Low voltage circuit breakers

www.lsis.biz
North American Edition
Super Solution
For Nuclear power plant
Low voltage circuit breakers
Susol Low voltage circuit breakers
Low voltage
circuit breakers
Super Solution
Contents
Overview
A-1
Main characteristics
A-2
Accessories
A-3
Technical information
A-4
Mounting & connection
A-5
Characteristics curves
A-6
Dimensions
A-7
>>>
UL MCCB
Beyond the limits...
The circuit breaker will supply more stable,
reliable, upgraded systems to customer
with high breaking capacity.
Susol UL TD and TS series
Molded Case Circuit Breakers
Susol MCCB
■Simplified product range
■Standards
■Various trip units
�AF: 125AF, 250AF, 400AF, 800AF
�Ampere Range: 15A ~ 800A
�World class with UL489
�FTU: Fixed thermal & Magnetic unit
�ATU: Adjustable thermal & Magnetic unit
�FMU: Adjustable thermal, Fixed magnetic unit
�MTU: Magnetic only trip unit (1.6~220A)
■High performance
�Ultimate breaking capacity (kA rms)
Icu: Max 65kA @480VAC
■Variable accessories
�Electrical auxiliaries
�Extended rotary handle
�Flange handle
�Locking devices
MCCB
8 Models in 4 Frames
Susol TD and TS circuit breakers
are rated from 15 through 800
amperes and are available in four
frame sizes.
UL 489 Listed
Circuit Breakers Family TD/ TS
65kA at 480VAC / 8 models in 4 frames
TD125U (Q)
In 15~125A
Icu: 35kA(NU), 65kA(HU)
90(W) x 164(H) x 86mm(D)
Enhanced high performance
N Type - 35kA, H Type - 65kA
Maximum breaking capacity for all Ampere Frame is 65kA at 480VAC.
TS800HU
TS800NU
Rated current (A)
65kA
35kA
TS400HU
TS250HU
TD125HU
TS400NU
TS250NU
800A
TD125NU
400A
250A
125A
65kA
35kA
High available fault current at 480V (kA)
TS800U (Q)
TS400U (Q)
TS250U (Q)
In 150~250A
Icu: 35kA(NU), 65kA(HU)
105(W) x 178(H) x 86mm(D)
In 300~400A
Icu: 35kA(NU), 65kA(HU)
140(W) x 292(H) x 110mm(D)
In 500~800A
Icu: 35kA(NU), 65kA(HU)
210(W) x 428(H) x 135mm(D)
TD & TS MCCB Index
A-1. Overview
Range of Susol products
A-1-1
Overview of TD/TS family
A-1-3
Marking and configuration
A-1-5
Overview of trip units
A-1-7
Switching mechanism
A-1-8
For Nuclear power plant
Overview of TD/TS family
TD series
TD125U (Q)
Frame size
125
[AF]
Rated current In
[A]
15, 20, 30, 40, 50, 60, 80, 100, 125
2, 3
No. of Poles
Rated operational voltage, Ue AC
UL interrupting rating
AC 50/60Hz
600
[V]
[kA]
NU
HU
120V
50
100
240 V
50
100
480 V
35
65
600 V
10
14
UL 489
Reference standard
Trip unit (Thermal-Magnetic)
●Fixed-thermal, Fixed-magnetic
FTU
●
●Adjustable-thermal, Fixed-magnetic
FMU
●
●Adjustable-thermal, Adjustable-magnetic (3Pole)
ATU
-
●Magnetic only
MTU
-
Variable accessories
AX
●
AL
●
SHT
●
UVT
●
Extended rotary handle
●
Flange handle
●
Locking devices (Removable, Fixed)
●
Mechanical interlock device
●
Mechanical life
[operations]
Electrical life @600V AC
[operations]
Weight 3-Pole
Basic dimension, W×H×D 3-Pole
[lbs/kg]
[inch/mm]
This product is designed for Nuclear power plant.
You can identify by “(Q)” sticker on the product, however, the nameplate does NOT contain any information to identify.
A-1-1
4,000
4,000
2.65/1.2
3.54×6.46×3.39/90×164×86
For Nuclear power plant
Overview of TD/TS family
TS series
TS250U (Q)
TS400U (Q)
TS800U (Q)
250
400
800
150, 160, 175, 200, 225, 250
300, 350, 400
500, 600, 700, 800
2, 3
2, 3
2, 3
600
600
600
NU
HU
NU
HU
NU
HU
50
100
50
100
50
100
35
65
35
65
35
65
10
18
14
20
18
25
UL 489
UL 489
UL 489
●
●
●
●
●
●
● (3∅)
● (3∅)
● (3∅)
●
-
-
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
5,000
5,000
3,000
1,000
1,000
500
4.19/1.9
12.57/5.7
29.98/13.6
4.13×7.01×3.39/105×178×86
5.51×11.50×4.33/140×292×110
8.27×16.85×5.31/210×428×135
A-1-2
For Nuclear power plant
Marking and configuration
Rated frequency
Standard
Manufacturer
UL listed number
Terminal Information
A-1-3
For Nuclear power plant
Marking and configuration
Model (Rating and breaking capacity)
�TS: Series
�250: Max. Ampere rating
�NU: Normal (Standard)
�HU: High
Standardized characteristics:
�Ui: Rated insulation voltage
�Uimp: Impulse withstand voltage
�Ue: Rated operational voltage
125AF
250AF
400AF
800AF
NU
TD125NU (Q) TS250NU (Q) TS400NU (Q) TS800NU (Q)
HU
TD125HU (Q) TS250HU (Q) TS400HU (Q) TS800HU (Q)
NU
50kA
50kA
50kA
50kA
HU
100kA
100kA
100kA
100kA
125AF
250AF
400AF
800AF
Interrupt Capacity:
Product: Molded Case Circuit Breaker
NU
HU
NU
HU
NU
HU
NU
HU
240V
50
100
50
100
50
100
50
100
480V
35
65
35
65
35
65
35
65
600V
10
14
10
18
14
20
18
25
Upstream connections
Fixing hole
Certificate plate
Indication of closed (I/ON) position
Brand name
Operating handle
Indication of open (O/OFF) position
Company logo
"push to trip" button
Trip
Fixing hole
Downstream connections
A-1-4
For Nuclear power plant
Overview of trip units
On TD125U (Q) to TS800U (Q) circuit breakers,
the thermal-magnetic is built in trip units.
Some models of the TD&TS series circuit
breakers are UL Listed to be applied at up to
100% of their current rating. Because of the
additional heat generated, the use of speciallydesigned enclosures and 90°C rated wire and
the wire size are required when applying circuit
breakers at 100% of continuous current rating.
Markings on the circuit breaker indicate the
minimum enclosure size and ventilation
required. The 90°C wire size shall be based on
the ampacity of the 75°C wire as indicated on
UL489. Circuit breakers with 100% rating can
also be used in applications requiring only 80%
continuous loading.
Ampere ratings
MCCB frame type
Rated current, In[A]
Thermal magnetic release
Type of trip unit
TD125U (Q)
FTU
FMU
15, 20, 30, 40, 50,
40, 50, 60, 80,
60, 80, 100, 125
100, 125
150, 160, 175,
TS250U (Q)
200, 225, 250
ATU
-
160, 200, 250
160, 200, 250
MTU
1.6, 3.2, 6.3, 12, 20, 32,
50, 63, 100, 160, 220
TS400U (Q)
300, 350, 400
300, 400
300, 400
-
TS800U (Q)
500, 600, 700, 800
500, 600, 800
500, 600, 800
-
Types of trip units
A-1-5
FTU
�Fixed thermal, Fixed magnetic
FMU
�Adjustable thermal, Fixed magnetic
ATU
�Adjustable thermal, Adjustable magnetic
MTU
�Magnetic only trip unit
For Nuclear power plant
Switching mechanism
Double contactor structure
Optimize
ON position
Repulsion force
Shape of contactor
�Induce easily the arc mobility to grid
direction
�Rapidly redeploy the arc from moving
contactor
�Prevent contact tip from erosion
�Unvarying contact force regardless of
over travel
�Open speed of moving contact is rapid by
optimized cam curve regardless of trip
signal
�Function of trip free
Optimized
cam curve
Unvarying
contact
Force
Open speed & contact force
Angle
Fig. 3 “ON“ position
OFF position
�Push to trip in OFF position
* Reset pin moment < Main spring moment
�Stability of endurance
Fig. 4 “OFF“ position
Stress Amplitude (MPa)
600.0
500.0
400.0
300.0
200.0
100.0
0.0
0.00E+00
4.00E+06
3.00E+06
1.20E+07
1.60E+07
2.00E+07
Life
TRIP position
�Enables tripping mechanically from
outside, for confirming the operation of
the accessory switches and the manual
resetting function
Fig. 5 “TRIP“ position
A-1-6
TD & TS MCCB Index
A-2. Main characteristics
MCCBs for power distribution
Thermal magnetic trip
Overview
A-2-3
FTU, FMU for TD125U (Q)
A-2-5
FTU, FMU for TS250U (Q), ATU for TS250U (Q)
A-2-8
FTU, FMU, ATU for TS400U (Q)
A-2-11
FTU, FMU, ATU for TS800U (Q)
A-2-14
MCCBs for motor protection
A-2-17
Molded case switch
A-2-21
MCCBs for power distribution
For Nuclear power plant
TD series
TD125U (Q)
Frame size
[AF]
125
No. of Poles
2, 3
Maximum voltage ratings
[V AC]
600
Switch ampere ratings
[A]
125
Magnetic override
[A]
1250
Short circuit
withstand ratings
NU
HU
120V AC
50
100
240V AC
50
100
480V AC
35
65
600V AC
10
14
Catalog number of wire connector
A-2-1
LSCA1
For Nuclear power plant
MCCBs for power distribution
TS series
TS250U (Q)
TS400U (Q)
250
TS800U (Q)
400
800
2, 3
600
600
-
250
400
800
2500
4000
8000
NU
HU
NU
HU
NU
HU
-
-
-
-
-
-
50
100
50
100
50
100
35
65
35
65
35
65
10
18
14
20
18
25
LSCA2
LGCA4
LSCA8
A-2-2
For Nuclear power plant
MCCBs for power distribution
Thermal magnetic trip
Overview
Susol TD & TS series circuit breakers be
installed with thermal magnetic trip units.
�Built-in trip units for TD & TS series
Some models of the TD&TS series circuit
breakers are UL Listed to be applied at up to
100% of their current rating. Because of the
additional heat generated, the use of speciallydesigned enclosures and 90°C rated wire and
the wire size are required when applying circuit
breakers at 100% of continuous current rating.
Markings on the circuit breaker indicate the
minimum enclosure size and ventilation
required. The 90°C wire size shall be based on
the ampacity of the 75°C wire as indicated on
UL489. Circuit breakers with 100% rating can
also be used in applications requiring only 80%
continuous loading.
Function
Protection of power distribution
�Overload protection: Thermal protection with
a fixed or adjustable threshold
�Short-circuit protection: Magnetic protection
with a fixed or adjustable pick-up
Operation
Trip bar
ATU
Bimetal
Armature
Thermal magnetic types
�Time-Delay operation
An overcurrent heats and warps the bimetal to actuate the
trip bar by the bimetal characteristic.
�Instantaneous operation
If the overcurrent is excessive, the armature is attracted
and the trip bar actuated by electromagnetic force.
Ratings
Thermal magnetic trip units(FTU/FMU/ATU)
Ratings(A)
In
15
20
30
40
50
60
80 100 125 150 160 175 200 225 250 300 350 400 500 600 700 800
TD125U (Q)
●
●
●
●
●
●
●
at 40℃
●
●
-
-
-
-
-
-
-
-
-
-
-
-
-
TS250U (Q)
-
-
-
-
-
-
-
-
-
●
●
●
●
●
●
-
-
-
-
-
-
-
TS400U (Q)
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
●
●
●
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
●
●
●
●
TS800U (Q)
Note) Rated current 500A~800A is available for TS800U (Q)FTU.
A-2-3
TD125U (Q) to TS800U (Q)
For Nuclear power plant
MCCBs for power distribution
Thermal magnetic trip
Overview
Characteristics
Fixed thermal, fixed magnetic trip units
FTU
�Fixed thermal
FTU
15A ... 800A rated currents
�Fixed magnetic
400A ... 8000A tripping currents
�Applicable to TD125U (Q) ... TS800U (Q) frames
Im=2500A
Ir
Im
Adjustable thermal, fixed magnetic trip units
FMU
�Adjustable thermal
40A ... 800A rated currents
Adjustable : 0.8~1×In
�Fixed magnetic
400A ... 8000A tripping currents
�Applicable to TD125U (Q) ... TS800U (Q) frames
Adjustable thermal, adjustable magnetic trip units
ATU
�Adjustable thermal
160A ... 800A rated currents
ATU
Adjustable : 0.8~1×In
�Adjustable magnetic
800A ... 8000A tripping currents
Adjustable : 5~10×In
�Applicable to TS250U (Q) ... TS800U (Q) frames
0.9
0.8
7
8
6
1
9
5
Ir
10
Im
A-2-4
MCCBs for power distribution
For Nuclear power plant
Thermal magnetic trip
FTU, FMU for TD125U (Q)
Configuration
Trip identification
Ratings (A), In at 40°C
Number of pole
Short circuit protection (magnetic)
Setting current, Im
Overload protection (thermal)
Setting current, Ir
TD125U (Q) FTU
- Fixed thermal & magnetic trip unit
FTU
Im=1250A
125A
TD125U (Q) FMU
t
0.9
Ir Im
0.8
1
TD125U (Q) FMU
- Adjustable thermal & fixed magnetic trip unit
0.9
FMU
0.8
1
Im=1250A
Ir Im
A-2-5
125A
0
Ir
Im
I
For Nuclear power plant
MCCBs for power distribution
Thermal magnetic trip
FTU, FMU for TD125U (Q)
Characteristics
Thermal magnetic trip units(FTU/FMU) ... TD125U (Q)
Rating(A)
at 40℃ In
15
20
30
40
50
60
80
100
125
TD125U (Q)
●
●
●
●
●
●
●
●
●
Overload protection(thermal)
Current setting(A) Ir
FTU
Fixed
FMU
Adjustable 0.8, 0.9, 1×In (3 settings)
Short - circuit protection(magnetic)
Current setting(A) Im
FTU
Fixed 400A
Fixed 10×In
FMU
Fixed 400A
Fixed 10×In
Catalogue numbering system
TD125U (Q)
FMU
Trip unit function
- FTU : Fixed thermal & magnetic unit
- FMU : Adjustable thermal, fixed magnetic unit
MCCB frame type
- TD125U (Q) : TD125NU (Q), TD125HU (Q)
A-2-6
For Nuclear power plant
MCCBs for power distribution
Thermal magnetic trip
FTU, FMU for TD125U (Q)
Setting details
Thermal overload protection
Trip unit type
Setting
Trip unit rating, In (A)
Ir
15
20
30
40
50
60
80
100
125
TD125U (Q) FTU
Fixed
15
20
30
40
50
60
80
100
125
TD125U (Q) FMU
0.8
-
-
-
32
40
48
64
80
100
0.9
-
-
-
36
45
54
72
90
112.5
1
-
-
-
40
50
60
80
100
125
Magnetic short-circuit protection
Trip unit type
Setting
current, Ir
A-2-7
current, Im
Trip unit rating, In (A)
15
20
30
40
50
60
80
100
125
Fixed
In×10
400
400
400
400
500
600
800
1000
1250
0.8×In
Fixed
In×10
-
-
-
400
500
600
800
1000
1250
0.9×In
Fixed
In×10
-
-
-
400
500
600
800
1000
1250
1.0×In
Fixed
In×10
-
-
-
400
500
600
800
1000
1250
TD125U (Q) FTU
TD125U (Q) FMU
Setting
For Nuclear power plant
MCCBs for power distribution
Thermal magnetic trip
FTU, FMU for TS250U (Q)
ATU for TS250U (Q)
Configuration
Trip identification
Ratings (A), In at 40°C
Number of pole
Short circuit protection (magnetic)
Setting current, Im
Overload protection (thermal)
Setting current, Ir
TS250U (Q) FTU
- Fixed thermal fixed magnetic trip unit
TS250U (Q) FMU
FTU
Im=2500A
Ir
Im
TS250U (Q) FMU
- Adjustable thermal fixed magnetic trip unit
TS250U (Q) ATU
t
Short circuit protection
(magnetic)
0.9
0.8
TS250U (Q) ATU
- Adjustable thermal adjustable magnetic trip unit
1
Short circuit protection
(magnetic)
7
ATU
0.8
7
8
5
6
1
10
9
5
Ir
8
9
6
0.9
10
0
Ir
Im
I
Im
A-2-8
For Nuclear power plant
MCCBs for power distribution
Thermal magnetic trip
FTU, FMU for TS250U (Q)
ATU for TS250U (Q)
Characteristics
Thermal magnetic trip units(FTU/FMU) ... TS250U (Q)
Rating(A)
FTU
FMU
FTU
FTU/FMU
FTU
FTU/FMU
at 40℃ In
150
160
175
200
225
250
TS250U (Q)
●
●
●
●
●
●
Overload protection(thermal)
Current setting(A) Ir
FTU
Fixed
FMU
Adjustable 0.8 to×In
ATU
Adjustable 0.8 to×In
Short - circuit protection(magnetic)
Current setting(A) Im
FTU
Fixed 10×In
FMU
Fixed 10×In
ATU
Adjustable 5, 6, 7, 8, 9, 10×In (6 settings)
Catalogue numbering system
TS250U (Q) FTU
Trip unit function
- FTU: Fixed thermal, fixed magnetic unit
MCCB frame type
-TS250U (Q): TS250NU (Q), TS250HU (Q)
TS250U (Q) FMU
Trip unit function
- FMU: Adjustable thermal, fixed magnetic unit
MCCB frame type
- TS250U (Q): TS250NU (Q), TS250HU (Q)
TS250U (Q) ATU
Trip unit function
- ATU: Adjustable thermal, adjustable magnetic unit
MCCB frame type
- TS250U (Q): TS250NU (Q), TS250HU (Q)
The trip unit ATU is available from 125A
A-2-9
For Nuclear power plant
MCCBs for power distribution
Thermal magnetic trip
FTU, FMU for TS250U (Q)
ATU for TS250U (Q)
Setting details
Thermal overload protection
Trip unit type
Setting
Trip unit rating, In (A)
Ir
150
160
175
200
225
250
TS250U (Q) FTU
Fixed
150
-
175
200
225
250
TS250U (Q) FMU
0.8
-
128
-
160
-
200
0.9
-
144
-
180
-
225
TS250U (Q) ATU
1
-
160
-
200
-
250
0.8
-
128
-
160
-
200
0.9
-
144
-
180
-
225
1
-
160
-
200
-
250
Magnetic short-circuit protection
Trip unit type
Setting
Setting
current, Ir
current, Im
TS250U (Q) FTU
TS250U (Q) FMU
Trip unit rating, In (A)
150
160
175
200
225
250
Fixed
In×10
1500
-
1750
2000
2250
2500
0.8×In
Fixed
In×10
-
-
-
2000
-
2500
0.9×In
Fixed
In×10
-
-
-
2000
-
2500
1.0×In
Fixed
In×10
-
-
-
2000
-
2500
In×5
-
800
-
1000
-
1250
In×6
-
960
-
1200
-
1500
In×7
-
1120
-
1400
-
1750
In×8
-
1280
-
1600
-
2000
TS250U (Q) ATU
0.8×In
0.9×In
1.0×In
Adjustable
Adjustable
Adjustable
In×9
-
1440
-
1800
-
2250
In×10
-
1600
-
2000
-
2500
In×5
-
800
-
1000
-
1250
In×6
-
960
-
1200
-
1500
In×7
-
1120
-
1400
-
1750
In×8
-
1280
-
1600
-
2000
In×9
-
1440
-
1800
-
2250
In×10
-
1600
-
2000
-
2500
In×5
-
800
-
1000
-
1250
In×6
-
960
-
1200
-
1500
In×7
-
1120
-
1400
-
1750
In×8
-
1280
-
1600
-
2000
In×9
-
1440
-
1800
-
2250
In×10
-
1600
-
2000
-
2500
A-2-10
For Nuclear power plant
MCCBs for power distribution
Thermal magnetic trip
FTU, FMU, ATU for TS400U (Q)
Configuration
Trip identification
Ratings (A), In at 40°C
Number of pole
Short circuit protection (magnetic)
Setting current, Im
Overload protection (thermal)
Setting current, Ir
TS400U (Q) FTU
- Fixed thermal fixed magnetic trip unit
TS400U (Q) FMU
FTU
t
Im=4000A
Ir
400A
0.9
0.8
1
Im
TS400U (Q) FMU
- Adjustable thermal fixed magnetic trip unit
0
Ir
Im
I
FMU
0.9
0.8
400A
Im=4000A
1
Ir
TS400U (Q) ATU
Im
t
0.9
0.8
TS400U (Q) ATU
1
- Adjustable thermal adjustable magnetic trip unit
7
ATU
6
0.9
0.8
7
6
1
A-2-11
Im
10
9
5
Ir
9
5
400A
8
8
10
0
Ir
Im
I
MCCBs for power distribution
For Nuclear power plant
Thermal magnetic trip
FTU, FMU, ATU for TS400U (Q)
Characteristics
Thermal magnetic trip units(FTU/FMU/ATU) ... TS400U (Q)
Rating(A)
FTU/FMU/ATU
FTU
FTU/FMU/ATU
at 40℃ In
300
350
400
TS400U (Q)
●
●
●
Overload protection(thermal)
Current setting(A) Ir
FTU
In=Ir (Fixed)
FMU
Adjustable 0.8, 0.9, 1×In (3 settings)
ATU
Adjustable 0.8, 0.9, 1×In (3 settings)
Short - circuit protection(magnetic)
Current setting(A) Im
FTU
Fixed 10×In
FMU
Fixed 10×In
ATU
Adjustable 5, 6, 7, 8, 9,10×In(6 settings)
Catalogue numbering system
TS400U (Q) ATU
Trip unit function
- FTU : Fixed thermal & magnetic unit
- FMU : Adjustable thermal & fixed magnetic unit
- ATU : Adjustable thermal & adjustable magnetic unit
MCCB frame type
- TS400U (Q) : TS400NU (Q), TS400HU (Q)
A-2-12
For Nuclear power plant
MCCBs for power distribution
Thermal magnetic trip
FTU, FMU, ATU for TS400U (Q)
Setting details
Thermal overload protection
Trip unit type
Setting
Trip unit rating, In (A)
Ir
300
350
400
TS400U (Q) FTU
Fixed
300
350
400
TS400U (Q) FMU
0.8
240
-
320
0.9
270
-
360
TS400U (Q) ATU
1
300
-
400
0.8
240
-
320
0.9
270
-
360
1
300
-
400
Magnetic short-circuit protection
Trip unit type
Setting
Setting
current, Ir
current, Im
TS400U (Q) FTU
TS400U (Q) FMU
350
400
Fixed
In×10
3000
3500
4000
0.8×In
Fixed
In×10
3000
-
4000
0.9×In
Fixed
In×10
3000
-
4000
1.0×In
Fixed
In×10
3000
-
4000
In×5
1500
-
2000
In×6
1800
-
2400
In×7
2100
-
2800
In×8
2400
-
3200
TS400U (Q) ATU
0.8×In
0.9×In
1.0×In
A-2-13
Trip unit rating, In (A)
300
Adjustable
Adjustable
Adjustable
In×9
2700
-
3600
In×10
3000
-
4000
In×5
1500
-
2000
In×6
1800
-
2400
In×7
2100
-
2800
In×8
2400
-
3200
In×9
2700
-
3600
In×10
3000
-
4000
In×5
1500
-
2000
In×6
1800
-
2400
In×7
2100
-
2800
In×8
2400
-
3200
In×9
2700
-
3600
In×10
3000
-
4000
For Nuclear power plant
MCCBs for power distribution
Thermal magnetic trip
FTU, FMU, ATU for TS800U (Q)
Configuration
Trip identification
Ratings (A), In at 40°C
Number of pole
Short circuit protection (magnetic)
Setting current, Im
Overload protection (thermal)
Setting current, Ir
TS800U (Q) FTU
- Fixed thermal fixed magnetic trip unit
FTU
TS800U (Q) FMU
Im=8000A
Ir
800A
t
0.9
Im
0.8
1
TS800U (Q) FMU
- Adjustable thermal fixed magnetic trip unit
0
FMU
0.9
0.8
Im=8000A
1
Ir
Ir
Im
I
800A
TS800U (Q) ATU
Im
t
0.9
0.8
1
TS800U (Q) ATU
- Adjustable thermal adjustable magnetic trip unit
7
ATU
6
0.9
0.8
7
6
1
9
5
10
9
5
Ir
800A
8
8
10
0
Ir
Im
I
Im
A-2-14
For Nuclear power plant
MCCBs for power distribution
Thermal magnetic trip
FTU, FMU, ATU for TS800U (Q)
Characteristics
Thermal magnetic trip units(FTU/FMU/ATU) ... TS800U (Q)
Rating(A)
FTU/FMU/ATU
FTU/FMU/ATU
FTU
FTU/FMU/ATU
at 40℃ In
500
600
700
800
TS800U (Q)
●
●
●
●
Overload protection(thermal)
Current setting(A) Ir
FTU
Fixed
FMU
Adjustable 0.8, 0.9,1×In (3 settings)
ATU
Adjustable 0.8, 0.9,1×In (3 settings)
Short - circuit protection(magnetic)
Current setting(A) Im
FTU
Fixed 10×In
FMU
Fixed 10×In
ATU
Adjustable 5, 6, 7, 8, 9, 10×In (6 settings)
Catalogue numbering system
TS800U (Q) ATU
Trip unit function
- FTU : Fixed thermal & magnetic unit
- FMU : Adjustable thermal & fixed magnetic unit
- ATU : Adjustable thermal & adjustable magnetic unit
MCCB frame type
- TS800U (Q) : TS800NU (Q), TS800HU (Q)
A-2-15
For Nuclear power plant
MCCBs for power distribution
Thermal magnetic trip
FTU, FMU, ATU for TS800U (Q)
Setting details
Thermal overload protection
Trip unit type
Setting
Trip unit rating, In (A)
Ir
500
600
700
800
TS800U (Q) FTU
Fixed
500
600
700
800
TS800U (Q) FMU
0.8
400
480
-
640
0.9
450
540
-
720
TS800U (Q) ATU
1
500
600
-
800
0.8
400
480
-
640
0.9
450
540
-
720
1
500
600
-
800
Magnetic short-circuit protection
Trip unit type
Setting
Setting
current, Ir
current, Im
TS800U (Q) FTU
TS800U (Q) FMU
Trip unit rating, In (A)
500
600
700
800
Fixed
In×10
5000
6000
7000
8000
0.8×In
Fixed
In×10
5000
6000
-
8000
0.9×In
Fixed
In×10
5000
6000
-
8000
1.0×In
Fixed
In×10
5000
6000
-
8000
In×5
2500
3000
-
2000
In×6
3000
3600
-
4800
In×7
3500
4200
-
5600
In×8
4000
4800
-
6400
TS800U (Q) ATU
0.8×In
0.9×In
1.0×In
Adjustable
Adjustable
Adjustable
In×9
4500
5400
-
7200
In×10
5000
6000
-
8000
In×5
2500
3000
-
2000
In×6
3000
3600
-
4800
In×7
3500
4200
-
5600
In×8
4000
4800
-
6400
In×9
4500
5400
-
7200
In×10
5000
6000
-
8000
In×5
2500
3000
-
2000
In×6
3000
3600
-
4800
In×7
3500
4200
-
5600
In×8
4000
4800
-
6400
In×9
4500
5400
-
7200
In×10
5000
6000
-
8000
A-2-16
MCCBs for motor protection
A-2-17
For Nuclear power plant
For Nuclear power plant
MCCBs for motor protection
TS series
TS250U (Q)
Frame size
[AF]
250
No. of Poles
3
Maximum voltage ratings
[V AC]
Rated current
1.6, 3.2, 6.3∙
∙
∙
∙
∙220 Note)
[A]
Short circuit
withstand ratings
600
NU
HU
120V AC
-
-
240V AC
50
100
480V AC
35
65
600V AC
10
18
Catalog number of wire connector
LSCA1 (1.6~12A), LSCA2 (20~220A)
This product is designed for Nuclear power plant.
You can identify by “(Q)” sticker on the product, however, the nameplate does NOT contain any information to identify.
A-2-18
For Nuclear power plant
MCCBs for motor protection
Intantaneous trip circuit break (ICB)
MTU for TS250U (Q)
For the protection of motors from 1.6 to 250kW(400V),
TS250U (Q) circuit Breakers must be equipped with a
special trip unit MTU adjustable thresholds.
L1
L2
L3
1
3
5
2
4
6
1
3
5
2
4
6
Breaker
Contactor
O/L
T1
T2
T3
M
Motor
Magnetic only
release
Configuration
Trip unit identification
Trip unit rating, In
Magnetic setting for short-circuit
protection
Catalogue numbering system
TS250U (Q) MTU
Magnetic only trip unit
MCCB frame type
- TS250U (Q): TS250NU (Q), TS250HU (Q)
A-2-19
For Nuclear power plant
MCCBs for motor protection
Intantaneous trip circuit break (ICB)
MTU for TS250U (Q)
Characteristics
Magnetic trip units(MTU) Note)
Rating(A)
NU/HU
In
TS250U (Q)
TS250U (Q)
1.6
3.2
6.3
12
20
32
50
63
100
160
220
●
●
●
●
●
●
●
●
●
●
●
Short - circuit protection(magnetic)
Pick - up
Im
setting
6..12×In (6 Point)
Note) TS250U (Q), Rated Currnet 1.6~63A products will provide only the NU Type
Setting details
In
1.6
3.2
6.3
12
20
32
Trip unit rating, In (A)
10
20
40
70
120
190
12
24
48
84
144
228
14
28
56
98
168
266
16
32
64
112
192
304
In
18
36
72
126
216
342
20
40
80
140
240
380
50
63
100
160
220
Trip unit rating, In (A)
300
360
400
480
600
720
960 1152
1320 1584
420
480
540
600
560
640
720
800
840 960 1080 1200
1344 1536 1728 1920
1848 2112 2376 2640
TS250U (Q) MTU
MTU
1848
1584
ICB
1320
2112
2376
220A
t
Im = 6...12×In
2640
Im
14
12
10
0
Im
16
18
20
I
A-2-20
TD & TS MCCB Index
A-3. Accessories
Electrical auxiliaries
Undervoltage release, UVT
Shunt release, SHT
Auxiliary switch (AX), Alarm switch (AL)
Possible configuration of electrical auxiliaries
A-3-1
A-3-2
A-3-3
A-3-4
Rotary handles
Extended handles
Flange Handle
A-3-5
A-3-5
Locking devices
Removable locking device
Fixed locking device
A-3-6
A-3-7
Interlock
Mechanical interlocking device
A-3-8
For Nuclear power plant
Accessories
Electrical auxiliaries
The following devices are installed into all TD &
TS circuit breakers regardless of frame size.
And, the electrical auxiliaries can be easily
installed in the accessory compartment of the
circuit breakers which is cassette type.
Undervoltage release, UVT
The undervoltage release automatically opens
a circuit breaker when voltage drops to a value
ranging between 35% to 70% of the line
voltage. The operation is instantaneous, and
after tripping, the circuit breaker cannot be reclosed again until the voltage returns to 85% of
line voltage.
UVT
Continuously energized, the undervoltage
release must be operating before the circuit
breaker can be closed. The undervoltage
release can be easily installed in the left
accessory compartment of the Susol TD and
TS circuit-breakers.
�Range of tripping voltage: 0.35 ~ 0.7Vn
�MCCB making is possible voltage: 0.85Vn (exceed)
�Frequency (only AC): 45Hz ~ 65Hz
Technical data
Consumption
Control voltage (V)
Power
consumption
DC (W)
mA
AC/DC 24V
0.64
0.65
27
AC/DC 48V
1.09
1.10
23
AC/DC 110~130V
0.73
0.75
5.8
AC 200~240V/DC 250V
1.21
1.35
5.4
AC 380~440V
1.67
-
3.8
AC 440~480V
1.68
-
3.5
Max.opening time (ms)
Tightening torque of terminal screw
50
8.2kgf∙cm
Transformer operating voltage (V)
- Drop (Circuit breaker trips)
- Rise (Circuit breaker can be switched on)
8.2kgf∙cm
A-3-1
Applicable
AC (VA)
0.7~1.35Vn
~0.85Vn
MCCBs
TD125U (Q),
TS250U (Q),
TS400U (Q),
TS800U (Q)
For Nuclear power plant
Accessories
Electrical auxiliaries
Shunt release, SHT
The shunt release opens the mechanism in
response to an externally applied voltage
signal. The releases include coil clearing
contacts that automatically clear the signal
circuit when the mechanism has tripped.
The shunt release can be installed in the left
accessory compartment of the Susol TD & TS
circuit-breakers.
�Range of operational voltage: 0.7 ~ 1.1Vn
�Frequency (only AC): 45Hz ~ 65Hz
SHT
Technical data
Consumption
Control voltage (V)
AC (VA)
DC 12V
DC (W)
Applicable
mA
MCCBs
-
0.36
30
Power
AC/DC 24V
0.58
0.58
24
consumption
AC/DC 48V
1.22
1.23
25
TD125U (Q),
AC/DC 110~130V
1.36
1.37
10.5
TS250U (Q),
AC 220~240V/DC250V
1.80
1.88
7.5
TS400U (Q),
AC 380~500V
1.15
-
2.3
TS800U (Q)
Max.opening time (ms)
50
Tightening torque of terminal screw
8.2kgf∙cm
8.2kgf∙cm
Click
A-3-2
For Nuclear power plant
Accessories
Electrical auxiliaries
Auxiliary switch (AX), Alarm switch (AL)
Auxiliary switch (AX)
Auxiliary switch is for applications requiring
remote “ON” and “OFF” indication.
Each switch contains two contacts having a
AX
Alarm switch (AL)
Alarm switches offer provisions for immediate
audio or visual indication of a tripped breaker
due to overload, short circuit, shunt trip, or
undervoltage release conditions.
They are particularly useful in automated
plants where operators must be signaled about
changes in the electrical distribution system.
common connection.
One is open and the other closed when the
circuit breaker is open, and vice-versa.
This switch features a closed contact when the
circuit breaker is tripped automatically. In other
words, this switch does not function when the
breaker is operated manually.
Its contact is open when the circuit breaker is
reset.
Contact operation
MCCB
AL
Position
ON
OFF
TRIP
AXa1
AXa1
AXc1
of AX
Position
of AL
AXc1
AXb1
AXb1
AXa1
AXa1
AXc1
AXc1
AXb1
AXb1
Technical data
Conventional thermal current Ith
Rated operational current Ie
5A
with rated operational voltage Ue
- Altemating current 50/60Hz AC
- Direct current DC
A-3-3
Ie
Voltage
Resistance
Inductance
125V
5
3
250V
3
2
500V
-
-
30V
4
3
125V
0.4
0.4
250V
0.2
0.2
TD125U (Q),
TS250U (Q),
TS400U (Q),
TS800U (Q)
For Nuclear power plant
Rotary handles
Extended handles
The rotary handle operating mechanism is
available in either the direct version or in the
extended version on the compartment door.
Extended rotary handles
MCCB
Extended Handle
TD125U (Q)
EHU1
TS250U (Q)
EHU2
TS400U (Q)
EHU3
TS800U (Q)
EHU4
Flange Handle
operated for its own flexibility And, also can be
selected various length (4 types) at each
frames.
The flange hanle is operated by cable and can
be applied on the compartment door.
This device is designed to easily installed and
Flange handle
(Cable operating handle)
MCCB
Flange Handle
TD125U (Q)
FH1
TS250U (Q)
FH2
TS400U (Q)
FH3
TS800U (Q)
FH4
A-3-4
For Nuclear power plant
Accessories
Electrical auxiliaries
Possible configuration of electrical auxiliaries
Maximum possibilities
Phase
Accessory
R (Left)
TS250U (Q)
TS400U (Q)
TS800U (Q)
AX
-
1
3
3
AL
1
1
-
-
SHT or UVT
1
1
1
1
AX
2
1
-
-
AL
-
-
1
2
T (Right)
TD125U (Q)
TD125U (Q)
TS250U (Q)
TS400U (Q)
TS800U (Q)
AL
AX AX
AX
AX
AL
SHT/
UVT
AX AX AX
SHT/
UVT
AL
AX AX AX
SHT/
UVT
SHT/
UVT
A-3-5
AL AL
TD &TS MCCB Index
A-5. Mounting & Connection
Fixed mounting
A-5-1
Connecting terminal & conductor
A-5-1
Safety clearance
A-5-2
For Nuclear power plant
Mounting & Connection
Fixed mounting
Susol TD and TS circuit-breakers can be
directly connected to the mounting plate.
If busbars or terminals are used to connect the
TD125U (Q)
circuit breaker on the back of the mounting
plate, the appropriate safety clearances must
be observed.
TS250U (Q)
TS400U (Q)
TS800U (Q)
2/3Pole: 2EA
(NO.10-24
UNC-2A, L120)
2/3Pole: 2EA
(1/4"-20
UNC-2A, L140)
Screw for mounting
2/3Pole: 2EA
(NO.8-32 UNC-2A, L100)
Screw for connection
of terminals,
2Pole:4EA(M5×L16) 2Pole:4EA(M8×L20)
3Pole:6EA(M5×L16) 3Pole:6EA(M8×L20)
Torque:
Max 78kgf∙cm
Torque:
Max 147kgf∙cm
Connecting terminal & conductor
Terminal (mm)
Conductor (mm)
8
18
TD125U (Q)
23
M5×16
22
Max 78kgf∙cm
20
TS250U (Q)
28
∅>8
∅>8
M8×20
21
≤10
22
Note) TS400U (Q), TS800U (Q) Only for lug
A-5-1
Max 147kgf∙cm
≤10
≤20
≤20
For Nuclear power plant
Mounting & Connection
Safety clearance
When a short circuit interruption occur, high
temperatures pressures are present in and
above the arc chambers of the circuit-breaker.
In order to allow the pressure to be distributed
and to prevent fire and arcing or short-circuit
currents, safety clearances are required.
When installing a circuit breaker, safety
clearances must be kept between the breaker
and panels, bars and other protection devices
installed nearby. These safety clearances are
depend on the ultimate breaking capacity and
are defined by tests carried out in accordance
with standard UL489.
W1
H2
H1
D1
D2
W2
240V
480V
240V
W1, W2 (inch)
480V
H1, H2 (inch)
TD125NU/HU/NA (Q)
0.6
1.0
1.2
1.4
TS250NU/HU/NA (Q)
0.6
1.0
1.2
1.4
TS400NU/HU/NA (Q)
0.6
0.8
2.0
2.4
TS800NU/HU/NA (Q)
0.8
1.8
3.1
3.9
240V / 480V / 600V
240V / 480V / 600V
D1 (mm)
D1 (inch)
D2 (mm)
D2 (inch)
TD125NU/HU/NA (Q)
87
3.4
100
3.9
TS250NU/HU/NA (Q)
89
3.5
130
5.1
TS400NU/HU/NA (Q)
112
4.4
180
7
TS800NU/HU/NA (Q)
137
5.4
234
9.2
A-5-2
TD &TS MCCB Index
A-6. Characteristics curves
Circuit breakers with thermal-magnetic trip units
TD125U (Q)
A-6-1
TS250U (Q)
A-6-2
TS400U (Q)
A-6-4
TS800U (Q)
A-6-6
Specific let-through energy curves
240V
A-6-9
480V
A-6-10
600V
A-6-11
Current-limiting curves
240V
A-6-12
480V
A-6-13
600V
A-6-14
For Nuclear power plant
Characteristics curves
Circuit breakers with thermal-magnetic trip units
10000
TD125U (Q)
120
100
FTU
5000
50
FMU
Minutes
15~30A
2000
1000
FTU:Ir=1 x In
FMU:Ir=0.8~1xIn
700
10
7
400
200
3
100
60
1
1
Second
Operating time
10
In:15A -> Im=400A
In:20A -> Im=400A
FTU/FMU:Im=10xIn
Min. 400A
0.1
In:30A -> Im=400A
0.01
0.001
0.5
0.8
1
2
3
4
5 6 7 8
10
20
30
X Normal Current In (I/Ir)
Rated current
compensation ratio(%)
150
100
50
0
10
20
30
40
Ambient temperature(40°C)
A-6-1
50
40 50
70
100
200
300
For Nuclear power plant
Characteristics curves
Circuit breakers with thermal-magnetic trip units
10000
TD125U (Q)
120
100
FTU
5000
50
FMU
Minutes
1000
FTU:Ir=1 x In
FMU:Ir=0.8~1xIn
700
10
7
400
200
3
100
60
1
10
Second
1
FTU/FMU:Im=10xIn
Min. 400A
0.1
0.01
0.001
0.5
0.8
1
2
3
4
5 6 7 8
10
20
30
40 50
70
100
200
300
X Normal Current In (I/Ir)
150
Rated current
compensation ratio(%)
Operating time
40~50A
2000
100
50
0
10
20
30
40
50
Ambient temperature(40°C)
A-6-2
For Nuclear power plant
Characteristics curves
Circuit breakers with thermal-magnetic trip units
10000
TD125U (Q)
120
100
FTU
5000
50
FMU
Minutes
60~100A
2000
1000
FTU:Ir=1 x In
FMU:Ir=0.8~1xIn
700
10
7
400
200
3
100
60
1
1
Second
Operating time
10
FTU/FMU:Im=10xIn
Min. 400A
0.1
0.01
0.001
0.5
0.8
1
2
3
4
5 6 7 8
10
20
30
X Normal Current In (I/Ir)
Rated current
compensation ratio(%)
150
100
50
0
10
20
30
40
Ambient temperature(40°C)
A-6-3
50
40 50
70
100
200
300
For Nuclear power plant
Characteristics curves
Circuit breakers with thermal-magnetic trip units
10000
TD125U (Q)
120
100
FTU
5000
50
FMU
Minutes
1000
FTU:Ir=1 x In
FMU:Ir=0.8~1xIn
700
10
7
400
200
3
100
60
1
10
Second
1
FTU/FMU:Im=10xIn
Min. 400A
0.1
0.01
0.001
0.5
0.8
1
2
3
4
5 6 7 8
10
20
30
40 50
70
100
200
300
X Normal Current In (I/Ir)
150
Rated current
compensation ratio(%)
Operating time
125A
2000
100
50
0
10
20
30
40
50
Ambient temperature(40°C)
A-6-4
Characteristics curves
For Nuclear power plant
Circuit breakers with thermal-magnetic trip units
TS250U (Q)
FTU
FMU
150~250A
FTU:Ir=1 × In
FMU:Ir=0.8~1×In
FTU/FMU:Im=10×In
pressure tripping
t
10ms
A-6-5
Characteristics curves
For Nuclear power plant
Circuit breakers with thermal-magnetic trip units
TS250U (Q)
ATU
160~250A
ATU:Ir=0.8~1×In
ATU:Im=5~10×In
pressure tripping
t 10ms
0.5
A-6-6
Characteristics curves
For Nuclear power plant
Circuit breakers with thermal-magnetic trip units
TS400U (Q)
FTU
FMU
300~400A
FTU:Ir=1 × In
FMU:Ir=0.8~1×In
FTU/FMU:Im=10 ×In
pressure tripping
t 10ms
A-6-7
Characteristics curves
For Nuclear power plant
Circuit breakers with thermal-magnetic trip units
TS400U (Q)
ATU
300~400A
ATU:Ir=0.8~1×In
ATU:Im=5~10 ×In
pressure tripping
t 10ms
A-6-8
Characteristics curves
For Nuclear power plant
Circuit breakers with thermal-magnetic trip units
TS800U (Q)
FTU
FMU
500~800A
FTU:Ir=1 × In
FMU:Ir=0.8~1×In
FTU/FMU:Im=10×In
pressure tripping
t 10ms
A-6-9
Characteristics curves
For Nuclear power plant
Circuit breakers with thermal-magnetic trip units
TS800U (Q)
ATU
500~800A
ATU:Ir=0.8~1×In
ATU:Im=5~10 ×In
pressure tripping
t 10ms
A-6-10
For Nuclear power plant
Characteristics curves
Circuit breakers with magnetic only trip units
10000
TS250U (Q)
120
100
Magnetic only
5000
50
MTU
Minutes
1.6~63A
2000
1000
700
10
7
Thermal withstand
400
200
3
100
60
1
MTU Type
63A:400~800A
50A:300~600A
32A:190~380A
20A:120~240A
12A:70 ~140A
6.3A:40 ~80A
3.2A:20 ~40A
1.6A:10 ~20A
MTU:Im=6~12xIn
1
Second
Operating time
10
0.1
pressure tripping
t 10ms
0.01
0.001
0.5
0.8
1
2
3
4
5 6 7 8
10
20
30
X Normal Current In (I/Ir)
A-6-11
40 50
70
100
200
300
For Nuclear power plant
Characteristics curves
Circuit breakers with magnetic only trip units
10000
TS250U (Q)
120
100
Magnetic only
5000
50
MTU
Minutes
1000
700
10
7
Thermal withstand
400
200
3
100
60
1
10
1
Second
Operating time
100~220A
2000
MTU:Im=6~12 xIn
0.1
pressure tripping
t 10ms
0.01
0.001
0.5
0.8
1
2
3
4
5 6 7 8
10
20
30
40 50
70
100
200
300
X Normal Current In (I/Ir)
A-6-12
Characteristics curves
For Nuclear power plant
Specific let-through energy curves
240V
Thermal stress
TS800U
TS400U
TS250U
TD125U
A-6-13
Characteristics curves
For Nuclear power plant
Specific let-through energy curves
480V
Thermal stress
TS800U
TS400U
TS250U
TD125U
A-6-14
Characteristics curves
For Nuclear power plant
Specific let-through energy curves
600V
Thermal stress
TS800U
TS400U
TS250U
TD125U
A-6-15
Characteristics curves
For Nuclear power plant
Current-limiting curves
240V
Peak current
TS800U
TS400U
TS250U
TD125U
A-6-16
Characteristics curves
For Nuclear power plant
Current-limiting curves
480V
Peak current
TS800U
TS400U
TS250U
TD125U
A-6-17
For Nuclear power plant
Characteristics curves
Current-limiting curves
600V
Peak current
TS800U
TS400U
TS250U
TD125U
A-6-18
TD & TS MCCB Index
A-7. Dimensions
TD125U (Q)
A-7-1
TS250U (Q)
A-7-2
TS400U (Q)
A-7-3
TS800U (Q)
A-7-4
Mechanical interlocking device
A-7-13
MIT13, MIT23, MIT33, MIT43
Mechanical interlocking device
Mounting dimension for MIT
A-7-14
For Nuclear power plant
Overall dimensions
TD125U (Q)
Dimensions : inch (mm)
3.035 (77.1)
2.958 (75.15)
2.716 (69)
3.543 (90)
0.192 (4.9)
0.81 (20.45)
0.846 (21.5)
6.456 (164)
2.362 (60)
1.496 (38)
1.062 (27)
3.389 (86.1)
0.95 (24.2)
0.59 (15)
3.496 (88.81)
1.181 (30)
3.625 (92.1)
1.181 (30)
4.212 (107)
0.578 (14.7)
Circuit breaker mounting
Circuit breaker
bolt drilling plan
escutcheon dimensions
C
L
CL
#8-32UNC Tap
(2holes)
1.141 (29)
A-7-1
2.519 (64)
4.212 (107)
CL
1.535 (39)
C
L
0.59 (15)
For Nuclear power plant
Overall dimensions
TS250U (Q)
Dimensions : inch (mm)
3.385 (86)
2.952 (75)
2.716 (69)
4.133 (105)
0.423 (10.75)
3.937 (100)
7.007 (178)
2.362 (60)
1.496 (38)
0.196 (5)
0.964 (24.5)
1.062 (27)
1.09 (27.8)
0.688 (17.5)
1.377 (35)
Circuit breaker mounting
Circuit breaker
bolt drilling plan
escutcheon dimensions
CL
0.69 (17.5)
CL
CL
2.677 (68)
1.259 (32)
1.102 (28)
4.921 (125)
2.5 (63.5)
CL
3.661 (93)
4.318 (109.7)
1.377 (35)
0.629 (16)
3.546 (90.1)
#8-32 UNC Tap
(2 Holes)
A-7-2
For Nuclear power plant
Overall dimensions
TS400U (Q)
Dimensions : inch (mm)
4.33 (110)
3.838 (97.5)
5.511 (140)
11.496 (292)
6.535 (166)
4.015 (102)
2.795 (71)
2.322 (59)
0.314 (8)
1.653 (42)
3.267 (83)
3.11 (79)
1.3 (33)
0.925 (23.5)
1.83 (46.5)
1.082 (27.5)
4.645 (118)
1.83 (46.5)
4.842 (123)
6.181 (157)
Circuit breaker mounting
Circuit breaker
bolt drilling plan
escutcheon dimensions
CL
CL
2.44 (62)
#10-24 UNC Tap
(2 Holes)
A-7-3
4.488 (114)
CL
CL
1.653 (42)
7.874 (200)
0.885 (22.5)
For Nuclear power plant
Overall dimensions
TS800U (Q)
Dimensions : inch (mm)
5.846 (148.5)
5.511 (140)
3.149 (80)
2.125 (54)
8.267 (210)
3.543 (90)
7.818 (198.6)
0.433 (11)
1.862 (47.3)
3.279 (83.3)
3.149 (80)
4.33 (110)
16.85 (428)
4.566 (116)
2.755 (35)
2.755 (70)
2.755 (70)
2.125 (54)
4.685 (119)
5.039 (128)
5.314 (135)
7.775 (197.5)
Circuit breaker mounting
Circuit breaker
bolt drilling plan
escutcheon dimensions
CL
CL
5.25 (133.3)
10.944 (278)
CL
3.188 (81)
3.279 (83.3)
CL
1.377 (35)
1
# 4"-20 UNC Tap
(2Holes)
A-7-4
For Nuclear power plant
Overall dimensions
Extended rotary handle
TD125U (Q)
Dimensions : inch (mm)
14.5 (368.3)
Min 14.5(368.3)
Max 26.5(673.1)-Shaft 24inch
Panel drilling
Way of installation
1.18 (30)
N
Ta o 8pp 32
Ho ing
les
)
(4
2)
(5
04 e)
2.
l
∅ (Ho
2.68 (68)
4.21 (107)
0.531 (13.5)
)
(5
)
19
0. oles
H
(2
∅
A-7-5
1.10 (28)
0.433 (11)
For Nuclear power plant
Overall dimensions
Extended rotary handle
TS250U (Q)
Dimensions : inch (mm)
14.54 (369.3)
Min 14.54 (369.3)
Max 26.54 (674.1)-Shaft 24inch
Panel drilling
1.39 (35.3)
0.79 (20)
1.38 (35)
2.68 (68)
4.90 (124.4)
∅
0.
1
Ho 9 (5
les )
)
No
Ta 8-32
p
(4H ping
ole
s)
(2
Way of installation
∅
2.0
(H 4 (5
ole 2)
)
0.433 (11)
A-7-6
For Nuclear power plant
Overall dimensions
Extended rotary handle
TS400U (Q)
Dimensions : inch (mm)
15.93 (404.6)
Min 15.93 (404.6)
Max 27.93 (709.4)-Shaft 24inch
Panel drilling
Way of installation
1.39 (35.3)
∅
0.
1.83 (46.5)
2.68 (68)
7.87 (200)
1.39 (35.4)
1
Ho 9 (5
les )
)
(2
∅
No
UN 10-32
Ta C-2A
p
(4H ping
ole
s)
(H
A-7-7
2.
04
ole (52
)
)
0.433 (11)
For Nuclear power plant
Overall dimensions
Extended rotary handle
TS800U (Q)
17.42 (442.5)
Dimensions : inch (mm)
Min 17.42 (442.5)
Max 29.42 (747.32)-Shaft 24inch
Panel drilling
Way of installation
2.22 (56.3)
∅
0.
1
Ho 9 (5
les )
)
0.57 (14.5)
2.76 (70)
2.68 (68)
10.94 (278)
(2
∅
2.
04
ole (52)
)
1
4
UN ''-2
Ta C- 0
(4 ppin 2A
Ho
g
les
)
(H
0.433 (11)
A-7-8
For Nuclear power plant
Overall dimensions
Flange handle
TD125U (Q)
Dimensions : inch (mm)
F
4.251 (108)
4.212
(107)
4.685 (119)
0.433 (11)
1.18
(30)
E
#8-32 UNC
Tap (4 Holes)
Panel drilling
Way of installation
E MAX
F "DOWN"
F "UP"
Table 1
Enclosure
Maximum “F” Dimension
Enclosure 60 cable
72 cable
FH1-60
FH1-72
10
25
30
10
17
31
20
34
12
24
29
12
17
31
19
33
16
23
28
16
17
28
19
30
18
22
27
18
17
28
19
30
20
21
26
20
16
26
18
28
24
20
25
24
14
26
16
28
30
19
24
30
11
24
13
26
36
18
23
36
6
21
8
22
Depth
A-7-9
Maximum “E” Dimension Table 2
Depth
Up Down Up Down
For Nuclear power plant
Overall dimensions
Flange handle
TS250U (Q)
1.377
(35)
F
4.921
(125)
4.251 (108)
0.433 (11)
4.685 (119)
2.5 (63.5)
Dimensions : inch (mm)
E
#8-32 UNC
Tap (4 Holes)
Panel drilling
Way of installation
E MAX
F "DOWN"
F "UP"
Table 1
Enclosure
Maximum “E” Dimension Table 2
Maximum “F” Dimension
Enclosure 60 cable
72 cable
FH2-60
FH2-72
10
25
30
10
17
31
20
34
12
24
29
12
17
31
19
33
16
23
28
16
17
28
19
30
18
22
27
18
17
28
19
30
20
21
26
20
16
26
18
28
24
20
25
24
14
26
16
28
30
19
24
30
11
24
13
26
36
18
23
36
6
21
8
22
Depth
Depth
Up Down Up Down
A-7-10
For Nuclear power plant
Overall dimensions
Flange handle
TS400U (Q)
Dimensions : inch (mm)
1.83 (46.5)
F
4.251 (108)
7.874 (200)
4.685 (119)
0.433 (11)
E
#10-24 UNC
Tap (4 Holes)
Panel drilling
Way of installation
E MAX
F "DOWN"
F "UP"
Table 1
Enclosure
Maximum “F” Dimension
Enclosure 60 cable
72 cable
FH3-60
FH3-72
10
25
30
10
17
31
20
34
12
24
29
12
17
31
19
33
16
23
28
16
17
28
19
30
18
22
27
18
17
28
19
30
20
21
26
20
16
26
18
28
24
20
25
24
14
26
16
28
30
19
24
30
11
24
13
26
36
18
23
36
6
21
8
22
Depth
A-7-11
Maximum “E” Dimension Table 2
Depth
Up Down Up Down
For Nuclear power plant
Overall dimensions
Flange handle
TS800U (Q)
Dimensions : inch (mm)
2.755 (70)
# 1 4"-20 UNC
Tap (4 Holes)
F
4.685 (119)
10.944
(278)
4.251 (108)
0.433 (11)
E
Panel drilling
Way of installation
E MAX
F "DOWN"
F "UP"
Table 1
Enclosure
Maximum “E” Dimension Table 2
Maximum “F” Dimension
Enclosure 60 cable
72 cable
FH4-60
FH4-72
10
25
30
10
17
31
20
34
12
24
29
12
17
31
19
33
16
23
28
16
17
28
19
30
18
22
27
18
17
28
19
30
20
21
26
20
16
26
18
28
24
20
25
24
14
26
16
28
30
19
24
30
11
24
13
26
36
18
23
36
6
21
8
22
Depth
Depth
Up Down Up Down
A-7-12
� For your safety, please read user's manual thoroughly before operating.
� Contact the nearest authorized service facility for examination, repair, or adjustment.
� Please contact a qualified service technician when you need maintenance.
Do not disassemble or repair by yourself!
Safety Instructions
� Any maintenance and inspection shall be performed by the personnel having expertise concerned.
ⓒ 2013. 08 LSIS Co.,Ltd. All rights reserved.
� HEAD OFFICE
LS Tower 1026-6, Hogye-dong, Dongan-gu,
Anyang-si, Gyeonggi-do 431-848, Korea
Tel. (82-2)2034-4887, 4873, 4918, 4148
Fax. (82-2)2034-4648
www.lsis.biz
� Global Network
�LSIS (Middle East) FZE �
�Dubai, U.A.E.
Address: LOB 19 JAFZA VIEW TOWER Room 205, Jebel Ali Freezone P.O. Box 114216, Dubai, United Arab Emirates
Tel: 971-4-886 5360 Fax: 971-4-886-5361 e-mail: dhleef@lsis.biz
�Dalian LSIS Co., Ltd. �
�Dalian, China
Address: No.15, Liaohexi 3-Road, Economic and Technical Development zone, Dalian 116600, China
Tel: 86-411-8273-7777 Fax: 86-411-8730-7560 e-mail: tangyh@lsis.com.cn
�LSIS (Wuxi) Co., Ltd. �
�Wuxi, China
Address: 102-A , National High & New Tech Industrial Development Area, Wuxi, Jiangsu, 214028, P.R.China
Tel: 86-510-8534-6666 Fax: 86-510-522-4078 e-mail: luw@lsis.com.cn
� CHEONG-JU PLANT
Cheong-Ju Plant #1, Song Jung Dong, Hung Duk Ku,
Cheong Ju, 361-720, Korea
�LSIS-VINA Co., Ltd. �
�Hanoi, Vietnam
Address: Nguyen Khe - Dong Anh - Ha Noi - Viet Nam
Tel: 84-4-882-0222 Fax: 84-4-882-0220 e-mail: sjbaik@lsis.biz
�LSIS-VINA Co., Ltd. �
�Hochiminh , Vietnam
Address: 41 Nguyen Thi Minh Khai Str. Yoco Bldg 4th Floor, Hochiminh City, Vietnam
Tel: 84-8-3822-7941 Fax: 84-8-3822-7942 e-mail: hjchoid@lsis.biz
�LSIS Shanghai Office �
�Shanghai, China
Address: Room 32 floors of the Great Wall Building, No. 3000 North Zhongshan Road, Putuo District, Shanghai, China
Tel: 86-21-5237-9977 Fax: 89-21-5237-7189 e-mail: baijh@lsis.com.cn
�LSIS Beijing Office �
�Beijing, China
Address: B-Tower 17FL.Beijing Global Trade Center B/D. No.36, BeiSanHuanDong-Lu, DongCheng-District,
Beijing 100013, P.R. China
Tel: 86-10-5825-6025,7 Fax: 86-10-5825-6026 e-mail: sunmj@lsis.com.cn
�LSIS Guangzhou Office �
�Guangzhou, China
Address: Room 1403, 14/F, New Poly Tower, No.2 Zhongshan Liu Road, Guangzhou 510180, P.R. China
Tel: 020-8326-6754 Fax: 020-8326-6287 e-mail: chenxs@lsis.com.cn
�LSIS Chengdu Office �
�Chengdu, China
Address: Room 1701 17Floor, huamin hanjun internationnal Building, No1 Fuxing Road Chengdu, 610016, P.R. China
Tel: 86-28-8670-3201 Fax: 86-28-8670-3203 e-mail: yangcf@lsis.com.cn
�LSIS Qingdao Office �
�Qingdao, China
Address: Room 2001,20/F,7B40, Galaxy Building, No.29 Shandong Road, Shinan District, Qingdao 266071, P.R. China
Tel: 86-532-8501-6058 Fax: 86-532-8501-6057 e-mail: wangzy@lsis.com.cn
�LSIS NETHERLANDS Co.Ltd �
�Schiphol-Rijk, Netherlands
Address: 1st. Floor, Tupolevlaan 48, 1119NZ,Schiphol-Rijk, The Netherlands
Tel: 31-20-654-1420 Fax: 31-20-654-1429 e-mail: junshickp@lsis.biz
Specifications in this catalog are subject to change without notice due to
continuous product development and improvement.