APPLICATION Evaluation of a new 3-phase dip definition by M Schilder and RG Koch, Eskom Experience has shown that a jump in the phase angle of the voltages at the start of a dip can cause some line-commutated variable-speed drives to trip, even if the dip magnitude is relatively small. This is a nuisence in mining and other industries and has led to the proposal for a new dip definition. Most dip definitions are based on the duration and magnitude of the dip event only (e.g. as specified in IEC-610004-30). A new definition has been proposed that considers the unbalance characteristics during a dip and the phase angle jump on initiation of the dip [1]. This paper evaluates the application of the two proposed algorithms in the classification of dips measured in South Africa. Although the new definition provides a better assessment of the severity of the dip based on both voltage magnitudes and phase angles, it was found that several types of dips are not classified correctly. This is particularly true for the case of measurements where the phase angle of one of the phases is set to a fixed reference (i.e. 0°). In this case the respective algorithms classify only 50% to 80% of measured dips correctly. The new definition provides better insight into complex dip characteristics, but further work is required on the classification algorithms as well as specifications for instruments to measure dips when applying this new definition. In contrast with the current Drop in Characteristic 6-phase: Type T PN factor dip definition that only phases voltage lowest phase uses voltage magnitude Ca 0 bc V=V1-V2 F=V1+V2 VBC (disregarding phase Dc 1 c VC’ V=V1+αV2 F=V1-αV2 angle changes) and dip Cb 2 ac VCA V=V1-α²V2 F=V1+α²V2 duration, the proposed Da 3 a V=V1+V2 F=V1-V2 VA’ dip definition attempts Cc 4 ab VAB V=V1-αV2 F=V1+αV2 better classification of unbalanced three-phase Db 5 b VB’ V=V1+α²V2 F=V1-α²V2 voltage dips in terms Table 1: Dip analysis characteristics. of both the voltage magnitude and the phase angle changes on the difference between the positive and that take place. It is based on a sound negative sequence remaining voltages. theoretical analysis deriving from simplified Depending on the phases that are involved in the fault, the negative sequence voltage symmetrical components using a voltage will be multiplied by a factor αx as shown in divider model [1, 2, 3]. According to the Table 1 where: proposed method, a dip is classified by a characteristic voltage and a PN factor and attempts to classify the dip in one of two main categories, C or D. The dip is further identified by a subscript that indicates the symmetrical phase, i.e. the least dipped phase for two-phase (C-type) dips, or the most dipped phase for single-phase (D-type) dips, as shown in Fig. 1. The main feature is the characteristic voltage or equivalent dip magnitude that is based α = e j120° and x=0, 1, 2 A few examples of measured dips are shown in Fig. 2. It is immediately clear that all dips do not fit into the definitions of Fig. 1; either the relative phase angles differ from the definition or the magnitudes of all three phases are different. The classifications shown in Fig. 2 are based on the relative magnitudes of the three phase voltages only. However, the severity of the dip (characteristic voltage) will depend on the relative phase angles between the phases. Fig. 1: D (single-phase) and C (two-phase) dip types. Fig. 2: Example vector diagrams of practically measured dips from Eskom dip database, which do not directly fit the definitions shown in Fig. 1. energize - June 2006 - Page 64 Two algorithms were previously proposed to classify the dips according to the new definition into either C - o r D -t y p e d i p s [1, 2]. This paper reports on the results of a study that was undertaken to evaluate whether the new definition is appropriate for use within the South African context – and if so, which algorithm should be used for the classification. The evaluation comprised APPLICATION Description # dips T=Tsym T=T6 Tsym=T6 T=Tsym T=T6 Transmission 520 222 459 220 42,69% 88,27% Distribution 913 352 846 365 38,55% 92,66% Table 2: Dip classification results for dips during 2003. several steps: Various dip types were simulated using Matlab, from this, the types and numbers of dips that may be classified incorrectly were identified, i.e. where the classified dip type does not correspond to the definition of Fig. 1 based on the phase magnitudes only, these results were then compared to measured dip data from the Eskom National Power Quality Database to determine how many of these poorly-classified dips occur in reality. Testing of classification algorithms Fig. 3: Characteristic voltage and PN factor for a single-phase dip, as calculated by the symmetrical components method. The following steps were implemented to test the success of the two algorithms in classifying simulated and practical dips into the C and D classes shown in Fig.1: Six-phase algorithm In this case, six voltages are calculated, namely the three line-to-line voltages as well as the three modified phase voltages. These voltage vectors exclude the zero-sequence component, which is first subtracted. (This is because the algorithms aim at providing an assessment of dip impacts on customer plant – and zero-sequence voltage components do not propagate far in most power systems). The characteristic voltage is, according to this algorithm, defined as the magnitude of the lowest of the six voltages, while the phase with the largest magnitude of the six voltages is the PN factor. The dip type is determined from Table 1 (last column) based on the lowest of the six-phase voltages. Symmetrical component algorithm In this case, the positive (V1) and negative (V2) sequence voltages are calculated using Fortesque’s decomposition matrix. Fig. 4: Dip type (six-phase method) for a SLGF (‘A’-phase) when varying both magnitude and phase jump (Dip type = 3). The dip type is classified according to the factor T given in Table 1, which is calculated by Eqn. 1. (It may be noted that the addition of the 20o before evaluating the argument in Eqn. 1 was determined empirically for practical cases [2]). (1) The characteristic voltage (V) and PN factor (F) can be found by using Eqn. 2: (2) Reference dip classification The above classification methods for C and D type events require voltage vector measurements. A recent paper [4] discusses classification of voltage dips when only RMS values are available. The dips are classified into the different dip types and an estimate of the voltage vectors is then made. A seven-dip type definition is used in this paper [4]. Fig. 5: Dip type (symmetrical component method) for a SLGF (‘A’-phase) when varying both magnitude and phase jump (‘A’-phase phase referenced to 0°). In order to study the two algorithms proposed by Bollen [1, 2, 3], a similar technique to that in [4] was implemented to determine the dip type based only on the magnitudes of the phase voltages. Only C and D type dips, as shown in Fig. 1, were studied. The most difficult dip types to classify are those where the difference between the maximum and middle, and between the middle and minimum voltage magnitudes energize - June 2006 - Page 66 APPLICATION an indication of the severity of a dip, based on either the voltage drop or the phase jump of the faulted phase. The characteristic voltage is constant at 0,33 pu when the faulted phase drops to 0 V (horizontal cur ve), correlating with practical results where it was found that a SLGF should not drop the voltage on the customer side of a delta-wye or wye-delta Fig. 6: Dip type (six-phase method) for a LLF (‘CA’-phases) when transformer to less than varying both magnitude and phase jump (Dip type = 2). 0,3 pu [5,6]. It also shows are the same. In classifying simulated and that a 180° phase shift of measured data with these characteristics; if the faulted phase will result in classification as the voltage on two of the phases was above a very severe dip event, even if the voltage 0,9 pu (classical dip threshold), the dip was magnitude does not drop significantly. Such classified as a single-phase event (D-type) an indication of severity, based on either a otherwise it was considered a two-phase drop in magnitude or a phase jump during event (C-type). the dip, may be advantageous to describe dips for plant sensitive to such phase angle Theoretical comparisons jumps, once the impact of phase jump on Bollen provides proof, using a set of synthetic these sensitive items has been quantified. dip events, to explain that a perfect algorithm Phase shifts measured by Eskom’s power does not exist to classify dip characteristics [2]. quality monitors range up to 127°. Dip Since the purpose of this project is to test the simulations using Digsilent show that phase two proposed characterisations for local dips, jumps of up to 180° can be expected for various dip types were generated in Matlab single-phase dips and up to 120° for twoto test which dips will be classified incorrectly, phase dips for any of the phase voltages, before analysing measured dips. when the ‘A’-phase angle is normalised to 0°. An example of the calculated characteristic The phase angle normalisation is required for voltage (using the symmetrical component comparison with the measurements, since method) for a single-phase dip (Da) is shown the instruments that were used normalise in Fig. 3. Each curve represents a constant the ‘A’-phase angle to 0° when assessing remaining voltage for the dipped phase the event. for various phase angle jumps, shown on Simulated dips the abscissa. and 7, where the symmetrical component Generic dips were simulated, varying both the magnitudes and phase angles of the three phase voltages symmetrically, i.e. only one phase is varied or the two phases are varied equally and symmetrically around the healthy phase. This method may include dips not generally measured in practice, but provides a good overview of the types of dips that may be classified incorrectly. the magnitude and phase values (in contrast Graphs showing the dip type vs. phase magnitude and angle for Da and Cb dip types are shown in Figs. 4 to 7. The impact of rotating the dip for a 0° ‘A’-phase reference is clear in Figs. 5 phase voltage magnitudes, while “sym” and The remaining voltage curves start at 1 pu, varied in steps of 0,125 pu to 0 pu. The graph shows that the characteristic voltage provides Fig. 7: Dip type (symmetrical component method) for a LLF (‘CA’phases) when varying both magnitude and phase jump (‘A’-phase phase referenced to 0°). energize - June 2006 - Page 68 method changes from all practical dips classified correctly, to very few dips classified correctly. The graph for dip type Cc is similar to the Cb graph. The inaccuracy of the symmetrical component method when rotating the measured dips to the 0° ‘A’-phase reference, is due to the denominator in Eqn. 1, namely the vector (1-V1). The positive and negative sequence components’ arguments vary symmetrically when the reference phase angle is varied, but the vector (1-V1) behaves completely differently – resulting in incorrect dip type classification. Note that if the vector (1-V1) is replaced by the positive sequence vector, the results are similar to that of the six-phase algorithm and the reference phase angle becomes unimportant. In theory, more than 65% of dips should be classified correctly by the symmetrical component method (based on the typical distributions of SLGF and LLF). In practice, phase shift on the ‘A’-phase is usually expected, even for Db, Dc and Ca dip types, resulting in many dips classified incorrectly. Some of the expected problems with the proposed algorithms have now been highlighted. However, it is clear that these may be useful, when looking at the characteristic voltage for the different types of dips (as was shown in Fig. 3). Eskom national power quality database analysis The instruments used to monitor power quality in transmission and distribution substations calculate and store vector events once every cycle. A Fourier transform is used to calculate to half-cycle RMS values specified for dips in IEC 61000-4-30). A fairly slow phase-lockedloop is implemented to synchronise the measurements, which may lead to further errors in the vector event data, especially if the reference phase voltage drops to zero. Various dip events measured on the transmission and distribution systems were analysed using the two algorithms. The results for dip type classification are presented in Table 2. No subscript to the T indicates the reference type classification based on the “6” subscripts indicate the result from the symmetrical component or six-phase method respectively. Note that all balanced dips (type A) are classified correctly by both algorithms and were therefore excluded from the results shown in Table 2. APPLICATION As expected, the symmetrical component algorithm yields very poor results, since most dips experience some phase shift on the reference ‘A’-phase. However, the results from the six-phase algorithm, ranging from 88% to 93%, are also unacceptable for practical purposes. An attempt to compensate for the loss of the ‘A’-phase angle information resulted in the symmetrical component method accuracy increasing to approximately 55%, which is still unacceptable. Conclusions and recommendations The new dip definition indicates the severity of a dip in terms of both the dip magnitude and the phase angle jump. However, this severity still needs to be linked to the sensitivity of motor drives and other equipment. From the studies based on simulated and measured dips, various shortcomings of the new classification algorithms and/or measurement methods were found. These are, the known impact of the phase jump during a dip on the accuracy of the six-phase algorithm was confirmed. Practical dips seem to be classified correctly only 88% to 93% of the time. It was also found that the symmetrical component method is dependent on the true phase angle of the References reference voltage, i.e. the dip should not be [1] Bollen, M.H.J., Zhang, L.D., “Different methods for classification of three-phase unbalanced voltage dips due to faults”, CIGRE, 10 pages. [2] Bollen, M.H.J., “Algorithms for characterizing measured three-phase unbalanced voltage dips”, IEEE Transactions on Power Delivery, Vol. 18, No. 3, July 2003, pp. 937944. [3] Anderson, P.M., “Analysis of Faulted Systems”, IEEE Press Power Systems Engineering Series, 1995, ISBN 0-78031145-0. [4] Bollen, M.H.J., Goossens, P., Robert, A., “Assessment of voltage dips in HVnetworks: Deduction of complex voltages from the measured RMS voltages”, IEEE Transactions on Power Delivery, Vol. 19, No. 2, April 2004, pp. 783-790. [5] Zhang, L., Bollen, M.H.J., “Characteristic of Voltage Dips (Sags) in Power Systems”, IEEE Transactions on Power Delivery, Vol. 15, No. 2, April 2000, pp. 827-832. [6] cGranaghan, M.F., Mueller, D.R., Samotyj, M.J., “Voltage sags in industrial systems”, IEEE Transactions on Industry Applications, rotated to have the reference phase at 0o Particular attention in further work should concentrate on the reference angle dependency of the symmetrical components method needs to be investigated further. Due to the reservations about dip voltage vector measurements, future specifications for measurement of dip vectors should be investigated and proposed. Equipment sensitive to phase jumps during dips should be tested in order to determine the real impact of the phase jump. Acknowledgements The authors would like to thank Eskom Distribution and Transmission for use of data in the dip database, as well as Mr. R Ragoonanthun for assistance in extracting the required dip information. This paper was first presented at Cigré’s 5th Southern Africa Regional Conference in October 2005 and is reproduced with permission. energize - June 2006 - Page 69 Vol. 29, No. 2, April 1993, pp. 397-403. Contact Melanie Schilder, Eskom, melanie.schilder@eskom.co.za