ZLM - Installation manual

advertisement
ZLM - Installation manual
Revision: A-02
Date: 2016-06-03
APPLICATION
Nemalux ZLM luminaires are suitable for permanent or fixed installation both indoors or outdoors, in dry
or wet locations, and where the fixture may be subject to moisture, dirt, corrosion, vibration and rough
usage.
UL listed in the United States and Canada, File No. #E477827. Certified for use in
ordinary (unclassified) locations as defined by the National Electrical Code (NEC) and
the Canadian Electrical Code (CEC)
Technical Specifications
MODEL
HOUSING
MOUNTING
CONECTIONS
INPUT VOLTAGE RANGE
INPUT POWER
INPUT CURRENT
COLOUR TEMPERATURE
COLOUR RENDERING INDEX (CRI)
LUMEN OUTPUT
Temperature Range
Case Temperature
Ingress Protection
Certifications
Lumen Maintenance
Weight
ZLM – Installation Manual
Revision A-02
ZLM
ZLM2
ZLM4
Extruded and cast Aluminum alloys
Customer mounted, Yoke mount, or custom options available
Standard: Turck quick-connect, 3m [9.8ft] flying lead
Dimming: 18/5 SOOW cable, 3m [9.8ft] flying lead
120VAC to 277VAC
296W
592W
1184W
2.5A @ 120VAC
4.9A @ 120VAC
9.9A @ 120VAC
1.1A @ 277VAC
2.1A @ 277VAC
4.3A @ 277VAC
5000K (Custom options available)
70 minimum (Higher values available as custom order)
See optical profile chart for details.
-40°C to +45°C
15°C above ambient (TYP)
IP66
CSA C22.2 No. 250.0, CSA No. 250.13-14, UL 1598, UL 8750
LM-80 > 60,500 hrs (Based on CREE long term testing)
22lbs (10kg)
44 lbs (20kg)
88 lbs (40kg)
1|P a g e
Mechanical Dimensions
ZLM Single Unit Physical Dimensions
ZLM2 and ZLM4 Physical Dimensions
ZLM – Installation Manual
Revision A-02
2|P a g e
WARNINGS





DISCONNECT POWER BEFORE SERVICING
NO SERVICEABLE PARTS
Class 1 Wiring Only
Suitable for operation in ambient not exceeding 45°C
To avoid the risk of fire, explosion, or electric shock, this product should be installed, inspected,
and maintained by a qualified electrician only, in accordane with all applicable electrical codes.
INSTALLATION
Nemalux accepts no liability for user-provided mounting hardware, for incorrect mounting, or incorrect
use of the product. User is responsible for ensuring mounting hardware is fit for purpose and securely
mounted.
Single-Unit Fixed Central Mount: Single ZLM modules only: Mounting to a single side of the
unit is acceptable using a minimum of two fasteners. ZLM2 and ZLM4 multi-unit assemblies must be
mounted using Yoke Mounting instructions below.
Installation of M6 mounting fasteners for fixed central mounting configuration. To provide adequate
engagement, fasteners must have a minimum of 8mm and a maximum of 10mm exposed threads after
insertion into user-supplied mounting hardware (not shown).
1. Mount unit to bracket or mounting surface using a minimum of (2) M6 fasteners. Torque
mounting fasteners to 45 in-lb. Use of medium strength thread-locker (Loctite 242 or
equivalent) is recommended for all mounting hardware.
2. (Optional) Attach secondary safety chain or cable to attachment point using cable, quick link, or
other locking connector system with a suitable load rating. It is recommended that at least one
secondary safety attachment is made for each unit. Secondary safety point is sized for ½” quick
link chain or other locking connector.
ZLM – Installation Manual
Revision A-02
3|P a g e
Yoke Mounting: Mounting for all ZLM, ZLM2, and ZLM4 configurations. Three M6 fasteners must be
used for each side (not provided). To provide adequate engagement, fasteners must have a minimum of
8mm and a maximum of 10mm exposed threads after insertion into mounting hardware.
1. Loosely install central M6 mounting fastener on each side. If using an adjustable or multiposition bracket, aim fixture in desired direction. Install remaining (2) fasteners per side and
torque all mounting fasteners to 45 in-lb. Use of medium strength thread-locker (Loctite 242 or
equivalent) is recommended for all mounting hardware.
2. Attach secondary safety chain or cable to attachment points using cable, quick link, or other
locking connector system with a suitable load rating. It is recommended that at least one
secondary safety attachment is made on for ZLM and ZLM2 models. Two secondary safety
attachment points should be used for ZLM4 models. Secondary safety point is sized for ½” quick
link chain or other locking connector.
ZLM – Installation Manual
Revision A-02
4|P a g e
WIRING
ZLM units may be supplied with flying lead cable or Turck minifast quick connects.
Turck mini-fast quick-connector:
If present, connect Turck 7/8” minifast receptacles to appropriate power cable or harness. Turck
connector harnesses may be purchased directly from Nemalux.



For single units, use Turck RKM 36-3M connector cable.
For ZLM2 units, use Turck T-36-1717-3/RKM 36-0.5/RKM 36-0.5 dual unit connector harness or
(2) Turck RKM 36-3M connector cables.
For ZLM4 units, use Turck T-34-198-3/0.2/0.2/RKM36-0.2/3RKM36-0.2/0.2/0.2 quad-unit
connector harness, or (2) Turck T-36-1717-3/RKM 36-0.5/RKM 36-0.5 dual unit connector
harnesses, or (4) Turck RKM 36-3M connector cables.
Electrical Terminations
Non-Dimming Units
Non-dimming units are connected using three-conductor cables. To connect power to luminaires, make
electrical terminations according to all applicable local codes and electrical safety regulations. Connect
Green wire to Ground, White wire to Neutral, and Black wire to Line. Single phase input, 120VAC to
277VAC only.
Dimming Units
Dimming units are connected using five-conductor cables. To connect power to luminaires, make
electrical terminations according to all applicable local codes and electrical safety regulations. Connect
Green wire to Ground, White wire to Neutral, Black wire to Line, single phase input, 120VAC to 277VAC
only. Connect Red to Positive 0-10V Dimming Control Line, Orange to Negative 0-10V Dimming Control
Line.
ZLM – Installation Manual
Revision A-02
5|P a g e