Smart Grid: Assignment 1 Q1) A single phase load draws 10 kW from a 416-V line at a power factor of 0.85 lagging. 1. Find S = P + jQ. 2. Find |I|. 3. Assume that I0 , find the instantaneous power p(t). Q2) Convert the following instantaneous currents to phasors, using cos(wt) as the reference. 1. i(t)=300cos(wt-30) 2. i(t)=400sin(wt-30) 3. i(t)=100sin(wt-15)+200cos(wt-20) Q3) Two balanced Y-connected loads, one drawing 10 kW at 0.8 power factor lagging and the other 15 kW at 0.9 power factor leading, are connected in parallel and supplied by a balanced three-phase Y-connected, 480-V source (line to line). Determine the source current. Q4) The fuel-cost curves for two generators are given as follows: C1(P1)= 600 + 15 P1 + 0.05 P12 C2(P2) =700 +20P2 + 0.04 P22 Constraints 200 ≤P1 ≤ 800 MW 100 ≤P2 ≤500 MW Assuming the system is lossless; calculate the optimal dispatch values of P1 and P2 for a total load of 1000 MW, the incremental operating cost, and the total operating cost. Repeat the calculations for a total load of 400 MW. ( Active and Reactive power). (1)Using the electricity price at EEX Load MW Q5) The figure shows A load during a day 4 3 2 1 Calculate the cost to run this load 22 7 EEX (www.eex.com) on 20.10.2014, 7 11 16 18 22 For simplicity assume the company pays only for the active power. Furthermore, multiply the electricity price on the EEX website by 3 (to reflect power transmission costs, EEG-Umlage, taxes…). (2) Then assume that it is possible to reallocate 1MWh. How much would be the savings? (3) What is the power factor at time 16:00? (4) Assume that the load is supplied by a 13.8 kV and the transmission line has an impedance of Z=1+2j, Determine the reactive power required from a parallel capacitor to bring the power factor of the parallel combination up to 0.9. 24