HID Coach Style Luminaire

advertisement
TITLE:
Engineering Specification
RECOMMENDED:
S. Edey
APPROVED:
D. O’Keefe
REV. DATE:
2010-01-07
NO:
1
LLS0001
City of Ottawa Street Lighting
HID Coach Style Luminaire
© For City of Ottawa Use Only
OF
9
REV:
5
REVISION SHEET
REVISION
DESCRIPTION
DATE
1
Add Lumec LU40,
adapter brackets, and Nema
Labelling.
Text and Drawing
2005-02-24
2
Title renamed
General Conditions & Electrical
Characteristics referenced in separate
specification
Light distribution: removed M-SCO-III
& bulb type
2006-01-15
csm jb
3
Associated Standard Drawings
identified (11.0)
Revised Marking (4.6.4)
Added reference to electrical
characteristics (4.12)
2007-01-15
jb
4
Included Full Cutoff & Type III (4.10)
2007-12-05
jb
5
Approval and Recommended
authorization changed
2010-01-07
© For City of Ottawa Use Only
LLS0001 Rev.5
INITIAL
csm/jb
se
do
Page 2 of 9
TABLE OF CONTENTS
1.0
1.1
GENERAL ......................................................................................................................... 4
SCOPE .............................................................................................................................. 4
2.0
REFERENCE STANDARDS .......................................................................................... 4
3.0
APPROVAL OF SOURCE .............................................................................................. 4
4.0
PHYSICAL CHARACTERISTICS ................................................................................ 4
4.1
4.2
4.3
4.4
4.5
4.6
4.7
4.8
4.9
4.10
4.11
4.12
MOUNTING ARRANGEMENTS ........................................................................................... 4
TERMINAL BLOCK AND GROUND LUG ............................................................................. 5
CONNECTION DIAGRAM ................................................................................................... 5
BALLAST, STARTER AND CAPACITORS ............................................................................. 5
LAMP SOCKET.................................................................................................................. 5
MARKING ......................................................................................................................... 5
HOUSING .......................................................................................................................... 6
TWIST LOCK RECEPTACLE ............................................................................................... 6
REFRACTOR PANELS ........................................................................................................ 6
LIGHT DISTRIBUTION PATTERN ....................................................................................... 6
COLOUR AND FINISHING .................................................................................................. 6
ELECTRICAL CHARACTERISTICS ...................................................................................... 6
5.0
INSPECTION.................................................................................................................... 6
6.0
PACKAGING AND SHIPPING ...................................................................................... 7
7.0
WARRANTY..................................................................................................................... 7
8.0
INSTRUCTIONS TO BIDDERS .................................................................................... 7
8.1
8.2
8.3
8.4
8.5
GENERAL ......................................................................................................................... 7
EXCEPTIONS ..................................................................................................................... 7
MODIFICATIONS ............................................................................................................... 7
TECHNICAL INFORMATION REQUESTED ........................................................................... 7
SAMPLES .......................................................................................................................... 8
9.0
MAINTENANCE PARTS ................................................................................................ 8
10.0
INFORMATION SUPPLIED TO THE BIDDER ......................................................... 9
11.0
DRAWINGS ...................................................................................................................... 9
© For City of Ottawa Use Only
LLS0001 Rev.5
Page 3 of 9
1.0 General
1.1
Scope
This specification covers the supply of High Pressure Sodium (HPS) luminaires complete with
integral ballast for post-top and side mounting. This specification shall be read in conjunction
with engineering specification LGC0001 and LLS0005.
2.0 Reference Standards
Luminaires shall comply with all applicable requirements in the latest issues of the following
standards:
ANSI/IES RP-8
ANSI Standard C78.1353
ANSI Standard C78.1354
ANSI Standard C78.1355
ANSI Standard C82.9
ANSI Standard C136.10
Roadway Lighting
Specifications for 70W S62 High Pressure Sodium Lamps
Specifications for 100W S54 High Pressure Sodium Lamps
Specifications for 150W S55 High Pressure Sodium Lamps
Definitions for HID Lamp Ballasts and Transformers
Lock-type Photocontrol Devices and Mating Receptacles
Physical and Electrical Interchangeability and Testing
ANSI Standard C136.15
Field Identification of High Intensity Discharge Lamps in
Luminaires
CSA Standard C22.2, No.9
Luminaires
CSA Standard C22.2, No. 43 Lamp holders
CSA Standard C22.2, No. 74 Equipment for use with Electric Discharge Lamps
CSA Standard C22.2, No. 97 Outdoor and Submersible Floodlights
CSA Standard C164
Hot Dip Galvanizing of Irregularly Shaped Articles
CSA Standard C653
Performance Standards for Roadway Lighting Luminaires
NEMA Standard OD150-1977 Field Identification of High-Intensity Discharge Lamps in
Luminaires used in Roadway Lighting Equipment.
3.0 Approval Of Source
Luminaires supplied to this specification shall be supplied only by manufacturers approved by the
City of Ottawa or its agent. Only luminaires evaluated and approved by the City of Ottawa or its
agent before or at the time a quotation is submitted will be accepted.
Luminaires supplied shall be of the same construction as the sample luminaire currently approved
by the City of Ottawa or its agent and, once approved, the supplier shall not change material, type
or source or production method without prior approval from the City of Ottawa or its agent.
4.0 Physical Characteristics
4.1
Mounting Arrangements
Slipfitter
The luminaire shall be designed with an integral slipfitter to accommodate a 76 mm OD by 64
mm tenon and provided with three ¼” - 20 set screws to secure the luminaire to the tenon.
© For City of Ottawa Use Only
LLS0001 Rev.5
Page 4 of 9
An adapter is required to mount the L40U to the standard 76mm tenon on the street lighting pole.
Side Mounted
The luminaire shall be designed to accept a scroll arm bracket. Refer to engineering specification
XBS0001.
4.2
Terminal Block and Ground Lug
A terminal block shall be provided and so placed that connection of No. 14 AWG solid copper
supply wires to it will be convenient and easy to make without special tools. In addition, a ground
lug shall be placed so that connection to it with a No. 14 AWG solid copper ground wire can be
made easily without special tools.
4.3
Connection Diagram
A connection diagram of a permanent material shall be located so as to be easily visible when
making connections.
4.4
Ballast, Starter and Capacitors
The ballast, starter and capacitors shall be mounted within the luminaire so that replacement may
be achieved easily. Further, special precautions in the form of spacing and barriers shall be taken
to shield the components from heat emitted by the lamp. Capacitors shall be non-PCB and
permanently marked "Non-PCB".
4.5
Lamp Socket
The standard lamp socket shall be a mogul screw base made from cold moulded porcelain and
pulse rated for HPS operation. The shell shall be nickel-plated with dimples or slots to prevent the
lamp loosening with vibration and shall be secured to the socket using a machine screw and nut
combination. The centre contact shall be nickel-plated and spring-loaded for positive contact.
4.6
Marking
4.6.1
Each luminaire shall have a permanent type nameplate indicating the manufacturers
name, catalogue/model number, wattage, supply voltage and frequency, input current and
year of manufacture. This nameplate may be a metallic nameplate attached to the
luminaire with self-tapping screws or alternatively a high quality stick-on foil type label
providing that the foil label is installed at the place of manufacture under quality
controlled conditions and will not fade, chip, peal or otherwise deteriorate under normal
service conditions.
4.6.2
A permanent label including a wiring diagram and stating ballast type and compatible
starter number and capacitor value shall be provided and attached to the ballast or interior
of the luminaire so that it is clearly visible during maintenance operations.
4.6.3
Labels identifying "House Side" and/or "Street Side" shall be affixed inside the
luminaire so they are clearly visible during installation and maintenance.
4.6.4
Each luminaire shall have an exterior identification marker affixed to the underside of the
luminaire near the bracket that would be visible from the ground and indicate the size of
© For City of Ottawa Use Only
LLS0001 Rev.5
Page 5 of 9
lamp used in the luminaire. When an underside location is not appropriate, a selfadhesive label is to be supplied with the fixture and attached in the location directed by
the City of Ottawa Street Light agent.
4.7
Housing
The luminaire housing/refractor assembly shall be designed and fabricated to prevent the ingress
of moisture, insects and other foreign material.
Suitable gaskets and filters shall be provided to minimize the accumulation of dirt on the lamp
reflector and refractor panels. Removable covers shall be firmly secured from under side of cover
but easily removed to allow access to the lamp socket, ballast, terminal block and ground
connector for field servicing.
4.8
Twist Lock Receptacle
The luminaire shall be equipped with a twist lock receptacle for a photoelectric controller. When
installed, the photoelectric controller shall be adjustable for a north-facing window and be
concealed within an imitation smoke chimney on top of the luminaire.
4.9
Refractor Panels
The refractor panels shall be heat-resistant acrylic, either clear or translucent white so as not to
distort the colour of the light.
4.10 Light Distribution Pattern
Luminaires shall be adjusted at the factory for a MSCO-II, MSCO-III, MFCO-II or MFCO-III
light distribution pattern. Lamp wattages are to be 70W, 100W, or 150W.
4.11 Colour and Finishing
Except for the refractor panels, all visible parts of the luminaire shall be finished with Black
Epoxy Baking Enamel. Permanent black anodizing to match is acceptable for aluminium parts.
Surfaces and edges shall be smooth and free from burrs and sharp corners
4.12 Electrical Characteristics
Refer to LLS0005.
5.0 Inspection
The City of Ottawa or its agent reserves the right to request and be granted permission to visit the
manufacturer's plant to inspect the luminaires and manufacturing methods during assembly and
testing.
© For City of Ottawa Use Only
LLS0001 Rev.5
Page 6 of 9
6.0 Packaging And Shipping
Luminaires shall be shipped complete, suitably packaged to ensure all parts are delivered as an
entity.
The supplier shall advise the City of Ottawa or its agent Purchasing Department three days prior
to his shipping date of his intent to deliver.
7.0 Warranty
The manufacturer shall warrant that the luminaires furnished by him conform to all the
requirements and conditions of this specification. The manufacture shall remedy, at no expense
to the City of Ottawa or its agent, defects due to faulty workmanship, material or design for the
period of one year after installation of the luminaires, but in no case for more than two years
after receipt of the units by the City of Ottawa or its agent.
8.0 Instructions To Bidders
8.1
General
Suppliers shall submit with their tenders the technical information requested herein. Suppliers
who fail to provide the information requested might have their tenders rejected as incomplete.
8.2
Exceptions
Where the tender is not in complete accordance with the requirements of this specification, the
supplier shall submit a detailed list specifically outlining the exceptions or changes. If such a list
is not provided, it will be understood that the supplier shall comply with all the requirements.
8.3
Modifications
The supplier shall also submit a list of any changes in the design, components, construction or
materials employed if the luminaires of the type being quoted differ from these previously
approved by the City of Ottawa or its agent. Failure to notify the City of Ottawa or its agent of
such changes when tendering may constitute sufficient reason to reject the tender.
8.4
Technical Information Requested
8.4.1
Manufacturer's Reference
a) Catalogue number of the luminaire
b) Catalogue number and manufacturer of major components including ballast, starter,
capacitor and refractor panels
8.4.2
Photometric Performance
a) Isocandela diagram
b) Iso-lux (iso-foot candle) diagram and utilization data.
© For City of Ottawa Use Only
LLS0001 Rev.5
Page 7 of 9
c) Vertical candlepower distribution curve
d) Luminaire maintenance factor (suggested by manufacturer)
8.4.3
Mechanical Characteristics
a) Dead weight
b) Effective projected area of luminaire
c) Gasket/filter mechanisms for preventing dirt build-up on the lamp, reflector and
refractor panels
d) Types of finishes applied to various parts
8.4.4
Electrical Characteristics and Performance (Rated Supply Voltage Assumed)
a)
b)
c)
d)
e)
f)
g)
h)
i)
j)
8.5
Under open circuit condition, ballast input current and lamp voltage (O.C.V.)
Inrush current on striking of arc
Normal or operating ballast input and lamp currents and maximum values of same
Normal or operating ballast lamp voltage
Variation in lamp wattage for rated supply voltage variation
Ballast power factor
Nominal ballast supply voltage
Input watts and losses
Rated Life of ballast
Ballast trapezoidal drawings
8.4.5
Luminaire drawings and ballast schematic drawing.
8.4.6
Quality control program carried out by manufacturer including description of tests and
sampling plan.
Samples
Unless the luminaire being proposed has been previously approved by the City of Ottawa or its
agent, the supplier shall provide a sample identical in every way to the units tendered. Samples
will be returned to the supplier after evaluation.
9.0 Maintenance Parts
Suppliers are requested to quote on the following maintenance parts or components:
a)
b)
c)
Ballast Kit, including ballast, capacitor, starter, and PEC receptacle prewired with
interconnecting wiring and mounting hardware as required by this specification
Refractor panels
Starter
© For City of Ottawa Use Only
LLS0001 Rev.5
Page 8 of 9
10.0 Information Supplied To The Bidder
The following minimum information will be supplied to the bidders when requesting a quotation:
a)
b)
c)
d)
Quantity
Lamp wattage
Light distribution pattern, if other than as specified in Section 4.10
Input voltage of ballast, if other than as specified in specification LLS0005
11.0 Drawings
LLD0001, LLD0006, LLD0008.
© For City of Ottawa Use Only
LLS0001 Rev.5
Page 9 of 9