WORKING DRAFT ISO/WD xxxx-3 Air-cooled air conditioners and air-to-air heat pumps — Testing and calculating methods for seasonal performance factors — Part 3: Annual performance factor APF 1 Scope 1.1 This International Standard specifies the testing and calculating methods for seasonal performance factor of equipment covered by ISO 5151, ISO 13253 and ISO 15042. 1.2 This International Standard also specifies the seasonal performance test conditions and the corresponding test procedures for determining the seasonal performance factor of equipment, as specified in 1.1., under mandatory test conditions and is intended for use only in marking, comparison, and certification purposes. 1.3 This International Standard does not apply to the testing and rating of: a) water-source heat pumps or water-cooled air conditioners; b) portable units having a condenser exhaust duct; c) individual assemblies not constituting a complete refrigeration system; or d) equipment using the absorption refrigeration cycle. 2 Normative references The following standards contain provisions which, through reference in this text, constitute provisions of this International Standard: ISO 5151, Non-ducted air-cooled air-conditioners and air-to-air heat pumps - Testing and rating for performance ISO 13253, Ducted air-cooled air-conditioners and air-to-air heat pumps - Testing and rating for performance ISO 15042, Multi-split system air-cooled air-conditioners and air-to-air heat pumps - Testing and rating for performance ISO xxxx-1, Air-cooled air conditioners and air-to-air heat pumps – Testing and calculating methods for seasonal performance factors – Part 1: Cooling seasonal performance factor CSPF ISO xxxx-2, Air-cooled air conditioners and air-to-air heat pumps – Testing and calculating methods for seasonal performance factors – Part 2: Heating seasonal performance factor HSPF © ISO 2010 – All rights reserved 1 ISO/WD xxxx-3 3 Definitions For the purposes of this International Standard, the definitions in ISO 5151, 13253 and 15042 apply, together with the following. 3.1 cooling seasonal total load (CSTL) total amount of heat that is removed from the indoor air when the equipment is operated for cooling the building during the cooling season 3.2 cooling seasonal energy consumption (CSEC) total amount of energy consumed by the equipment when it is operated for cooling during the cooling season 3.3 cooling seasonal performance factor (CSPF) ratio of the total amount of heat that the equipment can remove from the indoor air when operated for cooling during the cooling season to the total amount of energy consumed by the equipment during the same period 3.4 heating seasonal total load (HSTL) total amount of heat, including make-up heat, which is added to the indoor air when the equipment is operated for heating the building during the heating season 3.5 heating seasonal energy consumption (HSEC) total amount of energy consumed by the equipment, including make-up heat, when it is operated for heating during the heating season 3.6 annual performance factor (APF) ratio of the total amount of heat that the equipment can remove from and add to the indoor air during the cooling and heating seasons, respectively, to the total amount of energy consumed by the equipment for both seasons. 4 Tests These tests are additional to those in ISO 5151, ISO 13253 and ISO 15042. Test conditions and methods are according to Part 1 and Part 2 of this International Standard. The accuracy of the instruments used for tests shall conform to the test methods and uncertainties of measurements specified in ISO 5151, ISO 13253 and ISO 15042. 5 Calculation of annual performance factor (APF) Annual performance factor (APF) shall be calculated by equation (1). (1) Calculation of CSTL and CSEC is according to Part 1, and calculation of HSTL and HSEC is according to Part 2. For the cooling-only equipment, the annual performance factor (APF) shall be equal to the cooling seasonal performance factor (CSPF). 2 © ISO 2010 – All rights reserved ISO/WD xxxx-3 6 Test Report The test report shall be in accordance with Part 1 for cooling and Part 2 for heating. © ISO 2010 – All rights reserved 3 ISO/WD xxxx-3 Annex A (informative) Symbols Symbol 4 Description Unit CSTL : Cooling seasonal total load (Wh) CSEC : Cooling seasonal energy consumption (Wh) CSPF : Cooling seasonal performance factor HSTL : Heating seasonal total load (Wh) HSEC : Heating seasonal energy consumption (Wh) APF : Annual performance factor © ISO 2010 – All rights reserved ISO/WD xxxx-3 Annex B (normative) Calculation of total annual performance factor (TAPF) B.1 General This Annex applies only to the reverse cycle units. B.2 Definition of modes B.2.1 Active mode The mode corresponding to the hours with a cooling or heating demand of the building and cooling or heating function of the unit is switched on. whereby the B.2.2 Inactive mode The mode corresponding to the hours when the unit is not operating to meet cooling or heating demand. NOTE This mode may include the operation of a crankcase heater. B.2.3 Disconnected mode The mode corresponding to the hours when the unit is electrically disconnected from the main power supply. NOTE Power consumption is zero. B.3 Measurement of the electric power consumption during the inactive mode The unit shall be electrically connected to the main power source after shut-down for 6 hours. Indoor and outdoor temperature of 20 °C condition shall be reached. The power consumption shall be measured for one hour after the temperature conditions are stabilized. The same test is repeated with the temperature condition of 5 °C, 10 °C and then 15 °C with the stabilization period of 2 hours between each test. Each power consumption shall be weighted by weighting factors in Table B.1 and then integrated to obtain a weighted average power consumption, Pia. NOTE If the results of the tests at 20 °C and 5 °C are within 5 % or 1 W, then the tests at 15 °C and 10 °C are not mandatory. The average value of these results is used for the four considered temperature conditions. Table B.1 — Weighting factors Weighting factor 5 °C 10 °C 15 °C 20 °C 0.05 0.13 0.27 0.55 Inactive energy consumption (IAEC) shall be calculated by equation (B.1). © ISO 2010 – All rights reserved 5 ISO/WD xxxx-3 IAEC = Hia x Pia (B.1) Hia is the number of hours of inactive mode as given in Table B.2. B.4 Calculation of total annual performance factor (TAPF) Total annual performance factor (TAPF) shall be calculated by equation (B.2). TAPF = (CSTL + HSTL) / (CSEC + HSEC + IAEC) (B.2) Calculation of CSTL and CSEC is according to Part 1, and calculation of HSTL and HSEC is according to Part 2. Inactive energy consumption (IAEC) shall be calculated by equation (B.1). The mode hours for the standard bin distribution are shown in Table B.2. Table B.2 — Distribution of hours for each mode Active mode 6 (h) Inactive mode Hia (h) Disconnected mode (h) Cooling season 1817 - - Heating season 2866 - - Annual total hours 4683 2061 2016 © ISO 2010 – All rights reserved