RE: Job: ONU, Reed Hall, Phase 2 Bourbonnais, IL Submittal No./Rev: --Description: ONU PHASE II Lighting Controls REVIEWED REVISE AND RESUBMIT REVIEWED AND COMMENTED Checking is only for conformance with the design concept of the project and compliance with the information given in the contract documents. Contractor is responsible for dimension confirmation and correlation at the job site, for information that pertains solely to the fabrication processes or to techniques of construction, and for coordination of the work of all trades involved in the project. ELARA ENERGY SERVICES 30 N. Wolf Road Second Fl - Hillside, IL 60162 BY: Bhupendra Tailor DATE: 08-29-13 Notes: 1. No Mini-Z is required. Provide dimming relay “1DS’ in Greenmax panel as shown in the design documents for day light harvesting. 2. No model number selected for any of the product. 30 North Wolf Road, Second Floor, Hillside, IL 60162-1900 • Phone: (708) 236-0300 • Fax: (708) 236-0330 PRODUCT DATA Super Duty Power Pack Line High performance line includes models for daylight harvesting, bi-level switching, CA Title 24, occupancy sensing control, and manual switching OPP20 SOFTWARE FEATURES BY MODEL (CONT’D) OPP20-RD3 • Auto-ON occupancy sensor input • Photocell (switching only) ready DEFINITION The OPP20 is the latest addition to the Leviton Power Pack family, delivering a wide array of switching solutions in a single unit. Submitted for stringent testing, this robust Power Pack line is designed to deliver unmatched performance. The OPP20 line features robust and reliable mechanical latching relays, exclusive fail-safe circuitry, daylight harvesting, bi-level switching, and is configurable for energy code requirements (CA Title 24, ASHRAE, NYC LL48). Exclusive Leviton High Inrush Stability (H.I.S.™) circuitry is specifically designed to handle high inrush electronic ballast loads and offer unmatched durability and service. APPLICATIONS • Daylight Harvesting • Bi-level Switching • Plug Load Control • CA Title 24 • Auto-ON/Auto-OFF with Local Switch • Manual-ON/Auto-OFF with Local Switch OPP20 SOFTWARE FEATURES • Fail-safe/Return-to-Closed capability • Power interruption feature guarantees to close the relay; 5 seconds after power restoration, lights will return to current state OPP20 SOFTWARE FEATURES BY MODEL OPP20-OD1 • Auto-ON occupancy sensor input OPP20-RD4 • Exclusive self-detect configurable local switch input - momentary or maintained • Configurable for Auto-ON and Manual-ON occupancy sensor inputs • Photocell (switching only) ready • Complies with CA Title 24 OPP20 HARDWARE FEATURES • Robust and reliable mechanically held 20A latching relay provides dependability and robust performance for all load types and provides power savings over electrically held relay power packs • Industry exclusive fail-safe circuitry - in the event of product failure, Return-to-Closed capability causes relay to default to a closed position (ON) for safe operation and alleviates life safety concerns •Industry exclusive H.I.S. (High Inrush Stability) circuit designed to handle high inrush electronic ballast loads • Factory calibrated zero crossing for extended life of the relay •Submitted and passed for stringent testing: • Tested over 1,500,000 loaded cycles • Passed NEMA 410 testing for electronic ballast current overload at 16A • UL/cUL 916 Listed for Energy Management Equipment • Multiple compliance and regulatory UL and CSA testing - consult factory for details •Output short circuit protection •Internal voltage regulated at 24VDC, 225mA •Optimal installation flexibility • Class 2 wires are Teflon coated for UL2043 Plenum Rated applications • Mounts inside or outside fluorescent ballast cavity • Mounts inside or outside junction box • RoHS Compliant Leviton Mfg. Co., Inc. Lighting & Energy Solutions 20497 SW Teton Avenue, Tualatin, OR 97062 1-800-736-6682 Tech Line: 1-800-959-6004 Fax: 503-404-5594 www.leviton.com/les © 2013 Leviton Manufacturing Co., Inc. All rights reserved. Subject to change without notice. OPP20-0D1 • OPP20-0D2 • OPP20-RD3 • OPP20-RD4 OPP20-OD2 • Exclusive self-detect configurable local switch input - momentary or maintained • Configurable for Auto-ON and Manual-ON occupancy sensor inputs • Complies with CA Title 24 APPLICATION DIAGRAMS Auto ON/Auto OFF with Local Switch ue Local Switch ONLY Blue LOAD LOAD ed LOAD LOAD Red ck Black Occupancy Sensor Occupancy Sensor N White H Black Blue Blue Yellow/Orange OPP20-0 D2 OPP20-RD4 White/Blue N White Blue H Black Yellow/Orange OPP20-0 D2 OPP20-RD4 Blue Red White/Blue Blue Red Black Black m the same phase. Switch Switch Switch NOTE: Power Pack and the load switched by the power pack MUST be fed from the same phase. witch NOTE: Power Pack and the load switched by the power pack MUST be fed from the same phase. Dual Circuit with the “Add-a-relay” device Photocell with Local Switch ue Red Black Switching Photocell Required (by Others) Gray Switching Photocell Required (by Others) ue ed Blue N White H Black Yellow/Orange White/Blue All Models Blue Blue Blue Red Red Black Black LOAD LOAD ack LOAD LOAD Blue ed ack Occupancy Sensor LOAD LOAD Occupancy Sensor Gray Blue N White H Black Yellow/Orange OPP20-RD4 White/Blue Green Blue Blue Brown/White Blue Red OSA20-R00 N Black H Blue Brown Blue Red Black Switch m the same phase. Switch NOTE: Power Pack and the load switched by the power pack MUST be fed from the same phase. ad Rating NOTE: Power Pack and the load switched by the power pack MUST be fed from the same phase. JUNCTION BOX INSTALLATION Manual ON/Bi-Level Switching/Title 24 Figure 2 Figure 1 LOAD Blue LOAD Line Voltage Wires Red Black Line Voltage Wires Class 2 Wires Manual ON Class 2 Wires Occupancy Sensor Blue Yellow/Orange N White White/Blue H Black OPP20-RD4 Blue Blue Red Black k Mounts outside junction box Switch Occupancy Sensor LOAD FLUORESCENT BALLAST INSTALLATION Auto ON Figure 3A Blue Yellow/Orange N White White/Blue H Black Blue k OPP20-RD4 Figure 3B Class 2 Wires Blue Red Ballast Cavity Black Switch Class 2 Wires Ballast Cavity Ballast Occupancy Sensor m the same phase. Mounts inside junction box LOAD Ballast NOTE: Power Pack and the load switched by the power pack MUST be fed from the same phase. Nipple Adapter Line Voltage Wires Mounts inside Fixture Line Voltage Wires Mounts outside Fixture Leviton Mfg. Co., Inc. Lighting & Energy Solutions 20497 SW Teton Avenue, Tualatin, OR 97062 1-800-736-6682 Tech Line: 1-800-959-6004 Fax: 503-404-5594 www.leviton.com/les © 2013 Leviton Manufacturing Co., Inc. All rights reserved. Subject to change without notice. OPP20-0D1 • OPP20-0D2 • OPP20-RD3 • OPP20-RD4 Blue PRODUCT DATA SPECIFICATIONS ENVIRONMENTAL Operating Temperature Range 32°F to 122°F (o°C to 50°C) Relative Humidity 0% to 90% non-condensing, for indoor use only OTHER Construction Case: high impact, UL rated plastic Relay: 60A rated magnetic latching relay; silver alloy contacts Wire: 6” leads, 18AWG input; 14AWG load; LV connections: 8” leads 22AWG Dimensions 2.400”H x 3.811”W x 1.432”D (60.96mm x 96.80mm x 36.37mm) Listings UL/cUL Listed, FCC Certified, NOM Certified, Title 24 Compliant, and meets ASHRAE 90.1 requirements, RoHs Compliant Color Gray Warranty Limited Five-Year Warranty OPP20-0D1 • OPP20-0D2 • OPP20-RD3 • OPP20-RD4 ORDERING INFORMATION DESCRIPTION CAT. NO. Power Pack, Basic with Auto-ON OPP20-0D1 Power Pack with Auto-ON, Manual-ON, and Local Switch Inputs, Title 24 OPP20-0D2 Power Pack with Auto-ON and Photocell Input OPP20-RD3 Power Pack with Auto-ON, Manual-ON, Local Switch, and Photocell Input, Title 24 OPP20-RD4 CONTROL INPUTS POWER INPUT RELAY RATING 120-230-277VAC, 50/60 Hz 20A, 2400W @ 120V – Incandescent 20A, 2400VA @ 120V – Fluorescent 20A, 5540VA @ 277V – Fluorescent 16A, 4430VA @ 277V – Electronic Ballasts 1/2 HP @ 120V – Motor Load 2 HP @ 240/277V – Motor Load 2mA, 24VDC POWER SUPPLY OUTPUT 225mA, 24VDC, 5.4W POWER PACK CAPACITY FORMULA Leviton power packs can be used to provide power to one or more occupancy sensors. Since current consumptions of occupancy sensors may vary, the best way to ensure you order the correct number of power packs and add-a-relays is by using this formula: # of sensor Model As X + Sensor A current consumption # of sensor Model Bs X + Sensor B current consumption # of Add a Relays X 50mA < Power supply output per above chart DESCRIPTION CURRENT CONSUMPTION OSC04-I, OSC15-I, OSWHB-I, OSWLR-I, OSWWV-I 10-15mA OSC05-M, OSC05-U, OSW12-M 25mA OSC10-M, OSC10-U 35mA OSC20-M, OSC20-U 30mA OSA20-R Add-a-Relay 50mA Leviton Manufacturing Co., Inc. Global Headquarters 201 N. Service Rd., Melville, NY 11747-3138 • Tech Line: 1-800-824-3005 • FAX: 1-800-832-9538 Leviton Manufacturing Co., Inc. Lighting & Energy Solutions 20497 SW Teton Avenue, Tualatin, OR 97062 • Tel: 1-800-736-6682 • FAX: 503-404-5594 • Tech Line (6:00AM-4:00PM P.S.T. Mon-Fri): 1-800-959-6004 Leviton Manufacturing of Canada, Ltd. 165 Hymus Boulevard, Pointe Claire, Quebec H9R 1E9 • Telephone: 1-800-469-7890 • FAX: 1-800-563-1853 Leviton S. de R.L. de C.V. Lago Tana 43, Mexico DF, Mexico CP 11290 • Tel. (+52) 55-5082-1040 • FAX: (+52) 5386-1797 • www.leviton.com.mx Visit our Website at: www.leviton.com/les © 2013 Leviton Manufacturing Co., Inc. All rights reserved. Subject to change without notice. G-9008/B13-cds , Phone # Fax # ONU PHASE II Submittal For Leviton Manufacturing Co., Inc. Dimming and Lighting Control System Submittal Company Name: Address: City: Province / State: Postal Code / Zip: Country: Fax: Phone: Prepared By: August 26, 2013 Leviton Lighting & Energy Solutions Standard Warranty Statement Leviton Lighting & Energy Solutions, a division of Leviton Manufacturing Corporation Inc warrants its Dimmer, Relay, and Control Systems to be free of material and workmanship defects for a period of two years after system acceptance or 26 months after shipment, whichever comes first. This Warranty is limited to repair or replacement of defective equipment returned Freight PrePaid to Leviton Lighting & Energy Solutions at 20947 Teton Ave. Tualatin, Oregon 97062, USA. User shall call 1-800-959-6004 and request a return authorization number to mark on the outside of the shipping carton, to assure that the returned material will be properly received at Leviton. All equipment shipped back to Leviton must be carefully and properly packaged to avoid shipping damage. Replacements or repaired equipment will be returned to sender freight prepaid, F.O.B. factory. Leviton is not responsible for removing or replacing equipment on the job site, and will not honor charges for such work. Leviton will not be responsible for any loss of use time or subsequent damages should any of the equipment fail during the warranty period, but agree only to repair or replace defective equipment returned to its plant in Tualatin, Oregon. This Warranty is void on any product that has been improperly installed, overloaded, short circuited, abused or altered in any manner, or damaged by natural events such as lightning strike, or flood. Neither the seller nor Leviton Manufacturing shall be liable for any injury, loss or damage, direct or consequential arising out of the use of or liability to use the equipment. This Warranty does not cover lamps, ballasts, and other equipment that is supplied or warranted directly to the user by their manufacturer. Leviton makes no warranty as to the Fitness or Purpose of other implied Warranties. Warranty & Service Program Factory ECO · Leviton factory commissioning included with labor and travel expenses 24 hour / 7 days a week telephone support Expert Leviton Field Service Network Convenient product exchange program. Expedited shipping methods available upon request. SOME ITEMS MAY BE EXCLUDED FROM ENGINEERING SERVICES / COMMISSIONING. REFER TO THE BILL OF MATERIALS FOR MORE INFORMATION. Rep ECO · Rep agency is responsible for performing commissioning included with labor and travel expenses 24 hours/ 7 days a week, telephone support (factory support available). Agency is responsible for all system support for the warranty period (2 years). Parts and labor included. No ECO · Purchaser is responsible for commissioning the equipment including all labor and travel expenses. 24 hour / 7 days a week telephone support (factory support available). Purchaser is responsible for all system support for the warranty period (2 years) as per the Standard Warranty Statement above. Lighting & Energy Solutions 20497 S.W. TETON AVE TUALATIN, OR 97062 (503)404-5500 http://www.leviton.com PROJECT: ONU PHASE II TITLE: Warranty Statement QUOTE: DS-463343 LOCATION: QUOTE NAME: ONU PHASE II REVISION: 1 DATE: August 26, 2013 SHEET: 2 of 22 Bill of Material # 463343 ONU PHASE II August 26, 2013 ITEM QTY PART NO. 1.0 1 MZD30-101 1.1 1.2 1 10 PCSKY OSC20M0W 1.3 7 OSW12M0W 1.4 12 OSSMTGDW 1.5 1 R16TC-100 1.6 1 RPM08-108 1.7 1 R1600 1.8 1 1.9 1.10 1.11 15 1 1 RELAY1DS RELAY-1TB ODC0P-W RHDU1 2.0 1 FREIGHT 3.0 1 ECO 4.0 1 Lighting & Energy Solutions 20497 S.W. TETON AVE TUALATIN, OR 97062 (503)404-5500 http://www.leviton.com DESCRIPTION Advanced Bill of Materials miniZ™ Controller, Basic Model with (3) Zone 0-10VDC, Mark 7 Type Dimming Ballast Control and (1) 0-277VAC, 20A 1-pole Relay Photocell - Skylight 10-7500fc (out of the box default: 10-2000fc) Sensor Type: Multi-Technology, Mount: Ceiling, Coverage Range Sq. Ft.: 2000 Sq. Ft., Adjustment: Self-Adjusting, Pattern Degrees: 360, Title 24 Compliant: Yes, Grade: Commercial, Color: Off-white Sensor Type: Multi-Technology Wall Corner, Coverage Range Sq. Ft.: 1200 Sq. Ft., Pattern Degrees: 110, Title 24 Compliant: Yes, Grade: Commercial, Color: Off-white Product Line: OSSMT, Technology: Multi-Technology PIR/Ultrasonic, Switch Type: Single-Pole, Mounting: Wall Switch, Device Type: Occupancy Sensor, Coverage (Sq.Ft.): 2400 Sq. Ft., Pattern: 180°, Color: White, Warranty: 5-Year Limited GreenMAX Relay Cabinet, 16-Relay Size, Surface Mount, Domestic, with Locking Door, Nema 1 GreenMAX Main Command Module comprised of a Power Supply and Main Processor Unit, with an 8-port Low Voltage Input Card, 100-277VAC GreenMAX 16-position Relay Insert Panel (fits 16, 32, 48-relay cabinets), without relays GreenMAX Relay, Latching, 1-pole, Dimming and Switching with voltage and current sensing, 30A 24-277, 347VAC 50/60Hz GreenMAX Relay, Latching, 1-pole, basic, 30A 24-277, 347VAC 50/60Hz Photocell - Indoor 0-70fc GreenMAX Handheld Display Unit SYSTEM SERVICES Freight: This project is quoted F.O.B. factory, surface freight prepaid to the jobsite. Any special delivery services (air-freight, expedited delivery, etc.) may incur additional charges. Engineering Services: System Check-Out, Commissioning and Training by a Factory Authorized Engineer. Engineering Services require a minimum of three (3) weeks advance notice. Warranty: Leviton lighting systems are warranted against defects in material and workmanship for two (2) years from date of shipment. Units returned to the appropriate Leviton office will be repaired at no charge, excepting surface freight. Contact your Leviton Representative for details. PROJECT: ONU PHASE II TITLE: Bill of Materials QUOTE: DS-463343 LOCATION: QUOTE NAME: ONU PHASE II REVISION: 1 DATE: August 26, 2013 SHEET: 3 of 22 Product Specifications miniZ™ miniZ™ miniZ Intelligent Daylight Management System DESCRIPTION miniZ combines occupancy sensing, daylight harvesting and flexible lighting control functions into a single, easily installed package. miniZ features several methods of ladderless commissioning, one of which is the AutoCal feature, the world’s first ever 100% self-configuring daylight harvesting system. Installation requires little more than any other power-pack type product. The performance, features, and capabilities of the miniZ product provide a package that surpasses all others in the industry – at a price anyone can afford. FEATURES • Automatic Correction for Light Loss Factor (LLF) • Recognizes and corrects for Lumen Maintenance Issues • Cost effective energy code compliance • Ladderless Commissioning™ provides install-and-forget convenience • Automatic closed loop multi-zone daylight control • Convenient occupancy sensor and photocell integration SIMPLEST INSTALL STEPS • Simplified daylight harvesting with full range dimming 1. Physically install unit and any peripherals • Autocal™ (patent pending) automatic photocell calibration 2. Terminate power & control wiring • Accepts external time clock inputs 3. Enable AutoCal & Auto-Burn-In • Simplified integration with emergency systems 4. Power up system • Controls maximum lighting output for additional energy savings potential 5. Installation & configuration complete! • Daylight switching, full range 0-10V dimming and network models available Dimensions: 6.65"L x 6.65"H x 2.1"D Network Features: Shipping Weight: 4lbs. • Luma-CAN Network Support Unit Weight: 3.3lbs. • Network Digital Switches 1/2" & 3/4" conduit knockouts • Z-MAX Master/Slave Network Participation 1/2" nipple with pigtails for easy line voltage connections • Remote Shared Network Inputs • Scalable System Expansion Lighting & Energy Solutions 20497 S.W. TETON AVE TUALATIN, OR 97062 (503)404-5500 http://www.leviton.com PROJECT: ONU PHASE II TITLE: Product Cut Sheets - MZD30-101 QUOTE NAME: ONU PHASE II REVISION: 1 QUOTE: DS-463343 DATE: August 26, 2013 SHEET: 4 of 22 Product Specifications miniZ™ ............................. 1/2" nipple for convenient connection to junction box Control Input (100-277VAC or 200-347VAC)* Neutral Circuit 1 Line Circuit 1 Load Zone 1 Output (0-10V)* Circuit 2 Line Circuit 2 Load Zone 2 Output (0-10V)* Zone 3 Output (0-10V)* Low Voltage Terminal & Configuration Board AutoCal – enable automatic self-calibration Configuration Jumpers HVAC and/or Emergency Output Relays* Daylight Harvesting Target – Manual Adjustment Emergency Input Also can be configured as Occupancy Sensor disable Photocell Disable Temporarily disables daylight harvesting mode Switch Inputs + Momentary + Maintained + Supports SPDT Center Off Switches +Annunciator/Pilot Light Support Photocell Input Supplies +24vdc Expects +0-10vdc return Time Clock Turns off lights when input receives +24VDC Occupancy Sensor Input Supplies +24vdc Expects +24vdc return Load Shed When high, lights dim to load level *Varies depending on model Low Voltage Common ORDERING INFORMATION Load Ratings: 20A per relay, 120/277V Part # 15A per relay, 347V 20A Power Circuits 0-10V Control Circuits Control Input Voltage Network Functionality 2 0 100-277VAC No Fluorescent, non-dimmed and 0-10V dimmed mZb00-102 120mA power output for operation of occupancy sensors, etc. mZd20-102 2 2 100-277VAC No mZd30-101 1 3 100-277VAC No mZn20-102 2 2 100-277VAC Yes Power: mZn30-101 1 3 100-277VAC Yes Input Power: 120, 277, or 347V*; 10W Max, 50/60Hz mZb00-C02 2 0 200-347VAC No 1. Output Power 1 or 2* circuits, up to 277V, 20A, or, 1 or 2* circuits, up to 347V, 15A mZd20-C02 2 2 200-347VAC No mZd30-C01 1 3 200-347VAC No mZn20-C02 2 2 200-347VAC Yes mZn30-C01 1 3 200-347VAC Yes 2. Output 0-10V Control: 0, 2, or 3 zones* Available Peripheral Power: 120mA, 24V Lighting & Energy Solutions 20497 S.W. TETON AVE TUALATIN, OR 97062 (503)404-5500 http://www.leviton.com PROJECT: ONU PHASE II TITLE: Product Cut Sheets - MZD30-101 QUOTE NAME: ONU PHASE II REVISION: 1 QUOTE: DS-463343 DATE: August 26, 2013 SHEET: 5 of 22 PRODUCT DATA Photocells Photocells must be hardwired to a compatible Leviton lighting control system. The photocell measures ambient light in a specific area and sends this data to a dimmer or relay that, in turn, adjusts fixtures to a constant lighting level as measured in that specific area. Daylight Harvesting is achieved as lights in a room (with windows or significant, artificial ambient light) automatically brighten or dim depending on how much light the photocell detects. DAYLIGHT HARVESTING With Daylight Harvesting, ambient (often natural) light supplements in-room, artificial light in order to keep a constant lighting level while saving energy. This constant level is programmed into a compatible control device. Once hardwired to the photocell, the dimmer or relay will receive the photocell’s real-time light measurement and maintain a steady level within the photocell’s area of detection. Lighting & Energy Solutions 20497 S.W. TETON AVE TUALATIN, OR 97062 (503)404-5500 http://www.leviton.com RULES OF OPERATION Measured light level = Light Maintain Level Action: Output to lights remains constant Measured light level < Light Maintain Level Action: Lights are brightened Photocells Leviton’s Photocell sensors precisely monitor either task or ambient light levels. As part of a Leviton energy management system, photocells work with other components in the system to automatically adjust light levels to a userdefined level. Photocells are most suitable for installation in rooms with windows and open spaces receiving substantial ambient light. Measured light level > Light Maintain Level Action: Lights are dimmed Footcandles Energy Savings Begin Light Maintain Level Min. Light Level Perceived Light Level 6AM 8AM 10AM NOON Light generated from fixture attached to Leviton Lighting Control System 2PM 4PM 6PM Ambient light PROJECT: ONU PHASE II TITLE: Product Cut Sheets - PCSKY, ODC0P-W QUOTE NAME: ONU PHASE II REVISION: 1 QUOTE: DS-463343 DATE: August 26, 2013 SHEET: 6 of 22 Photocells PRODUCT DATA FEATURES • Indoor photocells designed with a flat Fresnel lens that looks downward in a 60° cone of reference to measure actual light on the work surface, and reducing the influence of stray light striking the photocell from nearby windows or incidental side lighting • Outdoor photocells are IP54 rated to guarantee ultimate protection from dirt, dust, oil, and other non-corrosive material • Measures light from any source in the visible spectrum within a 60º cone or 180º angle of response depending on the model • ODC0P photocell with 60° clear Fresnel lens operates between 0-70fc. ODC0P should be surface mounted or direct to ceiling box • PCIND indoor photocell with 60° clear Fresnel lens is default setting = 0-100fc sensing range; can be field adjusted to 750fc max sensing range. PCIND should be mounted to the ceiling, facing down • PCOUT outdoor photocell is enclosed in a weatherproof housing with a visor for shading and lens protection. Default setting = 0-250fc sensing range • PCIND-0SV side veiw photocell for applications where ceiling mounting is required yet the view should be of the lighting entering the space through a window; or, for insallation to the wall of skylights where the view should be up into the skylight. Default setting = 0-3fc sensing range; can be field configured with a jumper for a 3fc, 30fc, 300fc, or 600fc max sensing range • PCOUT-0SV side view photocell for applications where wall mounting is required yet the view should be of the lighting entering the space through a top/side and/or face of the photocell. Reference placement diagrams. Default setting = 0-3fc sensing range; can be field configured with a jumper for a 3fc, 30fc, 300fc, or 600fc max sensing range • PCATR atrium photocell with opaque dome lens filters 33% of light level in upper atrium. Default setting = 0-1000fc sensing range; can be field adjusted to 2500fc max sensing range • PCSKY skylight photocell with dark dome lens filters 90% of light level in skylight. Default setting = 0-2000fc sensing range; can be field adjusted to 7500fc max sensing range DIMENSIONS PHOTOCELL (ODC0P) Diameter: 2.511” 0.23” 0.99” OUTDOOR (PCOUT) INDOOR (PCIND) 1.85” 1.15” 1.35” 1.28” SIDE VIEW PHOTOCELL (PCIND-0SV/PCOUT-0SV) 1.36” Diameter: 2.04” ATRIUM/SKYLIGHT (PCATR/PCSKY) BENEFITS • Constant lighting at the optimal level for greater visual comfort and acuity, which contributes to improved productivity • Provides convenient, automatic hands-free daylight harvesting when integrated with Leviton lighting control products • Lowers electric bills by reducing usage of lighting where ambient natural light is also present • Lumen maintenance opportunity compatible Lighting & Energy Solutions 20497 S.W. TETON AVE TUALATIN, OR 97062 (503)404-5500 http://www.leviton.com 0.76” 2.25” 1.28” PROJECT: ONU PHASE II TITLE: Product Cut Sheets - PCSKY, ODC0P-W QUOTE NAME: ONU PHASE II REVISION: 1 QUOTE: DS-463343 DATE: August 26, 2013 SHEET: 7 of 22 PHOTOCELL PLACEMENT ODC0P/INDOOR PHOTOCELL MOUNTING LOCATION ATRIUM PHOTOCELL MOUNTING LOCATION PCATR ODC0P or PCIND 6-8 FT. Ideal photocell location is in the middle of the atrium glass pointing toward the glass REFLECTING WALL USING INDOOR SENSOR SKYLIGHT APPLICATION WITH SKYLIGHT PHOTOCELL 18” Sconces PCIND Photocell in 1/2” conduit. Photocell must be at least 12” from side of skylight and facing up PCIND UNISTRUT 60 NOTE: Support conduit from unistrut as required per NEC Photocells Light well - with sconces - (UP or UP/DOWN) Mount photocell in elevation on centerline of fixture. Do not mount directly in line with sconces. Top of photocell should be level with top of skylight curb 1/4” ANGLE SUPPORT JUNCTION BOX Light well - no sconces - indoor photocell OUTDOOR PHOTOCELL MOUNTED IN 1/2” CONDUIT North Snow Line Outdoor photocell mounted horizontally on roof or equal, facing northern sky Hooded portion on top, pointed away from any nighttime light sources Lighting & Energy Solutions 20497 S.W. TETON AVE TUALATIN, OR 97062 (503)404-5500 http://www.leviton.com PROJECT: ONU PHASE II TITLE: Product Cut Sheets - PCSKY, ODC0P-W QUOTE NAME: ONU PHASE II REVISION: 1 QUOTE: DS-463343 DATE: August 26, 2013 SHEET: 8 of 22 PRODUCT DATA INSTALLATION • Low Voltage Class 2 Wiring - Connect directly to dimmer or relay panel SPECIFICATIONS ODC0P PCIND PCOUT PCIND-0SV Input Voltage 24VDC Input Current 10mA IP Rating PCOUT-0SV PCATR PCSKY 32 20 54 20 54 65 65 Default Range 0-70 fc 50-750 fc 50-750 fc 0-30 fc 0-300 fc 200-2500 fc 1000-7500 fc Output Voltage 0-10VDC 10 VDC full output 0-10VDC 10VDC full output 0°C to 55°C -11°C to 60°C -40°C to 50°C -11°C to 60°C Operating Temperature Range Storage Temperature Range -10°C to 85°C Relative Humidity 20% to 90% non-condensing Warranty 2-Year Warranty SELECTION PHOTOCELL LENS MOUNTING ORIENTATIONHEIGHT DIAMETER ODC0P-000 PCIND-000 PCIND-0SV PCOUT-000 PCOUT-0SV PCATR-000 PCSKY-000 Diffuse Fresnel Diffuse Clear Hood Diffuse Dome/Frost Dome/Frost Ceiling Ceiling Ceiling/Wall ½” IPT Ceiling/Wall ½” IPT ½” IPT Down Down Up/Down Horizontal Up/Down Horizontal Up 2.51” (6.4cm) 1.23” (3.1cm) 2.04” (5.2cm) 1.28” (3.3cm) 2.04” (5.2cm) 1.28” (3.3cm) 1.28” (3.3cm) Photocells ORDERING INFORMATION CAT. NO. 0.99” (2.5cm) 2.00” (5.1cm) 1.36” (3.45cm) 1.85” (4.7cm) 1.36” (3.45cm) 2.25” (5.7 cm) 2.25” (5.7 cm) ADJUSTABLE CORRESPONDING FC RANGES DESCRIPTION COLOR ODC0P-000Photocell PCIND-000 Indoor Photocell PCIND-0SV Indoor Photocell PCOUT-000 Outdoor Photocell PCOUT-0SV Outdoor Photocell PCATR-000 Atrium Photocell PCSKY-000 Skylight Photocell White White White White White White White SENSOR MAXIMUM ODC0P 0-70FC PCIND 50-750FC PCIND-0SV 3, 30, 300 or 600FC PCOUT 50-750FC PCOUT-0SV 3, 30, 300 or 600FC PCATR 200-2500FC PCSKY 1000-7500FC LEVITON SPECIFICATION SUBMITTAL JOB NAME: JOB NUMBER: Lighting & Energy Solutions 20497 S.W. TETON AVE TUALATIN, OR 97062 (503)404-5500 http://www.leviton.com CATALOG NUMBERS: PROJECT: ONU PHASE II TITLE: Product Cut Sheets - PCSKY, ODC0P-W QUOTE NAME: ONU PHASE II REVISION: 1 QUOTE: DS-463343 DATE: August 26, 2013 SHEET: 9 of 22 PRODUCT DATA Multi-Technology Ceiling Occupancy Sensor FEATURES GENERAL OPERATION Occupancy sensors have two tasks: 1) Keeping the lights ON while the room is occupied, and 2) Saving energy by keeping the lights OFF while the room is unoccupied. Passive Infrared (PIR) is an excellent and precise technology for initially turning the lights ON, but lacks sensitivity for minor motion at distances. Ultrasonic (U/S) technology provides maximum sensitivity with continuous reflective high frequeny waves. This is opitmal for keeping the lights ON. Leviton’s multi-technology sensor combines the benefits of both PIR and U/S technologies for unrivaled performance and reliability. APPLICATIONS • Cafeterias • Computer rooms • Day care centers • Workspaces • Offices with cubicles • Restrooms • Storage rooms • Classrooms • Conference rooms • Filing rooms • Open warehouses • Open areas • Stairwells • Executive, open, and private offices OSCxx-M0W • Self-Adjusting: Internal microprocessor con­tin­u­al­ly analyzes, evaluates and adjusts the sensitivity and time delay. Performance is kept at a maximum and user complaints are eliminated. • Custom off-white color matched for shaded ceilings. • Fast, Simple In­stal­la­tion: Easy ceiling mount, three wire con­nec­tion (low voltage) and twist-lock sensor attachment for 360° rotation and flexibility. • Maximum Reliability, Low Cost: digital circuitry uses a minimum of components. • Small Motion Sensitivity: The ultrasonic tech­nol­o­gy provides excellent small motion sensitivity. • Timer Setting Feature: Automatic – 30sec – 30min. Test mode – 6sec with auto exit programming. • Non-Volatile Memory: Learned and adjusted settings saved in protected memory are not lost during power outages. • Walk-Through: Provides increased energy savings by decreasing the time delay to 2.5min when someone momentarily walks through the monitored space. • Wide Coverage: Units from 500 to 2000 sq. ft. available. • Power base (OPB 15) available for line voltage applications • Ambient Light Recognition: A Light Sensor prevents lights from turning on when the room is adequately lit by natural light. • Ultrasonic (U/S) Components: One or two U/S transducers and one or two narrow bandwidth receivers each 16mm in diameter. Frequency -Crystal controlled to ±.005%. • Device: Rug­ged, high-im­pact, in­jec­tion molded plas­ tic, off -white. Col­or coded leads 6” (16.24 cm). HOW THE OSCxx-M AUTOMATICALLY ADAPTS Condition Timer Left In Test Mode - The sensor remains in an 6 sec. test mode. Example An installer accidentally leaves the sensor in the 6 sec. timer test mode and the lights may go off or on every 6 sec. Self-Adaptive Reaction The sensor automatically resets the timer to 10 min after . 15 min of test mode. False-On - The sensor incorrectly turns the lights on. The sensor detects movement in the corridor or hall way and the room lights turn on. After an initial movement is sensed, if another mov ement is not sensed within the timer setting then the delayed off time setting is automatically reduced. False-Off - The sensor incorrectly turns the lights off. The sensor does not detect movement because an occupant sits virtually motionless at a desk and the lights turn off. If motion is sensed within a short period after the lights go off, then the current delayed off-time setting is increased. Lighting & Energy Solutions 20497 S.W. TETON AVE TUALATIN, OR 97062 (503)404-5500 http://www.leviton.com PROJECT: ONU PHASE II TITLE: Product Cut Sheets - OSC20-M0W QUOTE NAME: ONU PHASE II REVISION: 1 QUOTE: DS-463343 DATE: August 26, 2013 SHEET: 10 of 22 PRODUCT DATA DIP SWITCH SETTINGS SWITCH SWITCH FUNCTIONS BANK A OFF A1 N/A Multi-Tech A2 N/A PIR A3 Manual Mode Auto Adapting Enabled A4 Walk-Thru Disable Walk-Thru Enabled BANK B B1 Override to On Auto Mode B2 Override to Off Auto Mode B3 Test Mode OFF’ON’OFF B4 LED Disable LEDs Enabled DIMENSIONS SWITCH SETTINGS ON Single Tech Ultrasonic Auto Adapting Disabled Walk-Thru Disabled Lights forced On Lights forced Off Enter/Exit Test Mode LEDs Disabled *Bold items are factory defaults FIELD-OF-VIEW SPECIFICATIONS TOP VIEW ELECTRICAL20 20 Power Requirements 20 16 24 VDC, from11.5OSPxx Power Pack or OPB15 Power Base 8.5 11.5 8.5 Power Consumption 11.5 OSC05: 25mA, OSC10: 35mA, OSC20: 30mA 0 0 0 Output TOP VIEW TOP VIEW 24 VDC active high logic control signal with short circuit protection 8.5 8.5 11.5 11.5 11.5 CONTROLS 16 20 Ultrasonic Sensitivity 0-100%; green knob (factory setting: 50%) SIDE VIEW 8 Infrared Sensitivity SIDE VIEW 0-100%; red knob; (factory setting: 75%) 8 20 20 Light Sensor 0 0 3 5.6 9 11 Time Delay OCS05-M0W 15 20 to 3,000 Lux; blue knob; factory set at 0 20 20 15 11 9 5.6 3 0 3 5.6 9 11 15 100% (*grey wire23required) 23 17 17 17 20 30sec-30min;OSC10-M0W black knob (factory setting: 10min) OSCxx-M0W 15 11 9 5.5 3 0 3 5.5 9 11 15 20 22.5 OSC20-M, 2000 sq. ft. 32 TOP VIEW 20 TOP VIEW 20 20 U/S motion technology Red LED Infrared motion technology 20 11.5 8.5 16 8.5 11.5 11.5 11.5 8.5 8.5 Minor Motion, Ultrasonic 0 0 Major Motion, Ultrasonic 0 0 0 32°F to 104°F (o°C to 40°C) TOP VIEW 20 11.5 Major Motion, IR ENVIRONMENTAL 8.5 8.5 8.5 8.5 0% to 95% non-condensing, for indoor use only 8-12 feet Listings CUL/US Certified, meets ASHRAE Standard 90.1 and CEC Title 24 requirements 16 20 20 20 20 20 SIDE VIEW 8 0 0 Limited Five-Year Warranty 11.5 11.5 8 Mouting Height 11.5 11.5 11.5 OTHER Warranty OSC20-M0W 20 22.5 TOP VIEW Green LED Relative Humidity 32 23 INDICATORS Operating Temperature Range Major Motion, PIR SIDE VIEW 8 SIDE VIEW 0 03 5.6 3 5.6 9 119 11 15 0 0 1520 2320 23 17 23 17 OSC05-M, 500 sq. ft. OCS05-M0W OCS05-M0W SIDE VIEW SIDE VIEW 8 8 20 8 15 2011 9 155.6 11 3 90 5.6 3 5.6 15 92011 15 3 90 113 5.6 20 17 23 23 17 23 17 17 OSC10-M, 1000 sq. ft. OSC10-M0W OSC10-M0W PHYSICAL WIRING ORDERING INFORMATION CAT NO. DESCRIPTION OSC05-M0W Multi-Technology Ceiling Sensor, 500 sq. feet of coverage Major Motion, IR OSC10-M0W Multi-Technology Ceiling Sensor, 1000 sq. feet of coverage OSC20-M0W Multi-Technology Ceiling Sensor, 2000 sq feet of coverage Minor Motion, MajorUltrasonic Motion, IR Major Motion, Ultrasonic Minor Motion, Ultrasonic Major Motion, Ultrasonic NAFTA compliant and Made in USA models available Lighting & Energy Solutions 20497 S.W. TETON AVE TUALATIN, OR 97062 (503)404-5500 http://www.leviton.com PROJECT: ONU PHASE II TITLE: Product Cut Sheets - OSC20-M0W QUOTE NAME: ONU PHASE II REVISION: 1 QUOTE: DS-463343 DATE: August 26, 2013 SHEET: 11 of 22 32 OSC20-M0W PRODUCT DATA • • • • BASIC OPERATION Occupancy sensors have two tasks: 1) Keeping the lights ON while the room is occupied, and 2) Saving energy by keeping the lights OFF while the room is unoccupied. Passive Infrared (PIR) is an excellent and precise technology for initially turning the lights ON, but lacks sensitivity for minor motion at distances. Ultrasonic (U/S) technology provides maximum sensitivity with continuous reflective high frequeny waves. This is opitmal for keeping the lights ON. Leviton’s OSW12 sensor combines the benefits of both PIR and U/S technologies for unrivaled performance and reliability. • • • • • • APPLICATIONS • Cafeterias • Classrooms • Conference rooms • Computer rooms • Day care centers • Filing rooms • Offices with cubicles • Open areas • Partitioned restrooms • Storage rooms • Open warehouses • Workspaces • Executive, private and open offices • • • • HOW THE OSW12-M AUTOMATICALLY ADAPTS Condition Timer Left In Test Mode - The sensor remains in an 6 sec. test mode. Example An installer accidentally leaves the sensor in the 6 sec. timer test mode and the lights may go very 6 sec. Self-Adaptive Reaction The sensor automatically resets the timer to 10 min after . 15 min of test mode. False-On - The sensor incorrectly turns the lights on. The sensor detects movement in the corridor or hall way and the room lights turn on. After an initial movement is sensed, if another mov ement is not sensed within the timer setting setting is automatically reduced. The sensor does not detect movement because an occupant sits virtually motionless at a desk and the If motion is sensed within a short period after incorr The sensor Lighting & Energy Solutions 20497 S.W. TETON AVE TUALATIN, OR 97062 (503)404-5500 http://www.leviton.com • the sensor minimizes false triggering for high reliabil ity. Flexible Base Mounting: Supplied twist-and-lock base mount permits fast alignment. Supplied cover hides mounting hardware and wires. Can be used with raceways for hard surface installations. Adjustable canopy for wall or ceiling mount. Wide Coverage: Over 1200 sq. ft of coverage. Fast, Simple Installation: A single mounting post and three color coded wires make installation easy. Self-Adjusting: Internal microprocessor con tinually analyzes, evaluates and adjusts sensitivity and time delay settings. Performance is kept at a maximum and user complaints are eliminated. Non-Volatile Memory: Learned and adjusted settings saved in protected memory are not lost during power outages. Timer Setting Feature: Automatic – 30sec – 30min. Test mode – 6sec with auto exit programming. Ambient Light Recognition: A Light Sensor prevents lights from turning on when the room is adequately lit by natural light. Walk-Through: Provides increased energy savings by decreasing the time delay to 2.5min when someone momentarily walks through the monitored space. Custom off-white color matched for shaded ceiling/ corner spaces and most common ceiling tiles. Uses OSPxx Series Power Pack: Uses Class 2, 24 volt wiring, three wire connection (low voltage). Multiple sensors can control single or multiple power packs. Power base (OPB 15) available for line voltage applications High Motion Sensitivity: The large lens area and multi-element lens design give excellent range and sensitivity. Infrared Sensing: High sensitivity 9.8 micron detector dual element. Device: High-impact housing and injection molded plastic. Color coded wire leads are 6” long (16.24 cm). Lens: 110˚ aperture, lens opening 2.2” x 1.47”, 36 elements (72 zones) small motion range 31 ft, large motion 68 ft PROJECT: ONU PHASE II TITLE: Product Cut Sheets - OSW12-M0W QUOTE NAME: ONU PHASE II REVISION: 1 QUOTE: DS-463343 DATE: August 26, 2013 SHEET: 12 of 22 OSW12-M0W Multi-Technology Wall/Corner FEATURES Occupancy Sensor • Multi-Technology: By using both PIR and U/S signals, PRODUCT DATA ADJUSTMENT RANGE MOUNTING BRACKET DIMENSIONS Base Cover Sensor Mounting Base Base Cover Long Range Lens 6.43 inch Mounting Base 4.23 inch 4.67 inch Sensor DIP SWITCH SETTINGS SWITCH BANK A A1 N/A A2 N/A A3 Manual Mode A4 Walk-Thru Disable BANK B B1 Override to On B2 Override to Off B3 Test Mode B4 LED Disable 2.80 inch SWITCH FUNCTIONS SWITCH SETTINGS OFF ON Multi-Tech Single Tech PIR Ultrasonic Auto Adapting Enabled Auto Adapting Disabled Walk-Thru Enabled Walk-Thru Disabled Auto Mode Auto Mode OFF’ON’OFF LEDs Enabled Lights forced On Lights forced Off Enter/Exit Test Mode LEDs Disabled FIELD-OF-VIEW Field of View (in feet) TOP VIEW 58 31 16 11.5 *Bold items are factory defaults 0 SPECIFICATIONS 11.5 16 ELECTRICAL Power Requirements 24 VDC, 25 mA (.6W) from OSPxx Power Pack or OPB15 Power Base Power Consumption 25mA Stand-by Output 24 VDC active high logic control signal with short circuit protection 31 Minor Motion, IR Major Motion, IR 58 Minor Motion, Ultrasonic SIDE VIEW 8 Major Motion, Ultrasonic OSW12-M0W CONTROLS Ultrasonic (U/S) Sensitivity 0 to 100%: red knob (factory setting: 75%) Infrared Sensitivity 0 to 100%: green knob (factory setting: 50%) Light Sensor Blue knob 20 to 3,000 Lux. Factory set at 100% (Grey wire required) Time Delay 30sec-30min; black knob (Factory setting: 10min) 0 03 8 15 INDICATORS Red LED Infrared motion technology Green LED Ultrasonic (U/S) motion technology 68 31 32 23 PHYSICAL WIRING NC-Brown Common-Green NO-Brown/White Black ENVIRONMENTAL Sensor Blue (Control) Operating Temperature Range 32°F to 104°F (o°C to 40°C) Relative Humidity 0% to 95% non-condensing, for indoor use only Black Red OSPxx Series Power Pack OTHER Black Blue* (occupancy) Gray* Blue Mouting Height 8-10 feet Listings CUL/US Certified, meets ASHRAE Standard 90.1 and CEC Title 24 requirements Warranty Limited Five-Year Warranty Hot (Black) Blue Red Black Line 120-277-347VAC 60Hz Load (photocell + occupancy) Black White Blue* White (occupancy) Gray* (photocell + occupancy) ORDERING INFORMATION Neutral (White) CAT NO. DESCRIPTION OSW12-M0W Multi-Technology Wall/Corner Occupancy Sensor Lighting & Energy Solutions 20497 S.W. TETON AVE TUALATIN, OR 97062 (503)404-5500 http://www.leviton.com To HVAC System Red (24VDC) NAFTA compliant and Made in USA models available PROJECT: ONU PHASE II TITLE: Product Cut Sheets - OSW12-M0W QUOTE NAME: ONU PHASE II REVISION: 1 QUOTE: DS-463343 DATE: August 26, 2013 SHEET: 13 of 22 PRODUCT DATA Decora Wall Switch Multi-Technology Occupancy Sensor OSSMT-MD/GD The PIR sensors provide immunity to false ON through a specialized Fresnel lens which divides the field-ofview into sensor zones. When a person passes into or out of a sensor zone, the sensor detects motion and switches the lights ON. The Ultrasonic (U/S) sensors provide maximum sensitivity and range in difficult spaces with irregular shaped rooms and partitions that can block the PIR field-of-view. A pair of U/S sensors will detect Doppler shifts caused by motion in a space preventing false OFF. These sensors are more sensitive to small movements since they do not rely on zones. • Retrofit • Classrooms • Private and executive offices • Lounges • Conference rooms • Training areas • Storage areas • Restrooms • Multi-location switching (similar to 3-way) SELF-ADAPTIVE TECHNOLOGY Designed for “install and forget” use, the OSSMT automatically analyzes room conditions and adapts to errors or changing environment. HOW THE OSSMT-MD AUTOMATICALLY ADAPTS APPLICATIONS Leviton’s OSSMT Multi-Technology Decora Style Wall Switch Occupancy Sensor is used to provide automatic lighting control for energy savings and convenience in a variety of commercial applications: Lighting & Energy Solutions 20497 S.W. TETON AVE TUALATIN, OR 97062 (503)404-5500 http://www.leviton.com OSSMT BASIC OPERATION Occupancy sensors have two tasks: keeping the lights ON while the space is occupied and turning the lights OFF when unoccupied. CONDITION EXAMPLE ADAPTIVE REACTION False-ON: Sensor incorrectly turns the lights ON. The sensor detects movement in the corridor or hallway and the room light turns ON. After an initial movement is sensed, if another movement is not sensed within the timer setting the delayed off-time setting is automatically reduced. False-OFF: Sensor incorrectly turns the lights OFF. The sensor does not detect movement because an occupant is virtually motionless and the lights turn OFF. If motion is detected shortly after the lights go OFF, the current delayed offtime setting is increased. PROJECT: ONU PHASE II TITLE: Product Cut Sheets - OSSMT-GDW QUOTE NAME: ONU PHASE II REVISION: 1 QUOTE: DS-463343 DATE: August 26, 2013 SHEET: 14 of 22 OSSMT PRODUCT DATA Lighting & Energy Solutions 20497 S.W. TETON AVE TUALATIN, OR 97062 (503)404-5500 http://www.leviton.com • Exclusive Leviton H.I.S. Circuitry. Specifically designed to handle today’s high inrush electronic ballast loads and offer unmatched durability and service. • True Zero-Cross Relay switches at the zero crossing point of the AC power curve to ensure maximum contactor life and compatibility with electronic ballasts. FIELD-OF-VIEW The OSSMT provides a 180° field-of-view with a maximum coverage area of approximately 2400 square feet. The maximum sensing distance in front of the sensor is 40 feet, and side to side is 30 feet. The “minor motion” zone detects relatively small body movements and allows the lights to stay ON even though a person may not be moving or walking around the room. The remainder of the field-ofview, the “major motion” zone, exhibits a lesser degree of sensitivity and requires larger movements. TOP VIEW 30 Mounting Yoke Vandal Resistant PIR Lens 20 Patented Masking Blinders 0 2.60 (66.2 mm) FEATURES • Fast, simple Installation: Fits in a standard wall box and replaces a single-pole wall-switch; neutral and no neutral options available. Sensor can be ganged together with other units in a multiple-switch wall plate. • Low-profile design eliminates obtrusive “scanning-device” look. Elegant Decora styling complements any interior; uses Decora wallplates and coordinates with Leviton’s popular line of Decora wiring devices. • Convenient Pushbutton provides manual-ON/OFF light switching at any time. • Segmented Fresnel lens provides optimum sensitivity and performance. Designed with an extensive “minor motion” area where even slight body movements will be detected. • Vandal resistant PIR lens. • Patented Blinders: Adjustable horizontal field-of-view (PIR may be adjusted between 180° and 60° of arc by using integral blinders located on either side of the lens). No masking required. • Manual-ON/auto-OFF mode for installations where manual-ON switching is required but auto-OFF switching is still desired for CEC Title 24 energy savings. • To comply with CED Title 24, LED indicator light flashes when sensor detects motion to verify detection is active. Green flashes for ultrasonic, red flashes for PIR. • Time: The delayed OFF time is preset at 30 minutes in the Auto Adapting mode. A choice of four delayed-OFF time settings are available: 30-seconds (for walking test purposes only), 10, 20, and 30 minutes for fixed time and auto adapting. The LED will flash when the adjusting knob is set to the indicated time value. • Ambient Light Recognition: Integrated light sensor prevents lights from turning on when the room is adequately illuminated by natural light. • Self-Adaptive Technology: Callbacks for adjustment are eliminated. Time delay and sensitivity settings are continually adjusted to occupant patterns of use in auto adapt mode. • Exclusive Walk-through Feature provides increased energy savings by not leaving the lights ON for an extended period after only momentary occupancy. • Vacancy Confirmation: When the time out expires and the relays turn OFF, a 30 second (OSSMT-G) or 40 second (OSSMT-M) vacancy confirmation exists to turn the relays back on. • False detection circuitry. • Small Motion Sensitivity (U/S): Ultrasonic technology provides excellent minor motion sensitivity. • Ability to disable U/S (OSSMT-M). For added flexbility, OSSMT-G has the ability to disable both PIR and U/S. • Presentation Mode feature: For slide or film presentations, allows pushbuttons to turn lights OFF and keep them OFF while the room is occupied. 20 30 5 4 0 SIDE VIEW 0 Control Panel, Cover Removed 1 2 4 7 4 7 3 10 10 TIME RANGE LIGHT LED & Light Sensor Pushbutton 20 40 BOTTOM Major Motion, PIR Major Motion, U/S Major Motion, PIR Major Motion, U/S Minor Motion= Dual Technology coverage. This also represents the maximum ultrasonic range coverage. DIMENSIONAL DIAGRAMS 1.85in 46.99mm 1.75in 44.45mm .5in/12.62mm 1.35in 34.37mm 2.65in 67.26mm 4.06in 103.12mm PROJECT: ONU PHASE II TITLE: Product Cut Sheets - OSSMT-GDW QUOTE NAME: ONU PHASE II REVISION: 1 QUOTE: DS-463343 DATE: August 26, 2013 SHEET: 15 of 22 Ultrasonic Sensors INSTALLATION The OSSMT is preset to deliver optimum performance in a wide variety of applications without requiring any adjustments during installation. Exclusive self-adjusting operating features will automatically compensate for real-time occupancy patterns to provide maximum convenience and energy savings. The unit may replace a single-pole wall switch mounted in a standard wall box. The OSSMT-MD must have a neutral and be properly grounded in order to operate. The OSSMT-GD does not require a neutral for installation. The unit’s integral blinders may be used to restrict the field of view to prevent unwanted detection of traffic. It should be positioned at least 6 feet away from HVAC registers. Note that whenever the unit is powered up, it will take approximately 1 minute to begin normal operation. WIRING DIAGRAM Line 120-230-277/347VAC 50/60Hz OSSMT-MD Wall Switch Occupancy Sensor Wiring Diagram, Single Location Control SPECIFICATIONS ELECTRICAL Line Voltage 120-230-277/347 VAC U/S & PIR PIR only 120V 277V 347V 390mW 480mW 500mW 190mW 270mW 350mW OSSMT-GD 120V 277V 110mW 340mW 70mW 310mW Operational Frequency 50/60Hz Ultrasonic Operating Frequency 40kHz Wire Designation Line-Black Neutral-White Load-Blue Ground-Green Load Rating Incandescent/Tungsten: 800W @ 120V Fluorescent: 1200VA @ 120V 2700VA @ 277V , 1500VA @ 347V Motor: 1/4 HP @ 120V, OSSMT-MD Note: Ground wire must be connected. OSSMT-GD Wall Switch Occupancy Sensor Wiring Diagram, Single Location Control ENVIRONMENTAL Operating Temperature Range Storage Temperature Range Relative Humidity 32°F to 104°F (0°C to 40°C) 14°F to 185°F (-10°C to 85°C) 20% to 90% non-condensing OTHER Listings Warranty Line 120-230-277VAC 50/60Hz OSSMT-MD = Ul/cUL OSSMT-GD = ETL/cETL Listed, CSA OSSMT-M3 = cETL Listed, CSA CEC Title 24 Compliant, FCC Compliant Limited Five-Year Warranty Sensor 1 Black (Hot) Black Sensor 2 Blue Black Blue Black Line 120-230-277VAC 50/60Hz Load Green Ground Green Ground White Neutral (White) Note: Ground wire must be connected. OSSMT-GD Wall Switch Occupancy Sensor Wiring Diagram, Two Location Control ORDERING INFORMATION CAT. NO. * DESCRIPTION OSSMT-MDx OSSMT-GDx Multi-Technology Wall Switch Occupancy Sensor No Neutral, Multi-Technology Wall Switch Occupancy Sensor OSSMT-M3x Multi-Technology Wall Switch Occupancy Sensor 347V Lighting & Energy Solutions 20497 S.W. TETON AVE TUALATIN, OR 97062 (503)404-5500 http://www.leviton.com * Replace x with (W) White, (I) Ivory, (T) Light Almond, (G) Gray, Ebony (-E), or Red (-R) NOTE: OSSMT-M3x model available in (W) White and (I) Ivory only. * NAFTA compliant and Made in USA models available. PROJECT: ONU PHASE II TITLE: Product Cut Sheets - OSSMT-GDW QUOTE NAME: ONU PHASE II REVISION: 1 QUOTE: DS-463343 DATE: August 26, 2013 SHEET: 16 of 22 OSSMT Power Consumption PRODUCT DATA GreenMAXTM Relay Control Panels Modular Relay System Offers Unparalleled Flexibility • Cabinets and Relay Modules with 25,000A Short Circuit Current Rating (SCCR) at 277VAC • Relay Modules Rated at 30A General Fluorescent Ballast and 20A Incandescent • Relay Modules are Latching with Manual Actuator • Industry standard 0-10V Dimming and Switching Relay Module • Programming and Monitoring of the System is Done with the Exclusive Handheld Display Unit (HDU) • Empty Enclosure Ships Separately From Electrical Components • Supports Native Protocols of BACnet/IP, Ethernet, and LumaCAN • 8, 16, 32 and 48 Relay Sizes The Leviton GreenMAX Relay Control Panels line offers features and performance not available from any competing product on the market today. For increased reliability and durability, GreenMAX Cabinets and Relay Modules have a 25,000A Short Circuit Current Rating (SCCR) at 277VAC. Native communication network protocols – BACnet/ IP, Ethernet, and LumaCAN – are built into each GreenMAX Command Module (processor) to offer unparalleled connectivity. No additional parts or adapters are needed to communicate with other products utilizing these protocols. For increased flexibility, the modular GreenMAX system includes separate Cabinet enclosures, Command Modules (processor, power supply, and low voltage inputs), Relay Insert Panels, Relay Modules, and a Handheld Display Unit (HDU). For easier manageability and accessibility, Leviton ships empty cabinet enclosures separately from the electronic components. This makes the cabinets lighter and easier to handle and requires less effort to install. To further minimize handling and damage to the electronic components, Leviton can ship the electronic components later in the project schedule or as required. All GreenMAX Relay Modules are 1-pole or 2-pole Lighting & Energy Solutions 20497 S.W. TETON AVE TUALATIN, OR 97062 (503)404-5500 http://www.leviton.com latching relay types that reduce parasitic energy use. The relay modules are the same physical size, allowing the optimal mix of relays to be customized for each application. Models include a basic control relay module and/or a self-contained dimming and switching relay module that supports daylight harvesting capabilities. A Handheld Display Unit (HDU) can be detached from the cabinet mounting location and moved to the most convenient network connection point to connect to any open LumaCAN or port on the same network as the cabinets. Commissioning and start-up functions are easier with the HDU, which allows programming to be done in the space being controlled rather than from the electrical room. APPLICATIONS • Heavy retrofit applications • New construction projects • Government facilities • Office buildings • Hospitals/medical offices • Universities • Restaurants • Large campuses • Any other location where centralized lighting control, programming, and monitoring are required PROJECT: ONU PHASE II TITLE: Product Cut Sheets - R16TC-100 QUOTE NAME: ONU PHASE II REVISION: 1 QUOTE: DS-463343 DATE: August 26, 2013 SHEET: 17 of 22 GreenMAXTM Relay Control Panels GreenMAX Cabinet PRODUCT DATA FEATURES Circuit Current Rating (SCCR) at 277V for increased reliability and durability Relay Cabinet • GreenMAX cabinet has a 25,000A at 277VAC Short Circuit Current Rating (SCCR) for increased reliability and durability • Modular system includes separate empty cabinet enclosures, a command module, and relay insert panels to minimize handling and subsequent damage during installation •Command Module is the processor and power supply of the GreenMAX system and optionally includes a low voltage remote input card for analog devices • Relay insert panels feature quick install; each panel takes only two screws to install • All relays are latching with a manual actuator to reduce parasitic energy waste over NO/NC relays • Manual actuation lever on all GreenMAX relays allow users to manually bypass the system to turn lights on or off without a CPU or power • Self-contained dimming and switching relay module in 1-pole configurations supports daylight harvesting capabilities Handheld Display Unit (HDU) • Native communication network protocols – BACnet/IP, Ethernet, and LumaCAN – are built into each command module to offer unparalleled connectivity; no additional devices are needed to communicate with other products utilizing these protocols GreenMAXTM Relay Control Panels • Rated at 30A general fluorescent ballast (this rating is 20A, 347V in Canada) and 20A incandescent for all GreenMAX relays • Remote low voltage input cabinets can be installed closer to the devices they serve (such as occupancy sensors, LV switches and photocells) to reduce wiring and labor and provide additional power; this also makes commissioning and troubleshooting easier • Manage the GreenMAX system(s) remotely from any network device location • System configuration and scheduling is performed via the HDU – this can be done while standing in the room or controlled space; programming is no longer confined to the electrical room • Control entire GreenMAX system from any access point – relay cabinets, switches, or remote low voltage cabinets • Provides interface with all devices and relays in the system • Increased arc flash protection – the cabinet door opens to expose only the low voltage area of the cabinet • One HDU can be used for multiple systems • High voltage areas can be accessed by removing the wire-way covers – this requires the removal of retaining screws • Wire-way covers can be quickly removed and replaced • Can be stored in the cabinet or designated docking station • Communicate via LumaCAN • 7 hour run time on a single full charge (batteries included) • Door lock cannot be defeated by unscrewing cover • Astronomical clock - sunrise/sunset • Voltage barriers can be installed between individual relay modules. This allows voltages from mixed sources in the same cabinet • HDU does not need to be connected to system during operation. Full system functionality is provided independent of HDU Relay Modules • All GreenMAX relay modules have a 25,000A Short GreenMAX Handheld Display Unit (HDU) Comes Complete with four (4) AAA rechargeable Ni-MH batteries. Batteries charge when connected to lumacan GreenMAX Relay Modules Lighting & Energy Solutions 20497 S.W. TETON AVE TUALATIN, OR 97062 (503)404-5500 http://www.leviton.com PROJECT: ONU PHASE II TITLE: Product Cut Sheets - R16TC-100 QUOTE NAME: ONU PHASE II REVISION: 1 QUOTE: DS-463343 DATE: August 26, 2013 SHEET: 18 of 22 DIMENSIONS RELAY CABINETS WIDTH HEIGHT DEPTH R08TC-100 21” 22” 4” R16TC-100 25” 32” 4” R32TC-100 25” 48” 4” R48TC-100 25” 64” 4” RLV08-110 14” 10” 4” RLV16-110 14” 10” 4” 14” 10” 4” REMOTE LOW VOLTAGE CABINETS REMOTE POWER ONLY CABINET, NO INPUTS RLV00-110 SPECIFICATIONS Wiring • Internal: factory pre-wired and tested • System Communications: • LumaCAN requires standard CAT6 network cabling • Low voltage Class 2 wiring connects input cards to control devices such as occupancy sensors, low voltage switches, and photocells • Hard-wired dedicated Emergency input is provided in each cabinet and requires an external normally open (N/O) contact closure; the Cabinet provides the source of low voltage +24VDC for this circuit; programmable individual relay response to the Emergency signal • Line Voltage: • Feed for Command Module (control electronics) and load wiring only • Requires single phase hot and neutral connection • LumaCAN Network: • Cat 6 cable • RJ45 connectors • Wiring configuration (EIA/TIA 568B) • Power must be injected into LumaCAN cable every 900 feet • Use a Remote Low Voltage Cabinet or a Relay Cabinet • Power supply - two-sided allowing up to 750mA per side Lighting & Energy Solutions 20497 S.W. TETON AVE TUALATIN, OR 97062 (503)404-5500 http://www.leviton.com • Voltage barriers available to seperate circuits of different sources • Voltage barriers field install between Relay Modules Network Connections • Maximum LumaCan communication network length is 1600 feet from end to end. Longer network lengths can be achieved with the use of a LumaCan repeater • Ethernet connectivity is native to each Command Module • Only one cabinet on a single run of LumaCAN requires an Ethernet connection • Ethernet can be used to bridge between runs of LumaCAN to extend network length • BACnet/IP is native to each Command Module • BACnet/IP must be run to each cabinet - may require Ethernet/Network switch Physical • Enclosure: NEMA type 1, IP-20 protection; #16 US gauge steel; indoors only • Mounting: surface mount only Environmental • Ambient Temperature Range: 0°C - 50°C (32°F - 122°F) • Relative Humidity: < 90% non-condensing Listings • UL508, UL924, cUL, CEC Title 24 compliant, ASHRAE 90.1 compliant Warranty • Relay Modules backed by 10-year warranty • Relay Panels backed by 2-year warranty *ARRA compliant panels available - consult factory for availability PROJECT: ONU PHASE II TITLE: Product Cut Sheets - R16TC-100 QUOTE NAME: ONU PHASE II REVISION: 1 QUOTE: DS-463343 DATE: August 26, 2013 SHEET: 19 of 22 GreenMAXTM Relay Control Panels Electrical • Power Supply Input: 70W (max), 100-277VAC single phase • All Voltages: 50/60Hz Phase to Neutral • Non-volatile memory and micro SD card protect programming during blackouts PRODUCT DATA ORDERING INFORMATION CAT. NO. DESCRIPTION CAT. NO. Handheld Display Unit (HDU) R08TC-100 GreenMAX Relay Cabinet, 8-Relay Size, NEMA 1 RHDU1-000 Handheld Display Unit, Cabinet Mounting R16TC-100 GreenMAX Relay Cabinet, 16-Relay Size, NEMA 1 RHDU1-BKT Handheld Display Unit, Mounting Bracket R32TC-100 GreenMAX Relay Cabinet, 32-Relay Size, NEMA 1 R48TC-100 GreenMAX Relay Cabinet, 48-Relay Size, NEMA 1 Remote Inputs with Power Supply (all remote inputs are rated 100-277VAC) Command Modules (includes power supply and main processor unit) RLV08-110 Remote Low Voltage Input Cabinet, 8 Inputs, NEMA 1 Enclosure RPM00-100 Main Command Module, 100-277VAC, no inputs RLV16-110 RPM08-108 Main Command Module with 8-Port Low Voltage Input Card, 100-277VAC, 50/60Hz Remote Low Voltage Input Cabinet, 16 Inputs, NEMA 1 Enclosure RLV00-110 RPM16-116 Main Command Module with 16-Port Low Voltage Input Card, 100-277VAC, 50/60Hz Remote Low Voltage Input Cabinet, No Inputs, NEMA 1 Enclosure Relays (all relays are rated 30A, 120-230-277/347VAC, 50/60Hz) Panel Interiors (all panels are 16-position, rated 30A, 120-230-277/347VAC, 50/60Hz) GreenMAXTM Relay Control Panels DESCRIPTION Tubs and Covers (all cabinets are surface mount with a locking door) RELAY-1CB GreenMAX Latching Relay, 1-Pole RTC Basic RELAY-1DS GreenMAX Latching Relay, 1-Pole Dimming and Switching R0800-000 Relay Insert Panel, Empty with (8) Spaces R1600-000 Relay Insert Panel, Empty with (16) Spaces RELAY-1TB GreenMAX Latching Relay, 1-Pole Basic R1616-1CB Relay Insert Panel with (16) 1-Pole RTC Basic Relays RELAY-2CB GreenMAX Latching Relay, 2-Pole RTC R1616-1DS Relay Insert Panel with (16) 1-Pole Dimming and Switching Relays RELAY-2TB GreenMAX Latching Relay, 2-Pole Basic RELAY-BFM Blank Filler Module RGBAR-008 GreenMAX Voltage Barriers for 8 Relay Cabinets RGBAR-016 GreenMAX Voltage Barriers for 16, 32 and 48 Relay Cabinets R1616-1TB Relay Insert Panel with (16) 1-Pole Basic Relays R1616-2CB Relay Insert Panel with (16) 2-Pole RTC Relays R1616-2TB Relay Insert Panel with (16) 2-Pole Basic Relays LEVITON SPECIFICATION SUBMITTAL JOB NAME: JOB NUMBER: Lighting & Energy Solutions 20497 S.W. TETON AVE TUALATIN, OR 97062 (503)404-5500 http://www.leviton.com CATALOG NUMBERS: PROJECT: ONU PHASE II TITLE: Product Cut Sheets - R16TC-100 QUOTE NAME: ONU PHASE II REVISION: 1 QUOTE: DS-463343 DATE: August 26, 2013 SHEET: 20 of 22 PRODUCT DATA GreenMAXTM Relay Modules Offers Latching, Dimming and Daylight Harvesting Capabilities • 25,000A Short Circuit Current Rating (SCCR) at 277VAC • Rated at 30A General Fluorescent Ballast and 20A Incandescent, HID, Electronic Ballast • All Models are Latching Relays with Manual Actuator • Exclusive 0-10VDC (sinking) Dimming Relay Module for Daylight Harvesting for compatible Fluorescent and LED drivers GreenMAX Relay Modules All relays must be used in a GreenMAX system cabinet. APPLICATIONS • Heavy retrofit applications • New construction projects • Government facilities • Office buildings • Hospitals/medical offices • Universities • Restaurants • Large campuses • Any other location where centralized lighting control, programming, and monitoring are required Lighting & Energy Solutions 20497 S.W. TETON AVE TUALATIN, OR 97062 (503)404-5500 http://www.leviton.com FEATURES • All GreenMAX relay modules have a 25,000A at 277VAC Short Circuit Current Rating (SCCR) for increased reliability and durability • Rated at 30A general fluorescent ballast and 20A incandescent for all GreenMAX relays GreenMAXTM Relay Modules The Leviton line of GreenMAX Relay Modules offers features and performance not available from any competing product on the market today. For increased reliability and durability, GreenMAX Relay Modules have a 25,000A Short Circuit Current Rating (SCCR) at 277VAC. All GreenMAX Relay Modules are 1-pole or 2-pole latching relay types that reduce parasitic energy use. All relay modules are the same physical size, allowing the optimal mix of relays to be customized for each application. Models include a basic control relay module, a Return To Closed relay module, and a self-contained 0-10VDC (sinking) dimming relay module that features daylight harvesting capabilities. • All relays are latching with a manual actuator to reduce parasitic energy waste over NO/NC relays • Manual actuation lever on all GreenMAX relays allow users to manually turn lights ON or OFF without a CPU or power • No exposed printed circuit boards or components. The encased plastic housing provides the perimeter of safety. Wire terminations are safely contained within the plastic housing. Wires connect directly to terminators rather than terminals that are soldered to a circuit board, which are prone to breaking connections to the board • Self-contained 20A, 0-10VDC (sinking) Dimming relay module in 1-pole configurations features daylight harvesting capabilities • Conductors for the 20A, 0-10VDC (sinking) Dimming relay circuit must be run in the Line and Load conductor area in the GreenMAX cabinet. The insulation of these conductors must be in compliance with all applicable electrical codes. The NEC will allow this condition if the insulation of the low voltage wires is rated for the highest voltage available in the compartment. PROJECT: ONU PHASE II TITLE: Product Cut Sheets - R1600, RELAY-1TB, RELAY-1DS QUOTE NAME: ONU PHASE II REVISION: 1 QUOTE: DS-463343 DATE: August 26, 2013 SHEET: 21 of 22 PRODUCT DATA SPECIFICATIONS Environmental • Ambient Temperature Range: 0°C - 50°C (32°F - 122°F) • Relative Humidity: < 90% non-condensing Listings • UL916, UL508, UL924, cUL, CEC Title 24 compliant, ASHRAE 90.1 compliant Warranty • Relay Modules backed by 10-year warranty ORDERING INFORMATION CAT. NO. DESCRIPTION LOAD RATINGS SINGLE POLE RELAYS RELAY-1CB Return to Closed (RTC) Latching Relay 24-277VAC, 347VAC, 20A Tungsten Halogen Incandescent, 20A Electronic Ballast and HID 24-277VAC, 347VAC, 30A Magnetic Ballast, 20A Electronic Ballast, 120VAC 1/2 Hp Motor, 277VAC 1 Hp Motor, 240VAC 1Hp Motor Wire Range: #14 - #6 AWG Copper, Torque 16 in.-lbs. 25,000A SCCR Rating at 277VAC RELAY-1TB Latching Relay 24-277VAC, 347VAC, 20A Tungsten Halogen Incandescent, 20A Electronic Ballast and HID 24-277VAC, 347VAC, 30A Magnetic Ballast, 20A Electronic Ballast, 120VAC 1/2 Hp Motor, 277VAC 1 Hp Motor, 240VAC 1Hp Motor Wire Range: #14 - #6 AWG Copper, Torque 16 in.-lbs 25,000A SCCR Rating at 277VAC RELAY-1DS Dimming and Switching Latching Relay 24-277VAC, 347VAC, 20A 0-10V (sinking) Dimming Fluorescent and LED Driver Wire Range #14 - #6 AWG Copper, Torque 16 in.-lbs. Control Wire Range: #14 - 12 AWG Copper, Torque 14 in.-lbs. Maximum 0-10VDC (sinking) Dimming control circuit load: 200mA 25,000A SCCR Rating at 277VAC GreenMAXTM Relay Modules DOUBLE POLE RELAYS RELAY-2CB Return to Closed (RTC) Latching Relay 208/240/480/600VAC, 20A Tungsten Halogen Incandescent, 20A Electronic Ballast and HID, 208/240/480/600, 30A Magnetic Ballast, 20A Magnetic Ballast, 208/240VAC 1Hp Motor Wire Range: #14 - #6 AWG Copper, Torque 16 in.-lbs. RELAY-2TB Latching Relay 208/240/480/600VAC, 20A Tungsten Halogen Incandescent, 20A Electronic Ballast and HID, 208/240/480/600, 30A Magnetic Ballast, 20A Magnetic Ballast, 208/240VAC 1Hp Motor Wire Range: #14 - #6 AWG Copper, Torque 16 in.-lbs. RELAY-BFM Blank Filler Module - WIRING DIAGRAM LEVITON SPECIFICATION SUBMITTAL JOB NAME: JOB NUMBER: Lighting & Energy Solutions 20497 S.W. TETON AVE TUALATIN, OR 97062 (503)404-5500 http://www.leviton.com CATALOG NUMBERS: PROJECT: ONU PHASE II TITLE: Product Cut Sheets - R1600, RELAY-1TB, RELAY-1DS QUOTE NAME: ONU PHASE II REVISION: 1 QUOTE: DS-463343 DATE: August 26, 2013 SHEET: 22 of 22