ELECTRICAL INSTALLATION OF 63 KVA TRANSFORMER AT RRTC RUBBER BOARD HAHARA ASSAM SPECIFICATIONS AND SCHEDULE OF QUANTITIES ------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- --------------------------Item. Description Qty Unit Rate Amount No. Rs. Rs. ------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- -------------------------1 DRAWINGS 1.01 2.00 2.01 Preparation of drawings showing site plans, physical layouts line diagram of the equipment, switch boards, sectional details of switch gear, sub station, supplier structure, consumer structure, earthing arrangement etc as required by the Assam State Electricity Board/ Electrical Inspectorate for the technical approval of the installaton, arranging inspection, getting sanction for energisation, charging the transformer etc complete. NOTE:- Statutory fees remitted to Assam state Electricity Board/ Electrical Inspectorate will be reimbursed against production of fee receipt. REPAIRING OF THE EXISTING 11 KV STRUCTURE Supply and fixing / replacing the damaged air break switch (gang operated over head switch) full set including supply of all fixing acessories for the 63 KVA transformer. 1 Set 1 set 2.02 Supply and fixing /replacing the damaged 11 KV lightning arrestors 1 set 2.03 Supply and fixing/ replacing damaged drop out fuses ( D.O fuses). 1 set 2.04 Supply and fixing/ replacing damaged 11 KV insulators 3 Nos 2.05 Supply and fixing/ replacing damaged LT insulators 3 Nos 2.06 Supply and fixing/ replacing the damaged & rusted miscelleneous items like nuts, bolts,tie rod,interconnecting jumber and other connecting materials etc of the above substation structure. 1 LS 2.07 Painting of the 8 meter steel pole structure including supply of paint etc 2 Nos 2.08 Supply and fixing HT danger board 1 No 2.09 Supply and fixing LT danger board 1 No 3.00 Supply and providing electrical grade rubber mat of minimum 6 mm thickness 1 Sq m 4.00 Supply erection testing and commissioning of 63 KVA oil cooled aluminium wound Distribution transformer of reputed make as per relevant Indian standards with minimum 3 star rating including transportation, loading/ unloading in the existing foundation including supply of all acessories, transformer oil if required, connections etc complete and charging of the transformer. Note:- Specification of the transformer attached. EARTHING Design, fabrication, supply, and erection of earth pit, earth electrode, copper flat, copper wire etc. according to the standards of the Kerala Electrical Inspectrate and the relevant Indian Standards. Note: The quantites shown are only approximate and work has to be done as per actual site requirement and as per the electrical electrical inspectorate standard Providing Earth pit with 40 mm dia. GI pipe electrode 3.0 m long including earth work excavation, filling with charcol and salt, providing funnel, masonry chamber and plastering, cover plate etc. complete incuding supply of all items. 1 set 5.02 -DO- Earth pit with G.I plate earth electrode 1200X 1200 X12 mm size and total length not less than 3 meters including earth work excavation, erection of plate electrode, filling the plate sides with salt and charcol, providing funnel, GI pipe, masonry chamber and plastering, cover plate etc. Complete as per standard. 2 Set 6 Supply and laying/fixing of earthing conductor of copper flats/ wires of following sizes including necessary benches, copper sockets, drilling holes, tinning, fixing , jointing etc. complete as per approved scheme laid in trenches / walls with finishing plastering whereever required as directed. 6.01 Supply and laying Copper flat of size 25 X 3 mm 1 M 6.02 Supply and laying Copper wire SWG 6 2 M 6.03 Supply and laying Copper wire SWG 8 1 M 6.04 Supply and laying Copper wire SWG 10 1 M 6.05 Supply and laying Copper wire SWG 12 1 M 7.01 6.02 Supply and laying G.I earthing flat of size 25 X 6 mm Supply and laying G.I flat of size 25 X 3 mm 5 5.01 1 Set 80 M 10 M 7.03 7.04 7.05 7.08 7.09 Supply and laying Supply and laying Supply and laying Supply and laying Supply and laying G.I Earth wire SWG 4 G.I Earth wire SWG 6 G.I Earthing conductor SWG 8 G.I Earth wire SWG 10 G.I Earth wire SWG 12 TOTAL I/We hereby tender for the execution of works refered to above in the aforesaid documents upon the terms and conditions contained or referred to therein and in accordance in all respects with the specifications, designs, drawings and other relevant details at the rates quoted by me/us. Rate quoted is inclusive of all taxes and duties inlcluding applicable service tax Signature of the Tenderer Date ......... Hahara transformer 30 30 1 1 1 M M M M M See Factory Layout, Site Plan and Electrical Schematic 18.01 Supply and erection of GI Street light pole as per attached drawing inluding earth work escavation, plastering etc complete with the following acessories. (a) 3 inch size class B , GI pipe 3 M long for street light pole. (b) 40 mm size class B , GI pipe of approximate 1.3 M long on each street light pole for cable connection from bottom to PVC junction box. (c) Suitable PVC junction box of approximate size 200 X 150 X 100 mm weather proof on the street light pole with connector strip / terminals and 6 amp SP MCB of reputed make. 18.02 -DO- Supply and erection of GI Street light pole 3 M long with all acessories of above item. 8 Nos 4000 32000 4 Nos 3500 14000 19 LIGHTING 19.01 Supply of 1x40 Watts ordinary fluorescent tube light fittings. 40 Nos 350 14000 19.02 - DO - 1 x 40 W box type fiting PhilipsTMC 55/140 or uquavalent make 35 Nos 550 19250 19.03 - DO - 2 x 40 W box type fitting. 30 Nos 700 21000 19.04 Fixing of above 1x40 Watts/ 2x 40 Watts fluorescent tube light fittings to walls or to underside of roof or to bottom members of roof truss as directed including necessary down rods,ball and socket, bracket and fixing accessories,3 core flexible copper cable etc complete. 105 Nos 150 15750 19.05 Supply & fixing 60 Watts angle battern fittings complete with bulb. 8 Nos 100 800 19.06 Supply and fixing 60 Watts bulk head fittings complete with bulbs etc. including all fixing accessories. 10 Nos 300 3000 19.07 Supply and fixing 150 W High bay metal halide fittings of reputed make in the factory complete with lamp and all fixing acessories and should be fixed at the required height as per the machine lay out/ factory floor requirement. 30 Nos 4500 135000 19.08 Supply of 2x11 Watts CFL Street light fitting BJSLF 211 Bajaj with 2 Nos of 11 Watts CFL Lamp and anodised aluminium reflector and glass acrylic cover of Bajaj make or equavalent reputed. 2 Nos 1000 2000 19.09 Supply of 2x40 Watts fluorescent street light fittings with tube 4 Nos 1500 6000 19.10 Supply of street light fitting 1X 40 Watts Crompton Greaves or equavalent reputed with tube. 2 Nos 1500 3000 19.11 Supply of 70 W HPSV light fitting Cema make ASR 70 or equavalent reputed make including lamps. 1 Nos 2600 2600 19.12 Supply of CFL street light fitting of good finish with brass bulb holder and 18 Watts CF Lamp of reputed make and anodised aluminium reflector etc complete. 2 Nos 800 1600 19.13 Supply of 125 W HPMV lamp fittings type Crompton MSP 121 H or equivalent Philips 4 Nos 4000 16000 17 Nos 600 10200 30 M 30 M 2 Nos 20 15 100 600 450 200 20 Fixing of above light fittings of item 19.08 to 19.13 including supply of all acessories and suitable size G.I pipe for fixing the light fittings on street light poles / building walls and interconnection from street light pole junction box/ building ceiling rose using flexible copper cable. 21.01 Supply and laying 2 X 4 sq mm weather proof aluminium wire. 21.02 Supply and laying 2 X 2.5 sq mm weather proof aluminium wire. 22 Supply and fixing calling bell of reputed make including all fixing accessories complete. 23.01 Supply and fixing ceiling fans, 1200 mm sweep, Make Crompton Greaves/Rallis/Polar, including all fixing accessories, regulator etc complete. 2 Nos 1200 2400 23.02 4 Nos 100 400 100 3000 7000 7000 Fixing of 1200 MM ceiling fan (fan will be supplied ) 24 Supply and fixing 5A, 3pin receptacle plug socket with piano type control switch, Make Anchor or equavalent on lighting switch board. 25 Fabrication, Supply, Erection, Testing and Commissioning of TPN Sub Fuse Board, 32A X 8 way in dust and vermin proof sheet steel enclosure with 100 A SFU with 63 A HRC fuse incommer and 32 A fuse bases and fuselinks of adequate capacity complete with cable entry box, door interlock and internnections complete. 30 Nos. 1 Set 26 SAFETY ITEMS 26.01 Supply and laying 6 mm thick electrical grade rubber mats in front of switch boards. 18 M2 1000 18000 26.02 Supply and fixing LT metal danger boards. 1 Nos 100 100 26.03 Supply and fixing HT metal danger boards. 1 Nos. 100 100 26.04 Supply and fixing LT sticker danger boards. 20 Nos 50 1000 26.05 Supply and fixing LT fire extinguishers 5 Kg as per regulations. (Dry chemical powder type). 6 Nos 3000 18000 26.06 Supply and fixing 2 Nos fire bucket with MS stand as per std 4 Sets 950 3800 26.07 Supply and fixing statutory display boards like artificial respiration charts in photo framed display 1 No 400 400 26.08 Supply of 4.5 Kg Carbon dioxidefire extinguisher with ISI mark. 6 Nos 2500 15000 26.09 Supply of electrical grade rubber gloves. 26.3 Supply and fixing 9 litre capacity fire bucket with river sand. 2 Sets 6 Nos 600 750 1200 4500 27 Wiring of light points of factory building for group control (4 to 6 points as directed) using PVC insulated copper cable 1.5 sq.mm. of Finolex make and 16 SWG copper earthing conductor in ISI mark rigid PVC conduits complete with piano type control switches in sheet steel enclourse from Sub MCB Distribution Board upto and including ceiling rose. Note:(4 to 6 Nos of light in single control considered as one group point) 35 points 650 22750 28 Wiring of light and fan points of factory building/ office for independant control using PVC insulated copper cable of 1.0 sq.mm. of Finolex make and 16 SWG copper earthing conductor in ISI Marked rigid PVC conduits with independent switches in sheet steel enclosure from lighting Sub MCB DB upto and including ceiling rose. 20 Nos 350 7000 1 Nos 500 500 60 Nos 900 54000 4 Nos 100 400 45 112500 29.01 Supply and fixing of remote Locable Stop push button station in dust and vermin proof sheet steel enclosure,including all fixing accessories complete. 29.02 Supply and fixing of a remote start & stop locable push button station in dust and vermin proof sheet steel enclosure including all fixing accessories complete. 29.03 Fixing of the dismantled push button stations. 30 Fabrication, supply and erection of steel supports made 2500 Kg out of MS angles and flats as supports for starters,switches push button stations, capacitors and cables as directed including one coat of metal primer after fabrication and two or more coats of smoke grey enamel paint after erection. 31 Supply and fixing 20 A 3 pin industrial power socket and plug with 20 A MCB control in sheet steel enclosure with accessories complete. 8 Sets 600 4800 32 Supply and fixing 15 A 3 pin power socket and plug with 15 A piano type control switch (Anchor make or equivalent) on MS boxes including all fixing accessories complete. 10 Nos 250 2500 33.01 Supply and laying PVC insulated single core 2.5 sq mm copper cable make Finolex TWO runs with 14SWG copper earthing conductor in ISI marked rigid PVC pipes of suitable size for cicuit mains and for connecting 20 A / 15 A plug socket. 450 RM 90 40500 Note. For payment, one run will be measured. 33.02 - DO - THREE RUNS 1 RM 100 100 33.03 - DO - FOUR RUNS 150 RM 130 19500 33.04 - DO - FIVE RUNS 1 RM 140 140 33.05 - DO - SIX RUNS 60 RM 150 9000 33.06 - DO - EIGHT RUNS 60 RM 180 10800 60 RM 120 7200 34.01 Supply and laying PVC insulated single core 4.0 sq mm copper cable make Finolex TWO runs with 14SWG copper earthing conductor in ISI marked rigid PVC pipes of suitable size for connecting 32 Amp D P switvh/ industrial plug socket. Note. For payment, one run will be measured. 34.02 - DO - THREE RUNS 1 RM 135 135 34.03 - DO - FOUR RUNS 40 RM 140 5600 34.04 - DO - SIX RUNS 15 RM 160 2400 35.01 Earth work excavation for cable trenches in all classes of soil including backfilling. 140 M3 200 28000 35.02 Laying bricks in cable trenches after laying of cables and covering with 150 mm thick layer fine soil. 130 M2 220 28600 400 3200 300 9000 35.03 Supply outdoor LT cable markers and fixing them in concrete. 36.01 Supply and laying class B GI Pipe at road crossing, wall 8 Nos 30 M crossing etc. as directed - size 63 mm dia. 36.02 - DO - 50 mm . dia 6 M 280 1680 36.03 - DO - 40 mm . dia 30 M 270 8100 36.04 - DO - 25 mm . dia 6 M 250 1500 37.01 Supply and fixing suitable terminal boxes in dust and vermin proof sheet steel enclosure for motors from 1 HP upto and including 5 HP. 4 No 200 800 37.02 Supply and fixing suitable terminal boxes in dust and vermin proof sheet steel enclosure for motors from 7.5HP upto and including 15 HP. 1 No 350 350 37.03 Supply and fixing suitable terminal boxes in dust and vermin proof sheet steel enclosure for motors from 20 HP upto and including 30 HP. 2 Nos. 500 1000 37.04 Supply and fixing suitable terminal boxes for motors from 40 hp including 60 hp. 4 Nos. 900 3600 140 560 38 supply and fixing Electronic fan regulator 300/ 400 Watts for the 1200 mm 4 sweep ceiling fan. 39.01 Supply and fixing 63 A three phase ELCB of L&T Hagger/MDS/Dattar/GEC or equavalent reputed make in the MCB DB and interconnections inluding all fixing acessories. 1 Set 2500 2500 39.02 2 Sets 2000 4000 1600 M 50 80000 - DO - Supply and fixing 32 A three phase ELCB 40.01 Supply and laying of 32 mm PVC pipe(10 kg/cm2) at 60cm below the factory floor for drawing under ground cable. 40.02 -DO- Supply and laying 50 mm PVC pipe(10 kg/cm2) 380 M 65 24700 40.03 -DO- Supply and laying 75 mm PVC pipe (6 Kg/cm2) 300 M 110 33000 40.04 40.05 -DO- Supply and laying 100 mm PVC pipe (4 kg/cm2) -DO- Supply and laying 110 mm PVC pipe (4 kg/cm2) 500 M 60 M 150 170 75000 10200 41 CAPACITORS 1 1 1 1 9000 8000 4000 2000 9000 8000 4000 2000 Supply and fixing suitable capacitors for individual motors with all fixing acessories and interconnections complete with motors/ motor starters. 41.01 41.02 41.03 41.04 25 KVAR 20KVAR 10 KVAR 5 KVAR No No No No 41.05 2 KVAR 41.06 1 KVAR 1 No 1 No 800 400 800 400 42 APFC CAPACITOR PANEL 42.01 Supply of 125 KVAR (125+25)centralized power factor panel with L&T make MD-XL type low watt loss capacitors in completely factory assembled condition with components of L&T, Crompton Greaves or equavalent reputed make incorporating the following acessories. 1. Incomer L&T make 250A MCCB 2. Current limiting contactor specially designed for capacitor switching, GE or equavalent make. 3. HRC fuses for rack protection 4. Discharge resistors 5. Micro processor based APFC relay with programmable switching programmes- 8 stage. ( Make- Belook or equavalent reputed) 6. Provision for top and bottom cable entry. 7. Cooling fans. 8. Low loss MD-XL capacitors of L&T make in double layer configuration in impregenated oil sealed container. This shall be in 6 to 8 steps. 25-20–20 –20-15-10 -10--5 ratings. 9. Safety devices, controls etc pre wired and tested. 10. Powder coated cabinet using 14 swg sheet steel 11. Protection and cut off against leading PF 12. Provision for manual operation. NOTE:At present 125 KVAR capacitor only to be provided for automatic pf correction. But contactors , fuses, wiring etc to be done for 150 KVAR now itself. 25 KVAR capacitor will be provided by society in future if required. 1 Set 2E+05 160000 42.02 Supply and fixing additional 20 KVAR L&T make MD-XL capacitor in the above APFC panel and directly connected for the no load compensation of the 400 KVA transformer. 1 Set 16500 16500 42.03 Supply and fixing 63 Amp switch L&T make FN 63 with 50 A HRC fuses 1 No in the above APFC panel for the 20 kvar capacitor for the transformer no load compensation and connections etc complete. 1650 1650 42.04 Erection of the 125 KVAR APFC panel and inteconnections , minor civil works/ grouting etc complete. 2000 2000 1 Set 43.00 Supply and fixing MS box 6 X 4 inch size and providing connector strip and covering with hylam sheet. 2 Nos 75 150 44.01 Supply and laying 1 inch size PVC pipe. 44.02 Chipping of floor/ wall for laying 1 inch size PVC pipe and replastering. 6 M 6 M 15 30 90 180 45 3 Sets 200 600 10 M2 2000 20000 10 M2 500 5000 Supply and fixing 5A, 3pin receptacle plug socket 3 Nos with 3 Nos piano type control switch, Make Anchor or equavalent on MS box. 46.01 Supply of 6 mm thick chequared plate with 2 coats of primer and one coat of grey paint. 46.02 Laying of 6 mm thick chequared plate over the masonary duct including cutting, grinding and providing flush type hooks to pull out/ lift the plate easily. (For angle iron supports rate will be given as per item No.30) 2.10 Supply and fixing voltmeter with selector switch. 2 Sets 1000 2000 2.11 Supply and fixing suitable FASD starter contactors, O/L relays, push buttons etc of L&T make suitable for 50 Hp motor and interconnections etc complete in the above 125 A feeder. 1 Sets 20000 20000 2.12 -DO- Supply and fixing suitable FASD starter contactors, etc suitable for 40 Hp motor and interconnections etc complete in the above 125/ 100 A feeder. 2 Sets 19000 38000 2.13 -DO- suitable for 30 HP in the 100A feeder. 2 Sets 18000 36000 2.14 -DO- suitable for 60 HP in the 125A feeder. 1 Sets 26350 26350 2.15 -DO- suitable for 25 HP in the 100A/ 63A feeder. 2 Sets 17000 34000 2.16 -DO- suitable for 20 HP in the 63A feeder. 2 Sets 14000 28000 2.17 -DO- suitable for 15 HP in the 63A feeder. 2 Sets 12000 24000 2.18 -DO- suitable for 10 HP in the 63A feeder. 1 Sets 10000 10000 2.19 -DO- suitable FASD starter for 7.5 HP in the 63A/ 32A feeder. 1 Sets 7000 7000 2.20 2.21 2.22 -DO- suitable D.O.L starter for 7.5 HP in the 63A/ 32A feeder. -DO- suitable D.O.L starter for 5 HP in the 63A/ 32A feeder. -DO- suitable D.O.L starter for 3/2/1 HP in the 32A feeder. 1 Sets 1 Sets 1 Sets 5000 3500 2500 5000 3500 2500 2.23 Supply & fixing variable speed D.O.L starters for 5/3/1.5 Hp motors 8 Sets 4000 32000 3.00 3.01 MCC -3 Fabricate, supply,erection testing and commissioning of MCC 3 cubicle type, floor mounting with 40X6 mm aluminium busbar for phases and neutral with provision for fixing following acessories, interconnections, earthing etc complete as per drawing. Note:Panel MCC3 should be fabricated with space for providing suitable FASD / D.O.Lstarter contactors, O/L relays, push buttons etc in each feeder as per feeder ratings. 1 set 20000 20000 3.02 Supply & fixing 125 A TPN switch L&T make FN 125 incommer. 1 No 6700 6700 3.03 Supply and fixing 100 A HRC fuse for the above switch. 3 Nos 300 900 3.04 Supply and fixing 63 A TPN switch L&T make FN 63 with 50 /32A HRC fuse as outgoings. 2 Nos 3700 7400 3.05 Supply and fixing 100 A TPN switch L&T make FN 100 with 63A HRC fuse as outgoings. 1 Nos 4800 4800 3.05 Supply and fixing 32 A TPN switch L&T make FN 32 with 25 /20/16 A HRC fuse as outgoins. 10 Nos 3000 30000 3.06 Supply and fixing suitable FASD starter contactors, etc suitable for 15 Hp motor and interconnections etc complete in the above 63 A feeder. 1 Sets 12000 12000 3.07 -DO- suitable FASD starter for 7.5 HP in the 63A/ 32A feeder. 1 Sets 7000 7000 3.08 -DO- suitable D.O.L starter for 5 HP/ 3/ 2HP in the 32A feeder. 9 Sets 3500 31500 3.09 Supply and fixing RYB indications. 1 Set 700 700 3.10 Supply and fixing voltmeter with selector switch. 1 Set 1000 1000 4 4.01 MODIFICATION OF THE EXISTING MSB Modification of the existing MSB by extending one side with 2X 50X10 mm aluminium busbar for phases and 1 X 50 X 10 mm 1 set 27000 27000 Al. busbar for neutral for fixing following additional switches/ acessories, interconnections, earthing etc complete. (Existing MSB size:- Length- 3.85m, height-2.2m, width-0.50m ) 4.02 Supply and fixing 250 A TPN switch L&T make FN 250 with 200/ 160 A HRC fuse as outgoings. 3 Sets 9700 29100 4.03 Supply and fixing 250 A four pole MCCB of L&T make. 1 Sets 9900 9900 4.04 Supply and fixing 250 A four pole MCCB of L&T make. 1 Sets 9900 9900 4.05 Erection of the above modified MSB and grouting etc complete. (For angle iron supports /channels provided on the floor rate will be given as per item No.30) 1 Sets 1000 1000 5 5.01 MODIFICATION OF THE EXISTING SUB SWITCH BOARDS Modification of the existing SSB1 of 1.75m X 1.6m X 0.3m size by extending the cable alley portion at both ends of the switch board for fixing the seperately mounted FASD / D.O.L starter contactors, O/L relays, push buttons to the respective feeders shown in the drawing. 1 set 18000 18000 5.02 -DO- Modification of the existing SSB 2 of 1.6m X 1.6m X 0.3m size with feeders shown in the drawing for fixing the starter components. -DO- Modification of the existing SSB 6 of 1.0m X 1.45m X 0.25m size with feeders shown in the drawing for fixing the starter components. -DO- Modification of the existing SSB 7 of 1.5m X 1.5m X 0.3m size with feeders shown in the drawing for fixing the starter components. 1 set 16000 16000 1 set 12000 12000 1 set 14000 14000 5.05 Dismantling of existing FASD starter contactors, O/L relays of 40/ 30/25 HP motors from the existing starter panels and fixing in the above modified switch boards and interconnections etc complete with respective feeders. 8 Sets 1500 12000 5.06 -DO- Dismantling and fixing starter for 20/15/ 10/7.5 HP. motor in the modified SSB's. 6 Sets 1000 6000 5.07 -DO- Dismantling and fixing D.O.L starter for 5/3/2/1 Hp motor in the modified SSB's. 6 Sets 700 4200 6.00 Erection of the old / modified Sub Switch Boards of approximate size 1.6 m X 1.5 m X 0.3 M in the new switch board room and grouting etc complete. Note:The switch boards, FASD/ D.O.L starters, DB's, cables etc are dismantled and kept in the nearby genset room at a distance of approximate 10 meters. 9 sets 450 4050 7.00 Erection of the old 8 way/ 6 way/ 4 way MCB DB Three phase/ 3 sets 250 750 5.03 5.04 single phase wall mounting type. 8.00 Erection of the dismantled Fuse DB 8 way/ 6 way/ 4 way on the wall/ floor of the new factory building and grouting etc complete. 3 sets 300 900 9.01 Fixing of the old FASD starter in ss enclosures of 7.5/ 15 HP motors and connections. (For steel supports if required separate rate will be given as per item No. 30 ) -DO- Erection of the old FASD starter panels for 20/30 HP in the new switch board room. 2 sets 125 250 2 sets 250 500 9.03 -DO- Erection of the old FASD starter panels for 40/50 HP . 2 sets 250 500 9.04 -DO- Erection of the old Auto transformer panels for 60 HP motor the new switch board room. 1 sets 300 300 9.05 Fixing of the D.O.L starters for 5/3/2 HP motors and connections. 2 sets 50 100 9.02 10 MOTOR STARTERS 10.01 Supply & fixing of FASD starter in dust and vermin proof 1 SET sheet steel enclosure make L&T with suitable over load relay, isolator, single phasing preventor, cable entry boxes and interconnections with isolator using copper cables etc for 60 HP motors - complete. 40000 40000 10.02 Supply & fixing of DOL starter in dust and vermin proof sheet steel enclosure make L&T type MK1 with over load relay, isolator,cable entry boxes and interconnections with isolator using copper cables for 5 HP motor - complete. 1 Nos 3500 3500 10.03 Supply & fixing of DOL starter in dust and vermin proof sheet steel enclosure make L&T type MK1 with over load relay, isolator, cable entry boxes and interconnections with isolator using copper cables for 3/2/1 HP motors - complete. 1 Nos 2500 2500 SWITCHES AND ISOLATORS Supply and fixing switches/SFUs of the following rates. 11.01 63 A TPN fuse switch in S/S enclosure. 11.02 32 A TPN fuse switch in S/S enclosure. 11.03 32 A DP switch in M/S enclosure. 1 No 1 No 10 Nos 2000 1800 300 2000 1800 3000 11.04 Fixing of the old 63 /32A fuse switch in S/S enclosure. 1 No 2000 2000 12 3 sets 6000 18000 1 sets 6000 6000 11 Supply, Erection, Testing and Commissioning of TPN MCB DB, 8 way for lighting ,of reputed mke in dust and vermin proof sheet steel enclosure with 32 A 4 pole ELCB cum MCB as incomer with 24 SP MCB outlet (6A/10A/16A) with cable entry box,door interlock and interconnections etc complete. 13.00 MCB DB POWER VERTICAL 13.01 Supply, Erection, Testing and Commissioning of vertical TPN MCB DB, 12 way of reputed mke in dust and vermin proof sheet steel enclosure with door interlock and following acessories and interconnections etc complete. 13.02 13.03 13.04 13.05 13.06 13.07 Supply and fixing 4 pole 100 A MCCB set at 63A as incommer. Supply and fixing 63 A ELCB Four pole.. Supply and fixing 32 A / 20/16A TP MCB outgoings. Supply and fixing 32 A TP MCCB outgoings. Supply and fixing 32 A / 25A DP MCB outgoings. Supply and fixing 10/16/ 25A SP MCB outgoings. 14 LT POWER CABLES 1 1 2 1 2 24 Nos Nos Nos Nos Nos Nos 4000 4000 900 2000 400 150 4000 4000 1800 2000 800 3600 1 60 1 62 RM RM RM RM 1000 900 800 30 1000 54000 800 1860 Supply and laying 650/1100 V armoured PVC aluminium under ground cables of (make.Universal/ Incab/Fort Gloster/ Torrent/ CCI/Tropodur/NICCO of the following sizes & laying through PVC pipes provided 60 cm below the factory floor, in built up trenches, steel members of roof, walls,floors, including fixing identification tags, chipping of floors or walls and all fixing accessories and materials etc. as directed complete. Note. 1. The quantity shown is only approximate and the successful tenderer should measure the lengths at site for procurement. 2. Use solid core cables only upto 10 sq.mm. 14.01 14.02 14.03 14.04 3 1/2 X 400 Sq.mm Supply 3 1/2 x 300 Sq.mm Supply 3 1/2 x 240 Sq.mm Supply 3 1/2 x 400/ 300 / 240 Sq.mm Laying 14.05 14.06 3 1/2 x 185 Sq.mm Supply 3 1/2 x 185 Sq.mm Laying 400 RM 540 RM 650 25 260000 13500 14.07 14.08 14.09 3 1/2 x 150 Sq.mm supply 3 1/2 x 120 Sq.mm supply 3 1/2 x 120 Sq.mm Laying 1 RM 1 RM 2 RM 500 430 25 500 430 50 14.1 14.12 14.13 3 1/2 x 95 Sq.mm supply 3 x 95 Sq.mm supply 3 1/2 x 95 / 3 x 95 Sq.mm Laying 100 RM 100 RM 200 RM 300 270 20 30000 27000 4000 14.14 14.15 3 1/2 x 70 Sq.mm supply 3 1/2 x 70 Sq.mm Laying 120 RM 120 RM 250 20 30000 2400 14.16 14.17 3 x 70 Sq.mm supply 3 x 70 Sq.mm Laying 180 RM 180 RM 230 20 41400 3600 14.18 14.19 14.2 3 1/2 x 50 Sq.mm supply 3 x 50 Sq.mm supply 3 x 50 Sq.mm Laying 1 RM 60 RM 61 RM 200 190 20 200 11400 1220 14.21 14.22 3 1/2 x 35 Sq.mm supply 3 1/2 x 35 Sq.mm Laying 55 RM 55 RM 180 20 9900 1100 14.23 14.24 3 x 35 Sq.mm supply 3 x 35 Sq.mm Laying 200 RM 200 RM 175 20 35000 4000 14.25 14.26 3 1/2 x 25 Sq.mm Supply 3 1/2 x 25 Sq.mm Laying 200 RM 200 RM 170 20 34000 4000 14.27 14.28 3 x 25 Sq.mm Supply 3 x 25 Sq.mm Laying 700 RM 750 RM 165 20 115500 15000 14.29 14.3 4 x 16 Sq.mm 4 x 16 Sq.mm - Supply - Laying 20 RM 20 RM 150 20 3000 400 14.31 14.32 3 x 16 Sq.mm 3 x 16 Sq.mm - Supply - Laying 150 RM 180 RM 140 20 21000 3600 14.33 14.34 4 x 10 Sq.mm 4 x 10 Sq.mm - Supply - Laying 750 RM 790 RM 100 20 75000 15800 14.35 14.36 3 x 10 Sq.mm 3 x 10 Sq.mm - Supply - Laying 210 RM 210 RM 90 20 18900 4200 14.37 14.38 4 x 6 Sq.mm 4 x 6 Sq.mm - Supply - Laying 50 RM 50 RM 85 20 4250 1000 14.39 14.4 3 x 6 Sq.mm 3 x 6 Sq.mm - Supply - Laying 450 RM 484 RM 75 15 33750 7260 14.41 14.42 14.43 4 x 4 Sq.mm 3 x 4 Sq.mm 3 x 4 Sq.mm - Supply - Supply - Laying 1 RM 1400 RM 1500 RM 70 65 15 70 91000 22500 15 Supply & laying 650/1100 V armoured PVC copper under ground control cables of (make.Universal/CCI /Fort Gloster/ Torrent/ Incab/Tropodur/NICCO) of the following sizes and laying through PVC pipes provided 60 cm below the factory floor, in built up trenches, steel members of roof, walls,floors, including fixing identification tags, chipping of floors or walls and all fixing accessories and materials etc. as directed - complete. Note: The quantity shown is only approximate and the successful tenderer should measure the lengths at site for procurement. 15.01 15.02 15.03 12 X 1.5 Sq.mm - Supply 6 X 1.5 Sq.mm - Supply 12 X 1.5 / 6 X 1.5 Sq.mm - Laying 150 RM 1 RM 151 RM 200 150 15 30000 150 2265 15.04 15.05 4 X 1.5 Sq.mm - Supply 4 X 1.5 Sq.mm - Laying 1900 RM 1900 RM 100 15 190000 28500 15.06 15.07 3 X 1.5 Sq.mm - Supply 3 X 1.5 Sq.mm - Laying 1000 RM 1000 RM 80 15 80000 15000 15.08 15.09 15.10 2 X 2.5 Sq.mm - Supply 3 X 2.5 Sq.mm - Supply 3X 2.5/ 2 x 2.5 Sq.mm - Laying 300 RM 10 RM 310 RM 85 95 15 25500 950 4650 15.11 15.12 16 2 X 1.5 Sq.mm - Supply 2x 1.5 Sq.mm - Laying 2 RM 2 RM 70 15 140 30 CABLE GLANDING AND TERMINATION Glanding and termination of the following sizes of power and control cables including supply of glands, lugs, and all materials tools and accessories with crimping etc.complete. 16.01 3 1/2 X 400 / 3 1/2 x 300 Sq.mm Aluminium 2 Nos 900 1800 16.02 3 1/2 X 240 Sq.mm Aluminium 1 Nos 800 800 16.03 3 1/2 X 185 Sq.mm Aluminium 22 Nos. 500 11000 16.04 3 X 150 / 120 Sq.mm Aluminium 1 Nos. 300 300 16.05 3 1/2 X 95 Sq.mm Aluminium 2 Nos. 150 300 16 Nos 140 2240 16.06 3X70 or 3 1/2 X 70 Sq.mm Aluminium 16.07 3x50 or 3 1/2 X 50 Sq.mm Aluminium 4 Nos 140 560 16.08 3x35 or 3 1/2 X 35 Sq.mm Aluminium 10 Nos 140 1400 16.09 3x25 or 3 1/2 X 25 Sq.mm Aluminium 44 Nos. 130 5720 16.1 4 X 16 or 3 X 16 Sq.mm Aluminium 12 Nos 120 1440 16.11 4 X 10 or 3 X 10 Sq.mm Aluminium 38 Nos. 110 4180 16.12 3x6 or 4 X 6 Sq.mm Aluminium 50 Nos 100 5000 16.13 3x4 or 4 X 4 Sq.mm Aluminium 80 Nos 60 4800 16.14 12 X 1.5 Sq.mm Copper 6 Nos 60 360 16.15 4 X 1.5 Sq.mm Copper 18 Nos. 60 1080 16.16 3 X 1.5 Sq.mm Copper 124 Nos. 60 7440 16.17 2 X 2.5 Sq.mm Copper 6 Nos. 60 360 2 Sets 7000 -DO- Earth pit with copper plate electrode 600 X 600 X 3 mm size including supply of all items complete. excavation, erection of plate electrode, filling the plate sides with salt and charcol, providing funnel, GI pipe, masonry chamber and plastering, CI cover plate etc.complete. 14000 -------------------Amount ------------------- #REF! #REF! #REF! #REF! #REF! #REF! #REF! #REF! #REF! #REF! #REF!