INSTALLATION INSTRUCTIONS Exit and Emergency Lighting R-1 INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FOR NEB1400 1400-LUMEN FLUORESCENT EMERGENCY BALLAST IMPORTANT SAFEGUARDS: When using electrical equipment, always adhere to basic safety precautions including the following: READ AND FOLLOW ALL SAFETY INSTRUCTIONS 1. Do not use outdoors. This unit is for use with grounded, UL Listed indoor fixtures except in heated air outlets or in wet, damp or hazardous locations. 2. This device is designed for factory or field installation in either the wireway or on top of the indoor fixture. 3. This device should be mounted in locations and at heights where it will not be easily subjected to tampering by unauthorized personnel. 4. Do not install near gas or electric heaters. 5. Do not use this equipment for anything other than its intended use. 6. The use of accessory equipment not recommended by the manufacturer will void product listing and warranty and may cause an unsafe condition. 7. Prior to installation, battery connector must be open to prevent high voltage from being present on the output leads (red and yellow). 8. An AC power source of 120VAC or 277VAC is required. EMERGENCY BALLAST OVERVIEW The NEB1400 Emergency Ballast allows the same indoor fixture to be used for both normal and emergency operation. In the event of a power failure, the NEB1400 switches to the emergency mode and operates one or two of the existing lamps for a minimum of 90 minutes. The NEB1400 contains a battery, charger and inverter circuit in a single package. It can be mounted in the wireway or on top of the indoor fixture and is UL Listed for factory installation or retrofit applications. LAMP COMPATIBILITY In the emergency mode, this device will operate one (1) 2’ to 4’ rapid, instant or energy-saving T8-T12; one (1) or two (2) 2’-8’ rapid, instant, or energy savings T8-T12, HO, VHO; one (1) or two (2) 20W-40W Circline lamp; one (1) 13W, 18W, or 26W 4-pin compact fluorescent lamp; one (1) 13W-42W twin, quad or triple (4-pin) compact fluorescent lamp; one (1) 40W Biax; one (1) 50W Biax; or one (1) 55W Biax. 9. Make sure electrical connections are in conformance with the National Electrical Code (NEC) and local regulations where applicable. 10. To prevent electric shock, disconnect normal and emergency power supplies and battery connections from the emergency ballast before servicing. 11. This is a sealed unit that contains a maintenance-free, high temperature nickel-cadmium (Ni-Cad) battery that is not replaceable in the field. Do not attempt to service or replace battery. Replace entire unit when necessary. Batteries must be recycled or disposed of properly. Contact manufacturer for information. 12. Installation of or service on this equipment should be performed by qualified personnel only. DIAGRAM 1 SWITCHED FIXTURE UNSWITCHED FIXTURE BLACK HOT WHITE SINGLE POLE TEST SWITCH BREAKING THE HOT AC BALLAST EMERGENCY BALLAST WHITE COM AC BALLAST AC BALLAST WHITE BLACK SINGLE POLE TEST SWITCH BREAKING THE COMMON EMERGENCY BALLAST WHITE EMERGENCY BALLAST HOT WHITE BLACK 120V OR ORANGE 277V (CAP UNUSED LEAD) WALL SWITCH BLACK 120V OR ORANGE 277V (CAP UNUSED LEAD) COM BLACK HOT SINGLE POLE TEST SWITCH BREAKING THE COMMON SINGLE POLE TEST SWITCH BREAKING THE HOT WHITE BLACK 120V OR ORANGE 277V (CAP UNUSED LEAD) COM BLACK HOT COM WALL SWITCH WHITE AC BALLAST WHITE EMERGENCY BALLAST BLACK 120V OR ORANGE 277V (CAP UNUSED LEAD) DIAGRAM 3 DIAGRAM 2 DIAGRAM 4 EMERGENCY BALLAST EMERGENCY BALLAST EMERGENCY BALLAST * WIRE BUNDLE COVER CHARGING INDICATOR LIGHT CHARGING INDICATOR LIGHT DRILL 1/8" HOLE FOR MOUNTING SCREWS TEST SWITCH * WIRE BUNDLE COVER TEST SWITCH BALLAST CHANNEL COVER 1/2" STD. KNOCKOUT 7/8" HOLE W/BUSHING pg 1 of 4 INSTALLATION INSTRUCTIONS Exit and Emergency Lighting INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FOR NEB1400 1400-LUMEN FLUORESCENT EMERGENCY BALLAST INSTALLATION 1. Turn off AC power before installation. 2. Choose proper wiring diagram to connect this emergency ballast to AC ballast and lamp. 3. Emergency ballast must be fed from the same branch circuit as the AC ballast. 4. Follow directions to install emergency ballast on top of fixture or in ballast channel (Illustrations 2, 3 and 4). 5. The TEST switch should be installed either through the side of strip fixture or troffer cover in ballast channel. Follow directions to drill a small hole and install TEST switch (Illustration 5). Wire the TEST switch so that it disconnects AC power from both the emergency ballast and AC ballast at the same time. 6. Install the CHARGE indicator by connecting the violet and brown leads (Illustration 5). The CHARGE indicator light should be illuminated during normal fixture operation. 7. Place appropriate labels on CHARGE indicator light and TEST switch upon completion of installation. 8. Select a highly visible location and adhere warning label that states, (CAUTION: This unit has more than one power supply connection point. To reduce the risk of electric shock, disconnect both the branch circuit breakers or fuses and emergency power supplies before servicing.) 9. Wire nut unused AC voltage lead. 10. When the fixture is completely installed, connect the inverter. 11. Turn on AC power. 12. Check to see that CHARGE indicator light is illuminated. 13. Battery in emergency ballast must be charged for one (1) hour in order to perform short-term emergency function testing. Before attempting a long-term emergency function test (90 minutes), battery must be charged for 24 hours. OPERATION 1. The CHARGE indicator light should be illuminated when AC power is applied. 2. Emergency ballast should function and operate one (1) lamp for at least 90 minutes after AC power has failed. MAINTENANCE 1. To ensure that emergency ballast is operating properly, the following schedule is recommended: a. Every month - Visually inspect CHARGE indicator and confirm that it’s illuminated. b. Every month - Press TEST switch for 30 seconds and confirm lamp operation at reduced illumination. c. Every year - Perform a 90-minute long-term emergency function test to be sure lamp operates at reduced illumination for a minimum of 90 minutes. 2. Written records of testing shall be kept by the owner for inspection by the authority having jurisdiction. DIAGRAM 5 TROFFER STYLE FIXTURE OPTIONAL STRIP STYLE FIXTURE FIXTURE EMERGENCY BALLAST LEADS TO CHARGING INDICATOR LIGHT BALLAST CHANNEL COVER 7/8" BUSHGING INSERTED INTO BALLAST CHANNEL COVER 7/8" PUNCH PLASTIC TUBING (PLEASE CUT TO NECESSARY LENGTH) INDICATOR LIGHT 1/2" WHITE BUSHING TO HOLD CHARGING INDICATOR LIGHT CHARGING INDICATOR LIGHT FIXTURE INDICATOR LIGHT VIOLET (+) VIOLET (+) BROWN (-) BROWN (-) STEP 1 FIXTURE AC ON TEST STEP 2 FIXTURE LENS TABLE 1 LAMP DIAMETER BASE TYPE POWER (LENGTH) NUMBER OF EMER. LAMPS BROWN CONNECTOR 1”, 1-1/4”, 1-1/2” (T8, T10, T12) SINGLE OR BIPIN 17-24W 1 2 CLOSED OPEN 1”, 1-1/4”, 1-1/2” (T8, T10, T12) SINGLE OR BIPIN 1 2 1 CLOSED OPEN OPEN LONG COMPACT 4-PIN (2G11) 40-50 W 1 2 1 CLOSED OPEN OPEN 18-42 W 18-42 W 1 2 CLOSED OPEN COMPACT 32-40 W (2’-4’) 40-110 W (5’-8’) 4-PIN (G24q, GX24q) 18-39 W pg 2 of 4 INSTALLATION INSTRUCTIONS Exit and Emergency Lighting EMERGENCY BALLAST AND AC BALLAST MUST BE FED FROM THE SAME BRANCH CIRCUIT. TYPICAL SCHEMATICS ONLY. MAY BE USED WITH OTHER BALLASTS. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS. WIRING DIAGRAMS FOR ONE-LAMP EMERGENCY OPERATION A. ONE (1) LAMP INSTANT START BALLAST B. ONE (1) LAMP RAPID START BALLAST REFER TO TABLE 1 BROWN BLACK LINE BLUE WHITE BROWN BLUE ORANGE 277V BLUE/WHITE BLACK WHITE VIOLET (+) BROWN (-) 120V EMERGENCY BALLAST YELLOW/GREEN AC BALLAST RED REFER TO TABLE 1 BROWN YELLOW RED LINE BLACK BLUE BLUE WHITE BLUE RED RED BLUE/WHITE YELLOW YELLOW/GREEN CAP UNUSED LEAD AC BALLAST BATTERY CONNECTOR BROWN BLACK BLUE WHITE BLUE TO UNSWITCHED AC CAP UNUSED LEAD CHARGING INDICATOR LIGHT RED YELLOW/GREEN YELLOW RED REFER TO TABLE 1 EMERGENCY BALLAST ORANGE 277V BLACK WHITE VIOLET (+) BROWN (-) 120V WHITE BATTERY CONNECTOR COM TO UNSWITCHED AC LINE CAP UNUSED LEAD BLACK BLUE BLUE WHITE BLUE RED RED BLUE/WHITE YELLOW AC BALLAST YELLOW YELLOW YELLOW/GREEN BROWN EMERGENCY BALLAST RED CHARGING INDICATOR LIGHT ORANGE 277V BLACK 120V WHITE VIOLET (+) BROWN (-) COM WHITE RED BATTERY CONNECTOR LAMP 1 TO UNSWITCHED AC CAP UNUSED LEAD CHARGING INDICATOR LIGHT LAMP 2 (EMERGENCY) LAMP 2 (EMERGENCY) F. FOUR (4) LAMP INSTANT START BALLAST E. THREE (3) LAMP INSTANT START BALLAST REFER TO TABLE 1 REFER TO TABLE 1 BROWN AC BALLAST COM WHITE BROWN BLUE BLUE/WHITE LAMP 1 BLACK 120V WHITE VIOLET (+) VIOLET (-) BATTERY CONNECTOR BROWN RED WHITE 277V BLACK D. TWO (2) LAMP RAPID START BALLAST REFER TO TABLE 1 LINE ORANGE LAMP C. TWO (2) LAMP INSTANT START BALLAST AC BALLAST EMERGENCY BALLAST RED LAMP LINE BROWN RED CHARGING INDICATOR LIGHT WHITE RED COM TO UNSWITCHED AC BLUE BLUE BLUE BLUE/WHITE BLUE YELLOW/GREEN RED OR YELLOW YELLOW RED BROWN BROWN EMERGENCY BALLAST ORANGE 277V BLACK WHITE VIOLET (+) BROWN (-) 120V WHITE RED BATTERY CONNECTOR LAMP 1 COM TO UNSWITCHED AC LINE BLACK BLUE BLUE WHITE BLUE RED RED BLUE/WHITE YELLOW YELLOW CAP UNUSED LEAD AC BALLAST YELLOW/GREEN YELLOW BROWN EMERGENCY BALLAST RED CHARGING INDICATOR LIGHT ORANGE 277V BLACK 120V WHITE VIOLET (+) BROWN (-) COM WHITE RED BATTERY CONNECTOR LAMP 1 TO UNSWITCHED AC CAP UNUSED LEAD CHARGING INDICATOR LIGHT LAMP 2 LAMP 2 LAMP 3 LAMP 3 (EMERGENCY) LAMP 4 (EMERGENCY) WIRING DIAGRAMS FOR TWO-LAMP EMERGENCY OPERATION (2'-4', 17-40 W LAMPS ONLY) H. TWO (2) LAMP RAPID START BALLAST G. TWO (2) LAMP INSTANT START BALLAST REFER TO TABLE 1 REFER TO TABLE 1 BROWN BLACK LINE WHITE AC BALLAST BLUE BLUE BLUE RED YELLOW/GREEN RED BLUE/WHITE YELLOW BROWN BROWN EMERGENCY BALLAST ORANGE 277V BLACK WHITE VIOLET (+) BROWN (-) 120V WHITE RED BATTERY CONNECTOR LAMP 1 COM TO UNSWITCHED AC LINE BLACK BLUE BLUE WHITE BLUE BLUE/WHITE RED RED YELLOW YELLOW CAP UNUSED LEAD YELLOW AC BALLAST BROWN EMERGENCY BALLAST RED YELLOW/GREEN 277V BLACK 120V WHITE VIOLET (+) BROWN (-) COM WHITE RED CHARGING INDICATOR LIGHT ORANGE BATTERY CONNECTOR TO UNSWITCHED AC CAP UNUSED LEAD CHARGING INDICATOR LIGHT LAMP 1 LAMP 2 LAMP 2 J. THREE (3) LAMP RAPID START BALLAST I. THREE (3) LAMP INSTANT START BALLAST REFER TO TABLE 1 REFER TO TABLE 1 BROWN BLACK LINE WHITE AC BALLAST BLUE BLUE BLUE BLUE RED BLUE/WHITE YELLOW/GREEN YELLOW RED OR YELLOW BROWN BROWN EMERGENCY BALLAST ORANGE 277V BLACK 120V WHITE VIOLET (+) BROWN (-) COM WHITE RED BATTERY CONNECTOR BLACK TO UNSWITCHED AC CAP UNUSED LEAD CHARGING INDICATOR LIGHT LINE WHITE BLUE/WHITE BLUE/WHITE RED RED AC BALLAST BLUE BLUE BLUE BLUE/WHITE YELLOW YELLOW/GREEN YELLOW YELLOW RED BROWN EMERGENCY BALLAST RED LAMP 1 LAMP 1 LAMP 2 (EMERGENCY) LAMP 2 (EMERGENCY) LAMP 3 (EMERGENCY) BATTERY CONNECTOR ORANGE 277V BLACK WHITE VIOLET (+) BROWN (-) 120V WHITE COM TO UNSWITCHED AC CAP UNUSED LEAD CHARGING INDICATOR LIGHT LAMP 3 (EMERGENCY) K. FOUR (4) LAMP INSTANT START BALLAST REFER TO TABLE 1 BROWN LINE BLACK BLUE BLUE WHITE BLUE RED RED RED BLUE/WHITE YELLOW YELLOW AC BALLAST YELLOW/GREEN BROWN EMERGENCY BALLAST YELLOW RED LAMP 1 BATTERY CONNECTOR ORANGE 277V BLACK 120V WHITE VIOLET (+) BROWN (-) COM WHITE TO UNSWITCHED AC CAP UNUSED LEAD CHARGING INDICATOR LIGHT LAMP 2 LAMP 3 (EMERGENCY) LAMP 4 (EMERGENCY) pg 3 of 4 INSTALLATION INSTRUCTIONS Exit and Emergency Lighting R-1 EMERGENCY BALLAST AND AC BALLAST MUST BE FED FROM THE SAME BRANCH CIRCUIT. TYPICAL SCHEMATICS ONLY. MAY BE USED WITH OTHER BALLASTS. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS. WIRING DIAGRAMS FOR EMERGENCY-ONLY FIXTURES L. ONE (1) 17-110 W LAMP WITHOUT AC BALLAST M. TWO (2) 17-40 W LAMPS WITHOUT BALLAST REFER TO TABLE 1 BROWN CAP ] CAP ] REFER TO TABLE 1 BROWN BROWN BLUE ORANGE 277V BLUE/WHITE BLACK 120V YELLOW YELLOW/GREEN RED EMERGENCY BALLAST RED BATTERY CONNECTOR LAMP WHITE VIOLET (+) BROWN (-) WHITE COM TO UNSWITCHED AC CAP UNUSED LEAD CAP ] CAP ] BROWN BLUE BLUE/WHITE YELLOW YELLOW/GREEN RED CHARGING INDICATOR LIGHT EMERGENCY BALLAST ORANGE 277V BLACK 120V WHITE VIOLET (+) BROWN (-) COM WHITE RED BATTERY CONNECTOR TO UNSWITCHED AC CAP UNUSED LEAD CHARGING INDICATOR LIGHT LAMP 1 LAMP 2 © 2005 Juno Printed in USA Rev 08/05 P0097 pg 4 of 4 WARRANTY Juno Lighting Group warrants that its products are free from defects in material and workmanship. Juno Lighting Group’s obligation is expressly limited to repair or replacement, without charge, at Juno Lighting Group’s factory after prior written return authorization has been granted. This warranty shall not apply to products which have been altered or repaired outside of Juno Lighting Group’s factory. This warranty is in lieu of all other warranties, expressed or implied, and without limiting the generality of the foregoing phrase, excludes any implied warranty of merchantability. Also, there are no warranties which extend beyond the description of the product on the company’s literature setting forth terms of sale. Product Services Phone (888) 387-2212 1300 South Wolf Road • Des Plaines, IL 60018 • Phone 800-323-5068 • www.junolightinggroup.com ©2016 Acuity Brands Lighting, Inc. Printed in USA Rev 8/05 P0097 pg 4 of 4