ICMI Universal Recloser Controls

advertisement
ICMI Universal Recloser Controls
ICMI offers the most easily installed next-generation recloser control. The URC delivers
utilities a very flexible, cost-effective, control which adapts to most mechanisms,
maximizes a utility’s investment and minimizes training costs. There are multiple
methods of configuration that are intuitive and simple to use. In the electric utility
market for over 40 years, ICMI designs and builds advanced microprocessor-based
controls to demanding reliability standards. Products are supported with outstanding
technical support, field service and industry leading warranties. ICMI delivers flexible
and extensive communication options that ensure our controls are ready for
tomorrow’s smart grid applications today.
Flash Drive:
- Data/Event Logging
- Firmware Upgrade
- Configuration Upload
PC Connection to Utility Software
Control Keys for Easy Front Panel
Configuration and Quick Access
to Metered Data and Settings
Clear Visual Indicators Provide
Recloser Status
One Touch Function Keys with
LED Indicators
Hot Line Switch and Indicator
Clear-cut Recloser Position Status
•
•
•
Recloser Compatibility
Compatible with three phase (IIA) and
triple-single (URC-III TS) reclosers
Plug-in compatible with Cooper, G&W,
Tavrida, Creat, ABB
Can be adapted to any recloser
•
•
•
Flexible Communication Options
RS-232, Fiber and Ethernet
Optional communications: radio, RTU, modem
and others can be mounted in the cabinet
DNP 3.0 – ICMI offers easy setup of custom
point maps for seamless SCADA integration
10 Year Product Warranty
URC Control Configuration and Analysis
URC Utility Suite allows for recloser configuration, curve selection and modification, data
analysis, sequence of events data review and DNP 3.0 point mapping
Device Configuration Utility – Microsoft Windows®
compatible program used to configure all parameters
and set points and allows data to be read from the
control
Data Log Utility – Microsoft Windows® compatible
program used to display data log files
DNP Configuration Utility – Microsoft Windows®
compatible program used to customize the point map
Configuration, Curve Selection and Modification
Control settings can be programmed via a PC and
uploaded using a USB cable, flash drive or SCADA.
Save time and simplify configuration by copying
settings files and adjusting only what is required.
Curve selection and modification using the
Configuration Utility gives users a graphical display of
all applied curves and modifications allowing quick
and easy curve selection.
Basic Parameters Tab
Configuration Tab
Curve Selection and Modification Tab
URC Control Configuration and Analysis
Data Log and Sequence of Events Review
Data Log Utility provides advanced data
logging and sequence of events review.
Metered quantities include RMS phase
voltages, currents and power.
ICMI supplied USB Flash Drive stores data in
monthly files. Retrieve data using the USB
drive and download onto PC.
Graphical tools and a straightforward
interface allow for multiple views and
filtering to quickly get to your essential data.
Data Log Utility
DNP 3.0 Point Mapping
The ICMI DNP Configuration Utility offers
one of the easiest DNP setups in the industry
allowing for seamless integration to utility
SCADA systems.
DNP Point Map Selection
Binary and Analog Inputs and Outputs are
menu selectable to coordinate with utility
point maps. The Point Map Selection Tool is
the ultimate user-friendly DNP setup using a
point-and-click interface.
The DNP Class Selection Tool is a simple
drag-and-drop interface.
DNP Class Selection
URC-IIA and URC-III TS
Features
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Compatible with three phase (IIA) and triple-single (III TS) reclosers
Multiple methods of configuration: PC, USB Flash Drive or directly from the front panel
• Each method is quick and intuitive
Over 40 traditional time/current trip curves with modifiers
• Includes IEC and ANSI inverse, very inverse and extreme inverse curves
• Separate curves for Phase, Ground, Cold Load Pickup and Hot Line Tag
Comprehensive communication port options – RS-232, Fiber and Ethernet
DNP 3.0 Level 3 communication protocol (IEC 61850 optionally available)
Drag-and-drop DNP Points in the ICMI Utility Software to customize the point map
Intelligent battery and temperature monitoring and control
Sequential Events captured on USB Flash Drive and retained for 1 year in monthly files
Power RMS calculation for all three phases
Sequence coordination for down line devices
Cold Load Pick-Up (CLPU) with adjustable time delay
Sensitive Ground Fault (SGF/SEF) down to 2A
Ground Trip Precedence
High Current Trip (HCT)
High Current Lockout (HCLO)
Both Non-Reclose and Hot Line Tag modes
Configurable Auxiliary Inputs and Outputs available
Software
•
•
•
•
ICMI URC Utility Suite allows for recloser configuration, curve selection and modification, data analysis,
sequence of events data review and DNP 3.0 point mapping
Device Configuration Utility – Microsoft Windows® compatible program used to configure all parameters
and set points and allows data values to be read from the control
Data Log Utility – Microsoft Windows® compatible program used to display data log files
DNP Configuration Utility – Microsoft Windows® compatible program used to customize the point map
Cabinet and Options
•
•
•
•
•
Special Powder coated aluminum cabinet, 13 x 16 x 24 inches for control powered reclosers
Special application cabinet conversions available
Optional displays – either LCD (-20C to +70C) or VFL (-40C to +85C)
DC backup battery choices with intelligent battery power management
Optional communications – radio, RTU, modem, etc. can mount internally in cabinet space
Amelia, OH USA
Phone: (513) 752-4731  Fax: (513) 752-4738  www.icmiinc.com  info@icmiinc.com
© 2014 by Inductive Components Manufacturing, Inc.
Download