 1 4 1 7 2 1 1 1 2 3 4 5 6 7 Name of parts Q’ ty Cabinet 1 Controller 1 Power Bushing 1 Power Elbow ASS’ y 1 Gas-Injecting Part ASS’y 1 Current Transformer 12 Main Circuit Bushing 12 44-D-M-125(4-Circuit Manual Type) 5 6 7 8 9 B7-6 VITZROTECH Earth Bushing Earth Terminal Rating Plate Gas Pressure Gauge Hot-line Indicator QTY No. 1 7 1 1 4 1 2 3 4 Name of parts Cabinet Gas-Injecting Part ASS’y Main Circuit Bushing Actuator QTY 1 1 12 4 Gas Insulated Load Break Switch 33-D-M-125(3-Circuit Manual Type) B7 5 6 7 8 9 Name of parts Earth Bushing Earth Terminal Rating Plate Gas Pressure Gauge Hot-line Indicator QTY No. 1 7 1 1 4 1 2 3 4 Name of parts QTY Cabinet Gas-Injecting Part ASS’y Main Circuit Bushing Actuator 1 1 12 4 Internal Diagram of Body Gas Insulated Load Break Switch B7-7 Gas Insulated Load Break Switch No. For Underground Control Box @ @ @ @ @ @ Accessories Operating Handle It is an operating handle to be used when manually operating the switch to ON/OFF/Earth operation. •How to Use Insert the operating handle into the hole of state display panel and rotate it for operation. Lock Bar It is a lock device to prevent any operations when the switch is ON, OFF or in a earth state. •How to Use Insert the lock bar to the hook of state display panel and lock the lower part so that the switch cannot be operated. B7-8 VITZROTECH Gas Insulated Load Break Switch Internal Circuit Diagram & Controller Connection Diagram B7 Gas Insulated Load Break Switch Gas Insulated Load Break Switch B7-9 Gas Insulated Load Break Switch _ Feature For Pole Mounted(PGS) VITZRO TECH Gas Insulated Load Break Switch is a switch that is used at 22.9kV-Y / 10kV-△ overhead distribution line applied with SF6 gas as the insulating medium which is superior in terms of arc extinguishing. It is an optimal product to distinguish the overhead distribution line and to be used as a branch switch with the operating mechanism, a spring toggle method. B7-10 VITZROTECH Switch Body ▶ Operating Device The operating device of the switch is divided into a main circuit part and earth part. It is designed to require no special skills and all 3-phase contacts are opened / closed simultaneously and the switching. speed is always consistent regardless of the operation method. In case of an automatic switch, it can be operated by an electrical switching device of the control box and by a manual operating device of the body. It can be operated based on the designated operation method [Local/Remote]. ▶ Bushing Part It exceeds the standard impulse insulation density of the switch and all bonding parts are treated so that gas does not leak and air does not get in. It is structured to maintain the mechanical sticking force. It is made up of a qualitative magnetic material that has the freezing and thermal capability, it is firm enough to endure the mechanical impulse and it is moist-proof. In addition, it used a polysil insulating material that is molded by an advance insulating material, polymer concrete, which our company retains the patent, and it maintains the dielectric strength even at poor operational conditions since the electrical and mechanical strength and arc extinguishing are superior. ▶ Outside Connecting Terminal It maintains the sticking force by connecting the terminal or lead-out line to the bushing. An insulation wire for high-voltage which is flexible and weather-protected is used and the nominal sectional area of the conductor and the wire composition are 125㎟(159/1.0) or bigger for 400A and 200㎟(19/14/1.0) or bigger for 630A and the required length is 2m. The lead-out line is water-proof which prevents the water from entering and the connecting part within the mold cone is structured not to allow water from entering. The connecting part of mold cone and lead-out line is centralized with an electric field and it is glued firmly so that the connecting part is not disconnected and its surface is smoothly treated. Applied Standard •ES - 5925 - 0003(2007. 03. 27) •IEC 60265-1(1998) •ANSI C37.71(2001) •ANSI C37.63(1997) •GB3804-90 ▶ Gas Insulated Load Break Switch B7-11 B7 Gas Insulated Load Break Switch It is a 3-phase integrated operating single-tank type that consists of a switch body, mounting tool and control box. It easy to arm the concrete pole or power line and it can be installed stably. It is designed in a simple structure for an easy maintenance work. A stainless steel plate (KSD3705 2(Type & Mark), STS304L) of 3mm or bigger is used for the tank cabinet and it has a sufficient electrical and mechanical strength. Each part of the switch is simple and durable and the opening and closing are operated smoothly and accurately. There is no half-closing or half-opening during the opening/closing operations, it is not opened / closed due to vibrations or other causes and it is structured so that there is no water pool at any part of the switch. Bolts are not used in order to prevent gas leak and it is completely enclosed by TIG welding. The insulating material used in the inner part is the bisphenol, epoxy resin with excellent resistance to electrical and mechanical characteristics and SF6 gas. O-Ring that is used for the enclosure at the bonding part is made up of EPR and FPM that is heat-proof, weather-protected and gas-proof and the surface of the O-Ring is covered with grease that is heat-proof, weather-protected and gas-proof. Ratings VPS-M24 VPS-A24 VPS-M26 VPS-A26 VPS-M12 VPS-A12 (Automatic (Automatic (Automatic (Manual Type) Type) (Manual Type) (Manual Type) Type) Type) Type Rated Voltage 25.8 kV Rated Current 400A 400A Rated Frequency Rated Making Current 50Hz 16 kA /4s 32.5kAp 40kAp 400A 400A 630A 630A 630A 630A Load Current( 5%) 20A 20A 31.5A 31.5A 31.5A 31.5A LOOP Current 400A 400A 630A 630A 630A 630A 14A 14A 22A 22A - 10A Exciting Current Cable Charging Current(100%) 25A 25A 25A 25A 10A Cable Charging Current(30%) 7.5A 7.5A 7.5A 7.5 A - - Line Charging Current 1.5A 1.5A 1.5A 1.5A - - 5000 times Power Frequency Between Earths Withstand Between Poles Between Phases Voltage Lightning Impulse Withstand Voltage Weight 42kV/1min 60kV/1min 49kV/1min 60kV/1min 42kV/1min 150kVp 75kVp 150kVp 85kVp 150kVp - AC220V, DC24V 75kVp AC220V, - - DC24V AC220V, DC24V 0.15MPa・G(at 20℃) About 135kg About 170kg About 155kg About 190kg About 145kg About 155kg Certificated & Approval ES-5925-0003(07.03.27), IEC 60265-1(1998) Manual Operating Device It is operated safely and easily using a highvoltage (COS) operating bar and it is structured to complete the closing and opening with one operation. The position of the closing and opening operation device is facing the front and it is equipped with the closing at the right side and the opening at the left side. The shape is clearly distinguishable. Switch Operating Lock Device It can lock the operating device at open-circuit and closed-circuit positions and when it is locked, electrical and mechanical switching operations are impossible. Operating State Indicator An operating state indicator is installed to clearly identify the opening/closing of the disconnecting switch. Low Pressure Display & Lock Device It is equipped with an automatic lock device that enables to prohibit the electrical and mechanical opening and closing at a condition which may lead to a danger due to the low gas pressure. It is installed with an indicator that allows to easy checking. VITZROTECH 60kV/1min Between Earths Between Poles Between Phases SF6 Gas-Filled Pressure B7-12 630A Load Current(100%) Rated Operating Voltage Function & Performance 630A 12.5kA /1s Switching Capability(Mechanical) Dielectric Strength 630A 60Hz Rated Short Time Withstand Current Switching Capability 12kV 630A GB3804-90 Gas Emission Equipment When the inner gas pressure of the body increases sharply due to an internal failure, it prevents the destruction of tank for the safety of operators and people and the emission equipment is installed so that it does not spread outside. The equipment is manufactured in a structure that emits the gas in a direction that does not harm the operators. Earth Terminal It is structured for easy connection to 22㎟~38㎟ copper wire without a separate auxiliary tool and STS304 is used for the material. Counter A mechanical counter is installed outside so that it can be checked. Gas-Injection Valve A valve that can inject gas to the tank of the body when required is installed in the rear part of the tank and it is installed in a place where it is not damaged during the delivery, installation and operation. Gas Insulated Load Break Switch Controller Configuration It is manufactured based on KEPCO specifications (ES-5925-0003) so the structure is simple and the operation is convenient.The composition of the control box is shown below. B7 Gas Insulated Load Break Switch •Control Part •Battery : DC 24V(12V, 2EA) •Voltage Supply Unit : AC220V / DC24V •Modem Installing Tool •Plug Socket Functions Our control box is equipped with the following functions. 1) Control Function : It can control the switch. - Operation Switch“Close/Open” 2) Status Information Display : It displays the switch state. - Operation Switch“Close/Open” - Operation Lock“Control Box/Body” -“Gas Pressure” - Storage Battery Test“Charging Part/Storage Battery” 3) Selection Switch : It sets the control conditions. - Control Power“ON/OFF (Toggle)” - Selection of Operation“Site/Remote (Toggle)” - Operation Lock "Lock/Unlock (Momentary)" 4) Others - Connector to connect to FRTU (Located at the upper part of control part) - Door Limit Switch - 220V plug socket Gas Insulated Load Break Switch B7-13 25.8kV Mold Cone Type PGS Character Color 22.9kV A Unlock Lock Close Open No. Red Red Green Red Red Green 1 2 3 4 Name of parts QTY Hanger Bracket Ass’y 1 Body 1 Bushing Ass’y (Fixed Part) 3 Bushing Ass’y (Movable Part) 3 Body Material: STS304L (t=3mm) Body Weight: B kg Rated Current A B 400A 630A 400A 630A 160 175 12kV Terminal Type Character Color 12kV 630 Unlock 類 合 分 B7-14 VITZROTECH No. Red Red Green Red Red Green 1 2 3 4 Name of parts Hanger Bracket Ass’ y Body Bushing Ass’y (Fixed Part) Bushing Ass’y (Movable Part) QTY 1 1 3 3 Body Material: STS304L (t=3mm) Body Weight: A kg Rated Current A Manual Type Automatic Type 145 155 Gas Insulated Load Break Switch Body B7 Name of parts Bushing Current transformer Puffer housing Tulip contact Tulip contact Fixed contact Conductor Moving bar Puffer cone V-caracition Gas Insulated Load Break Switch NO. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. Material Porcelain, Polysil P.O On On+W On+W On On Teflon STS Control Box Gas Insulated Load Break Switch B7-15 PGS B7-16 VITZROTECH Gas Insulated Load Break Switch B7 Gas Insulated Load Break Switch Gas Insulated Load Break Switch B7-17 B7-18 VITZROTECH