COMPONENTS High-speed DC circuit-breakers for Fixed Installation (EN / IEC standards) Type UR General information The UR range of DC circuit-breakers has achieved worldwide acceptance as a well proven design for use in fixed installations. It has been regularly upgraded and adapted to new standard requirements and different applications over the years, continually improving the level of performance and functionality. This has led to an impressive service track record throughout the world for the UR product range. Combining a compact design with a high making and breaking capacity, the UR range, with its low number of parts also guarantees high reliability and low maintenance requirements. Applications • Line circuit-breaker for DC traction power substations • Interconnecting circuit-breaker for DC traction power substations • Rectifier circuit-breaker for DC traction power substations - + I> Rectifier circuit-breaker Line circuit-breaker I> I> Interconnecting circuit-breaker I> Main features • Conventional free air thermal current covering a range from 2600 A to 8000 A • Rated operational voltage 900 VDC, 1800 VDC and 3600 VDC • Safe with a high insulation level • Indoor installation • Bi-directional or uni-directional overcurrent release • Trip-free direct acting device • High rated short circuit making and breaking capacity • Limited maximum arc voltage • Electro-magnetic closing with electric or magnetic holding • A large number of different options to match the various application requirements • Very low maintenance requirements with high electrical and mechanical endurances • Simple design with few moving parts resulting in high reliability • Proven design with worldwide experience and acceptance • Reference standards: IEC77, EN50123-1 /-2 ,IEC61992-1 /-2 • Also available according to IEEE (ANSI) C37.14 / C37.16 standards (refer to our specific SG104309BEN brochure) • Insulation material according to relevant BS, NF, ASTM, IEC and DIN standards 2 * Product range UNe [V=] UR26-64 UR36-64 UR40-64 3600 * Not covered by this document. Refer to the SG104147BEN «High-Speed DC circuit-breaker Installation Type UR15». ** Not covered by this document. Refer to the SG150880BEN «High-Speed DC circuit-breaker Installation Type HPB45 & HPB60». brochure for Fixed brochure for Fixed UR15-42* UR26-82 UR36-82 UR40-82 UR46-82 HBP60-82** UR15-41* UR26-81 UR36-81 UR40-81 UR46-81 1800 UR60-81 900 1500 2600 3600 4000 4600 UR80-81 6000 Ith [A] 8000 High modularity concept 3600 Arc chute 64 UNe [V=] Arc chute 82 1800 Arc chute 81 900 UR26 UR36 UR40 UR 0 UR46 UR60 UR80 2600 3600 4000 4600 6000 8000 Ith [A] 3 Breaking current parameters Third rail or Over-head Catenary System powered by a rectifier f e f : duty f - peak of the short-circuit current e : duty e - maximum circuit-energy short-circuit d : duty d - distant fault short-circuit d Note: points f, e and d represent fault conditions along the line at different distances from the rectifier. Characteristics of the duties d, e and f d tc/TNc 1 TNc [ms] 1 16 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 Iss INss tc TNc e 31.5 >63 = = = = Prospective sustained short-circuit current Rated short-circuit current of the circuit-breaker Time-constant of the circuit Rated track time constant of the circuit-breaker f 0 0.4 0.6 0.8 1 Iss/INss 2INe/INss Breaking current parameters I tc Îss >1.42Iss Typical duty f Iss = Îss = di/dt = Id = Icut off = tc = tl = Ûarc = UNe = Iss di/d 0.63 Iss t Icut off Typical duty e and d Id t V Ûarc Prospective sustained short-circuit current Peak of Iss Initial current rate of rise Setting of maximum current release Cut-off current Time-constant of the circuit Opening time Maximum arc voltage Rated operational voltage UNe ti t Opening time Tl Relationship between opening time tl and the initial rate of rise of current di/dt for direct instantaneous over-current release. t l 20 [ms] 18 16 14 12 UR36/40 64 10 8 Example for a di/dt of 3.106 A/s: - for UR26: tl ~ 4.3 ms, - for UR60/80: tl ~ 4.1 ms. UR26 6 4 2 Note!: for a shorter opening time on low di/dt, the “indirect release” (shunt trip) option can be used (refer to “Options” section page 14). 0 3.105 5 7 106 3 5 7 3 di/dt [A/s] t l 10 [ms] 8 6 4 UR60/80 2 4 0 3.105 5 7 106 3 5 7 3 di/dt [A/s] Data for product selection Symbol Unit UR26 UR36 UR40 UR46 UR60 UR80 900 - 900 - 1000 - 1000 - 1800 6000 1800 8000 125/100 - (2) 6-18 - (2) 125/100 - (2) 8-24 - (2) 15 - 15 - 18 - 18 - 2500 - 2500 - MAIN HIGH VOLTAGE CIRCUIT Rated voltage UNe [VDC] - arc chute type 81 900 900 900 900 - arc chute type 82 1800 1800 1800 1800 - arc chute type 64 3600 3600 3600 Maximal operational voltage [VDC] - arc chute type 81 1000 1000 1000 1000 - arc chute type 82 2000 2000 2000 2000 - arc chute type 64 4000 4000 4000 Rated insulation voltage - arc chute type 81 UNm [VDC] 3000 3000 3000 3000 - arc chute type 82 3000 3000 3000 3000 - arc chute type 64 4800 4800 4800 Conventional free air thermal current (1) Ith [A] 2600 3600 4000 4600 Rated short-circuit making & breaking capacity - at UNe 900 VDC (arc chute type 81) INss/TNc [kA]/[ms] 125/100 125/100 125/100 125/100 80/31.5 80/31.5 80 /31.5 80/31.5 - at UNe 1800 VDC (arc chute type 82) - at UNe 3600 VDC (arc chute type 64) 40/31.5 40/31.5 40/31.5 Peak and rated short-time withstand current (250 ms) ÎNcw/INcw [kA]/[kA] Direct over-current instantaneous release (bi-directional) (3) [kA] 1.4-8.0 2-15 2-15 2-15 (uni-directional) Power frequency withstand voltage (60 Hz, 1 min): - arc chute type 81 Ua [kV] 15 15 15 15 - arc chute type 82 15 15 15 15 - arc chute type 64 15 15 15 Rated impulse withstand voltage [kVDC] 20 20 20 20 - arc chute type 81 UNi - arc chute type 82 20 20 20 20 - arc chute type 64 30 30 30 Maximum arc voltage [V] 2500 2500 2500 2500 - arc chute type 81 Ûarc - arc chute type 82 4000 4000 4000 4000 - arc chute type 64 8000 8000 8000 (1) At Tamb = +40°C and tested with high voltage connections according to standard IEC/EN 60943 (2) Under developement (3) For range selection, refer to the table the page 6 LOW VOLTAGE AUXILIARY CIRCUIT Control circuit Nominal voltage Un (4) [VDC] Range of voltage Closing power (5) [W]/[s] Holding power for electric holding (5) [W] Holding power for magnetic holding (5) [W] Opening power for magnetic holding (5) [W]/[s] Mechanical opening time on opening order (5)(7) to [ms] Mechanical closing time (5)(7) tc [ms] (4) The breaker can also be controlled with a rectified ac control voltage (5) At Un and Tamb = +20°C (6) Under development (7) Starting when the signal is received by the coil Auxiliary contacts Type of contacts (refer to definition on page 10) Number of auxiliary contacts Rated voltage [VDC] Conventional thermal current Ith [A] [A] Maximum breaking capacity at 110 VDC and =5 ms Minimum let-through current at 24 VDC (8) [mA] (8) For a dry and clean environment Low voltage interface Type of connection (9) (9) For mobile connector information refer to page 10 24, 36, 48, 64, 72, 110, 125, 220 [0.7 - 1.25] Un 1300/1 2.3 0 25/1 15 to 30 ~ 150 110, 125 [0.8 - 1.1] Un 2800/1 30 0 (6) - (6) 15 to 30 ~ 150 Potential free (PF) or change-over (CO) 5a +5b 24 to 220 10 6 10 Harting type HAN 32 / VEAM type 22 pins OPERATING CONDITIONS Installation Altitude Working ambient temperature Humidity Minimum mechanical durability [m] Tamb N Indoors <1400 [°C] -5 to +40 Class 5K2 Operations 4x50’000 8x25’000 8x25’000 8x25’000 4x20’000 4x20’000 5 Direct over-current instantaneous release Available setting ranges (in kA) with their corresponding codification: UR26 1.4 2.0 2.0 2.0 4.0 - UR36 2.7 5.0 5.0 8.0 8.0 2.0 2.0 2.0 4.0 4.0 4.0 6.0 9.0 - 5.0 5.0 8.0 8.0 15.0 10.0 10.0 15.0 UR40 - 2.0 2.0 2.0 4.0 4.0 4.0 6.0 9.0 5.0 5.0 8.0 8.0 15.0 10.0 10.0 15.0 UR46 UR60 UR80 Type - 6.0 - 10.0 9.0 - 14.0 13.0 - 18.0 - 8.0 - 14.0 12.0 - 18.0 16.0 - 24.0 DV1 DV2 DE1 DS1 DE2 DS2 DV2 DE3 DE4 (2) (2) 2.0 2.0 2.0 4.0 4.0 4.0 6.0 9.0 5.0 5.0 8.0 8.0 15.0 10.0 10.0 15.0 Designation code (1) Standard Option A B C D E F G H I J K L N O P U (2) (1) For selection page 16. (2) For uni-directional over-current instantaneous release (under development). Tripping device for UR26/36/40/46 Standard tripping devices DS tripping device Standard tripping device DV tripping device Tripping device adjustment method. Specific tripping device DE tripping device (optional) Tripping device adjustment method. 6 Tripping device for UR60/80 Tripping device Tripping device adjustment method. hod. Information for product integration The DIN-ISO 2768-1 coarse tolerances are applied to these dimensions. All dimensions are in mm. The maximum allowed flatness deviation of the support frame is 0.5 mm. Main dimensions for UR26/36/40/46 UR26/36-81/82 UR26/36/40/46-81/82 UR40/46-81/82 617 238 (1) 419 (2) 168 (1) Arc chute 82 (2) Arc chute 81 51 69 R4 56 HV connections for UR26/36/40/46 (exept upper connection of UR46) E 23 HV 4x Ø11 Ø LV 40 160 240 386 D 95 100 784 5 90 C 160 379 194 UR40-64S UR26/36-64S 320 A B UR26/36/40-64S 420 320 700 25 50 25 40 25 1025 4x Ø14 90 50 25 20 50 4x Ø18 160 56 23 23 30 HV 4x Ø11 371 90 E HV upper connection for UR46 only D 95 100 140,5 LV C 160 379 40 240 194 320 A B Dimensions [mm] A B C D E UR26 UR36 UR40 UR46 645 131 131 20 176 760 246 176 30 176 760 246 176 30 176 760 246 176 40 177 Weights Weights (1) [Kg] UR26 UR36 UR40 UR46 With arc chute 81 77 94 98 110 With arc chute 82 87 104 108 120 With arc chute 64 150 150 154 (1) Weights for standard circuit-breaker without any option. 7 Main dimensions for UR60/80 UR60 UR80 UR60/80 238 238 419 (1) (1) Arc chute 81 50.5 60 120 25 177 120 4x Ø11 320 40 182 75.5 160 240 411 40 160 240 8x Ø18 LV 39 30 56 386 HV 23 HV 783 30 51 69 718 Weights Weights (1) [Kg] With arc chute 81 UR60 UR80 139 150 (1) Weights for standard circuit-breaker without any option. Insulation distances for UR26/36/40/46/60/80 The below values correspond to the insulation distances in the cubicles used to perform duty cycles of “f”, “e” and “d” with the rated short-circuit breaking and making capacity INss / TNc of the circuit-breakers. For other installation conditions, please contact Sécheron. Minimum insulation distances [mm] UR..81S UR..82S To insulating wall UR..64S A 140 40 120 B 140 140 270 C* 765 765 670 To earth Please contact Sécheron *: Grid with 50% of surface opening. UR..64S 240 C 238 617(1) 419(2) B B B (1) Arc chute 82 (2) Arc chute 81 8 A A 700 632 C UR..81/82S B A A Arc chute installation Arc chutes 81 and 82 Vertical removal of the arc chute (for UR46/60/80). Opening of the arc chute on the LV connector side (for UR26/36/40). Opening of the arc chute on the LV connector opposite side (for UR26/36/40). Arc chutes 64 (only for UR26/36/40) The type SE includes two arc chute locking levers. The type S-CC includes an arc chute lifting lever located on connector side. The type S-OC includes an arc chute lifting lever located on the connector opposite side. The type SI-CC includes an arc chute lifting lever located on connector side and, for installation of circuit-breaker without insulation walls, an additional insulation around the arc chute. The type SI-OC includes an arc chute lifting lever located on the connector opposite side and, for installation of circuit-breaker without insulation walls, an additional insulation around the arc chute. Designation for arc chute installation Arc chute type Circuit-breaker Arc chute installation Opening on LV connector side Codification Standard Option 1 UR26/36/40 Opening on LV connector oposite side 81 / 82 UR46/60/80 64 (1) UR26/36/40 (1) Arc chute 82 is not available for UR60/80. 7 Vertical removal 8 SE 2 SI-CC 3 SI-OC 4 S-CC 5 S-OC 6 9 Low voltage interface Note!: Low voltage connectors are delivered with all pins mounted. Harting type HAN 32 VEAM type 22 pins (Standard) (Option - Only for UR26/36/40/46) Low voltage control scheme Electric holding: E type Magnetic holding: M type A B Ie C D E A S V= S V= + D C 100% + 100% B Ie F E 0 0,5 R1 G t [s] ~ 5% 0 ~ 20% 1 Customer scope A B C D E Rp Rs 0 – F t [s] 0,5 Sécheron scope 1 tc tc+0.5 tc+1 – Customer scope Start of the closing pulse: the contacts F + G close. Closing pulse: 0.5 to 1 s. Start of the holding current: the contact G opens. Holding: a R1 resistance limits the holding current to 5% of the closing current. Opening: the contact F opens to provoke the interruption of the holding current. A B C D Sécheron scope Start of the closing pulse: the contacts E close. Closing pulse: 0.5 to 1 s, then the contacts E open. Holding: achieved by the permanent magnet. Opening: the contacts F close to provoke a current pulse of the opposite polarity to the closing current. The duration of this pulse is 0.5-1 s, then the contact F opens. The opening current is 20 % of the closing current. E, F, G: contact R1 : resistor to be inserted in the holding circuit of the E type; the power to be considered for the resistor choice is 220 W (4x55 W) Rs : resistor to be inserted in series with the coil in the opening circuit of the M type; the power to be considered for the resistor choice is 50 W (200 W / 4) Rp : resistor to be inserted in parallel with the closing coil in the opening circuit of the M type S : automatic circuit-breaker Typical value for the closing coils for UR26/36/40/46 Coil characteristics Closing Pulse 0.5 to 1s Unom Inom Imin E Imin M Imax R1 Inom Imin Imax Rs Rp Inom Imin Imax [V] [A] [A] [A] [A] [] [A] [A] [A] [] [] [A] [A] [A] 24 41.7 22.5 25 70.9 11.4 2.0 1.4 2.5 2.4 1.3 6.1 3.8 8.5 36 32.7 17.7 19.6 55.6 25 1.4 0.1 1.7 5.3 3.0 4.3 2.7 6.0 48 20.9 11.3 12.5 35.4 45.7 1.0 0.7 1.3 9.4 5.4 3.1 1.9 4.3 64 17.6 9.5 10.6 29.9 79.4 0.8 0.5 1.0 17.2 9.0 2.3 1.5 3.2 72 16.4 8.8 9.8 27.8 100 0.7 0.5 0.9 21.2 12.0 2.2 1.4 3.0 110 11.7 6.3 7.0 19.9 210 0.5 0.4 0.6 40 20 1.6 1.0 2.3 125 10.5 5.6 6.3 17.8 272 0.4 0.3 0.6 52 26 1.4 0.9 2.0 220 5.9 3.2 3.5 9.9 840 0.3 0.2 0.3 160 80 0.8 0.5 1.1 400 400 2’200 55 2.3 1.2 3.6 200 15 25 12 38 Power consumption [W]: 1’300 10 M type opening Pulse 0,5 to 1s E type holding Typical value for the closing coils for UR60/80 Coil characteristics Closing Pulse 0.5 to 1 s E type holding Unom Inom Imin E Imax R1 Inom Imin Imax [V] [A] [A] [A] [] [A] [A] [A] 110 23.9 16.7 31.8 44.9 2.4 1.8 2.7 125 21.9 15.1 29.9 55.9 2.2 1.6 2.5 Power consumption [W]: 2’800 1’280 4’650 280 30 14 35 Low voltage wiring diagrams The following wiring schemes represent the low voltage connector pins assignement in function of the selected conectors and the configuration choosen for standard or optional functions. They are valid for all control voltages exept 24 VDC. For 24 VDC control scheme, please contact Sécheron. Legend of the schemes Circuit-breaker main contact I> Direct overcurrent release Circuit-breaker closing coil Standard and optional functions Description Line Designation code (1) a b 1a+1b - Switch PF 20 A a b 1a+1b - Switch CO 20 B (WI) Wear indicator switch 26 1 (I>) Overcurrent release detector switch 25 1 Indirect release (shunt trip) 19 2 I (1) Please refer to designation code page 16 Harting type HAN 32 connector (Standard) Only the pins related to your selected configuration page 16 will be wired according to the below’s pin assignment. The connector will be delivered with all 32 pins even if not all wired. Auxiliary contacts (switch PF) (I>) ( ) (WI 31 29 27 25 32 30 28 26 23 24 Auxiliary contacts (switch CO) I 21 22 I> (I>) ( ) (WI 19 17 15 13 11 9 7 5 3 1 31 29 27 25 20 18 16 14 12 10 8 6 4 2 32 30 28 26 23 24 I 21 22 15 14 12 11 9 8 6 5 3 2 13 10 7 4 1 I> 11 VEAM type 22 pins connector (Option - Only for UR26/36/40/46) Auxiliary contacts (switch PF) Each below’s scheme represents the low voltage connector pin wiring in function of the possible selected configuration (refer page 16) The connector will be delivered with all 22 pins even if not all wired. 19 20 21 22 19 17 15 13 11 9 7 5 3 1 20 18 16 14 12 10 8 6 4 2 I 21 22 I> 18 18 17 16 21 22 19 20 11 9 7 5 3 1 19 17 16 14 12 10 8 6 4 2 18 7 5 3 1 18 16 14 12 10 8 6 4 2 21 15 13 11 9 7 5 3 1 22 16 14 12 10 8 6 4 2 13 11 9 7 5 3 1 14 12 10 8 6 4 2 I> I (I>) 21 22 I> 12 11 9 (I>) 15 13 I> ( ) (WI 15 13 I> ( ) (WI 19 17 17 13 11 9 7 5 3 1 18 17 14 12 10 8 6 4 2 16 19 20 I 21 22 I> Auxiliary contacts (switch CO) Each below’s scheme represents the low voltage connector pin wiring in function of the possible selected configuration (refer page 16) The connector will be delivered with all 22 pins even if not all wired. 19 20 21 22 15 14 12 11 9 8 6 5 3 2 13 10 7 4 1 I 21 22 I> 16 17 18 16 9 8 6 5 3 2 13 10 7 4 1 15 14 12 11 9 8 6 5 3 2 13 10 7 4 1 15 14 12 11 9 8 6 5 3 2 13 10 7 4 1 (I>) 21 22 15 14 12 11 9 8 6 5 3 2 13 10 7 4 1 17 18 16 21 22 I> I> ( ) (WI 12 11 I> ( ) (WI 17 18 15 14 19 20 I (I>) 21 22 I> 15 14 12 11 9 8 6 5 3 2 13 10 7 4 1 17 18 16 19 20 I 21 22 I> 13 Options (subject to additional costs) Mobile connector (available for UR26/36/40/46/60/80) Mobile connector Auxiliary switches Device Number Type UR26/36 /40/46 /60/80 5a+5b PF or CO UR26/36 /40/46 5a+5b PF or CO Fixed connector type Number of pin Cable gland Sécheron’s number 32 M32 SG104063R10100 0 Ø25 to Ø34 SG101699R00001 Size 2.5 mm² Size 1.5 mm² Harting HAN 32 0 VEAM type 22 pins 22 Connector Options available for UR26/36/40/46 BIM indirect release (shunt trip) and manual release type M3 BIM5 BIM6 The terminal block allows the connection between 2.5 mm² cables from the BIM5 and 6 mm² cables from the CID-3. 2.5 mm² to coil BIM6 is delivered with 1.5 m cables sized 2.5 mm² free end or connected through the connector. 6 mm² cable from CID The indirect release enables to shorten the opening time when required by specific application. The choice of the relevant type has to be validated by Sécheron prior quoting. This device can also be manually activated. Opening time Control mode - BIM5 4.5 - 5.5 ms CID-3* - BIM6 12 - 19 ms Direct battery 77-140 VDC * Not included in the DC circuit-breaker - To be ordered separately Manual release Manual closing device Vertical Horizontal (Type M3) 14 Position indicator Contact wear indicator (WI) or Overcurrent release detector (I>) Options available for UR60/80 Position indicator 0 I Note!: Other options are in development. Designation code for ordering Designation code information • Be sure to establish the designation code from our latest version of the brochure by downloading it from our website “www.secheron.com”. • Be careful to write down 22 digits for the type designation code when placing your order. • The customer shall write down the setting value Ids in its order form. • It can happen for technical reasons that some variants and options indicated in the designation code cannot be combined. • The bold part of this designation code defines the device type as it is displayed on the identification plate attached to the product. Example of customer’s choice: UR 36 81 Line: S 1 E E 0 F 0 A C 0 0 0 0 0 S B 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 15 Designation code (options are subject to additional costs) - Order form Line Description 10 11 Designation Product type Conventional free air thermal current UR 2600 A 3600 A 4000 A 4600 A 6000 A 8000 A Standard UR 26 36 40 46 60 80 Options Customer’s Choice UR 12 Rated operational voltage 81 For UR26/36/40/46/60/80 900 V 82 For UR26/36/40/46 1800 V 64 For UR26/36/40 3600 V S S 13 Application Fixed Installation 14 Arc chute installation (Refer to page 9 for selection) For UR26/36/40 Arc chute 81/82 Opening on LV connector side 1 For UR26/36/40 Arc chute 64 Type SE 2 Vertical removal 8 For UR46/60/80 Arc chute 81/82 (1) For other selection, refer to codification table page 9 ..................... .... 15 Holding type Electric E Magnetic (2) M 16 Nominal control voltage A For UR26/36/40/46 24 VDC For UR26/36/40/46 36 VDC B For UR26/36/40/46 48 VDC C For UR26/36/40/46 64 VDC G For UR26/36/40/46 72 VDC D E For UR26/36/40/46/60/80 110 VDC For UR26/36/40/46/60/80 125 VDC R For UR26/36/40/46 220 VDC J 17 Varistor on coil No 0 Yes (battery voltage) 1 18 Direct over-current release (bi-directional) For UR26 1.4 - 2.7 kA A For UR26/36/40/46 2.0 - 8.0 kA D For UR36/40/46 4.0 - 15.0 kA F For UR60 13.0 - 18.0 kA L For UR80 16.0 - 24.0 kA P For other selection, refer to codification table page 6 ..................... .... Direct over-current release (uni-directional) - For UR60/80 (2) U U 19 Indirect release (shunt trip) No 0 For UR26/36/40/46 (includes also horizontal manual release type M3) BIM5 5 For UR26/36/40/46 (includes also horizontal manual release type M3) BIM6 2 For UR60/80 BIM7 (2) 4 20 Auxiliary contacts A For UR26/36/40/46/60/80 5a + 5b (3) - (switch PF) For UR26/36/40/46 5a + 5b - (switch CO) B 21 LV connector type on circuit-breaker For UR26/36/40/46/60/80 Harting type HAN 32 C For UR26/36/40/46 Veam type 22 pins B 22 Manual release No 0 For UR26/36/40/46 Horizontal type M3 1 For UR26/36/40/46 Vertical 2 23 Manual closing device (not compatible with line 25 nor 26) No 0 For UR26/36/40/46 Yes 3 24 Position indicator No 0 Yes 2 25 Overcurrent release detector (not compatible with line 23 nor 26) No 0 For UR26/36/40/46 Yes 1 26 Contact wear indicator (not compatible with line 23 nor 25) No 0 For UR26/36/40/46 Yes 1 27 HV main connections For UR26/36/40/46/60/80 according to pages 7 and 8 Standard S 28 Digit for Sécheron internal purpose For UR26/36/40 Arc chute 64 A A For UR26/36/40/46 Arc chute 81 & 82 B B For UR60/80 Arc chute 81 L L (1) Arc chute 82 only for UR46 (2) Under development for UR60/80 (3) For Veam type 22 pins mobile connector and options line 19 and/or 25 and/or 26 selected, the number of switches could be lower than 5a+5b Place and date: SG101699R00001 Name: Signature: Sécheron SA Rue du Pré-Bouvier 25 1217 Meyrin - Geneva CH - Switzerland Tel: +41 22 739 41 11 Fax: +41 22 739 48 11 info@secheron.com www.secheron.com This document is not contractual and contains information corresponding to the level of technology at the date of printing. Sécheron reserves the right to modify and/or improve the product, whose characteristics are described in these documents, as required by new technology at any time. It is the purchaser’s responsibility to inform himself, no matter what the circumstances, of the product’s maintenance conditions and requirements. Sécheron reserves all rights, especially those arising from our “General Delivery Conditions”. 16 Copyright© 2011 Sécheron SA SG101001BEN_F05-04.12 The low voltage connector must be ordered separately: SG104063R10100 VEAM type 22 pins: Harting type HAN 32: Value of the setting of the direct over-current release: . . . . . . . . . . . . .[A]