Canadian Farm & Food Biogas Conference 5th March 2012 Key Generator Parameters affecting Grid Connection – for Buyers and Sellers Aidan Foss ANF Energy Solutions Inc. amfoss@ieee.org Key Generator Parameters ANF Energy Solutions Inc Biogas Conference 5th March 2012 Motivation for Presentation • Key biogas generator parameters can significantly affect: – – – • • Grid Access Withstand to Power Quality Connection Cost This presentation seeks to explain the reasons for this, and raise awareness for buyers and sellers ahead of generator selection These parameters may have less impact in other jurisdictions using 3-wire networks and different technical connection requirements Key Generator Parameters ANF Energy Solutions Inc Biogas Conference 5th March 2012 ANF Energy Solutions • DG Grid Connection Specialists • 13 Completed biogas projects – – – – – – Terryland 1&2 (360kW), Pinehedge (100kW) Fepro (499kW), Donnandale (498kW) Georgian Bluffs (100kW), Lanidrac (100kW) LaForge (600kW), ENS Poultry (138kW) Geranik (374kW), Gardiner (250kW) Maryland (499kW), Petrocorn (499kW) • 9 Biogas projects in progress • Also PV, Landfill Gas, Wind & Small Hydro Key Generator Parameters ANF Energy Solutions Inc Biogas Conference 5th March 2012 The Role of the Electrical Engineer Farmer Proponent Electrical Engineer Rules Process Verification Connection Key Generator Parameters Electric Utility Generator Supplier ANF Energy Solutions Inc Often Out-of-Province (European) Biogas Conference 5th March 2012 European and Ontario Grids • • • European distribution grids are predominately 3-wire Ontario distribution grid at 27.6kV, 12.5kV, 8.3kV are 4-wire, with extensive use of 2-wire singlephase laterals This difference particularly impacts feeder over-voltage risk and imbalance Key Generator Parameters ANF Energy Solutions Inc Biogas Conference 5th March 2012 Feeder Over-voltage • • • • With perfect voltage quality, the three feeder voltages are: • Of equal magnitude • 120 degrees apart, A-B-C Equipment connecting to 3-wire feeders is based on phase-phase voltage (e.g. B-C) Equipment connecting to 4-wire feeders is often based on the voltage between a phase and ground (e.g. B-G) During a short-circuit fault on a 4-wire feeder, phase-to-ground voltages could increase to unsafe values (e.g. 120V to 208V) C Neutral B 3.0 3.0 2.0 2.0 1.0 1.0 0.0 0.0 -1.0 -1.0 -2.0 -2.0 -3.0 -3.0 Key Generator Parameters ANF Energy Solutions Inc Ground normally A Ground during fault Biogas Conference 5th March 2012 Single-Phase Laterals • • • • In practice, voltages and currents are not perfectly balanced, due mainly to imperfect load balancing across the phases With a single-phase lateral, all the load is on one-phase – creates imbalance Single-phase laterals are deployed extensively across the Ontario rural distribution network Probably the biggest source of feeder imbalance Key Generator Parameters ANF Energy Solutions Inc Biogas Conference 5th March 2012 Imbalance 2.0 • • • Imbalance is generally regarded as electrical pollution – it does not convey useful power Three-phase generators can act as a sink to imbalance Imbalance currents through transformers and alternators: • Reduces their available capacity (thus often oversized) • Cause heating and other stresses Key Generator Parameters 1.5 1.0 0.5 0.0 -0.5 -1.0 -1.5 -2.0 ANF Energy Solutions Inc Biogas Conference 5th March 2012 Types of Imbalance • • • Negative sequence imbalance: • Wrong phase order: A-C-B not A-B-C Zero sequence imbalance: • Causes ground and neutral currents Single-phase loads (laterals) cause roughly similar amounts of negative and zero sequence imbalance Europe (3-wire) Ontario (4-wire) Negative Sequence 1%-2% Standard 3% Standard Zero Sequence None 3% Standard Key Generator Parameters ANF Energy Solutions Inc Biogas Conference 5th March 2012 Negative Sequence Imbalance V2 • • • • • I2 = V2 / (X2+XT) Ohm’s Law A small voltage imbalance (V2) can give rise to a large current imbalance (I2) Key parameters are: • the alternator negative sequence impedance (X2) • the capability of the alternator to withstand imbalance X2 should be checked at the design stage Site single-phase loads also cause Negative Sequence imbalance Key Generator Parameters ANF Energy Solutions Inc XT I2 SITE LOADS X2 Biogas Conference 5th March 2012 Zero Sequence Imbalance • • • • • I0 = V0 / (X0+XT) if the generator is effectively grounded and a Y-gnd:Y-gnd transformer is employed Y-gnd:Y-gnd transformers avoid high voltage equipments and thus keep costs down A small voltage imbalance (V0) can give rise to a large neutral current (3xI0) Not an issue on 3-wire networks Key parameters are: • the alternator negative sequence impedance (X0) • the capability of the alternator to withstand neutral current Key Generator Parameters ANF Energy Solutions Inc V0 XT Y-gnd/Ygnd I0 SITE LOADS X0 3xI0 Biogas Conference 5th March 2012 Effective Grounding • • Effective grounding limits the rise of phase-to-ground voltages during a single-phase fault (e.g. 120V) Scenario of concern: SUBSTATION Open • Single-phase fault on feeder • Substation breaker/recloser opens before generator breaker • Generator and feeder not effectively grounded • Fault Nominal requirement before 2008 was for generation sites to be effectively grounded Closed 3.0 3.0 2.0 2.0 1.0 1.0 0.0 0.0 -1.0 -1.0 -2.0 -2.0 -3.0 -3.0 Key Generator Parameters Feeder with other Users ANF Energy Solutions Inc Biogas Conference 5th March 2012 Feeder Reclosers • • • • On 27.6kV feeders, utility reclosers generally disconnect all three phases for any feeder fault On 8.3kV and 12.5kV feeders, utility reclosers generally disconnect only one phase for a single-phase feeder fault The scenario of concern only applies to 27.6kV feeders Requirement for effective grounding on connections to 8.3kV and 12.5kV was dropped in Fall 2008 Key Generator Parameters ANF Energy Solutions Inc Biogas Conference 5th March 2012 Resistance Grounding • On biogas generators connecting to 8.3kV and 12.5kV feeders, the generally preferred solution is: – Employ a Y-gnd:Y-gnd transformer in order to avoid expensive high voltage equipments – Ground the generator neutral through a resistor – stops virtually all neutral current – X0 not an issue Y-gnd/Ygnd SITE LOADS • Not applicable to 27.6kV feeders – workin-progress to ground at LV Resistor Key Generator Parameters ANF Energy Solutions Inc Biogas Conference 5th March 2012 Grid Access • • • On many parts of the Hydro One network, grid access is limited by: • Thermal constraints (transformer, feeder) • Fault level constraints (switchgear) Although two alternators may have the same kW-load output, they may have very different fault current contribution can impact on grid access The initial generator fault current depends on the subtransient reactance (Xd”) Key Generator Parameters ANF Energy Solutions Inc Biogas Conference 5th March 2012 Changing/Selecting Alternators • • • • • Changing alternators resulting in an increase in fault current contribution can trigger a new CIA Changing alternators resulting in a decrease in fault current contributions has (to date) only required an Equipment Clarification Frequently a proponent wants a CIA to secure grid access ahead of alternator selection But, CIA is based on a specific alternator configuration Application is based on the candidate alternator with the highest fault current contribution Key Generator Parameters ANF Energy Solutions Inc ? Biogas Conference 5th March 2012 Other Key Alternator Parameters • Other alternator parameters are used for Protection Studies and impact on protection settings • Must be correct as affect ability to detect feeder faults • Used by utility to provide the signature of a remote feeder fault Key Generator Parameters ANF Energy Solutions Inc Biogas Conference 5th March 2012 Key Parameters Summary • Subtransient Reactance (Xd”): should be checked at the design stage as may prevent grid access and may require a new CIA • Negative Sequence Reactance (X2) and Negative Sequence Withstand : should be checked at the design stage • Zero Sequence Reactance (X0) and Neutral Current Withstand : should be checked at the design stage if connecting to 27.6kV • Changes to other parameters likely to result in protection study rework for the utility and consultant Thank you – Any Questions? Key Generator Parameters ANF Energy Solutions Inc Biogas Conference 5th March 2012