MHCEA 40th Annual Minnesota Health Care Engineers Seminar Jackpot Junction September 17, 2015 WELCOME MHCEA Ziegler Power Systems Loren Bahls: Senior Sales Engineer Kyle From: Customer Support Representative (CSR) TOPICS • Automatic Transfer Switch (ATS) Features and Operation • ATS Settings Transfer timers, delay Transfer settings, pick up, drop out • 10 Second Starting • ATS Options • Testing to Meet Codes and Accreditation • Ratings of Generators – Achieving 30% load • Questions & Answers ATS - Seven Major Functions • Carry Current Continuously • Detect Power Failures • Initiate Alternate Source Generator Set • Transfer Load • Sense Restoration of Normal • Re-Transfer Load to Normal • Withstand and Close On Fault Currents Standard “Factory Set” ATS Timing Loss of Normal Source: 1 second delay (adjustable) Verifies that Utility power is out and/or unstable Brownout, Single Phase, Blackout Closes contact to start generator set(s) Transfer to Emergency: 0 time delay (0 – 60 min. adjust.) Generator reaches 90% voltage (adjustable 85 – 100%) Generator reaches 95% frequency (adjustable 90-100%) Can be delayed in some schemes – lower priority ATS’s Can be inhibited in some schemes – prevent overload Retransfer to Normal: 30 minutes (adjustable 0-60 min.) Assures that Utility is stable. Timer resets if Utility falters. Cooldown: 5 minutes (adjustable 0-60 minutes) Allows generator to cool down and stabilize. Opens start contact. ATS Evolution Time (sec) Power Fails EVENT Generator Start Signal 10 Second Start and Transfer 1 Engine Cranks via DC Starter Motor(s) 2 Commit to transfer 3 4 Engine Builds Oil Pressure – Governor Accelerates to ATS Transfers 1800 RPM Load 60 HZ 5 6 7 8 9 10 Automatic Transfer Switches (ATS) • Open Transition • Closed Transition • Closed Transition with Soft loading • Bypass Isolation Open or Closed Transition ATS - Open Transition • Standard Automatic Transfer Switch • Most Common for Standby & Emergency System • Break Before Make Transfer • Transfer Time: 1/6th of a second during testing and re-transfer Automatic Transfer Operations(Open Transition) UTILITY OUTAGE TRANSFER OR PEAK SHAVING TRANSFER RETRANSFER TO UTILITY Interconnection for Closed Transition Transfer Bypass / Isolation ATS • Two ATS’s Bussed in Parallel Bypass ATS Fixed Type • One switch is drawout and used for regular operation as a normal ATS. • The other switch is fixed and used Standard ATS Drawout Type only as the Bypass Manual Transfer Switch when the regular ATS is removed for maintenance. • The twin ATS’s are mechanically and electrically interlocked to prevent accidental closure of both sources. Closed Transition ATS • Special Automatic Transfer Switch • Make Before Break Transfer Seamless Transfer - Only on Hot to Hot Transfers • On power failure, operates open transition • During monthly testing, delay in actual transfer time is likely to be more than 10 seconds • Overlap Time 100 Milliseconds Generator is “Block Loaded” • Utility Requirements for Intertie Approval (typical) Visible Disconnect Parallel Timer (62PL) Lockout Relay (86LO) Closed Transition Transfer Operation PEAK SHAVING TRANSFER UTILITY OUTAGE TRANSFER RETRANSFER TO UTILITY Closed Transition Transfer Operation PEAK SHAVING TRANSFER UTILITY OUTAGE TRANSFER RETRANSFER TO UTILITY Closed Transition Softloading • Make Before Break Transfer with Soft loading Controls • Active synchronizing, phase angle, voltage and frequency match • No power interruptions • No Deviation in Voltage or Frequency • Parallel with Utility – No-Break Curtailment Load is ramped from source to source • 10 - 30 second load/unload is typical • Transfer is invisible to the facility New Installations - Certifications • Generators are built to all standards applicable UL, NEMA, IEEE, NFPA, NEC, ISO 8528, IEC • Factory Testing, for Healthcare, at 0.8 PF Published Test Reports • Alternator Testing • Field Testing per NFPA 99/110 load bank test Published Test Reports • Training of Owner’s personnel Names of Trainers and Attendees recorded • Establish logs for monthly testing Calculating Loads • 3 Phase Power • Per regulatory agencies, U.S. Generators are rated and nameplated at 0.8 Power Factor (P.F.) KW = 1.73 x volts x amperes x P.F. 1000 Amperes = See conversion formulas at MHCEA.org KW x 1000 1.73 x volts x P.F. Generator Rating Documentation KW Amperes Controller Evolution Electro-Mechanical 1970 1975 1980 1985 1990 1995 2000 First digital • Early units only displayed volts, amps and frequency • Newer units have direct KW and P.F. on digital display 2005 2010 Power, Exhaust Temperature Measured at engine outlet POWER OUTPUT, KW PERCENT HORSEPOWE R EXHAUST TEMP FUEL RATE 600 100 900 994 42.7 540 90 808 957 39.1 480 80 718 930 35.9 420 70 629 902 32.4 360 60 541 870 28.5 300 50 454 833 24.2 240 40 370 779 19.5 180 30 286 712 14.6 120 20 201 635 10.2 60 10 114 543 6.7 EC.02.05.07, EPs 4-6 • EP 4 Twelve times a year, at intervals of not less than 20 days and not more than 40 days, the organization tests each emergency generator for at least 30 continuous minutes. The completion dates of the tests are documented. • EP 5 The emergency generator tests are conducted with a dynamic load that is at least 30% of the nameplate rating of the generator or meets the manufacturer’s recommended prime movers’ exhaust gas temperature. If the organization does not meet either the 30% of nameplate rating or the recommended exhaust gas temperature during any test in EC.02.05.07, EP 4 then it must test each emergency generator once every 12 months using supplemental (dynamic or static) loads of 25% of nameplate rating for 30 minutes, followed by 50% of nameplate rating for 30 minutes, followed by 75% of nameplate rating for 60 minutes, for a total of 2 continuous hours. • EP 6 Twelve times a year, at intervals of not less than 20 days and not more than 40 days, the organization tests all automatic transfer switches. The completion date of the tests is documented. Joint Commission - Generator Set Testing • Monthly Test Minimum 30 minute continuous run time Minimum 30% load --- OR --Must run at minimum required exhaust temperature per manufacturer Required to run 12 times per year Intervals to be from 20-40 days • 25/50/75 Annual Test Run at 25% load for 30 minutes, followed by; Run at 50% load for 30 minutes, followed by; Run at 75% load for 60 minutes, for 2 hour continuous test • Three Year Test Minimum of 4 continuous hours Minimum 30% load --- OR --Must run at minimum required exhaust temperature per manufacturer The Joint Commission - Reporting Features • Individual screens and reports for each generator set in the system • Date and time stamps Test initiated Test completed Generator mechanical and electrical set points ATS parameters BAS Interface • Generator Output values recorded Voltage (phase to phase) Current (phase) Frequency Output, real KW, % of full load Exhaust temperature The Joint Commission - Test Report Screen Generator & Electrical Equipment Maintenance Kyle From Customer Support Representative (CSR) Generator & Electrical Equipment Maintenance • Inspections • Air Systems • Starting System • Generator Systems • Cooling System • Load Bank Testing • Fuel System • Electrical Equipment • Lubrication System • Power System Safety Generator & Electrical Equipment Maintenance • Inspections • Air Systems • Starting System • Generator Systems • Cooling System • Load Bank Testing • Fuel System • Electrical Equipment • Lubrication System • Power System Safety Inspections Daily Walk around inspection Weekly Perform weekly inspection Monthly Perform monthly inspection & test run Semi-Annual Fluid analysis Inspections Annual Inspection Oil change w/ new oil & fuel filters Load bank test (2-hours) Megohmeter test Fuel analysis Triennial Annual maintenance Adjust intake/exhaust valve lash Cooling system service Replace batteries Generator & Electrical Equipment Maintenance • Inspections • Air Systems • Starting System • Generator Systems • Cooling System • Load Bank Testing • Fuel System • Electrical Equipment • Lubrication System • Power System Safety Starting System Components • • • Battery charger Starter Batteries Starting System Typical Battery Installation: (Unsafe) • • • No acid containment No terminal protection against shorts Batteries need cleaning & charge rate checked Starting System Fiberglass Battery Enclosures: (Safe) • Protects posts • Contains spills • Come in multiple sizes Starting System Battery Preventative Maintenance • Recommended every 36 months • Complete check of electrical system Charger, cables & connections • Check engine starter & amperage under normal operating conditions • Remove & dispose of old lead acid batteries (per EPA standard) • Install new batteries Generator & Electrical Equipment Maintenance • Inspections • Air Systems • Starting System • Generator Systems • Cooling System • Load Bank Testing • Fuel System • Electrical Equipment • Lubrication System • Power System Safety Cooling System Components • • • • Coolant system drain valve Water Pump Flex Connector Low Coolant Sensor Signals Temp to ECM Sounds alarm below 70 Deg. • High water temperature sender Signals coolant temperature to gauge Cooling System Components • Coolant ball valve shut off • Watlow Block Heater Cooling System Components • Kim Hotstart Heater - Thermostatically controlled Cooling System Signs of Trouble • Rust/scale deposits and thermostat failure • Can be prevented by servicing cooling system every 36 months • Fumes or debris clog radiator fins reducing cooling capacity Cooling System Crankcase Ventilation Filtration System • Filters fumes • Protects Radiator fins Air cleaner pleats Environment • Replaceable Filter Change every 250 hours Cooling System Cooling System Preventative Maintenance • Recommended every 36 months • Drain and flush the cooling system and refill with high-grade antifreeze • Replace coolant hoses. including engine block heater hoses • Replace engine thermostats and test for proper operation • Test run engine generator • Dispose of all parts and fluids per EPA standards Generator & Electrical Equipment Maintenance • Inspections • Air Systems • Starting System • Generator Systems • Cooling System • Load Bank Testing • Fuel System • Electrical Equipment • Lubrication System • Power System Safety Fuel System Components Priming pump Fuel pressure gauge Canister spin on fuel filters Fuel system shut-off valves Fuel lines Transfer pumps Governor (linkage) Fuel System Inspection Base / day tank Transfer pumps Priming pump Drain water seperator Fuel lines Governor (linkage) Filters Fuel System Testing Options Basic Fuel Test Comprehensive Fuel Test Water API gravity Stability Distillation Cetane index Flash point Color Stability Pour point Water Microbial Generator & Electrical Equipment Maintenance • Inspections • Air Systems • Starting System • Generator Systems • Cooling System • Load Bank Testing • Fuel System • Electrical Equipment • Lubrication System • Power System Safety Lubrication System Preventative Maintenance Change oil Annually / 250 hours Replace oil filters Oil sample Wear/condensation Coolant/fuel Debris Generator & Electrical Equipment Maintenance • Inspections • Air Systems • Starting System • Generator Systems • Cooling System • Load Bank Testing • Fuel System • Electrical Equipment • Lubrication System • Power System Safety Air System Components Intake Air cleaners Piping Exhaust Exhaust flex, piping Silencers Manifold Turbo(s) Preventative Maintenance Inspect piping for cracks or leaks Inspect air filters for dirt and/or debris Inspect air restriction indicator Generator & Electrical Equipment Maintenance • Inspections • Air Systems • Starting System • Generator Systems • Cooling System • Load Bank Testing • Fuel System • Electrical Equipment • Lubrication System • Power System Safety Generator System Components Generator barrel Electrical connections Voltage regulator Control panel Inspection / Testing Megohmeter Winding Resistance Perform annually Visually inspect generator components and bearing(s) Generator & Electrical Equipment Maintenance • Inspections • Air Systems • Starting System • Generator Systems • Cooling System • Load Bank Testing • Fuel System • Electrical Equipment • Lubrication System • Power System Safety Load Bank Testing Recommended Annually Exercise the cooling system Reseat engine piston rings in the cylinders and liners Reduces blow-by and oil consumption Burn off carbon deposits in combustion chamber, injector nozzles, piston rings, turbocharger and exhaust system Dissipate any condensation on generator copper windings Generator & Electrical Equipment Maintenance • Inspections • Air Systems • Starting System • Generator Systems • Cooling System • Load Bank Testing • Fuel System • Electrical Equipment • Lubrication System • Power System Safety Electrical Equipment - Transfer Switch Monthly Test transfer switch with generator Annually Visual inspection Dust, dirt & moisture accumulation Look for arcing or hot spots Clean by vacuuming, dry cloth, or soft brush Testing/Inspection Voltage drop across main contacts Voltage drop across emergency contacts* Loose contacts (wires, terminals & relays)* Operation of timers, remote start contacts and phase monitor* * Testing requires load transfer Electrical Equipment - Transfer Switch Annually Continued… Infrared inspection for evidence of hot spots (thermal imaging) Check with your insurance company to see if annual thermal imaging will reduce your premium Electrical Equipment - Switchgear Annually Clean and inspect Lubricate all moving parts Inspect insulators Physical damage Contaminated surfaces Exercise active components Perform ground-resistance tests Determine accuracy of meters and calibrate Verify correct function of control transfer relays located in the switchgear Electrical Equipment - Circuit Breaker Annually Operation & alignment Lubricate moving parts Inspect Arc chutes & contacts Primary & secondary injection testing Verify the trip results are set to manufacturers recommended trip intervals Long-time, short-time, instantaneous & ground fault Electrical Equipment - Relays Annually Inspect Bearings & pivots Tightness of mounting hardware Disc, contact & spring clearances Spiral spring convolutions Test & Record Insulation-resistance test Pickup, dropout & time delays Generator & Electrical Equipment Maintenance • Inspections • Air Systems • Starting System • Generator Systems • Cooling System • Load Bank Testing • Fuel System • Electrical Equipment • Lubrication System • Power System Safety Power Systems Safety NFPA 70E – Personal Safety Power Systems Safety Lockout / Tagout Boxes OSHA approved Easy to use Protects employees Thank You Questions? References Web sites • Ziegler Power Systems site: www.zieglercat.com/power Links to CAT, spec sheets, white papers etc. www.CAT.com www.activepower.com Ziegler Power Systems 8050 State Highway 101 Shakopee, MN 55379 952.445.4292