Installation instructions

advertisement
E
ERCO GmbH
Postfach 24 60
58505 Lüdenscheid
Brockhauser Weg 80-82
58507 Lüdenscheid
Germany
Tel.: +49 2351 551 0
Fax: +49 2351 551 300
info@erco.com
www.erco.com
Lightmark
Floorwashlight
Mounting instructions
3000045270
0615
1
Choosing the mounting location
Luminaire not suitable for covering
with thermal insulation material.
- Lateral air space according to
EN 60598:
The distance between the surface of the
luminaire and any parts of the building
must be no less than 50mm.
- Recess depth according to EN 60598:
No minimum distance is required between the back of the luminaire and any
parts of the building.
- The luminaire must be positioned so as
to avoid operation in direct sunlight or
near other sources of heat. High ambient
temperatures can reduce the life and efficiency of the control gear or LED module.
Electrical installation
To avoid any damage to the electronic
control gear on a 3-circuit installation,
the neutral conductor of electronic
control gear must never be interrupted.
Over-voltage protection
To protect electronic control gear from
voltage spikes, e.g. when switching
inductive loads, separate overvoltage
protection units may be used.
Notes on corrosion protection
Ensure that the powder coating is
not damaged during installation or
maintenance work. Any damage, which
becomes wet, can result in corrosion
occurring. In aggressive environments,
the installation and maintenance of
all parts will require the appropriate
protective measures. Chemicals damage
the corrosion protection.
English
Read the instructions carefully
before installation and commissioning!
Leave the instructions for users/
customers for future reference!
Our continually updated product
documentation can be accessed at www.erco.com/download.
General safety information
Warning!
Risk of electric shock!
Before carrying out maintenance and
installation on the luminaire, disconnect from the mains supply and ensure
that all power is switched off.
Attention!
- Do not operate luminaires with
da­maged or missing protective covers.
- Do not open the luminaire. In case of
damage or a defective LED module, the
entire luminaire must be returned to
the factory.
- When installing, always observe the
national installation and accident prevention regulations.
Intended use
- The luminaire is suitable for both outdoor and indoor use.
- The luminaire is approved for wall
mounting only.
- The recommended mounting height
for the luminaire is 0.8m.
Restrictions
The luminaire is approved for a mounting height of up to 5m.
Mounting
- Use the supplied frame to mount
the luminaire in the cavity wall or in
brickwork.
- Flush mounting in a cavity wall
requires an additional covering or further plastering.
- A concrete housing for mounting the
luminaire in concrete or in plastered
brickwork is available as an accessory.
Cavity wall
1. Prepare a wall opening.
2. Insert the mounting frame.
3. Place 4 mounting brackets from the
outside into the long holes of the frame
and secure the frame (Fig. 5).
Note for flush mounting:
Apply second covering or plastering prior to inserting the luminaire (Fig. 7).
4. Make the electrical connection via a
terminal (to be provided on-site) and
junction box (to be provided on-site).
Terminal requirements:
- 3-pole screw terminal or screwless
terminal
- 250V min.
- 1A min.
- Prepare conductor ends as specified
by the terminal manufacturer.
- Always fit the terminal in a suitable
junction box or branch sleeve in compli-
ance with the national regulations.
5. Insert the luminaire into the frame
without tools.
Brickwork
Note: The clearances specified in Fig. 1
do not apply to mounting in brickwork.
1. Prepare an installation opening, leaving space for a junction box.
2. Insert the mounting frame. The holes
on the back may be used to fix the mounting frame. The outer edge of the frame
must be flush with the wall surface.
Note for flush mounting:
The outer edge of the frame must sit
flush with the plastered wall surface.
3. Plaster the frame and fill in the hole.
4. Make the electrical connection via a
terminal (to be provided on-site) and
junction box (to be provided on-site).
Terminal requirements:
- 3-pole screw terminal or screwless
terminal
- 250V min.
- 1A min.
- Prepare conductor ends as specified
by the terminal manufacturer.
- Always fit the terminal in a suitable
junction box or branch sleeve in compliance with the national regulations.
5. Place the luminaire in the frame.
Concrete housing (accessory)
Follow the accessory instructions.
local facility available for the disposal
or recycling of electronic products.
Removing the luminaire
Surface-mounted luminaire
Carefully lift the luminaire out of the
frame using a flat object (e.g. screwdriver).
Flush-mounted luminaire
Remove the luminaire from the frame
using a suction cup, e.g. ERCO accessory
33799.
Flashing of the LED module
It is normal for the LED module to
flicker when switching on and off.
Dimming
The luminaire cannot be dimmed.
Cleaning
Regular cleaning is essential. The
required intervals and methods depend
on the mounting location, the mounting situation and the ambient conditions.
Outside cleaning of the luminaire
Clean with a damp, soft cloth. Take care
not to damage the powder-coating.
Cleaning the safety glass
Safety glass can be cleaned with cleaning agents that are also suitable for
glass-ceramic cooking hobs.
Disposal
In accordance with EU Directive
WEEE (Waste Electrical and Electronic Equipment), luminaires must not
be disposed of with other household
waste. At the end of their life, luminaires must be taken to the appropriate
3000045270
2
Download