Experimental Thermal and Fluid Science 29 (2005) 511–521 www.elsevier.com/locate/etfs A study of the heat transfer characteristics of a compact spiral coil heat exchanger under wet-surface conditions Paisarn Naphon, Somchai Wongwises * Fluid Mechanics, Thermal Engineering and Multiphase Flow Research Lab. (FUTURE), Department of Mechanical Engineering, King MongkutÕs University of Technology Thonburi, Bangmod, Bangkok 10140, Thailand Received 5 March 2004; accepted 16 July 2004 Abstract The heat transfer characteristics and the performance of a spiral coil heat exchanger under cooling and dehumidifying conditions are investigated. The heat exchanger consists of a steel shell and a spirally coiled tube unit. The spiral-coil unit consists of six layers of concentric spirally coiled tubes. Each tube is fabricated by bending a 9.27 mm diameter straight copper tube into a spiral-coil of five turns. Air and water are used as working fluids. The chilled water entering the outermost turn flows along the spirally coiled tube, and flows out at the innermost turn. The hot air enters the heat exchanger at the center of the shell and flows radially across spiral tubes to the periphery. A mathematical model based on mass and energy conservation is developed and solved by using the Newton–Raphson iterative method to determine the heat transfer characteristics. The results obtained from the model are in reasonable agreement with the present experimental data. The effects of various inlet conditions of working fluids flowing through the spiral coil heat exchanger are discussed. 2004 Elsevier Inc. All rights reserved. Keywords: Heat transfer characteristic; Spiral coil heat exchanger; Enthalpy effectiveness; Humidity effectiveness 1. Introduction Due to the curvature of the tube, a centrifugal force is generated as fluid flows through the curved tubes. Secondary flows induced by the centrifugal force has significant ability to enhance the heat transfer rate. Helical and spiral coils are known types of curved tubes which have been used in a wide variety of applications for example, heat recovery processes, air conditioning and refrigeration systems, chemical reactors, food and dairy processes. Heat transfer and flow characteristics in curved tubes have been widely studied by researchers both experimentally and theoretically. Garimella et al. [1] presented average heat transfer coefficients of lami- * Corresponding author. Tel.: +662 470 9115; fax: +662 470 9111. E-mail address: somchai.won@kmutt.ac.th (S. Wongwises). 0894-1777/$ - see front matter 2004 Elsevier Inc. All rights reserved. doi:10.1016/j.expthermflusci.2004.07.002 nar and transition flows for forced convection heat transfer in coiled annular ducts. Prabhanjan et al. [2] compared the heat transfer rates between a helically coiled heat exchanger and a straight tube heat exchanger. Due to complexity of the heat transfer processes in the curved tubes, experimental studies are very difficult to handle. Numerical investigations are needed. Bolinder and Sunden [3] solved the parabolized Navier–Stokes and energy equations by using a finitevolume method. The steady, fully developed laminar forced convective heat transfer in helical square ducts for various Dean and Prandtl numbers were analyzed. Zheng et al. [4] applied a control-volume finite difference method with second-order accuracy for solving the three-dimensional governing equations to analyze the laminar force convection and thermal radiation in a participating medium inside a helical pipe. Acharya et al. [5] numerically studied the phenomenon of steady heat 512 P. Naphon, S. Wongwises / Experimental Thermal and Fluid Science 29 (2005) 511–521 Nomenclature A D Eh Gmax h hr i J k M n Pr r Rc Rn T U a Cp De Ew hD ifg j area tube diameter, m enthalpy effectiveness mass flux based on minimum free flow area, kg/m2s heat transfer coefficient, W/m2 C combined conductance through tube surface and water inside tube, W/m2 C enthalpy, kJ/kg Colburn j factor thermal conductivity, W/m C mass flow rate per coil, kg/s number of coil turns Prandtl number tube radius, m coil characteristics, kg C/kJ average radius of curvature of each coil turn, m temperature, C overall heat transfer coefficient, W/m2 C radius change per radian, m/radian specific heat, kJ/(kg C) Dean number humidity effectiveness mass transfer coefficient, kg/m2s enthalpy of condensation, kJ/kg number of segments transfer enhancement in coiled-tube heat exchangers due to chaotic particle paths in steady, laminar flow with two different mixings. The velocity vectors and temperature fields were discussed. Lin and Ebadian [6] applied the standard k–e model to investigate three-dimensional turbulent developing convective heat transfer in helical pipes with finite pitches. The effects of pitch, curvature ratio and Reynolds number on the development of effective thermal conductivity and temperature fields, and local and average Nusselt numbers were discussed. Sillekens et al. [7] employed the finite difference discretization to solve the parabolized Navier–Stokes and energy equations. The effect of buoyancy forces on heat transfer and secondary flow was considered. In their second paper, Rindt et al. [8] studied the development of mixed convective flow with an axial varying wall temperature. The results were compared with the constant wall temperature boundary conditions. Lemenand and Peerhossaini [9] simplified the Navier–Stokes and energy equations as a thermal model to predict heat transfer rates in a twisted pipe of two tube configurations, helically coiled or chaotic. Compared to the numerous investigations in the helically coiled tubes, there are few researches on the heat Le m Nu Q Rmin Re t x Lewis number total mass flow rate, kg/s Nusselt number heat transfer rate, W minimum coil radius, m Reynolds number tube thickness, m humidity ratio Subscripts a air i inside L latent max maximum o outside s surface, wall sat saturated w water avg average in inlet m moist air min minimum out outlet S sensible T total wv water vapor transfer and flow characteristics in the spirally coiled tube in open literature. The most productive studies have been continuously carried out by Ho et al. [10–12]. The relevant correlations of the tube-side and air-side heat transfer coefficients reported in literature were used in the simulation to determine the thermal performance of the spiral-coil heat exchanger under cooling and dehumidifying conditions. The simulation results were validated by comparing with measured data. Due to the lack of the heat transfer coefficient correlations obtained directly from the spirally coiled tube configuration, Naphon and Wongwises [13] proposed a correlation for the average in-tube heat transfer coefficient for a spiral coil heat exchanger under dehumidifying conditions. Recently, in their second and third papers (Naphon and Wongwises [14,15]), mathematical models to determine the performance and heat transfer characteristics of spirally coiled finned tube heat exchangers under wet-surface conditions and dry-surface conditions were developed and investigated. There was reasonable agreement between the results obtained from the experiment and those from the developed model. As mentioned above, only a few works on the heat transfer characteristics in spiral coil heat exchangers P. Naphon, S. Wongwises / Experimental Thermal and Fluid Science 29 (2005) 511–521 have been reported. In the present study, the heat transfer characteristics and performance of a spiral coil heat exchanger under cooling and dehumidifying conditions which have never been investigated before, are studied. The results obtained from the developed model are validated by comparing with measured data. In addition, the effects of relevant parameters on the model prediction are also discussed. 513 Air inlet Water outlet Air outlet Water inlet 2. Experimental apparatus and method The experimental apparatus described in Naphon and Wongwises [13] was used in the present study. A schematic diagram of the experimental apparatus is shown in Fig. 1. The test loop consists of a test section, refrigerant loop, chilled water loop, hot air loop and data acquisition system. The water and air are used as working fluids. The test section is a spiral-coil heat exchanger which consists of a shell and spiral coil unit as shown in Fig. 2. The test section and the connections of the piping system are designed such that parts can be changed or repaired easily. In addition to the loop components, a full set of instruments for measuring and controlling the temperature and flow rate of all fluids is installed at all important points in the circuit. Air is discharged by a centrifugal blower into the channel and is passed through a straightener, heater, guide vane, test section, and then discharged to the atmosphere. The purpose of straightener is to avoid the distortion of the air velocity profile. The speed of the centrifugal blower is controlled by the inverter. Air velocity is measured by a hot wire anemometer. The test channel is fabricated from zinc, with an inner diameter of 300 mm and a length of 12 m. The channel wall is insulated with a 6.40 mm thick Aeroflex standard sheet. Fig. 2. Schematic diagram of the section of the spirally coiled tube heat exchanger. The inlet and outlet sections for hot air flowing through the test section unit are shown in Fig. 2. The hot air flows into the center core and then flows across the spiral coils, radially outwards the wall of the shell before leaving the heat exchanger at the air outlet section (Fig. 2). The inlet temperature of the air is raised to the desired level by using electric heaters controlled by a temperature controller. The entering and exiting air temperatures of the heat exchanger are measured by type T copper–constantan thermocouples extending inside the air channel in which the air flows. The 1 mm diameter thermocouple probes are located at different four positions at the same cross section, 60 cm upstream of the heat exchanger inlet and also four positions at 50 cm downstream of the exit of the heat exchanger. The inlet and outlet relative humidities of air are detected by humidity transmitters. The chilled water loop consists of a 0.3 m3 storage tank, an electric heater controlled by adjusting the voltage, a stirrer, and a cooling coil immerged inside a storage tank. R22 is used as the refrigerant in the cooling Fig. 1. Schematic diagram of experimental apparatus. 514 P. Naphon, S. Wongwises / Experimental Thermal and Fluid Science 29 (2005) 511–521 coil. After the temperature of the water is adjusted to the desired level, the chilled water is pumped out of the storage tank, and is passed through a filter, flow meter, test section, and returned to the storage tank. The by-pass is used for passing the excess water back to the water tank for the experiments of low water flow rate. The flow rate of the water is measured by a flow meter with a range of 0–10 GPM. The spiral-coil heat exchanger consists of a steel shell with a spirally coiled tube unit. The spiral-coil unit consists of six layers of spirally coiled copper tubes. Each tube is constructed by bending a 9.27 mm diameter straight copper tube into a spiral-coil of five turns. The innermost and outermost diameters of each spiralcoil are 6.77 and 22.76 cm, respectively. Each end of the spiral-coils is connected to the vertical manifold tube with outer diameter of 15.9 mm. The dimensions of the spiral-coil heat exchanger are listed in Table 1. The copper–constantan thermocouples are installed at the third layer of the spiral-coil unit from the uppermost layer, each with two thermocouples to measure the water temperature and wall temperature. The water temperature is measured in five positions with 1 mm diameter probes extending inside the tube in which the water flows. Thermocouples are also mounted at five positions on the tube wall surface to measure the wall temperatures. Thermocouples are soldered into a small hole drilled 0.5 mm deep into tube wall surface and fixed with special glue applied to the outside surface of the copper tubing. With this method, thermocouples are not biased by the fluid temperatures. An overall energy balance was performed to estimate the extent of any heat losses or gains from the surroundings. In the present study, only the data that satisfy the energy balance conditions; jQw Qaj/Qavg is less than 0.05, are used in the analysis. The total heat transfer rate, Qavg, is averaged from the air-side heat transfer rate, Qa, and the water-side heat transfer rate, Qw. Experiments were conducted with various temperatures and flow rates of hot air and chilled water entering the test section. The chilled water flow rate was increased Table 1 Dimensions of the spirally coiled tube heat exchanger Parameters Dimensions Outer diameter of tube, mm Inner diameter of tube, mm Innermost diameter of spiral coil, mm Outermost diameter of spiral coil, mm Number of coil turns Number of spiral coils Distance between the spiral coil layer, mm Diameter of shell, mm Length of shell, mm Diameter of hole at air- inlet, mm Diameter of closed plate at air-outlet, mm 9.3 7.8 67.8 227.6 5 6 13.7 300 250 65 230 Table 2 Experimental conditions Variables Range Inlet-air temperature, C Inlet-water temperature, C Air mass flow rate, kg/s Water mass flow rate, kg/s 50–60 10–20 0.01–0.08 0.08–0.24 Table 3 Uncertainty of measurement Instruments Accuracy Uncertainty Hot wire anemometer (air velocity, m/s) Rotameter (water mass flow rate, kg/s) Thermocouple type T Data logger, (C) Humidity transmitter (%RH) 2.0% 0.2% 0.1% 0.04% 0.5% ±0.23 ±0.003 ±0.03 ±0.22 in small increments while the hot air flow rate, inlet chilled water and hot air temperatures were kept constant. The flow rate of hot air was controlled by adjusting the speed of the centrifugal blower. An inverter was used to control the speed of the motor for driving the blower. The inlet hot air and chilled water temperatures were adjusted to the desired level by using electric heaters controlled by temperature controllers. The system was allowed to approach the steady state before data were recorded. The steady state condition was reached when the temperature and flow rates at all measuring points no longer fluctuated. After stabilization, the variables at the locations mentioned above were recorded. Temperatures at each position were measured five times. Period of each measurement was five minutes. Finally, temperature data at each position was averaged over the time period. The range of experimental conditions in this study and uncertainty of the measurement are given in Tables 2 and 3, respectively. 3. Mathematical modelling The heat transfer characteristics of the compact spiral coil heat exchanger under wet-surface conditions can be determined from the conservation equations of mass and energy. The mathematical model is based on that of Ho et al. [12] and, Naphon and Wongwises [14] with the following assumptions: • Flows of air and water are steady. • There is no heat loss between the system and surrounding. • Air-side convective heat transfer coefficients at each section of a coil turn in horizontal plane is equal. • Water-side convective heat transfer coefficient at each section of a coil turn in horizontal plane is equal. P. Naphon, S. Wongwises / Experimental Thermal and Fluid Science 29 (2005) 511–521 • Thermal resistance of liquid film is neglected. • Each completed coil turn is approximately circular. • Thermal conductivity of the spirally coiled tube is constant. 3.1. Air-side heat transfer When the surface temperature of the spirally coiled heat exchanger is below the dew-point temperature of the in-coming air, a portion of the vapor in the humid air stream is condensed on the coil surface and removed as liquid. By considering the control volume of each segment in Fig. 3, the total heat transfer rate is determined from the sum of latent and sensible heat as follows: dQT ¼ dQS þ dQL ð1Þ where dQT, dQS, and dQL are the total heat, sensible heat and latent heat, respectively. dQS ¼ ho dAo ðT a;in T s Þ ð2Þ where ho is the air-side heat transfer coefficient, dAo is the outside surface area, Ta,in is the inlet-air temperature, and Ts is the tube surface temperature. The heat released is given by the following latent heat transfer rate: dQL ¼ dM wv ifg C p;m ¼ C p;a þ xa C p;wv 515 ð6Þ Substituting Eq. (6) into Eq. (5) and assuming Le is approximately equal to 1, we get ho dAo dQT ¼ ð7Þ ðia;in isat;s Þ C p;m where ia, in is the inlet enthalpy of air, and isat, s is the enthalpy at saturated conditions at tube surface temperature. 3.2. Water-side heat transfer The heat transfer rate in terms of the water flow rate can be given as dQT ¼ M w C p;m dT w ð8Þ The heat transfer rate to the water can be expressed as dQT ¼ hr dAo ðT s T w Þ ð9Þ where 1 tdAo dAo ¼ þ hr kAave dAi hi ð10Þ where t is the tube thickness, Aave is the average surface area, and hr is the combined conductance through the tube surface and water inside tube. ð3Þ where ifg is the enthalpy of condensation and dMwv is the mass transfer rate of the water vapor, defined as dM wv ¼ hD dAo ðxa;in xsat;s Þ ð4Þ where hD is the mass transfer coefficient, xa,in is the inlet humidity ratio of air, and xsat,s is the humidity ratio at saturated conditions at the tube surface temperature. Substituting Eqs. (2)–(4) into Eq. (1) gives ho 1 dQT ¼ C p;m ðT a;in T s Þ þ ðxa;in xsat;s Þifg Le C p;m dAo ð5Þ where the Lewis number, Le, is defined by Le ¼ hDhCop;m The specific heat of the moist air, Cp,m, is the sum of the specific heat of dry air and water vapor 3.3. Energy balance Considering the energy balance over the control volume for each segment, we get ho dAo ðia;in isat;s Þ ¼ hr dAo ðT s T w Þ C p;m Rearranging gives ho ðT s T w Þ ¼ Rc ¼ hr C p;m ðia;in isat;s Þ isat;s ¼ 10:90748 þ 1:22045T s þ 0:05652T 2s Ta,out , ia,out, ωa,out Wate r flow j+1 Tube wall j j-1 dθ Rn-1 1 n-1 n n+1 Tw,in Tw,out Water flow 2 3 Ts,out Air flow Air flow ð12Þ The enthalpy of the saturated air, isat,s, at the wet surface temperature in Eq. (12) is determined from a equation used by Ho and Wijeysundera [12]: Air flow Air flow ð11Þ Ta,in, ia,in, ω a,in Ts,in Air flow Fig. 3. Schematic diagram of simulation approach and control volume of each segment. ð13Þ 516 P. Naphon, S. Wongwises / Experimental Thermal and Fluid Science 29 (2005) 511–521 Substituting Eq. (13) into Eq. (12) and rearranging, we get 1 0:05652T 2s þ 1:22045 þ Ts Rc Tw þ 10:90749 ia;in ¼0 ð14Þ Rc The energy balance over the control volume for each segment may be written in terms of the water flow rate as follows: T s;out þ T s;in T w;out T w;in hr dAo 2 2 ¼ M w C p;w ðT w;out T w;in Þ On rearranging, we get 1 ðb½T s;out þ T s;in T w;in ½b 1Þ T w;out ¼ ðb þ 1Þ ð15Þ hr dAo 2M w C p;w 1 þ 1:22045 þ T s;in Rc T w;in þ 10:90749 ia;in ¼0 Rc 0:05652T 2s;in ð22Þ for 300 < De < 2200, Pr P 5 The air-side heat transfer coefficient correlation of the spirally coiled heat exchanger for wet-surface conditions was also developed from the same experimental data of Naphon and Wongwises [13]. The equation is as follows: ho Pr2=3 ¼ 0:135Re0:318 o Gmax C p;m ð17Þ for Reo < 6000 In addition, the spiral coil heat exchanger configurations and properties of working fluids, as well as the operating conditions, are also needed. The iteration process is described as follows: ð19Þ Substituting Eq. (16) into Eq. (18) we get 1 b 2 0:05652T s;out þ 1:22045 þ T s;out Rc Rcðb þ 1Þ 1 þ 10:90749 ia;in ½bT s;in ðb 1ÞT w;in ¼ 0 Rcðb þ 1Þ ð20Þ 4. Solution method The spiral-coil unit consists of six layers of spirally coiled tubes. Each coiled tube is divided into five circular coil turns having the following mean radius: Rn ¼ ðRmin þ ð2n 1ÞapÞ hi d i ¼ 27:358De0:287 Pr0:949 k J¼ Eq. (14) can be written in term of Ts,out and Ts,in, as follows: 1 0:05652T 2s;out þ 1:22045 þ T s;out Rc T w;out þ 10:90749 ia;in ¼0 ð18Þ Rc and Nui ¼ ð16Þ where b¼ segment of the innermost coil turn and then is done segment by segment along the circular coil turn. In order to solve the model, relevant tube-side and air-side heat transfer coefficients are needed. The following correlation proposed by Naphon and Wongwises [13] for the spirally coiled tube is used to predict tube-side heat transfer coefficients. ð21Þ where Rmin is the minimum coil radius, n is the number of coil turns, and a is of radius change per radian. Each circular coil turn can be divided into several segments as shown in Fig. 3. The calculation begins at the ð23Þ • The outlet-water temperature is assumed. • Eqs. (16), (19) and (20) are solved simultaneously by using the Newton–Raphson method to obtain the inlet-tube temperature, (Ts,in), outlet-tube surface temperatures, (Ts,out), water temperature, (Tw,in), at Segment 1. • The heat transfer rate, (Q), and the outlet-air temperature, (Ta,out), are calculated. • The computation described above is next performed at segment 2 and then the remaining segments in turn until the last one. • The same computation is performed at the next circular coil. • The computation is terminated when the calculation at the last segment of the outermost coil turn is finished. • The calculated water temperature at the last segment of the outermost coil turn is compared with the inletwater temperature (initial condition). If the difference is within 106, the calculations is ended, and if not, another outlet-water temperature value of the first segment at the innermost coil turn is tried and the computations are repeated until convergence is obtained. 5. Results and discussion Fig. 4 shows the variation of the outlet-air temperatures with air mass flow rate obtained from the experiment for the different water mass flow rates of 0.11 P. Naphon, S. Wongwises / Experimental Thermal and Fluid Science 29 (2005) 511–521 60 25 Mathematical model 0.11 0.19 50 45 40 35 o 30 Ta,in = 50 C o T w,in = 11.5 C 25 ω a,in = 0.04 0.01 0.02 0.03 0.04 0.05 0.06 0.07 Air mass flow rate (kg/s) and 0.19 kg/s. At an inlet-air temperature of 50 C, inletwater temperature of 11.5 C and inlet-air humidity ratio of 0.04, the outlet-air temperature tends to increase as air mass flow rate increases. At the same air mass flow rate, the outlet-air temperature at mw = 0.11 kg/s seems slightly higher than that at mw = 0.19 kg/s. However, the effect of the water mass flow rate on the outlet-air temperature in the present experiment is quite low. The average difference between the measured data is 4.4%. The present numerical results are validated by comparing with experimental data. It can be noted that the model slightly underpredicts the present measured data at low air mass flow rate region. The low flow rate of air, together with the temperature which is higher than the ambient air downstream, causes the measured outlet-air temperatures to be higher than the calculated ones. Fig. 5 shows the variation of the outlet-air temperature with air mass flow rate for the different inlet-air 60 o Outlet air temperature ( C) o Ta,in ( C) Experiment Mathematical model 50 55 50 45 40 35 Tw,in = 11.5 oC m w = 0.11 kg/s ωa,in = 0.04 30 25 20 0.00 0.01 0.02 0.03 0.04 Experiment Mathematical model 0.11 20 0.19 15 10 5 0.00 o T a,in = 50 C o T w,in = 11.5 C ω a,in = 0.04 0.01 0.02 0.03 0.04 0.05 0.06 0.07 Air mass flow rate (kg/s) Fig. 4. Variation of the outlet-air temperatures with air mass flow rate for different water mass flow rates. 55 m w (kg/s) o o Outlet air temperature ( C) Experiment O utle t wa ter temp eratur e ( C ) m w (kg/s) 55 20 0.00 517 0.05 0.06 0.07 Air mass flow rate (kg/s) Fig. 5. Variation of the outlet-air temperatures with air mass flow rate for different inlet-air temperatures. Fig. 6. Variation of the outlet-water temperatures with air mass flow rate for different water mass flow rates. temperatures of 50 and 55 C. As expected, the inletair temperature has significant effect on the outlet-air temperature. Fig. 6 shows the variation of the outlet-water temperatures with air mass flow rate for the different water mass flow rates of 0.11 and 0.19 kg/s. For an inlet-water temperature of 11.5 C, inlet-air temperature of 50 C, and inlet-air humidity ratio of 0.04, the increase of the heat transfer rate resulted in an increase of the outletair temperature (Fig. 5) has a significant effect on the increase of the outlet-water temperature. As the outlet-air temperature increases, the temperature difference between inlet-and outlet-air temperature decreases. Therefore, the air mass flow rate must be increased for keeping the heat transfer rate equal to the water side. Therefore, it can be clearly seen that the outlet-water temperature increases with increasing air mass flow rate. At the same inlet-air and-water temperatures, inlet-air humidity ratio and air mass flow rate, the outlet-water temperature at lower water flow rate is higher than that at higher water flow rate. This is because at a specific air mass flow rate, inlet-air and-water temperatures the water mass flow rate slightly affects the outlet-air temperature. In other words, the heat transfer rate absorbed by the chilled water is mainly dependent on the mass flow rate and the outlet-water temperature. Therefore the lower water flow rate gives the higher water-outlet temperature. Considering Fig. 7, which shows the effect of inlet-air temperature on the outlet-water temperature, it is clearly seen that at the same air mass flow rate, the outlet-water temperature at Ta,in = 50 C is lower than at Ta,in = 55 C. The reason for this is similar to the one as described above. At a specific inlet-water temperature, inlet-air humidity ratio, and water and air mass flow rates, the increase of the outlet-water temperature results in the increases of the outlet-air temperature and the heat transfer rate. Again, in order to keep the heat 518 P. Naphon, S. Wongwises / Experimental Thermal and Fluid Science 29 (2005) 511–521 25 20 Ta,in (oC) Mathematical model o Experiment Tube surface temperature ( C ) Ta,in (oC) o O u t l e t w a t e r t em p e r a t u r e ( C ) 25 50 55 15 10 5 0.00 Tw,in = 11.5oC m w = 0.11 kg/s ωa,in = 0.04 0.01 0.02 0.03 0.04 0.05 0.06 20 Mathematical model 15 o 10 5 0.00 0.07 Experiment 50 55 Tw,in = 11.5 C m w = 0.11 kg/s ωa,in = 0.04 0.01 0.02 Air mass flow rate (kg/s) 0.03 0.04 0.05 0.06 0.07 Air mass flow rate (kg/s) Fig. 7. Variation of the outlet-water temperatures with air mass flow rate for different inlet-air temperatures. Fig. 9. Variation of the tube surface temperatures with air mass flow rate for different inlet-air temperatures. transfer rate equal to the water-side heat transfer rate, the inlet-air temperature must be increased. Considering the results obtained from the present model and those obtained from the experiment, it can be clearly seen from figure that the predicted outlet-water temperature is higher than the measured one. This may be due to the fact that the thermal resistance of the liquid film that covers the tube surface is not included in the mathematical model causing higher heat transfer rate from hot air to chilled water. Figs. 8 and 9 show the variations of the tube surface temperatures with air mass flow rate. The tube surface temperature is measured at the 3rd layer from the uppermost layer in five positions in which the water flows. It can be seen from both figures that the trends of the tube surface temperature are similar to those of the outletwater temperature curves as shown in Figs 6 and 7. It can be clearly seen that the water mass flow rate and the inlet air temperature have insignificant effects on the tube surface temperature. Again, considering the predicted and measured results, it is found that the model overpredicts the measured data. It may be because, in experiment, the tube surface is chilled by the liquid film. Figs. 10 and 11 illustrate the variations of the enthalpy effectiveness and humidity effectiveness with air mass flow rate, respectively at Tw,in = 11.5 C, mw = 0.11 kg/s, xa,in = 0.04, for different inlet-air temperatures of 50 and 55 C. For the whole range of inlet-water temperature, it is found that the tube surface temperatures is always lower than the dew-point temperature of the air. This results in condensing out of the moisture. The total load-removal performance and the latent load-removal performance of the spiral coil heat exchanger can be presented in terms of the enthalpy effectiveness and humidity effectiveness, respectively, as follows 1.0 m w (kg/s) Experiment Ta,in (oC) Mathematical model 20 Enthalpy effectiveness 0.11 o Tube surface temperature ( C ) 25 0.19 15 o Ta,in = 50 C Tw,in = 11.5oC ωa,in = 0.04 10 5 0.00 0.01 0.02 0.03 0.04 0.06 0.07 Air mass flow rate (kg/s) Fig. 8. Variation of the tube surface temperatures with air mass flow rate for different water mass flow rates. Mathematical model 0.6 0.4 o 0.2 0.05 Experiment 50 55 0.8 0.0 0.00 Tw,in = 11.5 C mw = 0.11 kg/s ωa,in = 0.04 0.01 0.02 0.03 0.04 0.05 0.06 0.07 Air mass flow rate (kg/s) Fig. 10. Variation of the enthalpy effectivenesses with air mass flow rate for different inlet-air temperatures. P. Naphon, S. Wongwises / Experimental Thermal and Fluid Science 29 (2005) 511–521 1.0 1.0 o Experiment Mathematical model mw (kg/s) Experiment 50 55 Enthalpy effectiveness Humidity effectiveness Ta,in ( C) 0.8 0.6 0.4 0.2 0.0 0.00 519 Tw,in = 11.5 oC mw = 0.11 kg/s ωa,in = 0.04 0.01 0.02 0.8 0.19 0.6 0.4 o 0.2 0.03 0.04 0.05 0.06 0.0 0.00 0.07 Ta,in = 50 C Tw,in = 11.5oC ωa,in = 0.04 0.01 0.02 Air mass flow rate (kg/s) Humidity effectiveness; Ew ¼ xa;in xa;out xa;in xsat;s 0.05 0.06 0.07 1.0 ð24Þ m w (kg/s) Experiment Mathematical model ð25Þ The humidity ratio of saturated air, xsat,s, at the wetsurface conditions can be obtained from the correlation given by Laing et al. [16] xsat;s ¼ ð3:7444 þ 0:3078T s þ 0:0046T 2s þ 0:0004T 3s Þ 103 0.04 Fig. 12. Variation of the enthalpy effectivenesses with air mass flow rate for different water mass flow rates. ð26Þ It is found from Figs. 10 and 11 that the enthalpy effectiveness and the humidity effectiveness decrease with increasing air mass flow rate for a given inlet-water temperature, inlet-air humidity ratio, and water mass flow rate. Increasing of the air mass flow rate directly affects the outlet enthalpy, ia,out, enthalpy of saturated air, isat,s, outlet humidity ratio, xa,out, and humidity ratio of saturated air, xsat,s. However, the increases of the outlet enthalpy and outlet humidity ratio of air are larger than those of the enthalpy of saturated air and humidity ratio of saturated air. Therefore, the enthalpy effectiveness and humidity effectiveness tend to decrease with increasing air mass flow rate. It can be noted that the air inlet temperature has an insignificant effect on the enthalpy effectiveness and humidity effectiveness. However, at a given lower air mass flow rate, higher inlet-air temperature may lead to a slight increase in enthalpy effectiveness and humidity effectiveness. The average discrepancies between experimental data are about 4.8% and 8.7%, respectively. Figs. 12 and 13 show the variation of enthalpy effectiveness with air mass flow rate and that of humidity effectiveness with air mass flow rate, respectively. It can be clearly seen from the experimental that the water mass flow rate show an insignifi- Humidity effectiveness ia;in ia;out ia;in isat;s 0.03 Air mass flow rate (kg/s) Fig. 11. Variation of the humidity effectivenesses with air mass flow rate for different inlet-air temperatures. Enthalpy effectiveness; Eh ¼ Mathematical model 0.11 0.11 0.8 0.19 0.6 0.4 0.2 0.0 0.00 Ta,in = 50oC Tw,in = 11.5 oC ωa,in = 0.04 0.01 0.02 0.03 0.04 0.05 0.06 0.07 Air mass flow rate (kg/s) Fig. 13. Variation of the humidity effectivenesses with air mass flow rate for different water mass flow rates. cant effect on the enthalpy effectiveness and humidity effectiveness. The average difference between experimental data are 5% and 5.5%, respectively. The uncertainties of the experimental enthalpy and humidity effectivenesses are between 0.34–0.56% and 0.5–0.93%, respectively. In general, the shape of the predicted and observed enthalpy effectiveness and humidity effectiveness profiles agree well. A number of graphs can be drawn from the output of the simulation but, because of the space limitation, only typical results are shown. Fig. 14 illustrates the variation of the predicted outlet-air temperatures with air mass flow rate for various water mass flow rates. It can be clearly seen from figure that the outlet-air temperature increases rapidly in the low air mass flow rate region and then increases moderately as air mass flow rate increases. In addition, the decrease of outlet-air 520 P. Naphon, S. Wongwises / Experimental Thermal and Fluid Science 29 (2005) 511–521 40 Ta,in = 60oC Tw,in = 10 oC ωa,in = 0.04 50 45 m w (kg/s) 40 0.05 0.10 0.15 0.50 35 30 0.00 0.02 Ta,in = 60oC Tw,in = 10oC ωa,in = 0.04 35 o Tube surface temperature ( C) 55 o Outlet air temperature ( C) 60 0.04 0.06 0.08 0.10 0.16 0.12 0.14 30 25 20 15 mw (kg/s) 0.05 0.10 0.15 0.50 10 5 0 0.18 0.00 0.02 0.04 Air mass flow rate (kg/s) Ta,in (oC) 0.50 50 60 70 80 0.45 0.40 0.35 0.25 Tw,in = 10oC mw = 0.15 kg/s ωa,in = 0.04 0.20 0.00 0.02 0.30 0.04 0.06 0.08 0.10 0.12 0.14 0.16 0.18 Air mass flow rate (kg/s) Fig. 17. Variation of the enthalpy effectivenesses with air mass flow rate for different inlet-air temperatures. 0.60 o Tw,in = 10 C mw = 0.15 kg/s ωa,in = 0.04 25 20 o Ta,in ( C) 15 50 60 70 80 10 5 0.02 0.04 Ta,in ( oC) 0.55 Humidity effectiveness o Tube surface temperature ( C) 0.18 0.55 40 0 0.00 0.16 0.12 0.14 Fig. 16. Variation of the tube surface temperatures with air mass flow rate for different water mass flow rates. Enthalpy effectiveness temperature becomes relatively smaller as water mass flow rate increases. Fig. 15 shows the effect of inlet-air temperature on the tube surface temperature. At a specific inlet-air temperature, the tube surface temperature generally increases with increasing air mass flow rate, however, the increase of the tube surface temperature at higher inlet-air temperatures is higher than at lower ones for the same range of air mass flow rates. In addition, at any air mass flow rate, the tube surface temperature increases relatively constantly with increasing inlet-air temperature. The effect of water mass flow rate on the tube surface temperature is shown in Fig. 16. It can be found that at a specific air mass flow rate, the tube surface temperature decreases as water mass flow increases. Figs. 17 and 18 show the variations of the enthalpy effectivenesses and humidity effectivenesses with air mass flow rate for various inlet-air temperatures, respec- 30 0.10 Air mass flow rate (kg/s) Fig. 14. Variation of the outlet-air temperatures with air mass flow rate for different water mass flow rates 35 0.06 0.08 0.06 0.08 0.10 0.12 0.14 0.16 0.45 0.40 0.35 0.30 0.25 0.18 Air mass flow rate (kg/s) Fig. 15. Variation of the tube surface temperatures with air mass flow rate for different inlet-air temperatures. 50 60 70 80 0.50 0.20 0.00 o Tw,in = 10 C mw = 0.15 kg/s ωa,in = 0.04 0.02 0.04 0.06 0.08 0.10 0.12 0.14 0.16 0.18 Air mass flow rate (kg/s) Fig. 18. Variation of the humidity effectivenesses with air mass flow rate for different inlet-air temperatures. P. Naphon, S. Wongwises / Experimental Thermal and Fluid Science 29 (2005) 511–521 tively. It should be noted that the enthalpy effectiveness and humidity effectiveness decrease with increasing air mass flow rate. These effectivenesses decrease rapidly in the low air mass flow rate region and then decrease moderately as the air mass flow rate increases. For a specific air mass flow rate at constant inlet-air andwater temperatures, both effectivenesses increase with increasing inlet-air temperature. The same explanation described above for Figs. 17 and 18 can be given. 6. Conclusions New experimental data from the measurement of the heat transfer characteristics and the performance of a spiral coil heat exchanger under cooling and humidifying conditions are presented. The results obtained from the developed model are validated by comparing with the measured data. The effects of the inlet conditions of the working fluids flowing through the spirally coiled heat exchanger are discussed. The following conclusions can be given: • There is reasonable agreement between the results obtained from the experiment and those from the developed model. • Air mass flow rate and inlet-air temperature have significant effect on the increase of the outlet-air andwater temperatures. • The outlet-air and water temperatures decrease with increasing water mass flow rate. • The enthalpy effectiveness and humidity effectiveness decrease as the air and water mass flow rates increase. • The enthalpy effectiveness and humidity effectiveness increase as the inlet-air temperature increases. Acknowledgements The authors would like to express their appreciation to the Thailand Research Fund (TRF) for providing financial support for this study. The authors also wish to acknowledge Miss Supajaree Maroongruang, Mr. Anucha Kasikapast and Mr. Chanit Somphol, for their assistance in some of the experimental work. 521 References [1] S. Garimella, D.E. Richards, R.N. Christensen, Experimental investigation of heat transfer in coiled annular ducts, J. Heat Transfer 110 (1988) 329–336. [2] D.G. Prabhanjan, G.S.V. Raghavan, T.J. Rennie, Comparison of heat transfer rates between a straight tube heat exchanger and a helically coiled heat exchanger, Int. Comm. Heat Mass Transfer 29 (2002) 185–191. [3] C.J. Bolinder, B. Sunden, Numerical prediction of laminar flow and forced convective heat transfer in a helical square duct with finite pitch, Int. J. Heat Mass Transfer 39 (1996) 3101–3115. [4] B. Zheng, C.X. Lin, M.A. Ebadian, Combined laminar forced convection and thermal radiation in helical pipe, Int. J. Heat Mass Transfer 43 (2000) 1067–1078. [5] N. Acharya, M. Sen, H.C. Chang, Analysis of heat transfer enhancement in coiled-tube heat exchangers, Int. J. Heat Mass Transfer 44 (2001) 3189–3199. [6] R.C. Lin, M.A. Ebadian, Developing turbulent convective heat transfer in helical pipes, Int. J. Heat Mass Transfer 40 (1997) 3861–3873. [7] J.J.M. Sillekens, C.C.M. Rindt, A.A. Van Steenhoven, Developing mixed convection in a coiled heat exchanger, Int. J. Heat Mass Transfer 41 (1998) 61–72. [8] C.C.M. Rindt, J.J.M. Sillekens, A.A. Van Steenhoven, The influence of the wall temperature on the development of heat transfer and secondary flow in a coiled heat exchanger, Int. Comm. Heat Mass Transfer 26 (1999) 187–198. [9] T. Lemenand, H. Peerhossaini, A thermal model for prediction of the Nusselt number in a pipe with chaotic flow, Appl. Therm. Eng. 22 (2002) 1717–1730. [10] J.C. Ho, N.E. Wijeysundera, S. Rajasekar, T.T. Chandratilleke, Performance of a compact spiral coil heat exchanger, Heat Recovery Syst. & CHP 15 (1995) 457–468. [11] J.C. Ho, N.E. Wijeysundera, Study of a compact spiral-coil cooling and dehumidifying heat exchanger unit, Appl. Therm. Eng. 16 (1996) 777–790. [12] J.C. Ho, N.E. Wijeysundera, An unmixed-air flow model of a spiral cooling dehumidifying heat transfer, Appl. Therm. Eng. 19 (1999) 865–883. [13] P. Naphon, S. Wongwises, An experimental study on the in-tube heat convective heat transfer coefficients in a spiral-coil heat exchanger, Int. Comm. Heat Mass Transfer 29 (2002) 797–809. [14] P. Naphon, S. Wongwises, Investigation of the performance of a spiral-coil finned tube heat exchanger under humidifying conditions, J. Eng. Phys. Thermophys. 76 (2003) 83–92. [15] P. Naphon, S. Wongwises, Experimental and theoretical investigation of the heat transfer characteristics and performance of a spiral-coil heat exchanger under dry-surface conditions, 2nd International Conference on Heat Transfer, Fluid Mechanics, and Thermodynamics, 24–26 June, 2003, Victoria Falls, Zambia. [16] S.Y. Laing, M. Liu, T.N. Wong, G.K. Nathan, Analytical study of evaporator coil in humid environment, Appl. Therm. Eng. 19 (1999) 1129–1145.