ZLM - Installation manual Revision: A-02 Date: 2016-06-03 APPLICATION Nemalux ZLM luminaires are suitable for permanent or fixed installation both indoors or outdoors, in dry or wet locations, and where the fixture may be subject to moisture, dirt, corrosion, vibration and rough usage. UL listed in the United States and Canada, File No. #E477827. Certified for use in ordinary (unclassified) locations as defined by the National Electrical Code (NEC) and the Canadian Electrical Code (CEC) Technical Specifications MODEL HOUSING MOUNTING CONECTIONS INPUT VOLTAGE RANGE INPUT POWER INPUT CURRENT COLOUR TEMPERATURE COLOUR RENDERING INDEX (CRI) LUMEN OUTPUT Temperature Range Case Temperature Ingress Protection Certifications Lumen Maintenance Weight ZLM – Installation Manual Revision A-02 ZLM ZLM2 ZLM4 Extruded and cast Aluminum alloys Customer mounted, Yoke mount, or custom options available Standard: Turck quick-connect, 3m [9.8ft] flying lead Dimming: 18/5 SOOW cable, 3m [9.8ft] flying lead 120VAC to 277VAC 296W 592W 1184W 2.5A @ 120VAC 4.9A @ 120VAC 9.9A @ 120VAC 1.1A @ 277VAC 2.1A @ 277VAC 4.3A @ 277VAC 5000K (Custom options available) 70 minimum (Higher values available as custom order) See optical profile chart for details. -40°C to +45°C 15°C above ambient (TYP) IP66 CSA C22.2 No. 250.0, CSA No. 250.13-14, UL 1598, UL 8750 LM-80 > 60,500 hrs (Based on CREE long term testing) 22lbs (10kg) 44 lbs (20kg) 88 lbs (40kg) 1|P a g e Mechanical Dimensions ZLM Single Unit Physical Dimensions ZLM2 and ZLM4 Physical Dimensions ZLM – Installation Manual Revision A-02 2|P a g e WARNINGS DISCONNECT POWER BEFORE SERVICING NO SERVICEABLE PARTS Class 1 Wiring Only Suitable for operation in ambient not exceeding 45°C To avoid the risk of fire, explosion, or electric shock, this product should be installed, inspected, and maintained by a qualified electrician only, in accordane with all applicable electrical codes. INSTALLATION Nemalux accepts no liability for user-provided mounting hardware, for incorrect mounting, or incorrect use of the product. User is responsible for ensuring mounting hardware is fit for purpose and securely mounted. Single-Unit Fixed Central Mount: Single ZLM modules only: Mounting to a single side of the unit is acceptable using a minimum of two fasteners. ZLM2 and ZLM4 multi-unit assemblies must be mounted using Yoke Mounting instructions below. Installation of M6 mounting fasteners for fixed central mounting configuration. To provide adequate engagement, fasteners must have a minimum of 8mm and a maximum of 10mm exposed threads after insertion into user-supplied mounting hardware (not shown). 1. Mount unit to bracket or mounting surface using a minimum of (2) M6 fasteners. Torque mounting fasteners to 45 in-lb. Use of medium strength thread-locker (Loctite 242 or equivalent) is recommended for all mounting hardware. 2. (Optional) Attach secondary safety chain or cable to attachment point using cable, quick link, or other locking connector system with a suitable load rating. It is recommended that at least one secondary safety attachment is made for each unit. Secondary safety point is sized for ½” quick link chain or other locking connector. ZLM – Installation Manual Revision A-02 3|P a g e Yoke Mounting: Mounting for all ZLM, ZLM2, and ZLM4 configurations. Three M6 fasteners must be used for each side (not provided). To provide adequate engagement, fasteners must have a minimum of 8mm and a maximum of 10mm exposed threads after insertion into mounting hardware. 1. Loosely install central M6 mounting fastener on each side. If using an adjustable or multiposition bracket, aim fixture in desired direction. Install remaining (2) fasteners per side and torque all mounting fasteners to 45 in-lb. Use of medium strength thread-locker (Loctite 242 or equivalent) is recommended for all mounting hardware. 2. Attach secondary safety chain or cable to attachment points using cable, quick link, or other locking connector system with a suitable load rating. It is recommended that at least one secondary safety attachment is made on for ZLM and ZLM2 models. Two secondary safety attachment points should be used for ZLM4 models. Secondary safety point is sized for ½” quick link chain or other locking connector. ZLM – Installation Manual Revision A-02 4|P a g e WIRING ZLM units may be supplied with flying lead cable or Turck minifast quick connects. Turck mini-fast quick-connector: If present, connect Turck 7/8” minifast receptacles to appropriate power cable or harness. Turck connector harnesses may be purchased directly from Nemalux. For single units, use Turck RKM 36-3M connector cable. For ZLM2 units, use Turck T-36-1717-3/RKM 36-0.5/RKM 36-0.5 dual unit connector harness or (2) Turck RKM 36-3M connector cables. For ZLM4 units, use Turck T-34-198-3/0.2/0.2/RKM36-0.2/3RKM36-0.2/0.2/0.2 quad-unit connector harness, or (2) Turck T-36-1717-3/RKM 36-0.5/RKM 36-0.5 dual unit connector harnesses, or (4) Turck RKM 36-3M connector cables. Electrical Terminations Non-Dimming Units Non-dimming units are connected using three-conductor cables. To connect power to luminaires, make electrical terminations according to all applicable local codes and electrical safety regulations. Connect Green wire to Ground, White wire to Neutral, and Black wire to Line. Single phase input, 120VAC to 277VAC only. Dimming Units Dimming units are connected using five-conductor cables. To connect power to luminaires, make electrical terminations according to all applicable local codes and electrical safety regulations. Connect Green wire to Ground, White wire to Neutral, Black wire to Line, single phase input, 120VAC to 277VAC only. Connect Red to Positive 0-10V Dimming Control Line, Orange to Negative 0-10V Dimming Control Line. ZLM – Installation Manual Revision A-02 5|P a g e