american security equipment company

advertisement
american
security
equipment
company
CORPORATE OFFICE & WAREHOUSE
228 East Star of India Lane, Carson, CA 90746
Phone (310) 538-4670 * Fax (310) 538-9932 * (800) 421-1096
EAST COAST OFFICE & WAREHOUSE
30 Chapin Road 1207, Pine Brook, New Jersey 07058
Phone (973) 575-4433 * Fax (973) 575-5504 * (800) 526-1060
http://www.amseco-kai.com / e-mail: info@amseco-kai.com
Select-A-Horn/Strobe Combination
SHW24-153075
TM
Patented
Description:
L
ST
A
F
IFO
R
LL
O
TE
APPROVED
A
FIR
E MAR
SH
E
ER
V I C
S
cd
I S TCIALN
TE
A
15
/75
FM
ST
Strobe Selectable Candela Output:
UL ULC
A
NI
Application:
The SHW24-153075 Horn/Strobe series are recommended
for use in areas such as; meeting rooms, schools, corridors,
apartments, office buildings, restaurants, hotels, and any
other application where effective Audible and Visual warning
is required by Federal, State, or local authority having
jurisdiction.
Horn/Strobe with Universal Mounting Plate Included
G
AMSECO’s Select-A-Horn/Strobe series are designed to
comply with the Americans with Disability Act (ADA) and
meet UL standard 1971 requirements for emergency
signaling devices for the hearing impaired. The SHW24
series Select-A-Horn/Strobe features a unique candela
intensity field selector switch for switching the candela
output from 15/75 to 30/120 cd. The Horn provides two
different field selectable tones, and a High / Low ouput
setting that can be accomplished with the use of mini
jumpers located on back of the unit. The strobe housing is
clearly labeled with vertical “FIRE” lettering and is polarized
for connecting to supervised fire alarm circuits. The strobe
is designed with a xenon flashtube and provide a candela
intensity field selector switch for maximum performance.
The Select-A-Horn/Strobe series is available in red and
white housing 15/75 or 30/120 cd. 24VDC models. The
SHW24-153075 can be synchronized by using the SMS13A sync module to comply with NFPA recommendations
concerning photosensitive epilepsy when installing 2 or
more visual appliances within the field of view. The strobe
signals are listed for indoor use, ceiling and wall mount,
under UL 1971 standard.
MEA
ADA
Features:
* Designed to meet or exceed NFPA/ANSI Standards and ADA
Accessibility Guidelines.
* UL listed for Wall or Ceiling mount.
* Screw terminal capacity up to 12 AWG.
* Universal mounting plate included with each unit.
* 24 volts DC strobe with two field selectable settings 15/75 or
30/120 cd.
* Polarized strobes with wide listed voltage ranges using filtered
DC or unfiltered FWR input voltage.
* Horn field selectable tones:
3000 Hz interrupted or Electro-mechanical
Temporal or Non-temporal
High or Low dBA output
* Meets ADA guidelines for minimum one flash per/sec (1Hz).
* All modelso 4” square, single gang, double gang,
Or octagonal back box.
* 24 volt strobe models 15/75 or 30/120 candela Intensity.
* Tamper-proof candela selector switch.
* Synchronization requires an AMSECO SMS1-3A Sync
Module.
* Available in red or white housing.
Horn Selectable Sound Output:
30
/12
0cd
F
I
R
E
15
PC3 PC2 PC1
30
Tamper Proof
Temporal
- Non-Temporal
Electro Mech - 3000 Hz
High
- Low
Ordering Information:
MODEL NUMBER
INPUT
VOLTAGE
(VDC)
STROBE
CANDELA
SHW24-153075R
24
15/75 or 30/120
SHW24-153075W
24
15/75 or 30/120
SYNCH W/
SMS1-3A
MODULE
WALL
MOUNT
CEILING
MOUNT
COLOR
RED
COLOR
WHITE
Engineering Specifications:
The Audible and Visual alarm indicating appliance shall be AMSECO model SHW24-153075 or equivalent device. The Strobe
shall be listed under UL 1971 standard for signaling devices for the hearing impaired and shall be approved for fire protective
service. The candela output shall be field selectable, having a dual setting of 15/75 cd or 30/120 cd output. The Horn shall provide
two different field selectable tones a High and Low field selectable sound output setting. The signaling Horn/Strobe shall operate
on 24VDC from a non-coded regulated DC supply or full-wave rectified, unfiltered supply. The signaling strobe shall be designed
to produce a signal flash of one flash per second with continuously applied minimum voltage. The Horn/Strobe shall be capable of
WALL or CEILING mounting to a universal backbox. Visual signaling devices shall be mounted 80”above the highest floor point or
6” below ceiling; wich ever is lowest and are to be installed as per plans and specifications.
Light Output Distribution / Horizontal and Vertical Dispersion:
CE
90
L
WAL
0
0
G
N
ILI
90
90
90
90
0
Vertical Dispersion (Wall Mount)
Degrees
5
-25
0
30
-45
50
Degrees
55 60 65
70 75 80 85
0
90
_
45 50 55
60
65
70
75
80
-90
UL Measured Min. Candela at 15/75cd. (30/120cd)
Wired Without Audible Silence Feature:
Horn/Strobe Combination Wiring:
+
40
(120 27 19.5 13.8 10.2 8.1 6.6 5.4 4.8 4.5 3.9 3.6)
UL Measured Min. Candela at 15/75cd. (30/120cd)
F.A.C.P.
Signal
Circuit_
To Next Device or
End-Of Line-Resistor
F
I
R
E
35
75 13.5 9.75 6.9 5.1 4.05 3.3 2.7 2.4 2.25 1.95 1.8
75 13.5 11.25 8.25 6.75 6 5.25 5.25 4.5 4.5 3.75 3.75
(120 27 22.5 16.5 13.5 12 10.5 10.5 9 9 7.5 7.5)
Control
Panel
5
- 30
SMS1-3A
_
H+H
+
IN_
+
OUT
_
+
To Next Device or
End-Of Line-Resistor
F
I
R
E
+ _
+ _
*The Sync module is rated for 3.0 amperes at 24 VDC.
Signals Wired for Independent Operation:
F.A.C.P.
Strobe Signal
Circuit
_
+
F.A.C.P.
Horn Signal
Circuit
+
_
F
I
R
E
To Next Device or
End-Of Line-Resistor
Strobe
Horn
+
+
_
_
+
_
Wired for Audible Silence Feature:
F.A.C.P.
Strobe Signal
Circuit
+
_
F.A.C.P.
Horn Signal
Circuit
+
_
SMS1-3A
_
H+H
IN
+
_
OUT
_
+
F
I
R
E
To Next Device or
End-Of Line-Resistor
+ _
To Next Device or
End-Of Line-Resistor
+
_
WARNING:
*Strobes must be use only on circuits with continuously operating voltage, DO NOT use strobe on coded or interrupted
circuits in which the applied voltage is interrupted ON and OFF as the strobe may fail to flash.
* The strobe applied voltage must be within its rated input voltage range.
* Fuse ratings on signaling circuits must handle peak currents from all devices connected to those circuits.
Horn/Strobe Current Draw Table:
Average Current (mA)
PC1
Volume
PC2
Tone
PC3
Pattern
Non-Temp
Electro
Mechanical Temporal
HIGH
Non-Temp
3000 Hz
Temporal
Non-Temp
Electro
Mechanical Temporal
LOW
Non-Temp
3000 Hz
Temporal
Non-Temp
Electro
Mechanical Temporal
HIGH
Non-Temp
3000 Hz
Temporal
Non-Temp
Electro
Mechanical Temporal
LOW
Non-Temp
3000 Hz
Temporal
Non-Temp
Electro
Mechanical Temporal
HIGH
Non-Temp
3000 Hz
Temporal
Non-Temp
Electro
Mechanical Temporal
LOW
Non-Temp
3000 Hz
Temporal
@
15
/
75
cd
@
30
/
120
cd
Horn
Only
P P
C C
1 2
P
C
3
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
0
1
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
16VDC
Sound
Output
dBA @ DC
88
82
88
82
0
1
0
1
0
1
0
1
75
75
79
75
88
82
88
82
0
1
0
1
0
1
0
1
75
75
79
75
88
82
88
82
75
75
79
75
0
1
0
1
0
24VDC
DC
FWR
Sound
Output
dBA @ DC
103
94
104
86
90
86
89
87
144
132
143
125
131
126
129
126
26
20
28
22
14
12
15
12
118
114
120
112
112
106
113
113
165
166
173
165
160
158
166
166
29
19
30
21
16
12
17
12
88
85
88
85
79
76
79
76
88
85
88
85
79
76
79
76
88
85
88
85
79
76
79
76
DC
88
80
89
82
74
71
74
71
113
103
114
106
98
94
98
94
40
33
42
35
26
23
27
23
33VDC
FWR
Sound
Output
dBA @ DC
98
91
100
92
91
85
91
88
129
122
132
122
120
116
123
120
42
29
42
30
29
22
29
23
88
85
88
85
82
79
82
79
88
85
88
85
82
79
82
79
88
85
88
85
82
79
82
79
DC
FWR
86
78
87
78
74
70
75
71
104
94
104
96
91
86
92
88
51
42
52
45
41
37
42
37
93
82
96
84
86
78
88
80
114
105
118
103
110
100
112
106
51
39
53
40
43
35
44
35
**Sound output varies with tone and options selected.
Strobe Only Current Draw Table:
Average Current (mA)
24 volt models
16V
Peak Current (mA)
24 volt models
33V
24V
16V
Candela DC FWR DC FWR DC FWR
112
62
81
58
30/120 130 174
92
123
79 104
15/75
83
74
In-Rush Current (mA)
24 volt models
33V
24V
Candela DC FWR DC FWR DC FWR
78
24V
33V
Candela DC FWR DC FWR DC FWR
220 70
180
15/75
30/120 145 270 105 270 90
250
30/120 310 340 350 370 380 375
15/75
90 245
16V
300 310 320 370 380 350
The SLW24-153075 series strobes are listed for indoor use with a temperature operating range of 32 F ~ 120 F ( 0 C ~ 49 C ).
UL Rated True RMS @ 24VDC
Candela Average
Peak
In-Rush
15cd
71mA
99mA
386mA
30cd
113mA
143mA
382mA
Mounting Options:
Strobe with Universal mounting
plate and single gang box.
Strobe with Universal mounting
plate and 4” square back box.
2” backbox
F
I
R
E
Strobe
F
I
R
E
Universal Mounting Plate
Strobe
Strobe with Universal mounting
plate and double gang box.
Strobe with Universal mounting
plate and BBX-4 weather proof
back box.
4” x 4” x 1-1/2”
backbox
4” x 4” x 1-1/2”
backbox
F
I
R
E
Universal Mounting Plate
Strobe
BBX-4 weather
proof back box
F
I
R
E
Universal Mounting Plate
Strobe
Universal Mounting Plate
Dimensions: Inches (mm)
3 3/8(85.7)
2 1/4(56.9)
5(127)
3 9/32(83.5)
3 3/8(85.7)
5(127)
3 9/32(83.5)
1 13/16(46)
SMS1-3A Sync Module:
When used with the SHW-24 Horn/Strobe series the SMS1-3A provides
synchronized temporal pattern and a synchronized strobe flash while using a
single pair of wires on a single class "A" circuit.
Model Number
SMS1-3A
Input
Voltage
(VDC)
24
Maximum Average Mounting
Load
Current Back Box
(Amps)
(mA)
3
9
4"x4"x1-1/2"
Color
SMS1-3A Sync Module
Red
* The total current draw from all devices connected to the SMS1-3A should not exceed 3.0A.
**The SMS1-3A should only be connected to circuits that provide continuously applied voltage.
SMS1-3A Current Draw Table:
Average
Voltage
Peak
In-Rush
DC
FWR
DC
FWR
DC
FWR
20V
8mA
8mA
31mA
57mA
44mA
62mA
24V
9mA
9mA
32mA
62mA
52mA
75mA
30V
10mA
10mA
33mA
66mA
70mA
94mA
Dimensions: Inch (mm)
4.33
(110)
3.374
(85.7)
The SMS1-3A module is listed for indoor use with a temperature
operating range of 32 F ~ 120 F ( 0 C ~ 49 C ).
0.2
(5)
4”x4”X11/2
3.374
(85.7)
4.33
(110)
Electrical Back box
SMS1-3A
* Due to continuous development of our product line, specifications are subject to change without notice.