annexure-ii technical specification of electrical items. sr.no

advertisement
ANNEXURE-II
TECHNICAL SPECIFICATION OF ELECTRICAL ITEMS.
SR.NO.
01
DESCRIPTION OF ITEMS
SUPPLY AND INSTALLATION OF G.I CABLE TRAY WITH
SUPPORT AND GROUTING ABOVE GROUND:
Specification: Wide-200mm, Depth-50mm, Perforated, Cable tray made
out of 14/16 swg CRCA sheet duly hot dip galvanised after fabrication
for min galvanising thickness of 84 microns with required GI coupler
plates & SS hardware. Inclusive M S Structure steel for installation of
tray panel. ROUTE- as per direction of EIC.
02
SUPPLY AND INSTALLATION OF 415VOLTS,THREE PHASE
NEUTRAL,63 AMPS, FP & WP SOCKET WITH TOP :
Specification:-The socket with top must be certified by CMRE, and
approved by CCE and DGFSAL.
Enclosure: Ex-d as per IS:2148-2004,suitable for installation in
hazardous location Zone-1 & 2 as per IS:5572/94,Protection:IP -65 as
per IS:12063/1987, Area Classification: Gas Gr. II A & II B, Material
of Construction: Cast Al. ALLOY LM-6,Component: Switch, Socket &
Plug ,Terminal : Clipon Type Rail Mounted, Temp Classification:T5
Gasket: Endless, Molded Neoprene, Finish: Anti corrosive Epoxy
powder coated, Voltage:415 V AC,50 Hz, Earthing: 1 No. Inside & 2
Nos. Outside M8, Cable Entry: 1.5” ET X 2 No., Recommended Make:
Baliga, or FCG or Exprotecta or Sudhir Switch Gear Pvt. Ltd.
03
SUPPLY AND INSTALLATION OF NON INTEGRAL TYPE
WATT HPMV FP,WP LIGHTING FIXTURE WITH LAMP:
125
Specification:-125 watt HPMV. The Fixture must be of certified by
CMRE, and approved by CCE and DGFSAL,Enclosure: Ex-d as per
IS:2148-2004,suitable for installation in hazardous location Zone-1 & 2
as per IS:5572/94,Protection:IP -65 as per IS:12063/1987, Area
Classification: Gas Gr. II A & II B, Material of Construction: Cast Al.
ALLOY LM-6,Rating:125 Watt HPMV Y, Temp Classification:T5
,Transparent Part :Heat & Impact Resistant clear Dome Toughened
Type “A” Glass as per IS:2206(Part-1),Lamp Holder: Porcelain ES
Cap-27, Hardware: SS, Wireguard: Welded steel construction, Gasket:
Endless, Molded Neoprene, Finish: Anti corrosive Epoxy powder
coated, Reflector: Internal Reflector,Voltage:230 V AC,50 Hz, Wiring:
Fiberglass class F insulated 1.5sqmm standard copper, Cable size:3x4
sq.mm, Earthing: 1 No. Inside & 2 Nos. Outside M6, Cable Entry: 3/4”
ET X 2 No., Recommended Make: Baliga, or FCG or Exprotecta or
Sudhir Switch Gear Pvt. Ltd.
04
SUPPLY AND INSTALLATION OF FP,WP CONTROL GEAR BOX
FOR 125 WATT HPMV LAMP :
Specification:-125 watt HPMV. The Fixture must be of certified by
CMRE, and approved by CCE and DGFSAL, Enclosure: Ex-d as per
IS:2148-2004,suitable for installation in hazardous location Zone-1 & 2
as per IS:5572/94,Protection:IP -65 as per IS:12063/1987, Area
Classification: Gas Gr. II A & II B, Material of Construction: Cast Al.
ALLOY LM-6,Rating:125 Watt HPMV Y, Temp Classification:T6 ,
Hardware: SS, Gasket: Endless, Molded Neoprene, Finish: Anti
corrosive Epoxy powder coated, Voltage:240 V AC,50 Hz decreasing
step up to 200V, Wiring: PVC insulated 2.5sq.mm standard copper,
Cable size:3x6 sq.mm, Earthing: 1 No. Inside & 2 Nos. Outside M6,
Cable Entry: 3/4” ET X 2 No., Terminal:4 way terminal block suitable
for 6 sq.mm, Recommended Make: Baliga, or FCG or Exprotecta or
Sudhir Switch Gear Pvt. Ltd.
04
SUPPLY AND INSTALLATION OF FP,WP 3-WAY DIV-2 JUNCTION
BOX :
The Junction box must be of certified by CMRE, and approved by
CCE and DGFSAL, Enclosure: Ex-d as per IS:2148-2004,suitable for
installation in hazardous location Zone-1 & 2 as per
IS:5572/94,Protection:IP -65 as per IS:12063/1987, Area Classification:
Gas Gr. II A & II B, Material of Construction: Cast Al. ALLOY LM-6,
Gasket: Endless, Molded Neoprene, Finish: Anti corrosive Epoxy
powder coated Terminal:3 way terminal block suitable for 10 sq.mm,
Recommended Make: Baliga, or FCG or Exprotecta or Sudhir Switch
Gear Pvt. Ltd.
05
SUPPLY AND INSTALLATION OF 230 VOLTS,SINGLE PHASE
NEUTRAL,16 AMPS, FP & WP SOCKET WITH TOP :
Specification:-The socket with top must be certified by CMRE, and
approved by CCE and DGFSAL.
Enclosure: Ex-d as per IS:2148-2004,suitable for installation in
hazardous location Zone-1 & 2 as per IS:5572/94,Protection:IP -65 as
per IS:12063/1987, Area Classification: Gas Gr. II A & II B, Material
of Construction: Cast Al. ALLOY LM-6,Component: Switch, Socket &
Plug ,Terminal : Clipon Type Rail Mounted, Temp Classification:T5
Gasket: Endless, Molded Neoprene, Finish: Anti corrosive Epoxy
powder coated, Voltage:230 V AC,50 Hz, Earthing: 1 No. Inside & 2
Nos. Outside M8, Cable Entry: 1.5” ET X 2 No., Recommended Make:
Baliga, or FCG or Exprotecta or Sudhir Switch Gear Pvt. Ltd.
06
SUPPLY AND INSTALLATION OF 415VOLTS,THREE PHASE
NEUTRAL,100 AMPS, FP & WP,6 WAY DISTRIBUTION BOARD:
Specification:-The distribution board must be certified by CMRE, and
approved by CCE and DGFSAL.
Enclosure: Ex-d as per IS:2148-2004,suitable for installation in
hazardous location Zone-1 & 2 as per IS:5572/94,Protection:IP -65 as
per IS:12063/1987, Area Classification: Gas Gr. II A & II B, Material
of Construction: Cast Al. ALLOY LM-6,Component: 100 A
TPN
MCB+ELCB 1 NO.(I/C) ,40A DP MCB 6 NO.S (O/G) ,Suitable
connector and FP&WP cable glands ,Gasket ,Temp Classification:T5
Gasket: Endless, Molded Neoprene, Finish: Anti corrosive Epoxy
powder coated, Voltage:415 V AC,50 Hz, Earthing: 1 No. Inside & 2
Nos. Outside M8, Cable Entry: 1.5” ET X 2 No., 3/4” ET X 6 No. for
O/G cables. Recommended Make: Baliga, or FCG or Exprotecta or
Sudhir Switch Gear Pvt. Ltd.
07
SUPPLY AND INSTALLATION OF GI LIGHTING POLE FOR
FLOOR MOUNTING OF 125 W HPMV,FP,WP LIGHTING FIXTURE:
Specification: Dia-4”,5MM wall thickness, LNTH-6 Mtr. Hot dip GI pipe
swan neck type bend at the top with suitable facility for mounting of
light fixture. Including Excavation, casting of foundation, AL painting &
fixing of lighting pole for floor mounting with necessary hardware and
connection & checking.
08
SUPPLY AND INSTALLATION OF CU, PVC INSULATED,
ARMOURED CABLE OF 1100 VOLT, 3.5 CORE, 2.5 SQ.MM FOR
LIGHTING SYSTEM:
Specification:3.5x2.5SQ.MM,laying on existing cable Tray/PCC/ RCC/
Wall/Supported on structure including supply & fixing of G.I saddles &
Bars ,Lugs and all necessary hardware’s.
09
SUPPLY AND INSTALLATION OF AL, PVC INSULATED,
ARMOURED CABLE OF 1100 VOLT, 3 CORE, 10 SQ.MM FOR
LIGHTING SYSTEM:
Specification:3x10 SQ.MM, laying on existing cable Tray/PCC/RCC/
Wall/Supported on structure including supply & fixing of G.I saddles &
Bars ,Lugs and all necessary hardware’s.
10
SUPPLY AND INSTALLATION OF CU, PVC INSULATED,
ARMOURED CABLE OF 1100 VOLT, 5 CORE, 2.5 SQ.MM FOR
LIGHTING SYSTEM:
Specification:5x2.5 SQ.MM, laying on existing cable Tray/PCC/RCC/
Wall/Supported on structure including supply & fixing of G.I saddles &
Bars, Lugs and all necessary hardware’s.
11
SUPPLY AND INSTALLATION OF FLAMEPROFF DOUBLE
COMPRESSION CABLE GLAND:
Specification: 5Cx2.5SQ.MM, 3.5Cx2.5SQ.MM & 3Cx10 SQ.MM.
The Gland must be of certified by CMRE, and approved by CCE and
DGFSAL.
12
SUPPLY AND LUGGING OF CU /AL LUG:
Specification: CU 2.5SQ.MM, & AL 10SQ.MM.
13
SUPPLY AND INSTALLATION OF TESTING COMMISIONING OF
EARTH PIT:
Specification: G.I Earth Electrode made up of 65MM DIA MS Pipe
with wall thickness of 3.5 mm (Class B),3000 mm long duly perforated
with connecting link of size 50x6 mm welded to the pipe for each
connection ,fabricated as per IS:3043 and hot dip galvanized after
fabrication for Zink coating of Minm 85 Micron(610 gms/sq.mtr)
.
Including Excavation of earth pits, filling with charcoal, salt, backfilling,
providing necessary brickwork chamber and with suitable cross welded
GI strip for connecting of earth Strip with electrodes.
14
SUPPLY AND LAYING OF EARTH STRIP & ROPE:
Specification: 50x6 mm /25x3/10 mm GI earth strip zink coating of
minm 85 microns (610 gms/sq.mtr).Laying of GI earth strip including
excavation work and clamping of GI strip laying overlapping ,welding
of joints ,putting anti corrosive material and applying hessian tape on
joints and connecting of newly built earth pit with existing earthing grid
of plant.
15
SUPPLY OF GI EARTH CHAMBER COVER :
Specification: Max size 60 x 60cm made up of 6 mm thickness
chequered plate along with lifting handle , one coat of red oxide
primer and two coats of synthetic epoxy paint duly painted with earth
pit symbol and no. and as directed by EIC.
16
SUPPLY OF GI EARTH CLAMP:
Specification: 5m long, 25sq.mm insulated single core cu. flexible
conductor with 100A, spring clamp (crocodile clamp).
Download