Fire Pumps - Electric - FM-NFPA20 - DNF, HSEF

advertisement
GRUNDFOS DATA BOOKLET
Fire DNF, Fire HSEF
Grundfos fire systems
Fire systems with electrically powered (50 Hz) pumps
approved by the FM according to NFPA 20
Contents
NFPA standards
Introduction to the NFPA
NFPA 20
FM Global
Standards approval process
Overview of fire system
Performance requirements
Other system components
Motor data
3
3
3
3
4
5
6
Product description
Introduction
DNF end-suction pumps
HSEF horizontal, split-case pumps
7
7
7
Performance range
DNF and HSEF, 2-pole, 50 Hz
HSEF, 4-pole, 50 Hz
Performance curves - overview
8
9
10
Bare shaft pumps
DNF
HSEF
HSEF
Flange dimensions
How to read the curve charts
Guide
Curve conditions
Selection of pumps
Calculation of total head
Performance tests
Performance curves, HSEF
35
12
13
21
21
21
Installation
Piping
Alignment
2
Installation dimensions
Controller
14
15
16
17
18
18
18
19
19
19
20
20
20
Operating conditions
Location
Ambient temperature and altitude
Inlet pressure
28
29
29
29
29
29
30
11
11
Construction
Sectional drawing, DNF
Material specification, DNF
Sectional drawing, HSEF
Material specification, HSEF
Mechanical construction
Pump housing
Bearing bracket and shaft
Stuffing box
Coupling
Impeller
Foundation
Test pressure
Motor
24
25
26
27
Curve charts
Identification
Nameplates
Type keys
23
23
Performance curves, DNF
Product range
Pump sets available
FM approval numbers
Motor range, 2-pole, 50 Hz
Motor range, 4-pole, 50 Hz
22
22
Controller types
Components
Control panel interface
Data recording
Technical data
Dimensions
66
66
66
66
67
67
NFPA standards
Fire DNF, Fire HSEF
Introduction to the NFPA
Standards approval process
The National Fire Protection Association (NFPA) is an
international, non-profit organisation of fire safety
professionals. The NFPA headquarters is located in the
USA.
The organisation creates and maintains minimum
acceptable standards and requirements for fire
prevention and suppression activities, training,
equipment and other life-safety codes and standards.
NFPA standards are typically revised every three years
in order to keep guidelines updated and to prevent the
loss of life and property due to fire.
See the NFPA homepage: www.nfpa.org.
NFPA 20
DNF and HSEF bare shaft pumps comply with the
NFPA 20 Standard for the Installation of Stationary Fire
Pumps for Fire Protection. The standard covers
systems for commercial, industrial and private
buildings.
APPROVED
• Expected pump performance, including total head,
power requirement and efficiency versus flow
characteristics.
If different impeller diameters are used to obtain the
rated head for the pump to be examined, complete
details must be provided concerning performance
specifications to be evaluated.
• Calculations to determine shaft size, casing bolt
size and anti-friction bearing life.
• General assembly drawings, a complete set of
manufacturing drawings, materials lists and physical
property specifications, expected marking format,
brochures, sales literature, specification sheets,
installation, operating and maintenance procedures.
When the application forms have been accepted, the
FM will attend the final test at the Grundfos premises.
When the evaluation of the test results is positive, the
FM will issue a certificate of compliance of the pump
with the standards specified.
When a pump component is replaced after the
certificate of compliance has been issued,
representative samples of the pump may need to be retested.
TM04 4901 2209
FM
TM03 5369 3606
The pumps have been tested and certified by FM
Global to comply with the requirements of the NFPA 20.
(FM is short for Factory Mutual.) Compliance with the
requirements is indicated by the FM mark affixed to the
pumps. See fig. 1.
Grundfos tests the pumps and fills in the application
forms for each individual pump size. We submit this
documentation to the FM:
Fig. 1 FM and NFPA 20 marks
Other NFPA standards
These standards are also of relevance to the products
described in this data booklet:
• NFPA 13. Installation of sprinkler systems
• NFPA 25. Standard for the inspection, testing and
maintenance of water-based fire protection systems
• NFPA 70. National Electrical Code.
FM Global
FM Global is a mutual commercial and industrial
property insurance and risk management organisation,
located in the USA with offices worldwide.
FM tests and approves industrial and commercial
products in compliance with its own standards, or other
nationally recognised requirements
The mark "FM APPROVED" indicates that the product
complies with the required standards. See fig. 1.
See the FM homepage: www.fmglobal.com.
3
NFPA standards
Fire DNF, Fire HSEF
Overview of fire system
4
4
5
6
5
8
6
5
5
7
9
2
5
8
9
6
10
12
6
1a
14
9
9
5
5
5
11
TM03 5471 1507
1b
13
3
3
Fig. 2 Overview of fire system
Pos. Description
4
Pos. Description
Pos. Description
1a
Fire pump, electrically powered (duty pump)
5
Valve
10
1b
Fire pump, diesel-powered (standby pump)
6
Expansion joint
11
Waste cone with sight glass
Discharge from relief valve
2
Jockey pump
7
Main relief valve
12
Flowmeter
3
From supply tank
8
Check valve/non-return valve
13
Discharge from test line
4
To system
9
Pressure gauge
14
Supply to jockey pump
NFPA standards
Fire DNF, Fire HSEF
System design
A fire system typically consists of three pumps: one
pressure pump (jockey pump) and two fire pumps, one
duty and the other acting as standby. Each of the fire
pumps is capable of achieving the required
performance.
Performance requirements
Systems with only one fire pump with a redundant
power supply or more than two fire pumps are,
however, also seen.
• motor power rating.
Operation
The jockey pump maintains pressure in the system and
compensates for any loss of pressure caused by leaks
and thus prevents the duty pump from starting
unnecessarily. The jockey pump has two pressure
levels:
FM-approved pumps comply with requirements
concerning these features:
• flow rate vs. pressure
• closed-valve pressure
Flow rate vs. pressure
The approval/listing of the pump is based on a certain
rated flow rate, indicated by the solid line in the curve
charts. The pump must be able to supply not less than
150 % of the rated flow rate (broken line) and still be
able to provide at least 65 % of the total rated pressure
when operating at a suction lift of at least 4.6 m (15 ft)
referred to water surface.
See fig. 3 and the example below.
• a low pressure level to start the jockey pump
• a high pressure level to stop the jockey pump.
The duty and standby pumps are not powered by the
same source. This ensures that if one pump fails, for
example due to fire damage, the other will operate. The
pumps are controlled by pressure sensors.
Although individually designed for the specific
installation, each fire unit must comply with NFPA
standards.
Fire pumps
FM-approved Grundfos end-suction and split-case
pumps are designed for the distribution of water in
automatic sprinkler and standpipe systems. They are
operated in case of fire and during tests.
Materials
Impeller, wear rings, guide or diffusion vane rings,
lantern rings, bottoms of stuffing boxes, interior nuts,
linings of stuffing-box throats, glands, gland nuts and
drain plugs are made of material approved by the FM
and UL.
100%
60
HSF 6-12
150%
n nom = 1450 min-1
ISO 9906 Annex A
/311
50
100%
44
40
34
65%
30
20
10
0
0
200
400
600
800
1000
1200
1400
1600
Q [US GPM]
TM04 4645 1809
In case of further decrease of system pressure due to
fire (i.e. sprinkler opens), the duty pump will start. In
case this pump fails to start or breaks down, the
standby pump will start.
p
[psi]
Fig. 3 Flow rate vs. pressure
Example
The pump complies with a flow requirement of 750 gpm
(170 m3/h). At this flow rate, the pump delivers a
pressure of 44 psi (31 mH). To be FM-approved or ULlisted, the pump must comply with these requirements:
Rated flow rate (100 %):
750 gpm (170 m3/h)
Maximum flow rate supplied by the pump
(150 %):
1125 gpm (256 m 3/h)
Rated pressure (100 %):
44 psi (31 metres head)
Minimum pressure supplied by the pump
(65 %):
34 psi (24 metres head)
At 150 % of the total rated flow rate, the pump delivers
a pressure of 34 psi (24 metres head). This means that
the pump complies with the requirements.
5
NFPA standards
Fire DNF, Fire HSEF
Closed-valve pressure
The closed-valve pressure must be at least 101 % and
not higher than 140 % of the total rated pressure.
See fig. 4 and the example below.
65
p
[psi]
140%
60
Example
The maximum power required for this pump is 25 kW.
If the motor service factor is 1, the minimum motor size
required will be 25/1 = 25 kW.
If the motor service factor is 1.15, the minimum motor
size required will be 25/1.15 = 21.7 kW.
HSF 6-12
n nom = 1450 min-1
ISO 9906 Annex A
53
/311
Other system components
50
100%
44
40
20
10
0
0
200
400
600
800
1000
1200
1400
1600
Q [US GPM]
TM04 4646 1809
30
Fig. 4 Closed-valve pressure
Rated pressure (100 %):
44 psi (31 metres head)
Minimum closed-valve pressure (101 %):
44 psi (31 metres head)
Maximum closed-valve pressure (140 %):
61 psi (43 metres head)
The pump has a closed-valve pressure of 53 psi
(37 metres head). This means that the pump complies
with the requirements.
Motor power rating
The maximum motor current under any condition of
pump load must not exceed the rated full-load current
multiplied by the service factor, if any. Service factors
must be in accordance with NEMA Standard MG-1.
To ensure that the motor is capable of operating the
pump at any time, the NFPA demands that the
manufacturer determines the maximum power required
at a certain duty range. The maximum power occurs
when there is no increase in power with an increase in
the flow rate. See fig. 5 and the example below.
P2
[kW]
30
25
10
0
400
600
800
1000
Fig. 5 Motor power rating
6
1200
1400
1600
Q [US GPM]
TM04 4647 1809
/311
20
200
Insulation class: F.
Enclosure class: IP55.
Note: NEMA motors are available on request.
Example
The curve shows a rated pressure of 44 psi (31 mH).
To be FM-approved or UL-listed, the pump must comply
with these requirements:
0
Electric motors
Grundfos electric fire systems are typically equipped
with MMG-E motors (sourced HEM EFF2 motors)
manufactured according to IEC 60034. Other motor
makes are available on request.
Jockey pumps
Grundfos CR pumps are used as jockey pumps,
maintaining the pressure. Under normal conditions, the
jockey pump will be activated by the low-pressure
switch as a result of small leakages, or if one or more
sprinklers are activated.
The jockey pump is not subject to any specific NFPA
requirements.
Control panel
The control panel has the CE-mark.
The control panel for the fire pumps must comply with
NFPA 20 requirements. In addition, the cabinet must be
listed by UL and ULC and approved by the FM and
CSA.
The control panel is painted with RAL 3002 (red) and
housed in a NEMA type-2 drip-proof enclosure.
The control panel is suitable for wall mounting or floor
mounting. See Type keys, page 13.
Product description
Fire DNF, Fire HSEF
Introduction
DNF end-suction pumps
This data booklet covers the DNF and HSEF pump
range. The pumps have been tested and certified by
FM to comply with the requirements of the NFPA 20
covering fire systems for commercial and private
buildings.
The DNF pumps are non-self-priming, single-stage,
centrifugal, volute pumps. The pumps have these
features:
Designations
• DNF and HSEF are pumps without motor
(bare shaft pumps).
• cast iron pump housing, bronze impeller, carbon
steel shaft, bronze shaft sleeves and wear rings
• Fire DNF is a fire pump set with a DNF pump and
motor mounted on a common base plate. The unit
can be incorporated into a fire system.
• Fire HSEF is a fire pump set with an HSEF pump
and motor mounted on a common base frame. The
unit can be incorporated into a fire system.
• axial suction port, radial discharge port and
horizontal shaft components
• dimensions and rated performance according to
DIN 24256 and ISO 2858
• dynamically balanced rotating parts according to
ISO 1940, class 6.3; hydraulically balanced
impellers
• two sturdy anti-friction bearings
• integral stuffing box.
Scope of delivery
A complete Fire DNF or Fire HSEF pump set
assembled and supplied from factory typically
comprises these elements:
TM03 5386 3606
• a pump and motor mounted on a common base
plate/frame
• a standard coupling protected by a coupling guard
• a controller
• pressure gauges
Grundfos offers a flowmeter as an accessory. The
flowmeter has been approved by FM or UL.
All fire pump sets are delivered to order.
Fig. 6 Fire DNF: DNF end-suction pump and motor
mounted on a base plate
HSEF horizontal, split-case pumps
The HSEF pumps are horizontal, split-case centrifugal
pumps. The pumps have these features:
• automatic air relief valve
• cast iron pump casing, double-suction bronze
impeller, carbon steel shaft, bronze shaft sleeves
and casing wear rings
• two sturdy, grease-lubricated, anti-friction bearings
• stuffing box as an integral part of the pump casing
• tested to NFPA performance standard.
GrA8205
• a circulation relief valve.
Fig. 7 Fire HSEF: HSEF horizontal, split-case pump and
motor mounted on a base frame
7
8
30
40
50
60
80
100
120
150
200
57 60
250
p
[psi]
TM04 4803 2109
30
40
50
60
70
80
90
100
H
[m]
70
DNF 65-20
DNF 65-25
80
90
DN
F6
100
5-2
5
500
600
HSEF 4-10G
HSEF 4-10
HSEF 4-12
800
200
1000
HSEF 5-8
HSEF 4-10
HSEF 4-12
HSEF 5-12
5-11
1200
300
HSEF 5-11
HSEF 6-10
HSEF
HSEF 5-12
1500
400
HSEF 6-10
HSEF 6-12
DNF / HSEF
Q [m³/h]
2000
2500
Q [US GPM]
HSEF 6-12
n nom = 2950 min-1
Performance range
Fire DNF, Fire HSEF
DNF and HSEF, 2-pole, 50 Hz
30
40
50
60
80
100
120
114
500
p
[psi]
TM04 4804 2109
30
40
50
60
70
80
90
H
[m]
600
HSEF 5-14
700
800
200
1000
1200
300
HSEF 6-16
1500
400
HSEF 6-16
2000
500
HSEF 8-15G
HSEF 8-20
600
HSEF 8-17A
HSEF 8-20G
700
3000
4000
HSF
12-19G
5000
HSF
12-19G
800 900 1000
HSEF 8-17A
HSEF 10-20
HSEF
HSF
12-19G
Q [m³/h]
6000 7000
Q [US GPM]
HSF
12-19G
n nom = 1460 min-1
Performance range
Fire DNF, Fire HSEF
HSEF, 4-pole, 50 Hz
9
Performance range
Fire DNF, Fire HSEF
Performance curves - overview
Rated flow rate
[GPM]
250
300
500
500
750
1000
1250
Pressure range
[psi]
2-pole
DNF 65-20
66-80
30
-
DNF 65-25
116-129
31
-
DNF 65-25
120-127
32
-
DNF 80-20
64-72
33
-
DNF 80-25
101-125
34
-
HSEF 5-14
40-65
-
35
HSEF 4-10G
49-80
36
-
HSEF 4-10
83-107
37
-
HSEF 4-12
104-173
38
-
HSEF 5-8
54-75
39
-
HSEF 4-10
83-107
40
-
95-164
41
-
HSEF 5-12
136-180
42
-
HSEF 6-16
56-85
-
43
HSEF 6-10
80-113
44
-
HSEF 5-11
70-130
45
-
HSEF 5-12
128-174
46
-
HSEF 6-16
55-81
47
-
HSEF 6-10
75-110
48
-
HSEF 6-12
103-182
49
-
40-63
-
50
51
HSEF 8-20
74-105
-
HSEF 6-12
108-177
52
-
HSEF 8-17A
55-93
-
53
HSEF 8-20G
74-118
-
54
HSEF 8-17A
66-90
-
55
HSEF 10-20
74-80
-
56
3000
HSEF 12-19G
83-115
-
57
3500
HSEF 12-19G
80-113
-
58
4000
HSEF 12-19G
79-111
-
59
4500
HSEF 12-19G
76-109
-
60
2000
2500
Other pump ranges are available on request. Contact Grundfos.
10
4-pole
HSEF 4-12
HSEF 8-15G
1500
Page reference
Pump type
Product range
Fire DNF, Fire HSEF
Pump sets available
Fire DNF and HSEF pump sets are available in the
following versions:
Flex unit:
Compact unit:
Pump and motor mounted on base
frame, and controller for wall
mounting.
Pump, motor and controller mounted
on base frame.
Note: Compact units with DNF
pumps are only available on
request.
FM approval numbers
DNF
Pump type
FM approval number
DNF 65-20
3019994
DNF 65-25
3019994 3022323
DNF 80-20
DNF 80-25
3019994
HSEF
Pump type
FM approval number
HSEF 4-10
3027512
HSEF 4-10G
3027512
HSEF 4-12
2T3A3.AH
HSEF 5-8
2T3A3.AH
HSEF 5-11
3027512
HSEF 5-12
1V3A2.AH
HSEF 5-14
0W6A5.AH
HSEF 6-10
1K7A1.AH
HSEF 6-12
3024553
HSEF 6-16
0P6A1.AH
HSEF 8-15G
1P4A5.AH
HSEF 8-17A
1P2A5.AH
HSEF 8-20
1R0A8.AH
HSEF 8-20G
2R4A7.AH
HSEF 10-20
2R4A7.AH
HSEF 12-19G
´2Z0A7.AH
11
Identification
Fire DNF, Fire HSEF
Nameplates
DNF
The nameplate shows a DNF end-suction pump with a
rated flow rate of 500 gpm (114 m3/h) at 2900 min-1.
See fig. 8. To deliver a rated net pressure of 115 psi,
the actual impeller size is 251 mm.
AV. H. A. CASTELO BRANCO. 630
SAO BERNARDO DO CAMPO - SP - BRASIL
CENTRIFUGAL FIRE PUMPS - END SUCTION 20SV
FM
APPROVED
SERIAL NUMMER
06040002
gal/min AT
RATED NET
PRESSURE
115
psi
NET PRES. AT 150%
RATED CAPACITY
rpm
IMPELLER
DIAMETER
DNF 80-25
CAPACITY
500
MAXIMUM NET
PRES. DEVELOPED
119
RATED
SPEED RPM.
2900
NUMBER OF
STAGES
1
psi
92
251
mm
MAXIMUM POSITIVE
SUCTION PRESSURE
MAXIMUM BRAKE-HORSEPOWER REQUIRED
AT RATED SPEED AT ANY CAPACITY CONDITION
psi
TM03 4621 2406
MODEL
100
psi
hp
71
Fig. 8 Nameplate, DNF end-suction pumps
HSEF
The nameplate shows an HSEF horizontal split-case
pump with a rated flow rate of 170 m 3/h at 2960 min-1.
See fig. 9. To deliver a rated net pressure of 654 kPa
(95 psi), the actual impeller size is 242 mm.
CENTRIFUGAL FIRE PUMP
HORIZONTAL SPLIT - CASE
U
R
L
LISTED
HSEF 4 - 10
Model
1
Stage
242
Imp. DIa. mm
170
3
Rated m / hr
654
Rated kPa
2960
Rated RPM
474
kPa 150%
768
kPa Max.
45
Max. kw
921G
HSEF 4 - 10
Serial
40.6
Rated kw
100
Max. Suction kPa
Indianapolis , IN
Fig. 9 Nameplate, HSEF horizontal split-case pumps
12
TM04 4747 2009
FM
Identification
Fire DNF, Fire HSEF
Type keys
Fire systems
Examples
Fire
DN
F
80
-25
/260
-E
-B
-X
-A
-B
-B
-B
Fire
HSE
F
8
-15
/323
-E
-B
-X
-A
-B
-B
-A
Fire: Fire system
Pump type
DN
HSE
F: The pump is approved for fire protection
Nominal diameter of discharge port (DN)
[mm] or [inch]
Pump housing size
[mm], [cm] or [inch]
Actual impeller diameter
[mm]
Driver
E: Electric motor, 50 Hz
X: Special configuration
Approval/listing, pump
B: FM
Approval, system
X: No approval
Pipe connection
A: ANSI
Control panel
F: For floor mounting
B: For mounting on base frame
W: For wall mounting
Stuffing box
B: SNEA
C: SNFA
Coupling
A: Standard
B: Spacer
Stuffing box
Example
S
N
E
A
S: Packing-type stuffing box
N: Uncooled stuffing box
E: With internal barrier fluid
F: With external barrier fluid
A: PTFE-impregnated fibre packing rings and EPDM
O-ring in pump housing
13
Construction
Fire DNF, Fire HSEF
Sectional drawing, DNF
6
49
20
72a
66a
20
26
96 96a
115a 115c
45b
115
51
86
154
114
76
156a
45a
11a
11
66
20
66a
67
159f
107
155b
88
88a
20
108
77
Fig. 10 Sectional drawing, DNF pump
14
116
106
109
159d
97
97
99
TM03 5505 3706
87
Construction
Fire DNF, Fire HSEF
Material specification, DNF
Material code
Pos.
Description
Material
DIN W.-Nr.
AISI/ASTM/SAE
Cast iron
EN-JS-1030
A536 - 60-40-18
Steel
1.0503
1045
6
Pump housing
11
Impeller key
11a
Key
Steel
1.0503
1045
20
Plug
Stainless steel
1.4301
304
26
Screw
45a
Wear ring
Bronze TM-23
45b
Wear ring
Bronze TM-23
49
Impeller
51
Shaft
66
Washer
66a
Pressure washer
67
Nut
72a
Gasket
76
Steel
Bronze
SAE 40
Steel
1.0503
1045
Stainless steel
1.4401
316
Steel
1.0633
1070
Stainless steel
1.4401
316
Plate
Stainless steel
1.4401
316
77
Cover
Cast iron
EN-JS-1030
A536 - 60-40-18
86
Bearing bracket
Cast iron
EN-JL-1030
A48-30
87
Support
Cast iron
EN-JS-1030
A536 - 60-40-18
88
Screw
88a
Washer
1.4301
304
96
Screw
96a
Pressure washer
97
Plug
1.4301
304
EN-JS-1030
A536 - 60-40-18
Steel
Stainless steel
Steel
Steel
Stainless steel
99
Oil dipstick
106
Packing gland
Polyethylene
107
Packing ring
PTFE-impregnated aramid
108
Lantern ring
Bronze TM-23
Cast iron
109
Gasket
114
Screw
Steel
115
Gland
Steel
1.0044
1020
115a
Nut
Stainless steel
1.4301
304
115c
Pressure washer
EN-JL-1030
A48-30
116
Shaft sleeve
Bronze TM-23
154
Ball bearing
Steel
155b
Gasket
156a
Bearing housing cover
159d
Deflector
NBR elastomer
Cast iron
159f
Seal
NBR elastomer
15
Construction
Fire DNF, Fire HSEF
TM04 4446 1309
Sectional drawing, HSEF
Fig. 11 Sectional drawing, HSEF pump
16
Construction
Fire DNF, Fire HSEF
Material specification, HSEF
Pos.
1A, 1B
Material code
ASTM
Description
Material
Upper and lower casing
Cast iron
ASTM A48 Class 35A
Bronze
ASTM B584 Alloy C87500
Steel
ASTM A193 Grade B7
ASTM B584 Alloy C93200
2
Impeller
6
Pump shaft
7
Casing ring
Bronze
8
Impeller ring (optional)
Bronze
ASTM B584 UNS C83600
13
Packing ring
Graphited/PTFE
John Crane Packing C1065/C1070
14
Shaft sleeve (right)
Bronze
ASTM B584 Alloy C93200
Bronze
ASTM B584 Alloy C93200
14A
Shaft sleeve (left)
16
Inboard ball bearing
17
Packing gland
17B
Gland bolt
(Steel assembly)
(Assembly)
304 stainless steel
ASTM A743 Grade CF-8
Steel
Steel-Open Designation
18
Outboard ball bearing
(Steel assembly)
(Assembly)
18A
Bearing-retaining ring
Steel
Steel-Open Designation
29
Lantern ring (optional)
31
Inboard bearing housing
32
Impeller key
33
Outboard bearing housing
Cast iron
ASTM A48 Class 30
35
Inboard bearing housing cover
Cast iron
ASTM A48 Class 30
37
Outboard bearing housing cover
Cast iron
ASTM A48 Class 30
Neoprene Rubber 65 Shore
PTFE
Teflon
Cast iron
ASTM A48 Class 30
Stainless steel
ASTM A582 Type 303
40A
Inboard deflector
Rubber
40B
Outboard deflector
Rubber
(Assembly)
41
Inboard bearing housing cap
Cast iron
ASTM A48 Class 30
43
Outboard bearing housing cap
Cast iron
ASTM A48 Class 30
46
Coupling key
Steel
ASTM A108 or A26
47
Inboard bearing cover seal
63
Stuffing box bushing
73A
Casing gasket (not shown)
73B
Bearing cover gasket
119A
O-ring, shaft sleeve
123
Bearing end shield
127
Water-seal piping (optional)
169
Bearing housing seal
Steel/rubber assembly
(Assembly)
Bronze
ASTM B584 UNS C83600
Vegetable fibre
ASTM F104, F326128E21M6
Fibre
ASTM D1170, SAE P3415-A
Buna-N rubber
Steel
Steel-Open Designation
Copper with brass fittings
ASTM B75-81a/B 124
Steel/rubber assembly
(Assembly)
17
Construction
Fire DNF, Fire HSEF
Mechanical construction
Bearing bracket and shaft
Pump housing
DNF
The bearing bracket has two sturdy, anti-friction
bearings.
DNF
The cast iron, volute pump housing has axial suction
port and radial discharge port. Flange dimensions are
according to DIN 2533.
The shaft is made of steel, SAE1045.
A rubber deflector on the shaft prevents water from
entering the bearing bracket.
TM03 4599 2306
TM03 0232 4504
The pump housing has a priming hole and a drain hole
closed by plugs.
The bearing bracket is made of cast iron, ASTM A48
CL30.
Fig. 12 Pump housing, DNF
HSEF
The cast iron, volute pump casing has radial suction
and discharge port. Flange dimensions are according
to ANSI B16.1.
The pump casing has a priming hole and a drain hole
closed by plugs.
Fig. 14 Bearing bracket and shaft, DNF
HSEF
The bearing bracket has two sturdy, anti-friction,
grease-lubricated bearings.
The bearing bracket supports are cast integral with the
lower casing half for permanent alignment of bearings
and all rotating parts. The material is minimum class-35
cast iron.
TM03 4600 2306
The shaft is made of steel, ASTM A193.
A rubber deflector on the shaft prevents water from
entering the bearing bracket.
TM03 4598 2306
Fig. 13 Pump casing, HSEF
Fig. 15 Bearing bracket and shaft, HSEF
18
Construction
Fire DNF, Fire HSEF
Stuffing box
Coupling
The stuffing box is sealed with braided packing rings.
The braided material ensures a long service life of
packing rings and protects the pump shaft (sleeve). The
packing rings are fitted symmetrically with parallel
faces to prevent tilting. The packing ring joints are
alternately staggered to aid sealing. Removal of the
upper casing allows for ease of inspection and service
of the stuffing box.
Electrically powered DNF and HSEF pumps are
available with two types of coupling:
• standard
• spacer (Fire DNF only).
TM03 0235 4504
Packing ring materials
PTFE-impregnated fibre packing rings and EPDM
O-rings in pump housing.
Barrier fluid
• DNF: internal barrier fluid (fig. 16).
Fig. 18 Standard coupling
Fig. 16 Sectional view of uncooled stuffing box with
internal barrier liquid for DNF pumps
TM03 0234 4504
TM03 4597 2306
• HSEF: external barrier fluid (fig. 17).
Fig. 19 Spacer coupling
DNF pumps fitted with a spacer coupling can be
serviced without removing the motor from the base
plate and without removing the pump housing from the
pipework. This saves realignment of pump and motor
after service.
The split-case construction of HSEF pump enables
removal and dismantling of the internal pump parts, e.g.
bearings, wear rings, impeller and packing rings,
without disturbing the motor or pipework.
TM03 4596 2306
Impeller
The closed impeller made of bronze has double-curved
blades with smooth surfaces for high efficiency.
Pump type
DNF
HSEF
TM03 4680 2506
Fig. 17 Sectional view of uncooled stuffing box with
external barrier liquid for HSEF pumps
Packing ring dimensions
[inch]
3/8 x 3/8
1/2 x 1/2
9/16 x 9/16
5/8 x 5/8
7/16 x 7/16
Fig. 20 Impeller for a DNF pump
19
Construction
Fire DNF, Fire HSEF
TM03 4681 2506
Test pressure
Fig. 21 Double-suction impeller for an HSEF pump
The impellers are hydraulically balanced and
dynamically balanced together with the shaft.
See fig. 21. The hydraulic balancing compensates for
axial thrust.
The direction of rotation of the impeller is clockwise
when viewed from the motor.
Note: HSEF pumps with counter-clockwise rotation are
available on request.
The impellers are adapted to the duty point required by
the customer by trimming the impeller.
Foundation
Electrically powered Fire DNF pumps and motors are
mounted on a common base plate. See fig. 22.
Before delivery, the pumps are hydrostatically tested
for 5 minutes to 1.5 times the sum of the closed-valve
pressure plus the maximum permissible suction head,
1.5 x (Pmax + Pmax suction), but not less than 250 psi.
Test liquid: Water at 20 °C (68 °F).
Motor
Grundfos electrical fire systems are equipped with the
following motors:
15 - 315 kW
MMG-E motors (sourced HEM EFF2 motors).
355 kW
Siemens motors.
All motors are produced according to IEC 60034.
Insulation class: F.
Enclosure class: IP55.
Note: Only NEMA motors are in compliance with the
NFPA standard. NEMA motors are available on
request.
The tables below show the motors available for
Fire DNF and Fire HSEF pumps.
Standard Hebei motor range (MMG-E), 50 Hz
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
•• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
TM03 0199 0203
Output
P2
[kW]
2-pole
4-pole
18.5
22
37
Electrically powered Fire HSEF pumps and motors are
mounted on a common base frame. See fig. 23.
55
Fire HSEF
75
90
132
160
200
TM04 4461 1309
Fire DNF
45
110
20
2-pole
15
30
Fig. 22 Schematic view of Fire DNF
Fig. 23 Schematic view of Fire HSEF
Standard motor range, 50 Hz
250
315
355
Fire HSEF
Operating conditions
Fire DNF, Fire HSEF
Location
The pump set is designed for installation in a nonaggressive and non-explosive atmosphere.
The relative air humidity must not exceed 95 %.
Ambient temperature and altitude
The ambient temperature must not exceed +40 °C
(104 °F).
If the ambient temperature exceeds +40 °C (104 °F), or
if the motor is installed more than 1000 metres (3280 ft)
above sea level, the motor must not be fully loaded due
to the low density and consequently low cooling effect
of the air. In such cases, it may be necessary to use a
motor with a higher output. See fig. 24.
P2
[%]
100
90
80
60
50
20 25 30 35 40 45 50 55 60 65 70 75 80
t [°C]
1000
2250
3500
m
TM00 2189 1598
70
Fig. 24 Relationship between motor output (P2) and
ambient temperature/altitude
Inlet pressure
Maximum inlet pressure
The inlet pressure is limited by the maximum operating
pressure of the pump and the packing material.
Minimum inlet pressure
Refer to the latest National Fire Protection Association
pamphlet 20 (NFPA 20) for rules and exceptions.
21
Installation
Fire DNF, Fire HSEF
Piping
Alignment
Make sure that the pump housing is not stressed by the
pipework. Comply with the pump's maximum forces and
moments allowed.
In a complete pump unit assembled and supplied from
factory, the coupling halves have been accurately
aligned. Alignment is made by inserting shims under
the pump and motor mounting surfaces, as required.
The suction and discharge pipes must be of an
adequate size, taking the pump inlet pressure into
account.
The pump/motor alignment may be affected during
transport. Always check the alignment after the pump
has been installed.
Refer to the rules and regulations of NFPA 20.
Install the pipes so that air locks are avoided, especially
on the suction side of the pump. See fig. 25.
If misalignment has occurred due to radial or angular
shifting, realign by inserting/removing shims under the
supporting feet of the pump or the motor.
Take care to align carefully as this will increase the
working life of the coupling, bearings and stuffing
boxes.
TM00 2263 3393
Note: Check the final alignment when the pump has
obtained its operating temperature under normal
operating conditions.
Fig. 25 Pipe sections
Fit isolating valves on either side of the pump to avoid
having to drain the system if the pump needs to be
cleaned or repaired.
TM03 2998 4006
Make sure the pipes are adequately supported as close
to the pump as possible, both on the suction and on the
discharge side. The counter-flanges should lie true
against the pump flanges without being stressed;
otherwise, the pump will be damaged.
Fig. 26 Example of piping, Fire DNF
22
Motor data
Fire DNF, Fire HSEF
GR7350
The tables below show technical data of 2- and 4-pole
motors for Fire DNF and Fire HSEF pumps.
Fig. 27 MMG motor, model E
Motor range, 2-pole, 50 Hz
P2
[kW]
I1/1
[A]
η
[%]
Cos ϕ 1/1
15
26.5/15.2
91.0
MMG 160L-E
18.5
32.5/18.8
MMG 180M-E
22
MMG 200LA-E
n
[min-1]
I Start
0.87
2940
5.8
91.6
0.89
2940
6.5
39.5/22.8
91.0
0.89
2950
7.4
30
57.5/33.0
92.2
0.88
2960
7.0
MMG 200LB-E
37
65.0/37.5
92.0
0.89
2960
7.6
MMG 225M-E
45
78.0/45.0
93.5
0.89
2980
7.4
55
96.5/55.5
93.0
0.90
2960
7.9
MMG 280S-E
75
130/75.0
94.0
0.89
2970
6.6
MMG 280M-E
90
154/89.0
95.0
0.90
2980
7.2
MMG 315S-E
110
188/108
94.0
0.90
2980
7.2
MMG 315M-E
132
222/128
95.0
0.90
2980
7.5
MMG 315LA-E
160
270/156
95.7
0.91
2980
6.0
MMG 315LB-E
200
330/190
95.0
0.92
2980
5.8
P2
[kW]
I1/1
[A]
η
[%]
Cos ϕ 1/1
n
[min-1]
I Start
MMG 180M-E
18.5
33.5/19.4
91.2
0.86
1465
7.6
MMG 180L-E
22
39.0/22.6
91.4
0.86
1465
7.8
MMG 200L-E
30
53.5/31.0
91.5
0.88
1470
7.5
MMG 225S-E
37
71.0/41.0
92.0
0.89
1480
6.9
MMG 225M-E
45
78.0/45.0
92.5
0.89
1480
7.5
MMG 250M-E
55
95.0/55.0
93.0
0.89
1480
7.5
75
128/74.0
94.5
0.87
1480
7.4
90
150/86.5
94.0
0.88
1480
7.5
110
192/110
94.5
0.91
1490
7.3
Frame size
Voltage
[V]
MMG 160MB-E
MMG 250M-E
3 x 380-415 Δ/
660-690 Y
------------I
1⁄1
Motor range, 4-pole, 50 Hz
Frame size
MMG 280S-E
MMG 280M-E
Voltage
[V]
3 x 380-415 Δ/
660-690 Y
MMG 315S-E
------------I1 ⁄ 1
MMG 315M-E
132
226/130
95.0
0.89
1490
6.7
MMG 315LA-E
160
270/156
95.0
0.89
1490
6.7
MMG 315LB-E
200
340/196
95.5
0.89
1490
5.5
MMG 355M-E
250
410/236
95.5
0.91
1490
6.4
MMG 355L-E
315
525/300
96.0
0.89
1490
6.8
355
610-610/355-355
96.3
0.87
1490
6.5
Siemens 355
3 x 380-420 Δ/
660-725Y
23
Bare shaft pumps
Fire DNF, Fire HSEF
DNF
d
DNs
DNd
m2
TM03 4784 2806
b
w
n3
m1
n2
n1
Fig. 28 DNF bare shaft pump
DNs
Pump type
DNF 65-20
DNF 65-25
DNF 80-20
DNF 80-25
24
DNd
[mm]
100
65
125
80
Pump [mm]
a
100
125
125
f
500
500
Supporting feet [mm]
h1
h2
b
m1
m2
n1
n2
180
225
65
200
250
80
125
95
320
250
160
120
360
280
180
250
65
225
280
80
125
95
345
280
160
120
400
315
n3
w
110
370
110
370
Shaft [mm]
s1
M12
M16
M12
M16
s2
d
l
M12
32
80
M12
32
80
x
Pump
moment
of inertia
[kgm 2]
Weight
[kg]
100
0.0963
71
140
0.2357
69
140
0.1397
72
0.2476
82
Bare shaft pumps
Fire DNF, Fire HSEF
HSEF
Suction port
TM04 4447 1309
Discharge port
Fig. 29 HSEF bare shaft pump
Pump type
DNs DNd
[inch]
Pump [mm]
a
f
af
s
d
sd
h1
h2
Supporting feet [mm]
hs
hd
ss
dd
qs qd
n1
n2
m1
m2
e1
b
øc
HSEF 4-10
5
4
305 406
711
279 279
559
279 200 165 165 311 298 35 32
368 152
330
140
25
86
19
HSEF 4-10G
5
4
305 406
711
279 279
559
279 200 165 165 311 298 35 32
368 152
330
140
25
86
19
HSEF 4-12
5
4
305 406
711
318 260
578
330 219 165 197 311 330 35 32
368 152
330
140
25
86
19
HSEF 5-8
6
5
327 416
743
305 305
610
279 188 146 146 292 286 25 24
368 152
330
140
25
86
19
HSEF 5-11
6
5
330 406
737
330 305
635
305 203 171 171 337 318 37 35
406 175
305
127
25
89
19
HSEF 5-12
6
5
330 406
737
356 330
686
356 246 203 216 368 362 37 35
400 175
305
127
25
86
19
HSEF 5-14
6
5
343 438
781
330 356
686
330 244 178 216 324 362 25 35
476 210
381
165
25
86
19
HSEF 6-10
8
6
330 406
718
330 260
591
356 206 191 171 368 337 28 37
368 152
330
140
25
86
19
HSEF 6-12
8
6
375 483
857
419 305
724
381 254 194 210 391 375 41 37
368 152
457
197
28
86
22
HSEF 6-16
8
6
381 476
857
406 457
864
381 289 232 273 409 438 28 37
476 203
432
191
25
86
19
HSEF 8-15G
10
8
375 483
857
449 406
856
406 305 229 254 457 451 48 41
457 191
483
210
28
86
22
HSEF 8-17A
10
8
394 502
895
483 381
864
457 353 254 305 483 502 48 41
559 241
483
210
28 102 25
895
483 381
864
HSEF 8-17Q
10
8
394 502
457 353 254 305 483 502 48 41
559 241
483
210
28 102 25
HSEF 8-20
10
8
476 610 1086 508 533 1041 457 378 279 330 489 527 30 41
559 241
483
210
28 102 25
HSEF 8-20G
10
8
476 610 1086 508 533 1041 457 378 279 330 489 527 30 41
559 241
483
210
28 102 25
HSEF 10-20
12
10
521 660 1181 559 584 1143 495 403 279 356 527 584 32 48
558 216
660
292
32 102 25
HSEF 12-19G
14
12
765 914 1679 610 711 1321 533 371 305 343 546 610 35 32
813 330
813
368
51 152 32
25
Bare shaft pumps
Fire DNF, Fire HSEF
HSEF
Suction port
TM04 4447 1309
Discharge port
Fig. 30 HSEF bare shaft pump
Pump type
DNs DNd
[inch]
Shaft
[mm]
l
v
Keyway
[inch]
Weight
[kg]
HSEF 4-10
5
4
51
0.312 x 0.156
143
5
4
1.3750 1)
1.3750 1)
95
HSEF 4-10G
95
51
0.312 x 0.156
143
HSEF 4-12
5
4
1.3750
2)
95
51
0.312 x 0.156
171
HSEF 5-8
6
5
1.3750 2)
83
57
0.312 x 0.156
143
HSEF 5-11
6
5
1.5625 1)
70
51
0.375 x 0.188
172
HSEF 5-12
6
5
1.5625 1)
70
51
0.375 x 0.188
257
HSEF 5-14
6
5
1.3750 2)
86
51
0.312 x 0.156
229
HSEF 6-10
8
6
1.5625 1)
70
51
0.375 x 0.188
204
HSEF 6-12
8
6
1.8750 1) 102
76
0.500 x 0.250
340
HSEF 6-16
8
6
1.5625 1)
51
0.375 x 0.188
313
89
HSEF 8-15G
10
8
0.500 x 0.250
386
10
8
1.8750 1) 102
1.8750 1) 102
76
HSEF 8-17A
76
0.500 x 0.250
458
HSEF 8-17Q
10
8
1.8750 1) 102
76
0.500 x 0.250
458
HSEF 8-20
10
8
2.2500 1) 124
102
0.500 x 0.250
603
HSEF 8-20G
10
8
2.2500 1) 124
102
0.500 x 0.250
603
HSEF 10-20
12
10
2.5000 1) 127
95
0.625 x 0.312
907
HSEF 12-19G
14
12
3.0000 1) 121
121
0.750 x 0.375
1489
1)
2)
26
db
[inch]
Tolerance: + 0.000 / – 0.001.
Tolerance: + 0.0000 / – 0.0005.
Bare shaft pumps
Fire DNF, Fire HSEF
Flange dimensions
DNF
HSEF
D
D
K
K
DN
DN
Fig. 31 Flange for DNF pumps
Fig. 32 Flange for HSEF pumps
Flange dimensions to DIN 2533
DNs and DNd
65
dz
TM03 4591 2306
dz
q
TM03 4592 2306
b
f
d4
Flange dimensions to ANSI B 16.1
Flange [mm]
D
K
b
f
d4
dz
185
145
20
3
122
4 x 18
80
200
160
22
3
138
8 x 18
100
220
180
24
3
158
8 x 18
125
250
210
26
3
188
8 x 18
DNs
Number of
class 125
holes
[inch]
Flange [mm]
D
K
q*
dz
4
8
228.6
190.5
19.0
5
8
254.0
215.9
22.2
6
8
279.4
241.3
22.2
8
8
342.9
298.5
22.2
10
12
406.4
362.0
25.4
12
12
482.6
431.8
25.4
14
12
533.4
476.3
25.4
D
K
DNd
Number of
class 250
holes
[inch]
Flange [mm]
q*
dz
4
8
254.0
200.2
5
8
279.4
235.0
22.2
22.2
6
12
317.5
269.7
22.2
8
12
381.0
330.2
25.4
10
16
444.5
387.4
28.58
12
16
520.7
450.9
31.75
* Dimensions of "qs" and "qd", see page 25.
27
Curve charts
Fire DNF, Fire HSEF
How to read the curve charts
QH curve of the individual pump
The solid line represents the rated flow
rate at which the pump has been FMapproved and UL-listed.
Size of impeller
H
[m]
p
[psi]
DNF 80-20
90
2-pole, 50 Hz
/210
60
Pump type and
rated pump speed
/205
80
50
ISO 9906 Annex A
/200
70
The broken line represents the maximum
permissible flow rate at
which the pump has been
FM-approved or UL-listed.
60
40
50
30
40
20
30
20
0
100
0
P2
[kW]
P2
[hp]
30
40
200
300
40
400
80
500
600
120
700
800
Q [US GPM] The power curve indicates
160
200
Q [m³/h]
pump input power, P2, of
the individual pump.
/210
/205
25
/200
35
30
20
25
15
20
The eta curve indicates
the pump efficiency of the
individual pump.
15
0
100
200
300
400
500
600
700
800
Q [US GPM]
Eta
[%]
80
70
60
/205
50
/210
/200
30
20
0
28
100
200
300
400
500
600
700
800
Q [US GPM]
TM02 9834 5004
40
Curve charts
Fire DNF, Fire HSEF
Guide
The tables above the curve charts on the following
pages show these data:
• FM-approved pressure range
• Rated motor power, P2, within a specific pressure
range.
FM-approved pressure range
Example: DNF 80-20, 500 gpm.
Pressure range Rated power
[psi]
[kW]
64-70
30
71-72
37
Curve conditions
Selection of pumps
The guidelines below apply to the performance curves
shown in the curve charts, pages 30 to 60.
• Tolerances according to ISO 9906, Annex A.
• The curves show pump performance with different
impeller diameters at the rated speed.
• The curves apply to the pumping of water at a temperature of + 20 °C (68 °F) and a kinematic viscosity
of 1 mm²/s (1 cSt).
Calculation of total head
The total pump head consists of the height difference
between the measuring points + the differential head +
the dynamic head.
H
total
= H
geo
+H
stat
+H
dyn
Hgeo: Height difference between measuring points.
Hstat: Differential head between the suction and the
discharge side of the pump.
Hdyn: Calculated values based on the velocity of the
pumped water on the suction and the discharge
side of the pump.
Note: Selection of the pump is based on the head given
by the customer.
Performance tests
The requested duty point of every pump is tested
according to ISO 9906, Annex A. The curve of the
performance test is supplied with the pump.
If the customer requires either more points on the curve
to be checked or certain minimum performances or
certificates, individual measurements must be made.
29
Performance curves, DNF
DNF 65-20
250 GPM, 66-80 psi
250 GPM, 66-80 psi
Pressure range Rated power
[psi]
[kW]
66-70
18.5
75-80
22
H
[m]
p
[psi]
DNF 65-20
90
60
80
/208
2-pole, 50 Hz
/202
ISO 9906 Annex A
/195
50
70
/190
60
40
50
30
20
40
30
20
10
10
0
0
0
50
0
P2
[kW]
100
150
20
200
40
250
300
60
350
400
80
450
500
100
Q [US GPM]
120
P2
[hp]
Q [m³/h]
30
20
/208
/202
/195
/190
25
15
10
20
15
10
5
5
0
50
100
150
200
250
300
350
400
450
500
Q [US GPM]
Eta
[%]
70
60
50
40
20
/190
/195 /202
10
0
30
/208
50
100
150
200
250
300
350
400
450
500
Q [US GPM]
TM02 9828 2606
30
Performance curves, DNF
DNF 65-25
250 GPM, 116-129 psi
250 GPM, 116-129 psi
Pressure range Rated power
[psi]
[kW]
116-120
37
125-129
45
H
[m]
100
p
[psi]
DNF 65-25
140
2-pole, 50 Hz
ISO 9906 Annex A
90
/260
/258
130
/253
/250
120
80
110
70
100
90
60
80
50
70
0
P2
[kW]
P2
[hp]
50
0
100
150
20
200
40
250
300
60
350
400
80
450
100
60
50
20
Q [m³/h]
/260
/258
/253
/250
40
30
Q [US GPM]
40
30
20
10
10
0
0
50
100
150
200
250
300
350
400
450
Q [US GPM]
Eta
[%]
60
/260
/258
/253
50
/250
40
30
20
10
0
50
100
150
200
250
300
350
400
450
Q [US GPM]
TM03 4690 2606
0
31
Performance curves, DNF
DNF 65-25
300 GPM, 120-127 psi
300 GPM, 120-127 psi
Pressure range Rated power
[psi]
[kW]
120
37
125-127
45
H
[m]
100
p
[psi]
DNF 65-25
140
2-pole, 50 Hz
/260
90
130
ISO 9906 Annex A
/255
/250
120
80
110
70
100
90
60
80
50
70
60
0
50
0
P2
[kW]
100
150
20
200
40
250
300
60
350
400
80
450
100
Q [US GPM]
120
P2
[hp]
Q [m³/h]
/260
/255
/250
50
30
500
40
30
20
20
10
10
0
50
100
150
200
250
300
350
400
450
500
Q [US GPM]
Eta
[%]
60
/250
50
/260
/255
40
20
10
0
32
50
100
150
200
250
300
350
400
450
500
Q [US GPM]
TM02 9801 5004
30
Performance curves, DNF
DNF 80-20
500 GPM, 64-72 psi
500 GPM, 64-72 psi
Pressure range Rated power
[psi]
[kW]
64-70
30
72
37
H
[m]
p
[psi]
DNF 80-20
90
2-pole, 50 Hz
/210
60
/205
80
50
ISO 9906 Annex A
/200
70
60
40
50
30
40
20
30
20
0
100
0
P2
[kW]
P2
[hp]
30
40
200
300
40
400
80
500
600
120
700
800
Q [US GPM]
160
200
Q [m³/h]
/210
/205
25
/200
35
30
20
25
20
15
0
100
200
300
400
500
600
700
800
Q [US GPM]
Eta
[%]
80
70
60
/205
50
/210
/200
40
30
20
0
100
200
300
400
500
600
700
800
Q [US GPM]
TM02 9834 5004
15
33
Performance curves, DNF
DNF 80-25
500 GPM, 101-125 psi
500 GPM, 101-125 psi
Pressure range Rated power
[psi]
[kW]
101-120
55
125
75
H
[m]
90
p
[psi]
120
80
110
70
DNF 80-25
/260
/256
/251
/246
/242
/240
130
2-pole, 50 Hz
ISO 9906 Annex A
100
90
60
80
50
40
70
60
50
30
40
30
0
P2
[kW]
P2
[hp]
60
80
50
0
100
20
200
40
300
60
400
80
500
100
120
600
140
700
160
800
180
Q [US GPM]
200
Q [m³/h]
/260
/256
/251
/246
/242
70
60
/240
40
50
30
20
40
30
20
0
100
200
300
400
500
600
700
800
Q [US GPM]
Eta
[%]
70
60
50
/240
/242
/246
30
/260
/256
/251
20
10
0
34
100
200
300
400
500
600
700
800
Q [US GPM]
TM03 4687 2606
40
Performance curves, HSEF
HSEF 5-14
500 GPM, 40-65 psi
500 GPM, 40-65 psi
Pressure range Rated power
[psi]
[kW]
40-41
18.5
42-49
22
50-65
30
H
[m]
p
[psi]
HSEF 5-14
90
n nom = 1460 min-1
60
ISO 9906 Annex A
80
50
70
/355
60
40
/316
50
30
20
/288
40
/285
30
20
10
10
0
0
0
P2
[kW]
P2
[hp]
30
40
100
0
200
300
400
50
500
600
100
700
150
Q [US GPM]
Q [m³/h]
/355
30
20
/285
20
10
10
0
0
100
200
300
400
500
600
700
Q [US GPM]
Eta
[%]
80
/355
70
60
50
40
30
0
100
200
300
400
500
600
700
Q [US GPM]
TM04 4209 1009
0
35
Performance curves, HSEF
HSEF 4-10G
500 GPM, 49-80 psi
500 GPM, 49-80 psi
Pressure range Rated power
[psi]
[kW]
49-57
18.5
58-70
22
71-80
30
H
[m]
p
[psi]
70
100
HSEF 4-10G
n nom = 2950 min-1
/226
ISO 9906 Annex A
90
60
/213
80
50
70
/193
/179
60
40
50
30
40
20
30
20
0
P2
[kW]
P2
[hp]
30
40
100
0
200
300
400
50
500
600
100
700
150
Q [US GPM]
Q [m³/h]
/226
30
20
/179
20
10
10
0
0
0
100
200
300
400
500
600
700
Q [US GPM]
Eta
[%]
80
/226
70
60
40
30
0
36
100
200
300
400
500
600
700
Q [US GPM]
TM04 4201 1009
50
Performance curves, HSEF
HSEF 4-10
500 GPM, 83-107 psi
500 GPM, 83-107 psi
Pressure range Rated power
[psi]
[kW]
83-95
45
96-107
55
H
[m]
90
p
[psi]
140
HSEF 4-10
130
n nom = 2950 min-1
/253
ISO 9906 Annex A
120
80
70
/242
110
/229
100
90
60
80
50
40
70
60
50
30
20
40
30
20
0
P2
[kW]
50
P2
[hp]
100
0
200
300
50
400
500
600
100
700
800
150
900
1000
200
Q [US GPM]
250
70
Q [m³/h]
/253
60
/229
40
50
20
40
30
20
0
100
200
300
400
500
600
700
800
900
1000
Q [US GPM]
Eta
[%]
80
/253
70
60
50
40
30
0
100
200
300
400
500
600
700
800
900
1000
Q [US GPM]
TM04 4202 1009
30
37
Performance curves, HSEF
HSEF 4-12
500 GPM, 104-173 psi
500 GPM, 104-173 psi
Pressure range Rated power
[psi]
[kW]
104-128
55
129-155
75
156-173
90
H
[m]
p
[psi]
190
HSEF 4-12
/303
130
n nom = 2950 min-1
180
120
110
ISO 9906 Annex A
170
/288
160
150
100
140
90
130
/258
120
80
70
/237
110
100
90
60
80
50
70
60
0
P2
[kW]
P2
[hp]
100
0
200
300
400
50
500
600
100
700
800
150
Q [US GPM]
200
Q [m³/h]
80
100
60
/303
80
60
/237
40
40
20
20
0
100
200
300
400
500
600
700
800
Q [US GPM]
Eta
[%]
80
/303
70
60
40
30
0
38
100
200
300
400
500
600
700
800
Q [US GPM]
TM04 4204 1009
50
Performance curves, HSEF
HSEF 5-8
750 GPM, 54-75 psi
750 GPM, 54-75 psi
Pressure range Rated power
[psi]
[kW]
54-63
30
64-75
37
H
[m]
p
[psi]
70
100
HSEF 5-8
n nom = 2950 min-1
ISO 9906 Annex A
90
/203
60
80
/190
50
70
/181
60
40
50
30
40
20
30
20
0
P2
[kW]
P2
[hp]
100
0
200
300
50
400
500
600
100
700
800
150
900
1000
200
Q [US GPM]
250
Q [m³/h]
40
/203
50
30
40
/181
30
20
20
10
10
0
100
200
300
400
500
600
700
800
900
1000
Q [US GPM]
Eta
[%]
80
/203
70
60
40
30
0
100
200
300
400
500
600
700
800
900
1000
Q [US GPM]
TM04 4206 1009
50
39
Performance curves, HSEF
HSEF 4-10
750 GPM, 83-107 psi
750 GPM, 83-107 psi
Pressure range Rated power
[psi]
[kW]
83-95
45
96-107
55
H
[m]
p
[psi]
HSEF 4-10
140
90
n nom = 2950 min-1
130
/254
ISO 9906 Annex A
120
80
70
/242
110
/229
100
90
60
80
50
40
70
60
50
30
20
40
30
20
0
P2
[kW]
50
P2
[hp]
100
0
200
300
50
400
500
600
100
700
800
150
900
1000
200
Q [US GPM]
250
70
Q [m³/h]
/254
60
/229
40
50
30
20
40
30
20
0
100
200
300
400
500
600
700
800
900
1000
Q [US GPM]
Eta
[%]
80
/254
70
60
40
30
0
40
100
200
300
400
500
600
700
800
900
1000
Q [US GPM]
TM04 4203 1009
50
Performance curves, HSEF
HSEF 4-12
750 GPM, 95-164 psi
750 GPM, 95-164 psi
Pressure range Rated power
[psi]
[kW]
95-114
55
115-140
75
141-164
90
H
[m]
p
[psi]
140
200
HSEF 4-12
n nom = 2950 min-1
/307
ISO 9906 Annex A
180
120
/288
160
100
140
/258
120
/237
80
100
60
40
80
60
40
20
20
0
P2
[kW]
P2
[hp]
100
0
200
300
50
400
500
600
100
700
800
150
900
1000
200
Q [US GPM]
250
Q [m³/h]
120
80
/307
100
60
40
80
/237
60
40
20
20
0
100
200
300
400
500
600
700
800
900
1000
Q [US GPM]
Eta
[%]
80
70
/307
60
40
30
0
100
200
300
400
500
600
700
800
900
1000
Q [US GPM]
TM04 4205 1009
50
41
Performance curves, HSEF
HSEF 5-12
750 GPM, 136-180 psi
750 GPM, 136-180 psi
Pressure range Rated power
[psi]
[kW]
136-140
90
141-167
110
168-180
132
H
[m]
140
p
[psi]
210
HSEF 5-12
200
n nom = 2950 min-1
ISO 9906 Annex A
190
/300
180
/288
130
120
110
170
160
/268
150
100
90
/266
140
130
120
80
70
110
100
90
0
P2
[kW]
100
P2
[hp]
100
0
200
300
50
400
500
600
100
700
800
150
900
1000
200
Q [US GPM]
250
Q [m³/h]
/300
140
120
80
/266
100
60
40
80
60
40
20
20
0
100
200
300
400
500
600
700
800
900
1000
Q [US GPM]
0
100
200
300
400
500
600
700
800
900
1000
Q [US GPM]
Eta
[%]
80
70
60
40
30
42
TM04 4208 1009
50
Performance curves, HSEF
HSEF 6-16
1000 GPM, 56-85 psi
1000 GPM, 56-85 psi
Pressure range Rated power
[psi]
[kW]
56-67
45
68-79
55
79-85
75
H
[m]
p
[psi]
70
100
HSEF 6-16
n nom = 1460 min-1
ISO 9906 Annex A
/422
90
/409
60
80
/383
50
70
/357
60
40
50
30
40
30
P2
[kW]
P2
[hp]
0
200
0
50
400
100
600
800
150
1000
200
1200
250
1400
300
1600
350
400
Q [m³/h]
/422
80
50
Q [US GPM]
70
60
40
50
30
20
/357
40
30
20
10
0
200
400
600
800
1000
1200
1400
1600
Q [US GPM]
Eta
[%]
90
/422
80
70
60
50
40
30
0
200
400
600
800
1000
1200
1400
1600
Q [US GPM]
TM04 4214 1009
10
43
Performance curves, HSEF
HSEF 6-10
1000 GPM, 80-113 psi
1000 GPM, 80-113 psi
Pressure range Rated power
[psi]
[kW]
80-100
75
101-113
90
H
[m]
p
[psi]
HSEF 6-10
140
90
n nom = 2950 min-1
130
ISO 9906 Annex A
/238
120
80
/228
110
70
100
/206
90
60
80
50
40
70
60
50
30
40
30
P2
[kW]
P2
[hp]
0
200
0
50
400
100
600
800
150
1000
200
1200
250
1400
300
1600
350
120
Q [US GPM]
400
Q [m³/h]
/238
80
100
60
40
80
/206
60
40
20
20
0
200
400
600
800
1000
1200
1400
1600
Q [US GPM]
Eta
[%]
90
/238
80
70
60
40
30
0
44
200
400
600
800
1000
1200
1400
1600
Q [US GPM]
TM04 4210 1009
50
Performance curves, HSEF
HSEF 5-11
1000 GPM, 70-130 psi
1000 GPM, 70-130 psi
Pressure range Rated power
[psi]
[kW]
70-73
45
74-90
55
91-119
75
120-130
90
H
[m]
110
100
p
[psi]
160
HSEF 5-11
150
n nom = 2950 min-1
/265
ISO 9906 Annex A
140
/256
90
130
120
80
70
110
/229
100
90
/212
80
/209
60
50
40
70
60
50
30
40
30
0
P2
[kW]
P2
[hp]
100
0
200
300
50
400
500
600
100
700
800
150
900 1000 1100 1200 1300 1400
200
250
300
120
Q [US GPM]
Q [m³/h]
/265
80
100
60
40
80
60
/209
40
20
20
0
0
100
200
300
400
500
600
700
800
900 1000 1100 1200 1300 1400
Q [US GPM]
Eta
[%]
/265
80
70
60
50
40
30
0
100
200
300
400
500
600
700
800
900 1000 1100 1200 1300 1400
Q [US GPM]
TM04 4207 1009
0
45
Performance curves, HSEF
HSEF 5-12
1000 GPM, 128-174 psi
1000 GPM, 128-174 psi
Pressure range Rated power
[psi]
[kW]
128-155
110
156-174
132
H
[m]
p
[psi]
140
HSEF 5-12
/304
n nom = 2950 min-1
190
130
120
110
ISO 9906 Annex A
/288
180
170
160
/269
150
100
140
90
130
120
80
70
110
100
90
60
80
50
70
60
0
P2
[kW]
P2
[hp]
0
100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600
50
100
150
200
250
300
160
100
350
Q [US GPM]
400
Q [m³/h]
/304
140
120
80
/269
100
60
40
80
60
40
20
20
0
100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600
Q [US GPM]
Eta
[%]
80
/304
70
60
40
30
0
46
100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600
Q [US GPM]
TM04 4226 1009
50
Performance curves, HSEF
HSEF 6-16
1250 GPM, 55-81 psi
1250 GPM, 55-81 psi
Pressure range Rated power
[psi]
[kW]
55-61
45
62-74
55
75-81
75
H
[m]
p
[psi]
70
100
HSEF 6-16
n nom = 1460 min-1
ISO 9906 Annex A
/422
90
/409
60
80
/383
50
70
/367
60
40
50
30
40
30
P2
[kW]
P2
[hp]
0
200
0
50
400
100
600
800
150
1000
200
1200
250
1400
300
1600
350
1800
400
Q [US GPM]
Q [m³/h]
/422
80
50
70
60
40
/367
50
30
20
40
30
20
10
0
200
400
600
800
1000
1200
1400
1600
1800
Q [US GPM]
Eta
[%]
90
80
/367
70
60
50
40
30
0
200
400
600
800
1000
1200
1400
1600
1800
Q [US GPM]
TM04 4215 1009
10
47
Performance curves, HSEF
HSEF 6-10
1250 GPM, 75-110 psi
1250 GPM, 75-110 psi
Pressure range Rated power
[psi]
[kW]
75-96
75
97-108
90
109-110
110
H
[m]
p
[psi]
HSEF 6-10
140
90
n nom = 2950 min-1
130
120
/241
80
/228
110
70
ISO 9906 Annex A
/243
100
/211
90
60
80
50
40
70
60
50
30
40
30
P2
[kW]
P2
[hp]
0
200
0
50
400
100
600
800
150
1000
200
1200
250
1400
300
1600
350
1800
400
Q [US GPM]
Q [m³/h]
/243
120
80
100
60
40
/211
80
60
40
20
20
0
200
400
600
800
1000
1200
1400
1600
1800
Q [US GPM]
Eta
[%]
90
/243
80
70
60
40
30
0
48
200
400
600
800
1000
1200
1400
1600
1800
Q [US GPM]
TM04 4211 1009
50
Performance curves, HSEF
HSEF 6-12
1250 GPM, 103-182 psi
1250 GPM, 103-182 psi
Pressure range Rated power
[psi]
[kW]
103-106
110
107-137
132
138-164
160
165-182
200
H
[m]
p
[psi]
HSEF 6-12
220
140
n nom = 2950 min-1
200
/305
180
/291
ISO 9906 Annex A
120
160
/264
100
140
/244
/235
120
80
100
60
40
80
60
40
P2
[kW]
P2
[hp]
0
200
0
50
400
100
600
800
150
1000
200
1200
250
1400
300
1600
350
1800
400
Q [US GPM]
Q [m³/h]
240
/305
150
200
160
100
/235
120
80
40
0
200
400
600
800
1000
1200
1400
1600
1800
Q [US GPM]
Eta
[%]
80
/305
70
60
50
40
30
0
200
400
600
800
1000
1200
1400
1600
1800
Q [US GPM]
TM04 4212 1009
50
49
Performance curves, HSEF
HSEF 8-15G
1500 GPM, 40-63 psi
1500 GPM, 40-63 psi
Pressure range Rated power
[psi]
[kW]
40-45
45
46-55
55
56-63
75
H
[m]
p
[psi]
HSEF 8-15G
90
n nom = 1460 min-1
60
ISO 9906 Annex A
80
50
/387
70
/356
60
40
/323
50
30
20
/310
40
30
20
10
10
0
0
P2
[kW]
P2
[hp]
60
80
0
200
0
50
400
100
600
150
800
200
1000
1200
250
1400
300
1600
350
1800
400
2000
450
2200
500
Q [US GPM]
550
Q [m³/h]
/387
60
40
/310
40
20
20
0
0
0
200
400
600
800
1000
1200
1400
1600
1800
2000
2200
Q [US GPM]
Eta
[%]
90
/387
80
70
60
40
30
0
50
200
400
600
800
1000
1200
1400
1600
1800
2000
2200
Q [US GPM]
TM04 4216 1009
50
Performance curves, HSEF
HSEF 8-20
1500 GPM, 74-105 psi
1500 GPM, 74-105 psi
Pressure range Rated power
[psi]
[kW]
74-86
90
87-103
110
104-105
132
H
[m]
90
p
[psi]
HSEF 8-20
130
n nom = 1470 min-1
120
110
70
ISO 9906 Annex A
/482
80
/478
100
/442
90
60
/408
80
50
40
70
60
50
30
20
40
30
20
0
P2
[kW]
P2
[hp]
120
160
200
0
400
600
100
800
1000
1200
200
1400
1600
300
1800
2000
400
2200
Q [US GPM]
500
Q [m³/h]
/482
120
80
/408
80
40
40
0
0
200
400
600
800
1000
1200
1400
1600
1800
2000
2200
Q [US GPM]
Eta
[%]
90
/482
80
70
60
50
40
30
0
200
400
600
800
1000
1200
1400
1600
1800
2000
2200
Q [US GPM]
TM04 4218 1009
0
51
Performance curves, HSEF
HSEF 6-12
1500 GPM, 108-177 psi
1500 GPM, 108-177 psi
Pressure range Rated power
[psi]
[kW]
108-129
132
130-156
160
157-177
200
H
[m]
p
[psi]
HSEF 6-12
220
140
n nom = 2950 min-1
200
/307
180
/291
ISO 9906 Annex A
120
160
/264
100
140
/245
120
80
100
60
40
80
60
40
P2
[kW]
P2
[hp]
0
200
0
50
400
100
600
150
800
200
1000
1200
250
1400
300
1600
350
1800
400
2000
450
Q [US GPM]
500
Q [m³/h]
/307
240
150
200
160
/245
100
120
50
80
40
0
200
400
600
800
1000
1200
1400
1600
1800
2000
Q [US GPM]
Eta
[%]
80
70
/307
60
40
30
0
52
200
400
600
800
1000
1200
1400
1600
1800
2000
Q [US GPM]
TM04 4213 1009
50
Performance curves, HSEF
HSEF 8-17A
2000 GPM, 55-93 psi
2000 GPM, 55-93 psi
Pressure range Rated power
[psi]
[kW]
55-57
75
58-66
90
67-77
110
78-86
132
87-93
160
H
[m]
p
[psi]
HSEF 8-17A
120
n nom = 1460 min-1
80
110
70
ISO 9906 Annex A
100
/457
/431
90
60
/408
80
50
40
70
/382
60
/357
/350
50
30
20
40
30
20
0
P2
[kW]
P2
[hp]
0
400
100
800
200
1200
1600
300
2000
400
2400
500
2800
600
3200
700
200
120
80
Q [US GPM]
800
Q [m³/h]
/457
160
120
/350
80
40
40
0
0
400
800
1200
1600
2000
2400
2800
3200
Q [US GPM]
Eta
[%]
90
/457
80
70
60
50
40
30
0
400
800
1200
1600
2000
2400
2800
3200
Q [US GPM]
TM04 4217 1009
0
53
Performance curves, HSEF
HSEF 8-20G
2000 GPM, 74-118 psi
2000 GPM, 74-118 psi
Pressure range Rated power
[psi]
[kW]
74-80
110
81-99
132
100-112
160
113-118
200
H
[m]
p
[psi]
HSEF 8-20G
140
90
130
n nom = 1470 min-1
/506
ISO 9906 Annex A
/493
120
80
110
70
/464
100
90
/429
80
/411
60
50
40
70
60
50
30
40
30
0
P2
[kW]
P2
[hp]
0
400
100
800
200
1200
1600
300
2000
400
2400
500
2800
600
3200
700
Q [US GPM]
800
240
Q [m³/h]
/506
160
200
120
160
/411
80
120
80
40
40
0
0
0
400
800
1200
1600
2000
2400
2800
3200
Q [US GPM]
Eta
[%]
90
80
/506
70
60
40
30
0
54
400
800
1200
1600
2000
2400
2800
3200
Q [US GPM]
TM04 4219 1009
50
Performance curves, HSEF
HSEF 8-17A
2500 GPM, 66-90 psi
2500 GPM, 66-90 psi
Pressure range Rated power
[psi]
[kW]
66-72
110
73-82
132
83-90
160
H
[m]
p
[psi]
HSEF 8-17A
120
n nom = 1460 min-1
80
110
70
ISO 9906 Annex A
100
/457
/431
90
60
/408
80
/392
50
40
70
60
50
30
20
40
30
20
0
P2
[kW]
P2
[hp]
0
400
100
800
200
1200
300
1600
2000
400
2400
500
2800
600
3200
700
3600
800
Q [m³/h]
/457
200
120
Q [US GPM]
160
/392
80
120
80
40
40
0
0
400
800
1200
1600
2000
2400
2800
3200
3600
Q [US GPM]
Eta
[%]
90
/457
80
70
60
50
40
30
0
400
800
1200
1600
2000
2400
2800
3200
3600
Q [US GPM]
TM04 4225 1009
0
55
Performance curves, HSEF
HSEF 10-20
2500 GPM, 87-127 psi
2500 GPM, 74-80 psi
Pressure range Rated power
[psi]
[kW]
87-94
160
95-112
200
113-127
250
H
[m]
p
[psi]
HSEF 10-20
150
100
90
n nom = 1470 min-1
140
/507
ISO 9906 Annex A
130
/480
120
80
110
/444
70
100
/427
90
60
80
50
40
70
60
50
30
40
0
P2
[kW]
P2
[hp]
240
320
200
0
400
100
800
200
1200
300
1600
2000
400
2400
500
2800
600
3200
700
3600
800
4000 Q
900
[US GPM]
Q [m³/h]
/507
280
240
160
200
120
80
/427
160
120
80
0
400
800
1200
1600
2000
2400
2800
3200
3600
4000 Q
[US GPM]
Eta
[%]
90
/507
80
70
60
40
30
0
56
400
800
1200
1600
2000
2400
2800
3200
3600
4000 Q
[US GPM]
TM04 4220 1009
50
Performance curves, HSEF
HSEF 12-19G
3000 GPM, 83-115 psi
3000 GPM, 83-115 psi
Pressure range Rated power
[psi]
[kW]
83-91
250
92-109
315
110-115
355
H
[m]
100
p
[psi]
HSF 12-19G
140
n nom = 1460 min-1
90
130
/481
120
/466
ISO 9906 Annex A
80
110
70
/424
100
/406
90
60
80
50
40
70
60
50
30
40
0
P2
P2
[kW] [hp]
300
250
500
0
1000
1500
200
2000
400
2500
3000
600
3500
4000
800
4500
1000
5000
1200
Q [US GPM]
Q [m³/h]
/481
400
350
300
/406
200
250
100
200
150
100
0
500
1000
1500
2000
2500
3000
3500
4000
4500
5000
Q [US GPM]
Eta
[%]
90
/481
80
70
60
50
40
30
0
500
1000
1500
2000
2500
3000
3500
4000
4500
5000
Q [US GPM]
TM04 4221 1009
150
57
Performance curves, HSEF
HSEF 12-19G
3500 GPM, 80-113 psi
3500 GPM, 80-113 psi
Pressure range Rated power
[psi]
[kW]
80-88
250
89-107
315
108-113
355
H
[m]
100
p
[psi]
HSF 12-19G
140
n nom = 1460 min-1
90
130
/481
120
/466
ISO 9906 Annex A
80
110
70
/424
100
/404
90
60
80
50
40
70
60
50
30
40
0
P2
P2
[kW] [hp]
300
250
500
0
1000
1500
200
2000
400
2500
3000
600
3500
4000
800
4500
1000
5000 Q
[US GPM]
1200 Q
400
[m³/h]
/481
350
300
200
/404
250
150
100
200
150
100
0
500
1000
1500
2000
2500
3000
3500
4000
4500
5000 Q
[US GPM]
Eta
[%]
90
/481
80
70
60
50
30
0
58
500
1000
1500
2000
2500
3000
3500
4000
4500
5000 Q
[US GPM]
TM04 4222 1009
40
Performance curves, HSEF
HSEF 12-19G
4000 GPM, 79-111 psi
4000 GPM, 79-111 psi
Pressure range Rated power
[psi]
[kW]
79-86
250
87-104
315
105-111
355
H
[m]
100
p
[psi]
HSF 12-19G
140
n nom = 1460 min-1
90
130
/481
120
/466
ISO 9906 Annex A
80
110
70
/424
100
/406
90
60
80
50
40
70
60
50
30
40
0
P2
P2
[kW] [hp]
500
0
1000
200
1500
2000
400
2500
3000
600
3500
4000
800
4500
1000
5000
5500
1200
Q [US GPM]
1400 Q
[m³/h]
450
300
400
250
350
/481
300
/406
200
250
100
200
150
100
0
500
1000
1500
2000
2500
3000
3500
4000
4500
5000
5500
Q [US GPM]
Eta
[%]
90
/481
80
70
60
50
40
30
0
500
1000
1500
2000
2500
3000
3500
4000
4500
5000
5500
Q [US GPM]
TM04 4223 1009
150
59
Performance curves, HSEF
HSEF 12-19G
4500 GPM, 76-109 psi
4500 GPM, 76-109 psi
Pressure range Rated power
[psi]
[kW]
76-83
250
84-102
315
103-109
355
H
[m]
100
p
[psi]
HSF 12-19G
140
n nom = 1460 min-1
90
130
/481
ISO 9906 Annex A
/466
120
80
110
70
/424
100
/408
90
60
80
50
40
70
60
50
30
40
0
P2
P2
[kW] [hp]
500
0
1000 1500
200
2000 2500 3000
400
600
3500 4000 4500
800
1000
5000 5500 6000
1200
1400
450
300
400
250
350
Q [US GPM]
Q [m³/h]
/481
300
/408
200
250
150
100
200
150
100
0
500
1000 1500
2000 2500 3000
3500 4000 4500
5000 5500 6000
Q [US GPM]
Eta
[%]
90
80
/481
70
60
50
30
0
60
500
1000 1500
2000 2500 3000
3500 4000 4500
5000 5500 6000
Q [US GPM]
TM04 4224 1009
40
Installation dimensions
Fire DNF
2-pole, 50 Hz
TM03 2929 4905
Flex unit, 2-pole, 50 Hz
Flex unit, 2-pole, 50 Hz
Pump type
Rated power
P2
[kW]
Fire DNF 65-20
Fire DNF 65-25
Fire DNF 80-20
Fire DNF 80-25
18.5
22
37
45
30
37
55
75
Dimensions [mm]
DNs
DNd
a
a1
a2
a3
h
h2
h3
100
65
100
150
75
150
100
225
280
100
65
125
150
75
150
100
250
300
125
80
125
150
75
150
100
250
280
125
80
125
150
80
150
100
280
325
L
1257
1295
1387
1437
1387
1540
1573
L1
L2
b2
b3
ød
1340
1040
790
740
13
1500
1200
790
740
13
1500
1200
790
740
13
1500
1200
790
740
13
Weight
[kg]
306
343
430
506
408
430
641
735
61
Installation dimensions
Fire HSEF
2-pole, 50 Hz
TM04 4445 1309
Flex unit, 2-pole, 50 Hz
Note: The dimensional sketch shows a pump with counter-clockwise direction. Clockwise rotation is available on
request.
Flex unit, 2-pole, 50 Hz
,
Pump type
Rated
power DNs DNd
P2
[kW]
[inch]
Dimensions [mm]
h1
h2
15
Fire HSEF 4-10G
Fire HSEF 4-10
Fire HSEF 4-12
18.5
22
Fire HSEF 5-11
5
4
430
633
a
694
264
264
100
240
305
L
L1
L2
1325
1260
960
410
1365
1300
1000
418
1405
1340
1040
1410
1110
37
727
1475
1410
1110
1525
1460
1160
45
5
4
430
633
750
264
264
100
240
305
55
789
1625
1560
1260
55
789
1625
1560
1260
1665
1600
1300
1716
1650
1350
1502
1415
1115
75
5
4
430
637
30
37
6
5
429
588
826
726
265
283
233
283
100
100
240
240
305
327
B
701
B1
661
s
279
q
279
442
565
565
701
661
279
279
643
747
787
701
661
318
263
844
890
701
661
305
305
511
534
45
776
1558
1455
1155
684
55
815
1653
1550
1280
788
1683
1580
1280
1728
1625
1325
1733
1630
1470
1943
1840
1540
2023
1920
1620
1690
1600
1300
1730
1640
1340
75
6
5
456
658
110
90
283
283
100
227
330
842
891
6
5
505
753
75
8
6
506
712
976
892
302
315
390
334
100
100
227
240
330
330
110
977
1920
1830
1530
110
1002
2058
1980
1780
2148
2070
1870
132
160
200
62
A
1475
132
Fire HSEF 6-12
C
727
90
Fire HSEF 6-10
hd
30
90
Fire HSEF 5-12
hs
678
90
Fire HSEF 5-8
h3
Weight
[kg]
8
6
531
785
1170
419
305
100
297
375
701
661
330
305
845
891
701
661
853
813
701
661
853
813
999
356
330
1479
1591
879
330
260
925
1405
1565
853
813
419
305
1682
1785
1867
Installation dimensions
Fire HSEF
2-pole, 50 Hz
Compact unit, 2-pole, 50 Hz
TM04 4444 1309
(view without control panel)
Note: The dimensional sketch shows a pump with counter-clockwise direction. Clockwise rotation is available on
request.
Compact unit, 2-pole, 50 Hz
,
Pump type
Rated
power DNs DNd
P2
[kW]
Fire HSEF 4-10G
Fire HSEF 4-10
Fire HSEF 4-12
L
L1
L2
1830
1765
1465
568
18.5
1870
1805
1505
576
1910
1845
1545
30
1980
1915
1615
37
1980
1915
1615
2030
1965
1665
55
2130
2065
1765
55
2130
2065
1765
2220
2155
1855
2271
2205
1905
2010
1920
1620
2063
1960
1660
842
2108
2005
1705
946
2238
2135
1835
2283
2180
1880
45
75
5
5
5
4
4
4
h1
430
430
430
h2
633
633
637
H
1320
1320
1320
hs
264
264
265
hd
264
264
233
C
100
100
100
A
240
240
240
a
305
305
305
90
Fire HSEF 5-8
30
37
6
5
429
588
45
Fire HSEF 5-11
55
75
6
5
456
658
283
283
100
240
327
283
283
100
227
330
1472
90
110
1320
1320
90
Fire HSEF 5-12
6
5
505
753
132
1472
302
390
100
227
330
1827
75
Fire HSEF 6-10
90
8
6
506
712
1472
315
334
100
240
330
110
110
Fire HSEF 6-12
Weight
[kg]
15
22
[inch]
Dimensions [mm]
132
160
200
1472
8
6
531
785
1827
419
305
100
297
375
2288
2185
2025
2498
2395
2095
2583
2570
2270
2245
2155
1825
2285
2195
1895
2475
2385
2085
2542
2535
2335
2798
2720
2520
B
701
B1
661
s
279
q
279
600
723
723
701
661
279
279
792
896
945
701
661
318
263
1050
1096
701
701
661
661
305
330
305
305
669
692
1051
1097
701
661
853
813
701
661
853
813
1205
356
330
1685
1901
1085
330
260
1131
1611
1771
853
813
419
305
1992
2095
2177
63
Installation dimensions
Fire HSEF
4-pole, 50 Hz
TM04 4445 1309
Flex unit, 4-pole, 50 Hz
Note: The dimensional sketch shows a pump with counter-clockwise direction. Clockwise rotation is available on
request.
Flex unit, 4-pole, 50 Hz
Pump type
Rated
power DNs DNd
P2
[kW]
[inch]
Dimensions [mm]
h1
h2
18.5
Fire HSEF 5-14
Fire HSEF 6-16
Fire HSEF 8-15
22
6
5
480
725
hs
hd
C
A
a
744
302
264
100
265
343
L1
L2
1360
1210
1478
1400
1250
777
1548
1470
1320
45
851
1691
1600
1400
1771
1680
1480
55
8
6
531
820
890
299
258
100
290
381
75
927
1806
1715
1515
45
886
1700
1635
1435
1775
1710
1510
1805
1740
1540
1844
1760
1560
1894
1810
1610
2028
2130
1740
55
10
8
556
861
328
302
100
310
375
994
90
110
915
942
75
10
8
608
960
132
353
302
100
310
394
1079
160
90
993
110
Fire HSEF 8-20
L
1438
30
75
Fire HSEF 8-17
h3
728
Weight
[kg]
132
10
8
607
985
160
1078
328
227
100
310
2214
2130
1930
2186
1920
1720
2216
2050
1850
2406
2240
2040
2504
2375
2075
2704
2575
2375
476
B
B1
s
q
701
661
330
356
549
651
808
701
661
406
457
901
701
661
318
263
250
1116
12
10
645
1049
1284
366
290
100
392
521
200
Fire HSF 12-19
250
315
355
64
1037
1138
701
661
853
813
701
661
1194
1241
482
381
1634
1806
1898
1407
1790
853
813
508
533
1965
2048
2145
160
200
923
1044
200
Fire HSEF 10-20
584
Dimensions available on request
2381
853
813
559
584
2479
2840
Installation dimensions
Fire HSEF
4-pole, 50 Hz
Compact unit, 4-pole, 50 Hz
TM04 4444 1309
(view without control panel)
Note: The dimensional sketch shows a pump with counter-clockwise direction. Clockwise rotation is available on
request.
Compact unit, 4-pole, 50 Hz
Pump type
Rated
power DNs DNd
P2
[kW]
[inch]
Dimensions [mm]
h1
h2
H
hs
hd
C
A
a
L
L1
L2
1943
1865
1715
1983
1905
1755
30
2053
1975
1825
45
2196
2105
1905
2276
2185
1985
2361
2270
2070
2205
2140
1940
2280
2205
2005
2355
2295
2095
2399
2315
2115
2449
2365
2165
2579
2495
2295
18.5
Fire HSEF 5-14
Fire HSEF 6-16
22
55
6
8
5
6
480
531
725
820
75
55
1320
1320
302
299
264
258
100
100
265
290
343
381
1472
45
Fire HSEF 8-15
10
8
556
861
75
1320
328
302
100
310
375
1472
75
90
Fire HSEF 8-17
110
1472
10
8
608
960
132
90
302
100
310
394
1472
110
132
353
1827
160
Fire HSEF 8-20
Weight
[kg]
10
8
607
985
160
328
227
100
310
2864
2780
2580
2741
2475
2275
2771
2605
2405
476
1827
3056
2890
2690
3154
3025
2725
B
B1
s
q
701
661
330
356
707
809
966
701
661
406
457
1059
701
661
318
263
250
1195
1344
701
661
853
813
1400
1447
482
381
1840
2116
2208
701
661
1613
1996
853
813
508
533
2275
2358
2455
160
200
1081
1250
200
Fire HSEF 10-20
742
12
10
645
1049
1827
366
290
100
392
521
3354
3225
3025
2691
853
813
559
584
2489
3150
200
Fire HSF 12-19
250
315
Dimensions available on request
355
65
Controller
Fire DNF, Fire HSEF
Controller types
The digital display digitally indicates:
Electrically powered Grundfos Fire DNF and Fire HSEF
pumps use the following standard controller types from
Tornatech inc.:
• phase loss
• GPA (direct-on-line)
• incoming undervoltage
• GPY (star-delta).
• motor overcurrent
Other controller types are available on request.
• motor undercurrent
The controllers are UL-listed and FM-approved and
meet the latest NFPA 20 and NFPA 70 requirements.
they are also CE-marked.
• motor run
Components
• power available
Power components
The controller is supplied with the following power
components:
• pump on demand
• Voltage surge arrester for protection from voltage
spikes.
• phase unbalance
• incoming overvoltage
• fail to start.
The LED’s on the panel indicates:
• phase reversal
• weekly test.
The buttons on the display interface have these
functions:
• alarm reset
• Isolating switch rated minimum 115 % of full-load
motor current.
• cut-in pressure setting
• Motor circuit breaker rated minimum 115 % of fullload motor current.
• run test
• Locked-rotor protector that trips within 8 to
20 seconds at 900 % of full-load current.
• Motor starter.
Operational components
The controller has the following operational
components on the front:
• cut-out pressure setting
• print.
Data recording
The controller is equipped with a pressure and event
recorder registering the following:
• time and date of retrieval of data
• cut-in and cut-out settings
• common operating handle for both the isolating
switch and motor circuit breaker
• date of the last change of the cut-in and cut-out
settings
• pump "START” button
• date, time and pressure readings of the minimum
and maximum pressure registered over the previous
seven days
• pump "STOP" button
• "Emergency" start and run handle.
• weekly test information
Control panel interface
The controller has a control panel interface with high
luminosity LED’s, back-lit digital display screen and
push-buttons.
The digital display numerically displays:
• individual phase-to-phase incoming voltage and
frequency
• individual phase motor current
• true pump elapsed run time
• pump start counts
• time and date
• cut-in and cut-out pressure settings
• system pressure
• minimum run period timer
• sequential start timer
• weekly test timer.
66
• minimum run period timer information
• pump start time and date
• pump stop time and date
• pump-on-demand time and date
• pump-room alarm time and date
• motor-trouble time and date
• power-on date and time
• power-off date and time.
General system information is stored for seven days,
and events and alarms for 15 days. The information is
retrievable through a USB slave communication port.
Controller
Fire DNF, Fire HSEF
Technical data
Enclosure
NEMA/UL/CSA type 2 - IP42.
Conductors
• GPA (direct-on-line): 3 conductors.
• GPY (star-delta):
6 conductors.
Short-circuit withstand rating
100 kA RMS at 200-480 V.
Operating temperature
5 °C to 50 °C.
TM04 4801 2109
Dimensions
Fig. 33 Dimensional sketch
Motor size
[kW]
Dimensions
[mm]
W
H
D1
D2
(panel door open)
773
3.7 - 37
508
914
305
45 - 75
610
1371
355
902
90 - 220
762
1727
457
1176
67
Being responsible is our foundation
Thinking ahead makes it possible
Innovation is the essence
96973740 0509
GB
Subject to alterations.
GRUNDFOS A/S . DK-8850 Bjerringbro . Denmark