381339-221L - Emerson Network Power

advertisement
Connectivity to the ASCO® Power Manager Xp
& 7000 Series Group 5 Controller via Modbus®
This design specification describes the Modbus
communications protocol as supported by the ASCO
Power Manager Xp and 7000 Series Group 5
Controller. It includes instructions on how to pass
information into and out of the either device via the
Modbus network. This publication should be used by
individuals wishing to integrate either device into their
facility by developing software to communicate with
either device. Additional information can be found in
Power Manager Xp Operator’s Manual 381333-199
and Group 5 Controller User’s Guide 381333-126.
Modbus Protocol
Implementation Basics
The following rules define the Modbus slave
implementation of the devices:
ƒ The devices operate as slaves only
(communication must be initiated by the master).
ƒ The maximum number of bytes contained within
one packet of communications is 64.
Transmission Format
Although the Modbus protocol supports both ASCII
and RTU modes of transmission, only the RTU mode
is implemented. Within the RTU mode, the ASCO
devices support the following communication
parameters:
ƒ 8 data bits
ƒ no parity
ƒ 1 stop bit
Modbus RTU Packet Format
Every Modbus Packet consists of the following fields:
ƒ
ƒ
ƒ
ƒ
Device Address Field
Function Code Field
Data Field
Error Check Field
Device Address Field. This is the first byte of
each Modbus RTU transmission. The device
address is a number limited to the range of 0 - 247
and is associated with a single device configured
with a matching address. Only the slave device
whose address matches the value in this field will
respond to the specified command. Device address
0 indicates a broadcast command. This means that
every slave on the network will act on the
command, but it will not issue any responses.
Function Code Field. This is a second byte of
each transmission and represents the commanded
action to the slave device (for queries from the
master) or the action that was taken by the slave
device (for responses from the slave). Codes
between 1 and 127 are defined as Modbus RTU
functions. The function codes supported by the
Power Manager Xp are detailed on page 4. The
function codes supported by the Group 5
Controller are detailed on page 10.
Data Field. The data field varies in length
depending on whether the message is a request or
a response packet. This field typically contains
information required by the slave device to
perform the command specified in a request
packet or data being passed back by the slave
device in a response packet.
Error Check Field. The error check field
consists of a 16 bit (2 byte) Cyclical Redundancy
Check (CRC16). It allows the receiving device to
detect a packet that has been corrupted with
transmission errors. Refer to CRC-16 Algorithm
on page 2 for details.
Packet Framing and Timing
Because the Modbus RTU protocol does not define
any explicit packet synchronization bytes, synchronization is accomplished implicitly with the use of silent
intervals. According to the Modbus RTU standard, all
messages must start with a silent interval of at least 3.5
character times. This means that every byte within a
packet must precede the previous byte by fewer than
3.5 character times based on the baud rate. And every
new packet of data must begin at least 3.5 character
times or more after the packet that had preceded it.
In summary, the three timing intervals associated with
the ASCO devices are as follows:
ƒ Maximum time between two consecutive bytes
within a packet < 3.5 character times.
ƒ Minimum time between two
packets is > 3.5 character times.
consecutive
ƒ Maximum response time from a Master request
to a slave response is < 50 milliseconds.
ASCO Power Technologies, L.P., 50 Hanover Rd., Florham Park, NJ 07932 USA www.asco.com
Modbus is a registered trademark of Gould Inc.
1
381339-221 L
CRC-16 Algorithm
Procedure. The algorithm essentially treats the
entire data packet (less the start, stop, and, if used,
parity bits) as one continuous binary number. Since we
are doing a 16-bit CRC calculation, the binary number
(entire packet) is multiplied by 216 and then divided by
the generator polynomial. In the case of the Modbus
protocol, the generator polynomial is x16 + x15 + x2 + 1.
The 16-bit remainder of the division, which is the 16bit CRC checksum, is then appended to the end of the
packet. The resulting data packet including the 16-bit
CRC checksum, when divided by the same Generator
Polynomial at the receiver, will give a zero remainder
if no transmission errors have occurred.
1. Initially, load the 16-bit CRC register with the value
FFFF hex.
2. Exclusive OR the 16-bit CRC register with the first
data byte of the packet and store the result in the 16bit CRC register.
3. If the Least Significant Bit (LSB) of the 16-bit CRC
register is equal to one, then shift the 16-bit CRC
register to the right by one bit and then Exclusive
OR the result with the generator polynomial, A001
hex. Otherwise, just shift the 16-bit CRC register to
the right by one bit.
4. Repeat step 3 until eight right shifts have been
performed.
The binary value of the Generator Polynomial is A001
hex. This is obtained by first dropping the mostsignificant-bit of the polynomial and then reversing the
bit order. This yields 1010000000000001 or A001h.
5. Exclusive OR the 16-bit CRC register with the next
data byte of the packet.
The steps for generating the 16-bit CRC checksum are
as follows:
7. The 16-bit CRC register contains the new checksum
to be appended to the end of the packet, Least
Significant Byte first.
6. Repeat steps 3-5 until all the bytes of the data packet
have been used in step 5.
CRC-16 Pseudocode. Below is the pseudocode for generating the 16-bit CRC checksum. XOR is the
Exclusive-OR function:
CRC16REG = FFFF hex
GENPOLY = A001 hex
FOR X = 1 to number of bytes in packet
BEGIN
XOR CRC16REG with the Xth data byte
FOR Y = 1 to 8
BEGIN
IF [(the least-significant-bit of CRC16REG) = 1] THEN
SHIFT CRC16REG one bit to the RIGHT
XOR CRC16REG with GENPOLY
OTHERWISE
SHIFT CRC16REG one bit to the RIGHT
END
NEXT Y
END
NEXT X
The resulting CRC16REG contains the 16-bit CRC checksum
CRC-16 C Programming Language Example. CRC16_checksum is a C language function that calculates
and returns the 16-bit CRC checksum of a string of characters. This is the brute force method as it consumes a lot
of processing power performing numerous bit shifts. A table look-up method based on this function would be
more suitable for embedded systems where processing power is at a premium. The following four parameters are
passed as part of the function
1. pointer to string
2. length of string (in bytes)
3. initial CRC value
4. desired Generator polynomial
Included to make this CRC-16 function generic for any generator polynomial
continued on next page
2
ASCO Power Technologies, L.P., 50 Hanover Rd., Florham Park, NJ 07932 USA www.asco.com
381339-221 L
The following C-language type definitions (typedef’s) are assumed:
1. typedef unsigned int uint;
2. typedef unsigned char uchar;
The function is defined as follows:
uint CRC16_checksum(uchar *Buffer, uint Length, uint CRC, uint Genpoly) {
uint index;
While (Length--) {
/* for each data byte in string */
CRC = CRC ^ (uint) *Buffer++;
/* exclusive OR data byte */
For (index = 0; index < 8; index++) {
/* for each of the 8 bits */
If ((CRC & 0x0001) == 1) CRC = (CRC >> 1) ^ Genpoly;
Else (CRC = CRC >> 1);
} /* for statement */
} /* while statement */
return(CRC);
}
An ASCO Example. Let’s assume the transmitting device desired to send the ASCII string “ASCO”. Using an
ASCII character look-up table, we have the following hexadecimal codes for each of the ASCO letters:
A = 0x65
S = 0x83
C = 0x67
O = 0x79
The transmitter would determine the 16-bit CRC checksum as follows (in C, both methods are equivalent):
CRC16_checksum(“ASCO”, 4, 0xFFFF, 0xA001) which returns CRC = 0xCD94
CRC16_checksum(“\x65\x83\x67\x79”, 4, 0xFFFF, 0xA001) which returns CRC = 0xCD94
Before sending the string, the transmitter would append the CRC checksum (in byte reverse order) to the string as
follows:
“ASCO\x94\xCD” or the equivalent in hexadecimal notation “\x65\x83\x67\x79\x94\xCD”
If the receiving device received the string without any transmission errors, then doing the 16-bit CRC checksum
on the entire received string would yield (again, both methods are equivalent):
CRC16_checksum(“ASCO\x94\xCD”, 4, 0xFFFF, 0xA001) which returns CRC = 0x0000
CRC16_checksum(“\x65\x83\x67\x79\x94\xCD”, 4, 0xFFFF, 0xA001) which returns CRC = 0x0000
Since the CRC checksum is equal to zero, the transmission is deemed valid.
Had an error been induced during the transmission, such as the ASCII character ‘A’ being inadvertently changed
to the character ‘B’ (which is hexadecimal 0x66), the receiving device would determine the new checksum as:
CRC16_checksum(“BSCO\x94\xCD”, 4, 0xFFFF, 0xA001) which returns CRC = 0x3300
CRC16_checksum(“\x66\x83\x67\x79\x94\xCD”, 4, 0xFFFF, 0xA001) which returns CRC = 0x3300
Since the CRC is NON-ZERO (0x3300), the receiver would assume an error had occurred and discard the packet.
ASCO Power Technologies, L.P., 50 Hanover Rd., Florham Park, NJ 07932 USA www.asco.com
381339-221 L
3
Supported Function Codes for Power Manager Xp
Function # 03 (03h) – Read Holding Registers
This function code allows the master to read one or
more consecutive data registers from the Power
Manager Xp. The data registers are always 16 bit (two
byte) values, transmitted high order byte first. Refer to
Register Map on page 12 for details about the data
register definitions of the Power Manager Xp.
The following example shows the format of a
transmission between a master requesting device and
the responding Power Manager Xp (slave device) at
address 24. The master desires to read the four values
of current, IA, IB, IC, IAVE, beginning at Holding
register location 40021 (which is a “Data starting
address” of 20 decimal or 14 hexadecimal).
40095
40200
40201
40202
40203
40204
Example (in hex)
18
03
00
14
00
04
06
04
40205
40206
40207
00CC
00CD
00CE
40208
40209
40210
00CC
00CD
00CE
40211
40212
40213
00CF
00D0
00D1
Example (in hex)
18
03
08
04
CE
04
D3
04
D3
04
CE
36
7F
40214
00D2
40215
00D3
Slave Response
Packet Format
Slave address
Function code
Byte count
Data word #1 (high byte)
Data word #1 (low byte)
Data word #2 (high byte)
Data word #2 (low byte)
Data word #3 (high byte)
Data word #3 (low byte)
Data word #4 (high byte)
Data word #4 (low byte)
CRC16 (low byte)
CRC16 (high byte)
The Power Manager Xp currently supports the
following Preset Single register addresses. If a
Function #06 command is issued without one of these
register addresses, the Power Manager Xp will
respond with an invalid address range Exception
Response (see Exception Responses on page 5).
Address
(in hex
notation)
005E
00C7
00C8
00C9
00CA
00CB
Master Transmission
Packet Format
Slave address
Function code
Data starting address (high byte)
Data starting address (low byte)
Number of registers (high byte)
Number of registers (low byte)
CRC16 (low byte)
CRC16 (high byte)
about the about the data register definitions of the
Power Manager Xp.
The Power Manger Xp supports the following Read
Holding Register addresses-decimal: 11-26, 31-48,
51-64, 71-84, 87-94, 96-125, 127-128, 130-137, 149159. The Type of those Registers is defined as RO
(Read only).
Function # 06 (06h) – Preset Single Register
Address
Description
Relay outputs (DO1-DO4)
System type
Source mode
Potential transformer ratio (PTR)
Current transformer ratio (CTR)
Neutral current transformer ratio
(CT4R)
SCI comm. port (J5) protocol
SCI comm. port (J5) baud rate
SCI comm. port (J5) device
address
485 comm. Port (J1) protocol
485 comm. Port (J1) baud rate
485 comm. port (J1) device
address
Menu language selection
Demand window size (in minutes)
Demand subinterval size (fixed at
1 minute)
Reset inst. & max. demand
registers
Reset energy registers
The following example shows the format of a
transmission between a master device and the
responding Power Manager Xp (slave device) at
address 24. The master desires to set the System Type
(Holding register 40200) to a Single Phase – 3 Wire
system (data value 02). See System Type on page 7 for
details.
Master Transmission
Packet Format
Slave address
Function code
Data address (high byte)
Data address (low byte)
Data word (high byte)
Data word (low byte)
CRC16 (low byte)
CRC16 (high byte)
Example (in hex)
18
06
00
C7
00
02
BB
FF
This function code allows the master device to modify
the contents of a single configuration register within
the Power Manager Xp. The data registers are always
16 bit (two byte) values, transmitted high order byte
first. Refer to Register Map on page 12 for details
4
ASCO Power Technologies, L.P., 50 Hanover Rd., Florham Park, NJ 07932 USA www.asco.com
381339-221 L
Function # 16 (10h) – Preset Multiple Registers
Slave Response
Packet Format
Slave address
Function code
Data starting address (high byte)
Data starting address (low byte)
Number of registers (high byte)
Number of registers (low byte)
CRC16 (low byte)
CRC16 (high byte)
Example (in hex)
18
06
00
C7
00
02
BB
FF
The Power Manger Xp supports the following Preset
Single Register addresses -decimal: 65-68, 95, 148,
160, and 200-215.
Address
Start
End
40141
40146
40200
40213
40230
40235
40326
40333
40334
40341
40342
40349
40350
40357
40358
40365
40366
40373
40374
40381
40382
40389
40390
40397
40398
40405
40406
40413
40414
40421
Register
Count
6
14
6
8
8
8
8
8
8
8
8
8
8
8
8
Description
PM Date & Time
General Settings
Setpoint Settings
S1 Status Input #1 name
S2 Status Input #2 name
S3 Status Input #3 name
S4 Status Input #4 name
S5 Status Input #5 name
S6 Status Input #6 name
S7 Status Input #7 name
S8 Status Input #8 name
Relay Output #1 name
Relay Output #2 name
Relay Output #3 name
Relay Output #4 name
The following example shows the format of a
transmission between a master requesting device and
the responding Power Manager Xp (slave device) at
address 24. The master desires to configure Setpoint
#1 (Holding Registers 40230 – 40235).
Slave Response
Packet Format
Slave address
Function code
Data starting address (high byte)
Data starting address (low byte)
Number of registers (high byte)
Number of registers (low byte)
CRC16 (low byte)
CRC16 (high byte)
Example (in hex)
18
10
00
E5
00
06
53
F5
The Power Manger Xp supports the following Preset
Single Register addresses -decimal: 141-146, 200-213,
230-235, 236-319, 322-325, 326-421, and 422-433.
This function code allows the master device to modify
the contents of consecutive configuration registers
within the Power Manager Xp. The data registers are
always 16 bit (two byte) values, transmitted high order
byte first. Refer to Register Map on page 12 for details
about the data register definitions of the Power
Manager Xp.
The Power Manager Xp currently supports the
following Preset Multiple register ranges. If a Function
#16 command is issued without one of these
corresponding register ranges, the Power Manager Xp
will respond with an invalid address range Exception
Response (see Exception Responses on page 6).
Command String (in Hex)
ADDR 10 00 8C 00 06 0C ..data.. CRCLO CRCHI
ADDR 10 00 C7 00 0E 1C ..data.. CRCLO CRCHI
ADDR 10 00 E5 00 06 0C ..data.. CRCLO CRCHI
ADDR 10 01 45 00 08 10 ..data.. CRCLO CRCHI
ADDR 10 01 4D 00 08 10 ..data.. CRCLO CRCHI
ADDR 10 01 55 00 08 10 ..data.. CRCLO CRCHI
ADDR 10 01 5D 00 08 10 ..data.. CRCLO CRCHI
ADDR 10 01 65 00 08 10 ..data.. CRCLO CRCHI
ADDR 10 01 6D 00 08 10 ..data.. CRCLO CRCHI
ADDR 10 01 75 00 08 10 ..data.. CRCLO CRCHI
ADDR 10 01 7D 00 08 10 ..data.. CRCLO CRCHI
ADDR 10 01 85 00 08 10 ..data.. CRCLO CRCHI
ADDR 10 01 8D 00 08 10 ..data.. CRCLO CRCHI
ADDR 10 01 95 00 08 10 ..data.. CRCLO CRCHI
ADDR 10 01 9D 00 08 10 ..data.. CRCLO CRCHI
Master Transmission
Packet Format
Slave address
Function code
Data starting address (high byte)
Data starting address (low byte)
Number of registers (high byte)
Number of registers (low byte)
Byte count
Data word #1 (high byte)
Data word #1 (low byte)
Data word #2 (high byte)
Data word #2 (low byte)
Data word #3 (high byte)
Data word #3 (low byte)
Data word #4 (high byte)
Data word #4 (low byte)
Data word #5 (high byte)
Data word #5 (low byte)
Data word #6 (high byte)
Data word #6 (low byte)
CRC16 (low byte)
CRC16 (high byte)
Example (in hex)
18
10
00
E5
00
06
0C
00
01
03
E8
00
00
03
20
00
05
00
02
D1
91
ASCO Power Technologies, L.P., 50 Hanover Rd., Florham Park, NJ 07932 USA www.asco.com
381339-221 L
5
Exception Responses
If the Modbus master device sends an unsupported
command, attempts to read an invalid holding register,
or attempts to write invalid data, the Power Manager
Xp (Modbus slave) issues an exception response. The
format for the exception response is as follows:
1. SLAVE ADDRESS
2. FUNCTION CODE*
(with the most-significant-bit set to a 1)
3. ERROR CODE
4. CRC16 – low order byte
5. CRC16 – high order byte
* Note: The high order bit of the function code
has been set to one to indicate an exception
response has been generated.
The following table is a list of the exception codes
supported by the Power Manager Xp.
Exception Response Error Codes
Error
code
01
02
03
04
Error
name
Illegal
function
Illegal
data
address
Illegal
data
value
Device
failure
Power Manager Xp
implementation
The slave does not support the
function code contained in the master
query packet.
The slave does not support the Holding
Register address referenced in the
data field of the master query packet.
The slave does not support the data
referenced in the data field of the
master query packet.
The addresses slave is unable to
perform the action requested due to an
internal failure or malfunction.
The following example shows the format of a transmission between a master device and the responding
Power Manager Xp (slave device) at address 24. The
master device attempts to write an invalid data value
(04) to the System Type holding register 40200. The
Power Manager Xp slave device responds with Error
code 03.
Master Transmission
Packet Format
Slave address
Function code
Data starting address (high byte)
Data starting address (low byte)
Data (high byte)
Data (low byte)
CRC16 (low byte)
CRC16 (high byte)
Example (in hex)
18
06
00
C7
00
04
3B
FD
Slave Response
Packet Format
Slave address
Function code
Error code
CRC16 (low byte)
CRC16 (high byte)
Example (in hex)
18
86
03
D3
A6
The following example shows the format of a
transmission between a master device and the
responding Power Manager Xp (slave device) at
address 24. The master device attempts to write to an
invalid address, 40216 (0x00D7). The Power Manager
Xp slave device responds with Error code 02.
Master Transmission
Packet Format
Slave address
Function code
Data starting address (high byte)
Data starting address (low byte)
Data (high byte)
Data (low byte)
CRC16 (low byte)
CRC16 (high byte)
Example (in hex)
18
06
00
D7
00
03
7B
FA
Slave Response
Packet Format
Slave address
Function code
Error code
CRC16 (low byte)
CRC16 (high byte)
6
Example (in hex)
18
86
02
12
66
ASCO Power Technologies, L.P., 50 Hanover Rd., Florham Park, NJ 07932 USA www.asco.com
381339-221 L
Configuration Register Details
System Type – Holding Register no. 40200
The system type register defines the type of system to
which the Power Manager Xp is connected.
Binary
value
0 (00h)
1 (01h)
2 (02h)
3 (03h)
Label
Description
4W_WYE
3W_DELTA
3W_1PHASE
2W_1PHASE
3 Phase, 4 wire WYE system
3 Phase, 3 wire DELTA system
Single phase, 3 wire system
Single phase, 2 wire system
Source Mode – Holding Register no. 40201
The source mode register defines the source bus, to
which the Power Manager Xp is connected. The
Energy register display window changes according to
the bus defined. The user can specify a normal bus
connection, an emergency bus connection, a
connection to the load side of the bus or no specific
designation.
Binary
value
0 (00h)
1 (01h)
2 (02h)
Label
NORMAL
EMERGENCY
LOAD
3 (03h)
OTHER
Current Transformer Ratio
– Holding Register no. 40203
This register defines the full-scale current input value
for the three phases of current. This is based on the
ratio of the external current transformers (CTs) connected between the Power Manager Xp and the power
bus.
Range
5 to 24,000
4th Current Input Transformer Ratio
– Holding Register no. 40204
This register defines the full-scale current input value for
the 4th or neutral current input. This is based on the ratio
of the external current transformer (CT) connected
between the Power Manager Xp and the power bus.
Range
5 to 24,000
Description
Normal power bus
Emergency power bus
Load power bus
Any power bus with no
designation on the Energy
registers
When the LOAD selection is chosen, the Power
Manager Xp uses the N/E INPUT status input to
determine ATS switch position. Two sets of Energy
registers are used; Normal energy registers &
Emergency energy registers.
Potential Transformer Ratio
– Holding Register no. 40202
This register defines the full-scale voltage input value
for the three phases of voltage. This is based on the
ratio of the external voltage transformers (PTs) connected between the Power Manager Xp and the power
bus.
Range
120 to 28,200
The value of 28,200 is the ratio 235:1 (120 * 235 =
28,200). Note that if external voltage transformers are
not required and subsequently not used, the ratio
should be set to 120, which is 1:1.
SCI Communications Port (J5) Protocol
– Holding Register no. 40205
Defines the protocol of the SCI communications port.
Binary
value
0 (00h)
1 (01h)
2 (02h)
Label
ASCOBusI
ASCOBusII
ModbusRTU
Description
ASCOBusI protocol
ASCOBusII protocol
ModbusRTU protocol
SCI Communications Port (J5) Baud Rate
– Holding Register no. 40206
Defines the baud rate of the SCI communications port.
Binary
value
1 (01h)
2 (02h)
Label
_9600
_19_2K
Description
9600 bps
19200 bps
SCI Communications Port (J5) Device Address
– Holding Register no. 40207
Defines the Power Manager Xp address of the SCI
communications port.
Protocol
ASCOBusI
ASCOBusII
ModbusRTU
Allowable address range
0-31
1-239
1-239
ASCO Power Technologies, L.P., 50 Hanover Rd., Florham Park, NJ 07932 USA www.asco.com
381339-221 L
7
485 Communications Port (J1) Protocol
– Holding Register no. 40208
Defines the protocol of the dedicated RS-485
communications port, if present on Power Manager
Xp. ‡
Binary
value
0 (00h)
1 (01h)
2 (02h)
Label
ASCOBusI
ASCOBusII
ModbusRTU
Description
ASCOBusI protocol
ASCOBusII protocol
ModbusRTU protocol
485 Communications Port (J1) Baud Rate
– Holding Register no. 40209
Defines the baud rate of the dedicated RS-485
communications port, if present on Power Manager
Xp. ‡
Binary
value
1 (01h)
2 (02h)
3 (03h)
4 (04h)
Label
_9600
_19_2K
_38_4K
_57_6K
Description
9600 bps
19200 bps
38400 bps
57600 bps
485 Communications Port (J1) Device Address
– Holding Register no. 40210
Defines the Power Manager Xp address of the
dedicated RS-485 communications port, if present on
Power Manager Xp.‡
Protocol
ASCOBusI
ASCOBusII
ModbusRTU
Allowable address range
0-31
1-239
1-239
‡ Power Managers with Transducers part # 629168 (Catalog 5200T)
support the RS-485 com port J1.
Data Monitors with Electronic Access Module part # 607607 Rev E or
higher support the RS-485 com port J1.
Language – Holding Register no. 40211
Defines the Language displayed on the liquid crystal
display (LCD) interface.
Binary
value
0 (00h)
Label
ENGLISH
Description
English language*
* Currently only the English language is available.
Demand Window Size
– Holding Register no. 40212
Defines the length of the demand period, in minutes,
used in calculating the sliding window demand values.
Range
1 to 15
Subinterval Size
– Holding Register no. 40213
Defines the length of the subinterval demand period, in
minutes, used in calculating the sliding window
demand values. This value is fixed at 1 minute.
Range
1
Reset Demand
– Holding Register no. 40214
Writing a value of 0xFFFF to this holding register
clears the Minimum and Maximum KWDemand
registers.
Clear Energy
– Holding Register no. 40215
Writing a value of 0xFFFF to this holding register
clears the Energy registers.
Part no.
629168
or
607607
Rev. E
8
ASCO Power Technologies, L.P., 50 Hanover Rd., Florham Park, NJ 07932 USA www.asco.com
381339-221 L
Status Input Names (8)
– Holding Register nos. 40326-40389
Relay Output Names (4)
– Holding Register nos. 40390-40421
Defines the name of the eight Status Inputs (S1 – S8).
The name consists of sixteen ASCII characters, which
are assigned two characters per register.
Defines the name of the four Relay Outputs (DO1 –
DO4). The name consists of sixteen ASCII characters,
which are assigned two characters per register.
Register
Address
Base
Base + 1
Base + 2
Base + 3
Base + 4
Base + 5
Base + 6
Base + 7
Register description
(2 ASCII characters per register)
INPUT_NAMEchar1 + INPUT_NAMEchar2
INPUT_NAMEchar3 + INPUT_NAMEchar4
INPUT_NAMEchar5 + INPUT_NAMEchar6
INPUT_NAMEchar7 + INPUT_NAMEchar8
INPUT_NAMEchar9 + INPUT_NAMEchar10
INPUT_NAMEchar11 + INPUT_NAMEchar12
INPUT_NAMEchar13 + INPUT_NAMEchar14
INPUT_NAMEchar15 + INPUT_NAMEchar16
Register
Address
Base
Base + 1
Base + 2
Base + 3
Base + 4
Base + 5
Base + 6
Base + 7
Register description
(2 ASCII characters per register)
OUTPUT_NAMEchar1 + OUTPUT_NAMEchar2
OUTPUT_NAMEchar3 + OUTPUT_NAMEchar4
OUTPUT_NAMEchar5 + OUTPUT_NAMEchar6
OUTPUT_NAMEchar7 + OUTPUT_NAMEchar8
OUTPUT_NAMEchar9 + OUTPUT_NAMEchar10
OUTPUT_NAMEchar11 + OUTPUT_NAMEchar12
OUTPUT_NAMEchar13 + OUTPUT_NAMEchar14
OUTPUT_NAMEchar15 + OUTPUT_NAMEchar16
ASCO Power Technologies, L.P., 50 Hanover Rd., Florham Park, NJ 07932 USA www.asco.com
381339-221 L
9
Supported Function Codes for Group 5 Controller
Function # 03 (03h) – Read Holding Registers
This function code allows the master to read one or
more consecutive data registers from the Group 5
Controller. The data registers are always 16 bit (two
byte) values, transmitted high order byte first. Refer to
Register Map on page 18 for details about the data
register definitions of the Group 5 Controller.
The following example shows the format of a
transmission between a master requesting device and
the responding Group 5 Controller (slave device) at
address 24 (24 decimal = 18 hex).. The master desires
to read the three values of voltage, NVAB, NVBC,
NVCA, IAVE, beginning at Holding register location
40016 (16 decimal = 10 hexadecimal).
Master Transmission
Packet Format
Slave address
Function code
Data starting address (high byte)
Data starting address (low byte)
Number of registers (high byte)
Number of registers (low byte)
CRC16 (low byte)
CRC16 (high byte)
Example (in hex)
18
03
00
10
00
03
04
0E
Slave Response
Packet Format
Slave address
Function code
Byte count
Data word #1 (high byte)
Data word #1 (low byte)
Data word #2 (high byte)
Data word #2 (low byte)
Data word #3 (high byte)
Data word #3 (low byte)
CRC16 (low byte)
CRC16 (high byte)
Example (in hex)
18
03
06
00
78
00
79
00
77
B7
10
The Group 5 Controller currently supports the
following Read Holding Register addresses (decimal):
11-54, 100, 105-173. Maximum number of registers
that can be read with a single 03H command is 12.
Attempting to read more than 12 registers with a single
03H command will result in Exception Response from
the Group 5 Controller.
Function # 06 (06h) – Preset Single Register
This function code allows the master device to modify
the contents of a single configuration register within
the Group 5 Controller. The data registers are always
16 bit (two byte) values, transmitted high order byte
first. Refer to Register Map on page 18 for details
10
about the about the data register definitions of the
Group 5 Controller.
The following example shows the format of a
transmission between a master device and the
responding Group 5 Controller (slave device) at
address 24 (24 decimal = 18 hex). The master desires
to set the time delay TDES at Holding register 40132
(132 decimal = 84 hex) to 5 seconds (data value 05).
Master Transmission
Packet Format
Slave address
Function code
Data address (high byte)
Data address (low byte)
Data word (high byte)
Data word (low byte)
CRC16 (low byte)
CRC16 (high byte)
Example (in hex)
18
06
00
84
00
05
0B
E9
Slave Response
Packet Format
Slave address
Function code
Data address (high byte)
Data address (low byte)
Number of registers (high byte)
Number of registers (low byte)
CRC16 (low byte)
CRC16 (high byte)
Example (in hex)
18
06
00
84
00
05
0B
E9
The Group 5 Controller currently supports the
following Preset Single Register addresses (decimal):
44, 101-173.
Function # 16 (10h) – Preset Multiple Registers
This function code allows the master device to modify
the contents of consecutive configuration registers
within the Group 5 Controller. The data registers are
always 16 bit (two byte) values, transmitted high order
byte first. Refer to Register Map on page 18 for details
about the data register definitions of the Group 5
Controller.
The following example shows the format of a
transmission between a master requesting device and
the responding Group 5 Controller (slave device) at
address 24 (24 decimal = 18 hex). The master desires
to set the following parameters occupying consecutive
register locations: NVDO at Holding register 40118
(118 decimal = 76 hex) to 85% (85 decimal = 55 hex),
NVPU at Holding register 40119 to 90% (90 decimal
= 5A hex) and NVTP at Holding register 40120 to
110% (110 decimal = 6E hex).
ASCO Power Technologies, L.P., 50 Hanover Rd., Florham Park, NJ 07932 USA www.asco.com
381339-221 L
Master Transmission
Packet Format
Slave address
Function code
Data starting address (high byte)
Data starting address (low byte)
Number of registers (high byte)
Number of registers (low byte)
Byte count
Data word #1 (high byte)
Data word #1 (low byte)
Data word #2 (high byte)
Data word #2 (low byte)
Data word #3 (high byte)
Data word #3 (low byte)
CRC16 (low byte)
CRC16 (high byte)
Example (in hex)
18
10
00
76
00
03
06
00
55
00
5A
00
6E
8A
1E
Slave Response
Packet Format
Slave address
Function code
Data starting address (high byte)
Data starting address (low byte)
Number of registers (high byte)
Number of registers (low byte)
CRC16 (low byte)
CRC16 (high byte)
Example (in hex)
18
10
00
76
00
03
63
DB
The Group 5 Controller currently supports the
following Preset Multiple Register addresses
(decimal): 44, 101-173.
Note: To access the Log Events data at Holding
Register addresses 40044-40053 first the selected Log
Event number has to be written into Register 40044
using Function 06H command and then the data of that
Event can be read from Registers 40045-40053 using
Function 03H command.
Similarly, to access the Feature F11C Schedules data
at Holding Registers addresses 40112-40117, first the
selected Schedule number to access (read or write) has
to be written into Register 40112 using Function 06H
command and then the data of that Schedule can be
accessed (read or written to) at Registers 40113-40117
using Function 03H, 06H, or 10H command. The
maximum number of registers that can be preset with a
single 10H command is 10.
1. SLAVE ADDRESS
2. FUNCTION CODE*
(with the most-significant-bit set to a 1)
3. ERROR CODE
4. CRC16 – low order byte
5. CRC16 – high order byte
* Note: The high order bit of the function code
has been set to one to indicate an exception
response has been generated.
The following table is a list of the exception codes
supported by the Group 5 Controller.
Exception Response Error Codes
Error
code
01
02
03
04
Error
name
Illegal
function
Illegal
data
address
Illegal
data
value
Device
failure
Group 5 Controller
implementation
The slave does not support the
function code contained in the master
query packet.
The slave does not support the Holding
Register address referenced in the
data field of the master query packet.
The slave does not support the data
referenced in the data field of the
master query packet.
The addresses slave is unable to
perform the action requested due to an
internal failure or malfunction.
The following example shows the format of a transmission between a master device and the responding
Group 5 Controller (slave device) at address 24. The
master device attempts to write data word 0015H to a
Read Only Register at 40016 (16 decimal = 10 hex).
The Group 5 Controller slave device responds with
Error code 02.
Master Transmission
Packet Format
Slave address
Function code
Data starting address (high byte)
Data starting address (low byte)
Data (high byte)
Data (low byte)
CRC16 (low byte)
CRC16 (high byte)
Example (in hex)
18
06
00
10
00
15
4B
C9
Slave Response
Exception Responses
If the Modbus master device sends an unsupported
command, attempts to read an invalid holding register,
or attempts to write invalid data, the Group 5
Controller (Modbus slave) issues an exception
response. The format for the exception response is as
follows:
Packet Format
Slave address
Function code
Error code
CRC16 (low byte)
CRC16 (high byte)
Example (in hex)
18
86
02
12
66
ASCO Power Technologies, L.P., 50 Hanover Rd., Florham Park, NJ 07932 USA www.asco.com
381339-221 L
11
VAN
VBN
VCN
VAVE
VAB
VBC
VCA
VLAVE
VLUNBAL
VUNBAL
IA
IB
IC
IAVE
IUNBAL
IN
kWA
kWB
kWC
kWT
kVARA
kVARB
kVARC
kVART
PfA
PfB
PfC
PfT
kVAA
kVAB
kVAC
kVAT
Freq.
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
Undefined
Phase A line to neutral voltage
Phase B line to neutral voltage
Phase C line to neutral voltage
Line to neutral average voltage
A-B line to line voltage
B-C line to line voltage
C-A line to line voltage
Line to line average voltage
Line to line voltage unbalance
Line to neutral voltage unbalance
Phase A current
Phase B current
Phase C current
Average current
Current unbalance
CT4 or neutral current
Undefined
Active Power phase A
Active Power phase B
Active Power phase C
Active Power total
Reactive Power phase A
Reactive Power phase B
Reactive Power phase C
Reactive Power total
Power Factor phase A
Power Factor phase B
Power Factor phase C
Power Factor total
volt-ampere Power phase A
volt-ampere Power phase B
volt-ampere Power phase C
volt-ampere Power total
Undefined
Frequency on phase VA
Parameter
Description
(40.00 to 80.00) * 100
-29,999 to +29,999
-29,999 to +29,999
-29,999 to +29,999
-29,999 to +29,999
-29,999 to +29,999
-29,999 to +29,999
-29,999 to +29,999
-29,999 to +29,999
(-.99 to +1.00) * 100
(-.99 to +1.00) * 100
(-.99 to +1.00) * 100
(-.99 to +1.00) * 100
0 – 29,999
0 – 29,999
0 – 29,999
0 – 29,999
0 – 59,999
0 – 59,999
0 – 59,999
0 – 59,999
0 – 59,000
0 – 59,000
0 – 59,000
0 – 59,000
0 – 100%
0 – 100%
0 – 29,999
0 – 29,999
0 – 29,999
0 – 29,999
0 – 100%
0 – 29,999
Data Range
ASCO Power Technologies, L.P., 50 Hanover Rd., Florham Park, NJ 07932 USA www.asco.com
1
381339-221 L
Parameter
Name
The addresses in the format of 4xxxx follow the MODICON MODBUS protocol for point addressing.
The actual address sent is the Register Address shown in the map minus the value 40001.
Register
Type
Note:
Modbus is a registered trademark of Gould Inc.
Register
Address
40001-40010
40011
40012
40013
40014
40015
40016
40017
40018
40019
40020
40021
40022
40023
40024
40025
40026
40027-40030
40031
40032
40033
40034
40035
40036
40037
40038
40039
40040
40041
40042
40043
40044
40045
40046
40047
40048
Register Map for Power Manager Xp
Hz x 100
kW
kW
kW
kW
kVAR
kVAR
kVAR
kVAR
Pf
Pf
Pf
Pf
kVA
kVA
kVA
kVA
Amp.
Amp.
Amp.
Amp.
Amp.
Volt
Volt
Volt
Volt
Volt
Volt
Volt
Volt
Units
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
Implemented in
Firmware Version
The following table describes the mapping of the registers within the Power Manager Xp to Holding Registers defined in the Modbus protocol.
40049-40050
40051
40052
40053
40054
40055
40056
40057
40058
40059
40060
40061
40062
40063
40064
40065
40066
40067
40068
40069-40070
40071
40072
40073
40074
40075
40076
40077
40078
40079
40080
40081
40082
40083
40084
40085-40086
40087
40088
40089
40090
40091
40092
40093
40094
40095
40096
40097
EmerkWHIMP
EmerkWHIMP
EmerkWHEXP
EmerkWHEXP
EmerkWHNET
EmerkWHNET
EmerkVarHIMP
EmerkVarHIMP
EmerkVarHEXP
EmerkVarHEXP
EmerkVarHNET
EmerkVarHNET
EmerkVAHNET
EmerkVAHNET
kWT
kWDemandT
MaxkWDeman
kWT
IAVE
VLAVE
Freq.
StatusInputs
RelayOutputs
SwitchPosition
kWT
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RW
RO
RO
Undefined
Normal kWH Import (HO word)
Normal kWH Import (LO word)
Normal kWH Export (HO word)
Normal kWH Export (LO word)
Normal kWH Net (HO word)
Normal kWH Net (LO word)
Normal kVarH Import (HO word)
Normal kVarH Import (LO word)
Normal kVarH Export (HO word)
Normal kVarH Export (LO word)
Normal kVarH Net (HO word)
Normal kVarH Net (LO word)
Normal kVAH Net (HO word)
Normal kVAH Net (LO word)
Nominal Voltage
Nominal Current
Nominal kW Capacity
Nominal Freq 0– 60Hz, 1–50Hz
Undefined
Emerg kWH Import (HO word)
Emerg kWH Import (LO word)
Emerg kWH Export (HO word)
Emerg kWH Export (LO word)
Emerg kWH Net (HO word)
Emerg kWH Net (LO word)
Emerg kVarH Import (HO word)
Emerg kVarH Import (LO word)
Emerg kVarH Export (HO word)
Emerg kVarH Export (LO word)
Emerg kVarH Net (HO word)
Emerg kVarH Net (LO word)
Emerg kVAH Net (HO word)
Emerg kVAH Net (LO word)
Undefined
Active Power (Watts) total
Instantaneous Watt Demand
Maximum Watt Demand
Active Power (Watts) total
Average current
Line to line average voltage
Frequency on phase VA
8 General purpose digital inputs
4 General purpose digital outputs
Main & auxiliary Switch positions
Active Power total
-29,999 to +29,999
-29,999 to +29,999
-29,999 to +29,999
-29,999 to +29,999
0 – 29,999
0 – 59,999
(40.00 to 80.00) * 100
Bits 0 – 7 ⇒ S1–S8
Bits 0 – 3 ⇒ DO1–DO4
0:norm & 1:emer.
-29,999 to +29,999
-1,999,999,999 to + 1,999,999,999
-1,999,999,999 to + 1,999,999,999
-1,999,999,999 to + 1,999,999,999
-1,999,999,999 to + 1,999,999,999
-1,999,999,999 to + 1,999,999,999
-1,999,999,999 to + 1,999,999,999
-1,999,999,999 to + 1,999,999,999
115-59999
0-29999
0-24999
0 or 1
-1,999,999,999 to + 1,999,999,999
-1,999,999,999 to + 1,999,999,999
-1,999,999,999 to + 1,999,999,999
-1,999,999,999 to + 1,999,999,999
-1,999,999,999 to + 1,999,999,999
-1,999,999,999 to + 1,999,999,999
-1,999,999,999 to + 1,999,999,999
ASCO Power Technologies, L.P., 50 Hanover Rd., Florham Park, NJ 07932 USA www.asco.com
381339-221 L
NormkWHIMP
NormkWHIMP
NormkWHEXP
NormkWHEXP
NormkWHNET
NormkWHNET
NormkVarHIMP
NormkVarHIMP
NormkVarHEXP
NormkVarHEXP
NormkVarHNET
NormkVarHNET
NormkVAHNET
NormkVAHNET
Nom_Volt
Nom_Amps
kW_Capacity
Nom_Freq
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RW
RW
RW
RW
kW
kW
kW
kW
kW
Amp.
Volt
Hz x 100
kWH
kWH
kWH
kWH
kWH
kWH
kVARH
kVARH
kVARH
kVARH
kVARH
kVARH
kVAH
kVAH
kWH
kWH
kWH
kWH
kWH
kWH
kVARH
kVARH
kVARH
kVARH
kVARH
kVARH
kVAH
kVAH
Volt
Amp.
kW
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
AS629262-004
AS629262-004
AS629262-004
AS629262-004
13
14
40098
40099
40100
40101
40102-40107
40108-40113
40114-40119
40120-40125
40126
40127
40128-Bit0
40128-Bit1
40128- Bit 2
40128- Bit 3
40128- Bit 4
40128- Bit 5
40128- Bit 6
40128- Bit 7
40128- Bit 8
40128- Bit 9
40128- Bit10
40128- Bit11
40128- Bit12
40128- Bit13
40128- Bit14
40128- Bit15
40129- Bit 0
40129- Bit 1
40129- Bit 2
40129- Bit 3
40129- Bit 4
40129- Bit 5
40129- Bit 6
40129- Bit 7
40129- Bit 8
40129
40130
40131
40132
40133
40134
40135
40136
40137
40138-40140
40141
H_STATUS
SP_STATUS
SP_STATUS
SP_STATUS
SP_STATUS
SP_STATUS
SP_STATUS
SP_STATUS
SP_STATUS
SP_STATUS
SP_STATUS
SP_STATUS
SP_STATUS
SP_STATUS
SP_STATUS
SP_STATUS
SP_STATUS
SP_STATUS
SP_STATUS
SP_STATUS
SP_STATUS
SP_STATUS
SP_STATUS
SP_STATUS
SP_STATUS
SP_STATUS
kWT
kWDemandT
MaxkWD
kWD_Date
kWD_Month
kWD_Year
kWD_Hour
kWD_Minute
PM_TIME
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RW
Reactive Power total
volt-ampere Power total
Power Factor total
Frequency on phase VA
Software Version string
Software build date string
Device serial number
Device model number
Undefined
Health status word
Setpoint #1 Output Status Normal/Tripped
Setpoint #1 Acknowledge State Ack/Pendg
Setpoint #2 Output Status Normal/Tripped
Setpoint #2 Acknowledge State Ack/Pendg
Setpoint #3 Output Status Normal/Tripped
Setpoint #3 Acknowledge State Ack/Pendg
Setpoint #4 Output Status Normal/Tripped
Setpoint #4 Acknowledge State Ack/Pendg
Setpoint #5 Output Status Normal/Tripped
Setpoint #5 Acknowledge State Ack/Pendg
Setpoint #6 Output Status Normal/Tripped
Setpoint #6 Acknowledge State Ack/Pendg
Setpoint #7 Output Status Normal/Tripped
Setpoint #7 Acknowledge State Ack/Pendg
Setpoint #8 Output Status Normal/Tripped
Setpoint #8 Acknowledge State Ack/Pendg
Setpoint #9 Output Status Normal/Tripped
Setpoint #9 Acknowledge State Ack/Pendg
Setpoint #10 Output Status Normal/Tripped
Setpoint #10 Acknowledge State Ack/Pendg
Setpoint #11 Output Status Normal/Tripped
Setpoint #11 Acknowledge State Ack/Pendg
Setpoint #12 Output Status Normal/Tripped
Setpoint #12 Acknowledge State Ack/Pendg
kW Demand Setpoint Status Normal/Trip
Not Used
Active Power (Watts) total
Instantaneous Watt Demand
Maximum Watt Demand
Maximum Watt Demand Date
Maximum Watt Demand Month
Maximum Watt Demand Year
Maximum Watt Demand Hour
Maximum Watt Demand Minute
Undefined
Power Manager Hours
0-23
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
Bit 9:Bit 15
-29,999 to +29,999
-29,999 to +29,999
-29,999 to +29,999
1-31
1-12
1-99
1-23
1-59
-29,999 to +29,999
0 – 29,999
(-0.99 to +1.00) * 100
(40.00 to 80.00) * 100
12 ASCII characters
12 ASCII characters
12 ASCII characters
12 ASCII characters
ASCO Power Technologies, L.P., 50 Hanover Rd., Florham Park, NJ 07932 USA www.asco.com
381339-221 L
kVART
kVAT
PfT
Freq.
V_String
SW_Date
SerialNumber
ModelNumber
RO
RO
RO
RO
RO
RO
RO
RO
kW
kW
kW
kVAR
kVA
Pf x 100
Hz x 100
AS629262-004
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
SP_ACK
SP_ACK
SP_ACK
SP_ACK
SP_ACK
SP_ACK
SP_ACK
SP_ACK
SP_ACK
SP_ACK
SP_ACK
SP_ACK
Event _LOG
Event _LOG#
Event_Year
Event _Month
Event _Day
Event _Week
Event _Hour
Event _Minute
Event _Second
WO
WO
WO
WO
WO
WO
WO
WO
WO
WO
WO
WO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
40158
Power Manager Minutes
Power Manager Year
Power Manager Month
Power Manager Day of Month
Power Manager Day of Week (0-S, 1-M, etc)
Undefined
Setpoint #1 Output Alarm Acknowledge
Setpoint #2 Output Alarm Acknowledge
Setpoint #3 Output Alarm Acknowledge
Setpoint #4 Output Alarm Acknowledge
Setpoint #5 Output Alarm Acknowledge
Setpoint #6 Output Alarm Acknowledge
Setpoint #7 Output Alarm Acknowledge
Setpoint #8 Output Alarm Acknowledge
Setpoint #9 Output Alarm Acknowledge
Setpoint #10 Output Alarm Acknowledge
Setpoint #11 Output Alarm Acknowledge
Setpoint #12 Output Alarm Acknowledge
Not Used
Not Used
Not Used
Not Used
Number of Unread Event Log Entries
Event Number (0 – The Latest One)
Event Year
Event Month
Event Month Day
Event Week Day
Event Hour
Event Minute
Event Second
Event Parameter:
1-kW Prealarm,
2-kW Alarm,
3-Over Voltage,
4-Under Voltage,
5-OverFrequency,
6-UnderFrequency,
7-Reverse Power,
8-Reverse VARs,
9-Reverse Current,
10-Negative Sequence Current,
11-Negative Sequence Voltage,
12-Input#1,
13-Input#2,
14-Input#3,
1-22
0-99
0-255
0-99
1-12
1-31
0-6
0-23
0-59
0-59
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
0-59
0-99
1-12
1-31
1-6
ASCO Power Technologies, L.P., 50 Hanover Rd., Florham Park, NJ 07932 USA www.asco.com
381339-221 L
Event _Event
PM_TIME
PM_DATE
PM_DATE
PM_DATE
PM_DATE
RW
RW
RW
RW
RW
40142
40143
40144
40145
40146
40147
40148-Bit 0
40148- Bit 1
40148- Bit 2
40148- Bit 3
40148- Bit 4
40148- Bit 5
40148- Bit 6
40148- Bit 7
40148- Bit 8
40148- Bit 9
40148- Bit10
40148- Bit11
40148- Bit12
40148- Bit13
40148- Bit14
40148- Bit15
40149
40150
40151
40152
40153
40154
40155
40156
40157
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
15
16
RW
RO
RO
RO
RO
RO
RO
RO
RO
40168
40169
40170
RO
R
W
R
W
R
W
40161
40162
40163
40164
40165
40166
40167
40160-Bit 2
40160-Bit 1
40160-Bit 0
40159
1-Enabled
1-Disable
1-Tripped
1-Enable
1-Not ready
1-Reset
0-20
0-11 setpoint #
2-(8-11) for nominals
1-(0-7) for setpoint
0-49
0-99
1-12
1-31
0-23
0-59
0-11 range
0-2
0-Disabled or
0-No change or
0-Normal
or
0-No change or
0-Ready
or
0-No change or
ASCO Power Technologies, L.P., 50 Hanover Rd., Florham Park, NJ 07932 USA www.asco.com
381339-221 L
setup_param
setup_sp
setup_feature
select_setup#
setup_year
setup_month
setup_date
setup_hour
setup_minute
Device 86
Device 86
Device 86
Event _Cause
15-Input#4,
16-Input#5,
17-Input#6,
18-Input#7,
19-Input#8,
20-Input#9(switch position),
21-None,
22-KW Demand
Event Cause: 0-Reset, 1-Tripped, 2-Acknowled
Device 86 Enable status
Device 86 Disable
Device 86 State status
Device 86 Enable
Device 86 Reset status
Device 86 Reset
Undefined
Select a setup log number to view
Setup log date stamp: year
Setup log date stamp: month
Setup log date stamp: date
Setup log time stamp: hour
Setup log time stamp: minute
Setup log feature:
1-Setpoint related:
Parameter, trip, dropout, reset, pickup, TDtrip,
TDreset, output.
2-Nominal settings related:
Voltage, current, frequency, kw capacity.
Setup log sepoint number
Setup log parameter:
0-No parameter
1-kW Prealarm,
2-kW Alarm,
3-Over Voltage,
4-Under Voltage,
5-OverFrequency,
6-UnderFrequency,
7-Reverse Power,
8-Reverse VARs,
9-Reverse Current,
10-Negative Sequence Current,
11-Negative Sequence Voltage,
12-Input#1,
13-Input#2,
14-Input#3,
15-Input#4,
16-Input#5,
AS629262-019
AS629262-019
AS629262-019
AS629262-019
AS629262-019
AS629262-019
AS629262-019
AS629262-019
AS629262-019
AS629262-004
AS629262-004
AS629262-004
AS629262-004
40171
40172
40173
40174-40175
40176
40177
40178
40179
40180
40181
40182
40183
40184
40185
40186
40187
40188
40189
40190
40191
40192
40193-40199
40200
40201
40202
40203
40204
40205
40206
40207
40208
40209
40210
40211
40212
40213
40214
40215
40216-40229
40230-40235
40236-40242
40236
EngineRunEnab
RunTimer
RunTimerMin
ClearEngineCnt
select_event#
event_year
event_month
event_date
event_day
event_hour
event _minute
event_second
event_event
event_cause
clear_event_log
TYPESYSTEM
MODESOURCE
PTR
CTR
CT4R
PROTOCOLSCI
BAUDSCI
ADDRSCI
PROTOCOL485
BAUD485
ADDR485
TYPELANG
Window_Size
Subintl_Size
Reset_Demand
Clear_Energy
SETPOINT
SETPOINT1
#I
RO
RO
RO
WO
RW
RO
RO
RO
RO
RO
RO
RO
RO
RO
WO
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
WO
WO
RW
RW
RW
0-11
0-99
0-99
1-12
1-31
0-6 (Mon-Sun)
0-23
0-59
0-59
1-22
0-2
0-Disable or 1-Enable
0-65535
0-59
0-1
ASCO Power Technologies, L.P., 50 Hanover Rd., Florham Park, NJ 07932 USA www.asco.com
381339-221 L
setup_from
setup_old
setup_new
RO
RO
RO
17-Input#6,
18-Input#7,
19-Input#8,
20-Switch position input
Setup log recorded from: 0-keypad, 1-serial
Setup log old parameter value
Setup log new parameter value
Undefined
Engine timer enable
Engine Timer: hour
Engine Timer: minute
Clear engine counter
Undefined
Select an event log number to view
Event log date stamp: year
Event log date stamp: month
Event log date stamp: date
Event log date stamp: day
Event log time stamp: hour
Event log time stamp: minute
Event log time stamp: second
Event log parameter: (see list on register 40158)
Event cause: 0-Reset, 1-Tripped, 2-Acknowled
Undefined
Register to clear event log database
Undefined
System Type
Source Mode
Potential Transformer Ratio
Current Transformer Ratio
4th Current Input Transformer Ratio
SCI comm. port (J5) protocol
SCI comm. port (J5) baud rate
SCI comm. port (J5) device address
485 comm. port (J1) protocol
485 comm. port (J1) baud rate
485 comm. port (J1) device address
Language selection
Demand Window size (in minutes)
Demand Subinterval size (fixed at 1 minute)
Resets Inst. & Max. demand registers
Clears Energy registers to 0
Undefined
Setpoint configuration settings
Setpoint#1 Configuration Settings:
Setpoint Number
min.
min.
AS629262-004
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
AS629262-019
AS629262-019
AS629262-019
AS629262-019
AS629262-019
AS629262-019
AS629262-019
AS629262-019
AS629262-019
AS629262-019
AS629262-019
AS629262-019
AS629262-019
AS629262-019
AS629262-019
AS629262-019
AS629262-019
AS629262-019
17
18
40237
40238
40239
40240
40241
40242-Bit0-3
40242-Bit 4
40242-Bit 5
40242-Bit 6
40242-Bit 7
40243-40249
40250-40256
40257-40263
40264-40270
40271-40277
40278-40284
40285-40291
40292-40298
40299-40305
40306-40312
40313-40319
40320-40321
40322-40325
40326-40333
40334-40341
40342-40349
40350-40357
40358-40365
40366-40373
40374-40381
40382-40389
40390-40397
40398-40405
40406-40413
40414-40421
40422-40431
40432
PM-Name
Status1_Name
Status2_Name
Status3_Name
Status4_Name
Status5_Name
Status6_Name
Status7_Name
Status8_Name
Relay1_Name
Relay2_Name
Relay3_Name
Relay4_Name
PM-Location
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
Setpoint Parameter
Setpoint Trip Level
Setpoint Trip Time Delay
Setpoint Reset Level
Setpoint Reset Time Delay
Setpoint Digital Output :DO1 To DO4
Output No Acknowledg/Acknowledg
Output Status Normal/Tripped
Previous Acknowledge/Pending
Present Acknowledge/Pending
Setpoint#2 Configuration Settings
Setpoint#3 Configuration Settings
Setpoint#4 Configuration Settings
Setpoint#5 Configuration Settings
Setpoint#6 Configuration Settings
Setpoint#7 Configuration Settings
Setpoint#8 Configuration Settings
Setpoint#9 Configuration Settings
Setpoint#10 Configuration Settings
Setpoint#11 Configuration Settings
Setpoint#12 Configuration Settings
Undefined
Power Manager Name
S1 Status Input name
S2 Status Input name
S3 Status Input name
S4 Status Input name
S5 Status Input name
S6 Status Input name
S7 Status Input name
S8 Status Input name
DO1 Relay Output name
DO2 Relay Output name
DO3 Relay Output name
DO4 Relay Output name
Power Manager Location
Undefined
8 ASCII chars
15 chars+ 1 byte eng. alarms
15 chars+ 1 byte eng. alarms
15 chars+ 1 byte eng. alarms
15 chars+ 1 byte eng. alarms
15 chars+ 1 byte eng. alarms
15 chars+ 1 byte eng. alarms
15 chars+ 1 byte eng. alarms
15 chars+ 1 byte eng. alarms
15 chars+ 1 byte eng. alarms
15 chars+ 1 byte eng. alarms
15 chars+ 1 byte eng. alarms
15 chars+ 1 byte eng. alarms
20 ASCII chars
0-20
0-500
0-600
0-500
0-600
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
Same Setting as SP#1
Same Setting as SP #1
Same Setting as SP #1
Same Setting as SP #1
Same Setting as SP #1
Same Setting as SP #1
Same Setting as SP #1
Same Setting as SP #1
Same Setting as SP #1
Same Setting as SP #1
Same Setting as SP #1
ASCO Power Technologies, L.P., 50 Hanover Rd., Florham Park, NJ 07932 USA www.asco.com
381339-221 L
Parameter
High_limit
TD_Operate
Low_Limit
TD_Release
Output
----SETPOINT2
SETPOINT3
SETPOINT4
SETPOINT5
SETPOINT6
SETPOINT7
SETPOINT8
SETPOINT9
SETPOINT10
SETPOINT11
SETPOINT12
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
AS629262-004
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
FS611842-006
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
AS629262-004
Register Map for Group 5 Controller
Register
Address
40001- 40011
40012
40013
40014
40015-Bit 0
40015-Bit 1
40015-Bit 2
40015-Bit 3
40015-Bit 4
40015-Bit 5
40016-Bit 0
40016-Bit 1
40016-Bit 2
40016-Bit 3
40016-Bit 4
40016-Bit 5
40016-Bit 6
40017
40018
40019
40020
40021
40022
40023
40024
40025
40026-Bit 0
40026-Bit 1
40026-Bit 2
40026-Bit3-4
40026-Bit 5
40026-Bit 6
40027
40028-40033
40034-40039
40040-Bit 0
PHASE_0
NFRQ_0
EFRQ_0
I_MAIN_ON_N
I_MAIN_ON_E
I_AUX_ON_N
I_AUX_ON_E
N.SrcAvl
E.SrcAvl
STATPHR.NABC
STATPHR.NCBA
STATPHR.EABC
STATPHR.ECBA
XRQ_F11C_LX
not used
I_F17_ON
NV_AB
NV_BC
NV_CA
NVUnblCur
EV_AB
EV_BC
EV_CA
EVUnblCur
I_NOM_V
I_FRQ_60
I_N3PHASE
I_E3PHASE
TSType
TSBypass
ATS/DualBreaker
TSAmp
LCD_CP_VER
LCD_CP_DATE
OPSave.b.ATSLout
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
Undefined
Phase Shift between Normal & Emergency
Normal Frequency
Emergency Frequency
Main on Normal
Main on Emergency
Auxiliary on Normal
Auxiliary on Emergency
Normal Source Available
Emergency Source Available
Normal Phase Rotation is ABC
Normal Phase Rotation is CBA
Emergency Phase Rotation is ABC
Emergency Phase Rotation is CBA
Engine Exerciser with Load Active
not used
External F17 is Active
Normal Voltage Phase AB
Normal Voltage Phase BC
Normal Voltage Phase CA
Normal Voltage Unbalance
Emergency Voltage Phase AB
Emergency Voltage Phase BC
Emergency Voltage Phase CA
Emergency Voltage Unbalance
Nominal Voltage
Nominal Frequency
Normal Source 3 Phase sensing
Emergency Source 3 Phase sensing
Transfer Switch Type (CTTS, OTTS,DTTS)
Transfer Switch Bypass or not
Transfer Switch or Dual Breaker
Transfer Switch Amp rating
Control Panel Software version
Control Panel Software date
Transfer Switch Locked Out
-1800 – 1800
0 – 7000
0 – 7000
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
0 to 28200
0 to 28200
0 to 28200
0 to 99 %
0 to 28200
0 to 28200
0 to 28200
0 to 99 %
0 to 15 (Note 1)
Bool (60-50 Hz)
Boolean
Boolean
0 to 3 (Note 2)
Boolean
Boolean
0 to 15 (Note 3)
10 char. string
10 char. string
Boolean
Data Range
ASCO Power Technologies, L.P., 50 Hanover Rd., Florham Park, NJ 07932 USA www.asco.com
381339-221 L
Parameter
Name
Register
Type
Parameter
Description
The addresses in the format of 4xxxx follow the MODICON MODBUS protocol for point addressing.
The actual address sent is the Register Address shown in the map minus the value 40001.
Real Time Data Registers
Note:
Volt
Volt
Volt
Volt
Volt
Volt
Volt
Volt
Volt
deg x 10
Hz x 100
Hz x 100
Units
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-033
607540-023
607540-023
607540-023
607540-023
Implemented in
Firmware Version
The following table describes the mapping of the registers within the Group 5 Controller to Holding Registers defined in the Modbus protocol.
19
20
40040-Bit 1
40040-Bit 2
40040-Bit 3
40040-Bit 4
40040-Bit 5
40040-Bit 6
40040-Bit 7
40041
40042
40043-Bit 0
40043-Bit 1
40043-Bit 2
40043-Bit 3
40043-Bit 4
40043-Bit 5
40043-Bit 6
40043-Bit 7
40044-Bit 0
40044-Bit 1
40044-Bit 2
40044-Bit 3
40044-Bit 4
40044-Bit 5
40044-Bit 6
40045
40046
40047
40048
40049
40050
40051
40052
40053
40054
40055-Bit0-6
40056-40100
40101-Bit0-5
40101-Bit 6
40101-Bit 7
SlcMode
SlcStat.NBrOpn
SlcStat.EBrOpn
RO
RO
RO
CTTS extended parallel alarm
CTTS failure to synch alarm
DTTS Load Disconnect
External parameter lock is active
Engine running
Normal Breaker Tripped
Emergency Breaker Tripped
Control Panel State
Control Panel Status State Data (Ælookup table)
Feature 6B
Feature 6C
Feature 17
not used
Feature 29
Feature 30
Feature 34A
Feature 34B
Feature 89
Feature CT Bypass
Feature Alarm Reset
Feature 6D
Feature 5
Feature 6Z
Feature 34T
Event number
Event year
Event month
Event day of month
Event day of week
Event hour
Event minute
Event second
Event type
Event cause
Number of entries in the control panel event log
Undefined
Soft Load Controller mode
SLC Normal Breaker status
SLC Emergency Breaker status
0 to 3 (Note 7)
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
0 to 255 (Note 4)
0 to 65535(Note 4)
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
0 to 99
0 to 99
1 to 12
1 to 31
0 to 6
0 to 23
0 to 59
0 to 59
1 to 11 (Note 5)
1 to 23 (Note 6)
0 to 99
ASCO Power Technologies, L.P., 50 Hanover Rd., Florham Park, NJ 07932 USA www.asco.com
381339-221 L
OPSave.b.XtdPrlAl
OPSave.b.SyncFail
DTTSLoadDisc
I_EXT_PLOCK_ON
Relay.NR
NBrkrTipped
EBrkrTipped
CPState
CPStateData
F.F6BOn
F.F6COn
I_F17_ON
not used
F.F29On
F.F30On
F.F34AOn
F.F34BOn
F.F89On
F.CTBypsOn
I_ALARM_RST
I_F6D_MAN_ON
F.F5On
I_F5F6Z_ON
F.SComF17Off
LogNum
LogYear
LogMonth
LogDayM
LogDayW
LogHour
LogMin
LogSec
LogType
LogCause
LogEntNr
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RW
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-033
607540-033
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
607540-023
SLC Mode
No SLC
Islanding
Parallel Base Load
Import/Export
SLC Mode
Note 7
Switch Type
OTTS
DTTS
CTTS
OTTS
Event Type
Engine Start
Transfer N>E
Transfer E>N
Engine Stop
Emerg Acceptable
Emerg Not Accept.
Normal Acceptable
Normal Not Accept.
Transfer Abort
Breaker Trip
YY Primary Fail
ASCO Power Technologies, L.P., 50 Hanover Rd., Florham Park, NJ 07932 USA www.asco.com
1
381339-221 L
Data
1
2
3
4
5
6
7
8
9
10
11
Event Type
Switch Type
Amp Rating
30A
70A
100A
150A
260A
400A
600A
800A
1000A
1200A
1600A
2000A
3000A
4000A
OTHER
OTHER
Note 5
Data
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Note 2
Voltage
115V
120V
208V
220V
230V
240V
277V
380V
400V
415V
440V
460V
480V
550V
575V
600V
Modbus is a registered trademark of Gould Inc.
Data
0
1
2
3
Data
0
1
2
3
Data
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Note 3
Switch Amp Rating
Note 1
Nominal Voltage
Data
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
Note 6
Event Cause
Load Shed
Normal Fail
Manual Transfer
Test 5
Test 17
Communication
Engine Exerciser
Emergency Fail
Normal Under Voltage
Normal Over Voltage
Normal Under Frequency
Normal Over Frequency
Normal Phase Rotation
Normal Voltage Unbal.
Emerg. Under Voltage
Emerg. Over Voltage
Emerg. Under Frequency
Emerg. Over Frequency
Emerg. Phase Rotation
Emerg. Voltage Unbal.
Feature 6
Normal Breaker
Emergency Breaker
Event Cause
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
E
E
E
E
E
E
E
E
E
E
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
State Description
time left in seconds
phase difference in degrees x 10
time left in seconds
time left in seconds
null
null
time left in seconds
if 11C with load is running, then time left in seconds else null
time left in seconds
null
time left in seconds
time left in seconds
null
phase difference in degrees x 10
time left in seconds
phase difference in degrees x 10
time left in seconds
phase difference in degrees x 10
time left in seconds
time left in seconds
time left in seconds
null
null
null
time left in seconds
if 11C without load is running, then time left in minutes, else null
State Data
ASCO Power Technologies, L.P., 50 Hanover Rd., Florham Park, NJ 07932 USA www.asco.com
1
381339-221 L
in phase monitor time delay with load shed (OTTS E to N
transfer)
waiting for in phase (OTTS E to N transfer)
in phase monitor time delay (OTTS E to N transfer)
timer 31G (E to N pre transfer signal) running
transfer to N inhibited by F34A
transfer to N inhibited by G6C
timer 3A (TDEN) running
load on E waiting for removal of transfer requests
timer 31M (N to E post transfer signal) running
N to E load shed is active
load disconnected (DTTS N to E transfer)
load disconnected CT bypass (CTTS N to E transfer)
sources paralleled (CTTS N to E transfer)
waiting for in sync (CTTS N to E transfer)
in sync monitor time delay (CTTS N to E transfer)
in phase monitor time delay with load shed (OTTS N to E
transfer)
waiting for in phase with load shed (OTTS N to E transfer)
waiting for in phase (OTTS N to E transfer)
in phase monitor time delay (OTTS N to E transfer)
timer 31F (N to E pre transfer signal) running
timer 2B (TDNE) running
transfer to E inhibited by F34B
transfer to E inhibited by F6Z
waiting for E acceptable
timer 1C (TDES) running
load on N, N ok
Modbus is a registered trademark of Gould Inc.
00
TS
Position
N
State
Note 4 - Look Up Table For Control Panel State & State Data
94
36
35
33
31
30
29
28
27
90,91
23
20
15
13
12
72
71
8
7
6
5
4
3
2
1
G5
state
0
E
E
E
E
E
E
N
N
N
N
?
-
26
27
28
29
30
31
32
33
34
35
36
255
1 if sources not acceptable, 2 if TS position unknown,
3 if transfer inhibit signal
null
time left in seconds
time left in seconds
time left in seconds
null
time left in seconds
time left in seconds
null
phase difference in degrees x 10
time left in seconds
phase difference in degrees x 10
ASCO Power Technologies, L.P., 50 Hanover Rd., Florham Park, NJ 07932 USA www.asco.com
381339-221 L
transition state (maintain last state)
power up inhibit
timer 1C (TDES) while timer 2E (TDEC) running
timer 2E (TDEC) running
timer 31N (E to N post transfer signal) running
E to N load shed is active
load disconnected (DTTS N to E transfer)
load disconnected CT bypass (CTTS E to N transfer)
sources paralleled (CTTS E to N transfer)
waiting for in sync (CTTS E to N transfer)
in sync monitor time delay (CTTS E to N transfer)
waiting for in phase with load shed (OTTS E to N transfer)
-
119
58
57
114,
115
55
51
47
42
40
39
95
23
Download