C57.12.00 Sect 5 Proposed Changes to Temperature Rise Proposal 1 REVISED March 2004 Sect 5.11.1.2 Other winding rises It is proposed to add before the first paragraph the following “If specified, the average winding temperature rise above ambient shall not exceed 70°C at rated kVA for transformers who’s windings are cooled using only forced-directed oil. These transformers are identified as OD . . , and typically are ODAF. The maximum hot spot rise shall not exceed 80°C and the top oil rise shall not exceed 60°C. The tendered losses and measured losses shall be corrected to 90°C in place of 85°C reference temperature.” Existing paragraph: “Other winding rises may be recognized for unusual ambient conditions or for special applications. These are in appropriate applications or in certain product standards” Background: When the transformer is cooled using oil pumps and the oil is forced and directed through at least the main windings as defined in note 2 in section 5.1 of C57.12.00-2000, the top oil rise will be substantially less than for ONAF cooling. This will vary between different manufacturers and sizes of transformers. For ONAF cooling the top oil temperature rise limit is 65°C. Most transformers in practice have top oil temperature rises around 60°C with ONAF cooling. For ODAF cooling the top oil rise will typically be 50°C or less. Thus the oil surrounding the uppermost part of the winding and leads may be 10°C cooler and thus the maximum (hottest-spot) winding temperature may be 10°C less than the 80°C allowed for the thermally upgraded insulation system. Thus, for these types of transformers it is possible to increase the average temperature rise of the windings that are cooled using oil pumps with directed oil flow to a higher value than 65°C and still maintain an 80°C hottestspot winding temperature. Many world standards, IEC 60076-2 and CAN/CSA-C88-M90 recognize an average temperature rise of 70°C for OD . . type cooling. CSA-C88 section 9.2 note (2) comments on this subject which we may want to consider for inclusion into C57.12.00. (This comment below was not recommended by the task force. JDMarlow) “The temperature-rise limits of the windings (measured by the resistance method) are chosen to give the same hot-spot temperature rise with different types of oil circulation. The hot-spot temperature rise cannot normally be measured directly. Transformers with forced-directed oil flow have a difference between the hot-spot and the average temperature rise in the windings which is smaller than that in transformers with natural or forced but not directed oil flow. For this reason, the windings of transformers with forced-directed oil flow can have temperature-rise limits (measured by the resistance method) which are 5°C higher than in other transformers” CSA –C88 section 9.2-note (3) also recommends that the losses may be corrected to 90°C if so specified by the user. We may want to include a similar note for C57.12.00 (This comment below was recommended by the task force with some different wording. JDMarlow) “In cases where an ODAF transformer is normally loaded close to the full output rating, and where the load losses are to be capitalized and used in bid comparison or for guarantee purposes, or both, and where these losses are based on full output rating of the transformer, the user should consider specifying that the tendered losses and measured losses be corrected to 90°C in place of 85°C.” This proposal will thus harmonize C57.12.00 with IEC for this type of cooling The present loading guide C57.91-1995 uses top oil rise and winding temperatures in determining permissible overloads. There will be some work necessary on this standard because of the two different designations OFAF and ODAF previously was FOA. Any changes that may be necessary to reflect the 70°C temperature rise for ODAF cooling should be revised when C57.91 is updated. C:\Documents and Settings\mcns02\Local Settings\Temporary Internet Files\OLKBE\C57.12.00 Sect 5 Proposal BackgroundInfo3_9_04 Sect 5.doc Proposal 2 REVISED March 2004 SECTION 5.11.1 Winding temperature rises It is proposed to add a new section after the first paragraph per the following: “In transformers with concentric winding arrangement, two or more separate windings may be situated one above the other. In this case, the winding temperature limit shall apply to the average of the readings for the stacked windings if they are of equal size and kVA rating and similar design. If they are not, the evaluation should be subject to agreement between the user and the manufacturer. For all rated loading conditions that are evaluated, a hot spot temperature rise limit of 80°C must still apply to all windings” Background Information For many years transformers, for step-down (substation) and step-up service (GSU) were occasionally specified to be supplied with dual LV windings that generally are of equal kVA and voltage ratings. Recently, this type of application is becoming more common, especially for GSU service. For this type of application, one winding arrangement commonly used is to locate the LV windings one above the other as shown in fig.1 This arrangement is called a split LV, Jones connection or stacked LV. Another possible winding arrangement would be to locate the LV windings in separate radial locations per fig. 2. This is in common use when the LV windings are of unequal kVA ratings or special impedances are required to each individual LV winding. Each winding has its own oil flow. The hot spot temperature rises are essentially the same as the windings in fig.1 From fig. 1, It can be seen that the cooling liquid flows through the LV windings in series. Although the average temperature rise of the upper LV winding may be higher than the guaranteed average temperature rise, the top oil rise for the upper LV winding is the same as the HV winding. Thus the hot spot rise for the upper LV winding is the same as if the LV windings were connected in series. The hot spot rise limit for the HV is essentially the same for the upper LV or a single LV. From the example shown it can be concluded that although the average winding temperature rise of the upper LV winding is 68°C that the hot-spot temperature rise still meets the 80°C limit. The average temperature rise of the upper and lower LV is 62°C and maximum hot spot is 80°C just as if it was a single LV winding. Fig.1 Split LV Winding Fig.2 Double Concentric LV Windings Core 57°C top oil Upper LV X H 45°C V mean oil LV Y Lower LV Y 33°C Bottom oil HV Winding Liquid Temp Rise LV X Hot Spot Gradient Hot spot rise Winding Avg. Gradient Mean oil rise Avg. Winding rise Max Oil rise Hot Spot Gradient Hot spot rise 51 39 45 DOUBLE CONCENTRIC LV WINDINGS FIG 2 Max Oil rise 17 17 19 HV Avg. Winding rise Avg. Gradient Upper X Lower Y HV Mean oil rise in winding Winding SPLIT LV WINDINGS FIG 1 HV Taps 68 56 64 57 45 57 6 6 4 80 68 80 LV X LV Y HV 17 17 19 45 45 45 62 62 64 57 57 57 6 4 4 80 78 80 C:\Documents and Settings\mcns02\Local Settings\Temporary Internet Files\OLKBE\C57.12.00 Sect 5 Proposal BackgroundInfo3_9_04 Sect 5.doc