Product Application Reference Sensors & Transmitters S6011-AT Air Conduit Temperature Transmitter Summary S6011-AT Air Conduit Temperature Transmitter o er an economical solution for a wide variety of temperature sensing needs, in the cooling heating, ventilation and air conditioning Model S6011-AT/V S6011-AT/I Operating voltage Output signal 0-10V 4-20mA Measuring range Measuring accuracy S6011-AT/VG S6011-AT/IG 24V DC 0-10V 4-20mA Temperature -20-50°C Temperature ±1°C Ambient temperature Temperature ±0.5°C -40-50°C Storage -40-50°C, non-condensing Housing ABS Mounting S6011-AT transmitters can be mounted into air conduit or vent. The gasket ring separates outside air from transmitter. Attentions: Locate the transmitters, where they will be exposed to representative conditions. Avoid non-representative air draughts, direct sunlight, etc. S6011-ATH Series of Air Conduit Temperature-Humidity Transmitter Summary S6011-ATH for a wide variety of temperature sensing needs, in the cooling heating, ventilation and air Model S6011-ATH/V S6011-ATH/I Operating voltage Output signal Measuring range S6011-ATH/VG S6011-ATH/IG 24V DC 0-10V 4-20mA 0-10V 4-20mA Temperature -20-50°C RH 0-100% Measuring accuracy Temperature ±1°C Temperature ±0.5°C RH ±5% RH Ambient temperature RH ±3% RH -40-50°C Storage -40-50°C, non-condensing Housing ABS Mounting Ordering code S6011-ATH/X X G-temperature accuracy±0.5°C (no alphabet-±1°C) I- current output 4-20mA V-voltage output 0-10V S6011-ATH series of transmitters can be mounted into air conduit or vent. The gasketring separates outside air from transmitter. Attentions: Locate the transmitters, where they will be exposed to representative conditions. Avoid non-representative air draughts, direct sunlight, etc. T: Temperature TH: Temperature and Humidity 24. CE Compliance EMC (89/336/EEC) according to the standard EN61000-6-1:2001, EN61000-6-3:2001. Product Application Reference Transmitters S6011-RT/RTH series of Temperature Transmitter & Temperature-Humidity Transmitter Summary S6011 series of transmitters provide a passive or active signal that corresponds with the air or water temperature in heating, ventilating and air conditioning applications. Model No Operation voltage Output signal Measuring range S6011-RT room temperature transmitter S6011-RTH room temperature-humidity transmitter DC 24V 0~10V or 4-20mA Temperature 0~50°C Humidity 0~100%RH Measuring Accuracy Temperature ±1°C or ±0.5°C RH ±5%RH or ±3% Ambient temperature -20°C~60°C Storage -40°C~70°C, non-condensing Material ABS Mounting The transmitters are suitable for direct wall mounting or ceiling-mounting using four screw holes on the base. The wiring must be entered from the back. For mounting, follow the instruction below: Choose an appropriate place to achieve good control of the ambient temperature. The room transmitters only sense the temperature or humidity at the place where it is mounted. The transmitters should not be mounted near to windows or doors to avoid draught. On the other hand, Put insulation material in the wiring conduit to prevent introduction of air from outside the room. The transmitter should not be exposed to direct radiation or to the sun, as it would lead to incorrect measurement. S6011-T Temperature Sensor Summary S6011-T temperature sensor is applicable with S2013 series Proportional-plus-integral (PI) controller. The temperature sensor shall be able to provide with temperature sensor in heating and cooling. When deviation happens between the ambient temperature and the set point, it is able to provide with temperature sensor. Ordering code Model Sensing element Precision Material Operation ambient S6011-T temperature sensor NTC thermistor ±1°C 10K 25°C ABS plastics Temperature -40°C 100°C RH 10 95%RH non-condensing +70°C Storage -40°C S6011-RXX/X X G-temperature accuracy±0.5°C (no alphabet-±1°C) I- current output 4-20mA V-voltage output 0-10V T-temperature; TH-temperature and humidity CE Compliance EMC (89/336/EEC) according to the standard EN61000-6-1:2001, EN61000-6-3:2001. 25. Product Application Reference Transmitters S6011-WTX series of Water Pipe Temperature Transmitter Summary S6011-WTX series of transmitter is used to measure the liquid temperature in pipes or the air temperature in heating, ventilating and air conditioning applications. The transmitters provide 0-10V voltage signal or 4-20mA current signal. Model S6011-WTA/V Input voltage Input signal Measuring range Measuring accuracy Operation temp Storage Material S6011-WTB/I 24V DC 0-10V or 4-20mA 0~50°C 0~100°C ±1°C or ±0.5°C 10~80°C 0~110°C -40-70°C, non-condensing poly carbonate Mounting To install S6011-WTX, please follow this process: mount casing pipe into pipe and insert the transmitter into casing pipe and lock it. Accessory S6011-WT, Casing pipe (required) There are two types of casing pipe, 55mm and 115mm. Ordering code S6011WT X / X X A:Precision,siou±0.5℃,±3% I:4-20MA V:0-10V A:Temperature :0-50℃ B:T emperature and Humidity 26. CE Compliance EMC (89/336/EEC) according to the standard EN61000-6-1:2001, EN61000-6-3:2001.