Current Switches: Adjustable Trip Point

advertisement
CURRENT MONITORING
DETECT BELT LOSS, COUPLING SHEAR, AND
MECHANICAL FAILURE
5Year
Warranty
H308
Smallest in the industry (patent pending)
H608
Small split-core housing is great for retrofits
Current Switches: Adjustable
Trip Point, Standard Output
Hx08 Series and H701 current switches offer high
performance, with a wide array of amperage range
options. These products can accurately detect belt
loss, coupling shear, or other mechanical failure on
loads from 1/5 to 100HP.
High performance devices in split- and solid-core
housings
 Minimum trip point as low as 0.5A (H608)...
eliminates the need for multiple wraps of the
conductor through the sensor even on loads as
small as 1/5HP
APPLICATIONS
 Small size...fits easily inside small enclosures
 Detecting belt loss, coupling shear, and
 Self-gripping iris on the split-core housing for
mechanical failure
easy installation
 Verifying lighting circuit and other electrical
 Status LEDs for easy setup and local indication
service run times
(no LED on the H701)
 Monitoring status of industrial process equipment  Bracket on H908 can be installed in three
different configurations
 Monitoring status of critical motors (compressor,
fuel, etc.)
 1 Amp status output for increased application
flexibility
 All devices are 100% solid state and polarity
insensitive, with a 5-year warranty
H701
Calibrated
Trip
Point Off
Economy solid-core model with no LEDs
H708
Fan/pump
On
Electrical
failure
Loss of belt/coupling shear
Off
Now you can easily detect when drive belts slip,
break, or pump couplings shear. In fact, a typical
HVAC motor that loses its load has a reduction of
current draw of up to 50%. That's why our sensors
are the industry standard for status.
Maximize Reliability
Minimize Installed Cost
Adjustable mounting bracket makes installing easy
H808
SPECIFICATIONS
Low 0.75A threshold, Ideal for small motor monitoring
H908
High amperage range in a split-core housing
22
800.354.8556
Sensor Power
Insulation Class
Frequency Range
Temperature Range
Humidity Range
Hysteresis
Terminal Block Maximum Wire Size
Terminal Block Torque (nominal)
Agency Approvals
Induced from monitored conductor
600VAC RMS (UL), 300VAC RMS (CE)
50/60 Hz
-15° to 60°C (5° to 140°F)
10-90% RH, non-condensing
10% (typical)
14 AWG (16 AWG for H308)
4 in-lbs (7 in-lbs for H308)
UL 508 open device listing
CE: EN61010-1:2001-02, CAT III, deg. 2, basic insulation
Do not use the LED status indicators as evidence of applied voltage.
For applications requiring double or reinforced insulation, please contact the factory.
503.598.4564
www.veris.com
©2008 Veris Industries
CURRENT MONITORING
DIMENSIONAL DRAWINGS
H608
H808
Removable Mounting Bracket
Removable/Adjustable Mounting Bracket
H308
0.6"
(16 mm)
1.6”
(40 mm)
0.7"
(18 mm)
2.1"
(54 mm)
2.5" *
(64 mm)
0.5"
(13 mm)
0.4” x 0.2”
Slot (x2)
APPLICATION/WIRING EXAMPLE
H908
Removable/Adjustable Mounting Bracket
Monitoring Fan /Pump Motors for
Positive Proof of Flow
Removable Mounting Bracket
0.9"
(23 mm)
1.0”
(25 mm)
1.1”
(26 mm)
*
1.1" * *
(27 mm)
2.3"
(58 mm)
2.9"
(74 mm)
3.5"
(89 mm)
H708/701
* 3.1”
(79 mm)
*
1.7
(43 mm)
1.0" * *
(26 mm)
0.4” x 0.2”
(10 mm x 5 mm)
Slot (2x)
3.0"
(75 mm)
2.8" *
(71 mm)
*
2.1"
(54 mm)
0.7" Dia
(19 mm)
0.9"
(23 mm)
ø 0.7"
(18 mm)
1.2"
(31 mm)
Bracket can be mounted
on either side for added
installation flexibility.
0.8”
(21 mm)
CONTACTOR
CONTROLLER
DI
9
2.8"
(68 mm)
2.8”
(70 mm)
1.1" *
(27 mm)
0.2” x 0.15”
slot (2x)
Self-gripping
Iris
3.8"
(95 mm)
4.2"
(106 mm)
1.4”
(36 mm)
Ø = 0.3”
(8 mm)
Fan or Pump
*
2.5”
(64 mm)
3.0”
(76 mm)
Motor
* Terminal block may extend up to 1/8” over the height
dimensions shown.
RoHS
ORDERING INFORMATION
MODEL AMPERAGE RANGE
H308
Compliant
STATUS OUTPUT (max.)
0.75 - 50A
H608
0.50 - 175A
H701
1 - 135A
H708
1 - 135A
H808
H908
MIN. TRIP POINT
0.75A or less
HOUSING STATUS LED
Split-Core
0.5A or less
Split-Core
1.0A or less
Solid-Core
1.0A or less
Solid-Core
0.75 - 50A
0.75A or less
Solid-Core
2.5 - 135A
2.5A or less
Split-Core
N.O. 1.0A@30VAC/DC
For high voltage outputs, see page 24
n
n
1
2
UL
CE
n
n
n
1
RoHS
2
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
Listed for use on 75°C insulated conductors.
Product provides functional insulation only.
ACCESSORIES
DIN Rail Clip Set, DIN Rail, and DIN Stop Clip...see page 219.
800.354.8556
503.598.4564
www.veris.com
©2008 Veris Industries
23
Download