Technical Data FLEX Ex 1797 Series Intrinsically Safe I/O FLEX ExTM is a modular I/O system that mounts directly to the controlled equipment in the hazardous area. This eliminates the need for IS barriers/isolators and separation of control and process. We have taken our experience gained with the standard FLEX I/OTM system and used it to create an intrinsically safe system with the same look, feel, and ease of use. Distributed Architecture FLEX Ex leverages advanced technologies allowing the application to move to a distributed architecture in the hazardous area. 2 Overview FLEX Ex Overview Overall Design of the FLEX Ex System FLEX Ex combines a terminal strip and intrinsic-safety isolation with an I/O interface. Use the terminal strip on the terminal base to wire your field devices directly. The FlexEx design also offers these features: • modularity for distributed IS systems • all of the features of a larger, rack-based system • installation near the field devices to reduce wiring costs and complexity • terminations for all field wiring eliminating the need for marshalling or extra terminal strips • ControlNetTM-based networking solution with ControlNet ExTM products • DIN rail mounting FLEX Ex provides additional value if system problems develop. The terminal base lets you remove and insert modules under power without rewiring or disrupting your system. Combining your field-wiring terminations, IS isolation, and the I/O interface into the same location saves you time, money, and makes your system easier to maintain and troubleshoot. Additional benefits include: • dual-fault protection IS circuits provide the highest fault tolerance • I/O circuitry provides full IS field-device protection • modules that are conformally coated to meet the noxious gas requirements of ISA-S71.04-1985 severity level G3 for: hydrogen sulfide, sulfur dioxide, chlorine, nitrogen dioxide, hydrogen fluoride, ammonia and ozone • the modules themselves are IS protected for installation in hazardous environments FLEX Ex modules may be removed and inserted while operating under power. Network module maintenance and cable connections can be made in the hazardous area while the system is in operation and the area is hazardous. No equipment shutdown or area purging is necessary during these procedures, as the modules, network, and their connections are intrinsically safe. Publication 1797-2.1 - August 2001 FLEX Ex Overview ControlNet Ex Synergy 3 The combination of a ControlNet fiber hub (1786-RPA and -RPFM) and a ControlNet Ex fiber hub (1797-RPA and -RPFM) allows for flawless, high-speed, deterministic data flow and messaging between hazardous and safe areas. This combination functions as an intrinsically safe isolator between hazardous and safe areas and can provide long-distance communication. Safe Area PLC-5/20CTM processor or PLC-5/40CTM processor ProcessLogixTM I/O SLC 500TM processor ControlNet network ControlLogixTM processor . . . . 1 host computer with 1784-KTC card 1786 fiber hub FLEX I/O fiber 1797 fiber hub Hazardous Area FLEX Ex . . 1 coax 40051 The diagnostic capabilities and determinism of the ControlNet network make it an ideal choice for hazardous area applications. The redundant media ControlNet Ex communications adapter (1797-ACNR15) is high-speed and capable of communicating with as many as 8 I/O modules for up to 128 I/O points. ControlNet and ControlNet Ex repeater hubs facilitate the mixing of IS and non-IS systems via a communications link incorporating fiber optics for effective high-speed communication between hazardous and safe areas. An intrinsically safe network and I/O system installed in the hazardous area allows your data to be gathered at its origin and transported out of the area with the minimum amount of wiring. Cable penetrations into the hazardous area, cable trays, and conduit are all drastically reduced. Publication 1797-2.1 - August 2001 4 Overview Entity-Based Architecture FLEX Ex Entity parameters provide a system of quantifying and matching safe levels for voltage, current, inductance, and capacitance when connecting field devices and system devices together. Configuration of the FLEX Ex system is based on the entity parameter method. Using entity parameters allows high system flexibility in matching field and system devices. This provides maximum utility to the IS system designer and installer. Entity Parameters FLEX Ex uses entity parameters to rate its intrinsically safe modules. Inputs and outputs are specified with: • open-circuit voltage (Uo or Voc) • short-circuit current (Io or Isc) • allowed capacitance (Co or Ca) • allowed inductance (Lo or La) Switched outputs are specified as if they were inputs. Field devices using entity parameters are specified with: • maximum input voltage (Ui or Vmax) • maximum input current (Ii or Imax) • maximum internal capacitance (Ci) • maximum internal inductance (Li) In use, the sum of all the input Ci or Li in a control loop cannot exceed the Co or Lo and the sum of all the Uo or Io cannot exceed the input Ui or Ii. This is not meant to be a design example, only a short explanation of how entity-based architectures help simplify IS system design. Publication 1797-2.1 - August 2001 FLEX Ex Overview Entity Parameters Example 5 An output channel and the valve it will drive are illustrated in the following figure. By comparing entity parameters, you can quickly determine the appropriate match. cable length = 10m + 268Ω 21V P/I transmitter EEx ia IIC T4 Ui=30V Ii=165mA Ci=22.5nF Li=730uH Ci<10pF/m Li<0.5uH/m R<0.1Ω/m sig 22Ω 1797-IE8 Analog Input EEx ia/ib IIB/IIC T4 Uo<23.7V Io<93.5mA IIB Ca=560nF La=10mH IIC Ca=66nF La=2.5mH Module Uo Io Ca La < or = < or = > or = > or = Module Uo<23.7V Io<92.5mA Ca=66nF La=2.5mH < or = < or = > or = > or = Total Loop Ui Ii Ci Li = = = = Total Loop Ui=30V Ii=165mA Ci=22.6nF Li=735uH = = = = Transmitter Ui Ii Ci + Li + Distance Transmitter Ui=30V Ii=165mA Ci=22.5nF + + Li=730uH Distance Cable (length * Ci per length) (length * La per length) Cable (10m * Ci=10pF/m) (10m * La =0.5uH/m) 40052 In this example, the combination is compatible because the valve can withstand: • Ui • Ii = 30V = 165mA These values are higher than what the output can provide: • Uo = • Io = 23.7V 93.5mA In the same way, the valve is characterized by: • Ci • Li = 22.5nF = 730µH These values are lower than what the output allows: • Co = • Lo = 66nF 2.5mH Publication 1797-2.1 - August 2001 6 Overview FLEX Ex About the FLEX Ex System FLEX Ex consists of three space-saving components: • communication (adapters) • terminal base units • I/O modules Bus Connectors Adapter Terminal Base Keyswitch Flexbus Connector Ex I/O Module 1797-ACNR15 Ex PWR PWR Terminal Strips 20125-M Field Power Connection Terminals Use the adapter to power the I/O bus for as many as eight modules. Two separate connection terminals for field power let you daisy-chain power connections to adjacent terminal bases depending on power consumption. Removable power connections allow for easy wiring. Publication 1797-2.1 - August 2001 Use a the three-tier terminal base to wire directly to field devices. Terminate all of your wiring on the terminal base with no need for terminal blocks. Use the terminals to daisy-chain power connections to adjacent terminal bases, or connect individual power supplies to each base to isolate modules as dictated by module power requirements. Adjust the keyswitch to prevent incorrect module insertion into a preconfigured terminal base. Exchange terminal bases without moving other bases in your system. Plug the Ex I/O module into the terminal base. Use the module to connect to the I/O bus and field devices. Remove and insert a module without disturbing field wiring, other I/O modules, or system power. FLEX Ex Mount and Remove Your System Easily Overview 7 You can horizontally or vertically mount the FLEX Ex system on a standard 35mm DIN rail. The adapter and terminal base easily snap on the DIN rail by hand. Use a flat-blade screwdriver to remove components from the DIN rail. Screw holes allow you to horizontally or vertically panel-mount your system in an enclosure. An example of a DIN-rail mounted system is shown below. ATTENTION ! When properly installed, FLEX Ex is grounded through the DIN rail to chassis ground. Use zinc-plated, yellow-chromated steel DIN rail to assure proper grounding. Using other DIN rail materials (e.g. aluminum, plastic, etc.) which can corrode, oxidize, or are poor conductors can result in improper or intermittent platform grounding. If installing FLEX Ex on non-recommended DIN rail materials, use the mounting holes provided in each terminal base or a 1794-NM1 mounting kit with approved mounting bracket. Use mounting screws with star washers to provide the FLEX Ex platform with a chassis ground connection that is not likely to be affected by shock, vibration, or oxidation over time. DIN Rail A-B part no. 199-DR1 DIN 46277-3 (35 x 7.5mm) Screw holes are available for panel-mounting. Components are slotted to accept a DIN rail. 1797-ACNR15 PWR 20127-M Locking tab connector holds terminal base onto DIN rail. ATTENTION The hook (on the terminal base) and adjacent connection point (on the communication adapter) keep the terminal bases tight together. ! Publication 1797-2.1 - August 2001 8 Overview FLEX Ex Design Your Configuration You can use as many as eight terminal bases per adapter. This flexibility allows a wide variety of I/O channels per adapter. Mix and match digital and analog I/O to meet your application needs. Some examples include: • • • • • 128 digital inputs 64 digital inputs and 16 digital outputs 64 analog inputs 32 analog inputs and 32 analog outputs 32 digital inputs, 8 digital outputs, 24 analog inputs, and 8 analog outputs Any combination of digital I/O or analog modules. Adapter 20128-M As many as eight terminal bases. What this Technical Data Contains Use the following tables to find more information on the FLEX Ex system. For Information On Intrinsic Safety Terminology 10 Common Specifications 13 Environmental Conditions 14 Support, Training, and Repair Services 54 For Information On Communications Dual Media Adapter System Repeaters Taps Terminators Publication 1797-2.1 - August 2001 See Page Catalog Number Description See Page 1797-ACNR15/B Dual Media ControlNet Ex 1.5 Adapter 20 1797-RPA ControlNet Ex Coax Drop Repeater Module 21 1797-RPFM ControlNet Ex 3km Fiber Media Port Adapter 22 1797-TPS ControlNet Ex Straight T-Tap 23 1797-TPR ControlNet Ex Right Angle T-Tap 23 1797-TPYS ControlNet Ex Straight Y-Tap 23 1797-TPYR ControlNet Ex Right Angle Y-Tap 23 1797-XT ControlNet Ex 75Ω Terminator 23 1797-TCAP ControlNet Tap Terminator 23 FLEX Ex Overview For Information On Terminal Bases Terminal Base Units Catalog Number Description See Page 1797-TB3 3-Tier Screw Clamp Terminal Base Unit 24 1797-TB3S 3-Tier Spring Clamp Terminal Base Unit 25 1797-IBN16 7.5V dc 16 pt Non-Isolated NAMUR Input Module 26 1797-OB4D 24V dc 4 pt Non-Isolated Source Output Module 28 1797-IE8 8 pt 16 bit Single-Ended Non-Isolated Analog Input Module 30 Analog Input 1797-IE8NF 8 pt 16 bit Single-Ended Non-Isolated Analog Input Module with Noise Filter 32 Analog Output 1797-OE8 8 pt 13 bit Single-Ended Non-Isolated Analog Output Module 34 1797-IRT8 8 pt 16 bit Non-Isolated RTD/Thermocouple mV Input Module 36 1797-IJ2 2 Input Frequency Module 38 1797-PS2N 24V DC In Quad-Ex DC Out Power Supply - Conduit Pipe Thread 41 1797-PS2E 24V DC In Quad-Ex DC Out Power Supply - Increased Safety 41 1797-BOOT ControlNet Ex BNC Boot 48 1797-INS ControlNet Ex Trunk Insulators Kit 48 1797-EXMK FLEX Ex Cable Marking Kit 48 1794-CE1 FLEX I/O Extender Cable, 0.3m (1ft) 49 1794-CE3 FLEX I/O Extender Cable, 0.9m (3ft) 49 1797-BIC Bus Isolator Module - Hazardous Modules to IS Modules 51 1797-CEC Flexbus Connector 51 - Flexbus Metric Feed-Through 53 - Flexbus NPT Feed-Through 53 1797-CE1S FLEX Ex Extender Cable, 0.3m (1ft) 53 1797-CE3S FLEX Ex Extender Cable, 0.9m (3ft) 53 Digital DC Input DC Output Analog Analog Input Specialty Thermocouple/mV/RT DInput Frequency Input Power Supply DC Quad-Ex Accessories Extender Cables Media Bus Isolator Module Feed Throughs Extender Cables 9 Publication 1797-2.1 - August 2001 10 Intrinsic Safety Terminology FLEX Ex Intrinsic Safety Terminology Understanding Some Intrinsic Safety Terminology Read the following sections for more information on the general guidelines of intrinsic safety. Hazardous Area Designation A hazardous area is designated as any location in which a combustible material is or may be present in the atmosphere in sufficient concentration to produce an ignitable mixture. The North American method identifies these areas by Class, Division, and Group while the IEC (CENELEC) designates these areas by Zone and Gas Group. Recently, North America has adopted the Zone method of identifying hazardous locations as an option to the Division method. Class Designation Class identifies the type of hazardous atmosphere. Class I Gas or vapor Class II Dust Class III Fiber or flying (no group designation) Division/Zone Designations Division/Zone identifies the likelihood of a hazardous atmosphere being present. Division Method (North America) Ignitable mixture present continuously (long periods) Division 1 Ignitable mixture present intermittently Ignitable mixture is not normally present Publication 1797-2.1 - August 2001 Division 2 IEC Standard Zone Method Zone 0 (Zone 20-Dust) Zone 1 (Zone 21-Dust) Zone 2 (Zone 22-Dust) FLEX Ex Intrinsic Safety Terminology 11 Gas/Dust Groups Hazardous locations are grouped according to their ignition properties. Typical Gas IEC Gas Group North American Gas Group Acetylene IIC A Hydrogen IIC B Ethylene IIB C IIA D I D1 Metal Dust - E Coal Dust - F Grain Dust - - Propane Methane 1 1 Mining applications under jurisdiction of MSHA. Use in Class II and III (Dusts and Fibers) Hazardous Locations (North America) FLEX Ex modules are rated for installation in Class I Division 1 & 2, Groups A-D hazardous areas. They are also rated to connect to field devices that are located in Class I, II, or III, Groups A-G hazardous areas. If FLEX Ex components are to be installed in a Class II or III location in your application, you must mount them in a suitable, dust-proof enclosure with the appropriate connectors, glans, and seals. For example, a NEMA 4 enclosure may be appropriate. As always, observe local code requirements when applying your FLEX Ex application. Use in Zone Method Dusts and Fibers Hazardous Locations FLEX Ex modules are rated for installation in North American Class I Zone 1 & 2, Groups IIC, IIB & IIA and European Zone 1 & 2, Groups IIC, IIB, & IIA hazardous areas. They are also rated to connect to field devices that are located in North American Class I Zone 0, 1, & 2 Groups IIC, IIB & IIA and European Zone 0, 1, & 2, Groups IIC, IIB, & IIA hazardous areas. If FLEX Ex components are to be installed in a North American or European Zone method dust or fiber location in your application, you must mount them in a suitable, dust-proof enclosure with the appropriate connectors, glans, and seals. For example, a North American NEMA 4 or European IP 6x enclosure may be appropriate. As always, observe local code requirements when applying your FLEX Ex application. Publication 1797-2.1 - August 2001 12 Intrinsic Safety Terminology FLEX Ex For Zone application, especially in Europe, normal practice calls for the end application to obtain the dust and fiber rating due to strong dependence on wiring and other non-equipment related requirements. For example, FLEX Ex’s North American Class I Zone 0, 1, & 2 Groups IIC, IIB & IIA and European Zone 0, 1, & 2, Groups IIC, IIB & IIA hazardous area rating is used as the basis for the overall application to gain its dust and fiber certification. Methods of Protection The following techniques are rated by methods of protection. Symbol for Protection Method Zone Division Technique IEC CENELEC NEC CEC Permitted Zone Permitted Division Oil Immersion Ex o EEx o AEx o Ex o 1 and 2 * Pressurization Ex p EEx p AEx p Ex p 1 and 2 1 (X, Y) and 2 (Z) Powder Filling Ex q EEx q AEx q Ex q 1 and 2 * Flameproof Ex d EEx d AEx d Ex d 1 and 2 Increased Safety Ex e EEx e AEx e Ex e Intrinsic Safety Dual Fault Single Fault Ex ia Ex ib EEx ia EEx ib AEx ia AEx ib Ex ia Ex ib Non-Incendive Limited Energy Non-Sparking Enclosed Break Restricted Breathing Simplified Pressurization Ex nL Ex nV Ex nW Ex nR Ex nP EEx nL EEx nV EEx nW EEx nR EEx nP AEx nL AEx nV AEx nW AEx nR AEx nP Ex nL Ex nV Ex nW Ex nR Ex nP Encapsulation Ex m EEx m Aex m Ex m Type X, Y, Z Explosionproof * XP 1 and 2 1 and 2 * IS 1 and 2 0, 1, and 2 1 and 2 NI 2 2 1 and 2 * These protection methods are not recognized in the Division method. However, they may be suitable for some North American Division applications. Temperature Category The temperature category defines the maximum surface temperature of the device. Ratings are given with reference to 40oC ambient unless otherwise stated. T1 450oC (842oF) T3A 180oC (356oF) T2 300oC (572oF) T3B 165oC (329oF) T2A 280oC (536oF) T3C 160oC (320oF) T2B 260oC (500oF) T4 135oC (275oF) T2C 230oC (446oF) T4A 120oC (248oF) T2D 215oC (419oF) T5 100oC (212oF) T3 200oC (392oF) T6 85oC (185oF) The additional temperature categories highlighted above are for North America only. Publication 1797-2.1 - August 2001 FLEX Ex Intrinsic Safety Terminology 13 The following table illustrates common FLEX Ex system specifications. Agency Certification ControlNet Ex System - II (1) 2G SYST EEx ia/ib IIB/IIC T4 DMT 99 ATEX E 065 X CENELEC UL, C-UL II 2G EEx ib IIB/IIC T4 Class I Division 1 & 2 Groups A-D T4 Class I Zone 1 & 2 AEx ib IIC T4 Class I Division 1 Groups A-D T4 Class I Zone 1 AEx ib IIC T4 DMT 99 ATEX E 008 X UL, C-UL 99.19699 FM 3009806 FM CENELEC UL, C-UL 1797-RPA FM CENELEC UL, C-UL 1797-RPFM FM 1797-TB3S Dimensions (HxWxD) CENELEC 1797-ACNR15/B 1797-TB3 Certificate CENELEC UL, C-UL FM II (1) 2G EEx ia/ib IIB/IIC T4 Class I Division 1 & 2 Groups A-D T4 Class I Zone 1 & 2 AEx ib IIC T4 Class I Division 1 Groups A-D T4 Class I Zone 1 AEx ib IIC T4 II (1) 2G EEx ia/ib IIB/IIC T4 Class I Division 1 & 2 Groups A-D T4 Class I Zone 1 & 2 AEx ib [ia] IIC T4 Class I Division 1 Groups A-D T4 Class I Zone 1 AEx ib IIC T4 II 2G EEx ia IIC T4 Class I Division 1 & 2 Groups A-D T4 Class I Zone 1 & 2 AEx ia IIC T4 Class I Division 1 & 2 Groups A-D T4 Class I Zone 1 & 2 AEx ia IIC T4 94mm x 94mm x 91mm (3.7in x 3.7in x 3.58in) DMT 99 ATEX E 011 X UL, C-UL 99.19699 FM 3009806 DMT 98 ATEX E 012 X UL, C-UL 99.19699 FM 3009806 1797-IBN16 DMT 98 ATEX E 013 X UL, C-UL 99.19699 FM 3009806 1797-OB4D DMT 98 ATEX E 040 X UL, C-UL 99.19699 FM 3009806 1797-IE8 1797-IE8NF 1797-OE8 CENELEC UL, C-UL FM II (1) 2G EEx ia/ib IIB/IIC T4 Class I Division 1 & 2 Groups A-D T4 Class I Zone 1 & 2 AEx ib/[ia] IIC T4 Class I Division 1 Groups A-D T4 Class I Zone 1 AEx ib/[ia] IIC T4 DMT 98 ATEX E 020 X UL, C-UL 99.19699 FM 3009806 DMT 99 ATEX E 051 X UL, C-UL 99.19699 FM 3009806 1797-IRT8 DMT 98 ATEX E 023 X UL, C-UL 99.19699 FM 3009806 1797-IJ2 DMT 98 ATEX E 033 X UL, C-UL 99.19699 FM 3009806 1797-PS2N/A UL, C-UL Class I Division 1 Groups C-D T4 Class I Division 2 Groups A-D T4 UL, C-UL 99.19699 UL, C-UL Class I Division 1 Groups B-D T4 Class I Division 2 Groups A-D T4 Mounting - Class I Division 1 Groups B-D T4, Class I Division 2, Groups A-D, T4, Class I Zone 1 IIC IS Power - Class I Division 1&2 Groups A-G T4 Class I Zone 1 AEx [ib] IIC UL, C-UL 99.19699 FM 3009806 FM 1797-PS2N/B 1797-PS2E CENELEC EEx de [ib] IIC T4 BVS 98.D.2055X 94mm x 94mm x 69mm (3.7in x 3.7in x 2.7in) 46mm x 94mm x 75mm (1.8in x 3.7in x 2.95in) 174mm x 174mm x 128mm (6.9in x 6.9in x 5.04in) 174mm x 174mm x 280mm (6.9in x 6.9in x 11.0in) Publication 1797-2.1 - August 2001 14 Intrinsic Safety Terminology FLEX Ex Agency Certification CENELEC FM 1797-BIC FM 1797-CEC Certificate Dimensions (HxWxD) II (2)G [EEx ib] IIC Nonincendure, use for Class I, Division 2 Groups A-D or Class I, Zone 2 Group IIC Provides intrinsically safe outputs to Class I, Division 1 Groups A-D or Class I, Zone 1 Group IIC DMT 00 ATEX E056 Declaration of Conformity Directive 94/9 EC Zone 2 II 3G EEx nA IIC T4 X FM 3010810 87mm x 94mm x 75mm (3.4in x 3.7in x 2.95in) Nonincendure, use for Class I, Division 2 Groups A-D or Class I, Zone 2 Group IIC Declaration of Conformity Directive 94/9 EC Zone 2 II 3G EEx nA IIC T4 X FM 3010810 80mm x 55mm x 69mm (3.15in x 2.17in x 2.72in) C US The following table illustrates FLEX Ex system environmental conditions. Operational Temperature Storage Temperature Relative Humidity Operating Shock Non-Operating Shock Vibration Noxious Gas Exposure Environmental Conditions -20 to 70oC (-4 to 158oF) -40 to 85oC (-40 to 185oF) 5 to 95% noncondensing Tested 15g peak acceleration, 11(+1)ms pulse width Tested 15g peak acceleration, 11(+1)ms pulse width Tested 2g @ 10-500Hz per IEC 68-2-6 Tested to severity level G3, ISA-S71.04-1985 About Entity Parameters Publication 1797-2.1 - August 2001 For a complete listing of I/O entity parameters, refer to the FLEX Ex System Certification Reference Manual, publication 1797-6.5.6. 30670-M Hazardous Area Zone 0 Safe Area Node 1 75 Ohm 1W Ci negl. Li negl. CNet Ex trk trm Uo=5.4V, Io=201mA, F-3>500kHz . . 4 5 Li < 1100uH CNet Ex tap trm Ci<68pF Li negl. Li < 1100uH Li < 560nH Ci < 60pF 2 Ch0 fiber . Ch1 fiber Ch0 fiber ControlNet Ex tap . . Ch1 fiber coax trunk cable Cable type 1189A, 3092A, or 3092A Blue from manufacturer Belden Wire or type RG6-CNet* . . 2 1797-RPFM/* or RSD-FC-Ex2.CN 3km Hazardous Area Zone 0 1797-RPFM/* or RSD-FC-Ex2.CN 3km 2 1 Power Supply Ui=9.5V, Ii=1A, Ci=<120nF, Li=negligible ControlNet Ex tap . 1797-RPA/* or RSD-CFA-Ex.CN Node 2 ChB Uo=5.4V, Io=160mA, F-3>500kHz . . ControlNet Ex tap Power Supply Ui=9.5V, Ii=1A, Ci=<120nF, Li=negligible 2 1 1 Flexbus Uo=5.4V, Io=400mA, Po=2.16W, Co=65µF, Lo=10µH ChA Uo=5.4V, Io=160mA, F-3>500kHz coax trunk cable 1 3 Node 4 ... 48 . ChB Uo=5.4V, Io=160mA, F-3>500kHz . . 2 . ControlNet Ex tap Power Supply Ui=9.5V, Ii=1A, Ci=<120nF, Li=negligible 1797-ACNR15/* or RSD-GW-Ex2.CN CNet Ex trk trm 1 Cable Attenuation (-20to+70oC) 0.2MHz > 0.93dB/100m 0.5MHz > 0.95dB/100m 1MHz > 1.07dB/100m 2MHz > 1.16dB/100m *RG6-CNet is defined as: Cable Impedance=75 Ohm + or -3 Ohm Cable Capacitance<5.94nF per 100m Cable Resistance>9.08 Ohm per 100m 5MHz > 1.39dB/100m 10MHz >1.86dB/100m 20MHz > 2.73dB/100m 50MHz > 4.33dB/100m Near the main components of the system a plate with the system marking must be attached. If the system is installed in a cabinet the plate must be fixed on the inside of the cabinet door. The ambient temperature range of the ControlNet Ex system is -20 to +70 oC. 1 75 Ohm 1W Ci negl. Li negl. Flexbus Uo=5.4V, Io=400mA, Po=2.16W, Co=65µF, Lo=10µH The Coax Trunk Cable is permitted to have a minimum length of 1,000m with only 2 connected ControlNet Ex Taps dropping to only 250m with the maximum allowed connected ControlNet Ex Taps of 48. ChA Uo=5.4V, Io=160mA, F-3>500kHz . . 1797-ACNR15/* or RSD-GW-Ex2.CN Node 3 Protect the system against electrostatic charge. Post a sign near the main components of the system: Attention! Avoid electrostatic charge. power density of the transmitter diode must be <5mW/mm2. For the transmittal between the safe area and the hazardous area only optical glass-fibers are permitted. The diameter of a single glass-fiber must be >6um. The The ControlNet Ex System is an intrinsically safe system according to EN 50039. When installing the system, the certificate of conformity and the national installation regulations must be heeded. The components of the ControlNet Ex system and the interconnections are shown on the installation drawing (A-B Pub. 1797-6.5.6). FLEX Ex Communication System 15 Communication System CENELEC ControlNet Ex System Diagram Publication 1797-2.1 - August 2001 Publication 1797-2.1 - August 2001 Hazardous (Classified) Location Zone 0, 1 or 2, IIC Class I, Zones 0, 1 and 2, Groups IIC, IIB, IIA Class I Division 1 and 2, Groups A, B, C, D Class II, Division 1 and 2, Groups E, F, G Class III, Division 1 and 2 1786-RPFM or any associated apparatus where the light emitting diode output is <5mW/mm2 Non-Hazardous Location CNet Ex tap trm ControlNet Ex tap 2 To any approved device or associated apparatus with Entity Concept parameters of Voc<9.5V and Isc<1A 1 . ControlNet Ex tap 2 Ch0 . Ch1 . . Ch1 4 . coax trunk cable 5 fiber optic cable Ch0 . 1797-RPFM The ambient temperature range of the ControlNet Ex system is -20 to +70 oC. CNet Ex trk trm . . 1797-RPFM Power Supply Vmax=9.5V, Imax=1A, Ci<120nF, Li=0 Node 1 . Node 2 1797-RPA 2 ChA . 1 1 . ControlNet Ex tap . 2 1 1 . 2 ÷ ControlNet Ex tap CNet Ex trk trm Power Supply Vmax=9.5V, Imax=1A, Ci<120nF, Li=0 30670-M 1 any IS device with entity concept parameters Vmax, Imax Ci, Li) appropriate for connection to associated apparatus with entity concept parameters listed in Table 1. Maximum devices=8. To any approved device or associated apparatus with Entity Concept parameters of Voc<9.5V and Isc<1A ChB . Node 4 ... 48 1797-ACNR15 Hazardous (Classified) Location Zone 1 or 2, IIC Class I, Zones 1 and 2, Groups IIC, IIB, IIA Class I Division 1 and 2, Groups A, B, C, D Class II, Division 1 and 2, Groups E, F, G Class III, Division 1 and 2 coax trunk cable ChA 1 any IS device with entity concept parameters Vmax, Imax Ci, Li) appropriate for connection to associated apparatus with entity concept parameters listed in Table 1. Maximum devices=8. Power Supply Vmax=9.5V, Imax=1A, Ci<120nF, To any approved device or associated Li=0 apparatus with Entity Concept parameters of Voc<9.5V and Isc<1A ChB . Node 3 1797-ACNR15 3 Hazardous (Classified) Location Zone 1 or 2, IIC Class I, Zones 1 and 2, Groups IIC, IIB, IIA Class I Division 1 and 2, Groups A, B, C, D 16 Communication System FLEX Ex UL, C-UL ControlNet Ex System Diagram Ch1 fiber optic cable Ch0 . . úö ⑧ ChB . ÷ ControlNet Ex tap ⑦ . ChA ⑧ ChB . Node 4 ... 48 1797-ACNR15 1 . From FM approved 1797-PS2N ⑦ Vmax=9.5V Imax=1A Ci<=120nF Li=0 For connection to other I/O modules, refer to General FM Certification Information in publication 1797-6.5.6 on page 31-1. ControlNet Ex tap ⑦ CNet Ex trk trm ⑦ Class I, Zone 1, 2 Group IIC, IIB, IIA Class I Division 1, Groups A, B, C, D Class II, Division 1, Groups E, F, G Class III, Division 1 Hazardous (Classified) Location coax trunk cable Vmax=9.5V Imax=1A Ci<=120nF Li=0 From FM approved 1797-PS2N ⑦ 1 . For connection to other I/O modules, refer to General FM Certification Information in publication 1797-6.5.6 on page 31-1. ó coax trunk cable Any associated apparatus where the light emitting diode output is <5mW/mm2 or total <1mW. ChA . Node 3 1797-ACNR15 Communication System 42476 . The ambient temperature range of the ControlNet Ex System is -20oC to +70oC. ÷ Class I, Zone 0, 1, 2 Group IIC, IIB, IIA Class I Division 1, Groups A, B, C, D Class II, Division 1, Groups E, F, G Class III, Division 1 Hazardous (Classified) Location ó CNet Ex trk trm ⑦ 11 ó ÷ ControlNet Ex tap ⑦ Ch1 . ç ControlNet Ex tap ⑦ Ch0 . . 1797-RPFM û Node 1 Vmax=9.5V From FM approved Imax=1A Ci<=120nF 1797-PS2N ⑦ Li=0 . . 1797-RPFM ç CNet Ex trk trm ⑦ . ó û ó û Any associated apparatus where the light emitting diode output is <5mW/mm2 or total <1mW. Any associated apparatus where the light emitting diode output is <5mW/mm2 or total <1mW. 1797-RPA Node 2 Class I, Zone 1, Group IIC Class I Division 1, Groups A, B, C, D Hazardous (Classified) Location ì 1786-RPFM or Non-Hazardous Location FLEX Ex 17 FM ControlNet Ex System Diagram ó ÷ Publication 1797-2.1 - August 2001 18 Communication System FLEX Ex Describing the ControlNet Ex System Diagram A maximum of 48 ControlNet Ex nodes may be connected together by 250m of coax cable and 48 taps. The distance increases to 1000m when you use only 2 taps. See the table below for more information. The fiber media of the 1797-RPFM can be installed in a hazardous location (Zone 0, 1 or 2; Class I, Zones 0, 1, and 2; Class I, Division 1 and 2; Class II, Division 1 and 2; Class III, Division 1 and 2) to connect two 1797-RPFM modules or they can be installed through different locations into the non-hazardous location to connect the 1797-RPFM with any approved associated apparatus. All cables and fiber media that are not light blue must be marked as IS using the 1797-EXMK marking kit or other locally approved IS identification and/or segregation method. During the installation of the ControlNet Ex system, all metallic parts must be isolated to prevent an earth connection (high voltage withstanding of isolating material must be > 500V ac). System Diagram Name 1797-RPA Catalog Number Catalog Name 1797-RPA ControlNet Ex Modular Repeater Adapter 1797-RPFM 1797-RPFM 1797-ACNR15 1797-ACNR15 CNet Ex Tap Trm 1797-TCAP ControlNet Ex Tap 1797-TPx CNet Ex Trk Trm 1797-XT Coax Trunk Cable 1786-RG6 None None Publication 1797-2.1 - August 2001 Description Represents one ControlNet Ex node and must be connected to a coax trunk cable by 1797-TPx ControlNet Ex Fiber Repeater Allows connection of a maximum of two devices per Module, Medium Distance 1797-RPA and is powered directly by 1797-RPA Redundant Media ControlNet Represents one ControlNet Ex node and must be Ex Adapter connected to a coax trunk cable by 1797-TPx -each one with two redundant output channels that are connected to different ControlNet Ex networks (coax cables and 1797-TPx) ControlNet Ex Tap (Dummy) Represents one ControlNet Ex node and is a simple Terminator capacitor (56pF) with a coax connector ControlNet Ex Coax Tap Four types of connections available: S (straight t-tap), R (right angle t-tap), YS (straight y-tap), and YR (right angle y-tap) - a maximum of 48 taps can be connected together by coax trunk cable ControlNet Ex Trunk Simple resistor (75Ω) with coax connector that must Terminator be on each end of the ControlNet Ex coax trunk for termination Quad-Shield, RG-6 75Ω Coax Maximum (functional) length between 2 1797-TPx is Trunk Cable 3280ft (1000m) - each 1797-TPx reduces the (functional) coax cable length by 53.4ft (16.3m) Standard Coax Trunk Cable Different standard cable couplers, 90o, 180o, etc. BNC Couplers FLEX Ex Communication System 19 Certified Equivalent ControlNet Ex System Diagram Items You may use these items as equivalents for the items shown on the system diagram. System Diagram Name Catalog Number Source 1797-RPA 1797-RPA1 Allen-Bradley 1797-RPFM 1797-RPFM1 Allen-Bradley 1797-ACNR15 1797-ACNR151 Allen-Bradley 1786-RG6 Allen-Bradley Coax Trunk Cable 2 3092A 3 Belden Wire & Cable Co. 3092A with blue jacket Belden Wire & Cable Co. ControlNet Ex Tap 1797-TPx Allen-Bradley CNet Ex Trk Trm 1797-XT Allen-Bradley CNet Ex Tap Trm 1797-TCAP Allen-Bradley 1 2 3 For complete information on interpreting the system drawings, refer to the FLEX Ex System Certification Reference Manual, publication 1797-6.5.6. In addition to these cable types, the following specification can be followed to allow additional types: Cable Impedance = 75Ω + 3Ω Cable Capacitance = <5.94nF per 100m Cable Resistance = >9.08Ω per 100m Cable Attenuation 0.2MHz > 0.93dB/100m5MHz > 1.39dB/100m 0.5MHz > 0.95dB/100m10MHz > 1.86dB/100m (-20 to +70oC) 1MHz > 1.07dB/100m20MHz > 2.73dB/100m 2MHz > 1.16dB/100m50MHz > 4.33dB/100m Belden Wire & Cable 1189A may be used, but with functional loss of communication distance and/or nodes. Publication 1797-2.1 - August 2001 20 Dual Media ControlNet Ex 1.5 Adapter Cat. No. 1797-ACNR15 FLEX Ex Product Features Dual Media ControlNet Ex 1.5 Adapter Cat. No. 1797-ACNR15 • Provides interface from the local backplane I/O bus to the network fieldbus • Provides power to the backplane to run bus interface circuitry aboard I/O modules 1797-ACNR15 • Capable of accepting dual ControlNet Ex cable media PWR 40054 Customer Connections +V Power Supply -V Channel A Bus Network Flexbus Dual Port RAM Channel B uC uC 40055 1797-ACNR15 Specifications 1797-ACNR15 Specifications I/O Capacity 8 modules Power Consumption 8.5W EEx ib IIB/IIC T4, AEx ib IIC T4, Class I, Division 1 Groups A-G T4 Power Dissipation 8.5W Thermal Dissipation 29 BTU/hr Conductor Wire Size 12 gauge (4mm2) stranded maximum 3/64in (1.2mm) insulation maximum Approximately 200g IS Media Type IS Module Type EEx ib IIB/IIC T4, AEx ib IIC T4, Class I Division 1 Groups A-D T4 Weight Communication Rate 5m bit/s Environmental Conditions ControlNet Ex BNC (ChA and Oscillation powered by: ChB) Uo < 5.4V dc Io < 160mA ac coupled with high-pass filter f-3 > 500kHz Indicators Output (Intrinsically Safe) (16 position male/female flexbus connector) Isolation Path Flexbus to Power Supply Flexbus to ControlNet ControlNet Ex Node to Other Node ControlNet Ex to Power Supply Power Supply (+V, -V Intrinsically Safe) Comm A Comm B Module Status Power Uo Io Po Lo Co red/grn red/grn red/grn grn < 5.8V dc < 400mA < 2.16W < 10µH < 65µF Galvanic to DIN EN50020 Galvanic functional Galvanic functional Operational Temperature -20 to 70oC (-4 to 158oF) Storage Temperature -40 to 85oC (-40 to 185oF) Relative Humidity 5 to 95% noncondensing Shock Tested 15g peak acceleration, 11 (±1)ms pulse width Operating Non-Operating Vibration Tested 15g peak acceleration, 11 (±1)ms pulse width Tested 2g @ 10-500Hz per IEC 68-2-6 Agency Certification CENELEC II 2G EEx ib IIB/IIC T4 UL, C-UL Class I Division 1 & 2 Groups A-D T4 Class I Zone 1 & 2 AEx ib IIC T4 FM Class I Division 1 Groups A-D T4 Class I Zone 1 AEx ib IIC T4 Certificates CENELEC DMT 98 ATEX E008 X UL, C-UL UL Certificate Number 99.19699 Galvanic to DIN EN50020 Ui Ii Pi Li Ci < 9.5V dc < 1A < 9.5W = Negligible < 120nF Publication 1797-2.1 - August 2001 C FM US Class I Division 1 Hazardous FM Certificate Number 3009806 FLEX Ex ControlNet Ex Coax Drop Repeater Module Cat. No. 1797-RPA Product Features ControlNet Ex Coax Drop Repeater Module Cat. No. 1797-RPA • Functions as part of the fiber repeater hub within the hazardous area to extend the length of the ControlNet Ex segments to interlink systems all operating within the area 1797-RPA COMM MODULE STATUS STATUS 21 REPEATER ADAPTER • Functions as the intelligent starter block for a multiport repeater PWR 1 2 3 4 +V -V +V -V • Configured with at least one media adapter 40056 Customer Connections power supply +V -V network bus channel fiber hub bus uC uC 41309 1797-RPA Specifications 1797-RPA Specifications I/O Capacity 2 fiber modules Thermal Dissipation 29 BTU/hr IS Media Type EEx ib IIB/IIC T4, AEx ib IIC T4, Class I, Division 1 Groups A-G T4 Conductors 12 gauge (4mm2) stranded maximum 3/64in (1.2mm) insulation maximum IS Module Type EEx ib IIB/IIC T4, AEx ib IIC T4, Class I Division 1 Groups A-D T4 Wire Size Dimensions 94mm x 94mm x 91mm (3.7in x 3.7in x 3.58in) Weight Approximately 200g Environmental Conditions Communication Rate 5m bit/s Operational Temperature ControlNet Ex BNC Oscillation powered by: < 5.4V dc Uo < 201mA Io ac coupled with high-pass filter f > 500kHz Storage Temperature -40 to 85oC (-40 to 185oF) Relative Humidity 5 to 95% noncondensing Indicators Output (Intrinsically Safe) (30 pin male TTL bus connector) Isolation Path Bus to Power Supply Adapter to Adapter ControlNet Ex Node to Other Nodes ControlNet to Power Supply Power Supply (-V, +V Intrinsically Safe) Comm green/red Module green/red Power green Manufacturer specific bus Uo < 5.4V Io < 201mA Po < 1.09W Lo < 0.45mH Co < 71µF Galvanic to DIN EN50020 Galvanic functional Galvanic functional Galvanic to DIN EN50020 Ui < 9.5V dc Ii < 1A Pi < 9.5W Li = negligible Ci < 120nF Power Consumption 8.5W Power Dissipation 8.5W Shock -20 to 70oC (-4 to 158oF) Operating Tested 15g peak acceleration, 11 (±1)ms pulse width Non-Operating Tested 15g peak acceleration, 11 (±1)ms pulse width Vibration Tested 2g @ 10-500Hz per IEC 68-2-6 Agency Certification CENELEC II (1) 2G EEx ia/ib IIB/IIC T4 UL, C-UL Class I Division 1 & 2 Groups A-D T4 Class I Zone 1 & 2 AEx ib IIC T4 FM Class I Division 1 Groups A-D T4 Class I Zone 1 AEx ib IIC T4 Certificates CENELEC DMT 98 ATEX E011 X UL, C-UL UL Certificate Number 99.19699 C FM US Class I Division 1 Hazardous FM Certificate Number 3009806 Publication 1797-2.1 - August 2001 22 ControlNet Ex 3km Fiber Media Port Adapter Cat. No. 1797-RPFM FLEX Ex Product Features ControlNet Ex 3km Fiber Media Port Adapter Cat. No. 1797-RPFM • Functions as part of the fiber repeater hub within the hazardous area to extend the length of the ControlNet Ex segments to interlink systems all operating within the area 1797-RPFM • Functions as a non-intelligent fiber to backplane conversion device FIBER MODULE MEDIUM RANGE Chan 1 Recv • Converts glass fiber infrared LED media signals to backplane signals for use by the coax drop repeater module (cat. no. 1797-RPA) Chan 2 Xmit Recv Xmit 40057 Customer Connections receiver channel transmitter bus fiber hub bus receiver proc channel transmitter 41310 1797-RPFM Specifications 1797-RPFM Specifications IS Media Type IS Module Type EEx ia IIB/IIC T4, AEx ia IIC T4, Class I, II, III Division 1 & 2 Groups A-G T4 EEx ib IIB/IIC T4, AEx ib IIC T4, Class I Division 1 & 2 Groups A-D T4 Communication Rate 5m bit/s Approximate Fiber Media Length 3km Fiber Type 62.5/125 mm Power Consumption Included in 1797-RPA Power Dissipation Included in 1797-RPA Thermal Dissipation Included in 1797-RPA Weight Approximately 100g Dimensions 94mm x 94mm x 91mm (3.7in x 3.7in x 3.58in) Environmental Conditions Operational Temperature -20 to 70oC (-4 to 158oF) Storage Temperature -40 to 85oC (-40 to 185oF) 5 to 95% noncondensing Fiber Termination Type ST (plastic or ceramic) Relative Humidity Fiber Operating Wavelength 1300 nm Shock Operating Tested 15g peak acceleration, 11 (±1)ms pulse width Non-Operating Tested 15g peak acceleration, 11 (±1)ms pulse width Optical Power Budget 13.3 dB Fiber Optic Transmitter Ch1 and Ch2 Optical peak output power Poptical < 1mW Indicators Channel 1 status - green Channel 2 status - green CENELEC II (1) 2G EEx ia/ib IIB/IIC T4 UL, C-UL Class I Division 1 & 2 Groups A-D T4 Class I Zone 1 & 2 AEx ib [ia] IIC T4 Ui < 5.4V Ii < 201mA Pi < 1.1W Li < 15µH Ci < 41µF FM Class I Division 1 Groups A-D T4 Class I Zone 1 AEx ib IIC T4 Input (Intrinsically Safe) (30 pin female TTL bus connector) Output (Intrinsically Safe) (30 pin male TTL bus connector) Isolation Path Bus to ControlNet Uo < 5.4V Io < 201mA Po < 1.1W Lo < 0.45mH Co < 71µF Galvanic to DIN EN50020 Publication 1797-2.1 - August 2001 Vibration Tested 2g @ 10-500Hz per IEC 68-2-6 Agency Certification Certificates CENELEC DMT 98 ATEX E011 X UL, C-UL UL Certificate Number 99.19699 C FM US Class I Division 1 Hazardous FM Certificate Number 3009806 FLEX Ex ControlNet Ex Taps and Terminators Cat. Nos. 1797-TPS, -TPR, -TPYS, -TPYR, -XT and -TCAP 23 ControlNet Ex Taps and Terminators Cat. Nos. 1797-TPS, -TPR, -TPYS, -TPYR, -XT and -TCAP ControlNet Ex Straight T-Tap Cat. No. 1797-TPS ControlNet Ex Right-Angle T-Tap Cat. No. 1797-TPR 40058 ControlNet Ex Straight Y-Tap Cat. No. 1797-TPYS 40059 ControlNet Ex Right-Angle Y-Tap Cat. No. 1797-TPYR 40060 ControlNet Ex 75Ω Terminator Cat. No. 1797-XT 40061 ControlNet Tap Terminator Cat. No. 1797-TCAP 40875 40874 Publication 1797-2.1 - August 2001 24 3-Tier Screw Clamp Terminal Base Unit Cat. No. 1797-TB3 3-Tier Screw Clamp Terminal Base Unit Cat. No. 1797-TB3 FLEX Ex Specifications - 1797-TB3 Flexbus Connection Ui Intrinsically Safe Ii Ci Li <10V dc <400mA <1nF Negligible Isolation Voltage Channel-to-channel isolation determined by inserted module Weight 200g (approximately) Dimensions (with module installed in base)Inches 3.7H x 3.7W x 2.7D (Millimeters) (94H x 94W x 69D) Environmental Conditions 40062 Operational Temperature -20 to 70oC (-4 to 158oF) Storage Temperature -40 to 85oC (-40 to 185oF) Relative Humidity 5 to 95% noncondensing Shock Tested 15g peak acceleration, 11 (±1)ms pulse width Operating Tested 15g peak acceleration, 11 (±1)ms pulse width ATTENTION ! ATTENTION ! Make certain that the hook on the terminal base you are installing is properly hooked into the adjacent terminal base/adapter. Failure to lock the hook into the adjacent base/adapter can result in loss of communication on the backplane. Do not force the terminal base into the adjacent base/adapter. Forcing the units together can bend or break the hook and allow the units to separate and break communication over the backplane. Non-Operating Vibration Conductors Tested 2g @ 10-500Hz per IEC 68-2-6 Wire Size 12 gauge (4mm2) stranded maximum 1.2mm (3/64in) insulation maximum Agency Certification CENELEC II 2G EEx ia IIC T4 UL, C-UL Class I Division 1 & 2 Groups A-D T4 Class I Zone 1 & 2 AEx ia IIC T4 FM Class I Division 1 & 2 Groups A-D T4 Class I Zone 1 & 2 AEx ia IIC T4 Certificates CENELEC DMT 98 ATEX E012 U UL, C-UL UL Certificate Number 99.19699 C The 1797-TB3 terminal base unit is intended for users preferring the screw-type wire retention method. You can use the 1797-TB3 terminal base unit with any module on the FLEX Ex system. Specific terminal function is governed by the I/O module itself. Check the installation instructions for each module to determine the specific terminal functions. Specifications - 1797-TB3 Number of Terminals 1 row of 16, 2 rows of 18 Terminal Screw Torque 7-9 inch-pounds Terminals Assignments1 +34, -35, +50, -51, and 96 pinifemale I/O connector pinsi30-32, 62-64, 94-96i Only for intrinsically safe circuits Ui <10V dc <2.5A Ii < 1nF Ci Negligible Li Must not be used for any connection <30V dc Ui <100mA Ii <1nF Ci Negligible Li 36, 49 All Other Terminals FM 1 US Class I Division 1 Hazardous FM Certificate Number 3009806 Termination connections are unique with each I/O module. Refer to the appropriate I/O module’s installation instructions. The 1797-TB3 terminal base also has connections for cold junction compensation and terminals designated for shield termination to chassis ground. The terminal base is equipped with a factory-installed tab cover for the backplane bus connection. The tab cover may be removed only when the terminal base unit is connected to other terminal base units or 1794-CE1 or -CE3 extender cables. Wiring Connections for Terminal Base 1797-TB3 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 A 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 B 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 C +V -V +V -V No connections allowed to terminals 36 and 49 41252 Publication 1797-2.1 - August 2001 FLEX Ex 3-Tier Spring Clamp Terminal Base Unit Cat. No. 1797-TB3S 3-Tier Spring Clamp Terminal Base Unit Cat. No. 1797-TB3S Only for intrinsically safe circuits Ui <10V dc <2.5A Ii <1nF Ci Negligible Li Must not be used for any connection <30V dc Ui <100mA Ii <1nF Ci Negligible Li Terminals Assignments1 +34, -35, +50, -51, and 96 pin female I/O connector pinsi30-32, 62-64, 94-96i 36, 49 All Other Terminals ATTENTION ! ATTENTION ! Do not force the terminal base into the adjacent base/adapter. Forcing the units together can bend or break the hook and allow the units to separate and break communication over the backplane. Ui Ii Ci Li Isolation Voltage Channel-to-channel isolation determined by inserted module Weight 200g (approximately) Dimensions (with module installed in base)Inches 3.7H x 3.7W x 2.7D (Millimeters) (94H x 94W x 69D) Environmental Conditions Operational Temperature -20 to 70oC (-4 to 158oF) Storage Temperature -40 to 85oC (-40 to 185oF) Relative Humidity 5 to 95% noncondensing Shock Tested 15g peak acceleration, 11 (±1)ms pulse width Operating Tested 15g peak acceleration, 11 (±1)ms pulse width Non-Operating Vibration Conductors Tested 2g @ 10-500Hz per IEC 68-2-6 Wire Size 12 gauge (4mm2) stranded maximum 1.2mm (3/64in) insulation maximum Agency Certification The 1797-TB3S terminal base unit is intended for users preferring the spring-type wire retention method. You can use the 1797-TB3S terminal base unit with any module on the FLEX Ex system. Specific terminal function is governed by the I/O module itself. Check the installation instructions for each module to determine the specific terminal functions. The 1797-TB3S terminal base has 36 wiring connections to/from a plug-in module. The use of each terminal depends on the module mounted in this base. It also has connections for cold junction compensation and terminals designated for shield termination to chassis ground. Specifications - 1797-TB3S Number of Terminals 1 row of 16, 2 rows of 18 Number of Terminals 1 row of 16, 2 rows of 18 Terminal Type <10V dc <400mA <1nF Negligible Flexbus Connection Intrinsically Safe 40063 Make certain that the hook on the terminal base you are installing is properly hooked into the adjacent terminal base/adapter. Failure to lock the hook into the adjacent base/adapter can result in loss of communication on the backplane. 25 Spring-clamp - To open, insert bladed screwdriver (0.100 - 0.120in/2.54-3.05mm) and lift up. CENELEC II 2G EEx ia IIC T4 UL, C-UL Class I Division 1 & 2 Groups A-D T4 Class I Zone 1 & 2 AEx ia IIC T4 FM Class I Division 1 & 2 Groups A-D T4 Class I Zone 1 & 2 AEx ia IIC T4 Certificates CENELEC DMT 98 ATEX E012 U UL, C-UL UL Certificate Number 99.19699 FM FM Certificate Number 3009806 C 1 US Class I Division 1 Hazardous Termination connections are unique with each I/O module. Refer to the appropriate I/O module’s installation instructions. The terminal base is equipped with a factory installed tab cover for the backplane bus connection. The tab cover may be removed only when the terminal base unit is connected to other terminal base units or 1794-CE1 or -CE3 extender cables. 0 1 16 17 34 2 18 35 36 3 4 5 6 7 8 9 10 11 12 13 14 19 20 21 22 23 24 25 26 27 28 29 30 37 38 39 40 41 42 43 44 45 46 47 48 15 31 49 32 33 50 51 Label placed at top of wiring area Row A Row B Row C Row A Row B Row C +V-V +V -V 41254 No connections allowed to terminals 36 and 49 Publication 1797-2.1 - August 2001 26 16 pt Non-Isolated NAMUR Input Module Cat. No. 1797-IBN16 FLEX Ex 16 pt Non-Isolated NAMUR Input Module Cat. No. 1797-IBN16 Ex 1797-IBN16 PWR 40064 Product Features • 16 single-ended input channels referenced to a single common • Maximum no load voltage/short-circuit current: U/V = 7.5V dc/ I = 7.5mA • Yellow LED to indicate input state, input ON = LED ON • Fault detection, fault bits in data table and LED (per channel) blinking red (1Hz) • DIN 19234, NAMUR compatible • Switching points/hysteresis: I = 1.2mA to 2.1mA/0.2mA • Input pulse width on/off: >500µs/>500µs • Lead breakage threshold: I<0.35mA • Lead breakage defeat on four-channel group basis via module DIP switch selection • Fault detection can be disabled via data table • Input frequency up to 1000Hz • Programmable digital input filtering 1 to 33ms (OFF-ON and ON-OFF) • All channels updated to flexbus<500µs • Module field-side power consumption: 2.8W Customer Connections lead break defeat +V -V Flexbus NAMUR Prox Bus + µC Publication 1797-2.1 - August 2001 Power Supply ~1.5K ~9K - FLEX Ex 16 pt Non-Isolated NAMUR Input Module Cat. No. 1797-IBN16 27 Terminal Base Assignment 0 1 2 3 4 + - + - + 5 6 7 8 9 10 11 12 13 14 15 + - + - Row A Ch 0 16 Ch 1 - + Ch 2 - + Ch 3 - + Ch 4 - Ch 5 Ch 6 Ch 7 17 18 19 20 21 22 23 24 25 26 27 28 29 30 + - + - + - + - + - + - + - 31 32 33 Row B Ch 8 34 Ch 9 35 36 Ch 10 37 38 Ch 11 39 40 Ch 12 41 42 Ch 13 43 44 + Ch 14 45 46 - Ch 15 47 48 49 50 51 Row C 41504 +V -V +V -V No connection allowed to terminals 36 and 49 Specifications - 1797-IBN16 Module Location Cat. No. 1797-TB3 or -TB3S Terminal Base Unit Number of Inputs 16 (1 group of 16), non-isolated, sinking Conductor Wire Size IS Input Type EEx ia IIB/IIC T4, AEx ia IIC T4, Class I, II, III Division 1 Group A-G T4 12 gauge (4mm2) stranded maximum 3/64in (1.2mm )insulation maximum Dimensions IS Module Type EEx ib IIB/IIC T4, AEx ib IIC T4, Class I, Division 1 & 2 Group A-D T4 46mm x 94mm x 75mm (1.8in x 3.7in x 2.95in) Weight 200g (approximate) Input Type DIN19234, NAMUR compatible Keyswitch Position 6 ON-State Current 2.1mA OFF-State Current 1.2mA Hysteresis 0.2mA Input Frequency 1000Hz maximum Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Shock Operating Nonoperating Vibration Input Pulse Width >500µs on or off Maximum Load Voltage U/V = 7.5V dc Short Circuit Current I = 7.5mA Short Circuit Threshold I > 6mA Lead Breakage Threshold I < 0.35mA Input Delay Times OFF to ON ON to OFF 1ms, 2ms, 3ms, 5ms, 9ms, 17ms, 33ms 1ms, 2ms, 3ms, 5ms, 9ms, 17ms, 33ms 1ms default - selectable thru output image table (see Setting Input Filter Times) Indicators (field side indication, customer device driven) 16 yellow status indicators 16 red fault indicators 1 green module power indicator Output (intrinsically safe) (16 pin male and female flexbus connector) Ui < 5.8V dc Ii < 400mA Li = Negligible Ci = Negligible Isolation Path Input to power supply Input to flexbus Input to input Power supply to flexbus Isolation Type Galvanic to DIN EN50020 Galvanic to DIN EN50020 None Galvanic to DIN EN50020 Power Supply (+V, -V intrinsically safe) Ui < 9.5V dc Ii < 1A Li = Negligible Ci = Negligible Module Field-Side Power Consumption 2.8W Power Dissipation 2.8W Thermal Dissipation Maximum 9.6 BTU/hr -20 to +70oC (-4 to +158oF) -40 to +85oC (-40 to +185oF) 5 to 95% noncondensing Tested to 15g peak acceleration, 11(+1)ms pulse width Tested to 15g peak acceleration, 11(+1)ms pulse width Tested 2g @ 10-500Hz per IEC68-2-6 Agency Certification CENELEC II (1) 2G EEx ia/ib IIB/IIC T4 UL, C-UL Class I Division 1 & 2 Groups A-D T4 Class I Zone 1 & 2 AEx ib/[ia] IIC T4 FM Class I Division 1 Groups A-D T4 Class I Zone 1 AEx ib/[ia] IIC T4 Certificates CENELEC DMT 98 ATEX E013 X UL, C-UL UL Certificate Number 99.19699 C FM US Class I Division 1 Hazardous FM Certificate Number 3009806 Publication 1797-2.1 - August 2001 28 24V dc 4 pt Non-Isolated Source Output Module Cat. No. 1797-OB4D FLEX Ex 24V dc 4 pt Non-Isolated Source Output Module Cat. No. 1797-OB4D Ex 1797-OB4D PWR 40067 Product Features • 4 output channels referenced to a single supply • Functional data: U = 12V at I = 45mA • Yellow LED to indicate output state, output ON = LED ON • Fault indication, signal to the backplane and LED (per channel) blinking red for fault • Output wire-off detection • Output wire-off detection on per channel basis via module data bit • Electronically short circuit protected, fault reported to controller • All channels updated from the backplane every 2ms • Output fault state programmable Customer Connections +V power supply -V + bus flexbus uC audible alarm valve solenoid 40069 Terminal Base Assignment 0 1 + - 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Row A + ch0 16 17 - + ch1 18 19 20 21 - + ch2 22 23 24 25 - ch3 26 27 28 29 30 31 32 33 Row B 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 Row C 40068 +V -V +V -V No connections allowed to terminals 2, 3, 6, 7, 10, 11, 14, 15, 17 to 32, 36, 37, 38, 39, 46, 47, 48, 49 Publication 1797-2.1 - August 2001 FLEX Ex 24V dc 4 pt Non-Isolated Source Output Module Cat. No. 1797-OB4D Specifications - 1797-OB4D Agency Certification Number of Outputs 4, non-isolated, sourcing CENELEC II (1) 2G EEx ia/ib IIB/IIC T4 IS Output Type EEx ia IIB/IIC T4, AEx ia IIC T4, Class I, II, III Division 1 & 2 Groups A-G T4 UL, C-UL Class I Division 1 & 2 Groups A-D T4 Class I Zone 1 & 2 AEx ib/[ia] IIC T4 FM IS Module Type EEx ib IIB/IIC T4, AEx ib IIC T4, Class I Division 1 & 2 Groups A-D T4 Class I Division 1 Groups A-D T4 Class I Zone 1 AEx ib/[ia] IIC T4 V-I Characteristics Refer to “Output Voltage/Current Capability” on page 29 Load Range 30-5000 Ω Fault Detection Fault bits in data table and LED (per channel) blinking red (1 Hz) Electronic Protection Lead break, overload, short circuit Maximum Output Delay Times OFF to ON ON to OFF <1.2ms <1.2ms Indicators 4 yellow status indicators 4 red fault indicators 1 green module power indicator Output (Intrinsically Safe) (16 pin Male and Female Flexbus Connector) Ui < 5.8V dc Ii < 400mA Li = Negligible Ci < 1.35µF Isolation Path Output to Power Supply Output to Flexbus Power Supply to Flexbus Output to Output Isolation type Galvanic to DIN EN 50020 Galvanic to DIN EN 50020 Galvanic to DIN EN 50020 None Power Supply (+V, -V Intrinsically Safe) Ui < 9.5V dc Ii < 1A Li = Negligible Ci = Negligible Module Field-Side Power Consumption Power Dissipation 7.5W Thermal Dissipation 17.07 BTU/hr Module Location Cat. No. 1797-TB3 or -TB3S Terminal Base Unit Conductors Wire Size 12 gauge (4mm2) stranded maximum 1.2mm (3/64in) insulation maximum Dimensions 46mm x 94mm x 75mm (1.8in x 3.7in x 2.95in) Weight 200g (approximate) Keyswitch Position 7 29 Certificates CENELEC DMT 98 ATEX E040 X UL, C-UL UL Certificate Number 99.19699 C FM US Class I Division 1 Hazardous FM Certificate Number 3009806 Output Voltage/Current Capability Voltage 30 25 20 15 10 5 0 0 5 10 15 20 25 30 mA 35 40 45 50 41313 5W Environmental Conditions Operational Temperature -20 to +70oC (-4 to +158oF) Storage Temperature -40 to +85oC (-40 to +185oF) Relative Humidity 5 to 95% noncondensing Shock Tested to 15g peak acceleration, 11(+1)ms pulse width Operating Nonoperating Vibration Tested to 15g peak acceleration, 11(+1)ms pulse width Tested 2g @ 10-500Hz per IEC68-2-6 Publication 1797-2.1 - August 2001 30 8 pt 16 bit Single-Ended Non-Isolated Input Module Cat. No. 1797-IE8 FLEX Ex 8 pt 16 bit Single-Ended Non-Isolated Input Module Cat. No. 1797-IE8 Ex 1797-IE8 8 CHANNEL ANALOG INPUT 3 IN0 IN1 IN2 IN3 IN4 IN5 IN6 IN7 PWR 40070 Product Features • Eight single-ended input channels referenced to a single common • 3-wire input for 2 and 3-wire transmitters • Functional data: U = 15V at I = 22mA, normal Input current = 4 to 20mA, full-current range 0 to 22mA to allow for over and underrange indication • Wire-off detection, signal to the backplane and LED (per channel) blinking red for fault • Wire-off detection on per channel basis via module data bits • Input filter cutoff programmable • Response time: 4ms to 99% of final value • All channels updated to the backplane every < 4ms • Resolution: 16 bits • Accuracy: 0.1% • Temperature drift: 50 ppm/°C Customer Connections +V -V + flexbus 286Ω 21V Bus 4-20mA Xmit I uC P 4-20mA Xmit I Isolated Power 4-20mA Xmit P sig 22Ω I P 40072 Publication 1797-2.1 - August 2001 FLEX Ex 8 pt 16 bit Single-Ended Non-Isolated Input Module Cat. No. 1797-IE8 31 Terminal Base Assignment 0 1 2 + sig - 3 4 5 6 + sig - 7 8 9 10 11 12 13 14 + sig 15 Row A Ch 0 16 + sig Ch 1 17 18 19 + sig - 20 - Ch 2 21 22 23 + sig - 24 25 26 - Ch 3 27 28 29 30 31 + sig 32 33 Row B Ch 4 34 + sig Ch 5 35 36 37 38 39 - Ch 77 Ch 6 40 41 42 43 - 44 45 46 47 48 49 50 51 Row C 40071 +V -V +V -V No connection allowed No connection allowed Specifications - 1797-IE8 Number of Inputs 8 single-ended, non-isolated IS Input Type EEx ia IIB/IIC T4, AEx ia IIC T4, Class I, II, III Division 1 Groups A-G T4 IS Module Type EEx ib IIB/IIC T4, AEx ib IIC T4, Class I Division 1 Groups A-D T4 Resolution 16 bits Transfer Characteristics Accuracy 0.1% of output signal range at 20°C (68°F) Temperature Drift 0.005%/C of output signal range Functional Data Range >15V @22mA >21.5V @ 0mA Data Format Configurable Step Response to 4ms 99% of FS Module from Adapter 50/1450µs Best/Worst Update Time Indicators 8 red fault indicators 1 green power Output (Intrinsically Safe) Ui < 5.8V dc (16 position male/female Ii < 400mA flexbus connector) Li = Negligible Ci < 1.35µF Isolation Path Isolation Type Input to Power Supply Galvanic to DIN EN50020 Input to Flexbus Galvanic to DIN EN50020 Input to Input None Power Supply to Galvanic to DIN EN50020 Flexbus Power Supply Ui < 9.5V dc (+V, -V intrinsically safe) Ii < 1A Li = Negligible Ci = Negligible Module Field-side Power 7.5W Consumption Power Dissipation 5.2W Thermal Dissipation 17.75 BTU/hr Module Location Cat. No. 1797-TB3 or -TB3S Conductor Wire Size 12 gauge (4mm2) stranded maximum 3/64in (1.2mm) insulation maximum Dimensions 46mm x 94mm x 75mm (1.8in x 3.7in x 2.95in) 200g (approximately) 3 Weight Keyswitch Position Environmental Conditions Operational Temperature -20 to +70oC (-4 to +158oF) Storage Temperature -40 to +85oC (-40 to +185oF) Relative Humidity Shock Operating Nonoperating Vibration Agency Certification CENELEC UL, C-UL FM Certificates CENELEC UL, C-UL 5 to 95% noncondensing Tested to 15g peak acceleration, 11(+1)ms pulse width Tested to 15g peak acceleration, 11(+1)ms pulse width Tested 2g @ 10-500Hz per IEC68-2-6 II (1) 2G EEx ia/ib IIB/IIC T4 Class I Division 1 & 2 Groups A-D T4 Class I Zone 1 & 2 AEx ib/[ia] IIC T4 Class I Division 1 Groups A-D T4 Class I Zone 1 AEx ib/[ia] IIC T4 DMT 98 ATEX E020 X UL Certificate Number 99.19699 C FM US Class I Division 1 Hazardous FM Certificate Number 3009806 Publication 1797-2.1 - August 2001 32 8 pt 16 bit Single-Ended Non-Isolated Input Module with Noise Filter Cat. No. 1797-IE8NF FLEX Ex 8 pt 16 bit Single-Ended Non-Isolated Input Module with Noise Filter Cat. No. 1797-IE8NF Ex 1797-IE8NF 8 CHANNEL ANALOG INPUT, FILTERED 3 IN0 IN1 IN2 IN3 IN4 IN5 IN6 IN7 PWR 42849 Product Features • Eight single-ended input channels referenced to a single common • 3-wire input for 2 and 3-wire transmitters • Functional data: U = 15V at I = 22mA, normal Input current = 4 to 20mA, full-current range 0 to 22mA to allow for over and underrange indication • Wire-off detection, signal to the backplane and LED (per channel) blinking red for fault • Wire-off detection on per channel basis via module data bits • Input filter cutoff programmable • Response time: 500ms to 99% of final value • All channels updated to the backplane every < 4ms • Resolution: 16 bits • Accuracy: 0.1% • Temperature drift: 50 ppm/°C Customer Connections +V -V + flexbus 286Ω 21V Bus 4-20mA Xmit I uC P 4-20mA Xmit I Isolated Power 4-20mA Xmit P sig 22Ω I P 40072 Publication 1797-2.1 - August 2001 FLEX Ex 8 pt 16 bit Single-Ended Non-Isolated Input Module with Noise Filter Cat. No. 1797-IE8NF 33 Terminal Base Assignment 0 1 2 + sig - 3 4 5 6 + sig - 7 8 9 10 11 12 13 14 + sig 15 Row A Ch 0 16 + sig Ch 1 17 18 19 + sig - 20 - Ch 2 21 22 23 + sig - 24 25 26 - Ch 3 27 28 29 30 31 + sig 32 33 Row B Ch 4 34 + sig Ch 5 35 36 37 38 39 - Ch 77 Ch 6 40 41 42 43 - 44 45 46 47 48 49 50 51 Row C 40071 +V -V +V -V No connection allowed No connection allowed Specifications - 1797-IE8NF Number of Inputs 8 single-ended, non-isolated IS Input Type EEx ia IIB/IIC T4, AEx ia IIC T4, Class I, II, III Division 1 & 2 Groups A-G T4 IS Module Type EEx ib IIB/IIC T4, AEx ib IIC T4, Class I Division 1 & 2 Groups A-D T4 Resolution 16 bits Transfer Characteristics Accuracy 0.1% of output signal range at 20°C (68°F) Temperature Drift 0.005%/C of output signal range Functional Data Range >15V @22mA >21.5V @ 0mA Data Format Configurable Step Response to 500ms 99% of FS Module from Adapter 50/1450µs Best/Worst Update Time Indicators 8 red fault indicators 1 green power Output (Intrinsically Safe) Ui < 5.8V dc (16 pin male and female Ii < 400mA flexbus connector) Li = Negligible Ci < 1.35µF Isolation Path Isolation Type Input to Power Supply Galvanic to DIN EN50020 Input to Flexbus Galvanic to DIN EN50020 Input to Input None Power Supply to Galvanic to DIN EN50020 Flexbus Power Supply Ui < 9.5V dc (+V, -V intrinsically safe) Ii < 1A Li = Negligible Ci = Negligible Module Field-side Power 7.5W Consumption Power Dissipation 5.2W Thermal Dissipation 17.75 BTU/hr Module Location Cat. No. 1797-TB3 or -TB3S Conductor Wire Size 12 gauge (4mm2) stranded maximum 3/64in (1.2mm) insulation maximum Specification 1797-IE8NF (Continued) Dimensions 46mm x 94mm x 75mm (1.8in x 3.7in x 2.95in) Weight 200g (approximately) Keyswitch Position 3 Environmental Conditions Operational Temperature -20 to +70oC (-4 to +158oF) Storage Temperature Relative Humidity Shock Operating Nonoperating Vibration Agency Certification CENELEC UL, C-UL FM Certificates CENELEC -40 to +85oC (-40 to +185oF) 5 to 95% noncondensing Tested to 15g peak acceleration, 11(+1)ms pulse width Tested to 15g peak acceleration, 11(+1)ms pulse width Tested 2g @ 10-500Hz per IEC68-2-6 II (1) 2G EEx ia/ib IIB/IIC T4 Class I Division 1 & 2 Groups A-D T4 Class I Zone 1 & 2 AEx ib/[ia] IIC T4 Class I Division 1 Groups A-D T4 Class I Zone 1 AEx ib/[ia] IIC T4 DMT 98 ATEX E020 X UL, C-UL UL Certificate Number 99.19699 FM FM Certificate Number 3009806 C US Class I Division 1 Hazardous Publication 1797-2.1 - August 2001 34 8 pt 13 bit Single-Ended Non-Isolated Output Module Cat. No. 1797-OE8 FLEX Ex 8 pt 13 bit Single-Ended Non-Isolated Output Module Cat. No. 1797-OE8 Ex 1797-OE8 PWR 40073 Product Features • Eight dual-ended output channels referenced over sense resistors to a single common • Functional data: U = 11V at I = 22mA, normal output current = 4-20mA, full current range = 0-22mA to allow for over and overrange indication • Load 0-500Ω • Output wire-off detection, LED (per channel) blinking red for fault, threshold < 2mA • Output wire-off detection on per channel basis via module data bits • Rise time: 4ms to 99% of final value • All channels updated to the backplane every < 4ms • Resolution: 13 bits • Accuracy: 0.1% • Temperature drift: 100ppm/°C • One power supply loop for one module • Output fault state programmable Customer Connections +V power supply -V flexbus + Bus 4-20mA actuator 4-20mA valve I F uC - 41441 Publication 1797-2.1 - August 2001 FLEX Ex 8 pt 13 bit Single-Ended Non-Isolated Output Module Cat. No. 1797-OE8 35 Terminal Base Assignment 0 1 2 3 4 5 + - 6 7 8 9 10 11 12 13 14 15 Row A + - ch0 16 17 + ch1 18 19 20 21 - + ch2 22 23 24 25 - ch3 26 27 28 29 30 31 32 33 Row B + - + ch4 - + ch5 34 35 +V -V 36 37 38 - + ch7 ch6 39 40 41 42 - 43 44 45 46 47 48 49 50 51 Row C 41440 +V No connections allowed to terminals 2, 3, 6, 7, 10, 11, 14, 15, 19, 20, 23, 24, 27, 28, 31, 32, 36, 37, 38, 39, 46, 47, 48, 49 Specifications - 1797-OE8 Number of Outputs 8 single-ended, non-isolated IS Output Type EEx ia IIB/IIC T4, AEx ia IIC T4, Class I, II, III Division 1 Groups A-G T4 IS Module Type EEx ib IIB/IIC T4, AEx ib IIC T4, Class I Division 1 Groups A-D T4 Resolution 13 bit Transfer Characteristics 0.1% of output signal range Accuracy at 20oC (68oF) 0.010%/C of output signal range Temperature Drift Load Range Current 0-22mA Voltage Available at 22mA >11V Load 0-500Ω @ 22mA Data Format Configurable Step Response to 99% of 4ms FS Indicators 8 red fault indicators 1 green power Output (Intrinsically Safe) Ui < 5.8V dc (16 pin male and female Ii < 400mA flexbus connector) Li = Negligible Ci = < 1.35µF Isolation Path Isolation Type Output to Power Supply Galvanic to DIN EN50020 Output to Flexbus Galvanic to DIN EN50020 Output to Output None Power Supply to Flexbus Galvanic to DIN EN50020 Power Supply Ui < 9.5V dc (+V, -V Intrinsically Safe) Ii < 1A Li = Negligible Ci = Negligible Module Field-Side Power 6.3W Consumption Power Dissipation 5.4W Thermal Dissipation 18.4 BTU/hr Module Location Cat. No. 1797-TB3 or -TB3S Terminal Base Unit Conductors Wire Size 12 gauge (4mm2) stranded maximum 1.2mm (3/64in) insulation maximum Dimensions 46 x 94 x 75mm (1.8 x 3.7 x 2.95in) Weight 200g (approximately) Keyswitch Position 4 Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Shock Operating Non-Operating Vibration Agency Certification CENELEC UL, C-UL -V -20 to +70oC (-4 to +158oF) -40 to +85oC (-40 to +185oF) 5 to 95% noncondensing Tested to 15g peak acceleration, 11(+1)ms pulse width Tested to 15g peak acceleration, 11(+1)ms pulse width Tested 2g @ 10-500Hz per IEC68-2-6 II (1) 2G EEx ia/ib IIB/IIC T4 Class I Division 1 & 2 Groups A-D T4 Class I Zone 1 & 2 AEx ib/[ia] IIC T4 Class I Division 1 Groups A-D T4 Class I Zone 1 AEx ib/[ia] IIC T4 FM Certificates CENELEC DMT 98 ATEX E042 U UL, C-UL UL Certificate Number 99.19699 C FM US Class I Division 1 Hazardous FM Certificate Number 3009806 Output Voltage/Current Capability Voltage 16 14 12 10 8 6 4 2 0 0 5 10 mA 15 20 25 43002 Publication 1797-2.1 - August 2001 36 8 pt 16 bit Non-Isolated RTD Thermocouple/mV Input Module Cat. No. 1797-IRT8 FLEX Ex 8 pt 16 bit Non-Isolated RTD Thermocouple/mV Input Module Cat. No. 1797-IRT8 Ex 1797-IRT8 PWR 40076 Product Features • Input channels referenced to a single common • Resolution: 16 bits • RTD mode – 2-, 3- and 4-wire connection – sensor lead breakage detection all 4 leads – sensor short circuit detection all 4 leads – measuring resistance 0 to 500Ω – accuracy: 0.1% of span @ 20oC, filter cutoff < 1Hz • Thermocouple mode – types B, E, J, K, TXK/XK (L), N, R, S, T – cold junction compensation (CJC) – external reference junction (programmable) – sensor breakage detection – accuracy: 0.1% of span, filter cutoff < 1 Hz – accuracy of CJC: +1°C/K • mV mode – input voltage -40 to 100 mV differential sensing – sensor breakage detection – accuracy: 0.1% of span @ 20oC, filter cutoff < 1Hz Customer Connections +V power supply -V + flexbus Bus 2W RTD L uC 3W RTD 4W RTD H thermocouple + mV - + CJC - CJC 41658 Publication 1797-2.1 - August 2001 FLEX Ex 8 pt 16 bit Non-Isolated RTD Thermocouple/mV Input Module Cat. No. 1797-IRT8 37 Terminal Base Assignment 0 1 2 + H L 3 4 5 - + H 6 7 8 9 + H 10 11 12 13 14 15 Row A Ch 0 16 L - Ch 1 17 18 19 20 21 + H L - + 22 L - + H Ch 2 23 24 L - Ch 3 25 26 27 + H L 28 29 30 31 32 33 Row B Ch 4 H L - Ch 5 34 35 +V -V 36 37 38 39 - + H Ch 6 40 41 42 43 L - Ch 7 44 45 46 47 48 49 50 51 Row C 41505 CJC CJC 0+ chassis 01+ chassis 1GND for GND for shield shield No connection allowed to terminals 36 and 49 Specifications - 1797-IRT8 Number of Inputs 8 channels IS Input Type EEx ia IIB/IIC T4, AEx ia IIC T4, Class I, II, III Division 1 Group A-G T4 IS Module Type EEx ib IIB/IIC T4, AEx ib IIC T4, Class I, Division 1 & 2 Group A-D T4 Input Type Suitable for Pt 100, Pt200, Ni 100, Ni120, Ni200, 10Cu RTD, Thermocouple Type B, E, J, K, N, R, S, T, TXK/XK (L) Configuration via internal bus Signal Input Range 0 to 500 ohms; -40 to 100mV Settling Time to 99% of 8ms (mV mode, oF thermocouple) Final Value Open RTD Detection Out of range upscale reading Lead Resistance < 15 ohm total Compensation Transfer Characteristics Accuracy RTDs: 0.1% of span @ 20oC, filter cutoff < 1Hz Thermocouples: 0.1% of span @ 20oC, filter cutoff < 1Hz Temperature Effect Cold junction compensation = +1oC 150ppm/oC (primary range) Indicators 8 red fault indicators 1 green module power indicator Data Organization Overrange Alarm Individually for each channel Lead Breakage Alarm Individually for each channel Fault State Individually for each channel (includes overrange, lead breakage and short circuit) Sensor Mode RTD 2, Common to groups of 4 channels (ch 0-3, ch 4-7) 3, or 4-wire, TC Sensor Type (e.g. TC, Common to groups of 4 channels (ch 0-3, ch 4-7) Type B, E, J..., RTD or mV Internal Reference Common to all channels (0oC, 20oC, 25oC, 30oC, 40oC, Junction (TC mode) 50oC, 60oC, 70oC selectable Output (intrinsically safe) Ui < 5.8V (16 position male/female Ii < 400mA flexbus connector) Li = Negligible Ci < 1.35µF Isolation Path Isolation Type Input to power supply Galvanic to DIN EN50020 Input to flexbus Galvanic to DIN EN50020 Input to input None Power supply to flexbus Galvanic to DIN EN50020 Power Supply (+V, -V intrinsically safe) Module Field-Side Power Consumption Power Dissipation Thermal Dissipation Module Location Conductor Wire Size Dimensions Weight Keyswitch Position Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Shock Operating Nonoperating Vibration Agency Certification CENELEC UL, C-UL FM +V -V Ui < 9.5V dc Ii < 1A Li = Negligible Ci = Negligible 1.6W 1.6W Maximum 5.46BTU/hr Cat. No. 1797-TB3 or -TB3S Terminal Base Unit 12 gauge (4mm2) stranded maximum 3/64in (1.2mm) insulation maximum 46mm x 94mm x 75mm (1.8in x 3.7in x 2.95in) 200g (approximate) 2 -20 to +70oC (-4 to +158oF) -40 to +85oC (-40 to +185oF) 5 to 95% noncondensing Tested to 15g peak acceleration, 11(+1)ms pulse width Tested to 15g peak acceleration, 11(+1)ms pulse width Tested 2g @ 10-500Hz per IEC68-2-6 II (1) 2G EEx ia/ib IIB/IIC T4 Class I Division 1 & 2 Groups A-D T4 Class I Zone 1 & 2 AEx ib/[ia] IIC T4 Class I Division 1 Groups A-D T4 Class I Zone 1 AEx ib/[ia] IIC T4 Certificates CENELEC DMT 98 ATEX E023 X UL, C-UL UL Certificate Number 99.19699 FM FM Certificate Number 3009806 C US Class I Division 1 Hazardous Publication 1797-2.1 - August 2001 38 2 Input Frequency Module Cat. No. 1797-IJ2 FLEX Ex 2 Input Frequency Module Cat. No. 1797-IJ2 Ex 1797-IJ2 PWR 40079 Product Features • Software configurable frequency operating mode, with independent selections per frequency input • Frequency inputs, two gate inputs and two outputs • Functional data: four selectable ranges, 50mV, 500mV (magnetic pickup), Flowmeter and NAMUR • Provides IS power to drive up to two NAMUR and two Flowmeter frequency inputs and/or contact switches and NAMUR gate inputs • NAMUR lead breakage indication for any lead, signal to the backplane and LED (per channel) blinking red for fault Publication 1797-2.1 - August 2001 • NAMUR lead breakage defeat on per channel basis via module data table (NAMUR inputs only) • Frequency count range up to 32k Hz • Calculate frequency on time interval or input count • Programmable scaling • Acceleration value calculated • Maximum frequency or acceleration alarms • All channels updated to the backplane every < 4 ms (according to sampling time) FLEX Ex 2 Input Frequency Module Cat. No. 1797-IJ2 39 Customer Connections +V power supply -V +V flexbus Bus 6V uC NAMUR prox 3V +8V N 50mV select vortex sensor jumper for 50mV sensor none for 500mV 500/50mV GND NAMUR prox magnetic sensor +8V N jumper for 50mV sensor none for 500mV 50mV select 500/50mV GND magnetic sensor R NO R Com R NC valve audible alarm solenoid 41302 Terminal Base Assignment 0 1 2 3V 6V 17 18 3 4 5 6 7 8 9 10 11 12 13 14 15 Row A 16 V+ GND 50 500/50 N 8V mV mV Sel Channel 0 Frequency Input 19 20 21 22 23 8V N 500/50 50 GND V+ 6V 3V mV mV Sel Channel 1 Frequency Input 24 25 26 27 28 29 30 8V 8V N 500/50 50 GND mV mV Sel 31 32 33 Row B R0 NO R0 NC GND 50 500/50 N mV mV Sel Channel 0 Gate Input Row C 34 35 36 37 38 39 R1 NO R1 NC Channel 1 Gate Input 40 41 42 43 44 45 46 47 48 49 50 51 41506 +V -V R0 COM R1 COM +V -V No connection allowed to terminals 19, 30, 36, 38, 39, 47, 48, 49 Publication 1797-2.1 - August 2001 40 2 Input Frequency Module Cat. No. 1797-IJ2 Specifications - 1797-IJ2 Number of Inputs 2 frequency channels 2 gate channels IS Input Type EEx ia IIB/IIC T4, AEx ia IIC T4, Class I, II, III Division 1 Group A-G T4 IS Module Type EEx ib IIB/IIC T4, AEx ib IIC T4, Class I, Division 1 & 2 Group A-D T4 Input (intrinsically safe) to DIN19234 (NAMUR) No load voltage short 8V dc/8mA circuit current Switching point/ 1.2-2.1mA/0.2mA switching hysteresis Input pulse length/ >20µs/>20µs pulse pause Lead breakage monitoring Breakage current <0.35mA Inputs to Flowmeter Input signal Threshold 3V or 6V selectable Voltage available at 20mA >15V Inputs to Magnetic pickup 50mV or 500mV selectable input signal Processing time <4ms Input Frequency 1.0Hz - 32,767Hz Resolution and accuracy Minimum FrequencyResolution Sampling Time (ms)Accuracy (%) 2 0.043 4 0.033 5 0.031 10 0.027 20 0.025 50 0.023 100 0.023 200 0.023 500 0.023 1000 0.023 Frequency Input Magnetic pickup: 50mV, 500mV Characteristics NAMUR: 8V, 8mA Flowmeter: low <3V, high >6V Frequency Input Impedance >5kΩ magnetic pickup Rating >10KΩ flowmeter Outputs 2 relay outputs Output Switching Time <10ms Gate Inputs 2 Input (intrinsically safe) to DIN19234 (NAMUR) No load voltage short 8V dc/8mA circuit current Switching point/ 1.2-2.1mA/0.2mA switching hysteresis Input pulse length/ >20µs/>20µs pulse pause Lead breakage monitoring Breakage current <0.35mA FLEX Ex Indicators Output (intrinsically safe) (16 pin male and female flexbus connector) Isolation Path Input to power supply Input to flexbus Input to input Output to power supply Output to flexbus Output to output Power Supply (+V, -V intrinsically safe) Module Field-Side Power Consumption Power Dissipation Thermal Dissipation Module Location Conductor Wire Size Dimensions Weight Keyswitch Position Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Shock Operating Nonoperating Vibration Agency Certification CENELEC UL, C-UL FM 6 yellow status indicators 4 red fault indicators 1 green module power indicator Uo < 5.8V Io < 400mA Li < Negligible Ci < 2.64µF Isolation Type Galvanic to DIN EN50020 Galvanic to DIN EN50020 None Galvanic to DIN EN50020 Galvanic to DIN EN50020 Galvanic to DIN EN50020 Ui < 9.5V dc Ii < 1A Li = Negligible Ci = Negligible 4.25W 4.25W Maximum 14.5BTU/hr Cat. No. 1797-TB3 or -TB3S Terminal Base Unit 12 gauge (4mm2) stranded maximum 3/64in (1.2mm) insulation maximum 46mm x 94mm x 75mm (1.8in x 3.7in x 2.95in) 200g (approximate) 1 -20 to +70oC (-4 to +158oF) -40 to +85oC (-40 to +185oF) 5 to 95% noncondensing Tested to 15g peak acceleration, 11(+1)ms pulse width Tested to 15g peak acceleration, 11(+1)ms pulse width Tested 2g @ 10-500Hz per IEC68-2-6 II (1) 2G EEx ia/ib IIB/IIC T4 Class I Division 1 & 2 Groups A-D T4 Class I Zone 1 & 2 AEx ib/[ia] IIC T4 Class I Division 1 & 2 Groups A-D T4 Class I Zone 1 AEx ib/[ia] IIC T4 Certificates CENELEC DMT 98 ATEX E033 X UL, C-UL UL Certificate Number 99.19699 C FM Publication 1797-2.1 - August 2001 US Class I Division 1 Hazardous FM Certificate Number 3009806 FLEX Ex FLEX Ex Power Supplies Cat. Nos. 1797-PS2N, and -PS2E 41 FLEX Ex Power Supplies Cat. Nos. 1797-PS2N, and -PS2E The 1797-PS2N is a 24V dc in/quad-Ex dc out power supply in an explosion-proof enclosure with 1 inch conduit pipe-thread input/output terminations. 1797-PS2N The 1797-PS2E is a 24V dc in/quad-Ex dc out power supply in a flame-proof enclosure with increased safety input/output terminations. The 24V dc glan is an M20 x 1,5 and can accept a cable from 6mm to 12mm in diameter. The Ex outputs are M16 x 1,5 and can accept a cable from 4mm to 8mm in diameter. 1797-PS2E 40468 30686 Product Features • Explosion-proof enclosure, IP 66, NEMA 4/4X, conduit input terminations (“N” versions) • Maximum conduit length of 10 inches • Explosion-proof enclosure, IP 65, NEMA 12/12K/13, increased safety input terminations (“E” versions) • 24V dc supply source • Four channels, 8.5W output each channel • Dual power feeds for source input redundancy • Outputs are IS galvanically isolated from the source • All channels are independently IS limited Customer Connections Type of Power Input dc IS Limiters Voltage and Current Dual Input Diodes IS Isolation Hazardous to IS IS Power Output -V + +V - - -V +V -V +V chassis GND -V Vin1 + Vin2 Out 1 Out 2 Out 3 Out 4 +V 41315 Publication 1797-2.1 - August 2001 42 FLEX Ex Power Supplies Cat. Nos. 1797-PS2N, and -PS2E FLEX Ex Understanding System Planning Modules Requires Fiber Hub 8.5W Part of system planning is determining what modules are needed for the application, how many power supplies are needed, how to best partition the system, and where to locate the system cabinets. Two ControlNet Adapters 8.5W each Two Analog Inputs 7.5W each Two Analog Outputs 6.3W each A key task in the development cycle is determining the number of power supply outputs (thus power supplies) you will need. For example, you will need eleven power outputs if you are using the fiber hub, which requires 8.5W: Each power supply has four independent IS power outputs capable of 8.5W each. In this example, we required eleven IS power outputs so three power supplies were sufficient. EEx d /e Two Thermocouple Inputs 1.6W each Two Digital Outputs 7.5W each Three NAMUR Digital Inputs 2.8W each Two Counter Inputs 4.25W each The total number of power supplies needed depends on the modules used and the total system configuration. The following illustration shows how this example may be configured. Spare IS Pwr IS Pwr IS Pwr EEx ib IS Pwr Hazardous Area IS 1797 I/O 1797 power supply ACNR Spare EEx d /e IE8 OE8 IRT8 Spare Spare IS Pwr IS Pwr IS Pwr EEx ib IS Pwr Unsafe Power Entrance ACNR EEx d /e OB4D IJ2 IS 1797 I/O 1797 power supply Safe Area IJ2 OB4D IBN16 IBN16 IBN16 IE8 IRT8 OE8 IS Pwr IS Pwr IS Pwr EEx ib IS Pwr 1797 power supply RPA RPFM RPFM IS 1797 Fiber Hub 41306 Publication 1797-2.1 - August 2001 FLEX Ex FLEX Ex Power Supplies Cat. Nos. 1797-PS2N, and -PS2E 43 Optimize Power Distribution Assigning Power Supplies Your FLEX Ex system must use adequate power supplies to support the physical locations determined earlier in this chapter. Each FLEX Ex I/O module in the system is rated for input power, and the FLEX Ex power supply is rated in the number of output channels and power available from each channel. Note the amount of power each module requires and assign it to a power supply output. Continue to assign modules to the power supply output until the supply’s output power rating is consumed. The graphic on the next page shows the number of modules per power supply output. IMPORTANT Each power supply output in the FLEX Ex system is rated for 8.5W. Modules can be attached to the output until their combined power equals that number. Do not exceed the power supply maximum of 8.5W. 5 4 IRT8 1.6W 3 IRT8 1.6W 2 IRT8 1.6W IBN16 2.8W 1 IRT8 1.6W IBN16 2.8W IJ2 4.25W 0 IRT8 1.6W IBN16 2.8W IJ2 4.25W Modules IRT8 1.6W RPFM (In RPA) RPFM IRT8 1.6W IE8 7.5W OE8 6.3W ACNR 8.5W IRT8 1.6W IRT8 1.6W IRT8 1.6W (In RPA) IRT8 1.6W IBN16 2.8W IBN16 2.8W IRT8 1.6W RPA 8.5W IBN16 2.8W IJ2 4.25W IBN16 2.8W IJ2 4.25W 41661 Modules Per Power Supply Output Publication 1797-2.1 - August 2001 44 FLEX Ex Power Supplies Cat. Nos. 1797-PS2N, and -PS2E FLEX Ex Hazardous Area Installation The following illustration provides an example of how power supplies are arranged within the FLEX Ex system. Programmable Logic Controller Optional 1786-RPA 1786-RPFM 1786-RPFM User Supplied 24V Supply (85 to 264V ac future) . . . 1 to other devices Non-Hazardous Location Fiber Cable Optional 1797-RPA 1797-RPFM 1797-RPFM Hazardous Location Class I, Division 1 or (Zone 1) . . . 1 to other hazardous devices Hardened Conduit 1797-PS2N or (1797-PS2E) Adapter Module . . . . . Hardened Conduit . . . . . . . . . . 1 . . . . . Adapter Module . . . . . . . . . . . 1797-PS2N or (1797-PS2E) . . Hardened Conduit . . 1 . . . . . 1797-PS2N or (1797-PS2E) 42304 Publication 1797-2.1 - August 2001 FLEX Ex FLEX Ex Power Supplies Cat. Nos. 1797-PS2N, and -PS2E 45 Terminal Assignment North America DC Power Input 1 2 3 4 5 1797-PS2N + - cha + GND Vin2 Vin1 1797-PS2E 3 1 2 4 + - + Vin1 cha GND Vin2 5 - IS Power Output 10 11 12 13 14 15 16 17 +V -V +V -V +V -V +V -V Out 1 Out 2 Out 3 Out 4 41256 10 11 12 13 14 15 16 17 +V -V +V -V +V -V +V -V Out 1 Out 2 Out 3 Out 4 41271 Publication 1797-2.1 - August 2001 46 FLEX Ex Power Supplies Cat. Nos. 1797-PS2N, and -PS2E Specifications IS Module Type IS Output Type 1797-PS2N/A Class I Division 1 Groups C-D T4 (UL and C-UL) Class I Division 2 Groups A-D T4 (UL and C-UL) 1797-PS2E EEx de [ib] IIC T4 1797-PS2N/B Class I Division 1 Groups B-D T4 (UL, C-UL and FM) Class I Division 2 Groups A-D T4 (UL, C-UL, and FM) Class I Zone 1 AEx IIB (FM) Class I Zone 2 AEx IIC (FM) Class I, II, III Division 1 & 2 Groups A-G (UL and C-UL) EEx ib IIC AEx ib IIC (FM) Class I, II, III Division 1 & 2 Groups A-G (UL, C-UL, and FM) Input Connectors Voltage Range Current Consumption Ripple Input Power Entrance FLEX Ex 3.1A 1” NPT, <6” conduit allowed between power supply and seal (UL and C-UL) Output Connectors Output Power Maximum Input Voltage Voltage UO Current IO 24V dc Terminals 1, 2, 4, 5 18 to 32V 1.6A 3.1A 5% ac Increased safety 1” NPT, 6” conduit allowed between power supply and seal (UL and C-UL) 1” NPT, 0” conduit allowed between power supply and seal (FM) Terminals 10-17 4x8.5W Um = 40V dc <9.5V <1A Co (IIC) <800 nF Lo (IIC) <10 µH Maximum Output Cable Resistance (both directions) Isolation Path Input Power to Output Power Output to Output Input Power Power Dissipation Thermal Dissipation <0.1Ω Publication 1797-2.1 - August 2001 Galvanic to DIN EN50020 None 55W 21W 71.67 BTU/hr FLEX Ex FLEX Ex Power Supplies Cat. Nos. 1797-PS2N, and -PS2E Specifications Continued Conductors Wire Size 1797-PS2N/A Dimensions Protections Class Weight (approximately) Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Shock Operating Non-Operating Vibration Agency Certification CENELEC UL, C-UL 1797-PS2E 1797-PS2N/B 12 gauge (4mm2) stranded maximum 1.2mm (3/64in) insulation maximum Use wire rated for 100oC operation 174mm x 174mm x 280mm 174mm x 174mm x 128mm (6.9in x 6.9in x 11.0in) (6.9in x 6.9in x 5.04in) IP 65/NEMA 7B IP66/NEMA 7B 7.7kg (17lbs) 7.3kg (16lbs) 174mm x 174mm x 128mm (6.9in x 6.9in x 5.04in) IP66/NEMA 7B 7.3kg (16lbs) -20 to 70oC (-4 to 158oF) -40 to 85oC (-40 to 185oF) 5 to 95% noncondensing Tested 15g peak acceleration, 11 (±1)ms pulse width Tested 15g peak acceleration, 11 (±1)ms pulse width Tested 2g @ 10-500Hz per IEC 68-2-6 Class I Division 1 Groups C-D T4 Class I Division 2 Groups A-D T4 FM EEx de [ib] IIC T4 - - Certificates CENELEC - BVS 98.D.2055X UL, C-UL UL Certificate Number 99.19699 - C FM 47 US Class I Division 1 Hazardous - Class I Division 1 Groups B-D T4 Class I Division 2 Groups A-D T4 Mounting - Class I Division 1 Groups B-D T4, Class I Division 2, Groups A-D, T4, Class I Zone 1 IIC IS Power - Class I Division 1&2 Groups A-G T4 Class I Zone 1 AEx [ib] IIC UL Certificate Number 99.19699 C - US Class I Division 1 Hazardous FM Certificate Number 3009806 Publication 1797-2.1 - August 2001 48 FLEX Ex Accessories Cat. Nos. 1797-BOOT, -INS, and -EXMK FLEX Ex FLEX Ex Accessories Cat. Nos. 1797-BOOT, -INS, and -EXMK Use the ControlNet BNC boot, trunk insulator, and marking kit in your cable connections. The 1797-BOOT covers the BNC connector on the ControlNet Ex trunk cable. tap IS insulators tap tap trunk terminator with intrinsically safe insulator trunk terminator with intrinsically safe insulator trunk-cable section trunk-cable section 30094 The 1797-INS is a bag of assorted insulators that you can use to replace those shipped with the product. The 1797-EXMK is a marking kit for FLEX Ex cable. Cable #A 38 Tab can be marked with cable system identification (example shown). 30597-M Publication 1797-2.1 - August 2001 FLEX Ex Extender Cables Cat. Nos. 1794-CE1 and -CE3 49 Extender Cables Cat. Nos. 1794-CE1 and -CE3 Extender Cables Use the optional 1794-CE1 (0.3m, 1ft) or 1794-CE3 (0.9m, 3ft) extender cable (one per system) to arrange your FLEX Ex system into two rows or split your system into horizontal and vertical orientation. 1794-CE1 or 1794-CE3 Extender Cable 20129-M Bus Isolator . . FLEX I/O . . . . . . . . . . . .. . . . . 1794-CE3 . 1 . . . . . . 1797-BIC 1797-CEC . . . .. . . . . FLEX Ex . . . 40089 Publication 1797-2.1 - August 2001 50 Intermixed Systems FLEX Ex Intermixed Systems Intermixed Systems The bus isolator modules, 1797-BIC and -CEC, allow you to configure FLEX Ex modules and FLEX I/O modules on the DIN rail when attached to the same adapter and grouped together on appropriate sides of the bus isolator module. This highly flexible, cost-effective solution combines intrinsically safe and non-intrinsically safe systems. Intermixed systems can be configured for use in the: • safe area much like traditional IS and I/O systems • hazardous and safe control equipment where the distance of physical separation is short • FLEX Ex I/O with communication adapters that are not intrinsically safe 1797-CEC any FLEX I/O communication adapter that supports FLEX Ex Nonhazardous Area or Class I Division 2, Groups A-D . . . . . . . . . . . . . Bus Isolator FLEX Ex . . .. . . . . . .. . . . . . Field Wiring to Zone 0 Class I, II, III Division 1, Groups A-G 1 . . . . . . . . . FLEX I/O 42848 Mixing Systems in the Safe Area Hazardous Area Zone 1 Class I Division 1, Groups A-D Bus Isolator any FLEX I/O communication adapter that supports FLEX Ex 1797-CEC 1794-CE3 . . . . . . . . . . . . . .. . . . Maximum of 1m . FLEX Ex . 1 . . . . . . . . . 1797-BIC Nonhazardous Area or Class I Division 2, Groups A-D . .. . . . FLEX I/O . . Field Wiring to Zone 0 Class I, II, III Division 1, Groups A-G . 40087 Mixing Systems in the Hazardous Area Hazardous Area Zone 1 Class I Division 1, Groups A-D any FLEX I/O communication adapter that supports FLEX Ex Nonhazardous Area 1797-CE1S . Flexbus Feed Through . . . . . 1 conduit . 1794-CE3 1797-CEC 1797-BIC Max of 1m FLEX Ex . . . . .. . . . . . . . . . .. . Field Wiring to Zone 0 Class I, II, III Division 1, Groups A-G Publication 1797-2.1 - August 2001 . . 40088 FLEX Ex Bus Isolator Module and Flexbus Connector Cat. Nos. 1797-BIC and -CEC 51 Bus Isolator Module and Flexbus Connector Cat. Nos. 1797-BIC and -CEC Slave Side Master Side 1797-CEC 1797-BIC FLEXBUS ISOLATOR PWR FLEXBUS CONNECTOR +V 1 -V 2 +V 3 -V 4 40082 Product Features • Provides an IS-compatible mechanism to separate two sections of the backplane allowing IS and non-IS field-device wiring to the same I/O group • Converts hazardous power to IS-safe power to run one side of the bus receiver/transmitter circuitry and IS-safe power to slave side modules • Up to 8 FLEX Ex modules may be attached to the slave side Customer Connections 1797-CEC 1797-BIC Bus flexbus flexbus PWR limit flexbus flexbus Bus +V power supply -V 41693 Publication 1797-2.1 - August 2001 52 Bus Isolator Module and Flexbus Connector Cat. Nos. 1797-BIC and -CEC 1797-BIC Specifications I/O Module Capacity FLEX Ex 1797-CEC Specifications 8 FLEX Ex modules Indicators Not applicable Indicators Power green Weight Approximately 100g Isolation Path Flexbus to Flexbus Flexbus Slave Side to Power Supply Galvanic to DIN EN50020 Galvanic to DIN EN50020 Power Consumption 18V - 32V dc @ 0.15A 1 Environmental Conditions Power Source Failure Maximum Input Um = 253V ac Power Dissipation 2.1W Thermal Dissipation 7.2 BTU/hr IS Module Type [EEx ib] IIC 12 gauge (4mm ) stranded maximum 3/64in (1.2mm) insulation maximum Weight Approximately 200g 2 Environmental Conditions Operational Temperature -20 to 70oC (-4 to 158oF) Storage Temperature -40 to 85oC (-40 to 185oF) Relative Humidity 5 to 95% noncondensing Shock Operating Tested 30g peak acceleration, 11 (±1)ms pulse width Non-Operating Tested 30g peak acceleration, 11 (±1)ms pulse width Vibration Tested 5g @ 10-500Hz per IEC 68-2-6 Uo Io Po Lo Co < < < < < 5.75V dc 400mA 2.05W 100µH 39µF Agency Certification CENELEC II (2)G [EEx ib] IIC FM Nonincendure, use for Class I, Division 2 Groups A-D or Class I, Zone 2 Group IIC Provides intrinsically safe outputs to Class I, Division 1 Groups A-D or Class I, Zone 1 Group IIC Certificates CENELEC DMT 00 ATEX E056 FM FM Certificate Number 3010810 Declaration of Conformity Directive 94/9 EC 1 Zone 2 II 3G EEx nA IIC T4 X A total of eight I/O modules can be attached to a 1794 FLEX I/O adapter. The 1797-CEC and -BIC are not included in this number. In intermixed systems, the number of 1797 FLEX Ex I/O modules (attached onto the 1797-BIC) plus the number of 1794 FLEX I/O modules (connected between the adapter and the 1797-CEC) cannot exceed eight. Publication 1797-2.1 - August 2001 -20 to 70oC (-4 to 158oF) Storage Temperature -40 to 85oC (-40 to 185oF) Relative Humidity 5 to 95% noncondensing Shock Operating Tested 30g peak acceleration, 11 (±1)ms pulse width Non-Operating Tested 30g peak acceleration, 11 (±1)ms pulse width Vibration Conductor Wire Size Output (Intrinsically Safe) (16 pin male and female flexbus connector) Operational Temperature Tested 5g @ 10-500Hz per IEC 68-2-6 Agency Certification FM Nonincendure, use for Class I, Division 2 Groups A-D or Class I, Zone 2 Group IIC Certificates FM FM Certificate Number 3010810 Declaration of Conformity Directive 94/9 EC Zone 2 II 3G EEx nA IIC T4 X FLEX Ex Extender Cables and Flexbus Feed Throughs Cat. Nos. 1797-CE1S, - CE3S, -CEFTN, and -CEFTE 53 Extender Cables and Flexbus Feed Throughs Cat. Nos. 1797-CE1S, - CE3S, -CEFTN, and -CEFTE Use the optional Bus Isolator 1797-CE1S (0.3m, 1ft) or 1797-CE3S (0.9m, 3ft) extender cable to mix systems in the hazardous area. Hazardous Area Zone 1 Class I Division 1, Groups A-D any FLEX I/O communication adapter that supports FLEX Ex Nonhazardous Area 1797-CE1S . Flexbus Feed Through . . . . . conduit 1 . 1794-CE3 1797-CEC 1797-BIC Max of 1m FLEX Ex . . . . .. . . . . . . . . . .. . Field Wiring to Zone 0 Class I, II, III Division 1, Groups A-G . . 40088 Flexbus Feed Throughs 41680 Flexbus Feed Through Specifications For Metric Threads on the Connector: Part Number Manufacturer RS-FEED.M Pepperl+Fuchs 07-9109-99979XP1 Bartec For NPT Threads on the Connector: Part Number Manufacturer RS-FEED.NPT Pepperl+Fuchs 07-9199-99979XP1 Bartec Agency Certification CENELEC EEx d IIC T6IBEx U 98 ATEX 1033U FM FM Approved per J.I. 3002937 Publication 1797-2.1 - August 2001 54 Support Services FLEX Ex Support Services Support Services At Allen-Bradley, customer service means experienced representatives at Customer Support Centers in key cities throughout the world for sales service and support. Our value-added services include: Technical Support • • • • SupportPlus programs Telephone support and 24-hour emergency hotline Software and documentation updates Technical subscription services Engineering and Field Services • • • • Application engineering assistance Integration and start-up assistance Field service Maintenance support Technical Training • • • • Lecture and lab courses Self-paced computer and video-based training Job aids and workstations Training needs analysis Repair and Exchange Services • • • • Publication 1797-2.1 - August 2001 Your only “authorized” source Current revisions and enhancements Worldwide exchange inventory Local support FLEX Ex Support Services 55 Notes: Publication 1797-2.1 - August 2001 The following are trademarks of Rockwell Automation: FLEX Ex, FLEX I/O, ControlNet Ex, PLC-5/20C, PLC-5/40C, SLC 500, and ProcessLogix. DeviceNet is a trademark of Open DeviceNet Vendor Association (O.D.V.A.). ControlNet is a trademark of ControlNet International. Publication 1797-2.1 - August 2001 Supersedes Publication 1797-2.1 - August 2000 Copyright 2000 of Rockwell International Corporation. Printed in the U.S.A.