Selection Guide Molded Case Circuit Breakers Bulletin 140G/140MG Bulletin 140G Molded Case Circuit Breakers Overview Bulletin 140G Molded Case Circuit Breakers 10..3000 A current range 3- & 4-pole devices Space-saving dimensions Thermal/Magnetic protection: 15..800 A Electronic protection: 10..3000 A Approved for global application: UL, CSA, CCC, and IEC performance interrupting/breaking capacity Wide range of mounting options Extensive range of factory- or field-installed accessories Cat. No. 140G-G6C3-D12 The Bulletin 140G family of Molded Case Circuit Breakers (MCCBs) offers a wide range of features include thermal/magnetic and electronic protection devices, high interrupting/breaking capacities and a complete line of factory and field installed accessories. The Bulletin 140G MCCBs are ideal for use in line protection of control panels. Overview............................. 3 Product Selection ........... 5 Accessories....................... 50 Specifications ................... 64 Approximate Dimensions........................ 68 Standards Compliance IEC 60947-2 UL489 CSA22.2, No. 5 Certifications CE Marked CCC CSA Certified UL Listed G-Frame H-Frame I-Frame J-Frame K-Frame M-Frame N-, NS-Frame R-Frame Visit our website: www.ab.com/catalogs 2 Table of Contents Publication 140G-SG001C-EN-P Bulletin 140G Molded Case Circuit Breakers Product Overview Frame Reference Rated Current In G-Frame H-Frame I-Frame J-Frame K-Frame M-Frame N-Frame NS-Frame R-Frame 125 A 125 A 225 A 250 A 400 A 800 A 1200 A 1200 A 3000 A 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 No. of Poles Interrupting Rating [kA] 240V 50 65 100 65 100 150 200 200 50 65 65 100 150 65 100 150 125 480V 25 35 65 25 35 65 100 150 25 35 25 35 65 100 35 65 100 150 50 65 100 50 65 100 50 65 100 125 600Y/347V 10 14 25 — 10 10 — — — — — — — 14 18 25 35 10 10 14 18 25 35 25 35 65 100 25 35 42 25 50 65 25 50 65 100 220…240V 65 85 100 65 85 100 150 200 65 85 65 85 100 150 85 100 200 200 85 100 200 85 100 200 85 100 200 130 415V 36 50 70 36 50 70 120 150 36 50 36 50 70 120 50 70 120 200 36 70 100 50 70 120 50 70 120 80 440V 36 50 65 36 50 65 100 150 25 40 36 50 65 100 40 65 100 180 35 50 65 50 65 100 50 65 100 80 690V 6 8 10 10 12 15 18 20 58 10 12 15 20 25 40 70 80 22 25 30 30 42 50 30 42 50 40 250V DC 36 50 70 36 50 70 85 100 36 50 36 50 70 85 — 36 50 65 — — — 500V DC 36 50 70 36 50 70 85 100 36 50 36 50 70 85 36 50 70 100 — — — — 750V DC — — — — 25 36 70 70 16 36 50 — — — 600V 65 100 150 200 100 150 200 200 100 200 200 Breaking Capacity [Icu (kA)] Protection Type Thermal Magnetic — — — Electronic — — Molded Case Switch Auxiliary Contact Alarm Contact AX/AL Combo Trip Unit Contact — — — — Internal Accessories Shunt Trip Shunt Close — — — — — — UV Relay Field Installable STD STD STD STD STD STD STD STD — External Accessories End Cap 25 mm Phase Barriers STD STD STD STD STD — — — — Insulators STD STD STD STD STD STD — — — Terminal Lugs Extended Terminal — Spreader Terminal Rear Terminal — — — — — — Phase barriers Terminal Cover — Direct Rotary — — Variable Depth (Door) — — Internal NFPA 79 — — Flange Operator — — Flange Cable — — Motor Operator — Field Installable Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 3 Bulletin 140G Molded Case Circuit Breakers Catalog Number Explanation — 125 A, G-Frame Complete Circuit Breaker Assemblies with Factory-Installed Options Examples given in this section are not intended to be used for product selection. Use ProposalWorks to configure the molded case circuit breaker. Use these configurations only to select all factory-installed options for shunt trips, undervoltage release units, auxiliary contacts, and alarm contacts. Use the codes from Table g to add on to the molded case circuit breaker cat. no. selected on the previous pages to form a complete cat. no. for a complete assembly with factory-installed options. 140G – G a b 6 C 4 – C70 – SD – KA c d e f g Cat. No. 140G-G6C3-D12 a d g Bulletin No. Protection Type Factory-Installed Internal Options♦ Code Description Code Description 140G Global Molded Case Circuit Breaker C Fixed thermal/fixed magnetic Code Description E Adjust thermal/fixed magnetic SJ Shunt Trip, 24…30V AC/DC S Molded case switch (Isolator) SK Shunt Trip, 48…60V AC/DC SD Shunt Trip, 110…127V AC; 110…125V DC SA Shunt Trip, 220…240V AC; 220…250V DC b Frame/Rating Code Description e G 125 A, Fixed Poles Shunt Trip and Undervoltage Release Units Code Description SB Shunt Trip, 380…440V AC c 3 3 poles SC Shunt Trip, 480…525V DC Interrupting Rating/Breaking Capacity (based on Ic at 480V) 4 4 poles UJ Undervoltage Release, 24…30V AC/DC Code Description 2 25 kA f 3 35 kA Current Range 6 65 kA UR Undervoltage Release, 48V AC/DC UD Undervoltage Release, 110…127V AC; 110…125V DC UA Undervoltage Release, 220…240V AC; 220…250V DC Code Description UB Undervoltage Release, 380…440V AC C e.g., C30 = 30 A UC Undervoltage Release, 480…525V AC D e.g., D16 = 160 A No Digit No Selection Auxiliary and Alarm Contacts Code Description KA 1 Aux. Contact, 250V TA 1 Alarm Contact, 250V AA 1 Aux., 1 Alarm Contact, 250V BA 2 Aux., 1 Alarm Contact, 250V AJ 1 Aux., 1 Alarm Contact, 24V ♦ Select up to two internal options: 1 for left side mounting (shunt trip or undervoltage release), 1 for right (auxiliary or alarm contact). Consult your local Rockwell automation sales office or Allen-Bradley distributor for further assistance. Visit our website: www.ab.com/catalogs 4 Publication 140G-SG001C-EN-P Bulletin 140G Molded Case Circuit Breakers Product Selection — 125 A, G-Frame Assembled Molded Case Circuit Breakers — 125 A, G-Frame Interrupting Rating/Breaking Capacity — Thermal-Magnetic Circuit Breakers Interrupting Rating (50/60 Hz), UL 489/CSA C22.2-5, No. 5-02 [kA] Breaking Capacity (50/60 Hz), IEC 60947-2 Icu [kA]/Ics % 220V 240V 50 65 100 480V 25 35 65 600Y/ 347V 10 14 25 440V 415V Icu [kA] Ics [%Icu] Icu [kA] Ics [%Icu] Icu [kA] 65 85 100 75 75 75 36 50 70 100 75 50 36 50 65 Breaking Capacity (DC), IEC 60947-2 250V DC (2500V DC (3pole in series) pole in series) 690V Ics [%Icu] Icu [kA] 50 50 50 6 8 10 Ics [%Icu] Icu [kA] Ics [%Icu] Icu [kA] Ics [%Icu] 75 50 50 36 50 70 100 100 75 36 50 70 100 100 75 Interrupting Code‡ G2 G3 G6 These ratings have not been tested for the CCC listing. ‡ See table below for Cat. No. selection Thermal-Magnetic, Fixed Thermal-Fixed Magnetic Rated Current In [A] Thermal Trip [A] Ir = In (Fixed) Magnetic Trip [A] Im 15 16 20 25 30 32 35 40 45 50 60 63 70 80 90 100 110 125 15 16 20 25 30 32 35 40 45 50 60 63 70 80 90 100 110 125 ‡ 500 500 500 500 500 500 500 500 500 500 600 630 700 800 900 1000 1100 1250 1600 160 Interrupting Code G2 Cat. No. 3 Poles 4 Poles 140G-G2C3-C15 140G-G2C4-C15 140G-G2C3-C16 140G-G2C4-C16 140G-G2C3-C20 140G-G2C4-C20 140G-G2C3-C25 140G-G2C4-C25 140G-G2C3-C30 140G-G2C4-C30 140G-G2C3-C32 140G-G2C4-C32 140G-G2C3-C35 140G-G2C4-C35 140G-G2C3-C40 140G-G2C4-C40 140G-G2C3-C45 140G-G2C4-C45 140G-G2C3-C50 140G-G2C4-C50 140G-G2C3-C60 140G-G2C4-C60 140G-G2C3-C63 140G-G2C4-C63 140G-G2C3-C70 140G-G2C4-C70 140G-G2C3-C80 140G-G2C4-C80 140G-G2C3-C90 140G-G2C4-C90 140G-G2C3-D10 140G-G2C4-D10 140G-G2C3-D11 140G-G2C4-D11 140G-G2C3-D12 140G-G2C4-D12 140G-G2E3-D16 140G-G2E4-D16 Interrupting Code G3 Cat. No. 3 Poles 4 Poles 140G-G3C3-C15 140G-G3C4-C15 140G-G3C3-C16 140G-G3C4-C16 140G-G3C3-C20 140G-G3C4-C20 140G-G3C3-C25 140G-G3C4-C25 140G-G3C3-C30 140G-G3C4-C30 140G-G3C3-C32 140G-G3C4-C32 140G-G3C3-C35 140G-G3C4-C35 140G-G3C3-C40 140G-G3C4-C40 140G-G3C3-C45 140G-G3C4-C45 140G-G3C3-C50 140G-G3C4-C50 140G-G3C3-C60 140G-G3C4-C60 140G-G3C3-C63 140G-G3C4-C63 140G-G3C3-C70 140G-G3C4-C70 140G-G3C3-C80 140G-G3C4-C80 140G-G3C3-C90 140G-G3C4-C90 140G-G3C3-D10 140G-G3C4-D10 140G-G3C3-D11 140G-G3C4-D11 140G-G3C3-D12 140G-G3C4-D12 140G-G3E3-D16 140G-G3E4-D16 Interrupting Code G6 Cat. No. 3 Poles 4 Poles 140G-G6C3-C15 140G-G6C4-C15 140G-G6C3-C16 140G-G6C4-C16 140G-G6C3-C20 140G-G6C4-C20 140G-G6C3-C25 140G-G6C4-C25 140G-G6C3-C30 140G-G6C4-C30 140G-G6C3-C32 140G-G6C4-C32 140G-G6C3-C35 140G-G6C4-C35 140G-G6C3-C40 140G-G6C4-C40 140G-G6C3-C45 140G-G6C4-C45 140G-G6C3-C50 140G-G6C4-C50 140G-G6C3-C60 140G-G6C4-C60 140G-G6C3-C63 140G-G6C4-C63 140G-G6C3-C70 140G-G6C4-C70 140G-G6C3-C80 140G-G6C4-C80 140G-G6C3-C90 140G-G6C4-C90 140G-G6C3-D10 140G-G6C4-D10 140G-G6C3-D11 140G-G6C4-D11 140G-G6C3-D12 140G-G6C4-D12 140G-G6E3-D16 140G-G6E4-D16 IEC only. ‡ Adjustable thermal trip. 112 A min., 136 A med., 160 A max. Molded Case Switch — UL489§ Rated Current In [A] Magnetic Trip [A] Im 125 1250 Cat. No. 3 Poles 4 Poles 140G-G6S3-D12 140G-G6S4-D12 § Does not provide overcurrent protection; may open above 1250 A. Cat. No. 140G-G6C3-D12 Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 5 Bulletin 140G Molded Case Circuit Breakers Catalog Number Explanation — 125 A, H-Frame Complete Circuit Breaker Assemblies — 125 A, H-Frame Examples given in this section are not intended to be used for product selection. Use ProposalWorks to configure the molded case circuit breaker. Use these configurations only to select all factory-installed options for shunt trips, undervoltage release units, auxiliary contacts, trip units, and alarm contacts. Use the codes from Table g to add on to the molded case circuit breaker cat. no. selected on the previous pages to form a complete cat. no. for a complete assembly with factory-installed options. 140G – H a b 3 C 3 – C60 – SD – AA c d e f g a d g Bulletin No. Protection Type Factory-Installed Internal Options♦ Code Description Code Description 140G Global Molded Case Circuit Breaker C Fixed thermal/fixed magnetic Code Description F Adjust thermal/ adjust magnetic SJ Shunt Trip, 24…30V AC/DC Shunt Trip and Undervoltage Release Units b H Electronic LSI- long, short, instant SK Shunt Trip, 48…60V AC/DC Frame/Rating I Electronic LSIG -Long, short, instant & ground fault SD Shunt Trip, 110…127V AC; 110…125V DC SA Shunt Trip, 220…240V AC; 220…250V DC SB Shunt Trip, 380…440V AC Code Description X Breaker frame H 125 A S Molded case switch (isolator) c Interrupting Rating/Breaking Capacity (based on Ic at 480V) Code Description 2 25 kA 3 35 kA e Poles Shunt Trip, 480…525V AC UJ Undervoltage Release, 24…30V AC/DC UR Undervoltage Release, 48V AC/DC UD Undervoltage Release, 110…127V AC; 110…125V DC 4 poles UA Undervoltage Release, 220…240V AC; 220…250V DC UB Undervoltage Release, 380…440V AC UC Undervoltage Release, 480…525V AC No Digit No Selection Code Description 3 3 poles 4 6 65 kA 0 100 kA f 15 150 kA Current Range T Trip unit Code SC Description Auxiliary and Alarm Contacts, Trip Units C e.g., C30 = 30 A D e.g., D16 = 160 A Code Description Blank Frame only KA 1 Aux. Contact, 250V TA 1 Alarm Contact, 250V AA 1 Aux., 1 Alarm Contact, 250V BA 2 Aux., 1 Alarm Contact, 250V DA 1 Trip Unit Alarm Contact, 250V FB 2 Aux. Contacts, 400V AB 1 Aux., 1 Alarm Contact, 400V AJ 1 Aux., 1 Alarm Contact, 24V DJ 1 Trip Unit Alarm Contact, 24V ♦ Select up to two internal options: 1 for left side mounting (shunt trip or undervoltage release), 1 for right (auxiliary or alarm contact). Consult your local Rockwell automation sales office or Allen-Bradley distributor for further assistance. Visit our website: www.ab.com/catalogs 6 Publication 140G-SG001C-EN-P Bulletin 140G Molded Case Circuit Breakers Product Selection — 125 A, H-Frame Breaker Frames & Trip Units + = Frame Trip Unit MCCB Breaker Frames, 125 A Rated Current Interrupting Rating (50/60 Hz), UL 489/CSA C22.2-5, No. 5-02 [kA] 240V 65 100 150 200 200 480V 25 35 65 100 150 Breaking Capacity (50/60 Hz), IEC 60947-2 Icu 600V 14 18 25 35 — 220V Ics [kA] [%Icu] 65 85 100 150 200 100 100 100 100 100 415V Icu [kA] Ics [%Icu] 36 50 70 120 150 100 100 100 100 100 Icu 440V Ics [kA] [%Icu] 36 50 65 100 150 Icu 100 100 100 100 100 Breaking Capacity (DC), IEC 60947-2 ‡ 250V DC (2500V DC (3690V pole in series) pole in series) Ics Ics Ics [kA] [%Icu] Icu [kA] [%Icu] Icu [kA] [%Icu] 10 12 15 18 20 100 100 100 75 75 36 50 70 85 100 100 100 100 100 100 36 50 70 85 100 100 100 100 100 100 Cat. No. 3 Poles 140G-H2X3 140G-H3X3 140G-H6X3 140G-H0X3 140G-H15X3 4 Poles 140G-H2X4 140G-H3X4 140G-H6X4 140G-H0X4 140G-H15X4 These ratings have not been tested for the CCC listing. ‡ DC rating is applicable for thermal-magnetic trip unit only. Trip Units, Thermal-Magnetic Rated Current In [A] Thermal Trip [A] Ir = In Magnetic Trip [A] Im Cat. No. 50 60 63 70 80 90 100 110 125 50 60 63 70 56...80 63…90 70…100 77…110 87…125 500 600 630 700 400…800 450…900 500…1000 550…1100 625…1250 Protection Type C (Fixed) C (Fixed) C (Fixed) C (Fixed) F (Adjustable) F (Adjustable) F (Adjustable) F (Adjustable) F (Adjustable) 3 Poles 140G-HTC3-C50 140G-HTC3-C60 140G-HTC3-C63 140G-HTC3-C70 140G-HTF3-C80 140G-HTF3-C90 140G-HTF3-D10 140G-HTF3-D11 140G-HTF3-D12 4 Poles 140G-HTC4-C50 140G-HTC4-C60 140G-HTC4-C63 140G-HTC4-C70 140G-HTF4-C80 140G-HTF4-C90 140G-HTF4-D10 140G-HTF4-D11 140G-HTF4-D12 Trip Units, Electronic LSI (Long, Short, Instantaneous) Cat. No. Protection Type Rated Current In [A] I1=0.4…1 x In t1=sec. I2=1…10 x In t2=sec. I I3=1…10 x In 60 100 125 24…60 40…100 50…125 3, 12, 36, 60 3, 12, 36, 60 3, 12, 36, 60 60…600 100…1000 125…1250 0.05, 0.1, 0.2, 0.4 0.05, 0.1, 0.2, 0.4 0.05, 0.1, 0.2, 0.4 60…600 100…1000 125…1250 L S 3 Poles 4 Poles 140G-HTH3-C60 140G-HTH4-C60 140G-HTH3-D10 140G-HTH4-D10 140G-HTH3-D12 140G-HTH4-D12 Trip Units, Electronic LSIG (Long, Short, Instantaneous, Ground Fault) Rated Current In [A] L I1=0.4…1 x In t1=sec. Protection Type S I G I2=1…10 x In t2=sec. I3=1…10 x In I4=0.2…1 x In 60 24…60 3, 12, 36, 60 60…600 100 40…100 3, 12, 36, 60 100…1000 125 50…125 3, 12, 36, 60 125…1250 0.05, 0.1, 0.2, 0.4 0.05, 0.1, 0.2, 0.4 0.05, 0.1, 0.2, 0.4 60…600 12…60 100…1000 20…100 125…1250 25…125 Cat. No. t4=sec. 0.1, 0.2, 0.4, 0.8 0.1, 0.2, 0.4, 0.8 0.1, 0.2, 0.4, 0.8 3 Poles 4 Poles 140G-HTI3-C60 140G-HTI4-C60 140G-HTI3-D10 140G-HTI4-D10 140G-HTI3-D12 140G-HTI4-D12 Assembled molded case circuit breakers found on pages 8…10 Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 7 Bulletin 140G Molded Case Circuit Breakers Product Selection — 125 A, H-Frame Assembled Molded Case Circuit Breakers — 125 A, H-Frame Interrupting Rating/Breaking Capacity — Thermal-Magnetic Circuit Breakers Interrupting Rating (50/60 Hz), UL 489/CSA C22.2-5, No. 5-02 [kA] Breaking Capacity (50/60 Hz), IEC 60947-2 220V 240V 65 100 150 200 200 480V 25 35 65 100 150 600V 14 18 25 35 42 Icu [kA] Ics [%Icu] 65 85 100 150 200 100 100 100 100 100 440V 415V Icu [kA] Ics [%Icu] 36 50 70 120 150 100 100 100 100 100 690V Icu [kA] Ics [%Icu] Icu [kA] Ics [%Icu] 36 50 65 100 150 100 100 100 100 100 10 12 15 18 20 100 100 100 75 75 Breaking Capacity (DC), IEC 60947-2 § 250V DC (2-pole 500V DC (3-pole in series) in series) Ics Ics Icu [kA] [%Icu] Icu [kA] [%Icu] 36 50 70 85 100 100 100 100 100 100 36 50 70 85 100 100 100 100 100 100 Interrupting Code‡ H2 H3 H6 H0 H15 These ratings have not been tested for the CCC listing. ‡ See table below for Cat. No. selection § DC rating is applicable for thermal-magnetic trip unit only. Thermal-Magnetic, Fixed & Adjustable Rated Current In [A] Thermal Trip [A] I r = In Magnetic Trip [A] Im 15 16 20 25 30 32 35 40 50 60 63 70 80 90 100 110 125 15 16 20 25 30 32 35 40 50 60 63 70 56...80 63…90 70…100 77…110 87…125 112…160 400 400 400 400 400 400 400 400 500 600 630 700 400…800 450…900 500…1000 550…1100 625…1250 800…1600 Interrupting Code H2 Cat. No. 3 Poles 4 Poles 140G-H2C3-C15 140G-H2C4-C15 140G-H2C3-C16 140G-H2C4-C16 140G-H2C3-C20 140G-H2C4-C20 140G-H2C3-C25 140G-H2C4-C25 140G-H2C3-C30 140G-H2C4-C30 140G-H2C3-C32 140G-H2C4-C32 140G-H2C3-C35 140G-H2C4-C35 140G-H2C3-C40 140G-H2C4-C40 140G-H2C3-C50 140G-H2C4-C50 140G-H2C3-C60 140G-H2C4-C60 140G-H2C3-C63 140G-H2C4-C63 140G-H2C3-C70 140G-H2C4-C70 140G-H2F3-C80 140G-H2F4-C80 140G-H2F3-C90 140G-H2F4-C90 140G-H2F3-D10 140G-H2F4-D10 140G-H2F3-D11 140G-H2F4-D11 140G-H2F3-D12 140G-H2F4-D12 140G-H2F3-D16 140G-H2F4-D16 Thermal Trip [A] Ir = In Magnetic Trip [A] Im 15 16 20 25 30 32 35 40 50 60 63 70 56...80 63…90 70…100 77…110 84…120 112…160 400 400 400 400 400 400 400 400 500 600 630 700 400…800 450…900 500…1000 550…1100 625…1250 800…1600 160 Interrupting Code H3 Cat. No. 3 Poles 4 Poles 140G-H3C3-C15 140G-H3C4-C15 140G-H3C3-C16 140G-H3C4-C16 140G-H3C3-C20 140G-H3C4-C20 140G-H3C3-C25 140G-H3C4-C25 140G-H3C3-C30 140G-H3C4-C30 140G-H3C3-C32 140G-H3C4-C32 140G-H3C3-C35 140G-H3C4-C35 140G-H3C3-C40 140G-H3C4-C40 140G-H3C3-C50 140G-H3C4-C50 140G-H3C3-C60 140G-H3C4-C60 140G-H3C3-C63 140G-H3C4-C63 140G-H3C3-C70 140G-H3C4-C70 140G-H3F3-C80 140G-H3F4-C80 140G-H3F3-C90 140G-H3F4-C90 140G-H3F3-D10 140G-H3F4-D10 140G-H3F3-D11 140G-H3F4-D11 140G-H3F3-D12 140G-H3F4-D12 140G-H3F3-D16 140G-H3F4-D16 Interrupting Code H6 Cat. No. Cat. No. 3 Poles 4 Poles 140G-H6C3-C15 140G-H6C4-C15 140G-H6C3-C16 140G-H6C4-C16 140G-H6C3-C20 140G-H6C4-C20 140G-H6C3-C25 140G-H6C4-C25 140G-H6C3-C30 140G-H6C4-C30 140G-H6C3-C32 140G-H6C4-C32 140G-H6C3-C35 140G-H6C4-C35 140G-H6C3-C40 140G-H6C4-C40 140G-H6C3-C50 140G-H6C4-C50 140G-H6C3-C60 140G-H6C4-C60 140G-H6C3-C63 140G-H6C4-C63 140G-H6C3-C70 140G-H6C4-C70 140G-H6F3-C80 140G-H6F4-C80 140G-H6F3-C90 140G-H6F4-C90 140G-H6F3-D10 140G-H6F4-D10 140G-H6F3-D11 140G-H6F4-D11 140G-H6F3-D12 140G-H6F4-D12 140G-H6F3-D16 140G-H6F4-D16 IEC only. Rated Current In [A] 15 16 20 25 30 32 35 40 50 60 63 70 80 90 100 110 125 160 Interrupting Code H0 Cat. No. 3 Poles 4 Poles 140G-H0C3-C15 140G-H0C4-C15 140G-H0C3-C16 140G-H0C4-C16 140G-H0C3-C20 140G-H0C4-C20 140G-H0C3-C25 140G-H0C4-C25 140G-H0C3-C30 140G-H0C4-C30 140G-H0C3-C32 140G-H0C4-C32 140G-H0C3-C35 140G-H0C4-C35 140G-H0C3-C40 140G-H0C4-C40 140G-H0C3-C50 140G-H0C4-C50 140G-H0C3-C60 140G-H0C4-C60 140G-H0C3-C63 140G-H0C4-C63 140G-H0C3-C70 140G-H0C4-C70 140G-H0F3-C80 140G-H0F4-C80 140G-H0F3-C90 140G-H0F4-C90 140G-H0F3-D10 140G-H0F4-D10 140G-H0F3-D11 140G-H0F4-D11 140G-H0F3-D12 140G-H0F4-D12 140G-H0F3-D16 140G-H0F4-D16 IEC only. Visit our website: www.ab.com/catalogs 8 Publication 140G-SG001C-EN-P Interrupting Code H15 Cat. No. 3 Poles 4 Poles 140G-H15C3-C15 140G-H15C4-C15 140G-H15C3-C16 140G-H15C4-C16 140G-H15C3-C20 140G-H15C4-C20 140G-H15C3-C25 140G-H15C4-C25 140G-H15C3-C30 140G-H15C4-C30 140G-H15C3-C32 140G-H15C4-C32 140G-H15C3-C35 140G-H15C4-C35 140G-H15C3-C40 140G-H15C4-C40 140G-H15C3-C50 140G-H15C4-C50 140G-H15C3-C60 140G-H15C4-C60 140G-H15C3-C63 140G-H15C4-C63 140G-H15C3-C70 140G-H15C4-C70 140G-H15F3-C80 140G-H15F4-C80 140G-H15F3-C90 140G-H15F4-C90 140G-H15F3-D10 140G-H15F4-D10 140G-H15F3-D11 140G-H15F4-D11 140G-H15F3-D12 140G-H15F4-D12 140G-H15F3-D16 140G-H15F4-D16 Bulletin 140G Molded Case Circuit Breakers Product Selection — 125 A, H-Frame Interrupting Rating/Breaking Capacity — Electronic Circuit Breakers Interrupting Rating (50/60 Hz), UL 489/CSA C22.2-5, No. 5-02 [kA] 240V 65 100 150 200 200 480V 25 35 65 100 150 Breaking Capacity (50/60 Hz), IEC 60947-2 440V 220V 415V 690V Icu [kA] Ics [%Icu] Icu [kA] Ics [%Icu] Icu [kA] Ics [%Icu] Icu [kA] Ics [%Icu] 65 100 36 100 36 100 10 100 85 100 50 100 50 100 12 100 100 100 70 100 65 100 15 100 150 100 120 100 100 100 18 75 200 100 150 100 150 100 20 75 600V 14 18 25 35 42 Breaking Capacity (DC), IEC 60947-2 250V DC (2-pole 500V DC (3-pole in series) in series) Icu Icu [kA] Ics [%Icu] [kA] Ics [%Icu] 36 50 70 85 100 100 100 100 100 100 36 50 70 85 100 100 100 100 100 100 Interrupting Code‡ H2 H3 H6 H0 H15 These ratings have not been tested for the CCC listing. ‡ See table below for Cat. No. selection Electronic LSI (Long, Short, Instantaneous) Rated Current In [A] Protection Type S I2=1…10 x In L I1=0.4…1 x In t1=sec. 25 10…25 3, 12, 36, 60 25…250 60 24…60 3, 12, 36, 60 60…600 100 40…100 3, 12, 36, 60 100…1000 125 50…125 3, 12, 36, 60 125…1250 160 64…160 3, 12, 36, 60 160…1600 Interrupting Code H2 Cat. No. I I3=1…10 x In t2=sec. 0.05, 0.1, 0.2, 0.4 0.05, 0.1, 0.2, 0.4 0.05, 0.1, 0.2, 0.4 0.05, 0.1, 0.2, 0.4 0.05, 0.1, 0.2, 0.4 3 Poles 4 Poles Interrupting Code H3 Cat. No. 3 Poles 4 Poles 25…250 140G-H2H3-C25 140G-H2H4-C25 140G-H3H3-C25 140G-H3H4-C25 60…600 140G-H2H3-C60 140G-H2H4-C60 140G-H3H3-C60 140G-H3H4-C60 100…1000 140G-H2H3-D10 140G-H2H4-D10 140G-H3H3-D10 140G-H3H4-D10 125…1250 140G-H2H3-D12 140G-H2H4-D12 140G-H3H3-D12 140G-H3H4-D12 160…1600 140G-H2H3-D16 140G-H2H4-D16 140G-H3H3-D16 140G-H3H4-D16 IEC only. Protection Type Rated Current In [A] L S I1=0.4…1 x In 25 60 100 125 10…25 24…60 40…100 50…125 64…160 160 t1=sec. 3, 3, 3, 3, 3, 12, 12, 12, 12, 12, 36, 36, 36, 36, 36, I2=1…10 x In 60 60 60 60 60 25…250 60…600 100…1000 125…1250 160…1600 I I3=1…10 x In t2=sec. 0.05, 0.05, 0.05, 0.05, 0.05, 0.1, 0.1, 0.1, 0.1, 0.1, 0.2, 0.2, 0.2, 0.2, 0.2, 0.4 0.4 0.4 0.4 0.4 25…250 60…600 100…1000 125…1250 160…1600 Interrupting Code H6 Cat. No. Cat. No. 3 Poles 140G-H6H3-C25 140G-H6H3-C60 140G-H6H3-D10 140G-H6H3-D12 140G-H6H3-D16 4 Poles 140G-H6H4-C25 140G-H6H4-C60 140G-H6H4-D10 140G-H6H4-D12 140G-H6H4-D16 IEC only. Rated Current In [A] L I1=0.4…1 x In 25 10…25 60 24…60 100 40…100 125 50…125 160 64…160 Protection Type S I2=1…10 x t1=sec. t2=sec. In 3, 12, 36, 60 3, 12, 36, 60 3, 12, 36, 60 3, 12, 36, 60 3, 12, 36, 60 25…250 60…600 100…1000 125…1250 160…1600 0.05, 0.1, 0.2, 0.4 0.05, 0.1, 0.2, 0.4 0.05, 0.1, 0.2, 0.4 0.05, 0.1, 0.2, 0.4 0.05, 0.1, 0.2, 0.4 I I3=1…10 x In Interrupting Code H0 Cat. No. 3 Poles 4 Poles Interrupting Code H15 Cat. No. 3 Poles 4 Poles 25…250 140G-H0H3-C25 140G-H0H4-C25 140G-H15H3-C25 140G-H15H4-C25 60…600 140G-H0H3-C60 140G-H0H4-C60 140G-H15H3-C60 140G-H15H4-C60 100…1000 140G-H0H3-D10 140G-H0H4-D10 140G-H15H3-D10 140G-H15H4-D10 125…1250 140G-H0H3-D12 140G-H0H4-D12 140G-H15H3-D12 140G-H15H4-D12 160…1600 140G-H0H3-D16 140G-H0H4-D16 140G-H15H3-D16 140G-H15H4-D16 IEC only. Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 9 Bulletin 140G Molded Case Circuit Breakers Product Selection — 125 A, H-Frame Electronic LSIG (Long, Short, Instantaneous, Ground Fault) Protection Type S I G I2=1…10 I3=1…10 x I4=0.2… t2=sec. t4=sec. x In In 1 x In L Rated Current In [A] I1=0.4… 1 x In t1=sec. 3, 12, 36, 60 3, 12, 36, 24…60 60 3, 12, 36, 40…100 60 3, 12, 36, 50…125 60 3, 12, 36, 64…160 60 25 10…25 60 100 125 160 25…250 60…600 100…10 00 125…12 50 160…16 00 0.05, 0.1, 25…250 5…25 0.2, 0.4 0.05, 0.1, 60…600 12…60 0.2, 0.4 0.05, 0.1, 100…1000 20…100 0.2, 0.4 0.05, 0.1, 125…1250 25…125 0.2, 0.4 0.05, 0.1, 160…1600 32…160 0.2, 0.4 0.1, 0.2, 0.4, 0.8 0.1, 0.2, 0.4, 0.8 0.1, 0.2, 0.4, 0.8 0.1, 0.2, 0.4, 0.8 0.1, 0.2, 0.4, 0.8 Interrupting Code H2 Cat. No. 3 Poles Interrupting Code H3 Cat. No. 3 Poles 4 Poles 140G-H2I3-C25 140G-H2I4-C25 4 Poles 140G-H3I3-C25 140G-H3I4-C25 140G-H2I3-C60 140G-H2I4-C60 140G-H3I3-C60 140G-H3I4-C60 140G-H2I3-D10 140G-H2I4-D10 140G-H3I3-D10 140G-H3I4-D10 140G-H2I3-D12 140G-H2I4-D12 140G-H3I3-D12 140G-H3I4-D12 140G-H2I3-D16 140G-H2I4-D16 140G-H3I3-D16 140G-H3I4-D16 IEC only. Rated Current In [A] L I1=0.4…1 x In t1=sec. Interrupting Code H6 Cat. No. Cat. No. Protection Type S I G I2=1…10 x In t2=sec. I3=1…10 x In I4=0.2…1 x In 25 10…25 3, 12, 36, 60 25…250 60 24…60 3, 12, 36, 60 60…600 100 40…100 3, 12, 36, 60 100…1000 125 50…125 3, 12, 36, 60 125…1250 160 64…160 3, 12, 36, 60 160…1600 0.05, 0.1, 0.4 0.05, 0.1, 0.4 0.05, 0.1, 0.4 0.05, 0.1, 0.4 0.05, 0.1, 0.4 0.2, 0.2, 0.2, 0.2, 0.2, 25…250 5…25 60…600 12…60 100…1000 20…100 125…1250 25…125 160…1600 32…160 t4=sec. 0.1, 0.2, 0.8 0.1, 0.2, 0.8 0.1, 0.2, 0.8 0.1, 0.2, 0.8 0.1, 0.2, 0.8 0.4, 0.4, 0.4, 0.4, 0.4, 3 Poles 4 Poles 140G-H6I3-C25 140G-H6I4-C25 140G-H6I3-C60 140G-H6I4-C60 140G-H6I3-D10 140G-H6I4-D10 140G-H6I3-D12 140G-H6I4-D12 140G-H6I3-D16 140G-H6I4-D16 IEC only. L Rated Current I1=0.4… t1=sec. 1 x In In [A] Protection Type S I G I2=1…1 I3=1…10 x I4=0.2… t2=sec. t4=sec. 0 x In In 1 x In 25 10…25 3, 12, 36, 60 60 24…60 3, 12, 36, 60 60…600 100 40…100 3, 12, 36, 60 100…10 00 125 50…125 3, 12, 36, 60 125…12 50 160 64…160 3, 12, 36, 60 160…16 00 25…250 Interrupting Code H0 Cat. No. 3 Poles 0.05, 0.1, 0.2, 140G-H0I3-C25 0.1, 0.2, 25…250 5…25 0.4, 0.8 0.4 0.05, 0.1, 0.2, 140G-H0I3-C60 0.1, 0.2, 60…600 12…60 0.4, 0.8 0.4 0.05, 0.1, 0.2, 140G-H0I3-D10 0.1, 0.2, 100…1000 20…100 0.4, 0.8 0.4 0.05, 0.1, 0.2, 140G-H0I3-D12 0.1, 0.2, 125…1250 25…125 0.4, 0.8 0.4 0.05, 0.1, 0.2, 140G-H0I3-D16 0.1, 0.2, 160…1600 32…160 0.4, 0.8 0.4 IEC only. Molded Case Switch — UL489§ Rated Current In [A] Magnetic Trip [A] Im 125 1250 Cat. No. 3 Poles 140G-H6S3-D12 4 Poles 140G-H6S4-D12 § Does not provide overcurrent protection; may open above 1250 A. Visit our website: www.ab.com/catalogs 10 Publication 140G-SG001C-EN-P Interrupting Code H15 Cat. No. 4 Poles 3 Poles 4 Poles 140G-H0I4-C25 140G-H15I3-C25 140G-H15I4-C25 140G-H0I4-C60 140G-H15I3-C60 140G-H15I4-C60 140G-H0I4-D10 140G-H15I3-D10 140G-H15I4-D10 140G-H0I4-D12 140G-H15I3-D12 140G-H15I4-D12 140G-H0I4-D16 140G-H15I3-D16 140G-H15I4-D16 Bulletin 140G Molded Case Circuit Breakers Product Selection — 125 A, H-Frame Page Intentionally Left Blank Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 11 Bulletin 140G Molded Case Circuit Breakers Catalog Number Explanation — 225 A, I-Frame Complete Circuit Breaker Assemblies — 225 A, I-Frame Examples given in this section are not intended to be used for product selection. Use ProposalWorks to configure the molded case circuit breaker. Use these configurations only to select all factory-installed options for shunt trips, undervoltage release units, auxiliary contacts, and alarm contacts. Use the codes from Table g to add on to the molded case circuit breaker cat. no. selected on the previous pages to form a complete cat. no. for a complete assembly with factory-installed options. 140G – a I 3 C 3 – C60 – SA – KA b c d e f g a d g Bulletin No. Protection Type Factory-Installed Internal Options♦ Code Description Code Description 140G Global Molded Case Circuit Breaker C Fixed thermal/fixed magnetic Code Description S Molded case switch (Isolator) SJ Shunt Trip, 24…30V AC/DC SK Shunt Trip, 48…60V AC/DC e SD Shunt Trip, 110…127V AC; 110…125V DC Poles SA Shunt Trip, 220…240V AC; 220…250V DC SB Shunt Trip, 380…440V AC b Frame/Rating Code Description I 225 A c Code Description 3 3 poles 4 4 poles Interrupting Rating/Breaking Capacity (based on Ic at 480V) Code Description 2 25 kA 3 35 kA Shunt Trip and Undervoltage Release Units f SG Shunt Trip, 480…525V AC UJ Undervoltage Release, 24…30V AC/DC UR Undervoltage Release, 48V AC/DC UD Undervoltage Release, 110…127V AC; 110…125V DC UA Undervoltage Release, 220…240V AC; 220…250V DC Current Range Code Description C e.g., C30 = 30 A UB Undervoltage Release, 380…440V AC D e.g., D16 = 160 A UC Undervoltage Release, 480…525V AC No Digit No Selection Auxiliary and Alarm Contacts Code Description KA 1 Aux. Contact, 250V TA 1 Alarm Contact, 250V AA 1 Aux., 1 Alarm Contact, 250V BA 2 Aux., 1 Alarm Contact, 250V CA 3 Aux., 1 Alarm Contact, 250V AJ 1 Aux., 1 Alarm Contact, 24V CJ 3 Aux., 1 Alarm Contact, 24V ♦ Select up to two internal options: 1 for left side mounting (shunt trip or undervoltage release), 1 for right (auxiliary or alarm contact). Consult your local Rockwell automation sales office or Allen-Bradley distributor for further assistance. Visit our website: www.ab.com/catalogs 12 Publication 140G-SG001C-EN-P Bulletin 140G Molded Case Circuit Breakers Product Selection — 225 A, I-Frame Assembled Molded Case Circuit Breakers — 225 A I-Frame Interrupting Rating/Breaking Capacity — Thermal-Magnetic Circuit Breakers Interrupting Rating (50/60 Hz), UL 489/CSA C22.2-5, No. 5-02 [kA] Breaking Capacity (50 Hz), IEC 60947-2 220V 240V 50 65 480V 25 35 600Y/ 347V 10 10 415V Icu [kA] Ics [%Icu] Icu [kA] Ics [%Icu] 50 85 75 50 36 50 75 50 Icu 440V Ics [kA] [%Icu] 25 40 75 50 690V Icu [kA] Ics [%Icu] 5 6 50 50 Breaking Capacity (DC), IEC 60947-2 250V DC 500V DC (2-pole in series) (3-pole in series) Ics Icu [kA] [%Icu] Icu [kA] Ics [%Icu] 36 50 100 75 36 50 100 75 Interrupting Code‡ I2 I3 These ratings have not been tested for the CCC listing. ‡ See table below for Cat. No. selection Thermal-Magnetic, Fixed & Adjustable Rated Current In [A] Thermal Trip [A] Ir = In (Fixed) Magnetic Trip [A] Im 60 63 70 80 90 100 110 125 150 160 175 200 225 60 63 70 80 90 100 110 125 150 160 175 200 225 600 630 700 800 900 1000 1100 1250 1500 1600 1750 2000 2250 Interrupting Code I2 Cat. No. 3 Poles 4 Poles 140G-I2C3-C60 140G-I2C4-C60 140G-I2C3-C63 140G-I2C4-C63 140G-I2C3-C70 140G-I2C4-C70 140G-I2C3-C80 140G-I2C4-C80 140G-I2C3-C90 140G-I2C4-C90 140G-I2C3-D10 140G-I2C4-D10 140G-I2C3-D11 140G-I2C4-D11 140G-I2C3-D12 140G-I2C4-D12 140G-I2C3-D15 140G-I2C4-D15 140G-I2C3-D16 140G-I2C4-D16 140G-I2C3-D17 140G-I2C4-D17 140G-I2C3-D20 140G-I2C4-D20 140G-I2C3-D22 140G-I2C4-D22 Interrupting Code I3 Cat. No. 3 Poles 4 Poles 140G-I3C3-C60 140G-I3C4-C60 140G-I3C3-C63 140G-I3C4-C63 140G-I3C3-C70 140G-I3C4-C70 140G-I3C3-C80 140G-I3C4-C80 140G-I3C3-C90 140G-I3C4-C90 140G-I3C3-D10 140G-I3C4-D10 140G-I3C3-D11 140G-I3C4-D11 140G-I3C3-D12 140G-I3C4-D12 140G-I3C3-D15 140G-I3C4-D15 140G-I3C3-D16 140G-I3C4-D16 140G-I3C3-D17 140G-I3C4-D17 140G-I3C3-D20 140G-I3C4-D20 140G-I3C3-D22 140G-I3C4-D22 Molded Case Switch — UL489§ Rated Current In [A] Magnetic Trip [A] Im 225 2250 Cat. No. 3 Poles 140G-I3S3-D22 4 Poles 140G-I3S4-D22 § Does not provide overcurrent protection; may open above 2250 A. Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 13 Bulletin 140G Molded Case Circuit Breakers Catalog Number Explanation — 250 A, J-Frame Complete Circuit Breaker Assemblies — 250 A, J-Frame Examples given in this section are not intended to be used for product selection. Use ProposalWorks to configure the molded case circuit breaker. Use these configurations only to select all factory-installed options for shunt trips, undervoltage release units, auxiliary contacts, trip units, and alarm contacts. Use the codes from Table g to add on to the molded case circuit breaker cat. no. selected on the previous pages to form a complete cat. no. for a complete assembly with factory-installed options. 140G – J a b 3 C 3 – C60 – SD – AA c d e f g a d g Bulletin No. Protection Type Factory-Installed Internal Options♦ Code Description Code Description 140G Global Molded Case Circuit Breaker C Fixed thermal/ fixed magnetic Code Description E Adjust thermal/ fixed magnetic SJ Shunt Trip, 24…30V AC/DC b F Adjust thermal/ adjust magnetic Frame/Rating H Electronic LSI-long, short, instant I Electronic LSIG -long, short, instant & ground fault X Breaker frame S Molded case switch (isolator) Code Description J 250 A Shunt Trip and Undervoltage Release Units SK Shunt Trip, 48…60V AC/DC SD Shunt Trip, 110…127V AC; 110…125V DC SA Shunt Trip, 220…240V AC; 220…250V DC SB Shunt Trip, 380…440V AC c SC Shunt Trip, 480…525V AC Interrupting Rating/Breaking Capacity (based on Ic at 480V) UJ Undervoltage Release, 24…30V AC/DC e UR Undervoltage Release, 48V AC/DC UD Undervoltage Release, 110…127V AC; 110…125V DC UA Undervoltage Release, 220…240V AC; 220…250V DC Poles Code Description 2 25 kA Code Description 3 35 kA 3 3 poles 6 65 kA 4 4 poles 0 100 kA T Trip unit f Current Range UB Undervoltage Release, 380…440V AC UC Undervoltage Release, 480…525V AC No Digit No Selection Auxiliary and Alarm Contacts, Trip Units Code Description C e.g., C30 = 30 A Code Description D e.g., D16 = 160 A KA 1 Aux. Contact, 250V Blank Frame only TA 1 Alarm Contact, 250V AA 1 Aux., 1 Alarm Contact, 250V BA 2 Aux., 1 Alarm Contact, 250V DA 1 Trip Unit Alarm Contact, 250V FB 2 Aux. Contacts, 400V AB 1 Aux., 1 Alarm Contact, 400V AJ 1 Aux., 1 Alarm Contact, 24V DJ 1 Trip Unit Alarm Contact, 24V ♦ Select up to two internal options: 1 for left side mounting, 1 for right. Consult your local Rockwell automation sales office or Allen-Bradley distributor for further assistance. Visit our website: www.ab.com/catalogs 14 Publication 140G-SG001C-EN-P Bulletin 140G Molded Case Circuit Breakers Product Selection — 250 A, J-Frame Breaker Frames & Trip Units + Breaker Frames, 250 A Rated Current Interrupting Rating (50/60 Hz), UL 489/CSA C22.2-5, No. 5-02 [kA] 240V 65 100 150 200 480V 25 35 65 100 = Frame Trip Unit Breaking Capacity (DC), IEC 60947-2 ‡ 250V DC (2-pole 500V DC (3-pole in series) in series) Ics Ics Icu [kA] [%Icu] Icu [kA] [%Icu] Breaking Capacity (50/60 Hz), IEC 60947-2 Icu 600V 14 18 25 35 220V Ics [kA] [%Icu] 65 85 100 150 415V Icu [kA] Ics [%Icu] 36 50 70 120 100 100 100 100 100 100 100 100 Icu 440V Ics [kA] [%Icu] 36 50 65 100 690V Icu [kA] Ics [%Icu] 10 12 15 20 100 100 100 100 100 100 100 100 MCCB 36 50 70 85 100 100 100 100 36 50 70 85 100 100 100 100 Cat. No. 3 Poles 140G-J2X3 140G-J3X3 140G-J6X3 140G-J0X3 4 Poles 140G-J2X4 140G-J4X4 140G-J6X4 140G-J0X4 These ratings have not been tested for the CCC listing. ‡ DC rating is applicable for thermal-magnetic trip unit only. Trip Units, Thermal-Magnetic Rated Current In [A] Thermal Trip [A] Ir = In (Fixed) Magnetic Trip [A] Im Cat. No. 25 30 32 35 40 50 60 63 70 80 90 100 110 125 150 160 175 200 225 250 25 30 32 35 40 50 60 63 70 56…80 63…90 70…100 77…110 87.5…125 105…150 112…160 122.5…175 140…200 157.5…225 175…250 400 400 400 400 400 500 600 630 700 400…800 450…900 500…1000 550…1100 625…1250 750…1500 800…1600 875…1750 1000…2000 1125…2250 1250…2500 Protection Type C (Fixed) C (Fixed) C (Fixed) C (Fixed) C (Fixed) C (Fixed) C (Fixed) C (Fixed) C (Fixed) F (Adjustable) F (Adjustable) F (Adjustable) F (Adjustable) F (Adjustable) F (Adjustable) F (Adjustable) F (Adjustable) F (Adjustable) F (Adjustable) F (Adjustable) 3 Poles 140G-JTC3-C25 140G-JTC3-C30 140G-JTC3-C32 140G-JTC3-C35 140G-JTC3-C40 140G-JTC3-C50 140G-JTC3-C60 140G-JTC3-C63 140G-JTC3-C70 140G-JTF3-C80 140G-JTF3-C90 140G-JTF3-D10 140G-JTF3-D11 140G-JTF3-D12 140G-JTF3-D15 140G-JTF3-D16 140G-JTF3-D17 140G-JTF3-D20 140G-JTF3-D22 140G-JTF3-D25 4 Poles 140G-JTC4-C25 140G-JTC4-C30 140G-JTC4-C32 140G-JTC4-C35 140G-JTC4-C40 140G-JTC4-C50 140G-JTC4-C60 140G-JTC4-C63 140G-JTC4-C70 140G-JTF4-C80 140G-JTF4-C90 140G-JTF4-D10 140G-JTF4-D11 140G-JTF4-D12 140G-JTF4-D15 140G-JTF4-D16 140G-JTF4-D17 140G-JTF4-D20 140G-JTF4-D22 140G-JTF4-D25 Cat. No. Cat. No. 3 Poles 140G-JTH3-C40 140G-JTH3-C60 140G-JTH3-D10 140G-JTH3-D15 140G-JTH3-D25 4 Poles 140G-JTH4-C40 140G-JTH4-C60 140G-JTH4-D10 140G-JTH4-D15 140G-JTH4-D25 Cat. No. Cat. No. 3 Poles 140G-JTI3-C40 140G-JTI3-C60 140G-JTI3-D10 140G-JTI3-D15 140G-JTI3-D25 4 Poles 140G-JTI4-C40 140G-JTI4-C60 140G-JTI4-D10 140G-JTI4-D15 140G-JTI4-D25 Trip Units, Electronic LSI (Long, Short, Instantaneous) Protection Type Rated Current In [A] I1=0.4…1 x In 40 60 100 150 250 16…40 24…60 40…100 60…150 100…250 L S t1=sec. 3, 3, 3, 3, 3, 12, 12, 12, 12, 12, 36, 36, 36, 36, 36, I2=1…10 x In 60 60 60 60 60 40…400 60…600 100…1000 150…1500 250…2500 I I3=1…10 x In t2=sec. 0.05, 0.05, 0.05, 0.05, 0.05, 0.1, 0.1, 0.1, 0.1, 0.1, 0.2, 0.2, 0.2, 0.2, 0.2, 0.4 0.4 0.4 0.4 0.4 40…400 60…600 100…1000 150…1500 250…2500 Trip Units, Electronic LSIG (Long, Short, Instantaneous, Ground Fault) Protection Type Rated Current In [A] I1=0.4…1 x In 40 60 100 150 250 16…40 24…60 40…100 60…150 100…250 L S t1=sec. 3, 3, 3, 3, 3, 12, 12, 12, 12, 12, 36, 36, 36, 36, 36, I2=1…10 x In 60 60 60 60 60 40…400 60…600 100…1000 150…1500 250…2500 I G I3=1…10 x In I4=0.2…1 x In t2=sec. 0.05, 0.05, 0.05, 0.05, 0.05, 0.1, 0.1, 0.1, 0.1, 0.1, 0.2, 0.2, 0.2, 0.2, 0.2, 0.4 0.4 0.4 0.4 0.4 40…400 60…600 100…1000 150…1500 250…2500 8…40 12…60 20…100 30…150 50…250 0.1, 0.1, 0.1, 0.1, 0.1, t4=sec. 0.2, 0.2, 0.2, 0.2, 0.2, 0.4, 0.4, 0.4, 0.4, 0.4, 0.8 0.8 0.8 0.8 0.8 Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 15 Bulletin 140G Molded Case Circuit Breakers Product Selection — 250 A, J-Frame Assembled Molded Case Circuit Breakers — 250 A J-Frame Interrupting Rating/Breaking Capacity — Thermal-Magnetic Circuit Breakers Interrupting Rating (50/60 Hz), UL 489/CSA C22.2-5, No. 5-02 [kA] Breaking Capacity (50/60 Hz), IEC 60947-2 220V 240V 65 100 150 200 480V 25 35 65 100 600V 14 18 25 35 Icu [kA] Ics [%Icu] 65 85 100 150 100 100 100 100 440V 415V Icu [kA] Ics [%Icu] 36 50 70 120 100 100 100 100 690V Icu [kA] Ics [%Icu] Icu [kA] Ics [%Icu] 36 50 65 100 100 100 100 100 10 12 15 20 100 100 100 100 Breaking Capacity (DC), IEC 60947-2 § 250V DC (2-pole 500V DC (3-pole in series) in series) Ics Ics Icu [kA] [%Icu] Icu [kA] [%Icu] 36 50 70 85 100 100 100 100 36 50 70 85 100 100 100 100 Interrupting Code‡ J2 J3 J6 J0 These ratings have not been tested for the CCC listing. ‡ See table below for Cat. No. selection § DC rating is applicable for thermal-magnetic trip unit only. Thermal-Magnetic, Fixed & Adjustable Rated Current In [A] Thermal Trip [A] Ir = In (Fixed) Magnetic Trip [A] Im 25 30 32 35 40 50 60 63 70 80 90 100 110 125 150 160 175 200 225 250 25 30 32 35 40 50 60 63 70 56…80 63…90 70…100 77…110 87.5…125 105…150 112…160 122.5…175 140…200 157.5…225 175…250 400 400 400 400 400 500 600 630 700 400…800 450…900 500…1000 550…1100 625…1250 750…1500 800…1600 875…1750 1000…2000 1125…2250 1250…2500 Rated Current In [A] Thermal Trip [A] Ir = In (Fixed) Magnetic Trip [A] Im 25 30 32 35 40 50 60 63 70 80 90 100 110 125 150 160 175 200 225 250 25 30 32 35 40 50 60 63 70 56…80 63…90 70…100 77…110 87.5…125 105…150 112…160 122.5…175 140…200 157.5…225 175…250 400 400 400 400 400 500 600 630 700 400…800 450…900 500…1000 550…1100 625…1250 750…1500 800…1600 875…1750 1000…2000 1125…2250 1250…2500 Interrupting Code J2 Cat. No. 3 Poles 4 Poles 140G-J2C3-C25 140G-J2C4-C25 140G-J2C3-C30 140G-J2C4-C30 140G-J2C3-C32 140G-J2C4-C32 140G-J2C3-C35 140G-J2C4-C35 140G-J2C3-C40 140G-J2C4-C40 140G-J2C3-C50 140G-J2C4-C50 140G-J2C3-C60 140G-J2C4-C60 140G-J2C3-C63 140G-J2C4-C63 140G-J2C3-C70 140G-J2C4-C70 140G-J2F3-C80 140G-J2F4-C80 140G-J2F3-C90 140G-J2F4-C90 140G-J2F3-D10 140G-J2F4-D10 140G-J2F3-D11 140G-J2F4-D11 140G-J2F3-D12 140G-J2F4-D12 140G-J2F3-D15 140G-J2F4-D15 140G-J2F3-D16 140G-J2F4-D16 140G-J2F3-D17 140G-J2F4-D17 140G-J2F3-D20 140G-J2F4-D20 140G-J2F3-D22 140G-J2F4-D22 140G-J2F3-D25 140G-J2F4-D25 Interrupting Code J3 Cat. No. 3 Poles 4 Poles 140G-J3C3-C25 140G-J3C4-C25 140G-J3C3-C30 140G-J3C4-C30 140G-J3C3-C32 140G-J3C4-C32 140G-J3C3-C35 140G-J3C4-C35 140G-J3C3-C40 140G-J3C4-C40 140G-J3C3-C50 140G-J3C4-C50 140G-J3C3-C60 140G-J3C4-C60 140G-J3C3-C63 140G-J3C4-C63 140G-J3C3-C70 140G-J3C4-C70 140G-J3F3-C80 140G-J3F4-C80 140G-J3F3-C90 140G-J3F4-C90 140G-J3F3-D10 140G-J3F4-D10 140G-J3F3-D11 140G-J3F4-D11 140G-J3F3-D12 140G-J3F4-D12 140G-J3F3-D15 140G-J3F4-D15 140G-J3F3-D16 140G-J3F4-D16 140G-J3F3-D17 140G-J3F4-D17 140G-J3F3-D20 140G-J3F4-D20 140G-J3F3-D22 140G-J3F4-D22 140G-J3F3-D25 140G-J3F4-D25 Interrupting Code J6 Cat. No. Cat. No. 3 Poles 4 Poles 140G-J6C3-C25 140G-J6C4-C25 140G-J6C3-C30 140G-J6C4-C30 140G-J6C3-C32 140G-J6C4-C32 140G-J6C3-C35 140G-J6C4-C35 140G-J6C3-C40 140G-J6C4-C40 140G-J6C3-C50 140G-J6C4-C50 140G-J6C3-C60 140G-J6C4-C60 140G-J6C3-C63 140G-J6C4-C63 140G-J6C3-C70 140G-J6C4-C70 140G-J6F3-C80 140G-J6F4-C80 140G-J6F3-C90 140G-J6F4-C90 140G-J6F3-D10 140G-J6F4-D10 140G-J6F3-D11 140G-J6F4-D11 140G-J6F3-D12 140G-J6F4-D12 140G-J6F3-D15 140G-J6F4-D15 140G-J6F3-D16 140G-J6F4-D16 140G-J6F3-D17 140G-J6F4-D17 140G-J6F3-D20 140G-J6F4-D20 140G-J6F3-D22 140G-J6F4-D22 140G-J6F3-D25 140G-J6F4-D25 Interrupting Code J0 Cat. No. 3 Poles 4 Poles 140G-J0C3-C25 140G-J0C4-C25 140G-J0C3-C30 140G-J0C4-C30 140G-J0C3-C32 140G-J0C4-C32 140G-J0C3-C35 140G-J0C4-C35 140G-J0C3-C40 140G-J0C4-C40 140G-J0C3-C50 140G-J0C4-C50 140G-J0C3-C60 140G-J0C4-C60 140G-J0C3-C63 140G-J0C4-C63 140G-J0C3-C70 140G-J0C4-C70 140G-J0F3-C80 140G-J0F4-C80 140G-J0F3-C90 140G-J0F4-C90 140G-J0F3-D10 140G-J0F4-D10 140G-J0F3-D11 140G-J0F4-D11 140G-J0F3-D12 140G-J0F4-D12 140G-J0F3-D15 140G-J0F4-D15 140G-J0F3-D16 140G-J0F4-D16 140G-J0F3-D17 140G-J0F4-D17 140G-J0F3-D20 140G-J0F4-D20 140G-J0F3-D22 140G-J0F4-D22 140G-J0F3-D25 140G-J0F4-D25 Visit our website: www.ab.com/catalogs 16 Publication 140G-SG001C-EN-P Bulletin 140G Molded Case Circuit Breakers Product Selection — 250 A, J-Frame Interrupting Rating/Breaking Capacity — Electronic Circuit Breakers Interrupting Rating (50/60 Hz), UL 489/CSA C22.2-5, No. 5-02 [kA] Breaking Capacity (50/60 Hz), IEC 60947-2 220V 240V 65 100 150 200 480V 25 35 65 100 600V 14 18 25 35 440V 415V Icu [kA] Ics [%Icu] 65 85 100 150 100 100 100 100 Icu [kA] Ics [%Icu] 36 50 70 120 100 100 100 100 690V Icu [kA] Ics [%Icu] Icu [kA] Ics [%Icu] 36 50 65 100 100 100 100 100 10 12 15 20 100 100 100 100 Breaking Capacity (DC), IEC 60947-2 § 250V DC (2-pole 500V DC (3-pole in series) in series) Ics Ics Icu [kA] [%Icu] Icu [kA] [%Icu] 36 50 70 85 100 100 100 100 36 50 70 85 100 100 100 100 Interrupting Code‡ J2 J3 J6 J0 These ratings have not been tested for the CCC listing. ‡ See table below for Cat. No. selection § DC rating is applicable for thermal-magnetic trip unit only. Electronic LSI (Long, Short, Instantaneous) Rated Current In [A] L I1=0.4…1 x In t1=sec. Protection Type S I2=1…10 x In 40 16…40 3, 12, 36, 60 40…400 60 24…60 3, 12, 36, 60 60…600 100 40…100 3, 12, 36, 60 100…1000 150 60…150 3, 12, 36, 60 150…1500 250 100…250 3, 12, 36, 60 250…2500 Rated Current In [A] I1=0.4…1 x In t1=sec. Protection Type S I2=1…10 x In 40 16…40 3, 12, 36, 60 40…400 60 24…60 3, 12, 36, 60 60…600 100 40…100 3, 12, 36, 60 100…1000 150 60…150 3, 12, 36, 60 150…1500 250 100…250 3, 12, 36, 60 250…2500 L t2=sec. 0.05, 0.1, 0.2, 0.4 0.05, 0.1, 0.2, 0.4 0.05, 0.1, 0.2, 0.4 0.05, 0.1, 0.2, 0.4 0.05, 0.1, 0.2, 0.4 t2=sec. 0.05, 0.1, 0.2, 0.4 0.05, 0.1, 0.2, 0.4 0.05, 0.1, 0.2, 0.4 0.05, 0.1, 0.2, 0.4 0.05, 0.1, 0.2, 0.4 Interrupting Code J2 Cat. No. Interrupting Code J3 Cat. No. I I3=1…10 x In 3 Poles 4 Poles 3 Poles 4 Poles 40…400 140G-J2H3-C40 140G-J2H4-C40 140G-J3H3-C40 140G-J3H4-C40 60…600 140G-J2H3-C60 140G-J2H4-C60 140G-J3H3-C60 140G-J3H4-C60 100…1000 140G-J2H3-D10 140G-J2H4-D10 140G-J3H3-D10 140G-J3H4-D10 150…1500 140G-J2H3-D15 140G-J2H4-D15 140G-J3H3-D15 140G-J3H4-D15 250…2500 140G-J2H3-D25 140G-J2H4-D25 140G-J3H3-D25 140G-J3H4-D25 I I3=1…10 x In Interrupting Code J6 Cat. No. Cat. No. Interrupting Code J0 Cat. No. 3 Poles 4 Poles 3 Poles 4 Poles 40…400 140G-J6H3-C40 140G-J6H4-C40 140G-J0H3-C40 140G-J0H4-C40 60…600 140G-J6H3-C60 140G-J6H4-C60 140G-J0H3-C60 140G-J0H4-C60 100…1000 140G-J6H3-D10 140G-J6H4-D10 140G-J0H3-D10 140G-J0H4-D10 150…1500 140G-J6H3-D15 140G-J6H4-D15 140G-J0H3-D15 140G-J0H4-D15 250…2500 140G-J6H3-D25 140G-J6H4-D25 140G-J0H3-D25 140G-J0H4-D25 Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 17 Bulletin 140G Molded Case Circuit Breakers Product Selection — 250 A, J-Frame Electronic LSIG (Long, Short, Instantaneous, Ground Fault) Rated Current In [A] 40 60 100 150 250 Rated Current In [A] 40 60 100 150 250 L I1=0.4… 1 x In t1=sec. 3, 12, 36, 60 3, 12, 36, 24…60 60 3, 12, 36, 40…100 60 3, 12, 36, 60…150 60 100…25 3, 12, 36, 0 60 16…40 L I1=0.4… 1 x In t1=sec. 3, 12, 36, 16…40 60 3, 12, 36, 24…60 60 3, 12, 36, 40…100 60 3, 12, 36, 60…150 60 100…25 3, 12, 36, 0 60 Protection Type S I G I2=1…10 I3=1…10 I4=0.2… t2=sec. t4=sec. x In x In 1 x In 40…400 60…600 100…10 00 150…15 00 250…25 00 0.05, 0.1, 0.2, 0.4 0.05, 0.1, 0.2, 0.4 0.05, 0.1, 0.2, 0.4 0.05, 0.1, 0.2, 0.4 0.05, 0.1, 0.2, 0.4 40…400 8…40 60…600 12…60 100…10 00 150…15 00 250…25 00 20…100 30…150 50…250 0.1, 0.2, 0.4, 0.8 0.1, 0.2, 0.4, 0.8 0.1, 0.2, 0.4, 0.8 0.1, 0.2, 0.4, 0.8 0.1, 0.2, 0.4, 0.8 Protection Type S I G I2=1…10 I3=1…10 I4=0.2… t2=sec. t4=sec. x In x In 1 x In 40…400 60…600 100…10 00 150…15 00 250…25 00 0.05, 0.1, 0.2, 0.4 0.05, 0.1, 0.2, 0.4 0.05, 0.1, 0.2, 0.4 0.05, 0.1, 0.2, 0.4 0.05, 0.1, 0.2, 0.4 40…400 8…40 60…600 12…60 100…10 00 150…15 00 250…25 00 20…100 30…150 50…250 0.1, 0.2, 0.4, 0.8 0.1, 0.2, 0.4, 0.8 0.1, 0.2, 0.4, 0.8 0.1, 0.2, 0.4, 0.8 0.1, 0.2, 0.4, 0.8 Interrupting Code J2 Cat. No. Interrupting Code J3 Cat. No. 3 Poles 4 Poles 3 Poles 4 Poles 140G-J2I3-C40 140G-J2I4-C40 140G-J3I3-C40 140G-J3I4-C40 140G-J2I3-C60 140G-J2I4-C60 140G-J3I3-C60 140G-J3I4-C60 140G-J2I3-D10 140G-J2I4-D10 140G-J3I3-D10 140G-J3I4-D10 140G-J2I3-D15 140G-J2I4-D15 140G-J3I3-D15 140G-J3I4-D15 140G-J2I3-D25 140G-J2I4-D25 140G-J3I3-D25 140G-J3I4-D25 Interrupting Code J6 Cat. No. Cat. No. Interrupting Code J0 Cat. No. 3 Poles 4 Poles 3 Poles 4 Poles 140G-J6I3-C40 140G-J6I4-C40 140G-J0I3-C40 140G-J0I4-C40 140G-J6I3-C60 140G-J6I4-C60 140G-J0I3-C60 140G-J0I4-C60 140G-J6I3-D10 140G-J6I4-D10 140G-J0I3-D10 140G-J0I4-D10 140G-J6I3-D15 140G-J6I4-D15 140G-J0I3-D15 140G-J0I4-D15 140G-J6I3-D25 140G-J6I4-D25 140G-J0I3-D25 140G-J0I4-D25 Molded Case Switch — UL489§ Rated Current In [A] Magnetic Trip [A] Im 250 2500 Cat. No. 3 Poles 140G-J0S3-D25 4 Poles 140G-J0S4-D25 § Does not provide overcurrent protection; may open above 2500 A. Visit our website: www.ab.com/catalogs 18 Publication 140G-SG001C-EN-P Bulletin 140G Molded Case Circuit Breakers Product Selection — 250 A, J-Frame Page Intentionally Left Blank Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 19 Bulletin 140G Molded Case Circuit Breakers Catalog Number Explanation — 400 A, K-Frame Complete Circuit Breaker Assemblies — 400 A, K-Frame Examples given in this section are not intended to be used for product selection. Use ProposalWorks to configure the molded case circuit breaker. Use these configurations only to select all factory-installed options for shunt trips, undervoltage release units, auxiliary contacts, and alarm contacts. Use the codes from Table g to add on to the molded case circuit breaker cat. no. selected on the previous pages to form a complete cat. no. for a complete assembly with factory-installed options. 140G – K a b 3 C 3 – C60 – SD – AA c d e f g a d g Bulletin No. Protection Type Factory-Installed Internal Options♦ Code Description Code Description 140G Global Molded Case Circuit Breaker F Adjust thermal/ adjust magnetic Code Description H Electronic LSI -long, short, instant SJ Shunt Trip, 24…30V AC/DC I Electronic LSIG -long, short, instant & ground fault b Frame/Rating Code Description K Electronic LSIG-MM -long, short, instant, ground fault & MM K 400 A S Molded case switch (isolator) X Breaker Frame c Interrupting Rating/Breaking Capacity (based on Ic at 480V) Shunt Trip and Undervoltage Release Units SK Shunt Trip, 48…60V AC/DC SD Shunt Trip, 110…127V AC; 110…125V DC SA Shunt Trip, 220…240V AC; 220…250V DC SB Shunt Trip, 380…440V AC SC Shunt Trip, 480…525V AC e UJ Undervoltage Release, 24…30V AC/DC Poles UR Undervoltage Release, 48V AC/DC UD Undervoltage Release, 110…127V AC; 110…125V DC Code Description Code Description 3 35 kA 3 3 poles 6 65 kA 4 4 poles UA 0 100 kA Undervoltage Release, 220…240V AC; 220…250V DC 15 150 kA f UB Undervoltage Release, 380…440V AC T Trip unit UC Undervoltage Release, 480…525V AC Current Range No Digit No Selection Code Description D25 e.g., 250 A D30 e.g., 300 A Code Description D40 e.g., 400 A AA 1 Aux., 1 Alarm Contact, 250V Blank Frame only CA 3 Aux., 1 Alarm Contact, 250V AB 1 Aux., 1 Alarm Contact, 400V Auxiliary and Alarm Contacts FB 2 Aux. Contacts, 400V CJ 3 Aux., 1 Alarm Contact, 24V ♦ Select up to two internal options: 1 for left side mounting (shunt trip or undervoltage release), 1 for right (auxiliary or alarm contact). Consult your local Rockwell automation sales office or Allen-Bradley distributor for further assistance. Visit our website: www.ab.com/catalogs 20 Publication 140G-SG001C-EN-P Bulletin 140G Molded Case Circuit Breakers Product Selection — 400 A, K-Frame Breaker Frames & Trip Units + Frame Breaker Frames, 400 A Rated Current Interrupting Rating (50/60 Hz), UL 489/CSA C22.2-5, No. 5-02 [kA] 2-pole 3-Pole in in series series 240V 100 150 200 200 480V 35 65 100 150 600V 25 35 65 100 500V DC ‡ 35 50 65 100 600V DC ‡ 25 35 50 65 = Trip Unit MCCB Breaking Capacity (DC), IEC 60947-2 ‡ Breaking Capacity (50/60 Hz), IEC 60947-2 Icu 220V Ics [kA] [%Icu] 85 100 200 200 100 100 100 100 415V Icu [kA] Ics [%Icu] 50 70 120 200 100 100 100 100 Icu 440V Ics [kA] [%Icu] 40 65 100 180 500V DC (3-pole in series) Ics Ics [%Icu] Icu [kA] [%Icu] Cat. No. 690V Icu [kA] 100 100 100 100 25 40 70 80 100 100 100 100 36 50 70 100 100 100 100 100 3 Poles 140G-K3X3 140G-K6X3 140G-K0X3 140G-K15X3 4 Poles 140G-K3X4 140G-K6X4 140G-K0X4 140G-K15X4 These ratings have not been tested for the CCC listing. ‡ DC rating is applicable for thermal-magnetic trip unit only. Trip Units, Thermal-Magnetic Rated Current In [A] Thermal Trip [A] Ir = In Magnetic Trip [A] Im Cat. No. 300 400 210…300 280…400 1500…3000 2000…4000 Protection Type F (Adjustable Thermal/ Adjustable Magnetic) F (Adjustable Thermal/ Adjustable Magnetic) 3 Poles 140G-KTF3-D30 140G-KTF3-D40 4 Poles 140G-KTF4-D30 140G-KTF4-D40 Trip Units, Electronic LSI (Long, Short, Instantaneous) Protection Type Cat. No. Rated Current In [A] I1=0.4…1 x In t1=sec. I2=0.6…10 x In t2=sec. I I3=1.5…12 x In 300 400 120…300 160…400 3, 6, 9, 18 3, 6, 9, 18 180…3000 240…4000 0.05, 0.1, 0.25, 0.5 0.05, 0.1, 0.25, 0.5 450…3600 600…4800 L S 3 Poles 3 Poles 140G-KTH3-D30 140G-KTH4-D30 140G-KTH3-D40 140G-KTH4-D40 Trip Units, Electronic LSIG (Long, Short, Instantaneous, Ground Fault) Rated Current In [A] L I1=0.4…1 x In t1=sec. Protection Type S I I2=0.6…10 x In t2=sec. I3=1.5…12 x In 300 120…300 3, 6, 9, 18 180…3000 400 160…400 3, 6, 9, 18 240…4000 0.05, 0.1, 0.25, 0.5 0.05, 0.1, 0.25, 0.5 G I4=0.2…1 x In 450…3600 60…300 600…4800 80…400 Cat. No. Cat. No. 3 Poles 4 Poles 140G-KTI3-D30 140G-KTI4-D30 140G-KTI3-D40 140G-KTI4-D40 t4=sec. 0.1, 0.2, 0.4, 0.8 0.1, 0.2, 0.4, 0.8 Trip Units, Electronic LSIG-MM (Long, Short, Instantaneous, Ground Fault - Maintenance Mode) Protection Type S I I2=0.6…10 x In t2=sec. I3=1.5…12 x In Rated Current In [A] L I1=0.4…1 x In t1=sec. 300 120…300 3, 6, 9, 18 180…3000 400 160…400 3, 6, 9, 18 240…4000 0.05, 0.1, 0.25, 0.5 0.05, 0.1, 0.25, 0.5 Cat. No. G I4=0.2…1 x In 450…3600 60…300 600…4800 80…400 t4=sec. 0.1, 0.2, 0.4, 0.8 0.1, 0.2, 0.4, 0.8 3 Poles 4 Poles 140G-KTK3-D30 140G-KTK4-D30 140G-KTK3-D40 140G-KTK4-D40 Assembled molded case circuit breakers found on pages 22…24 Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 21 Bulletin 140G Molded Case Circuit Breakers Product Selection — 400 A, K-Frame Assembled Molded Case Circuit Breakers — 400 A K-Frame Interrupting Rating/Breaking Capacity — Thermal-Magnetic Circuit Breakers Interrupting Rating (50/60 Hz), UL 489/CSA C22.2-5, No. 5-02 [kA] 2-pole 3-Pole in series in series 240V 100 150 200 200 480V 35 65 100 150 600V 25 35 65 100 500V DC 35 50 65 100 600V DC 25 35 50 65 Breaking Capacity (50/60 Hz), IEC 60947-2 220V 440V 415V Icu [kA] Ics [%Icu] 85 100 200 200 100 100 100 100 Icu [kA] Ics [%Icu] 50 70 120 200 100 100 100 100 690V Icu [kA] Ics [%Icu] Icu [kA] Ics [%Icu] 40 65 100 180 100 100 100 100 25 40 70 80 100 100 100 100 Breaking Capacity (DC), IEC 60947-2 § 500V DC (3-pole in series) Ics Interrupting Icu [kA] [%Icu] Code‡ 36 100 K3 K6 50 100 K0 70 100 K15 100 100 These ratings have not been tested for the CCC listing. ‡ See table below for Cat. No. selection § DC rating is applicable for thermal-magnetic trip unit only. Thermal-Magnetic, Fixed & Adjustable Rated Current In [A] Thermal Trip [A] Ir = In (Fixed) Magnetic Trip [A] Im 300 210…300 1500…3000 400 280…400 2000…4000 Rated Current In [A] Thermal Trip [A] Ir = In (Fixed) Magnetic Trip [A] Im 300 210…300 1500…3000 400 280…400 2000…4000 Protection Type F (Adjustable Thermal/ Adjustable Magnetic) F (Adjustable Thermal/ Adjustable Magnetic) Protection Type F (Adjustable Thermal/ Adjustable Magnetic) F (Adjustable Thermal/ Adjustable Magnetic) Interrupting Code K3 Cat. No. 3 Poles 4 Poles 140G-K3F3-D30 140G-K3F4-D30 140G-K6F3-D30 140G-K6F4-D30 140G-K3F3-D40 140G-K3F4-D40 140G-K6F3-D40 140G-K6F4-D40 Interrupting Code K0 Cat. No. 3 Poles 4 Poles Interrupting Code K15 Cat. No. 3 Poles 3 Poles 140G-K0F3-D30 140G-K0F4-D30 140G-K15F3-D30 140G-K15F3-D30 140G-K0F3-D40 140G-K0F4-D40 140G-K15F3-D40 140G-K15F3-D40 Visit our website: www.ab.com/catalogs 22 Interrupting Code K6 Cat. No. 3 Poles 4 Poles Publication 140G-SG001C-EN-P Bulletin 140G Molded Case Circuit Breakers Product Selection — 400 A, K-Frame Breaking Capacity/Interrupting Rating — Electronic Circuit Breakers Interrupting Rating (50/60 Hz), UL 489/CSA C22.2-5, No. 5-02 [kA] 2-pole 3-Pole in series in series 240V 100 150 200 200 480V 35 65 100 150 500V DC 35 50 65 100 600V 25 35 65 100 600V DC 25 35 50 65 Breaking Capacity (50/60 Hz), IEC 60947-2 220V 440V 415V Icu [kA] Ics [%Icu] 85 100 200 200 100 100 100 100 Icu [kA] Ics [%Icu] 50 70 120 200 100 100 100 100 690V Icu [kA] Ics [%Icu] Icu [kA] Ics [%Icu] 40 65 100 180 100 100 100 100 25 40 70 80 100 100 100 100 Breaking Capacity (DC), IEC 60947-2 § 500V DC (3-pole in series) Ics Icu [kA] [%Icu] 36 50 70 100 100 100 100 100 Interrupting Code‡ K3 K6 K0 K15 These ratings have not been tested for the CCC listing. ‡ See table below for Cat. No. selection § DC rating is applicable for thermal-magnetic trip unit only. Electronic LSI (Long, Short, Instantaneous), Adjustable Rated Current In [A] L I1=0.4…1 x In t1=sec. Protection Type S I2=0.6…10 x In 300 120…300 3, 6, 9, 18 180…3000 400 160…400 3, 6, 9, 18 240…4000 L t2=sec. 0.05, 0.1, 0.25, 0.5 0.05, 0.1, 0.25, 0.5 Protection Type S I2=0.6…10 t1=sec. t2=sec. x In Rated Current In [A] I1=0.4…1 x In 300 120…300 3, 6, 9, 18 180…3000 400 160…400 3, 6, 9, 18 240…4000 0.05, 0.1, 0.25, 0.5 0.05, 0.1, 0.25, 0.5 Interrupting Code K3 Cat. No. I I3=1.5…12 x In 3 Poles Interrupting Code K6 Cat. No. 4 Poles 3 Poles 4 Poles 450…3600 140G-K3H3-D30 140G-K3H4-D30 140G-K6H3-D30 140G-K6H4-D30 600…4800 140G-K3H3-D40 140G-K3H4-D40 140G-K6H3-D40 140G-K6H4-D40 I I3=1.5…12 x In Interrupting Code K0 Cat. No. 3 Poles Interrupting Code K15 Cat. No. 3 Poles 4 Poles 450…3600 140G-K0H3-D30 140G-K0H4-D30 4 Poles 140G-K15H3-D30 140G-K15H4-D30 600…4800 140G-K0H3-D40 140G-K0H4-D40 140G-K15H3-D40 140G-K15H4-D40 Electronic LSIG (Long, Short, Instantaneous, Ground Fault), Adjustable Rated Current In [A] L I1=0.4…1 t1=sec. x In 300 120…300 400 160…400 Rated Current In [A] 3, 6, 9, 18 3, 6, 9, 18 L I1=0.4…1 t1=sec. x In 300 120…300 400 160…400 3, 6, 9, 18 3, 6, 9, 18 Protection Type S I G I2=0.6…10 I3=1.5…12 I4=0.2… t2=sec. t4=sec. x In x In 1 x In 0.05, 0.1, 450…3600 60…300 0.25, 0.5 0.05, 0.1, 240…4000 600…4800 80…400 0.25, 0.5 180…3000 0.1, 0.2, 0.4, 0.8 0.1, 0.2, 0.4, 0.8 Protection Type S I G I2=0.6…12 I3=1.5…12 I4=0.2… t2=sec. t4=sec. x In x In 1 x In Interrupting Code K3 Cat. No. 3 Poles 4 Poles Interrupting Code K6 Cat. No. 3 Poles 4 Poles 140G-K3I3-D30 140G-K3I4-D30 140G-K6I3-D30 140G-K6I4-D30 140G-K3I3-D40 140G-K3I4-D40 140G-K6I3-D40 140G-K6I4-D40 Interrupting Code K0 Cat. No. Interrupting Code K15 Cat. No. 3 Poles 4 Poles 3 Poles 4 Poles 0.05, 0.1, 0.1, 0.2, 140G-K0I3-D30 140G-K0I4-D30 140G-K15I3-D30 140G-K15I4-D30 450…3600 60…300 0.25, 0.5 0.4, 0.8 0.05, 0.1, 0.1, 0.2, 140G-K0I3-D40 140G-K0I4-D40 140G-K15I3-D40 140G-K15I4-D40 240…4000 600…4800 80…400 0.25, 0.5 0.4, 0.8 180…3000 Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 23 Bulletin 140G Molded Case Circuit Breakers Product Selection — 400 A, K-Frame Electronic LSIG-MM (Long, Short, Instantaneous, Ground Fault - Maintenance Mode), Adjustable Rated Current In [A] Protection Type S I I2=0.6… I3=1.5… t2=sec. 10 x In 12 x In L I1=0.4… 1 x In t1=sec. 120… 300 160… 400 3, 6, 9, 18 3, 6, 9, 18 300 400 L Rated Current I1=0.4… t1=sec. 1 x In In [A] 180… 3000 240… 4000 0.05, 0.1, 0.25, 0.5 0.05, 0.1, 0.25, 0.5 450… 3600 600… 4800 Interrupting Code K3 Cat. No. G I4=0.2… 1 x In 60…300 80…400 t4=sec. 0.1, 0.2, 0.4, 0.8 0.1, 0.2, 0.4, 0.8 Protection Type S I G I2=0.6… I3=1.5… I4=0.2… t4=sec. 10 x In t2=sec. 12 x In 1 x In 300 120… 300 3, 6, 9, 18 180… 3000 400 160… 400 3, 6, 9, 18 240… 4000 0.05, 0.1, 0.25, 0.5 0.05, 0.1, 0.25, 0.5 Interrupting Code K6 Cat. No. 3 Poles 4 Poles 3 Poles 4 Poles 140G-K3K3-D30 140G-K3K4-D30 140G-K6K3-D30 140G-K6K4-D30 140G-K3K3-D40 140G-K3K4-D40 140G-K6K3-D40 140G-K6K4-D40 Interrupting Code K0 Cat. No. 3 Poles Interrupting Code K15 Cat. No. 4 Poles 3 Poles 4 Poles 450… 3600 60…300 0.1, 0.2, 140G-K0K3-D30 0.4, 0.8 140G-K0K4-D30 140G-K15K3-D30 140G-K15K4-D30 600… 4800 80…400 0.1, 0.2, 140G-K0K3-D40 0.4, 0.8 140G-K0K4-D40 140G-K15K3-D40 140G-K15K4-D40 Maintenance Mode (MM) Maintenance Mode (MM) offers a preset set of protection parameters. MM allows systems testing when the molded case circuit breaker is energized or ON. This feature is a manual adjustment on the molded case circuit breaker, via a DIP switch. The following table illustrates the preset values for Maintenance Mode. L S I MM I1=1 x In t1=MAX sec. I2=OFF t2=OFF sec. I3=4 x In I4=OFF t4=OFF sec. I5=2.5 x In 300 400 300 400 18 18 — — — — 1200 1600 — — — — 750 1000 Molded Case Switch — UL489§ Rated Current In [A] Magnetic Trip [A] Im 400 5000 Cat. No. 3 Poles 140G-K15S3-D40 4 Poles 140G-K15S4-D40 § Does not provide overcurrent protection; may open above 5000 A. Visit our website: www.ab.com/catalogs 24 G Rated Current In [A] Publication 140G-SG001C-EN-P Bulletin 140G Molded Case Circuit Breakers Product Selection — 400 A, K-Frame Page Intentionally Left Blank Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 25 Bulletin 140G Molded Case Circuit Breakers Catalog Number Explanation — 800 A, M-Frame Complete Circuit Breaker Assemblies — 800 A, M-Frame Examples given in this section are not intended to be used for product selection. Use ProposalWorks to configure the molded case circuit breaker. Use these configurations only to select all factory-installed options for shunt trips, undervoltage release units, auxiliary contacts, and alarm contacts. Use the codes from Table g to add on to the molded case circuit breaker cat. no. selected on the previous pages to form a complete cat. no. for a complete assembly with factory-installed options. 140G – M a b 6 K 3 – D60 – SD – AA c d e f g a d g Bulletin No. Protection Type Factory-Installed Internal Options♦ Code Description Code Description 140G Global Molded Case Circuit Breaker F Adjust thermal/ adjust magnetic Code Description H Electronic LSI -long, short, instant SJ Shunt Trip, 24…30V AC/DC I Electronic LSIG -long, short, instant & ground fault b Frame/Rating Code Description M 800 A K Electronic LSIG-MM -long, short, instant, ground fault & MM X Breaker frame S Molded case switch (isolator) c e Interrupting Rating/Breaking Capacity (based on Ic at 480V) Code Description 5 50 kA 6 65 kA 0 100 kA T Trip unit Poles Code Description 3 3 poles 4 4 poles f Current Range Shunt Trip and Undervoltage Release Units SK Shunt Trip, 48…60V AC/DC SD Shunt Trip, 110…127V AC; 110…125V DC SA Shunt Trip, 220…240V AC; 220…250V DC SB Shunt Trip, 380…440V AC SC Shunt Trip, 480…525V AC UJ Undervoltage Release, 24…30V AC/DC UR Undervoltage Release, 48V AC/DC UY Undervoltage Release, 60V AC/DC UD Undervoltage Release, 110…127V AC; 110…125V DC UA Undervoltage Release, 220…240V AC; 220…250V DC UB Undervoltage Release, 380…440V AC UC Undervoltage Release, 480…525V AC No Digit No Selection Code Description D60 e.g., 600 A D63 e.g., 630 A Code Description D80 e.g., 800 A AA 1 Aux., 1 Alarm Contact, 250V Blank Frame only CA 3 Aux., 1 Alarm Contact, 250V Auxiliary and Alarm Contacts, Trip Units FB 2 Aux. Contacts, 400V AB 1 Aux., 1 Alarm Contact, 400V CJ 3 Aux., 1 Alarm Contact, 24V ♦ Select up to two internal options: 1 for left side mounting (shunt trip or undervoltage release), 1 for right (auxiliary or alarm contact). Consult your local Rockwell automation sales office or Allen-Bradley distributor for further assistance. Visit our website: www.ab.com/catalogs 26 Publication 140G-SG001C-EN-P Bulletin 140G Molded Case Circuit Breakers Product Selection — 800 A, M-Frame Breaker Frames & Trip Units + = Frame Trip Unit MCCB Breaker Frames, 800 A Rated Current Interrupting Rating (50/60 Hz), UL 489/CSA C22.2-5, No. 5-02 [kA] 3-Pole in series 240V 100 200 200 480V 50 65 100 600V 25 35 42 600V DC 20 35 50 Breaking Capacity (DC), IEC 60947-2 § 750V DC (3-pole in 690V series) [kA] Ics [%Icu] Icu [kA] Ics [%Icu] Breaking Capacity (50/60 Hz), IEC 60947-2 220V Icu [kA] Ics [%Icu] 85 100 200 415V Icu [kA] Ics [%Icu] 100 100 75 50 70 100 Icu 100 100 75 22 25 30 75 75 75 16 36 50 75 75 75 Cat. No. 3 Poles 4 Poles 140G-M5X3 140G-M5X4 140G-M6X3 140G-M6X4 140G-M0X3 140G-M0X4 These ratings have not been tested for the CCC listing. ‡ See table below for Cat. No. selection § DC rating is applicable for thermal-magnetic trip unit only. Trip Units, Thermal-Magnetic Rated Current In [A] Thermal Trip [A] Ir = In Magnetic Trip [A] Im Cat. No. 600 800 420…630 560…800 3000…6000 4000…8000 Protection Type F (Adjustable Thermal/ Adjustable Magnetic) F (Adjustable Thermal/ Adjustable Magnetic) 3 Poles 140G-MTF3-D60 140G-MTF3-D80 4 Poles 140G-MTF3-D60 140G-MTF4-D80 Trip Units, Electronic LSI (Long, Short, Instantaneous) Cat. No. Protection Type Rated Current In [A] I1=0.4…1 x In t1=sec. I2=0.6…10 x In t2=sec. I I3=1.5…12 x In 600 800 240…600 320…800 3, 6, 9, 18 3, 6, 9, 18 360…6000 480…8000 0.05, 0.1, 0.25, 0.5 0.05, 0.1, 0.25, 0.5 900…7200 800…8400 L S 3 Poles 4 Poles 140G-MTH3-D60 140G-MTH4-D60 140G-MTH3-D80 140G-MTH4-D80 Trip Units, Electronic LSIG (Long, Short, Instantaneous, Ground Fault) Rated Current In [A] Protection Type S L I1=0.4…1 x In t1=sec. I2=0.6…10 x In 600 240…600 3, 6, 9, 18 360…6000 800 320…800 3, 6, 9, 18 480…8000 t2=sec. 0.05, 0.1, 0.25, 0.5 0.05, 0.1, 0.25, 0.5 Cat. No. I I3=1.5…12 x In G I4=0.2…1 x In 900…7200 120…600 800…8400 160…800 t4=sec. 0.1, 0.2, 0.4, 0.8 0.1, 0.2, 0.4, 0.8 3 Poles 4 Poles 140G-MTI3-D60 140G-MTI4-D60 140G-MTI3-D80 140G-MTI4-D80 Trip Units, Electronic LSIG-MM (Long, Short, Instantaneous, Ground Fault - Maintenance Mode) Rated Current In [A] Protection Type S L I1=0.4…1 x In t1=sec. I2=0.6…10 x In 600 240…600 3, 6, 9, 18 360…6000 800 320…800 3, 6, 9, 18 480…8000 t2=sec. 0.05, 0.1, 0.25, 0.5 0.05, 0.1, 0.25, 0.5 Cat. No. I I3=1.5…12 x In G I4=0.2…1 x In 900…7200 120…600 800…8400 160…800 t4=sec. 0.1, 0.2, 0.4, 0.8 0.1, 0.2, 0.4, 0.8 3 Poles 4 Poles 140G-MTK3-D60 140G-MTK4-D60 140G-MTK3-D80 140G-MTK4-D80 Assembled molded case circuit breakers found on pages 28…30 Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 27 Bulletin 140G Molded Case Circuit Breakers Product Selection — 800 A, M-Frame Assembled Molded Case Circuit Breakers — 800 A M-Frame Interrupting Rating/Breaking Capacity — Thermal-Magnetic Circuit Breakers Interrupting Rating (50/60 Hz), UL 489/CSA C22.2-5, No. 5-02 [kA] 3-Pole in series 240V 100 200 200 480V 50 65 100 600V 25 35 42 600V DC 20 35 50 Breaking Capacity (50/60 Hz), IEC 60947-2 220V Ics [%Icu] Icu [kA] 85 100 200 100 100 75 Icu [kA] 50 70 100 415V Ics [%Icu] Icu [kA] 100 100 75 22 25 30 690V Ics [%Icu] 75 75 75 Breaking Capacity (DC), IEC 60947-2 750V DC (3-pole in series) Icu [kA] Ics [%Icu] 16 36 50 75 75 75 Interrupting Code‡ M5 M6 M0 These ratings have not been tested for the CCC listing. ‡ See table below for Cat. No. selection Thermal-Magnetic, Adjustable & Adjustable Rated Current In [A] 600 630 § 800 Thermal Trip [A] Ir = I n Magnetic Trip [A] Im Protection Type Interrupting Code M5 Cat. No. 3 Poles 4 Poles Interrupting Code M6 Cat. No. 3 Poles 4 Poles 420…630 3000…6000 140G-M5F3-D60 140G-M5F4-D60 140G-M6F3-D60 140G-M6F4-D60 140G-M0F3-D60 140G-M0F4-D60 F (Adjustable 441…630 3150…6300 Thermal/ 140G-M5F3-D63 140G-M5F4-D63 140G-M6F3-D63 140G-M6F4-D63 140G-M0F3-D63 140G-M0F4-D63 Adjustable 560…800 4000…8000 Magnetic) 140G-M5F3-D80 140G-M5F4-D80 140G-M6F3-D80 140G-M6F4-D80 140G-M0F3-D80 140G-M0F4-D80 § IEC only. Visit our website: www.ab.com/catalogs 28 Interrupting Code M0 Cat. No. 3 Poles 4 Poles Publication 140G-SG001C-EN-P Bulletin 140G Molded Case Circuit Breakers Product Selection — 800 A, M-Frame Interrupting Rating/Breaking Capacity — Electronic Circuit Breakers Interrupting Rating (50/60 Hz), UL 489/CSA C22.2-5, No. 5-02 [kA] 3-Pole in series 240V 100 200 200 480V 50 65 100 600V 25 35 42 600V DC 20 35 50 Breaking Capacity (50/60 Hz), IEC 60947-2 220V Ics [%Icu] Icu [kA] 85 100 200 Icu [kA] 100 100 75 415V Ics [%Icu] 50 70 100 Icu [kA] 100 100 75 690V Ics [%Icu] 22 25 30 75 75 75 Breaking Capacity (DC), IEC 60947-2 750V DC (3-pole in series) Icu [kA] Ics [%Icu] 16 36 50 75 75 75 Interrupting Code‡ M5 M6 M0 These ratings have not been tested for the CCC listing. ‡ See table below for Cat. No. selection Electronic LSI (Long, Short, Instantaneous) Protection Type S I2=1…10 x In L Rated Current In [A] I1=0.4…1 x In t1=sec. 600 240…600 3, 6, 9, 18 360…6000 630 § 252…630 3, 6, 9, 18 378…6300 800 320…800 3, 6, 9, 18 480…8000 t2=sec. 0.05, 0.1, 0.25, 0.5 0.05, 0.1, 0.25, 0.5 0.05, 0.1, 0.25, 0.5 Interrupting Code M5 Cat. No. I I3=1…10 x In 3 Poles 4 Poles Interrupting Code M6 Cat. No. Cat. No. 4 Poles 3 Poles 900…7200 140G-M5H3-D60 140G-M5H4-D60 140G-M6H3-D60 140G-M6H4-D60 945…7560 140G-M5H3-D63 140G-M5H4-D63 140G-M6H3-D63 140G-M6H4-D63 800…8400 140G-M5H3-D80 140G-M5H4-D80 140G-M6H3-D80 140G-M6H4-D80 § IEC only. Protection Type Rated Current In [A] I1=0.4…1 x In t1=sec. I2=1…10 x In t2=sec. I I3=1…10 x In 600 630 § 800 240…600 252…630 320…800 3, 6, 9, 18 3, 6, 9, 18 3, 6, 9, 18 360…6000 378…6300 480…8000 0.05, 0.1, 0.25, 0.5 0.05, 0.1, 0.25, 0.5 0.05, 0.1, 0.25, 0.5 900…7200 945…7560 800…8400 L S Interrupting Code M0 Cat. No. 3 Poles 4 Poles 140G-M0H3-D60 140G-M0H4-D60 140G-M0H3-D63 140G-M0H4-D63 140G-M0H3-D80 140G-M0H4-D80 § IEC only. Electronic LSIG (Long, Short, Instantaneous, Ground Fault) Rated Current In [A] I1=0.4…1 x In t1=sec. Protection Type S I G I2=1…10 I3=1…10 I4=0.2…1 t2=sec. t4=sec. x In x In x In 240…60 0 252…63 0 320…80 0 3, 6, 9, 18 3, 6, 9, 18 3, 6, 9, 18 360…60 0.05, 0.1, 900…72 00 0.25, 0.5 00 378…63 0.05, 0.1, 945…75 00 0.25, 0.5 60 480…80 0.05, 0.1, 800…84 00 0.25, 0.5 00 L 600 630 § 800 120…60 0 126…63 0 160…80 0 0.1, 0.2, 0.4, 0.8 0.1, 0.2, 0.4, 0.8 0.1, 0.2, 0.4, 0.8 Interrupting Code M5 Cat. No. Interrupting Code M6 Cat. No. 3 Poles 4 Poles 3 Poles 4 Poles 140G-M5I3-D60 140G-M5I4-D60 140G-M6I3-D60 140G-M6I4-D60 140G-M5I3-D63 140G-M5I4-D63 140G-M6I3-D63 140G-M6I4-D63 140G-M5I3-D80 140G-M5I4-D80 140G-M6I3-D80 140G-M6I4-D80 § IEC only. Protection Type S I G I2=1…10 x In t2=sec. I3=1…10 x In I4=0.2…1 x In Rated Current In [A] I1=0.4…1 x In t1=sec. 600 240…600 3, 6, 9, 18 360…6000 630 § 252…630 3, 6, 9, 18 378…6300 800 320…800 3, 6, 9, 18 480…8000 L 0.05, 0.1, 0.25, 0.5 0.05, 0.1, 0.25, 0.5 0.05, 0.1, 0.25, 0.5 900…7200 120…600 945…7560 126…630 800…8400 160…800 Interrupting Code M0 Cat. No. t4=sec. 0.1, 0.2, 0.4, 0.8 0.1, 0.2, 0.4, 0.8 0.1, 0.2, 0.4, 0.8 3 Poles 4 Poles 140G-M0I3-D60 140G-M0I4-D60 140G-M0I3-D63 140G-M0I4-D63 140G-M0I3-D80 140G-M0I4-D80 § IEC only. Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 29 Bulletin 140G Molded Case Circuit Breakers Product Selection — 800 A, M-Frame Electronic LSIG-MM (Long, Short, Instantaneous, Ground Fault - Maintenance Mode) Protection Type L S I Rated I2=1…10 x I3=1…10 x Current I1=0.4…1 t1=sec. t2=sec. x In In In In [A] 600 240…600 3, 6, 9, 360…6000 18 630 § 252…630 3, 6, 9, 378…6300 18 800 320…800 3, 6, 9, 480…8000 18 0.05, 0.1, 0.25, 0.5 0.05, 0.1, 0.25, 0.5 0.05, 0.1, 0.25, 0.5 Interrupting Code M5 Cat. No. G I4=0.2…1 t4=sec. x In 3 Poles Interrupting Code M6 Cat. No. 4 Poles 3 Poles 4 Poles 900…7200 120…600 0.1, 140G-M5K3-D60 140G-M5K4-D60 140G-M6K3-D60 140G-M6K4-D60 0.2, 0.4, 0.8 945…7560 126…630 0.1, 0.2, 140G-M5K3-D63 140G-M5K4-D63 140G-M6K3-D63 140G-M6K4-D63 0.4, 0.8 800…8400 160…800 0.1, 140G-M5K3-D80 140G-M5K4-D80 140G-M6K3-D80 140G-M6K4-D80 0.2, 0.4, 0.8 § IEC only. Rated Current In [A] Protection Type S I G I2=1…10 x In t2=sec. I3=1…10 x In I4=0.2…1 x In L I1=0.4…1 x In t1=sec. 600 240…600 3, 6, 9, 18 360…6000 630 § 252…630 3, 6, 9, 18 378…6300 800 320…800 3, 6, 9, 18 480…8000 0.05, 0.1, 0.25, 0.5 0.05, 0.1, 0.25, 0.5 0.05, 0.1, 0.25, 0.5 900…7200 120…600 945…7560 126…630 800…8400 160…800 Interrupting Code M0 Cat. No. t4=sec. 0.1, 0.2, 0.4, 0.8 0.1, 0.2, 0.4, 0.8 0.1, 0.2, 0.4, 0.8 3 Poles 4 Poles 140G-M0K3-D60 140G-M0K4-D60 140G-M0K3-D63 140G-M0K4-D63 140G-M0K3-D80 140G-M0K4-D80 § IEC only. Maintenance Mode (MM) Maintenance Mode (MM) offers a preset set of protection parameters. MM allows systems testing when the molded case circuit breaker is energized or ON. This feature is a manual adjustment on the molded case circuit breaker, via a DIP switch. The following table illustrates the preset values for Maintenance Mode. L S I G MM Rated Current In [A] I1=1 x In t1=MAX sec. I2=OFF t2=OFF sec. I3=4 x In I4=OFF t4=OFF sec. I5=2.5 x In 600 630 § 800 600 630 800 18 18 18 — — — — — — 2400 2520 3200 — — — — — — 1500 1575 2000 § IEC only. Molded Case Switch — UL489 Rated Current In [A] Magnetic Trip [A] Im 800 10 000 Cat. No. 3 Poles 4 Poles 140G-M6S3-D80 140G-M6S4-D80 Visit our website: www.ab.com/catalogs 30 Publication 140G-SG001C-EN-P Bulletin 140G Molded Case Circuit Breakers Product Selection — 800 A, M-Frame Page Intentionally Left Blank Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 31 Bulletin 140G Molded Case Circuit Breakers Catalog Number Explanation — 1200 A, N-Frame Complete Circuit Breaker Assemblies — 1200 A, N-Frame Examples given in this section are not intended to be used for product selection. Use ProposalWorks to configure the molded case circuit breaker. Use these configurations only to select all factory-installed options for shunt trips, undervoltage release units, auxiliary contacts, and alarm contacts. Use the codes from Table h to add on to the molded case circuit breaker cat. no. selected on the previous pages to form a complete cat. no. for a complete assembly with factory-installed options. 140G – N a b 5 H 3 – E12 – c d e f – SD – AB g h a d h Bulletin No. Protection Type Factory-Installed Internal Options♦ Code Description Code Description 140G Global Molded Case Circuit Breaker H Electronic LSI-long, short & instant Code Description I Electronic LSIG -long, short, instant & ground fault SJ Shunt Trip, 24V AC/DC K Electronic LSIG-MM -long, short, instant, ground fault & MM S Molded case switch (isolator) b Frame/Rating Code Description N 1200 A e c Interrupting Rating/Breaking Capacity (based on Ic at 480V) Code Description 5 50 kA 6 65 kA 0 100 kA T Trip unit Poles Code Description 3 3 poles 4 4 poles f SK Shunt Trip, 48V AC/DC SD Shunt Trip, 110…120V AC/DC SA Shunt Trip, 220…240V AC/DC SB Shunt Trip, 380V AC SC Shunt Trip, 415…440V AC UJ Undervoltage Release, 24V AC/DC UD Undervoltage Release, 110…120V AC/DC UA Undervoltage Release, 220…240V AC/DC UB Undervoltage Release, 380…400V AC UC Undervoltage Release, 415…440V AC No Digit No Selection Auxiliary and Alarm Contacts Current Range Code Description Code Description E12 1200 A rating plug, standard AJ 1 Aux., 1 Alarm Contact, 24V AB 1 Aux., 1 Alarm Contact, 400V FB 2 Aux., 400V g Rating Code Description No Digit 80% Rated Z1 100% Rated Visit our website: www.ab.com/catalogs 32 Shunt Trip and Undervoltage Release Units Publication 140G-SG001C-EN-P ♦ Select up to two internal options: 1 for lower right side mounting (shunt trip or undervoltage release), 1 for upper right (auxiliary or alarm contact). Consult your local Rockwell automation sales office or Allen-Bradley distributor for further assistance. Bulletin 140G Molded Case Circuit Breakers Product Selection — 1200 A, N-Frame Interrupting Rating/Breaking Capacity — Electronic Circuit Breakers Interrupting Rating (50/60 Hz), UL 489/CSA C22.2-5, No. 5-02 [kA] 240V 65 100 150 480V 50 65 100 Icu 600V 25 50 65 Breaking Capacity (50/60 Hz), IEC 60947-2 220V 415V 440V 500V 690V [kA] Ics [kA] Icu [kA] Ics [kA] Icu [kA] Ics [kA] Icu [kA] Ics [kA] Icu [kA] Ics [kA] 85 100 200 85 100 200 50 70 120 50 70 120 50 65 100 50 65 100 40 50 85 40 50 64 30 42 50 Interrupting Code‡ N5 N6 N0 30 32 38 ‡ See table below for Cat. No. selection Electronic LSI (Long, Short, Instantaneous) - 80% Rated Protection Type§ S I2=1…10 x t1=sec. t2=sec. In L Rated Current In [A] I1=0.4…1 x In 1200 480…1200 Interrupting Code N5 Cat. No. I I3=1…10 x In 3 Poles 0.1, 0.2, OFF…12000 0.3, 0.4, 0.5, OFF…18000 140G-N5H3-E12 0.6, 0.7, 0.8 3, 12, 24, 36, 48, 72, 108,144 Interrupting Code N6 Cat. No. 4 Poles 3 Poles 4 Poles 140G-N5H4-E12 140G-N6H3-E12 140G-N6H4-E12 § Listed I1, I2, I3 & I4 values are based on a 1200 A Rating plug value. Protection Type§ Rated Current In [A] L 1200 S I1=0.4…1 x In t1=sec. 480…1200 3, 12, 24, 36, 48, 72, 108,144 I2=1…10 x In t2=sec. 180…12000 0.1, 0.2, 0.3, 0.4, 0.5, 5.8, 6.6., 7.4, 8.2, 9, 10 Interrupting Code N0 Cat. No. I I3=1…10 x In 3 Poles 4 Poles 1800…18000 140G-N0H3-E12 140G-N0H4-E12 § Listed I1, I2, I3 & I4 values are based on a 1200 A Rating plug value. Electronic LSIG (Long, Short, Instantaneous, Ground Fault) - 80% Rated L Rated Current In [A] 1200 I1=0.4…1 x In t1=sec. I2=1…10 x In Protection Type§ S I t2=sec. I3=1…10 x In 3, 12, 24, 0.1, 0.2, 0.3, 0.4, 480…1200 36, 48, 72, OFF…12000 OFF…18000 0.5, 0.6, 0.7, 0.8 108,144 G I4=0.2…1 x t4=sec. In 240…1200 Interrupting Code N5 Cat. No. Interrupting Code N6 Cat. No. 3 Poles 3 Poles 4 Poles 4 Poles 0.1, 0.2, 140G-N5I3- 140G-N5I4- 140G-N6I3- 140G-N6I4E12 E12 E12 E12 0.4, 0.8 § Listed I1, I2, I3 & I4 values are based on a 1200 A Rating plug value. Rated Current In [A] 1200 Protection Type§ S t2=sec. L I1=0.4…1 x In t1=sec. 480…1200 3, 12, 24, 36, 48, 72, 108,144 I2=1…10 x In 0.1, 0.2, 0.3, 0.4, 0.5, 5.8, 6.6., 7.4, 8.2, 9, 10 180…12000 Interrupting Code N0 Cat. No. I G I3=1…10 x In I4=0.2…1 x In 1800…18000 240…1200 t4=sec. 3 Poles 4 Poles 0.1, 0.2, 0.4, 0.8 140G-N0I3E12 140G-N0I4E12 § Listed I1, I2, I3 & I4 values are based on a 1200 A Rating plug value. Electronic LSIG-MM (Long, Short, Instantaneous, Ground Fault - Maintenance Mode) - 80% Rated L Rated Current In [A] 1200 I1=0.4…1 x In t1=sec. I2=1…10 x In Protection Type§ S I t2=sec. I3=1…10 x In Interrupting Code N5 Cat. No. Interrupting Code N6 Cat. No. 3 Poles 4 Poles 3 Poles 140G-N5K3E12 140G-N5K4E12 G I4=0.2…1 t4=sec. x In 0.1, 0.2, 0.3, 3, 12, 24, 0.4, 0.5, 5.8, 0.1, 0.2, 480…1200 36, 48, 72, 180…12000 1800…18000 240…1200 6.6., 7.4, 8.2, 0.4, 0.8 108,144 9, 10 4 Poles 140G-N6K3- 140G-N6K4E12 E12 § Listed I1, I2, I3 & I4 values are based on a 1200 A Rating plug value. Rated Current In [A] 1200 L I1=0.4…1 x In 480…1200 t1=sec. 3, 12, 24, 36, 48, 72, 108,144 Protection Type§ S I G I2=1…10 x In t2=sec. I3=1…10 x In I4=0.2…1 x In 180…12000 0.1, 0.2, 0.3, 0.4, 0.5, 5.8, 6.6., 7.4, 8.2, 9, 10 1800…18000 240…1200 Interrupting Code N0 Cat. No. t4=sec. 3 Poles 4 Poles 0.1, 0.2, 0.4, 0.8 140G-N0K3-E12 140G-N0K4-E12 Refer to page 30 for maintenance mode adjustment. § Listed I1, I2, I3 & I4 values are based on a 1200 A Rating plug value. Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 33 Bulletin 140G Molded Case Circuit Breakers Product Selection — 1200 A, N-Frame Electronic LSI (Long, Short, Instantaneous) - 100% Rated Protection Type§ S I2=1…10 x t1=sec. t2=sec. In L Rated Current In [A] I1=0.4…1 x In 3, 12, 24, 180…1200 480…1200 36, 48, 72, 0 108,144 1200 Interrupting Code N5 Cat. No. I I3=1…10 x In 0.1, 0.2, 0.3, 0.4, 0.5, 5.8, 6.6., 7.4, 8.2, 9, 10 3 Poles 4 Poles Interrupting Code N6 Cat. No. 3 Poles 4 Poles 1800…180 140G-N5H3-E12-Z1 140G-N5H4-E12-Z1 140G-N6H3-E12-Z1 140G-N6H4-E12-Z1 00 § Listed I1, I2, I3 & I4 values are based on a 1200 A Rating plug value. Protection Type§ Rated Current In [A] L S I1=0.4…1 x In t1=sec. 480…1200 3, 12, 24, 36, 48, 72, 108,144 1200 I2=1…10 x In t2=sec. 180…12000 0.1, 0.2, 0.3, 0.4, 0.5, 5.8, 6.6., 7.4, 8.2, 9, 10 I I3=1…10 x In 1800…18000 Interrupting Code N0 Cat. No. 3 Poles 4 Poles 140G-N0H3-E12-Z1 140G-N0H4-E12-Z1 § Listed I1, I2, I3 & I4 values are based on a 1200 A Rating plug value. Electronic LSIG (Long, Short, Instantaneous, Ground Fault) - 100% Rated Protection Type§ L S I G Rated I2=1…1 I3=1…1 I4=0.2 Current I1=0.4 In [A] …1 x In t1=sec. 0 x In t2=sec. 0 x In …1 x In t4=sec. 1200 0.1, 0.2, 0.3, 3, 12, 0.4, 0.5, 480…1 24, 36, 180…1 1800… 5.8, 200 48, 72, 2000 18000 6.6., 108,144 7.4, 8.2, 9, 10 Interrupting Code N5 Cat. No. 3 Poles 240…1 0.1, 0.2, 140G-N5I3-E12-Z1 200 0.4, 0.8 Interrupting Code N6 Cat. No. 4 Poles 3 Poles 4 Poles 140G-N5I4-E12-Z1 140G-N6I3-E12-Z1 140G-N6I4-E12-Z1 § Listed I1, I2, I3 & I4 values are based on a 1200 A Rating plug value. Rated Current In [A] 1200 Protection Type§ S L I1=0.4…1 x In t1=sec. I2=1…10 x In Interrupting Code N0 Cat. No. G I3=1…10 x In 0.1, 0.2, 0.3, 0.4, 0.5, 5.8, 1800…18000 6.6., 7.4, 8.2, 9, 10 3, 12, 24, 36, 48, 72, 180…12000 108,144 480…1200 t2=sec. I I4=0.2…1 x In 240…1200 t4=sec. 3 Poles 4 Poles 0.1, 0.2, 0.4, 0.8 140G-N0I3-E12-Z1 140G-N0I4-E12-Z1 § Listed I1, I2, I3 & I4 values are based on a 1200 A Rating plug value. Electronic LSIG-MM (Long, Short, Instantaneous, Ground Fault - Maintenance Mode) - 100% Rated L Rated Current I1=0.4…1 x In In [A] 1200 480…1200 Protection Type§ S I2=1…10 x t2=sec. In t1=sec. 3, 12, 24, 36, 48, 72, 108,144 I Interrupting Code N5 Cat. No. G I4=0.2…1 t4=sec. x In Interrupting Code N6 Cat. No. I3=1…10 x In 3 Poles 4 Poles 3 Poles 4 Poles 0.1, 0.2, 0.3, 0.4, 0.5, 5.8, 0.1, 0.2, 140G-N5K3- 140G-N5K4- 140G-N6K3- 140G-N6K4180…12000 1800…18000 240…1200 E12-Z1 E12-Z1 E12-Z1 E12-Z1 6.6., 7.4, 8.2, 9, 0.4, 0.8 10 § Listed I1, I2, I3 & I4 values are based on a 1200 A Rating plug value. Rated Current In [A] 1200 Protection Type§ S L I1=0.4…1 x In 480…1200 t1=sec. I2=1…10 x In 3, 12, 24, 36, 48, 72, 180…12000 108,144 t2=sec. I I3=1…10 x In 0.1, 0.2, 0.3, 0.4, 0.5, 5.8, 1800…18000 6.6., 7.4, 8.2, 9, 10 I4=0.2…1 x In 240…1200 § Listed I1, I2, I3 & I4 values are based on a 1200 A Rating plug value. Visit our website: www.ab.com/catalogs 34 Interrupting Code N0 Cat. No. G Publication 140G-SG001C-EN-P t4=sec. 3 Poles 4 Poles 0.1, 0.2, 0.4, 140G-N0K3-E12-Z1 140G-N0K4-E12-Z1 0.8 Bulletin 140G Molded Case Circuit Breakers Product Selection — 1200 A, N-Frame Maintenance Mode (MM) Maintenance Mode (MM) offers a preset set of protection parameters. MM allows systems testing when the molded case circuit breaker is energized or ON. This feature is a manual adjustment on the molded case circuit breaker, via a DIP switch. The following table illustrates the preset values for Maintenance Mode. L S I G MM Rated Current In [A] I1=1 x In t1=MAX sec. I2=OFF t2=OFF sec. I3=4 x In I4=OFF t4=OFF sec. I5=2.5 x In 1200 480…1200 3…144 — — — — — 1800…4800 Molded Case Switch — UL489‡ Rated Current In [A] Magnetic Trip [A] Im 1200 20 000 Cat. No. 3 Poles 140G-N6S3-E12 4 Poles 140G-N6S4-E12 ‡ Does not provide overcurrent protection; may open above 20,000 A. Trip Units, Electronic LSI (Long, Short, Instantaneous), LSIG (Long, Short, Instantaneous, Ground Fault), LSIG-MM (Long, Short, Instantaneous, Ground Fault - Maintenance Mode)§ Rated Current In [A] 1200 1200 1200 Cat. No. Protection Type H (LSI) I (LSIG) K (LSIG-MM) 3 Poles 140G-NTH-E12 140G-NTI-E12 140G-NTK-E12 § Supplied installed with each MCCB. Cat. Nos. listed are replacement parts. Rating Plugs Rated Current In [A] 400 600 800 1000 1200 1250 Cat. No. 140G-NRP-D40 140G-NRP-D60 140G-NRP-D80 140G-NRP-E10 140G-NRP-E12 140G-NRP-E125 IEC only. Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 35 Bulletin 140G Molded Case Circuit Breakers Catalog Number Explanation — 1200 A, NS-Frame Stored Energy Operating Mechanism Complete Circuit Breaker Assemblies — 1200 A, NS-Frame Examples given in this section are not intended to be used for product selection. Use ProposalWorks to configure the molded case circuit breaker. Use these configurations only to select all factory-installed options for shunt trips, undervoltage release units, auxiliary contacts, and alarm contacts. Use the codes from Table h and i to add on to the molded case circuit breaker cat. no. selected on the previous pages to form a complete cat. no. for a complete assembly with factory-installed options. 140G – NS a b 5 H 3 – E12 – MJ – RK – SD c d e f g h a d g Bulletin No. Protection Type Remote MCCB Operation♦ Code Description Code Description 140G Global Molded Case Circuit Breaker H Electronic LSI-long, short, instant Code Description I Electronic LSIG -long, short, instant & ground fault MJ Spring Charge Motor, 24…30V AC/DC K Electronic LSIG-MM -long, short, instant, ground fault & MM b Frame/Rating Spring Charge Motor MK Spring Charge Motor, 48…60V AC/DC MD Spring Charge Motor, 110…130V AC/DC Spring Charge Motor, 220…250V AC/DC Code Description MA NS 1200 A MC e Poles Spring Charge Motor, 380…415V AC Shunt Trip and Shunt Close Units c Code Description Code Description RJ Shunt Trip and Shunt Close, 24V AC/DC Interrupting Rating/Breaking Capacity (based on Ic at 480V) 3 3 poles RK Shunt Trip and Shunt Close, 48V AC/DC 4 4 poles RD Shunt Trip and Shunt Close, 110…120V AC/DC RA Shunt Trip and Shunt Close, 220…240V AC/DC Code Description 5 50 kA 6 65 kA 0 100 kA T Trip unit f Current Range Code Description RB Shunt Trip and Shunt Close, 380…400V AC E12 1200 A rating plug, standard No Digit No Selection h Factory-Installed Internal Options♦ Shunt Trip and Undervoltage Release Units Code Description SJ Shunt Trip, 24V AC/DC SK Shunt Trip, 48V AC/DC SD Shunt Trip, 110…120V AC/DC SA Shunt Trip, 220…240V AC/DC SB Shunt Trip, 380…400V AC UJ Undervoltage Release, 24V AC/DC UD Undervoltage Release, 110…120V AC/DC UA Undervoltage Release, 220…240V AC/DC UB Undervoltage Release, 380…400V AC UC Undervoltage Release, 415…440V AC No Digit No Selection ♦ Select one internal option for inner right mounting (shunt trip or undervoltage release). For remote control MCCB operation, select the spring charging motor and operating voltage for shunt trip and shunt close coils from table i. Consult your local Rockwell automation sales office or Allen-Bradley distributor for further assistance. Visit our website: www.ab.com/catalogs 36 Publication 140G-SG001C-EN-P Bulletin 140G Molded Case Circuit Breakers Product Selection — 1200 A, NS-Frame Stored Energy Operating Mechanism Assembled Molded Case Circuit Breakers — 1200 A NS-Frame Interrupting Rating/Breaking Capacity — Electronic Circuit Breakers Interrupting Rating (50/60 Hz), UL 489/CSA C22.2-5, No. 5-02 [kA] Breaking Capacity (50/60 Hz), IEC 60947-2 415V 440V 500V 220V 240V 65 100 150 480V 50 65 100 Icu [kA] 600V 25 50 65 690V Interrupting Code‡ NS5 NS6 NS0 Ics [kA] Icu [kA] Ics [kA] Icu [kA] Ics [kA] Icu [kA] Ics [kA] Icu [kA] Ics [kA] 85 100 200 85 100 200 50 70 120 50 70 120 50 65 100 50 65 100 40 50 85 40 50 64 30 42 50 30 32 38 ‡ See table below for Cat. No. selection Electronic LSI (Long, Short, Instantaneous) Protection Type§ S I2=1…10 x In L Rated Current In [A] I1=0.4…1 x In t1=sec. t2=sec. Interrupting Code NS6 Cat. No. I3=1…10 x In 3 Poles 4 Poles 3 Poles 4 Poles OFF…18000 140G-NS5H3E12 140G-NS5H4E12 140G-NS6H3E12 140G-NS6H4E12 0.1, 0.2, 0.3, 0.4, 3, 12, 24, 36, 480…1200 OFF…12000 0.5, 5.8, 6.6., 7.4, 48, 72, 108, 144 8.2, 9, 10 1200‡ Interrupting Code NS5 Cat. No. I ‡ Rated current = 1200 A for UL Ratings. § Listed I1, I2, I3 & I4 values are based on a 1200 A Rating plug value. Protection Type§ Rated Current In [A] L I1=0.4…1 x In 1200‡ S t1=sec. 3, 12, 24, 36, 48, 72, 108, 144 480…1200 I2=1…10 x In t2=sec. OFF…12000 0.1, 0.2, 0.3, 0.4, 0.5, 5.8, 6.6., 7.4, 8.2, 9, 10 Interrupting Code NS0 Cat. No. I I3=1…10 x In 3 Poles 4 Poles OFF…18000 140G-NS0H3-E12 140G-NS0H4-E12 ‡ Rated current = 1200 A for UL Ratings; 1250 A for IEC. § Listed I1, I2, I3 & I4 values are based on a 1200 A Rating plug value. Electronic LSIG (Long, Short, Instantaneous, Ground Fault) L Rated Current I1=0.4…1 x t1=sec. In In [A] 1200‡ 480…1200 Protection Type§ S I2=1…10 x In t2=sec. I I3=1…10 x In G I4=0.2…1 x t4=sec. In 0.1, 0.2, 0.3, 3, 12, 24, 0.4, 0.5, 5.8, 0.1, 0.2, 36, 48, 72, OFF…12000 OFF…18000 240…1200 6.6., 7.4, 8.2, 9, 0.4, 0.8 108, 144 10 Interrupting Code NS5 Cat. No. Interrupting Code NS6 Cat. No. 3 Poles 4 Poles 3 Poles 4 Poles 140GNS5I3-E12 140GNS5I4-E12 140GNS5I4-E12 140GNS6I4-E12 ‡ Rated current = 1200 A for UL Ratings. § Listed I1, I2, I3 & I4 values are based on a 1200 A Rating plug value. Rated Current In [A] 1200‡ Protection Type§ S L I1=0.4…1 x In 480…1200 t1=sec. I2=1…10 x In t2=sec. I I3=1…10 x In 0.1, 0.2, 0.3, 3, 12, 24, 36, 0.4, 0.5, 5.8, 48, 72, 108, OFF…12000 OFF…18000 6.6., 7.4, 8.2, 144 9, 10 Interrupting Code NS0 Cat. No. G I4=0.2…1 x In 240…1200 t4=sec. 3 Poles 4 Poles 0.1, 0.2, 0.4, 0.8 140G-NS0I3-E12 140G-NS0I4-E12 ‡ Rated current = 1200 A for UL Ratings; 1250 A for IEC. § Listed I1, I2, I3 & I4 values are based on a 1200 A Rating plug value. Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 37 Bulletin 140G Molded Case Circuit Breakers Product Selection —1200 A, NS-Frame Stored Energy Operating Mechanism Electronic LSIG-MM (Long, Short, Instantaneous, Ground Fault - Maintenance Mode) Rated Current In [A] 1200‡ L I1=0.4…1 x In t1=sec. Protection Type§ S I2=1…10 x t2=sec. In I I3=1…1 0 x In Interrupting Code NS5 Cat. No. G I4=0.2…1 t4=sec. x In Interrupting Code NS6 Cat. No. 3 Poles 4 Poles 3 Poles 0.1, 0.2, 0.3, 3, 12, 24, 0.4, 0.5, 5.8, 1800… 0.1, 0.2, 140G-NS5K3- 140G-NS5K4- 140G-NS6K3480…1200 36, 48, 72, 180…12000 240…1200 E12 E12 E12 6.6., 7.4, 8.2, 9, 18000 0.4, 0.8 108, 144 10 4 Poles 140G-NS6K4E12 ‡ Rated current = 1200 A for UL Ratings. § Listed I1, I2, I3 & I4 values are based on a 1200 A Rating plug value. Rated Current In [A] 1200‡ Protection Type§ S L I1=0.4…1 x In 480…1200 t1=sec. I2=1…10 x In 3, 12, 24, 36, 48, 72, 108, 180…12000 144 t2=sec. I I3=1…10 x In 0.1, 0.2, 0.3, 0.4, 0.5, 5.8, 1800…18000 6.6., 7.4, 8.2, 9, 10 Interrupting Code NS0 Cat. No. G I4=0.2…1 x In 240…1200 t4=sec. 3 Poles 4 Poles 0.1, 0.2, 0.4, 0.8 140G-NS0K3-E12 140G-NS0K4-E12 ‡ Rated current = 1200 A for UL Ratings; 1250 A for IEC. § Listed I1, I2, I3 & I4 values are based on a 1200 A Rating plug value. Maintenance Mode (MM) Maintenance Mode (MM) offers a preset set of protection parameters. MM allows systems testing when the molded case circuit breaker is energized or ON. This feature is a manual adjustment on the molded case circuit breaker, via a DIP switch. The following table illustrates the preset values for Maintenance Mode. L S I G MM Rated Current In [A] I1=1 x In t1=MAX sec. I2=OFF t2=OFF sec. I3=4 x In I4=OFF t4=OFF sec. I5=2.5 x In 1200 480…1200 3…144 — — — — — 1800…4800 Trip Units, Electronic LSI (Long, Short, Instantaneous), LSIG (Long, Short, Instantaneous, Ground Fault), LSIG-MM (Long, Short, Instantaneous, Ground Fault -Maintenance Mode)§ Rated Current In [A] 1200 1200 1200 Cat. No. Protection Type H (LSI) I (LSIG) K (LSIG-MM) 3 Poles 140G-NTH-E12 140G-NTI-E12 140G-NTK-E12 § Supplied installed with each MCCB. Cat. Nos. listed are replacement parts. Rating Plugs Rated Current In [A] 400 600 800 1000 1200 1250 Cat. No. 140G-NRP-D40 140G-NRP-D60 140G-NRP-D80 140G-NRP-E10 140G-NRP-E12 140G-NRP-E125 IEC only. Visit our website: www.ab.com/catalogs 38 Publication 140G-SG001C-EN-P Bulletin 140G Molded Case Circuit Breakers Product Selection — 1200 A, NS-Frame Stored Energy Operating Mechanism Page Intentionally Left Blank Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 39 Bulletin 140G Molded Case Circuit Breakers Catalog Number Explanation — 2000…3000 A, R-Frame Stored Energy Operating Mechanism Complete Circuit Breaker Assemblies — 2000…3000 A, R-Frame Examples given in this section are not intended to be used for product selection. Use ProposalWorks to configure the molded case circuit breaker. Use these configurations only to select all factory-installed options for shunt trips, undervoltage release units, auxiliary contacts, and alarm contacts. Use the codes from Table h and i to add on to the molded case circuit breaker cat. no. selected on the previous pages to form a complete cat. no. for a complete assembly with factory-installed options. 140G – R a b 12 I 3 – E25 – Z1 – MD – RD – SB c d e h i a d h Protection Type Remote MCCB Operation♦ Code Description Global Molded Case Circuit Breaker b Code Description I Electronic LSIG -Long, short, instant & ground fault S Frame/Rating R g Bulletin No. 140G Code f Molded case switch (isolator) Description e 2500…3000 A Poles c Interrupting Rating/Breaking Capacity (based on Ic at 480V) Code Description 12 125 kA Spring Charge Motor Code Description MJ Spring Charge Motor, 24…30V AC/DC MK Spring Charge Motor, 48…60V AC/DC MD Spring Charge Motor, 110…130V AC/DC MA Spring Charge Motor, 220…250V AC/DC Shunt Trip and Shunt Close Units Code Description Code Description 3 3 poles RJ Shunt Trip and Shunt Close, 24V AC/DC 4 4 poles RK Shunt Trip and Shunt Close, 48V AC/DC RD Shunt Trip and Shunt Close, 110…120V AC/DC RA Shunt Trip and Shunt Close, 220…240V AC/DC RB Shunt Trip and Shunt Close, 380…440V AC No Digit No Selection f Current Range Code Description E20 2000 A rating plug, installed E25 2500 A rating plug, installed E30 3000 A rating plug, installed g i Rating Factory-Installed Internal Options♦ Code Description No Digit 80% Rated Z1 100% Rated Shunt Trip and Undervoltage Release Units Code Description SJ Shunt Trip, 24V DC SK Shunt Trip, 48V AC/DC SD Shunt Trip, 110…120V AC/DC SA Shunt Trip, 220…240V AC/DC SB Shunt Trip, 380…440V AC SC Shunt Trip, 480…525V AC UJ Undervoltage Release, 24V DC UD Undervoltage Release, 110…120V AC/DC UA Undervoltage Release, 220…240V AC/DC UB Undervoltage Release, 380…400V AC UC Undervoltage Release, 440V AC No Digit No Selection ♦ Select up to four internal options: 3 for left side mounting, 1 for right. Consult your local Rockwell automation sales office or Allen-Bradley distributor for further assistance. Visit our website: www.ab.com/catalogs 40 Publication 140G-SG001C-EN-P Bulletin 140G Molded Case Circuit Breakers Product Selection — 2000…3000 A, R-Frame Stored Energy Operating Mechanism Assembled Molded Case Circuit Breakers — 2000…3000 A R-Frame Interrupting Rating/Breaking Capacity — Electronic Circuit Breakers Interrupting Rating (50/60 Hz), UL 489/CSA C22.2-5, No. 5-02 [kA] 240V 125 480V 125 Icu 600V 100 Breaking Capacity (50/60 Hz), IEC 60947-2 220V 415V 440V 500V 690V [kA] Ics [kA] Icu [kA] Ics [kA] Icu [kA] Ics [kA] Icu [kA] Ics [kA] Icu [kA] Ics [kA] 130 97.5 80 60 80 60 40 40 40 Interrupting Code‡ R12 40 ‡ See table below for Cat. No. selection Electronic LSIG (Long, Short, Instantaneous, Ground Fault) - 80% Rated Rated Current In [A] Protection Type S t2=sec. L I1=0.4…1 x In t1=sec. I2=1…10 x In 2000‡ 800…2000 3, 12, 24, 36, 48, 1200…20000 72, 108, 144 2500‡ 1000…2500 3, 12, 24, 36, 48, 1500…25000 72, 108, 144 3000‡ 1200…3000 3, 12, 24, 36, 48, 1800…30000 72, 108, 144 I G I3=1…10 x In I4=0.2…1 x In 0.1, 0.2, 0.3, 0.4, 0.5, 5.8, 6.6, 7.4, 8.2, 9, 10 0.1, 0.2, 0.3, 0.4, 0.5, 5.8, 6.6, 7.4, 8.2, 9, 10 0.1, 0.2, 0.3, 0.4, 0.5, 5.8, 6.6, 7.4, 8.2, 9, 10 Interrupting Code R12 Cat. No. t4=sec. 3 Poles 4 Poles 140GR12I4-E20 3000…30000 400…2000 0.1, 0.2, 0.4, 0.8 140GR12I3-E20 3750…37500 500…2500 0.1, 0.2, 0.4, 0.8 140GR12I3-E25 140GR12I4-E25 4500…45000 600…3000 0.1, 0.2, 0.4, 0.8 140GR12I3-E30 140GR12I4-E30 ‡ Listed I1, I2, I3 & I4 values are based on a 2000, 2500 & 3000 A rating plug value, respectively. Electronic LSIG (Long, Short, Instantaneous, Ground Fault) - 100% Rated Protection Type S L Rated Current In [A] I1=0.4…1 x In t1=sec. I I3=1…10 x In Interrupting Code R12 Cat. No. G I4=0.2…1 x In I2=1…10 x In t2=sec. 1500…25000 0.1, 0.2, 0.3, 0.4, 0.5, 5.8, 6.6, 7.4, 8.2, 9, 10 t4=sec. 3750…37500 500…2500 0.1, 0.2, 0.4, 140G-R12I3-E20- 140G-R12I4-E20Z1 Z1 0.8 3 Poles 4 Poles 2000§ 1000…2500 3, 12, 24, 36, 48, 72, 108, 144 2500§ 1000…2500 3, 12, 24, 36, 48, 72, 108, 144 1500…25000 0.1, 0.2, 0.3, 0.4, 0.5, 5.8, 6.6, 7.4, 8.2, 9, 10 3750…37500 500…2500 0.1, 0.2, 0.4, 140G-R12I3-E25- 140G-R12I4-E25Z1 Z1 0.8 3000§ 1200…3000 3, 12, 24, 36, 48, 72, 108, 144 1800…30000 0.1, 0.2, 0.3, 0.4, 0.5, 5.8, 6.6, 7.4, 8.2, 9, 10 4500…45000 600…3000 0.1, 0.2, 0.4, 140G-R12I3-E30- 140G-R12I4-E30Z1 Z1 0.8 § Listed I1, I2, I3 & I4 values are based on a 2000, 2500 & 3000 A rating plug value, respectively. Molded Case Switch — UL489§ Rated Current In [A] Magnetic Trip [A] Im 2500 25 000 Cat. No. 3 Poles 4 Poles 140G-R12S3-E25 140G-R12S4-E25 § Does not provide overcurrent protection; may open at 40,000 A. Rating Plugs Rated Current In [A] 1000 1200 1600 2000 2500 3000 Cat. No. 140G-NRP-E10 140G-NRP-E12 140G-RRP-E16 140G-RRP-E20 140G-RRP-E25 140G-RRP-E30 Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 41 Bulletin 140MG Motor Circuit Protectors Overview Cat. No. 140MG-H8P-D12 Bulletin 140MG Motor Circuit Protectors Table of Contents Current range 0.16…1200 A UL Listed/Recognized for motor loads − Short-circuit protection − Overload protection must be provided separately Visible trip indication High current limiting High switching capacity Product Selection ...... Accessories.................. Specifications.............. Approximate Dimensions................... The Bulletin 140MG Motor Circuit Protectors provide short circuit protection for individual motor loads. Factory-installed internal accessories make installation and wiring easy. Your order must include: cat. no. of the Motor Circuit Protector or Motor Protection Circuit Breaker selected and, if required, cat. no. of any accessories. 43 50 64 68 Standards Compliance IEC 60947-2 UL489 CSA22.2, No. 5 Certifications CE Marked CSA Certified (File No. LR1234) UR Recognized (File No. E224135) CCC General Information Motor Circuit Protectors may provide the following protective and control functions. Disconnect for Motor Branch Circuit Branch-Circuit, Short-Circuit Protection (Magnetic Protection) Switching (Manual) In North America, electrical codes require that an individual Motor Branch Circuit be protected by a UL/CSA Listed Fuse, Circuit Breaker or Self-Protected Combination Motor Controller. 140MG-G, H, I, J, K, M and N Frames: The 140MG-G, H, I, J, K, M and N frame Motor Circuit Protectors are UL/CSA Recognized as Circuit Breakers. They are UL/CSA Recognized, rather than UL/CSA Listed, since they only provide short circuit protection and not thermal overload protection for the motor. Visit our website: www.ab.com/catalogs 42 Publication 140G-SG001C-EN-P Bulletin 140MG Motor Circuit Protectors Product Selection Motor Circuit Protectors Short-Circuit Protection — Magnetic Trip Overload Protection — None (Magnetic Trip Only) Rated Operational Current (Ie) [A] Magnetic Trip Current [A] B C D E Max. kW, 3-Phase — AC-3 3-phase Hp Ratings Cam Setting A F G H I 200V 230V 460V 575V 230V 400/415V 500V 690V Cat. No.‡ 140MG-G8P-B30 G-Frame 3 9 12 15 18 21 24 27 30 33 0.5 0.5 1.5 2 0.6 0.75 1.1 1.5 7 21 28 35 42 49 26 63 70 77 1.5 2 3 5 1.1 2.2 3 4 140MG-G8P-B70 15 45 60 75 90 105 120 135 150 165 3 3 10 10 3 5.5 7.5 11 140MG-G8P-C15 30 90 120 150 180 210 240 270 300 330 7.5 10 20 25 5.5 11 15 22 140MG-G8P-C30 50 150 200 250 300 350 400 450 500 550 15 15 30 40 11 22 22 37 140MG-G8P-C50 70 210 280 350 420 490 560 630 700 770 20 25 50 60 15 30 37 55 140MG-G8P-C70 80 240 320 400 480 560 640 720 800 880 25 30 60 75 22 45 55 75 140MG-G8P-C80 100 300 400 500 600 700 800 900 1000 1100 30 30 75 100 30 55 75 110 140MG-G8P-D10 125 375 500 625 750 875 1000 1125 1250 1375 40 40 100 125 22 45 55 90 140MG-G8P-D12 140MG-H8P-B30 H-Frame 3 9 12 15 18 21 24 27 30 33 0.5 0.5 1.5 2 0.6 0.75 1.1 1.5 7 21 28 35 42 49 26 63 70 77 1.5 2 3 5 1.1 2.2 3 4 140MG-H8P-B70 15 45 60 75 90 105 120 135 150 165 3 3 10 10 3 5.5 7.5 11 140MG-H8P-C15 30 90 120 150 180 210 240 270 300 330 7.5 10 20 25 5.5 11 15 22 140MG-H8P-C30 50 150 200 250 300 350 400 450 500 550 15 15 30 40 11 22 22 37 140MG-H8P-C50 70 210 280 350 420 490 560 630 700 770 20 25 50 60 15 30 37 55 140MG-H8P-C70 80 240 320 400 480 560 640 720 800 880 25 30 60 75 22 45 55 75 140MG-H8P-C80 100 300 400 500 600 700 800 900 1000 1100 30 30 75 100 30 55 75 110 140MG-H8P-D10 125 625 703 781 859 938 1016 1094 1172 1250 40 40 100 125 22 45 55 90 140MG-H8P-D12 I-Frame 100 600 675 750 825 900 975 1050 1125 1200 30 30 75 100 22 37 45 55 140MG-I8P-D10 110 660 743 825 908 990 1073 1150 1238 1320 30 40 75 100 22 45 55 90 140MG-I8P-D11 125 750 844 938 1031 1125 1219 1313 1406 1500 40 40 100 125 22 45 55 90 140MG-I8P-D12 150 900 1013 1125 1238 1350 1463 1575 1688 1800 50 50 100 150 30 55 75 110 140MG-I8P-D15 J-Frame 150 750 844 938 1031 1125 1219 1313 1406 1500 50 50 100 150 30 55 75 110 140MG-J8P-D15 175 875 984 1094 1203 1313 1422 1531 1641 1750 50 60 125 150 37 55 90 132 140MG-J8P-D17 200 1000 1125 1250 1375 1500 1625 1750 1875 2000 60 75 150 200 45 75 90 132 140MG-J8P-D20 225 1125 1266 1406 1547 1688 1828 1969 2109 2250 75 75 150 200 55 90 110 160 140MG-J8P-D22 250 1250 1406 1563 1719 1875 2031 2188 2344 2500 75 100 200 250 55 90 132 160 140MG-J8P-D25 The Hp and kW ratings shown are for reference only. They allow for a magnetic trip setting of at least up to 13X the motor FLA. However, the final selection of the MCP should be made based on motor full load current and the requirements of local electrical codes. ‡ The interrupting rating for MCPs is dependent upon the controller used. Please contact your local Rockwell Automation sales office or Allen-Bradley distributor for further information. Rated Operational Current (Ie) [A] Magnetic Trip Current [A] I3 (adjustable) [A] 3-phase Hp Ratings 200V 230V 460V Max. kW, 3-Phase — AC-3 575V 230V 400/415V 500V 690V Cat. No.‡ K-Frame 300 300…3000 75 75 150 200 55 110 160 200 140MG-K8P-D30 400 400…4000 100 100 250 300 90 160 200 250 140MG-K8P-D40 M-Frame 600 600…6000 125 150 300 400 110 200 250 355 140MG-M8P-D60 800 800…8000 150 200 400 500 160 250 355 500 140MG-M8P-D80 200 250 500 710 140MG-N8P-E12 N-Frame 1200§ 1200…12000 250 300 600 700 The Hp and kW ratings shown are for reference only. They allow for a magnetic trip setting of at least up to 13X the motor FLA. However, the final selection of the MCP should be made based on motor full load current and the requirements of local electrical codes. ‡ The interrupting rating for MCPs is dependent upon the controller used. Please contact your local Rockwell Automation sales office or Allen-Bradley distributor for further information. § I3 is adjustable between 1…10x motor FLA. Values based on 1200 A rating plug. Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 43 Bulletin 140MG Motor Circuit Protectors Catalog Number Explanation — 125A, G-Frame & 150 A, I-Frame Complete Motor Circuit Protector Assemblies with Factory-Installed Options Examples given in this section are not intended to be used for product selection. Use these configurations only to select all factory-installed options for shunt trips, undervoltage release units, auxiliary contacts, and alarm contacts. Use the codes from Table f to add on to the motor circuit protector cat. no. selected on the previous pages to form a complete cat. no. for a complete assembly with factory-installed options. 140MG – a I 8 P – C70 – SD – KA b c d a d Bulletin No. Protection Type Code Description 140MG Global Motor Circuit Protector e Code Description P Adjustable magnetic only (less than 13 x In) b e Frame/Rating Code Description G 125 A I 150 A c Description 8 High break f Factory-Installed Internal Options♦ Shunt Trip and Undervoltage Release Units Code Description SJ Shunt Trip, 24…30V AC/DC SK Shunt Trip, 48…60V AC/DC SD Shunt Trip, 110…127V AC; 110…125V DC SA Shunt Trip, 220…240V AC; 220…250V DC Shunt Trip, 380…440V AC Current Range Code Description B e.g., D30 = 3 A SB C e.g., C30 = 30 A SC Shunt Trip, 480…525V AC D e.g., D12 = 120 A UJ Undervoltage Release, 24…30V AC/DC Interrupting Rating/Breaking Capacity (based on Ic at 480V) Code f UR Undervoltage Release, 48V AC/DC UD Undervoltage Release, 110…127V AC; 110…125V DC UA Undervoltage Release, 220…240V AC; 220…250V DC UB Undervoltage Release, 380…440V AC UC Undervoltage Release, 480…525V AC No Digit No Selection Auxiliary and Alarm Contacts Code Description KA 1 Aux. Contact, 250V TA 1 Alarm Contact, 250V AA 1 Aux., 1 Alarm Contact, 250V BA 2 Aux., 1 Alarm Contact, 250V AJ 1 Aux., 1 Alarm Contact, 24V ♦ Select up to two internal options: 1 for left side mounting (shunt trip or undervoltage release), 1 for right (auxiliary or alarm contact). Consult your local Rockwell automation sales office or Allen-Bradley distributor for further assistance. Visit our website: www.ab.com/catalogs 44 Publication 140G-SG001C-EN-P Bulletin 140MG Motor Circuit Protectors Catalog Number Explanation — 125A, H-Frame & 250 A, J-Frame Complete Motor Circuit Protector Assemblies with Factory-Installed Options Examples given in this section are not intended to be used for product selection. Use these configurations only to select all factory-installed options for shunt trips, undervoltage release units, auxiliary contacts, and alarm contacts. Use the codes from Table f to add on to the motor circuit protector cat. no. selected on the previous pages to form a complete cat. no. for a complete assembly with factory-installed options. 140MG – J a b 8 P – D15 – SD – AA c d a d Bulletin No. Protection Type Code Description 140MG Global Motor Circuit Protector e Code Description P Adjustable magnetic only (less than 13 x In) b e Frame/Rating Code Current Range Description H 125 A Code J 250 A B c Description e.g., B30 = 3 A C e.g., C30 = 30 A D e.g., D20 = 200 A Interrupting Rating/Breaking Capacity (based on Ic at 480V) Code Description 8 High break f f Factory-Installed Internal Options♦ Shunt Trip and Undervoltage Release Units Code Description SJ Shunt Trip, 24…30V AC/DC SK Shunt Trip, 48…60V AC/DC SD Shunt Trip, 110…127V AC; 110…125V DC SA Shunt Trip, 220…240V AC; 220…250V DC SB Shunt Trip, 380…440V AC SC Shunt Trip, 480…525V AC UJ Undervoltage Release, 24…30V AC/DC UR Undervoltage Release, 48V AC/DC UD Undervoltage Release, 110…127V AC; 110…125V DC UA Undervoltage Release, 220…240V AC; 220…250V DC UB Undervoltage Release, 380…440V AC UC Undervoltage Release, 480…525V AC No Digit No Selection Auxiliary and Alarm Contacts, Trip Units Code Description KA 1 Aux. Contact, 250V TA 1 Alarm Contact, 250V AA 1 Aux., 1 Alarm Contact, 250V BA 2 Aux., 1 Alarm Contact, 250V DA 1 Trip Unit Alarm Contact, 250V FB 2 Aux. Contacts, 400V AB 1 Aux., 1 Alarm Contact, 400V AJ 1 Aux., 1 Alarm Contact, 24V DJ 1 Trip Unit Alarm Contact, 24V ♦ Select up to two internal options: 1 for left side mounting (shunt trip or undervoltage release), 1 for right (auxiliary or alarm contact). Consult your local Rockwell automation sales office or Allen-Bradley distributor for further assistance. Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 45 Bulletin 140MG Motor Circuit Protectors Catalog Number Explanation — 400 A, K-Frame & 800 A, M-Frame Complete Motor Circuit Protector Assemblies with Factory-Installed Options Examples given in this section are not intended to be used for product selection. Use these configurations only to select all factory-installed options for shunt trips, undervoltage release units, auxiliary contacts, and alarm contacts. Use the codes from Table f to add on to the motor circuit protector cat. no. selected on the previous pages to form a complete cat. no. for a complete assembly with factory-installed options. 140MG – M a b P – D40 – SD – AA c d e f a d f Bulletin No. Protection Type Factory-Installed Internal Options♦ Code Description 140MG Global Motor Circuit Protector Code Description P Adjustable magnetic only (less than 13 x In) b e Frame/Rating Code 8 Current Range Description K 400 A Code M 800 A D30 e.g., 300 A D80 e.g., 800 A Blank Frame only c Description Interrupting Rating/Breaking Capacity (based on Ic at 480V) Code Description 8 High break Shunt Trip and Undervoltage Release Units Code Description SJ Shunt Trip, 24…30V AC/DC SK Shunt Trip, 48…60V AC/DC SD Shunt Trip, 110…127V AC; 110…125V DC SA Shunt Trip, 220…240V AC; 220…250V DC SB Shunt Trip, 380…440V AC SC Shunt Trip, 480…525V AC UJ Undervoltage Release, 24…30V AC/DC UR Undervoltage Release, 48V AC/DC UD Undervoltage Release, 110…127V AC; 110…125V DC UA Undervoltage Release, 220…240V AC; 220…250V DC UB Undervoltage Release, 380…440V AC UC Undervoltage Release, 480…525V AC No Digit No Selection Auxiliary and Alarm Contacts Code Description AA 1 Aux., 1 Alarm Contact, 250V CA 3 Aux., 1 Alarm Contact, 250V AB 1 Aux., 1 Alarm Contact, 400V FB 2 Aux. Contacts, 400V CJ 3 Aux., 1 Alarm Contact, 24V ♦ Select up to two internal options: 1 for left side mounting (shunt trip or undervoltage release), 1 for right (auxiliary or alarm contact). Consult your local Rockwell automation sales office or Allen-Bradley distributor for further assistance. Visit our website: www.ab.com/catalogs 46 Publication 140G-SG001C-EN-P Bulletin 140MG Motor Circuit Protectors Catalog Number Explanation — 1200 A, N-Frame Complete Motor Circuit Protector Assemblies with Factory-Installed Options Examples given in this section are not intended to be used for product selection. Use these configurations only to select all factory-installed options for shunt trips, undervoltage release units, auxiliary contacts, and alarm contacts. Use the codes from Table f to add on to the motor circuit protector cat. no. selected on the previous pages to form a complete cat. no. for a complete assembly with factory-installed options. 140MG – N a 8 b P – E12 – SD – AB c d e d f Bulletin No. Protection Type Factory-Installed Internal Options♦ Code Description 140MG Global Motor Circuit Protector Code Description P Adjustable magnetic only (less than 13 x In) b e Frame/Rating Code N f a Current Range Description 1200 A Shunt Trip and Undervoltage Release Units Code Description SJ Shunt Trip, 24V AC/DC SK Shunt Trip, 48V AC/DC SD Shunt Trip, 110…120V AC/DC SA Shunt Trip, 220…240V AC/DC Code Description SB Shunt Trip, 380V AC E12 1200 A SC Shunt Trip, 415…440V AC c UJ Undervoltage Release, 24V AC/DC Interrupting Rating/Breaking Capacity (based on Ic at 480V) UD Undervoltage Release, 110…120V AC/DC UA Undervoltage Release, 220…240V AC/DC Code Description UB Undervoltage Release, 380…400V AC 8 High break UC Undervoltage Release, 415…440V AC No Digit No Selection Auxiliary and Alarm Contacts Code Description AJ 1 Aux., 1 Alarm Contact, 24V AB 1 Aux., 1 Alarm Contact, 400V FB 2 Aux., 400V ♦ Select one internal option for inner right mounting (shunt trip or undervoltage release). For remote control MCCB operation, select the spring charging motor and operating voltage for shunt trip and shunt close coils from table i. Consult your local Rockwell automation sales office or Allen-Bradley distributor for further assistance. Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 47 Bulletin 140MG Motor Protection Circuit Breakers Product Selection — 10…150 A, H- and J-Frame Motor Protection Circuit Breakers Table of Contents Standards Compliance Product Selection .............. this page Accessories.......................... 50 Specifications ...................... 64 Approximate Dimensions—H-Frame..... 76 Approximate Dimensions—J-Frame...... 92 EN 60947-1, -2 UL 489 (Pending) CSA 22.2, No. 5 (Pending) Interrupting Rating/Breaking Capacity Interrupting Rating (50/60 Hz), UL 489/CSA C22.2-5, No. 5-02 [kA] 240V 150 480V 65 600V 25 Breaking Capacity (50/60 Hz), IEC 60947-2 220V Icu [kA] Ics [%Icu] 100 415V Icu [kA] Ics [%Icu] 100 70 100 440V Icu [kA] Ics [%Icu] 65 690V Icu [kA] Ics [%Icu] 100 15 100 Breaking Capacity (DC), IEC 60947-2 § 250V DC 500V DC (2-pole in series) (3-pole in series) Icu [kA] Ics [%Icu] Icu [kA] Ics [%Icu] 70 100 70 100 These ratings have not been tested for the CCC listing. Max. Rated Motor Current (In) [A] L (Motor FLC) I1 = 0.4…1 x In Trip Class U I 50% of I1 In = Instantaneous ON or OFF Adjustable from 6…13 x In Cat. No.‡ H-Frame 25 10…25 60 24…60 100 40…100 140MG-H8E-C25 3E, 5E, 10E, 20E (approx. 2…20 s) 140MG-H8E-C60 140MG-H8E-D10 J-Frame 40 16…40 60 24…60 100 40…100 150 60…150 140MG-J8E-C40 3E, 5E, 10E, 20E (approx. 2…20 s) ON or OFF 140MG-J8E-C60 140MG-J8E-D10 140MG-J8E-D15 ‡ Select the Motor Protection Circuit Breaker based on the motor FLC. Visit our website: www.ab.com/catalogs 48 Adjustable from 6…13 x In Publication 140G-SG001C-EN-P Bulletin 140MG Motor Protection Circuit Breakers Product Selection — 10…150 A, H- and J-Frame Page Intentionally Left Blank Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 49 Bulletin 140G Molded Case Circuit Breakers Accessories Accessories Table of Contents Description Page Internal Electrical Accessories Auxiliary/Alarm Contact (AX/AL)................................................ 50 Shunt Trip (SNT)............................................................................... 52 Shunt Close (SNC).......................................................................... 52 Description Page Undervoltage Release (UVR) ...................................................... 53 Residual Current Release Module ............................................ 53 Current Transformer for Neutral Current ................................ 54 Mechanical Accessories Terminal Lugs.................................................................................... 54 Extended Terminals ........................................................................ 55 Spreader Terminals......................................................................... 55 Rear Terminals.................................................................................. 56 Phase Barriers .................................................................................. 56 Terminal Covers ............................................................................... 56 Variable Depth Rotary Operating Kits ..................................... 58 Flex Cable Operators..................................................................... 59 Direct Rotary Operators................................................................ 60 Motor Operators .............................................................................. 60 Bulletin 1494V Variable Depth Flange-Mounted Circuit Breaker Operating Mechanism Components ..................................................................................... 61 Additional Accessories................................................................. 62 Replacement Parts......................................................................... 63 Internal Electrical Accessories Auxiliary/Alarm Contact (AX/AL) Auxiliary and alarm contacts are supplied in multiple variations for customer application. Auxiliary Contacts (AX) : Indicate ON/OFF status of the MCCB. Alarm Contacts (AL): Indicate trip status of the MCCB. Alarm trip can be initiated by pressing the test button on the molded case circuit breaker, a trip due to overcurrent, short circuit; or trip due to residual current, shunt, or undervoltage release signals. Thermal Trip Contacts (TU): Trips only when the MCCB has detected an overcurrent, short-circuit, or protection trip. H- and J-Frame MCCBs have a button to test this feature. Available only for H, J, N, NS, and R frames. These contacts are installed by removing the MCCB cover and accessing right-side pockets within the breaker with snap-in mounting provisions. Frames G…M are supplied with pig tail wiring, with each terminal wire marked. Frames N, NS, and R are wired internal to the breaker and are terminated for connection using a 3-pin quick connector. Description Designation Diagram Frame Size Cat. No. TU AL C H, J 140G-H-EA1TA (1) Auxiliary (1) Alarm Contact 250V AX2/AL1 D G, H, I, J 140G-G-EA1R1A (2) Auxiliary (1) Alarm Contact 250V AX1/AX2/AL1 E G, H, I, J 140G-G-EA2R1A (3) Auxiliary (1) Alarm Contact 250V AX1/AX2/AX3/AL1 F H, I, J 140G-H-EA3R1A (3) Auxiliary (2) Alarm Contact 250V AX1/AX2/AX3/AL1/AL2 G H, J 140G-H-EA3R2A (2) Auxiliary (2) Alarm (1) TU AL Contact 250V AX2/AX3/AL1/AL2/TU AL H H, J 140G-H-EA2R2TA (1) Auxiliary Contact 250V AX2 A G, H, I, J 140G-G-EA1A (1) Auxiliary Contact 250V or (1) Alarm Contact 250V AX2 A AL1 B G, H, I, J 140G-G-EA1AU 140G-G-EA1J (1) TU Alarm Contact 250V Representative Photo (1) Auxiliary Contact 24V AX2 A G, H, I, J (1) TU Alarm Contact 24V TU AL C H, J 140G-H-EA1TJ (1) Auxiliary (1) Alarm Contact 24V AX2/AL1 D G, H, I, J 140G-G-EA1R1J (3) Auxilary (1) Alarm Contact, 24V AX1/AX2/AX3/AL1 F H, I, J 140G-H-EA3R1J (1) Auxilary (1) Alarm Contact, 400V AX2/AL1 D H, J 140G-H-EA1R1B (2) Auxiliary Contact 400V AX1/AX2 I H, J 140G-H-EA2B (1) Auxiliary (1) Alarm Contact 250V AX1/AL1 J K, M 140G-K-EA1R1A (3) Auxiliary (1) Alarm Contact 250V AX1/AX2/AX3/AL1 F K, M 140G-K-EA3R1A (3) Auxiliary (1) Alarm Contact 24V AX1/AX2/AX3/AL1 F K, M 140G-K-EA3R1J (1) Auxiliary (1) Alarm Contact 400V AX1/AL1 J K, M 140G-K-EA1R1B (2) Auxiliary Contact 400V AX1/AX2 I K, M 140G-K-EA2B (1) Auxiliary (1) Alarm Contact 24V AX2/AL1 D N 140G-N-EA1R1J (2) Auxiliary Contact 24V AX1/AX2 I N, NS 140G-N-EA2J (1) Auxiliary (1) Alarm Contact 400V AX2/AL1 D N 140G-N-EA1R1B (2) Auxiliary Contact 400V AX1/AX2 I N, NS 140G-N-EA2B (1) TU Alarm Contact 250V TU AL C N, NS 140G-N-EA1TA (4) Auxiliary Contact 24V AX1/AX2/AX3/AX4 K R 140G-R-EA4J (4) Auxiliary Contact 400V AX1/AX2/AX3/AX4 K R 140G-R-EA4A (1) TU Alarm Contact 250V TU AL L R 140G-R-EA1TA This contact is supplied with unmarked wires. Contact can function as either an auxiliary or alarm contact, depending on connection method. Visit our website: www.ab.com/catalogs 50 Publication 140G-SG001C-EN-P Bulletin 140G Molded Case Circuit Breakers Accessories Diagrams D C 22 22 AX2 24 96 98 98 08 08 06 06 96 98 98 96 24 22 B 96 24 24 A 22 AX2 AL1 AL1 95 21 95 21 05 95 05 21 95 F E AX1 AX2 AX2 34 96 34 AX3 AL1 11 95 95 31 21 31 95 G AX1 AX2 H AX2 AL1 06 I 08 12 12 18 08 16 06 98 18 96 16 34 98 32 96 22 AX3 24 34 22 32 18 24 16 18 34 98 16 96 98 34 96 32 32 24 24 22 22 14 14 AX3 14 AX1 AL2 AL1 22 24 AX2 AL2 21 95 15 21 31 95 15 AX1 AX2 AX3 42 21 11 21 44 44 34 42 32 34 24 32 22 24 14 22 14 12 05 L K J 11 05 15 95 31 21 15 95 31 AX4 11 21 41 21 31 TU AL 11 11 12 21 31 TU AL 11 12 12 24 21 21 11 95 21 11 AL1 11 98 98 32 96 24 32 22 14 98 22 24 98 12 96 14 22 AX1 24 96 22 22 24 14 14 12 12 12 14 21 TU AL 31 41 Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 51 Bulletin 140G Molded Case Circuit Breakers Accessories Shunt Trip (SNT) Allows for remote tripping of the MCCB by applying control voltage to the shunt trip coil. Frames G, H, I, J, K, and M are supplied with pig-tail wiring (each terminal wire is marked). Frame N, NS, and R are wired internal to the breaker and terminated for connection using a 3-pin quick connector. Description Diagram 12V DC Frame Size 24…30V AC/DC 140G-G-SNJ SO 48…60V AC/DC 140G-G-SNKY 110…127V AC/110…125V DC G, H, I, J 220…240V AC/220…250V DC 480…525V AC C1 140G-K-SNR 24…30V AC/DC 140G-K-SNJ 48…60V AC/DC 140G-K-SNKY 110…127V AC/110…125V DC K, M 220…240V AC/220…250V DC 140G-K-SND 140G-K-SNA 140G-K-SNB 380…440V AC SNT 480…525V AC 140G-K-SNC 140G-N-SNJ C2 24V AC/DC 48V AC/DC 140G-N-SNKY C2 110…120V AC/DC N, NS 140G-N-SND 220…240V AC/DC 140G-N-SNA 380…400V AC 140G-N-SNB 24V DC 140G-R-SNJ 48V AC/DC 140G-R-SNKY 110…120V AC/DC R 220…240V AC/DC Representative Photo 140G-G-SNA 140G-G-SNC C1 12V DC Representative Photo 140G-G-SND 140G-G-SNB 380…440V AC Representative Photo Cat. No. 140G-G-SNR + ~ 380…400V AC/DC 140G-R-SND 140G-R-SNA ~ 140G-R-SNB Shunt Close (SNC) For use with motorized versions of the NS- and R-Frame MCCB. Allows for remote closing of the MCCB when the spring motor is charged. The shunt close unit is wired internal to the MCCB and terminated for connection using a 3-pin quick connect. Description Diagram 24V AC/DC + ~ 48V AC/DC SO Frame Size Cat. No. 140G-NS-SNCJ 140G-NS-SNCKY 110…120V AC/DC NS 140G-NS-SNCD C1 140G-NS-SNCA C1 220…240V AC/DC 380…400V AC 140G-NS-SNCB 24V DC 140G-R-SNCJ SNC 140G-R-SNCKY 48V AC/DC 110…120V AC/DC Representative Photo 380…400V AC R C2 220…240V AC/DC C2 ~ Visit our website: www.ab.com/catalogs 52 Publication 140G-SG001C-EN-P 140G-R-SNCD 140G-R-SNCA 140G-R-SNCB Bulletin 140G Molded Case Circuit Breakers Accessories Undervoltage Release (UVR) Opens the MCCB when supply voltage drops below 0.7 of the UV relay, with a trip rating from 0.7…0.35. The MCCB can be reset when the supply voltage is higher than 0.85 of the relay rating. When the UV is de-energized it is not possible to close the main contacts on the MCCB. R Resistor is supplied with the MCCB when reset is required. Description Diagram Frame Size 24…30V AC/DC + ~ 48V AC/DC 140G-G-UVR 60V AC/DC 140G-G-UVKY 110…127V AC/110…125V DC SO G, H, I, J 220…240V AC/220…250V DC 140G-G-UVD 140G-G-UVA 140G-G-UVB 380…440 V AC Representative Photo Cat. No. 140G-G-UVJ 480…525 V AC 140G-G-UVC D1 140G-K-UVJ D1 24…30V AC/DC 48V AC/DC 140G-K-UVR 60V AC/DC 140G-K-UVKY 110…127V AC/110…125V DC 140G-K-UVD K, M 220…240V AC/220…250V DC 140G-K-UVA 380…440 V AC 140G-K-UVB 480…525 V AC 140G-K-UVC Representative Photo 24V AC/DC 140G-N-UVJ UV 60V AC/DC 140G-N-UVKY 110…120V AC/DC N, NS D2 220…240V AC/DC 380…400V AC 140G-N-UVA 140G-N-UVB D2 140G-N-UVC 415…440V AC 24V DC 140G-R-UVJ 60V AC/DC 140G-R-UVKY R 110…120V AC/DC 380…400V AC 140G-R-UVD R 220…240V AC/DC Representative Photo 140G-N-UVD 140G-R-UVA ~ 140G-R-UVB 440…480V AC 140G-R-UVC Residual Current Release Module (IEC Only) The residual current release module provides protection against low levels of earth (ground) fault currents. It continuously monitors the state of the insulation, with adjustability to provide protection from direct and indirect contact. Compliant with IEC 60947-2 annex B, IEC 61000 for protection against unwarranted tripping. Alarm & Trip indication 0.03 A with 0.0 s override Current adjustment: 0.5…10 A Time adjustment: 0.0…3 s Test Representative Photo Frame Size 3-Pole Cat. No. 4-Pole Cat. No. G 140G-G-ELP1603 140G-G-ELP1604 H — 140G-H-ELP1604 I 140G-I-ELP2503 140G-I-ELP2504 J — 140G-J-EP2504 K — 140G-K-ELP Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 53 Bulletin 140G Molded Case Circuit Breakers Accessories Current Transformer for Neutral Current Rated Current [A] Frame Size Cat. No. 300 K 140G-K-NCTD30 Representative Photo 400 K 140G-K-NCTD40 600 M 140G-M-NCTD60 800 M 140G-M-NCTD80 400…1600 N, NS 140G-N-NCTE16 1000…3200 R 140G-R-NCTE30 Order with connector (Cat. No. 140G-K-CC). Mechanical Accessories Terminal Lugs Description Frame Size Cu wire, MCCB only (1) 14…1/0 AWG or 2.5…70 mm2 Cu wire, MCP only (1) 14…1/0 AWG or 1.5…70 mm2 G Multiple cable - Cu wire (6) 14…2 AWG or 2.5…35 mm2 Cu wire only (1) 14…1/0 AWG or 2.5…95 mm2 Representative Photo Multiple cable - Cu wire (6) 14…2 AWG or 2.5…35 mm2 Al or Cu wire (1) 4…300 MCM or 25…150 mm2 140G-G-MTL63 140G-G-MTL64 140G-H-TLC13 140G-H-TLC14 140G-H-MTL63 140G-H-MTL64 140G-I-TLA13 140G-I-TLA14 140G-I-TLA1A3 140G-I-TLA1A4 140G-I-MTL63 140G-I-MTL64 Al or Cu wire (1) 14…1/0 AWG or 2.5…50 mm2 140G-J-TLA13 140G-J-TLA14 Al or Cu wire (1) 4…300 MCM or 25…150 mm2 140G-J-TLA1A3 140G-J-TLA1A4 140G-J-TLA1B3 140G-J-TLA1B4 Cu wire only (1) 10…350 MCM or 6…185 mm2 140G-J-TLC13 140G-J-TLC14 Multiple cable - Cu wire (6) 12…2 AWG or 2.5…35 mm2 140G-J-MTL63 140G-J-MTL64 Al or Cu wire (1) 250…500 MCM or 120…240 mm2 140G-K-TLA13 140G-K-TLA14 Al or Cu wire (2) 2/0…250 MCM or 95…120 mm2 140G-K-TLA23 140G-K-TLA24 140G-K-TLC13 140G-K-TLC14 Cu wire only (2) 2/0…250 MCM or 95…120 mm2 140G-K-TLC23 140G-K-TLC24 Multiple cable - Cu wire (6) 6…1/0 AWG or 16…50 mm2 140G-K-MTL63 140G-K-MTL64 Al or Cu wire (2) 250…500 MCM or 120…240 mm2 140G-M-TLA23 140G-M-TLA24 140G-M-TLA33 140G-M-TLA34 140G-M-TLC23 140G-M-TLC24 140G-M-TLC33 140G-M-TLC34 140G-N-TLA43 140G-N-TLA44 140G-N-TLC43 140G-N-TLC44 140G-R-TLA63 — 140G-R-TLC63 — J K M Cu wire only (2) 3/0…350 MCM or 85…185 mm2 Cu wire only (3) 2/0…350 MCM or 70…185 mm2 Al or Cu wire (4) 4/0…500 MCM or 70…240 mm2 Cu wire only (4) 4/0…500 MCM or 70…240 mm2 N, NS Al or Cu wire (6) 1/0…750 MCM or 50…400 mm2 R Cu wire only (6) 1/0…750 MCM or 50…400 mm2 Visit our website: www.ab.com/catalogs 54 — 140G-I-TLC14 Al or Cu wire (3) 2/0…400 MCM or 70…185 mm2 Representative Photo 140G-G-TLC13A 140G-I-TLC13 Cu wire only (1) 250…500 MCM or 120…240 mm2 Representative Photo 140G-G-TLC14 Multiple cable - Cu wire (6) 12…2 AWG or 2.5…35 mm2 Al or Cu wire (1) 6 (Al)/10 (Cu)…350 MCM or 2.5…185 mm2 (Al) Representative Photo 140G-G-TLC13 I Cu wire only (1) 10…250 MCM or 6…185 mm2 Representative Photo Cat. No. (Pkg. Qty. 4) H Al or Cu wire (1) 14…1/0 AWG or 2.5…50 mm2 Representative Photo Cat. No. (Pkg. Qty. 3) Publication 140G-SG001C-EN-P Bulletin 140G Molded Case Circuit Breakers Accessories Extended Terminals Description Representative Photo Frame Size 3-Pole Cat. No. (Pkg. Qty. 3) 4-Pole Cat. No. (Pkg. Qty. 4) G 140G-G-EXT3 140G-G-EXT4 H 140G-H-EXT3 140G-H-EXT4 I 140G-I-EXT3 140G-I-EXT4 J 140G-J-EXT3 140G-J-EXT4 Extended Terminals for busbar or ring type connection • G- & I-frame supplied with 100 mm phase barrier • H- & J-frame supplied with insulator, 100 mm phase barrier, and terminal cover • K- & N-/NS-frame supplied with insulator and 100 mm phase barrier • M-frame terminals only K 140G-K-EXT3 140G-K-EXT4 M 140G-M-EXT3 140G-M-EXT4 N, NS 140G-N-EXT3 140G-N-EXT4 Frame Size 3-Pole Cat. No. (Pkg. Qty. 3) 4-Pole Cat. No. (Pkg. Qty. 4) G 140G-G-EXS3 140G-G-EXS4 H 140G-H-EXS3 140G-H-EXS4 I 140G-I-EXS3 140G-I-EXS4 J 140G-J-EXS3 140G-J-EXS4 K 140G-K-EXS3 140G-K-EXS4 M — 140G-M-EXS4 N, NS — 140G-N-EXS4 R 140G-R-EXS3 140G-R-EXS4 M 140G-M-EXSLI3 — N, NS 140G-N-EXSLI3 — M 140G-M-EXSLO3 — N, NS 140G-N-EXSLO3 — Frame Size 3-Pole Cat. No. (Pkg. Qty. 3) 4-Pole Cat. No. (Pkg. Qty. 4) N, NS 140G-N-TLH3 140G-N-TLH4 N, NS 140G-N-TLV3 140G-N-TLV4 R 140G-R-TLV3 140G-R-TLV4 Spreader Terminals Description Spreader Terminals for busbar or ring type connection • G- & I-frame supplied with 200 mm phase barrier • H- & J-frame supplied with insulator, 100 mm phase barrier, and terminal cover • K- & N-/NS-frame supplied with insulator and 100 mm phase barrier • M- & R-frame terminals only Representative Photo Top Spreader Terminals for busbar or ring type connection • M-frame terminals only Bottom Spreader Terminals for busbar or ring type connection • N/NS-frame supplied with insulator and 100 mm phase barrier Representative Photo Rear Terminals Description Rear flat horizontal terminals Rear flat vertical terminals 2000 A and 2500 A MCCBs only. Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 55 Bulletin 140G Molded Case Circuit Breakers Accessories Phase Barriers Provides additional clearance when special connections that extend beyond the frame of the MCCB are used. Frames G, H, I, J, and K are supplied with 25 mm barriers as standard. Frame Size Length 3-Pole Cat. No. (Pkg. Qty. 4) 4-Pole Cat. No. (Pkg. Qty. 6) 1 in. (25 mm) 140G-G-PB3M 140G-G-PB4M G, I 4 in. (100 mm) 140G-G-PB3L 140G-G-PB4L 8 in. (200 mm) 140G-G-PB3H 140G-G-PB4H 140G-H-PB4M H, J K, N, NS M Representative Photo R 1 in. (25 mm) 140G-H-PB3M 4 in. (100 mm) 140G-H-PB3L 140G-H-PB4L 8 in. (200 mm) 140G-H-PB3H 140G-H-PB4H 4 in. (100 mm) 140G-K-PB3L 140G-K-PB4L 8 in. (200 mm) 140G-K-PB3H 140G-K-PB4H 140G-M-PB4L 4 in. (100 mm) 140G-M-PB3L 4 in. (100 mm) 140G-R-PB3L 140G-R-PB4L 8 in. (200 mm) 140G-R-PB3H 140G-R-PB4H Height 3-Pole Cat. No. (Pkg. Qty. 2) 4-Pole Cat. No. (Pkg. Qty. 2) Terminal Covers Provide IP40 finger protection against accidental contact with live parts. Terminal covers are pre-punched to ease installation. Supplied as standard with the selection of multiple cable terminal lugs. Frame Size G H I Representative Photo J K M N, NS Representative Photo 0.08 in. (2 mm) 140G-G-TC3L 140G-G-TC4L 2 in. (50 mm) 140G-G-TC3H 140G-G-TC4H 0.08 in. (2 mm) 140G-H-TC3L 140G-H-TC4L 2 in. (50 mm) 140G-H-TC3H 140G-H-TC4H 0.08 in. (2 mm) 140G-I-TC3L 140G-I-TC4L 2.36 in. (60 mm) 140G-I-TC3H 140G-I-TC4H 0.08 in. (2 mm) 140G-J-TC3L 140G-J-TC4L 2.36 in. (60 mm) 140G-J-TC3H 140G-J-TC4H 0.08 in. (2 mm) 140G-K-TC3L 140G-K-TC4L 2.36 in. (60 mm) 140G-K-TC3H 140G-K-TC4H 0.08 in. (2 mm) 140G-M-TC3L 140G-M-TC4L 2.36 in. (60 mm) 140G-M-TC3H 140G-M-TC4H 0.1 in. (2.5 mm) 140G-N-TC3L 140G-N-TC4L 2.76 in. (70 mm) 140G-N-TC3H 140G-N-TC4H Visit our website: www.ab.com/catalogs 56 Publication 140G-SG001C-EN-P Bulletin 140G Molded Case Circuit Breakers Accessories Variable Depth Rotary Operating Kits Rotary, Variable Depth Operators • Supplied with external handle, operating shaft, and MCCB mounted operating mechanism. • Refer to page 56 to select as components. • Frames G, H, I, and J use a Bul. 140U P-style handle. • Frames K, M, and N use a Bul. 140U medium style handle. Frame Size Handle Color Black Red/Yellow G, I Black Red/yellow Black Red/yellow H, J Black Representative Photo Red/yellow Black Red/yellow K Black Red/yellow Black Red/yellow M Black Red/yellow Black Red/yellow N Black Representative Photo Red/yellow Shaft Length 12 in. (30.48 mm) 21 in. (53.34 mm) 12 in. (30.48 mm) 21 in. (53.34 mm) 12.6 in. (320 mm) 22.8 in. (580 mm) 12.6 in. (320 mm) 22.8 in. (580 mm) 12.6 in. (320 mm) 22.8 in. (580 mm) Cat. No. 140G-G-RVM12B 140G-G-RVM12R 140G-G-RVM21B 140G-G-RVM21R 140G-H-RVM12B 140G-H-RVM12R 140G-H-RVM21B 140G-H-RVM21R 140G-K-RVM12B 140G-K-RVM12R 140G-K-RVM21B 140G-K-RVM21R 140G-M-RVM12B 140G-M-RVM12R 140G-M-RVM21B 140G-M-RVM21R 140G-N-RVM12B 140G-N-RVM12R 140G-N-RVM21B 140G-N-RVM21R Rotary, Variable Depth Operators with Internal NFPA 79 Operating Handle • Supplied with external handle, NFPA handle with operating shaft, support bracket, and MCCB mounted operating mechanism. • Refer to page 58 to select as components. • Frames G, H, I, and J use a Bul. 140U P-style handle. • Frames K, M, and N use a Bul. 140U medium style handle. Frame Size Handle Color Black G, I Red/yellow Black Red/yellow Black H, J Representative Photo Red/yellow Black Red/yellow Black K Red/yellow Black Red/yellow Black M Red/yellow Black Red/yellow Black N Representative Photo Red/yellow Black Red/yellow Shaft Length 12 in. (30.48 mm) 21 in. (53.34 mm) 12 in. (30.48 mm) 21 in. (53.34 mm) 12.6 in. (320 mm) 22.8 in. (580 mm) 12.6 in. (320 mm) 22.8 in. (580 mm) 12.6 in. (320 mm) 22.8 in. (580 mm) Cat. No. 140G-G-NVM12B 140G-G-NVM12R 140G-G-NVM21B 140G-G-NVM21R 140G-H-NVM12B 140G-H-NVM12R 140G-H-NVM21B 140G-H-NVM21R 140G-K-NVM12B 140G-K-NVM12R 140G-K-NVM21B 140G-K-NVM21R 140G-M-NVM12B 140G-M-NVM12R 140G-M-NVM21B 140G-M-NVM21R 140G-N-NVM12B 140G-N-NVM12R 140G-N-NVM21B 140G-N-NVM21R Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 57 Bulletin 140G Molded Case Circuit Breakers Accessories Variable Depth Rotary Components Representative Photo Description Handle Color • P-style handle for G, H, I, and J frames • Medium handles for K, M, and N frames • Rated 3/3R/4/4X/12 • Accepts 3 padlocks Black/Grey Description Frame Size G, H, I, J Red/Yellow Black/Grey K, M, N Red/Yellow 140U-HM4E Shaft Length Frame Size G, H, I, J 21 in. (533 mm) 12 in. (305 mm) Representative Photo K, M, N 21 in. (533 mm) Representative Photo Description Shaft Length NFPA 79 internal operating handle with shaft Internal handle permits operation of the molded case circuit breaker when the door is open in compliance with NFPA 79. 12 in. (305 mm) Representative Photo 140U-PY 140U-HM4 12 in. (305 mm) Extension Shaft Cat. No. 140U-PB Frame Size G, H, I, J 21 in. (533 mm) 12 in. (305 mm) Cat. No. 194R-S1 194R-S2 140U-R5 140U-R6 Cat. No. 140G-N1 140G-N2 140G-N7 K, M, N 21 in. (533 mm) 140G-N8 Description Frame Size Cat. No. Rotary, Variable Depth Operating Mechanism • Direct molded case circuit breaker mount • G, H, I, and J frame use 194R-S1 or 194RS2 shafts (140G-N1 or 140G-N2 NFPA) • K, M, and N frames use 194R-R7 or 194RR8 shafts (140G-R7 or 140G-R8 NFPA) • Shaft secured with set screw or cotter pin G, I 140G-G-RMX H, J 140G-H-RMX K 140G-K-RMX M 140G-M-RMX N 140G-N-RMX Description Frame Size Cat. No. G, H, I, J 140G-G-OSB Support Bracket Supplied as standard with NFPA variable depth operator kits K 140G-K-OSB M 140G-M-OSB N 140G-N-OSB Auxiliary Contacts for Handle Mechanism Mounting Suitable for: 140G-G-RMB, -RMY, RMX 140G-H-RMB, -RMY, RMX 140G-K-RMB, -RMY, RMX 140G-M-RMB, -RMY, RMX Representative Photo Description Pkg. Qty Early Make Handle Auxiliary Contact Open 400V 2 Cat. No. 140G-G-EAM1B G, H, I, J Early Break Handle Auxiliary Contact Close 400V 2 Early Make Handle Auxiliary Contact Close 250V 2 Visit our website: www.ab.com/catalogs 58 Frame Size Publication 140G-SG001C-EN-P 140G-G-EAB1B K 140G-K-EAM1A M 140G-M-EAM1A Bulletin 140G Molded Case Circuit Breakers Accessories Direct Rotary Operators Mount with direct handle operation of the MCCB. Lockable in OFF position (three padlocks max.). Frame Size G, I H, J Representative Photo K M N Representative Photo Handle Color Cat. No. Black 140G-G-RMB Red/yellow 140G-G-RMY Black 140G-H-RMB Red/yellow 140G-H-RMY Black 140G-K-RMB Red/yellow 140G-K-RMY Black 140G-M-RMB Red/yellow 140G-M-RMY Black 140G-N-RMB Red/yellow 140G-N-RMY Motor Operators Remotely opens, closes, and resets the MCCB. Frame G & I motor operators are supplied with auto/manual selector, test feature, and special tool for local operation of the MCCB. Frames H, J, K, and M utilize a stored energy motor for local control of the motor without the use of special tools and include auto/manual/lock selection, lever to recharge the motor, and open & close push button operation. Description Frame Size 140G-G-EOPJ 48…60V DC 140G-G-EOPKY 140G-G-EOPD 110…125V AC/DC G, I 220…250V AC/DC Representative Photo 140G-G-EOPA 380…440V AC 140G-G-EOPB 480…525V AC 140G-G-EOPC 24V DC 140G-H-EOPJ 48…60V DC 140G-H-EOPKY 110…125V AC/DC 140G-H-EOPD H, J 220…250V AC/DC Representative Photo 140G-H-EOPA 380…440V AC 140G-H-EOPB 480…525V AC 140G-H-EOPC 24V DC 140G-K-EOPJ 48…60V DC 140G-K-EOPKY 110…125V AC/DC 140G-K-EOPD K 220…250V AC/DC 140G-K-EOPA 380V AC 140G-K-EOPB 24V DC 140G-M-EOPJ 48…60V DC 140G-M-EOPKY 110…125V AC/DC Representative Photo 140G-M-EOPD M 220…250V AC/DC 140G-M-EOPA 380V AC 140G-M-EOPB Description Frame Size 220…250V DC 140G-NS-SCMB NS 140G-NS-SCMD 24…30V DC 140G-NS-SCMJ 48…60V AC/DC 140G-NS-SCMKY 220…250V DC 140G-R-SCMA 100…130V AC/DC 140G-R-SCMD 24…30V DC Representative Photo Cat. No. 140G-NS-SCMA 380…415V AC 100…130V AC/DC Spring Charging Motor Cat. No. 24V DC 48…60V AC/DC R 140G-R-SCMJ 140G-R-SCMKY Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 59 Bulletin 140G Molded Case Circuit Breakers Accessories Flex Cable Operators For use with NEMA-style flange enclosures. Includes handle, MCCB operator, cable, and necessary hardware. Pre-assembled for ease of installation. Frame Size Handle Type Non-metallic Handle, Type 1/3/12/4/4X G, I Stainless Steel Handle, Type 4/4X Painted Metal Handle, Type 1/12 Non-metallic Handle, Type 1/3/12/4/4X H Stainless Steel Handle, Type 4/4X Painted Metal Handle, Type 1/12 Non-metallic Handle, Type 1/3/12/4/4X J Stainless Steel Handle, Type 4/4X Painted Metal Handle, Type 1/12 Non-metallic Handle, Type 1/3/12/4/4X K Stainless Steel Handle, Type 4/4X Painted Metal Handle, Type 1/12 Stainless Steel Handle, Type 4/4X M Painted Metal Handle, Type 1/12 Stainless Steel Handle, Type 4/4X N Painted Metal Handle, Type 1/12 Representative Photo Visit our website: www.ab.com/catalogs 60 Publication 140G-SG001C-EN-P Cable Length Cat. No. 4 ft (1.3 m) 140G-G-FCX04 6 ft (1.9 m) 140G-G-FCX06 10 ft (3.0 m) 140G-G-FCX10 4 ft (1.3 m) 140G-G-FCS04 6 ft (1.9 m) 140G-G-FCS06 10 ft (3.0 m) 140G-G-FCS10 4 ft (1.3 m) 140G-G-FMX04 6 ft (1.9 m) 140G-G-FMX06 10 ft (3.0 m) 140G-G-FMX10 4 ft (1.3 m) 140G-H-FCX04 6 ft (1.9 m) 140G-H-FCX06 10 ft (3.0 m) 140G-H-FCX10 4 ft (1.3 m) 140G-H-FCS04 6 ft (1.9 m) 140G-H-FCS06 10 ft (3.0 m) 140G-H-FCS10 4 ft (1.3 m) 140G-H-FMX04 6 ft (1.9 m) 140G-H-FMX06 10 ft (3.0 m) 140G-H-FMX10 4 ft (1.3 m) 140G-J-FCX04 6 ft (1.9 m) 140G-J-FCX06 10 ft (3.0 m) 140G-J-FCX10 4 ft (1.3 m) 140G-J-FCS04 6 ft (1.9 m) 140G-J-FCS06 10 ft (3.0 m) 140G-J-FCS10 4 ft (1.3 m) 140G-J-FMX04 6 ft (1.9 m) 140G-J-FMX06 10 ft (3.0 m) 140G-J-FMX10 4 ft (1.3 m) 140G-K-FCX04 6 ft (1.9 m) 140G-K-FCX06 10 ft (3.0 m) 140G-K-FCX10 4 ft (1.3 m) 140G-K-FCS04 6 ft (1.9 m) 140G-K-FCS06 10 ft (3.0 m) 140G-K-FCS10 4 ft (1.3 m) 140G-K-FMX04 6 ft (1.9 m) 140G-K-FMX06 10 ft (3.0 m) 140G-K-FMX10 4 ft (1.3 m) 140G-M-FCS04 6 ft (1.9 m) 140G-M-FCS06 10 ft (3.0 m) 140G-M-FCS10 4 ft (1.3 m) 140G-M-FMX04 6 ft (1.9 m) 140G-M-FMX06 10 ft (3.0 m) 140G-M-FMX10 4 ft (1.3 m) 140G-N-FCS04 6 ft (1.9 m) 140G-N-FCS06 10 ft (3.0 m) 140G-N-FCS10 4 ft (1.3 m) 140G-N-FMX04 6 ft (1.9 m) 140G-N-FMX06 10 ft (3.0 m) 140G-N-FMX10 Bulletin 140G Molded Case Circuit Breakers Accessories Bulletin 1494V Variable Depth Flange-Mounted Circuit Breaker Operating Mechanism Components Circuit Breaker Operating Mechanism The mechanism listed must be combined with a connecting rod, operating handle, and a circuit breaker (supplied by customer) to obtain a functional device. 3-Pole Circuit Breaker Operating Mechanism Brand Frame Size [A] Frame Designation Cat. No. Allen-Bradley 125, 225, 250 140G-G, H, I, J 1494V-M70 Allen-Bradley 400 140G-K 1494V-M71 Allen-Bradley 800, 1200 140G-M, N 1494V-M72 Circuit breakers to be provided by customer. Connecting Rods Approximate dimensions are in inches (millimeters). Approximate dimensions are not intended for manufacturing purposes. Circuit Breaker Frame Size [A] Enclosure Depth Minimum Maximum Cat. No. 6-3/4 (172) 9-1/8 (232) 1494V-RA3 6-3/4 (172) 21-5/8 (549) 1494V-RA4 Description Circuit Breaker Frame Size [A] Operating Handle Handle Type Type 1, 3R, 4, 4X, 12 Nonmetallic 125, 150, 250, 400 1494F-P1 Type 1, 3R, 4, 12 Painted Metal 125, 150, 250, 400 1494F-M1 Type 4, 4X Stainless Steel 125, 150, 250, 400 1494F-S1 Type 1, 3R, 4, 12 Painted Metal 800, 1200 1494F-M2 Type 4, 4X Stainless Steel 800, 1200 1494F-S2 For Use With Contact Type Cat. No. 1 N.O. 1495-N85 1 N.C. 1495-N86 125, 150, 250, 400, 600, 800, 1200 Operating Handle Cat. No. Auxiliary Contacts Description Auxiliary Contact Kit for Circuit Breakers (includes contacts and adapter) 125…1200 A Allen-Bradley Bul. 140G Circuit Breakers Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 61 Bulletin 140G Molded Case Circuit Breakers Accessories Additional Accessories Description Trip Test Unit Padlockable Handle Block Padlocking Hasp Lock-OFF only Representative Photo Direct Mechanical Lock to Door Description Frame Size Cat. No. All 140G-ELTT G, I 140G-G-PL H, J 140G-H-PL N 140G-N-PL NS 140G-NS-PL R 140G-R-PL N, NS 140G-N-SINT Frame Size G, I 3-Pole Cat. No. 140G-G-MH3 4-Pole Cat. No. ‡ 140G-G-MH4 H, J — 140G-H-MH4 K — § 140G-K-MH4 M — § 140G-M-MH4 N, NS — § G 140G-G-DRA Replacement Mounting Hardware Metric threads Representative Photo DIN Rail Adapter Adapts to 35 mm DIN Rail Representative Photo Escutcheon Plates Finsh Frame with Marking provision window. For flush mounted (to door) MCCB applications. Representative Photo IP54 Door protection Transparent plastic cover flush mounted to the enclosure door. Mounted on hinges and provided with a keyed lock. Representative Photo H, J 140G-H-DRA I 140G-I-DRA 140G-I-DRA4 G 140G-G-EP3 140G-G-EP4 H 140G-H-EP3 140G-H-EP4 I 140G-I-MH3 140G-I-MH4 J 140G-J-MH3 140G-J-MH4 K 140G-K-MH3 M 140G-M-MH3 N, NS 140G-N-MH3 R 140G-R-MH3 N, NS 140G-N-BC12 R 140G-R-BC12 Pkg. Qty. 2 ‡ Pkg. Qty. 3 § Pkg. Qty. 4 Visit our website: www.ab.com/catalogs 62 140G-N-MH4 140G-G-DRA4 Publication 140G-SG001C-EN-P Bulletin 140G Molded Case Circuit Breakers Replacement Parts Replacement Parts Description Replacement End Cap Kits End Caps are supplied as standard for G, H,I,J,K,M,N & NS frames. Provide connections for ring type or bolt-on terminals. Representative Photo Insulators Supplied as standard for G, H, I, J, K, and M frames. Provide insulating barrier for MCCB applications, required for all applications with a Ue>440V. Pkg Qty 10. Representative Photo Frame Size 3-Pole Cat. No. 4-Pole Cat. No. G 140G-G-ECM 140G-G-ECM4 H 140G-H-ECM 140G-H-ECM4 I 140G-I-ECM 140G-I-ECM4 J 140G-J-ECM 140G-J-ECM4 K 140G-K-ECM 140G-K-ECM4 M 140G-M-ECM 140G-M-ECM4 N 140G-N-ECM 140G-N-ECM4 H 140G-H-BP3 140G-H-BP4 J 140G-J-BP3 140G-J-BP4 K 140G-K-BP3 140G-K-BP4 M 140G-M-BP3 140G-M-BP4 Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 63 Bulletin 140G Molded Case Circuit Breakers Specifications — G- and H-Frame G-Frame Max. Rated Current [A] Rated insulation voltage, Ui, IEC [V] H-Frame‡ 125 125 160 160 800 1000 NEMA, UL, CSA Interrupting Rating Code G2 G3 G6 G2 G3 G6 H2 H3 H6 H0 H15 H2 H3 H6 H0 H15 240V AC, 50/60Hz [kA] 50 65 100 50 65 100 65 100 150 200 200 65 100 150 200 200 480V AC, 50/60Hz [kA] 25 35 65 25 35 65 25 35 65 100 150 25 35 65 100 150 600Y/347V AC, 50/60Hz [kA] 10 14 25 10 14 25 — — — — — — 600V AC, 50/60 Hz [kA] — — — — 14 18 25 35 42 14 18 35 35 42 65 85 100 150 200 65 85 100 150 200 IEC 60947-2 Rated ultimate short-circuit breaking capacity, Icu 220/230/240V AC, 50/60Hz [kA] 65 85 100 65 85 100 380V AC, 50/60Hz [kA] 36 50 70 36 60 70 36 50 70 120 150 26 50 70 120 150 415V AC, 50/60Hz [kA] 36 50 70 36 50 70 36 50 70 120 150 36 50 70 120 150 440V AC, 50/60Hz [kA] 36 50 65 36 50 65 36 50 65 100 150 36 50 65 100 150 500V AC, 50/60Hz [kA] 30 36 50 36 50 65 30 36 50 60 70 30 36 50 60 70 525V AC, 50/60Hz [kA] 22 35 35 22 35 35 20 25 30 36 50 20 25 30 36 50 690V AC, 50/60Hz [kA] 6 8 10 6 8 10 10 12 15 18 20 10 12 15 18 20 250V DC, 2 Poles in Series [kA] 36 50 70 36 50 70 36 50 70 85 100 36 50 70 85 100 500V DC, 2 Poles in Series [kA] — — — — — — — — — — 500V DC, 3 Poles in Series [kA] 36 50 70 36 50 70 36 50 70 85 100 36 50 70 85 100 750V DC, 3 Poles in Series [kA] — — — — — — — — — — Rated service short-circuit breaking capacity, Ics 220/230/240V AC, 50/60Hz [kA] 75% (50) 75% 75% 75% 75% 75% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 380V AC, 50/60Hz [kA] 100% 100% 75% 100% 100% 75% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 415V AC, 50/60Hz [kA] 100% 75% 50% 100% 75% 50% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 440V AC, 50/60Hz [kA] 50% 50% 50% 50% 50% 50% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 500V AC, 50/60Hz [kA] 50% 50% 50% 50% 50% 50% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 525V AC, 50/60Hz [kA] 50% 50% 50% 50% 50% 50% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 690V AC, 50/60Hz [kA] 75% 50% 50% 75 50 50% 100% 100% 100% 75% 75% 100% 100% 100% 75% 75% 250V DC, 2 Poles in Series [kA] 100% 100% 75% 100% 100% 75% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 500V DC, 2 Poles in Series [kA] — — — — — — — — — — 500V DC, 3 Poles in Series [kA] 100% 100% 75% 100% 100% 75% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 750V DC, 3 Poles in Series [kA] — — — — — — — — — — Mechanical Life Electrical Life @ 415V AC [No. Ops] 25 000 25 000 [Ops/hr] 240 240 [No. Ops] 8000 8000 [Ops/hr] 120 120 Ambient Temp. w/out derating ºF [ºC] 104 ºF [40 ºC] 104 ºF [40 ºC] Storage Temperature ºF [ºC] -40...+176 ºF [-40…+80 ºC] -40...+176 ºF [-40…+80 ºC] Dimensions [Width/Depth/Height] [mm] 3 poles: 76.2x70x130 3 poles: 90x82.5x130 [mm] 4 poles: 101.6x70x130 4 poles: 120x82.5x130 IEC version with a 160 A Icu rating ‡ Cannot be reverse fed above 480V Visit our website: www.ab.com/catalogs 64 Publication 140G-SG001C-EN-P Bulletin 140G Molded Case Circuit Breakers Specifications — I- and J-Frame I-Frame J-Frame‡ Max. Rated Current [A] 225 250 Rated insulation voltage, Ui, IEC [V] 800 1000 NEMA, UL, CSA Interrupting Rating Code I2 I3 J2 J3 J6 J0 240V AC, 50/60Hz [kA] 50 65 65 100 150 200 480V AC, 50/60Hz [kA] 25 35 25 35 65 100 600Y/347V AC, 50/60Hz [kA] 10 10 — — — — 600V AC, 50/60 Hz [kA] — — 14 18 25 35 IEC 60947-2 Rated ultimate short-circuit breaking capacity, Icu 220/230/240V AC, 50/60Hz [kA] 50 85 65 85 100 150 380V AC, 50/60Hz [kA] 36 50 36 50 70 120 415V AC, 50/60Hz [kA] 36 50 36 50 70 120 440V AC, 50/60Hz [kA] 25 40 36 50 65 100 500V AC, 50/60Hz [kA] 20 30 30 36 50 60 525V AC, 50/60Hz [kA] 13 20 20 25 45 50 690V AC, 50/60Hz [kA] 5 6 10 12 15 20 250V DC, 2 Poles in Series [kA] 36 50 36 50 70 85 500V DC, 2 Poles in Series [kA] — — 36 50 70 85 500V DC, 3 Poles in Series [kA] 36 50 36 50 70 85 750V DC, 3 Poles in Series [kA] — — — — — — Rated service short-circuit breaking capacity, Ics 220/230/240V AC, 50/60Hz [kA] 75% 50% 100% 100% 100% 100% 380V AC, 50/60Hz [kA] 75% 50% (27) 100% 100% 100% 100% 415V AC, 50/60Hz [kA] 75% 50% (27) 100% 100% 100% 100% 440V AC, 50/60Hz [kA] 75% 50% 100% 100% 100% 100% 500V AC, 50/60Hz [kA] 75% 50% 100% 100% 100% 100% 525V AC, 50/60Hz [kA] 75% 50% 100% 100% 100% 100% 690V AC, 50/60Hz [kA] 50% 50% 100% 100% 100% 100% 250V DC, 2 Poles in Series [kA] 100% 75% 100% 100% 100% 100% 500V DC, 2 Poles in Series [kA] — — 100% 100% 100% 100% 500V DC, 3 Poles in Series [kA] 100% 75% 100% 100% 100% 100% 750V DC, 3 Poles in Series [kA] — — — — — — Mechanical Life Electrical Life @ 415V AC [No. Ops] 25 000 25 000 [Ops/hr] 240 240 [No. Ops] 8000 8000 [Ops/hr] 120 120 Ambient Temp. w/out derating ºF [ºC] 104 ºF [40 ºC] 104 ºF [40 ºC] Storage Temperature ºF [ºC] -40...+176 ºF [-40…+80 ºC] -40...+176 ºF [-40…+80 ºC] Dimensions [Width/Depth/Height] [mm] 3 poles: 105x70x150 3 poles: 105x82.5x160 [mm] 4 poles: 140x70x150 4 poles: 140x82.5x160 ‡ Cannot be reverse fed above 600V Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 65 Bulletin 140G Molded Case Circuit Breakers Specifications — K- and M-Frame K-Frame M-Frame Max. Rated Current [A] 400 800 Rated insulation voltage, Ui, IEC [V] 1000 1000 NEMA, UL, CSA Interrupting Rating Code 240V AC, 50/60Hz K3 K6 K0 K15 K5 K6 K0 [kA] 100 150 200 200 100 200 200 480V AC, 50/60Hz [kA] 35 65 100 150 50 65 100 600Y/347V AC, 50/60Hz [kA] — — — — — — — 600V AC, 50/60 Hz [kA] 25 35 65 100 25 35 42 IEC 60947-2 Rated ultimate short-circuit breaking capacity, Icu 220/230/240V AC, 50/60Hz [kA] 85 100 200 200 85 100 200 380V AC, 50/60Hz [kA] 50 70 120 200 50 70 100 415V AC, 50/60Hz [kA] 50 70 120 200 50 70 100 440V AC, 50/60Hz [kA] 40 65 100 180 45 50 80 500V AC, 50/60Hz [kA] 30 50 85 150 35 50 65 525V AC, 50/60Hz [kA] — — — — — — — 690V AC, 50/60Hz [kA] 25 40 70 80 22 25 30 250V DC, 2 Poles in Series [kA] — — — — — — — 500V DC, 2 Poles in Series [kA] 36 50 70 100 — — — 500V DC, 3 Poles in Series [kA] — — — — — — — 750V DC, 3 Poles in Series [kA] 25 36 70 70 20 36 50 Rated service short-circuit breaking capacity, Ics 220/230/240V AC, 50/60Hz [kA] 100% 100% 100% 100% 100% 100% 75% 380V AC, 50/60Hz [kA] 100% 100% 100% 100% 100% 100% 75% 415V AC, 50/60Hz [kA] 100% 100% 100% 100% 100% 100% 75% 440V AC, 50/60Hz [kA] 100% 100% 100% 100% 100% 100% 75% 500V AC, 50/60Hz [kA] 100% 100% 100% 100% 100% 100% 75% 525V AC, 50/60Hz [kA] — — — — — — — 690V AC, 50/60Hz [kA] 100% 100% 100% 100% 75% 75% 75% 250V DC, 2 Poles in Series [kA] — — — — — — — 500V DC, 2 Poles in Series [kA] 100% 100% 100% 100% — — — 500V DC, 3 Poles in Series [kA] — — — — — — — [kA] 100% 100% 100% 100% 75% 75% 75% 750V DC, 3 Poles in Series Mechanical Life [No. Ops] [Ops/hr] Electrical Life @ 415V AC [No. Ops] [Ops/hr] 20000 20000 120 120 7000 (400 A) - 5000 (630 A) 7000 (630 A) - 5000 (800 A) - 4000 (1000 A) 60 60 Ambient Temp. w/out derating ºF [ºC] 104 ºF [40 ºC] 104 ºF [40 ºC] Storage Temperature ºF [ºC] -40...+176 ºF [-40…+80 ºC] -40...+176 ºF [-40…+80 ºC] Dimensions [Width/Depth/Height] [mm] 3 poles: 140x108.5x205 3 poles: 210x103.5x268 [mm] 4 poles: 185x103.5x205 4 poles: 280x103.5x268 Visit our website: www.ab.com/catalogs 66 Publication 140G-SG001C-EN-P Bulletin 140G Molded Case Circuit Breakers Specifications — N-, NS-, and R-Frame N-, NS-Frame R-Frame Max. Rated Current [A] 1200 2000/2500/3000 Rated insulation voltage, Ui, IEC [V] 1000 1000 NEMA, UL, CSA Interrupting Rating Code N5 N6 N0 240V AC, 50/60Hz [kA] 65 100 150 R12 125 480V AC, 50/60Hz [kA] 50 65 100 125 600Y/347V AC, 50/60Hz [kA] — — — — 600V AC, 50/60 Hz [kA] 25 50 65 100 IEC 60947-2 Rated ultimate short-circuit breaking capacity, Icu 220/230/240V AC, 50/60Hz [kA] 85 100 200 130 380V AC, 50/60Hz [kA] 50 70 120 80 415V AC, 50/60Hz [kA] 50 70 120 80 440V AC, 50/60Hz [kA] 50 65 100 80 500V AC, 50/60Hz [kA] 40 50 85 40 525V AC, 50/60Hz [kA] — — — — 690V AC, 50/60Hz [kA] 30 42 50 40 250V DC, 2 Poles in Series [kA] — — — — 500V DC, 2 Poles in Series [kA] — — — — 500V DC, 3 Poles in Series [kA] — — — — 750V DC, 3 Poles in Series [kA] — — — — 100% Rated service short-circuit breaking capacity, Ics 220/230/240V AC, 50/60Hz [kA] 100% 100% 100% 380V AC, 50/60Hz [kA] 100% 100% 100% 415V AC, 50/60Hz [kA] 100% 100% 100% 100% 440V AC, 50/60Hz [kA] 100% 100% 100% 100% 500V AC, 50/60Hz [kA] 100% 100% 75% 100% 525V AC, 50/60Hz [kA] — — — — 690V AC, 50/60Hz [kA] 100% 75% 75% 100% 250V DC, 2 Poles in Series [kA] — — — — 500V DC, 2 Poles in Series [kA] — — — — 500V DC, 3 Poles in Series [kA] — — — — 750V DC, 3 Poles in Series [kA] — — — — Mechanical Life [No. Ops] [Ops/hr] Electrical Life @ 415V AC [No. Ops] [Ops/hr] 10000 15000 60 60 2000 4500 (2000 A) - 4000 (2500 A) - 3000 (3200 A) 60 60 104 ºF [40 ºC] 104 ºF [40 ºC] Ambient Temp. w/out derating ºF [ºC] Storage Temperature ºF [ºC] -40...+176 ºF [-40…+80 ºC] -40...+176 ºF [-40…+80 ºC] Dimensions [Width/Depth/Height] [mm] 3 poles: 210x154(N)/178(NS)x268 3 poles: 427x282x382 [mm] 4 poles: 280x154(N)/178(NS)x268 4 poles: 553x282x382 Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 67 Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 125 A, G-Frame Dimensions are in millimeters. Dimensions are not intended to be used for manufacturing purposes. Panel Mounted Molded Case Circuit Breaker ‡ Overall dimensions of optional wiring ducts § Required 25 mm insulating phase barriers provided DIN Rail Mounted Molded Case Circuit Breaker Mounting bracket ‡ Overall dimensions of optional wiring ducts § Required 25 mm insulating phase barriers provided ♣ Optional front cover for DIN Rail Visit our website: www.ab.com/catalogs 68 Publication 140G-SG001C-EN-P Description No. of Poles A With flange 3…4 74 Without flange 3…4 71 3…4 79 Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 125 A, G-Frame Drilling Template for Molded Case Circuit Breaker Mounting 3 Poles 4 Poles Cat. Nos. 140G-G-ECM, -ECM4 Terminals Mounting bracket ♠ Required 25 mm insulating phase barriers provided Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 69 Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 125 A, G-Frame Cat. Nos. 140G-G-EXT3, -EXT4 Extended Terminals ‡ Extended terminals § Optional Terminal covers with IP40 protection provided Δ Required 100 mm insulating phase barriers provided ∇ Internal insulating plate required with phase barriers (customer provided) when mounted through the enclosure door Cat. Nos. 140G-G-EXS3, -EXS4 Spreader Terminals ♣ Extended spread terminals for busbar connection ♦ Required 200 mm insulating phase barriers provided Visit our website: www.ab.com/catalogs 70 Publication 140G-SG001C-EN-P Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 125 A, G-Frame Cat. Nos. 140G-G-TLC13, 140G-G-TLC14 Terminals (Copper Only Lug) ‡ Front terminals Cat. No. 140G-G-MTL63, -MTL64 Terminal (Multi-Cable Terminal Lug) ♣ Required terminal covers with IP40 protection provided Δ Terminal lugs for multi-cable connection Cat. No. 140G-G-RMB or 140G-G-RMY Direct Rotary Operating Handle Drilling: See Detail “A” Min. door rotation radius ‡ Rotary handle operating mechanism on molded case circuit breaker ♣ Door drilling template with direct rotary handle ♦ Required 25 mm insulating phase barriers provided Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 71 Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 125 A, G-Frame Cat. Nos. 140G-G-RVM…Variable Depth Rotary Mechanism with Door Mounted Handle 2.68 [68.0] 6.37 [161.8] 12 in. shaft: 11.38 [289] 21 in. shaft: 20.38 [517.8] 0.08 [2.0] 0.41 [10.5] 1.54 [39.0] 1.54 [39.0] 5.12 [130.0] 0.57 [14.5] 5.12 [130.0] 0.57 [14.5] 3.98 [101.2] 3.00 [76.2] 3-Pole Front of Cover 0.07 [1.8] 1.41 [35.8] 4-Pole 50 (1.97) ø 35 (ø 1.37) 25 (0.98) 25 (0.98) 25 (0.98) ø 35 (ø 1.37) 31.5 (1.23) (2) - ø 5.5 (2) - ø 0.22) (2) - ø 5.5 (2) - ø 0.22) Visit our website: www.ab.com/catalogs 72 63 (2.47) 50 (1.97) mm (in.) Publication 140G-SG001C-EN-P Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 125 A, G-Frame Cat. No. 140G-G-EOP… Motor Operator ♣ Motor operator Δ Door drilling template (without flange) ♦ Door drilling template (with flange) ♠ Cable connection ∇ Required 25 mm insulating phase barriers provided Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 73 Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 125 A, G-Frame Cat. No. 140G-G-ELP1603 Residual Current Release Module for 3-Pole Molded Case Circuit Breakers Description No. of Poles A With flange 3 74 Without flange 3 71 Terminals for busbar connection ‡ IP40 terminal covers § Drilling template — door with direct rotary mechanism and flange ♣ Drilling template — door with direct rotary mechanism, without flange Δ Drilling template — molded case circuit breaker mounting on mounting plate Visit our website: www.ab.com/catalogs 74 Publication 140G-SG001C-EN-P Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 125 A, G-Frame Cat. No. 140G-G-ELP1604 Residual Current Release Module for 4-Pole Molded Case Circuit Breakers Description No. of Poles A With flange 4 74 Without flange 4 71 Terminals for busbar connection ‡ IP40 terminal covers § Drilling template — door with direct rotary mechanism and flange ♣ Drilling template — door with direct rotary mechanism, without flange Δ Drilling template — molded case circuit breaker mounting on mounting plate Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 75 Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 125 A, H-Frame Dimensions are in millimeters. Dimensions are not intended to be used for manufacturing purposes. Panel Mounted Molded Case Circuit Breaker Description No. of Poles A With flange 3…4 86 3…4 83.5 3…4 91.5 Without flange ‡ Overall dimensions of optional wiring ducts § Required 25 mm insulating phase barriers provided DIN Rail Mounted Molded Case Circuit Breaker Mounting bracket § Required 25 mm insulating phase barriers provided Visit our website: www.ab.com/catalogs 76 Publication 140G-SG001C-EN-P Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 125 A, H-Frame Drilling Template for Molded Case Circuit Breaker Mounting 3 Poles 4 Poles Cat. Nos. 140G-H-ECM, -ECM4 Terminals Required 25 mm insulating phase barriers provided ‡ Front terminals for busbar connection Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 77 Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 125 A, H-Frame Cat. Nos. 140G-H-EXT3, -EXT4 Extended Terminals 3 Poles 4 Poles § Extended terminals ♣ Optional terminal covers with IP40 protection provided Δ Required 100 mm insulating phase barriers provided ♦ Required internal insulating plate provided for breakers with Ue>440V ♠ Drilling template for 3-pole molded case circuit breaker, Ue>440V (required) ∇ Drilling template for 4-pole molded case circuit breaker, Ue>440V (required) Visit our website: www.ab.com/catalogs 78 Publication 140G-SG001C-EN-P Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 125 A, H-Frame Cat. Nos. 140G-H-EXS3, -EXS4 Spreader Terminals 4 Poles 3 Poles Drilling template for 3-pole molded case circuit breaker, Ue>440V (required) ‡ Drilling template for 4-pole molded case circuit breaker, Ue>440V (required) § Extended spread terminals ♣ Required 200 mm insulating phase barriers provided Δ Required insulated plate provided for breakers, with Ue>440V Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 79 Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 125 A, H-Frame Cat. Nos. 140G-H-TLC13, -TLC14 Terminals § Required 25 mm insulating phase barriers provided ♦ Copper terminals. Cat. Nos. 140G-H-MTL63, -MTL64 Terminals ♦ Multi-cable terminals Cat. No. 140G-H-RMB, -RMY Direct Rotary Operating Handle ‡ Rotary handle operating mechanism on molded case circuit breaker ♦ Required 25 mm insulating phase barriers provided Visit our website: www.ab.com/catalogs 80 Publication 140G-SG001C-EN-P Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 125 A, H-Frame Cat. No. 140G-H-RVM… Rotary Handle Operating Mechanism — Door Mounted 3.17 [80.5] 12 in. shaft: 10.89 [276.5] 21 in. shaft: 19.89 [505.1] 6.86 [174.3] 1.44 [36.5] 0.08 [2.0] 1.57 [40.0] 1.28 [32.5] 1.28 [32.5] 5.12 [130.0] 5.12 [130.0] 0.89 [22.5] 0.89 [22.5] 4.88 [124.0] 3.54 [90.0] 3-Pole Front of Cover 4-Pole 50 (1.97) ø 35 (ø 1.37) 25 (0.98) 25 (0.98) 25 (0.98) ø 35 (ø 1.37) 31.5 (1.23) 63 (2.47) 50 (1.97) mm (in.) (2) - ø 5.5 (2) - ø 0.22) (2) - ø 5.5 (2) - ø 0.22) Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 81 Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 125 A, H-Frame Cat. No. 140G-H-EOP… Motor Operator 3 Poles 4 Poles Motor operator Δ Drilling template for 3-pole molded case circuit breaker, mounted on mounting plate ♦ Drilling template for 4-pole molded case circuit breaker, mounted on mounting plate ♠ Required 25 mm insulating phase barriers provided Visit our website: www.ab.com/catalogs 82 Publication 140G-SG001C-EN-P Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 125 A, H-Frame Cat. No. 140G-H-ELP1604 Residual Current Release Module 4 Poles Description No. of Poles A With flange 4 86 Without flange 4 83.5 Residual current module ‡ Front terminals ♠ Drilling template — door with direct rotary mechanism and flange ∇ Drilling template — door with direct rotary mechanism, without flange & Drilling template — molded case circuit breaker mounting on mounting plate Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 83 Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 225 A, I-Frame Dimensions are in millimeters. Dimensions are not intended to be used for manufacturing purposes. Panel Mounted Molded Case Circuit Breaker ‡ Overall dimensions of optional wiring ducts § Required 25 mm insulating phases barriers provided DIN Rail Mounted Molded Case Circuit Breaker Mounting bracket ‡ Optional wiring ducts § Optional front cover for DIN Rail ♣ Required 25 mm insulating phase barriers provided Visit our website: www.ab.com/catalogs 84 Publication 140G-SG001C-EN-P No. of Poles A 3…4 74 3…4 71 3…4 79 Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 225 A, I-Frame Drilling Template for Molded Case Circuit Breaker Mounting 3 Poles 4 Poles Cat. Nos. 140G-I-ECM, -ECM4 Terminals Front terminals for busbar connection ‡ Required 25 mm insulating phase barriers provided Cat. Nos. 140G-J-EXS3, -EXS4 Terminals ♣ Extended spread terminals ♦ Required 200 mm insulating phase barriers provided Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 85 Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 225 A, I-Frame Cat. Nos. 140G-I-EXT3, -EXT4 Extended Terminals ‡ Extended terminals § Optional terminal covers with IP40 protection provided Δ Required 100 mm insulating phase barriers provided Cat. Nos. 140G-I-TLA1A3, -TLA1A4 Terminals 30…150 mm2 terminals ‡ Required 25 mm insulating phase barriers provided Cat. Nos. 140G-I-TLA3, -TLA4 Terminals 1x90…185 mm2 terminal § Required 25 mm insulating phase barriers provided Visit our website: www.ab.com/catalogs 86 Publication 140G-SG001C-EN-P Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 225 A, I-Frame Cat. Nos. 140G-I-TLC13, -TLC14 Terminals ♦ Front terminals & Required 25 mm insulating phase barriers provided Cat. Nos. 140G-I-MTL63, -MTL64 Terminals § Optional terminal covers with IP40 protection provided Δ Multi-cable terminal lugs Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 87 Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 225 A, I-Frame Cat. No. 140G-G-RMB, -RMY Direct Rotary Operating Handle (For I- and G-Frame Molded Case Circuit Breaker) Drilling: See Detail “A” Min. door rotation radius ‡ Rotary handle operating mechanism on molded case circuit breaker ♣ Door drilling template with direct rotary handle ♦ Required 25 mm insulating phase barriers provided Cat. No. 140G-G-EOP… Motor Operator (I-Frame) ♣ Motor operator ♠ Required 25 mm insulating phase barriers provided Visit our website: www.ab.com/catalogs 88 Publication 140G-SG001C-EN-P Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 225 A, I-Frame Cat. No. 140G-G-RVM… Variable Depth Rotary Handle Operating Mechanism (For I-Frame Molded Case Circuit Breaker) 12 in. shaft: 11.38 [289] 21 in. shaft: 20.38 [517.8] 6.37 [161,8] 0.08 [2,0] 0.08 [2,0] 0.61 [15,5] 0.61 [15,5] 2.20 [55,9] 2.20 [55,9] 5.91 [150,0] 0.61 [15,6] Front of Cover 5.91 [150,0] 0.20 [5,1] 4.13 [105,0] 5.51 [140,0] 3-Pole 4-Pole 50 (1.97) ø 35 (ø 1.37) 25 (0.98) 25 (0.98) 25 (0.98) ø 35 (ø 1.37) 31.5 (1.23) 63 (2.47) 50 (1.97) mm (in.) (2) - ø 5.5 (2) - ø 0.22) (2) - ø 5.5 (2) - ø 0.22) Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 89 Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 225 A, I-Frame Cat. No. 140G-I-ELP2503 Residual Current Release Module Description No. of Poles A With flange 3 74 Without flange 3 71 Terminals for cable connection ‡ Terminal covers with IP40 protection Δ Drilling template — molded case circuit breaker mounting on mounting plate Visit our website: www.ab.com/catalogs 90 Publication 140G-SG001C-EN-P Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 225 A, I-Frame Cat. No. 140G-I-ELP2504 Residual Current Release Module for 4-Pole Molded Case Circuit Breakers Description No. of Poles A With flange 4 74 Without flange 4 71 Terminals for busbar connection ‡ Terminal covers with IP40 protection Δ Drilling template — molded case circuit breaker mounting on mounting plate Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 91 Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 250 A, J-Frame Dimensions are in millimeters. Dimensions are not intended to be used for manufacturing purposes. Panel Mounted Molded Case Circuit Breaker ‡ Overall dimensions of optional wiring ducts. § Required 25 mm insulating phase barriers provided. Description No. of Poles A With flange 3…4 86 Without flange 3…4 83.5 3…4 91.5 DIN Rail Mounted Molded Case Circuit Breaker Mounting bracket § Required 25 mm insulating phase barriers provided Visit our website: www.ab.com/catalogs 92 Publication 140G-SG001C-EN-P Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 250 A, J-Frame Drilling Template for Molded Case Circuit Breaker Mounting 3 Poles 4 Poles Cat. Nos. 140G-J-ECM, -ECM4 Terminals Required 25 mm insulating phase barriers provided ‡ Terminals for busbar connection Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 93 Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 250 A, J-Frame Cat. Nos. 140G-J-EXT3, -EXT4 Extended Terminals 3 Poles 4 Poles § Extended terminals ♣ Optional terminal covers with IP40 protection provided Δ Required 100 mm insulating phase barriers provided ♦ Required insulating plate provided for molded case circuit breaker with Ue>440V ♠ Drilling template for 3-pole molded case circuit breaker ∇ Drilling template for 4-pole molded case circuit breaker Visit our website: www.ab.com/catalogs 94 Publication 140G-SG001C-EN-P Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 250 A, J-Frame Cat. Nos. 140G-J-EXS3, -EXS4 Spreader Terminals 3 Poles 4 Poles Drilling template for 3-pole molded case circuit breaker ‡ Drilling template for 4-pole molded case circuit breaker § Extended spread terminals ♣ Required 200 mm insulating phase barriers provided Δ Required insulated plate provided for molded case circuit breaker with Ue>440V Cat. Nos. 140G-J-TLA13, -TLA14 Terminal Lugs Aluminum Conductor: 6…350 MCM (2.5…185 mm) Copper Conductor: 10…350 MCM (6…185 mm) 1x1…185 mm2 front terminal § Required 25 mm insulating phase barriers provided Cat. Nos. 140G-J-TLC13, -TLC14 Terminal Lugs 10…350 MCM (6…185 mm) External terminals ♣ Required 25 mm insulating phase barriers provided Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 95 Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 250 A, J-Frame Cat. Nos. 140G-J-MTL63, -MTL64 Terminals ‡ Multi-cable terminal lugs § Optional terminal covers with IP40 protection provided ‡ Rotary handle operating mechanism on molded case circuit breaker ♦ Required 25 mm insulating phase barriers provided Min. Door Rotation Radius Flange Mount Drill Template Visit our website: www.ab.com/catalogs 96 Publication 140G-SG001C-EN-P Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 250 A, J-Frame Cat. No. 140G-H-RVM… Variable Depth Rotary Handle Operating Mechanism (For J-Frame Molded Case Circuit Breaker) 3.2 [83] 12 in. shaft: 10.89 [276.5] 21 in. shaft: 19.89 [505.1] 6.86 [174.3] 0.08 [2.0] 0.61 [15.5] 1.99 [50.5] 1.85 [47.0] 1.85 [47.0] 6.30 [160.0] 0.89 [22.5] 6.30 [160.0] 0.89 [22.5] 4.13 [105.0] Front of Cover 5.51 [140.0] 3-Pole 50 4-Pole (1.97) ø 35 (ø 1.37) 25 (0.98) 25 (0.98) 25 (0.98) ø 35 (ø 1.37) 31.5 (1.23) 63 (2.47) 50 (1.97) mm (in.) (2) - ø 5.5 (2) - ø 0.22) (2) - ø 5.5 (2) - ø 0.22) Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 97 Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 250 A, J-Frame Cat. No. 140G-H-EOP… Motor Operator – For H- & J-Frame Molded Case Circuit Breaker 3 Poles 4 Poles Motor operator § Drilling template for door with motor operator with flange ♣ Drilling template for door with motor operator without flange Δ Drilling template for 3-pole molded case circuit breaker, mounted on mounting plate ♦ Drilling template for 4-pole molded case circuit breaker, mounted on mounting plate ♠ Required 25 mm insulating phase barriers provided Visit our website: www.ab.com/catalogs 98 Publication 140G-SG001C-EN-P Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 250 A, J-Frame Cat. No. 140G-J-EP2504 Residual Current Release Module for 4-Pole Molded Case Circuit Breakers Description No. of Poles A With flange 4 86 Without flange 4 83.5 Residual current module ‡ Front terminals ♠ Drilling template — door with direct rotary mechanism and flange ∇ Drilling template — door with direct rotary mechanism, without flange & Drilling template — molded case circuit breaker mounting on mounting plate Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 99 Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 400 A, K-Frame Dimensions are in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. Panel Mounted Molded Case Circuit Breaker Overall dimensions with cabled accessories mounted ‡ Overall dimensions with cabled auxiliary contacts mounted Drilling Templates for Molded Case Circuit Breaker Mounting Flange for compartment door Drilling template for compartment door with flange (3…4 poles) Drilling template for mounting plate 3 Poles 4 Poles Visit our website: www.ab.com/catalogs 100 Publication 140G-SG001C-EN-P without flange (3…4 poles) Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 400 A, K-Frame Cat. Nos. 140G-K-ECM, -ECM4 Terminals Cat. Nos. 140G-K-TLC13, -TLC14 Terminals 250…500 MCM (120…240 mm2) Cat. Nos. 140G-K-TLA23, -TLA24, -TLC23, -TLC24 Terminals (2) 2/0…250 MCM ((2) 95…120 mm2) Terminal covers with IP40 protection Cat. Nos. 140G-K-TLA13, -TLA14 Terminals 250…500 MCM (120…240 mm2) Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 101 Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 400 A, K-Frame Cat. Nos. 140G-K-EXT3, -EXT4 Extended Terminals Terminal covers with IP40 protection ‡ Required 100 mm insulating phase barriers provided Cat. Nos. 140G-K-EXS3, -EXS4 Spreader Terminals Required 200 mm insulating phase barriers provided Visit our website: www.ab.com/catalogs 102 Publication 140G-SG001C-EN-P Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 400 A, K-Frame Cat. No. 140G-K-RMB, -RMY Rotary Handle Operating Mechanism — Door Mounted Rotary handle operating mechanism on molded case circuit breaker ‡ Padlock device for open position (max. 3 padlocks; user provided) § Dimensions with cabled early make contact ♣ Compartment door lock Cat. No. 140G-K-ELP Residual Current Release Module for 4-Pole Molded Case Circuit Breakers Overall dimensions with cabled auxiliary contacts mounted Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 103 Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 400 A, K-Frame Cat. No. 140G-K-RVM… Variable Depth Rotary Handle Operating Mechanism 4.00 [101.5] 4.80 [122.0] 12 in. shaft: 17.75 [450.8] 21 in. shaft: 26.75 [679.4] 0.01 [0.3] 0.14 [3.5] 0.78 [19.7] 0.92 [23.3] 2.69 [68.3] 2.66 [67.6] 8.07 [205.0] 0.78 [19.7] 8.07 [205.0] 0.80 [20.4] 5.49 [139.5] 7.32 [186.0] 3-Pole 4-Pole 75 (2.95) 37.5 (1.47) mm (in.) 37.5 (1.47) 65 ø (2.56 ø) 75 (2.95) 4 - 5.5 ø (4) - 0.22 ø) Front of Cover Visit our website: www.ab.com/catalogs 104 Publication 140G-SG001C-EN-P Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 800 A, M-Frame Dimensions are in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. Panel Mounted Molded Case Circuit Breaker 210 (3P) 8.27 115 4.53 103.5 4.07 140 = 5.51 = 61.25 2.41 2.7 0.11 70 2.76 5.5 0.22 2.7 0.11 105 4.13 268 10.55 134 5.28 70 2.76 105 4.13 70 2.76 3 0.12 280 (4P) 11.02 107 4.21 159 6.26 2 0.08 Overall dimensions with cabled accessories mounted ‡ Overall dimensions with cabled auxiliary contacts mounted Drilling Templates for Molded Case Circuit Breaker Mounting 142 = 5.59 = 107 4.21 66.75 2.63 149 = 5.87 = 116 4.57 138 5.43 77.75 3.06 152 = 5.98 = 62.25 2.45 Drilling template for compartment door Flange for compartment door with flange without flange Drilling template for mounting plate 70 2.76 5.5 - M5 Ø 0.22 35 1.38 118.5 4.67 140 5.51 237 9.33 237 9.33 118.5 4.67 5.5 - M5 Ø 0.22 3 Poles 4 Poles Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 105 Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 800 A, M-Frame Cat. No. 140G-M-ECM Terminals Cat. No. 140G-M-TLA23, -TLA24, -TLC23, -TLC24 Terminals 70 2.76 MA X 40 50 1.97 20 0.79 59 2.32 25.5 1 19 Ø 0.75 45 1.77 33.5 1.32 90 3.54 45 1.77 8 0.31 116 4.57 116 4.57 116 4.57 88 3.46 45 1.77 88 3.46 45 1.77 13 Ø 0.51 116 4.57 116 4.57 88 3.46 23 0.9 45 1.77 90 3.54 13 Ø 0.51 50 1.97 8 0.31 230.5 9.07 134 5.28 134 5.28 167.5 6.59 134 5.28 45 1.77 90 3.54 88 3.46 23 0.9 116.5 4.59 53.5 2.11 14 0.55 120.5 4.74 Cat. Nos. 140G-M-EXSLI3, -EXSLO3, -EXS4 Spreader Terminals 70 2.76 116.5 4.59 70 2.76 70 2.76 134 5.28 Cat. Nos. 140G-M-EXT3, -EXT4 Extended Terminals 70 2.76 70 2.76 39 1.53 MIN5 MAX10 120.5 4.74 MAX 12 6.5 Ø 0.26 23 0.9 ±0 .1 18 MIN 22.5 0.89 Cat. No. 140G-M-RMB, -RMY Rotary Handle Operating Mechanism — Door Mounted 33 1.3 140 5.51 5.5 0.22 Ø4 Ø 0.16 190 7.48 146.5 5.77 103.5 4.07 5.5 0.22 42.5 1.67 84.5 3.33 140 5.51 5.5 0.22 2.7 0.11 ≥3 ≥ 0.12 140.5 5.53 ≤2 ≤ 0.08 2.7 0.11 41.5 1.63 Rotary handle operating mechanism on molded case circuit breaker ‡ Padlock device for open position (max. 3 padlocks; user provided) § Dimension with cabled early make contact ♣ Compartment door lock Drilling template for compartment door 43 1.69 14 0.55 43 1.69 14 0.55 148.5 5.85 R min. 200 R min. 7.87 with flange Visit our website: www.ab.com/catalogs 106 Publication 140G-SG001C-EN-P 96.5 3.8 142 5.59 85.5 3.37 5 5.94 90 3.54 100.25 3.95 173 6.81 152 5.98 96.5 38 Flange for compartment door 142 5.59 R min. 200 R min. 7.87 without flange Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 800 A, M-Frame Cat. No. 140G-M-RVM… Variable Depth Rotary Handle Operating Mechanism 3.80 [96.5] 8.74 [221.9] 12 in. shaft: 17.75 [450.8] 21 in. shaft: 26.75 [679.4] 0.24 [6.1] 1.38 [35.0] 2.99 [75.9] 10.55 [268.0] 1.68 [42.6] 8.23 [209.0] 3-Pole 75 (2.95) 37.5 (1.47) mm (in.) 37.5 (1.47) 65 ø (2.56 ø) 75 (2.95) 4 - 5.5 ø (4) - 0.22 ø) Front of Cover Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 107 Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 800 A, M-Frame Cat. No. 140G-M-EOP, -ECOP Motor Operator 1.1 Nm 140 = 5.51 = 5.5 5.5 0.22 0.22 140 5.51 70 2.76 191.5 7.54 5.5 0.22 Overall dimension with cabled accessories mounted ‡ Overall dimension with cabled auxiliary contacts mounted 3 0.12 222 8.74 233 9.17 Drilling template for compartment door Flange for compartment door 152 = 5.98 = Drilling template for mounting plate 118.5 4.66 Ø 5.5 - M5 Ø 0.22 - M5 237 9.33 237 9.33 118.5 4.66 70 2.76 140 5.51 35 1.38 Visit our website: www.ab.com/catalogs 108 142 = 5.59 = 142 5.59 71.25 2.8 151 5.94 75.75 2.98 173 6.81 86.5 3.4 148.5 = 5.85 = R min. 200 R min. 7.87 with flange Ø 5.5 - M5 Ø 0.22 - M5 2 0.08 Publication 140G-SG001C-EN-P R min. 200 R min. 7.87 without flange Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 1200 A, N-Frame Dimensions are in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. Panel Mounted Molded Case Circuit Breaker 103.6 4.08 70 2.76 18.75 0.74 14.5 0.58 105 4.13 204 8.03 268 10.55 102 4.02 70 2.76 10 0.39 10 0.39 24 0.94 6 0.24 134 5.28 147.5 5.81 70 2.76 50 1.97 25 0.98 125 4.92 97 3.82 10 0.39 2 0.08 154.25 6.07 152 5.98 225 8.86 125 4.92 160 6.3 280 11.02 3 0.12 210 8.27 Description A With flange 125…141 Without flange 147 190 7.48 206 8.11 Front terminals for flat connection ‡ Busbars § Door flange Δ Tightening torque: 18 N•m ♠ Padlock (optional) ∇ Tightening torque: 2.5 N•m & Terminal for auxiliary contacts Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 109 Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 1200 A, N-Frame Drilling Templates for Molded Case Circuit Breaker Mounting Flange for compartment door Drilling template for compartment door 268 10.55 192 7.56 with reduced flange 206 8.11 103 4.05 144.5 5.69 208 8.19 144.5 5.69 151 5.94 263 10.35 35.25 1.39 138 5.43 Front 190 x 105 241 9.49 226 8.9 203 7.99 19.75 0.78 107 4.21 24.25 0.95 116 4.57 304 11.97 152 5.98 201 7.91 2 0.08 155 6.1 § Door flange # Reduced flange for compartment door Ø 4 n°7 HOLES Ø 0.16 with flange 122.5 4.82 Drilling template for mounting plate 245 9.65 35 1.38 Ø 5.5 - M5 Ø 0.22 No. of Poles C 3 70 4 140 Visit our website: www.ab.com/catalogs 110 Publication 140G-SG001C-EN-P Front 206 x 204 Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 1200 A, N-Frame Cat. No. 140G-N-RVM… Variable Depth Rotary Handle Operating Mechanism 3.82 [97.0] 10.75 [273.0] 12 in. shaft: 17.75 [450.8] 21 in. shaft: 26.75 [679.4] 0.93 [23.6] 1.73 [44.0] 1.38 [35.0] 4.82 [122.5] 2.41 [61.1] 4.83 [122.6] 10.55 [268.0] 10.55 [268.0] 0.83 [21.0] 0.83 [221.1] 8.27 [210.0] 11.02 [280.0] 3-Pole 4-Pole 75 (2.95) 37.5 (1.47) mm (in.) 37.5 (1.47) 65 ø (2.56 ø) 75 (2.95) 4 - 5.5 ø (4) - 0.22 ø) Front of Cover Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 111 Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 1200 A, N-Frame Cat. Nos. 140G-N-TLH3, -TLV3, TLH4, TLV4 Terminals 109 4.29 218 8.58 237 9.34 273 10.75 118.5 4.66 44 1.73 59 2.32 70 2.76 70 2.76 44 1.73 25 0.98 1 Ø1 3 .4 Ø0 46.5 1.84 59 2.32 46.5 1.84 70 2.76 Ø Ø 11 0.4 3 25 0.98 15 0.59 18.5 0.73 15 0.59 70 2.76 No. of Poles B C 3 70 192.5 4 140 262.5 70 2.76 70 2.76 Rear horizontal terminals ‡ Rear vertical terminals ♠ Tightening torque: 20 N•m Drilling template for mounting plate 35 1.38 52.5 2.07 122.5 4.82 245 9.65 8 0.31 39.75 1.56 61.25 2.41 17.5 0.69 Ø 5.5 - M5 Ø 0.22 Visit our website: www.ab.com/catalogs 112 Publication 140G-SG001C-EN-P Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 1200 A, N-Frame Cat. No. 140G-N-EXT3, -EXT4 Extended Front Terminals 320 12.6 25 0.98 70 2.76 Y 125 70 4.92 2.76 44 1.73 100 3.94 29.5 29.5 15 0.59 1 Ø 11 Ø 0.43 79 3.11 118.5 4.66 250 9.84 12.5 0.49 160.5 6.32 199.5 7.85 229 9.02 25 0.98 70 2.76 250 9.84 X X X X Extended terminals ∇ Required 100 mm insulating phase barriers provided ♠ Tightening torque: 18 N•m & Required insulating plate provided for molded case circuit breaker Cat. Nos. 140G-N-EXSL13 Top (3-Pole), 140G-N-EXS4 (4-Pole) Rear Spread Terminals 116 / 4.57 116 90 / 3.54 90 / 3.54 / 4.57 Ø Ø 0 13 .51 100 116 / 4.57 40.5 90 / 3.54 45 1.77 45 1.77 79 3.11 15 55 2.17 100 3.94 118.5 258 10.16 334 33 1.3 268 10.55 134 5.28 79 3.11 100 3.94 23 0.91 144 5.67 189 7.44 45 1.77 45 1.77 147.5 5.81 ~200 ~10.16 23 X X ‡ Extended spread terminals # Required 200 mm insulating phase barriers provided ♠ Tightening torque: 18 N•m § Terminal for auxiliary contacts & Required insulating plate provided for molded case circuit breaker Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 113 Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 1200 A, N-Frame Cat. No. 140G-N-RMB, -RMY Rotary Handle Operating Mechanism 280 11.02 210 8.27 70 70 70 70 6 0.24 97 3.82 134 5.28 147.5 5.81 33 1.30 18.75 0.74 268 10.55 204 8.03 43.5 1.71 2 0.08 2 0.08 Description A With flange 125…141 Without flange 147 154 6.06 190 7.48 206 8.11 Rotary handle operating mechanism on molded case circuit breaker ‡ Compartment door interlock § Door flange ♦ Tightening torque: 2.5 N•m ♠ Terminal for auxiliary contacts ∇ Reduced flange of rotary handle for door (optional) Visit our website: www.ab.com/catalogs 114 2 0.08 152 5.98 189.5 7.46 184 7.24 Publication 140G-SG001C-EN-P 105 4.13 70 70 125 4.92 102 4.01 103.6 4.08 Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 1200 A, N-Frame Cat. No. 140G-N-TLA43, -TLA44, -TLC43, -TLC44 Terminals 320 12.6 70 2.76 250 9.84 70 2.76 70 2.76 34.75 0.52 1 0.04 28 1.1 66.25 2.61 79 3.11 202 7.95 150 5.9 Y 101 3.98 125 4.92 X X X Y Y X Ø 21.5 Ø 0.85 Terminal lugs for cables ‡ Tightening torque: 43 N•m ♠ Tightening torque: 18 N•m ∇ Required insulating plate provided for molded case circuit breaker Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 115 Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 1200 A, NS-Frame Dimensions are in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. Panel Mounted Molded Case Circuit Breaker 125 4.92 97 3.82 50 1.97 24 0.94 10 0.39 10 0.39 ≥3 ≥ 0.12 210 8.27 193.5 7.62 2 0.079 175 6.89 178 7.01 125 4.92 280 11.02 204 8.03 268 10.55 237 9.34 102 4.02 70 2.76 10 0.39 12 14.5 0.58 70 2.76 6 0.24 118.5 4.66 103.6 4.08 134 5.28 147.5 5.81 70 2.76 25 0.98 190 7.48 206 8.11 Description A With flange 125…184 (4.92…7.24) Without flange 170 (6.7) Description Standard B 208 (8.19) No. of Poles C 3 70 (2.76) 4 140 (5.51) Front terminals for busbar connection ‡ Busbars § Door flange Δ Drilling template for fixing onto mounting plate ♦ Tightening torque: 18 N•m ♠ Key lock (optional) ∇ Padlock (optional) & Tightening torque: 2.5 N•m # Compartment door with flange sheet drilling 11Compartment door without flange sheet drilling 12Terminal for auxiliary contacts Drilling Templates for Molded Case Circuit Breaker Mounting 208 8.19 268 10.55 Ø 5.5 - M5 Ø 0.22 Drilling template for compartment door Flange for compartment door Visit our website: www.ab.com/catalogs 116 35 1.38 245 9.65 304 11.97 206 8.11 103 4.05 263 10.35 151 5.94 144.5 5.69 144.5 5.69 152 5.98 11 122.5 4.82 Ø 4 n°7 HOLES Ø 0.16 241 9.49 226 8.9 Publication 140G-SG001C-EN-P Drilling template for mounting plate Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 1200 A, NS-Frame Cat. Nos. 140G-N-TLA63, -TLA64, -TLC63, -TLC64 Terminals 320 12.6 70 2.76 70 2.76 250 9.84 70 2.76 125 4.92 34.75 1.37 1 0.04 79 3.11 202 7.95 150 5.9 28 1.1 101 3.98 66.25 2.61 Ø 21.5 Ø 0.85 Front terminals for cables ‡ Tightening torque: 43 N•m ♠ Tightening torque: 18 N•m ∇ Required insulating plates provided for molded case circuit breaker Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 117 Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 1200 A, NS-Frame Cat. Nos. 140G-N-TLV3, -TLV4, -TLH3, -TLH4 Rear Terminals 59 2.32 X 109 4.29 X X 218 8.58 X 237 9.34 273 10.75 118.5 4.66 44 1.73 Y X 25 0.98 15 0.59 18.5 0.73 Y 70 2.76 44 1.73 70 2.76 25 0.98 46.5 1.84 59 2.32 Rear horizontal terminals ‡ Rear vertical terminals ♠ Tightening torque: 20 N•m 1 Ø1 3 .4 Ø0 46.5 1.84 70 2.76 Ø 11 Ø 0.43 Y 70 2.76 70 2.76 70 2.76 Y 15 0.59 Drilling template for mounting plate C X X 17.5 0.69 Ø 5.5 - M5 Ø 0.22 52.5 2.07 245 9.65 122.5 4.82 8 0.31 Y 39.75 1.56 61.25 2.41 No. of Poles B C 3 70 (2.76) 192.5 (7.58) 4 140 (5.51) 262.5 (10.33) R 10 Y B Visit our website: www.ab.com/catalogs 118 Publication 140G-SG001C-EN-P X Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 1200 A, NS-Frame Cat. No. 140G-N-EXSLI3, -EXSL03, -EXS4 Extended Front Spreader Terminals 320 12.6 250 9.84 116 4.57 90 3.54 45 1.77 116 4.57 116 4.57 90 3.54 45 1.77 90 3.54 23 0.9 90 3.54 45 1.77 45 1.77 100 3.94 40.5 1.59 Ø 13 Ø 0.51 15 0.59 79 3.11 79 3.11 118.5 4.66 229 9.02 258 10.16 79 3.11 278 10.94 334 13.15 33 1.3 Extended spread terminals ‡ Tightening torque: 18 N•m § Required 200 mm insulating phase barriers provided Δ Required insulating plate provided Cat. Nos. 140G-N-EXT3, -EXT4 Extended Front Terminals 320 12.6 25 0.98 70 2.76 125 70 4.92 2.76 44 1.73 100 3.94 29.5 1.16 15 0.59 Ø 11 Ø 0.43 250 9.84 118.5 4.66 79 3.11 12.5 0.49 160.5 6.32 199.5 7.85 229 9.02 25 0.98 70 2.76 250 9.84 ‡ Tightening torque: 18 N•m ♣ Required insulating plate provided Δ Extended terminals ♦ Required 100 mm insulating phase barriers provided ♠ Terminal for auxiliary contacts Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 119 Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 2000…3000 A, R-Frame Dimensions are in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. Panel Mounted Breakers 2500 A Breakers Drilling Templates Mounting Plate (4 Poles) Mounting Plate (3 Poles) Visit our website: www.ab.com/catalogs 120 Publication 140G-SG001C-EN-P Bulletin 140G Molded Case Circuit Breakers Approximate Dimensions — 2000…3000 A, R-Frame 3000 A Breakers Drilling Templates Mounting Plate (4 Poles) Mounting Plate (3 Poles) Compartment Door Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 121 Bulletin 140G Molded Case Circuit Breakers Page Intentionally Left Blank Visit our website: www.ab.com/catalogs 122 Publication 140G-SG001C-EN-P Bulletin 140G Molded Case Circuit Breakers Page Intentionally Left Blank Visit our website: www.ab.com/catalogs Publication 140G-SG001C-EN-P 123 Allen-Bradley, Rockwell Software, Rockwell Automation, and LISTEN. THINK. SOLVE are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies. Publication 140G-SG001C-EN-P - January 2014 Supercedes Publication 140G-SG001B-EN-P - January 2014 Copyright © 2014 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.