Industrial fuse solutions

advertisement
GE Consumer & Industrial
Power Protection
Industrial fuse solutions
WTN Plus and DI-FUS fuse links
DI-LINE fuse gear
Fuse links
WTN Plus gG and gF fuse links
A.3
Order codes
A.6
Dimensions
A.7
Technical data
A.9
Time/current characteristics
DI-FUS gG and aM fuse links
A.13 Order codes
A.16 Dimensions
A.16 Technical data
A.17 Time/current characteristics
Fuse links
A
Fuse bases
B
Fuse switch disconnectors
C
Numerical index
D
A.1
WTN Plus
WTN Plus gG and gF fuse links
• High Rupture Capacity fuselinks
• Low power dissipation
• Plain undrilled silver plated copper knife-blade tags
• Dual indicator - visual indicator situated in the top end
blade and in the centre of the front side of the ceramic
body
• Cadmium and lead free manufacturing process
• Two utilisation catagories: general purpose gG/gL and
special fast action gF fuse links operating in less than 5 sec
at In = 2.5 xIn
Fuse links
• Four types of special overrating gG fuses available for use
in RSA and RB2 fuse switch disconnectors
A
B
C
WTN-1/gG 315A and WTN-1/gG 355A
WTN-2/gG 500A and WTN-2/gG 630A
Standards
General data
IEC 60269
General purpose fuse links class ‘gG’
Current Rating
Voltage Rating
Breaking Capacity
Max Operating
Ambient Temperature
PN-91/E-06160/10
PN-91/E-06160/21
Fast action fuse links class ‘gF’
DIN 43620 (part 1 to 4)
European dimensional standard sizes
Approvals
(A)
(V)
(kA)
6-630
500*
120
(C)
40
* Voltage rating size 1 (315A and 355A) and size 2 (500A): 440V;
Voltage rating size 2 (630A): 400V
Associated switchable devices
RSA and RB2 fuse switch disconnector
FULOS and FULOS PLUS fuse switch disconnector
D
Applications
WTN Plus gG General purpose
With European dimensional standards to DIN 43620 and
performance standards to VDE 0636/21, operating class gG,
WTN Plus fuse Links are used for cable and line protection and
rated for use on systems up to 500 Volts ac
Technical Standard
IEC 60269-21 General purpose Fuse Links Class ‘gG’
WTN Plus gF Fast acting
Class ‘gF’ range of WTN Plus Fuse Links are specifically
designed for protection against electrical shock caused by
indirect touch. WTN Plus gF fuse links allow to break supply
voltage within 5 seconds in case fault current is higher or
equal 2.5 times the rated current of the fuse.
Technical Standard
Fuse links type WTN Plus gF meet all requirements of IEC
60269-21 in case of cables and line overload protection.
A.2
WTN Plus
WTN Plus General Purpose WTN-00C/gG 16A-100A
Rated Current
Max. Nominal
voltage
Packaging
Ref. No.
16A
20A
25A
32A
40A
50A
63A
80A
100A
500V
500V
500V
500V
500V
500V
500V
500V
500V
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
700536
700537
700538
700539
700540
700541
700542
700543
700544
Rated Current
Max. Nominal
voltage
Packaging
Ref No.
6A
10A
16A
20A
25A
32A
40A
50A
63A
80A
100A
125A
160A
500V
500V
500V
500V
500V
500V
500V
500V
500V
500V
500V
500V
500V
3/72
3/72
3/72
3/72
3/72
3/72
3/72
3/72
3/72
3/72
3/72
3/72
3/72
700545
700546
700547
700548
700549
700550
700551
700552
700553
700554
700555
700556
700557
Fuse links
WTN Plus General Purpose WTN-00/gG 6A-160A
A
B
C
WTN Plus General PurposeWTN-1C/gG 6A-160A
Rated Current
Max. Nominal
voltage
Packaging
Ref. No.
6A
10A
16A
20A
25A
32A
40A
50A
63A
80A
100A
125A
160A
500V
500V
500V
500V
500V
500V
500V
500V
500V
500V
500V
500V
500V
3/36
3/36
3/36
3/36
3/36
3/36
3/36
3/36
3/36
3/36
3/36
3/36
3/36
700589
700590
700591
700592
700593
700594
700595
700596
700597
700598
700599
700600
700601
D
A.3
WTN Plus
Fuse links
WTN Plus General Purpose WTN-1/gG 6A-355A
Rated Current
Max. Nominal
voltage
Packaging
Ref. No.
6A
10A
16A
20A
25A
32A
40A
50A
63A
80A
100A
125A
160A
200A
250A
315A
355A
500V
500V
500V
500V
500V
500V
500V
500V
500V
500V
500V
500V
500V
500V
500V
440V
440V
3/36
3/36
3/36
3/36
3/36
3/36
3/36
3/36
3/36
3/36
3/36
3/36
3/36
3/36
3/36
3/36
3/36
700602
700603
700604
700605
700606
700607
700608
700609
7 0 0 6 10
7 0 0 6 11
7 0 0 6 12
7 0 0 6 13
7 0 0 6 14
7 0 0 6 15
7 0 0 6 16
7 0 0 6 17
7 0 0 6 18
WTN Plus General Purpose WTN-2/gG 63A-630A
A
B
C
Rated Current
Max. Nominal
voltage
Packaging
Ref. No.
63A
80A
100A
125A
160A
200A
250A
315A
400A
500A
630A
500V
500V
500V
500V
500V
500V
500V
500V
500V
440V
400V
3/24
3/24
3/24
3/24
3/24
3/24
3/24
3/24
3/24
3/24
3/24
7 0 0 6 19
700620
700621
700622
700623
700624
700625
700626
700627
700628
700629
D
WTN Plus General Purpose WTN-3/gG 315A-630A
A.4
Rated Current
Max. Nominal
voltage
Packaging
Ref. No.
315A
400A
500A
630A
500V
500V
500V
500V
3/12
3/12
3/12
3/12
700630
700631
700632
700633
WTN Plus
WTN Plus Fast Acting (k < 2.5) WTN-00/gF 20A-160A
Rated Current
Max. Nominal
voltage
Packaging
Ref. No.
20A
25A
32A
40A
50A
63A
80A
100A
125A
160A
400V
400V
400V
400V
400V
400V
400V
400V
400V
400V
3/72
3/72
3/72
3/72
3/72
3/72
3/72
3/72
3/72
3/72
700526
700527
700528
700529
700530
700531
700532
700533
700534
700535
Rated Current
Max. Nominal
voltage
Packaging
Ref. No.
20A
25A
32A
40A
50A
63A
80A
100A
125A
160A
200A
250A
400V
400V
400V
400V
400V
400V
400V
400V
400V
400V
400V
400V
3/36
3/36
3/36
3/36
3/36
3/36
3/36
3/36
3/36
3/36
3/36
3/36
700577
700578
700579
700580
700581
700582
700583
700584
700585
700586
700587
700588
Fuse links
WTN Plus Fast Acting (K < 2.5) WTN-1/gF 20A-250A
A
B
C
D
A.5
WTN Plus
WTN Plus - Dimensions
6
e1
b
c
e2
a3
a2
a1
Fuse links
d
top
indicator
middle
indicator
A
B
C
D
A.6
Dim e ns io ns (m m )
D IN s iz e s
In ( A )
a1
00C
00
1C
1
2
3
16-100
6-160
6-160
6-355
63-630
315-630
78,7 ± 1,2
78,5 ± 1,5
135 ± 2,0
135 ± 2,0
150 ± 2,0
150 ± 2,0
a2
m a x.
49,4
49.4
67.7
67.7
67.7
68.7
a3
b
c
d
49,7+/-0,7
49,7+/-0,7
67,5+/-1,2
67,5+/-1,2
67,5+/-1,2
68,5+/-1,2
15,1
15,1
15,1
20,1
25,1
32,1
35+/-0,8
35+/-0,8
40+/-0,8
40+/-0,8
48+/-0,8
60+/-0,8
7,5
7
7
7
7
6,5
e1
m a x.
41
47.8
47.8
52.9
61
76
e2
m a x.
21
29.55
29.55
39.65
53.9
71.2
WTN Plus
WTN Plus gG general purpose I2t values
125 – 630Amp
6 – 100Amp
Rated
Current
I1 120kA at
500Vac
14
58
240
240
490
920
1200
1800
3300
5900
5600
6300
6600
9800
18100
20600
290
1170
1200
2500
4600
5600
9000
16500
29500
27800
24900
26100
38900
72300
82300
21
240
1000
1000
2000
3700
4500
7200
13200
23600
22300
18700
19600
29200
54300
61700
Rated
Current
125A - s ize 00
125A - s ize 1C
125A - s ize 1, 2
160A - s ize 00
160A - s ize 1C
160A - s ize 1, 2
200A - s ize 1
200A - s ize 2
250A - s ize 1
250A - s ize 2
315A - s ize 1
315A - s ize 2, 3
355A
400A
500A - s ize 2
500A - s ize 3
630A - s ize 2
630A - s ize 3
Min PreArcing
I2t (A2s)
20 x In at
500Vac
I1 120kA at
500Vac
25000
25000
25000
62000
62000
62000
97000
96900
151300
160800
299500
361700
299500
642900
1110000
886000
1930000
1590000
125000
125000
100000
310000
310000
248000
368600
367900
574900
642900
1197700
1446500
1197700
2571500
4422400
3898400
9047000
6996000
80000
72500
72500
204600
179800
179800
291000
290500
453800
417900
749000
940300
749000
1671500
2764000
2923800
5774700
5406000
Fuse links
6A
10A
16A - s ize 00
16A - s ize 1C , 1
20A
25A - s ize 00
25A - s ize 1C , 1
32A
40A
50A - s ize 00
50A - s ize 1C , 1
63A - s ize 00
63A - s ize 1C , 1, 2
80A
100A - s ize 00C , 00
100A - s ize 1, 2
Min PreArcing
I2t (A2s)
20 x In at
500Vac
WTN Plus gG general purpose cut off current characteristics
A
630 A
500 A
400 A
315 A
250 A (size 3)
250 A (size 1/2)
200 A
160 A
125 A
100 A
B
80 A
63 A
50 A
40 A
32 A
25 A
C
20 A
16 A
10 A
D
A.7
WTN Plus
WTN Plus gF fast acting I2t values
125 – 630Amp
Fuse links
20– 160Amp
A
B
C
D
A.8
Rating
and Type
WTN-00/gF 20A
WTN-00/gF 25A
WTN-00/gF 32A
WTN-00/gF 40A
WTN-00/gF 50A
WTN-00/gF 63A
WTN-00/gF 80A
WTN-00/gF 100A
WTN-00/gF 125A
WTN-00/gF 160A
Pre-Arcing
I2t (A2s)
Total at
400V
Nom.
Watts Loss
280
400
720
820
1900
3200
5100
11250
12800
23500
2400
3400
4600
6800
11800
23300
20000
51700
71800
120000
2.7
3.3
4.4
4.7
6.0
7.8
9.4
10.4
13.2
14.7
Rating
and Type
Pre-Arcing
I2t (A2s)
Total at
400V
Nom.
Watts Loss
WTN-1/gF 20A
WTN-1/gF 25A
WTN-1/gF 32A
WTN-1/gF 40A
WTN-1/gF 50A
WTN-1/gF 63A
WTN-1/gF 80A
WTN-1/gF100A
WTN-1/gF 125A
WTN-1/gF 160A
WTN-1/gF 200A
WTN-1/gF 250A
290
530
770
870
2260
3900
6350
10350
18100
27000
50600
69500
1800
4000
4700
7700
13000
20700
3150
47600
85000
108500
188800
275600
3.1
3.9
5.2
5.5
7.0
9.0
10.6
11.2
14.7
19.4
23.0
28.6
WTN Plus gF fast acting cut off current characteristics
WTN Plus gF, Size 00
WTN Plus gF, Size 1
WTN Plus
WTN Plus gG general purpose time/current characteristics
DIN size 00
DIN size 00C
10 000
10 000
6
6
4
4
160
100
63
1 000
1 000
50
40
6
4
100
32
25
20
6
16
2
125
100
2
80
2
80
6
63
4
50
40
32
25
20
2
100
6
4
4
TIME (Seconds)
TIME (Seconds)
16
2
10
6
4
2
2
10
6
10
6
4
2
1
1
6
6
4
4
2
2
0.1
0.1
6
4
4
2
2
0.01
2
4
6
8
10
2
4
6
8
100
2
4
6
8
1000
0.01
6
2
8
10
2
4
6
8
DIN size 1C
2
4
6
8
1000
2
4
6
DIN size 1
10 000
10 000
160
6
6
125
4
4
250
200
2
160
100
80
2
50
40
6
4
100
80
2
25
6
20
4
16
TIME (Seconds)
100
10
2
6
4
A
63
32
2
125
1 000
63
1 000
TIME (Seconds)
100
CURRENT (Amperes)
CURRENT (Amperes)
Fuse links
6
10
6
4
2
100
50
40
6
32
4
25
B
2
10
6
4
2
1
20
1
6
16
6
4
10
C
4
2
2
0.1
6
0.1
6
6
4
6
4
2
0.01
2
0.01
6
8
10
2
4
6
8
100
2
4
6
8
1000
2
4
4
6
10
8
2
4
6
8
100
2
4
6
8
1000
2
CURRENT (Amperes)
6
CURRENT (Amperes)
DIN size 2
4
D
DIN size 3
10 000
10 000
400
6
4
2
315
6
250
200
4
1 000
160
6
125
4
100
630
2
500
400
1 000
6
315
4
80
2
2
63
100
100
6
6
4
TIME (Seconds)
TIME (Seconds)
4
2
10
6
4
2
1
2
10
6
4
2
1
6
6
4
4
2
2
0.1
0.1
6
6
4
4
2
2
0.01
6
8
100
2
4
6
8
1000
CURRENT (Amperes)
2
4
6
8
10 000
2
0.01
2
4
6
8
100
2
4
6
8
1000
2
4
6
10,000
CURRENT (Amperes)
A.9
WTN Plus
WTN Plus gF fast acting time/current characteristics
Fuse links
WTN Plus gF, size 00
A
B
C
D
A.10
WTN Plus gF, size 1
DI-FUS
DI-FUS gG and aM type fuse links
• High Rupture Capcity fuse links
• Low power disspation
• Plain undrilled silver plated copper knife-blade tags
• visual indicator situated in the top end plate
• DI-FUS fuse links are VDE certified at 120kA RMS, 50Hz,
500VAc to IEC269
• Cadmium and Lead free manufacturing process
Fuse links
• Two uitlisation catagories: Genaral purpose class gG and
Motor starting class aM
A
Standards
General data
IEC 60269
General purpose fuse links class ‘gG’
Motor starting fuse links class ‘aM’
Current Rating
Voltage Rating
Breaking Capacity
Max Operating
Ambient Temperature
DIN 43620 (part 1 to 4)
European dimensional standard sizes
B
(A)
(V)
(kA)
(C)
6-630
500
120
40
VDE0636
Approvals
C
Associated switchable devices
DI-DISC and DI-STRIP fuse switch diconnector
FULOS and FULOS PLUS fuse switch disconnector
D
Applications
‘NHG’ general purpose
With European dimensional standards to DIN 43620 and
performance standards to VDE 0636/21, operating class gL,
‘NHG’ range of Fuse Links are rated for use on systems up to
500 Volts ac
Technical Standard
VDE 0636/21 Class ‘gL’
IEC 60269-21 General purpose Fuse Links Class ‘gG’
‘NHA’ motor starting
Class ‘aM’ range of DIN Fuse Links are specifically designed
for the short circuit protection of equipment in motor circuits.
The Fuse Links are used in combination with overload
protective devices ensuring total protection of the circuit.
The rating of the Fuse Link is selected against the nominal
current of the motor. This enables simple and effective
selection of Fuse Links for motor circuits.
Technical Standard
VDE 0636/22 Class ‘aM’
IEC 60269-21 Motor Starting Fuse Links Class ‘aM’
A.12
DI-FUS
DI-FUS General Purpose NHG-000 6A-160A
Rated Current
Max. Nominal
voltage
Packaging
Ref. No.
?6 A
10A
16A
20A
25A
32A
35A
40A
50A
63A
80A
100A
125A
160A
500V
500V
500V
500V
500V
500V
500V
500V
500V
500V
500V
500V
500V
500V
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
4? 0 3 0 0 0
403001
403002
403003
403004
403005
403006
403007
403008
403009
4 0 3 0 10
4 0 3 0 11
4 0 3 0 12
4 0 3 0 13
Rated Current
Max. Nominal
voltage
Packaging
Ref. No.
?125A
160A
500V
500V
3/60
3/60
4? 0 3 0 14
4 0 3 0 15
Fuse links
DI-FUS General Purpose NHG-00 125A-160A
A
DI-FUS General Purpose NHG-1 6A-250A
Rated Current
Max. Nominal
voltage
Packaging
Ref. No.
?6 A
10A
16A
20A
25A
32A
35A
40A
50A
63A
80A
100A
125A
160A
200A
224A
250A
500V
500V
500V
500V
500V
500V
500V
500V
500V
500V
500V
500V
500V
500V
500V
500V
500V
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
4? 0 3 0 16
4 0 3 0 17
4 0 3 0 18
4 0 3 0 19
403020
403021
403022
403023
403024
403025
403026
403027
403028
403029
403030
403031
403032
B
C
D
A.13
DI-FUS
Fuse links
DI-FUS General Purpose NHG-2 35A-400A
A
B
C
D
A.14
Rated Current
Max. Nominal
voltage
Packaging
Ref. No.
3? 5A
40A
50A
63A
80A
100A
125A
160A
200A
224A
250A
315A
350A
400A
500V
500V
500V
500V
500V
500V
500V
500V
500V
500V
500V
500V
500V
500V
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
4? 0 3 0 3 3
403034
403035
403036
403037
403038
403039
403040
403041
403042
403043
403044
403045
403046
DI-FUS General Purpose NHG-3 100A-630A
Rated Current
Max. Nominal
voltage
Packaging
Ref. No.
1?00A
125A
160A
200A
224A
250A
315A
350A
400A
500A
630A
500V
500V
500V
500V
500V
500V
500V
500V
500V
500V
500V
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
4? 0 3 0 4 7
403048
403049
403050
403051
403052
403053
403054
403055
403056
403057
DI-FUS
DI-FUS Motor Starting NHA-000 4A-50A
Rated Current
Max. Nominal
voltage
Packaging
Ref. No.
?4 A
6A
8A
10A
12A
16A
20A
25A
32A
40A
50A
500V
500V
500V
500V
500V
500V
500V
500V
500V
500V
500V
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
4? 0 3 0 5 8
403059
403060
403061
403062
403063
403064
403065
403066
403067
403068
DI-FUS Motor Starting NHA-00 63A-160A
Max. Nominal
voltage
Packaging
Ref. No.
?6 3A
80A
100A
125A
160A
500V
500V
500V
500V
500V
3/60
3/60
3/60
3/60
3/60
4? 0 3 0 6 9
403070
403071
403072
403073
DI-FUS Motor Starting NHA-1 40A-250A
Rated Current
Max. Nominal
voltage
Packaging
Ref. No.
? 0A
4
50A
63A
80A
100A
125A
160A
200A
250A
500V
500V
500V
500V
500V
500V
500V
500V
500V
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
4? 0 3 0 7 4
403075
403076
403077
403078
403079
403080
403081
403082
Fuse links
Rated Current
A
B
C
DI-FUS Motor Starting NHA-2 125A-400A
Rated Current
Max. Nominal
voltage
Packaging
Ref. No.
1?25A
160A
200A
250A
315A
400A
500V
500V
500V
500V
500V
500V
3/3
3/3
3/3
3/3
3/3
3/3
4? 0 3 0 8 3
403084
403085
403086
403087
403088
D
DI-FUS Motor Starting NHA-3 315A-630A
Rated Current
Max. Nominal
voltage
Packaging
Ref. No.
?3 15A
400A
500A
630A
500V
500V
500V
500V
3/3
3/3
3/3
3/3
4? 0 3 0 8 9
403090
403091
403092
A.15
DI-FUS
Fuse links
DI-FUS Dimensions
A
NHG fuse links
DINsize
000
00
1
1
2
2
3
3
In [A]
a1
a2
a3
a4
b (min)
c1
d
e1
e2
f
6-160
125-160
6-160
200-250
35-250
315-400
100-400
500-630
78
78
135
135
150
150
150
150
52
52
69
69
69
70
70
73
45
45
62
61
61
61
61
61
49
49
67
67
67
67
68
68
15
15
15
20
20
25
25
32
35
35
40
40
48
48
60
60
2
2
2,5
3
3
3
3
3,5
39.5
45
45
50
50
58
58
73
20.5
29
29
44.5
44.5
50
50
71
7
12
12
12
12
12
12
15
In [A]
a1
a2
a3
a4
b (min)
c1
d
e1
e2
f
4-50
63-100
125-160
40-160
200-250
125-250
315-400
315-400
500-630
78
78
78
135
135
150
150
150
150
52
52
52
69
69
69
70
70
73
45
45
45
62
61
61
61
61
61
49
49
49
67
67
67
67
68
68
15
15
15
15
20
20
25
25
32
35
35
35
40
40
48
48
60
60
2
2
2
2,5
3
3
3
3
3,5
39,5
38
45
45
50
50
58
58
73
20,5
29
29
29
44,5
44,5
50
50
71
7
7
12
12
12
12
12
12
15
NHA fuse links
B
C
DINsize
000
00
00
1
1
2
2
3
3
D
NHG general purpose fuse links I2t values
Rated
Current
?6
10
16
20
25
32
35
40
50
63
80
100
125
160
200
224
250
315
350
400
500
630
A.16
Pre-Arcing
I2t (A2sec)
20
110
230
650
1200
2000
3500
4500
4850
6100
7000
14000
9900
40000
95000
120000
140000
290000
400000
600000
700000
800000
NHA motor starting fuse links I2t values
I2t (A2s)
Total-Arcing
Total-Arcing
I2t (A2sec) at 380V I2t (A2sec) at 500V
300
940
1870
3500
5360
8930
10200
15300
21300
35700
68000
110500
89300
195500
331500
391000
493000
978000
1148000
1700000
2295000
4080000
350
1100
2200
4100
6300
10500
12000
18000
25000
42000
80000
130000
105000
230000
390000
460000
580000
1150000
1350000
2000000
2700000
4800000
Rated
Current
?
4
6
8
10
12
16
20
25
32
40
50
63
80
100
125
160
200
250
315
400
500
630
Pre-Arcing
I2t (A2sec)
31
64
93
290
290
700
860
1300
3000
6000
10000
1700
3400
16800
15500
25500
29000
56000
83000
160000
200000
370000
I2t (A2s)
Total-Arcing
Total-Arcing
I2t (A2sec) at 380V I2t (A2sec) at 500V
280
700
1280
3150
4170
5900
7060
9400
17900
27200
40000
63800
93500
162000
187000
264000
425000
723000
935000
1615000
1785000
3485000
330
820
1500
3700
4900
6900
8300
11000
21000
32000
47000
75000
110000
190000
220000
310000
500000
850000
1100000
1900000
2100000
4100000
DI-FUS
‘NHG’ general purpose time/current characteristics
DIN size 00
DIN size 1
DIN size 2
Fuse links
DIN size 000
A
B
C
D
DIN size 3
A.17
DI-FUS
Fuse links
‘NHA’ motor starting time/current characteristics
DIN size 000
DIN size 00
DIN size 1
DIN size 2
A
B
C
D
DIN size 3
A.18
Fuse bases
PBG and PBN plastic fuse bases
B.3
Order codes
B.2
Technical data
B.4
Dimensions
DI-BASE plastic and steel type NH fuse bases
B.7
Order codes
B.6
Technical data
B.8
Dimensions
Neutral links WTZ
B.12 Order codes
B.12 Dimensions
Fuse links
A
Fuse bases
B
Fuse switch disconnectors
C
Numerical index
D
B.1
PBG/PBN
PBG and PBN plastic NH fuse bases
• Available in sizes 00, 1, 2, and 3
• Supporting part of plastic fuse bases is made from
fibreglass reinforced moulding material with high
mechanical strength and high thermal resistance.
• IP00/IP20 protection
• Silver plated contacts
Fuse bases
• Rated at 690V
A
Standards
General data
EN 60 269-1, -2
Current Rating
Voltage Rating
DIN sizes
IEC 60 269-1, 2-1;
(A)
(V)
160-630
690
00,1,2,3
DIN 43620
B
Approvals
T echnical data P BG and P BN F use Bases
POL Y ES T ER NH FUS E BA S ES
PROPERT IES
Applications
D
US E
S CREW
CLA MP
MA X. TIGHTENING TORQUE
WITH MICROS WITCH 16A / 250V
B.2
160A / 690V 250A / 690V 400A / 690V 630A / 690V
20°C
30°C
40°C
50°C
MA X. POWER DIS IPA TION
DEGREE OF PROTECTION
FIXING
PBN3 NH3
CHROME-PLA TED S TEEL
S CREW, NUT A ND WA S HERS
CONNECTING
PBN2 NH2
S ILV ER PLA TING
CONTA CTS
DERA TING TEMPERA TURE
PBN1 NH1
THERMOPLA S TIC +25% F.V . UL94-V 0
IMA X A MPERA GE BY U ( V )
E L E C T R IC A L
C
MA T E R IA L S
PB00 NH00
BODY
DIN RA IL
S CREW
PRES ENCE /
FUS ION
1
0.95
0.9
0.8
12W
IP00/IP20
M8
2 x M6
10Nm
l
l
1
0.95
0.9
0.8
32W
IP00/IP20
1
0.95
0.9
0.8
45W
IP00/IP20
1
0.95
0.9
0.8
60W
IP00/IP20
M8
M8
M8
32Nm
l
l
32Nm
l
l
32Nm
l
l
-
l
l
l
PBG/PBN
PBG/PBN plastic fuseholder
Poles
Size
Type
Packaging
160A
Rated current In
1
00
pla s tic
3
Ref. Nr.
700645
250A (355A)
1
1
pla s tic
3
700567
400A (630A)
1
2
pla s tic
3
700569
630A
1
3
pla s tic
1
o n re que s t
160A
3
00
pla s tic
1
700646
250A (355A)
3
1
pla s tic
1
700568
400A (630A)
3
2
pla s tic
1
700570
630A
3
3
pla s tic
1
700571
Partition/Separating plate
and Separator connector
Rated current In
Fuse cover
Terminal cover
Packaging
Ref. Nr.
Packaging
160A
00
6
700823
3
700828
250A
1
6
700825
3
700830
Ref. Nr.
400A
2
6
700826
3
700830
630A
3
6
700827
3
700831
Rated current In
Size
Partition plate
Separator
Packaging
Ref. Nr.
Packaging
Ref. Nr.
160A
00
2
700815
2
700819
250A/400A
1/2
2
700817
2
700821
3
2
700818
2
700822
Size
Packaging
Ref. Nr.
00-3
1
700814
630A
Microswitch for fixation on
blades of all sizes WTN Plus
fuses
Size
Rated current In
160A
Fuse bases
Fuse base accessories
Terminal Contact and fuse
covers
A
B
C
D
B.3
PBG/PBN
Fuse bases
PBN/PBG Dimensions
A
B
C
D
B.4
DI-BASE
DI-BASE plastic and steel type
NH fuse bases
• Available in sizes 00*, 1, 2, and 3
• Different terminal connections available on request
• IP00/IP20 protection
• Supporting part of plastic fuse bases is made from
fibreglass reinforced moulding material with high
mechanical strength and high thermal resistance.
• Supporting part of steel fuse bases is made from zincchromated steel sheet.
Fuse bases
• Fuse-bases are always equipped with inter polar barriers.
End barrier must be ordered separately.
A
• Contact carriers of steel type are from steatite with high
mechanical strength.
* Either fuse links sizes 00, or 000 can be used with
Standards
General data
EN 60 269-1, -2
Current Rating
Voltage Rating
DIN sizes
IEC 60 269-1, 2-1;
(A)
(V)
160-250
690
00,1,2,3
DIN 43620
B
Applications
Approvals
C
D
General data DI-BASE SPB Plastic Fuse Bases
SPB00
Rated current
DIN-size
Usable DIN-size of fuses
Watt loss
Voltage
IP protection
Standards
In
Pv
Un
SPB1
SPB2
S3PB00
160 A
250 A
400 A
160 A
00
1
2
00
000, 00
1, (0, 01)
2, (02)
000, 00
12 W
32 W
45 W
12 W
690 V
690 V
690 V
690 V
IP00
IP00
IP00
IP00
IEC 60269-1, 2-1; DIN 43620; ČSN EN 60 269-1, -2; ČSN 35 4701-2-1;
General data DI-BASE SPF Steel Fuse Bases
SPF00
Rated current
DIN-size
Usable DIN-size of fuses
Watt loss
Voltage
IP protection
Standards
B.6
In
Pv
Un
SPF1
SPF2
SPF3
160 A
250 A
400 A
630 A
00
1
2
3
000, 00
1, (0, 01)
2, (02)
3, (03)
12 W
32 W
45 W
60 W
690 V
690 V
690 V
690 V
IP00
IP00
IP00
IP00
IEC 60269-1, 2-1; DIN 43620; ČSN EN 60 269-1, -2; ČSN 35 4701-2-1;
S3PB1
S3PB2
SPF3
250 A
1
1, (0, 01)
32 W
690 V
IP00
400 A
2
2, (02)
45 W
690 V
IP00
630 A
3
3, (03)
60 W
690 V
IP00
DI-BASE
DI-BASE plastic and steel type NH fuse bases
Poles
Size
Type
Packaging.
Ref No.
160A
250A
400A
1
1
1
00*
1
2
plastic
plastic
plastic
3
3
3
?772739
772746
772752
160A
250A
400A
3
3
3
oo*
1
2
plastic
plastic
plastic
1
1
1
772762
772766
772772
160A
250A
400A
630A
1
1
1
1
oo*
1
2
3
steel
steel
steel
steel
3
3
3
3
772270
772724
772730
772736
Fuse bases
Rated Current In
* for Size 00 both fuselinks sizes oo, and 000 can be used
All DI-BASE have terminals with pressed nuts and flat terminal screws; other terminal types on request
A
DI-BASE accessories
Contact cover
Rated Current In
Poles
Size
Type
Packaging.
Ref No.
1
1
1
oo*
250A
400A
1
2
plastic
plastic
plastic
2
2
2
772793
772794
772795
B
160A
160A
250A
400A
1
3
1
1
oo*
oo*
1
2
plastic
plastic
plastic
plastic
1
1
1
1
772789
772790
772791
772792
C
160A
End barrier
D
B.7
DI-BASE
DI-BASE Dimensions
SPB Single Pole Plastic Fuse base
Fuse bases
SPB00
SPB Single Pole Plastic Fuse base
SPB1,2
A
B
C
D
A
B
C
E
[mm]
F
H
I
K
? PB1
S
?SPB2
37
37.5
83.3
89.5
87.5
100
100.5
114
---
108
116
Ø 11
Ø 11
31
36
Contact covers
type K00
B.8
?Type
type K1
type K2
DI-BASE
SPB three Pole Plastic Fuse base
S3PB00,1,2
?C
D
E
G
H
I
K
L
[mm]
M
N
P
R
T
U
V
? 3PB00
S
?S3PB1
?S3PB2
25
35
35
-
Ø9
Ø11
Ø11
104
146
146
50
87.5
100
25
35
35
9
7
7
60
100
114
58.5
84
90
105
159
179
-
36
56
66
130
205
230
86
108
116
19
31
36
Fuse bases
Type
SPB three Pole Plastic Fuse base
S3PB00,1,2
A
B
C
?Combination
A
[mm]
S3PB00 - S3PB1
S3PB00 - S3PB2
70
75
D
B.9
DI-BASE
SPF single Pole Steel Fuse base
Fuse bases
SPF00,1,2,3
A
Type
?C
E
G
H
K
L
[mm]
M
N
P
U
V
? PF00
S
?SPF1
?SPF2
?SPF3
25
35
35
40
Ø9
Ø11
Ø11
Ø11
90
153
153
153
50
87.5
100
105
5.5
11
11
11
60.2
100
114
119
58.5
84
90
92
34
55
55
55
-
84
108
116
122
25
35
35
35
Contact covers
B
type K00
C
D
B.10
type K1
type K2
WTZ
WTZ Neutral Links
• Available in sizes 00*, 1, 2, and 3
• Conductive parts made of high quality tin coated copper
• Can be used in fuse bases, fuse rails or fuse switch
disconnectors
Fuse bases
* Can be used in fuse bases sizes 00, or fuse switch
disconnectors siez 000 and 00
Standards
General data
EN 60 269-1, -2
Current Rating
Voltage Rating
DIN sizes
IEC 60 269-1, 2-1;
A
(A)
(V)
160-630
690
00,1,2,3
DIN 43620
Approvals
Applications
B
C
Neutral Links
Rated
current In
D
Size
Material
Voltage
rating
Packaging
Ref. Nr.
160A
00
tin c o a te d c o ppe r
690V
3
700573
250A
1
tin c o a te d c o ppe r
690V
3
700574
400A
2
tin c o a te d c o ppe r
690V
3
700575
630A
3
tin c o a te d c o ppe r
690V
3
700576
Dimensions
Dimensions in mm
B.12
Size
A
B
C
D
E
OO
16
35
45
78.5
20
1
20
40
50
135
20
2
25
48
58
150
20
3
32
60
70
150
20
DI-LINE industrial fusegears
DI-DISC ‘FH’ horizontal fuse switch disconnector
C.4
Order codes
C.3
Technical data
C.5
Dimensions
DI-STRIP ‘FD’ vertical fuse switch disconnector
C.13 Order codes
C.12 Technical data
C.14 Dimensions
DI-RAIL ‘FR’ fuse rail
C.17 Order codes
C.16 Technical data
C.18 Dimensions
Fuse links
A
Fuse bases
B
Fuse switch disconnectors
C
Numerical index
D
C.1
DI-DISC
DI-DISC ‘FH’ horizontal fuse switch
disconnector
• Available in sizes 000, 00, 1, 2, and 3
• Versions with terminal clips or screws M10/M12
DI-LINE industrial fusegear
• Version with fuse monitor allows remote signaling in every
pole (using normal fuse links with blade contacts with visual
indicator on top)
A
• Possibility to lock the cover
• Measuring holes in the cover
• Label on cover to describe name of the circuit
• Mounting: direct on the panel with screws, on 60 mm rail
system with special adapter; on 35 mm rails acc. to DIN EN
50 022 (size 000),
Standards
General data
EN 60 269-1, -2
Current Rating
Voltage Rating
DIN sizes
IEC 60 269-1, 2-1;
DIN 43620
B
Approvals
C
Applications
D
C.2
(A)
(V)
160-630
690
000, 00,1,2,3
DI-DISC
General data DI-DISC FH
FH000
Un
Rated Voltage
In
Rated Current
Utilisation category
AC 690 V
DC 440 V
160 A
AC23B at AC 400 V
AC22B at AC 500 V
AC21B at AC 690 V
DC22B at DC 250 V
DC20B at DC 440 V
FH00
FH1
FH2
FH3
690 V
690 V
690 V
690 V
160 A
AC-23B
AC-22B
AC-21B
DC-22B
250 A
AC-23B
AC-22B
DC-21B
DC-21B
400 A
AC-23B
AC-23B
AC-22B
DC-21B
DC-21B
630 A
AC-23B
AC-23B
AC-22B
DC-21B
DC-21B
I th
160 A
160 A/ 250A
250 A/ 325 A
400 A/ 500 A
630 A/ 750 A
Rated frequency
Rated Insulation voltage
f
Ui
40 - 60 Hz
1000 V a.c.
120 kA
Conditional short-circuit
current (RMS)
I kn
40 - 60 Hz
800 V a.c.
80 kA for AC 690 V/100 A
120 kA for AC 500 V/100 A
50 kA for AC 500 V/160 A
120 kA for AC 400 V/160 A
8 kV for FH000 - 1(3)A/T
40 - 60 Hz
1000 V a.c.
> 25 kA for 690 V
50 kA for 500 V
120 kA for 400 V
40 - 60 Hz
1000 V a.c.
> 25 kA for 690 V
50 kA for 500 V
120 kA for 400 V
40 - 60 Hz
1000 V a.c.
> 25 kA for 690 V
50 kA for 500 V
120 kA for 400 V
12 kV for FH00 - .A/F
12 kV for FH1-1./F
12 kV for FH2-1./F
12 kV for FH3-1./F
Fuse link size
000
000, 00
1
2
3
Max. power losses of the fusePv
link
9W
12 W
23 W
34 W
48 W
Power losses at In without fusePv
link
7W
7W
9W
23 W
49 W
Electrical durability (operating
cycles)
300 at 100 A
200 at 160 A
300 at 100 A
200 at 160 A
200 at 250 A
200 at 400 A
200 at 630 A
Mechanical durability
(operating cycles)
2000
2000
1400
800
800
IP 30
IP 20
IP 30
IP 30
IP 30
IP 20
IP 20
IP 20
IP 20
IP 20
Impulse Withstand voltage
U imp
Degree of protection*
Degree of protection from
front side, built-in device, cover
open
Permissable ambient
temperature
- 25 - + 55 °C
- 25 - + 55 °C
- 25 - + 55 °C
- 25 - + 55 °C
- 25 - + 55 °C
Altitude above sea level
Pollution degree
max. 2000 m
3
max. 2000 m
3
max. 2000 m
3
max. 2000 m
3
max. 2000 m
3
Overvoltage category for 690V
a.c.
III
IV
IV
IV
IV
0,25 - 50 Hz/3g
0,25 - 50 Hz/3g
0,25 - 50 Hz/3g
3 - 3,5 Nm
IEC 60 947-1, -3
EN 60 947-1, -3
0,25 - 50 Hz/3g
2,5 - 3 Nm
IEC 60 947-1, -3
EN 60 947-1, -3
IEC 60 947-1, -3
EN 60 947-1, -3
IEC 60 947-1, -3
EN 60 947-1, -3
IEC 60 947-1, -3
EN 60 947-1, -3
Seismic resistance
Torque of outlet terminals
Standards
DI-LINE industrial fusegear
Thermal current with fuselink/disconnecting knife
A
B
* from front side, built-in device, cover closed (measuring holes filled)
C
D
C.3
DI-DISC
DI-LINE industrial fusegear
DI-DISC ‘FH’ horizontal fuse switch disconnector
A
B
Rated Current In
Poles
Size
fuse monitor
Terminal
Cat. No.
Ref No.
1?60A
160A
160A
160A
1
3
1
3
000
000
00*
00*
N
N
N
N
clips
clips
screws M8
screws M8
FH000-1A/T
?
FH000-3A/T
FH00-1A/F
FH00-3A/F
772605
?
772607
772850
772852
160A
160A
160A
160A
1
3
1
3
000
000
00*
00*
Y**
Y**
Y**
Y**
clips
clips
screws M8
screws M8
FH000-1S/T
FH000-3S/T
FH00-1S/F
FH00-3S/F
772606
772608
772851
772853
250A
250A
1
3
1
1
N
N
screws M10
screws M10
FH1-1A/F
FH1-3A/F
772628
772630
250A
250A
1
3
1
1
Y**
Y**
screws M10
screws M10
FH1-1S/F
FH1-3S/F
772629
772631
400A
400A
1
3
2
2
N
N
screws M10
screws M10
FH2-1A/F
FH2-3A/F
772646
772648
400A
400A
1
3
2
2
Y**
Y**
screws M10
screws M10
FH2-1S/F
FH2-3S/F
772647
772649
630A
630A
1
3
3
3
N
N
screws M12
screws M12
FH3-1A/F
FH3-3A/F
772662
772664
630A
630A
1
3
3
3
Y**
Y**
screws M12
screws M12
FH3-1S/F
FH3-3S/F
772663
772665
C
D
* both fuselinks sizes 00 and 000 can be used
** connector with 1 m cable included
DI-DISC ‘FH’ busbar adaptors for 60mm busbar system
Busbar
C.4
For use with
Size
FH000-3…
FH1-3./F
FH2-3./F
000
1
2
tickness (mm) width
5 or 10
5 or 10
5 or 10
(mm)
12-30
12-30
12-30
Cable outlet
Cat. No.
bottom
GA-60/100/81-1x15
?
bottom and top
OD-FH1-AL60
bottom and top
OD-FH2-AL60
Ref No.
On request
?772641
772657
DI-DISC
DI-DISC Dimensions
FH000-1A/T
FH000-3A/T
FH000-1A/T and FH000-3A/T
DI-LINE industrial fusegear
FH000-1A/T and FH000-3A/T
FH000-3A/T
*for FH000-3A/T=181
A
B
C
* for FH000-3A/T=82
D
FH000-1S/T and FH000-3S/T
FH000-1S/T and FH000-3S/T
* for FH000-3S/T=181
C.5
DI-DISC
DI-DISC Dimensions
DI-LINE industrial fusegear
FH1-1A/F
FH1-1A/F and FH1-3A/F
FH1-3A/F
FH1-3A/F
FH1-1A/F and FH1-3A/F
* for FH1-3A/F= 67°
A
** for FH1-3A/F= 315
B
C
D
FH1-1S/F and FH1-3S/F
FH1-1S/F and FH1-3S/F
* for FH1-1S/F= 78°
** for FH1-1S/F= 316
C.6
DI-DISC
DI-DISC Dimensions
FH2-1A/F
FH2-3A./F
DI-LINE industrial fusegear
FH2-1A/F and FH2-3A/F
FH2-3A/F
FH2-1A/F and FH2-3A/F
* for FH2-3A/F= 67°
** for FH2-3A/F= 347
A
B
C
D
FH2-1S/F and FH2-3S/F
FH2-1S/F and FH2-3S/F
* for FH2-1S/F= 78°
** for FH2-1S/F= 350
C.7
DI-DISC
DI-DISC Dimensions
DI-LINE industrial fusegear
FH3-1A/F
FH3-1A/F and FH3-3A/F
FH3-3A/F
FH3-3A./F
FH3-1A/F and FH3-3A/F
* for FH3-3A/F= 70°
A
** for FH3-3A/F= 356
B
C
D
FH3-1S/F and FH3-3S/F
FH3-1S/F and FH3-3S/F
* for FH3-1S/F= 78°
** for FH3-1S/F= 358
C.8
DI-DISC
DI-DISC Dimensions
Clearance and drilling plans blade contact size 000
1 - pole
2 - pole
4 - pole
1 - pole
2 - pole
4 - pole
DI-LINE industrial fusegear
Clearance and drilling plans blade contact size 1
A
B
C
D
Clearance and drilling plans blade contact size 2
1 - pole
2 - pole
4 - pole
C.9
DI-DISC
DI-DISC Dimensions
Clearance and drilling plans blade contact size 3
DI-LINE industrial fusegear
1 - pole
A
2 - pole
4 - pole
Remote signalling
Remote signalling of fuse condition in 1-pole fuse
switch-disconnector
Remote signalling of fuse condition in 3-pole
fuse switch-disconnector
State of contacts with not operated fuse-link:
contacts 1 – 3 connected
State of contacts with not operated fuse-link:
contacts 1 – 3, 2 – 8, 3 - 9 connected
B
C
D
C.10
Remote signalling of hinged cover position in 1-pole and 3-pole
fuse switch-disconnector
State of contacts with closed cover:
contacts C – NO connected
DI-STRIP
DI-STRIP ‘FD’ Vertical fuse switch
disconnector
• For applications in distribution and industrial LV-switch boards
with busbar spacing 185 mm
• Available in sizes 1, 2, and 3
DI-LINE industrial fusegear
• Modular design
A
• 1-Pole and 3-Pole control (additionally interchangeable)
• Remote signalling for fuse-link state
• Possibility to lock cover only with fuse link removed
• Cable outlet down or up
• Measuring holes in the cover
• Connection to busbars by screws M12
• Mounting width does not extend 100 mm
• Outlet description label
Standards
General data
EN 60 269-1, -2
Current Rating
Voltage Rating
DIN sizes
IEC 60 269-1, 2-1;
(A)
(V)
250-630
690
1,2,3
DIN 43620
B
Approvals
C
FD1
FD2
FD3
R a te d c urre nt
In
250 A
400 A
630 A
R a te d vo lta ge
Un
690 V
690 V
690 V
S ta nda rds
Applications
D
General data DI-STRIP FD
IEC 60 947-1, -3; EN 60 947-1, -3
Utilis a tio n c a te go ry
400 V a .c .
AC -23B
AC -23B
AC -23B
690 V a .c .
AC -22B
AC -22B
AC -22B
The rm a l c urre nt with fus e -link
Ith
250 A
400 A
630 A
The rm a l c urre nt with dis c o nne c ting knife
Ith
400 A
560 A
800 A/ 1000 A
R a te d fre que nc y
f
40 - 60 Hz
40 - 60 Hz
40 - 60 Hz
R a te d ins ula tio n vo lta ge
Ui
1000 V a .c .
1000 V a .c .
1000 V a .c .
C o nditio na l s ho rt c irc uit c urre nt with fus e -link DI-F US
(R M S )
400 V a .c .
Ikn
120 kA
120 kA
120 kA
500 V a .c .
Ikn
50 kA
50 kA
50 kA
Uimp
8 kV
8 kV
8 kV
1
2
3
In
250 A
400 A
630 A
M a xim um po we r lo s s e s o f the fus e -link
Pv
32 W
45 W
60 W
In witho ut fus e -link
Pv
18 W
39 W
90 W
Ele c tric a l dura bility (o pe ra ting c yc le s )
200
200
200
M e c ha nic a l dura bility (o pe ra ting c yc le s )
1400
800
800
De gre e o f pro te c tio n*
IP 20
IP 20
IP 20
Im puls withs ta nd vo lta ge
F us e -link s ize
M a xim um ra te d c urre nt o f the fus e -link
De gre e o f pro te c tio n*
P e rm is s a ble a m bie nt te m pe ra ture
Altitude a bo ve s e a le ve l
Ove rvo lta ge c a te go ry fo r 690V a .c .
S e is m ic re s is ta nc e
* fro m fro nt s ide , built-in de vic e , c o ve r c lo s e d
C.12
IP 20
IP 20
IP 20
-25 - +55 °C
-25 - +55 °C
-25 - +50 °C
m a x. 2000 m
m a x. 2000 m
m a x. 2000 m
III
III
III
1,5 g / 8 - 50 Hz 1,5 g / 8 - 50 Hz 1,5 g / 8 - 50 Hz
DI-STRIP
DI-STRIP ‘FD’ vertical fuse switch disconnector
Poles of
Control
Size
250A
250A
250A
250A
250A
250A
1
3
1
3
1
3
1
1
1
1
1
1
400A
400A
400A
400A
400A
400A
1
3
1
3
1
3
630A
630A
630A
630A
630A
630A
1
3
1
3
1
3
Terminal
Cat. No.
Ref No.
pressed-in nuts with screws M10
pressed-in nuts with screws M10
V-shaped clamps*
V-shaped clamps*
busbar systems coupler
busbar systems coupler
FD1-31/LM
?
FD1-33/LM
FD1-31/LW
FD1-33/LW
FD1-31/LL
FD1-33/LL
772679
772680
772681
772682
772691
772692
2
2
2
2
2
2
pressed-in nuts with screws M12
pressed-in nuts with screws M12
V-shaped clamps*
V-shaped clamps*
busbar systems coupler
busbar systems coupler
FD2-31/LM
FD2-33/LM
FD2-31/LW
FD2-33/LW
FD2-31/LL
FD2-33/LL
772683
772684
772685
772686
772693
772694
3
3
3
3
3
3
pressed-in nuts with screws M12
pressed-in nuts with screws M12
V-shaped clamps*
V-shaped clamps*
busbar systems coupler
busbar systems coupler
FD3-31/LM
FD3-33/LM
FD3-31/LW
FD3-33/LW
FD3-31/LL
FD3-33/LL
772687
772688
772689
772690
772695
772696
DI-LINE industrial fusegear
Rated Current In
A
* V-clamps have to be ordered separately
B
V-shaped clamps for DI-STRIP ‘FD’ vertical fuse switch disconnector
Size (mm2)
95
185
240
70x2
240x2
Conductor
cross section sm
type
max
C u o r Al
C u o r Al
C u o r Al
C u o r Al
C u o r Al
90m m
185m m
240m m
70m m x2
240m m x2
Torque (Nm)
Cat. No.
Ref No.
12-15
22-23
25
12-15
25
4
? 835 N-s
4835 N
4836 N-240
5836-2x70
5836-2x240
? 72818
7
772817
772816
772819
772820
C
D
C.13
DI-STRIP
DI-LINE industrial fusegear
DI-STRIP FD Dimensions
A
Remote signalling of fuse condition in
the fuse switch-disconnector
Remote signalling of hinged cover
position of the switch-disconnector
B
State of contacts with not operated fuselink: contacts C – NC connected
State of contacts with closed cover:
contacts C – NO connected
5 A/250 V a.c.
5 A/250 V a.c.
C
D
C.14
DI-RAIL
DI-RAIL ‘FR’ fuse rail
• For applications in LV cabinets and distribution switch baords
with busbar spacing 185 mm
• Available in sizes 1, 2, and 3
DI-LINE industrial fusegear
• Modular design
A
• Fully protected against accidental contact
• Insulated covers IP20
• Connection to busbars by screws M12
• Mounting width does not extend 100 mm
• Outlet description label
Standards
General data
EN 60 269-1, -2
Current Rating
Voltage Rating
DIN sizes
IEC 60 269-1, 2-1;
(A)
(V)
250-630
690
1,2,3
DIN 43620
B
Approvals
C
Applications
D
General data DI-RAIL FR
FR2
FR1
R a te d c urre nt
Ie
250 A
R a te d vo lta ge
Ue
690 V
S ta nda rds
630 A
690 V
690 V
IEC 60 269-1, 2-1; EN 35 4701-2-1
R a te d fre que nc y
f
40 - 60 Hz
40 - 60 Hz
40 - 60 Hz
R a te d ins ula tio n vo lta ge
Ui
1000 V a .c .
1000 V a .c .
1000 V a .c .
1
2
3
F us e -link s ize
M a xim um ra te d c urre nt o f the fus e -link
In
250 A
400 A
630 A
M a xim um po we r lo s s e s o f the fus e -link
Pv
32 W
45 W
60 W
400A/240 m m 2
560 A/ 183 m m 2
The rm a l c urre nt with dis c o nne c ting knife /c ro s s
s e c tio n
C.16
FR3
400 A
Ith
800 A/2x 185 m m 2
1000A/2x5x60 m m 2
De gre e o f pro te c tio n
IP 20
IP 20
IP 20
P e rm is s a ble a m bie nt te m pe ra ture
-25 - +55 °C
-25 - +55 °C
-25 - +50 °C
DI-RAIL
DI-RAIL ‘FR’ fuse rails
Size
250A
250A
250A
1
1
1
400A
400A
400A
630A
630A
630A
Terminal
Busbar spacing
Cat. No.
Ref No.
pressed-in nuts with screws M10
V-shaped terminals*
busbar system coupler
185 mm
185 mm
185 mm
FR1-3K/LM
FR1-3K/LW
FR1-3K/LL
772706
772708
772713
2
2
2
pressed-in nuts with screws M12
V-shaped terminals*
busbar system coupler
185 mm
185 mm
185 mm
FR2-3K/LM
FR2-3K/LW
FR2-3K/LL
772709
772712
772715
3
3
3
pressed-in nuts with screws M12
V-shaped terminals*
busbar system coupler
185 mm
185 mm
185 mm
FR3-3K/LM
FR3-3K/LW
FR3-3K/LL
772714
772711
772717
* V-clamps have to be ordered separately
A
V-shaped clamps for DI-RAIL ‘FR’ fuse rail
Size (mm2)
95
185
240
70x2
240x2
Conductor
cross section sm
type
max
C u o r Al
C u o r Al
C u o r Al
C u o r Al
C u o r Al
DI-LINE industrial fusegear
Rated Current In
90m m
185m m
240m m
70m m x2
240m m x2
Torque (Nm)
Cat. No.
Ref No.
12-15
22-23
25
12-15
25
? 835 N-s
4
4835 N
4836 N-240
5836-2x70
5836-2x240
?7 72818
772817
772816
772819
772820
B
C
D
C.17
DI-RAIL
DI-LINE industrial fusegear
DI-RAIL FR Dimensions
A
B
C
D
C.18
by reference number
Numerical index
A
B
C
D
X.2
Ref. No.
Cat. Numbers
page
403071
NHA00/100
A.15
700586
AP 033110
A.5
772631
F H1-3S /F
403000
?N HG000/006
A.13
403072
NHA00/125
A.15
700587
AP 033111
A.5
772641
OD-F H1-AL60
C .4
403001
NHG000/010
A.13
403073
NHA00/160
A.15
700588
AP 033112
A.5
772646
F H2-1A/F
C .4
403002
NHG000/016
A.13
403074
N
? HA1/040
A.15
700589
AP 033401
A.3
772647
F H2-1S /F
C .4
403003
NHG000/020
A.13
403075
NHA1/050
A.15
700590
AP 033402
A.3
772648
F H2-3A/F
C .4
403004
NHG000/025
A.13
403076
NHA1/063
A.15
700591
AP 033403
A.3
772649
F H2-3S /F
C .4
403005
NHG000/032
A.13
403077
NHA1/080
A.15
700592
AP 033404
A.3
403006
NHG000/035
A.13
403078
NHA1/100
A.15
700593
AP 033405
A.3
772657
OD-F H2-AL60
C .4
403007
NHG000/040
A.13
403079
NHA1/125
A.15
700594
AP 033406
A.3
772662
F H3-1A/F
C .4
403008
NHG000/050
A.13
403080
NHA1/160
A.15
700595
AP 033407
A.3
772663
F H3-1S /F
C .4
403009
NHG000/063
A.13
403081
NHA1/200
A.15
700596
AP 033408
A.3
772664
F H3-3A/F
C .4
403010
NHG000/080
A.13
403082
NHA1/250
A.15
700597
AP 033409
A.3
772665
F H3-3S /F
C .4
403011
NHG000/100
A.13
403083
N
? HA2/125
A.15
700598
AP 033410
A.3
772679
?F D1-31/LM
C .13
403012
NHG000/125
A.13
403084
NHA2/160
A.15
700599
AP 033411
A.3
772680
F D1-33/LM
C .13
403013
NHG000/160
A.13
403085
NHA2/200
A.15
700600
AP 033412
A.3
772681
F D1-31/LW
C .13
403014
?N HG00/125
A.13
403086
NHA2/250
A.15
700601
AP 033413
A.3
772682
F D1-33/LW
C .13
403015
NHG00/160
A.13
403087
NHA2/315
A.15
700602
AP 033501
A.4
772683
F D2-31/LM
C .13
403016
?N HG1/006
A.13
403088
NHA2/400
A.15
700603
AP 033502
A.4
772684
F D2-33/LM
C .13
403017
NHG1/010
A.13
403089
N
? HA3/315
A.15
700604
AP 033503
A.4
772685
F D2-31/LW
C .13
403018
NHG1/016
A.13
403090
NHA3/400
A.15
700605
AP 033504
A.4
772686
F D2-33/LW
C .13
772687
F D3-31/LM
C .13
772688
F D3-33/LM
C .13
772689
F D3-31/LW
C .13
772690
F D3-33/LW
C .13
C .13
C .4
403019
NHG1/020
A.13
403091
NHA3/500
A.15
700606
AP 033505
A.4
403020
NHG1/025
A.13
403092
NHA3/630
A.15
700607
AP 033506
A.4
403021
NHG1/032
A.13
700526
AP 030101
A.5
700608
AP 033507
A.4
403022
NHG1/035
A.13
700527
AP 030102
A.5
700609
AP 033508
A.4
403023
NHG1/040
A.13
700528
AP 030103
A.5
700610
AP 033509
A.4
403024
NHG1/050
A.13
700529
AP 030104
A.5
700611
AP 033510
A.4
772691
F D1-31/LL
403025
NHG1/063
A.13
700530
AP 030105
A.5
700612
AP 033511
A.4
772692
F D1-33/LL
C .13
403026
NHG1/080
A.13
700531
AP 030106
A.5
700613
AP 033512
A.4
772693
F D2-31/LL
C .13
403027
NHG1/100
A.13
700532
AP 030107
A.5
700614
AP 033513
A.4
772694
F D2-33/LL
C .13
403028
NHG1/125
A.13
700533
AP 030108
A.5
700615
AP 033514
A.4
772695
F D3-31/LL
C .13
403029
NHG1/160
A.13
700534
AP 030109
A.5
700616
AP 033515
A.4
772696
F D3-33/LL
C .13
403030
NHG1/200
A.13
700535
AP 030110
A.5
700617
AP 033516
A.4
772706
?F R 1-3K/LM
C .17
403031
NHG1/224
A.13
700536
AP 030491
A.3
700618
AP 033517
A.4
772708
F R 1-3K/LW
C .17
403032
NHG1/250
A.13
700537
AP 030492
A.3
700619
AP 034501
A.4
772709
F R 2-3K/LM
C .17
403033
?N HG2/035
A.14
700538
AP 030493
A.3
700620
AP 034502
A.4
403034
NHG2/040
A.14
700539
AP 030494
A.3
700621
AP 034503
A.4
772711
F R 3-3K/LW
C .17
403035
NHG2/050
A.14
700540
AP 030495
A.3
700622
AP 034504
A.4
772712
F R 2-3K/LW
C .17
403036
NHG2/063
A.14
700541
AP 030496
A.3
700623
AP 034505
A.4
772713
F R 1-3K/LL
C .17
403037
NHG2/080
A.14
700542
AP 030497
A.3
700624
AP 034506
A.4
772714
F R 3-3K/LM
C .17
403038
NHG2/100
A.14
700543
AP 030498
A.3
700625
AP 034507
A.4
772715
F R 2-3K/LL
C .17
403039
NHG2/125
A.14
700544
AP 030499
A.3
700626
AP 034508
A.4
772717
F R 3-3K/LL
C .17
403040
NHG2/160
A.14
700545
AP 030501
A.3
700627
AP 034509
A.4
772724
SP F1
B .7
403041
NHG2/200
A.14
700546
AP 030502
A.3
700628
AP 034510
A.4
772730
SP F2
B .7
403042
NHG2/224
A.14
700547
AP 030503
A.3
700629
AP 034511
A.4
772736
SP F3
B .7
403043
NHG2/250
A.14
700548
AP 030504
A.3
700630
AP 035501
A.4
772739
?S P B 00
B .7
772746
SP B1
B .7
772752
SP B2
B .7
772762
S 3P B 00
B .7
772766
S 3P B 1
B .7
772772
S 3P B 2
B .7
B .7
403044
NHG2/315
A.14
700549
AP 030505
A.3
700631
AP 035502
A.4
403045
NHG2/355
A.14
700550
AP 030506
A.3
700632
AP 035503
A.4
403046
NHG2/400
A.14
700551
AP 030507
A.3
700633
AP 035504
A.4
B.3
403047
?N HG3/100
A.14
700552
AP 030508
A.3
700645
AP 037000
403048
NHG3/125
A.14
700553
AP 030509
A.3
700646
AP 037001
B.3
403049
NHG3/160
A.14
700554
AP 030510
A.3
700814
AP 700814
B.3
403050
NHG3/200
A.14
700555
AP 030511
A.3
700815
AP 700815
B.3
772789
P K-S P B 00
403051
NHG3/224
A.14
700556
AP 030512
A.3
700817
AP 700817
B.3
772790
P K-S 3P B 00/168
B .7
403052
NHG3/250
A.14
700557
AP 030513
A.3
700818
AP 700818
B.3
772791
P K-S 3P B 1/168
B .7
B .7
403053
NHG3/315
A.14
700567
AP 031500
B.3
700819
AP 700819
B.3
772792
P K-S 3P B 2/230
403054
NHG3/350
A.14
700568
AP 031501
B.3
700821
AP 700821
B.3
772793
K00
B .7
403055
NHG3/400
A.14
700569
AP 031502
B.3
700822
AP 700822
B.3
772794
K1
B .7
403056
NHG3/500
A.14
700570
AP 031503
B.3
700823
AP 700823
B.3
772795
K2
B .7
403057
NHG3/630
A.14
700571
AP 031504
B.3
700825
AP 700825
B.3
772816
4836 N-240
C .13 / C .17
403058
?N HA000/004
A.15
700573
AP 032100
B .12
700826
AP 700826
B.3
403059
NHA000/006
A.15
700574
AP 032101
B .12
700827
AP 700827
B.3
403060
NHA000/008
A.15
700575
AP 032102
B .12
700828
AP 700828
B.3
403061
NHA000/010
A.15
700576
AP 032103
B .12
700830
AP 700830
B.3
403062
NHA000/012
A.15
700577
AP 033101
A.5
700831
AP 700831
B.3
403063
NHA000/016
A.15
700578
AP 033102
A.5
772270
SP F00
B.7
403064
NHA000/020
A.15
700579
AP 033103
A.5
772605
F? H000-1A/T
C.4
403065
NHA000/025
A.15
700580
AP 033104
A.5
772606
FH000-1S/T
403066
NHA000/032
A.15
700581
AP 033105
A.5
772607
FH000-3A/T
403067
NHA000/040
A.15
700582
AP 033106
A.5
772608
FH000-3S/T
C.4
403068
NHA000/050
A.15
700583
AP 033107
A.5
772628
FH1-1A/F
C.4
403069
?N HA00/063
A.15
700584
AP 033108
A.5
772629
FH1-1S/F
C.4
403070
NHA00/080
A.15
700585
AP 033109
A.5
772630
FH1-3A/F
C.4
772817
4835 N
C .13 / C .17
772818
?4 835 N-s
C .13 / C .17
772819
5836-2x70
C .13 / C .17
772820
5836-2x240
C .13 / C .17
772850
F H00-1A/F
C .4
772851
F H00-1S /F
C .4
C.4
772852
F H00-3A/F
C .4
C.4
772853
F H00-3S /F
C .4
o n re que s t ?G A-60/100/81-1x15
C .4
Download