www.lsis.biz North American Edition Super Solution For Nuclear power plant Low voltage circuit breakers Susol Low voltage circuit breakers Low voltage circuit breakers Super Solution Contents Overview A-1 Main characteristics A-2 Accessories A-3 Technical information A-4 Mounting & connection A-5 Characteristics curves A-6 Dimensions A-7 >>> UL MCCB Beyond the limits... The circuit breaker will supply more stable, reliable, upgraded systems to customer with high breaking capacity. Susol UL TD and TS series Molded Case Circuit Breakers Susol MCCB ■Simplified product range ■Standards ■Various trip units �AF: 125AF, 250AF, 400AF, 800AF �Ampere Range: 15A ~ 800A �World class with UL489 �FTU: Fixed thermal & Magnetic unit �ATU: Adjustable thermal & Magnetic unit �FMU: Adjustable thermal, Fixed magnetic unit �MTU: Magnetic only trip unit (1.6~220A) ■High performance �Ultimate breaking capacity (kA rms) Icu: Max 65kA @480VAC ■Variable accessories �Electrical auxiliaries �Extended rotary handle �Flange handle �Locking devices MCCB 8 Models in 4 Frames Susol TD and TS circuit breakers are rated from 15 through 800 amperes and are available in four frame sizes. UL 489 Listed Circuit Breakers Family TD/ TS 65kA at 480VAC / 8 models in 4 frames TD125U (Q) In 15~125A Icu: 35kA(NU), 65kA(HU) 90(W) x 164(H) x 86mm(D) Enhanced high performance N Type - 35kA, H Type - 65kA Maximum breaking capacity for all Ampere Frame is 65kA at 480VAC. TS800HU TS800NU Rated current (A) 65kA 35kA TS400HU TS250HU TD125HU TS400NU TS250NU 800A TD125NU 400A 250A 125A 65kA 35kA High available fault current at 480V (kA) TS800U (Q) TS400U (Q) TS250U (Q) In 150~250A Icu: 35kA(NU), 65kA(HU) 105(W) x 178(H) x 86mm(D) In 300~400A Icu: 35kA(NU), 65kA(HU) 140(W) x 292(H) x 110mm(D) In 500~800A Icu: 35kA(NU), 65kA(HU) 210(W) x 428(H) x 135mm(D) TD & TS MCCB Index A-1. Overview Range of Susol products A-1-1 Overview of TD/TS family A-1-3 Marking and configuration A-1-5 Overview of trip units A-1-7 Switching mechanism A-1-8 For Nuclear power plant Overview of TD/TS family TD series TD125U (Q) Frame size 125 [AF] Rated current In [A] 15, 20, 30, 40, 50, 60, 80, 100, 125 2, 3 No. of Poles Rated operational voltage, Ue AC UL interrupting rating AC 50/60Hz 600 [V] [kA] NU HU 120V 50 100 240 V 50 100 480 V 35 65 600 V 10 14 UL 489 Reference standard Trip unit (Thermal-Magnetic) ●Fixed-thermal, Fixed-magnetic FTU ● ●Adjustable-thermal, Fixed-magnetic FMU ● ●Adjustable-thermal, Adjustable-magnetic (3Pole) ATU - ●Magnetic only MTU - Variable accessories AX ● AL ● SHT ● UVT ● Extended rotary handle ● Flange handle ● Locking devices (Removable, Fixed) ● Mechanical interlock device ● Mechanical life [operations] Electrical life @600V AC [operations] Weight 3-Pole Basic dimension, W×H×D 3-Pole [lbs/kg] [inch/mm] This product is designed for Nuclear power plant. You can identify by “(Q)” sticker on the product, however, the nameplate does NOT contain any information to identify. A-1-1 4,000 4,000 2.65/1.2 3.54×6.46×3.39/90×164×86 For Nuclear power plant Overview of TD/TS family TS series TS250U (Q) TS400U (Q) TS800U (Q) 250 400 800 150, 160, 175, 200, 225, 250 300, 350, 400 500, 600, 700, 800 2, 3 2, 3 2, 3 600 600 600 NU HU NU HU NU HU 50 100 50 100 50 100 35 65 35 65 35 65 10 18 14 20 18 25 UL 489 UL 489 UL 489 ● ● ● ● ● ● ● (3∅) ● (3∅) ● (3∅) ● - - ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● 5,000 5,000 3,000 1,000 1,000 500 4.19/1.9 12.57/5.7 29.98/13.6 4.13×7.01×3.39/105×178×86 5.51×11.50×4.33/140×292×110 8.27×16.85×5.31/210×428×135 A-1-2 For Nuclear power plant Marking and configuration Rated frequency Standard Manufacturer UL listed number Terminal Information A-1-3 For Nuclear power plant Marking and configuration Model (Rating and breaking capacity) �TS: Series �250: Max. Ampere rating �NU: Normal (Standard) �HU: High Standardized characteristics: �Ui: Rated insulation voltage �Uimp: Impulse withstand voltage �Ue: Rated operational voltage 125AF 250AF 400AF 800AF NU TD125NU (Q) TS250NU (Q) TS400NU (Q) TS800NU (Q) HU TD125HU (Q) TS250HU (Q) TS400HU (Q) TS800HU (Q) NU 50kA 50kA 50kA 50kA HU 100kA 100kA 100kA 100kA 125AF 250AF 400AF 800AF Interrupt Capacity: Product: Molded Case Circuit Breaker NU HU NU HU NU HU NU HU 240V 50 100 50 100 50 100 50 100 480V 35 65 35 65 35 65 35 65 600V 10 14 10 18 14 20 18 25 Upstream connections Fixing hole Certificate plate Indication of closed (I/ON) position Brand name Operating handle Indication of open (O/OFF) position Company logo "push to trip" button Trip Fixing hole Downstream connections A-1-4 For Nuclear power plant Overview of trip units On TD125U (Q) to TS800U (Q) circuit breakers, the thermal-magnetic is built in trip units. Some models of the TD&TS series circuit breakers are UL Listed to be applied at up to 100% of their current rating. Because of the additional heat generated, the use of speciallydesigned enclosures and 90°C rated wire and the wire size are required when applying circuit breakers at 100% of continuous current rating. Markings on the circuit breaker indicate the minimum enclosure size and ventilation required. The 90°C wire size shall be based on the ampacity of the 75°C wire as indicated on UL489. Circuit breakers with 100% rating can also be used in applications requiring only 80% continuous loading. Ampere ratings MCCB frame type Rated current, In[A] Thermal magnetic release Type of trip unit TD125U (Q) FTU FMU 15, 20, 30, 40, 50, 40, 50, 60, 80, 60, 80, 100, 125 100, 125 150, 160, 175, TS250U (Q) 200, 225, 250 ATU - 160, 200, 250 160, 200, 250 MTU 1.6, 3.2, 6.3, 12, 20, 32, 50, 63, 100, 160, 220 TS400U (Q) 300, 350, 400 300, 400 300, 400 - TS800U (Q) 500, 600, 700, 800 500, 600, 800 500, 600, 800 - Types of trip units A-1-5 FTU �Fixed thermal, Fixed magnetic FMU �Adjustable thermal, Fixed magnetic ATU �Adjustable thermal, Adjustable magnetic MTU �Magnetic only trip unit For Nuclear power plant Switching mechanism Double contactor structure Optimize ON position Repulsion force Shape of contactor �Induce easily the arc mobility to grid direction �Rapidly redeploy the arc from moving contactor �Prevent contact tip from erosion �Unvarying contact force regardless of over travel �Open speed of moving contact is rapid by optimized cam curve regardless of trip signal �Function of trip free Optimized cam curve Unvarying contact Force Open speed & contact force Angle Fig. 3 “ON“ position OFF position �Push to trip in OFF position * Reset pin moment < Main spring moment �Stability of endurance Fig. 4 “OFF“ position Stress Amplitude (MPa) 600.0 500.0 400.0 300.0 200.0 100.0 0.0 0.00E+00 4.00E+06 3.00E+06 1.20E+07 1.60E+07 2.00E+07 Life TRIP position �Enables tripping mechanically from outside, for confirming the operation of the accessory switches and the manual resetting function Fig. 5 “TRIP“ position A-1-6 TD & TS MCCB Index A-2. Main characteristics MCCBs for power distribution Thermal magnetic trip Overview A-2-3 FTU, FMU for TD125U (Q) A-2-5 FTU, FMU for TS250U (Q), ATU for TS250U (Q) A-2-8 FTU, FMU, ATU for TS400U (Q) A-2-11 FTU, FMU, ATU for TS800U (Q) A-2-14 MCCBs for motor protection A-2-17 Molded case switch A-2-21 MCCBs for power distribution For Nuclear power plant TD series TD125U (Q) Frame size [AF] 125 No. of Poles 2, 3 Maximum voltage ratings [V AC] 600 Switch ampere ratings [A] 125 Magnetic override [A] 1250 Short circuit withstand ratings NU HU 120V AC 50 100 240V AC 50 100 480V AC 35 65 600V AC 10 14 Catalog number of wire connector A-2-1 LSCA1 For Nuclear power plant MCCBs for power distribution TS series TS250U (Q) TS400U (Q) 250 TS800U (Q) 400 800 2, 3 600 600 - 250 400 800 2500 4000 8000 NU HU NU HU NU HU - - - - - - 50 100 50 100 50 100 35 65 35 65 35 65 10 18 14 20 18 25 LSCA2 LGCA4 LSCA8 A-2-2 For Nuclear power plant MCCBs for power distribution Thermal magnetic trip Overview Susol TD & TS series circuit breakers be installed with thermal magnetic trip units. �Built-in trip units for TD & TS series Some models of the TD&TS series circuit breakers are UL Listed to be applied at up to 100% of their current rating. Because of the additional heat generated, the use of speciallydesigned enclosures and 90°C rated wire and the wire size are required when applying circuit breakers at 100% of continuous current rating. Markings on the circuit breaker indicate the minimum enclosure size and ventilation required. The 90°C wire size shall be based on the ampacity of the 75°C wire as indicated on UL489. Circuit breakers with 100% rating can also be used in applications requiring only 80% continuous loading. Function Protection of power distribution �Overload protection: Thermal protection with a fixed or adjustable threshold �Short-circuit protection: Magnetic protection with a fixed or adjustable pick-up Operation Trip bar ATU Bimetal Armature Thermal magnetic types �Time-Delay operation An overcurrent heats and warps the bimetal to actuate the trip bar by the bimetal characteristic. �Instantaneous operation If the overcurrent is excessive, the armature is attracted and the trip bar actuated by electromagnetic force. Ratings Thermal magnetic trip units(FTU/FMU/ATU) Ratings(A) In 15 20 30 40 50 60 80 100 125 150 160 175 200 225 250 300 350 400 500 600 700 800 TD125U (Q) ● ● ● ● ● ● ● at 40℃ ● ● - - - - - - - - - - - - - TS250U (Q) - - - - - - - - - ● ● ● ● ● ● - - - - - - - TS400U (Q) - - - - - - - - - - - - - - - ● ● ● - - - - - - - - - - - - - - - - - - - - - - ● ● ● ● TS800U (Q) Note) Rated current 500A~800A is available for TS800U (Q)FTU. A-2-3 TD125U (Q) to TS800U (Q) For Nuclear power plant MCCBs for power distribution Thermal magnetic trip Overview Characteristics Fixed thermal, fixed magnetic trip units FTU �Fixed thermal FTU 15A ... 800A rated currents �Fixed magnetic 400A ... 8000A tripping currents �Applicable to TD125U (Q) ... TS800U (Q) frames Im=2500A Ir Im Adjustable thermal, fixed magnetic trip units FMU �Adjustable thermal 40A ... 800A rated currents Adjustable : 0.8~1×In �Fixed magnetic 400A ... 8000A tripping currents �Applicable to TD125U (Q) ... TS800U (Q) frames Adjustable thermal, adjustable magnetic trip units ATU �Adjustable thermal 160A ... 800A rated currents ATU Adjustable : 0.8~1×In �Adjustable magnetic 800A ... 8000A tripping currents Adjustable : 5~10×In �Applicable to TS250U (Q) ... TS800U (Q) frames 0.9 0.8 7 8 6 1 9 5 Ir 10 Im A-2-4 MCCBs for power distribution For Nuclear power plant Thermal magnetic trip FTU, FMU for TD125U (Q) Configuration Trip identification Ratings (A), In at 40°C Number of pole Short circuit protection (magnetic) Setting current, Im Overload protection (thermal) Setting current, Ir TD125U (Q) FTU - Fixed thermal & magnetic trip unit FTU Im=1250A 125A TD125U (Q) FMU t 0.9 Ir Im 0.8 1 TD125U (Q) FMU - Adjustable thermal & fixed magnetic trip unit 0.9 FMU 0.8 1 Im=1250A Ir Im A-2-5 125A 0 Ir Im I For Nuclear power plant MCCBs for power distribution Thermal magnetic trip FTU, FMU for TD125U (Q) Characteristics Thermal magnetic trip units(FTU/FMU) ... TD125U (Q) Rating(A) at 40℃ In 15 20 30 40 50 60 80 100 125 TD125U (Q) ● ● ● ● ● ● ● ● ● Overload protection(thermal) Current setting(A) Ir FTU Fixed FMU Adjustable 0.8, 0.9, 1×In (3 settings) Short - circuit protection(magnetic) Current setting(A) Im FTU Fixed 400A Fixed 10×In FMU Fixed 400A Fixed 10×In Catalogue numbering system TD125U (Q) FMU Trip unit function - FTU : Fixed thermal & magnetic unit - FMU : Adjustable thermal, fixed magnetic unit MCCB frame type - TD125U (Q) : TD125NU (Q), TD125HU (Q) A-2-6 For Nuclear power plant MCCBs for power distribution Thermal magnetic trip FTU, FMU for TD125U (Q) Setting details Thermal overload protection Trip unit type Setting Trip unit rating, In (A) Ir 15 20 30 40 50 60 80 100 125 TD125U (Q) FTU Fixed 15 20 30 40 50 60 80 100 125 TD125U (Q) FMU 0.8 - - - 32 40 48 64 80 100 0.9 - - - 36 45 54 72 90 112.5 1 - - - 40 50 60 80 100 125 Magnetic short-circuit protection Trip unit type Setting current, Ir A-2-7 current, Im Trip unit rating, In (A) 15 20 30 40 50 60 80 100 125 Fixed In×10 400 400 400 400 500 600 800 1000 1250 0.8×In Fixed In×10 - - - 400 500 600 800 1000 1250 0.9×In Fixed In×10 - - - 400 500 600 800 1000 1250 1.0×In Fixed In×10 - - - 400 500 600 800 1000 1250 TD125U (Q) FTU TD125U (Q) FMU Setting For Nuclear power plant MCCBs for power distribution Thermal magnetic trip FTU, FMU for TS250U (Q) ATU for TS250U (Q) Configuration Trip identification Ratings (A), In at 40°C Number of pole Short circuit protection (magnetic) Setting current, Im Overload protection (thermal) Setting current, Ir TS250U (Q) FTU - Fixed thermal fixed magnetic trip unit TS250U (Q) FMU FTU Im=2500A Ir Im TS250U (Q) FMU - Adjustable thermal fixed magnetic trip unit TS250U (Q) ATU t Short circuit protection (magnetic) 0.9 0.8 TS250U (Q) ATU - Adjustable thermal adjustable magnetic trip unit 1 Short circuit protection (magnetic) 7 ATU 0.8 7 8 5 6 1 10 9 5 Ir 8 9 6 0.9 10 0 Ir Im I Im A-2-8 For Nuclear power plant MCCBs for power distribution Thermal magnetic trip FTU, FMU for TS250U (Q) ATU for TS250U (Q) Characteristics Thermal magnetic trip units(FTU/FMU) ... TS250U (Q) Rating(A) FTU FMU FTU FTU/FMU FTU FTU/FMU at 40℃ In 150 160 175 200 225 250 TS250U (Q) ● ● ● ● ● ● Overload protection(thermal) Current setting(A) Ir FTU Fixed FMU Adjustable 0.8 to×In ATU Adjustable 0.8 to×In Short - circuit protection(magnetic) Current setting(A) Im FTU Fixed 10×In FMU Fixed 10×In ATU Adjustable 5, 6, 7, 8, 9, 10×In (6 settings) Catalogue numbering system TS250U (Q) FTU Trip unit function - FTU: Fixed thermal, fixed magnetic unit MCCB frame type -TS250U (Q): TS250NU (Q), TS250HU (Q) TS250U (Q) FMU Trip unit function - FMU: Adjustable thermal, fixed magnetic unit MCCB frame type - TS250U (Q): TS250NU (Q), TS250HU (Q) TS250U (Q) ATU Trip unit function - ATU: Adjustable thermal, adjustable magnetic unit MCCB frame type - TS250U (Q): TS250NU (Q), TS250HU (Q) The trip unit ATU is available from 125A A-2-9 For Nuclear power plant MCCBs for power distribution Thermal magnetic trip FTU, FMU for TS250U (Q) ATU for TS250U (Q) Setting details Thermal overload protection Trip unit type Setting Trip unit rating, In (A) Ir 150 160 175 200 225 250 TS250U (Q) FTU Fixed 150 - 175 200 225 250 TS250U (Q) FMU 0.8 - 128 - 160 - 200 0.9 - 144 - 180 - 225 TS250U (Q) ATU 1 - 160 - 200 - 250 0.8 - 128 - 160 - 200 0.9 - 144 - 180 - 225 1 - 160 - 200 - 250 Magnetic short-circuit protection Trip unit type Setting Setting current, Ir current, Im TS250U (Q) FTU TS250U (Q) FMU Trip unit rating, In (A) 150 160 175 200 225 250 Fixed In×10 1500 - 1750 2000 2250 2500 0.8×In Fixed In×10 - - - 2000 - 2500 0.9×In Fixed In×10 - - - 2000 - 2500 1.0×In Fixed In×10 - - - 2000 - 2500 In×5 - 800 - 1000 - 1250 In×6 - 960 - 1200 - 1500 In×7 - 1120 - 1400 - 1750 In×8 - 1280 - 1600 - 2000 TS250U (Q) ATU 0.8×In 0.9×In 1.0×In Adjustable Adjustable Adjustable In×9 - 1440 - 1800 - 2250 In×10 - 1600 - 2000 - 2500 In×5 - 800 - 1000 - 1250 In×6 - 960 - 1200 - 1500 In×7 - 1120 - 1400 - 1750 In×8 - 1280 - 1600 - 2000 In×9 - 1440 - 1800 - 2250 In×10 - 1600 - 2000 - 2500 In×5 - 800 - 1000 - 1250 In×6 - 960 - 1200 - 1500 In×7 - 1120 - 1400 - 1750 In×8 - 1280 - 1600 - 2000 In×9 - 1440 - 1800 - 2250 In×10 - 1600 - 2000 - 2500 A-2-10 For Nuclear power plant MCCBs for power distribution Thermal magnetic trip FTU, FMU, ATU for TS400U (Q) Configuration Trip identification Ratings (A), In at 40°C Number of pole Short circuit protection (magnetic) Setting current, Im Overload protection (thermal) Setting current, Ir TS400U (Q) FTU - Fixed thermal fixed magnetic trip unit TS400U (Q) FMU FTU t Im=4000A Ir 400A 0.9 0.8 1 Im TS400U (Q) FMU - Adjustable thermal fixed magnetic trip unit 0 Ir Im I FMU 0.9 0.8 400A Im=4000A 1 Ir TS400U (Q) ATU Im t 0.9 0.8 TS400U (Q) ATU 1 - Adjustable thermal adjustable magnetic trip unit 7 ATU 6 0.9 0.8 7 6 1 A-2-11 Im 10 9 5 Ir 9 5 400A 8 8 10 0 Ir Im I MCCBs for power distribution For Nuclear power plant Thermal magnetic trip FTU, FMU, ATU for TS400U (Q) Characteristics Thermal magnetic trip units(FTU/FMU/ATU) ... TS400U (Q) Rating(A) FTU/FMU/ATU FTU FTU/FMU/ATU at 40℃ In 300 350 400 TS400U (Q) ● ● ● Overload protection(thermal) Current setting(A) Ir FTU In=Ir (Fixed) FMU Adjustable 0.8, 0.9, 1×In (3 settings) ATU Adjustable 0.8, 0.9, 1×In (3 settings) Short - circuit protection(magnetic) Current setting(A) Im FTU Fixed 10×In FMU Fixed 10×In ATU Adjustable 5, 6, 7, 8, 9,10×In(6 settings) Catalogue numbering system TS400U (Q) ATU Trip unit function - FTU : Fixed thermal & magnetic unit - FMU : Adjustable thermal & fixed magnetic unit - ATU : Adjustable thermal & adjustable magnetic unit MCCB frame type - TS400U (Q) : TS400NU (Q), TS400HU (Q) A-2-12 For Nuclear power plant MCCBs for power distribution Thermal magnetic trip FTU, FMU, ATU for TS400U (Q) Setting details Thermal overload protection Trip unit type Setting Trip unit rating, In (A) Ir 300 350 400 TS400U (Q) FTU Fixed 300 350 400 TS400U (Q) FMU 0.8 240 - 320 0.9 270 - 360 TS400U (Q) ATU 1 300 - 400 0.8 240 - 320 0.9 270 - 360 1 300 - 400 Magnetic short-circuit protection Trip unit type Setting Setting current, Ir current, Im TS400U (Q) FTU TS400U (Q) FMU 350 400 Fixed In×10 3000 3500 4000 0.8×In Fixed In×10 3000 - 4000 0.9×In Fixed In×10 3000 - 4000 1.0×In Fixed In×10 3000 - 4000 In×5 1500 - 2000 In×6 1800 - 2400 In×7 2100 - 2800 In×8 2400 - 3200 TS400U (Q) ATU 0.8×In 0.9×In 1.0×In A-2-13 Trip unit rating, In (A) 300 Adjustable Adjustable Adjustable In×9 2700 - 3600 In×10 3000 - 4000 In×5 1500 - 2000 In×6 1800 - 2400 In×7 2100 - 2800 In×8 2400 - 3200 In×9 2700 - 3600 In×10 3000 - 4000 In×5 1500 - 2000 In×6 1800 - 2400 In×7 2100 - 2800 In×8 2400 - 3200 In×9 2700 - 3600 In×10 3000 - 4000 For Nuclear power plant MCCBs for power distribution Thermal magnetic trip FTU, FMU, ATU for TS800U (Q) Configuration Trip identification Ratings (A), In at 40°C Number of pole Short circuit protection (magnetic) Setting current, Im Overload protection (thermal) Setting current, Ir TS800U (Q) FTU - Fixed thermal fixed magnetic trip unit FTU TS800U (Q) FMU Im=8000A Ir 800A t 0.9 Im 0.8 1 TS800U (Q) FMU - Adjustable thermal fixed magnetic trip unit 0 FMU 0.9 0.8 Im=8000A 1 Ir Ir Im I 800A TS800U (Q) ATU Im t 0.9 0.8 1 TS800U (Q) ATU - Adjustable thermal adjustable magnetic trip unit 7 ATU 6 0.9 0.8 7 6 1 9 5 10 9 5 Ir 800A 8 8 10 0 Ir Im I Im A-2-14 For Nuclear power plant MCCBs for power distribution Thermal magnetic trip FTU, FMU, ATU for TS800U (Q) Characteristics Thermal magnetic trip units(FTU/FMU/ATU) ... TS800U (Q) Rating(A) FTU/FMU/ATU FTU/FMU/ATU FTU FTU/FMU/ATU at 40℃ In 500 600 700 800 TS800U (Q) ● ● ● ● Overload protection(thermal) Current setting(A) Ir FTU Fixed FMU Adjustable 0.8, 0.9,1×In (3 settings) ATU Adjustable 0.8, 0.9,1×In (3 settings) Short - circuit protection(magnetic) Current setting(A) Im FTU Fixed 10×In FMU Fixed 10×In ATU Adjustable 5, 6, 7, 8, 9, 10×In (6 settings) Catalogue numbering system TS800U (Q) ATU Trip unit function - FTU : Fixed thermal & magnetic unit - FMU : Adjustable thermal & fixed magnetic unit - ATU : Adjustable thermal & adjustable magnetic unit MCCB frame type - TS800U (Q) : TS800NU (Q), TS800HU (Q) A-2-15 For Nuclear power plant MCCBs for power distribution Thermal magnetic trip FTU, FMU, ATU for TS800U (Q) Setting details Thermal overload protection Trip unit type Setting Trip unit rating, In (A) Ir 500 600 700 800 TS800U (Q) FTU Fixed 500 600 700 800 TS800U (Q) FMU 0.8 400 480 - 640 0.9 450 540 - 720 TS800U (Q) ATU 1 500 600 - 800 0.8 400 480 - 640 0.9 450 540 - 720 1 500 600 - 800 Magnetic short-circuit protection Trip unit type Setting Setting current, Ir current, Im TS800U (Q) FTU TS800U (Q) FMU Trip unit rating, In (A) 500 600 700 800 Fixed In×10 5000 6000 7000 8000 0.8×In Fixed In×10 5000 6000 - 8000 0.9×In Fixed In×10 5000 6000 - 8000 1.0×In Fixed In×10 5000 6000 - 8000 In×5 2500 3000 - 2000 In×6 3000 3600 - 4800 In×7 3500 4200 - 5600 In×8 4000 4800 - 6400 TS800U (Q) ATU 0.8×In 0.9×In 1.0×In Adjustable Adjustable Adjustable In×9 4500 5400 - 7200 In×10 5000 6000 - 8000 In×5 2500 3000 - 2000 In×6 3000 3600 - 4800 In×7 3500 4200 - 5600 In×8 4000 4800 - 6400 In×9 4500 5400 - 7200 In×10 5000 6000 - 8000 In×5 2500 3000 - 2000 In×6 3000 3600 - 4800 In×7 3500 4200 - 5600 In×8 4000 4800 - 6400 In×9 4500 5400 - 7200 In×10 5000 6000 - 8000 A-2-16 MCCBs for motor protection A-2-17 For Nuclear power plant For Nuclear power plant MCCBs for motor protection TS series TS250U (Q) Frame size [AF] 250 No. of Poles 3 Maximum voltage ratings [V AC] Rated current 1.6, 3.2, 6.3∙ ∙ ∙ ∙ ∙220 Note) [A] Short circuit withstand ratings 600 NU HU 120V AC - - 240V AC 50 100 480V AC 35 65 600V AC 10 18 Catalog number of wire connector LSCA1 (1.6~12A), LSCA2 (20~220A) This product is designed for Nuclear power plant. You can identify by “(Q)” sticker on the product, however, the nameplate does NOT contain any information to identify. A-2-18 For Nuclear power plant MCCBs for motor protection Intantaneous trip circuit break (ICB) MTU for TS250U (Q) For the protection of motors from 1.6 to 250kW(400V), TS250U (Q) circuit Breakers must be equipped with a special trip unit MTU adjustable thresholds. L1 L2 L3 1 3 5 2 4 6 1 3 5 2 4 6 Breaker Contactor O/L T1 T2 T3 M Motor Magnetic only release Configuration Trip unit identification Trip unit rating, In Magnetic setting for short-circuit protection Catalogue numbering system TS250U (Q) MTU Magnetic only trip unit MCCB frame type - TS250U (Q): TS250NU (Q), TS250HU (Q) A-2-19 For Nuclear power plant MCCBs for motor protection Intantaneous trip circuit break (ICB) MTU for TS250U (Q) Characteristics Magnetic trip units(MTU) Note) Rating(A) NU/HU In TS250U (Q) TS250U (Q) 1.6 3.2 6.3 12 20 32 50 63 100 160 220 ● ● ● ● ● ● ● ● ● ● ● Short - circuit protection(magnetic) Pick - up Im setting 6..12×In (6 Point) Note) TS250U (Q), Rated Currnet 1.6~63A products will provide only the NU Type Setting details In 1.6 3.2 6.3 12 20 32 Trip unit rating, In (A) 10 20 40 70 120 190 12 24 48 84 144 228 14 28 56 98 168 266 16 32 64 112 192 304 In 18 36 72 126 216 342 20 40 80 140 240 380 50 63 100 160 220 Trip unit rating, In (A) 300 360 400 480 600 720 960 1152 1320 1584 420 480 540 600 560 640 720 800 840 960 1080 1200 1344 1536 1728 1920 1848 2112 2376 2640 TS250U (Q) MTU MTU 1848 1584 ICB 1320 2112 2376 220A t Im = 6...12×In 2640 Im 14 12 10 0 Im 16 18 20 I A-2-20 TD & TS MCCB Index A-3. Accessories Electrical auxiliaries Undervoltage release, UVT Shunt release, SHT Auxiliary switch (AX), Alarm switch (AL) Possible configuration of electrical auxiliaries A-3-1 A-3-2 A-3-3 A-3-4 Rotary handles Extended handles Flange Handle A-3-5 A-3-5 Locking devices Removable locking device Fixed locking device A-3-6 A-3-7 Interlock Mechanical interlocking device A-3-8 For Nuclear power plant Accessories Electrical auxiliaries The following devices are installed into all TD & TS circuit breakers regardless of frame size. And, the electrical auxiliaries can be easily installed in the accessory compartment of the circuit breakers which is cassette type. Undervoltage release, UVT The undervoltage release automatically opens a circuit breaker when voltage drops to a value ranging between 35% to 70% of the line voltage. The operation is instantaneous, and after tripping, the circuit breaker cannot be reclosed again until the voltage returns to 85% of line voltage. UVT Continuously energized, the undervoltage release must be operating before the circuit breaker can be closed. The undervoltage release can be easily installed in the left accessory compartment of the Susol TD and TS circuit-breakers. �Range of tripping voltage: 0.35 ~ 0.7Vn �MCCB making is possible voltage: 0.85Vn (exceed) �Frequency (only AC): 45Hz ~ 65Hz Technical data Consumption Control voltage (V) Power consumption DC (W) mA AC/DC 24V 0.64 0.65 27 AC/DC 48V 1.09 1.10 23 AC/DC 110~130V 0.73 0.75 5.8 AC 200~240V/DC 250V 1.21 1.35 5.4 AC 380~440V 1.67 - 3.8 AC 440~480V 1.68 - 3.5 Max.opening time (ms) Tightening torque of terminal screw 50 8.2kgf∙cm Transformer operating voltage (V) - Drop (Circuit breaker trips) - Rise (Circuit breaker can be switched on) 8.2kgf∙cm A-3-1 Applicable AC (VA) 0.7~1.35Vn ~0.85Vn MCCBs TD125U (Q), TS250U (Q), TS400U (Q), TS800U (Q) For Nuclear power plant Accessories Electrical auxiliaries Shunt release, SHT The shunt release opens the mechanism in response to an externally applied voltage signal. The releases include coil clearing contacts that automatically clear the signal circuit when the mechanism has tripped. The shunt release can be installed in the left accessory compartment of the Susol TD & TS circuit-breakers. �Range of operational voltage: 0.7 ~ 1.1Vn �Frequency (only AC): 45Hz ~ 65Hz SHT Technical data Consumption Control voltage (V) AC (VA) DC 12V DC (W) Applicable mA MCCBs - 0.36 30 Power AC/DC 24V 0.58 0.58 24 consumption AC/DC 48V 1.22 1.23 25 TD125U (Q), AC/DC 110~130V 1.36 1.37 10.5 TS250U (Q), AC 220~240V/DC250V 1.80 1.88 7.5 TS400U (Q), AC 380~500V 1.15 - 2.3 TS800U (Q) Max.opening time (ms) 50 Tightening torque of terminal screw 8.2kgf∙cm 8.2kgf∙cm Click A-3-2 For Nuclear power plant Accessories Electrical auxiliaries Auxiliary switch (AX), Alarm switch (AL) Auxiliary switch (AX) Auxiliary switch is for applications requiring remote “ON” and “OFF” indication. Each switch contains two contacts having a AX Alarm switch (AL) Alarm switches offer provisions for immediate audio or visual indication of a tripped breaker due to overload, short circuit, shunt trip, or undervoltage release conditions. They are particularly useful in automated plants where operators must be signaled about changes in the electrical distribution system. common connection. One is open and the other closed when the circuit breaker is open, and vice-versa. This switch features a closed contact when the circuit breaker is tripped automatically. In other words, this switch does not function when the breaker is operated manually. Its contact is open when the circuit breaker is reset. Contact operation MCCB AL Position ON OFF TRIP AXa1 AXa1 AXc1 of AX Position of AL AXc1 AXb1 AXb1 AXa1 AXa1 AXc1 AXc1 AXb1 AXb1 Technical data Conventional thermal current Ith Rated operational current Ie 5A with rated operational voltage Ue - Altemating current 50/60Hz AC - Direct current DC A-3-3 Ie Voltage Resistance Inductance 125V 5 3 250V 3 2 500V - - 30V 4 3 125V 0.4 0.4 250V 0.2 0.2 TD125U (Q), TS250U (Q), TS400U (Q), TS800U (Q) For Nuclear power plant Rotary handles Extended handles The rotary handle operating mechanism is available in either the direct version or in the extended version on the compartment door. Extended rotary handles MCCB Extended Handle TD125U (Q) EHU1 TS250U (Q) EHU2 TS400U (Q) EHU3 TS800U (Q) EHU4 Flange Handle operated for its own flexibility And, also can be selected various length (4 types) at each frames. The flange hanle is operated by cable and can be applied on the compartment door. This device is designed to easily installed and Flange handle (Cable operating handle) MCCB Flange Handle TD125U (Q) FH1 TS250U (Q) FH2 TS400U (Q) FH3 TS800U (Q) FH4 A-3-4 For Nuclear power plant Accessories Electrical auxiliaries Possible configuration of electrical auxiliaries Maximum possibilities Phase Accessory R (Left) TS250U (Q) TS400U (Q) TS800U (Q) AX - 1 3 3 AL 1 1 - - SHT or UVT 1 1 1 1 AX 2 1 - - AL - - 1 2 T (Right) TD125U (Q) TD125U (Q) TS250U (Q) TS400U (Q) TS800U (Q) AL AX AX AX AX AL SHT/ UVT AX AX AX SHT/ UVT AL AX AX AX SHT/ UVT SHT/ UVT A-3-5 AL AL TD &TS MCCB Index A-5. Mounting & Connection Fixed mounting A-5-1 Connecting terminal & conductor A-5-1 Safety clearance A-5-2 For Nuclear power plant Mounting & Connection Fixed mounting Susol TD and TS circuit-breakers can be directly connected to the mounting plate. If busbars or terminals are used to connect the TD125U (Q) circuit breaker on the back of the mounting plate, the appropriate safety clearances must be observed. TS250U (Q) TS400U (Q) TS800U (Q) 2/3Pole: 2EA (NO.10-24 UNC-2A, L120) 2/3Pole: 2EA (1/4"-20 UNC-2A, L140) Screw for mounting 2/3Pole: 2EA (NO.8-32 UNC-2A, L100) Screw for connection of terminals, 2Pole:4EA(M5×L16) 2Pole:4EA(M8×L20) 3Pole:6EA(M5×L16) 3Pole:6EA(M8×L20) Torque: Max 78kgf∙cm Torque: Max 147kgf∙cm Connecting terminal & conductor Terminal (mm) Conductor (mm) 8 18 TD125U (Q) 23 M5×16 22 Max 78kgf∙cm 20 TS250U (Q) 28 ∅>8 ∅>8 M8×20 21 ≤10 22 Note) TS400U (Q), TS800U (Q) Only for lug A-5-1 Max 147kgf∙cm ≤10 ≤20 ≤20 For Nuclear power plant Mounting & Connection Safety clearance When a short circuit interruption occur, high temperatures pressures are present in and above the arc chambers of the circuit-breaker. In order to allow the pressure to be distributed and to prevent fire and arcing or short-circuit currents, safety clearances are required. When installing a circuit breaker, safety clearances must be kept between the breaker and panels, bars and other protection devices installed nearby. These safety clearances are depend on the ultimate breaking capacity and are defined by tests carried out in accordance with standard UL489. W1 H2 H1 D1 D2 W2 240V 480V 240V W1, W2 (inch) 480V H1, H2 (inch) TD125NU/HU/NA (Q) 0.6 1.0 1.2 1.4 TS250NU/HU/NA (Q) 0.6 1.0 1.2 1.4 TS400NU/HU/NA (Q) 0.6 0.8 2.0 2.4 TS800NU/HU/NA (Q) 0.8 1.8 3.1 3.9 240V / 480V / 600V 240V / 480V / 600V D1 (mm) D1 (inch) D2 (mm) D2 (inch) TD125NU/HU/NA (Q) 87 3.4 100 3.9 TS250NU/HU/NA (Q) 89 3.5 130 5.1 TS400NU/HU/NA (Q) 112 4.4 180 7 TS800NU/HU/NA (Q) 137 5.4 234 9.2 A-5-2 TD &TS MCCB Index A-6. Characteristics curves Circuit breakers with thermal-magnetic trip units TD125U (Q) A-6-1 TS250U (Q) A-6-2 TS400U (Q) A-6-4 TS800U (Q) A-6-6 Specific let-through energy curves 240V A-6-9 480V A-6-10 600V A-6-11 Current-limiting curves 240V A-6-12 480V A-6-13 600V A-6-14 For Nuclear power plant Characteristics curves Circuit breakers with thermal-magnetic trip units 10000 TD125U (Q) 120 100 FTU 5000 50 FMU Minutes 15~30A 2000 1000 FTU:Ir=1 x In FMU:Ir=0.8~1xIn 700 10 7 400 200 3 100 60 1 1 Second Operating time 10 In:15A -> Im=400A In:20A -> Im=400A FTU/FMU:Im=10xIn Min. 400A 0.1 In:30A -> Im=400A 0.01 0.001 0.5 0.8 1 2 3 4 5 6 7 8 10 20 30 X Normal Current In (I/Ir) Rated current compensation ratio(%) 150 100 50 0 10 20 30 40 Ambient temperature(40°C) A-6-1 50 40 50 70 100 200 300 For Nuclear power plant Characteristics curves Circuit breakers with thermal-magnetic trip units 10000 TD125U (Q) 120 100 FTU 5000 50 FMU Minutes 1000 FTU:Ir=1 x In FMU:Ir=0.8~1xIn 700 10 7 400 200 3 100 60 1 10 Second 1 FTU/FMU:Im=10xIn Min. 400A 0.1 0.01 0.001 0.5 0.8 1 2 3 4 5 6 7 8 10 20 30 40 50 70 100 200 300 X Normal Current In (I/Ir) 150 Rated current compensation ratio(%) Operating time 40~50A 2000 100 50 0 10 20 30 40 50 Ambient temperature(40°C) A-6-2 For Nuclear power plant Characteristics curves Circuit breakers with thermal-magnetic trip units 10000 TD125U (Q) 120 100 FTU 5000 50 FMU Minutes 60~100A 2000 1000 FTU:Ir=1 x In FMU:Ir=0.8~1xIn 700 10 7 400 200 3 100 60 1 1 Second Operating time 10 FTU/FMU:Im=10xIn Min. 400A 0.1 0.01 0.001 0.5 0.8 1 2 3 4 5 6 7 8 10 20 30 X Normal Current In (I/Ir) Rated current compensation ratio(%) 150 100 50 0 10 20 30 40 Ambient temperature(40°C) A-6-3 50 40 50 70 100 200 300 For Nuclear power plant Characteristics curves Circuit breakers with thermal-magnetic trip units 10000 TD125U (Q) 120 100 FTU 5000 50 FMU Minutes 1000 FTU:Ir=1 x In FMU:Ir=0.8~1xIn 700 10 7 400 200 3 100 60 1 10 Second 1 FTU/FMU:Im=10xIn Min. 400A 0.1 0.01 0.001 0.5 0.8 1 2 3 4 5 6 7 8 10 20 30 40 50 70 100 200 300 X Normal Current In (I/Ir) 150 Rated current compensation ratio(%) Operating time 125A 2000 100 50 0 10 20 30 40 50 Ambient temperature(40°C) A-6-4 Characteristics curves For Nuclear power plant Circuit breakers with thermal-magnetic trip units TS250U (Q) FTU FMU 150~250A FTU:Ir=1 × In FMU:Ir=0.8~1×In FTU/FMU:Im=10×In pressure tripping t 10ms A-6-5 Characteristics curves For Nuclear power plant Circuit breakers with thermal-magnetic trip units TS250U (Q) ATU 160~250A ATU:Ir=0.8~1×In ATU:Im=5~10×In pressure tripping t 10ms 0.5 A-6-6 Characteristics curves For Nuclear power plant Circuit breakers with thermal-magnetic trip units TS400U (Q) FTU FMU 300~400A FTU:Ir=1 × In FMU:Ir=0.8~1×In FTU/FMU:Im=10 ×In pressure tripping t 10ms A-6-7 Characteristics curves For Nuclear power plant Circuit breakers with thermal-magnetic trip units TS400U (Q) ATU 300~400A ATU:Ir=0.8~1×In ATU:Im=5~10 ×In pressure tripping t 10ms A-6-8 Characteristics curves For Nuclear power plant Circuit breakers with thermal-magnetic trip units TS800U (Q) FTU FMU 500~800A FTU:Ir=1 × In FMU:Ir=0.8~1×In FTU/FMU:Im=10×In pressure tripping t 10ms A-6-9 Characteristics curves For Nuclear power plant Circuit breakers with thermal-magnetic trip units TS800U (Q) ATU 500~800A ATU:Ir=0.8~1×In ATU:Im=5~10 ×In pressure tripping t 10ms A-6-10 For Nuclear power plant Characteristics curves Circuit breakers with magnetic only trip units 10000 TS250U (Q) 120 100 Magnetic only 5000 50 MTU Minutes 1.6~63A 2000 1000 700 10 7 Thermal withstand 400 200 3 100 60 1 MTU Type 63A:400~800A 50A:300~600A 32A:190~380A 20A:120~240A 12A:70 ~140A 6.3A:40 ~80A 3.2A:20 ~40A 1.6A:10 ~20A MTU:Im=6~12xIn 1 Second Operating time 10 0.1 pressure tripping t 10ms 0.01 0.001 0.5 0.8 1 2 3 4 5 6 7 8 10 20 30 X Normal Current In (I/Ir) A-6-11 40 50 70 100 200 300 For Nuclear power plant Characteristics curves Circuit breakers with magnetic only trip units 10000 TS250U (Q) 120 100 Magnetic only 5000 50 MTU Minutes 1000 700 10 7 Thermal withstand 400 200 3 100 60 1 10 1 Second Operating time 100~220A 2000 MTU:Im=6~12 xIn 0.1 pressure tripping t 10ms 0.01 0.001 0.5 0.8 1 2 3 4 5 6 7 8 10 20 30 40 50 70 100 200 300 X Normal Current In (I/Ir) A-6-12 Characteristics curves For Nuclear power plant Specific let-through energy curves 240V Thermal stress TS800U TS400U TS250U TD125U A-6-13 Characteristics curves For Nuclear power plant Specific let-through energy curves 480V Thermal stress TS800U TS400U TS250U TD125U A-6-14 Characteristics curves For Nuclear power plant Specific let-through energy curves 600V Thermal stress TS800U TS400U TS250U TD125U A-6-15 Characteristics curves For Nuclear power plant Current-limiting curves 240V Peak current TS800U TS400U TS250U TD125U A-6-16 Characteristics curves For Nuclear power plant Current-limiting curves 480V Peak current TS800U TS400U TS250U TD125U A-6-17 For Nuclear power plant Characteristics curves Current-limiting curves 600V Peak current TS800U TS400U TS250U TD125U A-6-18 TD & TS MCCB Index A-7. Dimensions TD125U (Q) A-7-1 TS250U (Q) A-7-2 TS400U (Q) A-7-3 TS800U (Q) A-7-4 Mechanical interlocking device A-7-13 MIT13, MIT23, MIT33, MIT43 Mechanical interlocking device Mounting dimension for MIT A-7-14 For Nuclear power plant Overall dimensions TD125U (Q) Dimensions : inch (mm) 3.035 (77.1) 2.958 (75.15) 2.716 (69) 3.543 (90) 0.192 (4.9) 0.81 (20.45) 0.846 (21.5) 6.456 (164) 2.362 (60) 1.496 (38) 1.062 (27) 3.389 (86.1) 0.95 (24.2) 0.59 (15) 3.496 (88.81) 1.181 (30) 3.625 (92.1) 1.181 (30) 4.212 (107) 0.578 (14.7) Circuit breaker mounting Circuit breaker bolt drilling plan escutcheon dimensions C L CL #8-32UNC Tap (2holes) 1.141 (29) A-7-1 2.519 (64) 4.212 (107) CL 1.535 (39) C L 0.59 (15) For Nuclear power plant Overall dimensions TS250U (Q) Dimensions : inch (mm) 3.385 (86) 2.952 (75) 2.716 (69) 4.133 (105) 0.423 (10.75) 3.937 (100) 7.007 (178) 2.362 (60) 1.496 (38) 0.196 (5) 0.964 (24.5) 1.062 (27) 1.09 (27.8) 0.688 (17.5) 1.377 (35) Circuit breaker mounting Circuit breaker bolt drilling plan escutcheon dimensions CL 0.69 (17.5) CL CL 2.677 (68) 1.259 (32) 1.102 (28) 4.921 (125) 2.5 (63.5) CL 3.661 (93) 4.318 (109.7) 1.377 (35) 0.629 (16) 3.546 (90.1) #8-32 UNC Tap (2 Holes) A-7-2 For Nuclear power plant Overall dimensions TS400U (Q) Dimensions : inch (mm) 4.33 (110) 3.838 (97.5) 5.511 (140) 11.496 (292) 6.535 (166) 4.015 (102) 2.795 (71) 2.322 (59) 0.314 (8) 1.653 (42) 3.267 (83) 3.11 (79) 1.3 (33) 0.925 (23.5) 1.83 (46.5) 1.082 (27.5) 4.645 (118) 1.83 (46.5) 4.842 (123) 6.181 (157) Circuit breaker mounting Circuit breaker bolt drilling plan escutcheon dimensions CL CL 2.44 (62) #10-24 UNC Tap (2 Holes) A-7-3 4.488 (114) CL CL 1.653 (42) 7.874 (200) 0.885 (22.5) For Nuclear power plant Overall dimensions TS800U (Q) Dimensions : inch (mm) 5.846 (148.5) 5.511 (140) 3.149 (80) 2.125 (54) 8.267 (210) 3.543 (90) 7.818 (198.6) 0.433 (11) 1.862 (47.3) 3.279 (83.3) 3.149 (80) 4.33 (110) 16.85 (428) 4.566 (116) 2.755 (35) 2.755 (70) 2.755 (70) 2.125 (54) 4.685 (119) 5.039 (128) 5.314 (135) 7.775 (197.5) Circuit breaker mounting Circuit breaker bolt drilling plan escutcheon dimensions CL CL 5.25 (133.3) 10.944 (278) CL 3.188 (81) 3.279 (83.3) CL 1.377 (35) 1 # 4"-20 UNC Tap (2Holes) A-7-4 For Nuclear power plant Overall dimensions Extended rotary handle TD125U (Q) Dimensions : inch (mm) 14.5 (368.3) Min 14.5(368.3) Max 26.5(673.1)-Shaft 24inch Panel drilling Way of installation 1.18 (30) N Ta o 8pp 32 Ho ing les ) (4 2) (5 04 e) 2. l ∅ (Ho 2.68 (68) 4.21 (107) 0.531 (13.5) ) (5 ) 19 0. oles H (2 ∅ A-7-5 1.10 (28) 0.433 (11) For Nuclear power plant Overall dimensions Extended rotary handle TS250U (Q) Dimensions : inch (mm) 14.54 (369.3) Min 14.54 (369.3) Max 26.54 (674.1)-Shaft 24inch Panel drilling 1.39 (35.3) 0.79 (20) 1.38 (35) 2.68 (68) 4.90 (124.4) ∅ 0. 1 Ho 9 (5 les ) ) No Ta 8-32 p (4H ping ole s) (2 Way of installation ∅ 2.0 (H 4 (5 ole 2) ) 0.433 (11) A-7-6 For Nuclear power plant Overall dimensions Extended rotary handle TS400U (Q) Dimensions : inch (mm) 15.93 (404.6) Min 15.93 (404.6) Max 27.93 (709.4)-Shaft 24inch Panel drilling Way of installation 1.39 (35.3) ∅ 0. 1.83 (46.5) 2.68 (68) 7.87 (200) 1.39 (35.4) 1 Ho 9 (5 les ) ) (2 ∅ No UN 10-32 Ta C-2A p (4H ping ole s) (H A-7-7 2. 04 ole (52 ) ) 0.433 (11) For Nuclear power plant Overall dimensions Extended rotary handle TS800U (Q) 17.42 (442.5) Dimensions : inch (mm) Min 17.42 (442.5) Max 29.42 (747.32)-Shaft 24inch Panel drilling Way of installation 2.22 (56.3) ∅ 0. 1 Ho 9 (5 les ) ) 0.57 (14.5) 2.76 (70) 2.68 (68) 10.94 (278) (2 ∅ 2. 04 ole (52) ) 1 4 UN ''-2 Ta C- 0 (4 ppin 2A Ho g les ) (H 0.433 (11) A-7-8 For Nuclear power plant Overall dimensions Flange handle TD125U (Q) Dimensions : inch (mm) F 4.251 (108) 4.212 (107) 4.685 (119) 0.433 (11) 1.18 (30) E #8-32 UNC Tap (4 Holes) Panel drilling Way of installation E MAX F "DOWN" F "UP" Table 1 Enclosure Maximum “F” Dimension Enclosure 60 cable 72 cable FH1-60 FH1-72 10 25 30 10 17 31 20 34 12 24 29 12 17 31 19 33 16 23 28 16 17 28 19 30 18 22 27 18 17 28 19 30 20 21 26 20 16 26 18 28 24 20 25 24 14 26 16 28 30 19 24 30 11 24 13 26 36 18 23 36 6 21 8 22 Depth A-7-9 Maximum “E” Dimension Table 2 Depth Up Down Up Down For Nuclear power plant Overall dimensions Flange handle TS250U (Q) 1.377 (35) F 4.921 (125) 4.251 (108) 0.433 (11) 4.685 (119) 2.5 (63.5) Dimensions : inch (mm) E #8-32 UNC Tap (4 Holes) Panel drilling Way of installation E MAX F "DOWN" F "UP" Table 1 Enclosure Maximum “E” Dimension Table 2 Maximum “F” Dimension Enclosure 60 cable 72 cable FH2-60 FH2-72 10 25 30 10 17 31 20 34 12 24 29 12 17 31 19 33 16 23 28 16 17 28 19 30 18 22 27 18 17 28 19 30 20 21 26 20 16 26 18 28 24 20 25 24 14 26 16 28 30 19 24 30 11 24 13 26 36 18 23 36 6 21 8 22 Depth Depth Up Down Up Down A-7-10 For Nuclear power plant Overall dimensions Flange handle TS400U (Q) Dimensions : inch (mm) 1.83 (46.5) F 4.251 (108) 7.874 (200) 4.685 (119) 0.433 (11) E #10-24 UNC Tap (4 Holes) Panel drilling Way of installation E MAX F "DOWN" F "UP" Table 1 Enclosure Maximum “F” Dimension Enclosure 60 cable 72 cable FH3-60 FH3-72 10 25 30 10 17 31 20 34 12 24 29 12 17 31 19 33 16 23 28 16 17 28 19 30 18 22 27 18 17 28 19 30 20 21 26 20 16 26 18 28 24 20 25 24 14 26 16 28 30 19 24 30 11 24 13 26 36 18 23 36 6 21 8 22 Depth A-7-11 Maximum “E” Dimension Table 2 Depth Up Down Up Down For Nuclear power plant Overall dimensions Flange handle TS800U (Q) Dimensions : inch (mm) 2.755 (70) # 1 4"-20 UNC Tap (4 Holes) F 4.685 (119) 10.944 (278) 4.251 (108) 0.433 (11) E Panel drilling Way of installation E MAX F "DOWN" F "UP" Table 1 Enclosure Maximum “E” Dimension Table 2 Maximum “F” Dimension Enclosure 60 cable 72 cable FH4-60 FH4-72 10 25 30 10 17 31 20 34 12 24 29 12 17 31 19 33 16 23 28 16 17 28 19 30 18 22 27 18 17 28 19 30 20 21 26 20 16 26 18 28 24 20 25 24 14 26 16 28 30 19 24 30 11 24 13 26 36 18 23 36 6 21 8 22 Depth Depth Up Down Up Down A-7-12 � For your safety, please read user's manual thoroughly before operating. � Contact the nearest authorized service facility for examination, repair, or adjustment. � Please contact a qualified service technician when you need maintenance. Do not disassemble or repair by yourself! Safety Instructions � Any maintenance and inspection shall be performed by the personnel having expertise concerned. ⓒ 2013. 08 LSIS Co.,Ltd. All rights reserved. � HEAD OFFICE LS Tower 1026-6, Hogye-dong, Dongan-gu, Anyang-si, Gyeonggi-do 431-848, Korea Tel. (82-2)2034-4887, 4873, 4918, 4148 Fax. (82-2)2034-4648 www.lsis.biz � Global Network �LSIS (Middle East) FZE � �Dubai, U.A.E. Address: LOB 19 JAFZA VIEW TOWER Room 205, Jebel Ali Freezone P.O. Box 114216, Dubai, United Arab Emirates Tel: 971-4-886 5360 Fax: 971-4-886-5361 e-mail: dhleef@lsis.biz �Dalian LSIS Co., Ltd. � �Dalian, China Address: No.15, Liaohexi 3-Road, Economic and Technical Development zone, Dalian 116600, China Tel: 86-411-8273-7777 Fax: 86-411-8730-7560 e-mail: tangyh@lsis.com.cn �LSIS (Wuxi) Co., Ltd. � �Wuxi, China Address: 102-A , National High & New Tech Industrial Development Area, Wuxi, Jiangsu, 214028, P.R.China Tel: 86-510-8534-6666 Fax: 86-510-522-4078 e-mail: luw@lsis.com.cn � CHEONG-JU PLANT Cheong-Ju Plant #1, Song Jung Dong, Hung Duk Ku, Cheong Ju, 361-720, Korea �LSIS-VINA Co., Ltd. � �Hanoi, Vietnam Address: Nguyen Khe - Dong Anh - Ha Noi - Viet Nam Tel: 84-4-882-0222 Fax: 84-4-882-0220 e-mail: sjbaik@lsis.biz �LSIS-VINA Co., Ltd. � �Hochiminh , Vietnam Address: 41 Nguyen Thi Minh Khai Str. Yoco Bldg 4th Floor, Hochiminh City, Vietnam Tel: 84-8-3822-7941 Fax: 84-8-3822-7942 e-mail: hjchoid@lsis.biz �LSIS Shanghai Office � �Shanghai, China Address: Room 32 floors of the Great Wall Building, No. 3000 North Zhongshan Road, Putuo District, Shanghai, China Tel: 86-21-5237-9977 Fax: 89-21-5237-7189 e-mail: baijh@lsis.com.cn �LSIS Beijing Office � �Beijing, China Address: B-Tower 17FL.Beijing Global Trade Center B/D. No.36, BeiSanHuanDong-Lu, DongCheng-District, Beijing 100013, P.R. China Tel: 86-10-5825-6025,7 Fax: 86-10-5825-6026 e-mail: sunmj@lsis.com.cn �LSIS Guangzhou Office � �Guangzhou, China Address: Room 1403, 14/F, New Poly Tower, No.2 Zhongshan Liu Road, Guangzhou 510180, P.R. China Tel: 020-8326-6754 Fax: 020-8326-6287 e-mail: chenxs@lsis.com.cn �LSIS Chengdu Office � �Chengdu, China Address: Room 1701 17Floor, huamin hanjun internationnal Building, No1 Fuxing Road Chengdu, 610016, P.R. China Tel: 86-28-8670-3201 Fax: 86-28-8670-3203 e-mail: yangcf@lsis.com.cn �LSIS Qingdao Office � �Qingdao, China Address: Room 2001,20/F,7B40, Galaxy Building, No.29 Shandong Road, Shinan District, Qingdao 266071, P.R. China Tel: 86-532-8501-6058 Fax: 86-532-8501-6057 e-mail: wangzy@lsis.com.cn �LSIS NETHERLANDS Co.Ltd � �Schiphol-Rijk, Netherlands Address: 1st. Floor, Tupolevlaan 48, 1119NZ,Schiphol-Rijk, The Netherlands Tel: 31-20-654-1420 Fax: 31-20-654-1429 e-mail: junshickp@lsis.biz Specifications in this catalog are subject to change without notice due to continuous product development and improvement. 2013. 08 �LSIS Gurgaon Office � �Gurgaon ,India Address: 109 First Floor, Park Central, Sector-30, Gurgaon- 122 002, Haryana, India e-mail: hwyim@lsis.biz Low voltage circuit breakers (E) 2013. 08/(01) 2013. 08 Printed in Korea STAFF