INSTALLATION INSTRUCTIONS
Exit and Emergency Lighting
R-1
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
FOR NEB1400 1400-LUMEN FLUORESCENT EMERGENCY BALLAST
IMPORTANT SAFEGUARDS:
When using electrical equipment, always adhere to basic safety precautions including the following:
READ AND FOLLOW ALL
SAFETY INSTRUCTIONS
1. Do not use outdoors. This unit is for
use with grounded, UL Listed indoor
fixtures except in heated air outlets or
in wet, damp or hazardous locations.
2. This device is designed for factory or
field installation in either the wireway
or on top of the indoor fixture.
3. This device should be mounted in
locations and at heights where it will
not be easily subjected to tampering
by unauthorized personnel.
4. Do not install near gas or electric
heaters.
5. Do not use this equipment for anything
other than its intended use.
6. The use of accessory equipment not
recommended by the manufacturer
will void product listing and warranty
and may cause an unsafe condition.
7. Prior to installation, battery connector
must be open to prevent high voltage
from being present on the output
leads (red and yellow).
8. An AC power source of 120VAC or
277VAC is required.
EMERGENCY BALLAST OVERVIEW
The NEB1400 Emergency Ballast allows
the same indoor fixture to be used for
both normal and emergency operation.
In the event of a power failure, the
NEB1400 switches to the emergency
mode and operates one or two of
the existing lamps for a minimum of
90 minutes.
The NEB1400 contains a battery, charger
and inverter circuit in a single package.
It can be mounted in the wireway or
on top of the indoor fixture and is UL
Listed for factory installation or retrofit
applications.
LAMP COMPATIBILITY
In the emergency mode, this device will
operate one (1) 2’ to 4’ rapid, instant or
energy-saving T8-T12; one (1) or two (2)
2’-8’ rapid, instant, or energy savings
T8-T12, HO, VHO; one (1) or two (2)
20W-40W Circline lamp; one (1) 13W,
18W, or 26W 4-pin compact fluorescent
lamp; one (1) 13W-42W twin, quad or
triple (4-pin) compact fluorescent lamp;
one (1) 40W Biax; one (1) 50W Biax; or
one (1) 55W Biax.
9. Make sure electrical connections
are in conformance with the
National Electrical Code (NEC) and
local regulations where applicable.
10. To prevent electric shock, disconnect normal and emergency power
supplies and battery connections
from the emergency ballast before
servicing.
11. This is a sealed unit that contains a
maintenance-free, high temperature nickel-cadmium (Ni-Cad)
battery that is not replaceable in the
field. Do not attempt to service or
replace battery. Replace entire unit
when necessary. Batteries must be
recycled or disposed of properly.
Contact manufacturer for information.
12. Installation of or service on this
equipment should be performed
by qualified personnel only.
DIAGRAM 1
SWITCHED FIXTURE
UNSWITCHED FIXTURE
BLACK
HOT
WHITE
SINGLE POLE
TEST SWITCH
BREAKING THE HOT
AC BALLAST
EMERGENCY
BALLAST
WHITE
COM
AC BALLAST
AC BALLAST
WHITE
BLACK
SINGLE POLE
TEST SWITCH
BREAKING THE
COMMON
EMERGENCY
BALLAST
WHITE
EMERGENCY
BALLAST
HOT
WHITE
BLACK 120V OR
ORANGE 277V
(CAP UNUSED LEAD)
WALL
SWITCH
BLACK 120V OR
ORANGE 277V
(CAP UNUSED LEAD)
COM
BLACK
HOT
SINGLE POLE
TEST SWITCH
BREAKING THE
COMMON
SINGLE POLE
TEST SWITCH
BREAKING THE HOT
WHITE
BLACK 120V OR
ORANGE 277V
(CAP UNUSED LEAD)
COM
BLACK
HOT
COM
WALL
SWITCH
WHITE
AC BALLAST
WHITE
EMERGENCY
BALLAST
BLACK 120V OR
ORANGE 277V
(CAP UNUSED LEAD)
DIAGRAM 3
DIAGRAM 2
DIAGRAM 4
EMERGENCY BALLAST
EMERGENCY BALLAST
EMERGENCY BALLAST
* WIRE BUNDLE COVER
CHARGING INDICATOR LIGHT
CHARGING INDICATOR LIGHT
DRILL 1/8" HOLE FOR
MOUNTING SCREWS
TEST SWITCH
* WIRE BUNDLE COVER
TEST SWITCH
BALLAST
CHANNEL
COVER
1/2" STD. KNOCKOUT
7/8" HOLE W/BUSHING
pg 1 of 4
INSTALLATION INSTRUCTIONS
Exit and Emergency Lighting
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
FOR NEB1400 1400-LUMEN FLUORESCENT EMERGENCY BALLAST
INSTALLATION
1. Turn off AC power before installation.
2. Choose proper wiring diagram to
connect this emergency ballast to
AC ballast and lamp.
3. Emergency ballast must be fed from
the same branch circuit as the AC
ballast.
4. Follow directions to install emergency
ballast on top of fixture or in ballast
channel (Illustrations 2, 3 and 4).
5. The TEST switch should be installed
either through the side of strip fixture
or troffer cover in ballast channel.
Follow directions to drill a small hole
and install TEST switch (Illustration 5).
Wire the TEST switch so that it
disconnects AC power from both
the emergency ballast and AC
ballast at the same time.
6. Install the CHARGE indicator by
connecting the violet and brown
leads (Illustration 5). The CHARGE
indicator light should be illuminated
during normal fixture operation.
7. Place appropriate labels on CHARGE
indicator light and TEST switch upon
completion of installation.
8. Select a highly visible location and
adhere warning label that states,
(CAUTION: This unit has more than
one power supply connection point.
To reduce the risk of electric shock,
disconnect both the branch circuit
breakers or fuses and emergency
power supplies before servicing.)
9. Wire nut unused AC voltage lead.
10. When the fixture is completely
installed, connect the inverter.
11. Turn on AC power.
12. Check to see that CHARGE indicator
light is illuminated.
13. Battery in emergency ballast must
be charged for one (1) hour in order
to perform short-term emergency
function testing. Before attempting
a long-term emergency function
test (90 minutes), battery must be
charged for 24 hours.
OPERATION
1. The CHARGE indicator light should
be illuminated when AC power is
applied.
2. Emergency ballast should function
and operate one (1) lamp for at
least 90 minutes after AC power has
failed.
MAINTENANCE
1. To ensure that emergency ballast is
operating properly, the following
schedule is recommended:
a. Every month - Visually inspect
CHARGE indicator and confirm
that it’s illuminated.
b. Every month - Press TEST switch for
30 seconds and confirm lamp
operation at reduced illumination.
c. Every year - Perform a 90-minute
long-term emergency function
test to be sure lamp operates
at reduced illumination for a
minimum of 90 minutes.
2. Written records of testing shall be
kept by the owner for inspection by
the authority having jurisdiction.
DIAGRAM 5
TROFFER STYLE FIXTURE
OPTIONAL STRIP STYLE FIXTURE
FIXTURE
EMERGENCY
BALLAST
LEADS TO CHARGING
INDICATOR LIGHT
BALLAST CHANNEL
COVER
7/8" BUSHGING
INSERTED INTO BALLAST
CHANNEL COVER
7/8" PUNCH
PLASTIC TUBING
(PLEASE CUT TO
NECESSARY LENGTH)
INDICATOR LIGHT
1/2" WHITE BUSHING
TO HOLD CHARGING
INDICATOR LIGHT
CHARGING INDICATOR LIGHT
FIXTURE
INDICATOR LIGHT
VIOLET (+)
VIOLET (+)
BROWN (-)
BROWN (-)
STEP 1
FIXTURE
AC ON
TEST
STEP 2
FIXTURE LENS
TABLE 1
LAMP
DIAMETER
BASE TYPE
POWER
(LENGTH)
NUMBER OF
EMER. LAMPS
BROWN
CONNECTOR
1”, 1-1/4”, 1-1/2”
(T8, T10, T12)
SINGLE OR BIPIN
17-24W
1
2
CLOSED
OPEN
1”, 1-1/4”, 1-1/2”
(T8, T10, T12)
SINGLE OR BIPIN
1
2
1
CLOSED
OPEN
OPEN
LONG COMPACT
4-PIN (2G11)
40-50 W
1
2
1
CLOSED
OPEN
OPEN
18-42 W
18-42 W
1
2
CLOSED
OPEN
COMPACT
32-40 W (2’-4’)
40-110 W (5’-8’)
4-PIN
(G24q, GX24q)
18-39 W
pg 2 of 4
INSTALLATION INSTRUCTIONS
Exit and Emergency Lighting
EMERGENCY BALLAST AND AC BALLAST MUST BE FED FROM THE SAME BRANCH CIRCUIT.
TYPICAL SCHEMATICS ONLY. MAY BE USED WITH OTHER BALLASTS. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS.
WIRING DIAGRAMS FOR ONE-LAMP EMERGENCY OPERATION
A. ONE (1) LAMP INSTANT START BALLAST
B. ONE (1) LAMP RAPID START BALLAST
REFER TO TABLE 1
BROWN
BLACK
LINE
BLUE
WHITE
BROWN
BLUE
ORANGE
277V
BLUE/WHITE
BLACK
WHITE
VIOLET (+)
BROWN (-)
120V
EMERGENCY
BALLAST
YELLOW/GREEN
AC
BALLAST
RED
REFER TO TABLE 1
BROWN
YELLOW
RED
LINE
BLACK
BLUE
BLUE
WHITE
BLUE
RED
RED
BLUE/WHITE
YELLOW
YELLOW/GREEN
CAP UNUSED LEAD
AC
BALLAST
BATTERY
CONNECTOR
BROWN
BLACK
BLUE
WHITE
BLUE
TO UNSWITCHED AC
CAP UNUSED LEAD
CHARGING
INDICATOR
LIGHT
RED
YELLOW/GREEN
YELLOW
RED
REFER TO TABLE 1
EMERGENCY
BALLAST
ORANGE
277V
BLACK
WHITE
VIOLET (+)
BROWN (-)
120V
WHITE
BATTERY
CONNECTOR
COM
TO UNSWITCHED AC
LINE
CAP UNUSED LEAD
BLACK
BLUE
BLUE
WHITE
BLUE
RED
RED
BLUE/WHITE
YELLOW
AC
BALLAST
YELLOW
YELLOW
YELLOW/GREEN
BROWN
EMERGENCY
BALLAST
RED
CHARGING
INDICATOR
LIGHT
ORANGE
277V
BLACK
120V
WHITE
VIOLET (+)
BROWN (-)
COM
WHITE
RED
BATTERY
CONNECTOR
LAMP 1
TO UNSWITCHED AC
CAP UNUSED LEAD
CHARGING
INDICATOR
LIGHT
LAMP 2 (EMERGENCY)
LAMP 2 (EMERGENCY)
F. FOUR (4) LAMP INSTANT START BALLAST
E. THREE (3) LAMP INSTANT START BALLAST
REFER TO TABLE 1
REFER TO TABLE 1
BROWN
AC
BALLAST
COM
WHITE
BROWN
BLUE
BLUE/WHITE
LAMP 1
BLACK
120V
WHITE
VIOLET (+)
VIOLET (-)
BATTERY
CONNECTOR
BROWN
RED
WHITE
277V
BLACK
D. TWO (2) LAMP RAPID START BALLAST
REFER TO TABLE 1
LINE
ORANGE
LAMP
C. TWO (2) LAMP INSTANT START BALLAST
AC
BALLAST
EMERGENCY
BALLAST
RED
LAMP
LINE
BROWN
RED
CHARGING
INDICATOR
LIGHT
WHITE
RED
COM
TO UNSWITCHED AC
BLUE
BLUE
BLUE
BLUE/WHITE
BLUE
YELLOW/GREEN
RED
OR
YELLOW
YELLOW
RED
BROWN
BROWN
EMERGENCY
BALLAST
ORANGE
277V
BLACK
WHITE
VIOLET (+)
BROWN (-)
120V
WHITE
RED
BATTERY
CONNECTOR
LAMP 1
COM
TO UNSWITCHED AC
LINE
BLACK
BLUE
BLUE
WHITE
BLUE
RED
RED
BLUE/WHITE
YELLOW
YELLOW
CAP UNUSED LEAD
AC
BALLAST
YELLOW/GREEN
YELLOW
BROWN
EMERGENCY
BALLAST
RED
CHARGING
INDICATOR
LIGHT
ORANGE
277V
BLACK
120V
WHITE
VIOLET (+)
BROWN (-)
COM
WHITE
RED
BATTERY
CONNECTOR
LAMP 1
TO UNSWITCHED AC
CAP UNUSED LEAD
CHARGING
INDICATOR
LIGHT
LAMP 2
LAMP 2
LAMP 3
LAMP 3 (EMERGENCY)
LAMP 4 (EMERGENCY)
WIRING DIAGRAMS FOR TWO-LAMP EMERGENCY OPERATION (2'-4', 17-40 W LAMPS ONLY)
H. TWO (2) LAMP RAPID START BALLAST
G. TWO (2) LAMP INSTANT START BALLAST
REFER TO TABLE 1
REFER TO TABLE 1
BROWN
BLACK
LINE
WHITE
AC
BALLAST
BLUE
BLUE
BLUE
RED
YELLOW/GREEN
RED
BLUE/WHITE
YELLOW
BROWN
BROWN
EMERGENCY
BALLAST
ORANGE
277V
BLACK
WHITE
VIOLET (+)
BROWN (-)
120V
WHITE
RED
BATTERY
CONNECTOR
LAMP 1
COM
TO UNSWITCHED AC
LINE
BLACK
BLUE
BLUE
WHITE
BLUE
BLUE/WHITE
RED
RED
YELLOW
YELLOW
CAP UNUSED LEAD
YELLOW
AC
BALLAST
BROWN
EMERGENCY
BALLAST
RED
YELLOW/GREEN
277V
BLACK
120V
WHITE
VIOLET (+)
BROWN (-)
COM
WHITE
RED
CHARGING
INDICATOR
LIGHT
ORANGE
BATTERY
CONNECTOR
TO UNSWITCHED AC
CAP UNUSED LEAD
CHARGING
INDICATOR
LIGHT
LAMP 1
LAMP 2
LAMP 2
J. THREE (3) LAMP RAPID START BALLAST
I. THREE (3) LAMP INSTANT START BALLAST
REFER TO TABLE 1
REFER TO TABLE 1
BROWN
BLACK
LINE
WHITE
AC
BALLAST
BLUE
BLUE
BLUE
BLUE
RED
BLUE/WHITE
YELLOW/GREEN
YELLOW
RED
OR
YELLOW
BROWN
BROWN
EMERGENCY
BALLAST
ORANGE
277V
BLACK
120V
WHITE
VIOLET (+)
BROWN (-)
COM
WHITE
RED
BATTERY
CONNECTOR
BLACK
TO UNSWITCHED AC
CAP UNUSED LEAD
CHARGING
INDICATOR
LIGHT
LINE
WHITE
BLUE/WHITE
BLUE/WHITE
RED
RED
AC
BALLAST
BLUE
BLUE
BLUE
BLUE/WHITE
YELLOW
YELLOW/GREEN
YELLOW
YELLOW
RED
BROWN
EMERGENCY
BALLAST
RED
LAMP 1
LAMP 1
LAMP 2 (EMERGENCY)
LAMP 2 (EMERGENCY)
LAMP 3 (EMERGENCY)
BATTERY
CONNECTOR
ORANGE
277V
BLACK
WHITE
VIOLET (+)
BROWN (-)
120V
WHITE
COM
TO UNSWITCHED AC
CAP UNUSED LEAD
CHARGING
INDICATOR
LIGHT
LAMP 3 (EMERGENCY)
K. FOUR (4) LAMP INSTANT START BALLAST
REFER TO TABLE 1
BROWN
LINE
BLACK
BLUE
BLUE
WHITE
BLUE
RED
RED
RED
BLUE/WHITE
YELLOW
YELLOW
AC
BALLAST
YELLOW/GREEN
BROWN
EMERGENCY
BALLAST
YELLOW
RED
LAMP 1
BATTERY
CONNECTOR
ORANGE
277V
BLACK
120V
WHITE
VIOLET (+)
BROWN (-)
COM
WHITE
TO UNSWITCHED AC
CAP UNUSED LEAD
CHARGING
INDICATOR
LIGHT
LAMP 2
LAMP 3 (EMERGENCY)
LAMP 4 (EMERGENCY)
pg 3 of 4
INSTALLATION INSTRUCTIONS
Exit and Emergency Lighting
R-1
EMERGENCY BALLAST AND AC BALLAST MUST BE FED FROM THE SAME BRANCH CIRCUIT.
TYPICAL SCHEMATICS ONLY. MAY BE USED WITH OTHER BALLASTS. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS.
WIRING DIAGRAMS FOR EMERGENCY-ONLY FIXTURES
L. ONE (1) 17-110 W LAMP WITHOUT AC BALLAST
M. TWO (2) 17-40 W LAMPS WITHOUT BALLAST
REFER TO TABLE 1
BROWN
CAP
]
CAP
]
REFER TO TABLE 1
BROWN
BROWN
BLUE
ORANGE
277V
BLUE/WHITE
BLACK
120V
YELLOW
YELLOW/GREEN
RED
EMERGENCY
BALLAST
RED
BATTERY
CONNECTOR
LAMP
WHITE
VIOLET (+)
BROWN (-)
WHITE
COM
TO UNSWITCHED AC
CAP UNUSED LEAD
CAP
]
CAP
]
BROWN
BLUE
BLUE/WHITE
YELLOW
YELLOW/GREEN
RED
CHARGING
INDICATOR
LIGHT
EMERGENCY
BALLAST
ORANGE
277V
BLACK
120V
WHITE
VIOLET (+)
BROWN (-)
COM
WHITE
RED
BATTERY
CONNECTOR
TO UNSWITCHED AC
CAP UNUSED LEAD
CHARGING
INDICATOR
LIGHT
LAMP 1
LAMP 2
© 2005 Juno
Printed in USA
Rev 08/05
P0097
pg 4 of 4
WARRANTY
Juno Lighting Group warrants that its products are free from defects in material and workmanship. Juno Lighting Group’s obligation
is expressly limited to repair or replacement, without charge, at Juno Lighting Group’s factory after prior written return authorization
has been granted. This warranty shall not apply to products which have been altered or repaired outside of Juno Lighting Group’s
factory. This warranty is in lieu of all other warranties, expressed or implied, and without limiting the generality of the foregoing phrase,
excludes any implied warranty of merchantability. Also, there are no warranties which extend beyond the description of the product