I.INTRODUCTION
The Series PFA FM approved fire pump system features the Preso Ellipse primary
flow sensor. Preso's patented elliptical design outperforms and provides greater
accuracy than traditional differential pressure flow measurement devices. This
differential pressure flow meter is designed with a series of ports facing the
upstream velocity pressures, as well as flow sensing ports strategically located
ahead of the trailing edge flow separation.
The multi-ported, self-averaging flow element consists of an elliptical shape with two independent flow sensing chambers. The
impact velocity sensing holes (high pressure) are located along
the leading edge and the true static sensing holes (low pressure)
are on the exterior probe side. Series PFA comes with instrument shut-off valves with provisions to accept a direct indicating
meter.
True static
sensing holes
Impact velocity
sensing holes
II.SPECIFICATIONS
Applications:
Pipe Sizes:
Pressure:
Temperature:
Accuracy:
Turndown Ratio:
Standard Components:
Reynolds Number:
Liquids
2 to 16 inches (50 to 406.4 mm)
400 PSI (2758 kPa) maximum
Gage
PFA Velocity Sensor
180 °F (80 °C) maximum
250 °F (121 °C) maximum
±1.75% of reading
17:1 with no vacuum effect
Y-type head, brass
Compression fitting;
2” to 5”, brass
6” to 16”, CS with SS ferrule
CS 3000 lb. weld fitting - ASTM A105
316/316L SS Ellipse sensor
Instrument valves (2 per sensor) - ¼” male SAE flare brass ball
Polycarbonate ID tag with wire
Direct reading gage, brass body, 270° arc
Greater than 75,000 maintains most accurate flow measurements
Less than 75,000 consult factory for estimated results
Double support required for the following Systems
Double Support:
Page 2
Pipe Size
4"
8"
10"
12"
16"
Pump Ratings
400 and 450 GPM
> 2000 GPM
> 2500 GPM
> 3000 GPM
> 5000 GPM
10-PTT-UM-00311 08/12
III.
PIPE ORIENTATION AND SENSOR MOUNTING
NOTE: Pipe must remain full at all
times during measurements.
FLOW
10°
10°
FIELD
WELD
H
FM
L
APPROVED
L
LIQUID
FLOW METERS
DEBITMETERS
MEDIDOR DE FLUJO
FM
APPROVED
FLOW METERS
DEBITMETERS
MEDIDOR DE FLUJO
FIGURE 1 − HORIZONTAL PIPE INSTALLATION
FL
D OW
E
ME BIT ME
DID ME TE
OR TER RS
DE S
FL
UJ
O
PR
AP
FIELD
WELD
H
ED
OV
F
M
L
L
H
FIELD
WELD
FLOW
FLOW
NOTE: Pipe must remain full at all
times during measurements.
FL
D OW
ME EBIT M
DID ME ETE
OR TE RS
DE RS
FL
UJ
O
F
AP
PR
OV
M
ED
LIQUID
FIGURE 2 − VERTICAL PIPE INSTALLATION
10-PTT-UM-00311 08/12
Page 3
IV.
INSTALLATION INSTRUCTIONS - SINGLE SUPPORT
1. Choose the proper location to install the PFA Ellipse using AGA/ASME standards (or
equivalent). Refer to the Location Instructions on Page 8.
2. Grind the surface of the pipe where the PFA Ellipse is to be inserted to provide a clean area for
welding.
3. Weld the supplied weld-o-let to the pipe using standard codes for your application
(1/16” weld gap recommended). Take care to protect the threads during the welding process.
4. Drill a hole through the pipe wall according to Table 1.
5. Deburr the hole just drilled, especially on the inside of the pipe.
PIPE SIZE
MODEL / SENSOR
WELD CONNECTOR
DRILL BIT
2” - 5”
½”
6” - 12”
PFA (½”)
PFA (⁷/₈”)
14” - 16”
PFA (1¼”)
1¼”
⁵/₈”
11/₈”
13/₈”
1”
TABLE 1 − SINGLE SUPPORT DRILL BIT SIZE
6. Install the supplied compression fitting by threading it into the weld-o-let manually. Then with
a wrench, tighten the fitting a further 1¼ turns taking care not to tighten the compression nut.
7. Install the instrument valves at the PFA Ellipse head connections. Ensure that the valves are
FULLY CLOSED to prevent them from leaking during start-up.
8. Insert the PFA Ellipse through the compression fitting See Figure 3. Carefully push the sensor
by hand further into the pipe until it reaches the opposite wall.
9. While holding the PFA Ellipse in its fully inserted position, align the arrow located on the sensor
head with the direction of flow. See Figure 4.
10. Thoroughly tighten the compression nut in order to prevent leakage. After tightening the
compression nut manually, turn it further 1¼ turns with a wrench.
Page 4
10-PTT-UM-00311 08/12
V.
INSTALLATION INSTRUCTIONS - DOUBLE SUPPORT
1. Follow Steps 1 through 7 in Section IV. At 180° from and on the same plane as the previously
drilled hole, grind the surface of the pipe to provide a clean area for welding. Drill a hole and
deburr, especially on the inside of the pipe. The hole used for the double support should be
sized according to Table 2.
2. Weld the double support weld-o-let making sure that it is centered with the drilled hole
(1/16” weld gap recommended).
3. Install the PFA Ellipse sensor through the two holes. Make sure that the double support pin
passes through the guide ring. See Figure 5.
4. Align the arrow located on the sensor head in the direction of flow as in Step 9, Section IV.
5. Ensure that the PFA Ellipse is in the correct orientation and spans the inside of the pipe.
Tighten the compression nut. After tightening the compression nut manually, tighten it 1¼
turns more using a wrench.
6. Install the plug into the end of the double support weld-o-let. Tighten the plug to prevent
leakage.
Nut
Insert
Thread nut loosely
onto body of the
compression fitting
Install insert
as shown
Body
Threaded portion
to be installed
into weld fitting
on pipe
FIGURE 3 − COMPRESSION FITTING ASSEMBLY
10-PTT-UM-00311 08/12
Page 5
L
H
L
F M VED
RO
APP
RS
TE
O
ME ERS FLUJ
OW ET
F L B IT M R D E
D E D ID O
ME
H
FIELD
WELD
FLOW
FIGURE 4 − SENSOR ALIGNMENT
PIPE SIZE
MODEL / SENSOR
WELD CONNECTOR
DRILL BIT
2” - 5”
6” - 12”
PFA (½”)
PFA (⁷/₈”)
1/₈”
½”
14” - 16”
PFA (1¼”)
1”
3/₈”
½”
⁷/₈”
TABLE 2 − DOUBLE SUPPORT DRILL BIT SIZE
Ellipse Sensor
Double Support Pin
Guide Ring
FIGURE 5 − DOUBLE SUPPORT PIN
Page 6
10-PTT-UM-00311 08/12
VI.
GAGE MOUNTING
1. The FGE gage can be line, bracket or panel mounted.
2. For liquid applications the FGE should be installed below the PFA Ellipse in a level position. See
Figure 6.
NOTE: If recommended mounting is not possible, care must be taken to ensure that the gage is vented periodically.
FLOW
H
FM
APPROVED
L
FLOW METERS
DEBITMETERS
MEDIDOR DE FLUJO
VENT
VALVES
2500
2000
3000
GPM
FM
APPROVED
3500
1500
1000
PFA-XXX
X inch
250 SWP
X/XX
S/N AXXXXXXX
4000
BY-PASS
VALVE
FIGURE 6 - RECOMMENDED INSTALLATION
10-PTT-UM-00311 08/12
Page 7
PRESO ELLIPSE LOCATION INSTRUCTIONS
Straight pipe requirements: Accuracy is affected by the piping configurations due to the disturbances of
the flow profile. A fully developed symmetrical flow profile is achieved with the minimum upstream and
downstream recommended lengths.
DISTANCES ARE EXPRESSED IN
NUMBER OF NOMINAL PIPE DIAMETERS
THROTTLED VALVE OR REGULATOR
27
4
FLOW
TWO ELBOWS IN DIFFERENT PLANES
FLOW
RS
O
METEERS FLUJ
FLOW TMET DE
DEBI DOR
MEDI
REGULATORY OR
PARTIALLY CLOSED
VALVE
11
6
5
2
10
4
5
PRESO
FLOW
RS
METEERS
FLOW TMET DE
DEBI DOR
MEDI
FLUJ
2
4
9
PRESO
4
10
6
2
FLUJ
TWO ELBOWS IN THE SAME PLANE
11
3
FLOW
O
4
4
PRESO
RS
FLUJ
10
4
6
2
9
4
PRESO
5
2
RS
O
METEERS FLUJ
FLOW TMET DE
DEBI DOR
MEDI
FLOW
O
FLOW
PRESO
3
RS
O
METEERS FLUJ
FLOW TMET DE
DEBI DOR
MEDI
PRESO
FLOW
STRAIGHTENING VANE
STRAIGHTENING VANE
STRAIGHTENING VANE
PRESO FIRE PUMP SYSTEM
APPROVED
FM
APPROVED
Throttle Valve
Discharge
RS
O
METEERS FLUJ
FLOW TMET DE
DEBI DOR
MEDI
FLOW
METEERS
FLOW TMET DE
DEBI DOR
MEDI
FM
RS
O
METEERS FLUJ
FLOW TMET DE
DEBI DOR
MEDI
STRAIGHTENING VANE
PRESO
RS
METEERS
FLOW TMET DE
DEBI DOR
MEDI
RS
O
METEERS FLUJ
FLOW TMET DE
DEBI DOR
MEDI
FLOW
PRESO
O
CHANGE IN PIPE SIZE
4
FLOW
PRESO
RS
O
METEERS FLUJ
FLOW TMET DE
DEBI DOR
MEDI
4
5
STRAIGHTENING VANE
9
4
24
PRESO
System By-pass Valve
Air Vent
2500
2000
Flow
3000
GPM
FM
APPROVED
3500
1500
1000
PFA-XXX
X inch
250 SWP
X/XX
S/N AXXXXXXX
3
Optional to
Pump Inlet
4000
PRESO
7
PFA
Pipe Diameters From Valve
Valve
Throttle Valve
Flow
Supply
Fire Pump
Page 8
10-PTT-UM-00311 08/12
VII.
GAGE INSTALLATION
1. The connecting tubing between the PFA Ellipse and the gage should be as short as possible
and should slope down a minimum of 1 inch per foot.
2. Secure and support tubing to prevent sagging and/or vibration.
3. Care must be taken to ensure that the head heights are even.
4. A bleed line should be run from the gage vent valves to a pan or drain.
VIII.
GAGE OPERATION
1. Identify Hi and Lo pressure inlets on the gage.
2. Ensure by-pass valve (blue) is OPEN!
WARNING
WARNING: Gage may be damaged if initially pressurized with the by-pass valve closed.
3. Connect gage to corresponding Hi and Lo pressure taps of the PFA Ellipse (via 3-valve
manifold, if being used).
4. Open Hi and Lo instrument valves on the PFA Ellipse.
5. Alternately open the Hi and Lo vent valves to purge the lines.
6. When venting is complete, close the by-pass valve to begin taking reading.
10-PTT-UM-00311 08/12
Page 9
Page 10
10-PTT-UM-00311 08/12
Badger Meter Warranty
PFA Ellipse
Fire Pump System
PRODUCTS COVERED
The Badger Meter warranty shall apply to the Preso PFA Ellipse Fire
Pump System (“Product”).
MATERIALS AND WORKMANSHIP
Badger Meter warrants the Product to be free from defects in
materials and workmanship for a period of 12 months from the
original purchase date.
PRODUCT RETURNS
Product failures must be proven and verified to the satisfaction
of Badger Meter. The Badger Meter obligation hereunder shall be
limited to such repair and replacement and shall be conditioned
upon Badger Meter receiving written notice of any asserted defect
within 10 (ten) days after its discovery. If the defect arises and a valid
claim is received within the Warranty Period, at its option, Badger
Meter will either (1) exchange the Product with a new, used or
refurbished Product that is at least functionally equivalent to the
original Product, or (2) refund the purchase price of the Product. DO
NOT RETURN ANY PRODUCT UNTIL YOU HAVE CALLED THE BADGER
METER CUSTOMER SERVICE DEPARTMENT AND OBTAINED A RETURN
AUTHORIZATION.
Product returns must be shipped by the Customer prepaid F.O.B.
to the nearest Badger Meter factory or distribution center. The
Customer shall be responsible for all direct and indirect costs
associated with removing the original Product and reinstalling the
repaired or replacement Product. A replacement Product assumes
the remaining warranty of the original Product or ninety (90)
days from the date of replacement, whichever provides longer
coverage.
LIMITS OF LIABILITY
With respect to products not manufactured by Badger Meter, the
warranty obligations of Badger Meter shall in all respects conform
and be limited to the warranty extended to Badger Meter by the
supplier.
THE FOREGOING WARRANTIES ARE EXCLUSIVE AND IN LIEU OF
ALL OTHER EXPRESS AND IMPLIED WARRANTIES WHATSOEVER,
INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE
(except warranties of title).
Any description of a Product, whether in writing or made orally by
Badger Meter or its agents, specifications, samples, models, bulletins,
drawings, diagrams, engineering sheets or similar materials used in
connection with any Customer’s order are for the sole purpose of
identifying the Product and shall not be construed as an express
warranty. Any suggestions by Badger Meter or its agents regarding
use, application or suitability of the Product shall not be construed
as an express warranty unless confirmed to be such, in writing, by
Badger Meter.
EXCLUSION OF CONSEQUENTIAL DAMAGES AND
DISCLAIMER OF OTHER LIABILITY
Badger Meter liability with respect to breaches of the foregoing
warranty shall be limited as stated herein. Badger Meter liability
shall in no event exceed the contract price. BADGER METER SHALL
NOT BE SUBJECT TO AND DISCLAIMS: (1) ANY OTHER OBLIGATIONS
OR LIABILITIES ARISING OUT OF BREACH OF CONTRACT OR OF
WARRANTY, (2) ANY OBLIGATIONS WHATSOEVER ARISING FROM
TORT CLAIMS (INCLUDING NEGLIGENCE AND STRICT LIABILITY)
OR ARISING UNDER OTHER THEORIES OF LAW WITH RESPECT TO
PRODUCTS SOLD OR SERVICES RENDERED BY BADGER METER, OR
ANY UNDERTAKINGS, ACTS OR OMISSIONS RELATING THERETO, AND
(3) ALL CONSEQUENTIAL, INCIDENTAL AND CONTINGENT DAMAGES
WHATSOEVER.
This warranty shall not apply to any Product repaired or altered
by any Product other than Badger Meter. The foregoing warranty
applies only to the extent that the Product is installed, serviced and
operated strictly in accordance with Badger Meter instructions. The
warranty shall not apply and shall be void with respect to a Product
exposed to conditions other than those detailed in applicable
technical literature and Installation and Operation Manuals (IOMs)
or which have been subject to vandalism, negligence, accident, acts
of God, improper installation, operation or repair, alteration, or other
circumstances which are beyond the reasonable control of Badger
Meter.
10-PTT-UM-00311 08/12
Badger Meter Warranty
Trademarks appearing in this document are the property of their respective entities.
Due to continuous research, product improvements and enhancements, Badger Meter reserves the right to change product or system specifications without notice, except to the extent an
outstanding contractual obligation exists. © 2012 Badger Meter, Inc. All rights reserved.
info@preso.com | www.preso.com | www.badgermeter.com
Phone: 262-639-6770 | Fax: 262-417-1148
The Americas | Badger Meter | 4545 West Brown Deer Rd | PO Box 245036 | Milwaukee, WI 53224-9536 | 800-876-3837 | 414-355-0400
México | Badger Meter de las Americas, S.A. de C.V. | Pedro Luis Ogazón N°32 | Esq. Angelina N°24 | Colonia Guadalupe Inn | CP 01050 | México, DF | México | +52-55-5662-0882
Europe, Middle East and Africa | Badger Meter Europa GmbH | Nurtinger Str 76 | 72639 Neuffen | Germany | +49-7025-9208-0
Czech Republic | Badger Meter Czech Republic s.r.o. | Maříkova 2082/26 | 621 00 Brno, Czech Republic | +420-5-41420411
Slovakia | Badger Meter Slovakia s.r.o. | Racianska 109/B | 831 02 Bratislava, Slovakia | +421-2-44 63 83 01
Asia Pacific | Badger Meter | 80 Marine Parade Rd | 21-04 Parkway Parade | Singapore 449269 | +65-63464836
China | Badger Meter | Rm 501, N° 11 Longyue Apartment | N° 180 Longjin Rd, Jiuting Songjiang District | Shanghai, China | 201615 | +86-21-5763 5412