Split Ducted Air Conditioners Air Cooled Fixed Speed Models E S TA B L I S HE D 1 9 6 1 >> Split Ducted Air Conditioners Air Cooled Fixed Speed R410a Refrigerant 6kw to 73kw R410a/R407c Refrigerant 80kw to 200kw >> www.dunnair.com.au 1 E S TA B L I S H E D 1 9 6 1 >> General Established 1961, Dunnair has a proud history of supply to the Australian Commercial HVAC Industry. Our quality range of Split Ducted models are designed and manufactured in accordance with strict quality control standards and for Australian conditions. >> Features • SHS6 to 35 single stage • Limit start timer • SH40 to 200 two stage • Quiet & efficient • Optional two stage available for 18kW to 35kW • Independent defrost dual circuit units for two stage units • SHS6 to 35 direct drive • SH40 to 200 belt drive • Automatic De-Ice • Liquid Accumulator • Phase reverse protection • Electric Reheat high temperature protection (optional) • Crankcase heater • Overload protection for both indoor and outdoor fan motor • 24 volt control • MEPS rated • Galvanised steel panelling • Manufactured for Australian Standards & Conditions • Durable powder coated cabinet (outdoor unit) • High quality control procedures • External stainless steel fittings • Made in our factory in China • Easy access panels with turn lock handles, no screws • R407c refrigerant is used in standard units. • 25mm insulation • Coil corrosion protection • High quality scroll compressors • High/low pressure protection for compressor • Time delay protection for compressor 2 Serving the HVAC industry since 1961 Units with R410a refrigerant are available on request. Split Ducted Air Conditioners Air Cooled Fixed Speed Models >> Optional Controller DAT - 770 multifunction thermostat Technologically advanced in design and performance, the DAT - 770 is the ideal thermostat control for any installation of air conditioning systems • Auto season change over • Selectable programmable or manual mode • Heat cool or heat pump (O/B) logic • 0-10v output option for Heating or Cooling • High & Low balance points • Single or 3 speed fan control • Keyboard and/or Temperature Locks • Occupancy sensor inputs • Programmable occupancy inputs • Adaptive Recovery (Optimised Start) • Smart Fan logic for Commercial Control • PIN protected menus (installer PIN) • Outside air temperature display >> Optional Features As an active market player in commercial air conditioning industry, we understand that every project is unique. Standard manufactured units may not meet the requirements of your system design. Dunnair always welcome enquiries for special air conditioning equipments. Available options are listed below: • Stainless steel drip tray • 50mm thickness insulation • Electric heating fitted to cooling only models • VSD on supply air fan • Higher ESP (external static pressure) up to 500pa • 2 stages or more depending on size of the unit • Belt drive instead of direct drive fan • Copper fins • BAS output /input connection Dunnair specialises in manufacturing equipments to suit the application. • 24V powered with memory backup • Volt Free (clean contact) relays • Large backlit LED Display • Remote temperature sensors available • Integrated Modbus option • Replaces almost all 24V thermostats. 3 E S TA B L I S H E D 1 9 6 1 >> Specifications Overview Total Cooling Capacity Sensible Cooling Capacity Heating Capacity Nominal Air Flow Power Supply Full Load Noise Level Fan kw kw kw L/S Ph/V/Hz Amps Indoor Unit Outdoor Unit dBA dBA Drive SHS6 6.6 5.3 6.5 350 SHS8 8.0 7.2 7.9 472 SHS10 9.3 8.0 9.4 SHS12 11.5 9.7 SHS15 14.8 SHS18 Model Refrigerant Circuits 12.4 47.8 55.5 Direct 1 14.6 46.5 56.4 Direct 1 555 24.7 48.6 56.7 Direct 1 11.7 695 13.9 68.4 57.5 Direct 1 13.0 14.6 850 13.9 61.8 58.2 Direct 1 17.1 14.4 17.5 1000 16.2 63.7 59.8 Direct 1 SHS20 20.5 16.3 20.7 1110 19.1 70.5 73.7 Direct 1 SHS25 23.8 19.1 24.2 1390 22.4 71.0 74.9 Direct 1 SHS30 30.6 24.9 30.6 1800 25.9 69.8 75.5 Direct 1 SHS35 34.8 28.3 32.2 2000 27.9 70.3 75.3 Direct 1 SH40 39.7 32.6 38.4 2200 30.8 71.4 75.7 Belt 2 SH45 44.6 36.4 44.2 2700 37.2 72.2 76.2 Belt 2 SH50 48.6 39.4 47.8 2800 41.2 72.8 76.7 Belt 2 SH56 55.1 44.5 55.6 3000 47.7 72.8 77.1 Belt 2 SH66 65.5 50.9 60.7 3500 54.5 73.1 77.7 Belt 2 SH73 72.8 59.3 66.6 3900 60.6 73.7 78.4 Belt 2 SH80 80.4 65.5 80.7 4300 66.2 74.6 79.0 Belt 2 SH85 86.6 68.2 87.1 4500 63.2 74.6 79.0 Belt 2 SH90 88.5 71.0 85.0 4800 74.4 75.5 79.6 Belt 2 SH95 95.8 72.3 96.2 5200 74.4 75.5 79.6 Belt 2 SH100 102.2 82.9 98.5 5500 85.2 77.3 80.6 Belt 2 SH120 117.6 95.2 116.2 6500 98.8 77.1 82.2 Belt 2 SH140 137.8 110.6 132.0 7500 117.5 77.7 83.3 Belt 2 SH160 156.2 127.5 152.5 8500 133.9 80.1 83.7 Belt 2 SH180 176.8 143.6 169.4 9500 153.2 82.5 85.4 Belt 2 SH200 201.8 164.3 196.2 10500 163.7 82.6 87.2 Belt 2 1/240/50 3/415/50 Cooling capacity is based on 27°C DB, 19°C WB entering air temperature & 35°C ambient. Heating capacity is based on 21°C DB entering air temperature & 7°C ambient. 4 Serving the HVAC industry since 1961 Split Ducted Air Conditioners >> Dimensions Air Cooled Fixed Speed Models Outdoor Unit Indoor Unit Dimensions L x W x H (mm) Weight (kg) Dimensions L x W x H (mm) Weight (kg) Supply Air Dimension (mm) Return Air Dimension (mm) SHS6 860 x 310 x 718 65 850 x 620 x 400 50 270 x 188 600 x 320 SHS8 950 x 340 x 840 77 1100 x 620 x 400 56 270 x 188 850 x 320 SHS10 950 x 340 x 840 82 1100 x 620 x 400 58 750 x 185 850 x 320 SHS12 950 x 350 x 950 89 1250 x 620 x 400 65 750 x 185 1000 x 320 SHS15 950 x 340 x 1245 105 1400 x 620 x 420 80 850 x 200 1150 x 320 SHS18 950 x 340 x 1230 105 1550 x 620 x 420 86 950 x 200 1300 x 320 SHS20 950 x 340 x 1230 122 1600 x 620 x 420 90 950 x 200 1350 x 320 SHS25 1300 x 950 x 700 241 1650 x 720 x 485 121 882 x 221 1450 x 384 SHS30 1300 x 950 x 930 276 1900 x 720 x 485 132 882 x 262 1700 x 385 SHS35 1300 x 1000 x 930 282 2100 x 720 x 485 140 1000 x 262 1900 x 385 SH40 1550 x 1200 x 900 360 1300 x 1200 x 940 220 507 x 507 1040 x 777 SH45 1550 x 1400 x 900 365 1500 x 1200 x 940 240 507 x 507 1220 x 777 SH50 1800 x 1755 x 910 530 1600 x 1200 x 940 290 507 x 507 1320 x 777 SH56 1800 x 1755 x 910 532 1600 x 1200 x 940 295 507 x 507 1320 x 777 SH66 1800 x 1755 x 910 535 2000 x 1250 x 1040 410 569 x 569 1760 x 884 SH73 1800 x 1755 x 910 538 2000 x 1250 x 1040 410 569 x 569 1760 x 884 SH80 1800 x 1803 x 910 615 2200 x 1200 x 1020 485 569 x 569 1960 x 884 SH85 1800 x1803 x1000 615 2200 x 1250 1040 485 569 x 569 1960 x 884 SH90 1800 x 2080 x 1100 710 2430 x 1250 x 1050 516 647 x 525 2180 x 884 SH95 1800 x 2018 x 1100 710 2430 x 1350 x 1140 516 638 x 638 2180 x 984 SH100 2050 x 2050 x 1350 1100 2150 x 1450 x 1450 620 638 x 638 2000 x 1200 SH120 2050 x 2050 x 1350 1170 2300 x 1550 x 1550 660 715 x 715 2150 x 1300 SH140 2050 x 2050 x 1750 1180 2650 x 1600 x 1550 660 715 x 715 2500 x 1300 SH160 2050 x 2050 x 1750 1250 2850 x 1800 x 1550 760 801 x 801 2700 x 1300 SH180 2150 x 2150 x 2350 1340 3050 x 1850 x 1650 820 801 x 801 2900 x 1400 SH200 2150 x 2150 x 2350 1400 3350 x 1850 x 1650 860 801 x 801 3200 x 1400 Model 5 E S TA B L I S H E D 1 9 6 1 >> Fan Curves Air Handling Performance SHS6 SHS8 Normal Air Flow 150 High 100 Medium 200 Pascals External Static Pressure 250 200 Pascals External Static Pressure 250 Normal Air Flow 150 High 100 Medium 50 Low 50 Low 270 310 350 390 430 400 440 Airflow l/s SHS10 SHS12 Normal Air Flow 100 1100 1200 Medium 520 560 600 640 500 600 SHS15 700 Airflow l/s Airflow l/s SHS18 Normal Air Flow Normal Air Flow 250 200 High 150 Medium 100 Low 650 750 850 950 1050 Airflow l/s Serving the HVAC industry since 1961 200 High Pascals External Static Pressure 250 Pascals 900 150 50 Low 480 External Static Pressure 800 Normal Air Flow High 50 Low 6 560 200 Pascals External Static Pressure High 100 Medium 50 520 250 200 Pascals External Static Pressure 250 150 480 Airflow l/s 150 100 Medium 50 Low 800 900 1000 Airflow l/s Split Ducted Air Conditioners Air Cooled Fixed Speed Models >> Fan Curves Air Handling Performance SHS20 Medium 100 200 Pascals External Static Pressure 150 Normal Air Flow 250 High 200 Pascals External Static Pressure 250 SHS25 Normal Air Flow 150 100 50 50 Low 710 910 1110 1310 990 1510 1190 SHS30 SHS35 Normal Air Flow 100 Normal Air Flow 150 100 50 1400 1600 1800 2000 2200 1600 1800 2000 Airflow l/s SH40 2200 2400 Airflow l/s SH45 Normal Air Flow Normal Air Flow 400 400 350 300 External Static Pressure 2.2 KW MOTOR LIMIT 250 200 150 100 3.0 KW MOTOR LIMIT 300 250 Pascals 350 Pascals 1790 200 Pascals External Static Pressure 150 50 External Static Pressure 1590 250 200 Pascals External Static Pressure 250 200 150 100 50 50 1600 1390 Airflow l/s Airflow l/s 1800 2000 2200 Airflow l/s 2400 2600 2800 2100 2300 2500 2700 2900 3100 3300 Airflow l/s 7 E S TA B L I S H E D 1 9 6 1 >> Fan Curves Air Handling Performance SH50 SH56 Normal Air Flow 400 3.0 KW MOTOR LIMIT 4.0 KW MOTOR LIMIT 250 200 150 100 300 250 Pascals External Static Pressure 350 300 Pascals External Static Pressure 350 200 150 100 50 50 2200 Normal Air Flow 400 2400 2600 2800 3000 3200 2400 3400 2600 2800 400 350 External Static Pressure 200 150 100 4.0 KW MOTOR LIMIT 200 150 100 50 3200 Airflow l/s SH90 3600 3800 4000 4200 4400 4600 Normal Air Flow 400 4.0 KW MOTOR LIMIT 5.5 KW MOTOR LIMIT 350 300 250 200 150 100 300 250 Pascals External Static Pressure 350 3400 Airflow l/s Normal Air Flow 400 Pascals Normal Air Flow 250 2700 2900 3100 3300 3500 3700 3900 4100 4300 External Static Pressure 3600 300 50 200 150 100 50 50 3500 3700 3900 4100 4300 4500 4700 4900 5100 Airflow l/s 8 3400 350 250 SH80 3200 400 4.0 KW MOTOR LIMIT 300 Pascals External Static Pressure SH73 Normal Air Flow Pascals SH66 3000 Airflow l/s Airflow l/s Serving the HVAC industry since 1961 3800 4000 4200 4400 4600 4800 5000 5200 5400 5600 5800 Airflow l/s Split Ducted Air Conditioners Air Cooled Fixed Speed Models >> Fan Curves Air Handling Performance SH100 7.5 KW MOTOR LIMIT 250 200 150 100 300 250 Pascals 300 7.5 KW MOTOR LIMIT 350 External Static Pressure 350 Pascals Normal Air Flow 400 400 External Static Pressure SH120 Normal Air Flow 200 150 100 50 50 5200 5325 5850 6175 6500 6825 7150 7475 7800 4400 4675 4950 5225 5500 5775 6050 6325 6600 Airflow l/s Airflow l/s SH140 SH160 Normal Air Flow 400 400 200 150 100 300 250 Pascals External Static Pressure 250 15 KW MOTOR LIMIT 350 11 KW MOTOR LIMIT 300 Pascals External Static Pressure 350 200 150 100 50 3500 Normal Air Flow 50 4500 5500 6500 7500 8500 9500 10500 11500 4500 5500 6500 Airflow l/s SH180 200 150 100 50 Normal Air Flow 15 KW MOTOR LIMIT 350 300 250 Pascals 250 5500 9500 10500 11500 12500 400 External Static Pressure 300 Pascals External Static Pressure SH200 15 KW MOTOR LIMIT 350 8500 Airflow l/s Normal Air Flow 400 7500 200 150 100 50 6500 7500 8500 9500 10500 11500 12500 13500 Airflow l/s 6500 7500 8500 9500 10500 11500 12500 13500 14500 Airflow l/s 9 E S TA B L I S H E D 1 9 6 1 >> Wiring Diagram SHS6 – 10 Reverse Cycle Model Single Phase Compressor, Single Phase Outdoor and Indoor Fan V4.3 PU1 L21 PU2 SH1 KM1 100 E PU3 24V AC 12 6 RH 5 KM1 KA2 U1 CM W1 C1 U FM1 T 4 6 RM 5 4 RL W C2 H1 KT1 6 C 5 M1 L1 N EM C3 RH RM Outdoor Unit H1 M1 L1 N E Indoor Unit Red Brown Blue Black Earth electrode RC1 Filter Relay KA2 Contactor KM1 RV1 Reversing valve RH/RM/RL Power relay HP/LP switch H/LP1 Transformer TR Code PU1/2/3 Compressor FuseInstruction: CM1 Condenser fan FM1 DF1 De ice 3Contactor Evaporator fan VAR KM1– Varistor EM Time Relay Sump heater KT1 TRTransformer SH1 Bypass Relay Capacitor FuseBR1 C1-3 PU1/2/3 DF1 De ice VARVaristor KT1 Time Relay C1– 3Capacitor RC1– 3Filter RV1 Reversing valve TK1 Overload protector L/HP1 HP/LP switch CM1Compressor 10 VAR θ 1P 240V50HZ RL H1 M1 L1 N E A1 KM1 A2 RC1 1 A1 KA2 A2 2 A RH B A RM B RL HP 5 KM1 LP 6 NC BR1 COM DF1 N 5 A 3 9 M1 L 12 10 B H RV1 A BR1 B MODEL OF COMPRESSOR: C-2RN170H5 FM1 EM SH1 BR1 Condenser fan Evaporator fan Sump heater Bypass Relay Serving the HVAC industry since 1961 Designed Checked Approved Technology Tang ZhJi Yang BoBo Zhengbin Standard Ratified Date 2010-11-10 Phase 1 Ph Total Wt. Scale 1:1 No. SHS10-Bd2-R Wiring Diagram Split Ducted Air Conditioners Air Cooled Fixed Speed Models >> Wiring Diagram SHS12 – 20 Reverse Cycle Model Three Phase Compressor, Single Phase Outdoor and Indoor Fan V4.3 PU1 A B C N TR L21 PU2 SH1 E KM1 100 VAR PU3 24V AC θ Three phase five line 415V 50HZ 3P 13 6 RH 5 KM1 1 3 5 5 2 4 6 9 U1 V1 CM W1 U KA2 FM1 6 W 4 RL 10 U C1 FM2 W C2 T L1 L2 L3 PRF 4 6 RM 5 6 com PRF on KT1 C 5 H1 M1 L1 N EM C3 A1 KM1 A2 RC1 1 A1 KA2 2 A2 Outdoor Unit H1 M1 L1 N E Indoor Unit Red Brown Blue Black Earth electrode H1 M1 L1 N E A RH B RM A RM B RL A RL B H TRTransformer PU1/2/3 Fuse DF1 De ice VARVaristor KT1 Time Relay PRF Phase protection RC1– 3Filter RV1 Reversing valve TK1 Overload protector L/HP1 HP/LP switch LP1 5 7 6 14 NC COM DF1 10 N M1 L 7 RV1 A1 Filter PRF Phase protection RC1 Relay KA2 Contactor KM1 FR RV1 Reversing valve Thermal Relay HP/LP switch H/LP1 Transformer TR PU1/2/3 Compressor CM1 CodeFuseInstruction: Condenser fan FM1 DF1 De ice MotorEMOverload Breaker Evaporator fan VAR QF1– 3Varistor Relay Sump heater KT1 KM1– Time SH1 3Contactor BR1 relayBypass Relay C1-3 FR Capacitor Thermal HP1 KM1 13 BR1 RH 3 BR1 A2 MODEL OF COMPRESSOR: C-SBS235H38A CM1Compressor FM1 Condenser fan EM Evaporator fan SH1 Sump heater BR1 Bypass Relay Designed Checked Approved Technology Tang ZhJi Yang BoBo Zhengbin Standard Ratified Date 2010-11-10 Phase 3 Ph Total Wt. Scale 1:1 No. SHS20-Bb2-C Wiring Diagram 11 E S TA B L I S H E D 1 9 6 1 >> Wiring Diagram SHS25 – 35 Reverse Cycle Model Three Phase Compressor, Three Phase Outdoor Fan and Two Three Phase Indoor Fans Three phase five line 415V 50HZ 3P E QF3 Set:5A A B C N PRF L1 L2 L3 PU1 L21 TR 21 PU2 21 SH1 22 22 SH2 100 101 KM1 KM2 Set:16A Set:16A QF1 1 1 3 5 2 4 6 U1 V1 CM1 KM1 2 W1 U3 3 4 6 V3 FM1 1 KM3 1 3 5 2 4 6 U2 W3 V2 CM2 KM2 2 W2 PU3 24V AC θ 13 FR QF2 5 VAR U4 3 5 4 6 V4 FM2 1 3 5 2 4 6 KM5 W4 U V W 14 18 T KM4 13 KT1 KM1 A2 RC1 1 A1 KM2 A2 RC2 2 A1 KM3 A2 RC3 C1 A1 C2 H1 1 3 21 3 22 KT2 1 3 TK1 TK2 KM1 13 14 A1 RV1 5 HP1 7 LP1 6 HP2 8 LP2 PRF com on 12 9 NC COM DF1 A2 6 BR2 A2 KM214 13 N BR1 10 L M M1 14 A1 Outdoor Unit U V W E Indoor Unit Red White Blue Earth electrode U V W E Red White Blue A1 EM PU1/2/3 Fuse DF1/DF2 De ice VARVaristor KT1– 2 Time Relay PRF Phase protection RC1– 3Filter RV1/RV2 Reversing valve TK1– 2 Overload protector L/HP1– 2 HP/LP switch 12 4 15 NC RV2 A1 H2 A1 A1 12 KM5 RC5 COM DF2 A2 6 EF RC1-3 Filter QF1-3 Motor Overload Breaker RV1/RV2 Reversing valve KM1--5 Contactor TK1-2 Overload protector L/HP1-2 HP/LP switch Transformer TR Code PU1/2/3 Fuse Instruction: CM1/CM2 Compressor Condenser fan FM1/FM2 Breaker DF1/DF2 De3ice QF1– Motor OverLoad Evaporator fan VAR EM Varistor KM1– 5 Contactor Time Relay Sump heater KT1-2 SH1-2 Phase protection Bypass Relay PRF TRTransformer BR1-2 KM4 A2 RC4 BR2 10 N 16 M M2 12 L BR2 A2 A2 MODEL OF COMPRESSOR C-SBN373H8A CM1/CM2Compressor FM1/FM2 Condenser fan EM Evaporator fan SH1– 2 Sump heater BR1– 2 Bypass Relay Serving the HVAC industry since 1961 Designed Checked Approved Technology Tang ZhJi Yang BoBo Zhengbin Standard Ratified Date 2010-11-10 Phase 3 Ph Total Wt. Scale 1:1 No. SH35-Bb2-R Wiring Diagram Split Ducted Air Conditioners Air Cooled Fixed Speed Models >> Wiring Diagram SH40 – 45 Reverse Cycle Model Two Three Phase Compressors, Two Three Phase Outdoor Fans and Two Three Phase Indoor Fans A B C N E QF3 Set:6.8A PRF L1 L2 L3 PU1 L21 TR 21 PU2 21 SH1 22KM1 KM2 22 SH2 100 101 Set:17A Set:17A QF1 1 1 3 5 2 4 6 U1 V1 CM1 KM1 2 W1 U3 3 4 6 V3 FM1 1 KM3 1 3 5 2 4 6 U2 W3 V2 CM2 KM2 2 W2 PU3 24V AC 13 FR QF2 5 VAR θ Three phase five line 415V 50HZ 3P U4 3 5 4 6 V4 FM2 1 3 5 2 4 6 KM5 W4 U V W 14 18 T KM4 13 KT1 KM1 A2 RC1 1 A1 KM2 A2 RC2 2 A1 KM3 A2 RC3 C1 A1 C2 H1 1 3 21 3 22 KT2 1 TK1 TK2 KM1 3 13 5 HP1 7 LP1 6 HP2 8 LP2 com on 12 9 14 NC COM DF1 RV1 A2 A1 PRF 6 BR2 A2 KM214 13 N BR1 10 L M M1 14 A1 Outdoor Unit U V W E Indoor Unit Red White Blue Earth electrode U V W E Red White Blue A1 H2 EM PU1/2/3 Fuse DF1/DF2 De ice VARVaristor KT1– 2 Time Relay PRF Phase protection RC1– 3Filter RV1/RV2 Reversing valve TK1– 2 Overload protector L/HP1– 2 HP/LP switch 4 15 NC RV2 A1 A1 A1 12 KM5 RC5 COM DF2 A2 6 EF RC1-3 Filter QF1-3 Motor Overload Breaker RV1/RV2 Reversing valve KM1--5 Contactor TK1-2 Overload protector L/HP1-2 HP/LP switch Transformer TR Code PU1/2/3 FuseInstruction: CM1/CM2 Compressor FM1/FM2 Condenser fan DF1/DF2 De ice QF1– 3 Motor OverLoad Breaker Evaporator fan VAR EM Varistor KM1– 5 Contactor Time Relay Sump heater KT1-2 SH1-2 Phase protection Bypass Relay PRF TRTransformer BR1-2 KM4 A2 RC4 BR2 10 N 16 M M2 12 L BR2 A2 A2 MODEL OF COMPRESSOR C-SBN523H8D Designed Tang ZhJi CM1/CM2Compressor Checked Yang BoBo Zhengbin Approved FM1/FM2 Condenser fan Technology EM Evaporator fan SH1– 2 Sump heater BR1– 2 Bypass Relay Standard Ratified Date 2010-11-10 Phase 3 Ph Total Wt. Scale 1:1 No. SH45-Bb2-R Wiring Diagram 13 E S TA B L I S H E D 1 9 6 1 >> Wiring Diagram SH50 – 73 Reverse Cycle Model Two Three Phase Compressors, Four Three Phase Outdoor Fans and Two Three Phase Indoor Fans Three phase five line 415V 50HZ 3P PRF E TR PU1 L21 L1 L2 L3 PU2 VAR QF1 Set:24.5A 1 3 2 5 4 U1 1 3 5 KM1 2 4 6 6 V1 W1 CM1 U3 V3 FM1 1 KM3 W3 U3 2 V3 FM2 W3 U2 3 5 4 1 3 5 KM2 2 4 6 6 V2 1 3 5 2 4 6 18 KM5 KM4 W2 U4 V4 FM3 W4 U4 V4 FM4 U W4 V W Outdoor Unit U V W E Indoor Unit Red White Blue Earth electrode U V W E Red White Blue KM1 100 22 KM2 101 SH1 SH2 EM 21 22 5 KA1 KA2 9 19 A1 KM1 A2 20 A1 KA1 A2 1 1 3 21 TK1 23 TK2 25 TK5 5 HP1 7 C2 A1 KA2 A2 2 1 3 22 TK3 24 TK4 26TK6 6 HP2 8 LP2 A1 KM3 RC3 A2 13 14 A1 RV1 FR Thermal Relay TRTransformer PU1/2/3 Fuse DF1/DF2 De ice VARVaristor KT1– 2 Time Relay PRF Phase protection RV1/RV2 Reversing valve TK1– 4 Overload protector TK5– 6Disch.temp.sensor 14 9 NC 9 A1 A2 A1 RC2 KM4 A2 RC4 H2 4 A1 BR1 A2 KM2 13 14 Intermediate relay FM1– 4 EM SH1– 2 BR1– 2 KA1– 2 Condenser fan Evaporator fan Sump heater Bypass Relay Intermediate relay Serving the HVAC industry since 1961 EF KM5 RC5 N 14 M M1 RV2 L 15 COM DF2 A2 6 Reversing valve Overload protector Disch.temp.sensor HP/LP switch Compressor Condenser fan Evaporator fan Sump heaterL/HP1– 2 HP/LP switch Bypass Relay CM1/CM2Compressor BR1 10 NC A1 A1 COM DF1 A2 6 A1 RV1/RV2 RC1-5 Filter QF1-3 Motor Overload Breaker TK1-4 KM1--5 Contactor TK5-6 L/HP1-2 Thermal Relay FR Transformer CM1/CM2 TR PU1/2/3 Fuse FM1-4 Code Instruction: DF1/DF2 De ice EM VAR SH1-2 RC1– 5 Varistor Filter Relay OverLoad Breaker KT1-2 BR1-2 QF1– 3 Time Motor Phase protection KA1-2 PRF KM1– 5Contactor 12 KM1 3 5 RC1 KM2 14 PRF on LP1 KT1 C1 H1 21 13 com T KT2 CM2 13 FR QF2 Set:24.5A PU3 24V AC θ QF3 Set:11.6A A B C N BR2 10 N 16 M M1 12 L BR2 A2 A2 12 MODEL OF COMPRESSOR C-SCP400H38A Designed Checked Approved Technology Tang ZhJi Yang BoBo Zhengbin Standard Ratified Date 2010-11-10 Phase 3 Ph Total Wt. Scale 1:1 No. SH73-Bb2-R Wiring Diagram Split Ducted Air Conditioners Air Cooled Fixed Speed Models >> Wiring Diagram SH80 – 200 Reverse Cycle Model Two Three Phase Compressors, Four Three Phase Outdoor Fans and Two Three Phase Indoor Fans Three phase five line 415V 50HZ 3P PRF QF3 A B C N TR PU1 L1 L2 L3 L21 PU2 E QF1 FR1 Set:37A 1 3 5 2 4 6 U1 V1 3 5 KM1 2 4 6 KM3 FR2 CM 1 13 FR QF2 1 W1 PU3 24V AC θ VAR U3 V3 FM1 W3 U3 1 3 5 2 4 6 V3 Set:37A U2 W3 FM2 V2 18 1 3 5 KM2 2 4 6 W2 CM2 U4 V4 FM3 KM4 W4 U4 V4 FM4 KM6 W4 1 3 5 2 4 6 1 3 5 FR3 2 4 6 Set:17.5A U5 V5 KT1 U5 1 1 C1 A1 KA1 A2 C2 A1 KA2 A2 2 1 21 3 KT2 W5 A1 W5 V5 3 22 TK1 23 TK2 25 TK5 5 HP1 7 TK3 24 TK4 26 TK6 6 HP2 8 LP2 12 KM1 3 13 KM3 A2 RC3 H1 9 14 NC Red White Blue Earth electrode U V W E U5 u v w Red White Blue u v w 1 3 5 2 4 6 KM7 A1 KM214 KM1 W5 Red White Blue V5 EM U5 100 W5 21 22 KM2 101 SH1 SH2 21 22 5 KA1 KA2 9 19 20 A1 KM1 15 RV2 A2 6 BR2 KT3 1 9 KM5 A2 RC5 KM6 30 21 KM6 32 32 31 FR1– 3 Thermal Relay TRTransformer PU1/2/3 Fuse DF1/DF2 De ice VARVaristor KT1– 3 Time Relay PRF Phase protection KA1–2 Intermediate relay RC1– 7Filter RV1/RV2 Reversing valve TK1– 4 Overload protector TK5 L1 L2 L3 L N B1 B2 11 M2 KT3 TK6 L1 L2 L3 9 KM6 L N B1 B2 11 M2 13 L21 N 240VAC 25 6 L21 N 26 6 240VAC 16 M M1 L A1 EF V5 Filter Reversing valve Overload protector Disch.temp.sensor HP/LP switch Compressor Condenser fan Evaporator fan Sump heater Bypass Relay N BR2 10 12 A2 33 5 6S KT3 KM7 21 31 22 13 SY380 Overload Protector inner compressor QF1-3 Motor Overload Breaker RC1-7 RV1/RV2 KM1--7 Contactor FR1-3 Thermal Relay TK1-4 Transformer TK5-6 TR PU1/2/3 Fuse L/HP1-2 CM1/CM2 DF1/DF2 De ice FM1-4 VAR Varistor Code Instruction: Time Relay EM KT1-3 protection PRF 3 Phase SH1-2 QF1– Motor OverLoad Breaker Intermediate relay KA1-2 BR1-2 KM1– 7Contactor COM DF2 A2 A1 RC2 L M M1 NC A1 9 A1 14 A2 5 RC1 KM2 A2 BR1 N BR1 10 4 13 KM4 A2 RC4 H2 Red White Blue U V W E Indoor Unit A1 COM DF1 RV1 A2 A1 6 Outdoor Unit 14 PRF on LP1 com T KM5 13 22 14 A1 KM7 A2 RC7 A1 KM6 A2 RC6 14 34 12 MODEL OF COMPRESSOR SY380-4 TK5– 6Disch.temp.sensor L/HP1– 2 HP/LP switch CM1/CM2Compressor FM1– 4 Condenser fan EM Evaporator fan SH1– 2 Sump heater BR1– 2 Bypass Relay Designed Checked Approved Technology Tang ZhJi Yang BoBo Zhengbin Standard Ratified Date 2010-11-10 Phase 3 Ph Total Wt. Scale 1:1 No. SH200-Bb2-C Wiring Diagram 15 Split Ducted Air Conditioners Air Cooled Fixed Speed Models E STA B L ISH ED 1 9 6 1 Dunnair (Aust) Pty Ltd Head Office: 140 Bernard Street, Cheltenham VIC 3192 Ph 03 8586 8200 Fax 03 8586 8201 Email salesaust@dunnair.com.au Web site www.dunnair.com.au Ph 02 9674 1577 Ph 03 9558 7001 Ph 07 3890 8796 Ph 08 8240 2888 Ph 08 9418 2444 Ph 0418 756 643 Fax 02 9674 1588 Fax 03 9551 1644 Fax 07 3890 8642 Fax 08 8240 2777 Fax 08 9418 2100 Fax 03 6425 3531 The Manufacturer reserves the right to modify the data in this catalogue without prior notice. Email salesnsw@dunnair.com.au Email salesvic@dunnair.com.au Email salesqld@dunnair.com.au Email salessa@bigpond.net.au Email saleswa@dunnair.com.au Email salestas@dunnair.com.au >> www.dunnair.com.au V30102013 Dunnair New South Wales: Dunnair Victoria: Dunnair Queensland: Dunnair SA & NT: Western Australia: Turner Engineering Tasmania: