PRODUCT NOTICE
Notice of Potential Product Concern
Rockwell Automation issues a Product Notice when it identifies a product(s) anomaly that may cause commercial or customer
satisfaction concerns.
CENTERLINE 2100 and CENTERLINE 2500 LVMCC
140G J-Frame Breaker with Incorrect Settings
Reference: 2015-03-001
Revision: A
Date:
March 2015
Revision A / March 2015 – This document has been revised to include the CENTERLINE 2500 LVMCC products.
Please read this revised document in its entirety.
This Product Notice informs you of a potential anomaly that exists with the CENTERLINE 2100 and CENTERLINE
2500 LVMCC using the 140G J-Frame circuit breaker. Breaker trip unit dip switches may not be correctly set to the
required product configuration. A required 225A setting may have been shipped as 250A.
PRODUCT NOTICE
Page 2 of 5
– Product Identification –
The affected products are the CENTERLINE 2100 and CENTERLINE 2500 LVMCC using 140G J-Frame Breakers.
CENTERLINE 2100 LVMCC 225A systems, unit catalog numbers 2193-C_C-46TJML and 2193-C_C-46TJXL:
 Systems using the 140G J-Frame circuit breaker catalog numbers 140G-J0H3-D25, 140G-J6H3-D25, 140GJ0X3, 140G-J6X3, and 140G-JTH3-D25.
 Systems shipped between February 1, 2014, and February 13, 2015.
CENTERLINE 2500 LVMCC 225A systems:
 Systems using the 140G J-Frame circuit breaker catalog numbers 140G-J0H3-D25, 140G-J6H3-D25, 140GJ0X3, 140G-J6X3, and 140G-JTH3-D25.
 Systems shipped between February 1, 2014, and February 13, 2015.
Affected product will be incorrectly set to 250A instead of the required 225A settings.
Important – This notification addresses standard system configurations preset to 225A. Systems configured to nonstandard specifications should consult product documentation to ensure as-shipped settings are correct. Customers
are advised to verify the trip settings on all circuit breakers prior to system start-up.
– Description –
A potential anomaly exists with the CENTERLINE 2100 and CENTERLINE 2500 LVMCC using the 140G J-Frame
circuit breaker. Breaker trip unit dip switches may not be correctly set to the required product configuration. A
required 225A setting may have been shipped as 250A.
– Temporary Workarounds –
No workaround has been identified. Switch settings must be set as described in the Correction section of this
document.
– Correction –
ATTENTION: Only skilled personnel should oversee the maintenance and servicing of motor
control centers. Equipment must be shut down and locked-out tagged-out prior to servicing. Be
sure to follow industry standard safety guidelines, including the use of appropriate personal
protective equipment (PPE). Follow NFPA 70E requirements.
Product as shipped from the factory may have been set to the breaker trip rating default of 250A. Most product
specifications require this setting be changed to 225A.
PRODUCT NOTICE
Page 3 of 5
To prevent electric shock, disconnect equipment from power source
before servicing.
The “L” dip switches on the trip unit of the circuit breaker should be set
as shown in the image at the left. This will set the trip rating to the
required 225A. Dip switch settings should be changed using a small,
non-metallic tool.
General information on configuring this breaker may also be found in
Rockwell Automation publication 140G-IN100A-MU, available for
download from the Rockwell Automation Literature Library. A copy of
this document is attached at the end of this notification for your
reference.
If your system requires a different trip rating for this breaker, please refer to your product documentation for details.
Important – On a small number of systems, the 140G-J breaker may have been shipped with an incorrect trip unit
label that covers the “L” dip switch settings not allowing you access to set the trip rating. If you have a system with
the incorrect label, contact Rockwell Automation Technical Support and reference this Product Notice 2015-03-001.
140G-J breakers potentially affected with this label anomaly include catalog numbers 140G-J0H3-D25, 140G-J6H3D25, 140G-J0X3, 140G-J6X3, and 140G-JTH3-D25.
– Requested Customer Action –
Rockwell Automation requests you take the following actions:




Check if you have a product affected by this Product Notice. Refer to the Product Identification and
Description sections of this document for product identification assistance.
Verify breaker trip unit settings as described in the Correction section of this document.
If you need additional assistance, please contact Rockwell Automation Technical Support. See Appendix A
for local telephone numbers. Customers without TechConnect contracts should reference this Product Notice
PN 2015-03-001 when calling.
Customers with TechConnect contracts may be able to chat online with support representatives. Reference
this Product Notice when connected to a support engineer.
The most current version of this Product Notice is posted on the Rockwell Automation Support Center,
http://www.rockwellautomation.com/knowledgebase, as ID number 674031. Additional languages may also
be available at the end of this article attached as downloadable PDF documents.
Customers using the Rockwell Automation Support Center in a non-English language should search for the
document by the article ID number listed above. The resulting article ID for non-English postings may be different
than the listed article ID number.
If this Product Notice does not affect you because you do not have the products any longer, or if you are a Distributor,
Rockwell Automation asks that you forward a copy of this notice, with any identifying documentation, immediately to
PRODUCT NOTICE
Page 4 of 5
the person or company that now has the product. We also ask that you contact Rockwell Automation Technical
Support and provide the location of the affected units.
We appreciate your immediate cooperation. If you have any questions, please contact us.
Sincerely,
ROCKWELL AUTOMATION
You can register for Automatic Product Safety Advisories and Product Notices from Rockwell Automation by email.
Go to the Support web page at http://www.rockwellautomation.com/support and click the Visit the Technical Support
Center link. Sign in with your Tech Connect Account or free Rockwell Automation Member Account and you can
subscribe to important product updates, including Product Safety Advisories and Product Notices.
PRODUCT NOTICE
Page 5 of 5
Appendix A
Regional Technical Support Information
The following list can help you to contact the correct technical support center for your location. If your country is not listed, you
can find a customer support number for your location on http://www.rockwellautomation.com/support/ by clicking Get Support
Now, selecting your country, and clicking the Phone/OnSite Support tab.
Region / Country
Asia/Pacific
Australia
China
Hong Kong
India
Japan
Korea
Malaysia
New Zealand
Taiwan
Thailand
Caribbean
All Countries
Central America
Argentina
Belize
Bolivia
Brazil
Chile
Colombia
Costa Rica
Ecuador
El Salvador
Guatemala
Honduras
Mexico
Nicaragua
Panama
Paraguay
Peru
Suriname
Uruguay
Venezuela
Phone Number
( ) International Code
1 800 762 593
400 620 6620
+852 2887 4666
1 800 2000 121
03 3206 2785
(82) 2 2188 4400
1 800 80 4851
0800 27 27 25
080 902 0908
(66) 2936 1500
Region / Country
Europe
Austria
Belgium
Czech Republic
Denmark
Finland
France
Germany
Hungary
Ireland
Italy (Brescia, Milano e Padova)
Italy (Bologna,Firenze,Napoli,
Roma e Torino)
(1) 440 646 3650
800.666.0320
(1) 440 646 3650
(54) 800 10 0632
(55) 11 5189 9500
800.53.0012
01.800.700.2107
0800.013.1215
58.212.949.0611
(52) 55 5246 2010
(52) 55 5246 2010
(52) 55 5246 2010
001.888.365.8677
(52) 55 5246 2010
001.800.203.3475
(54) 11 5554 4000
0800.535.36
(1) 440 646 3650
(54) 11 5554 4000
800.1.00.3062
Morocco
Netherlands
Poland
Portugal
Slovakia
Spain
Sweden
Switzerland (German)
Switzerland (French)
Switzerland (Italian)
United Kingdom
North America
Canada
United States
If you have a TechConnect Contract, please use the telephone number supplied to you with the contract.
Phone Number
( ) International Code
(49) 211 41553 664
(32) 2 716 8411
(420) 28401 5911
(45) 43 466 006
(358) 958 447 419
(33) 825303132
(49) 211 41553 664
(420) 28401 5911
(44) 01908 635245
(39) 199 11 99 00
(39) 199 11 99 22
(33) 825303132
(31) 10 266 55 80
(48) 22 32 60 707
(1) 440 646 3223
(420) 284015911
(34) 902 30 93 30
(46) 46 19 93 91
(41) 0844 84 84 11
(41) 0844 84 84 12
(41) 0844 84 84 13
(44) 01908 635245
(1) 440-646-3223
(1) 440-646-3223
Bul. 140G
140G-HT_, 140G-J-HT_
LSI-LSIG Adjustment instructions for 140G-H, 140G-J
Sganciatori LSI e LSIG
Auslöser LSI und LSIG
Dèclencheur LSI et LSIG
Relé LSI y LSIG
Installation - Installazione - Instalación
Instalação WARNING: To prevent electrical shock, disconnect from power source before
installing or servicing. Install in suitable enclosure. Keep free from contaminants.
(Follow NFPA70E requirements).
AVVERTENZA: Per prevenire infortuni, togliere tensione prima dell'installazione o
manutenzione. Installare in custodia idonea. Tenere lontano da contaminanti.
(Seguire i requisiti NFPA70E).
WARNUNG: Vor Installations- oder Servicearbeiten Stromversorgung zur
Vermeidung von elektrischen Unfällen trennen. Die Geräte müssen in einem
passenden Gehäuse eingebaut und gegen Verschmutzung geschützt werden. (Befolgen
Sie die Anforderungen nach NFPA70E).
AVERTISSEMENT: Avant le montage et la mise en service, couper l'alimentation
secteur pour éviter toute décharge. Prévoir une mise en coffret ou armoire appropriée.
Protéger le produit contre les environnements agressifs. (Vous devez respecter la
norme NFPA70E).
ADVERTENCIA: Desconéctese de la corriente eléctrica, antes de la instalación o
del servicio, a fin de impedir sacudidas eléctricas. Instálelo en una caja apropiada.
Manténgalo libre de contaminantes. (Cumpla con los requisitos NFPA70E).
ATENÇÃO: Para evitar choques, desconectar da corrente elétrica antes de fazer a
instalação ou a manutenção. Instalar em caixa apropriada. Manter livre de
contaminantes. (Cumpra as exigências da norma NFPA70E).
140G-H
1
140G-J
CLACK
1
2
1
DIR 1000721R0506 (L5086)
2
Manual default setting
Settaggio di default manuale
Manuelle Default-Einstellung
Configuration par défauit manuelle
Ajuste de default manual
(Neutral setting on fig. 8)
LED
Color
CONDITION Run time
Green
L
S
G
Red
Red
Red
L|S |I|G
Red
LED Fixed = Device active
LED Fixed = L pre alarm (0,9 * I1 < I < 1,2 * I1)
LED Blinking = L alarm (I > 1,2 * I1)
LED Blinking = S alarm (I > I2)
LED Blinking = G alarm (I > I4)
LED Blinking = Parameters inconsistency - L = S or S = I.
LED Blinking without Parameters inconsistency = generic fault (please contact Rockwell Automation)
3
Example - Esempio - Beispiel - Exemple - Ejemplo
In = 100A
I1 = 100x(0,4+0,08+0,32)=80A
t1 = 12s @240A (3I1)
In (A)
25
60
140G-H 100
125
160
40
60
140G-J 100
150
250
*
0,4
10
24
40
50
64
16,0
24
40
60
100
0,42
10,5
25,2
42
53
67,2
16,8
25,2
42
63
105
I1 (In)
0,44 … 0,96
11
24
26
58
44
96
55
120
70,4
153,6
17,6
38,4
26,4
57,6
44
96
66
144
110
240
0,98
24,5
58,8
98
123
156,8
39,2
58,8
98
147
245
1
25
60
100
125
160
40
60
100
150
250
(*) IEC ONLY
4
Example - Esempio - Beispiel - Exemple - Ejemplo
In = 100A
I2 = 100x(1+2)=300A
2
t2 (I t=ON) = 0,1s @1000A (10In)
In (A)
25
60
140G-H 100
125
160
40
60
140G-J 100
150
250
*
1
25
60
100
125
160
40
60
100
150
250
1,5
37,5
90
150
188
240
60
90
150
225
375
2
50
120
200
250
320
80
120
200
300
500
2,5
62,5
150
250
313
400
100
150
250
375
625
3
75
180
300
375
480
120
180
300
450
750
3,5
87,5
210
350
438
560
140
210
350
525
875
4,5
113
270
450
563
720
180
270
450
675
1125
I2 (In)
5,5
138
330
550
688
880
220
330
550
825
1375
6,5
7
7,5
8
163
175
188 200
390 420 450 480
650 700
750 800
813
875 938 1000
1040 1120 1200 1280
260 280 300 320
390 420 450 480
650 700
750 800
975 1050 1125 1200
1625 1750 1875 2000
8,5
9
10
213 225 250
510
540 600
850 900 1000
1063 1125 1250
1360 1440 1600
340 360 400
510
540 600
850 900 1000
1275 1350 1500
2125 2250 2500
(*) IEC ONLY
DIR 1000721R0506 (L5086)
(2)
5
Example - Esempio - Beispiel - Exemple - Ejemplo
In = 100A
I3 = 100x(1,5+5,5)=700A
(*) IEC ONLY
In (A)
25
60
140G-H 100
125
160
40
60
140G-J 100
150
250
*
1
25
60
100
125
160
40
60
100
150
250
1,5
37,5
90
150
188
240
60
90
150
225
375
2
50
120
200
250
320
80
120
200
300
500
2,5
62,5
150
250
313
400
100
150
250
375
625
3
75
180
300
375
480
120
180
300
450
750
3,5
87,5
210
350
438
560
140
210
350
525
875
I3 (In)
4,5
5,5
113
138
270 330
450
550
563 688
720 880
180 220
270 330
450
550
675 825
1125 1375
6,5
7
7,5
8
163
175
188 200
390 420 450 480
650 700
750 800
813
875 938 1000
1040 1120 1200 1280
260 280 300 320
390 420 450 480
650 700
750 800
975 1050 1125 1200
1625 1750 1875 2000
6
8,5
9
10
213 225 250
510
540 600
850 900 1000
1063 1125 1250
1360 1440 1600
340 360 400
510
540 600
850 900 1000
1275 1350 1500
2125 2250 2500
Example - Esempio - Beispiel - Exemple - Ejemplo
In = 100A
I4 = 100x(0,2+0,25)=45A
t4 = 0,2s @ I>I4
In (A)
25
60
140G-H 100
125
160
40
60
140G-J 100
150
250
*
0,2
5
12
20
25
32
8
12
20
30
50
0,25
6,25
15
25
31,3
40
10
15
25
37,5
62,5
0,45
11,3
27
45
56,3
72
18
27
45
67,5
113
I4 (In)
0,55 0,75
13,8 18,8
33
45
55
75
68,8 93,8
88
120
22
30
33
45
55
75
82,5 113
138
188
0,8
20
48
80
100
128
32
48
80
120
200
1
25
60
100
125
160
40
60
100
150
250
(*) IEC ONLY
NEUTRAL SETTING
8
7
Neutral setting
3p
III
4p
IV
Always
by means
System
Bus Bus
Always
only byonly
means
of EkipofT&P
or System
Always only by means of dip switches
Default setting
ON; 100%
ON; 100%
Example - Esempio - Beispiel - Exemple - Ejemplo
Electronic default setting
Settaggio di default elettronico
elektronische Default Einstellung
Configuration par défaut
électronique
Ajuste de default electrónico
L
t1
S
I
G
1 x In
60 s
Off
4,5 x In
Off
DIR 1000721R0506 (L5086)
Dip switches setting example
with 4p:
Ne=ON; 50%
(Neutral setting on fig. 8)
(3)
9
1
DIAGNOSTIC PROCEED
- UNIT CHECK LED:
all the leds in the relay
must come on
- LAST TRIP INDICATION:
if present in the relay's
data store
- LED:
remains on for
as long as the 140G-ELTT
Tester is connected to
the relay
- READY TO TRIP
PROCEDURA DI CONTROLLO
- CONTROLLO LED:
tutti i led del relè si
devono accendere
- ULTIMA INDICAZIONE DI TRIP:
se presente nella memoria
del relè
- LED:
resta acceso finchè 140G-ELTT
Tester è connessa al relè
- PRONTO PER TRIP
DIAGISTIKABLAUF
- EINEITHSPRUF-LED:
Alle LEDs des Relais müssen
aufleuchten
- ANGABE DER LETZTEN AUSLOSUNG:
Wenn im Speicher des Relais
vorhanden.
- LED: Bleibt angeschaltet,
bis die Einheit 140G-ELTT Tester
an die Relais angeschlossen ist.
- AUSLOSEBEREIT
PROCÉDURE DE DIAGNOSTIC
- UNIT CHECK LED : toutes les
diodes du relais doivent
s'allumer
- LAST TRIP INDICATION :
si présente dans la mémoire
du relais
- LED:
la DIODE reste
allumée tant que 140G-ELTT
Tester est connectée au relais
- READY TO TRIP
PROCEDIMIENTO DIAGNOSTICO
- LED CONTROL UNIDAD: todos los
led del relé se deben
encender
- INDICACION ULTIMA ACTUACION:
si está presente en la memoria
del relé
- LED: queda encendido
mientras la 140G-ELTT Tester
permanezca conectada con el relé
- LISTO PARA LA ACTUACION
LED TRIP TEST DEVICE
Green
Verde
Grün
Vert
Verde
Red
Rosso
Rot
Rouge
Rojo
Device ON
Change battery
Dispositivo acceso
Sostituire batterie
Einrichtung eingeschaltet Batterie ersetzen
Dispositif allumé
Remplacer batteries
Dispositivo encendido
Sustituir baterías
2
3
TRIP
140G-ELTT
4
CLACK
Allen-Bradley, Rockwell Software, and Rockwell Automation are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
DIR 1000721R0506 (L5086)
Publication 140G-IN100A-MU-P - April 2013
Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.