Explanatory note on the Draft Amendment to General Terms and Conditions of Supply (Enhancement of 33 kV and 11 kV Power Supply capacity): 1. Technical Feasibility: The technical feasibility of enhancing the capacity at 33 kV level is studied and is explained below. The maximum power that can be transmitted at a particular temperature and power factor, over a conductor mainly depends on the following factors: i) The maximum current carrying capacity of a conductor ii) The maximum kVA-km loading limit of a conductor at the voltage at which power is being transmitted. iii) Power factor and ambient temperature, etc. 2. Voltage Regulation: (i). The Voltage obtained from the source to the tail end under conditions of Maximum Loading and Maximum Demand on each feeder with reference to their capacity gives a picture of system condition. Since 33 kV and 11 kV lines are short-lines, the voltage regulation, which is defined as the percentage rise in voltage at the receiving end when the full load is thrown off, keeping the sending end voltage constant is given by the following equation: % Voltage Regulation = (ii). Es - Er X 100 Es It is the general practice to work out a constant in kW-km (Regulation constant) on the basis of 1% voltage drop (at 600 C) at different power factors for different voltages and conductor sizes. The length of the feeder should be such that the kW-km loading is within permissible limits to ensure voltage regulation as specified. 3. MW-km can be the unique parameter for ascertaining the maximum capacity a line can carry for the specified voltage regulation. MW-km depends on voltage level and type of conductor under pre-defined ambient conditions, power factor of the load and permissible percentage voltage drop specified in the regulations issued by the Commission. As per Regulation No. 7 of 2004, the Discoms have to maintain voltage at the Point of Commencement of supply within a limit + 6% and - 9% for11 kV and 33 kV. D:\GTC_supply\2015\Explanatory note_Capacity Rise_30112015.doc Page 1 of 4 4. The Continuous Current, max rated current and maximum kW-km loading limits of various types of conductors at 33 kV for 9 % Voltage Regulation are as follows. 33 kV, MW - km loading limit for 9% Voltage Regulation at 600 C conductor Temperature (0.9 pf) Conductor Continuous Current rating at MW-km loading Continuous Power Maximum Current rating 450C Amb.Temp limit at 9% voltage at 450C (0.9 P.F) Rated Power at at 450C (Thermal Loading) Reg (600C) in MW 450C (0.9 P.F) Amb.Temp (Amps) (Continuous in MW Rating) (Thermal (Amps) loading) (1) Dog (105) Wolf (158 Sq.mm) Panther (212 Sq.mm) (2) 283 (3) 334 (4) 191.23 (5) 14.56 (6) 17.18 336.7 481 308.00 17.32 24.74 405.3 579 382.46 20.85 29.78 Regulation constants considered at 600 C of conductor temperature and at a pf of 0.9 lag are shown in table below: 5. Conductor Type MW-km Dog 21.25 Wolf 34.22 Panther 42.50 Maharashtra has permitted (vide MERC Regulation, 2014) upto 20,000 kVA on 33 kV express feeder and upto 10,000 kVA on common 33 kV feeder. As per clause 48(5) of CEA (Technical Standards for construction of Electrical Plants & Electrical Lines), the maximum capacity of 33/11 kV substation shall be 60 MVA. MERC permitted 5 MVA demand on 11 kV express feeder vide clause 5.3(a) (iii) of MERC Regulations, 2014. 6. The technical feasibility for 33 kV & 11 kV is explained hereunder. Technical feasibility to extend 3 MVA power in 11 kV express feeder is furnished in the table below. The power factor considered here is 0.9 pf lag. But, due to prevailing kVAh tariff, all HT consumers are maintaining power factor of near 0.98 to unity. Hence, in practice the line length can be more. D:\GTC_supply\2015\Explanatory note_Capacity Rise_30112015.doc Page 2 of 4 Conductor Calculation of Line lengths for a capacity of 10 MW, 15 MW and 20 MW at 33 kV Continuous Continuous Maximum Max allowable Maximum allowable Current Power at 45 0 MW-km distance with distance rating at C (0.9 P.F) in loading limit continuous ct pf 0 0 10 15 20 45 C MW (60 C) For load in km MVA MVA MVA Amb.Temp (Continuous 9% VR col(4) / col(3) 1 Dog (105) Wolf (158 Sq.mm) Panther(212 Sq.mm) Conductor 1 Dog (105) Wolf (158 Sq.mm) Panther(212 Sq.mm) (in Amps) Rating) Amps 283 0.9 MW 14.56 MW-km 191.23 km 13.14 km 21.25 km 14.17 km ---- 336.7 0.9 17.32 308.01 17.78 ---- 22.82 17.11 405.3 0.9 20.85 382.46 18.34 ---- 28.33 21.25 MW-km for 9% voltage drop at UPF for 33 kV Voltage Continuous Continuous MW-km Max Current rating Power at 45 0 loading allowable at 450C C (0.9 P.F) in limit distance with Amb.Temp MW (600C) continuous ct (in Amps) (Continuous For 9% load in km Rating) VR col(4) / col(3) Amps MW MW-km km 283 16.18 300.65 18.59 336.7 19.24 452.59 23.52 405.3 23.17 601.29 25.96 Maximum allowable distance 10 MW 15 MW 20 MW km km 30.06 20.04 km --- 45.26 30.17 22.63 --- 40.09 30.06 Calculation of Line lengths for a capacity of 2500 kVA, 3000 kVA at 11 kV Continuous Max Maximum Continuous Maximum Power at allowable allowable Current rating kW-km 0 45 C (0.9 distance with distance Conductor at 450C pf loading limit P.F) in kW continuous ct Amb.Temp (600 C) For (Continuous load col(4) / 2500 3000 (in Amps) 9% VR Rating) col(3) kVA kVA 1 Amps pf kW kW-km km km Km Weasel (30 129 0.9 2211.94 8118.00 3.67 3.61 3.01 sq.mm) Rabbit (50 178 0.9 3052.13 12204.00 4.00 5.42 4.52 sq.mm) Dog(100 283 0.9 4852.54 23490.00 4.84 10.44 8.70 Sq.mm) D:\GTC_supply\2015\Explanatory note_Capacity Rise_30112015.doc Page 3 of 4 7. If 33 kV sales volume increases, the distribution losses would come down, technically, the distribution losses will also be less, as the resistance of higher size conductor (Wolf or Panther) is less compared Dog conductor. The details of calculations are furnished below: kV Conductor 33 33 33 Dog Wolf Panther Continuous ct Rating(I) 283 336.7 405.3 Ac Resistance I² (Ohms/km) 0.33 80089.0 0.223 113366.9 0.136 164268.1 I²R 26429.37 25280.82 22340.46 Loss in kW 26.429 25.281 22.340 Input in kW 14557.63 17319.98 20848.79 % loss 0.182 0.146 0.107 Commercially, the DISCOM gets more revenue as the 33 kV tariff is considerably higher, compared to 132 kV tariff. The tariff details are furnished; HT-1 (a) Tariff: 132 kV tariff 33 kV tariff - Rs. 5.15 Rs. 5.57 The difference is Rs 0.42/unit. The revenue gain is explained below; Consider a 15 MVA load. The load factor for this much size load would be around 80%. Tariff Additional Units Demand LF Pf hours rate Revenue (kWh) Difference (Rs.) 15000 0.8 0.98 720 8467200 0.42 3556224 The additional revenue to the DISCOM would be around Rs 35 lakhs per month from 15000 kVA demand consumers at 33 kV. D:\GTC_supply\2015\Explanatory note_Capacity Rise_30112015.doc Page 4 of 4