M-PACT PlusED.02

advertisement
37420
GE Consumer & Industrial
Power Protection
GE Consumer & Industrial
The Power Protection division (formerly
GE Power Controls) of GE Consumer & Industrial
is a first class European supplier of low-voltage
products including wiring devices, residential
and industrial electrical distribution
components, automation products, enclosures
and switchboards. Demand for the company’s
products comes from wholesalers, installers,
panel-board builders, contractors, OEMs
and utilities worldwide
GE Consumer & Industrial
Power Protection
www.ge.com/eu/powerprotection
www.gepowercontrols.com
M-PACT Plus - Air Circuit Breakers
ED.02
GE POWER CONTROLS
International Sales
Nieuwevaart 51
B-9000 Gent - Belgium
Tel.
+32/9 265 21 11
Fax
+32/9 265 28 90
E-mail: gepcbel@gepc.ge.com
M-PACT Plus
Air Circuit Breakers
400 - 6300A
GE POWER CONTROLS Ltd
Lincoln Road
Enfield
Middlesex EN1 1SB
United Kingdom
Tel.
0800 587 1251
Fax
0800 587 1239
E-mail: gepcuk@gepc.ge.com
GE imagination at work
GE imagination at work
680809
Ref. I/3197/E/EX 5.0 Ed. 04/06
© Copyright GE Power Controls 2006
ED.02
M-PACT Plus
Technical overview
A
Order codes
B
Wiring diagrams / Dimensional drawings
C
Numerical index
X
Just rel
M-PACT Plus
A.3
Introduction
A.4
A.6
A.8
Fixed pattern circuit breaker - frame 1, 2, 3
Withdrawable circuit breaker - frame 1, 2, 3
Characteristics
A.11
A.12
A.13
A.16
A.18
A.19
A.20
M-PRO protection relays - Electronic trip units
Range
Curves & terminology
M-PRO 17 Plus, M-PRO 18 Plus
Current protection
MCR making current release, reset mechanism, thermal memory,
healthy LED, test connector and test box
LCD display
M-PRO 17 Plus, M-PRO 18 Plus, M-PRO 30/40
Specifications
Other functions
A.22
A.23
A.24
Trip curves
M-PRO Plus - frame 1 & 2
M-PRO Plus - frame 3
M-PRO 30/40 - frame 1 & 2
A.26
A.28
Earth fault protection curves
M-PRO 30/40 - frame 1 & 2
M-PRO 17 Plus/18 Plus - frame 1 & 2
A.29
A.34
A.36
Accessories
Frame 1 & 2
Frame 3
Performance data all accessories
Technical overview
A
Order codes
B
Wiring diagrams / Dimensional drawings
C
Numerical index
X
y on us
A.1
M-PACT Plus
Technical overview
Notes
A
B
C
X
A.2
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
M-PACT Plus
Introduction
Specification
M-PACT Plus air circuit breakers comply with the
following specifications for low voltage switchgear:
• IEC 947-1
• IEC 947-2
• IEC 947-3
• VDE 0660 Part 101 and Part 107
• Utilization category B
Approvals
LOVAG certification in accordance with
IEC 947-2, BS EN 60947-2 ASTA, KEMA
Introduction
Rated from 400 to 6300A the M-PACT Plus circuit
breaker has been designed to meet the most stringent
demands in fault detection and safe interruption
thereof.
Available in 3 frame sizes:
• Frame size 1 ranging from 400 to 2500A
• Frame size 2 ranging from 800 to 4000A
• Frame size 3 ranging from 5000 to 6300A
The range has been developed aesthetically and
technically to co-ordinate with other protective devices
within our company for industrial/domestic
applications.
All 3 frame sizes have unique look available with both
fixed pattern and drawout versions which can be
manually or electrically operated. These ACBs are
designed to offer multiple mains connection options it
also comes with a wide range of easy-to-install
accessories.
A
B
C
X
ICU (kA)
100 90
80 Type C
70
60
Type H
-
Frame 3
50 40
Type N
Frame 1
30
Frame 2
20
Type S
10
0
400
630
800
1000
3 compact frame sizes
Frame size 1 - 400 to 2500A
Frame size 2 - 800 to 4000A
Frame size 3 - 5000 to 6300A
• Frame 1 & 2
Fixed & withdrawable version is offered with
3 or 4 pole configuration, front and rear access
connections (horizontal / vertical).
• Frame 3
Fixed and withdrawable version is offered with
3 Pole only, rear connections (horizontal/vertical)
• Devices provided with or without protection relay
• Manual or electrical operation and built-in safety
features e.g. safety shutters
1250
1600
2000
2500
3200
4000
5000
6300
Ith (A)
• Wide range of protection settings offering full selectivity
combinations of earth fault protection with simple &
easy service on site
4 performance ranges(1)
Type S : 50 kA
Icu =
Type N : 65 kA
Icu =
Type H : 80 kA
Icu =
Type C(2) : 100 kA Icu =
Ics
Ics
Ics
Ics
=
=
=
=
Icw
Icw
Icw
Icw
(1) Ratings shown at 500V AC
(2) Ratings shown at 690V AC
A.3
M-PACT Plus
Technical overview
Fixed pattern circuit breaker
Frame 1 & 2
All M-PACT Plus fixed pattern air circuit breakers
incorporate a stored energy mechanism. The spring
can be charged either manually or electrically via a
motor operator that is automatically activated after the
closing operation.
IP43 front panel and door escutcheon seals are
standard features with IP20 protected secondary
isolating contacts. For enhanced protection, an
optional IP54 door panel is also available.
Installation
Fixed pattern M-PACT Plus can be fastened into any
suitable switchboard or cubicle arrangement using four
M8 bolts.
Clearance is only required above the unit for the
removal and inspection of the arc chutes (see
dimensional drawings for mounting details and
recommended clearance distances).
An earthing point is provided on either side of the
circuit breaker.
Power supply
All stated short-circuit ratings are certified with
incoming supply connection made to either upper or
lower terminals.
3
3
4
5
6
8
2
7
9
A
10
B
1
11
C
X
12
•
•
•
•
•
•
•
•
•
•
•
•
•
•
A.4
Trip-free operating mechanism
Positive ’ON/OFF’ main contact indication
Mechanical/electrical anti-pumping device
Charging spring status indication
Ergonomic manual spring charging handle
Field-mountable range of accessories
Auxiliary switches 5 NO and 3 NC,
potential free 10A 250V (standard)
Mechanical trip alarm switch (1 NO/NC) (optional)
Padlockable push-button cover (for mechanical and
electrical lock)
Mechanical cable interlocking (optional)
Termination: rear, horizontal or front access (optional)
Electrical clearances according to IEC 947-2
Front access of secondary terminals for simple
connection
Maintainable arcing contacts are offered as a
standard feature.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
Motorised spring charging unit (optional)
M-PRO protection relay (optional)
Secondary contacts
Shunt trip (optional)
Closing coil (optional)
Undervoltage release (optional)
Manual charging handle
ON/OFF push-buttons
Push-button padlockable covers
Positive contact indication
Charging spring status indication
Mounting plate
M-PACT Plus
Frame 3
Power supply
M-PACT Plus frame 3 fixed pattern air circuit breakers
incorporate a stored energy mechanism. The spring
can be charged either manually or electrically via a
motor operator that is automatically activated after
the closing operation.
incoming supply connection made to either upper or
All stated short-circuit ratings are certified with
lower terminals.
2
1
7
IP43 front panel and door escutcheon seals are
standard features.
3
8
10
9
6
8
12
•
•
•
•
•
•
•
•
•
•
•
•
Trip-free operating mechanism
Positive ’ON/OFF’ main contact indication
Mechanical/electrical anti-pumping device
Charging spring status indication
Manual spring charging handle
Auxiliary switches 4 NO and 6 NC, 10A 500V
(standard)
Mechanical trip alarm switch (1NO) (potential free)
(standard)
Padlockable push-button cover
Mechanical cable interlocking (optional)
Termination: horizontal
Electrical spring charge indication
Easy replacement of main and arcing contacts
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
11
Motorised spring charging unit (optional)
M-PRO protection relay (optional)
Secondary contacts
Shunt trip (optional)
Closing coil (optional)*
Undervoltage release (optional)
Manual charging handle
ON/OFF push-buttons
Push-button padlockable cover
Positive contact indication
Charging spring status indication
Rear fixation point
Fixed pattern
4
A
B
C
* Feature not visible in picture.
X
Installation
Fixed pattern M-PACT Plus frame 3 can be fastened into
any suitable switchboard or cubicle arrangement using
four M10 bolts (see dimensional drawings for mounting
details and recommended clearance distances).
An earthing point is provided on left side of the circuit
breaker.
A.5
M-PACT Plus
Technical overview
Withdrawable circuit breaker
Frame 1 & 2
Pre-mounted into a self-contained ’cassette’, this
versatile circuit breaker can be inserted or withdrawn
via sliding rails using a racking drive mechanism
controlled by a racking handle.
It provides three set positions:
Disconnected / Test / Connected.
Any attempt to withdraw the unit whilst in service will
automatically trip the breaker, either by the racking
position safety mechanism or by the insertion of the
racking handle. It can be racked to the disconnected
position with the cubicle door closed or open.
Installation
Circuit breakers are delivered pre-mounted in the
cassette (standard)
Versatile fixing arrangements allow mounting onto any
switchboard or cubicle using four M8 bolts (see
dimensional drawings for mounting details and
recommended clearance distances)
Earthing point situated on the right hand side of
cassette (front view)
Power supply
All stated short-circuit ratings are certified with
incoming supply connection made to either upper or
lower terminals.
4
3
A
2
B
1
5
10
C
9
8
7
6
X
•
•
•
•
•
•
•
•
•
•
•
A.6
Insulated shutters to isolate the main contact zone
Front access padlocking for safety shutters
Secure padlocking in the "Disconnect" position
Clearly visible operational position indication
Carriage position switch (optional)
Termination: Flat copper palms (standard) with
captive M10 fixing nuts
Rear terminal adaptors for horizontal/vertical
connection (optional)
Front access connections (optional)
Automatic disconnect of secondary circuits
Lifting lugs for ease of removing the circuit breaker
from the cassette (M-PACT Plus handling truck
required)
Front access of secondary terminals for simple
connection
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
Carriage position switch (optional)
Slide rails
Insulated safety shutter
Secondary terminals
2 or 3 way interlock mechanism (optional)
Racking handle (storage)
Padlocking for safety shutters
Insertion hole for racking handle
Padlocking in the DISCONNECTED position
Operational position indication
Key interlock (optional)*
* Feature not visible in picture
M-PACT Plus
Frame 3
5
2
1
8
11
3
4
Installation
The carrier is designed to be fastened in the
switchboard on horizontal mounting rails using eight
M8 screws (see dimensional drawings for mounting
details and recommended clearance distances).
Power supply
All stated short-circuit ratings are certified with
incoming supply connection made to either upper or
lower terminals.
9
Withdrawable version
Pre-mounted into a self-contained ’cassette’, this
versatile circuit breaker can be inserted or withdrawn
via sliding rails using a racking drive mechanism
controlled by a racking handle.
It provides three set positions:
Disconnected / test / connected
Any attempt to withdraw the unit whilst in service will
automatically trip the breaker (by the racking position
safety mechanism)
It can be racked to the disconnected position with the
cubicle door closed or open.
• Carriage position switch (optional)
• Shutters and padlocking facility
• Contact indication
• Termination: 5000A rear horizontal or vertical /
6300A rear vertical
• Automatic disconnect of secondary circuits
• Easy wiring of the control circuit contacts
• Carrying handles for easy of removing the circuit
breaker from the cassette
A
3
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
Secondary contacts
Carriage position switch (optional)
Connection busbars
Connection point cover
Safety shutter
2 way cable interlock mechanism (optional)*
Racking handle *
Spindle mechanism
Operational position indication
Locating spring for door interlock*
Sliding unit
B
C
X
* Features not visible in picture
A.7
M-PACT Plus
Characteristics
Technical overview
Performance data
A
B
C
Characteristics
Symbol Units
400
A
Rated current (40°C)
In
Endurance (n° of operating cycles)
20000
Mechanical (with maintenance)
10000
Mechanical (without maintenance)
5000
Electrical (at rated current)
690
V
Rated service voltage (50/60 Hz)
Ue
1000
V
Rated insulation voltage
Ui
8000
V
Rated impulse withstand voltage
Uimp
3&4
Number of poles
100%
Rating of 4th pole
ACB type
S
N
Frame size
1
1
kA (rms)
Rated ultimate short-circuit
Icu
Breaking capacity
220V
50
65
415V
50
65
500V
50
65
600V
50
50
690V
40
40
kA (rms)
Rated service short-circuit
Ics
Breaking capacity
220V
50
65
415V
50
65
500V
50
65
600V
50
50
690V
40
40
Rated short time withstand current
kA (rms) 50
1 second
Icw
65
kA (rms) 40
3 seconds
Icw
50
kA (peak) 143
Rated short-circuit
415V
143
making capacity
500V
143
143
600V
143
105
690V
84
84
Watt
Power dissipation at In (fixed breaker)
W
16
11
Watt
Power dissipation at In (withdrawable)
W
33
22
630
800
1000
1250
20000
10000
5000
690
1000
8000
3&4
100%
S
N
1
1
S
1
20000
10000
5000
690
1000
8000
3&4
100%
N
1
H
2
S
1
20000
10000
5000
690
1000
8000
3&4
100%
N
1
H
2
S
1
20000
10000
5000
690
1000
8000
3&4
100%
N
1
H
2
50
50
50
50
40
65
65
65
50
40
50
50
50
50
40
65
65
65
50
40
80
80
80
65
60
50
50
50
50
40
65
65
65
50
40
80
80
80
65
60
50
50
50
50
40
65
65
65
50
40
80
80
80
65
60
50
50
50
50
40
65
65
65
50
40
50
50
50
50
40
65
65
65
50
40
80
80
80
65
60
50
50
50
50
40
65
65
65
50
40
80
80
80
65
60
50
50
50
50
40
65
65
65
50
40
80
80
80
65
60
50
40
143
143
143
84
39
75
65
50
143
143
105
84
27
53
50
40
143
143
143
84
63
127
65
50
143
143
105
84
43
86
80
50
176
176
143
105
23
49
50
40
143
143
105
84
106
211
65
50
143
143
105
84
68
135
80
50
176
176
143
105
36
77
50
40
143
143
143
84
175
351
65
50
143
143
105
84
105
211
80
50
176
176
143
105
60
128
X
Temperature deratings
Free Air (1)
The M-PACT Plus ACBs may operate at higher ambient
temperatures than 40°C in certain installation
conditions. In this case the current rating in Amperes
should be reduced as indicated below.
Ambient temp.
around
the breaker
Current rating (A) above 40°C
Rated current (A) 800 1000 1250 1600 2000 2500 3200 4000
50°C
800 1000 1250 1600 2000 2450 3200 3727
60°C
800 1000 1250 1445 2000 2232 3200 3367
The figures specified apply to withdrawable ACB’s with
flat face vertical copper connections.
No derating up to 50°C for 5000A - 6300A.
Other values on request .
(1) Protection degree IP00. For use in enclosures with interior
temperatures of 40°C to 60°C the relevant IP values can be applied.
A.8
Rated short-circuit capacity
In accordance with IEC 947-2 at 415V
Breaker
range
Rating
(A)
S
400 to 4000
N
H
C
Type
Fixed or
withdrawable
400 to 4000
Fixed or
withdrawable
800 to 4000
Fixed or
withdrawable
5000, 6300
Fixed or
withdrawable
Icu
Ics
Icw
1 sec 500 ms
50kA
50kA
50kA
-
65kA
65kA
65kA
-
80kA
80kA
80kA
-
100kA
100kA
-
100kA
Recommended minimum copper size
In accordance with IEC 947-2
Rating (A)
Copper / phase
400
630
800
1000
1250
1600
2000
2500
3200
4000
5000
6300
2 x 50 x 5
2 x 50 x 5
2 x 50 x 5
2 x 60 x 5
2 x 50 x 10
2 x 50 x 10
3 x 50 x 10
4 x 50 x 10
4 x 100 x 10
4 x 100 x 10 + 1 x 100 x 5
8 x 60 x 12
12 x 60 x 12 or 6 x 120 x 12
M-PACT Plus
2000
2500
3200
4000
5000
5000
6300
6300
S
1
20000
10000
5000
690
1000
8000
3&4
100%
N
1
H
2
S
1/2
20000
10000
5000
690
1000
8000
3&4
100%
N
1/2
H
2
S
1/2
20000
10000
5000
690
1000
8000
3&4
100%
N
1/2
H
2
S
2
20000
10000
5000
690
1000
8000
3&4
100%
N
2
H
2
S
2
20000
10000
5000
690
1000
8000
3&4
100%
N
2
H
2
5000
2500
2500
690
1000
8000
3
C
3
3000
1500
1000
690
1000
8000
3
C
3
50
50
50
50
40
65
65
65
50
40
80
80
80
65
60
50
50
50
50
40
65
65
65
50
40
80
80
80
65
60
50
50
50
50
40
65
65
65
50
40
80
80
80
65
60
50
50
50
50
40
65
65
65
50
40
80
80
80
65
60
50
50
50
50
40
65
65
65
50
40
80
80
80
65
60
100
100
100
100
100
100
50
50
50
50
40
65
65
65
50
40
80
80
80
65
60
50
50
50
50
40
65
65
65
50
40
80
80
80
65
60
50
50
50
50
40
65
65
65
50
40
80
80
80
65
60
50
50
50
50
40
65
65
65
50
40
80
80
80
65
60
50
50
50
50
40
65
65
65
50
40
80
80
80
65
60
100
100
100
100
100
100
50
40
143
143
143
84
287
574
65
50
143
143
105
84
196
392
80
50
176
176
143
105
98
209
50
40
143
143
143
84
224
490
65
50
143
143
105
84
224
490
80
50
176
176
143
105
163
347
50
40
143
143
143
84
224
490
65
50
143
143
105
84
224
490
80
50
176
176
143
105
163
347
50
40
143
143
143
84
418
888
65
50
143
143
105
84
418
888
80
50
176
176
143
105
418
888
50
40
143
143
143
84
571
1224
65
50
143
143
105
84
571
1224
80
50
176
176
143
105
571
1224
100(1)
55
220
220
220
570
975
100(1)
55
220
220
220
1510
(1) 500ms
Performance data
1600
A
B
C
X
Dimensions (mm)
Frame size
Rating (A)
Poles
Version (1)
Height (2)
Length (3)
Depth (4)
1
400 to 2500
3
W
F
W
F
W
F
W
F
W
F
W
F
W
F
W
440
430
440
430
440
430
440
430
440
430
440
430
578
518
578
329
329
429
429
419
419
549
549
419
419
549
549
969
902
969
390
328
390
328
392
328
392
328
482
328
482
328
729
411
729
4
2
800 to 3200
3
4
2
4000
3
4
3
5000
3
3
6300
3
(1) Version
W = Withdrawable
F = Fixed
(2) Height (H) is from mounting surface
to highest part of the ACB
(3) Length (L) is distance between
widest part of the breaker
(4) Depth (D) is from the cubicle door to
the rear moulding
A.9
M-PACT Plus
Selectivity/Discrimination
Downstream device
Upstream device
M-PACT Plus ACB
Technical overview
M-PRO 17 Plus & 18 Plus
A
B
Ir factor
1.6
Ist factor
1.5
STD timing
0.2
Instantaneous : 30kA minimum
Record PlusTM MCCB
SMR1s
SMR2
Ir factor
1.6
Ist factor
1.5
STD set at one band higher
Instantaneous : 30kA minimum
X
Ir factor
1.6
LTD class
20
Ist factor
1.5
STD timing
0.2
A2S band
0.1
Ir factor
1.6
LTD set at one class higher
Ist factor
1.5
STD set at one band higher
2
A S set at one band higher
* LTD set at class 20
Selectivity/Discrimination
M-PACT Plus
Upstream
Frame 1, N and H ranges
In (A)
400
800
1000
1250
1600
Frame 2, N and H ranges
2000
Downstream
Redline
G60/100/GT25
Surion
GPS
Hti
S90
Record PlusTM
FD160 E, S, N, H & L
FE160 N, H & L
FE250 N, H & L
FG400 N, H & L
FG630 N, H & L
C
M-PRO 30/40
Record PlusTM MCCB
SMR1
FK800 N, H & L
FK1250 N, H & L
FK1600 N and H
M-PACT Plus
Frame 1
Frame 2
2500
1000
1250
1600
2000
2500
3200
4000
Selectivity limit in kA
All
T
T
T
T
T
T
T
T
T
T
T
T
T
T
All
All
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
All
All
All
250
350
400
400
500
630
All
1000
1250
1600
400
800
1000
1250
1600
2000
2500
T
T
T
T
-
T
T
T
T
T
T
T
T
-
T
T
T
T
T
T
T
T
T
T
-
T
T
T
T
T
T
T
T
T
T
T
T
-
T
T
T
T
T
T
T
T
T
T
T
T
T
T
-
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
-
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
-
T
T
T
T
T
T
T
T
T
T
T
-
T
T
T
T
T
T
T
T
T
T
T
T
T
-
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
-
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
-
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
-
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
-
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
* T = Total: selective until the Icu of the downstream device OR the Icu of the upstream device
Weights (kg)
S range
Fixed pattern ACB
400 to 1600A
2000 to 2500A
800 to 3200A
4000A
5000A
Withdrawable ACB
A.10
N range
H range
C range
Frame
3 Pole
4 Pole
3 Pole
4 Pole
3 Pole
4 Pole
3 Pole
4 Pole
1
1
2
2
3
36
43
53
53
N/A
44
54
68
68
N/A
39
43
53
53
N/A
49
54
68
68
N/A
N/A
N/A
53
53
N/A
N/A
N/A
68
68
N/A
N/A
N/A
N/A
N/A
170
N/A
N/A
N/A
N/A
N/A
Frame
3 Pole
4 Pole
3 Pole
4 Pole
3 Pole
4 Pole
3 Pole
4 Pole
400 to 1600A
2000 to 2500A
800 to 3200A
4000A
5000A
6300A
1
1
2
2
3
3
63
72
90
111
N/A
N/A
77
90
117
144
N/A
N/A
68
72
90
111
N/A
N/A
84
90
117
144
N/A
N/A
N/A
N/A
90
111
N/A
N/A
N/A
N/A
117
144
N/A
N/A
N/A
N/A
N/A
N/A
250
265
N/A
N/A
N/A
N/A
N/A
N/A
Cassette only
Frame
3 Pole
4 Pole
3 Pole
4 Pole
3 Pole
4 Pole
3 Pole
4 Pole
400 to 1600A
2000 to 2500A
800 to 3200A
4000A
5000A
6300A
1
1
2
2
3
3
27
29
37
58
N/A
N/A
33
36
49
76
N/A
N/A
29
29
37
58
N/A
N/A
36
36
49
76
N/A
N/A
N/A
N/A
37
58
N/A
N/A
N/A
N/A
49
76
N/A
N/A
N/A
N/A
N/A
N/A
75
80
N/A
N/A
N/A
N/A
N/A
N/A
M-PACT Plus
M-PRO 17 Plus
M-PRO protection relays Electronic trip units
There are four types of electronic trip unit (ETU):
1. M-PRO 17 Plus - Rotary switch settings
2. M-PRO 18 Plus - Rotary switch settings and display
feature
3. M-PRO 30 - Digital settings and display feature
(only for frame 1 & 2)
4. M-PRO 40 - Digital settings and display feature
(only for frame 1 & 2)
Protection relays
M-PRO 18 Plus
A
11
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
12
1
5
6
2
7
3
8
9
10
4
Long time setting
Short time setting
Unrestricted earth fault setting*
Test connector
Instantaneous setting
Reset switch*
Short time delay
Curve followed
Unrestricted earth fault delay setting*
Healthy light emitting diode
Liquid crystal display
Scroll switch
B
C
X
* Not in frame 3
M-PRO 30/40 (frame 1&2)
3
4
5
6
2
1
7
8
1. Overload/short-circuit protection curve
incorporating 7 red LED's; indication of fault type.
2. Earth fault protection curve incorporating 2 red
LED's for fault indication.
3. LCD 2 line display for clear indication of menus,
settings, recorded information.
4. Warn / alarm LED
5. Healthy LED
6. Selectable manual / automatic reset button.
7. Four button tactile key pad.
8. Multi pin socket for test box and/or portable power
box.
A.11
M-PACT Plus
M-PRO curve
Terminology
NORMAL
A
ST
Ir
Isd
Ig
Current in multilples of I
B
C
X
Ii
Current in multiples of Ir
Time to trip (sec)
Technical overview
Time to trip (sec)
LT
In
Ir
Isd
Ii
If or Ig
Ibr
LT
ST
ACB
ETU
LCD
LED
PMCA
MCR
HSISC
UEF
REF
SEF
APU
SI
EI
VI
NO
NC
PAMM
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
Nominal Current
Rated Current
Short time current
Instantaneous Current
Unrestricted Earth Fault Current
Current Flowing Through Breaker
Long time
Short time
Air Circuit Breaker
Electronic Trip Unit (M-PRO)
Liquid Crystal Display
Light Emitting Diode
Primary Contact Maintenance Alarm
Making Current Release
High Set Instantaneous Short Circuit
Unrestricted Earth Fault
Restricted Earth Fault
Standby Earth Fault
Auxiliary Power Unit
Standard Inverse
Extremely Inverse
Very Inverse
Normally open (contact)
Normally closed (contact)
Plant Associated Memory Module
Breaker rating can be set from 40% to 100% of the
nominal value, using the long time pickup switch. The
unit will be in normal condition for all the currents
less than the rated value. So the curve is parallel to
the time axis.
Warning
Do not disconnect trip unit when breaker is in
service.
Do not change settings on the trip unit when breaker
is in service.
Do not interchange trip units between breakers.
These trip unit conform to IEC 60947-2, annex F.
A.12
M-PACT Plus
M-PRO protection relay electronic trip units
M-PRO 17 Plus & 18 Plus
The rated current of the breaker Ir can be set from 40%
to 100% of the nominal value In, using the long time
pickup switch. The breaker status will be “Normal” for
current Ibr less than the rated value set Ir.
The top most portion of the curve indicates this region
of normal operation where the line runs parallel to the
time axis (Y-axis).
The ETU is capable of providing protection in the Long
time zone in accordance with IEC Class 20.
If the current Ibr is greater than the “Short Time pickup”
set by the user on the M-PRO the unit will initiate a trip
after the set delay time. There are eight different
settings for the ST pickup levels with least at 1.5 times
the Ir to maximum of 12 times (10 times for Frame 3) Ir.
Also there are seven definite delay settings for the
Short Time.
Depending on the type of installation and application, it
is possible to set the tripping curve of your trip unit
using the parameters presented below.
Long-time protection
The long-time protection function protects cables
(phase and neutral) against overloads; this function is
based on true RMS measurements. Switch number 1 is
for the long time pickup setting (Ir) as shown in the unit
diagram. User can choose the LT pickup as 0.4 to
1.0 x In in steps of 0.1.
Type of curve
Protection curve is in accordance to IEC (International
Electro-technical Commission)
IEC Curve
IEC Curve specification is as follows:
• For 1.05 x Ir there will be no tripping with in 2 hr
• For 1.5 x Ir tripping time will be < 480 seconds
• For 7.2 x Ir tripping time will be < 20 seconds
Protection relays
When the ETU senses that the load current greater
than the rated Ir, it goes into “overload condition”.
On the M-PRO 18 Plus this is indicated on the display
on breaker status page that breaker is in “overload
pickup”.
Current protection
A
B
The unit also has a instantaneous pick up zone which is
set by the user wherein if the current Ibr through the
breaker is greater than pickup set the unit will initiate a
trip with no intentional time delay. Instantaneous
protection feature overrides the fixed time short-circuit
protection.
There are eight possible different settings for the
pickup including OFF.
C
X
The earth fault protection feature is optional and
detects any fault current downstream of the breaker.
An intentional user defined time delay can be set
before the unit can initiate a trip after having seen the
fault . There are five settings for the unrestricted earth
fault with minimum setting at 0.4 to a maximum of
1.0 times In.
M-PRO18 Plus - Example of LED display status
A.13
M-PACT Plus
Technical overview
Timing & accuracy
Timing shall be as per the curve selected, with accuracy of
± 10%.
A
B
C
X
Example
For 1000A breaker if the long time setting is at 0.5 then
for IEC selected curve
LT pick up is at Ir = In x 0.5; 1000 x 0.5 = 500A
For 1.05 x Ir i.e. at 1.05 x 500 = 525A
there will be no tripping with in 2 hr
For 1.5 x Ir i.e. at 1.5 x 500 = 750A
tripping time will be with in 480 seconds.
For 7.2 x Ir i.e. at 7.2 x 500 = 3600A
tripping time will be <20 seconds.
Short-time protection
The short-time protection function protects the
distribution system against impedant short-circuits.
The short-time tripping delay can be used to ensure
discrimination with a downstream circuit breaker.
This function carries out true rms measurements.
Switch number 2 is for the short time pickup setting
(Isd), as shown in the unit diagram, which is dependent
on the LT switch setting as 1.5, 2, 3, 4, 6, 8, 10 & 12 x Ir.
In case of frame 3 it is 1.5, 2, 3, 4, 6, 8 & 10 x Ir.
Switch number 7 is for a short time delay setting as
0.1, 0.2, 0.4, 0.5, 0.6, 0.8 & 1.0 second for
frame 1 & 2 and 0.1, 0.2, 0.3 & 0.4 for frame 3.
Timing & accuracy
Tripping time is dependent on delay setting. If the fault
current is detected then,the unit intiates a trips after
waiting up to the set delay time. The accuracy of
pickup is ±10% of the set value.
Example
For 1000A breaker if the long time pickup setting is at
0.4 & short time pickup setting is at 10 with short time
delay at 0.5 then, LT pick up is at
Ir = In x 0.4; 1000 x 0.4 = 400A ST pick up is at
Isd = Ir x 10; 400 x 10 = 4000A
At 4000A, breaker goes into ST pickup and trips after
the delay 0.5 sec.
Instantaneous protection
The instantaneous protection function protects the
distribution system against solid short-circuits.
Contrary to the short-time protection function, the
tripping delay for instantaneous protection is not
adjustable.
The tripping order is sent to the circuit breaker as soon
as current exceeds the set value. This function carries
out peak measurements.
Switch number 5 is for the instantaneous pickup (I i).
User can choose the instantaneous pickup as OFF, 2, 3,
4, 6, 8, 10 & 12 x In.
For OFF setting instantaneous will be disabled.
In case of frame 3 the settings are: OFF, 2, 3, 4, 6, 8
and 10 x In.
Time & accuracy
If current greater than the set INST pickup is detected,
the unit will initiate a trip pulse, with in 50msec of
having seen the current .
The accuracy of pickup is ±10% of the set value.
Example
For 1000A rated breaker if the instantaneous setting
is at 10 then, instantaneous pick up is at
Ii = In x 10; 1000 x 10 = 10000A
If the current is more than 10000A then unit trips
instantaneously.
Unrestricted earth fault protection for frame 1 & 2
only
The unrestricted earth fault-protection function
protects the the distribution system against downstream earth fault in the system.
The unrestricted earth fault tripping delay can be
used to ensure discrimination with a downstream
circuit breaker.
The tripping order is sent to the circuit breaker as
soon as current exceeds the set value.
This function carries out true rms measurements.
Switch number 3 is for the unrestricted earth fault pickup (Ig).
User can choose the UEF pickup values as OFF
0.4, 0.6, 0.8 & 1 x In. Switch number 9 is for a UEF time
delay setting as 0.1, 0.2, 0.4, 0.6, 0.8 & 1.0 second.
Timing & accuracy
Tripping time is dependent on delay setting. If pick up
detected, the unit intiates trips after waiting up to the
set delay time.
The accuracy of pickup is ±10% of the set value.
Example
For 1000A breaker if the unrestricted earth fault setting
is at 0.8 with unrestricted earth fault delay at 0.2sec
then, UEF pick up is at
Ig = In x 0.8; 1000 x 0.8 = 800A
At 800A of leakage earth fault current , breaker goes
into UEF pickup and trips after the delay 0.2sec.
A.14
M-PACT Plus
Protection of the fourth pole on four-pole circuit
breakers(1) (Factory setting)
Protection of the neutral conductor depends on the
distribution system and the cross-section of the
conductor used.
Modes of neutral protection (factory settings)
There are three types of neutral protection:
• Neutral unprotected (0%)
• Half neutral protection (50%)
• Full neutral protection (100%)
Protection settings available in frame 1 and frame 2
Half neutral protection(2)
The cross-sectional area of the neutral conductor is
half of the phase conductors. The long-time current
setting Ir for the neutral is equal to half the setting
value.
The short-time pick-up Isd for the neutral is equal to
half the setting value.
Full neutral protection
The cross-sectional area of the neutral conductor is
same as that of the phase conductors. The long-time
current setting Ir for the neutral is equal to the set
value.
The short-time pick-up Isd for the neutral is equal to the
set value.
Timing & accuracy
Tripping time is dependent on setting. For long time &
short time settings, after pick up, the unit trips, waiting
up to the set delay time as mentioned above.
The accuracy of pickup is ±10% of the set value.
Parameter
Pickup settings
Delay settings
Long time trip (Ir)
0.4, 0.5, 0.6, 0.7, 0.8,
Fixed
0.9 & 1.0 xIn
Short time trip (Isd)
Instantaneous trip (Ii)
1.5, 2, 3, 4, 6, 8,
0.1, 0.2, 0.4, 0.5, 0.6,
10 & 12 xIr
0.8 & 1.0 second
OFF, 2, 3, 4, 6, 8,
N/A
Protection relays
Neutral unprotected
The distribution system does not require protection of
the neutral conductor.
Example
For a breaker rating of 1000A, LT pickup setting of 1.0 &
ST pickup setting of 10,
LT pick up is at Ir = In x 1; 1000 x 1=1000A
ST pick up is at Isd = Ir x 10; 1000 x 10 =10000A.
If neutral is none rated then there is no neutral
protection.
If neutral is half rated then for neutral protection,
LT pick up is at 0.5 x 1000 = 500A & ST pickup is at
10 x 500 = 5000A.
If neutral is full rated then for neutral protection,
LT pick up is at 1.0 x 1000 = 1000A & ST pickup is at
10 x 1000 = 10000A.
10 & 12 xIn
Unrestricted earth
OFF, 0.4, 0.6, 0.8
0.1, 0.2, 0.4, 0.6,
Fault trip (Ig)
& 1xIn
0.8 & 1.0 second
A
B
Protection settings available in frame 3
Parameter
Pickup settings
Delay settings
Long time trip (Ir)
0.4, 0.5, 0.6, 0.7, 0.8,
Fixed
C
0.9 & 1.0 xIn
Short time trip (Isd)
1.5, 2, 3, 4, 6, 8, & 10 xIr
0.1, 0.2, 0.3, 0.4
Instantaneous trip (Ii)
OFF, 2, 3, 4, 6, 8,10 xIn
N/A
X
(1) This is a configuration parameter in M-PRO Plus.
(2) Set the LT setting to 1.0 while using half neutral protection.
A.15
M-PACT Plus
Technical overview
MCR making current release (1)
Making current release (MCR) is a breaker protection
which prevents the ACB from making and latching onto
a current that is greater than its make and latch
capability, typically a short-circuit . In order to ignore
the transient response of the system under different
power factors the first millisecond of any high level
signal is completely ignored. After this the signal must
exist for at least 1ms in order to cause a trip, to reduce
the likelihood of trips occurring due to signal or noise
spikes. As default the MCR protection will be enabled ,
and the pick-up level set to 50kA.
On an M-PRO Plus without auxiliary power, the unit will
be powering up as the ACB begins to close, i.e. as soon
as any current begins to flow through the breaker.
It is, therefore, necessary for the MCR protection and
trip circuitry to be enabled at power-up.
If the M-PRO Plus detects an MCR condition it will
initiate a trip.
MCR protection is only during closing of the breaker,
MCR will operate only when the bus bar switch is
open.
A
(1) Not applicable for frame 3
B
Timing & accuracy
Timing for the MCR is less than 10msec assuming a
50Hz or a 60Hz sinusoidal waveform, with accuracy of
0 to -20%.
C
Reset mechanism (2)
X
The M-PRO Plus unit will incorporate a mechanical
reset mechanism. When the M-PRO unit initiates the
breaker to trip, the reset button will be forced out
through the front of the M-PRO Plus unit , this can be
clearly seen at the front . The breaker cannot be closed
untill this switch has been reset or pushed in.
Reset will be manual or automatic - user selected
position.
(2) Not available in frame 3
Thermal memory
If the M-PRO Plus has an auxiliary power supply, the
thermal content will continue to decrease after the trip
has occurred (following the cooling method in use), and
therefore, if the ACB is re-closed soon after the trip, the
thermal effect of the previous current will have been
remembered, i.e. the unit will have a thermal memory.
For M-PRO 17 Plus/18 Plus in the presence of auxiliary
power supply, the thermal memory duration will be
defaulted to 20 min.
Healthy LED
After the power up healthy LED starts blinking.
Normally, when the unit is healthy, LED blinks like a
heartbeat .
If the healthy LED is continuously ON or OFF, then it is
an indication that unit is not operating normally.
Test connector & test box
A 26-pin connector is provided at the bottom side of
the unit with a protection cover over it .
The testing personnel for testing the healthiness and
configuration of the unit use this.
The M-PRO test box is used as a means of powering up
an M-PRO Plus, simulating faults by secondary injection
or for performing a forced trip of the breaker.
M-PACT Plus breaker will be in the test mode while
M-PRO Plus is connected to test box through test
connector.
Connection
Ensure that the battery is fully charged before
attempting any work that may require an extended
operating period. Full charge of a flat battery will be
achieved in an 8-hour charging period.
To maintain the battery life span it is not advisable to
charge a battery that still holds a charge, so always
allow the battery to discharge fully before re-charging.
Turn the test box on using the “Power On/Off” button;
the lamp above the switch should illuminate. Connect
the test box to the M-PRO Plus via the front panel
26-pin connector using 15-pin to 26-pin converter.
Do not test the M-PRO Plus with the charger still
connected, as this will disable power to the M-PRO Plus.
The thermal memory is a means to simulate cooling
characteristics of the load, when the breaker is in
series with the said load has tripped due to overload
condition (long time region)
The overload condition may be caused by:
• Repetitive motor starting
• Loads fluctuating near the protection settings
• Repeated circuit breaker closing on a fault
Even very short overloads produce a temperature rise
that is stored in the memory. This information stored in
the thermal memory reduces the tripping time.
The thermal content will start from zero at
power-up. On an M-PRO Plus, which has no auxiliary
power supply, if the ACB is re-closed soon after a trip,
any thermal effect of the current flowing prior to the
trip will be forgotten.
A.16
Note: should the “Battery Low” warning light illuminate
at any time then there is approximately 20 minutes of
usage left in the battery before power will be removed
from the M-PRO Plus.
M-PACT Plus
Re-charging
Ensure that the ambient temperature is between +15ºC
and +50ºC. With the test box unplugged from M-PRO
Plus, connect the charger unit via the charger socket at
the top of the test unit . The “Battery Charging” lamp
should illuminate. Wait a few seconds and ensure that
the lamp remains illuminated, as there can be enough
power in the charger to illuminate this lamp for a short
period of time even with the mains supply off.
MCR test(1)
This test use secondary injection. A DC signal is
imposed on the Rogowski input circuits of the
M-PRO Plus. Red, yellow and blue phases may be
tested individually. The neutral phase does not offer
this protection. The making current release (MCR) is set
to 50kA as standard and is active only whilst the ACB is
open/closing, and switches off when closed and
latched.
With the ACB open, the test box on and connected; turn
“Trip Enable“ on and select the “MCR Phase” test . Start
the test by pressing the “Test Now” button on the test
box. Immediately the M-PRO Plus recognizes the fault it
will try to fire the sensitive trip.
(1) Not available in frame 3
Powering M-PRO Plus
The test box may be used as a simple power box to
facilitate viewing of faults (e.g. after a trip) or the
history of trips. The feature may also be required for
changing protection settings.
For setting of the inputs, outputs and re-configuring the
factory settings, the breaker must be open. In this case
some form of external power is mandatory
(power box, APU or test box).
Portable power box only for M-PRO 30/40. For M-Pro 30
and 40, the auxiliary power supply is provided as standard.
Protection relays
Calibration
The equipment does not require calibration. It is
recommended that the general condition and
functionality be checked before each usage.
The M-PRO Plus power supply may be damaged if the
test connector is misinserted.
Force trip
This is the final test available on the test box. This test
is a quick way of tripping the breaker in order to test
the mechanical operation and reset mechanism. To
perform a forced trip, turn the test box on, connect to
M-PRO Plus, turn “Trip Enable” on and select “Force
Trip”. Pressing the “Test Now” button will cause the
M-PRO Plus to initiate a trip, reporting the trip as
normal (the fault level reported in the trip history is the
highest phase current at the time the trip was initiated).
A forced trip clears itself on removal of the test box.
There is no need to clear the existing fault as is
necessary for the other tests.
A
B
C
X
A.17
M-PACT Plus
LCD display
In M-PRO 18 Plus user can scroll different pages of the
display using the scroll switch.
There are four pages in the display menu which
scroll as follows:
Technical overview
1) Phase currents
L1 phase current (Amps) L2 phase current (Amps) L3
phase current (Amps)
Range is from 0 to 9999A.
A
B
If current is less than 8% of breaker rating then it shall
be displayed as <####A.
If current is greater than 9999 then it will be displayed
as 9999 in frame 1 and frame 2
In frame 3 readings above 9999A are displayed with ‘k’
replacing ‘000’.
If breaker is open, the currents will be displayed as 0.
TRIP SC L1,
TRIP SC L2,
TRIP SC L3,
INDICATES BREAKER TRIPPED ON
SHORT-CIRCUIT
TRIP SC N,
TRIP LT L1,
TRIP LT L2,
TRIP LT L3,
INDICATES BREAKER TRIPPED ON
OVERLOAD
TRIP LT N,
TRIP UEF,
O/L PICK UP,
INDICATES BREAKER TRIPPED ON
EARTH FAULT
INDICATES BREAKER IS IN OVERLOAD
REGION
NORMAL,
INDICATES BREAKER IS IN NORMAL
CONDITION
L1
L2
L3
<### <### <###A
TRIP INST,
INDICATES BREAKER IS TRIPPED ON
INSTANTANEOUS
2) Neutral and UEF current
FORCED TRIP,
Neutral current shall be displayed
Scroll
in the following format
switch
N = 0.5 x In UEF
<###A <###A
INDICATES BREAKER IS TRIPPED
THROUGH FORCE TRIP
SELF TEST TRIP.
• History will be updated of the last trip occurred at
the next power up of the unit overwriting the
previous history.
Scroll
C
3) Breaker status
switch
BREAKER STATUS
NORMAL
X
Scroll
4) History
switch
TRIP HISTORY
NO FAULTS
Scroll
switch
Display features
• After startup the display will be blank for the first 2
seconds. The first menu (all three phase currents) is
displayed by default . (After power up)
• The user can view other pages by pressing the scroll
switch (provided on the front panel).
• Backlit will function only when auxiliary power is
provided.
• The backlit can be turned on by pressing the Scroll
switch provided on the front panel. Backlit ON time is
one minute. On subsequent presses of the scroll key
various display pages can be viewed & backlit time
starts for one minute after last press of the scroll
switch.
• Breaker status can be following: (similar is for the
history)
A.18
Neutral and UEF page
• If UEF option is not provided for the unit , this page
displays only neutral current .
• If neutral protection is not provided then neutral
page will not be displayed.
• If neutral is not enabled, only UEF is provided, then
only UEF current will be displayed.
• If neutral is enabled, and UEF is disabled, then only
feutral current will be displayed.
• If both neutral and UEF are not provided then this
page will be removed, only 3 pages will scroll on the
display.
N = 0.5 x In
<###A
UEF
<###A
N = 0.5 x In ¤ Half rated neutral
N = 1.0 x In ¤ Full rated neutral
Wiring diagram M-PRO Plus
For frame 1, 2 & 3 refer pages C.5 and C.6
M-PACT Plus
M-PRO protection relays - Specifications
Trip unit
O
M-PRO
18 Plus
18Plus*
L
H
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O(1)
O
O
O
O
O
O(1)
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O(5)
O(5)
O(5)
O(5)
O
O
O
O(2)
O
O
O
O(2)
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O(3)
O
O(2)
O
O(3)
O
O(2)
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O(4)
O
O
O
O
O(4)
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O(5)
O
M-PRO 40
H
O
O
O
M-PRO 30
L
O(5)
O
O
O
O
O
O
O
O
O
O
O
O
O
Protection relays
Long Time Protection
Pickup adjustable from 0.4 to 1.0x In in steps of 0.1
Pickup adjustable from 0.4 to 1.0x In in steps of 0.01
Long Time Characteristic
To IEC 947-4, Class 20
To IEC 947-4, Class 40 (& IEC255, 80 combinations)
Fixed Short Time Protection
1.5, 2, 3, 4, 5, 6, 8 ,10 & 12 x Ir (frame 1 & 2 size)
1.5, 2, 3, 4, 6, 8 & 10 x Ir (frame 3 size only)
Instantaneous Trip (Ii)
OFF, 2, 3, 4, 6, 8 ,10 & 12 x In (frame 1 & 2 size)
OFF, 2, 3, 4, 6, 8 & 10 x In (frame 3 size only)
Fixed (MCR function)
Short time delay
0.1, 0.2, 0.4, 0.5, 0.6, 0.8, 1.0s. (frame 1& 2 size)
0.1, 0.2, 0.3, 0.4s. (frame 3 size only)
Inst to 1.0s in 0.1 steps
Short time I2t Protection (Inverse Short Circuit)
0.1 times selected long time
Pick-up, 1.5, 2, 3, 4, 6, 8, 10 and 12 x Ir
Neutral Protection
Fixed Neutral Protection (50% or 100%) (Factory setting)
Adjustable Neutral Protection
Earth fault protection
Unrestricted Earth Fault (UEF) (6)
Restricted Earth Fault (REF)
Standby Earth Fault (SEF)
Combinations of UEF, REF & / or SEF
Earth fault pickup, OFF, 0.1 to 1.0x In. 0.01In steps
Earth fault pickup, OFF, 0.4 to 1.0x In. 0.2In steps
Time Delay: <100ms, 0.1, 0.2, 0.4, 0.6, 0.8 and 1.0s
Time Delay: Inst. To 1.0s in 0.1 steps
Earth fault cropping, 1 (OFF), 1.5, 2, 2.5, 3, 4, 5 and 6
Thermal Memory / Cooling Time
Fixed to at time constant of 20 minutes
Adjustable time constants, inst., 10,20,30,45,60,120,180 mins
Trip Indication
Healthy Unit LED
Warning & / or Alarm LED
Discrete LED’s for each fault type
Remote Indication (Fault code via communication facility)
Fault Analysis
Existing Fault Notification
Historic Trips (last 16)
Historic Fault (last trip only)
System Status
Breaker Status
Auxiliary Power Supply
Output Relays
Trip Initiated
HV Inter trip (linked to REF)
Watchdog/Watchdog disable (No output relay)
Remote ACB Switching (Open / Close via Comms. Unit)
Communications MODBUS Protocol
Trip Reset
Manual (Push Button) - Frame 1 & 2
Automatic - Frame 1 & 2
Monitoring
Ammeters
Load Monitoring
Operations Counter
Trip Alarm Contact (mechanical C/O)
Main Contact Maintenance Indication
Inputs
24-48V d.c.
110-130V d.c. or 110-250Va.c.
Auxiliary Power Supply
Plant Associated Memory Module (PAMM)
Circuit Protection Memory
Test Connector
16 way DIL Heater
26 way D-Type
M-PRO
17 Plus
17Plus*
A
B
C
X
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
(1) Mpro30 units can be provided with REF as standard feature to replace UEF but please specify correct order code.
(2) Remote indication becomes a standard feature when the Communications facility is specified.
(3) Standard feature when Restricted Earth Fault option is specified.
(4) Feature not available if communications option is specified.
(5) Requires permanent auxiliary power to operate continuously.
(6) For 3P breaker, 4 wires system, please order rogowski coil and CT separately.
L = Low voltage inputs
H = High voltage inputs
Standard O
Optional O
A.19
M-PACT Plus
Technical overview
M-PRO protection relays
M-PRO 30/40: Any combinations of two or three types
of protection can be factory pre-set earth fault curve
cropping: available for unrestricted or stand-by earth
fault options. This feature enables the user to vary the
tripping time in accordance with the prospective earth
fault detected.
A ‘Cropping Factor’ may be selected which is a multiple
of the chosen earth fault pick-up current .
This selects the desired level of current at which the
fixed time delay becomes effective.
Earth fault protection zone diagram
Plant associated memory module
M-PRO 30/40
Module (PAMM), fitted remote from the protection unit
that stores the M-PRO settings. This feature reduces
set-up time by down loading the original data if the
M-PRO is replaced or the moving portion of the ACB is
changed. The new unit will not require re-configuration
while ensuring error-free replacement and maintenance.
A
Adjustment method of setting
M-PRO 17 Plus: front panel rotary switches.
M-PRO 18 Plus: front panel rotary switches.
M-PRO 30/40: four key tactile keypad.
B
C
X
Neutral pole protection
M-PRO 17/18 Plus: factory-set to OFF, 50% or 100%
M-PRO 30/40: customer selectable between ‘OFF’, 50%
and 100%.
Thermal memory (with permanent auxiliary power
supply only)
To protect against unacceptable recurring or cyclic
overloads the M-PRO will track and memorise the
thermal effects of load current while the breaker is on
line. Tripping will be initiated when the cumulative
thermal effect of cyclic overloading reaches a
predetermined level.
M-PRO 17/18 Plus: factory adjustable time constants
(auxiliary power supply mandatory).
M-PRO 30/40: customer adjustable time constants
(auxiliary power supply included).
Trip alarm switch
All M-PRO’s: A 1 x NO or 1 x nc switch is operated by
the protection management unit trip mechanism when
the M-PRO has initiated a trip. Tripping is indicated until
the reset button on the M-PRO is pressed. In case of
automatic reset an impulse will be generated.
A.20
RESET function
All M-PRO’s: manual or auto reset function. (except
specific version)
Inputs
M-PRO 30/40: are provided with four opto-coupled
remote inputs to initiate alarm signals or tripping of the
circuit breaker in response to signals indicating a change
in the state of devices remotely positioned in the system.
The supply voltage of the remote inputs are 24/48V DC
(M-PRO 30L or M-PRO 40L) and 110/250V AC or
110/130V DC (M-PRO 30H or M-PRO 40H).
M-PACT Plus
Outputs
M-PRO 30/40 are provided with four relay outputs to
permit remote indication of changes in the state of the
circuit breaker and its protection, e.g. M-PRO initiated
trip / watchdog alarm / breaker main contact
maintenance alarm / remote fault / pre-trip alarm/load
monitoring.
This facility may also be used to transmit a remote trip
signal to a high voltage circuit breaker.
An external power supply is required to permit remote
output facilities.
Communication
M-PRO 40: by means of a RS485 4-wire serial link using
a MODBUS protocol, M-PRO protection units can be
linked for remote communication to provide a complete
system management and control.
Communication occurs in both directions.
Remote switching - each unit can be remotely opened
and closed
Remote adjustment - user settings and inputs may be
altered by remote command
Monitoring - ammeters, load monitoring, operations
counter, existing faults, trip history
Protection relays
Load monitoring
M-PRO 30/40 offers two alternative facilities of
monitoring the load, pre-alarm or load shedding.
Pre-trip alarm: this alarm will provide a warning when
the current measured is above 1.1x Ir and the thermal
content is above 60% thus indicating that a trip is likely
to occur.
Load shedding: load shedding will have two user
configurable current levels, the level which shedding
will start , and the level at which shedding will stop
(auxiliary power supply mandatory).
A
B
C
X
A.21
M-PACT Plus
*
**
Trip curves*
Overload & delayed short-circuit curves at Ir = 1.0 x In
N=I/Ir for overload & delayed short-circuit
N=I/In for instantaneous & ground
M-PRO Plus - frame 1 & frame 2
Technical overview
(2500 used as example)
10000
LT
has
7 available
LT has
7 available
settingsset tings :
0.4 toto
1.01.0xI
x ln innsteps
0.1 of 0.1
0.4
in softeps
Indicated: 1.0 x ln
Indi
cated : 1 .0 x I n
1000
A
100
B
X
Time to trip in seconds (s)
C
ST has 8 available set tings :
10
ST has 8 available settings:
1.5,2,2,
3,6,4,8, 6,
10x lr& 1 2 x Ir
1.5,
3, 4,
10 8,
& 12
Indicated:
1.5:x1lr,.56 x
x lrI r,
& 12
Indi cated
6 xx lrI r & 12
x Ir
1
ST Dadjustable
adjus table:
STD
0.1,
0.4,0.4,
0.5, 0.6,
& 1.0s
0.1,0.2,
0.2,
0.5,0.80.6,
0.8
Indicated: 0.1, 0.5, & 1.0s
& 1.0s
Indi cated : 0 .1, 0.5 & 1 .0s
0.1
Inst antane ous
re le as e
Instantaneous release
0.01
Making
Cu rre nt
Making
Current
Release:
50kA50k A
Re le ase:
0.001
0.1
1
10
Current as multiples of N**
A.22
100
M-PACT Plus
*
**
Trip curves*
Overload & delayed short-circuit curves at Ir = 1.0 x In
N=I/Ir for overload & delayed short-circuit
N=I/In for instantaneous & ground
M-PRO Plus - frame 3
10000
Trip curves
LT has 7 available set tings :
LT has 7 available settings
0.4
to 1.0xI n in s teps of 0.1
0.4 to 1.0 x ln in steps of 0.1
Indi
cated
Indicated:
1.0:x1ln.0 x I n
1000
A
Time to trip in seconds (s)
100
10
B
ST has 7 available
ST
has
7 available
settings:
set
tings
:
1.5,
3, 4,
1.5,2, 2,
3,6,4,8 &6,108x&lr 10 xIr
Indicated: 1.5 x lr, 6 x lr & 10 x lr
Indi cated : 1 .5 x I r, 6 x I r &
10 x I r
C
X
ST D adjus table:
STD
0.1,adjustable
0.2, 0.3 & 0.4
0.1, 0.2, 0.3, & 0.4s
Indi cated
Indicated:
0.1 : 0 .1
1
0.1
Inst antane ous
Instantaneous
release
8 xelr 8 x I r
re le as
0.01
0.1
1
10
100
Current as multiples of N**
A.23
M-PACT Plus
*
**
Trip curves*
Overload & delayed short-circuit curves at Ir = 1.0 x In
N=I/Ir for overload & delayed short-circuit
N=I/In for instantaneous & ground
M-PRO 30/40 - frame 1 & 2
Technical overview
100000
LT set at 1 x ACB rating (In)
LTD set at 35 s
SC set at 6 x Ir
SCD = 3 s
ST set at 12 x Ir
STD set at 300 ms
Type H: Instantaneous release at 80kA
10000
1000
LTD has 16 available settings
0,25...35 seconds at 7.2 x Ir
Indicated: 5 and 35 seconds
A
B
C
X
Time to trip in seconds (s)
100
LT set at 1 x ACB rating, In
LTD set at 5 s
ST set at 1.5 Ir
STD set at 300 ms
Type S: Instantaneous release at 50kA
SC has 8 available settings
1.5, 2, 3, 4, 6, 8, 10, 12 x Ir
Indicated: 6 x Ir
10
SCD is fixed at 10 x the
configured LT curve
Indicated: 3.5 seconds
1
Instantaneous release:
Type S 50kA
Type N 65kA
Type H 80kA
Indicated: S and H
ST has 8 available settings
1.5, 2, 3, 4, 6, 8, 10, 12 x Ir
Indicated: 1.5 x Ir and 12 x Ir
STD adjustable:
Inst to 1.0 s in 0.1 steps
Indicated: Inst, 100 & 300 ms
0.1
LT set at 1 x ACB rating, In
LTD set at 5 s
ST set at 1.5 Ir
STD set at INST
Type S: Instantaneous release at 50kA
0.01
0.1
1
10
Current as multiples of N**
A.24
100
M-PACT Plus
*
**
Trip curves*
Overload & delayed short-circuit curves at Ir = 1.0 x In
N=I/Ir for overload & delayed short-circuit
N=I/In for instantaneous & ground
M-PRO 30/40 - frame 1 & 2
100000
LT set at 1 x ACB rating, In
LTD set at 30 s
SC set at 6 x Ir
SCD = 3 s
ST set at 12 x Ir
STD set at 1 s
Type H: Instantaneous release at 80kA
Trip curves
10000
1000
A
LTD has 16 available settings
0.25...35 seconds at 7.2 x Ir
Indicated: 0.2 and 30 seconds
LT set at 1 x ACB rating, In
LTD set at 0.2 s
ST set at 1.5 Ir
STD set at Inst
Type S: Instantaneous release at 50kA
B
Time to trip in seconds (s)
100
C
X
SC has 8 available settings
1.5, 2, 3, 4, 6, 8, 10, 12 x Ir
Indicated: 6 x Ir
10
SCD is fixed at 10 x the
configured LT curve
Indicated: 3 seconds
ST has 8 available settings
1.5, 2, 3, 4, 6, 8, 10, 12 x Ir
Indicated: 1.5 x Ir and 12 x Ir
1
Instantaneous release:
Type S 50kA
Type N 65kA
Type H 80kA
Indicated: S and H
0.1
STD adjustable:
Inst to 1.0 s in 0.1 steps
Indicated: Inst and 1 s
0.01
0.1
1
10
100
Current as multiples of N**
A.25
M-PACT Plus
*
**
Earth fault protection curves*
Overload & delayed short-circuit curves at Ir = 1.0 x In
N=I/Ir for overload & delayed short-circuit
N=I/In for instantaneous & ground
M-PRO 30/40 - frame 1 & 2
Technical overview
1000
Earth fault pickup If
Adjustment = 0.1 to 1.0 x In
in 0.01 x In steps
Pickup If set at 1 x In
Cropping set at 6
Time delay set at 1 s
100
A
B
X
Time to trip in seconds (s)
C
10
Earth fault cropping C
Trip Time = Time delay x C x If/I
Adjustment = 1, 1.5, 2, 2.5, 3, 4, 5 & 6
Note: 1 = OFF
Indicated: C = 1.5 and 6
1
Time delay has 11 settings
Inst. to 1 s in steps of 0.1 s
Indicated: Inst., 0.1 s and 1 s
Pickup If set at 0.1 x In
Time delay set at 0.1 s
0.1
Pickup If set at 0.1 x In
Time delay set at inst.
0.01
0.01
0.1
1
10
Current as multiples of N**
A.26
100
1000
M-PACT Plus
*
**
Earth fault protection curves*
Overload & delayed short-circuit curves at Ir = 1.0 x In
N=I/Ir for overload & delayed short-circuit
N=I/In for instantaneous & ground
M-PRO 30/40 - frame 1 & 2
Earth fault protection curves
1000
Earth fault pickup If
Adjustment = 0.1 to 1.0 x In
in 0.01 x In steps
Pickup If set at 1 x In
Cropping set at 6
Time delay set at 1 s
100
A
B
Time to trip in seconds (s)
10
C
Earth fault cropping C
trip Time = Time delay x C x I f/I
Adjustment = 1, 1.5, 2, 2.5, 3, 4, 5 & 6
Note: 1 = OFF
Indicated: C = 1.5 and 6
X
1
Time delay has 11 settings
Inst. to 1 s in steps of 0.1 s
Indicated: Inst., 0.1 s and 1 s
Pickup If set at 0.1 x In
Time delay set at 0.1 s
0.1
Pickup If set at 0.1 x In
Time delay set at inst.
0.01
0.01
0.1
1
10
100
1000
Current as multiples of N**
A.27
M-PACT Plus
Earth fault protection curves*
*
**
Overload & delayed short-circuit curves at Ir = 1.0 x In
N=I/Ir for overload & delayed short-circuit
N=I/In for instantaneous & ground
M-PRO 17 Plus/18 Plus
frame 1 & frame 2
Technical overview
1000
100
C
Time to trip in seconds (s)
A
B
UEFhas
h as
4 availa
ble set tings
UEF
4 available
settings
0.4,
0.8,0.8
& 1.0
ln
0.4,0.6,
0.6,
& x1.0xI
n
Indicated:
0.4: x0ln,
& 1.0
Indi cated
.40.8
x Ixn,ln,0.8
x xI nln &
1.0 x I n
10
UEFDelay
Delay
adjust able :
UEF
adjustable:
<0.1,
0.1,
<
0.1, 0.2,
0.4,0.2,
0.6, 0.4,
0,8 & 0.6,
1.0 0.8
Indicated:
0.1,: 0
0.4
Indi cated
.1,& 1.0s
0.4 & 1 .0s
& 1 .0
1
X
0.1
0.01
0.1
1
10
Current as multiples of N**
A.28
100
M-PACT Plus
Accessories for frame 1 & 2
Shunt trip
A wide range of optional accessories have been
developed that are compatible with all M-PACT Plus air
circuit breakers, regardless of nominal rating or Frame
size. Each one incorporates ‘easy-fit’ design features
for quick installation, either in the factory or
by the user on site.
Motorised spring charging unit
The unique motor/gearbox unit is specially designed to
operate with the full range of M-PACT Plus breakers.
It is easily fitted with just three bolts.
In the event of circuit breaker closure, this unit will
automatically recharge the spring and makes it ready
for instant reclosure should the need arise.
High speed recharging ensures that the springs are
fully charged within approximately three seconds
following a release.
As an optional feature, a “springs charged” contact is
available for the motor unit .
Closing coil
The closing coil is an easy-to-fit , clip-on unit , with
simple plug-in connectors. This permits either local or
remote release of the spring charged closing
mechanism by electrical operation.
An additional anti-pumping safety feature also ensures
that the electrical closing signal must be released
before further closure is attempted, and a cut-off is
instigated should a closing signal be maintained.
Because each coil operates within a wide voltage
range, the number of individually rated coils required is
drastically reduced.
Undervoltage release
Accessories
Energisation, locally or remote, will instantaneously
activate the circuit breaker mechanism, ensuring rapid
disconnection of the main contacts.
In addition, a series connected auxiliary switch ensures
automatic isolation whenever the circuit breaker is
open.
Shunt trip releases also have a wide operational
voltage range, and they include the same easy-fit ,
clip-on/plug-in connectors as the closing coil.
A
B
C
Instantaneously releases the circuit breaker trip
mechanism when the supply voltage dip below the
pre-set value. Simple to install, these devices have the
same easy-fit features as previously described.
Note: This is a ‘no-volt/no-close device. The circuit
breaker cannot be closed (manually or electrically)
unless the undervoltage release coil is energized.
X
Time delay undervoltage release
Similar to the above, but this electronic device prevents
nuisance tripping of the circuit breaker if circuit
interruption is not desirable when supply voltage drop
is only transient . Fixed time delay
3 sec ± 1 sec.
Due to its principle of action the UV is suitable for
emergency stop situations.
A.29
M-PACT Plus
Auxiliary trip combination
The M-PACT Plus circuit breaker can be equipped with
the following auxiliary trips or releases
1 x shunt trip + 1 x closing coil +
1 x undervoltage release or 1 time delay
undervoltage release
Technical overview
Auxiliary switches
A
B
C
The M-PACT Plus circuit breaker is equipped with 5 NO
and 3 NC auxiliary switches as standard.
Maximum number of contacts is 8, for alternative
configurations please contact your local customer
service for availability.
Lock and key types
Castell: type FS1 lock with key type FK4 key, 45° clockwise rotation to trap the key, 7/8"x3/8" square spindle.
Ronis: type 1104B lock with standard key, 1/4" turn
rotation to trap the key, compulsory spindle size.
Profalux: type B20D4Y lock with key type S1 (without
cam), 1/4" turn rotation to trap the key, compulsory
spindle size.
Fortress: type H31/LH lock with flip cap and standard
key, 45° clockwise rotation to trap the key, 7/8"x3/8"
square spindle.
Cassette main terminal
adaptors
Mechanical operation counter
Easily fitted, this useful
accessory may be specified
for use with either manual
or motor charged M-PACT
Plus circuit breakers. It is
clearly visible through the
front panel, and the counter
provides an accurate record
of the cumulative number
of complete breaker closing
operations.
Type ‘N’: 65kA rear connection shown above.
Circuit breaker
Key interlock facility
Combinations of rear and front access connections
possible for entire range. Tested and approved from 50
to 80kA.
X
Ready-to-fit interlocking devices such as Castell, Ronis,
Profalux and Fortress, for installation between separate
circuit breakers, available in kit form. This valuable
safeguard ensures that a circuit breaker cannot be
closed unless the dedicated key has been inserted and
secured within the lock.
Note: Castell, Fortress or Profalux locks and keys cannot be supplied by GE. Please order separately from
your local supplier.
A.30
Type ‘N’: 1600A, 65kA front access connection shown above.
To simplify main busbar or cable termination,
M-PACT Plus provides a full range for rear and/or front
access connection.
Bolt-on adaptor kits can be fitted easily to suit either
horizontal or vertical connections.
M-PACT Plus
Cable/busbar earthing device
Carriage position switch
These are the main isolating contacts which are fitted
to the rear terminals on the moving portion of the
withdrawable unit .
As part of standard inspection and maintenance
procedures, cluster contacts have been designed to be
easily and quickly removed and replaced using
universal cluster pliers.
Circuit breaker insertion
interlock
Accessories
All M-PACT Plus circuit breakers can be fitted with an
earthing device. It has a short-circuit fault capacity
equal to the Icw rating of the breaker. This permits
either the feeder cables or the busbar to be safety held
at earthed potential and locked during system
maintenance operations.
Cluster contacts
A
B
C
X
Available as an optional device for mounting within the
base of the cassette, this switch provides six single pole
changeover contacts for local or remote electrical
indication of the circuit breaker status:
connected, test and disconnected.
The disconnected position is indicated only when
minimum isolating distances between contacts on both
the main and auxiliary circuits have been achieved.
This option is in addition to the mechanical indicators
which are fitted as standard.
When installed, the carriage switch is IP2X protected
and includes wiring to a terminal block located on the
left-hand side of the cassette.
By incorporating this optional security interlock device
into a system, it prevents the inadvertent insertion of
an incorrectly rated withdrawable circuit breaker into a
cassette.
Note: The carriage position switch is an option only
suitable for withdrawable circuit breakers.
A.31
M-PACT Plus
Cassette interlock
Automatic transfer switches (ATS)
Technical overview
The ATS ensures the continuity of electric supply to an
installation with minimum interruption by making an
automatic transfer from the normal supply to
emergency source. The emergency source can be
either a transformer or generator supply and the
M-PACT Plus air circuit breakers are governed
automatically by the transfer controller, which selects
the available source.
A
Available for withdrawable circuit breakers only, this
sophisticated interlock system secures the circuit
breaker in the disconnected position by means of a
Ronis or Profalux key. When the key is removed, the
safety shutters are automatically locked in position,
thus preventing access to the contacts and also ensuring
that the racking mechanism is not operable. For lock
and key details refer to key interlock facility section
(page A30)
Sealed door panel escutcheon
B
C
An optional IP54
complete front door
panel is available
should a higher degree
of protection be
necessary.
(Only for frame 1 & 2)
X
Cable interlocks
Circuit breaker handling truck
Specifically
designed for use
with the M-PACT
Plus range, this
dedicated handling
truck is a useful
accessory when
faced with the task
of inserting or
removing the circuit
breaker from its
panel, or when
transporting the
unit should it be
outside its cassette.
Installers will also
find it particularly
valuable for top-tier
mounted circuit
breakers.
A.32
Cable interlocking version shown above available for
fixed and withdrawable circuit breakers.
These units enable the direct interlocking of
M-PACT Plus circuit breakers, either mounted side by
side or stacked. The interlocking mechanisms are
connected by a specially designed cable and provides
interlocking between the breakers 1 from 2, 1 from 3
and 2 from 3 configurations
Any mix of current ratings / pole configurations can be
accommodated.
Standard cable lengths available: 1.0, 1.6, 2.0, 2.5, 3.0,
3.5 and 4.0 meters.
(Please contact our technical customer service
department if longer length is required.)
M-PACT Plus
Interlocks
Mechanical interlocks can be fitted to the following electrical systems and can link 2 and/or 3 circuit breakers.
Any nominal rating, frame size, number of poles or type (fixed pattern or withdrawable) can be interlocked.
Typical circuit
Interlock configuration
Possible combinations
B1
0
I
0
Type A
1 from 2 way interlock
2 cable configuration
Interlocking between 2 circuit breakers.
1 normal power supply
1 generator (emergency) supply
1 from 3 way interlock
6 cable configuration
Interlocking between 3 circuit breakers.
3 power supplies (generator or
transformers) feeding the same busbar but
parallel operation is prevented.
Circuit breaker B1 can only close
if B2 is open
Circuit breaker B2 can only close
if B1 is open
B1
0
I
0
0
B2
0
0
I
0
B3
0
0
0
I
Accessories
Type B
B2
0
0
I
Only 1 from 3 breakers can be closed
A
B
Type C
2 from 3 way interlock
6 cable configuration
Interlocking between 3 circuit breakers.
2 bus sections can be powered by a single
transformer (bus coupler closed) or by both
transformers (bus coupler open).
Type D
1 from 3 way interlock variant
4 cable configuration (2 cables for bus
coupler)
Interlocking between 3 circuit breakers.
2 normal power supplies not set in parallel
1 power supply may assist the priority
circuit
B1
0
I
0
0
I
0
I
B2
0
0
0
I
I
I
0
B3
0
0
I
0
0
I
I
Any 2 from 3 breakers can be closed
Any 1 from 3 breakers can be closed
2 breakers must be closed to prevent the
3rd breaker from closing
B1
0
I
0
I
0
B2
0
0
0
0
I
C
X
B3
0
0
I
I
0
Circuit breaker B1 and/or B3 can be closed
only if B2 is open
Circuit breaker B2 can only be closed
if B1 & B3 are both open
A.33
M-PACT Plus
Accessories for frame 3 only
Shunt trip
A wide range of optional accessories are designed
exclusively for frame size 3 of M-PACT Plus and can be
installed, either in the factory or by the user at site.
Technical overview
Motorised spring charging unit
The shunt trip can be easily fitted with just two screws.
Energised locally or remote and will instantaneously
activate the circuit breaker mechanism, ensuring rapid
disconnection of the main contact .
An auxiliary switch connected in series ensures
automatic isolation whenever the circuit breaker is
open.
A
Undervoltage release
B
C
X
The motor/gearbox unit is easily fitted with just three
screws bolts. In the event of circuit breaker closure, this
unit will automatically recharge the spring and make it
ready for instant reclosure should the need arise (other
charging methods on request). Speed recharging
ensures that the springs are fully charged within
approximately 9 seconds after motor starts.
As an optional feature “breaker ready for closure”
contact is available.
Circuit breaker closing coil
The closing coil is fitted with just two screws. This
permits either local or remote release of the spring
charged closing mechanism by electrical operation.
A.34
The undervoltage release is simple and easy to install.
The unit is suitable for remote tripping, voltage
monitoring and for interlocking purposes. The circuit
breaker cannot be closed manually or electrically if the
release is denergised.
The undervoltage release is designed for continuous
operation. Due to its principle of action the undervoltage release is suitable for EMERGENCY STOP
situations. Time delayed undervoltage release (delay
time tv = 1.5 ± 0.5s) is available by connecting to the
standard UVR 220V DC an additional electronic delay
circuit . Circuit is housed in separate CK1 steel
enclosure.
Auxiliary trip combination
Auxiliary trip combination is available with 2 x shunt
trip + 1 x closing coil + 1 x undervoltage release or 1
time delay undervoltage release.
M-PACT Plus
Auxiliary switches
Lock and key types
The M-PACT Plus Frame 3 circuit breaker is equipped
with 4NO and 6NC auxiliary switches as standard.
Castell: type FS1 lock with key type FK4 key, 45° clockwise rotation to trap the key, 7/8"x3/8" square spindle.
Ronis: type 1104B lock with standard key, 1/4" turn
rotation to trap the key, compulsory spindle size.
Mechanical operation counter
Carriage position switch
Accessories
Easily fitted with two screws may be specified for use
with either manual or motor charged M-PACT Plus
Frame 3 circuit breakers.
It is clearly visible through the front panel, and the
counter provides an accurate record of the cumulative
number of complete breaker charging operations.
Key interlock facility
A
B
Available as an optional device for mounting within
the base of the cassette. This switches are provided
for monitoring the positions connected, test and disconnected of the circuit breaker in the cradle and are
suitable for electrical interlocking purposes.
Max four auxiliary switches with 2NC and 2NO each.
C
X
Note: the carriage position switch is an option only
suitable for withdrawable circuit breakers.
Cable interlock - type A
Mounting kit for mechanical interlock of two
M-PACT Plus Frame 3 circuit breakers for fixed
installation or withdrawable pattern without electrical
interlock: (provided supplementary), installation
alternatively side-by-side or stacked. One 2.3 m cable
is provided in standard with each frame 3 interlock kit .
Typical circuit
Interlock configuration
Type A
Ready-to-fit interlocking devices such as Ronis or
Castell for installation into circuit breakers, available in
kit form. This valuable safeguard ensures that a circuit
breaker cannot be closed unless the dedicated key has
been inserted and secured within the lock.
Interlocking between 2 breakers.
1 normal power supply
1 emergency supply
Possible combinations
B1
0
0
I
B2
0
I
0
Circuit breaker B1 can only close
if B2 is open
Circuit breaker B2 can only close
if B1 is open
Note: Castell lock and key are not supplied by GE.
Please order separately from your local supplier.
A.35
M-PACT Plus
Accessories performance data
Operating voltage (V)
AC
DC
Auxiliary and
carriage swtich
250
Frame 1 & 2
125
250
Technical overview
230
Auxiliary contacts
Frame 3
Carriage switch
Frame 3
Frame 1 & 2
220
110
60
24
400
220 - 250
110 - 127
220 - 240
Motor operator
110 - 120
Frame 3
110
220 - 250
110 - 127
42 - 48
24 - 30
220 - 240
125
110 - 120
60
48
Operating range
-
0.85 to 1.1 times
rated voltage
Frame 1 & 2
Frame 3
A
B
Frame 1 & 2
110 - 120
60
48
42
24
220 - 250
110 - 130
220
125
110 - 120
60
48
24
220 - 250
110 - 130
40 - 48
24 - 30
400
410
0.85 to 1.1 times
rated voltage
C
Frame 3
X
Frame 1 & 2
Instantanious
undervoltage
release
Frame 3
Auxiliary power unit Frame 1 , 2 & 3
A.36
110 - 120
60
48
42
24
380 - 440
220 - 250
110 - 130
240
220 - 230
120 / 125
110
60
48
42
24
95 - 265
350
350
350
350
350
350
0.70 to 1.1 times
rated voltage
220 - 240
Shunt trip
350
440
500
440
420
410
300
24
220 - 250
110 - 130
40 - 48
24 - 30
220 - 240
Closing coil
500
450
42
220 - 250
110 - 130
Power consumption
VA max.
Watt max.
185
185
185
185
185
185
410
350
220
125
110 - 120
60
48
24
110 - 130
42 - 48
24 - 30
240
220 - 230
120 / 125
110
60
48
42
24
24 - 264
0.85 to 1.1 times
rated voltage
350
350
350
350
350
holds 0.85 to 1.1 x
rated voltage
release 0.7 to 0.35 x
rated voltage
-
185
185
185
185
185
185
400
80 mA
90 mA
160 mA
190 mA
330 mA
420 mA
490 mA
910 mA
-
80 mA
90 mA
160 mA
190 mA
330 mA
420 mA
490 mA
910 mA
12
Rating
(Amps resistive)
10
5
0.25
10
1
2
4
10
10
6
-
M-PACT Plus
B.2
B.4
B.6
B.8
B.10
B.12
B.14
B.15
B.16
B.17
B.18
B.20
Air circuit breaker - type S - 50kA - Non-automatic
Air circuit breaker - type S - 50kA - Automatic
Air circuit breaker - type N - 65kA - Non-automatic
Air circuit breaker - type N - 65kA - Automatic
Air circuit breaker - type H - 80kA - Non-automatic
Air circuit breaker - type H - 80kA - Automatic
Air circuit breaker - type C - 100kA - Non-automatic/ Automatic
M-PRO protection relay
Frame 1 & 2 - electrical accessories
Frame 3 - electrical accessories
Mechanical accessories
Spare parts
Technical overview
A
Order codes
B
Wiring diagrams / Dimensional drawings
C
Numerical index
X
B.1
M-PACT Plus
Air circuit breaker - type S - 50kA - Non-automatic
Frame 1 & 2
Basic circuit breaker manually operated, non automatic (switch only, no protection unit option
available), 5 NO and 3 NC auxiliary switches.
Withdrawable pattern - basic circuit breaker and cassette with flat copper terminals, rear
connected. Fixed Pattern - basic circuit breaker with rear horizontal terminals.
Withdrawable and fixed pattern
Frame size Rating (A)
1
400
Order codes
1
800
1
1000
1
1250
1
1600
1
2000
1
B
2500
2
C
2000
2
2500
2
X
3200
2
4000
Withdrawable
Position
of the neutral
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
630
1
A
Poles
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Fixed pattern
Cat. No.
Ref. No.
Cat. No.
Ref. No.
MS31W04
MS4L1W04
MS4R1W04
MS31W06
MS4L1W06
MS4R1W06
MS31W08
MS4L1W08
MS4R1W08
MS31W10
MS4L1W10
MS4R1W10
MS31W12
MS4L1W12
MS4R1W12
MS31W16
MS4L1W16
MS4R1W16
MS31W20
MS4L1W20
MS4R1W20
MS31W25
MS4L1W25
MS4R1W25
MS32W20
MS4L2W20
MS4R2W20
MS32W25
MS4L2W25
MS4R2W25
MS32W32
MS4L2W32
MS4R2W32
MS32W40
MS4L2W40
MS4R2W40
405103
405102
405316
405105
405104
405318
405107
405106
405320
405109
405108
405322
405111
405110
405324
405113
405112
405326
405115
405114
405328
405117
405116
405330
405119
405118
405332
405121
405120
405334
405123
405122
405336
405125
405124
405338
MS31F04
MS4L1F04
MS4R1F04
MS31F06
MS4L1F06
MS4R1F06
MS31F08
MS4L1F08
MS4R1F08
MS31F10
MS4L1F10
MS4R1F10
MS31F12
MS4L1F12
MS4R1F12
MS31F16
MS4L1F16
MS4R1F16
MS31F20
MS4L1F20
MS4R1F20
MS31F25
MS4L1F25
MS4R1F25
MS32F20
MS4L2F20
MS4R2F20
MS32F25
MS4L2F25
MS4R2F25
MS32F32
MS4L2F32
MS4R2F32
MS32F40
MS4L2F40
MS4R2F40
405133
405132
405366
405135
405134
405368
405137
405136
405370
405139
405138
405372
405141
405140
405374
405143
405142
405376
405145
405144
405378
405147
405146
405381
405149
405148
405384
405151
405150
405387
405153
405152
405391
405155
405154
405393
Rear connections
Frame
size Rating (A) Poles
1
400 to 1600
1
400 to 1600
1
2000 & 2500
2
800 to 3200
2
4000
3
4
3
4
3
4
3
4
3
4
Withdrawable or cassettes
Fixed pattern
Cat. No.
Ref. No.
Type
Cat. No.
Ref. No.
Type
RT1HOR
RT1HOR
RT1VER
RT1VER
RT1UNI
RT1UNI
RT2UNI
RT2UNI
N/A
N/A
403680
403680
403681
403681
405600
405600
405601
405601
N/A
N/A
Horizontal
Horizontal
Vertical
Vertical
Universal
Universal
Universal
Universal
Vertical
Vertical
RT1SVFIX
RT1SVFIX
RT1SNVFIX
RT1SNVFIX
RT2SNHVFIX
RT2SNHVFIX
RT2SNHVFIX
RT2SNHVFIX
405603
405603
405609
405609
405621
405621
405621
405621
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Rear Connections specified in multiples of 3, 4, 6 or 8 dependant on 3 or 4 pole configuration - top and / or
bottom connections.
Front access connections
Withdrawable
TOP connections
BOTTOM connections
B.2
Frame size
Rating (A)
Poles
Cat. No.
Ref. No.
Cat. No.
Ref. No.
1
400 to 1600
1
2000 to 2500
2
800 to 3200
2
4000
3
4
3
4
3
4
3
4
FA31WS16T
FA41WS16T
FA31WS25T
FA41WS25T
FA32WS32T
FA42WS32T
FA32WS40T
FA42WS40T
405921
405922
405923
405924
405925
405926
405927
405928
FA31WS16B
FA41WS16B
FA31WS25B
FA41WS25B
FA32WS32B
FA42WS32B
FA32WS40B
FA42WS40B
406021
406022
406023
406024
406025
406026
406027
406028
M-PACT Plus
Front access connections
Fixed pattern
TOP connections
BOTTOM connections
Frame size
Rating (A)
Poles
Cat. No.
Ref. No.
Cat. No.
Ref. No.
1
400 to 1600
1
2000 to 2500
2
800 to 3200
2
4000
3
4
3
4
3
4
3
4
FA31FS16T
FA41FS16T
FA31FS25T
FA41FS25T
FA32FS32T
FA42FS32T
FA32FS40T
FA42FS40T
405933
405934
405935
405936
405937
405938
405939
405940
FA31FS16B
FA41FS16B
FA31FS25B
FA41FS25B
FA32FS32B
FA42FS32B
FA32FS40B
FA42FS40B
406033
406034
406035
406036
406037
406038
406039
406040
Cassette only
Frame size
Rating (A)
Poles
Cat. No.
Ref. No.
1
400 to 1600
1
2000 to 2500
2
800 to 3200
2
4000
3
4
3
4
3
4
3
4
MS31C16
MS41C16
MS31C25
MS41C25
MS32C32
MS42C32
MS32C40
MS42C40
405341
405340
405343
405342
405355
405354
405365
405364
Moving portion only
Basic circuit breaker manually operated, non automatic (switch only, no protection unit
option available), 5 NO and 3 NC auxiliary switches and cluster contacts.
Frame size
Rating (A)
Poles
1
400
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
1
1
1
1
1
1
1
2
2
2
2
630
800
1000
1250
1600
2000
2500
2000
2500
3200
4000
Position
of the neutral
Cat. No.
Ref. No.
Left
Right
MS31M04
MS4L1M04
MS4R1M04
MS31M06
MS4L1M06
MS4R1M06
MS31M08
MS4L1M08
MS4R1M08
MS31M10
MS4L1M10
MS4R1M10
MS31M12
MS4L1M12
MS4R1M12
MS31M16
MS4L1M16
MS4R1M16
MS31M20
MS4L1M20
MS4R1M20
MS31M25
MS4L1M25
MS4R1M25
MS32M20
MS4L2M20
MS4R2M20
MS32M25
MS4L2M25
MS4R2M25
MS32M32
MS4L2M32
MS4R2M32
MS32M40
MS4L2M40
MS4R2M40
405803
405804
405524
405805
405806
405526
405807
405808
405528
405809
405810
405542
405811
405812
405548
405813
405814
405582
405815
405816
405584
405817
405818
405586
405819
405820
405588
405821
405822
405590
405823
405824
405592
405825
405826
405594
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
ACB’s - type S
Basic cassette with flat copper terminals rear connected, integral racking handle, safety
shutters and lockable safety features.
A
B
C
X
Earthing device
Frame size
Rating (A)
Poles
Cat. No.
Ref. No.
1
400 to 1600
1
2000 to 2500
2
3200 to 4000
3
4
3
4
3
4
EDF13P16
EDF14P16
EDF13P25
EDF14P25
EDF23P40
EDF24P40
405661
405660
405663
405662
405665
405664
B.3
M-PACT Plus
Air circuit breaker - type S - 50kA - Automatic
Frame 1 & 2 (Please select trip unit type in page B.15)
Basic circuit breaker manually operated, automatic (must be fitted with an M-Pro Protection Unit as
listed on page B15), 5 NO and 3 NC auxiliary switches.
Withdrawable pattern - basic circuit breaker and cassette with flat copper terminals, rear
connected. Fixed Pattern - basic circuit breaker with rear horizontal terminals.
Withdrawable and fixed pattern
Frame size Rating (A)
1
400
Order codes
1
800
1
1000
1
1250
1
1600
1
2000
1
B
2500
2
2000
2
C
2500
2
X
3200
2
4000
Withdrawable
Position
of the neutral
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
630
1
A
Poles
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Fixed pattern
Cat. No.
Ref. No.
Cat. No.
Ref. No.
MS31W04-A
MS4L1W04-A
MS4R1W04-A
MS31W06-A
MS4L1W06-A
MS4R1W06-A
MS31W08-A
MS4L1W08-A
MS4R1W08-A
MS31W10-A
MS4L1W10-A
MS4R1W10-A
MS31W12-A
MS4L1W12-A
MS4R1W12-A
MS31W16-A
MS4L1W16-A
MS4R1W16-A
MS31W20-A
MS4L1W20-A
MS4R1W20-A
MS31W25-A
MS4L1W25-A
MS4R1W25-A
MS32W20-A
MS4L2W20-A
MS4R2W20-A
MS32W25-A
MS4L2W25-A
MS4R2W25-A
MS32W32-A
MS4L2W32-A
MS4R2W32-A
MS32W40-A
MS4L2W40-A
MS4R2W40-A
406177
406178
406260
406179
406180
406262
406181
406182
406264
406183
406184
406266
406185
406186
406268
406187
406188
406270
406189
406190
406272
406191
406192
406274
406193
406194
406276
406195
406196
406278
406197
406198
406280
406199
406200
406282
MS31F04-A
MS4L1F04-A
MS4R1F04-A
MS31F06-A
MS4L1F06-A
MS4R1F06-A
MS31F08-A
MS4L1F08-A
MS4R1F08-A
MS31F10-A
MS4L1F10-A
MS4R1F10-A
MS31F12-A
MS4L1F12-A
MS4R1F12-A
MS31F16-A
MS4L1F16-A
MS4R1F16-A
MS31F20-A
MS4L1F20-A
MS4R1F20-A
MS31F25-A
MS4L1F25-A
MS4R1F25-A
MS32F20-A
MS4L2F20-A
MS4R2F20-A
MS32F25-A
MS4L2F25-A
MS4R2F25-A
MS32F32-A
MS4L2F32-A
MS4R2F32-A
MS32F40-A
MS4L2F40-A
MS4R2F40-A
405217
405216
405186
405219
405218
405278
405239
405238
405296
405241
405240
405298
405247
405246
405390
405249
405248
405392
405251
405250
405404
405253
405252
405682
405255
405254
405712
405269
405268
405722
405271
405270
405748
405277
405276
405786
Rear connections
Fram
e size Rating (A) Poles
1
400 to 1600
1
400 to 1600
1
2000 &
2500
2
800 to 3200
2
4000
3
4
3
4
3
4
3
4
3
4
Withdrawable or cassettes
Fixed pattern
Cat. No.
Ref. No.
Type
Cat. No.
Ref. No.
Type
RT1HOR
RT1HOR
RT1VER
RT1VER
RT1UNI
RT1UNI
RT2UNI
RT2UNI
N/A
N/A
403680
403680
403681
403681
405600
405600
405601
405601
N/A
N/A
Horizontal
Horizontal
Vertical
Vertical
Universal
Universal
Universal
Universal
Vertical
Vertical
RT1SVFIX
RT1SVFIX
RT1SNVFIX
RT1SNVFIX
RT2SNHVFIX
RT2SNHVFIX
RT2SNHVFIX
RT2SNHVFIX
405603
405603
405609
405609
405621
405621
405621
405621
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Rear Connections specified in multiples of 3, 4, 6 or 8 dependant on 3 or 4 pole configuration - top and / or
bottom connections.
Front access connections
Withdrawable
TOP connections
BOTTOM connections
B.4
Frame size
Rating (A)
Poles
Cat. No.
Ref. No.
Cat. No.
Ref. No.
1
400 to 1600
1
2000 to 2500
2
800 to 3200
2
4000
3
4
3
4
3
4
3
4
FA31WS16T
FA41WS16T
FA31WS25T
FA41WS25T
FA32WS32T
FA42WS32T
FA32WS40T
FA42WS40T
405921
405922
405923
405924
405925
405926
405927
405928
FA31WS16B
FA41WS16B
FA31WS25B
FA41WS25B
FA32WS32B
FA42WS32B
FA32WS40B
FA42WS40B
406021
406022
406023
406024
406025
406026
406027
406028
M-PACT Plus
Front access connections
Fixed pattern
TOP connections
BOTTOM connections
Frame size
Rating (A)
Poles
Cat. No.
Ref. No.
Cat. No.
Ref. No.
1
400 to 1600
1
2000 to 2500
2
800 to 3200
2
4000
3
4
3
4
3
4
3
4
FA31FS16T
FA41FS16T
FA31FS25T
FA41FS25T
FA32FS32T
FA42FS32T
FA32FS40T
FA42FS40T
405933
405934
405935
405936
405937
405938
405939
405940
FA31FS16B
FA41FS16B
FA31FS25B
FA41FS25B
FA32FS32B
FA42FS32B
FA32FS40B
FA42FS40B
406033
406034
406035
406036
406037
406038
406039
406040
Cassette only
Frame size
Rating (A)
Poles
Cat. No.
Ref. No.
1
400 to 1600
1
2000 to 2500
2
800 to 3200
2
4000
3
4
3
4
3
4
3
4
MS31C16
MS41C16
MS31C25
MS41C25
MS32C32
MS42C32
MS32C40
MS42C40
405341
405340
405343
405342
405355
405354
405365
405364
Moving portion only
Basic circuit breaker manually operated, automatic (must be fitted with an M-Pro Protection
Unit as listed on page B15), 5 NO and 3 NC auxiliary switches and cluster contacts.
Frame size
Rating (A)
Poles
1
400
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
1
1
1
1
1
1
1
2
2
2
2
630
800
1000
1250
1600
2000
2500
2000
2500
3200
4000
Position
of the neutral
Cat. No.
Ref. No.
Left
Right
MS31M04-A
MS4L1M04-A
MS4R1M04-A
MS31M06-A
MS4L1M06-A
MS4R1M06-A
MS31M08-A
MS4L1M08-A
MS4R1M08-A
MS31M10-A
MS4L1M10-A
MS4R1M10-A
MS31M12-A
MS4L1M12-A
MS4R1M12-A
MS31M16-A
MS4L1M16-A
MS4R1M16-A
MS31M20-A
MS4L1M20-A
MS4R1M20-A
MS31M25-A
MS4L1M25-A
MS4R1M25-A
MS32M20-A
MS4L2M20-A
MS4R2M20-A
MS32M25-A
MS4L2M25-A
MS4R2M25-A
MS32M32-A
MS4L2M32-A
MS4R2M32-A
MS32M40-A
MS4L2M40-A
MS4R2M40-A
405905
405906
406162
405907
405908
406164
405909
405910
406166
405911
405912
406168
405913
405914
406170
405915
405916
406172
405995
405918
406174
405919
405920
406176
405929
405930
406208
405931
405932
406214
405941
405942
406216
405943
405944
406218
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
ACB’s - type S
Basic cassette with flat copper terminals rear connected, integral racking handle, safety
shutters and lockable safety features.
A
B
C
X
Earthing device
Frame size
Rating (A)
Poles
Cat. No.
Ref. No.
1
400 to 1600
1
2000 to 2500
2
3200 to 4000
3
4
3
4
3
4
EDF13P16
EDF14P16
EDF13P25
EDF14P25
EDF23P40
EDF24P40
405661
405660
405663
405662
405665
405664
B.5
M-PACT Plus
Air circuit breaker - type N - 65kA - Non-automatic
Frame 1 & 2
Basic circuit breaker manually operated, non automatic (switch only, no protection unit option
available), 5 NO and 3 NC auxiliary switches.
Withdrawable pattern - basic circuit breaker and cassette with flat copper terminals, rear
connected. Fixed Pattern - basic circuit breaker with rear horizontal terminals.
Withdrawable and fixed pattern
Frame size Rating (A)
1
400
Order codes
1
800
1
1000
1
1250
1
1600
1
2000
1
B
2500
2
C
2000
2
2500
2
X
3200
2
4000
Withdrawable
Position
of the neutral
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
630
1
A
Poles
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Fixed pattern
Cat. No.
Ref. No.
Cat. No.
Ref. No.
MN31W04
MN4L1W04
MN4R1W04
MN31W06
MN4L1W06
MN4R1W06
MN31W08
MN4L1W08
MN4R1W08
MN31W10
MN4L1W10
MN4R1W10
MN31W12
MN4L1W12
MN4R1W12
MN31W16
MN4L1W16
MN4R1W16
MN31W20
MN4L1W20
MN4R1W20
MN31W25
MN4L1W25
MN4R1W25
MN32W20
MN4L2W20
MN4R2W20
MN32W25
MN4L2W25
MN4R2W25
MN32W32
MN4L2W32
MN4R2W32
MN32W40
MN4L2W40
MN4R2W40
405163
405162
405430
405165
405164
405432
405167
405166
405434
405169
405168
405436
405171
405170
405438
405173
405172
405456
405175
405174
405458
405177
405176
405460
405179
405178
405462
405181
405180
405464
405183
405182
405466
405185
405184
405468
MN31F04
MN4L1F04
MN4R1F04
MN31F06
MN4L1F06
MN4R1F06
MN31F08
MN4L1F08
MN4R1F08
MN31F10
MN4L1F10
MN4R1F10
MN31F12
MN4L1F12
MN4R1F12
MN31F16
MN4L1F16
MN4R1F16
MN31F20
MN4L1F20
MN4R1F20
MN31F25
MN4L1F25
MN4R1F25
MN32F20
MN4L2F20
MN4R2F20
MN32F25
MN4L2F25
MN4R2F25
MN32F32
MN4L2F32
MN4R2F32
MN32F40
MN4L2F40
MN4R2F40
405193
405192
405470
405195
405194
405472
405197
405196
405474
405199
405198
405476
405201
405200
405478
405203
405202
405480
405205
405204
405482
405207
405206
405484
405209
405208
405486
405211
405210
405488
405213
405212
405490
405215
405214
405492
Rear connections
Frame
size Rating (A) Poles
1
400 to 2500
2
800 to 3200
2
4000
3
4
3
4
3
4
Withdrawable or cassettes
Fixed pattern
Cat. No.
Ref. No.
Type
Cat. No.
Ref. No.
Type
RT1UNI
RT1UNI
RT2UNI
RT2UNI
N/A
N/A
405600
405600
405601
405601
N/A
N/A
Universal
Universal
Universal
Universal
Vertical
Vertical
RT1SNVFIX
RT1SNVFIX
RT2SNHVFIX
RT2SNHVFIX
RT2SNHVFIX
RT2SNHVFIX
405609
405609
405621
405621
405621
405621
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Rear Connections specified in multiples of 3, 4, 6 or 8 dependant on 3 or 4 pole configuration - top and / or
bottom connections.
Front access connections
Withdrawable
TOP connections
BOTTOM connections
B.6
Frame size
Rating (A)
Poles
Cat. No.
Ref. No.
Cat. No.
Ref. No.
1
400 to 1600
1
2000 to 2500
2
800 to 3200
2
4000
3
4
3
4
3
4
3
4
FA31WN16T
FA41WN16T
FA31WN25T
FA41WN25T
FA32WN32T
FA42WN32T
FA32WN40T
FA42WN40T
405945
405946
405947
405948
405949
405950
405951
405952
FA31WN16B
FA41WN16B
FA31WN25B
FA41WN25B
FA32WN32B
FA42WN32B
FA32WN40B
FA42WN40B
406045
406046
406047
406048
406049
406050
406051
406052
M-PACT Plus
Front access connections
Fixed pattern
TOP connections
BOTTOM connections
Frame size
Rating (A)
Poles
Cat. No.
Ref. No.
Cat. No.
Ref. No.
1
400 to 1600
1
2000 to 2500
2
800 to 3200
2
4000
3
4
3
4
3
4
3
4
FA31FN16T
FA41FN16T
FA31FN25T
FA41FN25T
FA32FN32T
FA42FN32T
FA32FN40T
FA42FN40T
405957
405958
405959
405960
405961
405962
405963
405964
FA31FN16B
FA41FN16B
FA31FN25B
FA41FN25B
FA32FN32B
FA42FN32B
FA32FN40B
FA42FN40B
405557
405558
405559
405560
405561
405562
405563
405564
Cassette only
Frame size
Rating (A)
Poles
Cat. No.
Ref. No.
1
400 to 2500
2
800 to 3200
2
4000
3
4
3
4
3
4
MN31C25
MN41C25
MN32C32
MN42C32
MN32C40
MN42C40
405345
405344
405347
405346
405349
405348
ACB’s - type N
Basic cassette with flat copper terminals rear connected, integral racking handle, safety
shutters and lockable safety features.
Moving portion only
Basic circuit breaker manually operated, non automatic (switch only, no protection unit
option available), 5 NO and 3 NC auxiliary switches and cluster contacts.
Frame size
Rating (A)
Poles
1
400
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
1
1
1
1
1
1
1
2
2
2
2
630
800
1000
1250
1600
2000
2500
2000
2500
3200
4000
Position
of the neutral
Cat. No.
Ref. No.
Left
Right
MN31M04
MN4L1M04
MN4R1M04
MN31M06
MN4L1M06
MN4R1M06
MN31M08
MN4L1M08
MN4R1M08
MN31M10
MN4L1M10
MN4R1M10
MN31M12
MN4L1M12
MN4R1M12
MN31M16
MN4L1M16
MN4R1M16
MN31M20
MN4L1M20
MN4R1M20
MN31M25
MN4L1M25
MN4R1M25
MN32M20
MN4L2M20
MN4R2M20
MN32M25
MN4L2M25
MN4R2M25
MN32M32
MN4L2M32
MN4R2M32
MN32M40
MN4L2M40
MN4R2M40
405833
405834
405596
405835
405836
405598
405837
405838
405602
405839
405840
405604
405841
405842
405622
405843
405844
405624
405845
405846
405626
405847
405848
405628
405849
405850
405630
405851
405852
405632
405853
405854
405634
405855
405856
405636
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
A
B
C
X
Earthing device
Frame size
Rating (A)
Poles
Cat. No.
Ref. No.
1
400 to 1600
1
2000 to 2500
2
3200 to 4000
3
4
3
4
3
4
EDF13P16
EDF14P16
EDF13P25
EDF14P25
EDF23P40
EDF24P40
405661
405660
405663
405662
405665
405664
B.7
M-PACT Plus
Air circuit breaker - type N - 65kA - Automatic
Frame 1 & 2 (Please select trip unit type in page B.15)
Basic circuit breaker manually operated, automatic (must be fitted with an M-Pro Protection
Unit as listed on page B15), 5 NO and 3 NC auxiliary switches.
Withdrawable pattern - basic circuit breaker and cassette with flat copper terminals, rear
connected.
Fixed Pattern - basic circuit breaker with rear horizontal terminals.
Withdrawable and fixed pattern
Frame size Rating (A)
1
400
Order codes
1
800
1
1000
1
1250
1
1600
1
B
2000
1
2500
2
C
2000
2
2500
2
X
3200
2
4000
Withdrawable
Position
of the neutral
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
630
1
A
Poles
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Fixed pattern
Cat. No.
Ref. No.
Cat. No.
Ref. No.
MN31W04-A
MN4L1W04-A
MN4R1W04-A
MN31W06-A
MN4L1W06-A
MN4R1W06-A
MN31W08-A
MN4L1W08-A
MN4R1W08-A
MN31W10-A
MN4L1W10-A
MN4R1W10-A
MN31W12-A
MN4L1W12-A
MN4R1W12-A
MN31W16-A
MN4L1W16-A
MN4R1W16-A
MN31W20-A
MN4L1W20-A
MN4R1W20-A
MN31W25-A
MN4L1W25-A
MN4R1W25-A
MN32W20-A
MN4L2W20-A
MN4R2W20-A
MN32W25-A
MN4L2W25-A
MN4R2W25-A
MN32W32-A
MN4L2W32-A
MN4R2W32-A
MN32W40-A
MN4L2W40-A
MN4R2W40-A
405351
405350
405832
405353
405352
405864
405361
405360
405866
405363
405362
405882
405412
405410
405902
405415
405414
405904
405417
405416
405994
405419
405418
405996
405425
405424
406020
405445
405444
406032
405453
405452
406042
405455
405454
406044
MN31F04-A
MN4L1F04-A
MN4R1F04-A
MN31F06-A
MN4L1F06-A
MN4R1F06-A
MN31F08-A
MN4L1F08-A
MN4R1F08-A
MN31F10-A
MN4L1F10-A
MN4R1F10-A
MN31F12-A
MN4L1F12-A
MN4R1F12-A
MN31F16-A
MN4L1F16-A
MN4R1F16-A
MN31F20-A
MN4L1F20-A
MN4R1F20-A
MN31F25-A
MN4L1F25-A
MN4R1F25-A
MN32F20-A
MN4L2F20-A
MN4R2F20-A
MN32F25-A
MN4L2F25-A
MN4R2F25-A
MN32F32-A
MN4L2F32-A
MN4R2F32-A
MN32F40-A
MN4L2F40-A
MN4R2F40-A
405657
405656
406054
405659
405658
406094
405681
405680
406096
405721
405720
406098
405731
405730
406114
405733
405732
406116
405735
405734
406118
405737
405736
406120
405779
405778
406122
405781
405780
406124
405783
405782
406126
405785
405784
406128
Rear connections
Frame
size Rating (A) Poles
1
400 to 2500
2
800 to 3200
2
4000
3
4
3
4
3
4
Withdrawable or cassettes
Fixed pattern
Cat. No.
Ref. No.
Type
Cat. No.
Ref. No.
Type
RT1UNI
RT1UNI
RT2UNI
RT2UNI
N/A
N/A
405600
405600
405601
405601
N/A
N/A
Universal
Universal
Universal
Universal
Vertical
Vertical
RT1SNVFIX
RT1SNVFIX
RT2SNHVFIX
RT2SNHVFIX
RT2SNHVFIX
RT2SNHVFIX
405609
405609
405621
405621
405621
405621
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Rear Connections specified in multiples of 3, 4, 6 or 8 dependant on 3 or 4 pole configuration - top and / or
bottom connections.
Front access connections
Withdrawable
TOP connections
BOTTOM connections
B.8
Frame size
Rating (A)
Poles
Cat. No.
Ref. No.
Cat. No.
Ref. No.
1
400 to 1600
1
2000 to 2500
2
800 to 3200
2
4000
3
4
3
4
3
4
3
4
FA31WN16T
FA41WN16T
FA31WN25T
FA41WN25T
FA32WN32T
FA42WN32T
FA32WN40T
FA42WN40T
405945
405946
405947
405948
405949
405950
405951
405952
FA31WN16B
FA41WN16B
FA31WN25B
FA41WN25B
FA32WN32B
FA42WN32B
FA32WN40B
FA42WN40B
406045
406046
406047
406048
406049
406050
406051
406052
M-PACT Plus
Front access connections
Fixed pattern
TOP connections
BOTTOM connections
Frame size
Rating (A)
Poles
Cat. No.
Ref. No.
Cat. No.
Ref. No.
1
400 to 1600
1
2000 to 2500
2
800 to 3200
2
4000
3
4
3
4
3
4
3
4
FA31FN16T
FA41FN16T
FA31FN25T
FA41FN25T
FA32FN32T
FA42FN32T
FA32FN40T
FA42FN40T
405957
405958
405959
405960
405961
405962
405963
405964
FA31FN16B
FA41FN16B
FA31FN25B
FA41FN25B
FA32FN32B
FA42FN32B
FA32FN40B
FA42FN40B
405557
405558
405559
405560
405561
405562
405563
405564
Cassette only
Basic cassette with flat copper terminals rear connected, integral racking handle, safety
shutters and lockable safety features.
Rating (A)
Poles
Cat. No.
Ref. No.
1
400 to 2500
2
800 to 3200
2
4000
3
4
3
4
3
4
MN31C25
MN41C25
MN32C32
MN42C32
MN32C40
MN42C40
405345
405344
405347
405346
405349
405348
ACB’s - type N
Frame size
Moving portion only
Basic circuit breaker manually operated, automatic (must be fitted with an M-Pro Protection
Unit as listed on page B15), 5 NO and 3 NC auxiliary switches and cluster contacts.
Frame size
Rating (A)
Poles
1
400
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
1
1
1
1
1
1
1
2
2
2
2
630
800
1000
1250
1600
2000
2500
2000
2500
3200
4000
Position
of the neutral
Cat. No.
Ref. No.
Left
Right
MN31M04-A
MN4L1M04-A
MN4R1M04-A
MN31M06-A
MN4L1M06-A
MN4R1M06-A
MN31M08-A
MN4L1M08-A
MN4R1M08-A
MN31M10-A
MN4L1M10-A
MN4R1M10-A
MN31M12-A
MN4L1M12-A
MN4R1M12-A
MN31M16-A
MN4L1M16-A
MN4R1M16-A
MN31M20-A
MN4L1M20-A
MN4R1M20-A
MN31M25-A
MN4L1M25-A
MN4R1M25-A
MN32M20-A
MN4L2M20-A
MN4R2M20-A
MN32M25-A
MN4L2M25-A
MN4R2M25-A
MN32M32-A
MN4L2M32-A
MN4R2M32-A
MN32M40-A
MN4L2M40-A
MN4R2M40-A
405953
405954
406220
405955
405956
406222
405965
405966
406224
405967
405968
406226
405969
405970
406228
405971
405972
406230
405977
405978
406232
405979
405980
406234
405981
405982
406236
405983
405984
406238
405989
405990
406240
405991
405992
406242
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
A
B
C
X
Earthing device
Frame size
Rating (A)
Poles
Cat. No.
Ref. No.
1
400 to 1600
1
2000 to 2500
2
3200 to 4000
3
4
3
4
3
4
EDF13P16
EDF14P16
EDF13P25
EDF14P25
EDF23P40
EDF24P40
405661
405660
405663
405662
405665
405664
B.9
M-PACT Plus
Air circuit breaker - type H - 80kA - Non-automatic
Frame 2
Basic circuit breaker manually operated, non automatic (switch only, no protection unit option
available), 5 NO and 3 NC auxiliary switches.
Withdrawable pattern - basic circuit breaker and cassette with flat copper terminals, rear
connected. Fixed Pattern - basic circuit breaker with rear horizontal terminals.
Withdrawable and fixed pattern
Frame size Rating (A)
2
800
Order codes
2
1250
2
1600
2
2000
2
2
3200
2
B
C
2500
4000
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Fixed pattern
Cat. No.
Ref. No.
Cat. No.
Ref. No.
MH32W08
MH4L2W08
MH4R2W08
MH32W10
MH4L2W10
MH4R2W10
MH32W12
MH4L2W12
MH4R2W12
MH32W16
MH4L2W16
MH4R2W16
MH32W20
MH4L2W20
MH4R2W20
MH32W25
MH4L2W25
MH4R2W25
MH32W32
MH4L2W32
MH4R2W32
MH32W40
MH4L2W40
MH4R2W40
405227
405226
405494
405229
405228
405496
405231
405230
405498
405233
405232
405500
405235
405234
405502
405237
405236
405504
405243
405242
405506
405245
405244
405508
MH32F08
MH4L2F08
MH4R2F08
MH32F10
MH4L2F10
MH4R2F10
MH32F12
MH4L2F12
MH4R2F12
MH32F16
MH4L2F16
MH4R2F16
MH32F20
MH4L2F20
MH4R2F20
MH32F25
MH4L2F25
MH4R2F25
MH32F32
MH4L2F32
MH4R2F32
MH32F40
MH4L2F40
MH4R2F40
405257
405256
405509
405259
405258
405510
405261
405260
405512
405263
405262
405514
405265
405264
405516
405267
405266
405518
405273
405272
405520
405275
405274
405522
Rear connections
Frame
size Rating (A) Poles
X
Withdrawable
Position
of the neutral
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
1000
2
A
Poles
2
800 to 3200
2
4000
3
4
3
4
Withdrawable or cassettes
Fixed pattern
Cat. No.
Ref. No.
Type
Cat. No.
Ref. No.
Type
RT2UNI
RT2UNI
N/A
N/A
405601
405601
N/A
N/A
Universal
Universal
Vertical
Vertical
RT2SNHVFIX
RT2SNHVFIX
RT2SNHVFIX
RT2SNHVFIX
405621
405621
405621
405621
Vertical
Vertical
Vertical
Vertical
Rear Connections specified in multiples of 3, 4, 6 or 8 dependant on 3 or 4 pole configuration - top and / or
bottom connections.
Front access connections
Withdrawable
TOP connections
BOTTOM connections
Frame size
Rating (A)
Poles
Cat. No.
Ref. No.
Cat. No.
Ref. No.
2
800 to 3200
2
4000
3
4
3
4
FA32WH32T
FA42WH32T
FA32WH40T
FA42WH40T
405973
405974
405975
405976
FA32WH32B
FA42WH32B
FA32WH40B
FA42WH40B
405553
405554
405555
405556
Front access connections
Fixed pattern
TOP connections
BOTTOM connections
B.10
Frame size
Rating (A)
Poles
Cat. No.
Ref. No.
Cat. No.
Ref. No.
2
800 to 3200
2
4000
3
4
3
4
FA32FH32T
FA42FH32T
FA32FH40T
FA42FH40T
405985
405986
405987
405988
FA32FH32B
FA42FH32B
FA32FH40B
FA42FH40B
405565
405566
405567
405568
M-PACT Plus
Cassette only
Basic cassette with flat copper terminals rear connected (800-3200A), integral racking handle,
safety shutters and lockable safety features.
4000A units fitted with rear vertical terminals as standard (not to be removed).
Frame size
Rating (A)
Poles
Cat. No.
Ref. No.
2
800 to 3200
2
4000
3
4
3
4
MH32C32
MH42C32
MH32C40
MH42C40
405357
405356
405359
405358
Basic circuit breaker manually operated, non automatic (switch only, no protection unit
option available), 5 NO and 3 NC auxiliary switches and cluster contacts.
Frame size
Rating (A)
Poles
2
800
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
2
2
2
2
2
2
2
1000
1250
1600
2000
2500
3200
4000
Position
of the neutral
Cat. No.
Ref. No.
Left
Right
MH32M08
MH4L2M08
MH4R2M08
MH32M10
MH4L2M10
MH4R2M10
MH32M12
MH4L2M12
MH4R2M12
MH32M16
MH4L2M16
MH4R2M16
MH32M20
MH4L2M20
MH4R2M20
MH32M25
MH4L2M25
MH4R2M25
MH32M32
MH4L2M32
MH4R2M32
MH32M40
MH4L2M40
MH4R2M40
405867
405868
405638
405869
405870
405640
405871
405872
405642
405873
405874
405644
405875
405876
405646
405877
405878
405648
405883
405884
405650
405885
405886
405652
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
ACB’s - type H
Moving portion only
A
B
C
X
Earthing device
Frame size
Rating (A)
Poles
Cat. No.
Ref. No.
2
800 to 4000
3
4
EDF23P40
EDF24P40
405665
405664
B.11
M-PACT Plus
Air circuit breaker - type H - 80kA - Automatic
Frame 2 (Please select trip unit type in page B.15)
Basic circuit breaker manually operated, automatic (must be fitted with an M-Pro Protection
Unit as listed on page B15), 5 NO and 3 NC auxiliary switches.
Withdrawable pattern - basic circuit breaker and cassette with flat copper terminals, rear
connected.
Fixed Pattern - basic circuit breaker with rear horizontal terminals.
Withdrawable and fixed pattern
Frame size Rating (A)
2
800
Order codes
2
1250
2
1600
2
2000
2
2500
2
B
C
X
3200
2
4000
Withdrawable
Position
of the neutral
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
1000
2
A
Poles
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Fixed pattern
Cat. No.
Ref. No.
Cat. No.
Ref. No.
MH32W08-A
MH4L2W08-A
MH4R2W08-A
MH32W10-A
MH4L2W10-A
MH4R2W10-A
MH32W12-A
MH4L2W12-A
MH4R2W12-A
MH32W16-A
MH4L2W16-A
MH4R2W16-A
MH32W20-A
MH4L2W20-A
MH4R2W20-A
MH32W25-A
MH4L2W25-A
MH4R2W25-A
MH32W32-A
MH4L2W32-A
MH4R2W32-A
MH32W40-A
MH4L2W40-A
MH4R2W40-A
405797
405796
406130
405799
405802
406134
405801
405798
406132
405829
405828
406136
405831
405830
406138
405859
405858
406140
405861
405860
406142
405863
405862
406144
MH32F08-A
MH4L2F08-A
MH4R2F08-A
MH32F10-A
MH4L2F10-A
MH4R2F10-A
MH32F12-A
MH4L2F12-A
MH4R2F12-A
MH32F16-A
MH4L2F16-A
MH4R2F16-A
MH32F20-A
MH4L2F20-A
MH4R2F20-A
MH32F25-A
MH4L2F25-A
MH4R2F25-A
MH32F32-A
MH4L2F32-A
MH4R2F32-A
MH32F40-A
MH4L2F40-A
MH4R2F40-A
405881
405880
406146
405889
405888
406148
405891
405890
406150
405893
405892
406152
405895
405894
406154
405897
405896
406156
405899
405898
406158
405901
405900
406160
Rear connections
Frame
size Rating (A) Poles
2
800 to 3200
2
4000
3
4
3
4
Withdrawable or cassettes
Cat. No.
Ref. No.
Type
RT2UNI
RT2UNI
N/A
N/A
405601
405601
N/A
N/A
Universal
Universal
Vertical
Vertical
Fixed pattern
Cat. No.
Ref. No.
Type
RT2SNHVFIX
RT2SNHVFIX
RT2SNHVFIX
RT2SNHVFIX
405621
405621
405621
405621
Vertical
Vertical
Vertical
Vertical
Rear Connections specified in multiples of 3, 4, 6 or 8 dependant on 3 or 4 pole configuration - top and / or
bottom connections.
Front access connections
Withdrawable
TOP connections
BOTTOM connections
Frame size
Rating (A)
Poles
Cat. No.
Ref. No.
Cat. No.
Ref. No.
2
800 to 3200
2
4000
3
4
3
4
FA32WH32T
FA42WH32T
FA32WH40T
FA42WH40T
405973
405974
405975
405976
FA32WH32B
FA42WH32B
FA32WH40B
FA42WH40B
405553
405554
405555
405556
Front access connections
Fixed pattern
TOP connections
BOTTOM connections
B.12
Frame size
Rating (A)
Poles
Cat. No.
Ref. No.
Cat. No.
Ref. No.
2
800 to 3200
2
4000
3
4
3
4
FA32FH32T
FA42FH32T
FA32FH40T
FA42FH40T
405985
405986
405987
405988
FA32FH32B
FA42FH32B
FA32FH40B
FA42FH40B
405565
405566
405567
405568
M-PACT Plus
Cassette only
Basic cassette with flat copper terminals rear connected (800-3200A), integral racking handle,
safety shutters and lockable safety features.
4000A units fitted with rear vertical terminals as standard (not to be removed).
Frame size
Rating (A)
Poles
Cat. No.
Ref. No.
2
800 to 3200
2
4000
3
4
3
4
MH32C32
MH42C32
MH32C40
MH42C40
405357
405356
405359
405358
Basic circuit breaker manually operated, automatic (must be fitted with an M-Pro Protection
Unit as listed on page B15), 5 NO and 3 NC auxiliary switches and cluster contacts.
Frame size
Rating (A)
Poles
2
800
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
3
4
4
2
2
2
2
2
2
2
1000
1250
1600
2000
2500
3200
4000
Position
of the neutral
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Cat. No.
Ref. No.
MH32M08-A
MH4L2M08-A
MH4R2M08-A
MH32M10-A
MH4L2M10-A
MH4R2M10-A
MH32M12-A
MH4L2M12-A
MH4R2M12-A
MH32M16-A
MH4L2M16-A
MH4R2M16-A
MH32M20-A
MH4L2M20-A
MH4R2M20-A
MH32M25-A
MH4L2M25-A
MH4R2M25-A
MH32M32-A
MH4L2M32-A
MH4R2M32-A
MH32M40-A
MH4L2M40-A
MH4R2M40-A
405997
405998
406244
405999
406000
406246
406001
406002
406248
406003
406004
406250
406005
406006
406252
406007
406008
406254
406009
406010
406256
406011
406012
406258
ACB’s - type H
Moving portion only
A
B
C
X
Earthing device
Frame size
Rating (A)
Poles
Cat. No.
Ref. No.
2
800 to 4000
3
4
EDF23P40
EDF24P40
405665
405664
B.13
M-PACT Plus
Air circuit breaker - type C - 100kA - Non-automatic
Frame 3
Basic circuit breaker manually operated, non automatic, 4 NO and 6 NC auxiliary switches.
Withdrawable pattern: 5000A: rear horizontal / vertical - 6300A: rear vertical.
Fixed pattern: rear horizontal.
Withdrawable and fixed pattern
Withdrawable
Rating (A)
Poles
3
3
5000
6300
3
3
Cat. No.
MC33W50
MC33W63
Fixed pattern
Ref. No.
Cat. No.
Ref. No.
406700
406702
MC33F50
-
406703
-
Order codes
Frame size
A
B
C
X
Air circuit breaker - type C - 100kA - Automatic
Frame 3 (Please select trip unit type in page B.15)
Basic circuit breaker manually operated, automatic, 4 NO and 6 NC auxiliary switches.
Withdrawable pattern: 5000A: rear horizontal / vertical - 6300A: rear vertical.
Fixed pattern: rear horizontal.
Automatic breaker include in standard, one alarm contact (N/O).
Withdrawable and fixed pattern
Withdrawable
B.14
Frame size
Rating (A)
Poles
3
3
5000
6300
3
3
Cat. No.
MC33W50 - A
MC33W63 - A
Fixed pattern
Ref. No.
Cat. No.
Ref. No.
406898
406899
MC33F50 - A
-
406900
-
M-PACT Plus
M-PRO protection relays
Frame 1, 2 & 3
M-PRO protection relay
Type
Cat. No.
Ref. No.
MPRO17PLUSF1&2
MPRO18 PLUSF1&2
MPRO17PLUSF3
405327
405329
406879
MPRO18PLUSF3-ENG
406889
MPRO18PLUSF3-FR
406890
MPROPLUSUEF
MPROPLUSNTL100
MPROPLUSNTL50
MPROPLUSUEF3P3W
405331
406910
406911
405535
M-PRO 30L protection unit
M-PRO 30 L protection unit with Restricted Earth Fault only (English)
M-PRO 30L protection unit French version
M-PRO 30L protection unit (English version) without auto/manual reset button
M-PRO 30L protection unit (French version) without auto/manual reset button
M-PRO 30H protection unit
M-PRO 30 H protection unit with Restricted Earth Fault only (English)
M-PRO 30H protection unit French version
M-PRO 30H protection unit (English version) without auto/manual reset button
M-PRO 30H protection unit (French version) without auto/manual reset button
M-PRO 40L protection unit English version with MODBUS protocol
M-PRO 40L protection unit French version with MODBUS protocol
M-PRO 40L protection unit (English version) without auto/manual reset button
M-PRO 40L protection unit (French version) without auto/manual reset button
M-PRO 40H protection unit English version with MODBUS protocol
M-PRO 40H protection unit French version with MODBUS protocol
M-PRO 40H protection unit (English version) without auto/manual reset button
M-PRO 40H protection unit (French version) without auto/manual reset button
MPRO30L-ENG
MPRO30LR
MPRO30L-FRF
MPRO30L-ENGNR
MPRO30L-FRFNR
MPRO30H-ENG
MPRO30HR
MPRO30H-FRF
MPRO30H-ENGNR
MPRO30H-FRFNR
MPRO40L-ENG
MPRO40L-FRF
MPRO40L-ENGNR
MPRO40L-FRFNR
MPRO40H-ENG
MPRO40H-FRF
MPRO40H-ENGNR
MPRO40H-FRFNR
406055
406058
405128
406108
406102
406056
406057
405129
406109
406103
405530
405130
406110
406104
405534
405131
406111
406105
Restricted Earth Fault Protection (M-PRO 30 only)
Standby Earth Fault Protection ( M-PRO 30 only)
M-PRO 30/40 no-trip on fatal error (warn only) software facility
Communications facility (MODBUS protocol)
Auxiliary Power Unit
Portable Test Unit (for M-PRO 17 or 18 Plus) UK power lead
Portable Test Unit (for M-PRO 17 & 18 Plus) Euro power lead
Portable Test Unit (for M-PRO 30/40) Euro power lead
Portable Test Unit (for M-PRO 30/40) UK power lead
Portable Power Box (for M-PRO 30/40)
Add-on Mechanical Alarm Contact (1 x N/O)
Add-on Mechanical Alarm Contact (1 x N/C)
Spare PAMM for use with M-PRO 20
Spare PAMM for use with M-PRO 30 or M-PRO 40
MPROREF
MPROSEF
MPRONTSW
MPROCOM
MPROAPU
MPROPTU17
MPROPLUSTU-EURO
MPROPTU-EURO
MPROPTU
MPROPPB
MPROMAC
MPROMACNC
PAMM20
PAMM30/40
405537
405538
405540
405545
405547
405550
405222
405223
405551
405552
405575
406777
405297
405299
Operations manual(1)
French
Spanish
German
Italian
Portuguese
Dutch
Polish
MPRO18PLUSF3-G
ACB’s - type C
M-PRO 17 Plus (for Frame size 1 & 2) for overcurrrent and short circuit protection only
M-PRO 18 Plus (Digital display) for overcurrrent and short circuit protection only
M-PRO 17 Plus (for Frame size 3 M-PACT Plus) - overcurrrent and short circuit protection
only (non-resettable)
M-PRO 18 Plus (for Frame size 3 M-PACT Plus) - overcurrrent and short circuit protection
only (non-resettable)
M-PRO 18 Plus (for Frame size 3 M-PACT Plus) - overcurrrent and short circuit protection
only (non-resettable)
M-PRO 18 Plus (for Frame size 3 M-PACT Plus) - overcurrrent and short circuit protection
only (non-resettable)
Unrestricted Earth Fault option for M-PRO 17 and 18 Plus protection relay's.
100% rated Neutral Protection option for M-PRO 17 and 18 Plus protection unit
50% rated Neutral Protection for M-PRO 17 and 18 Plus protection unit
3 phase 3 wire Unrestricted Earth Fault option for M-PRO 17 Plus and 18 Plus
A
B
C
X
406372
406373
406374
406375
406376
406377
406378
(1) English manual standard available in packaging.
B.15
M-PACT Plus
Frame 1 & 2
Electrical accessories
MPRO optional features
Voltage
Cat. No.
Ref. No.
24/30V
48V
110/130V
220/250V
380/440V
DC
DC
AC/DC
AC/DC
AC/DC
ST30
ST48
ST130
ST250
ST440
405380
405382
405386
405388
405389
Motor operator (MOP)
24/30V
48V
110/130V
110/130V
220/250V
DC
DC
AC
DC
AC/DC
MOP30
MOP48
MOP130A
MOP130D
MOP250A
405440
405442
405446
405917
405448
Closing coil (CC)
24/30V
48V
110/130V
220/250V
DC
DC
AC/DC
AC/DC
CC30
CC48
CC130
CC250
405420
405422
405426
405428
Under voltage release (UV)
24/30V
48V
110/130V
110/130V
220/250V
380/440V
DC
DC
AC
DC
AC
AC
UV30
UV48
UV130A
UV130D
UV250
UV440
405400
405402
405406
405407
405408
405409
Under voltage release time delayed (UVTD)
48V
110/130V
220/250V
380/440V
DC
AC
AC
AC
UVTD48
UVTD130
UVTD250
UVTD440
406322
406326
405411
405413
250V
250V
AC/DC
AC/DC
CSWFF
CSWL
405580
405581
Springs charged signal ( x 1 n/o)
SCC
405450
Springs charged contact ( x 1 c/o)
2WPFC
405451
Trip circuit supervision (shunt trip required)
TRIPCS
406112
Order codes
Range
Shunt trip (ST)
A
B
C
X
Carriage switch
B.16
Factory fitted
Loose kit form
M-PACT Plus
Frame 3
Electrical accessories
Shunt trip (ST)
Closing coil (CC)
Voltage
24V
48V
60V
110V
220V
110V
240V
DC
DC
DC
DC
DC
AC
AC
F3ST24D
F3ST48D
F3ST60D
F3ST110D
F3ST220D
F3ST110A
F3ST240A
Cat. No.
406707
406708
406709
406710
406712
406714
406717
24V
48V
60V
110V
220V
110V
230V
220V
240V
DC
DC
DC
DC
DC
AC
AC
AC
AC
F3MOP24D
F3MOP48D
F3MOP60D
F3MOP110D
F3MOP220D
F3MOP110A
F3MOP230A
F3MOP220A
F3MOP240A
406750
406751
406752
406754
406757
406753
406756
406755
406758
24V
48V
60V
110V
110V
220V
110…120V
220…240V
DC
DC
DC
AC
DC
DC
AC
AC
F3CC24D
F3CC48D
F3CC60D
F3CC110A
F3CC110D
F3CC220D
F3CC120A
F3CC240A
406723
406724
406725
406726
406727
406729
406730
406731
Ref. No.
Electrical accessories
Motor operator (MOP)
Range
A
B
C
Undervoltage release
Carriage switch
Microswitch (on drive)
24V
48V
60V
110V
220V
230/240V
DC
DC
DC
AC/DC
AC/DC
AC
F3UV24D
F3UV48D
F3UV60D
F3UV110
F3UV220
F3UV240A
406732
406733
406734
406735
406737
406741
1 switch
2 switches
3 switches
4 switches
2NO,2NC
4NO,4NC
6NO,6NC
8NO,8NC
F3CSW22
F3CSW44
F3CSW66
F3CSW88
406743
406744
406745
406746
F3MSRTC
F3MSDCS
406748
406749
Signal "ready to close" (M4)
Signal "drive charged" (M3)
X
B.17
M-PACT Plus
Frame 1, 2 & 3
Type A: order 1 interlock kit and 1 cable per ACB
Type B: order 1 interlock kit and 2 cable per ACB
Type C: order 1 interlock kit and 2 cable per ACB
Type D: order 1 interlock kit and 1 cable per Supply breaker plus 1 interlock kit for the Control breaker and 2 cables
For type D configuration 2 Supply Breakers and one Control Breaker are required.
Mechanical accessories
Type A - 2 way interlock / Cable
2 way Interlocking
Frame
size
Version
Poles
1
Withdrawable
3
4
3
4
3
4
3
4
3
3
Order codes
Fixed
A
2
Withdrawable
Fixed
3
Withdrawable
Fixed
Cat. No.
Ref. No.
406342
406343
406340
406341
405459
405461
405463
405465
406760
406762
B13WCI3PW
B13WCI4PW
B13WCI3PF
B13WCI4PF
B13WCIF23PW
B13WCIF24PW
B13WCIF23PF
B13WCIF24PF
406350
406351
406348
406349
405475
405477
405479
405481
Frame
size
Version
Poles
Cat. No.
Ref. No.
1
Withdrawable
3
4
3
4
3
4
3
4
C23WCI3PW
C23WCI4PW
C23WCI3PF
C23WCI4PF
C23WCIF23PW
C23WCIF24PW
C23WCIF23PF
C23WCIF24PF
406358
406359
406356
406357
405491
405493
405495
405497
2
Withdrawable
Fixed
C
X
2WCI3PW
2WCI4PW
2WCI3PF
2WCI4PF
2WCIF23PW
2WCIF24PW
2WCIF23PF
2WCIF24PF
MICWDF33P
MICFXF33P
Ref. No.
Type D - 1 from 3 way interlock/cable - Supply Breakers
Type D - 1 from 3 way interlock/cable - Control Breaker
Frame
size
Version
Poles
Cat. No.
Ref. No.
Cat. No.
Ref. No.
1
Withdrawable
3
4
3
4
3
4
3
4
D13WCI3PW
D13WCI4PW
D13WCI3PF
D13WCI4PF
D13WCIF23PW
D13WCIF24PW
D13WCIF23PF
D13WCIF24PF
406366
406367
406364
406365
405511
405513
405515
405517
D13WCI3PWCON
D13WCI4PWCON
D13WCI3PFCON
D13WCI4PFCON
D13WCIF23PWCON
D13WCIF24PWCON
D13WCIF23PFCON
D13WCIF24PFCON
406966
406967
406968
406969
406970
406971
406972
406973
Fixed
2
Withdrawable
Fixed
Cable for interlock (for Frame 1 & 2 only)
Length
Cat. No.
Ref. No.(1)
1.0 metre
1.6 metre
2.0 metre
2.5 metre
3.0 metre
3.5 metre
4.0 metre
100BCMCI
160BCMCI
200BCMCI
250BCMCI
300BCMCI
350BCMCI
400BCMCI
405531
405532
405533
405610
405611
405612
405613
(1) Reference is for one cable
B.18
one interlock kit for frame 3 include one 2,3 m cable
Type C - 2 from 3 way interlock / Cable
Fixed
B
Cat. No.
Type B - 1 from 3 way interlock / Cable
M-PACT Plus
Frame 1, 2 & 3
Interlocks
Frame
size
3
Item
Cat. No.
Ref. No.
Castell key breaker interlock (supplied loose) (1)
CASLOK
405570
Fortress key breaker interlock (supplied loose) (1)
FORLOK
405569
(1)
Profalux key breaker interlock (supplied loose)
PROLOK
405572
(1)
Profalux key cassete interlock (supplied loose)
PROCAS
405574
(2)
Ronis key breaker interlock (factory fitted)
RONLKEY 406335
(2)
Ronis key breaker interlock (supplied loose)
RONWKEY 406338
Ronis key breaker interlock (supplied loose) ((1)
RONLOK
405571
(2)
Ronis key cassete interlock (factory fitted)
RONWKEYFF 406339
(2)
Ronis key cassete interlock (supplied loose)
RONCASLD 406336
Ronis key cassete interlock (supplied loose) (1)
RONCASNK 406337
(1)
Ronis key cassete interlock (factory fitted)
RONCAS
405573
Castell key breaker interlock (factory fitted) (1)
CASF3FF
406767
(2)
Ronis key breaker interlock (factory fitted)
RONF3FF
406768
(1)
Castell key breaker interlock (supplied loose)
CASF3LD
406769
(2)
Ronis key breaker interlock (supplied loose)
RONF3LD 406770
(1) Without lock and key
(2) With lock and key
Frame
size
1, 2
3
Item
Operations counter
Left hand door interlock - hinged right
Right hand door interlock - hinged left
Mis-insertion device (factory fitted)
Mis-insertion device (supplied loose)
IP54 door
Handling (lifting) truck
Spare or replacement racking handle
Operator counter
Cat. No.
Ref. No.
MOC
DILHS
DIRHS
ACBMID
ACBMIL
IP54DOOR
ACBLIFT
MPRACKHAN
F3MOC
405576
405578
405579
405605
405505
405606
405607
406393
406771
Mechanical accessories
1, 2
Miscellaneous
A
B
C
X
B.19
M-PACT Plus
Frame 1, 2 & 3
Spare parts
Neutral / Earth leg (4th)
Current transformer with mounting kit
Neutral (4th) Rogowski coil
with mounting kit
Order codes
Current transformer
Frame size
Rating (A)
1
2
1
2
1
2
1
2
1
2
1
2
2
2
800
1000
1250
1600
2000
2500
3200
4000
Cat. No.
Ref. No.
ELCT8001
ELCT8002
ELCT10001
ELCT10002
ELCT12501
ELCT12502
ELCT16001
ELCT16002
ELCT20001
ELCT20002
ELCT25001
ELCT25002
ELCT32002
ELCT40002
405683
405713
405684
405714
405685
405715
405686
405716
405687
405717
405688
405718
405689
405690
Rogowski coil
Cat. No.
Ref. No.
RCMK8001
RCMK8002
RCMK10001
RCMK10002
RCMK12501
RCMK12502
RCMK16001
RCMK16002
RCMK20001
RCMK20002
RCMK25001
RCMK25002
RCMK32002
RCMK40002
405703
405723
405704
405724
405705
405725
405706
405726
405707
405727
405708
405728
405709
405710
Spare items available as SINGLE unit ONLY
Fixed and moving arcing contact
Fixed
A
B
C
X
(1)
Frame size
Rating (A)
1
1
2
2
1
1
2
2
2
2
800 to1600
2000 to 2500
3200
4000
800 to1600
2000 to 2500
3200
4000
800 to3200
4000
ACB Qty. required
per pole
type
S
S
S
S
N
N
N
N
H
H
2
4
6
6
3
4
6
6
6
6
Moving
Cat. No.
Ref. No.
Qty. required
per pole
Cat. No.
Ref. No.
FACS116
FAC125
FAC232
FAC240
FACN116
FAC125
FAC232
FAC240
FAC232
FAC240
405738
405742
405744
405746
405740
405742
405744
405746
405744
405746
1
1
1
1
1
1
1
1
1
1
MACS116
MAC125
MAC232
MAC240
MACN116
MAC125
MAC232
MAC240
MAC232
MAC240
405739
405743
405745
405747
405741
405743
405745
405747
405745
405747
Cluster contacts
Frame size
Rating (A)
ACB type
Per pole
1
800 to1250
S
1
2000 to 2500
S
2
3200
S
2
4000
S
1
800 to1600 (N) and 1600 (S)
N
1
2000 to 2500
N
2
3200
N
2
4000
N
2
800 to 3200
H
2
4000
H
Universal Cluster pliers (to remove cluster contact)
2
2
2
2
2
2
2
2
2
2
Cat. No.
Ref. No.
CLCS116
CLC125
CLC232
CLC240
CLCN116
CLC125
CLC232
CLC240
CLC232
CLC240
UNIPLIER
405769
405771
405772
405773
405770
405771
405772
405773
405772
405773
405800
Cat. No.
Ref. No.
ARC16
ARC25
ARC32SN
ARC32H
ARC40SN
ARC40H
F3ARC
405787
405790
405791
405788
405792
405789
406776
Arc chute
Frame size
Rating (A)
ACB type
Per pole
1
1
2
2
2
2
3
400 to 1600
<2500
3200
3200
4000
4000
5000 to 6300
S
S&N
S &N
H
S &N
H
C
1
1
1
1
1
1
4
One piece only
Main and arcing contact
Arcing contact
Main contact
Frame size
Rating (A)
Per pole (2)
Cat. No.
Ref. No.
Per pole
Cat. No.
Ref. No.
3
3
5000
6300
1 set
1 set
F3ACK
F3ACK
406772
406772
1 set
1 set
F3MCS50
F3MCS63
406774
406775
(1) Rogoswki coil provided with twisted pair of cable (max. length 2 m)
(2) 1 set includes all parts required for fixed and moving parts for 1 pole.
B.20
M-PACT Plus
C.2
C.4
C.5
C.6
C.9
C.13
C.15
C.16
Wiring diagrams
Circuit breakers
M-PRO 17, 17 Plus & 18 Plus
M-PRO 30/40
Dimensional drawings
Circuit breaker - Type S - 50kA
Horizontal, rear access connection - Fixed pattern
Rear access connection - Withdrawable pattern
Front access connection - Withdrawable pattern
Front access connection - Fixed pattern
Front access connection - Withdrawable pattern
Technical overview
A
Order codes
B
Wiring diagrams / Dimensional drawings
C
C.18
C.21
C.24
C.25
C.26
C.27
Circuit breaker - Type N - 65kA
Horizontal, rear access connection - Fixed pattern
Rear access connection - Withdrawable pattern
Front access connection - Fixed pattern
Front access connection - Withdrawable pattern
Front access connection - Fixed pattern
Front access connection - Withdrawable pattern
C.28
C.29
C.31
C.32
Circuit breaker - Type H - 80kA
Horizontal, rear access connection - Fixed pattern
Rear access connection - Withdrawable pattern
Front access connection - Fixed pattern
Front access connection - Withdrawable pattern
C.33
Circuit breaker - Type C - 100kA
Rear and horizontal connection - Withdrawable and fixed version
C.35
C.37
C.38
C.39
C.40
Adaptor connections
Door cut-outs
Cassette mounting details
2-Way cable interlocking
3-Way cable interlocking
Numerical index
X
C.1
M-PACT Plus
Wiring diagrams
Wiring diagram
Frame 1 & 2 (3 & 4 pole)
A
B
Terminal references
C
X
B1 to B16
C1 to C16
D1 to D6
D7 to D12
D13 to D18
Automatic disconnect L.T. blocks
Automatic disconnect L.T. blocks
Carriage switch blocks for disconnected position
Carriage switch blocks for test position(1)
Carriage switch blocks for connected position(1)
(1) Changeover contacts can be reconfigured by user.
Key
C.2
LP1
LP2
LP3
LP4
LP5
LP6
Disconnected indication
Test indication
Connected indication
ACB tripped indication
ACB OFF indication
ACB ON indication
Optional features
LP7
CC
UV
UVTD
AL
ML
M
ST
Closing springs charged indication
Closing coil
Undervoltage release
Time delayed undervoltage release
M-PRO trip alarm (N/O)
Charging motor limit switch
Closing spring charging motor
Shunt trip
M-PACT Plus
for DC
Voltage -
X1
Motor
Operator
Wiring diagram
Frame 3 (3 pole)
6
4
2
10
16 X2 18
14
12
20
26
22
28
32 X3 33
30
34
35
46
39
48
DC
X14
1
V4 ~
+
-
M
4 X15
2 X12
X13
2
33
~
2
X14
8
31
261
C2
C2
C1
C1
1
A2
U<
14
22
24
264
54
52
64
74
72
84
82
13
21
23
272
53
51
63
73
71
83
81
9
4 22
2
A1
SU-CONTROLUNIT
10
271
X12
3 X15
1 X12
X13
1
12
41
11
19
17
18
8
X13
7
F
42
15 16
F
3
251
251
01
04
X47
20
21
MPRO
Plus
11 12 14 13
4
5
201
6 2 1
1
X47
2
AC D
C1
201
C2
+
X1
1
5
3
9
11
13
15 X2 17
19
21
25
27
29
31 X3 36
37
45
38
Wiring diagrams
X12
AC
1
X46
2
32/34
47
Auxiliarypower
supply24VDC
Tripalarm
for w/o breaker X1 + X2 + X3 =X20
Closingcoil
Breakerready
for close
Undervoltage
release
Shunt trip2
Shunt trip1
+ for DC +
voltage
A
B
L1
L2
L3
L4
L5
ST1
ST2
UV
CC
M
S1
S2
S3
S4
S5.1; S5.2
M-PRO PLUS
APU
X1, X2, X3
X20
Terminals 33
Terminals 35
Terminals 34
Terminals 39
-
36
36
37
38
Breaker opened
Breaker closed
Breaker ready for close
Breaker charged
Breaker tripped by ETU
Shunt trip coil 1
Shunt trip coil 2
Undervoltage trip
Closing coil
Motor operator
Breaker opening switch
Breaker opening switch
Breaker opening switch
SU power off switch
Breaker closing switch
M-PRO17/18 Plus trip unit
Auxiliary power supply
Fix breaker terminals
Withdrawable breaker terminals
SU operating voltage
Springs charging motor voltage
Closing coil voltage
Breaker charged signal
C
X
C.3
M-PACT Plus
Wiring diagram
M-PRO 17 Plus & 18 Plus - Frame 1 & 2
A8
A9
External Rogowski coil
B5
Wiring diagrams
Power CT
(power inputs 1, 2 , 3 )
B6
Ro gowski coils
(analogue input s 1, 2 , 3 )
Rogowski coil
(analogue input 4)
Unrestricted Eart h / Neutral position
TestBox
Connection
SWITCH I/P
TRIP COIL OUTPUT
A
B
Aux. Power input
Frame 3
C
A8
X
A9
External Rogowski coil
X3
47
Power CT
(power input s 1, 2 , 3 )
Aux. Power input
48
Rogowski coils
(analogue input s 1, 2 , 3 )
TestBox
Connection
SWITCH I/P
TRIP COIL OUTPUT
Note: X3 = 3 3 - 48, refer pag e 4 for furthur details
Connections for M-PRO 17 Plus & 18 Plus
Location
Terminal
LT ‘A’ block*
LT ‘A’ block*
X3 or X20
X3 or X20
A8
A9
47
48
* not applicable for Frame 3
C.4
Function
Remote Rogowski coil - positive for earth fault and/or neutral protection
Remote Rogowski coil - negative for earth fault and/or neutral protection
Auxiliary power supply input - positive
Auxiliary power supply input - negative
M-PACT Plus
Wiring diagram
M-PRO 30/40
Wiring diagrams
A
B
C
X
Connections for M-PRO 30/40
Terminal
Terminal
Location
M-PRO 30
M-PRO 40
PAMM
PAMM
PAMM
PAMM
PAMM
PAMM
PAMM
PAMM
PAMM
PAMM
PAMM
PAMM
PAMM
PAMM
PAMM
LT ‘B’ block
LT ‘B’ block
LT ‘B’ block
LT ‘B’ block
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10
A11
A12
A13
A14
A15
B3
B4
B5
B6
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10
A11
A12
A13
A14
A15
B3
B4
B5
B6
Function
OUTPUT 4, normally open volt free contact: Operates when the REF (or SEF) element trips the ACB
This is used to trip an upstream HV breaker.
OUTPUT 3, normally open volt free contact: Operates when M-PRO has opened the ACB due to a trip
condition.
OUTPUT 2, normally open volt free contact: Load monitoring output operates if pre-trip alarm or load
shedding limits are exceeded.
OUTPUT 1, normally closed volt free contact, opens under the following conditions: Microprocessor
malfunction, primary contact maintenance alarm or a digital input is active.
Input 4
Input 3
Input 2
Input 1
Input common
Remote Rogowski coil - positive for earth fault and/or neutral protection
Remote Rogowski coil - negative for earth fault and/or neutral protection
Earth leg CT input - non polarised
Auxiliary power supply input - positive
Auxiliary power supply input - negative
C.5
M-PACT Plus
Horizontal, rear access connection
Fixed pattern
Minimum space to earth metal
and for arc chute removal
182 Min
Arc chute
removal
Insulated metal
or insulated sheet
(customer supplied)
Centre line of operating panel
Centre line of
operating panel
Fascia
centre
Dimensional drawings
Type S - 3 pole - Frame size 1, In = 400A to 1600A
Fascia centre
100 to door
ACB fascia
cut-out dimensions
A
B
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
Copperwork must be supported within 200 mm of
breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
C
X
Type S - 4 pole - Frame size 1, In = 400A to 1600A
Minimum space to earth metal
and for arc chute removal
182 Min
Arc chute
removal
Insulated metal
or insulated sheet
(customer supplied)
Centre line of operating panel
Fascia
centre
Centre line of
operating panel
Fascia centre
100 to door
ACB fascia
cut-out dimensions
Copperwork must be supported within 200mm of breaker
connections – busbars or cables.
All connections to be tightened to 50Nm.
C.6
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
M-PACT Plus
Horizontal, rear access connection
Fixed pattern
Type S - 3 pole - Frame size 1, In = 2000A and 2500A
Minimum space to earth metal
and for arc chute removal
182 Min
Arc chute
removal
Insulated metal
or insulated sheet
(customer supplied)
Centre line of operating panel
Fascia
centre
Centre line of
operating panel
Dimensions
Fascia centre
100 to door
ACB fascia
cut-out dimensions
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
Copperwork must be supported within 200 mm of
breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
A
B
C
X
Type S - 4 pole - Frame size 1, In = 2000A and 2500A
Minimum space to earth metal
and for arc chute removal
182 Min
Arc chute
removal
Insulated metal
or insulated sheet
(customer supplied)
Centre line of operating panel
Fascia
centre
Centre line of
operating panel
100 to door
Fascia centre
ACB fascia
cut-out dimensions
Copperwork must be supported within 200 mm of
breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
C.7
M-PACT Plus
Horizontal, rear access connection
Fixed pattern
Insulated metal
or insulated sheet
(customer supplied)
Minimum space to earth metal
and for arc chute removal
182 Min
Arc chute
removal
Centre line of operating panel
Centre line of
operating panel
Fascia
centre
Dimensional drawings
Type S - 3 pole - Frame size 2, In = 2000A to 4000A
Fascia centre
100 to door
ACB fascia
cut-out dimensions
A
B
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
Copperwork must be supported within 200 mm of
breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
C
X
Type S - 4 pole - Frame size 2, In = 2000A to 4000A
Minimum space to earth metal
and for arc chute removal
182 Min
Arc chute
removal
Insulated metal
or insulated sheet
(customer supplied)
Centre line of operating panel
Fascia
centre
Centre line of
operating panel
100 to door
Fascia centre
ACB fascia
cut-out dimensions
Copperwork must be supported within 200mm of
breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
C.8
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
M-PACT Plus
Rear access connection
Withdrawable pattern
Type S - 3 pole - Frame size 1, In = 400A to 1600A
Minimum clearance
to cassette side.
382 to door
Fascia
centre
Ventilation
35 Test
50 Disconnected
275 Fully withdrawn
Centre line of
operating panel
Connected 414
ACB fascia
cut-out dimensions
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
Copperwork must be supported within 200 mm of breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
Captive plate behind copper terminal, tapped M10 x 1.5 6H.
Minimum insertion of screw 16mm. Maximum insertion of screw 34mm.
Dimensions
Fascia
centre
Centre line of
operating panel
A
B
C
X
Type S - 4 pole - Frame size 1, In = 400A to 1600A
Minimum clearance to
cassette side.
382 to door
Fascia
centre
Ventilation
Fascia
centre
Centre line of
operating panel
35 Test
Connected 414
Centre line of
operating panel
50 Disconnected
275 Fully withdrawn
ACB fascia
cut-out dimensions
Copperwork must be supported within 200 mm of breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
Captive plate behind copper terminal, tapped M10 x 1.5 6H.
Minimum insertion of screw 16mm. Maximum insertion of screw 34mm.
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
C.9
M-PACT Plus
Rear access connection
Withdrawable pattern
Minimum clearance
to cassette side.
382 to door
Fascia
centre
Ventilation
Centre line of
operating panel
Fascia
centre
Dimensional drawings
Type S - 3 pole - Frame size 1, In = 2000A & 2500A
35 Test
50 Disconnected
275 Fully withdrawn
Centre line of
operating panel
Connected 414
ACB fascia
cut-out dimensions
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
A
B
Copperwork must be supported within 200mm of breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
Captive plate behind copper terminal, tapped M10 x 1.5 6H.
Minimum insertion of screw 16mm. Maximum insertion of screw 34mm.
C
X
Type S - 4 pole - Frame size 1, In = 2000A & 2500A
Minimum clearance to
cassette side.
382 to door
Fascia
centre
Ventilation
Fascia
centre
Centre line of
operating panel
35 Test
50 Disconnected
275 Fully withdrawn
Connected 414
Centre line of
operating panel
ACB fascia
cut-out dimensions
Copperwork must be supported within 200mm of breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
Captive plate behind copper terminal, tapped M10 x 1.5 6H.
Minimum insertion of screw 16mm. Maximum insertion of screw 34mm.
C.10
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
M-PACT Plus
Rear access connection
Withdrawable pattern
Type S - 3 pole - Frame size 2, In = 2000A to 3200A
Minimum clearance to
cassette side.
382 to door
Fascia
centre
Ventilation
Fascia
centre
35 Test
50 Disconnected
275 Fully withdrawn
Centre line of
operating panel
Connected 414
ACB fascia
cut-out dimensions
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
Copperwork must be supported within 200mm of breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
Captive plate behind copper terminal, tapped M10 x 1.5 6H.
Minimum insertion of screw 16mm. Maximum insertion of screw 34mm.
Dimensions
Centre line of
operating panel
A
B
C
X
Type S - 4 pole - Frame size 2, In = 2000A to 3200A
Minimum clearance
to cassette side.
382 to door
Fascia
centre
Centre line of
operating panel
Fascia
centre
Ventilation
35 Test
50 Disconnected
275 Fully withdrawn
Connected 414
Centre line of
operating panel
ACB fascia
cut-out dimensions
Copperwork must be supported within 200mm of breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
Captive plate behind copper terminal, tapped M10 x 1.5 6H.
Minimum insertion of screw 16mm. Maximum insertion of screw 34mm.
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
C.11
M-PACT Plus
Rear access connection
Withdrawable pattern
Must not be removed
or fitted horizontally
Minimum clearance
to cassette side.
382 to door
Fascia
centre
Ventilation
Centre line of
operating panel
Fascia
centre
Dimensional drawings
Type S - 3 pole - Frame size 2, In = 4000A
35 Test
50 Disconnected
Centre line of
operating panel
Connected 414
275 Fully withdrawn
ACB fascia
cut-out dimensions
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
A
B
Copperwork must be supported within 200mm of breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
C
X
Type S - 4 pole - Frame size 2, In = 4000A
Must not be removed
or fitted horizontally
Minimum clearance
to cassette side.
382 to door
Ventilation
Fascia centre
Fascia centre
Centre line of
operating panel
35 Test
50 Disconnected
Connected 414
Centre line of operating panel
275 Fully withdrawn
ACB fascia
cut-out dimensions
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
Copperwork must be supported within 200mm of breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
C.12
M-PACT Plus
Front access connection
Withdrawable pattern
Type S - 3 pole - Frame size 1, In = 400A to 1600A
Dimensions
ACB fascia
cut-out dimensions
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
A
B
C
X
Type S - 4 pole - Frame size 1, In = 400A to 1600A
ACB fascia
cut-out dimensions
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
C.13
M-PACT Plus
Front access connection
Withdrawable pattern
Dimensional drawings
Type S - 3 pole - Frame size 1, In = 2000A & 2500A
ACB fascia
cut-out dimensions
A
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
B
C
X
Type S - 4 pole - Frame size 1, In = 2000A & 2500A
ACB fascia
cut-out dimensions
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
C.14
M-PACT Plus
Front access connection
Fixed pattern
Type S - 3 pole - Frame size 2, In = 2000A & 4000A
Insulated metal or
insulated sheet
(customer supplied)
Minimum space to earth metal
and for arc chute removal
182 Min
Arc chute
removal
Minimum clearance
to breaker side.
Fascia centre
Dimensions
100 to door
Fascia centre
ACB fascia
cut-out dimension
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
Copperwork must be supported within 200mm of breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
A
B
C
X
Type S - 4 pole - Frame size 2, In = 2000A & 4000A
Insulated metal or
insulated sheet
(customer supplied)
Minimum space to earth metal
and for arc chute removal
182 Min
Arc chute
removal
Fascia centre
Minimum clearance
to breaker side.
100 to door
Fascia centre
ACB fascia
cut-out dimension
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
Copperwork must be supported within 200mm of breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
C.15
M-PACT Plus
Front access connection
Withdrawable pattern
Type S - 3 pole - Frame size 1, In = 400A to 2500A
Minimum clearance
to cassette side.
Fascia centre
Dimensional drawings
382 to door
Connected 414
50 Disconnected
35 Test
Fascia centre
ACB fascia
cut-out dimensions
A
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
B
C
X
Copperwork must be supported within 200mm of breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
Type S - 4 pole - Frame size 1, In = 400A to 2500A
Minimum clearance
to cassette side.
Fascia centre
382 to door
Connected 414
50 Disconnected
35 Test
Fascia centre
ACB fascia
cut-out dimensions
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
Copperwork must be supported within 200mm of breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
C.16
M-PACT Plus
Front access connection
Withdrawable pattern
Type S - 3 pole - Frame size 2, In = 2000A & 4000A
Minimum clearance
to cassette side.
Connected 414
50 Disconnected
35 Test
Dimensions
Fascia centre
382 to door
Fascia centre
ACB fascia
cut-out dimension
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
A
B
C
Copperwork must be supported within 200mm of breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
X
Type S - 4 pole - Frame size 2, In = 2000A & 4000A
Minimum clearance
to cassette side.
Fascia centre
382 to door
Connected 414
50 Disconnected
35 Test
Fascia centre
ACB fascia
cut-out dimension
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
Copperwork must be supported within 200mm of breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
C.17
M-PACT Plus
Horizontal, rear access connection
Fixed pattern
Minimum space to earth metal
and for arc chute removal
182 Min
Arc chute
removal
Insulated metal
or insulated sheet
(customer supplied)
Centre line of operating panel
Centre line of
operating panel
Fascia
centre
Dimensional drawings
Type N - 3 pole - Frame size 1, In = 400A to 1600A
Fascia centre
100 to door
ACB fascia
cut-out dimensions
A
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
B
Copperwork must be supported within 200mm of
breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
C
X
Type N - 4 pole - Frame size 1, In = 400A to 1600A
Minimum space to earth metal
and for arc chute removal
182 Min
Arc chute
removal
Insulated metal
or insulated sheet
(customer supplied)
Centre line of operating panel
Fascia
centre
Centre line of operating
panel
Fascia centre
100 to door
ACB fascia
cut-out dimensions
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
Copperwork must be supported within 200mm of
breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
C.18
M-PACT Plus
Horizontal, rear access connection
Fixed pattern
Type N - 3 pole - Frame size 1, In = 2000A and 2500A
Minimum space to earth metal
and for arc chute removal
182 Min
Arc chute
removal
Insulated metal
or insulated sheet
(customer supplied)
Centre line of operating panel
Fascia centre
100 to door
ACB fascia
cut-out dimensions
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
Copperwork must be supported within 200mm of
breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
Dimensions
Fascia
centre
Centre line of
operating panel
A
B
C
X
Type N - 4 pole - Frame size 1, In = 2000A and 2500A
Insulated metal
or insulated sheet
(customer
supplied)
Minimum space to earth metal
and for arc chute removal
182 Min
Arc chute
removal
Centre line of operating panel
Fascia
centre
Centre line of
operating panel
Fascia centre
100 to door
ACB fascia
cut-out dimensions
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
Copperwork must be supported within 200mm of
breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
C.19
M-PACT Plus
Horizontal, rear access connection
Fixed pattern
Minimum space to earth metal
and for arc chute removal
182 Min
Arc chute
removal
Insulated metal
or insulated sheet
(customer supplied)
Centre line of operating panel
Centre line of
operating panel
Fascia
centre
Dimensional drawings
Type N - 3 pole - Frame size 2, In = 2000A to 4000A
Fascia centre
100 to door
ACB fascia
cut-out dimensions
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
A
B
Copperwork must be supported within 200mm of
breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
C
X
Type N - 4 pole - Frame size 2, In = 2000A to 4000A
Insulated metal
or insulated sheet
(customer supplied)
Minimum space to earth metal
and for arc chute removal
182 Min
Arc chute
removal
Centre line of operating panel
Fascia
centre
Centre line of operating
panel
Fascia centre
100 to door
ACB fascia
cut-out dimensions
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
Copperwork must be supported within 200mm of
breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
C.20
M-PACT Plus
Rear access connection
Withdrawable pattern
Type N - 3 pole - Frame size 1, In = 400A to 2500A
Minimum clearance
to cassette side.
382 to door
Fascia
centre
Ventilation
Fascia
centre
35 Test
50 Disconnected
275 Fully withdrawn
Centre line of
operating panel
Connected 414
Dimensions
Centre line of
operating panel
ACB fascia
cut-out dimensions
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
Copperwork must be supported within 200mm of breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
Captive plate behind copper terminal, tapped M10 x 1.5 6H.
Minimum insertion of screw 16mm. Maximum insertion of screw 34mm.
A
B
C
X
Type N - 4 pole - Frame size 1, In = 400A to 2500A
Minimum clearance
to cassette side
382 to door
Fascia
centre
Ventilation
Fascia
centre
Centre line of
operating panel
35 Test
50 Disconnected
275 Fully withdrawn
Connected 414
Centre line of operating
panel
ACB fascia
cut-out dimensions
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
Copperwork must be supported within 200mm of breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
Captive plate behind copper terminal, tapped M10 x 1.5 6H.
Minimum insertion of screw 16mm. Maximum insertion of screw 34mm.
C.21
M-PACT Plus
Rear access connection
Withdrawable pattern
Minimum clearance to
cassette side.
382 to door
Fascia
centre
Ventilation
Centre line of
operating panel
Fascia
centre
Dimensional drawings
Type N - 3 pole - Frame size 2, In = 2000A to 3200A
35 Test
50 Disconnected
275 Fully withdrawn
Centre line of
operating panel
Connected 414
ACB fascia
cut-out dimensions
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
A
B
Copperwork must be supported within 200mm of breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
Captive plate behind copper terminal, tapped M10 x 1.5 6H.
Minimum insertion of screw 16mm. Maximum insertion of screw 34mm.
C
X
Type N - 4 pole - Frame size 2, In = 2000A to 3200A
Minimum clearance
to cassette side
382 to door
Ventilation
Fascia
centre
Fascia
centre
Centre line of
operating panel
35 Test
50 Disconnected
275 Fully withdrawn
Connected 414
Centre line of operating
panel
ACB fascia
cut-out dimensions
Copperwork must be supported within 200mm of breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
Captive plate behind copper terminal, tapped M10 x 1.5 6H.
Minimum insertion of screw 16mm. Maximum insertion of screw 34mm.
C.22
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
M-PACT Plus
Rear access connection
Withdrawable pattern
Type N - 3 pole - Frame size 2, In = 4000A
Must not be removed
or fitted horizontally
Minimum clearance
to cassette side.
382 to door
Fascia
centre
Ventilation
35 Test
50 Disconnected
Dimensions
Fascia
centre
Centre line of
operating panel
Centre line of
operating panel
Connected 414
275 Fully withdrawn
ACB fascia
cut-out dimensions
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
A
B
Copperwork must be supported within 200mm of breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
C
X
Type N - 4 pole - Frame size 2, In = 4000A
Minimum clearance
to cassette side.
Ventilation
Must not be removed
or fitted horizontally
382 to door
Fascia
centre
Fascia
centre
Centre line of
operating panel
35 Test
50 Disconnected
Connected 414
Centre line of operating panel
275 Fully withdrawn
ACB fascia
cut-out dimensions
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
Copperwork must be supported within 200mm of breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
C.23
M-PACT Plus
Front access connection
Fixed pattern
Type N - 3 pole - Frame size 1, In = 400A to 1600A
Minimum space to earth metal
and for arc chute removal
182 Min
Arc chute
removal
Minimum clearance
to breaker side.
Fascia centre
Dimensional drawings
Insulated metal or
insulated sheet
(customer supplied)
100 to door
Fascia centre
ACB fascia
cut-out dimensions
A
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
B
C
X
Copperwork must be supported within 200mm of breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
Type N - 4 pole - Frame size 1, In = 400A to 1600A
Insulated metal or insulated
sheet (customer supplied)
Minimum space to earth metal
and for arc chute removal
182 Min
Arc chute
removal
Fascia centre
Minimum clearance
to breaker side.
100 to door
Fascia centre
ACB fascia
cut-out dimensions
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
Copperwork must be supported within 200mm of breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
C.24
M-PACT Plus
Front access connection
Withdrawable pattern
Type N - 3 pole - Frame size 1, In = 400A to 2500A
Minimum clearance
to cassette side.
Connected 414
50 Disconnected
35 Test
Dimensions
Fascia centre
382 to door
Fascia centre
ACB fascia
cut-out dimensions
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
Copperwork must be supported within 200mm of breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
A
B
C
X
Type N - 4 pole - Frame size 1, In = 400A to 2500A
Minimum clearance
to cassette side.
Fascia centre
382 to door
Connected 414
50 Disconnected
35 Test
Fascia centre
ACB fascia
cut-out dimensions
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
Copperwork must be supported within 200mm of breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
C.25
M-PACT Plus
Front access connection
Fixed pattern
Type N - 3 pole - Frame size 2, In = 2000A to 4000A
Minimum space to earth metal
and for arc chute removal
182 Min
Arc chute
removal
Minimum clearance
to breaker side.
Fascia centre
Dimensional drawings
Insulated metal or
insulated sheet
(customer supplied)
100 to door
Fascia centre
ACB fascia
cut-out dimensions
A
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
B
C
X
Copperwork must be supported within 200mm of breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
Type N - 4 pole - Frame size 2, In = 2000A to 4000A
Minimum clearance
to breaker side.
Fascia centre
Minimum space to earth metal
and for arc chute removal
182 Min
Arc chute
removal
Insulated metal or
insulated sheet
(customer supplied)
100 to door
Fascia centre
ACB fascia
cut-out dimensions
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
Copperwork must be supported within 200mm of breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
C.26
M-PACT Plus
Front access connection
Withdrawable pattern
Type N - 3 pole - Frame size 2, In = 2000A to 4000A
Minimum clearance
to cassette side.
Connected 414
50 Disconnected
35 Test
Dimensions
Fascia centre
382 to door
Fascia centre
ACB fascia
cut-out dimensions
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
A
B
C
Copperwork must be supported within 200mm of breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
X
Type N - 4 pole - Frame size 2, In = 2000A to 4000A
Minimum clearance
to cassette side.
Fascia centre
382 to door
Connected 414
50 Disconnected
35 Test
Fascia centre
ACB fascia
cut-out dimensions
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
Copperwork must be supported within 200mm of breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
C.27
M-PACT Plus
Horizontal, rear access connection
Fixed pattern
Minimum space to earth metal
and for arc chute removal
182 Min
Arc chute
removal
Insulated metal
or insulated sheet
(customer supplied)
Centre line of operating panel
Centre line of
operating panel
Fascia
centre
Dimensional drawings
Type H - 3 pole - Frame size 2, In = 800A to 4000A
Fascia centre
100 to door
ACB fascia
cut-out dimensions
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
A
B
Copperwork must be supported within 200mm of
breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
C
X
Type H - 4 pole - Frame size 2, In = 800A to 4000A
Insulated metal
or insulated sheet
(customer supplied)
Minimum space to earth metal
and for arc chute removal
182 Min
Arc chute
removal
Centre line of operating panel
Fascia
centre
Centre line of
operating panel
100 to door
Fascia centre
ACB fascia
cut-out dimensions
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
Copperwork must be supported within 200mm of
breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
C.28
M-PACT Plus
Rear access connection
Withdrawable pattern
Type H - 3 pole - Frame size 2, In = 800A to 3200A
Minimum clearance to
cassette side.
382 to door
Fascia
centre
Ventilation
35 Test
50 Disconnected
275 Fully withdrawn
Dimensions
Fascia
centre
Centre line of
operating panel
Centre line of
operating panel
Connected 414
ACB fascia
cut-out dimensions
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
A
B
Copperwork must be supported within 200mm of breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
Captive plate behind copper terminal, tapped M10 x 1.5 6H.
Minimum insertion of screw 16mm. Maximum insertion of screw 34mm.
C
X
Type H - 4 pole - Frame size 2, In = 800A to 3200A
Minimum clearance
to cassette side.
Ventilation
382 to door
Fascia
centre
Fascia
centre
Centre line of
operating panel
35 Test
50 Disconnected
275 Fully withdrawn
Connected 414
Centre line of
operating panel
ACB fascia
cut-out dimensions
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
Copperwork must be supported within 200mm of breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
Captive plate behind copper terminal, tapped M10 x 1.5 6H.
Minimum insertion of screw 16mm. Maximum insertion of screw 34mm.
C.29
M-PACT Plus
Rear access connection
Withdrawable pattern
Must not be removed
or fitted horizontally
Minimum clearance
to cassette side.
Fascia
centre
382 to door
Ventilation
Centre line of
operating panel
Fascia
centre
Dimensional drawings
Type H - 3 pole - Frame size 2, In = 4000A
35 Test
50 Disconnected
Centre line of
operating panel
Connected 414
275 Fully withdrawn
ACB fascia
cut-out dimensions
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
A
B
C
X
Copperwork must be supported within 200mm of breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
Type H - 4 pole - Frame size 2, In = 4000A
Minimum clearance
to cassette side.
Ventilation
Must not be removed
or fitted horizontally
382 to door
Fascia
centre
Fascia
centre
Centre line of
operating panel
Centre line of operating panel
35 Test
50 Disconnected
275 Fully withdrawn
Connected 414
ACB fascia
cut-out dimensions
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
Copperwork must be supported within 200mm of breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
C.30
M-PACT Plus
Front access connection
Fixed pattern
Type H - 3 pole - Frame size 2, In = 800A to 4000A
Insulated metal or
insulated sheet
(customer supplied)
Minimum space to earth metal
and for arc chute removal
Minimum clearance
to breaker side.
Dimensions
Fascia centre
182 Min
Arc chute
removal
100 to door
Fascia centre
ACB fascia
cut-out dimensions
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
A
B
C
Copperwork must be supported within 200mm of breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
X
Type H - 4 pole - Frame size 2, In = 800A to 4000A
Insulated metal or insulated
sheet (customer supplied)
Minimum space to earth
metal and for arc chute
182 Min
Arc chute
removal
Fascia centre
Minimum clearance to
breaker side.
100 to door
Fascia centre
ACB fascia
cut-out dimensions
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
Copperwork must be supported within 200mm of breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
C.31
M-PACT Plus
Front access connection
Withdrawable pattern
Type H - 3 pole - Frame size 2, In = 800A to 4000A
Minimum clearance
to cassette side.
Fascia centre
Dimensional drawings
382 to door
Connected 414
50 Disconnected
35 Test
Fascia centre
ACB fascia
cut-out dimensions
A
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
B
C
X
Copperwork must be supported within 200mm of breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
Type H - 4 pole - Frame size 2, In = 800A to 4000A
Minimum clearance
to cassette side.
Fascia centre
382 to door
Connected 414
50 Disconnected
35 Test
Fascia centre
ACB fascia
cut-out dimensions
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
Copperwork must be supported within 200mm of breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
C.32
M-PACT Plus
Rear connection
Withdrawable pattern
100*)
282,5
70
70
70
40 30
1)
90
517
7
Dimensions
148
210
Ø14,5
578
min.
282,5
200*)
100*)
OFF (83)
100*)
TEST (59)
100*)
ON (0)
Type C - 3 pole - Frame size 3, In = 5000A
3)
124,5
425
30
124,5
574,5
280
Ø9
280
68
280
945
673,5
729 2)
969
756,5
A
M-Pact Frame 3 - 5000A 3-pole withdrawable
Busbar dimensions: 60x12 - 8 busbars: copper black painted.
High-quality M8 screws of properity class 8.8 shall be used to make the connection.
The screws shall not be lubricated, the tightening torque is 70Nm.
Copperwork must be supported within 100mm of breaker connections - busbars or cables.
B
*) Min clearances of arc chute to insulated or grounded parts.
C
Horizontal connection
Fixed pattern
X
Type C - 3 pole - Frame size 3, In = 5000A
100*)
818
100*)
100*)
178
33
183
200*)
100*)
X1
M12
Ø14
G
S
S
20
S
20
8
96
F
39
3
16
101
89
860
902
F
107
60
15
297
327
361
366
367
418
F
165
350
518
F
334
349
411
M12
450
255
60 60
Ø14
ACB fascia
cut-out dimensions
282,5
Busbar dimensions: 60x12 - 8 busbars: copper black painted.
High-quality M8 screws of properity class 8.8 shall be used to make the connection.
The screws shall not be lubricated, the tightening torque is 70Nm.
Copperwork must be supported within 100mm of breaker connections - busbars or cables.
15
282,5
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
364
60
40
20
526
481
303
*) Min clearances of arc chute to insulated or grounded parts.
C.33
M-PACT Plus
Rear access connection
Withdrawable pattern
Ø14,5
min.
70
1)
517
644,5
124,5
30
124,5
Ø9
Busbar dimensions: 120x12 - 8 busbars: copper black painted.
High-quality M8 screws of properity class 8.8 shall be used to make the connection.
The screws shall not be lubricated, the tightening torque is 70Nm.
Copperwork must be supported within 100mm of breaker connections - busbars or cables.
*) Min clearances of arc chute to insulated or grounded parts.
C.34
280
945
969
2)
M-Pact Frame 3 - 6300A 3-pole withdrawable
X
280
12
280
68
578
30 30 30
3)
425
A
C
70
90
673,5
729
756,5
B
100*)
282,5
200*)
282,5
290
120
25
100*)
OFF (83)
TEST (59)
100*)
63
Dimensional drawings
100*)
ON (0)
Type C - 3 pole - Frame size 3, In = 6300A
M-PACT Plus
Adaptor connections
(for cassette only)
Rear Adapter Vertical Connection
Type S - Frame 1 - In = 400A to 1600A (max)
Rear Adapter Horizontal Connection
Type S - Frame 1 - In = 400A to 1600A (max)
Dimensions
A
B
C
Rear Adapter Vertical / Horizontal Connection
Type S - Frame 1 - In = 2000A & 2500A (max)
Type S - Frame 2 - In = 2000A to 3200A (max)
Type N - Frame 1 - In = 400A to 2500A (max)
Type N - Frame 2 - In = 2000A to 3200A (max)
X
Type H - Frame 2 - In = 800A to 3200A (max)
C.35
M-PACT Plus
Adaptor connections
(for cassette only)
Copper connections - Front access (Fixed and/or withdrawable)
Type S - Frame 1 - In = 400A to 2500A (max)
Type S - Frame 2 - In = 2000A to 4000A
Type N - Frame 1 - In = 400A to 2500A (max)
Type N - Frame 2 - In = 2000A to 4000A
Dimensional drawings
Type H - Frame 2 - In = 800A to 4000A
A
B
C
X
IP54 Door (Withdrawable unit only - Frame 1 & 2 only)
479
114.5
391
C.36
M-PACT Plus
Door cut-outs
Fixed pattern - Facia cut-out
Frame 3
Dimensions
15
364
Frame 1 & 2
481
Frame
= 42,5
Frame
= 102,5
A
303
B
The cut-out dimensions shown above give
an approximate nominal clearance of 3mm around
ACB fascia. These sizes are for guidance
and can be scaled if a different aperture
is required.
C
X
Withdrawable pattern - Cubicle door/panel
Frame 1 & 2
Frame3
Escutcheon
(LLA11PD055)
Escutcheon seal
(LLA11RS001)
ACB fascia
16 off 3.0 x 6
Self tapping screws
3.6
19
9
122
384
266.6
281
9
Ø28
405
2 x Ø4.5
358
Frame 1 - Up to 2500A max. = 40
Frame 2 - Up to 4000A max. = 100
3.6
263
9
8
91
186
425
28
52
218
417.2
400
30
28
28
Datum for 16 off Ø 4 holes in door / panel
– bottom left hand corner of cassette
viewed from front.
C.37
M-PACT Plus
Cassette
Dimensional drawings
Cassette mounting details
Type S - Frame 1 - In = 400A to 2500A (max)
Type S - Frame 2 - In = 2000A to 4000A
Type N - Frame 1 - In = 400A to 2500A (max)
Type N - Frame 2 - In = 2000A to 4000A
Type H - Frame 2 - In = 800A to 4000A
rom top
to 2500 A (max.)
to 2500 A (max.)
Cassette viewed from top
Type 'S', In = 3200 and 4000 A
Type 'N', In = 3200 and 4000 A
Type 'H', In = 800 to 4000 A
Terminals
Ventilation in base
of cassette
(leave unobstructed)
Terminals
Ventilation in base
of cassette
(leave unobstructed)
9,6
All holes
4 Pole only
6 Holes
Centre line
of operating
panel
Centre line of operating panel
A
3 Pole 358
4 Pole 488
3 Pole 419
4 Pole 549
3 Pole 268 4 Pole 368
B
3 Pole 287 4 Pole 387
3 Pole 329 4 Pole 429
C
X
Type C - Frame 3 - In = 5000A to 6300A (max)
425
center of cassette
188
Ø9
door
breaker cover
124,5
424
68
280
357
280
3 /4 Pole 969
C.38
280
9,6
M-PACT Plus
2-Way cable interlocking
Fixed pattern - Front/rear access
140 Min
Dimensions
900 Max vertical base to base
2000 Max
A
Min. bend radius 120
B
Min. bend radius 120
C
X
Withdrawable pattern - Front/rear access
Min.
clearance
below
cassette
140 Min
Min.
clearance
below
cassette
900 Max vertical base to base
2000 Max
Min. bend radius 120
Min. bend radius 120
C.39
M-PACT Plus
3-Way cable interlocking
Dimensional drawings
Fixed pattern - Front/rear access
A
B
C
X
C.40
Withdrawable pattern - Front/rear access
M-PACT Plus
X.1
X.5
Numerical index by reference number
Numerical index by catalogue number
Technical overview
A
Order codes
B
Wiring diagrams / Dimensional drawings
C
Numerical Index
X
X.1
M-PACT Plus
Numerical index
Ref. no.
A
B
C
X
X.2
403…
403680
403681
405…
405102
405103
405104
405105
405106
405107
405108
405109
405110
405111
405112
405113
405114
405115
405116
405117
405118
405119
405120
405121
405122
405123
405124
405125
405128
405129
405130
405131
405132
405133
405134
405135
405136
405137
405138
405139
405140
405141
405142
405143
405144
405145
405146
405147
405148
405149
405150
405151
405152
405153
405154
405155
405162
405163
405164
405165
405166
405167
405168
405169
405170
405171
405172
405173
405174
405175
405176
405177
405178
405179
405180
405181
405182
405183
405184
405185
405186
405192
405193
405194
405195
405196
405197
405198
Cat. no.
Page
RT1HOR
RT1VER
B.2
B.2
MS4L1W04
MS31W04
MS4L1W06
MS31W06
MS4L1W08
MS31W08
MS4L1W10
MS31W10
MS4L1W12
MS31W12
MS4L1W16
MS31W16
MS4L1W20
MS31W20
MS4L1W25
MS31W25
MS4L2W20
MS32W20
MS4L2W25
MS32W25
MS4L2W32
MS32W32
MS4L2W40
MS32W40
MPRO30L-FRF
MPRO30H-FRF
MPRO40L-FRF
MPRO40H-FRF
MS4L1F04
MS31F04
MS4L1F06
MS31F06
MS4L1F08
MS31F08
MS4L1F10
MS31F10
MS4L1F12
MS31F12
MS4L1F16
MS31F16
MS4L1F20
MS31F20
MS4L1F25
MS31F25
MS4L2F20
MS32F20
MS4L2F25
MS32F25
MS4L2F32
MS32F32
MS4L2F40
MS32F40
MN4L1W04
MN31W04
MN4L1W06
MN31W06
MN4L1W08
MN31W08
MN4L1W10
MN31W10
MN4L1W12
MN31W12
MN4L1W16
MN31W16
MN4L1W20
MN31W20
MN4L1W25
MN31W25
MN4L2W20
MN32W20
MN4L2W25
MN32W25
MN4L2W32
MN32W32
MN4L2W40
MN32W40
MS4R1F04-A
MN4L1F04
MN31F04
MN4L1F06
MN31F06
MN4L1F08
MN31F08
MN4L1F10
B.2
B.2
B.2
B.2
B.2
B.2
B.2
B.2
B.2
B.2
B.2
B.2
B.2
B.2
B.2
B.2
B.2
B.2
B.2
B.2
B.2
B.2
B.2
B.2
B.15
B.15
B.15
B.15
B.2
B.2
B.2
B.2
B.2
B.2
B.2
B.2
B.2
B.2
B.2
B.2
B.2
B.2
B.2
B.2
B.2
B.2
B.2
B.2
B.2
B.2
B.2
B.2
B.6
B.6
B.6
B.6
B.6
B.6
B.6
B.6
B.6
B.6
B.6
B.6
B.6
B.6
B.6
B.6
B.6
B.6
B.6
B.6
B.6
B.6
B.6
B.6
B.4
B.6
B.6
B.6
B.6
B.6
B.6
B.6
Ref. no.
Cat. no.
Page
Ref. no.
405199
405200
405201
405202
405203
405204
405205
405206
405207
405208
405209
405210
405211
405212
405213
405214
405215
405216
405217
405218
405219
405222
405223
405226
405227
405228
405229
405230
405231
405232
405233
405234
405235
405236
405237
405238
405239
405240
405241
405242
405243
405244
405245
405246
405247
405248
405249
405250
405251
405252
405253
405254
405255
405256
405257
405258
405259
405260
405261
405262
405263
405264
405265
405266
405267
405268
405269
405270
405271
405272
405273
405274
405275
405276
405277
405278
405296
405297
405298
405299
405316
405318
405320
405322
405324
405326
405327
405328
MN31F10
MN4L1F12
MN31F12
MN4L1F16
MN31F16
MN4L1F20
MN31F20
MN4L1F25
MN31F25
MN4L2F20
MN32F20
MN4L2F25
MN32F25
MN4L2F32
MN32F32
MN4L2F40
MN32F40
MS4L1F04-A
MS31F04-A
MS4L1F06-A
MS31F06-A
MPROPLUSTU-EURO
MPROPTU-EURO
MH4L2W08
MH32W08
MH4L2W10
MH32W10
MH4L2W12
MH32W12
MH4L2W16
MH32W16
MH4L2W20
MH32W20
MH4L2W25
MH32W25
MS4L1F08-A
MS31F08-A
MS4L1F10-A
MS31F10-A
MH4L2W32
MH32W32
MH4L2W40
MH32W40
MS4L1F12-A
MS31F12-A
MS4L1F16-A
MS31F16-A
MS4L1F20-A
MS31F20-A
MS4L1F25-A
MS31F25-A
MS4L2F20-A
MS32F20-A
MH4L2F08
MH32F08
MH4L2F10
MH32F10
MH4L2F12
MH32F12
MH4L2F16
MH32F16
MH4L2F20
MH32F20
MH4L2F25
MH32F25
MS4L2F25-A
MS32F25-A
MS4L2F32-A
MS32F32-A
MH4L2F32
MH32F32
MH4L2F40
MH32F40
MS4L2F40-A
MS32F40-A
MS4R1F06-A
MS4R1F08-A
PAMM20
MS4R1F10-A
PAMM30/40
MS4R1W04
MS4R1W06
MS4R1W08
MS4R1W10
MS4R1W12
MS4R1W16
MPRO17plusF1&2
MS4R1W20
B.6
B.6
B.6
B.6
B.6
B.6
B.6
B.6
B.6
B.6
B.6
B.6
B.6
B.6
B.6
B.6
B.6
B.4
B.4
B.4
B.4
B.15
B.15
B.10
B.10
B.10
B.10
B.10
B.10
B.10
B.10
B.10
B.10
B.10
B.10
B.4
B.4
B.4
B.4
B.10
B.10
B.10
B.10
B.4
B.4
B.4
B.4
B.4
B.4
B.4
B.4
B.4
B.4
B.10
B.10
B.10
B.10
B.10
B.10
B.10
B.10
B.10
B.10
B.10
B.10
B.4
B.4
B.4
B.4
B.10
B.10
B.10
B.10
B.4
B.4
B.4
B.4
B.15
B.4
B.15
B.2
B.2
B.2
B.2
B.2
B.2
B.15
B.2
405329
405330
405331
405332
405334
405336
405338
405340
405341
405342
405343
405344
405345
405346
405347
405348
405349
405350
405351
405352
405353
405354
405355
405356
405357
405358
405359
405360
405361
405362
405363
405364
405365
405366
405368
405370
405372
405374
405376
405378
405380
405381
405382
405384
405386
405387
405388
405389
405390
405391
405392
405393
405400
405402
405404
405406
405407
405408
405409
405410
405411
405412
405413
405414
405415
405416
405417
405418
405419
405420
405422
405424
405425
405426
405428
405430
405432
405434
405436
405438
405440
405442
405444
405445
405446
405448
405450
405451
Cat. no.
MPRO18 plusF1&2
MS4R1W25
MPROPlusUEF
MS4R2W20
MS4R2W25
MS4R2W32
MS4R2W40
MS41C16
MS31C16
MS41C25
MS31C25
MN41C25
MN31C25
MN42C32
MN32C32
MN42C40
MN32C40
MN4L1W04-A
MN31W04-A
MN4L1W06-A
MN31W06-A
MS42C32
MS32C32
MH42C32
MH32C32
MH42C40
MH32C40
MN4L1W08-A
MN31W08-A
MN4L1W10-A
MN31W10-A
MS42C40
MS32C40
MS4R1F04
MS4R1F06
MS4R1F08
MS4R1F10
MS4R1F12
MS4R1F16
MS4R1F20
ST30
MS4R1F25
ST48
MS4R2F20
ST130
MS4R2F25
ST250
ST440
MS4R1F12-A
MS4R2F32
MS4R1F16-A
MS4R2F40
UV30
UV48
MS4R1F20-A
UV130A
UV130D
UV250
UV440
MN4L1W12-A
UVTD250
MN31W12-A
UVTD440
MN4L1W16-A
MN31W16-A
MN4L1W20-A
MN31W20-A
MN4L1W25-A
MN31W25-A
CC30
CC48
MN4L2W20-A
MN32W20-A
CC130
CC250
MN4R1W04
MN4R1W06
MN4R1W08
MN4R1W10
MN4R1W12
MOP30
MOP48
MN4L2W25-A
MN32W25-A
MOP130A
MOP250A
SCC
2WPFC
Page
Ref. no.
Cat. no.
Page
B.15
B.2
B.15
B.2
B.2
B.2
B.2
B.3
B.3
B.3
B.3
B.7
B.7
B.7
B.7
B.7
B.7
B.8
B.8
B.8
B.8
B.3
B.3
B.11
B.11
B.11
B.11
B.8
B.8
B.8
B.8
B.3
B.3
B.2
B.2
B.2
B.2
B.2
B.2
B.2
B.16
B.2
B.16
B.2
B.16
B.2
B.16
B.16
B.4
B.2
B.4
B.2
B.16
B.16
B.4
B.16
B.16
B.16
B.16
B.8
B.16
B.8
B.16
B.8
B.8
B.8
B.8
B.8
B.8
B.16
B.16
B.8
B.8
B.16
B.16
B.6
B.6
B.6
B.6
B.6
B.16
B.16
B.8
B.8
B.16
B.16
B.16
B.16
405452
405453
405454
405455
405456
405458
405459
405460
405461
405462
405463
405464
405465
405466
405468
405470
405472
405474
405475
405476
405477
405478
405479
405480
405481
405482
405484
405486
405488
405490
405491
405492
405493
405494
405495
405496
405497
405498
405500
405502
405504
405505
405506
405508
405509
405510
405511
405512
405513
405514
405515
405516
405517
405518
405520
405522
405524
405526
405528
405530
405531
405532
405533
405534
405535
405537
405538
405540
405542
405545
405547
405548
405550
405551
405552
405553
405554
405555
405556
405557
405558
405559
405560
405561
405562
405563
405564
405565
MN4L2W32-A
MN32W32-A
MN4L2W40-A
MN32W40-A
MN4R1W16
MN4R1W20
2WCIF23PW
MN4R1W25
2WCIF24PW
MN4R2W20
2WCIF23PF
MN4R2W25
2WCIF24PF
MN4R2W32
MN4R2W40
MN4R1F04
MN4R1F06
MN4R1F08
B13WCIF23PW
MN4R1F10
B13WCIF24PW
MN4R1F12
B13WCIF23PF
MN4R1F16
B13WCIF24PF
MN4R1F20
MN4R1F25
MN4R2F20
MN4R2F25
MN4R2F32
C23WCIF23PW
MN4R2F40
C23WCIF24PW
MH4R2W08
C23WCIF23PF
MH4R2W10
C23WCIF24PF
MH4R2W12
MH4R2W16
MH4R2W20
MH4R2W25
ACBMIL
MH4R2W32
MH4R2W40
MH4R2F08
MH4R2F10
D13WCIF23PW
MH4R2F12
D13WCIF24PW
MH4R2F16
D13WCIF23PF
MH4R2F20
D13WCIF24PF
MH4R2F25
MH4R2F32
MH4R2F40
MS4R1M04
MS4R1M06
MS4R1M08
MPRO40L-ENG
100BCMCI
160BCMCI
200BCMCI
MPRO40H-ENG
MPROPLUSUEF3P3W
MPROREF
MPROSEF
MPRONTSW
MS4R1M10
MPROCOM
MPROAPU
MS4R1M12
MPROPTU17
MPROPTU
MPROPPB
FA32WH32B
FA42WH32B
FA32WH40B
FA42WH40B
FA31FN16B
FA41FN16B
FA31FN25B
FA41FN25B
FA32FN32B
FA42FN32B
FA32FN40B
FA42FN40B
FA32FH32B
B.8
B.8
B.8
B.8
B.6
B.6
B.18
B.6
B.18
B.6
B.18
B.6
B.18
B.6
B.6
B.6
B.6
B.6
B.18
B.6
B.18
B.6
B.18
B.6
B.18
B.6
B.6
B.6
B.6
B.6
B.18
B.6
B.18
B.10
B.18
B.10
B.18
B.10
B.10
B.10
B.10
B.19
B.10
B.10
B.10
B.10
B.18
B.10
B.18
B.10
B.18
B.10
B.18
B.10
B.10
B.10
B.3
B.3
B.3
B.15
B.18
B.18
B.18
B.15
B.15
B.15
B.15
B.15
B.3
B.15
B.15
B.3
B.15
B.15
B.15
B.10
B.10
B.10
B.10
B.7
B.7
B.7
B.7
B.7
B.7
B.7
B.7
B.10
M-PACT Plus
Ref. no.
Cat. no.
FA42FH32B
FA32FH40B
FA42FH40B
FORLOK
CASLOK
RONLOK
PROLOK
RONCAS
PROCAS
MPROMAC
MOC
DILHS
DIRHS
CSWFF
CSWL
MS4R1M16
MS4R1M20
MS4R1M25
MS4R2M20
MS4R2M25
MS4R2M32
MS4R2M40
MN4R1M04
MN4R1M06
RT1UNI
RT2UNI
MN4R1M08
RT1SVFIX
MN4R1M10
ACBMID
IP54DOOR
ACBLIFT
RT1SNVFIX
250BCMCI
300BCMCI
350BCMCI
400BCMCI
RT2SNHVFIX
RT2SNHVFIX
MN4R1M12
MN4R1M16
MN4R1M20
MN4R1M25
MN4R2M20
MN4R2M25
MN4R2M32
MN4R2M40
MH4R2M08
MH4R2M10
MH4R2M12
MH4R2M16
MH4R2M20
MH4R2M25
MH4R2M32
MH4R2M40
MN4L1F04-A
MN31F04-A
MN4L1F06-A
MN31F06-A
EDF14P16
EDF13P16
EDF14P25
EDF13P25
EDF24P40
EDF23P40
MN4L1F08-A
MN31F08-A
MS4R1F25-A
ELCT8001
ELCT10001
ELCT12501
ELCT16001
ELCT20001
ELCT25001
ELCT32002
ELCT40002
RCMK8001
RCMK10001
RCMK12501
RCMK16001
RCMK20001
RCMK25001
RCMK32002
RCMK40002
MS4R2F20-A
ELCT8002
ELCT10002
ELCT12502
Page
Ref. no.
Cat. no.
B.10
B.10
B.10
B.19
B.19
B.19
B.19
B.19
B.19
B.15
B.19
B.19
B.19
B.16
B.16
B.3
B.3
B.3
B.3
B.3
B.3
B.3
B.7
B.7
B.2
B.2
B.7
B.2
B.7
B.19
B.19
B.19
B.2
B.18
B.18
B.18
B.18
B.2
B.12
B.7
B.7
B.7
B.7
B.7
B.7
B.7
B.7
B.11
B.11
B.11
B.11
B.11
B.11
B.11
B.11
B.8
B.8
B.8
B.8
B.3
B.3
B.3
B.3
B.3
B.3
B.8
B.8
B.4
B.20
B.20
B.20
B.20
B.20
B.20
B.20
B.20
B.20
B.20
B.20
B.20
B.20
B.20
B.20
B.20
B.4
B.20
B.20
B.20
405716
405717
405718
405720
405721
405722
405723
405724
405725
405726
405727
405728
405730
405731
405732
405733
405734
405735
405736
405737
405738
405739
405740
405741
405742
405743
405744
405745
405746
405747
405748
405769
405770
405771
405772
405773
405778
405779
405780
405781
405782
405783
405784
405785
405786
405787
405788
405789
405790
405791
405792
405796
405797
405798
405799
405800
405801
405802
405803
405804
405805
405806
405807
405808
405809
405810
405811
405812
405813
405814
405815
405816
405817
405818
405819
405820
405821
405822
405823
405824
405825
405826
405828
405829
405830
405831
405832
405833
ELCT16002
ELCT20002
ELCT25002
MN4L1F10-A
MN31F10-A
MS4R2F25-A
RCMK8002
RCMK10002
RCMK12502
RCMK16002
RCMK20002
RCMK25002
MN4L1F12-A
MN31F12-A
MN4L1F16-A
MN31F16-A
MN4L1F20-A
MN31F20-A
MN4L1F25-A
MN31F25-A
FACS116
MACS116
FACN116
MACN116
FAC125
MAC125
FAC232
MAC232
FAC240
MAC240
MS4R2F32-A
CLCS116
CLCN116
CLC125
CLC232
CLC240
MN4L2F20-A
MN32F20-A
MN4L2F25-A
MN32F25-A
MN4L2F32-A
MN32F32-A
MN4L2F40-A
MN32F40-A
MS4R2F40-A
ARC16
ARC32H
ARC40H
ARC25
ARC32SN
ARC40SN
MH4L2W08-A
MH32W08-A
MH4L2W12-A
MH32W10-A
UNIPLIER
MH32W12-A
MH4L2W10-A
MS31M04
MS4L1M04
MS31M06
MS4L1M06
MS31M08
MS4L1M08
MS31M10
MS4L1M10
MS31M12
MS4L1M12
MS31M16
MS4L1M16
MS31M20
MS4L1M20
MS31M25
MS4L1M25
MS32M20
MS4L2M20
MS32M25
MS4L2M25
MS32M32
MS4L2M32
MS32M40
MS4L2M40
MH4L2W16-A
MH32W16-A
MH4L2W20-A
MH32W20-A
MN4R1W04-A
MN31M04
Page
Ref. no.
Cat. no.
B.20
B.20
B.20
B.8
B.8
B.4
B.20
B.20
B.20
B.20
B.20
B.20
B.8
B.8
B.8
B.8
B.8
B.8
B.8
B.8
B.20
B.20
B.20
B.20
B.20
B.20
B.20
B.20
B.20
B.20
B.4
B.20
B.20
B.20
B.20
B.20
B.8
B.8
B.8
B.8
B.8
B.8
B.8
B.8
B.4
B.20
B.20
B.20
B.20
B.20
B.20
B.12
B.12
B.12
B.12
B.20
B.12
B.12
B.3
B.3
B.3
B.3
B.3
B.3
B.3
B.3
B.3
B.3
B.3
B.3
B.3
B.3
B.3
B.3
B.3
B.3
B.3
B.3
B.3
B.3
B.3
B.3
B.12
B.12
B.12
B.12
B.8
B.7
405834
405835
405836
405837
405838
405839
405840
405841
405842
405843
405844
405845
405846
405847
405848
405849
405850
405851
405852
405853
405854
405855
405856
405858
405859
405860
405861
405862
405863
405864
405866
405867
405868
405869
405870
405871
405872
405873
405874
405875
405876
405877
405878
405880
405881
405882
405883
405884
405885
405886
405888
405889
405890
405891
405892
405893
405894
405895
405896
405897
405898
405899
405900
405901
405902
405904
405905
405906
405907
405908
405909
405910
405911
405912
405913
405914
405915
405916
405917
405918
405919
405920
405921
405922
405923
405924
405925
405926
MN4L1M04
MN31M06
MN4L1M06
MN31M08
MN4L1M08
MN31M10
MN4L1M10
MN31M12
MN4L1M12
MN31M16
MN4L1M16
MN31M20
MN4L1M20
MN31M25
MN4L1M25
MN32M20
MN4L2M20
MN32M25
MN4L2M25
MN32M32
MN4L2M32
MN32M40
MN4L2M40
MH4L2W25-A
MH32W25-A
MH4L2W32-A
MH32W32-A
MH4L2W40-A
MH32W40-A
MN4R1W06-A
MN4R1W08-A
MH32M08
MH4L2M08
MH32M10
MH4L2M10
MH32M12
MH4L2M12
MH32M16
MH4L2M16
MH32M20
MH4L2M20
MH32M25
MH4L2M25
MH4L2F08-A
MH32F08-A
MN4R1W10-A
MH32M32
MH4L2M32
MH32M40
MH4L2M40
MH4L2F10-A
MH32F10-A
MH4L2F12-A
MH32F12-A
MH4L2F16-A
MH32F16-A
MH4L2F20-A
MH32F20-A
MH4L2F25-A
MH32F25-A
MH4L2F32-A
MH32F32-A
MH4L2F40-A
MH32F40-A
MN4R1W12-A
MN4R1W16-A
MS31M04-A
MS4L1M04-A
MS31M06-A
MS4L1M06-A
MS31M08-A
MS4L1M08-A
MS31M10-A
MS4L1M10-A
MS31M12-A
MS4L1M12-A
MS31M16-A
MS4L1M16-A
MOP130D
MS4L1M20-A
MS31M25-A
MS4L1M25-A
FA31WS16T
FA41WS16T
FA31WS25T
FA41WS25T
FA32WS32T
FA42WS32T
Page
Ref. no.
Cat. no.
B.7
B.7
B.7
B.7
B.7
B.7
B.7
B.7
B.7
B.7
B.7
B.7
B.7
B.7
B.7
B.7
B.7
B.7
B.7
B.7
B.7
B.7
B.7
B.12
B.12
B.12
B.12
B.12
B.12
B.8
B.8
B.11
B.11
B.11
B.11
B.11
B.11
B.11
B.11
B.11
B.11
B.11
B.11
B.12
B.12
B.8
B.11
B.11
B.11
B.11
B.12
B.12
B.12
B.12
B.12
B.12
B.12
B.12
B.12
B.12
B.12
B.12
B.12
B.12
B.8
B.8
B.5
B.5
B.5
B.5
B.5
B.5
B.5
B.5
B.5
B.5
B.5
B.5
B.16
B.5
B.5
B.5
B.2
B.2
B.2
B.2
B.2
B.2
405927
405928
405929
405930
405931
405932
405933
405934
405935
405936
405937
405938
405939
405940
405941
405942
405943
405944
405945
405946
405947
405948
405949
405950
405951
405952
405953
405954
405955
405956
405957
405958
405959
405960
405961
405962
405963
405964
405965
405966
405967
405968
405969
405970
405971
405972
405973
405974
405975
405976
405977
405978
405979
405980
405981
405982
405983
405984
405985
405986
405987
405988
405989
405990
405991
405992
405994
405995
405996
405997
405998
405999
406…
406000
406001
406002
406003
406004
406005
406006
406007
406008
406009
406010
406011
406012
406020
406021
FA32WS40T
FA42WS40T
MS32M20-A
MS4L2M20-A
MS32M25-A
MS4L2M25-A
FA31FS16T
FA41FS16T
FA31FS25T
FA41FS25T
FA32FS32T
FA42FS32T
FA32FS40T
FA42FS40T
MS32M32-A
MS4L2M32-A
MS32M40-A
MS4L2M40-A
FA31WN16T
FA41WN16T
FA31WN25T
FA41WN25T
FA32WN32T
FA42WN32T
FA32WN40T
FA42WN40T
MN31M04-A
MN4L1M04-A
MN31M06-A
MN4L1M06-A
FA31FN16T
FA41FN16T
FA31FN25T
FA41FN25T
FA32FN32T
FA42FN32T
FA32FN40T
FA42FN40T
MN31M08-A
MN4L1M08-A
MN31M10-A
MN4L1M10-A
MN31M12-A
MN4L1M12-A
MN31M16-A
MN4L1M16-A
FA32WH32T
FA42WH32T
FA32WH40T
FA42WH40T
MN31M20-A
MN4L1M20-A
MN31M25-A
MN4L1M25-A
MN32M20-A
MN4L2M20-A
MN32M25-A
MN4L2M25-A
FA32FH32T
FA42FH32T
FA32FH40T
FA42FH40T
MN32M32-A
MN4L2M32-A
MN32M40-A
MN4L2M40-A
MN4R1W20-A
MS31M20-A
MN4R1W25-A
MH32M08-A
MH4L2M08-A
MH32M10-A
Page
B.2
B.2
B.5
B.5
B.5
B.5
B.3
B.3
B.3
B.3
B.3
B.3
B.3
B.3
B.5
B.5
B.5
B.5
B.6
B.6
B.6
B.6
B.6
B.6
B.6
B.6
B.9
B.9
B.9
B.9
B.7
B.7
B.7
B.7
B.7
B.7
B.7
B.7
B.9
B.9
B.9
B.9
B.9
B.9
B.9
B.9
B.10
B.10
B.10
B.10
B.9
B.9
B.9
B.9
B.9
B.9
B.9
B.9
B.10
B.10
B.10
B.10
B.9
B.9
B.9
B.9
B.8
B.5
B.8
B.13
B.13
B.13
MH4L2M10-A
MH32M12-A
MH4L2M12-A
MH32M16-A
MH4L2M16-A
MH32M20-A
MH4L2M20-A
MH32M25-A
MH4L2M25-A
MH32M32-A
MH4L2M32-A
MH32M40-A
MH4L2M40-A
MN4R2W20-A
FA31WS16B
B.13
B.13
B.13
B.13
B.13
B.13
B.13
B.13
B.13
B.13
B.13
B.13
B.13
B.8
B.2
By reference number
405566
405567
405568
405569
405570
405571
405572
405573
405574
405575
405576
405578
405579
405580
405581
405582
405584
405586
405588
405590
405592
405594
405596
405598
405600
405601
405602
405603
405604
405605
405606
405607
405609
405610
405611
405612
405613
405621
405621
405622
405624
405626
405628
405630
405632
405634
405636
405638
405640
405642
405644
405646
405648
405650
405652
405656
405657
405658
405659
405660
405661
405662
405663
405664
405665
405680
405681
405682
405683
405684
405685
405686
405687
405688
405689
405690
405703
405704
405705
405706
405707
405708
405709
405710
405712
405713
405714
405715
A
B
C
X
X.3
M-PACT Plus
Numerical index
Ref. no.
A
B
C
X
X.4
406022
406023
406024
406025
406026
406027
406028
406032
406033
406034
406035
406036
406037
406038
406039
406040
406042
406044
406045
406046
406047
406048
406049
406050
406051
406052
406054
406055
406056
406057
406058
406094
406096
406098
406102
406103
406104
406105
406108
406109
406110
406111
406112
406114
406116
406118
406120
406122
406124
406126
406128
406130
406132
406134
406136
406138
406140
406142
406144
406146
406148
406150
406152
406154
406156
406158
406160
406162
406164
406166
406168
406170
406172
406174
406176
406177
406178
406179
406180
406181
406182
406183
406184
406185
406186
406187
406188
406189
Cat. no.
FA41WS16B
FA31WS25B
FA41WS25B
FA32WS32B
FA42WS32B
FA32WS40B
FA42WS40B
MN4R2W25-A
FA31FS16B
FA41FS16B
FA31FS25B
FA41FS25B
FA32FS32B
FA42FS32B
FA32FS40B
FA42FS40B
MN4R2W32-A
MN4R2W40-A
FA31WN16B
FA41WN16B
FA31WN25B
FA41WN25B
FA32WN32B
FA42WN32B
FA32WN40B
FA42WN40B
MN4R1F04-A
MPRO30L-ENG
MPRO30H-ENG
MPRO30HR
MPRO30LR
MN4R1F06-A
MN4R1F08-A
MN4R1F10-A
MPRO30L-FRFNR
MPRO30H-FRFNR
MPRO40L-FRFNR
MPRO40H-FRFNR
MPRO30L-ENGNR
MPRO30H-ENGNR
MPRO40L-ENGNR
MPRO40H-ENGNR
TRIPCS
MN4R1F12-A
MN4R1F16-A
MN4R1F20-A
MN4R1F25-A
MN4R2F20-A
MN4R2F25-A
MN4R2F32-A
MN4R2F40-A
MH4R2W08-A
MH4R2W12-A
MH4R2W10-A
MH4R2W16-A
MH4R2W20-A
MH4R2W25-A
MH4R2W32-A
MH4R2W40-A
MH4R2F08-A
MH4R2F10-A
MH4R2F12-A
MH4R2F16-A
MH4R2F20-A
MH4R2F25-A
MH4R2F32-A
MH4R2F40-A
MS4R1M04-A
MS4R1M06-A
MS4R1M08-A
MS4R1M10-A
MS4R1M12-A
MS4R1M16-A
MS4R1M20-A
MS4R1M25-A
MS31W04-A
MS4L1W04-A
MS31W06-A
MS4L1W06-A
MS31W08-A
MS4L1W08-A
MS31W10-A
MS4L1W10-A
MS31W12-A
MS4L1W12-A
MS31W16-A
MS4L1W16-A
MS31W20-A
Page
Ref. no.
B.2
B.2
B.2
B.2
B.2
B.2
B.2
B.8
B.3
B.3
B.3
B.3
B.3
B.3
B.3
B.3
B.8
B.8
B.6
B.6
B.6
B.6
B.6
B.6
B.6
B.6
B.8
B.15
B.15
B.15
B.15
B.8
B.8
B.8
B.15
B.15
B.15
B.15
B.15
B.15
B.15
B.15
B.16
B.8
B.8
B.8
B.8
B.8
B.8
B.8
B.8
B.12
B.12
B.12
B.12
B.12
B.12
B.12
B.12
B.12
B.12
B.12
B.12
B.12
B.12
B.12
B.12
B.5
B.5
B.5
B.5
B.5
B.5
B.5
B.5
B.4
B.4
B.4
B.4
B.4
B.4
B.4
B.4
B.4
B.4
B.4
B.4
B.4
406190
406191
406192
406193
406194
406195
406196
406197
406198
406199
406200
406208
406214
406216
406218
406220
406222
406224
406226
406228
406230
406232
406234
406236
406238
406240
406242
406244
406246
406248
406250
406252
406254
406256
406258
406260
406262
406264
406266
406268
406270
406272
406274
406276
406278
406280
406282
406322
406326
406335
406336
406337
406338
406339
406340
406341
406342
406343
406348
406349
406350
406351
406356
406357
406358
406359
406364
406365
406366
406367
406372
406373
406374
406375
406376
406377
406378
406393
406700
406702
406703
406707
406708
406709
406710
406712
406714
406717
Cat. no.
MS4L1W20-A
MS31W25-A
MS4L1W25-A
MS32W20-A
MS4L2W20-A
MS32W25-A
MS4L2W25-A
MS32W32-A
MS4L2W32-A
MS32W40-A
MS4L2W40-A
MS4R2M20-A
MS4R2M25-A
MS4R2M32-A
MS4R2M40-A
MN4R1M04-A
MN4R1M06-A
MN4R1M08-A
MN4R1M10-A
MN4R1M12-A
MN4R1M16-A
MN4R1M20-A
MN4R1M25-A
MN4R2M20-A
MN4R2M25-A
MN4R2M32-A
MN4R2M40-A
MH4R2M08-A
MH4R2M10-A
MH4R2M12-A
MH4R2M16-A
MH4R2M20-A
MH4R2M25-A
MH4R2M32-A
MH4R2M40-A
MS4R1W04-A
MS4R1W06-A
MS4R1W08-A
MS4R1W10-A
MS4R1W12-A
MS4R1W16-A
MS4R1W20-A
MS4R1W25-A
MS4R2W20-A
MS4R2W25-A
MS4R2W32-A
MS4R2W40-A
UVTD48
UVTD130
RONLKEY
RONCASLD
RONCASNK
RONWKEY
RONWKEYFF
2WCI3PF
2WCI4PF
2WCI3PW
2WCI4PW
B13WCI3PF
B13WCI4PF
B13WCI3PW
B13WCI4PW
C23WCI3PF
C23WCI4PF
C23WCI3PW
C23WCI4PW
D13WCI3PF
D13WCI4PF
D13WCI3PW
D13WCI4PW
MPRACKHAN
MC33W50
MC33W63
MC33F50
F3ST24D
F3ST48D
F3ST60D
F3ST110D
F3ST220D
F3ST110A
F3ST240A
Page
Ref. no.
Cat. no.
Page
B.4
B.4
B.4
B.4
B.4
B.4
B.4
B.4
B.4
B.4
B.4
B.5
B.5
B.5
B.5
B.9
B.9
B.9
B.9
B.9
B.9
B.9
B.9
B.9
B.9
B.9
B.9
B.13
B.13
B.13
B.13
B.13
B.13
B.13
B.13
B.4
B.4
B.4
B.4
B.4
B.4
B.4
B.4
B.4
B.4
B.4
B.4
B.16
B.16
B.19
B.19
B.19
B.19
B.19
B.18
B.18
B.18
B.18
B.18
B.18
B.18
B.18
B.18
B.18
B.18
B.18
B.18
B.18
B.18
B.18
B.15
B.15
B.15
B.15
B.15
B.15
B.15
B.19
B.14
B.14
B.14
B.17
B.17
B.17
B.17
B.17
B.17
B.17
406723
406724
406725
406726
406727
406729
406730
406731
406732
406733
406734
406735
406737
406741
406743
406744
406745
406746
406748
406749
406750
406751
406752
406753
406754
406755
406756
406757
406758
406760
406762
406767
406768
406769
406770
406771
406772
406774
406775
406776
406777
406879
406889
406890
406898
406899
406900
406910
406911
406966
406967
406968
406969
406970
406971
406972
406973
F3CC24D
F3CC48D
F3CC60D
F3CC110A
F3CC110D
F3CC220D
F3CC120A
F3CC240A
F3UV24D
F3UV48D
F3UV60D
F3UV110
F3UV220
F3UV240A
F3CSW22
F3CSW44
F3CSW66
F3CSW88
F3MSRTC
F3MSDCS
F3MOP24D
F3MOP48D
F3MOP60D
F3MOP110A
F3MOP110D
F3MOP220A
F3MOP230A
F3MOP220D
F3MOP240A
MICWDF33P
MICFXF33P
CASF3FF
RONF3FF
CASF3LD
RONF3LD
F3MOC
F3ACK
F3MCS50
F3MCS63
F3ARC
MPROMACNC
MPRO17plusF3
MPRO18plusF3-ENG
MPRO18plusF3-FR
MC33W50 - A
MC33W63 - A
MC33F50 - A
MPROPLUSNTL100
MPROPLUSNTL50
D13WCI3PWCON
D13WCI4PWCON
D13WCI3PFCON
D13WCI4PFCON
D13WCIF23PWCON
D13WCIF24PWCON
D13WCIF23PFCON
D13WCIF24PFCON
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.18
B.18
B.19
B.19
B.19
B.19
B.19
B.20
B.20
B.20
B.20
B.15
B.15
B.15
B.15
B.14
B.14
B.14
B.15
B.15
B.18
B.18
B.18
B.18
B.18
B.18
B.18
B.18
M-PACT Plus
Cat. no.
Ref. no. Page
405531 B.18
405532 B.18
405533
405610
406340
406342
406341
406343
405463
405459
405465
405461
405451
B.18
B.18
B.18
B.18
B.18
B.18
B.18
B.18
B.18
B.18
B.16
405611 B.18
405612 B.18
405613 B.18
405607
405605
405505
405787
405790
405788
405791
405789
405792
B.19
B.19
B.19
B.20
B.20
B.20
B.20
B.20
B.20
406348
406350
406349
406351
405479
405475
405481
405477
B.18
B.18
B.18
B.18
B.18
B.18
B.18
B.18
406356
406358
406357
406359
405495
405491
405497
405493
406767
406769
405570
405426
405428
405420
405422
405771
405772
405773
405770
405580
405581
B.18
B.18
B.18
B.18
B.18
B.18
B.18
B.18
B.19
B.19
B.19
B.16
B.16
B.16
B.16
B.20
B.20
B.20
B.20
B.16
B.16
406364
406968
406366
406966
406365
406969
406367
406967
405515
406972
405511
406970
405517
406973
405513
406971
405578
405579
B.18
B.18
B.18
B.18
B.18
B.18
B.18
B.18
B.18
B.18
B.18
B.18
B.18
B.18
B.18
B.18
B.19
B.19
405661
405663
405660
405662
405665
405664
405684
B.3
B.3
B.3
B.3
B.3
B.3
B.20
Cat. no.
ELCT10002
ELCT12501
ELCT12502
ELCT16001
ELCT16002
ELCT20001
ELCT20002
ELCT25001
ELCT25002
ELCT32002
ELCT40002
ELCT8001
ELCT8002
F…
F3ACK
F3ARC
F3CC110A
F3CC110D
F3CC120A
F3CC220D
F3CC240A
F3CC24D
F3CC48D
F3CC60D
F3CSW22
F3CSW44
F3CSW66
F3CSW88
F3MCS50
F3MCS63
F3MOC
F3MOP110A
F3MOP110D
F3MOP220A
F3MOP220D
F3MOP230A
F3MOP240A
F3MOP24D
F3MOP48D
F3MOP60D
F3MSDCS
F3MSRTC
F3ST110A
F3ST110D
F3ST220D
F3ST240A
F3ST24D
F3ST48D
F3ST60D
F3UV110
F3UV220
F3UV240A
F3UV24D
F3UV48D
F3UV60D
FA31FN16B
FA31FN16T
FA31FN25B
FA31FN25T
FA31FS16B
FA31FS16T
FA31FS25B
FA31FS25T
FA31WN16B
FA31WN16T
FA31WN25B
FA31WN25T
FA31WS16B
FA31WS16T
FA31WS25B
FA31WS25T
FA32FH32B
FA32FH32T
FA32FH40B
FA32FH40T
FA32FN32B
FA32FN32T
FA32FN40B
FA32FN40T
FA32FS32B
FA32FS32T
FA32FS40B
FA32FS40T
FA32WH32B
FA32WH32T
FA32WH40B
FA32WH40T
FA32WN32B
Ref. no. Page
405714
405685
405715
405686
405716
405687
405717
405688
405718
405689
405690
405683
405713
B.20
B.20
B.20
B.20
B.20
B.20
B.20
B.20
B.20
B.20
B.20
B.20
B.20
406772
406776
406726
406727
406730
406729
406731
406723
406724
406725
406743
406744
406745
406746
406774
406775
406771
406753
406754
406755
406757
406756
406758
406750
406751
406752
406749
406748
406714
406710
406712
406717
406707
406708
406709
406735
406737
406741
406732
406733
406734
405557
405957
405559
405959
406033
405933
406035
405935
406045
405945
406047
405947
406021
405921
406023
405923
405565
405985
405567
405987
405561
405961
405563
405963
406037
405937
406039
405939
405553
405973
405555
405975
406049
B.20
B.20
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.20
B.20
B.19
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.17
B.7
B.7
B.7
B.7
B.3
B.3
B.3
B.3
B.6
B.6
B.6
B.6
B.2
B.2
B.2
B.2
B.10
B.10
B.10
B.10
B.7
B.7
B.7
B.7
B.3
B.3
B.3
B.3
B.10
B.10
B.10
B.10
B.6
Cat. no.
FA32WN32T
FA32WN40B
FA32WN40T
FA32WS32B
FA32WS32T
FA32WS40B
FA32WS40T
FA41FN16B
FA41FN16T
FA41FN25B
FA41FN25T
FA41FS16B
FA41FS16T
FA41FS25B
FA41FS25T
FA41WN16B
FA41WN16T
FA41WN25B
FA41WN25T
FA41WS16B
FA41WS16T
FA41WS25B
FA41WS25T
FA42FH32B
FA42FH32T
FA42FH40B
FA42FH40T
FA42FN32B
FA42FN32T
FA42FN40B
FA42FN40T
FA42FS32B
FA42FS32T
FA42FS40B
FA42FS40T
FA42WH32B
FA42WH32T
FA42WH40B
FA42WH40T
FA42WN32B
FA42WN32T
FA42WN40B
FA42WN40T
FA42WS32B
FA42WS32T
FA42WS40B
FA42WS40T
FAC125
FAC232
FAC240
FACN116
FACS116
FORLOK
I…
IP54DOOR
M…
MAC125
MAC232
MAC240
MACN116
MACS116
MC33F50
MC33F50 - A
MC33W50
MC33W50 - A
MC33W63
MC33W63 - A
MH32C32
MH32C40
MH32F08
MH32F08-A
MH32F10
MH32F10-A
MH32F12
MH32F12-A
MH32F16
MH32F16-A
MH32F20
MH32F20-A
MH32F25
MH32F25-A
MH32F32
MH32F32-A
MH32F40
MH32F40-A
MH32M08
MH32M08-A
MH32M10
Ref. no. Page
405949
406051
405951
406025
405925
406027
405927
405558
405958
405560
405960
406034
405934
406036
405936
406046
405946
406048
405948
406022
405922
406024
405924
405566
405986
405568
405988
405562
405962
405564
405964
406038
405938
406040
405940
405554
405974
405556
405976
406050
405950
406052
405952
406026
405926
406028
405928
405742
405744
405746
405740
405738
405569
B.6
B.6
B.6
B.2
B.2
B.2
B.2
B.7
B.7
B.7
B.7
B.3
B.3
B.3
B.3
B.6
B.6
B.6
B.6
B.2
B.2
B.2
B.2
B.10
B.10
B.10
B.10
B.7
B.7
B.7
B.7
B.3
B.3
B.3
B.3
B.10
B.10
B.10
B.10
B.6
B.6
B.6
B.6
B.2
B.2
B.2
B.2
B.20
B.20
B.20
B.20
B.20
B.19
405606 B.19
405743
405745
405747
405741
405739
406703
406900
406700
406898
406702
406899
405357
405359
405257
405881
405259
405889
405261
405891
405263
405893
405265
405895
405267
405897
405273
405899
405275
405901
405867
405997
405869
B.20
B.20
B.20
B.20
B.20
B.14
B.14
B.14
B.14
B.14
B.14
B.11
B.11
B.10
B.12
B.10
B.12
B.10
B.12
B.10
B.12
B.10
B.12
B.10
B.12
B.10
B.12
B.10
B.12
B.11
B.13
B.11
Cat. no.
MH32M10-A
MH32M12
MH32M12-A
MH32M16
MH32M16-A
MH32M20
MH32M20-A
MH32M25
MH32M25-A
MH32M32
MH32M32-A
MH32M40
MH32M40-A
MH32W08
MH32W08-A
MH32W10
MH32W10-A
MH32W12
MH32W12-A
MH32W16
MH32W16-A
MH32W20
MH32W20-A
MH32W25
MH32W25-A
MH32W32
MH32W32-A
MH32W40
MH32W40-A
MH42C32
MH42C40
MH4L2F08
MH4L2F08-A
MH4L2F10
MH4L2F10-A
MH4L2F12
MH4L2F12-A
MH4L2F16
MH4L2F16-A
MH4L2F20
MH4L2F20-A
MH4L2F25
MH4L2F25-A
MH4L2F32
MH4L2F32-A
MH4L2F40
MH4L2F40-A
MH4L2M08
MH4L2M08-A
MH4L2M10
MH4L2M10-A
MH4L2M12
MH4L2M12-A
MH4L2M16
MH4L2M16-A
MH4L2M20
MH4L2M20-A
MH4L2M25
MH4L2M25-A
MH4L2M32
MH4L2M32-A
MH4L2M40
MH4L2M40-A
MH4L2W08
MH4L2W08-A
MH4L2W10
MH4L2W10-A
MH4L2W12
MH4L2W12-A
MH4L2W16
MH4L2W16-A
MH4L2W20
MH4L2W20-A
MH4L2W25
MH4L2W25-A
MH4L2W32
MH4L2W32-A
MH4L2W40
MH4L2W40-A
MH4R2F08
MH4R2F08-A
MH4R2F10
MH4R2F10-A
MH4R2F12
MH4R2F12-A
MH4R2F16
MH4R2F16-A
MH4R2F20
Ref. no. Page
405999
405871
406001
405873
406003
405875
406005
405877
406007
405883
406009
405885
406011
405227
405797
405229
405799
405231
405801
405233
405829
405235
405831
405237
405859
405243
405861
405245
405863
405356
405358
405256
405880
405258
405888
405260
405890
405262
405892
405264
405894
405266
405896
405272
405898
405274
405900
405868
405998
405870
406000
405872
406002
405874
406004
405876
406006
405878
406008
405884
406010
405886
406012
405226
405796
405228
405802
405230
405798
405232
405828
405234
405830
405236
405858
405242
405860
405244
405862
405509
406146
405510
406148
405512
406150
405514
406152
405516
B.13
B.11
B.13
B.11
B.13
B.11
B.13
B.11
B.13
B.11
B.13
B.11
B.13
B.10
B.12
B.10
B.12
B.10
B.12
B.10
B.12
B.10
B.12
B.10
B.12
B.10
B.12
B.10
B.12
B.11
B.11
B.10
B.12
B.10
B.12
B.10
B.12
B.10
B.12
B.10
B.12
B.10
B.12
B.10
B.12
B.10
B.12
B.11
B.13
B.11
B.13
B.11
B.13
B.11
B.13
B.11
B.13
B.11
B.13
B.11
B.13
B.11
B.13
B.10
B.12
B.10
B.12
B.10
B.12
B.10
B.12
B.10
B.12
B.10
B.12
B.10
B.12
B.10
B.12
B.10
B.12
B.10
B.12
B.10
B.12
B.10
B.12
B.10
By catalogue number
1…
100BCMCI
160BCMCI
2…
200BCMCI
250BCMCI
2WCI3PF
2WCI3PW
2WCI4PF
2WCI4PW
2WCIF23PF
2WCIF23PW
2WCIF24PF
2WCIF24PW
2WPFC
3…
300BCMCI
350BCMCI
4…
400BCMCI
A…
ACBLIFT
ACBMID
ACBMIL
ARC16
ARC25
ARC32H
ARC32SN
ARC40H
ARC40SN
B…
B13WCI3PF
B13WCI3PW
B13WCI4PF
B13WCI4PW
B13WCIF23PF
B13WCIF23PW
B13WCIF24PF
B13WCIF24PW
C…
C23WCI3PF
C23WCI3PW
C23WCI4PF
C23WCI4PW
C23WCIF23PF
C23WCIF23PW
C23WCIF24PF
C23WCIF24PW
CASF3FF
CASF3LD
CASLOK
CC130
CC250
CC30
CC48
CLC125
CLC232
CLC240
CLCN116
CSWFF
CSWL
D…
D13WCI3PF
D13WCI3PFCON
D13WCI3PW
D13WCI3PWCON
D13WCI4PF
D13WCI4PFCON
D13WCI4PW
D13WCI4PWCON
D13WCIF23PF
D13WCIF23PFCON
D13WCIF23PW
D13WCIF23PWCON
D13WCIF24PF
D13WCIF24PFCON
D13WCIF24PW
D13WCIF24PWCON
DILHS
DIRHS
E…
EDF13P16
EDF13P25
EDF14P16
EDF14P25
EDF23P40
EDF24P40
ELCT10001
A
B
C
X
X.5
M-PACT Plus
Numerical index
Cat. no.
A
B
C
X
X.6
MH4R2F20-A
MH4R2F25
MH4R2F25-A
MH4R2F32
MH4R2F32-A
MH4R2F40
MH4R2F40-A
MH4R2M08
MH4R2M08-A
MH4R2M10
MH4R2M10-A
MH4R2M12
MH4R2M12-A
MH4R2M16
MH4R2M16-A
MH4R2M20
MH4R2M20-A
MH4R2M25
MH4R2M25-A
MH4R2M32
MH4R2M32-A
MH4R2M40
MH4R2M40-A
MH4R2W08
MH4R2W08-A
MH4R2W10
MH4R2W10-A
MH4R2W12
MH4R2W12-A
MH4R2W16
MH4R2W16-A
MH4R2W20
MH4R2W20-A
MH4R2W25
MH4R2W25-A
MH4R2W32
MH4R2W32-A
MH4R2W40
MH4R2W40-A
MICFXF33P
MICWDF33P
MN31C25
MN31F04
MN31F04-A
MN31F06
MN31F06-A
MN31F08
MN31F08-A
MN31F10
MN31F10-A
MN31F12
MN31F12-A
MN31F16
MN31F16-A
MN31F20
MN31F20-A
MN31F25
MN31F25-A
MN31M04
MN31M04-A
MN31M06
MN31M06-A
MN31M08
MN31M08-A
MN31M10
MN31M10-A
MN31M12
MN31M12-A
MN31M16
MN31M16-A
MN31M20
MN31M20-A
MN31M25
MN31M25-A
MN31W04
MN31W04-A
MN31W06
MN31W06-A
MN31W08
MN31W08-A
MN31W10
MN31W10-A
MN31W12
MN31W12-A
MN31W16
MN31W16-A
MN31W20
Ref. no. Page
406154
405518
406156
405520
406158
405522
406160
405638
406244
405640
406246
405642
406248
405644
406250
405646
406252
405648
406254
405650
406256
405652
406258
405494
406130
405496
406134
405498
406132
405500
406136
405502
406138
405504
406140
405506
406142
405508
406144
406762
406760
405345
405193
405657
405195
405659
405197
405681
405199
405721
405201
405731
405203
405733
405205
405735
405207
405737
405833
405953
405835
405955
405837
405965
405839
405967
405841
405969
405843
405971
405845
405977
405847
405979
405163
405351
405165
405353
405167
405361
405169
405363
405171
405412
405173
405415
405175
B.12
B.10
B.12
B.10
B.12
B.10
B.12
B.11
B.13
B.11
B.13
B.11
B.13
B.11
B.13
B.11
B.13
B.11
B.13
B.11
B.13
B.11
B.13
B.10
B.12
B.10
B.12
B.10
B.12
B.10
B.12
B.10
B.12
B.10
B.12
B.10
B.12
B.10
B.12
B.18
B.18
B.7
B.6
B.8
B.6
B.8
B.6
B.8
B.6
B.8
B.6
B.8
B.6
B.8
B.6
B.8
B.6
B.8
B.7
B.9
B.7
B.9
B.7
B.9
B.7
B.9
B.7
B.9
B.7
B.9
B.7
B.9
B.7
B.9
B.6
B.8
B.6
B.8
B.6
B.8
B.6
B.8
B.6
B.8
B.6
B.8
B.6
Cat. no.
MN31W20-A
MN31W25
MN31W25-A
MN32C32
MN32C40
MN32F20
MN32F20-A
MN32F25
MN32F25-A
MN32F32
MN32F32-A
MN32F40
MN32F40-A
MN32M20
MN32M20-A
MN32M25
MN32M25-A
MN32M32
MN32M32-A
MN32M40
MN32M40-A
MN32W20
MN32W20-A
MN32W25
MN32W25-A
MN32W32
MN32W32-A
MN32W40
MN32W40-A
MN41C25
MN42C32
MN42C40
MN4L1F04
MN4L1F04-A
MN4L1F06
MN4L1F06-A
MN4L1F08
MN4L1F08-A
MN4L1F10
MN4L1F10-A
MN4L1F12
MN4L1F12-A
MN4L1F16
MN4L1F16-A
MN4L1F20
MN4L1F20-A
MN4L1F25
MN4L1F25-A
MN4L1M04
MN4L1M04-A
MN4L1M06
MN4L1M06-A
MN4L1M08
MN4L1M08-A
MN4L1M10
MN4L1M10-A
MN4L1M12
MN4L1M12-A
MN4L1M16
MN4L1M16-A
MN4L1M20
MN4L1M20-A
MN4L1M25
MN4L1M25-A
MN4L1W04
MN4L1W04-A
MN4L1W06
MN4L1W06-A
MN4L1W08
MN4L1W08-A
MN4L1W10
MN4L1W10-A
MN4L1W12
MN4L1W12-A
MN4L1W16
MN4L1W16-A
MN4L1W20
MN4L1W20-A
MN4L1W25
MN4L1W25-A
MN4L2F20
MN4L2F20-A
MN4L2F25
MN4L2F25-A
MN4L2F32
MN4L2F32-A
MN4L2F40
Ref. no. Page
405417
405177
405419
405347
405349
405209
405779
405211
405781
405213
405783
405215
405785
405849
405981
405851
405983
405853
405989
405855
405991
405179
405425
405181
405445
405183
405453
405185
405455
405344
405346
405348
405192
405656
405194
405658
405196
405680
405198
405720
405200
405730
405202
405732
405204
405734
405206
405736
405834
405954
405836
405956
405838
405966
405840
405968
405842
405970
405844
405972
405846
405978
405848
405980
405162
405350
405164
405352
405166
405360
405168
405362
405170
405410
405172
405414
405174
405416
405176
405418
405208
405778
405210
405780
405212
405782
405214
B.8
B.6
B.8
B.7
B.7
B.6
B.8
B.6
B.8
B.6
B.8
B.6
B.8
B.7
B.9
B.7
B.9
B.7
B.9
B.7
B.9
B.6
B.8
B.6
B.8
B.6
B.8
B.6
B.8
B.7
B.7
B.7
B.6
B.8
B.6
B.8
B.6
B.8
B.6
B.8
B.6
B.8
B.6
B.8
B.6
B.8
B.6
B.8
B.7
B.9
B.7
B.9
B.7
B.9
B.7
B.9
B.7
B.9
B.7
B.9
B.7
B.9
B.7
B.9
B.6
B.8
B.6
B.8
B.6
B.8
B.6
B.8
B.6
B.8
B.6
B.8
B.6
B.8
B.6
B.8
B.6
B.8
B.6
B.8
B.6
B.8
B.6
Cat. no.
MN4L2F40-A
MN4L2M20
MN4L2M20-A
MN4L2M25
MN4L2M25-A
MN4L2M32
MN4L2M32-A
MN4L2M40
MN4L2M40-A
MN4L2W20
MN4L2W20-A
MN4L2W25
MN4L2W25-A
MN4L2W32
MN4L2W32-A
MN4L2W40
MN4L2W40-A
MN4R1F04
MN4R1F04-A
MN4R1F06
MN4R1F06-A
MN4R1F08
MN4R1F08-A
MN4R1F10
MN4R1F10-A
MN4R1F12
MN4R1F12-A
MN4R1F16
MN4R1F16-A
MN4R1F20
MN4R1F20-A
MN4R1F25
MN4R1F25-A
MN4R1M04
MN4R1M04-A
MN4R1M06
MN4R1M06-A
MN4R1M08
MN4R1M08-A
MN4R1M10
MN4R1M10-A
MN4R1M12
MN4R1M12-A
MN4R1M16
MN4R1M16-A
MN4R1M20
MN4R1M20-A
MN4R1M25
MN4R1M25-A
MN4R1W04
MN4R1W04-A
MN4R1W06
MN4R1W06-A
MN4R1W08
MN4R1W08-A
MN4R1W10
MN4R1W10-A
MN4R1W12
MN4R1W12-A
MN4R1W16
MN4R1W16-A
MN4R1W20
MN4R1W20-A
MN4R1W25
MN4R1W25-A
MN4R2F20
MN4R2F20-A
MN4R2F25
MN4R2F25-A
MN4R2F32
MN4R2F32-A
MN4R2F40
MN4R2F40-A
MN4R2M20
MN4R2M20-A
MN4R2M25
MN4R2M25-A
MN4R2M32
MN4R2M32-A
MN4R2M40
MN4R2M40-A
MN4R2W20
MN4R2W20-A
MN4R2W25
MN4R2W25-A
MN4R2W32
MN4R2W32-A
Ref. no. Page
405784
405850
405982
405852
405984
405854
405990
405856
405992
405178
405424
405180
405444
405182
405452
405184
405454
405470
406054
405472
406094
405474
406096
405476
406098
405478
406114
405480
406116
405482
406118
405484
406120
405596
406220
405598
406222
405602
406224
405604
406226
405622
406228
405624
406230
405626
406232
405628
406234
405430
405832
405432
405864
405434
405866
405436
405882
405438
405902
405456
405904
405458
405994
405460
405996
405486
406122
405488
406124
405490
406126
405492
406128
405630
406236
405632
406238
405634
406240
405636
406242
405462
406020
405464
406032
405466
406042
B.8
B.7
B.9
B.7
B.9
B.7
B.9
B.7
B.9
B.6
B.8
B.6
B.8
B.6
B.8
B.6
B.8
B.6
B.8
B.6
B.8
B.6
B.8
B.6
B.8
B.6
B.8
B.6
B.8
B.6
B.8
B.6
B.8
B.7
B.9
B.7
B.9
B.7
B.9
B.7
B.9
B.7
B.9
B.7
B.9
B.7
B.9
B.7
B.9
B.6
B.8
B.6
B.8
B.6
B.8
B.6
B.8
B.6
B.8
B.6
B.8
B.6
B.8
B.6
B.8
B.6
B.8
B.6
B.8
B.6
B.8
B.6
B.8
B.7
B.9
B.7
B.9
B.7
B.9
B.7
B.9
B.6
B.8
B.6
B.8
B.6
B.8
Cat. no.
MN4R2W40
MN4R2W40-A
MOC
MOP130A
MOP130D
MOP250A
MOP30
MOP48
MPRACKHAN
MPRO17plusF1&2
MPRO17plusF3
MPRO18 plusF1&2
MPRO18plusF3-ENG
MPRO18plusF3-FR
MPRO18plusF3-G
MPRO30H-ENG
MPRO30H-ENGNR
MPRO30H-FRF
MPRO30H-FRFNR
MPRO30HR
MPRO30L-ENG
MPRO30L-ENGNR
MPRO30L-FRF
MPRO30L-FRFNR
MPRO30LR
MPRO40H-ENG
MPRO40H-ENGNR
MPRO40H-FRF
MPRO40H-FRFNR
MPRO40L-ENG
MPRO40L-ENGNR
MPRO40L-FRF
MPRO40L-FRFNR
MPROAPU
MPROCOM
MPROMAC
MPROMACNC
MPRONTSW
MPROPLUSNTL100
MPROPLUSNTL50
MPROPLUSTU-EURO
MPROPlusUEF
MPROPLUSUEF3P3W
MPROPPB
MPROPTU
MPROPTU17
MPROPTU-EURO
MPROREF
MPROSEF
MS31C16
MS31C25
MS31F04
MS31F04-A
MS31F06
MS31F06-A
MS31F08
MS31F08-A
MS31F10
MS31F10-A
MS31F12
MS31F12-A
MS31F16
MS31F16-A
MS31F20
MS31F20-A
MS31F25
MS31F25-A
MS31M04
MS31M04-A
MS31M06
MS31M06-A
MS31M08
MS31M08-A
MS31M10
MS31M10-A
MS31M12
MS31M12-A
MS31M16
MS31M16-A
MS31M20
MS31M20-A
MS31M25
MS31M25-A
MS31W04
MS31W04-A
MS31W06
MS31W06-A
Ref. no. Page
405468
406044
405576
405446
405917
405448
405440
405442
406393
405327
406879
405329
406889
406890
406056
406109
405129
406103
406057
406055
406108
405128
406102
406058
405534
406111
405131
406105
405530
406110
405130
406104
405547
405545
405575
406777
405540
406910
406911
405222
405331
405535
405552
405551
405550
405223
405537
405538
405341
405343
405133
405217
405135
405219
405137
405239
405139
405241
405141
405247
405143
405249
405145
405251
405147
405253
405803
405905
405805
405907
405807
405909
405809
405911
405811
405913
405813
405915
405815
405995
405817
405919
405103
406177
405105
406179
B.6
B.8
B.19
B.16
B.16
B.16
B.16
B.16
B.19
B.15
B.15
B.15
B.15
B.15
B.15
B.15
B.15
B.15
B.15
B.15
B.15
B.15
B.15
B.15
B.15
B.15
B.15
B.15
B.15
B.15
B.15
B.15
B.15
B.15
B.15
B.15
B.15
B.15
B.15
B.15
B.15
B.15
B.15
B.15
B.15
B.15
B.15
B.15
B.15
B.3
B.3
B.2
B.4
B.2
B.4
B.2
B.4
B.2
B.4
B.2
B.4
B.2
B.4
B.2
B.4
B.2
B.4
B.3
B.5
B.3
B.5
B.3
B.5
B.3
B.5
B.3
B.5
B.3
B.5
B.3
B.5
B.3
B.5
B.2
B.4
B.2
B.4
M-PACT Plus
Cat. no.
Ref. no. Page
405107
406181
405109
406183
405111
406185
405113
406187
405115
406189
405117
406191
405355
405365
405149
405255
405151
405269
405153
405271
405155
405277
405819
405929
405821
405931
405823
405941
405825
405943
405119
406193
405121
406195
405123
406197
405125
406199
405340
405342
405354
405364
405132
405216
405134
405218
405136
405238
405138
405240
405140
405246
405142
405248
405144
405250
405146
405252
405804
405906
405806
405908
405808
405910
405810
405912
405812
405914
405814
405916
405816
405918
405818
405920
405102
406178
405104
406180
405106
406182
405108
406184
405110
406186
405112
406188
405114
B.2
B.4
B.2
B.4
B.2
B.4
B.2
B.4
B.2
B.4
B.2
B.4
B.3
B.3
B.2
B.4
B.2
B.4
B.2
B.4
B.2
B.4
B.3
B.5
B.3
B.5
B.3
B.5
B.3
B.5
B.2
B.4
B.2
B.4
B.2
B.4
B.2
B.4
B.3
B.3
B.3
B.3
B.2
B.4
B.2
B.4
B.2
B.4
B.2
B.4
B.2
B.4
B.2
B.4
B.2
B.4
B.2
B.4
B.3
B.5
B.3
B.5
B.3
B.5
B.3
B.5
B.3
B.5
B.3
B.5
B.3
B.5
B.3
B.5
B.2
B.4
B.2
B.4
B.2
B.4
B.2
B.4
B.2
B.4
B.2
B.4
B.2
Cat. no.
MS4L1W20-A
MS4L1W25
MS4L1W25-A
MS4L2F20
MS4L2F20-A
MS4L2F25
MS4L2F25-A
MS4L2F32
MS4L2F32-A
MS4L2F40
MS4L2F40-A
MS4L2M20
MS4L2M20-A
MS4L2M25
MS4L2M25-A
MS4L2M32
MS4L2M32-A
MS4L2M40
MS4L2M40-A
MS4L2W20
MS4L2W20-A
MS4L2W25
MS4L2W25-A
MS4L2W32
MS4L2W32-A
MS4L2W40
MS4L2W40-A
MS4R1F04
MS4R1F04-A
MS4R1F06
MS4R1F06-A
MS4R1F08
MS4R1F08-A
MS4R1F10
MS4R1F10-A
MS4R1F12
MS4R1F12-A
MS4R1F16
MS4R1F16-A
MS4R1F20
MS4R1F20-A
MS4R1F25
MS4R1F25-A
MS4R1M04
MS4R1M04-A
MS4R1M06
MS4R1M06-A
MS4R1M08
MS4R1M08-A
MS4R1M10
MS4R1M10-A
MS4R1M12
MS4R1M12-A
MS4R1M16
MS4R1M16-A
MS4R1M20
MS4R1M20-A
MS4R1M25
MS4R1M25-A
MS4R1W04
MS4R1W04-A
MS4R1W06
MS4R1W06-A
MS4R1W08
MS4R1W08-A
MS4R1W10
MS4R1W10-A
MS4R1W12
MS4R1W12-A
MS4R1W16
MS4R1W16-A
MS4R1W20
MS4R1W20-A
MS4R1W25
MS4R1W25-A
MS4R2F20
MS4R2F20-A
MS4R2F25
MS4R2F25-A
MS4R2F32
MS4R2F32-A
MS4R2F40
MS4R2F40-A
MS4R2M20
MS4R2M20-A
MS4R2M25
MS4R2M25-A
Ref. no. Page
406190
405116
406192
405148
405254
405150
405268
405152
405270
405154
405276
405820
405930
405822
405932
405824
405942
405826
405944
405118
406194
405120
406196
405122
406198
405124
406200
405366
405186
405368
405278
405370
405296
405372
405298
405374
405390
405376
405392
405378
405404
405381
405682
405524
406162
405526
406164
405528
406166
405542
406168
405548
406170
405582
406172
405584
406174
405586
406176
405316
406260
405318
406262
405320
406264
405322
406266
405324
406268
405326
406270
405328
406272
405330
406274
405384
405712
405387
405722
405391
405748
405393
405786
405588
406208
405590
406214
B.4
B.2
B.4
B.2
B.4
B.2
B.4
B.2
B.4
B.2
B.4
B.3
B.5
B.3
B.5
B.3
B.5
B.3
B.5
B.2
B.4
B.2
B.4
B.2
B.4
B.2
B.4
B.2
B.4
B.2
B.4
B.2
B.4
B.2
B.4
B.2
B.4
B.2
B.4
B.2
B.4
B.2
B.4
B.3
B.5
B.3
B.5
B.3
B.5
B.3
B.5
B.3
B.5
B.3
B.5
B.3
B.5
B.3
B.5
B.2
B.4
B.2
B.4
B.2
B.4
B.2
B.4
B.2
B.4
B.2
B.4
B.2
B.4
B.2
B.4
B.2
B.4
B.2
B.4
B.2
B.4
B.2
B.4
B.3
B.5
B.3
B.5
Cat. no.
MS4R2M32
MS4R2M32-A
MS4R2M40
MS4R2M40-A
MS4R2W20
MS4R2W20-A
MS4R2W25
MS4R2W25-A
MS4R2W32
MS4R2W32-A
MS4R2W40
MS4R2W40-A
P…
PAMM20
PAMM30/40
PROCAS
PROLOK
R…
RCMK10001
RCMK10002
RCMK12501
RCMK12502
RCMK16001
RCMK16002
RCMK20001
RCMK20002
RCMK25001
RCMK25002
RCMK32002
RCMK40002
RCMK8001
RCMK8002
RONCAS
RONCASLD
RONCASNK
RONF3FF
RONF3LD
RONLKEY
RONLOK
RONWKEY
RONWKEYFF
RT1HOR
RT1SNVFIX
RT1SVFIX
RT1UNI
RT1VER
RT2SNHVFIX
RT2UNI
S…
SCC
ST130
ST250
ST30
ST440
ST48
T…
TRIPCS
U…
UNIPLIER
UV130A
UV130D
UV250
UV30
UV440
UV48
UVTD130
UVTD250
UVTD440
UVTD48
Ref. no. Page
405592
406216
405594
406218
405332
406276
405334
406278
405336
406280
405338
406282
B.3
B.5
B.3
B.5
B.2
B.4
B.2
B.4
B.2
B.4
B.2
B.4
405297
405299
405574
405572
B.15
B.15
B.19
B.19
405704
405724
405705
405725
405706
405726
405707
405727
405708
405728
405709
405710
405703
405723
405573
406336
406337
406768
406770
406335
405571
406338
406339
403680
405609
405603
405600
403681
405621
405601
B.20
B.20
B.20
B.20
B.20
B.20
B.20
B.20
B.20
B.20
B.20
B.20
B.20
B.20
B.19
B.19
B.19
B.19
B.19
B.19
B.19
B.19
B.19
B.2
B.2
B.2
B.2
B.2
B.2
B.2
405450
405386
405388
405380
405389
405382
B.16
B.16
B.16
B.16
B.16
B.16
By catalogue number
MS31W08
MS31W08-A
MS31W10
MS31W10-A
MS31W12
MS31W12-A
MS31W16
MS31W16-A
MS31W20
MS31W20-A
MS31W25
MS31W25-A
MS32C32
MS32C40
MS32F20
MS32F20-A
MS32F25
MS32F25-A
MS32F32
MS32F32-A
MS32F40
MS32F40-A
MS32M20
MS32M20-A
MS32M25
MS32M25-A
MS32M32
MS32M32-A
MS32M40
MS32M40-A
MS32W20
MS32W20-A
MS32W25
MS32W25-A
MS32W32
MS32W32-A
MS32W40
MS32W40-A
MS41C16
MS41C25
MS42C32
MS42C40
MS4L1F04
MS4L1F04-A
MS4L1F06
MS4L1F06-A
MS4L1F08
MS4L1F08-A
MS4L1F10
MS4L1F10-A
MS4L1F12
MS4L1F12-A
MS4L1F16
MS4L1F16-A
MS4L1F20
MS4L1F20-A
MS4L1F25
MS4L1F25-A
MS4L1M04
MS4L1M04-A
MS4L1M06
MS4L1M06-A
MS4L1M08
MS4L1M08-A
MS4L1M10
MS4L1M10-A
MS4L1M12
MS4L1M12-A
MS4L1M16
MS4L1M16-A
MS4L1M20
MS4L1M20-A
MS4L1M25
MS4L1M25-A
MS4L1W04
MS4L1W04-A
MS4L1W06
MS4L1W06-A
MS4L1W08
MS4L1W08-A
MS4L1W10
MS4L1W10-A
MS4L1W12
MS4L1W12-A
MS4L1W16
MS4L1W16-A
MS4L1W20
A
B
C
X
406112 B.16
405800
405406
405407
405408
405400
405409
405402
406326
405411
405413
406322
B.20
B.16
B.16
B.16
B.16
B.16
B.16
B.16
B.16
B.16
B.16
The policy of GE Consumer &
Industrial is one of continuous
improvement.
The right is reserved to alter the
design or any structural details of
the products at any time without
giving notice.
April 2006
GE Consumer & Industrial
X.7
37420
GE Consumer & Industrial
Power Protection
GE Consumer & Industrial
The Power Protection division (formerly
GE Power Controls) of GE Consumer & Industrial
is a first class European supplier of low-voltage
products including wiring devices, residential
and industrial electrical distribution
components, automation products, enclosures
and switchboards. Demand for the company’s
products comes from wholesalers, installers,
panel-board builders, contractors, OEMs
and utilities worldwide
GE Consumer & Industrial
Power Protection
www.ge.com/eu/powerprotection
www.gepowercontrols.com
M-PACT Plus - Air Circuit Breakers
ED.02
GE POWER CONTROLS
International Sales
Nieuwevaart 51
B-9000 Gent - Belgium
Tel.
+32/9 265 21 11
Fax
+32/9 265 28 90
E-mail: gepcbel@gepc.ge.com
M-PACT Plus
Air Circuit Breakers
400 - 6300A
GE POWER CONTROLS Ltd
Lincoln Road
Enfield
Middlesex EN1 1SB
United Kingdom
Tel.
0800 587 1251
Fax
0800 587 1239
E-mail: gepcuk@gepc.ge.com
GE imagination at work
GE imagination at work
680809
Ref. I/3197/E/EX 5.0 Ed. 04/06
© Copyright GE Power Controls 2006
ED.02