4074EJM Resistor Kit FOR ECONOMIZER LOGIC MODULES INSTALLATION INSTRUCTIONS APPLICATION This resistor kit provides the necessary resistors for proper checkout of Honeywell ECONOMIZER Logic Modules. It also has resistors for wiring a Honeywell Series 90 actuator to a W7210 or W7215 Logic Module. Refer to Table 1 for details on kit contents. Table 1. 4074EJM Contents. Item Comments For checkout of W7459, W6210/W7210, W6215/W7215/W7460 Jumper assembly — Resistor assemblies 620 ohm (white) 1.2K ohm (purple) 5.6K ohm (blue) 6.8K ohm (amber) For wiring Honeywell Series 90 Actuators to W7210/W7215 instead of Q7230. See Fig. 1. Resistors 536 ohm 665 ohm 3480 ohm INSTALLATION CAUTION Electrical Shock or Equipment Damage Hazard. Can shock individuals or short equipment circuitry. Disconnect all power supplies before installation. When Installing this Product... 1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition. 2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application. 3. Installer must be a trained, experienced service technician. 4. After installation is complete, check out product operation as provided in these instructions. ®U.S. Registered Trademark Copyright © 1998 Honeywell Inc. • All Rights Reserved WIRING When using a Honeywell Series 90 actuator with a W7210/ W7215 Logic Module, wire the devices either: 1. With a Q7230 Interface Module; see details in form 63-2235. 2. With the resistors in this kit; see Fig. 1. X-XX UL 62-0151 4074EJM RESISTOR KIT W7215A 24 VAC HOT TR TR1 HONEYWELL SERIES 90 ACTUATOR 24 VAC COM (ML9175, ML9185, M9175, M9185) 3480 Ohms + W 2-10V OUT 536 Ohms R 1 – B 665 Ohms 1 USE 1/2 WATT, 1% RESISTORS OF SPECIFIED OHM RATINGS (INCLUDED IN 4074EJM RESISTOR KIT). FOR MOD IV MOTORS, THE Q7230 MODULE CAN REPLACE THE RESISTORS. M11903 Fig. 1. W7215A used with Honeywell Series 90 Actuator. CHECKOUT Refer to the Logic Module Product Data instructions for detailed checkout procedures. By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys’ fees, arising out of, or resulting from, any modification to the literature by you. Home and Building Control Honeywell Inc. Honeywell Plaza P.O. Box 524 Minneapolis, MN 55408-0524 62-0151 B.B. 4-98 Printed in Mexico Home and Building Control Honeywell Limited-Honeywell Limitée 155 Gordon Baker Road North York, Ontario M2H 3N7 2 www.honeywell.com