Blue Box™ BLUE BOX LTD TM QUICK START GUIDE WARNINGS 1. All servicing should be performed by qualified service personnel. 2. “WARNING, Battery may explode if mistreated. Do not recharge, disassemble or dispose of in fire.” 3. “CAUTION - This equipment provides more than one power supply output source. To reduce the risk of electric shock disconnect both normal and emergency sources within this unit before servicing any equipment connected to this unit” 4. When using electrical equipment, basic safety precautions should always be followed including the following: a. READ AND FOLLOW ALL SAFETY INSTRUCTIONS. b. Do not use outdoors. c. Do not mount near gas or electric heaters. d. Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel. e. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition. f. Do not use this equipment for other than intended use. g. SAVE THESE INSTRUCTIONS. 5. If any Emergency Circuits are fed or controlled from this panel, it must be located electrically where fed from a UPS, generator, or other guaranteed source of power during emergency and power outage situations. 2 Blue Box LTD Quick Start Guide PANEL MOUNTING INSTRUCTIONS SURFACE MOUNT HINGED LOCKING DOOR 8-RELAY PANEL SHOWN, BUT APPLIES TO ALL OTHER SIZES TO REMOVE DOOR FOR EASE OF INSTALLATION: 1) UNLOCK KEYLOCK 2) REMOVE SCREWS THRU ACCESS HOLES ON LEFT SIDE OF DOOR AS SHOWN (QTY: 3 for 4-RELAY, QTY: 4 for 8-RELAY, QTY: 6 for 16-RELAY) 3) DOOR CAN BE LIFTED STRAIGHT OFF OF PANEL. REPEAT STEPS IN REVERSE TO REATTACH DOOR. BE SURE TO TIGHTEN SCREWS SNUGLY TO ENSURE PROPER ATTACHMENT AND BONDING. Blue Box LTD Quick Start Guide 3 ACCESSING INTERNALS 8-RELAY PANEL SHOWN, BUT APPLIES TO ALL OTHER SIZES CLOCK DOOR ON MASTER UNITS ONLY (LOW VOLTAGE COMPARTMENT UNDERNEATH) DEAD FRONT (HIGH VOLTAGE COMPARTMENT) TAB INSERTS REMOVING DEADFRONT - CAUTION: HIGH VOLTAGE COMPARTMENT: 1) REMOVE TWO SCREWS. 2) USE FLANGED PULLS TO LIFT AND REMOVE TABS FROM INSERTS. OPENING CLOCK DOOR, MASTER UNITS ONLY - LOW VOLTAGE COMPARTMENT: 1 ) REMOVE TWO SCREWS. 2) USE FLANGED PULL TO SWING DOOR OPEN. REPEAT STEPS IN REVERSE TO REPLACE. BE SURE TO TIGHTEN SCREWS SNUGLY TO ENSURE PROPER ATTACHMENT AND BONDING. 4 Blue Box LTD Quick Start Guide REMOVING CHASSIS FROM ENCLOSURE BOX 8-RELAY PANEL SHOWN, BUT APPLIES TO ALL OTHER SIZES ENCLOSURE BOX CHASSIS MOUNTING STUD 2X CHASSIS ASSEMBLY LOCKNUT CLOCK DOOR ON MASTER UNITS ONLY LOCKNUT REMOVING CHASSIS: 1) REMOVE TWO NUTS WHILE KEEPING CHASSIS SECURED TO PREVENT IT FROM FALLING OUT. 2) LIFT CHASSIS OUT OF ENCLOSURE BOX. REPEAT STEPS IN REVERSE TO REPLACE. BE SURE TO TIGHTEN SCREWS SNUGLY TO ENSURE PROPER ATTACHMENT AND BONDING. Blue Box LTD Quick Start Guide 5 MOUNTING BOX 8-RELAY PANEL SHOWN, BUT APPLIES TO ALL OTHER SIZES 1/4” DIA. HOLES FOR MOUNTING 4 PLACES 1/2 & 3/4 DUAL KNOCKOUTS 4 PLACES 3/16” DIA. PILOT HOLES ON SIDES FOR FLUSH-MOUNT (IN-WALL) INSTALLATIONS. 4 PLACES NOTE: REFER TO "BLUE BOX LTD: GENERAL ARRANGEMENT, TABULATED" DRAWING FOR ADDITIONAL NOTES RELATED TO INSTALLATION, SUCH AS: - FEATURE LOCATIONS AND DIMENSIONS - PUNCH-OUT LOCATIONS FOR ADDED CONDUIT FEEDS - AVAILABLE COVER OPTION CONFIGURATIONS AND DIMENSIONS - FLUSH-MOUNT ROUGH-OUT DIMENSIONS FOR HINGED COVER CONFIGURATIONS 6- DOOR-SWING Blue Box LTD CONDITIONS Quick Start Guide GENERAL ARRANGEMENT DRAWING 8.2 2.05 2X OPTIONAL: AVAILABLE AREA FOR ADDED HIGH VOLTAGE CONDUIT FEEDS VIA FIELD ADDED PUNCH-OUTS 2.05 2X HIGH VOLTAGE DEAD FRONT 1.30 2X 2.6 CLOCK INTERFACE DOOR ON MASTER PANEL UNITS ONLY REMOTE PANEL UNITS ON SAME BUS ARE CONTROLLED BY MASTER UNIT DUAL KNOCKOUTS FOR 1/2" & 3/4" TRADE SIZE (Ø.88 / Ø1.13) TYP @ TOP & BOTTOM 4 TOTAL 3/4 5/8 FOR FLUSH MOUNT APPLICATIONS: GUIDE MARKS FOR 5/8" & 3/4" WALLBOARD FOR ALIGNMENT WITH WALL STUDS TYP @ EACH SIDE LCD DISPLAY AND USER INTERFACE (MASTER PANEL UNITS ONLY) 12.10 .28 MOUNTING HOLE 4X 10.00 2.6 MASTER PANELS ONLY: CONNECTING CABLE FOR DTC CLOCK INTERFACE. 2.0 .21 PILOT MOUNTING HOLES FOR FLUSH MOUNT INSTALLS 2 EACH SIDE OF 4 & 8 RELAY ENCLOSURES OPTIONAL: AVAILABLE AREA FOR ADDED HIGH VOLTAGE CONDUIT FEEDS VIA FIELD ADDED PUNCH-OUTS 4-RELAY: 8.50"H 4-RELAY: 8.25 8-RELAY: 14.10"H 8-RELAY: 12.50"H 8-RELAY: 12.25 8-RELAY: 12.7"H 16-RELAY: 22.10"H 4-RELAY: 10.10"H 16-RELAY: 20.50"H 16-RELAY: N/A 16-RELAY: 20.7"H 4-RELAY: 8.7"H OPTIONAL MULTI-POLE RELAY KIT(S) AVAILABLE FOR FIELD-CONFIGURING RELAYS FOR TWO- OR THREE-POLE OPERATION (BRIDGE & LABEL CLIP-ON COMPONENTS) OPTIONAL POSITIONABLE BARRIER CAN BE PLACED BETWEEN RELAYS TO ISOLATE NORMAL AND EMERGENCY POWER CIRCUITS REMOVE TWO FASTENERS TO REMOVE CHASSIS FROM ENCLOSURE LOW VOLTAGE COMPARTMENT HIGH VOLTAGE COMPARTMENT CLOCK INTERFACE & DEAD-FRONT REMOVED FOR CLARITY SCALE 1 : 1 PANEL BOXES COME STANDARD WITH THE FOLLOWING COVERS: - MASTER PANEL - STANDARD SURFACE MOUNT HINGED DOOR WITH CAT60 KEYLOCK - REMOTE PANEL - STANDARD SURFACE MOUNT SCREW COVER AVAILABLE OPTIONS FOR ANY CONFIGURATION (SEE SHEET 2 FOR DIMENSIONS): - SURFACE MOUNT HINGED DOOR WITH CAT60 KEYLOCK - SURFACE MOUNT SCREW COVER - FLUSH MOUNT HINGED DOOR WITH CAT60 KEYLOCK - FLUSH MOUNT SCREW COVER NOTES: 1. PANELS AVAILABLE IN 4-RELAY, 8-RELAY (SHOWN), AND 16-RELAY SIZES, IN BOTH REMOTE AND MASTER CONFIGURATIONS. 2. SEE SHEET 2 FOR PANEL COVER OPTIONS Blue Box LTD Quick Start Guide 7 BLUE BOX LTD WIRING DIAGRAM OTHER GR2400 BUS ACCESSORIES Examples: - Outdoor Photocell with PCC1 or PCC3 Card Brighton Switch - Remote Panel TERMINATE LAST DEVICE ON BUS WITH TERMINATOR (BLUE). CAT5 CABLE DIGITAL SWITCH LOW VOLTAGE SIDE LOW/HIGH VOLTAGE BARRIER HIGH VOLTAGE SIDE BREAKER PANEL NEUTRAL BUS BAR CIRCUIT BREAKERS 120V 277V USE NON-BOOTED RJ45 CONNECTORS CLOCK DISPLAY & INTERFACE CARD (MASTER ONLY) NEUT + TERMINATOR (BLUE) GROUND LUG ON LINE LOAD 3 4 #1 #2 #3 #4 to any Scene Input * ON LOAD LINE LOAD LINE LOAD LINE ON #5 #6 #7 #8 LINE ON 2 ON 1 LOAD ON OCCUPANCY SENSOR (Check with LC&D for a list of approved manufacturers) 300mA available for power YELLOW = PULL LOW ORANGE = PULL HIGH 24V GND SC5 SC6 SC7 SC8 SC9 SC10 SC11 SC12 BLUE = 24V GREEN = GROUND JUMPERS FOR FIELD-CONFIGURABLE RELAYS LINE COLOR LEGEND: CONTACT CLOSURE INPUTS * Refer to submittal documentation where LOAD applicable -or- Document inputs used and forward information to LC&D Tech-support ON LINE LOAD ON LINE LOAD UNIVERSAL INDOOR PHOTOSENSORS (PCELL 3WI TZ) Up to 4 per CARD (One per each input) 1 2 3 4 BLUE BOX LTD NUMBER OF RELAYS - QTY: 4 (1404LTD) - QTY: 8 (1408LTD SHOWN) - QTY: 16 (1416LTD) 8 Blue Box LTD Quick Start Guide TO LOADS WIRING INSTRUCTIONS DE-ENERGIZE THE PANEL BEFORE MAKING ANY WIRING CONNECTIONS. APPLYING POWER • NOTE: Make certain that high voltage and low voltage wiring enters the enclosure separately. Once the wiring is complete, make certain that the enclosure is clean of any wire clippings and that no fragments are lodged in the relay circuit boards. • High Voltage wiring should be brought into the right section of the enclosure. Ensure that there are no loose wires or exposed wires that could short to other wires or components. • Power up the unit from the circuit breaker. Low Voltage wire should enter in the low voltage wiring compartment on the left side of the enclosure. RELAY WIRING Failure to separate high voltage from low voltage wiring may cause interference with the control board function. • The standard relay is configured for single-pole load use only. • Connection of multi-pole circuits/loads to the relay will require a change in the relay configuration. See Multi-Pole Relay Configuration on page 10 of this document. • Connect the leads from a de-energized branch circuit breaker to the line side of the relay terminal block. • Please see Relay Overview on page 10 for max Voltage/amps before applying. • Tighten down relay terminal screws per torque spec, located in the high voltage compartment. WARNING: Failure to do so may result in loose contact, electrical shock, overheating and/or permanent component damage! • Document relay to circuit information for future reference. HIGH VOLTAGE CONNECTIONS • • • • • Do not discard these installation instructions. Please keep for future reference and operation information. Always de energize panel before wiring. Use only at the listed voltage per panel specs All installation service must be performed by qualified personnel. Document all wiring that is terminated to the relays so that the lighting control equipment can be properly configured and programmed for operation. WIRING THE TRANSFORMER • • • The Blue Box LTD is factory configured with a 120/277V 56VA transformer. The transformer voltages are color-coded. a) 120V- black wire b) 277V- red wire c) Neutral- white wire Connect wires to the transformer. You must provide a dedicated circuit with circuit protection for the transformer. Earth ground must be connected to the lug labeled “GND”, located in the high voltage compartment. MODEM INSTALLATION DETAILS • • • Run an analog phone line to a phone outlet near Blue Box LTD. Write the modem phone number on the outlet. Connect to the modem using a low voltage cable through the 1/2” knockout located on the top left side of the enclosure. Note: Do not use Digital Phone lines from a PBX or other system, it will not work and may damage the modem. LOW VOLTAGE CONNECTIONS EMERGENCY LOADS • It is recommended that all low voltage wiring be done with power removed to the control card to protect from potential shorts during the wiring process. To switch relays on automatically in the event of a loss of normal power, feed the power supply with a dedicated normal-power breaker. • All low voltage wiring must be run in separate conduit from linevoltage wiring. • Test all low voltage wiring for shorts to AC ground before connection to the relay panel. To maintain relay status (on or off) in the event of a loss of normal power, feed the power supply with a dedicated emergency-power breaker via a server-quality UPS (load is less than 10 watts). Blue Box LTD Quick Start Guide 9 DEVICE OVERVIEW MULTI-POLE RELAY CONFIGURATION To drive a single pole relay, the red shorting jumper should be positioned horizontally on the control card. CONVERTING RELAYS TO NORMALLY OPEN Normally closed relay jumper cable To set a multi pole relay, remove and re-position the red shorting jumper vertically, following the drive relay. Shorting jumper positioning to show a field configured 3 pole relay. Rotating one end of the relay jumper cable 180° will cause the relay to operate in a normally open mode. RELAY OVERVIEW DIMMING CONTROL CARD OVERVIEW Terminator (blue) Clock connector 2 pole clip 2 pole bridge GR2400 bus connectors screw terminal cover 8 Programmable inputs plus 24 volts DC and Ground Address Button 1 (LCP1) relays 1-4 DIN rail Photocell/Slider inputs Isolated 0 - 10v output to ballasts/drivers for relays 1-4 Address Button 2 (LCP2) relays 5-8 Isolated 0 - 10v output to ballasts/drivers for relays 5-8 10 Blue Box LTD Quick Start Guide AC power input LOW VOLTAGE CABLING NOTE: PLEASE DO NOT USE BOOTED CABLES WITH BLUE BOX LTD PANEL CONNECTIONS. Digital devices have two RJ45 connectors and are daisy-chained using Cat. 5. cable. Non-digital devices (photosensors, toggle switches, etc.) are cabled per their installation guides (not daisy-chained). Adhere to 568A or 568B standards for Cat. 5 cables. Always use a dedicated twisted pair for the center pins. Refer to individual product installation guides for line-voltage cabling details and low voltage connection details Do not “home run” digital switches back to a relay panel. No spurs or T-Taps are allowed. Low Voltage Cable Bus Switch Relay Relay Panel Line Voltage Cable ELIMINATE INTERFERENCE; ISOLATE CAT. 5 CABLES …From Line Voltage Cable: Cat. 5 cable must be at least 12” from all line voltage conductors, except to cross or make terminations. Low voltage cabling must not be run in parallel with line voltage cable, and must not share the same conduit, whether digital cable (Cat. 5) or low voltage cable (3#18 from a photosensor). …From Line Voltage Devices: Low voltage cabling must avoid EMF or RF from ballasts, arc welders or other “noisy” loads. EMF or RF interference can create an unstable bus. The more feet of Cat. 5 cable used, the fewer bus-powered devices before adding another active device. DRY CONTACT CLOSURE INPUTS WIRE COLOR DESCRIPTION BLUE 24VOLTS FUNCTION GREEN GROUND YELLOW SCENE 5 PULL LOW YELLOW SCENE 6 PULL LOW YELLOW SCENE 7 PULL LOW YELLOW SCENE 8 PULL LOW ORANGE SCENE 9 PULL HIGH ORANGE SCENE 10 PULL HIGH ORANGE SCENE 11 PULL HIGH ORANGE SCENE 12 PULL HIGH AC POWER FROM TRANSFORMER TO CONTROL BOARD WIRE COLOR DESCRIPTION BLUE 10 VOLTS BLACK MIDDLE TAP RED 10 VOLTS Low Voltage Cable Bus Switch Relay 12" or more Relay Panel Line Voltage Cable There is a limit to how many switches and photocell cards you can add in a row over long runs of Cat. 5 cabling. Bus-Powered Devices Allowed for Each Active Device 900 ft. 800 ft. 12 9 6 700 ft. 3 Total Feet of Cable from One Active Device 1000 ft. Number of Bus-Powered Devices Active Device - Device with power supply (a transformer). It acts as a source of electrical energy for the bus. Bus-Powered Device - Any device that relies on the 12v supplied by the bus for its power. Example: digital switches, and photosensor cards. Blue Box LTD Quick Start Guide 11 MAKING UP RJ45 CONNECTORS Correct installation of RJ45 Cat.5 tips on Cat5 cable is critically important to the proper operation of your system. The sequence of the color-coded wires inside the Cat. 5 cable must be arranged in the order shown below before being inserted into the RJ45 tip. 6. Using your LAN cable testing tool, insert both ends of your finished cable into the tool to check for a signal. The cable should now be ready to use. Acuity Controls recommends that EZ RJ45 connectors be used for successful installations. NOTE: Never make hot RJ45 crimps. This can damage equipment. INSTRUCTIONS 1. Determine the length needed for your cable and use the wire cutting tool on the crimping tool to cut the cable to this length. 2. Prepare the ends of the cable for crimping. Use the wire cutting tool to strip away about half an inch of the cable jacket on each end of the cable. You will see eight small colored wires twisted into four pairs. Carefully untwist each pair so that each of the 8 wires is separate. Now arrange the wires in the proper order. From top to bottom, put the wires in this order: orange/white, orange, green/ white, blu, blue/white. green, brown/white and brown. 3. Place the Cat-5 cable ends into the RJ-45 heads. 4. Line the 8 wires up neatly so that they will fit into the plastic head. Carefully insert the wires (all at once) into the plastic head, pushing them in as far as they will go. The exposed wires should line up with the 8 small metal contacts in the head. 5. With the locking prong face down, place the plastic head into the appropriate slot in the crimping tool, being careful not to dislodge the 8 wires. With the head positioned properly, apply pressure to the crimper’s handles to clamp the head down onto the wires. The metal contacts should now be touching each of the 8 wires. Repeat this process on the other end of the cable. 12 Blue Box LTD Quick Start Guide HARDWARE ACTIVATION TESTS Before starting, note total approximate bus cable length: EARTH GROUND TEST This test is intended to detect any pathways to earth ground. Set your meter for the mega ohm resistance range. Once each cable has been checked with a LAN cable tester and pluggedin, it is still possible for the entire connected cable structure to become problematic. For instance, dirt may accumulate inside the RJ45 sockets, the strain on the Cat. 5 when pushing switches into the wall may weaken connections, break conductors, or the bus length may exceed 4000 ft. Each test must be passed before moving onto the next. If any readings are out of range, refer to “Hardware Activation Troubleshooting” section at the end of this document or call Technical Support at 1-800-345-4448. This test is intended to verify bus length, continuity, and detect crossed data-pair wires. 2. 3. De-power every item on the bus and check the voltage at both ends to ensure a reading of 0vdc. Remove any terminators. At one end of the bus, plug in the “Data/Power Jumper.” At the other end of the bus, plug in the “Bus Checker Card” and measure resistance across the following terminals: Gnd to A ____ohms B to +12 ____ohms 4. All test values must be within 10% of the values in the chart below to be considered valid. Continuity Test Results (Gnd to A & B to +12) Length Measure resistance between the terminals mentioned below, and “Earth ground” (a metallic enclosure or conduit). Gnd A +12 B 8. All readings between each terminal and “Earth ground” should be infinite or “Open” END OF LINE TERMINATOR TEST CONTINUITY TEST 1. 7. Ohms Length Ohms 100 ft. 3 Ω to 6 Ω 2000 ft. 68 Ω to 80 Ω 500 ft. 12 Ω to 20 Ω 3000 ft. 102 Ω to 120 Ω 1000 ft. 34 Ω to 40 Ω 4000 ft. 130 Ω to 160 Ω This test is intended to ensure that only 2 terminators exist, one at each end of the bus. If the readings are out of range, it would indicate a missing, misplaced, or an extra terminator (terminators are shipped in the Master Panel). 9. Add a “Terminator” on the first and last device. On the “Bus Checker Card“, measure A to B ____ohms 10. Test reading should be within 62 Ω to 92 Ω 11. Remove the bus checker card and call our Tech Support with your results at: 1-800-345-4448. Figure A: Bus Checker Card Data/Power Jumper SHORT CIRCUIT TEST This test is intended to detect any short circuits along the bus. Please use the lowest resistance range (200 Ω) setting on your multi-meter. DO NOT use a “beep” test. 5. Remove the “Data Power Jumper” and measure the resistance across the following terminals on the “Bus Checker Card,” 6. All test values should be greater than 1K ohm. Gnd to A ____ohms A to B ____ohms Gnd to B ____ohms A to +12 ____ohms Gnd to +12 ____ohms B to +12 ____ohms Blue Box LTD Quick Start Guide 13 HARDWARE ACTIVATION TROUBLESHOOTING Always re-perform all tests after correcting a failed result. The “Bus-Splitting Technique” is the fastest way to find a bad cable and/or damaged device. Be sure to document the cable path. Cat. 5 cables that pass a LAN cable test can still short or break from stress and strain during installation. If re-testing a suspected cable, firmly wiggle and tug the conductors near the RJ45 while keeping an eye on the LAN tester: conductors should remain properly engaged throughout the test. CONTINUITY TEST TROUBLE SHOOTING 1. Fluctuating resistance readings indicate one or more devices are still powered. De-power all devices and re-test. 2. High resistance readings indicate broken or resistive connections. Use the Bus Splitting Technique to find: • RJ45 connectors not properly pushed into sockets (check to make sure that the wires are not extended beyond the end of the RJ45 connector) • Cable strain can break conductors or pull conductors out of RJ45 contacts (visually inspect cable and connector). • Unseated RJ45 sockets (rough install environment) • Damaged contacts in the RJ45 sockets SHORT CIRCUIT TEST TROUBLE SHOOTING 1. A low resistance reading indicates a crossed or shorted pair or a damaged device. Cable strain when pushing switches into a wall can short nicked conductors. Use the Bus Splitting Technique to find the bad cable, crimp or device. 2. Resistance readings below 120Ω or less on A-B only indicate an extra terminator. Use the bus splitting technique to find the short or extra terminator. 3. After the problem has been resolved, please complete the “Continuity Test” again. EARTH GROUND TROUBLE SHOOTING LAN-tested cables can still have a path to earth ground. 1. An abraded or “folded” cable inside the conduit will cause a short to earth ground. 2. Other low voltage or high voltage wires touching any device on the bus will cause continuity to earth ground Use the Bus Splitting Technique to locate the problem. TERMINATOR TROUBLE-SHOOTING 1. Ensure that the Data/Power Jumper is removed. 2. Visually inspect both terminators are present and properly seated on each bus-end device. ERROR CHECK TROUBLESHOOTING If the hardware activation tests have just been completed and the bus is unstable, consider the following causes: 14 Blue Box LTD Quick Start Guide 1. Failure to follow the 568A or 568B color code (or minimally to use a dedicated pair for the center pins) will cause the Error Check test to fail. Visually inspect RJ45 connectors. 2. The cable connecting the DTC to the master panel can become damaged. Visually inspect the cable – if damaged, replace it with a new cable. 3. An external source of EMF (electromagnetic field) or RF (radio frequency) interference may be present and affecting the bus (or digital devices). Refer to the Low Voltage Cabling section of this guide on running low voltage cables across or parallel to line voltage cables or exposing low voltage cables to EMF or RF sources (e.g. welders, ballasts, improperly grounded wireless devices, etc.); any of which can interfere with the bus operation and stability. Identify and correct any external sources of interferance - a digital device can also become damaged and create signal noise. An oscilloscope can be used to locate the source of the bus failure. The Oscilloscope test procedure can be found in the “Blue Box LTD Troubleshooting with an Oscilloscope” manual. BUS SPLITTING TECHNIQUE Note:To speed up troubleshooting when readings are less than 200Ω on the Continuity or Short-Circuit test, refer to the “Bus Length Chart” earlier in this document before splitting the bus; this can provide an approximate distance to a shorted pair or extra terminator from the test point. 1. On the middle device of the bus, disconnect one Cat. 5 cable to create two smaller “half-buses”. 2. Test each “half-bus” to find the side with the out-of-range values. 3. Repeat steps 1 & 2 on the out-of-range “half-bus,” to create another “half-bus” until the cable, crimp or device creating the out of range measurements is located. Note: The idea is to split a bus in half and then half again – over and over until the bad area has been located. Visually inspect each cable, crimp or device to detect the problem. SYSTEM ACTIVATION AUTO ADDRESS DEVICES NOTE: NOT APPLICABLE FOR FACTORY PRE-PROGRAMMED PANELS. Starting up a new system requires a few simple steps. Please follow the steps below to set-up the system. 1. A fter completing the Hardware Activation Tests, power up all remote panels, and active devices (any device with an onboard—120 or 277— power supply) first and then power up the master panel. Check that the power-indicator LEDs on all digital devices are on. 2. T he main screen will be displayed for a few seconds, after which the “device detection” screen will be displayed. TAB to YES and press ENTER to auto-address devices. Found 1 devices On the system that Are not used. Found 1 devices Would you like to On the system that Auto‐assign them ? Are not used. Would you like to Auto‐assign them ? Yes / No ‐> Found 1 devices Never Ask Again On the system that Yes / No ‐> Are not used. Never Ask Again Would you like to Auto‐assign them ? If the number of devices detected do not match the number of devices present on the bus, proceed to troubleshooting section. 3. T o view address assignments in the “Serial Number Scan” screen TAB to YES and press ENTER. Assigned 1 device. Yes / No ‐> Review assignment by Never Ask Again Scanning all serial Assigned 1 device. Numbers? Review assignment by Scanning all serial Yes / No Numbers? Yes / No Assigned 1 device. Review assignment by Scanning all serial Numbers? SCAN BY SERIAL# SERIAL# CE80 Yes / No ADR: 1 SCAN BY SERIAL# Item Type: Switch SERIAL# CE80 Address OK ADR: 1 Item Type: Switch SAVE ADDRESS CHANGES Address OK SCAN BY SERIAL# SAVE ADDRESS CHANGES SERIAL# CE80 ADR: 1 The “Serial Number Scan” screen displays the serial number, address, and device-type of added device(s) SYSTEM DEVICE SCHEDULE: (for Master Panels) (Master) (Master)LCP1 LCP1 3 btn sw 6 btn sw LCP 2 Device Type Device Type Device Type Device Type Location Location Location Location elec rm ce80 Hallway 8875 lobby 4685 telecom af97 R E T S A Y L M N R O O S F L E N A P Serial # Address 1 Serial # Address DI-6 3 Serial # Address 4 Serial # 5 Address Device Type Device Type Device Type Device Type Location Location Location Location Serial # Serial # Serial # Address Address Address Device Type Device Type Device Type Serial # Serial # Serial # Serial # LCP 1 4055 Address 7 ERROR CHECK Device Type The system is now ready for Error Checking. Press EXIT repeatedly to go Location Location Location Location back to the main menu. Serial # 7.Address Navigate to the “Error Statistics” screen. Use the path USER MENU Address Address Address > SETUP MENU > RESTRICTED > ADDRESSING-BUS SCAN > ERROR STATISTICS. The password to enter the RESTRICTED area is 900001. Device Type Device Type Device Type Device Type Location Location 8.Location TAB to the field thatLocation says CLEAR and press ENTER to clear errors. If after your system is # Serial # 3 minutes no errors Serial #accumulate on this Serialscreen, # Serial stable. Address Address Address Address 9. If errors continue to accumulate refer to the Error Check Troubleshooting section of Hardware Activation Troubleshooting section of this guide. 905 Allen Ave • Glendale, CA 91201 • Support 800-345-4448 • www.lightingcontrols.com LIGHTING CONTROL & DESIGN LCDBBIG13Aug08 4. In the “Serial#” field SCROLL to review each device. If collisions are present, refer to the “Scan by Serial Number” section of the Blue Box LTD System Diagnostics Tools manual. BB Panel Schedule.indd 4 8/13/2008 1:37:47 P Item Type: Switch Address OK SAVE ADDRESS CHANGES Fill out the “System Device Schedule” located on the back of the “Panel Schedule” inside the master panel. If unable to correlate the serial numbers and device locations when filling out the “System Device Schedule”, refer to the address label on each device or follow the “Read Address” section of the Blue Box LTD Programming Guide. YOUR SYSTEM IS NOW READY. PLEASE REFER TO THE BLUE BOX LTD PROGRAMMING GUIDE FOR DETAILED INFORMATION ON HOW TO PROGRAM THE DEVICES ON YOUR SYSTEM. Blue Box LTD Quick Start Guide 15 WARRANTY Lighting Control & Design Inc. warrants each new unit for 36 months from date of shipment to be free of defects in material and workmanship under conditions of normal use and specified ambient temperature when installed and operated under LC&D’s product specifications and in accordance with the National Electrical Code. LC&D shall at its option, repair or replace any defective unit which in its opinion, has not been improperly installed, wired, insulated, used or maintained, provided however that LC&D shall not be required to remove, install or reinstall any defective unit and provided that LC&D is properly notified of said defect within the aforementioned warranty period. Additionally, LC&D shall also replace any relay that fails within the first 36 months under a “no questions asked” exchange policy. The foregoing warranty and optional remedies are exclusive and, except for the foregoing warranties THERE ARE NO OTHER WARRANTIES OF MERCHANTABILITY OR OF ANY OTHER TYPE. In no event shall LC&D or any other seller be liable for consequential or special damages, nor for any repair work, undertaken without its prior written consent, nor shall LC&D’s liability on any claim for damages arising out of or connected with the manufacture, sale, installation, delivery or use of said unit ever exceed the price paid therefore. Support (800)345-4448 www.acuitycontrols.com ©2015 Acuity Brands Lighting. All Rights Reserved. Rev. 2.6.2015