AIR CONDITIONER 10000 10,000 BTU/HR. AIR CONDITIONER DANTHERM’s line of Air Conditioners is specifically designed for the removal of heat from cabinets containing temperature-sensitive electrical, electronic, or telecommunications equipment. Closed-loop cooling maintains a clean, sealed internal environment to ensure optimum performance and maximum service life of the enclosed electronics, while protecting against the intrusion of airborne contaminants and humidity. FEATURES AND BENEFITS FEATURES AND BENEFITS Standard Features Closed-loop cooling to prevent ingress of environmental 450 contaminants Available in 230VAC Designed for electronics cooling with high ambient temperatures operates to 55°C/131°F Integrated Dantherm USACG-6 controller High-quality, high-performance, high-pressure drop BCI fans Easy access to critical components for better service Bottom intake allows for reduced noise and better protection from contaminants Environmentally-friendly R134A refrigerant Compact mono-block unit for easy installation in indoor and outdoor applications Optional Features Ambient filter Power plugs Optional heater available Stainless steel material and custom paint finishes available Extended warranty & maintenance packages Closed-Loop Cooling The closed-loop internal circuit protects the enclosed equipment from heat and airborne contaminants in all types of hostile environments. The creation of a controlled environment allows the enclosed equipment to operate under the best possible temperature and environmental conditions. Applications Radio base stations Telecom shelters Indoor & outdoor cabinets and enclosures Power supply cabinets, Battery cabinets and Rectifier cabinets Network switching rooms, Computer rooms Automation control cabinets, Process control centers Machine cooling & CNC machines Drive cabinets, Turbine control cabinets Digital advertisement boards, Kiosk display systems www.dantherm.com TECHNICAL DATA 10,000 BTU/HR. AIR CONDITIONER General Model number Mounting method Unit dimensions (height×width×depth) Weight Inch [mm] lbs [kg] iA/C T- B10000 Outdoor 47x19x12 [1193.8x482.6x304.8] 171 [77.6] Performance (240V/60Hz) Cooling capacity at 131°F internal/ 131°F ambient (55°C/55°C) Cooling capacity at 95°F internal/ 95°F ambient (35°C/35°C) Internal airflow by air conditioning External airflow by air conditioning Refrigerant type Operational temperature range Noise, 1.5m distance Heater BTU/h [W] BTU/h [W] CFM [m³/h] CFM [m³/h] °F [°C] dB(A) Watts 10700 [3133] 10170 [2977] 450 [765] 710 [1205] R134a -40 to 131 [-40 to 55] 74 2000 Electrical Data Input voltage Frequency Max power consumption (Cooling) Volts Hz Amps 230 VAC 50/60 Hz 11.0 SA10718 Approvals RoHS, UL and cUL compliant Construction Galvanized Steel, Stainless Steel Optional Textured Powder Coat Standard, Color options available by request Material Finish China Russia USA MEX tel: tel: tel: tel: +86 512 6667 8500 +7 495 642 95 60 +1 864 595 9800 +52 1 55 54047568 e-mail: e-mail: e-mail: e-mail: dantherm.cn@dantherm.com thj@dantherm.com dantherm.usa@dantherm.com dantherm.mx@dantherm.com Denmark Sweden Germany France tel: tel: tel: tel: +45 +46 +49 +33 96 14 37 00 (0) 121 130 40 (0) 821 8155 7655 612 698 604 e-mail: dantherm.dk@dantherm.com e-mail: infose@dantherm.com e-mail: kw@dantherm.com e-mail: ylr@dantherm.com AC 10000 COOLING CAPACITY CURVE 16000 14000 Cooling Capacity (Btu/hr) 12000 10000 8000 35C Ambient 6000 45C Ambient 55C Ambient 4000 35 40 45 50 55 Return Air Temperature (°C) DIMENSIONAL DIAGRAM-MOUNTING INTERFACE 18.03 458.00 17.24 438.00 12.59 319.80 19.14 486.11 .39 10.00 12.15 308.60 11.50 292.00 37.60 955.00 28.19 716.00 29.53 750.00 46.91 1191.52 17.24 438.00 18.82 478.00 5.91 150.00 9.41 239.00 9.06 230.00 Subject to change without notice 08_2014 China Russia USA MEX tel: tel: tel: tel: +86 512 6667 8500 +7 495 642 95 60 +1 864 595 9800 +52 1 55 54047568 e-mail: e-mail: e-mail: e-mail: dantherm.cn@dantherm.com thj@dantherm.com dantherm.usa@dantherm.com dantherm.mx@dantherm.com Denmark Sweden Germany France tel: tel: tel: tel: +45 +46 +49 +33 96 14 37 00 (0) 121 130 40 (0) 821 8155 7655 612 698 604 e-mail: dantherm.dk@dantherm.com e-mail: infose@dantherm.com e-mail: kw@dantherm.com e-mail: ylr@dantherm.com