SUPPLY OF CAST RESIN TRANSFORMERS 11/0.433 KV, 1000 kVA – 2 Nos A. General 1. The offered Transformer Make shall be VoltAmp/Voltas/BHEL /PS Electric only 2. Manufacturer or their Authorised dealer offer only will be considered. Dealers certificate and supply list of similar transformer to be furnished B. The Offer shall be submitted in TWO PARTS. i. Techno-Commercial. The Techno-Commercial offer shall contain the technical compliance statement in same format and order. Necessary technical Catalogues supporting the product to be enclosed. II. Financial: The cost of the item in the financial bid shall be stated as below. a. Transformer with standard accessories and Optional Fittings b. Customer Routine Inspection charges if any c. Charges for Heat run test d. Charges for impulse test (optional). e. Any other please specify clearly. C. D. E. F. G. H. Clause by Clause technical Specification compliance for our specification should be furnished (compliance shall be furnished for all the information given in page 1 to 6 as per given format) I. Deviations if any shall be highlighted in the offer. II. Detail GA diagram should be submitted along with the offer III. Better features other than specified shall be highlighted IV. Transformer will be inspected and Tested before dispatch, Type test and Impulse test report of similar Transformer to be enclosed V. Spares and optional items shall be indicated with price. Documentation: Two sets of Operation, Maintenance and Service manuals. Two sets of Test reports with GA, Control circuit Drawings Warranty: System supplied shall be covered under a warranty period of 18 months from the date of receipt of the material at our Stores or 12 months from the date of commissioning of the unit at site. Bank Guarantee: Bank guarantee shall be given as per Department norms Validity of the offer should not be less than 120 days from the tender due date The item shall be delivered at ISRO, MCF - Hassan Page 1 SUPPLY OF CAST RESIN TRANSFORMERS 11/0.433 kV, 1000 kVA – 2 Nos TECHNICAL SPECIFICATIONS The design, manufacturing and performance of equipment shall comply with all currently applicable standards, regulations and safety codes Sl No. 1. Specification Scope 2. 3. 4. Quantity Make: Standards (with latest amendments) 5. System of supply 6. 7. 13. Service KVA Rating (kVA) a) HV winding b) LV winding Rated Voltage (kV) a) HV winding b) LV winding Rated Frequency (Hz) Number of phases Connections a) HV winding b) LV winding * Separate neutral bushing to be provided externally apart from the neutral provided in LV terminal box Connection symbol a) HV –LV / IS Winding 14. Core 15. Tappings 1. Range 2. No. of steps 3. For high voltage variation/for low voltage variation 8. 9. 10. 11. 12. Supply of Cast resin (Dry) type outdoor TRANSFORMER 2 Nos. VoltAmp/Voltas/BHEL/PS Electric IS 11171 IS 2026 IEC 60726 11 kV, 3 phase, 50 cycles solidly earthed system Continuous duty, OUT DOOR 1000 kVA 11 kV 433 Volts 50 Hz 3 Delta Star * required for neutral earthing Dyn 11 / IS 2026/77 Copper winding – double wound core Cast resin type CRGO or better version +7.5% to -7.5% in steps of 2.5% off circuit tap changing links at HV side The links and terminals shall be suitably insulated / covered for accidental short circuit Page 2 16. 17. 18. 19. 20. 21. 22. 23. 24. 25. 26. 27. 28. 29. 30. Reference ambient temperature (0C) a) Max. ambient air temp. b) Min ambient temp. Type of cooling Temperature raise (0C) Of winding above ambient Insulation class Enclosure Total loss at rated voltage at principal tapping and rated frequency (kW) Component losses (kW) a) No load loss at rated voltage on principal tapping and at rated freq b) Load loss at rated current at principal tapping at 75 0C Impedance voltage at rated current for the principal tapping (%) a) HV-LV Reactance at rated current & freq.(%) a) HV-LV No load current at rated voltage and rated frequency (%) Input to cooling plant (kW) Insulation level (kV rms) a) Separate source power frequency voltage with stand i) HV winding ii) LV winding b) Induced over voltage with stand i) HV winding iii) LV winding c) Full wave lightning Impulse withstand voltage (kV peak) i) HV winding ii) LV winding d) Switching Impulse withstand voltage (kV peak) i) HV winding ii) LV winding Efficiencies at 75 0C at UPF (%) a) AT Full load b) At 3/4 Full load c) At ½ Full load Over Load Capacity Regulation at Full load at 75 0C (%) a) At UPF b) At 0.8 PF lag 50 0C - 5 0C AN 90 0C above ambient of 50 0C Class F (90 0C temp rise) IP 44 or better for outdoor application Less than 11.5 kW 2.5 kW (Max) 9.0 kW (Max) 5.00 % 4.92 < 2% Nil As per IS 28 kV 3kV As per IS 866 V As per IS As per IS Better than 98.86 % Better than 99 % Better than 99.06 % As per IS 6600 less than 1.02 % 3.73 % Page 3 31. 32. OFF circuit voltage variation by OFF circuit link /details Terminal arrangement a) HV b) LV c) Neutral 33. 34. 35. 36. 37. Sl No. 1. 2. 3. 4. 5. 6. 7. Approximate masses (Kg) a) Core and winding b) Enclosure, fittings and accessories c) Total mass Approx. Overall Dimensions (mm) a) Length b) Breadth c) Height Despatch Details a) Approx. Mass of heaviest package (kg) b) Approx. Dimension of largest pack (mm) Un-tanking provision Reference standards 2.5% Out door cable box for 3C, 150 mm2 XLPE Cable termination with cable disconnecting chamber Out door cable box for 6 runs of 4C, 300 mm2 PVC Cable termination with cable disconnecting chamber. Terminal brass palm connector as per IS and Copper Bus bar for each phase cable terminations in side disconnecting chamber Separate external bushing with brass palm connector for earthing Note: Cable termination height shall suit to present cables at site. Details will be furnished during GA approval Enclosure mounted IS 11171 FITTINGS Description Specification RTDs on LV winding Digital Temperature scanner with RS 232 / 485 serial interface facility Protection against over load through RTD with alarm and trip contacts Safety door interlocking limit switches duly wired up to TB Inspection / view window ( tough glass) Rating plate Terminal marking plate 3 Nos 1 No. Required Industrial type switches required (Make: Keycee / BCH) Required Required Required Page 4 8. 9. 10. 11. 12. 13. 14. Two Earthing pad & terminal Lifting lugs Plain bi-directional Rollers Detachable type Mounted on C channels Skids Cable box LV: 4 pole bus duct adopter box HT Cable box for XLPE cable termination LV terminal connector (brass type as per IS) with bi-metal shim for busbar Required Required Required Required Required Required 5 Nos. Required 15. Jacking pads Required 16. Enclosure 17. Control wiring 18. Painting Epoxy Siemens Grey (RAL 7032) 19. GA Drawing To be furnished for approval 20. Control drawing To be furnished for approval The structure material used for the enclosure shall be of high quality MS. Main frame shall be of suitable equal angles / channels. Sheet covers used shall be not less than 1.8 mm thickness. Additional stiffener to be provided for doors. The enclosure shall provide not less than IP 44 protections for outdoor use. Separate detachable rain protection hood of slope type in addition to top cover shall be provided. Suitable toughen glass View window to be provided wherever required. All doors / covers shall be fixed with high quality gaskets to with stand the rated temperature. Each door shall have Interlock for tripping HT CB. Sufficient bottom clearance for cooling to be incorporated The enclosure shall be housed on MS C Channel, which will be used for resting on installation platform at site. The system shall have heavy-duty detachable rollers. Through 1.1KV grade, FINOLEX / RR make flame proof Copper stranded pre twisted conductor of 2.5 mm2 shall be used for control circuits. All auxiliary contact terminals to be extended up to a poly propylene / wago type common terminal block for remote monitoring purposes Page 5 Sl No. 1. 2. 3. INSPECTION AND TESTING Inspected before despatch Description Specification ROUTINE TEST a) Measurement of winding resistance b) Measurement of voltage ratio and check of voltage vector relation ship c) Measurement of impedance voltage / short circuit impedance and load loss d) Measurement of no load loss and current e) Measurement of insulation resistance f) Dielectric tests TYPE TEST a) Measurement of winding resistance b) Measurement of voltage ratio and check of voltage vector relation ship c) Measurement of impedance voltage / short circuit impedance and load loss d) Measurement of no load loss and current e) Measurement of insulation resistance f) Dielectric tests g) Temperature raise SPECIAL TESTS (OPTIONAL ) Impulse voltage withstand test as per IS If Similar transformer has under gone this test enclose the test reports To be witnessed by our Engineers at factory To be WITNESSED by our Engineers at factory To be WITNESSED by our Engineers (OPTIONAL) at Approved HV Lab / CPRI OTHER 1. Any other better features 2. Deviations if any 3. Payment terms Within 30 days of receipt and acceptance 4. Warrantee 18 Months from the date of supply OR 12 months from the date of Commissioning 5. Bank Gaurantee Performance of Bank guarantee as per dept. terms to be furnished 6. Delivery FOR Hassan 7. Validity 120 days Page 6 TECHNICAL BID GENERAL TERMS COMPLIANCE FORMAT Sl No. A. Description General 1. Make 2 a) Supplier details b) c) d) e) f) B a) Technical bid compliance b) Price bid compliance c) C a) Clause by Clause compliance b) c) D a) Documentation b) Minor modifications Specification Compliance Supply of VoltAmp / Voltas / BHEL / PS Electric make Cast Resin Transformer Offered make to be mentioned Manufacturer / Authorised Dealer If Authoriesd Dealer, Valid Certificate to be enclosed List of similar items supplied to be enclosed Company profiles to be enclosed GA drawing and OEM catalogues should be submitted. The Engineering Drawing should contain Structural Details with dimensions Type test / Impulse test reports of similar Transformer to be enclosed Techno commercial terms to be enclosed Price offer compliance for DO NOT indicate a)Transformer with standard price here accessories b) spares and Optional Fittings, c) Customer Inspection – routine, Heat run and Impulse with stand test as per Inspection at Works clause Any other please specify clearly. Clause by clause Technical specification compliance along with the Bill of Material Any other better features Deviation if any Two sets of Operation, Maintenance and Service manuals. Two sets of Test reports with GA, Control circuit Drawings Any minor modifications/deviations in Electrical or Mechanical, pointed out by our Engineer during Inspection has to be carried out without any additional cost implications Page 7 c) Test equipment Calibration reports E Warrantee F G Performance Bank Guarantee Validity H Delivery Calibration reports of testing equipments and test certificates of accessories to be supplied by you, to be submitted to our inspecting engineer during inspection The equipment shall carry the warrantee against faulty materials, design or workmanship for a period not less than 18 months from the date of receipt of material at our stores OR 12 months from the date of Commissioning whichever is earlier Performance Bank Guarantee shall be provided as per department terms Offer validity should not be less than 120 days from the tender due date FOR MCF - Hassan TECHNICAL SPECIFICATIONS COMPLIANCE FORMAT The design, manufacturing and performance of equipment shall comply with all currently applicable standards, regulations and safety codes Sl Description Specification Compliance No. 1. Scope Supply of Cast resin (Dry) type outdoor TRANSFORMER 2. Quantity 2 Nos. 3. Make: VoltAmp/Voltas/BHEL/PS Electric 4. Standards IS 11171 (with latest amendments) IS 2026 , IEC 60726 5. System of supply 11 kV, 3 phase, 50 cycles solidly earthed system 6. Service Continuous duty, OUT DOOR 7. KVA Rating (kVA) 1000 kVA a) HV winding b) LV winding 8. Rated Voltage (kV) a) HV winding 11 kV b) LV winding 433 Volts 9. Rated Frequency (Hz) 50 Hz Page 8 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. Number of phases Connections a) HV winding b) LV winding * Separate neutral bushing to be provided externally apart from the neutral provided in LV terminal box Connection symbol a) HV –LV / IS Winding Core Tappings 4. Range 5. No. of steps 6. For high voltage variation/for low voltage variation Reference ambient temperature (0C) c) Max. ambient air temp. d) Min ambient temp. Type of cooling Temperature raise (0C) Of winding above ambient Insulation class Enclosure Total loss at rated voltage at principal tapping and rated frequency (kW) Component losses (kW) c) No load loss at rated voltage on principal tapping and at rated freq d) Load loss at rated current at principal tapping at 75 0C Impedance voltage at rated current for the principal tapping (%) a) HV-LV 3 Delta Star * required for neutral earthing Dyn 11 / IS 2026/77 Copper winding – double wound core Cast resin type CRGO or better version +7.5% to -7.5% in steps of 2.5% off circuit tap changing links at HV side The links and terminals shall be suitably insulated / covered for accidental short circuit 50 0C - 5 0C AN 90 0C above ambient of 50 0 C Class F (90 0C temp rise) IP 44 or better for outdoor application Less than 11.5 kW 2.5 kW (Max) 9.0 kW (Max) 5.00 % Page 9 24. 25. 26. 27. 28. 29. 30. 31. Reactance at rated current & freq.(%) a) HV-LV No load current at rated voltage and rated frequency (%) Input to cooling plant (kW) Insulation level (kV rms) e) Separate source power frequency voltage with stand iv) HV winding v) LV winding f) Induced over voltage with stand j) HV winding vi) LV winding g) Full wave lightning Impulse withstand voltage (kV peak) iii) HV winding iv) LV winding h) Switching Impulse withstand voltage (kV peak) j) HV winding iii) LV winding Efficiencies at 75 0C at UPF (%) d) AT Full load e) At 3/4 Full load f) At ½ Full load Over Load Capacity Regulation at Full load at 75 0C (%) c) At UPF d) At 0.8 PF lag OFF circuit voltage variation by OFF circuit link /details 4.92 < 2% Nil As per IS 28 kV 3kV As per IS 866 V As per IS As per IS Better than 98.86 % Better than 99 % Better than 99.06 % As per IS 6600 less than 1.02 % 3.73 % 2.5% Page 10 32. 33. 34. 35. 36. 37. Sl 38. 39. 40. 41. 42. 43. 44. Out door cable box for 3C, 150 mm2 XLPE Cable termination with cable disconnecting chamber Out door cable box for 6 runs of 4C, 300 e) LV mm2 PVC Cable termination with cable disconnecting chamber. Terminal brass f) Neutral palm connector as per IS and Copper Bus bar for each phase cable terminations in side disconnecting chamber Separate external bushing with brass palm connector for earthing Note: Cable termination height shall suit to present cables at site. Details will be furnished during GA approval Approximate masses (Kg) d) Core and winding e) Enclosure, fittings and accessories f) Total mass Approx. Overall Dimensions (mm) d) Length e) Breadth f) Height Despatch Details c) Approx. Mass of heaviest package (kg) d) Approx. Dimension of largest pack (mm) Un-tanking provision Enclosure mounted Reference standards IS 11171 Terminal arrangement d) HV FITTINGS Description/ Specification RTDs on LV winding 3 Nos Digital Temperature scanner with RS 1 No. 232 / 485 serial interface facility Protection against over load through Required RTD with alarm and trip contacts Safety door interlocking limit switches Industrial type duly wired up to TB switches required (Make: Keycee / BCH) Inspection / view window ( tough Required glass) Rating plate Required Terminal marking plate Required Page 11 45. 46. 47. 48. 49. 50. 51. Two Earthing pad & terminal Lifting lugs Plain bi-directional Rollers Detachable type, Mounted on C channels Skids Cable box LV: 4 pole bus duct adopter box HT Cable box for XLPE cable termination LV terminal connector (brass type as per IS) with bi-metal shim for busbar Required Required Required Required Required Required 5 Nos. Required 52. Jacking pads Required 53. Enclosure 54. Control wiring 55. Painting The structure material used for the enclosure shall be of high quality MS. Main frame shall be of suitable equal angles / channels. Sheet covers used shall be not less than 1.8 mm thickness. Additional stiffener to be provided for doors. The enclosure shall provide not less than IP 44 protections for outdoor use. Separate detachable rain protection hood of slope type in addition to top cover shall be provided. Suitable toughen glass View window to be provided wherever required. All doors / covers shall be fixed with high quality gaskets to with stand the rated temperature. Each door shall have Interlock for tripping HT CB. Sufficient bottom clearance for cooling to be incorporated The enclosure shall be housed on MS C Channel, which will be used for resting on installation platform at site. The system shall have heavyduty detachable rollers. Through 1.1KV grade, FINOLEX / RR make flame proof Copper stranded pre twisted conductor of 2.5 mm2 shall be used for control circuits. All auxiliary contact terminals to be extended up to a poly propylene / wago type common terminal block for remote monitoring purposes Epoxy Siemens Grey (RAL 7032) 56. GA Drawing To be furnished for approval Page 12 57. Control drawing To be furnished for approval INSPECTION AND TESTING Inspected before dispatch at works Sl No. 58. 59. 60. Description Specification ROUTINE TEST a) Measurement of winding resistance b) Measurement of voltage ratio and check of voltage vector relation ship c) Measurement of impedance voltage / short circuit impedance and load loss d) Measurement of no load loss and current e) Measurement of insulation resistance f) Dielectric tests To be witnessed by our Engineers at factory TYPE TEST a) Measurement of winding resistance b) Measurement of voltage ratio and check of voltage vector relation ship c) Measurement of impedance voltage / short circuit impedance and load loss d) Measurement of no load loss and current e) Measurement of insulation resistance f) Dielectric tests g) Temperature raise (Heat run) To be WITNESSED by our Engineers at factory SPECIAL TESTS (OPTIONAL) Impulse voltage withstand test as per IS, Furnish the report If similar transformer has under gone this test To be WITNESSED by our Engineers (OPTIONAL) at Approved HV Lab / CPRI Page 13