ARTICLE 90 -- INTRODUCTION Log # 1568 1- 1- (Articles 90, 100, 110): Reject SUBMITTER: Allen KnicKrehm, Los ~geles, CA RECOMMENDATION: Delete the word "approved" when used to mean the use of alternate method(s) or materials. SUBSTANTIATION: The NEC is incorporated in most construction contract documents by reference. Therefore, the authority having jurisdiction - the owner or the owner's representative, will not " be the third party qualified person contemplated by the Code Making Panel. Section 90-4 covers the case for governmental bodies exercising legal jurisdiction. PANEL ACTION: Reject. PANEL COMMENT: The use of the term described in the proposal substantlatlon is consistent with the definition of "approved" in Article 100 and amplified in Section 90-4. The application of this philosophy is essential to the proper application of devices and materials. VOTE ON PANEL ACTION: AFFIRMATIVE: 8 NEGATIVE: Hart. EXPLANATION OF VOTE: HAMI: I do not believe that the Panel Action as expressed in the Panel Comment is responsive to this proposal. The submitter's substantiation is not answered in the Panel Comment. The intent of this proposal could be accomplished by changing the definition of "Apprgved" to, "Acceptable to the governmental authority having jurisdiction." Log # 1008 1- 2 - (Articles 90,100, 110): Reject Secretary's Note: The Correlating Committee feels that this proposal is editorial in nature and that i t is unnecessary to repeat information already in the Code. SUBMITTER: Ivan P. Nordstrand, Consumers Power Company RECOMMENDATION: Propose each article have the Panel designation thus: Article 90 - Introduction (Panel No. 1) Article 100 - Definitions (Panel No. i) Article 110 - Requirements for Electric Installations Panel No. 1) r t i c l e 200 - Use and Identification of Grounded Conductors Panel No. 5) r t i c l e 210 - Branch Circuits Panel No. 2) tc. SUBSTANTIATION: The present format of the published Code book makes i t d i f f i c u l t and time consuming to determine the appropriate Panel responsible for the article in which a problem is developing. The addition of one line in parenthesis under the article number giving the panel designation will quickly provide the proper source. PANEL ACTION: Reject. ~ : Not within the Scope of CMP i to make such a change. Refer to NEC CorrelatinB Committee. VOTE ON PANEL ACTION: Unanimously Affirmative. ~ ~ I Log # 707 1- 3 - (90-2(a)): Reject SUBMITTER: James F. Meehan, New Haven, CT ~ATION: Amend to read as follows: (a) Covered: This Code covers all installations of electrical conductors, devices, f i t t i n g s , appliances or equipment for l i g h t , heat, power, distribution of electrical energy, transmission of sound, signal, pictures, characters of information, whether alpha or numerical, not specifically exempted in Section 90-2(b) of this Code. SUBSTANTIATION: Historically, i t was the intention of the early Code-writing authorities to include everything of an electrical nature except those items, which they specifically exempted. I t is ~y opinion, that present day Code Writers should have the same intention. By the adoption of this requirement, i t will never again be necessary to add such words as, "within and on," or Nfloating dwelling units" a~ain. Everything electrical is covered except that which is speciflcally exempted. I t would not make any difference how the electrical energy is generated:, i.e. by steam, atomic, solar, chemical, etc. In future editions of the Code when someone desires to be exempted from the provisions of the Code, i t will be necessary for the proponent to supply the documentation for such exemption, rather than. the Code Panel, for any additional wording for Section 90-2(a). PANEL ACTION: Reject. PANEL COMMENT: The Panel agrees with the intent of the proposal but feels that the present wording more clearly expresses that intent. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 1446 1- 4 - (90-2(a)): Reject SUBMITTER: Leo Witz, Continental Electric Co. ~ h a n , New Haven, CT Fred Smith, Elgin, IL Les Rinder, Chicago, IL Paul M~ore, Paducah, KY Robert P. Brooks, Chicago, IL Bill Conrardy, The Conrardy Co. Anton Ganje, North Dakota Kenny Gebert, Minneapolis, MN Bill Hogan, Chicago, IL Homer M. Lefler, Chicago, IL John W. Erickson, Boltswitch Inc. RECOMMENDATION: AmendSection 90-2(a) so as to read as follows: "(a) Covered. This Code covers all installations of electrical conductors, devices, appliances or equipment for l i g h t , heat, power, distribution of e l e c t r i c i t y , transmission of sound, signals, pictures, characters or information not specifically exempted in Section go-2(b) of this Code." (There would be no 1, 2 or 3.) SUBSTANTIATION: I t seems to us that i t was the intention of the early code writing people to include in the code everything of an electrical nature, except those things which were specifically exempted because of rules, regulations or laws propounded and enforced by some legally constituted authority. I t is further our opinion that we, today, should be likeminded. By adopting the suggested wording we will have expressed quite clearly such a position. I t will never again be necessary to l i s t all of the things that are covered, since everything except those things that are SPECIFICALLY exempted are covered. In future editions of the Code, when someone desires to be exempted from the provisions of the Code, i t will be necessary for that person to supply the documentation necessary to convince the C~; rather than the CMP having to supply documentation supporting their position. All they will have to say is, "IT IS COVERED.". PANEL ACTION: Reject. FANEL COMMENT: See Panel Action and Comment on Proposal I-3. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 797 I - 5 - (90-2(a)(4)-(New)): Reject SUBMITTER: Hy A. Bershad, The Staten Island Hospital RECOMMENDATION: "Add" a new subparagraph (4) as follows: "(4) New installations, as specified above. Existing installations shall be covered by the edition of the NATIONAL ELECTRICAL CODEin effect at the date of the I n s t a l l a t i o n . " SUBSTANTIATION: Modifications to new editions of the NEC guarantee that f a c i l i t i e s , once in compliance with former editions of NFPA70, will no longer comply with this continually revised document. A reasonable approach for any new edition is to make that edition apply "only" to installations performed after the effective date of that edition. PANEL ACTION: Reject. PANEL COMMENT: All electrical installations were not necessarily installed in accordance with the Code in effect at the date of installation. The effective date, insofar as tile NEC is concerned, is the NFPA adoption date, but there is invariably a lag in adoption dates at the local level. Rejection is based on the fact that this is an administrative matter for the authority exercising legal jurisdiction. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 1135 i - 6 - (90-2(a)(4)-(New)): Accept SUBMITTER: L. H. Sessler, Telephone Group RECOMMENDATION: Add go-2(a)(4) to the Scope under Section 90-2(a) covered. (4) Installations of optical fiber cable. SUBSTANTIATION: This statement in the scope will permit the inclusion of proposed Article 770 on Optical Fiber Cables. The Scope Section from the proposed Article 770 follows: 770-1. Scope. The provisions of this article apply to the installation of optical fiber cables along with electrical conductors. This article does not cover the construction of optical fiber cables. I t also does not cover the installation of optical fiber cables in circumstances other than those covered in this article. The substantiation for the proposed Article 770 follows: Fiber optic technology should be included in the Code to permit its orderly development and usage for communications, signaling and control circuits in lieu of metallic conductors. I t is reasonable for an optical fiber cable to be installed in electrical raceway and enclosures along with associated electrical conductors. An example of such an application is an optical fiber control circuit for electrically noisy equipment. Since optical fibers are not affected by electrical noise, one could, i f permitted by the Code, run the optical fiber cable in the same raceway with the power wiring. A further example is the use of optical fiber communications cable. One would expect to place this cable in a common raceway along with ordinary metallic ' conductor telephone cable. However, i f the Code is not changed to recognize optical fiber technology, a separate conduit system may be demanded by some local authorities. The proposed article divides optical fiber cables into three types: nonconductive, conductive and hybrid. Obviously the nonconductive types cannot be accidentally energized when placed in raceway so i t is proposed that they be permitted in raceway with conductors for electric light, power or Class i circuits operating at less than 600 volts only where the functions of optical fiber cables and electrical conductors are associated. Since the conductive optical fiber cables have a potential for inadvertant ener~izlng of metallic strength members and metallic vapor barriers, i t is proposed that these cables be permitted to share raceway with low voltage wiring systems only, and the conductive members of these cables must be grounded. Grounding (or isolation) is also proposed for entrance cables in a manner consistent with the Code requirements for ordinary communications cable. The proposed article deals with f i r e properties of optical fiber cables in a manner identical with other low voltage wiring. The scope statement, in order to be consistent with the purpose of the Code, which is the "practical safeguarding of persons and property from hazards arising from the use of e l e c t r i c i t y , " limits the coverage of the proposed Article to j o i n t installations of electrical cable and optical fiber cable. PANEL ACTION: Accept. PANEL COMMENT: The Panel Action is conditional upon the acceptance of Article 770 by CMP 16. Referred to CMP 16. VOTE ON PANELACTION: UnanimouslyAffirmative. Log # 900 1- 7 - (90-2(a)(4)-(New)): Accept SUBMITTER: Ad Hoc Subcommittee on Fiber Optics RECOI~MENDATION: Add 90-2(a)(4) to the Scope under Section 90-2(a) covered. (4) Installations of optical fiber cable. SUBSTANTIATION: This statement in the scope will permit the inclusion of proposed ArticIe 770 contains a more detailed scope statement. PANEL ACTION: Accept. PANEL COMt~NT: See Panel Action and Comment on Proposal I-6. VOTE ON PANELACTION: UnanimouslyAffirmative. Log # 512 1- 8 - (90-2(b)(I), Exception-(New)): Reject SUBMITTER: J . K . Daugherty, Flint, MI RECOI~MENDATION: Revise Section 90-2(b)(1) to: (1) Installation in ships, watercraft, railway rolling stock, aircraft, or automotive vehicles. Exception: Floating dwelling units, mobile homes, and recreational vehicles. SUBSTANTIATION: Floating dwelling units, n~bile homes, and recreational vehicles are exceptions to the basic statement and as such should comply with Section 3-4.3 of the Manual of Style for NFPA Technical Committee Documents 1978. PANEL ACTION: Reject. PANEL COI~¢4ENT: The Panel does not agree with the proposer's substantiation and feeIs that no additional clarification would be achieved by the proposal. VOTE ON PANELACTION: Unanimously Affirmative. Log # 904 1- 9 - (90-2(b)(2)): Reject SUBMITTER: Ad Hoc Committee on Mining Related Subjects ]TE'i~R~IQE'-N-I]ATION: Revise Section 90-2(b)(2) to read: (2) Installations underground in mines and equipment and installations located above ground that are used exclusively in conjunction with the mining operation, that are under the exclusive control of the mine, and where the conditions of maintenance and supervision assure that only qualified persons will operate and service the installation. (FPN) I t is the intent that this Code cover installations in buildings used by the mine for purposes other than the mining operation, such as office buildings, warehouses, garages, machine shops, and recreational buildings. SUBSTANTIATION: The existing Code wording excludes only installations underground in mines and not the equipment located above ground that is essential for the mining operation, such as the equipment installed at the top of a hoist and the handling or processing equipment and installations. A mining operation regardless of its location, underground or above ground, has special features and demands. These inject unique electrical system requirements that are not covered in the Code. Mine Safety and Health Administration (MSHA) of the Department of Labor has specific regulatory and inspection responsibilities for all mining operations. MSHAregulations would certainly satisfy Section 90-1(a) of the Code. Furthermore, to bring the Code into line with the needs of the mining industry and its federal and state regulatory agencies would require expanding the Code with a separate section to f i t within those needs, including revision of the present Code line-by-line and article-by-article to provide the necessary exclusions. A separate document, apart from the Code, appears a more logical way to satisfy the mining-industry requlrements. The Industry Applications society in the IEEE has already formed working groups of mine-electrical experts; these individuals are pursuing the IEEE Standards Projects 791, "Recommended Electrical Practices for Underground Gassy Mines," and 794, "Recommended Electrical Practices for Underground Non-Gassy Mines." The resulting standards will more than adequately cover any missing safety area connected to underground-mining operations that might be encountered by the adoption of the above recommendation or that is not covered under present federal regulations. Nevertheless, to eliminate conflicting reguIations between the Code and that of MSHA, the Code should be revised to exclude all equipment and installations used exclusively in a mining operation regardless of its location, underground or above ground. PANEL ACTION: Reject. PANEL COMMENT: Abovegroundmining operations should continue to be covered by the NEC. VOTE ON PANEL ACTION: AFFIRMATIVE: 8 NOT VOTING: PaIko. EXPLANATION OF NOT VOTING: PALKO: I am abstaining from voting because I do not feel that the Panel gave due consideration to the findings of the Ad Hoc Subcommittee that worked over a period of 10 months to develop the proposal. I feel that this proposal--developed by consensus of a well-balanced Ad Hoc Subcommittee comprising 27 members--should have been deliberated in nmre depth. Log # 657 1- 10 - (90-2(b)(5)): Reject SUBMITTER: George C. Gingher, Association of Iron and Steel ~'nglneers RECOMMENDATION: Changeto read: "Installations for the purpose of communication or metering; or for the generation, control, transformation, transmission, and distribution of an electric supply located in buildings or outdoors on property owned or leased for such purposes or on public highways, streets, roads, etc. or outdoors by established rights on private property under the exclusive control of electric u t i I i t i e s , or similar systems under the control of qualified persons such as those associated with an industrial complex.N SUBSTANTIATION: Many industrial complexes have electric supply systems installed under the provisions of the National Electric Safety Code, ANSI-C2-1981, and are covered by the scope of that standard, Sec. 1-011. The scope of the NATIONAL ELECTRICAL CODE does' not recognize ANSI-C2 and this, the NEC language can be interpreted to include such installations despite the fact that the Code does not, and is not intended, to cover such installations. This fact of an overlap between both Standards became apparent in testimony at the Public Hearings in Washington, DC in 1980 when OSHA promulgated the revised electrical standard 1910 Subpart S. OSHA has confirmed in writing that the steel industry does have electric supply systems that are similar to those of electric utilities. This proposal is intended to eIiminate the overlap between standards by a marriage of the existing language from the scope of each document. No change in actual coverage of these standards is anticipated, but the change will clearly delineate the application of the standards to al] concerned. PANEL ACTION: Reject. PANEL COMMENT: Such industrial systems should be covered by the NEC requirements. The Panel dues recognize that there is a problem and would suggest that the NEC Correlating Committee pursue the establishment of a joint committee with the ANSI C.2 Committee to further investigate this area. VOTE ON PANELACTION: AFFIRMATIVE: 8 NEGATIVE: Palko. EXPLANATION OF VOTE: PALKO: Utility-type systems should be covered by the National Electrical Safety Code (ANSI C2)--and not the NEC--whether they are owned by a public u t i l i t y company or not. Exempting utility-owned " u t i l i t y - t y p e " systems from the NEC is justified by the fact that such systems are "different." Different is different--and this fact does not change as a function of ownership. Arguments have been presented to the effect that adoption of this proposal would open the door to everyone claiming the exemption (even 120/240 volt u t i l i t y distribution systems are exempt from the NEC). These objections can be disposed of by prescribing minimum cohditions that must be met to qualify for the exemption. This proposaI should be adopted in principle by defining those types of systems that are exempt. I suggest as possibilities for the Pane] to consider power distrubition systems operating at more than 15 kv (nominal), and generating installations of 5 mva capacity or larger. Such limits would keep typical industrial and commercial distribution systems--and standby and emergency power generators--within the NEC, while exempting u t i l i t y - t y p e distribution systems and large, base-loaded generators that are operated in the same manner as u t i l i t y company generating equipment. Log # 791 I - 11 - (90-2(b)(5) FPN): Reject SUBMITTER: Dan Leaf, Westlake Village, CA ~ATION: Insert the words "service drop conductors and service lateral conductors" between the words "wiring or," and delete the words (on the load side of the service point), in the f i r s t sentence. SUBSTANTIATION: "Service point" is not defined in the Code but could be defined as the point of connection of service entrance conductors and service drop or service lateral conductors, which are generally installed and/or owned by the serving u t i l i t y . By definition of "premises wiring (system)" in Article 100, this FPN appears to exclude Code requirements for service drops or service laterals. This appears to conflict with Article 230 which contains specific requirements for these portions of wiring systems. PANEL ACTION: Reject. PANEL COMMENT: The installation of the aforementioned conductors is covered by the NEC. Also the definition of "service point" is defined in Section 230-200. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 903 I - 12 - (90-2(b)(6)-(New)): Reject SUBMITTER: Ad Hoc Subcommittee on Mining Related Subjects RECOMMENDATION: Add new Section 90-2(b)(6) to read: (6) Equipment and installations under the exclusive control of a mining company which are used exclusively for the purpose of surface mining, strip mining, or opeD ~ i t mining, and where the conditions of maintenance and supervlslon assure that only qualified persons will operate and service the equipment and installation. FPN I t is the intent that this Code cover installations in buildings used by the mine for purposes other than the mining operation, such as office buildings, warehouses, garages, machine shops, dining f a c i l i t i e s , v i s i t o r centers, and recreational buildings. SUBSTANTIATION: The existing Code, by inference, applies to surface-mining operations, commonly referred to as strip mining or open-pit mining. These mining operations have special features and demands, such as power-system mobility and p o r t a b i l i t y , extremely d~namic loading, the remote location of many loads, and so forth. The differences from other general industrles inject unique electrical-system requirements that are not covered in the Code. Mine Safety and Health Administration (MSHA) of the Department of Labor has specific regulatory and inspection responsibility for all mining operations. MSHAregulations would certainly satisfy Section 90-1(a) of the Code. Furthermore, to bring the Code into line with the needs of the mining industry and its federal and state regulatory agencies would require expanding the Code with a separate section to f i t within those needs, including revision of the present Code line-by-line and article-by-article to provide the necessary exclusions. A separate document, apart from the Code, appears a more logical way to satisfy the mining-industry requirements. The Industry Applications Society of the IEEE has already formed working groups of mine-electrical experts; one group is pursuing the IEEE Standards Project 795, "Recommended Electrical Practices for Surface Mines." The resulting standard will more than adequately cover any missing safety area connected to underground-mining operations that might be encountered by the adoption of the above recommendation or that is not covered under present federal regulations. Nevertheless, to eliminate the potential of conflicting regulations between the Code and that of MSHA, the Code should be revised to exclude all equipment and installations used exclusively in a surface-mining operation. PANEL ACTION: Reject. PANEL COMMENT: See Panel Action and Comment on Proposal i-9. VOTE ON PANEL ACTION: AFFIRMATIVE: 8 NOT VOTING: Palko. EXPLANATION OF NOT VOTING: PALKO: I abstain for the same reason given for Proposal 1-9. Log # 901 I - 13 - (90-2(b)(6)-(New)): Reject SUBMII-FER: Ad Hoc Subcommittee on Fiber Optics RECOMMENDATION: Add 90-2(b)(6) to the Scope Section 90-2(b) not covered. (6) I n s t a l l a t i o n of noncurrent-carrying f i b e r optic communications, signaling and control systems. However, t h i s Code does not preclude the i n s t a l l a t i o n of optical f i b e r cable in or out of raceway with e l e c t r i c a l conductors provided requirements covering grounding, bonding and f i r e resistance are met. SUBSTANTIATION: Fiber o p t i c technology should be recognized by the Code to permit i t s o r d e r l y development and usage f o r communications, signaling and control c i r c u i t s in lieu of m e t a l l i c conductors. However, the scope of the Code which states 'The purpose of t h i s Code is the practical safeguarding of persons and property from hazards arising from the use of e l e c t r i c i t y , ' can be interpreted to exclude optical f i b e r s . The issues that the Code should address are the hazards associated with the inadvertent energizing of metallic members of f i b e r optic cable and the f i r e hazards associated with the combustible components of such cable. PANEL ACTION: Reject. PANEL COMMENT: See Panel Action and Comment to Proposal I-6. two sentences of the proposal are conflicting. VOTE ON PANEL ACTION: UnanimouslyAffirmative. The Log # 1128 I - 14 - (90-2(b)(6)-(New)): Reject SUBMI1-FER: D. J. Christofersen, United Power Association RECOMM-M~-N-DATION: Add No. (6): Installations of electrical load management equipment under the exclusive control of electric u t i l i t i e s installed in sealed cabinets located outside or immediately inside the building near the service entrance. SUBSTANTIATION: Allows electric u t i l i t i e s to secure an installation of electrical load management equipment at a building or household for the express purpose to offer an interruptible load rate. The seal on the equipment prevents unauthorized operation or tampering. PANEL ACTION: Reject. PANEL COh%MENT: Already covered by Section 90-2(b)(5). These types of installations are under the exclusive control of utilities. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 902 1- 15 - (90-2(b)(7)-(New)): Reject SUBMII-FER: Ad Hoc Subcommittee on Minin 9 Related Subjects ]TE'?~-OI;~'I{~OATION: Add new Section 90-2(b)(7) to read: (7) Installations in mining-related tipples, mills, concentration beneficiation, and preparation plants that are used exclusively in conjunction with a mining operation, that are under the exclusive control of the mine, and where the conditions of maintenance and supervision assure that only qualified persons will operate and service the installation. FPN I t is the intent that this Code cover installations in buildings used by the mine for purposes other than the mining operation and its mining-related plants, such as office buildings, warehouses, garages, machine shops, and recreational buildings. SUBSTANTIATION: The existing Code, by inference, applies to mining-related preparation plants and other similar f a c i l i t i e s , such as concentration plants, beneficiation plants, mills, and tipples. These operations can often contain special features and demands that inject unique electrical system requirements that are not covered in the Code. Mine Safety and Health Administration (MSHA) of the Department of Labor has specific regulatory and inspection responsibility for all mining operations. MSHA regulations would certainly satisfy Section 90-i(a) of the Code. Furthermore, to bring the Code into line with the needs of the mining industry and its federal and state regulatory agencies would require expanding the present separate section of the Code to f i t within those needs, including revision'of the balance of the Code line-by-line and article-by-article to provide the necessary exclusions. A separate document, apart from the Code, appears a more logical way to satisfy the mining-industry requirements. The Industry Applications Society in the IEEE has already formed working groups of mine-electrical experts; one group is now pursuing the IEEE Standards Project 793, "Recommended Electrical Practices for Mining-Related Preparation Plants." The resulting standard will more than adequately cover any missing safety area connected to underground-mining operations that might be encountered by the adoption of the above recommendation or that is not covered under present federal regulations. Nevertheless, to eliminate conflicting regulations between the Code and that of MSHA, the Code should be revised to exclude all equipment and installations used exclusively in a mining operation or its mining-related plants. PANEL ACTION: Reject. PANEL COI~MENT: Abovegroundmining operations should continue to be covered by the NEC. See Panel Action and Comment on Proposal 1-9. VOTE ON PANEL ACTION: AFFIRMATIVE: 8 NOT VOTING: Palko. EXPLANATION OF NOT VOTING: PALKO: I abstain for the same reason given for Proposal I-9. Log m 619 1- 16 - (90-3): Reject SUBMI~ER: Earl W. Roberts, General Electric Co. RECOMMENDATION: Revise last sentence and add new paragraph as follows: Chapter 9 consists of tables. Examples, which are not o f f i c i a l l y part of this Code but which can be useful in applying the Code, are included in an Appendix. SUBSTANTIATION: Present wording states that examples are part of Chapter 9 and Chapter 9 is part of the Code. Decision has been made by NFPA that the Examples are not part of Panel responsibility. Therefore, i t should be clearly spelled out that the Examples are not part of the Code. PANEL ACTION: Reject. PANEL COMMENT: The Panel Action is based on the present instructions from the NEC Correlating Committee which make the Examples part of the Code and the responsibility of the Panel Chairman and the Secretary of the National Electrical Code Committee. The Panel points out that the second sentence of the substantiation is incorrect. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 1800 I - 17 - (90-4): Accept in Principle SUBMITTER: F. K. Kitzantides, NEMA I~E~O-~g~L'~-~ATION: Add new third paragraph as follows: Some requirements in this Code specify new products, constructions, or materials which may not yet be available at the time the Code is adopted. In such event, the authority having jurisdiction may permit the use of the products, constructions, or materials which comply with the most recent previous edition of this Code adopted by the jurisdiction. SUBSTANTIATION: There is a need to c l a r i f y what is acceptable during the interim period between the acceptance of a new edition of the Code and the a v a i l a b i l i t y of new products, constructions, or materials. This was highlighted in the 1981 Code by the new cable bending space requirements. PANEL ACTION: Accept in Principle. Replace the words "some requirements in this Code specify" with the words "This Code may require." PANEL COMMENT: Editorial clarification. VOTE ON PANEL ACTION: AFFIRMATIVE: 8 NECV~TIVE: Hart. EXPLANATION OF VOTE: HART: I am opposed to the acceptance of this proposal because there is no real need. A new Code is adopted by NFPA at its Annual Meeting in May and I am not aware of any jurisdiction which adopts a new Code prior to January 1st of the following year. This is approximately eight months and should be ample time for the manufacturers of new euipment or equipment with new requirements to have these products available. In most cases the manufacturers are aware that such changes will be adopted as early as the January of the preceding year, even before the Code is o f f i c i a l l y adopted by NFPA. This proposal, i f adopted, would be used to delay perhaps forever a change adopted by the National Electrical Code Committee, depending upon the influence of the manufacturers involved and the weakness of local enforcement authorities. I can recall that thermal protection of ballasts was delayed for more than ten years until the manufacturers could "get tooled-up" to produce these devices. Also, i t is not f a i r to the public to permit manufacturers to have additional time available to deplete existing stock. I f the National Electrical Code Committee believes that a new product or a change in design is necessary then the public should not be forced to accept the risk of inferior equipment simply for the convenience of the manufacturers. Another example is the delay in the effective date of 4-6 milliampere t r i p levels for ground-fault circuit-interrupters. The public was forced to accept these devices with t r i p levels as low as 2.2 milliamperes and they are s t i l l paying for i t many years later. I f manufacturers are willing to accept the advantages of nationwide acceptance of their products which results from acceptance by the NATIONAL ELECTRICAL CODE, then they should be willing to also accept the need for change in equipment design which might be caused by the NATIONAL ELECTRICAL CODE. The manufacturersparticipate in this process and their risks should not have to be born by the public, which we all serve. Log # 2016 I - 18 - (90-4(b)-(New)): Reject SUBMITTER: Idaho Chapter IAEI ITE~C'~I~]~E-NrDATION: The authority having jurisdiction may waive the specific requirements of a new Code change that involves electrical equipment, material or wiring methods that are not immediately available at the time this edition of the Code was adopted only where Section go-4(b) is specifically referenced in the new or revised sections involved. The authority having jurisdiction'shall then require the installation in question to comply with, i f any, the most recently adopted previous edition of this Code or in its absence, other equivalent appropriate requirements u n t i l , such time as, the necessary electrical equipment or material becomes available as determined by the authority having jurisdiction. SUBSTANTIATION: In many Code enforcing localities, due to their laws covering the adoption of the NEC, no grace periods or waiver of the Code requirements, as written, are permitted. The Code in some instance creates a problem due the time required to retool, manufacture, and make available to the industry the new electrical equipment, materials and wiring methods necessary to comply with Code at the time of its adoption. The addition of Section gO-4(b) would permit the supplier, contractor, and the inspector to work in harmony during the extension of time granted by the authority having jurisdiction. PANEL ACTION: Reject. PANEL COMMENT: The Panel feels that inserting the reference to Section 90-4(b) in the body of the Code is unnecessary and cumbersome. There may also be cases where the Panel would not recognize the need for the reference. See Panel Action and Comment on Proposal 1-17. VOTE ON PANELACTION: Unanimously Affirmative. Log # 705 1- 19 - (90-5): Accept in Principle SUBMITTER: James F. Meehan, New Haven, CT RECOMMENDATION: Section 90-5 be amended by adding thereto the following: "These procedures may be found in Section 16 of the NFPA "Regulations Governing Committee Projects." Note: I f future changes in the Regulation Governing Committee Projects are changes then i t would be an editorial change for indicating such change. SUBSTANTIATION: The addition of this sentence will provide information for many people who at the present time write to Code-Making Panel chairmen, secretaries in the NFPAseeking Official Interpretations, or "Formal Interpretations." The inclusion of this information may forestall some of those requests. PANEL ACTION: Accept in Principle. Change the text of Section 90-5 to read as follows: "To promote uniformity of interpretation and application of the provisions of this Code, Formal Interpretation procedures have been established." FPN: These procedures may be found in the "NFPA Regulations Governing Committee Projects." PANEL COMMENT: The proposal has been revised to be technically correct. CMP 1 requests that the NEC Correlating Committee consider the advisability of including the rule in the rear of the Code book. VOTE ON PANELACTION: UnanimouslyAffirmative. Log # 1447 1- 20 - (90-5): Accept in Principle SUBMII'[ER: Leo Witz, Continental Electric Co. ~T~ Meehan, New Haven, CT Fred Smith, Elgin, IL Les Rinder, Chicago, IL Paul Moore, Paducah, KY Robert P. Brooks, Chicago, IL Bill Conrardy, The Conrardy Co. Anton Ganje, North Dakota Kenny Gebert, Minneapolis, MN Bill Hogan, Chicago, IL Homer M. Lefler, Chicago, IL John W. Erickson, Boltswitch Inc. RECOMMENDATION: Amend Section 90-5 by adding thereto the following: These procedures may be found in Section 16 of the "NFPA Regulations Governing Committee Projects. SUBSTANTIATION: The addition of this sentence will provide information for the many people who presently write to the C~P Chairmen seeking "Official Interpretations". The inclusion of this information may forestall many of these requests and head the people in the right direction. PANEL ACTION: Accept in Principle. PANEL COMMENT: See Panel Action and Comment on Proposal 1-19. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 85 i - 21 - (90-7(a)): Reject SUBMII-TER: Victor S. Whitoomb, Brooks, ME ~ATION: Add a new penultimate sentence as follows: Space should be provided f o r the future i n s t a l l a t i o n of manual or automatic transfer switch equipment. SUBSTANTIATION: The informative language of A r t i c l e 90 should caution that designs and specifications should include space f o r transfer equipment. All too many times complete i n s t a l l a t i o n s have to be altered immensely to provide t h i s space. Future additions of transfer equipment have proven costly f o r t h i s reason. PANEL ACTION: Reject. PANEL COMMENT: The Panel Action is based on Section gO-l(c). This requirement would allocate space wherein the vast m a j o r i t y of e l e c t r i c a l i n s t a l l a t i o n s would never u t i l i z e such space. Proposal is too sweeping in nature. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 706 i - 22 - (90-8): Reject SUBMII-TER: James F. Meehan, New Haven, CT RECOMMENDATION: Amend A r t i c l e 90 of the NATIONAL ELECTRICAL CODE 6y deleting therefrom Section 90-8. SUBSTANTIATION: This document i~ intended to be the NATIONAL ELECTRICAL CODE: The people who use the Code on a day to day basis, -- the e l e c t r i c a l mechanics, the e l e c t r i c a l contractors, the e l e c t r i c a l inspectors, the e l e c t r i c a l d i s t r i b u t o r s , and most e l e c t r i c a l manufacturers have no e a r t h l y use f o r these additional figures that have been added in only parts of the Code. In my READILY ACCESSIBLE: Admitting close approach; not guarded by locked doors, elevator, or other effective means (as applied to equipment). Capable of being reached quickly for operation, renewal, or inspections, without requiring those to whom ready access is requisite to climb over or remove obstacles or to resort to portable ladders, chairs, etc. SUBSTANTIATION: The term accessible is effectively the same as readily accessible. A switch located 7 feet from the ground is not readily accessible nor is i t accessible. Change all sections that require i t to be accessible to readily accessible. PANEL ACTION: Reject. PANEL COMMENT: The submitter's substantiation is. in error. The differences in the two definitions can be quite substantial and this proposal would change the intent of the specific Code rules that were written based on the existing definitions. VOTE ON PANEL ACTION: Unanimously Affirmative. opinion the United States is not on the verge of changing to the modernized metric system, "International System of Units." The addition of these values do nothi•ng to assist the daily users of the Code, but do tend to make the book longer and more costly. Does not tend to c l a r i f y rules. PANEL ACTION: Reject. PANEL COMMENT: Proposal is inconsistent with the directions of the NFPA Standards Council. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 1448 I - 23 - (90-8): Reject SUBMITTER: Leo Witz, Continental Electric Co. ~ g a n , Chicago, IL Jim Meehan, New Haven, CT Anton Ganje, North Dakota , Kenny Gebert, Minneapolis, MN Robert P. Brooks, Chicago, IL Paul Moore, Paducah, KY Les Rinder, Chicago, IL Leo Nagel, North Dakota Homer M. Lefler, Chicago, IL John W. Erickson, Boltswitch Inc. RECOMMENDATION: AmendArticle go of the NEC by deleting therefrom "Section 90-8." SUBSTANTIATION: This document is intended to be the NATIONAL Electrical Code; not the INTERNATIONAL Electrical Code. The people who use this Code on a day to day basis; mechanics, contractors, inspectors, engineers, distributors, unions, trade schools and many manufacturers have no earthly use for these additional figures or words. The United States is not on the verge Of changing to the metric system. The metric values in the present code serve no function for the people in the USA. Their presence serves only to make the code longer, wordier, more obtuse and costlier with no benefit for the users. PANEL ACTION: Reject. PANEL COMMENT: See Panel Action and Comment on Proposal 1-22. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 720 1- 26 - (Article lO0-Ampacity): Accept Secretary's Note: I t was the action of the Correlating Committee that this proposal be referred to CME's 2, 4 and 6 for comment. SUBMII-TER: Allen KnicKrehm, Los Angeles, CA ~ATION: Revise definition of the word "An~)acity" as shown below. Ampacity. The current in amperes a conductor can carry continuously under the conditions of use without exceeding its temperature rating. SUBSTANTIATION: In the present definition, use of the word "capacity" infers that a conductor has a precise numerical limit of current i t can safely carry. This is an incomplete statement. The variables which must be recognized in arriving at the ampere value which must be observed to limit temperature, are not alluded to in the present definition. The proposed definition recognizes the work of Nehr-McGrath, Shurig & Frick and others. This proposal is the combined opinion of a CMP 6 Task Force studying the matter of ampacity. PANEL ACTION: Accept. PANEL COMMENT: Referred to CMP's 2, 4, and 6 for comment. VOTE ON PANELACTION: Unanimously Affirmative. ARTICLE 100 -- DEFINITIONS Log # 216 I - 27 - (Article lO0-Allowable Load Current-(New)): Reject SUBMITTER: John C. Miller, Abolite Lighting, Inc. RECOMMENDATION: Create a new definition for "Allowable Load Current" as follows: Allowable Load Current: The amount of load current permitted to be imposed on a conductor under specified conditions expressed in amperes. SUBSTANTIATION: Since CMP 6, in the f i r s t paragraph of Note 8 to Tables 310-16 and 310-18, has indicated that there is a difference in the meaning and application of the terms "Ampacity" and "Allowable Load Current" and since "Ampacity" is already defined i t seems that "Allowable Load Current" should also be defined. PANEL ACTION: Reject. PANEL COMMENT: CMP i feels the proposed wording describes ;'ampacity." See Panel Action and Comment on Proposal 1-26. Referred to CMP's 2, 4 and 6 for comment. VOTE ON PANELACTION: Unanimously Affirmative. I - 23A - (Article 100) Secretary's Note: The Correlating Committee directs that each Panel review the articles under its responsibility for conflicts which may arise because of changes in the definitions and revise those areas that require consistency with the actions of CMP I . Log # 1450 I - 24 - (Article 100): Reject SUBMITTER: B i l l Hogan, Chicago, IL ~ z , Continental Electric Co. Fred Smith, Elgin, IL Jim Meehan, New Haven, CT Kenny Gebert, Minneapolis, MN Bill Conrardy, The Conrardy Co. Robert P. Brooks, Chicago, IL Paul Moore, Paducah, KY Les Rinder, Chicago, IL Leo Nagel, North Dakota Anton GanJe, North Dakota Homer M. Lefler, Chicago, IL John W. Erickson, Boltswitch Inc. RECOMMENDATION: AmendArticle 100 by deleting the words, "under specified test conditions," from each definition in which they appear; and further amend Article 100 by inserting in lieu thereof the words, "under standard test conditions." SUBSTANTIATION: Rather than repeat the same substantiation for each time these words appear in the definitions we refer you to our proposal for the change in the definition for Interrupting Rating and use that as our substantiation for this proposal. PANEL ACTION: Reject. PANEL COMMENT: The proposal does not meet Section 10-10 of "NFPA Regulations Governing Committee Projects." Proposal is nonspecific in regards to which definitions the proposal references. Standard test conditions could vary with various testing agencies. VOTE ON PANEL ACTION: Unanimously Affirmative. COMMENTON VOTE: SEELBACH: I have voted in support of the motion to reject as the proposal does not conform to Section 10-10. I do not agree with the statement in the Panel Comment that - "Standard test conditions could vary with various testing agencies." They should not. Log # 626 1- 28 - (Article lO0-Ampacity): Reject SUBMITTER: R. P. O'Riley, Dallas Joint Electrical Apprenticeship and Training Committee RECOMMENDATION: Add new definition. Ampacity-As Applied to Electrical Conductors: .The ampacity of an electrical conductor is the listed ampacity iven in the Code ampacity Tables 310-16 through 310-19. UBSTANTIATION: There is considerable confusion concerning the use of the terms "ampacity" and "load current" as applied to electrical conductors. Therefore, there is need for a definition for clarification of these two terms. PANEL ACTION: Reject. PANEL COMMENT: A definition cannot include the term being defined. See Panel Action and Comment on Proposal 1-26. Referred to CMP's 2, 4, and 6 for comment. VOTE ON PANEL ACTION: UnanimouslyAffirmative. ~ q Log # 1657 1- 29 - (Article lO0-Ampacity): Reject SUBMII-FER: Charles "Mike" Holt, Concepts in E l e c t r i c i t y , Inc. RECOMMENDATION: Revise definition of Ampacity. "The a b i l i t y of a conductor to carry current where no load limiting factors apply." SUBSTANTIATION: The Code throughout uses the term ampacity. However, what does ampacity mean. Table 310-16 through 310-19 are conductor ampacities but the load on conductors are limited by continuous loads, Note 8, and ambient temperature factors. PANEL ACTION: Reject. PANEL COMMENT: The Ioad-limlting factors do apply to the ampacity of conductors. See Panel Action and Comment on Proposal 1-26. Referred to CMP's 2, 4 and 6 for comment. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 1703 I - 25 - (Article lO0-Accessible): Reject SUBMITTER: Charles "Mike" Holt, Concepts in Electricity, Inc. RECOI~MENDATION: Delete definition of Accessible and incorporate i t with Readily Accessible. 5 READILY ACCESSIBLE: Admitting close approach; not guarded by locked doors, elevator, or other effective means (as applied to equipment). Capable of being reached quickly for operation, renewal, or inspections, without requiring those to whom ready access is requisite to climb over or remove obstacles or to resort to portable ladders, chairs, etc. SUBSTANTIATION: The term accessible is effectively the same as readily accessible. A switch located 7 feet from the ground is not readily accessible nor is i t accessible. Change all sections that require i t to be accessible to readily accessible. PANEL ACTION: Reject. PANEL COMMENT: The submitter's substantiation is. in error. The differences in the two definitions can be quite substantial and this proposal would change the intent of the specific Code rules that were written based on the existing definitions. VOTE ON PANEL ACTION: Unanimously Affirmative. opinion the United States is not on the verge of changing to the modernized metric system, "International System of Units." The addition of these values do nothi•ng to assist the daily users of the Code, but do tend to make the book longer and more costly. Does not tend to c l a r i f y rules. PANEL ACTION: Reject. PANEL COMMENT: Proposal is inconsistent with the directions of the NFPA Standards Council. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 1448 I - 23 - (90-8): Reject SUBMITTER: Leo Witz, Continental Electric Co. ~ g a n , Chicago, IL Jim Meehan, New Haven, CT Anton Ganje, North Dakota , Kenny Gebert, Minneapolis, MN Robert P. Brooks, Chicago, IL Paul Moore, Paducah, KY Les Rinder, Chicago, IL Leo Nagel, North Dakota Homer M. Lefler, Chicago, IL John W. Erickson, Boltswitch Inc. RECOMMENDATION: AmendArticle go of the NEC by deleting therefrom "Section 90-8." SUBSTANTIATION: This document is intended to be the NATIONAL Electrical Code; not the INTERNATIONAL Electrical Code. The people who use this Code on a day to day basis; mechanics, contractors, inspectors, engineers, distributors, unions, trade schools and many manufacturers have no earthly use for these additional figures or words. The United States is not on the verge Of changing to the metric system. The metric values in the present code serve no function for the people in the USA. Their presence serves only to make the code longer, wordier, more obtuse and costlier with no benefit for the users. PANEL ACTION: Reject. PANEL COMMENT: See Panel Action and Comment on Proposal 1-22. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 720 1- 26 - (Article lO0-Ampacity): Accept Secretary's Note: I t was the action of the Correlating Committee that this proposal be referred to CME's 2, 4 and 6 for comment. SUBMII-TER: Allen KnicKrehm, Los Angeles, CA ~ATION: Revise definition of the word "An~)acity" as shown below. Ampacity. The current in amperes a conductor can carry continuously under the conditions of use without exceeding its temperature rating. SUBSTANTIATION: In the present definition, use of the word "capacity" infers that a conductor has a precise numerical limit of current i t can safely carry. This is an incomplete statement. The variables which must be recognized in arriving at the ampere value which must be observed to limit temperature, are not alluded to in the present definition. The proposed definition recognizes the work of Nehr-McGrath, Shurig & Frick and others. This proposal is the combined opinion of a CMP 6 Task Force studying the matter of ampacity. PANEL ACTION: Accept. PANEL COMMENT: Referred to CMP's 2, 4, and 6 for comment. VOTE ON PANELACTION: Unanimously Affirmative. ARTICLE 100 -- DEFINITIONS Log # 216 I - 27 - (Article lO0-Allowable Load Current-(New)): Reject SUBMITTER: John C. Miller, Abolite Lighting, Inc. RECOMMENDATION: Create a new definition for "Allowable Load Current" as follows: Allowable Load Current: The amount of load current permitted to be imposed on a conductor under specified conditions expressed in amperes. SUBSTANTIATION: Since CMP 6, in the f i r s t paragraph of Note 8 to Tables 310-16 and 310-18, has indicated that there is a difference in the meaning and application of the terms "Ampacity" and "Allowable Load Current" and since "Ampacity" is already defined i t seems that "Allowable Load Current" should also be defined. PANEL ACTION: Reject. PANEL COMMENT: CMP i feels the proposed wording describes ;'ampacity." See Panel Action and Comment on Proposal 1-26. Referred to CMP's 2, 4 and 6 for comment. VOTE ON PANELACTION: Unanimously Affirmative. I - 23A - (Article 100) Secretary's Note: The Correlating Committee directs that each Panel review the articles under its responsibility for conflicts which may arise because of changes in the definitions and revise those areas that require consistency with the actions of CMP I . Log # 1450 I - 24 - (Article 100): Reject SUBMITTER: B i l l Hogan, Chicago, IL ~ z , Continental Electric Co. Fred Smith, Elgin, IL Jim Meehan, New Haven, CT Kenny Gebert, Minneapolis, MN Bill Conrardy, The Conrardy Co. Robert P. Brooks, Chicago, IL Paul Moore, Paducah, KY Les Rinder, Chicago, IL Leo Nagel, North Dakota Anton GanJe, North Dakota Homer M. Lefler, Chicago, IL John W. Erickson, Boltswitch Inc. RECOMMENDATION: AmendArticle 100 by deleting the words, "under specified test conditions," from each definition in which they appear; and further amend Article 100 by inserting in lieu thereof the words, "under standard test conditions." SUBSTANTIATION: Rather than repeat the same substantiation for each time these words appear in the definitions we refer you to our proposal for the change in the definition for Interrupting Rating and use that as our substantiation for this proposal. PANEL ACTION: Reject. PANEL COMMENT: The proposal does not meet Section 10-10 of "NFPA Regulations Governing Committee Projects." Proposal is nonspecific in regards to which definitions the proposal references. Standard test conditions could vary with various testing agencies. VOTE ON PANEL ACTION: Unanimously Affirmative. COMMENTON VOTE: SEELBACH: I have voted in support of the motion to reject as the proposal does not conform to Section 10-10. I do not agree with the statement in the Panel Comment that - "Standard test conditions could vary with various testing agencies." They should not. Log # 626 1- 28 - (Article lO0-Ampacity): Reject SUBMITTER: R. P. O'Riley, Dallas Joint Electrical Apprenticeship and Training Committee RECOMMENDATION: Add new definition. Ampacity-As Applied to Electrical Conductors: .The ampacity of an electrical conductor is the listed ampacity iven in the Code ampacity Tables 310-16 through 310-19. UBSTANTIATION: There is considerable confusion concerning the use of the terms "ampacity" and "load current" as applied to electrical conductors. Therefore, there is need for a definition for clarification of these two terms. PANEL ACTION: Reject. PANEL COMMENT: A definition cannot include the term being defined. See Panel Action and Comment on Proposal 1-26. Referred to CMP's 2, 4, and 6 for comment. VOTE ON PANEL ACTION: UnanimouslyAffirmative. ~ q Log # 1657 1- 29 - (Article lO0-Ampacity): Reject SUBMII-FER: Charles "Mike" Holt, Concepts in E l e c t r i c i t y , Inc. RECOMMENDATION: Revise definition of Ampacity. "The a b i l i t y of a conductor to carry current where no load limiting factors apply." SUBSTANTIATION: The Code throughout uses the term ampacity. However, what does ampacity mean. Table 310-16 through 310-19 are conductor ampacities but the load on conductors are limited by continuous loads, Note 8, and ambient temperature factors. PANEL ACTION: Reject. PANEL COMMENT: The Ioad-limlting factors do apply to the ampacity of conductors. See Panel Action and Comment on Proposal 1-26. Referred to CMP's 2, 4 and 6 for comment. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 1703 I - 25 - (Article lO0-Accessible): Reject SUBMITTER: Charles "Mike" Holt, Concepts in Electricity, Inc. RECOI~MENDATION: Delete definition of Accessible and incorporate i t with Readily Accessible. 5 This proposal introduces a mandatory requirement which is an improper use of the definitions. VOTE ON PANELACTION: Unanimously Affirmative. Log # 416 1- 30 - (Article lO0-Appliance): Reject SUBMII-TER: Southwestern Section IAEI ~ATION: Add to appliance definition the following: "and requires no more than one approved exterior cord to supply po~r, with no other exposed cords or unprotected wiring to complete its function, u SUBSTANTIATION: The deletion of appliances fixed, appliances portable and appliances stationary, in the 1981NEC, l e f t a hole in the Code which has initiated considerable controversy. Someof the more enterprising marketeers, especially in the ranks of solar 'and wind power promoters, are attempting to assemble and cord-connect their equipment in the field and then call the entire assembly an appliance. The TSC expected that other Code Committees involved in appliances would refine their sections to include specific definitions. With the exception of Article 550 we cannot find that scrupulous attention to this detail that the Committee hoped for. Either the suggested addition should be accepted or anticipated refinements in other sections of the NEC should be initiated. Excerpt from 1980 NFPAReport of the NATIONAL ELECTRICAL CODE Committee Log # 360 1- 31 - (Article lO0-Appliance, Fixed-(New)): Reject SUBMI1-TER: Steven J. Vitzthum, Sheldon, IA RECOMMENDATION: Appliance, Fixed - An appliance securely placed or fastened and not l i k e l y to be moved. SUBSTANTIATION: Fixed appliance is referred to in the NATIONAL ELECTRICAL CODEmore than three times, therefore should be defined in Article 100. PANEL ACTION: Reject. PANEL COMMENT: The Ad Hoc Subcommittee had recommended that this term be deleted on appliances. VOTE ON PANELACTION: UnanimouslyAffirmative. "Article lO0-Appliance (HOD 1978 NEC): Accept CMP 1 SUBMITTER: Technical Subcommittee on Definitions of Stationary Appliances PROPOSAL: 13 Delete the following terms and definitions: Appliances fixed, appliances portable, appliances stationary. SUBSTANTIATION: Although the TSC is considering these three terms as a group, i t did conclude as a result of its study that there is nothing unique about the term "stationary appliance." In recognition of the possibility that not all of the recommendations will be adopted for the 1978 NEC, the terms under consideration may continue to appear in certain NEC requirements. Therefore, the deletion of the terms and definitions neednot be taken as a f i r s t step. With the acceptance of the TSC approach, the terms and definitions should f a l l into disuse and found to be unnecessary for future editions of the NEC. Note: The "Findings" section of the TSC report, as follows, is intended to provide general supporting comment. Findings The Technical Subcommittee found that some requirements for fixed appliances, portable appliances, and stationary appliances were based on different meanings of the terms. These differences arise from the intent of the authors of the requirements at the time the text is adopted. In some cases the requirements are based on the means of electrical connection of the appliance to the supply c i r c u i t . In other instances the requirements involve the physical location of the appliance. The TSC noted some requirements that appeared to involve both meanings and s t i l l others where i t was not clear from the wording what the concerned Code-Making Panel intended. The Technical Subcommittee suggests that the requirements pertaining to appliances differentiate between those that are necessitated by virtue of the method of the electrical connection and those that relate to the physical location of the appliance. With regards to the electrical connections, i t is suggested that this be accomplished either by the use of a cord and plug or by a permanent connection, that is, without the use of a cord and plug. Requirements pertinent to appliance location involve physically fastening the appliance in place by means other than the electrical connection or locating the appliance in dedicated space. These appliances may be movable within the space. The result of either approach is to place the appliance on a specific circuit. The Technical Subcommittee believes that i f these delineations were scrupulously observed and universally applied throughout the Code, both in the drafting of new requirements pertaining to appliances and revising current appliance requirements, the confusion surrounding the interpretation and application of the three terms under review would disappear. Moreover, the TSC believes that adherence to this understanding ~)uld obviate the need for the three terms. As an aid to clarifying the intent of the requirements, the TSC suggests that, as required, the following terms or phrases be employed: Permanently connected; cord- and plug-connected; fastened in place; or located to be on a specific circuit. I There are requirements where in the opinion of the TSC the deleting of the terms "fixed," "I~rtable," or "stationary" will in no way affect the requirements. In such cases, i t is necessary to substitute any of the foregoing. PANEL RECOMMENDATION: Accept. PANEL COMMENT: Accept and so advise other Panels. VOTE ON PANEL RECOMMENDATION: UnanimouslyAffirmative." • Log # 2090 1- 32 - (Article lO0-Autotransformer): Reject SUBMITTER: Charles "Mike" Holt, Concepts in Electricity Inc. RECOMMENDATION: Eliminate the sentence, "An autotransformer is a ~ransformer in which a part of the winding is common to both primary and secondary circuits." from 210-9 and move i t to Article 100. SUBSTANTIATION: Definition for autotransformers should be included under Article 100 where most would look for a definition. All definitions should be in Article 100 except where i t would conflict with other Code sections. PANEL ACTION: Reject. PANEL COMMENT: The word "autotransformer" is not peculiar to and essential to the proper use of this Code as stated in the Scope of Article 100. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 357 1- 33 - (Article lO0-Bathroom-(New)): Reject SUBMII-TER: Mark Meyer, Sheldon, I A RECOMMENDATION: Bathroom: A bathroom is an area including a basin with one or more of the following: a tub, a t o i l e t , or a shower. SUBSTANTIATION: This would prevent any confusion on what consists in a bathroom. PANEL ACTION: Reject. PANEL COMJ~ENT: Definition is intended only for the purpose of clarifying the requirements of Section 210-8. VOTE ON PANELACTION: Unanimously Affirmative. Log # 81 1- 34 - (Article 100-Building): Accept SUBMI~ER: Joseph C. Roohan, International Conference of Building ~FTT~ RECOb~MENDATION: Building: A structure which stands alone or which is cut off from adjoining structures by fire-resistance rated walls, partitions, floors, or ceilings and with all openings therein protected by approved fire-resistance rated doors or other approved methods. SUBSTANTIATION: The definition of "building" in Article 100 of the 1981NEC appears obsolete, and the use of the term " f i r e wall" seems to be the result of an unintended oversight in the NEC that occurred when Article 300-21 was changed. In the 1965 NEC the term " f i r e wall" appeared both in Article 100, definition of "building" and in Article 300-21. In the 1971 NEC some modification was made in Article 300-21 and in the 1975 NEC the term was completely dropped from Article 300-21, to be replaced by the phrase, " . . . f i r e rated, f i r e resistant, or fire stopped walls..." which was continued in the 1978 NEC. The wording was further changed in the 1981NEC using the phrase, " . . . f i r e resistance rated." However, the use of " f i r e wall" in Article 100, definition of "building" has remained unchanged. The absence of " f i r e wall" in the Uniform Building Code and similar codes in preference to phrases like " f i r e rated" and "fire resistive," and the use of " f i r e wall" in the definition of "building" in Article 100 should have also been changed and is no~ obsolete. This proI~)sal attempts to correct this oversight. PANEL ACTION: Accept. VOTE ON PANELACTION: Unanimously Affirmative. i - 35 - (Article lO0-Communication Circuit): Accept SUBMII-FER: CMP 1 ~ATION: Delete the following: "Communication Circuit: See Section 800-1." PANEL ACTION: Reject. PANEL COMMENT: I f accepted as written a user of the Code could infer that you don't have an appliance unless i t is connected with an exterior cord. B SUBSTANTIATION: Just a reminder as to how a covered conductor should be hand]ed. PANEL ACTION: Reject. PANEL COMMENT: The proposal is an attempt to put requirements in the definitions and this is not proper. VOTE ON PANELACTION: Unanimeusly Affirmative. SUBSTANTIATION: The Panel considers a definition for "communication c i r c u i t " unnecessary to the Code. The scopes of the various articles contain descriptions of the systems intended to be covered. The Panel Proposal responds to the confusion expressed in Proposal 1-36. PANEL ACTION: Accept. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 1977 1- 39 - (Article lO0-Conduit Body): Reject Secretary's Note: I t was the action of the Correlating Committee that this proposal be referred to C~ 9 for action. SUBMITTER: F. K. Kitzantides, NEMA RECOMMENDATION: Change the second paragraph of the definition of Conduit Body to read: Boxes, such as FS, FD or larger cast metal sheet metal, nonmetallic boxes, as well as capped elbows and service-entrance elbows, are not classified as conduit bodies. SUBSTANTIATION: The present definition of conduit bodies is too broad and unintentionally covers some products which f i t the definition, but they are not conduit bodies under the typical and normal use of the term in the trade. This has created a situation where the UL listing of conduit bodies is being applied to products which do not f i t the conduit body requirements in Sections 370-6(c) and 370-18. Nonmetallic boxes f i t the present definition of conduit body in Article 100 and just about everyone knows that they really are not conduit bodies. The proposed change will pinpoint more accurately the definition of conduit bodies so that unintended products will not be included. Under the present definition capped elbows and service-entrance elbows are about to be delisted because they are within the broad definition of conduit bodies but do not serve the same function and therefore do not meet the requirements of the conduit bodies such as twice the cross-sectional area of the largest conduit attached or the 6 and 8 times rule as noted in Sections 370-6(c) and 370-18. Neither of these products contain splices and they are primarily used in the termination of a conduit run especially in the case of service-entrance elbows. They are angle f i t t i n g s rather than junction points or f i t t i n g s used as junction boxes. Capped elbows and service-entrance elbows have been in the electrical trade for well over 30 years and have served the industry well. They have an exemplary record to trouble-free performance in the f i e l d , and i t would be a grave injustice to rule them out of the industry due to a technicality such as the definition of conduit body being too broad. PANEL ACTION: Reject. PANEL COMMENT: This proposal is w r i t i n g rules f o r the Code through the use of d e f i n i t i o n s . Referred to CMP 9 f o r action. VOTE ON PANEL ACTION: AFFIRMATIVE: 8 NEGATIVE: Sleesman. EXPLANATION OF VOTE: SLEESMAN: The e x i s t i n g d e f i n i t i o n in the NEC was a NEMA proposal that was never intended to include e i t h e r service o r capped elbows. The proposed revision was intended to c l a r i f y that these products (service elbows and capped elbows.) are used f o r specific applications such as machine tool i n s t a l l a t i o n s . Normally, they are installed with f l e x i b l e conductors. There is a proposal in CMP 8 f o r Section 300-18 which w i l l permit wires to be i n s t a l l e d in the conduit under certain conditions similar to the method generally applicable to the use of service entrance and capped elbows. Log # 1925 1- 36 - (Article lO0-Communication Circuit): Reject SUBMITTER: William C. Bible, OMNI Professional Services ~ o n RECOMMENDATION: Revise definition of: Communication Circuit. The conductors devices, and equipment, including related operating and signaling power supplies, comprising a system of interconnected parts used solely to encode, decode and transmit coherent information or intelligence between two or more locations; to annunicate the presence or a v a i l a b i l i t y of such information or intelligence; or to activate a program of predetermined events or actions. SUBSTANTIATION: The term "communication c i r c u i t " is not defined ~,, th= presenL Code. The definition (?) for "communication circuit" simply says "See Section 800-1." The Code user who follows this advice does not find a meaningful definition in Section 800-1 but instead is further referred to Article 760 where again - no definition! Communication circuits are an integral part of the systems and equipment covered by many of the articles in Chapters 5, 6, 7 and 8. Therefore, i t seems most appropriate that the Code move away from the historical myth that communication circuits can only be so designated i f they are so-called "central station" systems or "telephone systems using similar equipment." The proposed definition will provide Code guidance based on function and will be broad enough to include all of the so-called central station systems as well as other developed and developing technologies of information transmission. More importantly, i t will cover the circuits of other communication systems such as data communication, telemetry, electronic mail, and similar systems used for communication between two or more points either on the same premises or on different premises. The definition is compatible with the use of the term "communication circuit" throughout the Code. I t will not create any conflicts in interpretation of the various Code sections as now written, but will add needed clarification in their application, particularly in those areas relating to wiring methods and limitations of these systems and other parts of the premises wiring system. PANEL ACTION: Reject. PANEL COMMENT: The Panel considers the proposed definition unnecessary to the Code. The scopes of the various articles contain descriptions of the systems intended to be covered. See Panel Proposal 1-35 to delete the term. VOTE ON PANELACTION: Unanimously Affirmative. Log # 618 1- 37 - (Article lO0-Conductor): Reject Secretary's Note: I t was the action of the Correlating Committee that further consideration be given to the comments expressed in the negative voting. SUBMITTER: Earl W. Roberts, General Electric Co. RECOMMENDATION: Add to definition of "Conductor" as follows: Conductor: A substance or body that allows a current of e l e c t r i c i t y to pass continuously along i t . SUBSTANTIATION: There is no Code definition for "Conductor," even though the word is listed. The definition addresses only specific conductors, namely "Bare," "Covered," and "Insulated." There is a misunderstanding among some who believe that "Conductor" applies only to wire and cable rather than to busway, terminals, and all current-carrying parts. The proposed definition is identical to that in the IEEE Standard Dictionary of Electrical and Electronic Terms, ANSI/IEEE Std. 100. PANEL ACTION: Reject. PANEL COMMENT: The Panel feels the present wording is consistent with the use of the term throughout the Code. The proposal adds nothing to the present c l a r i t y of the Code. VOTE ON PANEL ACTIOn: AFFIRMATIVE: 8 NEGATIVE: Sleesman. EXPLANATION OF VOTE: SLEESMAN: "Conductor" is not presently defined in Article 100. There are other sections of the NEC, such as Section 384-10 and Section 610-21, where "conductor" is used to mean something other than wire or cable. Log # 1063 1- 40 - (Article 100-conduit Body): Reject Secretary's Note: I t was the action of the Correlating Committee that this proposal be referred to CMP 9 for action. SUBMITTER: F. K. Kitzantides, NEMA RECOMMENDATION: Changethe second paragraph of the definition of Conduit Body to read: Cast, sheet metal, nonmetallic, and other boxes such as FS, FD and larger boxes and f i t t i n g s such as capped elbows and service entrance elbows are not classified as conduit bodies. SUBSTANTIATION: The present definition of conduit bodies is too broad and unintentionally covers some products which f i t the definition, but they are not conduit bodies under the typical and normal use of the term in the trade. This has created a situation where the UL listing of conduit bodies is being applied to roducts which do not f i t the conduit body requirements in ections 370-6(c) and 370-18. Nonmetallic boxes f i t the present defintion of Conduit Body in Article 100 and just about everyone knows that they really are not conduit bodies. The proposed change will pinpoint more accurately the definition of conduit bodies so that unintended products will not be included. Under the present definition capped elbows and service entrance elbows are about to be delisted because they are within the broad definition of conduit bodies but do not serve the same function and therefore do not meet the requirements of conduit bodies such as twice the cross sectional area of the largest conduit attached or the 6 and 8 times rule as noted ill Sections 370-6(c) and 370-18. Neither of these products contains splices and they are primarily used in the termination of a conduit run especially in ~ Log # 262 1- 38 - (Article lO0-Conductor, Covered): Reject SUBMITTER: C. E. Muhleman, Marion, IN ~ATION: Conductor, Covered: Add: A covered conductor shall be considered a bare conductor for working clearances, etc. 7 the case of service entrance elbows. They are angle f i t t i n g s rather than junction points or f i t t i n g s used as Junction boxes. Capped elbows and service entrance elbows have been in the electrical trade for well over 30 years and have served the industry well. They have an exemplary record to trouble-free performance in the f i e l d , and i t would be a grave injustice to rule them out of the industry due to a technicality such as the definition of conduit body being too broad. PANEL ACTION: Reject. PANEL COMMENT: See Panel Action and Comment on Proposal 1-39, VOTE ON PANEL ACTION: AFFIRMATIVE: 8 NEGATIVE: Sleesman. EXPLANATION OF VOTE: SLEESMAN: The existing definition in the NEC was a NEMA proposal that was never Intended to include either service or capped elbows. The proposed revision was intended to c l a r i f y that these products (service elbows and capped elbows) are used for specific applications such as machine tool installations. Normally, they are installed with flexible conductors. There is a proposal in CMP 8 for Section 300-18 which will permit wires to be installed in the conduit under certain conditions similar to the method generally applicable to the use of service'entrance and capped elbows. to review all sections of Code that use the term ampacity and see i f that is what the intent is. Or is i t the conductor's current-carrying capacity. For example, 220-10(b), 430-22, 430-24, 430-25, etc. PANEL ACTION: Reject. PANEL COMMENT: See Panel Action and Comment on Proposal 1-27. Referred to CMP's 2, 4 and 6 for comment. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 1345 1- 44 - (Article lO0-Damage, Extensive-(New)): Reject SUBMITTER: Paul P. Gubany, Bussmann Division, McGraw-Edison Co. RECOMMENDATION: After the definition of "cutout box" insert the definition for extensive damage as used in 110-10. Damage, Extensive: The type of damage that requires the removal and replacement of the electrical system's component(s). FPN: This is not to be interpreted to apply to fuses or other protective devices that are designed to be replaced after they perform their protective function. SUBSTANTIATION: The present Code is not clear on what extensive damage is. The Code addresses protection in 240-1 and 240-2. Eachof these sections requires "protection not" destruction. Section 90-1 addresses safeguarding of persons and property from hazards arising from the use of e l e c t r i c i t y . PANEL ACTION: Reject. PANEL COMMENT: This is a subjective term that requires Judgement of Indi¢idual products and cannot be defined in Article 100. VOTE ON PANELACTION: Unanimously Affirmative. Log # 1926 1- 41 - (Article lO0-Continuous Load): Reject SUBMITTER: Joseph C. Roohan, Whittier, CA ~ATION: Delete a11 reference to "Continuous Load." SUBSTANTIATION: The inclusion of "Continuous Load" and the accompanying derating rules in the NATIONAL ELECTRICAL CODEsome time ago was a well intended, but unnecessary refinement in the practical application of the Code. The consideration of "Continuous Load" clearly belongs in electrical handbooks and other designers' guides but not in a safety code. In Section 90-1(c) i t is stated that "This is not intended as a design specification..." I t is ludicrous to consider an installation safe where i t carries current for slightly less than three hours and unsafe where this time is exceeded. I t is just as ridiculous to consider an installation safe where i t is carrying continuous current and is momentarily interrupted every three hours. The ampacity ratings for conductors in Article 310 are continuous ratings and the derating factors for continuous loads are design considerations to reduce nuisance tripping current breakers that are not temperature compensated where enclosed in panelboards. Nuisance tripping is not generally considered a safety hazard. By deleting the references to "Continuous Load" in the National Electrical Code an important step toward practicality will be achieved allowing inspectors, plan reviewers, and others whose duties consist of evaluating an installation to concern themselves with the safety provided by conductor size, material, insulation, and overcurrent protection. The time element of an in installation is an impractical, unenforceable and unrelated element of safety within the referenced sections. PANEL ACTION: Reject. PANEL COMMENT: The term is used extensively throughout the Code and the definition is necessary to understand the application of Code rules. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 378 i - 45 - (Article lO0-Electric-Discharge Lighting-(New)): Reject SUBMITTER: Dennis Schmit, Hospers, IA RECOMMENDATION: Electric-Discharge Lighting: All lighting that Involves the use of ballasts. SUBSTANTIATION: There is no place in the Code that defines i t and i t is talked about frequently. PANEL ACTION: Reject. PANEL COMMENT: The proposal does not add any c l a r i t y to the use of the Code. VOTE ON PANELACTION: Unanimously Affirmative. Log # 256 I - 46 - (Article lO0-Enclosed, Raceway): Reject SUBMITTER: C. E. Muhleman, Marion, IN RECOMMENDATION: Delete the term "enclosed" and include cable trays as a type of raceway. SUBSTANTIATION: This makes the term more inclusive. There seems to be no place throughout the Code that a cable tray would not be permitted where the term "raceway" has been used. After a l l , cable trays under specified conditions are permitted in hazardous areas. PANEL ACTION: Reject. PANEL COF~MENT: Cable trays are not a raceway. They are adequately defined in Section 318-I. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 1766 1- 47 - (Article lO0-Fire Resistant): Reject SUBMITTER: Tom Tombarello, Paul Revere Chapter IAEI RECOMMENDATION: Fire Resistant: (as applies to Article 450), see Sectlon 450-2. SUBSTANTIATION: A reference is needed to pin-point the definition much the same as "dust-ignition-proof" or "branch-circult selection current" as they appear in Article 100. PANEL ACTION: Reject. PANEL COMMENT: Similar terms are used throughout the Code. VOTE ON PANELACTION: UnanimouslyAffirmative. Log # 658 i - 42 - (Article lO0-Controller): Reject SUBMITTER: George C. Gingher, Association of Iron and Steel RECOMMENDATION: Changedefinition to read: "A device or group of devices that serves to govern, in some predetermined may ", the electric power delivered "directly" to the apparatus tL .ch i t is connected." SUBSTANTIATION: The addition of the word "directly" in the definition makes i t clear that pilot devices, often remote n~unted, such as limit switches, push-button stations, master switches, etc. are "not" a controller. This would c l a r i f y application of this definition such as Section 430-102, where only the Handbook now makes i t clear that a master switch is not the location for a disconnecting means. PANEL ACTION: Reject. PANEL COMMENT: The devices mentioned in the supporting comment could be considered controllers on specific installations as covered in Section 430-81(a). VOTE ON PANELACTION: Unanimously Affirmative. Log # 314 I - 48 - (Article lO0-Ground, Grounding): Reject SUBMITTER: TomeyW. Long, TWL, Inc. dba Commercial Electric RECOMMENDATION: Delete the word "ground" and replace i t with the word " n e u t r a l . " Delete the word "grounding" and replace i t with the word "bond." SUBSTANTIATION: There is constant confusion between the words "ground" and "grounding" by customers, wiremen, inspectors, architects, engineers and contractors. PANEL ACTION: Reject. PANEL COMMENT: The proposal is technically inconsistent with present Code rules and definitions. The submitter does not identify where the changes should be made. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 1660 1- 43 - (Article lO0-Current-Carrying Capacity): Reject SUBMIl-rER: Charles "Mike" Holt, Concepts in Electricity, Inc. ~ATION: Revise definition of Current-Carrying Capacity to read: "The maximum load that a conductor can carry after all load limiting factors have applied." SUBSTANTIATION: The Code uses the term ampacity but in reality they mean current-carrylng capacity. A committee ~hould be set up B Log # 1764 1- 52 - (Article lO0-Ground-FauIt Protection of Equipment-(New)): Accept in Principle SUBMITTER: Tom Tombarello, Paul Revere Chapter IAEI RECOMMENDATION: Ground-Fault Protection of Equipment: A system intended to provide protection of equipment from damaging line-to-ground arcing fault currents by operating to cause a disconnecting means to open all ungrounded conductors of the faulted circuit. This protection is provided at current levels less than that required to protect conductors from damage through the operation of a supply c i r c u i t overcurrent device. SUBSTANTIATION: The definition is as provided for the 1981NEC and i t is believed that CMP 1 should take another look at i t for revision or acceptance. PANEL ACTION: Accept in Principle. Delete the word "arcing." PANEL COMMENT: Low level ground faults are not necessarily arcing faults. Referred to CV~'s 4 and 11 for information. VOTE ON PANEL ACTION: AFFIRMATIVE: 7 NEGATIVE: Hart, Moser. EXPLANATION OF VOTE: HART: I believe that this proposal should be rejected for the same reasons that i t was rejected for the 1981 Code. There is a considerable amount of confusion regarding ground-fault protection of equipment and ground-fault protection of personnel. There even seems to be some confusion in the Panel as evidenced by the discussion during the recent Panel meeting. As I stated last time, this definition is not any different from the ordinary dictionary definition and in fact i t is also a good description of ground-fault protection of personnel as well as a ground-fault circuit-interrupter. I do agree that there is need to differentiate between the two systems, but I do not believe that i t can be done through definitions, especially the one now being proposed. I t would only add to the confusion already existing. MOSER: Proposal 1-52 should be rejected because the definition does not clarly mention the use of an alarm only for those systems designed to have a very low level of ground-fault current. A fine print note stating, " I t is recognized that systems designed to have a very low level of ground-fault current are sometimes provided with an alarm only to indicate the presence of a ground fault" would make the proposal acceptable. Log # 261 1- 49 - (Article lO0-Grounded Conductor, Grounding Conductor): Reject SUBMITTER: C. E. Muhleman, Marion, IN ~ATION: Grounded Conductor: Add: A grounded conductor is intended to carry current during normal operation. Grounding Conductor: Add: A grounding conductor is intended to carry current only during abnormal conditions. SUBSTANTIATION: Better differentiates the electrical purpose. PANEL ACTION: Reject. PANEL COMMENT: The purpose of these conductors is adequately covered in Article 250 and should not be included in the definitions. VOTE ON PANEL ACTION: Unanimously Affirmative. COMMENTON VOTE: SUMMERS: I agree with the Panel Action but the Panel Comment is so bland that readers of the Preprint (Technical Committee Report) could conclude that CMP I was in agreement with the submitter's proposed definitions. Both definitions are technically incomplete. A grounded conductor also carries f a u l t currents back to the source of the system during abnormal conditions in addition to carrying current during normal operation. The term "grounding conductor" is a generic term that applies to several specifically defined conductors; one of these defined conductors is the "grounding electrode conductor." The grounding electrode conductor, because i t is connected to the grounded conductor at the service, provides an alternate path through the earth to the source of the system during normal conditions. Log # 418, 503, 1234 I - 50 - (Article lO0-Grounding Electrode-(New)): Reject Secretary's Note: I t was the action of the Correlating Committee that this proposal be referred to CMP 5 for action. SUBMITTERS: Southwestern Section IAEI (418) Ernest E. Cannon, Tempe, AZ (503) IAEI (1234) RECOMMENDATION: Add a definition of grounding electrode, such as: GROUNDING ELECTRODE. A provision made to allow a conductive path to the earth or to a conducting body that serves in place of the earth. SUBSTANTIATION: The term "groundin 9 electrode" is used many places, including Sections 250-24(b), 250-24(b), Exception, 2B0-26(c), 250-80(a) and (b), 250-81 and 250-83. In all places i t assumed that there is f u l l knowledge of exactly what the "grounding electrode" actually is. Perhaps a part of the inherent confusion on grounding is caused by lack of a precise and understandable definition, PANEL ACTION: Reject. PANEL COMMENT: The Panel feels the proposal is not within the jurisdiction of CMP i and refers i t to CMP 5 for action. VOTE ON PANELACTION: AFFIRMATIVE: 8 NEC~ATIVE: Summers. EXPLANATION OF VOTE: SUMMERS: Although I concur with the Panel Comment, the term should be defined. Log # 934 1- 53 - (Article lO0-Ground-Fault Protector): Reject , SUBMITTER: C. D. Hansell, GTE Service Corporation RECOMMENDATION: Add a new definition for the device or system described in Section 230-95: Ground-Fault Protector: A device or system of devices intended to limit damage to conductors and equipment in the event of an arcing round fault on the load s l d e o f the service disconnecting means. UBSTANTIATION: The definition should be added following and to differentiate from Ground-Fault Circuit Interruptor. The term is used in at least two Sections, 517-14 and 701-17. PANEL ACTION: Reject. PANEL COMMENT: See Panel Action and Comment on Proposal 1-52. VOTE ON PANEL ACTION: Unanimously Affirmative. ~ Log #935 1- 51 - (Article lO0-Grounded, Effectively): Reject SUBMITTER: C. D. Hansell, GTE Service Corporation RECOMMENDATION: Part B Over 600 Volts, Nominal. Change the definition, Grounded, Effectively, to the identical text used in the fine print note following Section 800-2(c)(1)d: Grounded, Effectively: Effectively grounded means intentionally connected to earth through a ground connection or connections of s u f f i c i e n t l y low impedance and having sufficient current carrying capacity to prevent the buildup of voltages which may result in undue hazard to connected equip~lent or to persons. SUBSTANTIATION: The two definitions should be identical. The major difference is that the proposed text says "to prevent the buildup of voltages which may result in undue hazard to connected equipment or to persons," in place of "that ground-fault current which may occur cannot build up to voltages dangerous to personnel." PANEL ACTION: Reject. PANEL COMMENT: Article 100 presently has a note to refer to Section 800-2(c)(1). The inclusion of such a definition without the cross reference would lead to an incorrect use of the term. VOTE ON PANEL ACTION: Unanimously Affirmative. COMMENTON VOTE: SUMMERS: The Panel should have referred this to CMP 5 for action. The Panel Comment is in error because the proposal is directed to the definition in Part B Over 600 Volts, Nominal and not the cross reference in Part A. I am not convinced that the proposal is even sound. Low voltage and high voltage systems are not usually grounded by the same methods nor do they achieve the same end result. The use of the term "effectively grounded" as used in the NEC has a t o t a l l y different connotation applied to the term in the IEEE Green Book ANSI/IEEE C114.1. This recommended practice for grounding of Industrial and Commercial Power Systems uses the term "effectively grounded" to describe grounding accomplished by the use of surge arresters. I - 54 - (Article lO0-1nterrupting Rating): Accept SUBMINER: CMP I RECOMMENDATION: Rev~rd the present definition by replacing the word "specified" with "standard." SUBSTANTIATION: Specified test conditions should be given in the form of a Fine Print Note where possible. In this instance i t is impossible to do so; therefore, the substitution of "standard" is appropriate: PANEL ACTION: Accept. VOlE ON PANEL ACTION: Unanimously Affirmative. Log # 1449 i - 55 - (Article lO0-1nterrupting Rating): Reject SUBMITTERS: Leo, Witz, Continental Elec. Co. J-Jlm-Meehan, New'Haven, CT Fred Smith, Elgin, IL Leo Nagel, North Dakota Les Rinder, Chicago,-IL Paul Moore, Paducah, KY Robert P. Brooks, Chicago, IL B i l l Conrardy, The Conrardy Co. Anton Ganje, North Dakota Kenny Gebert, Minneapolis, MN Bill Hogan, Chicago, IL Homer M. Lefler, Chicago, IL John W. Erickson, Boltswitch Inc. RECOMMENDATION: AmendArticle 100 so that the definition of "Interrupting Rating" reads as follows: "Interrupting Rating. The highest current at rated voltage that an overcurrent protective device has proven that i t can interrupt, under standard test conditions, without unacceptable damage to i t s e l f or its related equipment. 9 RECOMMENDATION: Add a definition for "MADEELECTRODES" such as: A "made grounding electrode" is a grounding electrode made by electrical installation specifically for the purpose of serving as a grounding electrode. SUBSTANTIATION: There is a reasonable confusion concerning Just what the intent of NEC is in Sections 250-83 and 250-84 when the term is used. In fact, grounding electrodes formerly listed under 83 section have been moved to Section 250-81, specifically "concrete-encased electrode. ~ This serves to further confuse the issue. Certainly, made electrodes in contrast to nonmade electrodes is in order. Perhaps those grounding electrodes which exist because of structure construction and/or f a c i l i t y installation such as metallic water piping, effectively grounded steel frames, other metallic piping systems or underground tanks are in the class of nonmade and the made electrodes for grounding do consist of those which are intentionally installed for the purpose and/or of electrical materials. Clarification is in order. PANEL ACTION: Reject. PANEL CO~b4ENT: See Panel Action and Comment on Proposal 1-50. VOTE ON PANELACTION: AFFIRMATIVE: 8 NEGATIVE: Summers. COMMENTON VOTE: SEELBACH: The Panel Comment should mention a referenceto CMP 5 for action, instead of learning this after reviewing Proposal 1-50. EXPLANATION OF VOTE: SUMMERS: Although I concur with the Panel Comment, the term should be defined. Equipment intended to break current at other than fault conditions may have their interrupting ratings expressed in other than levels of current, such as horsepower." SUBSTANTIATION: The use of the words, "is intended to interrupt under specified test conditions," means l i t t l e or nothing to the inspector and far less in law. I f the NEC is to become a legal document i t is necessary to eliminate as many loopholes through which many less than honest people crawl in their attempt to evade the intention of the Code as is possible. As i t is presently written, the sentence contains two indeterminate provisions. The f i r s t is that, "the overcurrent protective device IS INTENDEDto i n t e r r u p t . . . " Now, we might design and manufacture an overcurrent protective device with the very best of INTENTIONS and make some very explicit claims about what that OCP is INTENDEDto do. I t is historically possible, probable and likely that certain manufacturers will continue to do just exactly that when they know and we can prove that the OCP will not and cannot perform as intended. Secondly, we might SPECIFY a very complex and meaningless set of TEST CONDITIONS under which the device is to be tested. Having done these two things, we would be in conformance with the provisions of the present wording of the Code. However, we all know that the road to hell is paved with good INTENTIONS and that sets of specifications drawn up by manufacturers to prove the acceptability of one of their products are really not INTENDED to prove that products unacceptability, but rather its acceptability. No one writes a set of specifications that will be detrimental to ones own product. In recent history we have had clear and unrefutable evidence of overcurrent devices that have been given interruping ratings at which they are INTENDEDto perform under SPECIFIED TEST CONDITIONS that have failed miserably in the f i e l d . I t is our opinion that the insertion of the words, "has proven" will make i t mandatory that manufacturers will have to provide tangible evidence that their products have been tested and have passed such tests. The words, "standard test conditions," will make i t mandatory that all similar products are tested to the same standard and that such a standard has some r e l a t i v i t y to the real world. To our knowledge there is no place in the code where, "specified test conditions" is defined, explained or even alluded to except in these definitions in Article 100. As such the term is meaningless. For further substantiation see our proposal for the definitions that include the term, "specified test conditions. ~ PANEL ACTION: Reject. PANEL COMMENT: The Panel believes the proposed revision would not accomplish the purpose intended by the proposer's substantiation. VOTE ON PANELACTION: Unanimously Affirmative. Log # 1668 1- 59 - (Article 100-Neutral Conductor): Accept SUBMINER: Charles "Mike" Holt, Concepts in Electricity, Inc. ~ T I O N : Delete the definition. SUBSTANTIATION: Neutral is referred to as the grounded conductor. Most sections of the NEC refer to the neutral as the grounded conductor, also the word common is used. Why not just call i t the grounded conductor and be done with i t . By omitting this meaningless definition, and using the grounded conductor as the reference, the Code will provide some consistency with its terminology. Have all sections of NEC reviewed and make changes to the term grounded conductor. PANEL ACTION: Accept. PANEL COMMENT: The Panel accepts the proposal as i t realizes that no proper definition presently appears in Article 100. However, the Panel disagrees with the proposer's substantiation as some grounded conductors are not neutral conductors. VOTE ON PANELACTION: Unanimously Affirmative. Log # 954 I - 56 - (Article 100-Load Current-(New)): Reject SUBMITTER: R. P. O'Riley, Dallas Joint Electrical Apprenticeship and~ing Committee. RECOMMENDATION: Add new definition: Load Current - As Applied to Electrical Conductors - The ampacity of an electrical conductor after one or more of the correction factors are applied to the listed ampacity as given in the Code ampacity Tables 310-16 thru 310-19. SUBSTANTIATION: There is considerable confusion concerning the use of the terms "ampacity" and "load current" as applied to electrical conductors. Therefore, there is need for a definition for clarification of these two terms. PANEL ACTION: Reject. PANEL COMMENT: The Panel is in sympathy with the substantiation proposed. See Panel Action and Comment on Proposal 1-26. Referred to CMP's 2, 4 and 6 for comment. VOTE ON PANELACTION: UnanimouslyAffirmative. Log # 100 1- 60 - (Article 100-Neutral Conductor): Reject Secretary's Note: I t was the action of the Correlating Committee that this proposal be referred to CMP 5 for action. SUBMITTER: Robert G. MacManus, Pawtucket, RI ~DATION: Replace the existing words with the following: Neutral Conductor: The conductor of single-phase three-wire and three-phase four-wire wye systems which is common to a11 phases and having an equal potential difference between i t and each of the phases. In the case of the three-wlre system derived from the "red leg" delta system, i t is the midpoint of the two phases used. See applicable sections of Article 250 for grounding. SUBSTANTIATION: The present definition is not a definition at a l l . I t refers to Note 10 to Tables 310-16 through 310-19 which determines i f the neutral conductor shallbe counted when applying the provisions of Note 8. PANEL ACTION: Reject. PA%4ELCOMMENT: The proposal is not all inclusive. The Pane] agrees with the proposer's substantiation. See Panel Action and Comment on Proposal 1-59. Referred to CI~° 5 for action. VOTE ON PANELACTION: Unanimously Affirmative. Log # 373 1- 57 - (Article lO0-Location: Commercial Location-(New); Industrial Location-(New)): Reject SUBMITTER: RandyHeikes, Ellsworth, MN ~ATION: Commercial location: A place that is engaged in the selling of goods or services, with the intent of making a profit. Industrial location: A company or place that is engaged in industrial production of goods or services. Residential location: A place made up of one or more dwelling units. SUBSTANTIATION: The definitions do not very clearly define the locations above. PANEL ACTION: Reject. PANEL COf~MENT: Proposed definitions would cause a conflict with the various building codes. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 1398 I - 61 - Article lO0-Noncombustible Materia1-(New)): Reject Secretary's Note: The Correlating Committee directs that this proposal be referred to the NFPA Committee on Air Conditioning for comment. SUBMII'TER: C. W. Beile, Allied Tube & Conduit Corporation RECOMMENDATION: Add the following definition: Noncombustible Material: A material which, in the form in which i t is used and under the conditions anticipated, will not ignite, burn, support combustion or release flammable vapors when subjected to f i r e or heat. Materials reported as noncombustible, when tested in accordance with ASTME136, Standard Method of Testing for Noncombustibility of Elementary Materials, shall be considered noncombustible materials. SUBSTANTIATION: This term is found in at least two places in the NEC and is proposed for addition to Sections 300-22 (b) and (c), 347-2 and 384-7. Proposals to the 1978 and 1981 NEC were rejected because the Code Panel professed lack of knowledge of what this term meant. This definition is extracted word for word from NFPA90A and 220. I t is especially apropos to the NEC at this time considering the Standards Council action toward 90A responsibility system for ducts and plenums. Log # 419, 502, 1235 1- 58 - (Article lO0-Made Electrodes-(New)): Reject Secretary's Note: I t was the action of the Correlating Committee that this proposal be referred to C~ 5 for action. SUBMITTERS: Southwestern Section IAEI (419) Ernest E. Cannon, Tempe, AZ (502) IAEI (1235) 10 SUBSTANTIATION: This wording is used in the NEC Sections 300-21 and 800-3(c) meeting the requirements of having i t defined in Article 100. The publicity that has been given to products that will combust in recent fires involving the electrical industry in the controversy of toxic fumes is damaging to the industry. Vital insulations of conductors can be challenged as well as raceways and other plastic equipment. There is a proposal like the above worded definition that uses "toxic fumes" instead of just the word "fumes." We should stay clear of the word "toxic" until we know more about t o x i c i t y and what products of combustion produce toxic fumes. There is a definite need for the definition at this time. PANEL ACTION: Reject. PANEL COMMENT: See Panel Action and Comment on Proposal 1-64. VOTE ON PANEL ACTION: AFFIRMATIVE: 8 NEGATIVE: Summers. EXPLANATION OF VOTE: SUMMERS: Samecomment as Proposal 1-64. As evidenced by pages 15 and 16 of the attached "Survey for the Collection of Professional Opinion on Selected Fire Protection Engineering Topics" present non-combustible definitions are not even adequate. However, i t seems the NEC would need to agree with NFPA 90A until needed changes take place there. Note: (A copy of the attachments is available from NFPAon request.) PANEL ACTION: Reject. PANEL COI~MENT: The submitter's substantiation (NBS Technical Note 861) indicates the lack of adequacy of present definitions. In view of this shortcoming the proposed definition would be inappropriate for the NEC. The pending action alluded to in the last sentence of the substantiation is compelling reason to refer the proposal to NFPA for action by the appropriate committee. VOTE ON PANELACTION: Unanimously Affirmative. Log # 12 1- 62 - (Article lO0-Overcurrent): Reject SUBMI1-FER: Russell A. Pasco, San Diego, CA ~ATION: In OVERCURRENT definition change " I t may result from overload (see definition) short circuit or ground f a u l t . " to " I t may result from overload (see definition) or short c i r c u i t . " SUBSTANTIATION: The definition of Ground-Fault Circuit-lnterrupter indicates that a ground fault is "less than that required to operate the overcurrent protective device" and therefore is NOT an overcurrent. The change will eliminate this apparent contradiction. PANEL ACTION: Reject. PANEL COMMENT: The proposer's substantiation is not correct. There is no contradiction between the two definitions. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 417 1- 66 - (Article lO0-Products of Combustion-(New)): Reject Secretary's Note: The Correlating Committee directs that this proposal be referred to the NFPA Committee on Air Conditioning for comment. SUBMITTER: Southwestern Section IAEI ~ATION: Amend Article 100 by adding the following definition: "Products of Combustion. Smoke, gases or toxic fumes resulting from the exposure of materials or equipment to temperatures in excess of their ratings or f i r e . " SUBSTANTIATION: There is a very definite need for a specific definition of this nature since the term is used in more than one section of the Code. PANEL ACTION: Reject. PANEL CO~aMENT: See Panel Action and Comment on Proposal 1-64. VOTE ON PANEL ACTION: AFFIRMATIVE: 8 NEGATIVE: Summers. EXPLANATION OF VOTE: SUMMERS: Samecomment as Proposal 1-64. Log # 2017 1- 63 ~ (Article 100, Physical Damage-(New)): Reject SUBMITTER: Idaho Chapter IAEI RECOMMENDATION: Add the following definition to Article 100: Physical Damage: A term used to describe the material impairment, to various degrees, of the usefulness of installed electrical equipment and materials. SUBSTANTIATION: This wording is used in the NEC in many locations, thus i t meets the requirements of having i t defined in Article 100. Manytimes the question has been asked, "What is physical damage?" This has been discussed at NFPA technical committee meetings and there is indeed a need for the definition. The above proposed definition coincides with Webster's definition of the words physical and damage. PANEL ACTION: Reject. PANEL COMMENT: The definition is not peculiar to and essential to the proper use of this Code. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 1368 i - 67 - (Article lO0-Products of Combustion-(New)): Reject Secretary's Note: The Correlating Committee directs that this proposal be referred to the NFPA Committee on Air Conditioning for comment. SUBMITTER: M. H. Lounsbury, Albany, NY RECOMMENDATION: AmendArticle 100 by adding the following definition: "Products of Combustion. Heat and smoke consisting of toxic and corrosive products, carbon particles, carbon dioxide in large amounts and water vapors generated as a result of combustion in a flaming or non-flaming f i r e . " SUBSTANTIATION: There is a very definite need for a specific definition of this nature, since the term is used in more than one Section of the Code (300-21, 800-3(c), 760-4(a), 725-2(a), 820-14(a)). Along with a definition for non-combustible, Products of Combustion must be defined and a guideline for evaluation of combustible products established. PANEL ACTION: Reject. PANEL COMMENT: See Panel Action and Comment on Proposal 1-64. VOTE ON PANEL ACTION: AFFIRMATIVE: 8 NEGATIVE: Summers. EXPLANATION OF VOTE: SUMMERS: Samecomment as Proposal 1-64 Log # 1233 1- 64 - (Article lO0-Products of Combustion-(New)): Reject Secretary's Note: The Correlating Committee directs that this proposal be referred to the NFPA Committee on Air Conditioning for comment. SUBMITTER: IAEI RECOMMENDATION: AmendArticle 100 by adding the following definition: "Products of Combustion. Smoke, gases or toxic fumes resulting from the exposure of materials or equipment to temperatures in excess of their ratings or f i r e . " SUBSTANTIATION: There is a very definite need for a specific definition of this nature since the term is used in more than one section of the Code. Sections 300-21, 725-2(a), 760-4(a), 800-3(c), 820-14(a). PANEL ACTION: Reject. PANEL COMMENT: Pending release of the NFPA report on t o x i c i t y , the Pane] refers this proposal to NFPA for action by the appropriate committee. VOTE ON PANEL ACTION: AFFIRMATIVE: 8 NEGATIVE: Summers. EXPLANATION OF VOTE: SUMMERS: Although I agree with the Panel Comment, the term should be defined. Log # 652 1- 68 - (Article lO0-Raceway): Reject SUBMITTER: Nils Jonsson, RELOCDivision of Lithonia Lighting RECOMMENDATION: Raceway Last line - delete the word "and" after wireways but before busways and add after the word busways the following "and manufactured wiring systems." SUBSTANTIATION: Article 604, Manufactured Wiring Systems, has now been accepted as a "Branch Wiring Method." Subsequently, i t should take its rightful place under "Raceway" Article 100. PANEL ACTION: Reject. PANEL COMMENT: The substantiation is in error as manufactured wiring systems are not raceways. Wiring methods are covered in Chapter 3. VOTE ON PANEL ACTION: Unanimously Affirmative. L o g # 2018 1- 65 - (Article 100, Products of Combustion-(New)): Reject Secretary's Note: The Correlating Committee directs that this proposal be referred to the NFPA Committee on Air Conditioning for comment. SUBMITTER: Idaho Chapter IAEI RECOMMENDATION: Add the following definition to Article 100: Products of combustion. Smoke, gases or fumes resulting from the exposure of materials or equipment to temperatures in excess of their ratings or f i r e . Log # 1765 I - 69 - (Article lO0-Readily Accessible): Accept in Principle Secretary's Note: I t was the action of the Correlating Committee that further consideration be given to the comments expressed in the voting. 11 SUBMITTER: Tom Tombarello, Paul Revere Chapter IAEI ~ATION: Relocate Readily Accessible to follow "Accessible (as applied to equipment)" as follows: Accessible, Readily: (Readily Accessible) Capable of being reached quickly . . . . SUBSTANTIATION: The attempt is to group the definitions u t i l i z i n g the word "accessible" so that users of the NEC can distinguish at a glance the differences in their applications. PANEL ACTION: Accept in Principle. Revise the proposal by adding a third sentence as follows: Add "Readily Accessible: (See "Accessible.")" in alphabetical order under the letter "R." PANEL COfC~4ENT: To assist the reader in finding the relocated definition. VOTE ON PANELACTION: UnanimouslyAffirmative. COMMENTON VOTE: SEELBACH: My notes indicate that in addition to the Action shown, we also planned to retain "Readily Accessible - See Accessible" as i t now appears in Article 100. SUMMERS: The Panel Action is confusing but my notes reflect the following: Accept the proposal and in the present location in Article 100 of "Readily Accessible" add the following cross reference: Read!ly Accessible: (See Accessible). SUBSTANTIATION: The definitions should be consistently found in Article 100, Or i f they conflict with other sections, should be located at the front of each section where they are applicable. PANEL ACTION: Reject. PANEL COMMENT: Proposal is contrary to the Scope of Article 100 as the definition is not used in two or more articles. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 837 1- 74 - (Article lO0-Smoke (New)): Reject Secretary's Note: The Correlating Committee directs that this proposal be referred to the NFPA Committee on Air Conditioning for comment. SUBMITTER: Robert E. Taylor, Smoke Control Association RECOMMENDATION: Add (New) Definition: SMOKE: The airborne solid and liquid particulates and gases evolved when a material undergoes pyrolosis or combustion. SUBSTANTIATION: Reference to word occurs in at least two sections. To make code interpretation more precise and accurate, an accepted "scientific" definition of smoke should be in the NEC, the ASTMdefinition. Smoke appears in articles: 725-2(b)760_4(d)Exception tOException to l~I 800-3(d) Exception to (d) The term "products of combustion" likewise should be deleted wherever i t is used in Standard No. 70 and replaced with the word "smoke." Companion proposals will so recommend, since "products of combustion" is not an ASTMor enforceable definition. PANEL ACTION: Reject. PANEL COMMENT: See Panel Action and Comment on Proposal 1-64. Referred to C~'s 3, 16 and 17 for information. VOTE ON PANELACTION: Unanin~ouslyAffirmative. Log # 211 1- 70 - (Article lO0-Service): Reject SUBMITTER: Dan Leaf, Westlake Village, CA ]TE'T~OI~I;{E~-DATION: Revise definition of service as follows: Service: The conductors and equipment for delivering energy from the e l e c t r i c i t y supply system of the serving u t i l i t y , or energy-generating plant providin~ the sole source of energy, to the wiring system(s) of the premlses served. SUBSTANTIATION: While the present wording does not exclude such a generating plant~ i t couid also be construed as including conductors and equipment supplied from a premises wiring system transformer, (standby or emergency) generator, battery, etc. This proposal attempts to provide a more definitive description of what "System" is involved. A generating plant providing the sole source of electrical energy to a premises wiring system should warrant the same requirements of Article 230 as a supply system from a serving u t i l i t y . PANEL ACTION: Reject. PANEL COMMENT: The service may not be the sole service of energy to the wiring system of the premises served. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 1753 I - 71 - (Article lO0-Service Conductors): Reject SUBMII~FER: Charles "Mike" Holt, Concepts in Electr.icity, Inc. ~ATION: Omit this definition. SUBSTANTIATION: This definition does not provide any more information than service entrance conductors (overhead, underground) service drop, service lateral. PANEL ACTION: Reject. PANEL COMMENT: The definition applies to all the definitions mentioned in the substantiation and therefore is a generic term necessary to properly apply the existing Code rules. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 911 1- 75 - (Article lO0-Solar Photovoltaic System): Accept SUBMITTER: Ad Hoc Subcommittee on Solar Photovoltaics RECOMMENDATION: Add new definition as follows: Solar Photovoltaic System: The total components and subsystems which in combination convert solar energy into electrical energy suitable for connection to a u t i l i z a t i o n load. SUBSTANTIATION: The term may be defined in Article 690 and i f accepted may appear in more than two articles of the Code. PANEL ACTION: Accept. PANEL COMMENT: The Panel Action is conditional upon the acceptance of Article 690 by CMP 3. Referred to CMP 3. VOTE ON PANELACTION: Unanimously Affirmative. Log # 1419 1- 76 - (Article lO0-Switch Loop-(New)): Reject SUBMITTER: Karl F. Steinhauer, Des Plaines, IL RECOMMENDATION: Switch Loop: In a configuration where supply raceway goes directly to the outlet, the off-side wiring to/from a controlling switch (and lacking the grounded identified conductor) is a "switch loop." SUBSTANTIATION: To c l a r i f y that Section 200-7 Exception No. 2: a) applies for BX as well as for Romex, and b) is not a contradiction of Section 380-2(a). PANEL ACTION: Reject. PANEL COMMENT: The proposed definition is a trade term and does not meet the Scope of Article 100 as i t is not used in more than one article. VOTE ON PANELACTION: UnanimouslyAffirmative. Log # 200 1- 72 - (Article 100-Service Equipment): Reject SUBMII-FER: Dan Leaf, Westlake Village, CA ~ATION: Revise definition of Service Equipment as follows: Service Equipment: The necessary equipment, usually consisting of a circuit breaker or switch and fuses, and their accessories~ located near the point of entrance of service conductors to a building or other structure, or an otherwise defined area, and intended to constitute the main control and means of disconnection of the service conductors. SUBSTANTIATION: As presently worded, without specifying what constitutes "supply" conductors, this section could be interpreted to define the disconnect means required in Section 230-84 as service equipment, particularly since such equipment shall be suitable (listed) for such, Formal Interpretation 70-78-7 apparently dealt with a problem arising from an installation where i t was necessary to define service equipment and/or service conductors. The definition of Service Conductors define particular supply conductors, and Sections 230-71~a) and 230-72(c) maintain consistency by specifying requirements of service equipment in relationship to certain specified supply conductors. The use of the word, "service" in lieu of "supply" would encompass Service Entrance Conductors-Overhead System, Service Entrance Conductors-Underground System, and Service lateral. PANEL ACTION: Reject. PANEL COMMENT: The proposed definition does not add to the additional understanding of what constitutes service equipment. VOTE ON PANELACTION: UnanimouslyAffirmative. Log ~ 973 1- 77 - (Article lO0-Switches, Motor-Circuit Switch): Accept SUBMITTER: R. W. Seelbach, Underwriters Laboratories Inc. RECOMMENDATION: Motor-Circuit Switch: A switch capable of Tnterrupting the maximom operating overload current (including locked-rotor) of a motor. SUBSTANTIATION: This revision deletes "rated in horsepower" on the basis that this is an unnecessary specification. Some switches suitable for motor circuit uses are essentially circuit-breakers with the tripping element either blocked or removed. These are known by various names, such as "nonautomatic c i r c u i t interrupters" and "molded case switches." These switches do not require marked horsepower ratings since, like circuit breakers, the information included in the listing or labeling indicates that they are tested at 6 times the marked ampere rating and therefore are suitable for interrupting the maximum operating overload current (including locked-rotor) of any motor for which the voltage and ampere ratings are adequate. The marking of horsepower ratings would unnecessarily limit the use of these switches since the individual units do not have sufficient room on their face, where the marking weuld be visible, for a table of the applicable horsepower ratings considering the various voltage both single and three phase, involved. A proposal to delete "rated in horsepower" is also being made for Section 430-109. PANEL ACTION: Accept. Log # 1687 1- 73 - (Article 100-Service Point): Reject SUBMITTER: Charles "Mike" Holt~ Concepts in Electricity Inc. ITL-CI)I~E~ZI~IIATION: Removedefinitlon from Section 230-200 and place i t in Artlcle 10(3. 12 Log # 2086 1- 81 - (Article 110): Reject SUBMITTER: Richard Reddy, Reddy Electric Company, Inc. O R~ A T I O N : Eliminate reducing washers. SUBSTANTIATION: Instead use a reducing bushing threaded inside and out that could be secured in the hole with a locknut and the pipe size f i t t i n g screwed into the bushing. This would require the manufacture of reducing bushings with a shoulder on one side similar to those used by the plumbing industry, instead of the ones currently being used in the electrical industry where the thread is straight all the way across the bushing. PANEL ACTION: Reject. PANEL COMMENT: See Panel Action and Comment on Proposal 1-80. VOTE ON PANEL ACTION: Unanimously Affirmative. PANEL COMMENT: The Panel Action is conditional upon acceptance of this proposa! by CMP 11. VOTE ON PANELACTION: AFFIRMATIVE: 8 NEGATIVE: Sleesman. EXPLANATION OF VOTE: SLEESMAN: CMP I accepted this proposal contingent upon CMP 11 acceptance of a proposal to delete "rated in HP" from Section 430-109. That proposal was NOT accepted by CMP 11. Log # 506 I - 78 - (Article lO0-Tap, Service, Feeder, Branch Circuit-(New)): Reject SUBMITTER: Joseph E. McCann, City of Coral Springs, FL ~ATION: Article lO0-Tap, Service, Feeder, Branch Circuit-(New) SUBSTANTIATION: A clear cut definition or explanation of a tap, separating i t from a junction point or splice point. Does a tap necessarily mean a change in wire size from a point protected by a larger size O.C.P? PANEL ACTION: Reject. PANEL COMMENT: Proposal does not contain any proposed language. This is in violation of Section 10-10 of NFPARegulations Governing Committee Projects. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 477 I - 82 - (110-xx): Reject SUBMITTER: David J. Snitzer, City of Los Angeles, CA RECOMMENDATION: 110-xx Tests. All wiring shall be .free from short-circuits and grounds and shall be tested for these defects prior to being connected to the circuit. SUBSTANTIATION: The provision for wiring to be free from short-circuits and grounds should be a general provision which would include wiring for appliances, motors, etc., and not be limited to Article 410, which applies only to lighting fixtures, l ampholders, lamps, receptacles, and rosettes. PANEL ACTION: Reject. PANEL COMMENT: Already covered by Section 110-7. VOTE ON PANEL ACTION: Unanimously Affirmative. COMMENTON VOTE: SUMMERS: Although the concept is covered by Section 110-7, the mandatory aspect of testing is not. In spite of the recognized desirability of testing prior to connection, the legal l i a b i l i t y to authorities enforcing the Code should not be overlooked. Log # 685 I - 79 - (Article lO0-Volatile Flammable Liquid): Reject Secretary's Note: I t was the action of the Correlating Committee that this proposal be referred to CMP 14 for comment. SUBMITTER: Dr. R. Y. Levine, Technical Committee on Electrical Equipment in Chemical Atmospheres RECOMMENDATION: Delete: Existing definition for 'Volatile Flammable Liquid.' Replace With: 'Flammable Gas: A gas which will burn either alone or when mixed in any proportion with air, oxygen, or other oxidizer.' 'Flammable Liquid: A liquid having a flash point of less than lO0°F (37.8°C), a vapor pressure not exceeding (276 kPa) ~0 psia at 38°C (lO0OF), and is defined as a Class I flammable liquid by NFPA No. 321, Standard on the Basic Classification of Flammable and Combustible Liquids, 19xx; or Class I I or Class I l l combustible liquids as defined in NFPA No. 321 and heated above the liquids flash point. SUBSTANTIATION: Although the change made in the 1980 Code i~Droved previous definitions, the present definition does not agree with many other widely used NFPA Standards (e.g., Flammable and Combustible Liquids Code). The above wording provides proper and consistent definitions for the terms used in Chapter 5 of the Code. This improved consistency will f a c i l i t a t e interpretation of other NFPA Standards which rely on the NEC for electrical installation requirements (e.g., NFPANos. 30, 58, etc.). The proposed wording also corrects the present definition and recognizes flammable gases and Class I l l liquids directly. In particular, Class I I - 8 liquids are specifically excluded from the Code. PANEL ACTION: Reject. PANEL COMMENT: The change in definition mandates a change in Code requirements under the jurisdiction of CMP 14. Therefore, the proposal is referred to CMP 14 with the suggestion that i t be correlated with NFPA 30. VOTE ON PANEL ACTION: AFFIRMATIVE: 8 NEGATIVE: Summers. EXPLANATION OF VOTE: SLUMMERS: The Panel Action should have been "Accept" and refer to CMP 14 for comment. Log # 305 I - 83 - (110-3(a)(4)): Reject SUBMITTER: H. C. Taylor, Rio Rancho, NM RECOMMENDATION: Revise to read: Electrical insulation, of what ever type, when used for conductor insulation, whether single or multiple assembled shall be nontoxic. The effective date of this requirement shall be January 1st, 1990 or earlier i f possible. SUBSTANTIATION: With the on-set of plastics taking place of the older type of insulations and their ease and workability of application, no realization of the t o x i c i t y of these materials seemingly was apparent. Several fires and lives later this truth is now evident. I t now seems some definitive action should be initiated to correct this situation as early as possible. A suggested date is indicated to give sufficient lead time for the development of a chemical neutralizer to our present plastics, or the development of new insulation. PANEL ACTION: Reject. PANEL COMMENT: Almost all insulations are toxic to some degree. Contrary to what the substantiation indicates even older insulations could be a source of toxic conditions. Under instructions of the NFPA Board of Directors, a study on t o x i c i t y is presently being carried out. Therefore, neither the Panel nor the proposer are in a position at the present time to make a judgement. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 1451 I - 84 - (110-3(a)(8)): Reject Secretary's Note: The Correlating Committee directs that this proposal be referred to the NFPA Committee on Air Conditioning for comment. SUBMITTERS: Leo Witz, Continental Electrical Co. Hogan, Chicago, IL Fred Smith, Elgin, IL Jim Meehan, New Haven, CT. Anton Ganje, North Dakota Kenny Gebert, Minneapolis, MN Bill Conrardy, The Conrardy Co. Robert P. Brooks, Chicago, IL Paul Moore, Paducah, KY Les Rinder, Chicago, IL Homer M. Lefler, Chicago, IL John W. Erickson, Boltswitch, Inc. RECOMMENDATION: Amend Section 110-3(a)(8) so as to read as follows: "(8). All other factors which may contribute or can be expected to contribute to the practical safeguarding of persons using, contacting or exposed to such equipment or the results of heating or overheating of said equipment under normal or abnormal conditions."ISUBSTANTIATION: Section 90-1 indicates that the sole purpose of the NEC is the practical safeguarding of persons or property from the hazards arising from.the use of e l e c t r i c i t y . Section 110-3 l i s t s the characteristics of electrical equipment that are to be evaulated in order to assure the practical safeguarding of the people and the property for whom we are ARTICLE 110 -- REQUIREMENTS FOR ELECTRICAL INSTALLATIONS Log # 2085 I - 80 - (Article 110): Reject SUBMITTER: Richard Reddy, Reddy Electric Company, Inc. RECOMMENDATION: The complete elimination of all concentric knockouts in panels, pull boxes, gutters and motor junction boxes or any other electrical enclosure. SUBSTANTIATION: Seven-eighths inch knockouts could be spaced in all enclosures to allow for punching the required size hole. With the ease that holes can be punched today this should present no problem on any construction job. PANEL ACTION: Reject. PANEL COMMENT: The proposal is not directed to any specific Code section and therefore does not meet Section 10-10 of the NFPA Regulations Governing Committee Projects. There is no substantiation provided for such elimination. VOTE ON PANELACTION: Unanimously Affirmative. 13 Log # 2086 1- 81 - (Article 110): Reject SUBMITTER: Richard Reddy, Reddy Electric Company, Inc. O R~ A T I O N : Eliminate reducing washers. SUBSTANTIATION: Instead use a reducing bushing threaded inside and out that could be secured in the hole with a locknut and the pipe size f i t t i n g screwed into the bushing. This would require the manufacture of reducing bushings with a shoulder on one side similar to those used by the plumbing industry, instead of the ones currently being used in the electrical industry where the thread is straight all the way across the bushing. PANEL ACTION: Reject. PANEL COMMENT: See Panel Action and Comment on Proposal 1-80. VOTE ON PANEL ACTION: Unanimously Affirmative. PANEL COMMENT: The Panel Action is conditional upon acceptance of this proposa! by CMP 11. VOTE ON PANELACTION: AFFIRMATIVE: 8 NEGATIVE: Sleesman. EXPLANATION OF VOTE: SLEESMAN: CMP I accepted this proposal contingent upon CMP 11 acceptance of a proposal to delete "rated in HP" from Section 430-109. That proposal was NOT accepted by CMP 11. Log # 506 I - 78 - (Article lO0-Tap, Service, Feeder, Branch Circuit-(New)): Reject SUBMITTER: Joseph E. McCann, City of Coral Springs, FL ~ATION: Article lO0-Tap, Service, Feeder, Branch Circuit-(New) SUBSTANTIATION: A clear cut definition or explanation of a tap, separating i t from a junction point or splice point. Does a tap necessarily mean a change in wire size from a point protected by a larger size O.C.P? PANEL ACTION: Reject. PANEL COMMENT: Proposal does not contain any proposed language. This is in violation of Section 10-10 of NFPARegulations Governing Committee Projects. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 477 I - 82 - (110-xx): Reject SUBMITTER: David J. Snitzer, City of Los Angeles, CA RECOMMENDATION: 110-xx Tests. All wiring shall be .free from short-circuits and grounds and shall be tested for these defects prior to being connected to the circuit. SUBSTANTIATION: The provision for wiring to be free from short-circuits and grounds should be a general provision which would include wiring for appliances, motors, etc., and not be limited to Article 410, which applies only to lighting fixtures, l ampholders, lamps, receptacles, and rosettes. PANEL ACTION: Reject. PANEL COMMENT: Already covered by Section 110-7. VOTE ON PANEL ACTION: Unanimously Affirmative. COMMENTON VOTE: SUMMERS: Although the concept is covered by Section 110-7, the mandatory aspect of testing is not. In spite of the recognized desirability of testing prior to connection, the legal l i a b i l i t y to authorities enforcing the Code should not be overlooked. Log # 685 I - 79 - (Article lO0-Volatile Flammable Liquid): Reject Secretary's Note: I t was the action of the Correlating Committee that this proposal be referred to CMP 14 for comment. SUBMITTER: Dr. R. Y. Levine, Technical Committee on Electrical Equipment in Chemical Atmospheres RECOMMENDATION: Delete: Existing definition for 'Volatile Flammable Liquid.' Replace With: 'Flammable Gas: A gas which will burn either alone or when mixed in any proportion with air, oxygen, or other oxidizer.' 'Flammable Liquid: A liquid having a flash point of less than lO0°F (37.8°C), a vapor pressure not exceeding (276 kPa) ~0 psia at 38°C (lO0OF), and is defined as a Class I flammable liquid by NFPA No. 321, Standard on the Basic Classification of Flammable and Combustible Liquids, 19xx; or Class I I or Class I l l combustible liquids as defined in NFPA No. 321 and heated above the liquids flash point. SUBSTANTIATION: Although the change made in the 1980 Code i~Droved previous definitions, the present definition does not agree with many other widely used NFPA Standards (e.g., Flammable and Combustible Liquids Code). The above wording provides proper and consistent definitions for the terms used in Chapter 5 of the Code. This improved consistency will f a c i l i t a t e interpretation of other NFPA Standards which rely on the NEC for electrical installation requirements (e.g., NFPANos. 30, 58, etc.). The proposed wording also corrects the present definition and recognizes flammable gases and Class I l l liquids directly. In particular, Class I I - 8 liquids are specifically excluded from the Code. PANEL ACTION: Reject. PANEL COMMENT: The change in definition mandates a change in Code requirements under the jurisdiction of CMP 14. Therefore, the proposal is referred to CMP 14 with the suggestion that i t be correlated with NFPA 30. VOTE ON PANEL ACTION: AFFIRMATIVE: 8 NEGATIVE: Summers. EXPLANATION OF VOTE: SLUMMERS: The Panel Action should have been "Accept" and refer to CMP 14 for comment. Log # 305 I - 83 - (110-3(a)(4)): Reject SUBMITTER: H. C. Taylor, Rio Rancho, NM RECOMMENDATION: Revise to read: Electrical insulation, of what ever type, when used for conductor insulation, whether single or multiple assembled shall be nontoxic. The effective date of this requirement shall be January 1st, 1990 or earlier i f possible. SUBSTANTIATION: With the on-set of plastics taking place of the older type of insulations and their ease and workability of application, no realization of the t o x i c i t y of these materials seemingly was apparent. Several fires and lives later this truth is now evident. I t now seems some definitive action should be initiated to correct this situation as early as possible. A suggested date is indicated to give sufficient lead time for the development of a chemical neutralizer to our present plastics, or the development of new insulation. PANEL ACTION: Reject. PANEL COMMENT: Almost all insulations are toxic to some degree. Contrary to what the substantiation indicates even older insulations could be a source of toxic conditions. Under instructions of the NFPA Board of Directors, a study on t o x i c i t y is presently being carried out. Therefore, neither the Panel nor the proposer are in a position at the present time to make a judgement. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 1451 I - 84 - (110-3(a)(8)): Reject Secretary's Note: The Correlating Committee directs that this proposal be referred to the NFPA Committee on Air Conditioning for comment. SUBMITTERS: Leo Witz, Continental Electrical Co. Hogan, Chicago, IL Fred Smith, Elgin, IL Jim Meehan, New Haven, CT. Anton Ganje, North Dakota Kenny Gebert, Minneapolis, MN Bill Conrardy, The Conrardy Co. Robert P. Brooks, Chicago, IL Paul Moore, Paducah, KY Les Rinder, Chicago, IL Homer M. Lefler, Chicago, IL John W. Erickson, Boltswitch, Inc. RECOMMENDATION: Amend Section 110-3(a)(8) so as to read as follows: "(8). All other factors which may contribute or can be expected to contribute to the practical safeguarding of persons using, contacting or exposed to such equipment or the results of heating or overheating of said equipment under normal or abnormal conditions."ISUBSTANTIATION: Section 90-1 indicates that the sole purpose of the NEC is the practical safeguarding of persons or property from the hazards arising from.the use of e l e c t r i c i t y . Section 110-3 l i s t s the characteristics of electrical equipment that are to be evaulated in order to assure the practical safeguarding of the people and the property for whom we are ARTICLE 110 -- REQUIREMENTS FOR ELECTRICAL INSTALLATIONS Log # 2085 I - 80 - (Article 110): Reject SUBMITTER: Richard Reddy, Reddy Electric Company, Inc. RECOMMENDATION: The complete elimination of all concentric knockouts in panels, pull boxes, gutters and motor junction boxes or any other electrical enclosure. SUBSTANTIATION: Seven-eighths inch knockouts could be spaced in all enclosures to allow for punching the required size hole. With the ease that holes can be punched today this should present no problem on any construction job. PANEL ACTION: Reject. PANEL COMMENT: The proposal is not directed to any specific Code section and therefore does not meet Section 10-10 of the NFPA Regulations Governing Committee Projects. There is no substantiation provided for such elimination. VOTE ON PANELACTION: Unanimously Affirmative. 13 responsible. In view of the serious questions that have been raised, and which have not been answered, concerning materials that are con~nonly used in many different types of electrical equipment, i t is only reasonable that we respond to these questions in some positive manner. The inspector in the field cannot make these determinations! They must be made by the manufacturer and a qualified testing laboratory. We cannot answer the questions by dodging the issues! We the standards making people are morally and legally responsible to assure to the best of our a b i l i t y and knowledge that the standards we write and accept; the materials we accept or permit; are not in themselves creating a hazard for the people who use, contact or are exposed to them. Additional substantiation for proposals made by William P. Hogan et. al. on Sections: 110-3(a)(8), 230-43, 300-22(b), 300-22(c), 338-2, 338-3, 340-5, 344-2, 347-2, 351-2, 352-21 and 370-23. I t should be obvious that the thrust of all these proposals is the limitation or actual elimination of the use of those MATERIALS, which when exposed either to the environment, temperatures in excess of their ratings, whether from normal or abnormal causes, or flame emit toxic ~ases, fumes or harmful chemicals. For years the electrical industry has not only permitted but also has encouraged the use of materials that f a l l into this category. These materials do emit toxic gases and do result in harmful chemicals when exposed to the varying atmospheres experienced in everyday living. For instance, i t is not an unco~on phenomenon to observe hydrochloric acid dripping out of a rigid steel conduit in which PVC conductors have been exposed to temperatures higher than their ratings or flame and water has been used to control the source of that heat or flame. There are documented experiences of this reaction where the acid was eating through the switch enclosure. When the inspector attempted to catch the acid in a tin can so that he could have i t analyzed, i t ate right thru the can. What is startling about this phenomenon is the fact that we are told that the plastic people have known about i t for years and have never f e l t that this information should be publicized because the incidence weuld be so rare that i t was not worth alerting the electrical industry. In spite of their lack of concern many people in the industry and out of i t are aware of this possibility and t~e other ramifications of the decomposition of PVC and are deeply concerned. We are told over and over again that the amount of plastics and polyvinyl chlorides that are introduced in any building by the electrical installation is infinitesimal when compared with the total of all the other furnishings and building finishes. There are two errors in such statements. The f i r s t is corrected by the reports printed in Modern Plastics based upon the monthly Sales/Production report issued by SPI's Committee on Resin Statistics. According to their figures, published in January of 1981 there were 3,581,000 tons of resins converted into building materials in 1979. Of that 1,114,000 tons were PVC Conduit. Is that to be considered infinitesimal? The figures for 1980 are Just as revealing; 3,078,000 tons total, 938,000 tons in PVC Conduit. In addition to that there were 841,000 tons of resins converted into electrical/electronic plastics in 1979 of which 195,000 tons were PVC. Likewise, in 1980 out of a total of 736.000 tons, there were 177,000 tons of PVC. These are NOT infinitesimal fractions! The second error is the attempt by the people, who spew forth this falacious claptrap~ to hide the fact that we, who are responsible for formulating the National Electrical Code, have one prlme responsibility, the safety of the people. We are completely and solely responsible for the electrical installation. We and only we must bear the responsibility for what is in the NEC. We are not in any, shape or form responsible for the furnishings nor the building finishes. Regardless of what others may introduce into the building, we are s t i l l responsible for those things that we permit or require in the electrical installation. We can never loose sight of the prime purpose of the NEC, " . . . t h e practical safeguarding of persons and properly from the hazards arising from the use of e l e c t r i c i t y . " For many years a great number of knowledgeable and highly respected people in the scientific world have been aware of the fact that the use of certain materials and wiring methods, which by the very nature of their chemical composition, are certain to add significantly to the toxic gases and harmful chemicals in any f i r e situation. I t has been and s t i l l is their contention that the use of these materials should be curtailed or prohibited. We can no longer afford the luxury of sitting back waiting for someone else to take the f i r s t step. We cannot hide behind a disclaimer saying we know nothing about t o x i c i t y . I f we don't know, i t is because we haven't taken the time to read what is available on the subject or listen to what is being said from every direction. The numbers of people being killed in recent fires is staggering. The ratio of f i r e deaths to f i r e damage is astounding. I t is completely out of line with historical f i r e data. The number of people died 20 stories away from the closest flame in the MGM is unforgiveable. The number of people who died in that building after the f i r e was out, but while the hallways and stairwells were f u l l of toxic gases and smoke will never be known, but the fact that many did is additional reason for us to act. We cannot wait until other standards~writing bodies take the lead. We cannot wait until slow moving committees bring in the BODYCOUNTS! We can no longer ignore the warnings that have been made public in the form of test results from widely divergent groups, government, industry, scholastic and testing f a c i l i t i e s . Here is what just a few highly regarded scientists have to say about this matter: A report compiled by the Uniformed Firefighters Association in 1980 five years after the telephone company f i r e shows that of the 194 firefighters who received medical treatment at the time of the f i r e 71 reported permanent respiratory ailments. The unprotected cables that burned in that f i r e produced "billowing clouds of hydrogen chloride smoke." (American Lung Association Bulletin, (81)). "Large amounts of hydrogen chloride gas (HCL) are released by either HEATING or BURNINGPVC".* "In the case of a rapid electrical overload in PVC insulated wire, smoke which is usually the f i r s t indication of f i r e , is only noticeable AFTER significant quantities of HCL have been released." * "Calculations show that for 100 pounds of PVC pyrolyzed (chemically decomposed by heat) in an apartment 8 feet X 25 feet X 50 feet (10,000 cubic feet) a concentration of HCL as high as 57,385 ppm could be reached, about 57 times the concentration that will cause lung edema on very short exposure.W* Referring to the MGMf i r e deaths the Clark County Coroner-Medical Examiner reports, "The fact that the concentration of carboxyhe~w)globin in most of the victims was not high enough to have caused death indicates that other toxic gases or smoke particles MUSTalso have been involved." * (carboxyhemeglobin is the result of carbon monoxide in the blood). • A Literature Study of the Combustion Hazards of PVC and ABS. Judith E. Hall and Eric L. Tolefson, University of Calgary. In a discussion concerning the Beverly Hills Supper Club Fire, Deborah Wall ace, who is a Toxicologist and the President of Public Interest Scientific Consulting Service states the following about the causes of death at that f i r e , " - - - , the carboxyhemoglobin levels found during the autopsies showed that all assayed victims but one had concentrations well below lethal levels. Manywere as low as 10%." Yet they all died of something that they inhaled. There was a tremendous amount of PVC in that building! Jay A. Young, Ph.D., a Chemical Consultant has this to say, "Structural disintegration of PVC Conduit in a f i r e situation. Such disintegration allows the release of hydrogen chloride or phosgene, or both, formed from the decomposition of PVC insulation on the wiring inside, the conduit and confined inside the conduit until the conduit disintegrates." "The thermal decomposition of PVC has been observed at temperatures below 100 degrees C, although most studies show that the evolution of HCL in significant amounts requires temperatures of about 200-300 degrees C. That is, long before the PVC has reached the temperature at which i t will burn, well in advance of the time when any combustible structural components near PVC conduit weuld be likely to be burning in a f i r e situation." Dr. Young further states, "Hydrogen Chloride is an i r r i t a t i n g gas At concentrations in air as low as 5ppm, i t causes choking in most people." Dr. Young continues, "Concentrations of 100ppm are rated as, "Immediately dangerous to l i f e and health" by OSHAand the National Institute for Occupational Safety and Health. Unless removed immediately from an atmosphere containing a concentration of 100ppm death by suffocation will follow." There are no less than 132 books, papers and articles available to you on this subject. You can rest assured that each will point out the t o x i c i t y of the products of combustion of PVC and of the t o x i c i t y of HCL which is produced simply by heating PVC Conduit or insulation. You may be able to ignore this information, but we can not. As far as we are concerned, the facts are in front of you and you must act. We have, - with these proposals. The problem is not going to go away by i t s e l f . Nor is i t going to lessen in intensity. You can be absolutely sure that i t and you will be in the public eye and in every form of mass news media as long as people are killed in fires. I t will make headlines and bring more and more court cases, which will further highlight the shortcomings of the Code. I t seems to be a foolish course of action, or is i t INACTION, to wait until public furor forces us change. I f we in NFPAthrough the NEC i n i t i t a t e the act, we at least retain the respect and confidence of the people we serve. I f we do not, you can be assured that those same people will have no respect for this organization or us. I t is f u t i l e to deny, or attempt to minimize, the presence of the harmful chemicals in the materials used to manufacture insulations and raceways that not only can, but do, emit toxic gases in amounts sufficient to cause instantaneous paralysis when exposed to temperatures in excess of their ratings, or f i r e . The peaceful attitudes of so many of their victims is grim testimony to the speed of these k i l l e r s and the fact that the victims were t o t a l l y unaware of their impending fate. Our proposals are intended to minimize or eliminate the exposure of human beings to this peril. Note: I t is most important to understand that this proposal is not intended to do away with a l l , nor any, nonmetallic wiring method. This proposal and all others like i t that we have submitted for the 1984 edition of the NEC are intended to eliminate the MATERIALSwhich emit toxic fumes or gases under various conditions of use. I t is our opinion that the manufacturers of this equipment or these MATERIALSmust prove that their products do NOT emit toxic gases or harmful chemicals under the conditions specified. I t should not be the responsibility of the NFPA nor any Code-Making Panel to perform the tests or make the investigations that are needed to prove the presence of the toxic gases, fumes or harmful chemicals. PANEL ACTION: Reject. 14 Log # 227 i - 86 - (110-9): Reject SUBMITTER: H. K. Glenn, Pacific Coast Electrical Association, Inc. RECOMMENDATION: Amend 110-9 to read: Interrupting Rating: Switches, circuit breakers and fuse assemblies intended to break current at fault levels shall have closing, momentary and/or interrupting ratings sufficient for system voltage and the current which is available at the line terminals of the equipment. Switches, circuit breakers and fuse assemblies intended to break current other than at f a u l t levels shall have an interrupting rating at system voltage sufficient for the current that must be interrupted. SUBSTANTIATION: The present wording does not cover closing and momentary ratings as covered in Section 710-21. These ratings should be required on low as well as high-voltage equipment in order to assure safe operation of the equipment. Low voltage switches and breakers can and have blown up when closing into high current faults. PANEL ACTION: Reject. PANEL COMMENT: Not all devices that have interrupting ratings need closing ratings. Fuses are one example. The proposed section gives two additional alternatives that could result in equipment without adequate interrupting ratings. VOTE ON PANEL ACTION: AFFIRMATIVE: 8 NEGATIVE: Hart. EXPLANATION OF VOTE: HART: I do not believe that this Panel Action and Panel Comment are responsive to the proposer as stated in his substantiation. I would suggest that the Panel review the second paragraph of the substantiation and reconsider this action. PANEL COMMENT: The proposal adds no new material to the Code, but only combines paragraphs (5) and (8) under Section 110-3. The issue of t o x i c i t y as discussed in the substantiation is being studied by NFPA and the Panel is awaiting the results of that study. VOTE ON PANEL ACTION: Unanimously Affirmative. COMMENTON VOTE: PALKO: I vote for rejection, but I do not concur with the Panel's reason given for rejection. This proposal should be rejected because i t conflicts with the opening sentence of the Code, and because of invalid substantiation. Section 90-I(a) states "The purpose of this Code is the PP~ACTICAL safeguarding of persons and property arising from the USE OF ELECTRICITY. Substantiation submitted with the proposal indicates that the intent of the proposal is to outlaw the use of all materials in all electrical equipment that have not been proven to not emit toxic fumes when subjected to heat or flame from any cause--whether electrical or nonelectrical. The substantiation does not corroborate that any of the cases cited resulted from the USE OF ELECTRICITY, and is therefore ~ot pertinent to the proposal. The proposal further conflicts with Section 90-I(a) in that i t is not PPJ&CTICAL; its adoption and subsequent enforcement would be tantamount to shutting down the country. I f this proposal were adopted--and its intent as indicated in the substantiation were achieved--every electrical product currently available would have to undergo testing before its installation were permitted. A few products such as steel and aluminum conduit and bare bus bar would pass the test; possibly 99 percent of the products now in use would not. Substitute products could not be introduced until after they passed the "ordeal by f i r e . " The proposal is further impractical in .that i t suggests no alternative materials to those now in common use. Are we to revert to only paper and varnished cambric conductor insulation? What assurance have we that these materials will not be considered to be toxic, inasmuch as t o x i c i t y is undefined in the proposal? What materials will replace the materials now used for bus insulation and in relays, motor starters, and common wall switches and receptacles? Who defines t o x i c i t y for NEC purposes? What are the constituent elements or chemical compounds present in toxic fumes? Who prescribes how much heat a material must be able to withstand without emitting toxic fumes? I f a definition of toxocity existed for NEC purposes, who defines acceptable levels? I f acceptable levels were defined, who prescribes acceptable quantities? Would the fumes emitted by a single burning wall receptacle be acceptable? What about 10 receptacles in the same room? What i f the size of the room were quadrupled? To cite that the proposal is already covered in paragraphs (5) and (87 of Section 110-3 begs the issue; the proposer apparently feels that i t is not. The outcome of a t o x i c i t y study is also not needed to determine that this proposal is not within the purview of the NEC. Its admirable intent should be pursued via other codes. Log # 1354 i - 87 - (110-9, FPN-(New)7: Reject SUBMII-TER: Melvin K. Sanders, Ankeny, IA RECOMMENDATION: Add a Fine Print Note: See 230-98 for service equipment. SUBSTANTIATION: Manytimes the interrupting rating requirement is treated as an isolated incident and there is a lack of awareness of the fact that fault levels and short-circuit current references concern themselves with the same problem. PANEL ACTION: Reject. PANEL COMMENT: Section 110-9 applies to equipment that is intended to interrupt current at fault levels and those that interrupt current at other than fault levels. Section 230-98 only applies to fault current levels for service equipment and a cross-reference would be misleading. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 1504 1- 88 - (110-9, FPN-(New~): Reject SUBMI~ER: Melvin K. Sanders, Ankeny, IA RECOMMENDATION: Add Fine Print Note ~fter the f i r s t paragraph: See Section 240-60(b) for use of current limiting fuses. SUBSTANTIATION: This is proposed in order to assure that equipment prohibiting insertion of noncurrent-limiting fuses will be used when i t is necessary to make use of their characteristics to protect downstream equipment. Many installations are completed with current-limiting devices installed and upon replacement there is nothing to prevent incorrect substitution. PANEL ACTION: Reject. PANEL COMMENT: There is no logical connection between interrupting ratings and the requirements of Section 240-60(b) that prohibits the insertion of noncurrent-limiting fuseholders. Equipment with high interrupting ratings are not necessarily current-limiting. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 1583 1- 85 - (110-5): Reject SUBMITTER: Peter Pollak, The Aluminum Association, Inc. RECOMMENDATION: "Conductors normally used to carry current shall be of copper or aluminum unless otherwise provided in this Code." (Remainder of Section unchanged.) SUBSTANTIATION: Questions have arisen in the field from Inspection authorities and the contracting trade regarding the specific recognition of aluminum conductors by the National Electrical Code. There is need for clarification concerning the recognition of aluminum conductors throughout the code. Individual panels changed the following sections of the 1981 Code to c l a r i f y the proper use of aluminum conductors: 210-19b 250-155 215-2A 250-22 215-2B 310-21b ) 225-6(a) 318-2(b7(i) 250-23b 318-8 250-60b 318-9 250-92a 339-i(a) 250-93c 250-94 Exception - Nos. 1 & 2 This proposal would effectively not change any section of the Code but instead would help Code readers to determine the proper use of aluminum conductors where already permitted throughout the Code. Finally i t should be noted that the second sentence of Section 110-5: "Where the conductor material is not specified, the sizes given in this Code shall apply to copper conductors" will remain unchanged. PANEL ACTION: Reject. PANEL COMMENT: The substantiation indicates that the Code-Making Panels made changes where Section 110-5 did not apply and for this reason no further change is necessary. VOTE ON PANEL ACTION: Unanimously Affirmative. Log m 323 1- 89 - (110-117: Reject SUBMII-TER: RaymondT. Vasoli, Vasoli Electric Co. Inc. RECOMMENDATION: All outdoor equipment rated at 440 volts or more mall be constructed to be rodent-proof. SUBSTANTIATION: Rodents entering high voltage gear and causing power outages. PANEL ACTION: Reject. PANEL COMMENT: The proposed revision is an inappropriate design consideration for outdoor equipment over 440 volts. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 372 1- go - (110-12): Reject SUBMII-TER: Bruce A. Weaver, Sioux City, IA RECOMMENDATION: Additional paragraph: "All flush mounted, snap switch and receptacle faceplates to be installed so as to completely cover the wall openings and seat against the wall surface-in compliance with Sections 380-9 and 410-56(c7." 15 option of lower construction cost with increased f i r e risk. 2. insisting that aluminum be made as safe as copper and giving the appearance of a pro-copper sentiment. PANEL ACTION: Reject. PANEL COMMENT: Other suitable alternatives are available. The submitter's substantiat~oh is both confusing and lacking in any data to warrant acceptance of the proposal. VOTE ON PANELACTION: Unanimously Affirmative. SUBSTANTIATION: Since faceplates are often installed in violation ot "a neat and workmanlike manner" I propose this addition to the Code while leaving the other two sections untouched. The item of faceplates can be d i f f i c u l t to find, especially to newcomers in the Code. PANEL ACTION: Reject. PANEL COM~NT: Already covered in appropriate sections of the Code. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . Log # 1782 1- 96 - (110-14): Reject SUBMITFER: Leo F. Martin, Paul Revere Chapter IAEI RECOMMENDATION: In the last sentence, delete the word "installation" and replace with "conductor insulation." Text will then read, ....adversely effect the conductors, conductor insulation, or equipment. SUBSTANTIATION: "Insulation" appears to have been intended. The present word "installation" is vague and is redundant to the word "equipment." PANEL ACTION: Reject. PANEL COMMENT: The present text already covers the insulation within the use of the term "conductor." VOTE ON PANELACTION: Unanimously Affirmative. COMMENTON VOTE: HART: Although I have voted on the affirmative on Proposal 1-96, I have done some research and found that the f i r s t printing of this section, which was in the "Preprint" of the Proposed Amendments for the 1965 NEC, used the word "installation" and not "insulation." There is, of course, the possibility that the Panel had 4ntended to say "insulation" but I would doubt i t . The chairman of the Panel at that time was Howard Michener, who made very few, i f any, errors of this type. I also noted that in the Walter Stone editorial revision, there was no recommendation.for a change in this section. Log # 346 I - 91 - (110-12): Reject SUBMITTER: DougWarner, Sheldon, IA ~ATION: Delete the section as follows: Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases or housings shall be effectively closed to afford rotection substantially equivalent to the wall of the equipment. UBSTANTIATION: I believe that this part added to Section 110-12 detracts from its meaning and is relatively unassociated with the idea the section is trying to convey. Also much of the s~ction is stated in other sections such as unused openings in boxes and f i t t i n g s , Section 370-8, and unused openings in cabinets or cutout boxes, Section 373-4. The whole Code is based on Section 110-12 so I think i t should be as clear and clean cut as possible. PANEL ACTION: Reject. PANEL COMMENT: The present wording of Section 110-12 does relate ~o tee mechanical execution of work and Sections 370-8 and 373-4 do not cover all of the necessary equipment. VOTE ON PA~NELACTION: Unanimously Affirmative. ~ Log # 354 1- 92 - (110-12): Reject SUBMITTER: Michael Weeks, Sheldon, IA RECOMENDATION: Omit-Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases or housings shall be effectively closed to afford protection substantially equivalent to the wall of the equipment. SUBSTANTIATION: This has nothing to do with electrical work being installed in a neat and workmanshiplike manner. -PANEL ACTION: Reject. PANEL COMMENT: See Panel Action and Comment on Proposal 1-91. VOTE ON PANELACTION: Unanimously Affirmative. Log # 1783 1- 97 - (110-14): Reject SUBMITTER: Leo F. Martin, Paul Revere Chapter IAEI RECOMMENDATION: Add new paragraph as follows: Inhibitor, and application thereof, identified for the purpose shall be used on all aluminum conductors of sizes No. 8 AWG and larger, at all points of termination and on all splices regardless of the type of termination used. SUBSTANTIATION: Listed inhibitors will provide for a better termination of aluminum conductors. PANEL ACTION: Reject. PANEL COI~MENT: No supporting information has been supplied to show that inhibitors are necessary in every case nor that i t is an improvement for all devices and connections. VOTE ON PANELACTION: Unanimously Affirmative. Log # i67 1- 93 - (110-12): Reject SUBMITTER: Dave Williams, Sheldon, IA ITE'L~Q~IT~ATION: Last paragraph of Section 110-12 be deleted. SUBSTANTIATION: The last paragraph of Section 110-12 doesn't belong under 3ection 110-12. Unused opening is clearly defined in Section 370-8. The f i r s t sentence of Section 110-12 should stand as is and no other statement need be required. PANEL ACTION: Reject. PANEL COMMENT: See Panel Action and Comment on Proposal 1-91. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 95 1- 98 - (110-14): Reject SUBMITTER: Joseph S. Pangborn, F. N. Zaino & Associates RECOMMENDATION: Add the following to the end of the f i r s t paragraph: ". . . . . , or equipment." "An OXIDE INHIBITER, and application thereof, approved for the purpose shall be used on all aluminum conductors of sizes number 8 AWG and larger at all points of termination and on all splices regardless of the type of termination used." Add the following sub-paragraphs (c), (d), and (e) after sub-paragraph (b): (b) Splices. Conductors. . . . . . . . . . . . purpose. (c) Terminations. Terminal lugs and supply connectors used with aluminum conductors for circuits with connected loads of 35 amps and larger shall be all aluminum bodied and UL listed AL/CU or CO/ALR. Retaining screws in aluminum mechanical connectors indirect contact with the conductor shall be aluminum or brass. Setscrews of mechanical connectors shall entrap all the strands of the conductor by means of a saddle or similar device. (d) Conductor Connections. Aluminum conductor connections to equipment terminals not marked AL/CU or CO/ALR shall be made with a special adapter approved for that purpose or by pigtailing to a short length of copper conductor with an approved compression connector. (e) Lug Connections. Aluminum lugs shall be connected to aluminum bus with aluminum bolts, and heavy f l a t washers, or with steel bolts, heavy f l a t washers and belleville spring washers. Connections of aluminum terminal lugs to copper bus shall be made with cadmium plated steel bolts, heavy f l a t washers and Belleville washers. Aluminum lug connections to equip~!~ent pads having copper studs shall employ f l a t washers and Bellev111e washers. SUBSTANTIATION: By inserting these sections, i t will define the requirement for properly terminating aluminum conductors which i f improperly terminated, are the major causes of electrical fires. PANEL ACTION: Reject. PANEL COMMENT: The proposal contains no substantiation to show that oxide inhibitors are necessary or even desirable for every type of termination device. The proposal also contains extensive specification-type information that is in conflict with Section 90-1(c). VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 1499 1- 94 - (110-12): Reject SUBMII-FER: Ra)nnond P. Pelletier, Auburn, ME ~ATION: Add 3rd paragraph to read: When using nonmetallic wiring methods, care should be taken not to cause injury by f r i c t i o n . SUBSTANTIATION: On one installation comprising of 43 four room apartments 12 damaged cables were found and replaced. See enclosed photos. i . One 14-3 NM cable with ground. CATV lead wire in the same hole in the 2 X 4 inch stud. 2. CATVwire removed showing damaged NM cable cover. 3. 14-3 NM removed for closer observation. 4. Shows the extent of the damage. Friction damaged the cover and insulation down to the copper conductor. NOTE: (Copy of the enclosed photos are available from NFPAon request.) PANEL ACTION: Reject. PANEL COMMENT: This proposal only points out one of many unworkmanlike practices. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 208 1- 95 - (110-14): Reject SUBMII-FER: Alexander M. Stevens, A. M. Stevens & Assoc. RECOMMENDATION: That the termination of all aluminum conductors be required in high press type connections specifically approved for the purpose intended and that the construction job is performed according to the manufacturer's instructions. SUBSTANTIATION: The problem with high resistance connections with aluminum wires is nothing new. The problem, however, is not very well addressed in the 1981 Code. The question boils down to which of the following alternatives is preferable: 1. giving the IB Wire Size 18-16 AWG 14-8 6-4 3-I 0-2/0 3/0 AWG-200 MCM 250-350 400 500 600-750 800-1,000 1,250-2,000 Log # 1835 i - 99 - (llO-14(a)): Reject SU~MII-FER: Paul E. Phelan, Trade Education Inc. and New Hampshire ~ l Contractors Inc. RECOMMENDATION: Add, either as part of Section 110-14(a) or create a Section 110-14(c) to advise that certain terminations are suitable only for 60°C loading of conductors and olhers suitable only for the 75°C loading of conductors. SUBSTANTIATION: I don't believe that more than one person in 100. is aware of this restriction on termination temperatures, including authors of several texts. I realize that Section 110-3(b) should lead one to the UL Green Book, but i t just doesn't happen. PANEL ACTION: Reject. PANEL COF~MENT: Material not suitable for inclusion in Section 110-14. The proposal does not contain the specific text and therefore does not comply with Section 10-10 of NFPARegulations Governing Committee Projects. VOTE ON PANEL ACTION: Unanimously Affirmative. Driver Bolt 1.67 6.25 1.67 6.25 3 12.5 4.2 21 4.2 29 37.5 50 62.5 62.5 75 83.25 83.25 Other 4.2 6.25 8.0 10.4 12.5 17 21 21 25 25 33 42 Screws Screw Size Inches Across Hex Flats 1/8 5/32 3/16 7/32 1/4 Log # 183 1- 100 - (110-14(a) and (b)): Reject SUBMITTER: Archie W. Brown, Phoenix, AZ ~ATION: (a) Terminals. Connections of conductors to terminal parts shall insure a thoroughly good connection without damaging the conductors. Copper conductors shall be terminated by means of pressure connectors (including set-screw type), solder lugs, or splices to flexible leads. Aluminum and copper clad aluminum conductors shall terminate in compression lugs or shall be spliced to copper pigtails with compression connectors. Exception: Connection of copper conductors by means of wire binding screws or studs and nuts having upturned lugs or equivalent shall be permitted for No. 10 or smaller conductors. Terminals for more than one conductor and terminal lugs used to connect aluminum conductors to studs and nuts shall be of a type approved for the purpose. (b) Splices. Copper conductors shall be spliced or joined with splicing devices suitable for the use or by brazing, welding, or soldering with a fusible metal or alloy. Soldered splices shall f i r s t be so spliced or joined as to be mechanically and electrically secure without solder and then soldered. Aluminum conductors shall be spliced by means of compression connectors. All splices and joints and the free ends of conductors shall be covered with an insulation equivalent to that of the conductors or with an insulating device suitable for the purpose. SUBSTANTIATION: Aluminum wire and cable have a hi~her coefficient of expansion than copper. As i t heats up due to I:R loss i t expands or flattens i f confined by mechanical connectors. When i t cools i t contracts resulting in less pressure of contact. Aluminum wire when cleaned and l e f t exposed to the atmosphere quickly develops a non-conducting oxide film. Expansion and contraction and the oxide film can result in increased terminal or j o i n t electrical resistance and heating. Increased contact resistance can result in electric arcing and burning of insulation. Compression connectors and compression lugs of the proper size, design and material for use with aluminum and/or copper conductors and applied with tools approved for the purpose, provide solid joints which do not deteriorate due to expansion, contraction or the development of oxide film. Copper pigtails joined to aluminum conductors which have been freshly cleaned of oxide film, provide a termination much less prone to develop increasing resistance and overheating than aluminum conductors terminated at wire-binding screw posts, studs and nuts, set screw connectors or screw-on connectors for splicing to flexible leads. The merits of terminating aluminum conductors with copper pigtails and compatible compression connectors have been recognized and recommended by aluminum wire manufacturer Kaiser Aluminum and by the Consumer Product Safety Commission. PANEL ACTION: Reject. PANEL COMMENT: I t is not the intent of the Panel to rule out the use of properly designed connectors identified for use with copper and/or aluminum conductors. VOTE ON PANEL ACTION: Unanimously Affirmative. Torque Pound-Feet 4.2 8.3 15 23.25 42 Bolts Size Duronze Nonlubricated 3/8 20 1/2 40 5/8 70 3/4 100 Standard Steel Aluminum High Strength Steel 15 25 50 90 16 40 70 100 16 35 50 70 Lubricated 3/8 15 10 13 13 1/2 30 20 25 30 5/8 50 40 40 50 3/4 85 70 60 80 SUBSTANTIATION: We have all experienced electrical failures because of poor mechanical connections. All t e s t i n g , and especially that testing done with aluminum wire in the 12-10 AWG sizes, indicates that torqued connections are b e t t e r . Enforcing would not be as hard as enforcing interrupting r a t i n g . A f t e r a l l , the amount of torque can be checked. We must do everything possible to make better mechanical connections. This w i l l c e r t a i n l y help by making sure the device i n s t a l l e r s torque those connections. These are the values which seem to be used by all equipment and device manufacturers. They are even providing f o r torquing, especially f o r bus-ducts. These are the values used by UL f o r testing lugs, etc. PANEL ACTION: Reject. PANEL COMMENT: The proposal is adequately covered in Section 110-3(b). VOTE ON PANEL ACTION: AFFIRMATIVE: 8 NEGATIVE: Seelbach. EXPLANATION OF VOTE: SEELBACH: Although the proposal has technical problems (see Proposal 1-125), I am voting against the action to reject to point out the need for the Code to specifically address this important matter. While the requirement is in fact covered by Section 110-3(b), tightening torques marked on equipment or terminations are new and attention needs to be directed to this change. Even a FPN stating "Many terminations and equipment are marked with a tightening torque" would help. Log # 1784 1- 102 - (110-14(c)-(New)): Reject SUBMIi-FER: Leo F. Martin, Paul Revere Chapter IAEI RECOMMENDATION: Add new paragraph as follows: (c) Terminal Lugs and Connectors. Terminal lugs and connectors directly connected to aluminum conductors shall be listed and marked AL/CU. Exception: As provided by Sections 380-14(c) and 410-56(g). SUBSTANTIATION: Field conditions show that aluminum conductors are being connected to equipment with improper lugs and connectors. PANEL ACTION: Reject. PANEL COMMENT: This type of information is suitable for listing and labeling agencies and is not necessary in the Code. The markings referenced in the proposal should be permitted to be located on the equipment in which the terminal is used. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 253 1- 101 - (110-14(c)-(New)): Reject SUBMITTER: C. E. Muhleman, Marion, IN ~ATION: Mechanical connections in circuits IOOA and larger shall be torqued to the values given in Table 110-14(c). I t is suggested that all other mechanical connections be torqued. Table 110-14(c) Torquing Connections The following table shall be used as a guide for all electrical connections of No. 8 AWG wire size and larger, and all bolted or Allen screwed connections. Torquing Values-Copper Connections Wiring Connections Tightening Torque In Pound-Feet Screw Split Log # 1734 1- 103 - (110-16): Reject SUBMITTER: Charles "Mike" Holt, Concepts in Electricity Inc. RECOM~NDATION: 110-16. "Standing" Working Space About Electric Equipment (600 volts, nominal, or less). "Sufficient access and standing working space shall be provided..." 110-16(a). "Except as elsewhere required or permitted in this Code, the dimension of the "standing" working space...considered as grounded." II "In addition to the dimensions shown in Table 110-16(a), the standing work space shall not be less than 30 inches (762 mm) wide in front of the electric equipment." Table 110-16(a). "~tanding" Working Clearances 1. "Exposed live parts on one side and no live or grounded parts on the other side of the "standing" working space, or exposed live p a r t s . . . " 3. Exposed live parts on both sides of the "standing" work space (not guarded as provided in Condition 1) with the operator between. SUBSTANTIATION: Manypeople are installing disconnecting means (for example) over air conditioners, pool pumps and equipment and since there is sufficient working space in front of the equipment, with nothing blocking him, he feels he is working in compliance with this Code section. However, the intent of this section is to insure 30 inches of clear working space, where one can stand up, and not have to reach over equipment to install the disconnecting means. PANEL ACTION: Reject. PANEL COMMENT: Such a change could be interpreted to permit other obstructions in the workspace provided standing space was available. I t is intended that the entire working space be clear. VOTE ON PANELACTION: Unanimously Affirmative. Log # 1735 1- 104 - (110-16): Reject SUBMII-FER: Charles "Mike" Holt, Concepts in Electricity Inc. RECOMMENDATION: 110-16. Working Space About Electric Equipment (600 volts, nominal, or less). Sufficient access and working space shall be provided and maintained about all electric equipment to permit ready and safe operation and maintenance of such equipment. "This working space shall be a minimum of 6 1/4 feet from the f l o o r . " SUBSTANTIATION: Clarifying the working space to be from the floor to a minimum of 6 1/4 feet would eliminate the possibility of workmen sitting on a compressor or other equipment to perform their service. PANEL ACTION: Reject. PANEL COMMENT: The proposal adds nothing to the understanding of the Code and may even add confusion. See Panel Action and Comment on Proposal 1-103. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 1275 I - 107 - (110-16(a)): Accept in Principle SUBMITTER: IAEI RECOFtMENDATION: Delete words "while alive." Replace with "while normally energized." SUBSTANTIATION: Use of the words "while alive" is unenforceable as all electrical equipment has some disconnecting means somewhere. PANEL ACTION: Accept in Principle. ~ o r d "normally" from the proposal. PANEL COMMENT: The intent of the rule is to provide an electrically safe working environment during the period of time the equipment is being serviced. VOTE ON PANELACTION: UnanimouslyAffirmative. Log # 1059 i- 108 - (110-16(a), Exception No. 1): Reject SUBMI1-FER: HeydonZ. Lewis, Thermo-Scan Engineering, Inc. RECOMMENDATION: Delete or reword Exception No. 1 to paragraph (a). Add a paragraph (g) as follows: (g) Access for inspection under load. All equipment of 30 ampere or greater capacity single-phase and all 3-phase equipment shall be installed to permit inspection in operating configuration under load. This shall include bypassable door interlocks and access to all splices, terminations, finger joints, etc. which may occur in the rear of cabinets. SUBSTANTIATION: A major advantage of thermal imaging inspection is the a b i l i t y to perform nondestructive, non-contact inspection under full-load, normal operating conditions. Doors which cannot be opened without deactivating a c i r c u i t defeats the purpose. The bus bar-finger contact point on plug-in control centers is a common problem area, particularly in corrosive environments. Installation of cabinets with no rear access prevents inspection of these points. PANEL ~CTION: Reject. PANEL COMMENT: The proposal would result in costly redesign which could be detrimental to safety by encouraging access by unauthorized persons. VOTE ON PANELACTION: Unanimously Affirmative. m m Log # 1236 I-- 109 " (110--16(C)): Accept in Principle SUBMITTER: IAEI RECOMMENDATION: 110-16(c). Revise to read: At least one entrance 24 inches wide by 6 foot 6 inches high shall be provided to give access to the working space about electric equipment. For switchboards, panelboards, and control panels are rated 1200 amperes or more and are over 6 feet wide, the working space required by Section 110-16(c) shall be doubled or access shall be provided so that egress from the working area can be made in two different directions. SUBSTANTIATION: Present wording is based on "practicality," a vague term and often unenforceable. The intent of two means of egress for "people safety" is accomplished clearly by the revised wording and an alternate of two means of egress is provided. PANEL ACTION: Accept in Principle. Retain present wording of Section 110-16(c) in the Code but delete the words "where reasonably practicable" and add the following two Exceptions: "Exception No. i: Where the work space configuration permits an escape route. Exception No. 2: Where the workspace required bY Section 110-16(a) is doubled.= PANEL COMM~NT: Exception No. i is to correct an oversight in the proposal wherein workspace configurations could permit a ready escape route without the necessity of providing two doors or doubling the workspace. "Sufficient area" was retained as there is no substantiation for changing to specific dimensions. VOTE ON PANELACTION: AFFIRMATIVE: 8 NEGATIVE: Palko. EXPLANATION OF VOTE: PALKO: Exception No. 1 is meaningless, in that i t is as much subject to differing interpretations as the present wording "where reasonably practicable." Where there is a means of ingress, there is always a means of egress. Whether such egress constitutes an "escape route" must s t i l l be resolved on a case-by-case basis. A person in an equipment room having a maximum dimension of 12 feet is no further from an exit than a person in a room 100 feet long with an exit at each end. Exemption No. i should be amplified to cite a maximum distance to an exit that shall, in all cases, be considered to constitute an escape route. Log # 105 1- 105 - (110-16(a) and Exception): Reject SUBMI1-FER: Dan Leaf, Westlake Village, CA ~ATION: Add the following to paragraph (a): For service equipment, panelboards, switchboards, and control centers the working space shall extend from-the floor or staoding surface to the top of such equipment, and to a minimum of 6-i/4 feet above such surfaces. Exception: See Section 110-16(f) Exception. SUBSTANTIATION: Work space not clearly defined. Present wording does not clearly indicate that space below equipment that is elevated above floor or ground level is included in the required clearances. Such equipment installed above piping, motors, benches, or counters, etc, can present a hazard because of grounded surfaces or the necessity to lean over to reach the equipment. Section 550-4(a) contains a similar requirement for panelboards in mobile homes, and i t seems reasonable to clearly provide the same safety requirement in other occupancies. PANEL ACTION: Reject. PANEL COMMENT: Already covered by Section 110-16(a). See Panel Action and Comment on Proposal 1-103. VOTE ON PANELACTION: Unanimously Affirmative. Log # 57 1- 106 - (110-16(a)): Reject SUBMITTER: Dan Leaf, Westlake Village, CA ITE'L~QfE'I~II~ATION: Delete the f i r s t word "exposed" in conditions 1, 2, and 3. SUBSTANTIATION: Present wording is confusing and contradictory. The f i r s t paragraph of (a) clearly states that distances shall be measured from live parts i f exposed OR the enclosures therefor. The word "exposed" in conditions i, 2, and 3 confuse the conditions to be app!ied, as the definition of exposed means capable of being inadvertently touched, while the definition o f enclosure is a case or housing to prevent contact with energized live) parts. Conditions 1, 2, and 3 do not appear to apply to ive parts which are enclosed (not exposed). PANEL ACTION: Reject. HANLL COMMENT: The proposal is already covered in the second sentence of Section 110-16(a) and the deletion of the words "exposed" would change the meaning of the requirements of that sentence. VOTE ON PANEL ACTION: Unanimously Affirmative. l Log # 275 1- 110 - (110-16(c)): Accept in Principle SUBMITTER: W. Creighton Schwan, Hayward, CA RECOM~NDATION: In line 5, place a period after "end" add delete "where reasonably practicable." 18 PANEL COMMENT: See Panel Action and Comment on Proposal 1-109. VOTE ON PANEL ACTION: AFFIRMATIVE: 8 NEGATIVE: Palko. EXPLANATION OF VOTE: PALKO: I vote negative for the same reason given for Proposal 1-109. SUBSTANTIATION: There are far too many cases of electricians belng trapped in a dead-end corridor between rows of switchgear with the only escape route leading past arching, burning, or exploding equipment. The phrase "where reasonably practicable" renders the requirement for an alternate escape route unenforceable, and slmuld be deleted. PANEL ACTION: Accept in Principle. PANEL COMMENT: See Panel Action and Comment on Proposal 1-109. VOTE ON PANEL ACTION: AFFIRMATIVE: 8 NEGATIVE: Palko. EXPLANATION OF VOTE: PALKO: I vote negative for the same reason given for Proposal 1-109. I also feel that the substantiation is deficient. The substantiation states as fact that there are far too many cases of electricians being trapped...but cites no cases where injuries have occurred that could have been prevented by redundant exits. Log # 421 1- 114 - (110-16(c)): Reject SUBMII-TER: Southwestern Section IAEI RECOM~LENDATION: Add, 2nd paragraph Permanent ladders on stairways shall be provided to give safe access to the working space around electric equipment installed on platforms, balconies, mezzanine f]oors, or in attic or roof rooms or spaces. SUBSTANTIATION: Access to electrical equipment under 60() volts is just as important as the access in Section 110-33(b) for over 60(] volts. PANEL ACTION: Reject. PANEL COMMENT: The sweeping nature of this proposal could provide ready access for unauthorized persons to spaces that require security. The substantiation does not j u s t i f y such a change for • equipment under 600 volts. VOTE ON PANELACTION: Unanimously Affirmative. Log # 299, 302 1- 111 - (110-16(c)): Accept in Principle SUBMITTERS: Joseph Marcelino, NECACodes and Standards (299) Jack Smith, East Bay Uniform Electrical Code Committee (302) RECOMMENDATION: In the second sentence, delete the last three words: "where reasonably practicable." SUBSTANTIATION: The term "where reasonably practicable" makes the requirement vague and therefore d i f f i c u l t to enforce. The need for a workman to have two ways out from the working space in front of a wide assembly of switchgear is too important to be compromised by vague language in the Code. PANEL ACTION: Accept in Principle. PANEL COMMENT: See Panel Action and Comment on Proposal 1-109. VOTE ON PANEL ACTION: AFFIRMATIVE: 8 NEGATIVE: Palko. EXPLANATION OF VOTE: PALKO: I vote negative for the same reason given for Proposal 1-109. Log # 123 1- 115 - (110-17(a)): Reject SUBMITTER: Joseph L. Yosafat, General Electric Co. Sectetary's Note: This comment (No. 70-49, CMP i) on Proposal 106 was for the 1981 Code and was held for further study. See NEC-TCD-1980 Annual Meeting. RECOMMENDATION: Change 50 volts to read 42.4 volts. SUBSTANTIATION: For conformance with UL 478 and the standards of the IEC. Voluntary conformance and standardization must be practiced diligently i f the voluntary standards and codes industry of this country is to survive the attempted efforts of federal mandatory requirements of the FTC. PANEL ACTION: Reject. PANEL COMMENT: CMP 1 has no information to confirm the substantiation of the proposal. Referred to CMP 16 for information. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 420, 501 1- 112 - (110-16(c)): Accept in Principle SUBMITTER: Southwestern Section IAEI (420) ~ E . Cannon, Tempe, AZ (501) RECOMMENDATION: 110-16(c) Revise to read: "At least one entrance 24-inches wide by 6-foot high shall be provided to give access to the working space about electrical equipment. For switchboards, panelboards, and control panels are rated 1200 amperes or more and are over 6-feet wide, the working space required by Section 110-16(c) shall be doubled or access shall be provided so that egress from the working area can be made in two different directions." SUBSTANTIATION: Recent wording is based on "practicality"; a vague term and often unenforcible. The intent of two means of egress for "people safety" is accomplished clearly by the revised wording and an alternate to two means of egress is provided. PANEL ACTION: Accept in Principle. PANEL COMMENT: See Panel Action and Comment on Proposal 1-109. VOTE ON PANEL ACTION: AFFIRMATIVE: 8 NEGATIVE: Palko. EXPLANATION OF VOTE: PALKO: I vote negative for the same reason given for Proposal 1-109. Log # 393, 1894 1- 116 - (110-17(a), FPN-(New)): Reject SUBMITTER: Kenneth L. Gebert, City of Minneapolis, MN {393) B. Auger/H. B. Love, Michigan Chapter IAJ~I (1894) RECOMMENDATION: Add a Fine Print Note to Section 110-17(a) as follows: As used herein, approved enclosures shall mean, for other than dead front devices, the l~)x cover and switch operating means shall be n~chanically interlocked so that the main cover of the cabinet (1) is normally prevented from being opened when the switch contacts are in a closed position and (2) the switch contacts are normally prevented from being closed when the cover of the switch cabinet is open. SUBSTANTIATION: Mechanical interlocking systems have been in use for many years on all types of disconnect switches. Even the 115 volt, two-fuse service disconnect switch associated with the turn of the century knob and tube systems had an interlock which precluded opening the fuse plug access door while the current was on. A present day manufacturer insists that interlocking is not required even though the equipment is subject to ready access by the public and of a moderate ampacity {600 amperes) and fault current potential (15000+ amperes). PANEL ACTION: Reject. PANEL COMMENT: The proposal is too all-encompassing which makes its application impracticable and, furthermore, mandatory requirements cannot be put in a fine print note. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 422 i - 113 - (110-16(c)): Accept in Principle SUBMITTER: Southwestern Section IAEI ~ATION: Revise Section 110-16(c). Access and Entrance to Working Space. Access and entrances to working spaces shall be at least 24-inches wide by 6-feet 6-inches high. At least one entrance to the equipment room shall be provided to give access to the working space about electric equipment. For switchboards and control panels rated 1200 amperes or more and over 6-feet wide, the working space shall be twice that required by Section 110-16(a) or a second equipment room entrance shall be provided so that egress from the working space can be in different directions with no common path of travel. SUBSTANTIATION: i . Complete rewrite. Use local Code wording. 2. Where reasonably practicable, is too vague. Phrases such as "except by special permission" do not contribute to uniformity in Code compliance. Section 90-4 is available for any unusual conditions i f the authority enforcing the Code chooses to waive specific requirements. The design of the building sometimes makes a second door requirement a major problem. Above proposal permits an alternative and yet provides the workman with a greater degree of safety of movement in emergency conditions. Security of tenant spaces has been one of the reasons mentioned by builders for not wanting a second door. First door opens to a corridor, end walls of the room are suite division walls and outside wall is not adaptable for a door due to terrain. PANEL ACTION: Accept in Principle. Log # 1065, 1386 i- 117 - (110-17(c)): Reject SUBMII-FER: Frank K. Kitzantides, NEMA(1065) ---~i~--~qale, Baltimore, MD (1386) RECOMMENDATION: In second line, replace "warning" with "precautionary." Add Fine Print Note: FPN: See Section 110-23. SUBSTANTIATION: See Section 110-23-(New). PANEL ACTION: Reject. PANEL COMMENT: "Precautionary" is not strong enough language where safety is concerned. See Panel Action and Comment on Proposal 1-120. 19 VOTE ON PANEL ACTION: AFFIRMATIVE: 8 NEGATIVE: Sleesman. EXPLANATION OF VOTE: SLEESMAN: The NEMAvote is contingent upon the a v a i l a b i l i t y of the adopted ANSI Z535 standards in time for the next meeting of the CMP. PANEL ACTION: Reject. VANbL CUMMENI: The Panel considers that the standards referenced in the proposal are insufficient to replace the present wording in the Code. The Panel feels i t cannot reference a standard which does not exist. VOTE ON PANELACTION: AFFIRMATIVE: 8 NEGATIVE: Sleesman. EXPLANATION OF VOTE: SLEESMAN: The NEMAvote is contingent upon the a v a i l a b i l i t y of the adopted ANSI Z535 standards in time for the next meeting of the CMP. Log # 1220 1- 118 - (110-21): Reject SUBMITTER: Aaron Goldsmith, Safety Engineering Laboratories ~ATION: All equipment capable of causing a f i r e or electrical shock or other hazardous condition should have a permanent, fireproof identification tag so that the equipment can be traced back to its source and date of manufacture. SUBSTANTIATION: Fires are often caused by products that can not be identified as to source and date of manufacture because such identification has been destroyed in the resulting f i r e . I f permanent, fireproof ID tags were required on such items, both the manufacturer and other agencies concerned with f i r e and shock hazards could determine what equipment is unsafe and then analyze the subject equipment so that changes can be made to eliminate or reduce the particular hazard. PANEL ACTION: Reject. PANEL COMMENT: The Panel feels the proposal is impracticable and unenforceable. Fireproof tags are beyond technology known to the Panel. VOTE ON PANEL ACTION: Unanimously Affirmative. _ _ i - 121 - (110-33(a)): Accept SUBMII-TER: CMP i RECOMMENDATION: Revise Section 110-33(a) by changing "48 inches (1.22 m)" to "6 feet (1.83 m)" and delete the words "where reasonably practicable" in the second sentence. Add the following two Exceptions to follow the second sentence: Exception No. 1: Where the workspace configuration permits an escape route. Exception No. 2: Where the workspace required in Section 110-34(a) is doubled. SUBSTANTIATION: To achieve correlation in the requirements accepted in Proposal 1-109. PANEL ACTION: Accept. PAN'EL COMMENT: The Panel recognizes that total correlation has not been achieved. A public comment will be generated to correct any deficiencies. VOTE ON PANELACTION: AFFIRMATIVE: 8 NEGATIVE: Palko. EXPLANATION OF VOTE: PALKO: I vote negative because I do not agree with the premise on which this proposal is made; I do not feel that Proposal 1-109 should have been accepted with Exception No. 1 limited to the wording adopted by the Panel. m Log # 423 I - 119 - (110-22): Reject SUBMITTER: Southwestern Section IAEI ]R-E~-O-~--E-N-DATION: Revise Section 110-22. Identification of Disconnecting Means. Each disconnecting means required by this Code for motors and appliances, and each service, feeder, or branch circuit at the point where i t originates shall be legibly marked to indicate its purpose unless located and arranged so the purpose is evident. The marking shall be of sufficient durability to withstand the environment involved. All service equipment shall bear a sign showing the rated ampacity of the service-entrance conductors or service equipment, whichever is smaller. Label shall be of engraved plastic, stamped metal or other approved material with minimum i/4-inch high letters. SUBSTANTIATION: Many400 ampere disconnects are wired and fused at 225 amperes, giving the impression to owner that 400 amperes is available. This holds true for many reduced overcurrent protected devices, with conductor ampacity reduced accordingly. PANEL ACTION: Reject. , PANELCOMMENT: The proposal is too all-encompassing and would not overcome the problem inferred in the substantiation. Service equipment is under the jurisdiction of CMP 4 to which i t is referred. VOTE ON PANELACTION: Unanimously Affirmative. Log # 56 I - 122 - (110-34(a)): Reject SUBMITTER: Dan Leaf, Westlake Village, CA RECOMMENDATION: Delete the f i r s t word "exposed" in conditions 1, 2, and 3. SUBSTANTIATION: Present wording is confusing and contradictory. The last sentence of the f i r s t paragraph (a) clearly states that distances shall be measured from live parts i f exposed, OR the enclosures therefor. The word "exposed" in conditions i , 2, and 3 confuse the conditions to be applied, as the definition of exposed means capable of being inadvertently touched, while the definition of enclosure is a case or housing to prevent contact with energized (live) parts. Conditions 1, 2, and 3 do not appear to #~b~ to live parts which are enclosed (not exposed). ACTION: Reject. PANEL COMMENT: The proposal is already covered in the second sentence of Section 110-34(a) and the deletion of the words "exposed" would change the meaning of the requirements of that sentence. VOTE ON PANELACTION: Unanimously Affirmative. Log # 1064, 1385 1- 120 - (110-23-(New)): Reject SUBMITTERS: Frank K. Kitzantides, NEMA(1064) ~ l e , Baltimore, MD (1385) RECOMMENDATION: "P~eoautionary Labeling" When i t is considered necessary, appropriate precautionary labeling shall be required on equipment and in locations. FPN: Per further information see "Safety Code for Marking Physical Hazards," ANSI Z53.1-1979 and "Specifications for Accident Prevention Signs," ANSI Z35.1-1972." SUBSTANTIATION: The use of standard precautionary signs, symbols ~ cplors, js becoming increasingly important to advise workers ~ne public OT zne presence OT various hazards which may be involved. Adopted and proposed national standards take into account such factors as recognition, acceptance, v i s i b i l i t y , etc., as well as harmonization with international standards developed for the same purpose. ANSI Committee Z535 was recentl~ formed as a combination of former ANSI Committees Z53 (Color) and Z35 (Signs). The new Z535 Committee has four Subcommittees including Z535.1 (Color), Z535.2 (Signs), Z535.3 (Symbols), and Z535.4 (Product Alerting). These Subcommittees are working to produce new safety standards relating to color, signs, symbols, and product alerting. Until the new standards are available, existing standards ANSI Z35.1-1972 and ANSI Z53.1-1979 will continue in use. A number of NEC sections require specific labels or signs. There is inconsistency among the requirements and a lack of agreement with existing national standards. I t is believed that elimination of specific requirements from the NEC with reference to the national standards will enhance the objective of the various NEC sections by supporting a national approach to safety signs, codes and symbols. The addition of Section 110-23 involves proposals for correlation purposes for Sections 110-17(c), 110-34(c), 230-203, 410-91, 424-86(5), 450-7(d), 516-i, 710-21(c), 710-24(o)(2), 710-43, and 710-45. Log # 1066, 1387 i- 123 - (110-34(c)): Reject SUBMITTER: Frank K. Kitzantides, NEMA(1066) W. N. Hale, Baltimore, MD (1387) RECOI~MENDATION: Revise third paragraph as follows: In line 7 (following conspicuous), replace the word "warning' with "precautionary." Replace the comma following "provided" with a period and delete "reading" through "out". Add a Fine Print Note: FPN: See Section 110-23. SUBSTANTIATION: See Section 110-23-(New). PANEL ACTION: Reject. PANEL COMMENT: Proposed new Section 110-23 gives no clue as to the intended type of sign. See Panel Action and Comment on Proposal 1-117. VOTE ON PANELACTION: AFFIRMATIVE: 8 NEGATIVE: Sleesman. EXPLANATION OF VOTE: SLEESMAN: The NEMAvote is contingent upon the a v a i l a b i l i t y of the adopted ANSI Z535 standards in time for the next meeting of the CMP. Log # 1452 1- 124 - (110-34(c)): Reject SUBMITTERS: Bill Hogan, Chicago, IL Leo Witz, Continental Electric Co. Fred Smith, Elgin, IL Jim Meehan, New Haven, CT 20 Log # 1959 5- 3 - (200-4-(New)): Reject SUBMII-FER: Saul Rosenbaum, East Meadow, NY RECOMMENDATION: Add a new Section 200-4 as follows: 200-4. Grounded Conductor Required at Switch Enclosures. All enclosures f o r snap switches rated 20 amperes or less shall contain a grounded conductor. See companion Proposal 200-7, Exception No. 2. SUBSTANTIATION: This requirement would prevent the hazardous practice of using the "grounding" conductor f o r a grounded conductor. This s i t u a t i o n occurs very frequently under the f o l l o w i n g circumstances: a. When attempting to replace a single-pole switch with a combination switch and receptacle. b. When attempting to replace a single-pole switch with a combination switch and p i l o t l i g h t . c. In today's environment, many people are i n s t a l l i n g time clocks to turn switch controlled l i g h t s on and o f f f o r security purposes. All of these motor-driven time clocks require the a v a i l a b i l i t y of a grounded conductor, d. Very often when an additional receptacle needs to be i n s t a l l e d , i t is very convenient to run a cable up to the switch box. The a v a i l a b i l i t y of a grounded conductor, here again, would preclude the general practice of using the grounding conductor f o r a grounded conductor. PANEL ACTION: Reject. PANEL COMMENT: The Panel f e e l s that the Code cannot make mandatory provisions f o r a l l f u t u r e modifications. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . Anton Ganje, North Dakota Kenny Gebert, Minneapolis, MN B i l l Conrardy, The Conrardy Co. Robert P. Brooks, Chicago, IL Paul Moore, Paducah, KY Les Rinder, Chicago, IL Leo Nagel, North Dakota Homer M. Lefler, Chicago, IL John W. Erickson, Boltswitch Inc. RECOMMENDATION: Amend Section 110-34(c) by deleting from the third paragraph thereof the words, "reading substantially as follows;" and amend Section 110-34(c) further by inserting in lieu thereof the following, "containing the words, "WARNING - HIGH VOLTAGE - KEEP OUT." Said words shall be in block printing no less than 2 inches high and at least I/2 inch wide strokes." SUBSTANTIATION: In 50 percent of the IAEI Chapter meetings since September of 1980 the question was raised concerning the word, "substantially." There has been no definite answer given and as a matter of fact there is no real answer to the question. We o f f e r this wording in lieu of the consternation that prevails. There can be no question concerning the need f o r the sign and there is no reason why the Code should not prescribe the wording. PANEL ACTION: Reject. PANEL COMMENT: The proposal leaves no latitude f o r other suitable language. VOTE ON PANEL ACTION: Unanimously Affirmative. ARTICLE 200 - - USE AND IDENTIFICATION OF GROUNDEDCONDUCTORS Log # 2095 5- 4 - (200-7): Reject SUBMITTER: Karl F. Steinhauer, Des Plaines, IL RECOMMENDATION: In Section 200-7, at about the 35th word-group, I suggest that at "the supply" either omit "the" or change i t to "a supply." SUBSTANTIATION: To accomodate 4-way switches. PANEL ACTION: Reject. PANEL COMMENT: The intent of the present wording is clear. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 1633 5- 0 - ( A r t i c l e s 200, 250, 280): Reject SUBMITTER: Allen KnicKrehm, Los Angeles, CA ITE'-C'~PL'-~(DATION: Delete the word "approved" when used to mean the use of alternate method(s) or materials. SUBSTANTIATION: The NEC is incorporated in most construction contract documents by reference. Therefore, the authority having j u r i s d i c t i o n - the owner or the owner's representative, w i l l not be the t h i r d party q u a l i f i e d person comtemplated by the Code-Making Panel. Section 90-4 covers the case f o r governmental bodies exercising legal j u r i s d i c t i o n . PANEL ACTION: Reject. PANEL COMMENT: No specific proposal has been submitted. Any review would be subjective on the part of the Panel to determine proposer's intent. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . Log # 45 5- 5 - (200-7, Exception No. 1): Reject SUBMII-FER: Dan Leaf, Westlake Village, CA ]TL~C~O-~IBI~N-DATION: Revise Exception No. i as follows: insert the words "that is part of a cable assemble" after the word " f i n i s h . " SUBSTANTIATION: Present wording permits all conductors of a wlrlng system to be installed with factory-colored white insulation. This Exception permits white-colored conductor i n s t a l l a t i o n in a raceway system where the p o s s i b i l i t y of improper or ineffective f i e l d i d e n t i f i c a t i o n (especially when many conductors are installed and v i s i b l e at many openings) permits an unwarranted potential safety hazard. There appears no real need f o r this Exception as written, as conductors of all sizes are generally readily available with other than white insulation. This Exception also appears to be in c o n f l i c t with Section 310-12(c) which has no comparable Exception to permit f i e l d identification. PANEL ACTION: Reject. PANEL COMMENT: The present Exception No. 1 provides the intended safety. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 2054 5- 1 - (Articles 200, 250,280): Reject Secretary's Note: The Correlating Committee feels that this proposal is e d i t o r i a l in nature and that i t is unnecessary to repeat information already in the Code. SUBMITTER: Ivan P. Nordstrand, Consumers Power Company RECOMMENDATION: Propose each a r t i c l e have the Panel designation thus: A r t i c l e 90 - Introduction (Panel No. 1) A r t i c l e 100 - Definitions (Panel No. 1) A r t i c l e 110 - Requirements f o r E l e c t r i c I n s t a l l a t i o n s (Panel No. i ) A r t i c l e 200 - Use and I d e n t i f i c a t i o n of Grounded Conductors (Panel No. 5) A r t i c l e 210 - Branch Circuits (Panel No. 2) Etc. SUBSTANTIATION: The present format of the published Code book makes i t d i f f i c u l t and time consuming to determine the appropriate Panel responsible f o r the a r t i c l e in which a problem is developing. The addition of one line in parentheses under the a r t i c l e number giving the Panel designation w i l l quickly provide the proper source. PANEL ACTION: Reject. PANEL COMMENT: This change is e d i t o r i a l and the Panel leaves i t to the discretion of the Correlating Committee and NFPA to include or exclude this information in the Table of Contents in the NATIONAL ELECTRICAL CODE. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . I Log ~ 384 5- 6 - (200-7, Exception No. 2): Reject SUBMITTER: Jon Nelson, Sheldon, IA RECOMMENDATION: A cable containing an insulating conductor with white or natural gray outer f i n i s h shall be permitted f o r a single-pole, 3-way or 4-way, where the white or natural gray conductor is used f o r the supply to the switch, but not as a • return conductor from the switch to the switched outlet. The white wire cannot be used as a traveler for 3-way or 4-way switches unless they are permanently reidentified. SUBSTANTIATION: At least one of the travelers on a 3-way or 4-way switch are hot a l l the time. I f the traveler is reidentified black i t w i l l not be confused with the neutral or the feeder wire in the c i r c u i t . PANEL ACTION: Reject. RANLL COMMENT: Identification of the grounded conductor is f o r convenience. With switches i t is understood that none of the wires connected to the switch are grounded and no r e i d e n t i f i c a t i o n is necessary. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 919 5- 2 - (200-2, Exception): Accept in Principle SUBMITTER: Ad Hoc Subcommittee on Solar Photovoltaics ITE'CI)I~'I~I~ATION: Revise Section 200-2 Exceptio~ to delete "and" in second line, and add "and 690-41 Exception" at end of sentence. SUBSTANTIATION: For correlation with proposed A r t i c l e 690. PANEL ACTION: Accept in Principle. PANEL COMMENT: Accept based upon acceptance of proposal f o r ~roposed new A r t i c l e 690. OTE ON PANEL ACTION: Unanimously Affirmative. Log # 362 5- 7 - (200-7, Exception No. 2): Reject SUBMITTER: David C. Winterfeld, Sheldon, IA RECOMMENDATION: A cable containing an insulated conductor with a white or natural gray outer f i n i s h shall be permitted f o r single-pole, 3-way or 4-way switch loops where the white or • 21 Log # 1959 5- 3 - (200-4-(New)): Reject SUBMII-FER: Saul Rosenbaum, East Meadow, NY RECOMMENDATION: Add a new Section 200-4 as follows: 200-4. Grounded Conductor Required at Switch Enclosures. All enclosures f o r snap switches rated 20 amperes or less shall contain a grounded conductor. See companion Proposal 200-7, Exception No. 2. SUBSTANTIATION: This requirement would prevent the hazardous practice of using the "grounding" conductor f o r a grounded conductor. This s i t u a t i o n occurs very frequently under the f o l l o w i n g circumstances: a. When attempting to replace a single-pole switch with a combination switch and receptacle. b. When attempting to replace a single-pole switch with a combination switch and p i l o t l i g h t . c. In today's environment, many people are i n s t a l l i n g time clocks to turn switch controlled l i g h t s on and o f f f o r security purposes. All of these motor-driven time clocks require the a v a i l a b i l i t y of a grounded conductor, d. Very often when an additional receptacle needs to be i n s t a l l e d , i t is very convenient to run a cable up to the switch box. The a v a i l a b i l i t y of a grounded conductor, here again, would preclude the general practice of using the grounding conductor f o r a grounded conductor. PANEL ACTION: Reject. PANEL COMMENT: The Panel f e e l s that the Code cannot make mandatory provisions f o r a l l f u t u r e modifications. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . Anton Ganje, North Dakota Kenny Gebert, Minneapolis, MN B i l l Conrardy, The Conrardy Co. Robert P. Brooks, Chicago, IL Paul Moore, Paducah, KY Les Rinder, Chicago, IL Leo Nagel, North Dakota Homer M. Lefler, Chicago, IL John W. Erickson, Boltswitch Inc. RECOMMENDATION: Amend Section 110-34(c) by deleting from the third paragraph thereof the words, "reading substantially as follows;" and amend Section 110-34(c) further by inserting in lieu thereof the following, "containing the words, "WARNING - HIGH VOLTAGE - KEEP OUT." Said words shall be in block printing no less than 2 inches high and at least I/2 inch wide strokes." SUBSTANTIATION: In 50 percent of the IAEI Chapter meetings since September of 1980 the question was raised concerning the word, "substantially." There has been no definite answer given and as a matter of fact there is no real answer to the question. We o f f e r this wording in lieu of the consternation that prevails. There can be no question concerning the need f o r the sign and there is no reason why the Code should not prescribe the wording. PANEL ACTION: Reject. PANEL COMMENT: The proposal leaves no latitude f o r other suitable language. VOTE ON PANEL ACTION: Unanimously Affirmative. ARTICLE 200 - - USE AND IDENTIFICATION OF GROUNDEDCONDUCTORS Log # 2095 5- 4 - (200-7): Reject SUBMITTER: Karl F. Steinhauer, Des Plaines, IL RECOMMENDATION: In Section 200-7, at about the 35th word-group, I suggest that at "the supply" either omit "the" or change i t to "a supply." SUBSTANTIATION: To accomodate 4-way switches. PANEL ACTION: Reject. PANEL COMMENT: The intent of the present wording is clear. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 1633 5- 0 - ( A r t i c l e s 200, 250, 280): Reject SUBMITTER: Allen KnicKrehm, Los Angeles, CA ITE'-C'~PL'-~(DATION: Delete the word "approved" when used to mean the use of alternate method(s) or materials. SUBSTANTIATION: The NEC is incorporated in most construction contract documents by reference. Therefore, the authority having j u r i s d i c t i o n - the owner or the owner's representative, w i l l not be the t h i r d party q u a l i f i e d person comtemplated by the Code-Making Panel. Section 90-4 covers the case f o r governmental bodies exercising legal j u r i s d i c t i o n . PANEL ACTION: Reject. PANEL COMMENT: No specific proposal has been submitted. Any review would be subjective on the part of the Panel to determine proposer's intent. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . Log # 45 5- 5 - (200-7, Exception No. 1): Reject SUBMII-FER: Dan Leaf, Westlake Village, CA ]TL~C~O-~IBI~N-DATION: Revise Exception No. i as follows: insert the words "that is part of a cable assemble" after the word " f i n i s h . " SUBSTANTIATION: Present wording permits all conductors of a wlrlng system to be installed with factory-colored white insulation. This Exception permits white-colored conductor i n s t a l l a t i o n in a raceway system where the p o s s i b i l i t y of improper or ineffective f i e l d i d e n t i f i c a t i o n (especially when many conductors are installed and v i s i b l e at many openings) permits an unwarranted potential safety hazard. There appears no real need f o r this Exception as written, as conductors of all sizes are generally readily available with other than white insulation. This Exception also appears to be in c o n f l i c t with Section 310-12(c) which has no comparable Exception to permit f i e l d identification. PANEL ACTION: Reject. PANEL COMMENT: The present Exception No. 1 provides the intended safety. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 2054 5- 1 - (Articles 200, 250,280): Reject Secretary's Note: The Correlating Committee feels that this proposal is e d i t o r i a l in nature and that i t is unnecessary to repeat information already in the Code. SUBMITTER: Ivan P. Nordstrand, Consumers Power Company RECOMMENDATION: Propose each a r t i c l e have the Panel designation thus: A r t i c l e 90 - Introduction (Panel No. 1) A r t i c l e 100 - Definitions (Panel No. 1) A r t i c l e 110 - Requirements f o r E l e c t r i c I n s t a l l a t i o n s (Panel No. i ) A r t i c l e 200 - Use and I d e n t i f i c a t i o n of Grounded Conductors (Panel No. 5) A r t i c l e 210 - Branch Circuits (Panel No. 2) Etc. SUBSTANTIATION: The present format of the published Code book makes i t d i f f i c u l t and time consuming to determine the appropriate Panel responsible f o r the a r t i c l e in which a problem is developing. The addition of one line in parentheses under the a r t i c l e number giving the Panel designation w i l l quickly provide the proper source. PANEL ACTION: Reject. PANEL COMMENT: This change is e d i t o r i a l and the Panel leaves i t to the discretion of the Correlating Committee and NFPA to include or exclude this information in the Table of Contents in the NATIONAL ELECTRICAL CODE. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . I Log ~ 384 5- 6 - (200-7, Exception No. 2): Reject SUBMITTER: Jon Nelson, Sheldon, IA RECOMMENDATION: A cable containing an insulating conductor with white or natural gray outer f i n i s h shall be permitted f o r a single-pole, 3-way or 4-way, where the white or natural gray conductor is used f o r the supply to the switch, but not as a • return conductor from the switch to the switched outlet. The white wire cannot be used as a traveler for 3-way or 4-way switches unless they are permanently reidentified. SUBSTANTIATION: At least one of the travelers on a 3-way or 4-way switch are hot a l l the time. I f the traveler is reidentified black i t w i l l not be confused with the neutral or the feeder wire in the c i r c u i t . PANEL ACTION: Reject. RANLL COMMENT: Identification of the grounded conductor is f o r convenience. With switches i t is understood that none of the wires connected to the switch are grounded and no r e i d e n t i f i c a t i o n is necessary. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 919 5- 2 - (200-2, Exception): Accept in Principle SUBMITTER: Ad Hoc Subcommittee on Solar Photovoltaics ITE'CI)I~'I~I~ATION: Revise Section 200-2 Exceptio~ to delete "and" in second line, and add "and 690-41 Exception" at end of sentence. SUBSTANTIATION: For correlation with proposed A r t i c l e 690. PANEL ACTION: Accept in Principle. PANEL COMMENT: Accept based upon acceptance of proposal f o r ~roposed new A r t i c l e 690. OTE ON PANEL ACTION: Unanimously Affirmative. Log # 362 5- 7 - (200-7, Exception No. 2): Reject SUBMITTER: David C. Winterfeld, Sheldon, IA RECOMMENDATION: A cable containing an insulated conductor with a white or natural gray outer f i n i s h shall be permitted f o r single-pole, 3-way or 4-way switch loops where the white or • 21 natural gray conductor is used f o r the supply to the switch, but not as a return conductor from the switch to the switched outlet. In these applications, r e i d e n t i f i c a t i o n of the white or natural gray conductor shall not be required. Where a white or natural gray conductor is used as traveler between switches i t shall be reidentified. SUBSTANTIATION: I t should be c l a r i f i e d that when the grounded conductor is used as a traveler between switches i t shall be reidentified so i t concurs with Section 200-7 in i t s entirety. PANEL ACTION: Reject. PANEL COMMENT: Sameas Proposal 5-6. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 1960 5- 12 - (200-7, Exception No. 2): Reject SUBMITTER: Saul Rosenbaum, East Meadow, NY RECOMMENDATION: Delete from the second line "single-pole." SUBSTANTIATION: See companion proposal for new Section 200-4.' To comply with proposed Section 200-4, the (white) conductor would be used as a grounded conductor. Single-pole switch legs would now require 3 conductors, i . e . , black and red (armored cable or nonmetallic cable) conductors would be used f o r the single-pole switch leg and the white conductor would then be the required grounded conductor for use with timers, energy saving devices or f o r extension of the c i r c u i t to an added receptacle, or combination device. PANEL ACTION: Reject'. PANEL COMMENT: Same as Proposal 5-3. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 379 5- 8 - (200-7, Exception No. 2): Reject SUBMITTER: Jeff Vanderhoff, Sheldon, IA ~ATION: A cable containing an insulated conductor with a white or natural gray outer finish shall be permitted f o r single-pole, 3-way, or 4-way switch loops where the white or natural gray is used to supply the switch, or as a traveler between 4-way switching, but not as a return conductor from the switch to the switched o u t l e t . In these applications the reidentification of the white or natural gray conductor shall not be required. SUBSTANTIATION: When using the white or natural gray conductor as a traveler between 4-ways, there are fewer wires in a box, thus a smaller box can be used. The white or natural gray conductor w i l l be feeding one or more of the 4-ways. PANEL ACTION: Reject, PANEL COMMENT: Sameas Proposal 5-6. VOTE ON PANEL"ACTION: Unanimously Affirmative. Log # 348 5- 13 - (200-7, Exception No. 5-(New)): Reject SUBMITTER: Joel Weigand, Rockford, IA R~ATION: Exception No. 5: Unless permanently reidentified at all openings the white or natural gray conductor w i l l not be used as a traveler. SUBSTANTIATION: In same openings and enclosures the white or natural gray conductor may be used as the grounded conductor when i t is the switch leg f o r a 3-way or 4-way switch loop. PANEL ACTION: Reject. PANEL COMMENT: Sameas Proposal 5-6. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 411 5- 14 - (200-I0(b)): Reject SUBMITTER: Nabil L. Mina, Appleton Electric Company ~ATION: ~Identification shall be by a metal coating substantially white in color, the word "WHITE" "or the l e t t e r W" - - - etc. (a) Exception: Terminal identification shall not be required for: 2-wire nonpolarized attachment plugs. (b) Where conditions of maintenance and supervision assure that only qualified persons w i l l service the i n s t a l l a t i o n , terminals f o r grounded conductors shall be permitted to be permanently identified at the time of i n s t a l l a t i o n , by a d i s t i n c t i v e white marking or other equally effective means. SUBSTANTIATION: Limited space on the plug and receptacle terminal blocks f o r marking the word "WHITE," the l e t t e r "W" is equally effective i d e n t i f i c a t i o n . Pin and sleeve plugs, receptacles and connectors are used in d i f f e r e n t applications, and voltage ratings configurations. A selection and application of the proper device should be done only by competent engineering personnel and backed up by a planned professional. See Guide pin and sleeve plugs, receptacle and connectors PR3-1980. Under code and safety requirements PR3-4.01. PANEL ACTION: Reject. PANEL COMMENT: We feel that the positive identification is necessary and there are already several acceptable methods provided. Proposed new paragraph (b) is redundant and is already covered in Section 200-9, Exception. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 382 5- 9 - (200-7, Exception No. 2): Reject SUBMITTER: David Nase, Orange City, IA RECOMMENDATION: Proposed Wording: A cable containing an insulated conductor with a white or natural gray outer Kinish shall be permitted f o r single-pole, 3-way, or 4-way switch loops where white or natural gray conductor is used f o r the supply to the switch, but not as a return conductor from the switch to the switched o u t l e t , "or as a traveler between switches." In these applications, r e i d e n t i f i c a t i o n of the white or natural gray conductor shall not be required. SUBSTANTIATION: I f a white or natural gray conductor is used as a traveler i t should be r e i d e n t i f i e d , because they are sometimes carrying current and i f run across in a box where i t is i t may be mistaken as a neutral i f not reidentified. PANEL ACTION: Reject. ISABEL COMMENT: Sameas Proposal 5-6. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 371 5- i0 - (200-7, Exception No. 2): Reject SUBMITTER: Larry Schmit, Hospers, IA ~ATION: A cable containing an insulated conductor with a white or natural gray f i n i s h shall be permitted f o r single-pole, 3-way or 4-way switch loops where used as supply or as a traveler. In these applications, r e i d e n t i f i c a t i o n shall not be required. SUBSTANTIATION: I do not think that the r e i d e n t i f i c a t i o n of the above situations should be required. I f the supply to the switch is allowed to be white then the travelers of the switch should also be allowed. Since all cables have a white conductor i t is impossible to run a 3- or 4-way without the white conductor so I believe i t should be allowed f o r what I have written above. PANEL ACTION: Reject. PANEL COMMENT: Sameas Proposal 5-6. VOTE ON PANEL ACTION: Unanimously Affirmative. Log ~ 608 5- 15 - (200-10 (b), Second Paragraph): Reject SUBMITTER: Leon Rabin, Rabin E l e c t r i c Service REC~ATION: Change to read: I d e n t i f i c a t i o n shall be by a metal or metal coating s u b s t a n t i a l l y white in color f o r those devices intended f o r use with copper or copper clad wire or by the word "white" located adjacent to the i d e n t i f i e d terminal. SUBSTANTIATION: Receptacles are being produced with the screws a l l white or a l l brass in color. The word white is in raised l e t t e r s made of the same material of which the body of the device is made. The word white is not c l e a r l y v i s i b l e , in fact i n v i s i b l e in bad lighting conditions. The mechanic picks up a receptacle, sees a white screw, and connects the identified wire to i t . (Substitute "brass" and "hot" in the reverse case). The training of years has ingrained the habit of looking f o r the white screw and connecting the white wire. To permit current procedure is to ask f o r accidents. The wording of the proposed change w i l l allow manufacturers t o proceed with whatever they need f o r aluminum wire devices. The Code must be practical in i t s regulations, and not introduce changes that cause trouble. PANEL ACTION: Reject. PANEL COMMENT: The Panel feels that the present methods are adequate and were considered in depth in t h e i r adoption in the 1981 NATIONAL ELECTRICAL CODE and are substantiated in the TCR and TCD for the 1981 NATIONAL ELECTRICAL CODE. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 369 5- 11 - (200-7, Exception No. 2): Reject SUBMITTER: Joe Downing, Sheldon, IA RECOMMENDATION: A cable containing an insulated conductor with a white or natural gray outer f i n i s h shall be permitted f o r single-pole, 3-way or 4-way switch loops where the white or natural gray conductor is used f o r supply to the switch shall be reidentified. SUBSTANTIATION: Because I think that i f a switch is fed with a whi'te wire, i t should be reidentified so you won't get i t mixed up with a grounded conductor. PANEL ACTION: Reject. PANEL COMMENT: Sameas Proposal 5-6. VOTE ON PANEL ACTION: Unanimously Affirmative. 22 SUBSTANTIATION: The present format of the published Code book makes i t d i f f i c u l t and time consuming to determine the appropriate Panel responsible for the a r t i c l e in which a problem is developing. The addition of one line in parenthesis under the a r t i c l e number giving the panel designation w i l l quickly provide the proper source. PANEL ACTION: Reject. PANEL COMMENT: The information is already covered in the front of the Code. VOTE ON PANEL ACTION: Unanimously Affirmative. ARTICLE 210 -- BRANCH CIRCUITS Log # 461 2- 1 - (2XX-Supply Mains-(New)): Reject Secretary's Note: The Correlating Committee advises CMP 2 that a r t i c l e scope statements are the responsibility of the Correlating Committee and that the Correlating Committee accepts the Panel Action. SUBMITTER: Donald H. Mclntosh, E.I. du Pont de Nemours and Co. ~ATION: Article 2XX-Supply Mains. 2XX-I Scope - The provisions of this article apply to the installation of electrical conductors and equipment that serve as supply mains installed in premises wiring systems. 2XX-2 Definition - For the purpose of this a r t i c l e : Main - Any supply c i r c u i t to which other energy-consuming circuits (submains, branches, or services) are connected through automatic overcurrent devices (fuses or circuit breakers) at different points along i t s length and which is of the same size conductor for its entire length and which has no overcurrent devices in series with i t for its entire length. (FPN)- Where a main is supplied by a feeder, the main frequently has smaller conductors than the feeder which serves i t . An energy-utilizing device is never connected directly to a main, overcurrent devices being interposed between the energy-utilizing device and the main. Submain - A subsidiary main, fed through an overcurrent device from a main or from another submain, to which branch circuits or services are connected through overcurrent devices. (FPN) - A submain conductor is usually a smaller conductor than the main or other submain which serves i t . 2XX-3 Application of Other Articles - All requirements of this Code shall apply except as specifically amended in this a r t i c l e . For branch circuits, feeders, services, and overcurrent protection, refer to Articles 210, 215, 230 and 240 respectively. SUBSTANTIATION: For years the NEC has ignored one significant electrical distribution system element which has led to bastardizing the meaning of the word "feeder." Scores upon scores of so-called "feeders" are in r e a l i t y , supply mains. The only specific recognition of the term "main" appearing in the 1981 NEC is in the definition of "service conductors" with use of the words "street main." I have included Figure i and 2 extracted from the American Electricians Handbook to help i l l u s t r a t e a "main" and a "submain." Of course, the tap rules of 240-21 describing the location of overcurrent devices apply equally well to mains and submains for protection of conductors. The use of mains and submains inside manufactured equipment, such as motor control centers, without general recognition of these terms, has been going on for years, but the addition of these terms w~uld enhance proper application of electric conductors and equipment both inside manufactured equipment and in premises wiring (distribution systems). This proposal adds a new article to cover Code requirements for safe application of supply mains and submains. PANEL ACTION: Reject. PANEL COMMENT: In the Panel's opinion the subject is adequately covered with the present Code terminology. VOTE ON PANEL ACTION: UnanimouslyAffirmative. 2- 4 - (210-3): Accept Secretary's Note: In accordance with the NFPA Manual of Style, the Correlating Committee suggests that this proposal be an exception. SUBMITTER: CMP 2 ~ATION: Add a new second paragraph to read as follows: Multioutlet branch circuits greater than 50 amperes shall be permitted on industrial premises where maintenance and supervision indicate that qualified persons w i l l service equipment. SUBSTANTIATION See CMP 2 Proposal 2-54. PANEL ACTION: Accept. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 1010 2- 5 - (210-4): Reject SUBMITTER: J. H. Richards, Finksburg, MD RECOMMENDATION: In last paragraph following Exception No. 2 delete "IN DWELLING UNITS." The paragraph would then read "A multiwire branch circuit supplying more than one receptacle on the same yoke shall be provided with means to disconnect simultaneously all ungrounded conductors at the panelboard where the branch c i r c u i t orlginated. SUBSTANTIATION: By deleting the words "IN DWELLING UNITS" the requirement to disconnect all ungrounded conductors of multiwire circuits feeding multioutlet receptacles on a single yoke simultaneously w i l l apply to any occupancy. Maintenance personnel on systems in schools, churches, industrial and commercial occupancies are not always f u l l y competent electricians and added protection is due them as well as the homeowners. This ruling only applies where the s p l i t wired receptacles are used on a single yoke and should not prove a hardship nor increase costs to a prohibitive extent. PANEL ACTION: Reject. PANEL COMMENT: No substantiation is provided to indicate that a hazard exists in other than dwelling units. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 1009 2- 6 - (210-4): Accept in Principle SUBMITTER: J. H. Richards, Finksburg, MD ~ATION: Add to f i r s t paragraph. "3 wire multiwire circuits shall be considered as 2 circuits, 4 wire circuits shall be considered as 3 c i r c u i t s . " SUBSTANTIATION: A note stipulating that multiwire circuits were equal to two or three single two wire circuits was removed from a former code. Due to the ruling that when run through end to end fixture assemblies multiwire circuits can be considered as a single c i r c u i t , some authorities do not 3 wire circuits of 20 ampere ampacity running to the kitchen meeting the requirement of the two required circuits. PANEL ACTION: Accept in Principle. Revise Section 210-4 to read as follows: Branch circuits recognized by this article shall be permitted as multiwire circuits. A multiwire branch circuit shall be permitted to be considered as multiple circuits. All conductors shall originate from the same panelboard. In dwelling units a multiwire branch circuit supplying more than one device on the same yoke shall be provided with a means to disconnect simultaneously a l l ungrounded conductors at the panel board where the branch c i r c u i t originated. Multiwire branch circuits shall supply only line to neutral load. Insert Exceptions No. 1 and No. 2 at the end of Section 210-4. PANEL COMMENT: The revised wording more accurately reflects the Panel's intent. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 1630 2- 2 - (Articles 210, 215, 220)): Reject SUBMITTER: Allen KnicKrehm, Los Angeles, CA ~ATION: Delete the word "approved" when used to mean the use of alternate method(s) or materials. SUBSTANTIATION: The NEC is incorporated in most construction contract documents by reference. Therefore, the authority having jurisdiction - ~he owner or the owner's representative, w i l l not be the third party qualified person contemplated by the Code-Making Panel. Section 90-4 covers the case for governmental bodies exercising legal jurisdiction. PANEL ACTION: Reject PANEL COMMENT: Reject. No use of "approved" in Articles 210, 215, and 220. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 2057 2- 3 - (Articles, 210, 2151 220): Reject Secretary's Note: The Correlating Committee feels that this proposal is editorial i n nature and that i t is unnecessary to repeat information already in the Code. SUBMITTER: Ivan P. Nordstrand, Consumers Power Company RECOMMENDATION: Proposeeach a r t i c l e have the panel designation thus: Article 90 - Introduction (Panel No. 1) Article 100 - Definitions (Panel No. 1) Article 110 - Requirements f o r Electric Installations (Panel No. 1) Article 200 - Use and, ldentification of Grounded Conductors (Panel No. 5) Article 210 - Branch Circuits (Panel No. 2) Etc. Log # 1785 2- 7 - (210-4): Accept SUBMITTER: Leo F. Martin, Hyde Park, ~ . RECOMMENDATION: In the third paragraph delete the word "receptacle" and replace with "device." SUBSTANTIATION: As written, ~ext applies to a receptacle only. The use of the term "device" would include switches or switch/receptacle combinations, etc. PANEL ACTION: Accept. VOTE ON PANEL ACTION: Unanimously Affirmative. 23 The i d e n t i f i c a t i o n of ungrounded conductors of a multiwire branch c i r c u i t permits the electrician to i n s t a l l devices in a manner that w i l l result in a balancing of the phase loadings and neutral load. Detection of improper phasing of a multiwire c i r c u i t by the inspecting authority is extremely d i f f i c u l t without conductor i d e n t i f i c a t i o n and v i r t u a l l y impossible when making a f i n a l inspection of work that is not energized as is often the case. The proposal, as written, would o f f e r a simple means f o r both the e l e c t r i c i a n , inspector, and subsequent electricians to determine and maintain correct c i r c u i t . PANEL ACTION: Reject. PANEL COMMENT: See Panel Comment f o r Proposal 2-14. VOTE ON PANEL ACTION: AFFIRMATIVE: 9 NECV~TIVE: Schuck. EXPLANATION OF VOTE: SCHUCK: Same as comment as on Proposal 2-14. Log # 1876 2- 8 - (210-5(a)): Reject SUBMI1-FER: Leonard F. Devine, J r . , West Palm Beach, FL ~ATION: Add the following to Section 210-5(a) at the end of paragraph. , Multiwire branch c i r c u i t s shall conform to the following color code. Three wire c i r c u i t s one black, one white, one red, four wire c i r c u i t s one black, one white, one red, one blue; f i v e wire c i r c u i t s one black, one white, one red, one blue, one yellow. After the f i r s t set of multiwire branch c i r c u i t s are installed in the same raceway, other combinations may be used. All c i r c u i t conductors of the same color shall be connected to the same ungrounded conductors throughout the c i r c u i t . SUBSTANTIATION: The problem is that there is no uniformity in the colors used f o r branch c i r c u i t s and the fact that a c i r c u i t may change color throughout the c i r c u i t . By not having some standard to go by i t becomes at times d i f f i c u l t to troubleshoot, repair and change c i r c u i t r y because you don't know what the other person has done, or was thinking of doing. Many times mistakes are made on the i n i t i a l i n s t a l l a t i o n also. PANEL ACTION: Reject. PANEL COMMENT: See P~nel Comment f o r Proposal 2-14. VOTE ON PANEL ACTION: AFFIRMATIVE: g NEGATIVE: Schuck. EXPLANATION OF VOTE: SCHUCK: Same comment as on Proposal 2-14. Log # 59 2- 11 - (210-5(c)-(New)): Reject SUBMITTER: Dan Leaf, Westlake Village, CA ~ECOM~ZNDATION: Add paragraph (c) as follows: (c) Ungrounded Conductors. When a color has been established f o r an insulated conductor of a c i r c u i t , that color shall be maintained throughout the total length of the c i r c u i t . Exception No. 1 Cable-type wiring systems. Exception No. 2 Additions or extensions to existing c i r c u i t s . Exception No. 3 Conductors on the load side of switching devices. SUBSTANTIATION: No requirement f o r maintaining a color code, once established. The present lack of Code requirements f o r color-coding permits any number of d i f f e r e n t colored conductors to be spliced or otherwise connected together throughout a c i r c u i t . This permits an unwarranted potential safety hazard when using color-coding to ascertain proper c i r c u i t connections. As the Code requires color-coding of certain other conductors, i t appears reasonable to provide minimum requirements f o r ungrounded conductors. PANEL ACTION: Reject. PANEL COMMENT: See Panel Comment f o r Proposal 2-14. VOTE ON PANEL ACTION: AFFIRMATIVE: 9 NEGATIVE: Schuck. EXPLANATION OF VOTE: SCHUCK: Sameas comment on Proposal 2-14. Log # 1121 2- 9 - (210-5(c)): Reject SUBMITTER: Jack B. Smith, East Bay Uniform Electrical Code RECOMMENDATION: Add new subsection (c) as follows: (cl Ungrounded Conductors of Multiwire Branch Circuits. Ungrounded conductors of a multiwire branch c i r c u i t shall each be of a color or distinguishment to identify the feeder by which i t is supplied and each conductor of the same i d e n t i f i c a t i o n shall be connected to the same feeder. SUBSTANTIATION: Many neutral conductors of multiwire branch c i r c u i t s are overloaded due to improper phasing of conductors, splices and connection of devices. Color coding of the ungrounded conductors of a multiwire branch c i r c u i t is a safety, as well as a design consideration f o r safe and proper wiring. Much e l e c t r i c a l work is installed with the N.E.C., minimum requirements, as the only design c r i t e r i a . Failure to connect the proper conductor to loads supplied by multiwire branch c i r c u i t s can result in overloading of the unprotected neutral conductor to as much as three times i t s allowable ampacity or in the case of two, four wire c i r c u i t s , to as much as six times i t s allowable ampacity. The resultant overheating of a neutral wire is no less a hazard than of an ungrounded conductor. The i d e n t i f i c a t i o n of ungrounded conductors of a multiwire branch c i r c u i t permits the e l e c t r i c i a l to i n s t a l l devices in a ' manner that w i l l result in a balancing of the phase loadings and neutral load. Detection of improper phasing of a multiwire c i r c u i t by the inspecting authority is extremely d i f f i c u l t without conductor i d e n t i f i c a t i o n and v i r t u a l l y impossible when making a f i n a l inspection of work that is not energized as is often the case. The proposal, as written, would o f f e r a simple means f o r both the e l e c t r i c i a n , inspector, and subsequent electricians to determine and maintain correct c i r c u i t . PANEL ACTION: Reject. PANEL COMMENT: See Panel Comment f o r Proposal 2-14. VOTE ON PANEL ACTION: AFFIRMATIVE: 9 NEGATIVE: Schuck. EXPLANATION OF VOTE: SCHUCK: Same as on Proposal 2-14. Log # 293 2- 12 - (210-5(c)-(New)): Reject SUBMITTER: J. H. (Jim) Richards, Maryland E l e c t r i c a l Inspectors X~Tr~ RECOMMENDATION: Add to Section 210-5 the f o l l o w i n g : 210-5(c) Multiwire branch c i r c u i t s shall be i n s t a l l e d using color coded conductors in order to f a c i l i t a t e proper connections. Circuits of d i f f e r e n t voltages shall be wired with a d i f f e r e n t set of colored conductors. I t is suggested that f o r 120/208 systems one white (N) one black, one red and one blue conductor be used. This was standard f o r many years. For 277/480 v o l t systems i t is suggested one grey (N) one brown, one orange and one yellow conductor be used. SUBSTANTIATION: With enclosures containing a number of conductors of multiwire branch c i r c u i t s i t is very d i f f i c u l t to assure that ungrounded c i r c u i t conductors are connected so that they have a potential differenceJbetween them. I f improperly connected the grounded neutral conductor is stressed by having amperages imposed • on i t by as much as two or three times i t s ampacity. Conditions in branch c i r c u i t panels when using a l l black conductors on the ungrounded portions of multiwire branch c i r c u i t s make proper connections d i f f i c u l t and doubtful. Color coding is badly needed. Many local areas have refused to adopt the Code without making special rules on this matter and we do not feel that this is conducive to establishment of a good NATIONAL ELECTRICAL CODE. PANEL ACTION: Reject. PANEL COMMENT: See Panel Comment f o r Proposal 2-14. VOTE ON PANEL ACTION: AFFIRMATIVE: 9 NEGATIVE~ Schuck. EXPLANATION OF VOTE: SCHUCK: Sameas comment on Proposal 2-14. Log # 1120 2- 10 - (210-5(c)): Reject SUBMITTER: Joe Marcelino, East Bay Codes and Standards RECOMMENDATION: Add new subsection (c) as follows: (c} Unground Conductors o f Multiwire Branch Circuits. Ungrounded conductors of a multiwire branch c i r c u i t shall each be of a color or distinguishment to i d e n t i f y the feeder by which i t is supplied and each conductor of the same i d e n t i f i c a t i o n shall be connected to the same feeder. SUBSTANTIATION: Many neutral conductors of multiwire branch c i r c u i t s are overloaded due to improper phasing of conductors, splices and connection of devices. Color coding of the ungrounded conductors of a multiwire branch c i r c u i t is a safety, as well as a design consideration f o r safe and proper wiring. Much e l e c t r i c a l work is installed with the NEC, minimum requirements, as the only design c r i t e r i a . Failure to connect the proper conductor to loads supplied by multiwire branch c i r c u i t s can result in overloading of the unprotected neutral conductor to as much as three times i t s allowable ampacity or in the case of two, four wire c i r c u i t s , to as much as six times its allowable ampacity. The resultant overheating of a neutral wire is no less a hazard than of an ungrounded conductor. Log # 625 2- 13 - (210-5(c)-(New)): Reject SUBMITTER: Henry Garrett, Southern Nevada Chapter of ICBO RECOMMENDATION: Wheremultiwire branch c i r c u i t s comprising voltages of 480/277-208/120 are installed in the same building(s) the following color code shall be observed throughout the system: 24 208/120 Systems 480/277 Systems A Phase Black B Phase Red C Phase Blue D Phase White A Phase Brown B Phase Orange C Phase Yellow D Phase Gray 480V phase voltage, and the balance of conductors f o r lower voltage c o n t r o l ; (3) some conductors at 240V phase voltage with other conductors at 120V, etc. As you can see, each one of these cables would require a d i f f e r e n t color coding and y e t , as discussed above, with no requirement f o r consistency i t would not contribute anything to personnel safety. VOTE ON PANEL ACTION: A~'~IRMATIVE: 9 NEGATIVE: Schuck. EXPLANATION OF VOTE: SCHUCK: The submitter proposes that i d e n t i f i c a t i o n be by "color or distinguishment." The Panel Comment addresses the possible l i m i t a t i o n s of a "color code," but ignores the provision of the proposal which permits the i d e n t i f i c a t i o n of the ungrounded conductors by other means. With the increased use of several d i f f e r e n t voltage systems within the same building, i d e n t i f i c a t i o n of the conductors is more important than ever. I t would provide an additionalmeasure of safety f o r the personnel who w i l l be maintaining and a l t e r i n g these i n s t a l l a t i o n s in the f u t u r e . I t would also be in the best i n t e r e s t of the customer to be assured t h a t in buildings with various voltages, the conductors would be r e a d i l y i d e n t i f i e d so as to avoid costly errors, safety hazards or inadvertant overloads. The preponderance of proposals on t h i s subject at every Code revision c e r t a i n l y indicates the need f o r such a provision. (1) Conductors smaller than No. 8 AWG shall be i d e n t i f i e d by the outer covering of the conductor. (2) Conductors No. 8 and larger shall be s u i t a b l y i d e n t i f i e d at t h e i r point of termination with a l i s t e d i d e n t i f i c a t i o n marker. SUBSTANTIATION: With increasing numbers of i n s t i t u t i o n a l , educational and commercial f a c i l i t i e s using the above mentioned voltages, some guidelines should be established on a national basis. In the past, Code Panel No. 2 has rejected color coding on the grounds that i t is a matter of design consideration. This may be true to some extent, but we ask" you to consider the f o l l o w i n g : (A) Safety--For the installer-maintenance personnel; and consumer. (B) Uniformity--For the ease of design, i n s t a l l a t i o n and inspection. (C) Consumer Satisfaction--To avoid future confusion and hazardous errors in the expansion and maintenance of occupied buildings. We would also remind you t h a t : At present, we have both design engineers, e l e c t r i c i a n s and inspectors in the f i e l d that are not aware there ever was a color section in the NATIONAL ELECTRICAL CODE. Many of these people now belong to a highly mobile work force and the r e s u l t has been increasing confusion as to what good wiring practices are regarding the above color system. Without some type of guideline to f o l l o w , t h i s condition can only become more serious as time passes. **THE ABOVE IS NOT INTENDED TO EXCLUDE THE USE OF MANUFACTURED CABLE. PANEL ACTION: Reject. PANEL COMMENT: See Panel Comment f o r Proposal 2-14. VOTE ON PANEL ACTION: AFFIRMATIVE: 9 NEGATIVE: Schuck. EXPLANATION OF VOTE: ~ a s comment on Proposal 2-14. I Log # 645 2- 14 - (210-5(c)-(New)): Reject Secretary's Note: I t was the action of the Correlating Committee that f u r t h e r consideration be given to the comments expressed in the negative voting. SUBMITTER: Allen Sligh, Bureau of E l e c t r i c i t y , City of Alameda, CA RECOMMENDATION: Add as follows: "(c) Ungrounded Conductors of Multiwire Branch C i r c u i t . Ungrounded conductors of a multiwire branch c i r c u i t shall each be of a color or distinguishment to i d e n t i f y the feeder by which i t is supplied and each conductor of the same i d e n t i f i c a t i o n shall be connected to the same feeder." SUBSTANTIATION: Many neutral conductors of multiwire branch c i r c u i t s are overloaded due to improper phasing of conductors, splices and connection of devices. Color coding of the ungrounded conductors of a multiwire branch c i r c u i t is a safety, as well as a design consideration f o r safe and proper wiring. Much electrical work is installed with the NEC, minimum requirements, as the only design c r i t e r i a . Failure to connect the proper conductor to receptacles supplied by multiwire branch circuits can result in overloading of the unprotected neutral conductor to as much as three times its allowable ampacity or in the case of two, four-wire circuits, to as much as six times its allowable ampacity. The resultant over-heating of a neutral wire is no less a hazard than that of an ungrounded conductor. The identification of ungrounded conductors of a multiwire branch circuit permits the electrician to install devices in a manner that will result in a balancing of the phase loadings and neutral load. Detection of improper phasing of a multiwire circuit by the inspecting authority is extremely d i f f i c u l t without conductor identification and v i r t u a l l y impossible when making a final inspection of work that is not energized, as is often the case. The proposal, as written, would offer a simple means for both the electrician, inspector, and subsequent electricians to determine and maintain correct circuit phasing. PANEL ACTION: Reject. ~ T : There are not enough colors to cover the variations in systemsand voltages. Green, white and grey are committed in Section 210-5. Orange and brown are committed in Section 517-104(a)(5) for isolated c i r c u i t s . . The diverse practices in existing installations would cause incompatibility problems with the proposed color coding requirements. A false sense of security, leading to unsafe practices could result. Everyconductor should be considered alive unless proven otherwise. The logistics and cost problems of manufacturing, shipping, stocking and installing the many colors of conductors would be unjustifiably severe. When factory assembled cables are used, TC, ALS, CS, MC, NM, SNM, etc., i t becomes almost an "impossibility to comply with this section. The cables can be ordered with specific color coding provided a minimum manufacturing quantity is needed; however, there will be a delivery delay and a higher cost for less than normal manufacturing runs. For example, when a seven conductor, 600 volt cable is manufactured for stock, the manufacturer has no way of knowing the ultimate application: (1) all conductors at the samo voltage in a control c i r c u i t ; (2) some conductors at 25 2- 15 - (210-6(a), Exception No. 1): Accept Secretary's Note: The Correlating Committee directs CMP 2 to c o r r e l a t e the discrepancy between the Panel Actions on Proposals 2-15 and 2-16. SUBMITTER: CMP 2 ~DATION: Change " i n i n d u s t r i a l establishments" in second i i n ' ~ T o '~-w~t--h~n the confines of i n d u s t r i a l premises." SUBSTANTIATION: To c l a r i f y t h a t i t is the Panel's i n t e n t that the Exception includes i n d u s t r i a l areas outside of i n d u s t r i a l buildings, such as parking l o t s , storage areas, and roadways. PANEL ACTION: Accept. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . 2- 16 - (210-6): Accept Secretary's Note: I t was the action of the Correlating Committee t h a t f u r t h e r consideration be given to the comments expressed in the negative voting. SUBMITTER: CMP 2 ITEIjOI~'I~ATION: Revise Section 210-6. Maximum Voltage to read as follows: 210-6. Maximum Voltage. (a) 150 Volts to Ground. Branch c i r c u i t s shall not exceed 150 v o l t s to ground when supplying medium-base screw-shell l ampholders or 125-volt receptacles. (b) 300 Volts to Ground. Branch c i r c u i t s shall not exceed 300 v o l t s to ground when supplying ( i ) mogul-base screw-shell l ampholders or, (2) l ampholders of other types, applied within t h e i r voltage or, (3) b a l l a s t of electric-discharge lamps. Exception No. 1: For l ampholders of infrared i n d u s t r i a l heating appliances as provided in Section 422-15(c). Exception No. 2: The railway properties described in Section 110-19. Exception No. 3: Branch c i r c u i t s which supply only electric-discharge l i g h t i n g provided all of the f o l l o w i n g conditions are met: (a) The voltage between conductors does not exceed 600 v o l t s . (b) The b a l l a s t is i d e d t i f i e d f o r use on ungrounded c i r c u i t s . (c) The f i x t u r e s are mounted outdoors on poles or similar structures, not buildings, at not less than 22 feet (6.71 m) in height or in tunnels at not less than 18 feet (5.49 m) in height. (c) Exceeding 300 Volts to Ground. Branch-circuits exceeding 300 v o l t s to ground which do not exceed 600 v o l t s between conductors, shall only be permitted to supply b a l l a s t of electric-discharge lamps in permanently i n s t a l l e d f i x t u r e s mounted as follows: ( i ) Mounted outdoors not less than a height of 22 f e e t (6.71 m) on poles or similar structures (not b u i l d i n g s ) . (2) In tunnels not less than a height of 18 f e e t (5.49 m). FPN: See Section 410-78. SUBSTANTIATION: To c l a r i f y that the 22 f e e t and 18 f e e t minimum mounting heights apply only where the voltage exceeds 300 volts betwoen conductors. PANEL ACTION: Accept. VOTE ON PANEL ACTION: AFFIRMATIVE: 9 NEGATIVE: Yerke. EXPLANATION OF VOTE: YERKE: The proposal would permit the i n s t a l l a t i o n of the presently limited-use equipment to be accessible to the general public in dwelling units and in commercial and i n d u s t r i a l establishments. There are risks associated with the equipment presently specified in these exceptions that their use should not be expanded without the existing safeguards. The changes 9o beyond the substantiation since such aspects such as establishment exception, supervision, height, integral switch, permanently installed features have not been addressed. Log # 860 2- 20 - (210-8-(New)): Accept in Part SUBMITTER: H. Brooke Stauffer, NEMA ~ T I O N : All 125-volt, single-phase, 15- and 20-ampere receptacles installed in basements shall have ground-fault circuit-interrupter protection for personnel. Exception: Single receptacle outlets permanently marked or identified for supplying specific cord- and plug-connected appliances. SUBSTANTIATION: a. Basements have the same degree of shock hazard potential as bathrooms and garages, and should therefore be provided with ground-fault protected receptacle circuits for portable tool and appliance use. b. An Exception is needed for stationary or fixed appliances such as freezers, washers and refrigerators. These appliances are likely to have high leakage currents and to cause considerable inconvenience i f de-energized. c. During the period January i, 1975, through December 31, 1980, the UL Clipping Service recorded 14 deaths and 2 injuries from electrical shock in basements of dwelling units. These deaths and injuries would likely have been prevented had GFCI's been installed. As the UL Clipping Service reports only a fraction of the electrical accidents occurring in the United States, the number must actually be much higher. A summary of the accident data follows: Injury Death 1975 5 1976 2 1977 2 1978 2 2 1979 2 1980 1 Log # 80 2- 17 - (210-7(d) Exception): Reject SUBMII-TER: Howard A. Miller, Parma, OH ITET~R~J~[E'N-~ATION: None. SUBSTANTIATION: In regard to the Exception, i t no doubt has been inserted for valid reasons, but i t also can cause confusion. The thousands of home owners who know nothing about grounding, bonding or other terms are only interested in purchasing a receptacle and installing i t , either a two prong or a three prong, as long as i t is new, works and has a shiney wall plate. When a two prong receptacle is replaced with another two prong we are telling the manufacturer to continue making appliances with different types of wiring, residential two-wire and commercial three-wire, setting up two types of standards. I f a home owner buys a three-prong cord o÷ piece of equipment i t will not f i t in the two-prong receptacle so they use an illegal adapter, do not use the grounding wire, which does nothing anyhow, or else break off the grounding prong on the equipment, thus making useless the grounding feature, i f used, in another three-prong grounded receptacle. Instead of gradually eliminating two-prong receptacles in older homes, we are continuing the process and also continuing a more dangerous situation. People with newer homes and three-prong grounded receptacles are s t i l l forced to use antiquated two-wire pieces of residential equipment due to tw~ standards s t i l l in existence. Two-wire equipment i f continued to be made can s t i l l be plugged, any position, into older type two-wire receptacles, thus at times making "Hot" lamps, radios, and some appliances. Possibly, what could be done, would be to replace a two-wire receptacle with a three-wire one and also labeling the receptacle as not grounded. PANEL ACTION: Reject. PANEL COM~NT: Could lead to a false sense of security and discourage the installation of a properly installed equipment grounding conductor. VOTE ON PANEL ACTION: Unanimously Affirmative. TOTAL ~2~ 1-4- The following are summarized from the UL Clipping Service and describe the accidents in more d e t a i l . In addition, a chart is appended providing an overview of all data considered in preparing this and other proposals. (See Chart on "Shock and Burn Incidents-Basements" on next page.) PANEL ACTION: Accept in Part. PANEL COF~ENT: See Panel Proposal 2-19. VOTE ON PANEL ACTION: AFFIRMATIVE: 8 NEGATIVE: Craig, Reign. EXPLANATION OF VOTE: CRAIG: See comment on Proposal 2-19. REIGN: See my comment on Proposal 2-19. Log # 666 2- 18 - (210-7(d), Exception): Accept Secretary's Note: I t was the action of the Correlating Committee that this proposal be referred to C~ 5 for comment and that the conflict with Section 210-7(b) be resolved. SUBMITTER: Warren H. Cook, IEEE ~ATION: Exception: Where a grounding means does not exist in the receptacle enclosure either a nongrounding "or a ground-fault circuit-interrupter" type of receptacle shall be used. (Change in quotations) SUBSTANTIATION: In older buildings where a ground is not available in the receptacle enclosure, i t should be permissible to provide some type of personnel protection. This is particularly important in areas designated in Section 210-8(a). PANEL ACTION: Accept. VOTE ON PANEL ACTION: Unanimously Affirmative. 2- 19 - (210-8(a)(4)-(New)): Accept SUBMITTER: CMP 2 ~ATION: Add a new paragraph to read as follows: "(4) At least one 125-volt, single-phase, 15- or 20-ampere receptacle outlet installed in a basement shall have ground-fault circuit-interrupter protection for personnel, and i t shall be so identified." SUBSTANTIATION: Manybasements have habitable rooms and dedicated appliances. I t is the Panel's opinion that all receptacle outlets in all basements do not require GFCI protection. PANEL ACTION: Accept. VOTE ON PANELACTION: AFFIRMATIVE: 8 NEGATIVE: Craig, Reign. EXPLANATION OF VOTE: CRAIG: Grounding type receptacles as required by Section 210-7 already recognized safe and effective means of protection. The constant effort to employ the use of G.F.C.I. only adds to cost. REIGN: Three-wire, 120-volt, 15- and 20-ampere branch circuits together with grounding-type receptacles required by the Code provide an OSHArecognized safe and effective means of protecting people from electric shock when using or touching 3-wire cord- and plug-connected equipment. Rather than continue the practice of expanding the requirements for GFCI's with each Code revision and further adding to skyrocketing construction costs, our efforts should be directed toward requiring all cord- and plug-connected equipmeot to be furnished to take advantage of the safety already afforded by 3-wire systems and grounding-type receptacles. 26 SHOCK A N D ~ January INCIDENTS-BASFJ~E~LTS thru December 19~U Comments Incident Identification Number Electric Product Involved Age & Sex Inj. or Dead Date of Incident and Location 1-75-34 Drill 50-M Dead 3-14-75 Basement Des Rlaines, IL Electrocuted while using a drill. 3-75-75 Drill 34-M Dead 7-8-75 Basement Watertown, NY Electrocuted while using an ungrounded electric dri11. 3-75-15 Fan Cord 42-F Dead 7-16-78 Basement Reading, PA Electrocuted by plugging in a fan while standing in water. 3-75-30 Lamp' 21-F Dead 7-24-75 Basement Newark, NJ Electrocuted by plugging in a lamp while standing barefooted on a sewer pipe. 3-75-72 Drill 50-M Dead 8-21-75 Basement Oxford, NC Electrocuted while using a small electric d r i l l . 1-76-3 Cord 20-F Dead 2-11-76 Basement Cincinnati, OH Electrocuted when plugging in an appliance while standing barefooted on a wet floor. 1-76-19 Cord 33-F Dead 2-19-76 Basement Springfield, IL Electrocuted when checking a cord connected pump in 6 inches of water. 3-77-82 Drill 28-M Dead 7-i-77 Basement Omaha, NE Electrocuted while using an electric d r i l l . 3-77-45 Lamp 78-F Dead 8-26-77 Basement Thetford, VT Electrocuted while plugging in a metal lamp in a wet environment. 2-78-48 Toy Train 15-M Dead 6-14-78 Basement Pine Township, PA Using electric train in basement. 3-78-107 Drill 48-M Inj. 7-1-78 Basement Spirit Lake,IO Shocked by an electric d r i l l while standing barefooted on a wet floor. 3-78-90 Sander 16-M Inj. 8-14-78 3-78-71 Sump Pump 16-M Dead 8-3-78 Basement Arthur, IL 2-79-27 Pump 33-M Dead 4-12-79 Basement Mt. Pulaski, Shocked unconscious by a sander while barefooted. Taken to hospital. Went barefoot into wet basement to check sump pump. IL Electrocuted when plugging in a sump pump while standing in water. 3-79-22 Clothes Dryer or Sump Pump 32-F Dead 9-14-79 Basement Garretsville, OH Attempted to turn o f f dryer while standing in basement in 2 f t . of water. Had been trying to pump basement with new, non-submersible electric pump. 1-80-17 Sewer cleaning machine 27-M Dead 1-26-80 Basement Ft. Dodge, IA Standing in water in basement of a home attempting to open a drain. Switched on machine. 21 SHOCKAND BURN INCIDENTS SUMMARY 1975 THROUGH1980 KIT BATHROOMS IN HOTELS/MOTELS YEAR INJ. DEATHITOTAL 1 1975 COUNTER TOP RECEPTACLES INJ. DEATH TOTAL 1 1976 ,1977 J 2 l 1 2 2 2 1978. ] ,1979 ] , AV/yj SCHOOLS OTHER RECEPTACLES INJ. DEATHITOTAL RECEPTACLES 6' FROM B A S I N OTHER RECEPTACLES INJ. )EATH TOTAL INJ. DEATH FOTAL l 1 1 l l 1 l l 2 BASEMENTS IN DWELLING! INJ. 3 3 .5 .5 0.2 DEAT TOTAL l l 2 5 5 1 I 2 2 2 2 2 2 4 2 2 1 1 14 16 2.3 2.6 l l 2 1 I ,TOTALI HENS 1 2 1 1 5 6 4 4 1 1 2 3 2 5 2 0.8 1.0 0.7 0.7 0.2 0.2 0.3 0.5 0.3 0.8 0.3 Review of the data did not reveal any accidents in the following areas: Bathrooms in dormitories Bathrooms in nursing homes Bathrooms in shopping centers Bathing rooms in R.V. parks Laundry areas in R.V. parks Bathrooms in service stations Bathrooms in airports Bathrooms in R.V. parks Bathrooms in other locations Vehicle repair areas in R.V. parks Log # 96 2- 21 - (210-8(a)): Reject SUBMITTER: Joseph S. Pangborn, F. N. Zaino & Associates ~ATION: Change210-8(a) to read as follows: 210-8 Ground Fault Protection for Personnel. (a) Dwelling Units, Industrial, Institutional and ~ommercial Occupancies. (1) All 120 volt, single-phase, 15- and 20-ampere receptacles installed in bathroom and garages of dwelling units shall have ground-fault circuit interrupter. (2) All 120 volt, single-phase 15- and 20-ampere receptacles installed in bathrooms of commercial, institutional and industrial occupancies shall have ground-fault circuit-interrupter protection for personnel. (3) All 120 volt, single-phase 15- and 20-ampere receptacles installed outdoors of dwelling units, industrial, institutional, and commercial occupancies, shall have ground-fault circuit-interrupter protection for personnel. Exception: Whenthe sole purpose of an outdoor receptacle is to provide for wheelchair l i f t a NEMA6-15 R receptacle may be installed. That receptacle shall be in addition to those required by in accordance with the provisions of Section 410-57. (4) For the purposes of Article 210-8(a) dwelling units shall also include hotel and motel. Guest rooms and public t o i l e t rooms. (51 Provide ground-fault circuit-interrupter protection for the two (2) 20-ampere small appliance circuits required in kitchens of all dwelling units. "BATHROOM: A bathroom is an area including a basin with one or more of the following: a t o i l e t , a tub, or a shower." Such ground-fault circuit-interrupter protection may be provided for other circuits, locations and occupancies, and where used, will provide additional protection against line-to-ground shock hazard. FPN: See Section 215-9 for feeder protection. SUBSTANTIATION: We feel that ground-fault receptacles should be provided in bathrooms of all institutional, residential and commercial occupancies (hotels and motels) as personnel are as likely to use hair dryers, hair curlers, electric razors, etc. in these f a c i l i t i e s as in dwelling units. Also, we feel that the two 20-ampere appliance circuits in the kitchen should be on ground-fault due to the fact there are now numerous electrical appliances for use in the kitchen which are furnished, "UL approved" with two wire non-grounded cords. These appliances, in most cases, are utilized in close proximity to the grounded sink or range. PANEL'ACTION:Reject. PANEL COF~MENT: The Panel does not feel that there is substantiation to support such a broad requirement. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 424, 1237 2- 22 - (210-8(a)(i)): Accept in Part Secretary's Note: The Correlating Committee requests that CMP 2 clarify their action and the appropriateness of the location in the Code. SUBMITTERS: Southwestern Section IAEI (424) ~ 3 7 ) RECOMMENDATION: All 120-volt, single-phase, 15- and 20-ampere receptacles installed in bathrooms and garages of dwelling units and bathrooms of guest rooms in hotels, motels and similar occupancies shall have ground-fault circuit-interrupter protection for personnel. SUBSTANTIATION: Section 210-25(c) requires that receptacles be installed in guest rooms for hotels, motels, and similar occupancies in accordance with 210-25(b), but since these rooms are not considered dwelling units as pe~ definition in Article 100, the bathroom receptacle is not required to be on a ground-fault circuit-interrupter. PANEL ACTION: Accept in Part, Revise as follows: 'All 125-volt, single-phase, 15- and 20-ampere receptacles installed in bathrooms of guest rooms in hotels and motels shall have ground-fault circuit-interrupter protection. PANEL COM~NT: I t is not the intent of the Panel to extend the GFCI protection to "similar occupancies" because of lack of substantiating data. VOTE ON PANELACTION: AFFIRhV~TIVE: 9 NEDATIVE: Reign. EXPLANATION OF VOTE: REIGN: See my comment on Proposal 2-19. 28 Log # 1119,1122 2- 23 - (210-8(a)(1)): Reject SUBMITTER: Joe Marcelino, E l e c t r i c a l Contractors Trust of Alameda County (1119) Jack Smith, East Bay Uniform Electrical Code Committee (1122) RECOMMENDATION: Delete entire paragraph and substitute the following paragraph. (1) all 125-volt, single-phase, 15- and 20-ampere receptacles •installed in bathrooms within seven (7) feet of a bathtub, shower, or basin shall be groundfault circuit-interrupter protection for personnel. SUBSTANTIATION: Present wording allows the installation in an area of a bathtub or shower to have an outlet installed nearby without ground-fault protection i f they are not in an "area" with a basin. This unsafe practice would be eliminated with this roposal. ANEL ACTION: Reject. PANEL COMMENT: No substantiation that the proposed requirement would be safer than the present requirement. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 793 2- 28 - (210-8(a)(2)): Reject SUBMITTER: Bob Raymer, California Building Industry Association RECOMMENDATION: (Delete) "All 125-volt, single-phase, 15- or 20-ampere receptacles installed in garages shall have ground-fault circuit-interrupter protection for personnel." SUBSTANTIATION: The periodic surge in current associated with a freezer unit kicking on is often enough to t r i p the ground-fault circuit-interrupter which is currently required in garages. This has resulted in the commonplace nuisance of food spoilage in the garage freezer. In response to t h i s problem a high number of builders are providing a conventional o u t l e t in the garage as a dedicated o u t l e t f o r a freezer in addition to the required GFCI. A survey of builders is c u r r e n t l y underway which deals with the GFCI problem. The r e s u l t s , once compiled, w i l l be promptly forwarded to your o f f i c e . PANEL ACTION: Reject. PANEL COMMENT: Present Code provides exceptions to cover the problems described. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . Log # 67 2- 24 - (210-8(a)(1), Exception-(New)): Reject SUBMITTER: John E. Grant, Kittery, ME E~FECO-MMENDATION: Exception: Receptacles for appliances occupying dedicated space which are cord- and plug-connected in accordance with Section 400-7(a)(6), (a)(7), or (a)(8). SUBSTANTIATION: A similar Exception appears in Section 210-8(a)(2) for garages. The same reqdirement for bathrooms would c l a r i f y that receptacles installed for clothes washers or clothes dryers (120V) would not require GFCI protection for personnel. PANEL ACTION: Reject. PANEL COM~NT: There is a lack of substantiation for a proposal which would decrease the safety requirements. VOTE ON PANEL ACTION: Unanimously Affirmative. Log ~ 426 2- 29 - (210-8(a)(2), Exception No. 2): Reject SUBMITTER: Southwestern Section IAEI RECOMMENDATION: ChangeException to read: "Receptacles for appliances when of the single type, located behind appliance space and not more than 34 inches above floor or grade." SUBSTANTIATION: This practice has been used for 3 years and has eliminated the problem of dedicated space where appliance must be in place prior to final inspection. The single receptacle does away with hazard of receptacle being used for portable tool use. By its location and height behind the appliance does not provide for ready accessibility for use. The present wording of dedicated space created a major problem for inspectors in getting final inspections as appliances are not moved in until dwelling is occupied. Also, as this is an extra cost, the owners do not have receptacle installed i f they do not have freezer or other appliances for use in this area. PANEL ACTION: Reject. PANEL COMMENT: Proposal does not provide as much safety as present wording. VOTE ON PANEL ACTION: AFFIRMATIVE: 9 NEGATIVE: Bowling. EXPLANATION OF VOTE: BOWLING: See comment regarding Proposal 2-31. ~ Log # 425 2- 25 - (210-8(a)(2)): Reject SUBMITTER: Southwestern Section IAEI ~ATION: Revise Section 210-8(a)(2). Where 12B-volt, single-phase, 15- and 20-ampere receptacles are installed in garages, at least "one of the receptacles shall have ground-fault circuit-interrupter protection for personnel and shall be so identified. This receptacle shall not be one of those dedicated for the use of freezers, water softeners, clothes washers, door openers, or other similar appliances. SUBSTANTIATION: Due to confusion over present wording, the intent can be obtained by above wording. PANEL ACTION: Reject. PANEL COMMENT: The proposal would provide less protection than the present requirements. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 861 2- 30 - (210-8(a)(2), Exception No. 2): Reject SUBMITTER: H. Brooke Stauffer, NEMA RECOMMENDATION: Change text to: "Exception No. 2 Single receptacle outlets permanently marked or identified for supplying specific cord- and plug-connected appliances." SUBSTANTIATION: The present wording has been misinterpreted and misunderstood. I t is d i f f i c u l t to enforce because appliances are not present when inspection is made. Also, the present v~rding allows use of a duplex receptacle for the "appliance occupying dedicated space." The second half of the unprotected duplex receptacle might be used for other purposes, which might create a hazard. PANEL ACTION: Reject. PANEL COMMENT: The proposal could encourage the use of wiring methods which will provide a lesser degree of safety. VOTE ON PANELACTION: Unanimously Affirmative. Log # 84 2 - 26 - (210-8(a)(2)): Reject SUBMITTER: Aron P. Larson, Bangor, ME ~ATION: Require outside GFCI receptacles on all attached ~garages (located near point of entry to garage) and a l l non-attached garages that are wired. Delete inside GFCI in arages. UBSTANTIATION: The GFCI protected receptacle located at entrance to garage will serve to protect personnel using lawn equipment, snowblowers, etc. I f receptacles within garages are to be GFCI'd, there also should be receptacles in basements. PANEL ACTION: Reject. PANEL COMMENT: The proposal would provide less protection than the present requirements in the Code. VOTE ON PANEL ACTION: Unanimously Affirmative. ~ Log # 1238 2- 31 - (210-8(a)(2), Exception No. 2): Reject SUBMITTER: IAEI RECOMMENDATION: Change exception to read: "A single receptacle located behind an appliance space and not more than 34 inches above floor or grade." SUBSTANTIATION: This practice has been used for 3 years and has eliminated the problem of dedicated space where appliance must be in place p r i o r to final inspection. The single receptacle does away with hazard of receptacle being used for portable tool use. By i t s location and height behind the appliance does not provide for ready accessibility for use. The present wording of dedicated space created a major problem for inspectors in getting final inspections as appliances are not moved in until dwelling is occupied. Also, as this is an extra cost, the owners do not have receptacle installed i f they do not have freezer or other appliances for use in this area. PANEL ACTION: Reject. PANEL COMMENT: See Panel Comment for Proposal 2-29. VOTE ON PANEL ACTION: A~-FIRMATIVE: 9 NEGATIVE: Bowling. EXPLANATION OF VOTE: BOWLING: This proposal would enhance enforcement in that i t would eliminate the present requirements that appliances be in place at time of inspection. Log # 509 2- 27 ~ (210-8(a)(2)): Reject SUBMIl-[ER: Tom Burnett, Sheldon, IA ~ATION: I recommend that the ceiling receptacles in the attached garage be stated as single. SUBSTANTIATION: So as to prevent use other than garage door opener. I f a duplex receptacle is to be installed in ceiling i t should be on GFI for personal safety, so as to prevent potential shock hazard. PANEL ACTION: Reject. PANEL COMMENT: Since the receptacle is not readily accessible the Panel believes that a single receptacle is not necessary. VOTE ON PANELACTION: Unanimously Affirmative. 29 Log # 83 2- 32 - (210-8(a)(3)): Reject SUBMII-FER: Richard Reeves, Reeves Electric Co. RI~-C"OI~IREITDATION: Delete the words, "where there is direct grade level access to the dwelling unit and to the receptacles." SUBSTANTIATION: All outdoor receptacles at dwellings should have GFCI protection for personnel. PANEL ACTION: Reject. PANEL COMMENT: Substantiation does not support the proposal. VOTe'ON PANELACTION: UnanimouslyAffirmative. VOTE ON PANELACTION: AFFIRMATIVE: 8 NEGATIVE: Craig, Reign. EXPLANATION OF VOTE: CRXfG: See comment of Proposal 2-19. REIGN: See my comment on Proposal 2-19. Log # 374 2- 38 - (210-8(a)(4)-(New)): Accept in Principle SUBMITTER: Lee Peterson, Sheldon, IA ~DATION: All 125-volt single-phase, 15- and 20-ampere receptacles installed in workshops in the basement shall shall ground-fault circuit-interrupter protection for personnel. SUBSTANTIATION: Workshops are often located in the basement where many hand-tools are operated. This area, is often a damp or wet location. This requirement would protect personnel from ground-fault currents. PANEL ACTION: Accept in Principle. PANEL COF~MENT: See Panel Action on Proposal 2-20. VOTE ON PANELACTION: AFFIRMATIVE: 8 NEGATIVE: Craig, Reign. EXPLANATION OF VOTE: CRAIG: See comment of Proposal 2-19. REIGN: See my comment on Proposal.2-19. Log # 862 2- 33 - (210-8(a)(3)): Reject SUBMII-FER: H. Brooke Stauffer, NEMA ~ATION: Movedefinition of "Bathroom" to Article 100-Definitions. SUBSTANTIATION: The term "Bathroom" appears also in Sections 551-7(c)(1), 550-4(a), 550-6(b), and 550-6(d). PANEL ACTION: Reject. PANEL COMMENT: The definition is unique to the requirements of this Section. VOTE ON PANELACTION: Unanimously Affirmative. Log # 1663 2- 34 - (210-8(a)(3)): Reject SUBMIITER: Charles "Mike" Holt, Concepts in Electricity, Inc. ~ATION: Removedefinition of Bathroom from 210-8(a)(3) and move to Article 100. SUBSTANTIATION: All definitions should be consistently found in Article 100, or i f they conflict with other sections, should be located at the front of each section where they are applicable. PANEL ACTION: Reject. PANEC COM~NT: See Panel Comment for Proposal 2-33. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 863 2- 39 - (210-8(a)(4)-(New)): Accept in Principle SUBMITTER: H. Brooke Stauffer, NEMA RECOMMENDATION: All 125-volt, single phase, 15- and 20-ampere receptacles installed at counter tops as required by Section 210-52(b) shall have ground-fault circuit-interrupter protection for personnel. SUBSTANTIATION: a. Metal frames of electrically heated appliances operating at less than 150 volts to ground, such as toasters and electric coffee makers, are not required to be, and often are not, grounded (Ref. Section 422-16). b. Certain appliances commonly found in kitchens may have live parts necessarily exposed, such as toasters and g r i l l s (Ref. Section 422-2). c. Kitchens have large areas of grounded metal which, with a. and b. above, offer a substantial opportunity for ground-fault accidents involving personnel. These grounded devices include, but are not limited to: ~I tainless steel sinks and metal faucets Electric ranges 3) Refrigerators and f[eezers Log # 511 2- 35 - (210-8(a)-Bathroom): Reject SUBMITTER: James Lofflin, Sheldon, IA RECOMMENDATION: 1. Should be included in Article lO0-Definitions, also; 2. Bathroom: A bathroom is an area including a basin with one or more of the following:. A t o i l e t , a tub, or a shower, without separation by walls, partitions, or room dividers. SUBSTANTIATION: In some cases the distance between the basin and other porcelain fixtures is less than 8 feet horizontally yet physically impossible to reach because of walls, partitions, or permanent room dividers. Does this eliminate the need for GFCI or does i t necessitate 2 GFCI's? Generally speaking the GFCI is needed at the basin location i f i t ' s a bathroom or not. PANELACTION: Reject. PANEL COMMENT: See Panel Comment for Proposal 2-33. VOTE ON PANELACTION: Unanimously Affirmative. d. This proposal does not have the effect of requiring refrigerators, freezers, and other fixed and stationary kitchen appliances to be protected by GFCI's. e. During the period January 1, 1975, through December 31, 1980, the UL Clipping Service recorded 5 deaths and I injury from electrical shock in kitchens of dwelling units that would likely have been prevented had GFCI's been installed. As the UL Clipping Service reports only a fraction of the electrical accidents occurring in the United States, the number must actually be much higher. A summary of the accident data follows: Log # 361 2- 36 - (210-8(a)(4)-(New)): Reject SUBMITTER: Dale M. Konz, Alton, IA RECOMMENDATION: 210-8(a)(4) Receptacles by kitchen sink which are not intended for motorized equipment such as blenders and mixers shall be GFCI. SUBSTANTIATION: When washing dishes and sink is f u l l of water, personnel could plug radio into outlet and be shocked. PANELACTION: Reject. PANEL COMMENT: See Panel Action on Proposal 2-37. VOTE ON PANELACTION: UnanimouslyAffirmative. 1975 1976 1977 1978 1979 1980 TOTAL Injury Death 1 2 i T 1 The following is summarized from the UL Clipping Service and describes the accidents in more detail, (See Chart on "Shock and Burns Incidents-Home Kitchens" on next page.) Log # 375 2- 37 - (210-8(a)(4)-(New)): Accept in Principle SUBMITTER: Bryan Petersen, Marcus, IA ~ATION: All 125-volt, single-phase, 15- and 20-ampere receptacles installed within 3 feet on either side of the kitchen sink shall be ground-fault circuit-interrupter protected for personnel. SUBSTANTIATION: I feel that the outlets in the kitchen need to be protected the same as the outlets in the bathroom. Small appliances are used around the sink and the person running them should be protected from hazardous shock. PANEL ACTION: Accept in Principle. t Revise to read as follows: All 125-volt, single-phase, 15- and 20-ampere receptacles above countertops installed within 6 feet on either side of the kitchen sink shall be ground-fault circuit-interrupter protected for personnel. PANEL COMMENT: The Panel f e l t that in recognition of the lengths of appliance cords, the distance should be increased to 6 feet. There is no supporting data to include other than countertop receptacle outlets. 30 SHOCK AND BURN INCIDENTS-HOME KITCHENS January 1975 thru December 1980 Comments Incident Identification Number Electric Product Involved Age & Sex Inj, or Dead Date of Incident and Location 1-75-4 Toaster 20-F Dead 2-24-75 Kitchen of Home Buffalo, MN Electrocuted by a toaster. 3-76-21 Lamp Cord 52-M Dead 7-28-76 Kitchen of Home Boston, MA Electrocuted by touching an incorrectly wired lamp while leaning naked on a metal counter rim in the kitchen. 4-76-205 Appliance I-F Dead 1-8-77 Kitchen of Home Bath, NY Electrocuted by an appliance while sitting in a sink with water in i t , 2-78-49 Washing Machine 33-F Dead 5-19-78 Kitchen of Home Berkley, MI Electrocuted while repairing a belt on an old washer while i t was plugged in 2-79-8 Toaster 5-F Dead 5-9-79 Kitchen of Home Pontiac, MI Electrocuted by sticking a knife in an electric toaster while touching a stainless steel sink. 2-80-15 Cord 9mo-F Dead 5-31-80 Phoenix, AZ Grasped frayed cord on kitchen floor. 3-80-33 Toaster 5-M Dead 8-14-80 Kitchen of Home Eagle, WI Apparently electrocuted by touching faulty toaster while soaking foot in a cast iron sink. 4-80-1 Receptacle 26-F Inj. 11-18-80 Kitchen of Home Wilimgton, DE Shocked unto unconsciousness by touching an outlet with a metal pan, while standing on a wet floor Sent to hospital. PANEL ACTION: Reject. PANEL COMMENT: Present UL Standard has approximately 100 milliamperes in I00 milliseconds and 160 milliamperes in 50 milliseconds. Typical Class "A" GFCI's t r i p at 10 milliampere in 100 milliseconds and 20 milliamperes in 50 milliseconds, essentially where proposed values with minus tolerance would be, namely 12 milliamperes in 100 milliseconds and 20 milliamperes in 50 milliseconds. The proposal has not addressed the long time effects, longer than 100 milliseconds. I t is an incomplete requirement and n~ guidance is provided as to which value device must meet. I t is more restrictive at the two points selected than present UL Standard. VOTE ON PANEL ACTION: Unanimously Affirmative. PANEL ACTION: Accept in Principle. PANEL COM~NT: See Panel Comment for Proposal 2-37. VOTE ON PANEL ACTION: AFFIRMATIVE: 8 NEGATIVE: Craig, Reign. EXPLANATION OF VOTE: CRAIG: See comment of Proposal 2-19. REIGN: See my comment on Proposal 2-19. Log # 1202 2- 40 - (210-8(b)): Accept Secretary's Note: The Correlating Committee has transferred the ground-fault circuit-interrupter requirements for construction sites to Article 305. SUBMITTER: Charles J. Hart, NECA ~ATION: Delete Section 210-8(b). SUBSTANTIATION: This proposal is in conjunction with a proposal to add a new Section 305-4, Ground-Fault Protection. PANEL ACTION: Accept. VDTE ON PANELACTION: Unanimously Affirmative. Log # 864 2- 42 - (210-8(c)-(New)): Accept in Part SUBMITTER: H. Brooke Stauffer, NEMA ~ T I O N : Add new paragraph as follows: (c) Hotels, Motels and School Buildings. All 125-volt, single-phase, 15- and 20-ampere receptacles installed within 6 feet of a basin in hotels, motels, and school buildings shall have ground-fault circuit-interrupter protection for personnel. SUBSTANTIATION: a. Shock and injury hazards exist in these areas where portable electrical appliances are commonly used close to grounded surfaces. Use of these receptacles is similar to their use in dwelling occupancies, and the Code should be consistent in requiring the same protection. b. During the period January i , 1975, through December 31, 1980, the UL Clipping Service recorded 4 deaths and 1 injury from electrical shock in locations determined to be in the v i c i n i t y of basins in hotels, motels, and schools. The victims would l i k e l y have been protected had GFCI's been installed. As the UL Clipping Service reports only a fraction of the electrical accidents occurring in the United States, the number must actually be much higher. A summary of the accident data follows: Log # 124 2- 41 - (210-8(c) (New)): Reject Secretary's Note: This comment (No. 70-36, CMP 2) on Proposal No. 65 was for the 1981 Code and was held for further study. See NEC-TCD 1980 Annual Meeting. SUBMITTER: Richard P. Kuchnicki, National Association of Home Builders RECOMMENDATION: Add a new subsection (c) as follows: (c) Construction Specification. All 15- and 20-ampere ground-fault circuit-protection devices shall be manufactured to conform to one of the two following broad specifications: (1) 25 milliamperes, plus or minus 20 percent in 50 milliseconds maximum time. (2) 15 milliamperes, plus or minus 20 percent in 100 milliseconds maximum time. SUBSTANTIATION: Currently manufactured GFCI devices are not performing adequately and therefore should be removed from the market place so that the consumer can truly be protected. GFCI's meeting the above construction specs, can replace the inadequate devices. Injury 1975 1976 1977 1978 1979 1980 TDTAL 3i Death i 2 - 2 ~ 1 4 The following are summarized from the UL Clipping Service and describe the accidents in more d e t a i l . SHOCK AND BURN INCIDENTS-HOTEL - MOTELS BATHROOM January 1975 thru December 1980 Incident Identification Number Electric Product Involved Age & Sex Inj. or Dead Date of Incident and Location 4-75-67 Heater 46-M Dead 11-20-75 Bathroom of Hotel C l a r k s v i l l e , TN Found electrocuted in bathroom with burn marks on his body. There was an e l e c t r i c heater present. 4-77-4 Coffee Warmer 47-M Dead 11-23-77 Bathroom of Hotel Was using an e l e c t r i c coffee warmer a f t e r showering. 4-77417 Shaver 48-M Dead 12-30-77 Bathroom of Motel Tupelo, Miss Comments Using an e l e c t r i c shaver while running water in the tub SHOCK AND BURN INCIDENTS SCHOOLS January 1975 thru December 1980 Incident Identification Number Electric Product Involved Age & Sex Inj. or Dead Date of Incident and Location 1-75-3 Ext. Cord Ad-F Inj. 2-12-75 School kitchen Minn. Shocked by a food warmer while plugging i t into a receptacle - Taken to hospital. 1-75-23 Receptacle 15-M Dead 3-27-75 School Lab Failed to unplug an e l e c t r i c a l device before working inside it. PANEL ACTION: Accept See Panel Action on PANEL COMMENT: I t is is too broad. VOTE ON PANEL ACTION: in Part. Proposal 2-22. the opinion of the Panel that the proposal Comments PANEL ACTION: Reject. PANEL COMMENT: Panel has proposed to transfer t e x t and j u r i s d i c t i o n of Section 210-9 to Panel 13. VOTE ON PANEL ACTION: ~FIRMATIVE: 8 NEGATIVE: Cunningham, Reign. EXPLANATION OF VOTE: CUNNINGHAM: Panel 13 has not received a proposal to include Section 210-9 in A r t i c l e 450. The vote to reject could leave Section 210-9 as i t was before in A r t i c l e 210. This proposal for a t h i r d exception to allow autotransformer-supplied branch c i r c u i t s is needed to supply equipment with d i f f e r e n t or unusual voltage ratings. This practice is already accepted f o r feeders, especially in industrial i n s t a l l a t i o n s . I f the Correlating Committee is able to transfer the t e x t of Section 210-9 to A r t i c l e 450, the proposed exception should be allowed. REIGN: The proposed Exception No. 3, whether or not Section 210-9 is transferred to Panel 13, should be accepted because i t allows a c o s t - e f f e c t i v e method of operating u t i l i z a t i o n equipment that is not compatible With the existing voltage in an industrial or commercial f a c i l i t y . Unanimously A f f i r m a t i v e . Log # 1710 2- 43 - (210-9, FPN): Reject SUBMITTER: Charles "Mike" Holt, Concepts in E l e c t r i c i t y , Inc. ~OMMENDATION: Eliminate t h i s sentence from 210-9 and move i t to A r t i c l e 100. SUBSTANTIATION: D e f i n i t i o n ' f o r Autotransformers should be included under A r t i c l e 100 where most would look f o r a definition. All d e f i n i t i o n s should be in A r t i c l e 100 except where i t would c o n f l i c t with other Code sections. PANEL ACTION: Reject~ PANEL COMMENT: Present FPN is f o r information only. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . Log # 1883 2- 44 - (210-g,Exception No.3-(New)): Reject Secretary's Note: I t was the action of the Correlating Committee that the requirements in Section 210-9 f o r branch c i r c u i t s are the r e s p o n s i b i l i t y of CMP 2. SUBMITTER: Robert J. Cunningham, Duquesne Light Company RECOMMENDATION: Add new Exception No. 3 as follows: Exception No. 3. Autotransformers may supply branch c i r c u i t equipment loads, other than l i g h t i n g , at any voltage up to 600 v o l t s in commercial or industrial applications. SUBSTANTIATION: Frequently customers with 240 v o l t three-phase or 480 v o l t three-phase, three-wire ungrounded services purchase equipment rated to operate on either 240, 380, 480 or 600 v o l t systems. U t i l i t y companies cannot always supply individual services at more than one voltage. Autotransformers provide a safe and most economical means to supply this equipment usually at less that two-thirds the cost of a conventional transformer and sometimes one-tenth the cost. Typical examples of equipment that would be supplied by autotransformers are: motors, welders, x-ray machines, a i r - c o n d i t i o n i n g and r e f r i g e r a t i o n equipment, imported machines requiring unusual operating voltages, process heating, commercial cooking equipment, etc. 2- 45 - (210-9): Accept Secretary's Note: I t was the action of the Correlating Committee that the requirements in Section 210-9 f o r branch c i r c u i t s are the r e s p o n s i b i l i t y of CMP 2. SUBMITTER: CMP 2 ~ATION: Correlating Committee t r a n s f e r the t e x t and I j u r i s d i c t i o n of 210-9 Rules f o r Autotransformers to CMP 13 f o r inclusion in A r t i c l e 450. SUBSTANTIATION: CMP 13 has accepted rules governing protection of autotransformers. PANEL ACTION: Accept. VO~E'ON PANEL ACTION: Unanimously A f f i r m a t i v e . 32 Log # 1134 2- 46 - (210-19(a)): Accept SUBMITTER: H. I . Stanback, Lexington, KY RECOMMENDATION: Replace f i r s t sentence with the following two sentences: (a) General. Branch-circuit conductors shall have an ampacity not less than the maximum load to be served. In addition, conductors of m u l t i o u t l e t branch c i r c u i t s supplying r e a d i l y accessible receptacles shall have an ampacity of not less than the rating of the branch c i r c u i t . SUBSTANTIATION: A c o n f l i c t has existed in 1981 and previous Codes between Sections 210-19(a) and 240-3 Exception No. I . Section 240-3 Exception No. 1: allows the next highest ampere rating of fuse or c i r c u i t breaker when conductor ampacity does not correspond with a standard r a t i n g . Section 210-19(a) now requires conductor ampacity not less than the rating of the branch c i r c u i t (which Section 210-3 indicates is the ampere rating or setting of the fuses or c i r c u i t breaker). Taken l i t e r a l l y , Section 210-19(a) would prevent using Section 240-1 Exception No. I : f o r any branch circuit. The more r e s t r i c t i v e requirement of Section 210-1g(a) is only needed f o r m u l t i o u t l e t branch c i r c u i t s supplying readily accessible receptacles. The loading of such branch c i r c u i t s is unpredictable and, therefore, the branch c i r c u i t overcurrent protection should be selected or set no higher than the ampacity of the conductors. Correlating changes are proposed f o r Sections 210-19(a) and 240-3 Exception No. 1: to eliminate the c o n f l i c t and r e t a i n the more r e s t r i c t i v e requirement f o r m u l t i o u t l e t branch c i r c u i t s supplying r e a d i l y accessible receptacles. PANEL ACTION: Accept. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . Log # 1584 2- 49 - (210-19(b), Exception No. 1): Reject SUBMITTER: Peter Pollak, The Aluminum Association, Inc. RECOMMENDATION: Revise l a s t l l n e to read: "... conductors and shall not be smaller than No. i0 copper or No. 8 aluminum." SUBSTANTIATION: This proposal is submitted to c l a r i f y the proper' size equivalent of aluminum conductor f o r the application. The size l i m i t a t i o n is based upon an ampacity requirement which can be met with an aluminum conductor sized to provide the required ampacity per Tables 310-16 through 310-19. While Section 110-5 says "Where the conductor material is not specified, the sizes given in t h i s code shall apply to copper conductor" and "Where other materials are used, the size shall be changed accordingly," i t does not indicate to the code reader s p e c i f i c a l l y where aluminum conductors can be used or how to a r r i v e at the equivalent aluminum conductor size. PANEL ACTION: Reject. PANEL COMMENT: Panel believes subject is adequately covered in Section 110-5, A r t i c l e 310, Tables 310-16 thru 310-19 and Table Nos. 8 and 9 in Chapter 9. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . Log # 1585 2- 50 - (210-19(c)): Reject SUBMII-FER: Peter Pollak, The Aluminum Association, Inc. ~DATION: Revise l a s t line to read: "smaller than No. 14 copper or No. 12 aluminum." SUBSTANTIATION: This proposal is submitted to c l a r i f y the proper size equivalent of aluminum conductor f o r the application. The size l i m i t a t i o n is based upon an ampacity requirement which can be met with an aluminum conductor sized to provide the required ampacity per Tables 310-16 through 310-19. While Section 110-5 says "Where the conductor material is not specified, the sizes given in t h i s code shall apply to copper conductor" and "Where other materials are used, the size shall be changed accordingly," i t does not indicate to the code reader s p e c i f i c a l l y where aluminum conductors can be used or how to a r r i v e at the equivalent aluminum conductor size. PANEL ACTION: Reject. PANEL COMMENT: See Panel Comment f o r Proposal 2-49. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . Log # 1736 2- 47 - (210-19(a)): Accept in Principle SUBMITTER: Charles "Mike" Holt, Concepts in Electricity, Inc. ~ T I O N : "15-, 20-, 30-, 40'-, and 50-amp" branch circuit conductors shall have an ampacity of not less than the rating of the branch circuit and not less than the maximum load to be served... SUBSTANTIATION: Article 21043 is the reference for 15-, 20-, "30-, 40-, and 50-amp circuits. Manypeople are reading 210-19(a) and 210-20(a) and noting a conflict between the two. For example, i f you had a piece of equipment that required a conductor of 55 amps, you could install a No. 6 TW rated 55 amps and using Exception No. I of 240-3 and Note 9 of Table 320-16, a 60-amp breaker would be permitted. But 210-19(a) would almost give the impression that this is not permitted since the conductor does not have the ampacity of the overcurrent device. The above proposal would alleviate the conflict between these two sections. PANEL ACTION: Accept in Principle. PANEL COM~NT: See Panel Comment f o r Proposal 2-46. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . COMMENT ON VOTE: SCHUCK: Panel Action should read "See Panel Action f o r Proposal 2-46 ." Log # 894 2- 51 - (21~-20, Exception Nos. 1 and 2-(New)): Accept in Principle SUBMITTER: Ad Hoc Subcommittee on Control C i r c u i t Protection RECOMMENDATION: Replace the Exception to Section 210-20 with the following two Exceptions: Exception No. i : Tap conductors as permitted in Section 210-19(c) shall require only s h o r t - c i r c u i t and ground-fault protection and shall be permitted to be protected by the branch-circuit overcurrent device. Exception No. 2: Fixture wire and cords as permitted in Section 240-4. SUBSTANTIATION: The wording in the Code should better express the intent of the r u l e . I f the rule intends that the conductor need only be protected against low impedance f a u l t s , then the rule should say i t . The phrase "shall be considered as being protected by" is not s p e c i f i c , and is not s u f f i c i e n t to properly express the i n t e n t of the r u l e . PANEL ACTION: Accept in P r i n c i p l e . PANEL COMMENT: See Proposal 2-52. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . Log # 1613 2- 48 - (210-19(a), FPN): Reject SUBMITTER: Allen KnicKrehm, Los Angeles, CA RECOMMENDATION: Raise Voltage Drop note to f u l l size p r i n t ; makin~ i t a requirement. Insert "shall be" before the word "sized" in the f i r s t l i n e and delete the l a s t phrase, ending the sentence with . . . 5 per cent. SUBSTANTIATION: The problem is that A r t i c l e 310 does not provide f o r voltage drop. In the past the smaller branch c i r c u i t conductors were underrated with minimized voltage drop problems. This is no longer necessarily true, and i t is not r i g h t to not make a provision to protect the public from the problem associated with low voltage. PANEL ACTION: Reject. PANEL COMMENT: I t is a design consideration. Proposal does not consider other elements of the system and other variables such as temporary voltage f l u c t u a t i o n s and variations in impedance. MOTE ON PANEL ACTION: AFFIRMATIVE: 8 NEGATIVE: Bowling, Craig. EXPLANATION OF VOTE: BOWLING: This proposal provides the inspector additional enforceable data on which to judge an i n s t a l l a t i o n . This would be especially relevant on i n s t a l l a t i o n s which have not employed formal engineering techinques. CPJ~IG: I agree with the substantiation. The public needs protection from the problems associated with low voltage. 2- 52 - (210-20): Accept SUBMITTER: CMP 2 RECOMMENDATION: Delete "Ca) General" Replace the Exception with the following: "Exception No. I : ,Tap conductors as permitted in Section 210-19(c) shall be permitted to be protected by the branch-circuit overcurrent device. Exception No. 2: Fixture wire and cords as permitted in Section 240-4." SUBSTANTIATION: There is no (b) in the 1981 Code. The changes in the Exception are required to support the Report of the NEC Correlating Committee Ad Hoc Subcommittee on Control C i r c u i t Protection, Ampacities and Use of No. 16 and No. 18 Conductors. PANEL ACTION: Accept. VU[E ON PANEL ACTION: Unanimously A f f i r m a t i v e . 33 Log # 217 2- 56 - (210-22(c), Exception No. 2): Accept Secretary's Note: I t was the action of the Correlating Committee that further consideration be given to the comments expressed in the negative voting. SUBMITTER: John C. Miller, Abolite Lighting, Inc. ~ATION: Delete Exception No. 2. SUBSTANTIATION: With the increased ampacities of some of the conductors in Tables 310-16 through 310-19 the derating requirements of Note No. 8 to the tables would permit the load to be the same as the branch circuit rating, ie, No. 14 TW = 20 A, 6 conductors in a raceway requires 80 percent derating, 20 X .80 = 16 AMP. Table 310-16 Footnote limits the load to 15 amp, which is the same as the branch circuit rating. This deletion would also bring the requirement in line with Section 384-16(c) which does not have this Exception. PANEL ACTION: Accept. VOTE ON PANEL ACTION: AFFIRMATIVE: 8 NEGATIVE: Lordi, Reign. EXPLANATION OF VOTE: LORDI: Reject action is consistent with reject action on Proposal 2-124. REIGN: Exception No. 2 should not be deleted because this exception points out that the Code does not require double derating for both a continuous load and a raceway f i l l of more than three conductors. The increased ampacity of some of the conductors in Tables 310-16 to 19 of the 1981 Code recognizes that the higher temperature insulations can withstand the I~R heat produced with higher load currents. As the submitter points out, these higher ampacitites do permit the derated load current to be the same as the branch-circuit rating. However, the Code permits branch circuits with protective devices listed for 100 percent load and multioutlet branch circuits supplying receptacles to have the load the same as the branch-circuit rating. Log # 201 2- 53 - (210-21(b)(i), Exception-(New)): Reject SUBMITTER: Dan Leaf, Westlake Village, CA RECOMMENDATION: Add Exception as follows: Exception: A receptacle installed for a specific motor-operated equipment, permitted to be cord- and plug-connected, other than room air conditioners specified in Part G of Article 440. SUBSTANTIATION: Various sections of the Code permit receptacles for the connection of motors, e.g., 430-81(c), 430-109 Exception 5, and 680-7. Since not specifically indicated as amending Section 210-21(b)(1), i t is not clear whether these sections may be applied with application of overcurrent device values specified or permitted by Article 430 or 630. A specific motor-operated equipment rated 3/4 HP 115 V l-phase, cord- and plug-connected to a properly rated 15-ampere receptacle/interlocked switch device on an individual circuit may have overcurrent protection (nontime-delay fuse) rated at 45 amperes per Section 430-52, but Section 210-21(b)(1) limits overcurrent protection for this receptacle rating to 15 amperes. I f i t is the intent that other articles may modify this section i t seems desirable to clearly indicate this. PANEL ACTION: Reject. PANEL COMMENT: Covered in Articles 430 and 440. Beyondthe Scope of Article 210. VOTE ON PANELACTION: UnanimouslyAffirmative. Log # 1509 2- 54 - (210-21(b)(3), Exception-(New)): Accept in Principle SUBMITTER: Melvin K. Sanders, Ankeny, IA ITE'~TOI~'IqI~ATION: Add Exception: Exception: In industrial establishments where the conditions of maintenance and supervision assure that only qualified persons will service the installation. SUBSTANTIATION: I t is common in industrial establishments to provide several single receptacles of 30, 60, or higher amperage rating on a single branch circuit to allow quick relocation of equipment for production and/or maintenance use, such as electric welders. Generally, only one piece of equipment is operated at a time, and restricting this to industrial establishments with qualified personnel to service these receptacles will help insure proper usage. The type of receptacles used are of the non-NEMA type configuration, known as a pin-and-sleeve receptacle. These may or may not be horsepower rated and their uses are not now covered in any sections of the NEC Article 210. PANEL ACTION: Accept in Principle. PANEL COMMENT: See Proposal 2-4. VOTE ON PANELACTION: Unanimously Affirmative. 2- 57 - (210-23): Accept Secretary's Note: I t was the action of the Correlating Committee that further consideration be given to the comments expressed in the negative voting. SUBMITTER: CMP 2 RECOMMENDATION: Revise as stated: 210-23, No change. 210-23(a), Change "appliances" to "other utilization equipment" in the second, fourth, f i f t h , and seventh lines. 210-23(b), Change "appliances" to "utilization equipment" in the third and fourth line. 210-23(c), Revise to read: "(c) 40- and 50-Ampere Branch Circuits. A 40- or 50-ampere branch circuit shall be permitted to supply cooking appliances that are fastened in place in any occupancy. In other than dwelling units, such circuits shall be permitted to supply fixed lighting units with heavy duty l ampholders, infrared heating units or other utilization equipment." SUBSTANTIATION: To allow the use of "utilization equipment" on multioutlet branch circuits. PANEL ACTION: Accept. VOTE ON PANELACTION: AFFIRMATIVE: 8 NEGATIVE: Reign, Schuck. EXPLANATION OF VOTE: REIGN: The proposed wording in Section 210-23(a) is incorrect. The word "appliance(s)" in the 4th, 5th and 7th lines should be changed to " u t i l i z a t i o n equipment" NOT "other utilization equipment." SCHUCK: Section 210-23(a) should read "other utilization equipment" in 2nd line and " u t i l i z a t i o n equipment" in the 4th, 5th, and 7th lines. Log # 1927 2- 56 - (210-22(c)): Reject SUBMITTER: Joseph C. Roohan, Whittier, CA I~E'~)I;I~P~N]~ATION: Delete all reference to "Continuous Load." . SUBSTANTIATION: The inclusion of "Continuous Load" and the accompanying derating rules in the NATIONAL ELECTRICAL CODEsome time ago was a well intended, but unnecessary refinement in the practical application of the Code. The consideration of "Continuous Load" clearly belongs in electrical handbooks and other designers' guides but not in a safety code. "In Section 90-1(c) i t is stated that "This is not intended as a design specification..." I t is ludicrous to consider an installation safe where i t carries current for slightly less than three hours and unsafe where this time is exceeded. I t is just as ridiculous to consider an installation safe where i t is carrying continuous current and is momentarily interrupted every three hours. The ampacity ratings for conductors in Article 310 are continuous ratings and the derating factors for continuous loads are design considerations to reduce nuisance tripping current breakers that are not temperature compensated where enclosed in panelboards. Nuisance tripping is not generally considered a safety hazard. By deleting the reference to "Continuous Load" in theNATIONAL ELECTRICAL CODEan important step toward practicality will be achieved allowing inspectors, plan reviewers and others, whose duties consist of evaluating an installation to concern themselves with the safety provided by conductor size, material, insulation, and overcurrent protection. The time element of. an installation is an impractical, unenforceable and unrelated element of safety within the referenced sections. PANEL ACTION: Reject. PANEL COMMENT: The proposal would eliminate the use of the term "Continuous Load," but i t would not eliminate the need to recognize the interreIated heating effects such a change would cause in the various system components. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 1224 2- 58 - (210-23(a)): Reject SUBMITTER: Richard Lloyd, Huntinton, NY RECOM~NDATION: After the words "The total rating of" in the third sentence of this paragraph, insert the words "fixtures used for continuous lighting and." SUBSTANTIATION: This revision would prevent using receptacle outlets on branch circuits used for continuous lighting in stores and offices where the lighting load is already at or near 80 percent. Using additional receptacle load on these circuits could cause overheating of the supply panelboard and would defeat the intent of the present 80 percent limit on continuous load. The proposed revision would limit the continuous lighting load to 50 ercent where receptacles were also used. ANEL ACTION: Reject. PANEL COMMENT: The system is inherently protected. VOTE ON PANEL ACTION: UnanimouslyAffirmative. ~ 34 SUBSTANTIATION: This w i l l bring the National Electrical Code and the Uniform Mechanical Code in line with each other. Sections 708 and 709 in the Uniform Mechanical Code state that "a permanent electric outlet and lighting f i x t u r e , controlled by a switch located at the passageway opening, shall be provided at or near the furnace." 50 AMP The outlets are installed by the electrician on the job and should be in the National Electrical Code. PANEL ACTION: Reject. 6 PANEL COMMENT: The Panel presumes the submitter referenced 4 Section 210-70(a). Panel considers proposal a design consideration. 12. 10 VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 1586 2- 59 - (Table 210-24): Reject SL~3MII-TER: Peter Pollak, The Aluminum Association, Inc. ~ATION: Table 210-24 expanded to read: CIRCUIT RATING CONDUCTORS: (Min Size) 15 AMP 20 AMP 30 AMP 40 AMP Copper C i r c u i t Wires* Aluminum C i r c u i t Wires* Copper Taps Aluminum Taps 14 12 14 12 12 10 14 12 10 8 14 12 8 6 12 I0 Footnote: *These ampacities are for conductors where derating is not required. The ampacities of copper-clad aluminum are identical to those for aluminum. See Tables 310-16 through 310-19. Log # 82 2- 63 - (210-52(a)): Reject SUBMITTER: Stephen M. Peckham, Peckham & Sons E l e c t r i c a l , Inc. RECOF~MENDATION: F i r s t paragraph, f i f t h and s i x t h lines change to read: . . . i n c l u d i n g any "usable" wall space 2 f e e t (~i0 mm) or more in w i d t h . . . SUBSTANTIATION: Many'times, receptacles are required in wall spaces, 2 feet wide, that are t o t a l l y unusable, because the space is behind open doors or in walkways. PANEL ACTION: Reject. PANEL COMMENT: "Usable" is undefined. See Panel Action on Proposal 2-65. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . SUBSTANTIATION: This proposal is submitted to c l a r i f y the proper size equivalent of aluminum conductor for the application. The size limitation is based upon an ampacity requirement which can be met with an aluminum conductor sized to provide the required ampacity per Tables 310-16 through 310-19. While Section 110-5 says "Where the conductor material is not specified, the sizes given in this code shall apply to copper conductor" and "Where other materials are used, the size shall be changed accordingly," i t does not indicate to the code reader specifically where aluminum conductors can be used or how to arrive at the equivalent aluminum conductor size. PANEL ACTION: Reject. PANEL COM~NT: See Panel Comment for Proposal 2-49. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 359 2- 64 - (210-52(a)): Reject SUBMITTER: Dennis Westervelt, Sheldon, IA RECOMMENDATION: Receptacle outlets in floors shall not be counted as part of the required number .of receptacle outlets unless located within 12 inches from the wall. SUBSTANTIATION: To set an exact distance between the wall and the receptacle, so there is not a l o t of confusion in determining as what is close or not. PANEL ACTION: Reject. PANEL COMMENT: Subject is adequately covered. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 218 2- 60 - (Table 210-24-Single Asterisk Note): Reject SUBMITTER: John C. Miller, Abolite Lighting, Inc. ~ATION: Rewritethis Note to read: These ampacities are for copper conductors where the Correction Factors of Tables 310-16 through 310-19 are not required. SUBSTANTIATION: 1) Derating is not defined. 2) For the past several Codes there has been confusion as to what constitutes derating. 3) With the rewording of this Footnote the requirement would be specific and the confusion eliminated. PANEL ACTION: Reject. PANEL COMMENT: Panel does not believe that there would be any meaningful improvement in the Code by this proposal. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 1281, 1912 2- 61 - (210-24): Accept in Principle SUBMI~ERS: IAEI (1281) H. B. Love/M. Shapiro, Michigan Chapter IAEI (1912) RECOMMENDATION: ReviseSection 210-24 to read: Branch-Circuit Requirements - Summary. The requirements for circuits having two or more outlets, other than the receptacle circuits of Section 220-3(b) as specifically provided for above, are summarized in Table 210-24. Branch circuits in dwelling-type occupancies shall not be connected to serve more than one dwelling unit. SUBSTANTIATION: ASHRAE-90-75R which has been widely adopted requires that, "In any multi-tenant residential building, provisions shall be made to separately determine the energy consumed by each tenant." This amendment is needed to compliment that requirement. I t also would prevent two tenants from overloading a circuit by having a situation where each tenant would be attempting to plug in appliances that were rated at 80 percent of the branch c i r c u i t . PANEL ACTION: Accept in Principle. Change "dwelling-type occupancies" to "dwelling units." PANEL COMMENT: Clarification. VOTE ON'PANEL ACTION: UnanimouslyAffirmative. Log # 428 2- 65 - (210-52(a)): Accept Secretary's Note: I t was the action of the Correl'ating Committee to direct the Panel to c l a r i f y the location of the added wording. SUBMITTER: Southwestern Section IAEI RECO~ENDATION: Add "any wall space made inaccessible by the opening of a door, other than a closet or cabinet door, shall not be included in the measurement for determination of outlet locations." SUBSTANTIATION: The inclusion of this inaccessible space serves no useful purpose in the completed home. Usually such a door is open 99 percent of the time and an outlet located behind i t is not available. The requirement only adds expense without returning benefit. Sometimes, a bedroom entry door opens against the end of wardrobe closets which qualify f o r "not being counted." This results presently with an outlet being placed on the 2 1/2- to 3-feet space in back of the entry door to meet the requirement of Section 210-52(a). PANEL ACTION: Accept. VOTE ON PANEL ACTION: UnanimouslyAffirmative. COMMENT ON VOTE: YERKE: T h i s proposal has been argued back and forth and the concern is whether anything new has been brought up that would" effect former Code decisions. Please note Section 550-6(d), Exception No. 3 which chose to specifically treat this situation and addresses the problem of doors installed side by side which could result in an extensive wall space without a receptacle. Log # 1227 2- 62 - (210-26(a)): Reject SUBMITTER: Robert M. Milatovich, Clovis, CA ~ATION: Change second paragraph to read: At least one permanent electric outlet and lighting outlet, controlled by a switch located at the passageway opening, shall be provided at or near the equipment installed in an attic, underfloor space, u t i l i t y room and basement only where these spaces are used for storage or containing equipment requiring servicing. Log # 500 2- 66 - (210-52(a)):. Accept Secretary's Note: I t was the action of the Correlating Committee to direct the Panel to c l a r i f y the location of the added wording. SUBMITTER: Ernest E. Cannon, Tempe, AZ RECOMMENDATION: Add "any wall space made inaccessible by the opening o9 a door, other than a closet or cabinet door, shall not be included in the measurement for determination of outlet locations." o 35 ROBERTS: This proposal is unnecessarily r e s t r i c t i v e in that i t does not consider receptacle outlets f o r special purposes such as wall-mounted clocks, through-wall a i r conditioners, etc., which can be installed over baseboard heaters as long as the location of receptacle outlets or length o f cord is such that the cord cannot be draped over the baseboard heater. Also, this proposal does not consider either the i n s t a l l a t i o n or subsequent removal of baseboard heaters by the occupant years after the original construction which could result in hazards. Section 210-52(a) would not be met and the occupant would be l e f t without receptacles or the occupant would i n s t a l l the baseboard heater under a receptacle. The problem is the use of the receptacle, which has not been addressed, and not the location of the receptacle. SUBSTANTIATION: The inclusion of this inaccessible space serves no useful purpose in the completed home. Usually such a door is open 99 percent of the time and an outlet located behind i t is not available. The requirement only adds expense without returning benefit. Sometimes, a bedroom entry door opens against the end of wardrobe closets which qualify f o r "not being counted." This results presently with an outlet being placed on the 2 1/2 to 3 feet space in back of the entry door to meet the requirement of Section 210-52(a). PANEL ACTION: Accept. PANEL COMMENT: See Panel Action on Proposal 2-65. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 1691 2- 67 - (210-52(a)): Reject SUBMI~ER: Charles "Mike" Holt, Concepts in E l e c t r i c i t y Inc. RECOMMENDATION: Revise 210-52(a) to read: "... from an outlet in that space, including any wall space 2 feet (610 mm) or more in width and the wall space occupied by "non-transparent" sliding panels in exterior walls." SUBSTANTIATION: This proposed addition of the words "non-transparent" would c l a r i f y that receptacles are not required in front of sliding glass doors, since this would cause a potential hazard by having cords in front of walkways. PANEL ACTION: Reject. PANEL COMMENT: See Panel Action on Proposal 2-65. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 145 2- 70 - (210-52(a) Exception): Reject Secretary's Note: I t was the action of the Correlating Committee that this proposal be reported as "Reject" because less than two-thirds of the members e l i g i b l e to vote have voted in the affirmative. SUBMITTER: Bob K. Middleton, City of Pocatello, ID RECOMMENDATION: Add: No receptacle shall be installed where a supply cord w i l l hang over a baseboard heater. SUBSTANTIATION: I feel this w i l l bring Section 110-3(b) in line the rough-in of a house. The listed instructions on most baseboard heaters prohibit cords over base~ards. PANEL ACTION: Accept in Principle. PANEL COMMENT: See Panel Action on Proposal 2-69. VOTE ON PANEL ACTION: • AFFIRMATIVE: 6 NEGATIVE: Bowling, Craig, Cunningham, Roberts. EXPLANATION OF VOTE: BOWLING: I concur in the comments which were made on this proposal by Mr. Robert J. Cunningham. CRAIG: See comment on Proposal 2-69. CUNNINGHAM: This proposal covers steam, hot water, fuel fired and e l e c t r i c baseboard heaters and is more consistent than Proposal 2-69. However, the same negative co~nents on Proposal 2-69 apply here. This proposal also leaves the burden on the inspector to determine "whether a supply cord from a receptacle could hang over a baseboard heater." How long a cord do you consider? ROBERTS: See comment on Proposal 2-69. Log # 1911 2- 68 - (210-52(a)): Reject SUBMITTERS: H. B. Love/M. Shapiro, Michigan Chapter IAEI ~ T I O N : In the last paragraph of Section 210-52(a) but before the exception remove the following words: "5 i / 2 feet above the f l o o r . " and insert the following: "Twenty-four (24) inches above the f l o o r or more than twenty-four (24) inches above a fixed work surface they are intended to serve and pendant receptacle outlets are not to be counted as any of the receptacle outlets required by Section 210-52(a) and (c) except as provided f o r in bathrooms." SUBSTANTIATION: We have found many cases where the required receptacles, recreation rooms p a r t i c u l a r l y , were installed on or near the ceiling and were almost useless. The Code requirement f o r a maximum distance of 12 feet between receptacles is predicated on the assumption that a standard 6 foot cord can then reach an outlet. I f the receptacle is 5 feet high we then have a triangle, the hypotenuses of which is over 6 feet long. This would also take care of the barrier-free design concepts and other changes in building codes that are being promulgated. PANEL ACTION: Reject. PANEL COMMENT: Would not contribute to safety and would be too complicated to enforce. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 349 2- 71 - (210-52(a), Paragraph I ) : Reject SUBMITTER: Steve Wipf, Sheldon, IA RECOMMENDATION: Delete- "and the wall space occupied by sliding pa-a-neTs'i'n-exterior walls." SUBSTANTIATION: The purpose of this section is to minimize the use of cords across doorways and similar openings. To f u r t h e r minimize this hazard, I propose t h a t " s l i d i n g panels in exterior walls" be treated as a doorway or similar opening. PANEL ACTION: Reject. F~NE'~'-C~-O-M-N~E'-NT: See Panel Action on Proposal 2-65. VOTE ON PANEL ACTION: Unanimously A f f l n ~ a t i v e . Log # 1786 2- 69 - (210-52(a)): Reject Secretary's Note: I t was the action of the Correlating Committee that this proposal be reported as "Reject" because less than two-thirds of the members e l i g i b l e to vote have voted in the affirmative. SUBMITTER: Leo F. Martin, Paul Revere Chapter IAEI R-R~-C~T~F~NFDATION: Add a paragraph before the exception as follows: Receptacles required by this section shall not be located above permanent e l e c t r i c baseboard heaters. SUBSTANTIATION: The exception presently applies to requirements that are found in l i s t i n g and/or manufacturers instructions and authorities must reference Section 110-3(b) and the l i s t i n g or labeling instructions. PANEL ACTION: Accept. VOTE ON PANLL ACTION: AFFIRMATIVE: 6 NEGATIVE: Bowling, Craig, Cunningham, Roberts. COMMENT ON VOTE: YLRKt: i t is suggested that the proposal be modified to indicate that receptacle outlets f o r special purposes such as wall-mounted clocks can be installed over baseboard heaters as long as the location of the receptacle outlet or length of cord is such that the cord cannot be draped over the baseboard heater. EXPLANATION OF VOTE: ~UWLING: I concur Mr. Robert J. Cunningham comments and feel that we must rely on instructions required by the l i s t i n g laboratories as we do on almost all electrical products. CRAIG: UL forbids the i n s t a l l a t i o n of baseboard heaters under outlets. The substantiation does not show a need f o r additional requirements. CUNNINGHAM: The UL l i s t i n g No. ULlO42, paragraph 48.1 requires caution notices on each baseboard unit and the i n s t a l l a t i o n requirements forbid i n s t a l l a t i o n under outlets. The substantiation does not prove that this change is required. I f this rule is necessary, baseboard heaters with other heat sources such as hot water, steam, and direct fuel f i r e d should be included. Log # 363 2- 72 - (210-52(a) and (b)): Reject SUBMITTER: Barton Peters, Sheldon, IA RECOMMENDATION: (a) In every family room, dining room, living room, parlor, l i b r a r y , den, sunroom, bedroom, recreation room, kitchen, or similar rooms of dwelling units, "except counter tops in kitchen," receptacle outlets shall be installed . . . . . . (b) Counter tops: a receptacle outlet should be "installed three feet" from "edges," and every "six feet" after that, so no point on counter is "three feet" from a receptacle outlet. SUBSTANTIATION: I think the minimum Code requirements on counter outlet spaclng was not enough. According to Section 210-52(a) an outlet was only required f o r the six feet of counter top from an edge, and every 12 feet after that, so no point along counter top space was 6 feet from a receptacle outlet. I agree that the counter space wider than 12 inches needs a receptacle. 210-B2(b). PANEL ACTION: Reject. PANEL COMMENT: Present wording r e f l e c t s Panel's i n t e n t . VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . Log # 1787 2- 73 - (210-52(b)): Reject SUBMITTER: Leo F. Martin, Paul Revere Chapter IAEI RECOM--~-M~N-DATION: In the f i r s t sentence, delete "12" and replace "6". Also change metric equivalent accordingly. SUBSTANTIATION: As presently written, a counter than measures 12 ~ - f e s s does not require a receptacle and consequently cords of many appliances are draped across sinks and ranges to usable counter top spaces "not wider than" 12 inches. 3B Les Rinder, Chicago, IL Leo Nagel, North Dakota John W. Erickson, Boltswitch, Inc. Homer M. Lefler, Chicago, IL RECOFI~ENDATION: Amend Section 210-52(d) so as to read as follows: "(d) Outdoor Outlets. For each dwelling unit with grade access there shall be at least one receptacle outlet installed outdoors, supplied fromthe electrical system of the dwelling unit that i t serves. See Section 210-8(a)(3)." SUBSTANTIATION: As the section presently reads the requirement applies only to one- and two-family dwellings and there only has to be one receptacle. You don't have to be a mental giant to know all the d i f f i c u l t y that this wording has caused. Such inane discussions such as, "Who has p r i o r i t y of use?", "Who pays the b i l l ? " , "Where shall i t be located?", etc., etc." Just saying there will be two receptacles will clear up these inane questions, but i t certainly will not answer the major question! I f there is a documented need for receptacles outdoors on one- and two-family dwellings, then the same documentation must hold true for not only the duplex, but also the t r i p l e x , the quadriplex, etc. As long as the people can come out of their dwelling and use the ground around, in front of, or in back of that dwelling the need for that receptacle is identical to the need for one- and two-family dwellings. PANEL ACTION: Reject. PANEL COMMENT: See Panel Action on Proposals 2-79 and 2-61. VOTE ON PANEL ACTION: Unanimously Affirmative. PANEL ACTION: Reject. PANEL COMMENT: Appliance counters would normally be at least 12 inches. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 387 2- 74 ° (210~52(c)): Reject SUBMITTER: Merlyn Winter, George, IA ITE~C~QB~T~ATION: In dwelling units at least one wall receptacle outlet shall be installed in the bathroom wi.thin 3 feet measured horizontally along the wall from the center of the basin location. SUBSTANTIATION: Most personal appliances such as electric shavers only have 3-4 foot cords. I f they are used above the basin the receptacles have to be within at least 3 feet of the basin, otherwise the cord will be stretched too far causing damage to the cord and appliance. PANEL ACTION: Reject, PANEL COMMENT: Already covered. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 364 2- 75 - (210-52(c), Exception-(New)): Reject SUBMITTER: Mark Markey, Sheldon, IA ITE'L'-OI~IT~ATION: Exception: I f medicine cabinet is installed adjacent to basin that has an UL listed receptacle then wall receptacle does not have to be installed. SUBSTANTIATION: Because of the space taken up by some medicine cabinets in some bathrooms above the basin. PANEL ACTION: Reject. PANEL COMMENT: Does not contribute to safety. VOTE ON PANLL ACTION: Unanimously Affirmative. Log # 1239 2- 79 - (210-52(d)): Accept in Principle Secretary's Note: I t was the action of the Correlating Committee that further consideration be given to the comments expressed in the voting. SUBMITTER: IAEI ITE~C'I~I~'I~I~ATION: Changeparagraph (d) to read: "(d} Outdoor Outlets. For one-family dwelling at least one receptacle outlet shall be installed outdoors. For two-family dwelling at least one receptacle for each unit at grade level shall be installed outdoors." SUBSTANTIATION: With the present wording only one outdoor receptacle is required for two dwelling units. As this is for safety of use of hand held appliances, this is not being accomplished with only one receptacle, as most of two family dwellings have separate power supply; i f the one having the outdoor receptacle is vacant with power o f f , then the other unit has no outdoor receptable available. Also, with separate power supply, the owner or tenant of unit having control of the receptacle circuit refuses to let other unit have use of the receptacle. PANEL ACTION: Accept in Principle. Revise as follows: Insert "a" between "For" and "one-family" in the f i r s t sentence. Insert "a" between "For" and "two-family" in the second sentence. Insert "outlet" between "receptacle" and "for" in the second sentence. Insert "shall be installed outdoors" after "outlet" and before "for" in the second sentence. Insert "located" between "unit" and "at" in the second sentence. Add "See Section 210-8(a)(3)" at the end of the paragraph. PANEL COMMENT: More accurately reflects Panel intent. VUlt UN PANLL ACTION: UnanimouslyAffirmative. COMMENTON VOTE: CUNNINGHAM: I am concerned that this wording may be misinterpreted to require a GFCI outlet for the second unit of a twn-family dwelling where the second unit has no direct connection to grade level. Example, a second floor duplex unit where the stairway is at grade level. REIGN: I believe the Panel Action should have the whole paragraph, complete with changes, written out. All the "insert betweens" are very confusing and hard to follow. SCHUCK: Panel intent was to delete "shall be installed outdoors" at the end of 2nd'sentence as this phrase was inserted elsewhere in the sentence. Log # 228 2- 76 - (210-52(d)): Accept in Principle SUBMII-FER: H. K. Glenn, Pacific Coast Electrical Association, Inc. RECOMMENDATION: Revise Section 210-52(d) to read: For one-family dwellings, at least one receptacle outlet shall be installed outdoors. For two-family dwellings, at least one receptacle outlet shall be installed outdoors for each dwelling unit. See Section 210-8(a)(3). SUBSTANTIATION: The text in the 1981 Code has drawn considerable criticism in "implying" that tenants occupying both units of a two-family dwelling would be required to share the use of the "one" required outdoor receptacle outlet. Comment Text by NFPA in the NATIONAL ELECTRICAL CODEHANDBOOK supports the need for one receptacle for each dwelling unit. On many occasions an electrical inspector, making what he considers a reasonable judgement, that being requiring one for each unit, has no supporting text with which to operate. PANEL ACTION: Accept in Principle. PANEL COMMENT: See Panel Action on Proposal 2-79. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 427 2- 77 - (210-52(d)): Accept in Principle SUBMITTER: Southwestern Section IAEI ITE~LR~E~NI~ATION: Changeparagraph (d) to read: "(d) Outdoor Outlets. For one-family dwelling at least one receptacle outlet shall be installed outdoors. For two-family dwelling at least one, receptacle for each unit at grade level shall be installed outdoors." SUBSTANTIATION: With the present wording only one outdoor receptacle is required for two dwelling units. As this is for safety of use of hand-held appliances, this is not being accomplished with only one receptacle, as most of two-family dwellings have separate power supply; i f the one having the outdoor receptacle is vacant with power off,.then the other unit has no outdoor receptacle available. Also, with separate power supply, the owner or tenant of unit having control of the receptacle circuit refuses to let other unit have use of the receptacle. PANEL ACTION: Accept in Principle. PANEL COMMENT: See Panel Action on Proposal 2-79. VOTE ON PANEL ACTION: Unanimously Affirmative. 2- 78 - (210-52(d)): Reject SUBMITTER: Leo Witz, Continental Electric C o . Bill Hogan, Chicago, IL Fred Smith, Elgin, IL Jim Meehan, New Haven, CT Anton Ganje, North Dakota Kenny Gebert, Minneapolis, MN Bill Conrardy, The Conrardy Co. Robert P. Brooks, Chicago, IL Paul Moore, Paducah, KY Log # 1773 2- 80 - (210-52(d)): Reject SUBMITTER: Tom Tombarello, Paul Revere Chapter IAEI ~DATION: Revise f i r s t section as follows: For a dwelling unit(s), at least one receptacle outlet shall be installed outdoors at direct grade level access for each unit that is at grade level. (Second sentence remains the same.) SUBSTANTIATION: The revision clarifies that a receptacle outlet at direct grade level access is required for each dwelling unit that is at grade level. That is, one receptacle outlet for a one-family dwelling, two receptacle outlets for a two-family dwelling, three receptacle outlets for a three-family dwelling, etc. However, where a dwelling unit is not at direct grade level, a receptacle outlet is not required for that unit. PANEL ACTION: Reject. PANEL COMMENT: See Panel Action on Proposal 2479. VOTE ON PANELACTION: Unanimously Affirmative. Log # 1453 37 Log # 118 2- 85 - (210-52(f)): Reject SUBMITTER: Robert S. Dennison, County of Riverside, CA ~DATION: Delete the word "attached" preceding the word garage. New "Basements and garages. For a one-family dwelling at least one receptacle outlet in addition to any provided for laundry equipment shall be installed in each basement and in each garage." SUBSTANTIATION: In every garage there is a need for at least one receptacle outlet for an automobile battery charger, or power tools. When i t is not installed we see cords, exposed Romex and other unsafe wiring being run to a detached garage without permit or inspection. This change would recognize that the same needs exist in a detached garage as an attached garage for which the Code now provides. PANEL ACTION: Reject. PANEL CO{~MENT: See Panel Comment for Proposal 2-84. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 1788 2- 81 - (210-52(d)): Accept in Principle SUBMITTER: Leo F. Martin, Hyde Park, MA RECOMMENDATION: Revise as follows: (d) Outdoor Receptacle Outlets. For one- and two-family dwelling at least one receptacle outlet at direct grade level access shall be installed outdoors for each dwelling unit. See Section 210-8 (a)(3). SUBSTANTIATION: To c l a r i f y the intended requirements as I don't believe i t was intended for two families to share one receptacle at one family's expense. PANEL ACTION: Accept ih Principle. PANEL COMMENT: See Panel Action on Proposal 2-79. VOTE ON PANELACTION: Unanimously Affirmative. Log # 865 2- 82 - (210-52(d)(i) and (2)): Reject SUBMITTER: H. Brooke Stauffer, NEMA RECOF~MENDATION: Revise as follows: Outdoor outlets. (1) For each dwelling unit with direct grade • level access, at least one receptacle outlet shall be installed outdoors. See Section 210-8(a)(3). (2) For each dwelling unit having outdoor living space above grade without direct grade level access, e.g. a balcony, porch or deck, at least one receptacle outlet shall be installed outdoors within the outdoor living space. This receptacle outlet shall be in addition to any required by Section 210-52(d)(1). SUBSTANTIATION: There is confusion in the present text as to whether or not each unit of a two-family dwelling, such as a duplex, with direct grade level access to each unit, requires at least one receptacle outlet outdoors. I f only one outlet is provided, there is a safety problem with the other unit. There is a need to provide adequate electric service with equipment grounding for electrical appliances frequently used on balconies, porches, and decks above grade. Requiring a receptacle outlet at these locations will minimize the unsafe use of extension cords, adapters, and other temporary wiring methods. PANEL ACTION: Reject. PANEL COMMENT: See Panel Action on Proposal 2-79. Panel feels that a receptacle on a balcony is a design consideration. VOTE ON PANEL ACTION: AFFIRMATIVE: 9 NEGATIVE: Roberts. EXPLANATION OF VOTE: ROBERTS: Every location in the Code where receptacle outlets are required was presumably decided on by considering the merits of "safety considerations" dominant over "design considerations." The trend in housing is towards multiple dwelling units, often with each unit having direct grade level access and an individual garden area. I t is d i f f i c u l t to understand why a two-family dwelling requires an outdoor receptacle outlet for each unit with direct grade level access when a similar dwelling with three garden apartments requires none. The lack of requirements for receptacle outlets onbalconies, porches or decks above grade leads to unsafe use of extension cords, adapters and other temporary wiring methods. We believe that "safety considerations" j u s t i f y accepting the proposal. Log # 1772 2- 86 - (210-52(g)-(New)): Reject SUBMITTER: Tom Tombarello, Paul Revere Chapter IAEI ~DATION: Add a new (g) as follows: (g) Refrigerator Outlets. In dwelling units, at least one 20-ampere branch circuit shall be provided to supply refrigerator outlet(s). This circuit shall have no other outlets. SUBSTANTIATION: This new addition would relieve some of the load that is presently permitted on the "two or more" circuits provided for small appliances. Also, i f accepted, changes in calculations would be necessary in Examples of Chapter g. PANEL ACTION: Reject. PANEL COMMENT: Adequately covered. No substantiation as to need. VOTE ON PANELACTION: UnanimouslyAffirmative. Log # 1910 2- 87 - (210-52(g)-(New)): Reject SUBMITTERS: H. B. Love/M. Shapiro, Michigan Chapter, IAEI ~ T I O N : Add new (g) to read: Halls and Corridors. Halls, corridors, etc., multi-family dwellings shall have at least one receptacle outlet for each twenty-five (25) linear feet for major fraction of hall length. SUBSTANTIATION: This proposal is necessary for maintenance equipment to scrub or vacuum halls and/or corridors. Where receptacles are not provided, unsafe methods are used to provide power to operate such machines. Hall receptacles are necessary due to the separate metering requirements of ASHRAE90-75R. Lack of such receptacles also leads to flexible cords being run through doorways and similar openings. PANEL ACTION: RejeCt. PANEL COMMENT: Panel believes this is a design consideration. VOTE ON PANELACTION: AFFIRMATIVE: 9 NEGATIVE: Bowling. EXPLANATION OF VOTE: BOWLING: I concur with the proposal but do not concur with the Panel Comments regarding design consideration. Proposal 2-61 prohibits a receptacle from being installed from a dwelling unit in the hallway of multifamily dwellings. Buildings management provides illumination of hallways and should provide hallway and corridor receptacle for maintenance purposes. 2- 83 - (210-52(f)): Accept SUBMITTER: CMP 2 ~ATION: Revise last sentence to read: "See Sections 210-8(a)(4) and 210-8(a)(2)." SUBSTANTIATION: To reference the addition of Section 210-8(a)(4). PANEL ACTION: Accept. VOTE ON PANELACTION: Unanimously Affirmative. Log # 1282, 1909 2- 88 - (210-52(h)-(New)): Reject SUBMITTERS: IAEI (1282) ~ v e / M . Shapiro, Michigan Chapter IAEI (1909) RECO~,MENDATION: Add: Unfinished attic space in dwelling-type occupancies adaptable for living which is accessible by permanent stairs shall be provided with at least one (1) receptacle outlet which shall be wired on an independent circuit of at least 15 ampere capacity. SUBSTANTIATION: To provide for future wiring of this space when i t is turned into living quarters are overloaded when extension cord wiring and other unapproved methods are used by untrained persons when finishing o f f these areas into living space. With increasing sophistication among consumers on the use of fans for cooling and with rising energy costs creating reluctance to use air conditioners; more and more attic fans are coming into use. Unapproved and hazardous wiring methods involving extension cords run into attics or improperly connected in attics are the norm not the exception. This rule makes provision for this need as well as providing for safe use of the area when i t is made into living area (again the norm). PANEL ACTION: Reject. PANEL COMMENT: Panel feels this is a design consideration. VOTE ON PANELACTION: AFFIRMATIVE: 9 NEGATIVE: Bowling. EXPLANATION OF VOTE: BOWLING: This proposal recognizes the homeowner who is postponing or delaying the completion of a dwelling. A 15-ampere circuit would provide a minimum source of power for areas to be completed in the future or as needs dictate. Log # 370 2- 84 - (210-52(f)): Reject SUBMII'[ER: Terry Teunissen, Alvord, IA ~TEqL~O-~U~N ' -~ATION: For a one-family dwelling, at least one receptacle outlet, in addition to any provided for laundry equipment, shall be installed in each basement and in each single attached garage. In attached garages, larger than single garages, an additional receptacle outlet shall be installed for each car. SUBSTANTIATION: In two and three car attached garages, one receptacle outlet i s n ' t sufficient. Each car should have an outlet in which the water heater of the car, or other equipment can be plugged into. This would minimize the use of cords across doorways, cars, and similar places. PANEL ACTION: Reject. PANEL COMMENT: Already adequately covered. Additional receptacle outlets are a design consideration. VOTE ON PANEL ACTION: Unanimously Affirmative. 38 Log # 1240 2- 93 - (210-61-(New)): Reject SUBMITTER: IAEI ~ATION: New Section: 210-61 Other Than One- or Two-Family Dwellings. In other than one- or two-family dwellings at least one receptacle outlet shall be installed within 25 feet (7.62 m) of any equipment requiring servicing. SUBSTANTIATION: Equipment repair persons, when electric tools on trouble lights are needed, are using alligator clips and attaching ahead of fuse or disconnect and grounding to the case of the switch with an adapter on the other end. Many serious injuries have resulted from this practice. This is not only on roofs, but in attic spaces, and at grade level outside. Two f a t a l i t i e s were recorded last year in Southern California, one on a roof connected clips to a 480 volt switch) and one in an attic connected soldering iron and touched a gas line). PANEL ACTION: Reject. PANEL COMMENT: See Panel Comment for Proposal 2-91. VOTE ON PANEL ACTION: AFFIRMATIVE: 9 NEGATIVE: Bowling. EXPLANATION OF VOTE: BOWLING: See comments on Proposal 2-91. Log # 1508 2- 89 - (210-52(x)-(New)): Reject SUBMII-FER: Melvin K. Sanders, Ankeny, IA ~ATION: Add a new section: Hallways. There shall be one receptacle outlet for each 10 feet or major fraction of hall ways. SUBSTANTIATION: The only way receptacle outlets can be required in dwelling unit hallways as now presently worded is to f a l l back upon Section 210-50(b) since i t is expected that floor cleaning equipment will be used. This creates a misunderstanding problem with the installer and requires a call back to provide an outlet in hallways. Most vacuum sweepers are equipped with a cord of sufficient length so that in most homes one receptacle would suffice. The Code requires receptacles in many areas of the dwelling for convenience sake, but neglects to include hallways as one of the specified areas. PANEL ACTION: Reject. PANEL COMMENT: No substantiation as to need. VOTE ON PANEL ACTION: Unanimously Affirmative. I 2- 90 - (210-60): Accept SUBMITTER: C~ 2 RECOMMENDATION: Add the following sentence: "See Section 210-8(b)." SUBSTANTIATION: To call attention to new G~CI requirements. PANEL ACTION:" Accept. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 1283, 1908 2- 94 - (210-63-(New)): Reject SUBMITTERS: IAEI (1283) ~ v e / M . Shapiro, Michigan Chapter IAIE (1908) RECOMMENDATION: Add new section: 210-63 Receptacle Outlets (In Other Than Dwelling-Type Occupancies). (i) Receptacle outlets shall not be connected to circuits supplying general lighting including office portions of buildings. (2) A readily accessible duplex receptacle, fed from any 115 volt receptacle circuit, shall be installed on the roof within twenty-five (25) feet of each roof-top heating, air conditioning and refrigeration unit or any combination of these units. SUBSTANTIATION: (1) Our experience shows that receptacle circuits are much more often overloaded resulting in overloads and outages. Losing the lights in a public building can have serious negative consequences. (2) To provide means to service these rooftop units without resorting to unsafe methods. PANEL ACTION: Reject. PANEL COMMENT: Design consideration. No data to support substantiation. VOTE ON PANELACTION: AFFIRMATIVE: 9 NEGATIVE: Bowling. EXPLANATION OF VOTE: BOWLING: Item 1: See Substantiation. Item 2: Adoption would more closely align this Code with other building and mechanical codes now in force. Log # 429 2- 91 - (210-61-(New)): Reject SUBMII-TER: Southwestern Section IAEI ~ATION: 210-61. Other Than One- or Two-Family Dwellings. In other than one- or two-family dwellings at least one receptacle outlet shall be installed within 25 feet (7.62 m) of any equipment requiring servicing. SUBSTANTIATION: Equipment repair persons, when electric tools on trouble lights are needed, are using alligator clips and attaching ahead of fuse or disconnect and grounding to the case of the switch with an adapter on the other end. Manyserious injuries have resulted from this practice. This is not only on roofs, but in attic spaces, and at grade level outside. Two f a t a l i t i e s were recorded last year in Southern California, one on a roof connected clips to a 480 volt switch) and one in an attic connected soldering iron and touched a gas line). PANEL ACTION: Reject. PANEL COMMENT: Substantiation does not support need. VOTE ON PANEL ACTION: AFFIRMATIVE: 9 NEGATIVE: Bowling. EXPLANATION OF VOTE: BOWLING: Means should be provided for servicing equipment. Adoption would more closely align this Code with other building and mechanical codes now in force. I Log # 156 2- 95 - (210-70): Reject SUBMII-TER: Michael J. Goeb, baltimore, MD RECOMMENDATION: None. SUBSTANTIATION: Below please find a copy of complaint concerning a situation concerning an incident which happened to my wife in the sanitary f a c i l i t i e s in the Osler Medical Building in Baltimore County, MD which I believe speaks for i t s e l f . Yesterday May 6, 1981 I had a long conversation with the Baltimore Co. Electrical Engineers. I was informed at this time there was nothing in the Electrical Code that compels the offending parties from operating such a hazardous f a c i l i t y , and only your office can be instrumental i n its elimination. Therefore on behalf of my wife and I, the aged and infirm, the p a r t i a l l y and permanently handicapped, throughout the United States, I plea your office for prompt attention and hopefully a correction of the hazards of such f a c i l i t i e s . (The following is the l e t t e r of complaint mentioned above.) On Wednesday, April 22, 1981 at approximately 9:30 a.m. my wife made a v i s i t to the office of Dr. "X". During the time of her v i s i t there, i t became necessary that she use the sanitary f a c i l i t i e s provided on the second floor. Upon entry, there was some visible l i g h t . Several minutes later she heard a click and all the lights went out. Not knowing what had happened she (my wife) groped around in fear and darkness trying to find a way out as there is not window for the penetration of natural l i g h t . Had she collapsed from coronary arrest or other injury while groping around in the darkness and fear of what was to come, she could have lain there without medical attention for any length of time and death could have been the consequences. Upon returning to the doctor's office, s t i l l in fear and nervous, my wife was informed that several complaints about the lighting in the ladies room have thus far gone unheeded. She was also informed that the light was on a timer switch and thus, had gone out after an allotted time. Having returned home in a state of nervous shock which lasted throughout the day, I decided on Thursday to call the building management. Log # 1115 2- 92 - (210-61-(New)): Reject SUBMITTER: J. H. (Jim) Richards, Maryland Electrical Inspectors ~ o n RECOMMENDATION: One or more receptacle outlets shall be installed outdoors for every building (or structure) regardless of the type of occupancy. These outlets shall have either ground fault protection breakers at the panelboard or be of a type incorporating ground f a u l t protection in the receptacle. Such receptacles shall be located within five feet of grade or floor level. SUBSTANTIATION: Outdoor connections are needed for work or decorations used at commercial, industrial, church, school and other occupancies as well as at dwellings. This presents a need for these proposed receptacles. Receptacles that are out of reach on outdoor installations are often ignored and cords are connected inside the building, from unprotected outlets, and run outside through doors or windows thus bypassing the protection provided for persons. The theory that i t ' s all right to get a serious shock injury away from home but protect yourself at home makes l i t t l e common sense. Note: Somecorrelation with Section 210-52(d) may be needed. PANEL ACTION: Reject. PAIWEL COMMENT: Panel feels this is a design consideration. VOTE ON PANEL ACTION: Unanimously Affirmative. 39 At precisely 10:08 a.m. on Thursday, April 23, 1981, I made a call at which time the lady who answered the phone did not f u l l y understand my complaint. The lady in turn called Ms. "Y". Having been made f u l l y aware of the nature of my complaint, the lady, whom I do not know, called my home and was in agreement that such a deplorable condition should not exist, especially in a medical f a c i l i t y which is frequented primarily by elderly citizens with visual, mental, and bodily handicaps. Secondly, lighting f a c i l i t i e s are, in my opinion, a part of our medical fee, and any deprivation of same is a violation of our health, education and welfare laws, i.e. Federal, State and Local Building Codes. Should the unlighted windowless f a c i l i t y be in violation of the building code of either, and or, all of the aforementioned governments and on behalf of all parties compelled by nature to use same such f a c i l i t i e s , I seek a complete investigation of same such f a c i l i t i e s . And, furthermore, with the rampant increase in criminal activity throughout Baltimore County and elswhere, i t is the express opinion of this complaintant that these blacked-out f a c i l i t i e s are in part blame for same. Should my complaint be found in disfavor of the American public, I extend my apologies to those whom I have inconvenienced. Should my complaint prove positive in regard to the health and safety of the American public, and in consideration of the rampant crime throughout the nation, I question why such vital areas such as the sanitary f a c i l i t i e s are constructed in total darkness and why permits are granted for the construction of same. PANEL ACTION: Reject. PANEL COMMENT: Material included is clearly covered by other than NEC. VOTE ON PANEL ACTION: Unani~w)uslyAffirmative. Log # 1832 2- 99 - (210-70(a)): Reject SUBMII-[ER: Paul E. Phelan, Trade Education Inc. and New Hampshire ~ l Contractors Inc. RECOMMENDATION: Rewrite last sentence which presently reads, "equipment requiring servicing" to read "equipment requiring periodic inspection or servicing." SUBSTANTIATION: Whether equipment requires maintenance is largely a judgement question, but adding "periodic inspection" would provide for illumination to read meters or inspect heating equipment. PANEL ACTION: Reject. PANEL COI~ENT: Present wording adequately reflects Panel intent. VOTE ON PANELACTION: Unanimously Affirmative. Log # 2020 2- 100 - (210-70(a)): Reject SUBMITTER: Idaho Chapter IAEI RECOMMENDATION: Change second paragraph to read: At least one lighting outlet shall be installed in an a t t i c , under floor space, u t i l i t y room and basement, only where these spaces contain equipment requiring servicing or are used for storage. Storage space fixtures shall be located over an area which is unobstructed to the floor maintaining an 18 inch clearance horizontally between the fixture and a storage area where combustible material ma~vbe stored. SUBSTANTIATION: Code requires lighting in areas used for storage without concern as to whether or not the area will ever be used to , store combustible material. In residential occupancies any type of storage is going to be involved with combustible materials, this even holds true in canned goods and vegetable storage areas. PANEL ACTION: Reject. PANEL COM~ZNT: Adequately covered by Code. VOTE ON PANELACTION: Unanimously Affirmative. Log # 119 2- 96 - (210-70(a)): Reject SUBMITTER: Robert S. Dennison, County of Riverside, CA ~ATION: Delete the word "attached" preceding the word "garage." New "Dwelling Unit(s). At least one wall switch-controlled lighting outlet shall be installed in every habitable room; in bathrooms, hallways, stairways, and garages; and at outdoor entrances." SUBSTANTIATION: The same hazards exist in an unlighted detached garage as in an attached garage. The danger of a f a l l exiting or entering an unlighted detached garage are great, and most of the time greater than an attached garage. In addition homeowners are "bootlegging" cords, exposed Romex and jmpr?per overhead wiring after moving into a new home or after construczlng a new detached garage. This change would recognize that the same needs exist in a detached garage as an attahced garage for which the Code now rovides. ANEL ACTION: Reject. PANEL COMMENT: Panel feels this is a design consideration. ~ A C T I O N : UnanimouslyAffirmative. Log # 102 2- 101 - (210-70(a), Exception No. I ) : Reject SUBMIl-[ER: Arnold G. Wencel, Robbinsdale, MN RECOMMENDATION: Add: Wall switch-controlled receptacles installed for this purpose shall be in addition to the receptacles required in 210-52(a). Wall switches intended for lighting control shall be adjacent to room entries. SUBSTANTIATION: In order to make the provisions of Section 210-52(a) effective, i t seems necessary to spell out, that generally; the purpose of receptacles is to supply cord-connected equipment and that switched lighting outlets are not intended as substitutes for the receptacle outlets mentioned in 210-52(a). Section 90-i(b) supports the principle of providing adequate electrical installations to ensure the safety of the use of electricity. PANEL ACTION: Reject. PANEL COMMENT: Panel feels this is a design consideration. Adequately covered by Code. VOTE ON PANELACTION:' Unanimously Affirmative. p Log # 1825 2- 97 - (210-70(a)): Accept SUBMITTER: Paul E. Phelan, Trade Education Inc. and New Hampshire Electrical Contractors Inc. RECOMMENDATION: Changeword "containing" to "contain" so as to read "only where these s~aces are used for storage or contain equipment requiring servlcing." SUBSTANTIATION: Readability. PANEL A~IIUN: Accept. VOTE ON PANELACTION: Unanimously Affirmative. Log # 1132 2- 102 - (210-70(a), Exception No. I : ) : Reject SUBMITTER: Robert C. Halverson, Cargill, Inc RECOMMENDATION: Add the following to Exception No. I: Such receptacles shall be in addition to or in combination with those receptacles required by Section 210-52. SUBSTANTIATION: The present NEC text makes no distinction between receptacle outlets which are energized at all times and those which are wall switch controlled. Consequently, the permanently energized receptacles intended to be required by Section 210-52 are sometimes eliminated entirely and replaced by lighting receptacles. This presents a potentially unsafe condition, in that extension cords Would have to be used to provide continuous power in the affected area(s), contrary to the intent of Section 210-52. The proposed change would require either separate lighting outlets/receptacles or "split-bus" duplex receptacles with half wall switch controlled and half permanently energized where lighting outlets are required. PANEL ACTION: Reject. PANEL COMMENT: Present wording does reflect Panel°s intent. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 1831 2- 98 - (210-70(a)):' Reject SUSMITTER: Paul E. Phelan, Trade Education Inc. and New Hampshire ~ I Contractors Inc. RECOMMENDATION: Reword the sentence "only where these spaces are used for" to read "odly where these spaces are, or may be, used for." SUBSTANTIATION: Electrical Work is usually done prior to occupancy. I t is unlikely that these spaces will be used for storage "prior" to occupancy. This may also be the case with certain pieces of equipment installed by occupant. PANEL ACTION: Reject. PANLL COMMENT: Panel feels that one cannot speculate on future use. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 1254 2- 103 - (210-70(a), Exception No. 1): Reject SUBMITTER: IAEI ITE"C'I~WQB~ATION: Rewrite to read: In habitable rooms other than the kitchens, pantry, breakfast room, and dining room, one or more receptacles controlled by a wall switch shall be permitted in lieu of lighting outlets. SUBSTANTIATION: To move a conflict of Code. Section 220-3(b)(1) does not permit any other outlets onthe small appliance branch circuits. However, Section 210-70(a), Exception No. 1 then ermits wall switch-controlled receptacles in dining rooms, reakfast rooms, and pantries. ~ 40 EXPLANATION OF VOTE: BOWLING: Multiple switching capability would eliminate the necessity of negotiating stairways when not illuminated. The conflict arises that where a receptacle is permitted to be wall switched by Section 210-70(a), Exception No. 1, in lieu of the wall switch-controlled lighting outlet, as required by Section 210-7(a), in fact then permits lighting outlets to be installed on the small appliance circuit. This is a violation of Section 220-3(b)(1) which does not permit any other outlets on a small appliance c i r c u i t . PANEL ACTION: Reject. PANEL COMMENT: I t is the intent of the Panel that the small appliance branch circuits should not supply switched receptacles -used in lieu of switched lighting outlets, as permitted by Section 210-70(a). Exception No. i . VOTE ON PANEL ACTION: AFFIRMATIVE: 8 NEGATIVE: Bowling, Reign. EXPLANATION OF VOTE: BOWLING: This proposal clarifies the intent and eliminates the present conflict of Code sections. REIGN: I f i t ' s the Panel's intent, and i t appears to be from the Panel Comment, that the small appliance branch circuits should NOT supply switched receptacles used in lieu of switched lighting outlets, them the submitter's proposal should be accepted because that is what he is trying to do by eliminating this conflict now allowed by Section 210-70(a), Exception No. 1. Log # 1906 2- 107 - (210-70(d)-(New)): Reject SUBMITTER: M. Shapiro/P. Van Putten, Michigan Chapter IAEI R~ATION: Add 210-70(d) "Stairways and Hallways" (In Dwelling-Type Occupancies). (d) All stairway lighting outlets shall have multiple switch control at head and foot of stairway unless supplied by house meter and controlled by time clock or controls accessible to authorized persons only. SUBSTANTIATION: To provide for safetyand to allow for energy conservation. PANEL ACTION: Reject. PANEL COMFIENT: Panel feels this is a design consideration. VOTE ON PANEL ACTION: AFFIRMATIVE: 9 NEGATIVE: Bowling. EXPLANATION OF VOTE: BOWLING: See comments on Proposal 2 - i 0 6 . Log # 1905 2- 108 - (210-71-(New)): Reject SUBMITTERS: M. Shapiro/P. Van Putten, Michigan Chapter, IAEI ~ T I O N : Add new: ZI0-/I. "Switches" (In Other Than Dwelling-Type Occupancies). All stairway lighting outlets shall have multiple switch control at head and foot of stairway unless supplied by house meter and controlled by time clock or controls accessible to authorized persons only. SUBSTANTIATION: To provide for safety and encourage energy conservation. PANEL ACTION: Reject. PANEL COMMENT: Panel feels this is a design consideration. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 144 2- 104 - (210-70(a)): Reject SUBMITTER: Dan Leaf, Westlake Village, CA ~ATION: Revise second paragraph of (a) as follows: (b) All occupancies. At least one wall switch-controlled lighting outlet shall be installed in an a t t i c , underfloor space, above ceiling space, u t i l i t y room and basement only where these spaces are used for storage or containing equipment requiring servicing. Change paragraph (b) to (c). SUBSTANTIATION: I f safety requires a lighting outlet in these areas of a dwelling, the need is no less in a commercial occupancy where the same spaces may have the same or similar type equipment installed. The present wording does not cover equipment locations in above-ceiling spaces (between floors). These are not generally defined as attics. I am presently involved in the construction of a large building complex where several dozen electric water heaters and air conditioning units with external motors and belts, and associated controls have been installed in above-ceiling spaces, with no lighting outlets provided for servicing this equipment. In my opinion this lack of lighting increases the potential hazard for tripping, f a l l i n g , injury from moving parts, and electric shock. PANEL ACTION: Reject. PANEL COMMENT: Panel feels this is adequately covered by Code. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 1904 2- 109 - (210-72-(New)): Reject SUBMITTERS: M.'Shapiro/P. Van Putten, Michigan Chapter IAEI RECOMMENDATION: Add new Section 210-72: Toilet Ventilation. Toilets requiring mechanical ventilation shall be provided with a light and vent fan operated simultaneously with the light switch, unless ventilation is provided by a fan whose controls are accessible to authorized persons only and are operated during normal occupancy of the building. In dwellings, a switch separate from the light shall be rovided. UBSTANTIATION: The NEC makes no provisions for this yet all the building codes do address themselves to this problem and we should also. The reason for a separate switch in dwellings is to provide a no-draft condition while a baby is being bathed and energy conservation i f the bathroom was used for washing or bathing only. PANEL ACTION: Reject. PANEL COMMENT: Panel feels this is a design consideration. VOTE ON PANELACTION: Unanimously AfFirmative. ~ Log # 1284, 1907 2- 105 - (210-70(c)-(New)): Reject SUBMITTERS: IAEI (1284) H. B. Love/M. Shapiro, Michigan Chapter IAEI (1907) RECOMMENDATION: Add new subsection as follows: Basement Lighting. Basements in dwelling-type occupancies shall be wired for a minimum of one ( i ) lighting outlet in each 200 square feet or major fraction of area for use as general illumination. All enclosed areas that may be walked into such as t o i l e t rooms, f r u i t storage room, u t i l i t y rooms, excavated areas under porches, etc., shall be provided with at" least one (i) lighting outlet (except coal bins). SUBSTANTIATION: This proposal provides for more adequate lighting in large areas. Under the present rule only one light is required even in large areas. PANEL ACTION: Reject. PANEL COMMENT: Panel feels this is a design consideration. VOTE ON PANEL ACTION: AFFIRMATIVE: 9 NEGATIVE: Bowling. EXPLANATION OF VOTE: BOWLING: This proposal assures illumination of all divisions or partitioned areas of a basement. ARTICLE 212 -- MINIMUMSTANDARDS Log # 1893 2- 110 - (Article 212-(New)): Reject SUBMITTERS: Pete Van Putten/B. L. Auger/Mark Shapiro, Michigan Chapter of IAEI RECOMMENDATION: Minimum Standards for the Wiring of Existing Dwelling-Type Occupancies. 212-i. Scope. This article covers the wiring of existing wired dwelling type occupancies. 212-2. Inadequate Wiring. Evidence of the inadequacy of wiring of an existing dwelling-type occupancy shall be one or more of the following: (a) Use of cords in lieu of permanent wiring. (b) Oversizing of conductor overcurrent protection for branch circuits, feeders or services. (c) Unapproved extensions to the wiring system in order to provide l i g h t , heat or power. (d) Existence of less than two (2) duplex electrical receptacle outlets in each habitable room or one (1) duplex electrical receptacle outlet on each wall in the living room or one ( i ) duplex electrical receptacle outlet in the bathroom. (e) Electrical overloads. ( f ) Misuse of electrical equipment. (g) Lack of an operable light f i x t u r e in every t o i l e t room, bathroom, laundry room, kitchen, furnace room, hall or stairway. (h) Lack of an operable laundry receptacle on an independent circuit. (i) Lack of at least one (I) lighting outlet in basement area. Log # 1285 2- 106 - (210-70(d)-(New)): Reject SUBMITTER: IAEI ITE'C'~PElql)ATION: Add 210-70(d) Stairways and Hallways, (In Dwelling-Type Occupancies). (d) All stairway lighting outlets shall have multiple switch control at head and foot of stairway unless supplied by time clock or controls accessible to authorized persons only. SUBSTANTIATION: To provide for safety and to allow for energy conservation. PANEL ACTION: Reject. PANEL COMMENT: Panel feels this is a design consideration. VOTE ON PANEL ACTION: AFFIRMATIVE: 9 NEGATIVE: Bowling. 41 C. EXPLANATION OF VOTE: BOWLING: Multiple switching capability would eliminate the necessity of negotiating stairways when not illuminated. The conflict arises that where a receptacle is permitted to be wall switched by Section 210-70(a), Exception No. 1, in lieu of the wall switch-controlled lighting outlet, as required by Section 210-7(a), in fact then permits lighting outlets to be installed on the small appliance circuit. This is a violation of Section 220-3(b)(1) which does not permit any other outlets on a small appliance c i r c u i t . PANEL ACTION: Reject. PANEL COMMENT: I t is the intent of the Panel that the small appliance branch circuits should not supply switched receptacles -used in lieu of switched lighting outlets, as permitted by Section 210-70(a). Exception No. i . VOTE ON PANEL ACTION: AFFIRMATIVE: 8 NEGATIVE: Bowling, Reign. EXPLANATION OF VOTE: BOWLING: This proposal clarifies the intent and eliminates the present conflict of Code sections. REIGN: I f i t ' s the Panel's intent, and i t appears to be from the Panel Comment, that the small appliance branch circuits should NOT supply switched receptacles used in lieu of switched lighting outlets, them the submitter's proposal should be accepted because that is what he is trying to do by eliminating this conflict now allowed by Section 210-70(a), Exception No. 1. Log # 1906 2- 107 - (210-70(d)-(New)): Reject SUBMITTER: M. Shapiro/P. Van Putten, Michigan Chapter IAEI R~ATION: Add 210-70(d) "Stairways and Hallways" (In Dwelling-Type Occupancies). (d) All stairway lighting outlets shall have multiple switch control at head and foot of stairway unless supplied by house meter and controlled by time clock or controls accessible to authorized persons only. SUBSTANTIATION: To provide for safetyand to allow for energy conservation. PANEL ACTION: Reject. PANEL COMFIENT: Panel feels this is a design consideration. VOTE ON PANEL ACTION: AFFIRMATIVE: 9 NEGATIVE: Bowling. EXPLANATION OF VOTE: BOWLING: See comments on Proposal 2 - i 0 6 . Log # 1905 2- 108 - (210-71-(New)): Reject SUBMITTERS: M. Shapiro/P. Van Putten, Michigan Chapter, IAEI ~ T I O N : Add new: ZI0-/I. "Switches" (In Other Than Dwelling-Type Occupancies). All stairway lighting outlets shall have multiple switch control at head and foot of stairway unless supplied by house meter and controlled by time clock or controls accessible to authorized persons only. SUBSTANTIATION: To provide for safety and encourage energy conservation. PANEL ACTION: Reject. PANEL COMMENT: Panel feels this is a design consideration. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 144 2- 104 - (210-70(a)): Reject SUBMITTER: Dan Leaf, Westlake Village, CA ~ATION: Revise second paragraph of (a) as follows: (b) All occupancies. At least one wall switch-controlled lighting outlet shall be installed in an a t t i c , underfloor space, above ceiling space, u t i l i t y room and basement only where these spaces are used for storage or containing equipment requiring servicing. Change paragraph (b) to (c). SUBSTANTIATION: I f safety requires a lighting outlet in these areas of a dwelling, the need is no less in a commercial occupancy where the same spaces may have the same or similar type equipment installed. The present wording does not cover equipment locations in above-ceiling spaces (between floors). These are not generally defined as attics. I am presently involved in the construction of a large building complex where several dozen electric water heaters and air conditioning units with external motors and belts, and associated controls have been installed in above-ceiling spaces, with no lighting outlets provided for servicing this equipment. In my opinion this lack of lighting increases the potential hazard for tripping, f a l l i n g , injury from moving parts, and electric shock. PANEL ACTION: Reject. PANEL COMMENT: Panel feels this is adequately covered by Code. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 1904 2- 109 - (210-72-(New)): Reject SUBMITTERS: M.'Shapiro/P. Van Putten, Michigan Chapter IAEI RECOMMENDATION: Add new Section 210-72: Toilet Ventilation. Toilets requiring mechanical ventilation shall be provided with a light and vent fan operated simultaneously with the light switch, unless ventilation is provided by a fan whose controls are accessible to authorized persons only and are operated during normal occupancy of the building. In dwellings, a switch separate from the light shall be rovided. UBSTANTIATION: The NEC makes no provisions for this yet all the building codes do address themselves to this problem and we should also. The reason for a separate switch in dwellings is to provide a no-draft condition while a baby is being bathed and energy conservation i f the bathroom was used for washing or bathing only. PANEL ACTION: Reject. PANEL COMMENT: Panel feels this is a design consideration. VOTE ON PANELACTION: Unanimously AfFirmative. ~ Log # 1284, 1907 2- 105 - (210-70(c)-(New)): Reject SUBMITTERS: IAEI (1284) H. B. Love/M. Shapiro, Michigan Chapter IAEI (1907) RECOMMENDATION: Add new subsection as follows: Basement Lighting. Basements in dwelling-type occupancies shall be wired for a minimum of one ( i ) lighting outlet in each 200 square feet or major fraction of area for use as general illumination. All enclosed areas that may be walked into such as t o i l e t rooms, f r u i t storage room, u t i l i t y rooms, excavated areas under porches, etc., shall be provided with at" least one (i) lighting outlet (except coal bins). SUBSTANTIATION: This proposal provides for more adequate lighting in large areas. Under the present rule only one light is required even in large areas. PANEL ACTION: Reject. PANEL COMMENT: Panel feels this is a design consideration. VOTE ON PANEL ACTION: AFFIRMATIVE: 9 NEGATIVE: Bowling. EXPLANATION OF VOTE: BOWLING: This proposal assures illumination of all divisions or partitioned areas of a basement. ARTICLE 212 -- MINIMUMSTANDARDS Log # 1893 2- 110 - (Article 212-(New)): Reject SUBMITTERS: Pete Van Putten/B. L. Auger/Mark Shapiro, Michigan Chapter of IAEI RECOMMENDATION: Minimum Standards for the Wiring of Existing Dwelling-Type Occupancies. 212-i. Scope. This article covers the wiring of existing wired dwelling type occupancies. 212-2. Inadequate Wiring. Evidence of the inadequacy of wiring of an existing dwelling-type occupancy shall be one or more of the following: (a) Use of cords in lieu of permanent wiring. (b) Oversizing of conductor overcurrent protection for branch circuits, feeders or services. (c) Unapproved extensions to the wiring system in order to provide l i g h t , heat or power. (d) Existence of less than two (2) duplex electrical receptacle outlets in each habitable room or one (1) duplex electrical receptacle outlet on each wall in the living room or one ( i ) duplex electrical receptacle outlet in the bathroom. (e) Electrical overloads. ( f ) Misuse of electrical equipment. (g) Lack of an operable light f i x t u r e in every t o i l e t room, bathroom, laundry room, kitchen, furnace room, hall or stairway. (h) Lack of an operable laundry receptacle on an independent circuit. (i) Lack of at least one (I) lighting outlet in basement area. Log # 1285 2- 106 - (210-70(d)-(New)): Reject SUBMITTER: IAEI ITE'C'~PElql)ATION: Add 210-70(d) Stairways and Hallways, (In Dwelling-Type Occupancies). (d) All stairway lighting outlets shall have multiple switch control at head and foot of stairway unless supplied by time clock or controls accessible to authorized persons only. SUBSTANTIATION: To provide for safety and to allow for energy conservation. PANEL ACTION: Reject. PANEL COMMENT: Panel feels this is a design consideration. VOTE ON PANEL ACTION: AFFIRMATIVE: 9 NEGATIVE: Bowling. 41 C. 212-3. Entrance and Exits. Entrances and exits shall be illuminated by exterior lighting outlets. Lighting outlets shall be controlled by interior wall switches, located for convenient and readily accessible use. 212-4. Living Rooms. The living room shall be provided with illumination, The lightin 9 outlet shall be controlled by a wall switch, located, for convenlent and readily accessible use, nearest to the entrance into the room. A receptacle outlet controlled by a wall switch in lieu of a lighting outlet shall be permitted. Convenient duplex electrical receptacle outlets shall be provided equally spaced around the room, at least one (1) duplex electrical outlet on each wall. 212-5. Kitchens. Kitchens shall be provided w4th illumination. A lighting outlet(s) shall be controlled by a wall switch, located for convenient and readily accessible use, nearest to the entrance to the room. A separate small appliance circuit shall be provided, supplying a minimum of three (3) grounding type duplex electrical receptacle outlets. Two (2) of these receptacles shall be located for convenient and readily accessible use. New appliance circuits shall be a minimum of twenty (20) ampere capacity. 212-6. Bathrooms or Washrooms. Bathrooms or washrooms shall be illuminated. The lighting outlet or outlets shall be controlled by a wall switch. In bathrooms; a receptacle outlet, separate from the lighting fixture shall be provlded adjacent to the wash basin. 212-7. Habitable Rooms. All habitable rooms shall be illuminated. Lighting outlets shall be controlled by a wall switch. Wall switches shall be located for conyenient and readily accessible use. Convenient duplex electrical receptacle outlets shall be provided with a minimum of two (2) outlets equally spaced around the room. An additional receptacle outlet, controlled by a wall switch, shall be permitted in lieu of a light outlet. 212-8. Basement. Basements shall be wired for a minimum of one (1) lighting outlet. All additional enclosed a~eas used for storage or containing equipment requiring servicing such as furnace rooms, f r u i t storage rooms etc. shall be provided with at least one ( i ) lighting outlet (except coal bins). 212-9. Laundry Areas. Laundry areas shall be provided with illumination. Laundry circuit shall be an individual circuit. A wall-mounted grounding type duplex receptacle outlet shall be provided, located near the laundry equipment. An existing drop cord receptacle outlet on a separate circuit shall be acceptable providing i t is a grounding type receptacle outlet not more than five (5) feet six (6) inches above the floor. 212-10. Stairways. Stairways and/or each stair section shall be adequately illuminated. Lighting outlets shall be controlled by wall switches. Wall switches shall be located for convenient and readily accessible use. 212-11. Service and Feeders. Service to existing dwelling unit shall be at a minimum three (3) wire f i f t y - f i v e (55) ampere capacity. Service equipment shall be dead front. Type "S" fuses shall be installed where fusible equipment is used. Ampacity of existing feeder conductors shall be t h i r t y (30) amperes, minimum. I f the existing service does not comply with the above and i t is then necessary to increase service or change service equipment, the service shall be increased in compliance with Section 230-41(b). 212-12. Existing Wiring and Electrical Equipment. Existing wiring and equipment shall be in good repair. Existing wiring and electrical equipment shall be maintained and used as originally listed and designed to be used. Circuit extensions made with flexible cord wiring in lieu of permanent wiring shall be eliminated. 212-13. New Work. All new wiring and electrical equipment used to replace existing inadequate wiring shall comply with all of the provisions of the NATIONAL ELECTRICAL CODE(NFPA 70). SUBSTANTIATION: This proposal has been entitled Article 212 since the proposors have visions of its being adopted and taking its rightful position in the Code. We would not be opposed to Code-Making Panel designating the article as new Chapter 10 so that local units may elect by ordinance to adopt the Code with or without Chapter 10. Section gO-l(a), properly states the PURPOSEof the Code as "the practical safeguarding of persons and property from hazards arising from the use of e l e c t r i c i t y . " Further, the fine print note to part "(b) Adequacy," alludes to the misuse of electrical systems due to increases (new) in uses of e l e c t r i c i t y . The l a t t e r statement probably presents more succinctly the need we have for new Article 212. The development of electrical appliances in our homes for culinary, personal care, temperature control and liesure time recreational purposes has extended the use of the original system, designed for basic lighting, far beyond its safe limits. Since these systems are installed to service every area of our homes we are l i t e r a l l y wrapped up in an envelope of electrical branch c i r c u i t r y . Therefore, any abrogation of safe wiring practices can place any area of the home in jeopardy. The lack of receptacle outlets has led to a proliferation of fixture cord type extensions to f a c i l i t a t e the use of today's appliances. With Table 402-5 declaring a No. 18 cord to operate at a maximum of 6 amperes, we should not feel complacent about this misuse since the preponderance of inspections show that these cords are not in free air as tested for their use as fixture cords. The facts are that they are covered with carpeting, furniture or the l i t t e r of living which in effect chokes off the free air and therefore we must derate the allowable ampacity accordingly. The'cords are also cascaded, i f the cord does not reach the desired area, patch on another. Our friends from Underwriters Lab have very f i t t i n g l y either by design or coincidence assigned a product category index of ZIPR to this anomalous wiring method product. Tables 40045 and 402-5 are the optimum condition ampacities and the overcurrent protection specified in Section 240-4 definitely cannot take into account the conditions which we observe in the f i e l d . Is i t then any wonder that these cords and all the combustible items adjacent thereto are often completely incinerated before the overcurrent device can perform its designed task? With nationwide statistics indicating up to 20-25 percent of building fires being of an electrical ignition source i t is imperative that we adopt a minimum standard for rewiring these inadequately wired older homes. The Michigan Chapter, IAEI, has proffered this Article 212 for the 1978 and 1981 Codes. Our model for the proposal is the City of Detroit, Michigan Chapter 10, Electrical Code, "Minimum Standards." This standard has been in effect for over two decades and is bein9 used as a mandatory requirement in over 150 governmenta] units in Michigan to obtain commitments for. V.A., F.H.A. and other Federal funds guaranteeing loans on prlor owoed housing units. The United States Department of Housing and Urban Development commissioned a research on rehabilitation of used housing through the National Institute of Building Sciences. Out of that study a "Rehabilitation Guidelines, 1980" was produced which details the problem, cites that NATIONAL ELECTRICAL CODE, suggests solutions and lists as an appendix, Chapter 10, Detroit Electric Code. The "Guidelines" were a Congressional mandate. The booklet can be ordered from the Superintendent of Documents, U.S. Government Printing Office, Washington, D.C. 20402. The stock number for the book is 023-000-00640-5~ The t i t l e is,, "Electrical Guidelines for Residential Rehabilitation.~' We as an industry and also the Code-Making Panel should adopt the proposal as a standard. F o r too long we have lived with building code o f f i c i a l s ' attempts at writing minimum electrical standards. Those standards are so woefully inadequate that the application thereof encourages the use of extension cords. I f we delay our efforts we may see some bureaucratic group use the "Guidelines" to promulgate a standard which may well be in conflict with tested and proven practices in the electrical industry. Among the groups who worked on the Guidelines were; U.S. Conference of Mayors, National League of Cities, National Assoc. of Housing and Redevelopment Officials, AFL-CIO Building and Construction Trades Council, National Assoc. of Home Builders, U.S. League of Savings Assoc's., Council of American Building Officials, National Fire Protection Association, and the American Institute of Architects. The need for a minimum housing standard is clearly attested to by the thousands of governmental units across the country that have enacted their own rules. While we are not in a position to know of and l i s t them all (and this is just the point), we are aware that the State of Massachusetts, the City of Minneapolis, and our own 150 plus communities in Michigan are a relative handfull amongmany. Yet, we boast of being the only trade with one uniform national code. PANEL ACTION: Reject. PANEL COMMENT: The Code is designed to provide the minimum requirements needed for safeguarding persons and property. Any deviation from this Standard for existing occupancies is better l e f t to local government agencies. VOTE ON PANEL ACTION: Unanimously Affirmative. CO~MENT ON VOTE: CUNNINGHAM: I disagree with Panel Comment. I t should not be suggested that governmental agencies should adopt or accept" rules less stringent than the minimum safety standards of the NEC. The second sentence should be dropped. 42 ARTICLE 215 -- FEEDERS Log # 347 2- 115 - (215-2, Paragraph 1): Reject SUBMITTER: DougOppedal, Story City, IA ~ T I O N : Feeder conductors shall' have an ampacity not lower than required to supply the load as computed in Parts B, C, and D, of Article 220. The minimum sizes shall be as specified in (a) and (b) below under the conditions stipulated. Feed conductors for "all occupancies" need not be larger than service-entrance conductors. SUBSTANTIATION: This Code states that feeder conductors for a dwelling unit or a mobile home need not be larger than service-entrance conductors. In any occupancy feeder conductors need not be larger than the service-entrance conductors. This section doesn't state that. PANEL ACTION: Reject. PANEL COMMENT: There is a lack of substantiation for extending the practice of reducing the feeder size. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 1506 2- 111 - (215-x-(New)): Reject SUBMII-TER: Melvin K. Sanders, Ankeny, IA ~ATION: Add new section: 215-X. Ground-fault Protection for Equipment. Ground-fault protection for equipment shall be permitted to be installed where required elsewhere in the Code. The ground-fault protection system shall be performance tested when f i r s t installed. The test shall be conducted in accordance with approved instructions which shall be provided with the equipment. A written record of this test shall be made and shall be available to the authority having jurisdiction. SUBSTANTIATION: I t is just as c r i t i c a l for feeder ground-fault equipment to be performance tested as for service equipment, especially when i t is necessary that proper coordination be achieved when required in large capacity hosptial feeders as covered in Section 517-14(a). This proposal coordinates with a proposal to the Panel having jurisdiction over Article 517 that the required additional step of ground-fault circuit interrupter be performance tested similar to services in Section 230-95. PANEL ACTION: Reject. PANEL COMMENT: Substantiation does not support the proposal. VOTE ON PANELACTION: Unanimously Affirmative. Log # 627 2- 112 - (215-2): Accept SUBMII'TER: R. P. O'Riley, Dallas Joint Electrical Apprenticeship and Training Committee RECOMMENDATION: Last sentence of Section 215~2 now reads: "Feeder conductors for a dwelling unit or etc." Drop the "a" before dwelling unit and change the word "unit" to "units." New reading: "Feeder conductors for dwelling units or etc." SUBSTANTIATION: There is a conflict between Section 215-2 and Table 310-16, Note 3. Section 215-2 is singular using a dwelling unit. Table 310-16, Note 3 is plural using the term dwelling units. This change would make Section 215-2 and Table 310-16, Note 3 read the same. PANEL ACTION: Accept. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 1776 2- 116 - (215-8, FPN-(New)): Reject SUBMITTER: Tom Tombarello, Paul Revere Chapter IAEI ~ATION: Add a new fine print note as follows: FPN: See Section 384-3(e) and (f) for phase arrangement. SUBSTANTIATION: Correlation is necessary among Sections 215-8, ZJO-b6, and 384-3(e) and (f) and any exception or modifications to these requirements. PANEL ACTION: Reject. PANEL COMMENT: Panel feels this is not required. VOTE ON PANEL ACTION: UnanimouslyAffirmative. I Log # 352 2- 113 - (215-2): Reject SUBMITTER: Gary McPherson, Sheldon, IA ~ATION: Existing feeder conductors shall not be overloaded by additions to the systems. Overloaded feeder conductors shall be replaced with conductors not smaller than required to supply the load. SUBSTANTIATION: According to 215-i this article is for new installation and does not cover existing installations. I t is not in the Code that you can't overload existing installations by installing additional equipment or branch circuits. PANEL ACTION: Reject. PANEL COMMENT: Feeder ampacities are presently covered in the ~ode. I t is up to local enforcement agencies to determine deficiencies in existing systems. See Section 220-35. VOTE ON PANEL ACTION: Unanimously Affirmative. 2- 117 - (215-9): Accept SUBMITTER: CMP 2 DATION: Add to last line: "and Article 305." SUBSTANTIATION: The Correlating Committee has voted to direct CMP 2 and CMP 3 to transfer the text of Section 210-8(b) to an appropriate section in Article 305. PANEL ACTION: Accept. VOTE ON PANEL ACTION: Unanimously Affirmative. ARTICLE 220 -- BRANCH-CIRCUIT AND FEEDER CALCULATIONS 2- 118 - (220-i): Accept Secretary's Note: The Correlating Committee advises CI~~ 2 that article scope statements are the responsibility of the Correlating Committee and that the Correlating Committee accepts the Panel Action. SUBMITTER: C/~° 2 RECOMMENDATION: Add a second paragraph to the scope as follows: "Unless other voltages are specified, for purposes of computing branch-circuit and feeder loads, nominal system voltages of 120, 120/240, 208Y/120, 240, 480Y/277, 480, and 600 volts shall be used." SUBSTANTIATION: There is a need to specify what voltage level the Panel intends should be used for branch-circuit and feeder computations. The voltage levels selected are in keeping with the nominal system voltages listed in ANSI Standard C84.1. 'PANEL ACTION: Accept. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 1614 2- 114 - (215-2(b), FPN): Reject SUBMITTER: Allen KnicKrehm, Los Angeles, CA I~-E~R~'tQ~IE'N'I~ATION: Raise voltage drop note to f u l l size print, making i t a requirement. Insert "shall be" before the word Usized" in the f i r s t line and delete the last phrase, ending the sentence with . . . 5 percent. SUBSTANTIATION: The problem is that Article 310 does not p~ovide for voltage drop. In the past the smaller branch circuit conductors were underrated with minimized voltage drop. problems. This is no longer necessarily true, and i t is not right to not make a provision to protect the public from the problem associated with low voltage. PANEL ACTION: Reject. PANEL COMMENT: See Panel Comment for Proposal 2-48. VUl~ UN PANELACTION: AFFIRMATIVE: 8 NEGATIVE: Bowling, Craig. EXPLANATION OF VOTE: BOWLING: See comments on Proposal 2-48. CRAIG: I agree with the substantiation. The public needs protection from the problems associated with low voltage. Log # 667 2- 119 - (Article 220 & Examples in Chapter 9): Reject SUBMITTER: Warren H. Cook, IEEE ~ATION: Replace all reference to "watts" or "kilowatts" to read "voltamps" or "kilovoltamps." SUBSTANTIATION: The terms "watts" does not necessarily reflect true ampere load on a circuit and except for 100 percent power-factor loads could result in calculated loads using watts resulting in currents considerably less than actual. An example for a fluorescent lighting system is as follows: A typical rapid start, high power factor ballast for one F40T12/RS lamp at 115 volts (GE #6G3106W) lists an input of 50 watts and 0.45 amperes. Their low power factor ballast for one F40T12 preheat start lamp (#6G3022) lists an input of 45 watts and 0.73 amperes. Example 3 blithely equates receptable load in volt-amperes to equal watts. PANEL ACTION: Reject. PANEL COMMENT: Correction for power factor is already covered in Sections 210-22(b) and 220-2(b), FPN. 43 ARTICLE 215 -- FEEDERS Log # 347 2- 115 - (215-2, Paragraph 1): Reject SUBMITTER: DougOppedal, Story City, IA ~ T I O N : Feeder conductors shall' have an ampacity not lower than required to supply the load as computed in Parts B, C, and D, of Article 220. The minimum sizes shall be as specified in (a) and (b) below under the conditions stipulated. Feed conductors for "all occupancies" need not be larger than service-entrance conductors. SUBSTANTIATION: This Code states that feeder conductors for a dwelling unit or a mobile home need not be larger than service-entrance conductors. In any occupancy feeder conductors need not be larger than the service-entrance conductors. This section doesn't state that. PANEL ACTION: Reject. PANEL COMMENT: There is a lack of substantiation for extending the practice of reducing the feeder size. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 1506 2- 111 - (215-x-(New)): Reject SUBMII-TER: Melvin K. Sanders, Ankeny, IA ~ATION: Add new section: 215-X. Ground-fault Protection for Equipment. Ground-fault protection for equipment shall be permitted to be installed where required elsewhere in the Code. The ground-fault protection system shall be performance tested when f i r s t installed. The test shall be conducted in accordance with approved instructions which shall be provided with the equipment. A written record of this test shall be made and shall be available to the authority having jurisdiction. SUBSTANTIATION: I t is just as c r i t i c a l for feeder ground-fault equipment to be performance tested as for service equipment, especially when i t is necessary that proper coordination be achieved when required in large capacity hosptial feeders as covered in Section 517-14(a). This proposal coordinates with a proposal to the Panel having jurisdiction over Article 517 that the required additional step of ground-fault circuit interrupter be performance tested similar to services in Section 230-95. PANEL ACTION: Reject. PANEL COMMENT: Substantiation does not support the proposal. VOTE ON PANELACTION: Unanimously Affirmative. Log # 627 2- 112 - (215-2): Accept SUBMII'TER: R. P. O'Riley, Dallas Joint Electrical Apprenticeship and Training Committee RECOMMENDATION: Last sentence of Section 215~2 now reads: "Feeder conductors for a dwelling unit or etc." Drop the "a" before dwelling unit and change the word "unit" to "units." New reading: "Feeder conductors for dwelling units or etc." SUBSTANTIATION: There is a conflict between Section 215-2 and Table 310-16, Note 3. Section 215-2 is singular using a dwelling unit. Table 310-16, Note 3 is plural using the term dwelling units. This change would make Section 215-2 and Table 310-16, Note 3 read the same. PANEL ACTION: Accept. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 1776 2- 116 - (215-8, FPN-(New)): Reject SUBMITTER: Tom Tombarello, Paul Revere Chapter IAEI ~ATION: Add a new fine print note as follows: FPN: See Section 384-3(e) and (f) for phase arrangement. SUBSTANTIATION: Correlation is necessary among Sections 215-8, ZJO-b6, and 384-3(e) and (f) and any exception or modifications to these requirements. PANEL ACTION: Reject. PANEL COMMENT: Panel feels this is not required. VOTE ON PANEL ACTION: UnanimouslyAffirmative. I Log # 352 2- 113 - (215-2): Reject SUBMITTER: Gary McPherson, Sheldon, IA ~ATION: Existing feeder conductors shall not be overloaded by additions to the systems. Overloaded feeder conductors shall be replaced with conductors not smaller than required to supply the load. SUBSTANTIATION: According to 215-i this article is for new installation and does not cover existing installations. I t is not in the Code that you can't overload existing installations by installing additional equipment or branch circuits. PANEL ACTION: Reject. PANEL COMMENT: Feeder ampacities are presently covered in the ~ode. I t is up to local enforcement agencies to determine deficiencies in existing systems. See Section 220-35. VOTE ON PANEL ACTION: Unanimously Affirmative. 2- 117 - (215-9): Accept SUBMITTER: CMP 2 DATION: Add to last line: "and Article 305." SUBSTANTIATION: The Correlating Committee has voted to direct CMP 2 and CMP 3 to transfer the text of Section 210-8(b) to an appropriate section in Article 305. PANEL ACTION: Accept. VOTE ON PANEL ACTION: Unanimously Affirmative. ARTICLE 220 -- BRANCH-CIRCUIT AND FEEDER CALCULATIONS 2- 118 - (220-i): Accept Secretary's Note: The Correlating Committee advises CI~~ 2 that article scope statements are the responsibility of the Correlating Committee and that the Correlating Committee accepts the Panel Action. SUBMITTER: C/~° 2 RECOMMENDATION: Add a second paragraph to the scope as follows: "Unless other voltages are specified, for purposes of computing branch-circuit and feeder loads, nominal system voltages of 120, 120/240, 208Y/120, 240, 480Y/277, 480, and 600 volts shall be used." SUBSTANTIATION: There is a need to specify what voltage level the Panel intends should be used for branch-circuit and feeder computations. The voltage levels selected are in keeping with the nominal system voltages listed in ANSI Standard C84.1. 'PANEL ACTION: Accept. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 1614 2- 114 - (215-2(b), FPN): Reject SUBMITTER: Allen KnicKrehm, Los Angeles, CA I~-E~R~'tQ~IE'N'I~ATION: Raise voltage drop note to f u l l size print, making i t a requirement. Insert "shall be" before the word Usized" in the f i r s t line and delete the last phrase, ending the sentence with . . . 5 percent. SUBSTANTIATION: The problem is that Article 310 does not p~ovide for voltage drop. In the past the smaller branch circuit conductors were underrated with minimized voltage drop. problems. This is no longer necessarily true, and i t is not right to not make a provision to protect the public from the problem associated with low voltage. PANEL ACTION: Reject. PANEL COMMENT: See Panel Comment for Proposal 2-48. VUl~ UN PANELACTION: AFFIRMATIVE: 8 NEGATIVE: Bowling, Craig. EXPLANATION OF VOTE: BOWLING: See comments on Proposal 2-48. CRAIG: I agree with the substantiation. The public needs protection from the problems associated with low voltage. Log # 667 2- 119 - (Article 220 & Examples in Chapter 9): Reject SUBMITTER: Warren H. Cook, IEEE ~ATION: Replace all reference to "watts" or "kilowatts" to read "voltamps" or "kilovoltamps." SUBSTANTIATION: The terms "watts" does not necessarily reflect true ampere load on a circuit and except for 100 percent power-factor loads could result in calculated loads using watts resulting in currents considerably less than actual. An example for a fluorescent lighting system is as follows: A typical rapid start, high power factor ballast for one F40T12/RS lamp at 115 volts (GE #6G3106W) lists an input of 50 watts and 0.45 amperes. Their low power factor ballast for one F40T12 preheat start lamp (#6G3022) lists an input of 45 watts and 0.73 amperes. Example 3 blithely equates receptable load in volt-amperes to equal watts. PANEL ACTION: Reject. PANEL COMMENT: Correction for power factor is already covered in Sections 210-22(b) and 220-2(b), FPN. 43 VOTE ON PANELACTION: AFFIRMATIVE: 8 NEGATIVE: Lordi, Reign. EXPLANATION OF VOTE: LORDI: Volt-amperes more accurately reflect circuit loading than watts. Watts and volt-amperes are presently indiscriminately mixed in the present Code ( i . e . , Section 220-2(c) listing for outlets uses "volt-amperes" while Exception No. 3 uses "watts"). A SLm=nary of the necessary changes is as follows: Section 2 2 0 - 2 ( c ) Exception No. 3. Change "200 watts" to "200 volt-amperes" Table 220-2(b) Change "Unit Load per Sq. Ft. (Watts)" to "Unit Load per Sq. Ft. (Volt-amperes)" **Change "1 watt per square foot" to "1 volt-ampere per square foot" Section 220-3(d) Change "watts-per-square-foot" to ."volt-amperes-per-square-foot" Section 220-12 Change "200 watts" to "200 volt-amperes" Table 220-11 Change "(wattaqe)" in column t i t l e to "(volt-amperes)" Change "Total Wattage" in "All Others" line to "Total Volt-amperes" Table 220-13 Change "(wattage)" in column t i t l e to "(volt-amperes)" Change "First 10 kW or less" to " f i r s t 10 kVa or less" Change "Remainder over 10 kW at" to "Remainder over 10 kVa at" Section 220-16(a) Change "1500 watts" to "1500 volt-amperes" (2 places) Change "1500 watts" to "1500 vol t-amperes~ 16(b) Log # 866 2- 120 - (220-xx): Reject SUBMITTER: H. Brooke Stauffer, NEMA ITE"~-6]~E:-N-F]~TION: Section 220-xx-Sign or Outline Lighting Load. The load for the circuit required by Section 220-3(x)(x) for signs or outline lighting shall be computed at a minimum of 1200 vol t-amperes. SUBSTANTIATION: Section 600-6(c) requires, in the text of this proposal, the consideration of this load when this specific circuit is required. The submitter believes this text more appropriately belongs within Article 220 than its present location. Companion and correlating proposals have been submitted to Code-Making Panels 2 and 18. PANEL ACTION: Reject. PANEL COM#4ENT: Panel feels this is adequateIy covered in Section 225-10. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Section 220-18 After 5000 watts add "(volt-amperes)" Section 220-19 At the end of the f i r s t chapter add: "KVA shall be considered equiyalent to kW for loads computed under this section" Section 220-30(b)(i) Change"1500 watts" to "1500 volt-amperes" Section 220-39(b)(2) Change"3 watts" to "3 volt-amperes" Table 220-30 In column t i t l e delete "kW or" Change "10 kW" to "10 kVA" Table 220-31 In column t i t l e delete "kW or" Change "SkW" to "8 kVA" Section 220-31 Second paragraph Change "3 watts" to "3 volt-amperes" Change "1500 watts" to "1500 volt-amperes" Log # 230 2- 122 - (220-xx-(New)): Reject SUBMITTER: H. K. Glenn, Pacific Coast Electrical Association, Inc. ~ATION: Section 220-xx - Sign or Outline Lighting Load. The load for the circuit required by Section 220-3(x)(x) for signs or outline]ighting shall be computed at a minimum of 1200 volt-ampereC. SUBSTANTIATION: Section 600-6(c) requires, in the text of this proposal, the consideration of this load when this specific circuit is required. This text more appropriately belongs within Article 220 than its present location. Companion and correlating proposals have been submitted to CME 2 and CMP 18. PANEL ACTION: Reject. PANEL COMMENT: See Panel Action on Proposal 2-120. VOTE ON PANELACTION: UnanimouslyAffirmative. Fourth paragraph Change "First 8 kW" to "First 8 kVA" Change "1500 watts" to "1500 volt-amperes" Change "3 watts" to "3 volt-amperes" Section 220-32(c)(1) Change"1500 watts'~ to "1500 volt-amperes" Section 220-32(c)(2) Change"3 watts" to "3 volt-amperes" Table 220-34 In column t i t l e change "watts" to "volt-amperes" Examples 1 thru 5 Change "watts" to "volt-amperes" and "kW" to "kVA" Log # 1350 2- 121 - (220-X-(New)): Reject SUBMI~ER: Melvin K. Sanders, Ankeny, IA RECOMMENDATION: Add new section: 220-X "Optional Calculation for Non-Dwelling Type Occupancies. For those occupancies where the heating, ventilating and cooling loads are unknown prior to construction, i t shall be permitted where acceptable to the authority having jurisdiction, to provide 8 watts per square foot in the feeder for such loads." SUBSTANTIATION: Manyspeculative shopping centers and proposed multi-purpose tenant buildings are completed before leasing or rental arrangements are complete, and in many instances months may pass before the area(s) are occupied. In order to insure that adequate capacity shall exist in the feeder and service when the equipment is f i n a l l y installed, the provision for 8 watts per square foot figure allows a conservative figure to be used. Using this in conjunction with Table 220-2(b) for general lighting loads and Section 220-13 for non-dwelling receptacle loads, i t would provide adequate capacity. This 8 watts per square foot figure is now being used by designers and in many cases i t is impossible to otherwise know what figures to use. I t is not possible to approve plans in some instances without resorting to Section 90-4 for special permission and involves many discussions with designers as well. This will give help and guidance to inspectors, designers, and contractors. (This proposal should be coordinated with the proposal for a double asterisk note to be used with the 3 watts per square foot now required for stores.) PANEL ACTION: Reject. PANEL COMMENT: Present Code adequately addresses the problem. VOTE ON PANELACTION: Unanimously Affirmative. Log # 2088 2- 123 - (220-2(a)): Reject SUBMITTER: Joseph C. Roohan, Whittier, CA RECOMMENDATION: Delete all reference to "Continuous Load." SUBSIANTIATION: The inclusion of "Continuous Load" and the accompanying derating rules in the National Electrical Code some time ago was a well intended, but unnecessar] refinement in the practical application of the Code. The consideration of "Continuous Load" clearly belongs in electrical handbooks and other designers' guides but not in a safety code. "In Section 90-1(c) i t is stated that "This is not intended as a design specification..." I t is ludicrous to consider an installation safe where i t carries current for slightly less than three hours and unsafe where this time is exceeded. I t is just as ridiculous to consider an installation safe where i t is carrying continuous current and is momentarily interrupted every three hours. The ampacity ratings for conductors in Article 310 are continuous ratings and the derating factors for continuous loads are design considerations to reduce nuisance tripping current breakers that are not temperature compensated where enclosed in panelboards. Nuisance tripping is not generally considered a safety hazard. Other Code articles where changes from watts to volt-amweres should be addressed: Sections 550-5,-11, -22 551-8, -44 600-6(c ) REIGN; The substantiation is correct. The Correlating Committee should appoint a Technical Subcommittee to correlate these changes throughout the Code. 44 Log # 356 2- 128 - (220-2(b)(2)-(New)): Reject SUBMITTER: George Schulz, Sheldon, IA ~ATION: Receptacle Loads. The total allowable load for branch circuits 15 or 20 amperes shall be computed at 1 i / 2 amperes per outlet. Where computed according to this the amperage of the outlets shall not exceed the amperage of the circuit. SUBSTANTIATION: The number of outlets allowed on a branch circuit now is unlimited due to calculating by watts per square foot. I t would be very easy to put an excess number of outlets on i circuit. Limiting each outlet to 1 i / 2 amperes each and calculating the maximum number of outlets by that would help eliminate the possibility of an overload. PANEL ACTION: Reject. PANEL COMMENT: Adequately covered by the Code. VOTE ON PANEL ACTION: Unanimously Affirmative. By deleting the references to "Continuous Load" in the National Electrical Code an important step toward practicality will be achieved allowing inspectors, plan reviewers, and others whose duties consist of evaulating an installation to concern themselves with the safety provided by conductor size, material, insulation, and overcurrent protection. The time element of an installation is an impractical, unenforceable and unrelated element of safety within the referenced sections. PANEL ACTION: Reject. ~ : See Panel CoF~nent for Proposal 2-55. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 219 2- 124 - (220-2(a), Exception No. I ) : Reject Secretary's Note: I t was ~he action of the Correlating Committee that further consideration be given to the comments expressed in the voting. SUBMITTER: John C. Miller, Abolite Lighting, Inc. RECOMMENDATION: Delete Exception No. 1. SUBSTANTIATION: With the increased ampacities of some of the conductors in Tables 310-16 through 310-19 the derating requirements of Note No. 8 to the tables would permit the load to be the same as the branch circuit rating, ie, No. 14 TW = 20 A, 6 conductors in a raceway requires 80 percent derating, 20 X .80 = 16 AMP. Table 310-16 Footnote limits the load to 15 amp, which is the same as the branch circuit rating. This deletion would also bring the requirement in line with Section 384-16(c) which does not have this Exception. PANEL ACTION: Reject. PANEL COMMENT: See Panel Action on Proposal 2-56. VOTE ON PANEL ACTION: Unanimously Affirmative. COMMENTON VOTE: REIGN: See my co~Inent on Proposal 2-56. 2- 129 - (Table 220-2(b)): Accept SUBMITTER: CMP 2 RECOMMENDATION: Change last type of occupancy to: "In any of the above occupancies except one-family dwellings and individual dwelling units of two-family and multifamily dwellings:" etc. SUBSTANTIATION: To reflect Panel's intent in view of Article 100 definition of "Multifamily Dwelling." PANEL ACTION: Accept. VOTE ON PANEL ACTION: UnanimouslyAffirmative. 2- 130 - (Table 220-2(b)): Accept SUBMITTER: CMP 2 R~'-C-OI~'I~ATION: Change asterisk note to: "All receptacle outlets of 20-ampere or less rating in one-family, two-family and multifamily" ---etc. SUBSTANTIATION: To reflect Panel's intent in view of Article 100 definition of "Multifamily Dwelling." PANEL ACTION: Accept. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 1351 2- 125 - (Table 220-2(b)): Reject SUBMII-FER: Melvin K. Sanders, Ankeny, IA RECOMMENDATION: Add a double asterisk note to the row listing stores as requiring 3 watts per square foot: Type of Occupancy Stores Unit load per Sq. Ft (Watts) 3** Log # 466 2- 131 - (220-2(c), Exception No. 5-(New)): Reject SUBMII-FER: Darrell Hazelwood, J. M. Perry Institute RECOMMENDATION: Add a new Exception. Exception No. 5. For motor loads in dwelling units, the branch circuit load for each motor shall be the f u l l load current rating of the motor when those motors operate on a diversity, such as: garbage disposals and water pumps that supply the dwelling units with water. SUBSTANTIATION: I f motor loads, such as disposals, are required ~ ~ u p by 125 percent to Sections 430-22 or 430-24, too large of a service load will be calculated for these motors, particularly in a multifamily dwelling situation. These loads, by their nature of operation and function, are never on for any length of time. Consequently, no increase of the f u l l load current is justified to allow for continuous operation. The "NATIONAL ELECTRICAL CODEHandbook" which the NFPAendorses by the presence of the coupon offering in the front of the 1981 NEC, does not increase the f u l l load current values for i t ' s disposal and water pump's load in a dwelling unit (see page 94, Section 220-17). I f the NFPA does not intend for these loads to be increased by 125 percent, then the Code Sections 220-2(c)(2) should be changed or the endorsed handbook should reflect Section 220-2(c)(2). PANEL ACTION: Reject. PTTNEL COMMENT: Proposal would create a conflict in other sections of the Code. VOTE ON PANEL ACTION: UnanimouslyAffirmative. SUBSTANTIATION: This would allow speculative type store occupancies to use the same allowance as offices for receptacle loads when the total is not known at the time of building. Many stores are b u i l t where the final occupant is unknown and in order to ensure adequate feeder and service capacity, many designers are using rule-of-thumb aids which require the inspecting agency to give special permission and involve Section 90-4. This will give guidance to designers, installers, and inspectors alike. (This proposal should be coordinated with a proposal for a new Section 220-X.) PANEL ACTION: Reject. PANEL COMMENT: Load calculations are adequately covered in • present Code. VOTE ON PANELACTION: Unanimously Affirmative. Log # 668 2- 126 - (Table 220-2(b)): Accept SUBMITTER: Warren H. Cook, IEEE ~ATION: Halls, Corridors, Closets, "Stairways" i/2 (Addition in quotations) SUBSTANTIATION: Stairways are equivalent to halls and corridors. PANEL ACTION: Accept. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 38 2- 127 - (220-2(b), and Exception (New)): Reject SUBMITTER: Dan Leaf, Westlake Village, CA RE-RE-C~~ i M-~--N-~ATION: Revise last sentence as follows: For dwelling unit{s), the computed floor area shall not include open porches, garages, unused or unfinished spaces not adaptable for future u s e nor the areas stipulated in Section 220-3(b)(1). The minimum load for each outlet in these areas shall be as specified in Section 220-2(c). Exception: Outlets installed on circuits specified or permitted by Section 220-3(b)(1) and (2). SUBSTANTIATION: Requires a watts/square foot load for areas served by small appliance branch circuits. I f 3 watts per square f o o t are deemed sufficient for general lighting loads, the areas supplied by small appliance branch circuits (which may be a considerable portion of the total dwelling area) should not be included, In addition, other outlets which may be installed in exterior areas for lawo or 9arden lighting, floodlights, patios, etc., may add considerable load and should be indicated as load which is additional to the watts per square foot load. PANEL ACTION: Reject. ~ : Already covered by the Code. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 20 2- 132 - (220-2(c), Exception Nos. 5 and 6 (New)): Reject SUBMITTER: Dan Leaf, Westlake Village, CA RECOMMENDATION: Change paragraph (c) to: Lighting and Other Loads-All Occupancies. Except when computed as specified in (b) above, the minimum load for each outlet for general-use receptacles, lighting, and other outlets shall be not less than the following, the loads shown being based on nominal branch circuit voltages. Remainder of paragraph (c) to remain the same. Add Exceptions as follows: Exception No. 5: Receptacles specified in the FPN to Table 220-2(b). Exception No. 6: Outlets supplying intermediate or candelabra base l ampholders for decorative lighting may be computed at not less than the volt-ampere rating of the lamp(s). 45 SUBSTANTIATION: No requirement for a minimum load per outlet used for general illumination in non-listed occupancies. The words "other loads" and "NOT used for general illumination" which follow paragraph (b) do not leave Code users with a specific minimum load to be applied to GENEP~ALILLUMINATIONoutlets installed in non-listed occupancies (which do not have a minimum watts-per-square-foot requirement). Further, this proposal will limit the number of outlets installed on a branch circuit when the actual fixture load is not known. The lastsentence of 220-2(d)(1) and (d)(2) which refer back to paragraph (c) is somewhat confusing, because (c) as presently worded, EXCLUDES general illumination outlets. PANEL ACTION: Reject. HANbL CUMMENF: Panel believes t h i s is adequately covered. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . 2- 136 - (220-3(b)(2)): Accept SUBMITTER: CMP 2 ~ATION: Changeparagraph to read as follows: "(2} Countertop receptacle outlets installed in the kitchen shall be supplied by not less than two small appliance branch circuits, either or both of which shall also be permitted to supply receptacle outlets in kitchen and other rooms specified in (b)(1) above. Additional small appliance branch circuits shall be permitted to supply receptacle outlets in kitchen and other rooms specified in (b)(1) above." SUBSTANTIATION: To minimize activation of branch-circuit overcurrent device caused by overload when all kitchen counter receptacles are wired to one circuit. PANEL ACTION: Accept. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 1714 2- 133 - (220-2(c)(5), Exception No.l): Accept SUBMII-[ER: Charles "Mike" Holt, Concepts in Electricity Inc. ~ATION: 220-2(c)(5),Exception No. 1: "Where fixed multi-outlet assemblies are employed, each 5 feet (1.52 m) or fraction thereof of each separate and continuous length shall be considered as one outlet of not less than (1 1/2 ampere)"18OVA" capacity, except in locations where a number of appliances are likely to be used simultaneously, when each 1 foot (305 mm) or fraction thereof shall be considered as an outlet of not less than (1 1/2 ampere) "180VA." The requirements of this section shall not apply to dwelling unit(s) or the guest rooms of hotels or motels. (Deletions in parentheses, additions in quotations.) SUBSTANTIATION: Section 220-2(c)(5) establishes the values at 180VA which is equal to 1 I/2 amps. The above change is necessary for consistency since most load calculations are designated with VA not amps, such as examples to NEC Chapter 9. PANEL ACTION: Accept. VOTE ON PANELACTION: Unanimously Affirmative. LoI # 1454 2~ 137 - (220-3(b), Exception No. 1, Exception No. 2-(New} : Accept SUBMITTER: Leo Witz, Continental Electric Co. Bill Hogan, Chicago, IL Fred Smith, Elgin, II Jim Meehan, New Haven, CT Anton Ganje, North Dakota Kenny Gebert,. Minneapolis, MN B i l l Conrardy, The Conrardy Co. Robert P. Brooks, Chicago, IL Paul Moore, Paducah, KY Les Rinder, Chicago, IL John W. Erickson, Boltswitch, Inc. Homer M. L e f l e r , Chicago, IL RECOMMENDATION: Amend Section 220-3(b) so that the exceptions thereto read as follows: "Exception No. i . A receptacle i n s t a l l e d solely f o r the e l e c t r i c supply to and support of an e l e c t r i c clock in any of the rooms specified above." "Exception No. 2. Outdoor receptacles." SUBSTANTIATION: As the present "Exception" is written i t appears to cover two separate and distinct sets of circumstances. However, grammatically i t does not. I f i t is the intention of CMP 2 that there be two sets of circumstances where the small appliance circuit may supply receptacles other than as stipulated in Section 220-3(b)(i), this proposed wording does the job cleanly and succinctly. There is no need for the additional verbiage concerning the circuits, etc. That is already covered by the Code and does not have to appear in an "exception." This has been the subject of many discussions at various IAEI Chapter meetings during the past year. Since there is only one "exception" the outside receptacles must be supplying clock outlets. Since that really doesn't make sense, we suggest that CMP 2 clean up the wording as indicated so as to eliminate the possibility of future disagreements. PANEL ACTION: Accept. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 628 2- 134 - (220-2(c)(5)-(New) and 220-2(c)(6)): Reject SUBMITTER: R. P. O'Riley, Dallas Joint Electrical Apprenticeship ~ i n g Committee RECOMMENDATION: Existingnumber (5) move down and make i t number (6) but leave i t read as is. "(6) *Other outlets . . . . . . . . . . . . . . . . . . 180 volt-amperes per outlet. Add a new (5) The load for the required branch circuit installed for the supply of exterior signs or outline lighting shall be computed at a minimum of 1200 volt-amperes. This receptacle is not subject to demand factors f o r nondwelling receptacle loads but is a continuous load. SUBSTANTIATION: Number (5) is moved to make room f o r number (6). Section 600-6 requires a receptacle to be i n s t a l l e d f o r outside sign and gives the minimum computed load. This seems to be out of place or hidden in the Code when calculations are being considered. Also due to the f a c t i t has a d i f f e r e n t volt-ampere rating of any other receptacle loads. There is a need f o r the minimum load requirement f o r the required sign o u t l e t to be l i s t e d in A r t i c l e 220 "Branch Circuits and Feeder Calculations" as this is where a l l other calculations s t a r t from. Due to the f a c t the receptacle is l i s t e d at 1200 volt-ampere and has a specific application i t should not be derated with these other receptacles through the demand factors. I f a sign o u t l e t is going to be required, t h i s indicates planned use. I f a sign is plugged into the receptacle, i t w i l l burn for more than three hours continuously. PANEL ACTION: Reject. PANEL COMMENT: Panel feels this is adequately covered in Section 225-10. VOTE ON PANELACTION: Unanimously Affirmative. Log # 1011 2- 138 - (220-3(b)(1)): Reject SUBMITTER: J. H. (Jim) Richards, Maryland Electrical Inspectors ~ o n RECOMMENDATION: Add after dining room "and a general purpose room adjacent to the kitchen." Change Section 220-3(b)(I) to read as follows; (i) In addition to the number of branch circuits determined in accordance with (a) above, two or more 20 ampere small appliance branch circuits shall be provided for all receptacle outlets specified by Section 210-52 for small appliance loads, including refrigeration equipment in the kitchen, pantry, breakfast room, dining room and any general purpose room adjacent to the kitchen or dining area which is used by the family for study, entertainment or general home tasks, in all dwelling units. SUBSTANTIATION: The wording Family Room (which has been removed in the 1981 Code) was never f u l l y defined and the ruling was either ignored or used very restrictively by some inspection authorities. The use of "GENERAL PURPOSEROOMADJACENT TO THE KITCHEN OR DINING AREA USEDBY THE FAMILY FOR STUDY, ENTERTAINMENT OR GENERAL HOMETASKS FULLY DEFINES THIS ROOM." I t is f e l t that a small appliance circuit is needed in such areas. PANEL ACTION: Reject. PANEL COF~MENT: Panel feels this is adequately covered. VOTE ON PANELACTION: UnapimouslyAffirmative. Log # 58 2- 135 - (220-3(b)): Reject SUBMITTER: Dan Leaf, Westlake Village, CA ~ATION: Suggest that the Panel provide a requirement to proportion the load evenly between the two REQUIRED small appliance branch circuits, or limit the floor area that may be served by only one of these required circuits. SUBSTANTIATION: No requirement for evenly proportioned load, or limitation of area served by one of the two required small appliance branch circuits. With no Code requirement to proportion the load evenly between the two required small appliance branch circuits, or to limit the area (square feet) that may be served by one of these circuits, a condition could result in which one of these circuits is serving a square foot area which is larger than that permitted for a 20-ampere general lighting circuit. For example, i f one of the required circuits serves only one receptacle outlet in the kitchen for refrigeration equipment, and the other required circuit serves all other receptacles, in the kitchen and other specified rooms with a combined area greater than 800 square feet, a load capacity may not be provided to equal that required for general lighting circuits. PANEL ACTION: Reject. PANEL COMMENT: No substantiation as to need. Not practical to implement. VOTE ON PANELACTION: UnanimouslyAffirmative. Log # 513 2- 139 - (220-3(b)(1)): Reject SUBMITTER: J. K. Daugherty, Flint, MI RECOMMENDATION: Delete "or more" in the 2nd and 6th lines. SUBSTANTIATION: "or more" should be deleted because: I~ two'20-ampere branch circuits should be sufficient and, with "or more" you have technically disallowed appliances fastened in place that are rated 12-16 amperes (see Section 210-23(a)) because this would require a 20-ampere circuit. 4B PANEL ACTION: Reject. PANEL COM~NT: Panel feels this would not be in the interest of safety. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 1241 2- 144 - (220-3(b)(2)): Reject SUBMITTER: IAEI ~ T I O N : Change Section 220-3(b)(2) to read as follows: Receptacle outlets installed in the kitchen shall be of the split-wired multiple-type receptacle supplied by not less than two small appliance branch circuits, either or both of which shall also be permitted to supply receptacle outlets in the other rooms specified in (1) above. Additional small appliance branch circuits shall be permitted to supply receptacle outlets in such other rooms. Exception: Receptacles rendered inaccessible by appliances occupying dedicated spaces. SUBSTANTIATION: The general public overloads the circuits with heavy kitchen appliances which creates nuisance tripping of circuit breakers. We have found in our area that some contractors and the general public change the breaker to a larger one, which creates a hazardous condition due to overheating of the conductor and receptacles. PANEL ACTION: Reject. PANEL COMMENT: See Panel Proposal 2-136. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 1860 2- 140 - (220-3(b)(i)): Reject SUBMITTER: H. Brooke Stauffer, NEMA RECOMMENDATION: Delete "including refrigeration equipment" in the fourth line. SUBSTANTIATION: With the proliferation and increased usage of kitchen counter-top appliances, the capacity of the small lappliance branch circuits is often f u l l y utilized. There are frequent instances where the simultaneous usage of counter-top appliances and the starting current of a refrigerator on the same branch circuit has caused the branch-circuit overcurrent device to operate. Removing the refrigeration equipment from the small appliance branch circuits will provide needed capacity on these circuits for supplying the counter-top appliances for which they were originally intended. PANEL ACTION: Reject. ~ i See Panel Action for Proposai 2-37. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 64 2- 145 - (220-3(c)): Reject SUBMII-FER: Lawrence H. Chapman, Chapman Electric" RECOMMENDATION: (c) Laundry Branch Circuits -- Dwelling Unit. In addition to the number of branch circuits determined in accordance with (a) and (b) above, at least one additional 20-ampere branch circuit shall be provided to supply the receptacle outlet(s) required by Section 210-52(e). A lighting load of 300 watts or less for the laundry area controlled by a wall switch will be permitted on this br~nch c i r c u i t . This circuit shall have no other outlets. SUBSTANTIATION: Section 220-3(c) as i t now stands without allowing for minimum lighting, especially in remote laundry areas, both creates an unnecessary, arbitrary hardship upon the electrician and a hazardous situation when the resident attempts to obtain lighting by using a plug in extension or tap for a lamp next to laundry tubs. A permanently mounted light fixture controlled by a light switch is certainly safer than plug in lamps which are in the proximity of laundry tubs, or plumbing outlets to a washing machine. The electrician in complying with 210-52(e) and 220-3(c) by installing the separate 20-ampere branch laundry c i r c u i t has computed loading of 1500 watts from 220-16(b) to wit: 1500 watts + 300 watts (lighting load) = 1800 watts, and 1800 watts x 1.25 = 2250 watts (calculated minimum capacity for conductor capacity. The electrician has calculated that up to even 1920 watts at 120 volts is a permissible safe loading easily permitting a 300 watt lighting load on the laundry branch c i r c u i t , to wit: 1920 watts x 1.25 = 2400 watts and, 20 Amperes x 120 volts = 2400 watts. In the past there have been local jurisdictions which allowed such a lighting outlet on the laundry branch circuit in these cases without any overloading problems being caused by the lighting load. To prohibit the small lighting load on this branch c i r c u i t would seem that the NATIONAL ELECTRICAL CODE is r e a l l y placing an a r b i t r a r y and capricious r e s t r i c t i o n upon the working e l e c t r i c a l contractor which can not be j u s t i f i e d by the ultimate test of increasing e l e c t r i c a l safety. In f a c t , by not allowing a small l i g h t i n g load in the laundry area, in cases i n v o l v i n g a remote laundry area; a hazard has a c t u a l l y been created should the resident s t a r t to tap in l i g h t i n g f i x t u r e s from m u l t i - t a p extension cords when no l i g h t has been i n s t a l l e d by the e l e c t r i c a l contractor because the Code would not allow a permanent small l i g h t and wall switch to be loaded onto the laundry c i r c u i t . Furthermore, even with the l i g h t i n g w r i t t e n into the 220-3(c) Code language proposed above there w i l l s t i l l b'e unused capacity of 6-1/4 percentum in t h i s laundry branch c i r c u i t to w i t : 2400 watts - 2250 watts = 150 watts and, 150 : .0625 (%) Log # 2084 2- 141 - (220-3(b)(1)): Reject SUBMITTER: Tom Tombarello, Paul Revere Chapter IAEI ~ATION: Delete the words "including refrigeration equipment" from Section 220-3(b)(1) fourth line. SUBSTANTIATION: This new addition would relieve some of the load that is presently permitted on the "two or more" circuits provided for small appliances. Also, i f accepted, changes in calculations would be necessary in Examples of Chapter 9. PANEL ACTION: Reject. PANEL COM~IENT: See Panel Action for Proposal 2-37. VOTE ON PANEL ACTION: Unanimously Affirmative. \ Log # 39 2- 142 - (220-3(b)(1) Exception): Reject SUBMITTER: Dan Leaf, Westlake V i l l a g e , CA R~E'~]~E']~R~ATION: Revise as follows: Receptacles i n s t a l l e d solely f o r the e l e c t r i c supply and support of e l e c t r i c clocks in any of these stipulated rooms, or AN outdoor receptacle o u t l e t MAY be supplied by a small appliance branch circuit. SUBSTANTIATION: May be i n t e r p r e t e d to p r o h i b i t an individual branch c i r c u i t f o r outdoor receptacle, or the i n s t a l l a t i o n of more than one clock o u t l e t . Present wording may be interpreted to l i m i t clock o u t l e t s to one, and to preclude an individual branch c i r c u i t f o r outdoor receptacles. I t does not l i m i t the number of outdoor.receptacle o u t l e t s which may be i n s t a l l e d , such as in gardens, lawn areas, e t c . , which may supply permanent loads which are cord- and plug-connected, which may c o n s t i t u t e substantial load. PANEL ACTION: Reject. PANEL COMMENT: Present wording r e f l e c t s Panel intent not to l i m i t the clock and outdoor receptacle o u t l e t s to one. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . Log # 430 2- 143 - (220-3(b)(2)): Reject SUBMITTER: Southwestern Section IAEI ~ATION: ChangeSection 220-3(b)(2) to read as follows: Receptacle outlets installed in the kitchen shall be of the split yoke multiple type receptacle supplied by not less than two small appliance branch circuits, either or both of which shall also be permitted to supply receptacle outlets in the other rooms specified in (1) above. Additional small appliance branch circuits shall be permitted to supply receptacle outlets in such other rooms. Exception: Receptacles rendered inaccessible by appliances occupying dedicated spaces. SUBSTANTIATION: The general public overloads the circuits with heavy kitchen appliances which creates nuisance tripping of circuit breakers. We have found in our area that some contractors and the general public change the breaker to a larger one, which creates a hazardous condition due to overheating of the conductor and receptacles. PANEL ACTION: Reject. PANEL COMMENT: The wiring method in the proposal is more restrictive than the Panel intent. See Panel Proposal 2-136. VOTE ON PANEL ACTION: Unanimously Affirmative. PANEL ACTION: Reject. PANEL COMMENT: Proposal would defeat the Panel intent of retaining the laundry c i r c u i t as a dedicated c i r c u i t . VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . Log # 669 2- 146 - (220-3(d)): Reject SUBMITTER: Warren H. Cook, IEEE RECOMMENDATION: Add at end of paragraph: "Panelboard branch-c~rcuit overcurrent device space shall be included to serve the calculated load." (Change in quotations) SUBSTANTIATION: Capacity to the panelboard but not used f o r the connected load should be r e a d i l y available f o r future additions. PANEL ACTION: Reject. PANEL COM~IENT: The present wording requires that panelboard branch-circuit overcurrent device space be included to serve the calculated load. VOTE ON PANEL ACTION: UnanimouslyAffirmative. 47 Log # 1286, 1903 2- 147 - (220-3(e)-(New)): Reject SUBMITTER: IAEI (1286) "~iro/P. Van Putten, Michigan Chapter IAEI (1903) RECOMMENDATION: To end of Section 220-3 add: (e) Space Heating Equipment (Other Than Electric Heat). ( i ) At least one ( i ) individual branch c i r c u i t of not less than 15 ampere capacity shall be installed for the heating equipment. (2) Only those motors which are an integral part of the heating equipment shall be permitted to be connected to the c i r c u i t required by Section 220-3(e)(i). SUBSTANTIATION: To assure continuity of heat in the dwelling, this heating equipment shall be divorced from other c i r c u i t s . PANEL ACTION: Reject. PANEL COMMENT: Substantiation does net j u s t i f y proposal requ~ rements. VOTE ON PANELACTION: AFFIRMATIVE: 9 NEGATIVE: Bowling. EXPLANATION OF VOTE: BOWLING: Would provide c i r c u i t for furnace controls with assurance that i t would not be overloaded with other equipment. Leg # 2089 2- 151 - (220-10(b)): Reject SUBMITTER: Joseph C. Roohan, Whittier, CA ~ATION: Delete all reference to "Continuous Load." SUBSTANTIATION: The inclusion of "Continuous Load" and the accompanying derating rules in the National Electrical Code some time ago was a well intended, but unnecessary refinement in the practical application of the Code. The consideration of "Continuous Load" clearly belongs in electrical handbooks and other designers' guides but not in a safety code. "In Section 90-1(c) i t is stated that "This is not intended as a design specification..." I t is ludicrous to consider an installation safe where i t carries current for slightly less than three hours and unsafe where this time is exceeded. I t is just as ridiculous to consider an installation safe where i t is carrying continuous current and is momentarily interrupted every three hours. The ampacity ratings for conductors in Article 310 are continuous ratings and the derating factors for continuous loads are design considerations to reduce nuisance tripping current breakers that are not temperature compensated where enclosed in panelboards. Nuisance tripping is not .generally considered a safety hazard. By deleting the references to "Continuous Load" in the Nation~ Electrical Code an important step toward practicality will be achieved allowing inspectors, plan reviewers, and others whose duties consist of evaluating an installation to concern themselves with the safety provided by conductor size, material, insulation, and overcurrent protection. The time element of an installation is an impractical, unenforceable and unrelated element of safety within the referenced sections. PANEL ACTION: Reject. PANEL COMMENT: See Panel Comment for Proposal 2-55. VOTE ON PANELACTION: Unanimously Affirmative. Log # 867 2- 148 - (220-3(x)(x)): Reject SUBMII-FER: H. Brooke Stauffer, NEMA ~ATION: Section 220-3(x)(x). Each commercial building and each commercial occupancy with ground floor footage accessible to pedestrians shall be provided, at an accessible location outside the occupancy, with at least one outlet for sign or outline lighting use. This outlet shall be supplied by an individual 20 ampere-branch circuit. Exception: Interior hallways or corridors shall not be considered outside the occupancy. SUBSTANTIATION: Section 660-6(b) requires, in the text of this proposal, the circuit and outlet for such a purpose. Article 220 and specifically, Section 220-3, addresses "Branch C,ircuits Required." The submitter believes this text more appropriately belongs within Article 220 than its present location. Companion and correlating proposals have been submitted to Code Making Panels 2 and 18. PANEL ACTION: Reject. PANEL COMMENT: Panel feels this is adequately covered in Sections 225-10 and 600-6. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 710 2- 152 - (Table 220-11): Reject SUBMITTER: Donald M. Maston, Copper Development Association Inc. RECOMMENDATION: Change "next 20,001 to 100,000 at" To: ';from 20,001 to 100,000 at" SUBSTANTIATION: As presently worded, the statements are confusing. The proposed change will c l a r i f y this and make these statements consistent with a similar statement in Table 220-34. PANEL ACTION: Reject. PANEL COMMENT: Present wording expresses the intent of the Panel, VOTE ON PANELACTION: AFFIRMATIVE: 9 NEGATIVE: Schuck. EXPLANATION OF VOTE: SCHUCK: Agree with the proposer that the present wording is confusing because i t is inconsistent with the obvious intent of the Panel. Log # 229 2- 149 - (220-3(x)(x)-(New)): Reject SUBMITTER: H . K . Glenn, Pacific Coast E l e c t r i c a l Association, Inc. ]T~-(~-~-~ATION: Each commercial building and each commercial occupancy with ground f l o o r footage accessible to pedestrians shall be provided, at an accessible location outside the occupancy, with at least one o u t l e t for sign or outline lighting use. This o u t l e t shall be supplied by an individual 20-ampere branch c i r c u i t . SUBSTANTIATION: Section 600-6(b) requires, in the t e x t of this proposal, the c i r c u i t and o u t l e t f o r such a purpose. A r t i c l e 220 and s p e c i f i c a l l y , Section 220-3, addresses "Branch Circuits Required." This text more appropriately belongs within A r t i c l e 220 than i t s present location. Companion and correlating proposals have been submitted to CMP 2 and CMP 18. PANEL ACTION: Reject. PANEL COMMENT: See Panel Comment f o r Proposal 2-148. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 709 2- 153 - (Table 220-11): Reject SUBMITTER: Donald M. Maston, Copper Development Association Inc. RECOMMENDATION: Change "next 3001 to 120,000 at" To: "from 3001 to 120,000 at" SUBSTANTIATION: As presently worded, the statements are confusing. The proposed change will c l a r i f y this and make these statements consistent with a similar statement in Table 220-34. PANEL ACTION: Reject. PANEL COMMENT: Present w~rding expresses the intent of the Panel. VOTE ON PANEL ACTION: AFFIRMATIVE: 9 NEGATIVE: Schuck. EXPLANATION OF VOTE: SCHUCK: Samecomment as on Proposal 2-152. Log # 1698 2- 150 - (220-10(b)): Reject SUBMITTER: Charles "Mike" Holt, Concepts in Electricity Inc. RECOMMENDATION: Add fine print note: "Does not apply to the grounded conductor. (See Section 220-22. )" SUBSTANTIATION: 220-I0(b) sometimes referred to by some Inspectors which requires that the grounded conductor be sized as a feeder conductor. This will identify that continuous loads do not affect the grounded conductor. PANEL ACTION: Reject. PANEL COMMENT: Panel feels that the proposal could be misinterpreted and lead to erroneous computations. VOTE ON PANELACTION: Unanimously Affirmative. Log # 1920 2- 154 - (220-15, Exception No. 3-(New)): Reject Secretary's Note: I t was the action of the Correlating Committee that further consideration be given to the comments expressed in the negative voting. SUBMITTER: Mark Shapiro/Richard Emmons, Michigan Chapter IAEI ~TION: Add a new Exception as follows: Exception No. 3: The service or feeder conductors shall not be smaller than the branch circuit conductors. SUBSTANTIATION: Article 220, Section 220-15 and Article 424, Section 424-3(b) as presently written i t is possible to have a smaller feeder to fixed electric space heating equipment than the required branch circuit; especially i f the feeder is not supplying other loads. PANEL ACTION: Reject. PANEL COMMENT: See Panel Comment for Proposal 2-115. VOTE ON PANELACTION: AFFIRMATIVE: 9 NEGATIVE: Reign. 4B EXPLANATION OF VOTE: RLIGN: The substantiation appears to be correct. Section 220-15 says feeders to fixed elecric space heating are to be computed using 100 percent of the connected load while Section 424-3(b) says branch circuits supplying fixed electric space heating shall not be less than 125 percent of the total load. Based on the above, i t is conceivable that a branch circuit could be larger than the feeder. This proposal should be accepted in principle, but rather than add Exception No. 3 as proposed, a semicolon should be inserted at the end of the f i r s t sentence and the following words added: "however in no case shall a feeder load current rating be less than the rating of the largest branch circuit supplied." The Panel added these exact words to Section 220-20 in the 1981 Code when i t was pointed out by Proposal 162 in the 1981TCR that a similar situation existed in this section. SUBSTANTIATION: The wording in Part B of Article 220 makes i t unclear that the feeder demand factors listed in Part B of Article 220 also apply to service-entrance conductors. The only way to determine that the listed feeder demand factors apply to service-entrance conductors is to draw that conclusion by looking at the examples in Chapter 9. Even then the words "main feeder" and "feeder" found in Examples 1, l ( a ) , l(b), 1(c), 3, 4, and 4(a) should not be used to describe the service-entrance conductors. Article 100 has specific definitions for these two conductor types. The words "feeder" and "service-entrance conductor" are not interchangable. PANEL ACTION: Reject. PANEL COMMENT: Panel feels this is adequately covered in Section 230-41. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 499 2- 159 - (220-18, Exception-(New)): Accept in Principle SUBMITTER: Ernest E. Cannon, Tempe, AZ RECOMMENDATION: Add an Exception to read: Exception: In multifamily dwelling units where constructed provisions are made for dryers which preclude the later installation of larger capacity and ampacity dryers, the branch circuit ampacity and the load calculations may use the nameplate date of the dryer. (shall be permitted in place of may?) SUBSTANTIATION: A new generation of residential dryers and washer-dryers has been developed specifically for the compact apartment developer. These units have a load requirement some 60 percent of the NEC normal requirement. The Exception permits further economies in the construction of multifamily units without having an adverse affect. One such unit combines the washer and dryer and operates under a nameplate designation of 3000 watts at 240 volts. (For the normal large multifamily installation on 120/208 volt supply, the heating element rating is reduced so that this rating is correspondingly lower). These units are all sub-compact, that is, physically they occupy less space. The intent of the Exception should be to require that partitions be b u i l t to "preclude" installing f u l l size units. PANEL ACTION: Accept in Principle. PANEL COMMENT: See Panel Proposal 2-160. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 1662 2- 155 - (220-15(b)-(New)): Reject SUBMITTER: Charles "Mike" Holt, Concepts in Electricity Inc. RECOMMENDATION: Add new section as follows: , 220-15(b) Air conditioning equipment load shall be computed in accordance with Sections 440-32, 440-33, and 440-34. SUBSTANTIATION: Sections 440-32, -33, -34 indicate how to size conductors with air conditioning equipment. There are no sections in Article 220 which reference these sections of Article 440. I t would provide logical reference for sizing the feeder conductor for air conditioning equipment. • PANEL ACTION: Reject. PANEL COMMENT: Already covered in Section 210-2. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 1828 2- 156 - (220-16(b)): Reject SUBMITTER: Paul E. Phelan, Trade Education Inc. and New Hampshire ~ l Contractors Inc. RECOMMENDATION: Last sentence changed to read: " I t shall be permissible to include this load with the general lighting load and "subject i t " to the demand factors provided in Section 220-11." SUBSTANTIATION: Readability. The present form doesn't mean anything. PANEL ACTION: Reject. PANEL COMMENT: Panel feels that the present wording is understandable. VOTE ON PANEL ACTION: AFFIRMATIVE: 9 NEGATIVE: Schuck. EXPLANATION OF VOTE: SCHUCK: Agree with submitter. 2- 160 - (220-18, Exception): Accept Secretary's Note: I t was the action of the Correlating Committee that further consideration be given to the comments expressed in the negative voting. SUBMITTER: C~ 2 ~ATION: In multifamily dwelling units, where provisions are made for dryers which preclude the later installation of larger capacity dryers, the nameplate rating of the dryers to be installed shall be permitted to be used. SUBSTANTIATION: See Panel Comment for Proposal 2-161. PANEL ACTION: Accept. VOTE ON PANEL ACTION: AFFIRMATIVE: 9 NEGATIVE: Cunningham. EXPLANATION OF VOTE: CUNNINGFLAM: This proposed exception indicates that dryers with lower ratings will have their feeder size calculated by using the actual nameplate ratings and the demand factors in Table 220-18. Table 220-18 was developed from extensive u t i l i t y test data using conventional dryers with ratings close to 5000 watts. There is no test data supporting demand factors for dryers with lower ratings. (The Panel was discussing 3 kW units.) The use of nameplate data for smaller units should be permitted without using the demand factors in Table 220-18. The total of the connected loads of smaller units without a demand factor or the diversified load of 5000 watt units, whichever is smaller, should be permitted. The Pane] Comment should have been referenced to Proposal 2-159 instead of 2-161. Log # 1684 2- 157 - (220-17): Accept in Part SUBMITTER: Charles "Mike" Holt, Concepts in Electricity Inc. RECOW~MENDATION: 220-17. (Fixed Appliance) Load - Dwelling Unit(s). I t shall be permissible to apply a demand factor of 75 percent to the nameplate-rating load of four or more appliances fastened in place served by the same feeder in a one-family, two-family, or multifamily dwelling. The term "fixed appliance" should be changed to whichever of the following terms would be most appropriate: "Permanently connected appliance" "Cord- and plug-connected appliance" "Fastened in place appliance" "Located to be on a specific current" (Deleted material in parentheses, added material in quotations). SUBSTANTIATION: For consistency, the term "fixed appliance" should be removed and other appropriate phrase should be used. Since the 1981 Code removed the words "fixed appliances" from Article 100, possibly the words of Section 220-32(c)(3) could better identify its intent. PANEL ACTION: Accept in Part. Revise Section 220-17 t i t l e as follows: Delete "Fixed" PANEL COMMENT: The term "f'ixed" is confusing and is no longer defined in Article 100 - Definitions. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 629 2- 161 - (Table 220-19, Note 5, FPN-(New) and Examples, Chapter 9, Example No. 9-(New)): Accept in Part SUBMITTER: R. P. O'Riley, Dallas Joint Electrical Apprenticeship Training Committee RECOMMENDATION: Add Fine Print Note after Note (5) of Table 220-19 to read: "See Example No. 9 Chapter 9 for application of notes to Table 220-19" Add to Chapter 9 Example No. 9 which will be applications of the various notes. Log # 468 2- 158 - (Article 220, Part B): Reject SUBMITTER: Darrell Hazelwood, J. M. Perry Institute ~ATION: Where the wording in Part "B" of Article 220 mentions "feeders," the wording should also include the words "and service-entrance conductors." Example No. 9 Table 220-19 COLUMN A Two ranges equal ratings less than 12 kW Two ranges from Col A = 11 kW feeder demand 49 Table 220-19 COLUMNA Two ranges unequal, over 8 kW but not over 12 kW The feeder demand shall not be less than the sum of the largest two kitchen equipment loads. SUBSTANTIATION: Using a term such as "other kitchen equipment" permits the use of all loads not s p e c i f i c a l l y exempted. The feeder being only required to be as large as the largest branch c i r c u i t would at times allow an overloaded feeder. Manywork areas have a bank of heat lamps that are on continuously and they need total nameplate with no d i v e r s i t y . Example - 20 kW quick recovery water heater; 5 kW f r y e r ; 4 heat lamps at 250 watts each - total 26 kW at 65 percent = 16.9. Largest branch c i r c u i t would be No. 6 cu at 60 amperes. Heater and f r y e r would require 69 amperes assuming a 120/208 v o l t supply. PANEL ACTION: Accept. VOTE ON PANEL ACTION: AFFIRMATIVE: 9 NEGATIVE: Reign. EXPLANATION OF VOTE: REIGN: I could accept t h i s proposal i f the second paragraph was deleted. The requirement f o r the feeder being only as large as the sum of the largest two kitchen equipment loads could lead to an undersized feeder. Example: 4 kW booster heater; 3 kW f r y e r ; and four 2 kW food warmers - 15 kW total x 65% demand factor = 9.75 kW ÷ 208V = 46.9 amperes or a 50 ampere feeder. The largest two loads would be 4 kW + 3 kW : 7 kW ÷ 208 = 33.7 amperes or a 35 ampere feeder. Treat as two ranges under 12 kW Two ranges from Col A = 11 kW feeder demand Table 220-19 Note 3 COLUMN C Three cooking appliances 2 1/2 kW each (less than 3 kW) From Col B demand factor f o r 3 units less than 3 1/2 kW = 70% 2.5 kW X 3 units X 70% = 13.2 kW feeder load Table 220-19 COLUMN A 28 apartments each have a 12 kW range From Col A 26 - 30 ranges = 15 + 1 f o r each range 15 kW + 28 units X 1 kW = 15 kW = 43 kW feeder load Table 220-19 COLUMNA 50 unit multifamily dwelling with 12 kW range in each unit From Col A 41 to 50 ranges = 25 kW + 3/4 per range 25 kW +50 X 3/4 kW = 62.5 kW feeder demand Table 220-19 COLUMNA Note 1 20 unit multifamily dwelling with a 15.5 KE range in each unit Ranges over 12 kWI 6% per kW in excess of 12 kW 15.5 kW rating - 2 kW listed = 3.5 kW over 12 kW 3.5 use next larger 04 4kW 5% per kW excess = 4kW X 5% = 20% From Col A 20 ranges ~ 35 kW X 120% = 42 kW feeder demand Log # 1242 2- 164 - (220-20): Accept SUBMITTER: IAEI RECOF~MENDATION: Revise Section 220-20 as follows: Kitchen Equipment - Other than Dwelling Unit(s). I t shall be permissible to compute the load f o r commercial e l e c t r i c cooking equipment, dishwasher booster heaters, water heaters, and other kitchen equipment in accordance with Table 220-20. These demand factors may be applied to all equipment rated 2 kW and larger which has either thermostatic control or intermittent use as kitchen equipment. They shall not apply to space heating, ventilating or air-conditioning equipment. The feeder demand shall not be less than the sum of the largest two kitchen equipment loads. SUBSTANTIATION: Using a term such as "other kitchen equipment" permits the use of all loads not s p e c i f i c a l l y exempted. The feeder being only required to be as large as the largest branch c i r c u i t would at times allow an overloaded feeder. Manywork areas have a bank of heat lamps that are on continuously and they need total nameplate with no d i v e r s i t y . Example - 20 kW quick recovery water heater; 5 kW f r y e r ; 4 heat lamps at 250 watts each - total 26 kW at 65 percent = 16.9. Largest branch c i r c u i t would be No. 6 copper at 60 amperes. Heater and f r y e r would require 69 amperes assuming a 120/208 v o l t supply. PANEL ACTION: Accept. VOTE ON PANEL ACTION: AFFIRMATIVE: 9 NEGATIVE: Reign. EXPLANATION OF VOTE: REIGN: See my comment on Proposal 2-163. Table 220-19 COLUMNA Note 2 Three 10 kW ranges, three 12 kW ranges, and three 14 kW ranges to be installed in a multifamily dwelling unit. Ranges of unequal rating average then increase in: three ranges @ 10 kW (12 kW shall be used ) X 3 : 36 kW three ranges @ 12 kW X 3 = 36 kW three ranges @ 14 kW X 3 = 42 kW Total kW =114 kW 114 kW divided by 9 units = 12.67 average or 13 kW each 13 kW exceeds 12 by 1 - increase by 1 X 5% or 5% From Col A 9 units = 24 kW 24 kW X 105% = 25.2 kW feeder demand Table 200-19 Note 4 COLU~ A A dwelling unit i n s t a l l a t i o n 3 kW oven, 12 kW range, and 8 kW b r o i l e r all on the same branch c i r c u i t and feeder. Add all together and treat as one range 3 kW + 12 kW + 8kW = 23 kW From Col A one range = 8 kW Note i - Over 12 kW increase 5% per kW in excess of 12 23 kW - 12 kW : 11 kW increase 11 kW X 5% = 55% 8 kW X 155% = 12.4 kW feeder load SUBSTANTIATION: Application of the notes to Table 220-19 are often misunderstood and misused. Fine print note is to l e t i t be known that the notes are i l l u s t r a t e d with an example in Chapter 9. By adding the Examples i t w i l l help c l a r i f y the intent and the applications of Table 220-19. PANEL ACTION: Accept in Part. Add Fine Print Note to Section 220-19 to read as follows: "See Examples, Chapter 9." PANEL COF~MENT: Enclosed information is explained in the Examples. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 72 2- 165 - (220-22): Accept SUBMITTER: Dan Leaf, Westlake Village, CA RECO#LMENDATION: Delete the word "connected" in the second sentence and substitute the words "net computed." S~STANTIATION: Does not correlate with examples of neutral calculations in Chapter 9, and may require neutral conductors larger than ungrounded conductors in many cases. Connected load is generally interpreted as a computed, or nameplate rating load, before application of any demand factors. Examples of neutral conductor calculations in Chapter 9 apply demand factors to computed loads other than cooking appliances. Literally interpreted, this section would require a feeder neutral larger than the ungrounded conductors in many cases. For example: a balanced 120/240 volt receptacle load of 30 KW; this section requires the neutral load to be computed at 125 amperes. The ungrounded conductors may be sized f o r a net computed load of 20 KW (per Sec. 220-13), or 83 amperes. I t seems reasonable to permit a reduction in size of the neutral based on the allowable demand factors wi~ich may be applied to the load. PANEL ACTION: Accept. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 1692 2- 162 - (Table 220-19): Reject SUBMITTER: Charles "Mike" Holt, Concepts in E l e c t r i c i t y Inc. ITE~C~PRE'I~I)ATION: Table 220-19. Heading "Demand loads f o r household e l e c t r i c ranges, wall-mounted ovens, counter-mounted cooking units, and other household cooking appliances over 1 3/4 kW rating. Column A to be used in all cases except as otherwise permittea in Note 3(below)." SUBSTANTIATION: In handbook and paperback editions of the NEC, Note 3, is not printed below this table and therefore the word "below" should be removed. PANEL ACTION: Reject. PANEL COMMENT: Already covered in the Code. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 431 2- 163 - (220-20): Accept SUBMITTER: Southwestern Section IAEI RECOMMENDATION: Revise Section 220-20. Kitchen Equipment - Other than Dwelling Unit(s). I t shall be permissible to compute the load f o r commercial e l e c t r i c cooking equipment, dishwasher booster heaters, water heaters, and other kitchen equipment in accordance with Table 220-20. These demand factors may be applied to all equipment rated 2 kW and larger which has either thermostatic control or intermittent use as kitchen equipment. They shall not apply to space heating, ventilating or air-cbnditioning equipment. Log # 255 2- 166 - (220-22): Reject SUBMITTER: C. E. Muhleman, Marion, IN RECOM--~-'-N-DATION: Amend the last sentence in the f i r s t paragraph of Section 220-22 to read: There shall be no reduction of the neutral capacity f o r lighting loads. 50 SUBSTANTIATION: This would preclude any problems developing when a single-phasing condition happened to any type of l i g h t i n g system. And single-phasing is preferrable to having a l l the l i g h t s go out in a building. Instead o f stating that the neutral of discharge l i g h t i n g feeders shall be f u l l size; the Code should state that a l l l i g h t i n g feeders must have f u l l - s i z e neutrals. Otherwise, should single-phasing occur, the neutral would be too small to handle the current. I t is c e r t a i n l y desirable to keep on as much of the normal l i g h t i n g system, yes, even 1/3, which w i l l provide more i l l u m i n a t i o n than the emergency l ! g h t i n g system. 00 ;i}::::{x00 IOOA '1 3 SUBSTANTIATION: There is presently no mechanism that allows such a reduction f o r clothes dryers as there is f o r e l e c t r i c ranges. Yet the t y p i c a l clothes dryer uses the neutral only f o r a f r a c t i o n a l HP motor and a small timer. The 5000 watt requirement of Section 220-18 should not apply to the neutral and i f i t does hot, i t should so state. PANEL ACTION: Accept in P r i n c i p l e . PANEL COMMENT: See Panel Proposal 2-171. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . ;I 2- 171 - (220-22): Accept SUBMII~ER: Chip 2 ~ T I O N : Change 3rd sentence as f o l l o w s : For a feeder supplying household e l e c t r i c ranges, wall-mounted ovens, counter-mounted cooking u n i t s , and e l e c t r i c dryers the maximum unbalanced load shall be considered as 70 percent of the load on the ungrounded conductors, as determined in accordance with Table 220-19 f o r ranges and Table 220-18 f o r dryers. SUBSTANTIATION: To allow reasonable derating of a neutral f o r dryers as is allowed f o r ranges. PANEL ACTION: Accept. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . COMMENT ON VOTE: YERKE: Add "3-wire dc or single-phase ac" before " e l e c t r i c dryers." This is needed to point out that the neutral reduction does not apply to 115-volt dryer i n s t a l l a t i o n s wherein there is no b u i l t - i n d i v e r s i t y f a c t o r such as exists on e l e c t r i c ranges, etc. ,1. IOOA -~ OA * * --~200--A - - Fault at 'X' PANEL ACTION: Reject. PANLL COMMENT: Already required by f i r s t 220-22. sentence of Section Log # 1837 2- 172 - (220-22): Reject SUBMITTER: Paul E. Phelan, Trade Education Inc. and New Hampshire ~ I Contractors Inc. RECOMMENDATION: Possible change of last sentence to read: "There shall be no reduction of the neutral capacity f o r that portion of the load which consists of electric-discharge l i g h t i n g , data processing equipment, or s i m i l a r equipment supplied from a 4-wire 3-phase wye system. SUBSTANTIATION: T i e - i n with note lO(c) to the Tables 310-16 through 310-19. Is this harmonic problem prevalent on ac single-phase systems? I took the time to measure (with a hook-on ammeter) the neutral current on a job I did with a balanced load of fluoresent f i x t u r e s on a single-phase 3-wire system having approximately 180 amps on each ungrounded conductor and we measured only six (6) amperes on the neutral. There was no apparent neutral heating. I f this is also a single-phase problem, Note lO(c) should so state. I f i t is "not" a single-phase problem, Section 220-22 should so read. PANEL ACTION: Reject. PANEL COMMENT: Lack of s u f f i c i e n t data to support proposal. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . Log # 1198 2- 167 - (220-22): Reject SUBMII~ER: Olaf G. Ferm, Ferm's Fast Finder Index RECOMMENDATION: The last sentence of the paragraph should be changed to read: There shall be no reduction of the neutral capacity f o r that portion of the load which consists of electric-discharge l i g h t i n g , data processing, or s i m i l a r equipment where there are harmonic currents present in the neutral conductor. SUBSTANTIATION: This w i l l correlate Section 220-22 with Note lO(c) under Notes to Table 310-16 through 310-19 which had the words data processing, or s i m i l a r equipment added to the 1981 Code. PANEL ACTION: Reject. HANbL CUMMENT: There is a reduced size neutral f o r neutral current over 200 amperes except electric-discharge l i g h t i n g . VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . Log # 1688 2- 168 - (220-22): Reject SUBMITTER: Charles "Mike" Holt, Concepts in E l e c t r i c i t y Inc. ~ATION: Add last sentence: "The grounded conductor shall not be required to be increased in size f o r continuous loads." SUBSTANTIATION: This is the intent of the Code at the present time but many people are reading 220-i0(b) and r e f e r r i n g to feeder conductors as grounded conductors also, and therefore requiring the grounded conductor to be increased f o r continuous loads. PANEL ACTION: Reject. PANEL COMMENT: On a 2-wire c i r c u i t , a neutral conductor shouid not be reduced. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . Log # 1738 2- 173 - (220-22): Reject SUBMITTER: Charles "Mike" Holt, Concepts in E l e c t r i c i t y Inc. RECOMMENDATION: 220-22. Feeder "Grounded Conductor" Load. The feeder (neutral) "grounded conductor" load shall be the maximum unbalance of the load determined by this a r t i c l e . The maximum unbalanced load shall be the maximum connected load between the neutral grounded conductor and any one ungrounded conductor, except that the l o a d . . . " Change a l l references from neutral to grounded conductor. SUBSTANTIATION: Throughout the Code the neutral conductor is referred to as the grounded conductor. By changing the word neutral to grounded conductor, i t would provide an easier t r a n s i t i o n knowing which conductor is being referred to. PANEL ACTION: Reject. PANEL COMMENT: Neutral conductors are not always grounded and grounded conductors are not always neutral conductors. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . Log # 1830 2- 169 - (220-22): Reject SUBMITTER: Paul E. Phelan, Trade Education Inc. and New Hampshire ~ I Contractors Inc. RECOMMENDATION: Rewrite t h i s paragraph in a subtopic form such as a, b, c, etc. or as a series of exceptions to the general rule s t a r t i n g at the word "except" on line 4. SUBSTANTIATION: Readability. There is too much information here to be presented as an essay. PANEL ACTION: Reject. PANEL COMMENT: Panel is unclear as to how proposed t e x t is to be written. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . Log # 02 2- 174 - (220-23 (New)): Reject Secretary's Note: This proposal is f o r a revision of the 1978 edition but was received a f t e r the deadline f o r proposals. SUBMITTER: E.A. Bartsch, J r . , Bible Engineering Corporation RECOMMENDATION: Add new Section as f o l l o w s : 220-23 Loads Served by a Transformer. (a) Single Transformer: The load served by a transformer shall be computed as 125 percent of the rated current of the transformer rated 600 volts and below, or as 150 percent of the rated current o f the transformer rated above 600 v o l t s , in place of summarizing the unit loads. (b) M u l t i p l e Transformers and Other Loa'ds: Conductors supplying one or more transformers and other loads shall have ampacity s u f f i c i e n t f o r the sum o f : ( i ) The ampacity required by Section 220-23 (a) f o r the transformer with the largest r a t i n g . Log # 1833 2- 170 - (220-22): Accept in P r i n c i p l e SUBMITTER: Paul E. Phelan, Trade Education Inc. and New Hampshire ~ l Contractors Inc. RECOMMENDATION: Add to this section a reasonable derating of the neutral conductor f o r feeders supplying one or more household or commercial e l e c t r i c clothes dryers. 51 l~I 00 percent rated current for all other transformers. Other loads in accordance with Section 430-25. Exception: The ampacity may not be less than that required by Section 450-3. SUBSTANTIATION: Here is a proposal for a new paragraph for the 1981 NATIONAL ELECTRICAL CODEto c l a r i f y the handling of loads that are served by transformers and the feeder sizing for these loads. The 1978 NATIONAL ELECTRICAL CODE, Article 220, in simple terms; requires feeders sized, as a minimum, to handle 125 percent of the long term loads and the largest motor, plus 100 percent of the other load. Article 450, requires overcurrent protection for the transformer at certain maximums. Except for control and special use transformers, transformers are a i00 percent rated device with short time overload capabilities. (Roughly similar to motor ratings.) Transformers, conductors and overcurrent devices come in discrete size increments which are poorly related to each other. Thus, i t frequently happens in our experience, that Article 220 requires large sized conductors for primary and secondary connections to the transformer and for the bus of the panelboards, both feeding the primary and fed by the secondary, which are protected by overcurrent devices which are smaller than the conductor ampacity. On the other hand, selection of a larger transformer would allow part of its capacity to be unused i f conductors based upon the load are properly protected. This paragraph therefore, attempts to recognize that a transformer is a " f i l t e r " to the electrical system just as a motor is to the mechanical load, consequently should be recognized as such and not ignored by the Code in this matter and the loads served by a transformer should lose their identity. Further, that the conductors and busses surrounding the transformer are sized to the transformer rating and not to its calculated secondary load. We realize f u l l well that this is contrary to the long standing tradition in the Codes of sizing services based upon the unit loads. PANEL ACTION: Reject. PANEL COMMENT: Load should determine size of transformer. VOTE ON PANELACTION: Unanimously Affirmative. Log # 1726 2- 177 - (220-31): Accept SUBMITTER: Charles "Mike" Holt, Concepts in Electricity Inc. RECOMMENDATION: 220-31. Optional Calculation for Additional Loads in Existing Dwelling Unit. For an existing dwelling unit presently being served by an existing 120/240 volt or 208Y/120, 3-wire, (60-ampere service) i t shall be permissible to compute load calculations as follows: Delete 60-ampere service. SUBSTANTIATION: The use of the optional method really cannot be used by this stringent requirement that i t be limited to 60-amp existing services. I t should apply to all services. PANEL ACTION: Accept. VOTE ON PANELACTION: UnanimouslyAffirmative. Log # 505 2- 178 - (220-31): Accept SUBMITTER: Joseph E. McCann, City of Coral Springs, FL RECOMMENDATION: Section 220-31 - Optional Calculation for Additional Loads in Existing Dwelling Units. For an existing dwelling unit presently being served by an existing 120/240 or ,208Y/120, (delete "60-ampere service") i t shall be pemissible to compute load calculation as follows~ SUBSTANTIATION: In reading Section 220-31 optional calculations for additional load in existing dwelling's units i t states for 120/240 volt or 208Y/120 3~wire, "60-ampere service" i t shall be permissible to compute the load as follows: I notice that Section 220-31 directs attention only to "60-ampere services" and not to any other. What about additional loads on existing 100 ampere, 150, etc?, Does Section 220-35 optional calculations for additional loads to existing installations apply to dwelling units? PANEL ACTION: Accept. VOTE ON PANELACTION: UnanimouslyAffirmative. Log # 1715 2- 179 - (Table 220-34): Reject SUBMITTER: Charles "Mike" Holt, Concepts in Electricity Inc. -RIL'C'O-~/~E~T(~TION: Table 220-34 Connected load up to and including 3, (plus) 100 Connected load over 3 and including 20, (plus) 75 Connected load over 20 at 25 SUBSTANTIATION: Eliminate words "plus" as i t is understood that these would be added and the words cause confusion. PANEL ACTION: Reject. PANEL COMMENT: Present wording more clearly reflects Panel intent. VOTE ON PANELACTION: Unanimously Affirmative. Log # 1709 2- 175 - (220-30(b)(3)): Accept in Principle SUBMITTER: Charles "Mike" Holt, Concepts in Electricity Inc. RECOI~MENDATION: 220-30(b)(3). "The nameplate rating of all (fixed) appliances, ranges, wall-mounted ovens, counter-mounted cooking units, and including four or more separately controlled space heating units." Change the word "fixed" to include whichever of the following terms is appropriate: "Permanently connected appliance" "Fastened in place appliance" "Cord and plug connected appliance" "Located to be on a specific circuit" SUBSTANTIATION: For consistency, the term "fixed" should be removed and other appropriate phrase should be used. PANEL ACTION: Accept in Principle. PANEL COMMENT: Revise Section 220-30(b)(3) as follows: "The nameplate of all "fastened in place" appliances, etc." VOTE ON PANELACTION: Unanimously Affirmative. Log # 170 2- 180 - (220-36-(New)): Reject SUBMITTER: Alexander M. Stevens, A. M. Stevens and Assoc. RECOMMENDATION: That service entrance section sizing on structures which are repetitive in,nature such as restaurant franchises be governed by demand history of the average of at least three other identical installations in the geographical area. SUBSTANTIATION: For the most part I have been forced by code considerations to specify 1,000 amperes and even 1,200 amperes service for McDonald's Hamburger restaurants. During cursory checks of these restaurants I have never run across a demand running higher than 600 Amperes. When remodeling occurs, one is permitted to base service entrance sizes on the demand history of the existing structure. A repeatedl~ built franchise operation is even more predictable than a remodellng operation. PANEL ACTION: Reject. PANEL COMMENT: Not justified by the Substantiation. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 1718 2- 176 - (220-30(c)(4)): Accept SUBMITTER: Charles "Mike" Holt, Concepts in Electricity Inc. ~ATION: Delete Section 220-30(c)(4). SUBSTANTIATION: Delete Section 220-30(c)(4) because the heading states that the largest of ( c ) ( I ) , (c)(2), (c)(3) and (c)(4) is to be used in determining the air conditioning or heating load for optional calculations. (c)(4) creates confTicts and confusion because 220-30(b)(3) also states four or more separately controlled space heating units. PANEL ACTION: Accept. VOTE ON PANEL ACTION: AFFIRMATIVE: 8 NEGATIVE: Cunningham, Reign. COMMENTON VOTE: YERKE: By deleting "(4) the connected load of four or more separately..." from Section 220-30c, i t does not become subject to the application of Section 220-21. As i t reads, air conditioning would always have to be included when there are four or more separately controlled space heating units. EXPLANATION OF VOTE: CUNNINGHAM: The Panel appointed a Task Group with Robert J. Cunningham as chairman with members David Brown, Anthony Lordi, ahd Thomas Sparling. We are to recommend action on Proposals 2-176, 2-177, 2-178 which propose revisions of Sections 220-30 and 220-31 and the examples. Possible action that can be taken by the Task Force and the Panel at the next meeting could be to revise Sections 220-30 and 220-31 or perhaps to delete Section 220-30(c) altogether because Table 220-30 already covers this material. REIGN: My notes indicate the Panel appointed a Task Group consisting of Cunningham (Chairman), Brown~ Lordi and Sparling to investigate and recommend action on this proposal. 52 SUBSTANTIATION: The problem with the original proposal, as stated by the pane-~-~[~-,was that i t contained primarily design requirements. The specific design specification therefore, have them eliminated and the only "design requirements" remaining are those required for the protection of electricians maintaining or repairing electrical systems within the enclosure or for the protection of conductors. These "design requirements" are consistent with other Sections of the NEC which establish design c r i t e r i a for these purposes. The problem with the present NEC, in relation to this type of enclosure, is that i t does not specifically recognize i t as an approved wiring method. Section 110-8 wiring method states, "only wiring methods recognized as suitable are included in this Code." Article 370 makes no mention of this type of enclosure nor the conditions or environment in which i t is installed. Consequently, there are no minimum standards to provide for workman safety. Working in a manhole is hazardous at best and i f the conductors have not been installed to provide a working area or there are ungrounded metal parts i t can be deadly.. Furthermore, the conductors in manholes and handholes which have restricted work space and dimensions will be subject to damage by workmen standing on them or working in the confined space. PANEL ACTION: Reject. ~NTCL~T: The Panel feels that i t is impractical to include speC~Ci-c details which will cover all design contingencies for all areas of the country. The Code is not intended to be a design manual. VOTE ON PANEL ACTION: Unanimously Affirmative. ARTICLE 225 -- OUTSIDE BRANCHCIRCUITS AND FEEDERS Log #125 4- 1 - (Article 225): Reject Secretary's Note: This Comment (No. 70-66, CMP 2) on Proposal No. 194 was for the 1981 Code and was held for further study. See NEC-TCD-1980 Annual Meeting. The following was the Secretary's Note with this comment. "The Correlating Committee agrees with the Panel's original comment that this is primarily a design consideration and does not feel a Technical Subcommittee is necessary." SUBMITTER: R. S. Pinkerton, Electrical Code Advisory Committee for City of Los Angeles. RECOI~IENDATION: The following revised proposal is intended to answer the Panel's objection by deleting design requirements. In following revision, the new words and sentences are in captial letters and the deleted wording is struck out. B. Manholes and Handholes 225-40. Scope. The provisions of Section 225-40 through 225-43 apply to the construction and installation of manholes and handholes CONSTRUCTED OF CONCRETE, MASONRYOR OTHER SUITABLE CORROSION-RESISTANT MATERIAL. For the purpose of these provisions a manhole is a chamber in an underground conduit system containing working space large enough for a person to enter. A handhole is a permanent opening in an underground conduit system, an enclosure smaller than a manhole, with a removable top and used in lieu of an approved pull or junction box. The handhole shall be so designed that the conductors may be pulled, spliced or otherwise handled without requiring a person to enter the enclosure. 225-41. Manholes. (a) Manholes shall be constructed in accordance with all Municipal and State Codes and in accordance with the following: 1. Inside measurements shall be not less than 4 feet between the side walls thereof, or i f circular in shape not less than 4 feet in diameter inside measurement and not less than 5 feet at all points between the floor and the top or ceiling. 2. Any access opening to outer air shall be not less than 26 inches i f circular in shape, or not less than 24 X 26 inches clear measurement i f rectangular in shape. 3. Floors shall be of concrete, stone, brick or similar material not subject to decomposition. (b) Manholes shall be installed only in permanently accessible locations outside the exterior perimeter wall of buildings. Exception: Manholes may be installed inside of buildings by special permission. (c) Conduits shall enter AND BE TERMINATED in the manhole in a manner consistent with the type of wiring method used and in accordance with the following: 1. Conduits shall enter the enclosure through the walls and be terminated in a manner that provides suitable protection for the type of wiring method used. 2. Direct burial conductors shall enter the enclosure by means of conduit nipples which shall be suitably sealed. (d)' Means For draining the enclosure shall be.provided where practical. (e) Suitable wall supports or racks shall be provided to secure open conductors in a fixed position 2 inches or more above the floor. (f) Different systems including high and low voltage systems, may be installed in a manhole where separated satisfactorily to the enforcing authority. 225-42. Handholes. (a) HANDHOLESSHALL HAVEwalls ~nd floors of handholes shall be of concrete having a minimum thickness of 6 inches with dimensions not less than set Forth in Article 370 and the following: 1. The minimum depth shall be 18 inches; and 2. The width shall be not less than half the depth. Exception: Prefabricated concrete boxes (or other suitable material) and their covers that are designed for the purpose, with wall thickness less than set forth in the foregoing may be used as handholes where satisfactory to the enforcing authority. (b) Covers for handholes shall be f u l l opening and be of carbon steel floor plate or equal with a minimum thickness of 1/4 inch except where prefabricated boxes are permitted by other provisions of this Section. (b) Handholes shall be installed only in permanently accessible locations outside the exterior perimeter walls of buildings except by special permission. (c) HANDHOLESAND THEIR where exposed to vehicular t r a f f i c , the enclosure and its related covers shall be specifically designed for the LOCATION AND LOADS TO BE I~OSED, INCLUDINGVEHICULAR TRAFFIC. (d) Conduits may enter a handhole through the lower wall or bottom of the enclosure and shall be terminated in a manner consistent with the type of wiring method used. (e) Conductors shall be so arranged or secured so they maintain a position 2 inches or more above the bottom of the handhole. 225-43. Grounding in Manholes and Handholes. Exposed noncurrent-carrying metal parts of equipment, conductor supports or racks, conduits and other metal appurtenances including any metal cover and its supporting ring shall be bonded together and connected to a common ground. The size of the grounding means shall be as prescribed in Section 250-95 except that where run exposed, the grounding conductor shall be not smaller than No. 8. Log # 14 4- 2 - (Article 225, Part A, Part B (New)): Reject SUBMITTER: C.F. Pernick, City of Los Angeles, CA RECOMMENDATION: Add below the heading for Article 225 the word ~ f - p ~ e f - T x e d with a Capitol A and add a Part B to read: B. Manholes and Handholes 225-40 Scope. The provisions of Section 225-40 through 225-43 apply to the installation of manholes and handholes. For the purpose of these provisions a manhole is a chamber in an underground conduit system containing working space large enough for a person to enter. A handhole is a permanent opening in an underground conduit system, an enclosure smaller than a manhole, with a removable top and used in lieu of an approved pull or junction box. The handhole shall be so designed that the conductors may be pulled, spliced or otherwise handled without requiring a person to enter the enclosure. 225-41 Manholes. (a) Manholes shall comply with all Municipal and State Codes and shall be in accordance with the Following: (1) Inside measurements shall be not less than four feet between the side walls ther~Jf, or i f circular in shape not less than four feet in diameter inside measurement and not less than five feet at all points between th~ floor and the top or ceiling. (2) Any access opening to outer air shall be not less than 26 inches i f circular in shape, or not less than 24 X 26 inches clear measurement i f rectangular in shape. (3) Floors shall be of concrete, stone brick or similar material not subject to decomposition. (b) Manholes shall be installed only in permanently accessible locations outside the exterior perimeter wall of buildings. Exception: By special permission, manholes may be installed inside of buildings. (c) Conduits shall enter the manhole in a manner consistent with the type of wiring method used and in accordance with the following: (1) ~onduits entering the enclosure shall be terminated not less than two inches from the bottom or one foot from the tqp. (2) Conduits shall enter the enclosure through the walls and be terminated in a manner that provides suitable protection for the type of wiring method used. (3) Direct burial conductors shall enter the enclosure by means of c)nduit nipples ~hich shall be suitably sealed. (d) Means For draining the enclosure shall be provided where practical. (e) Suitable wall supports or racks shall be provided to secure open conductors in a fixed position two inches or more above the floor. (f) Different systems including high and low voltage systems, may be installed in a manhole where separated satisfactory to the enforcing authority. 225-42 Handholes. (a) Walls and Floors of handholes shall be of concrete having a minimum thickness of six inches with dimensions not less than set forth in Article 370 and the following: {1) The minimum depth shall be 13 ilches; and (2) The width shall b~ not les than half the depth. Exception: By special permission, prefabricated concrete boxes (or other suitable material) and t h e i r covers that are designed f o r ti~e purpose, with wall thickness less than set f o r t h in the Foregoing may be used as handholes. (b) Covers f o r handholes shall be f u l l opening and be of carbon steel f l o o r plate or equal with a minimum thickness of 1/4 inch except where prefabricated boxes are permitted by other provisions of this section. 53 (c) Handholes shall be installed only in permanently accessible locations outside the exterior perimeter walls of buildings. Exception: By special permission, handholes.may be installed in buildings. Where exposed to vehicular t r a f f i c , the enclosure and its related cover shall be s p e c i f i c a l l y designed for the purpose. (d) Conduits may enter a handhole through the lower wall or bottom of the enclosure and shall be terminated in a manner consistent with the type of wiring method used. (e) Conductors shall be so arranged or secured so they maintain a position two in. or more above the bottom of the handhole. 225-43 Grounding in Manholes and Handholes. Exposed noncurrent-carrying metal parts of equipment, conductor supports or racks, conduits and other metal appurtenences including any metal cover and its supporting ring sha]! be bonded together and connected to a common ground. The size of the grounding means shall be as prescribed in Section 250-95 except that where run exposed,'the grounding conductor shall be not smaller than No. 8. SUBSTANTIATION: Although i l is a common trade practice to install concrete manholes ~nd handholes in outdoor underground conduit systems, i t is not s p e c i f i c a l l y recognized by the NATIONAL ELECTRICAL CODE. Properly designed manholes and handholes are safe and meet the intent and purposes of the NATIONAL ELECTRICAL CODE, however, boxes which are improperly designed ,nay o f f e r an unsafe and hazardous work condition and greatly increases the chance for an electrical f a i l u r e . The proposed requirements for manholes and handholes are practical and reasonable and provide for reasonable safety. These requirements have been in effect for many years in the state of California with notable success in providing for workman safety and safety for the system. PANEL ACTION: Reject. COMMENT: See Panel Comment for Proposal 4-1. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 231 4- 5 - (225-XX:(New)): Reject SUBMITTER: H. K. Glenn, Pacific Coast Electrical Association, Inc. RECOMMENDATION: New 225-XX t i t l e to be: Manholes, Handholes and Underground Pull Boxes. Section 225 XX Scope: The provisions of Section 225 XX through 225 XXXXX apply to the i n s t a l l a t i o n of manholes, handholes and underground pull boxes. Definitions: Manhole: A manhole means a chamber in an underground system containing working space large enough for a person to enter, which provides space and access f o r i n s t a l l a t i o n and maintenance of cables, transfonners, or other equi~nent or apparatus. Pull Box: A box with a blank cover into which worktnen may reach but not enter, which is inserted in one or more runs of raceway to f a c i l i t a t e pulling, joining, supporting or inspecting conductors. The term "Pull Box" includes but is not limited to junction boxes, splice boxes, conductor support boxes, inspection boxes and handholes. Section 225 XXX Manholes Manholes shall comply with the following requirements: 1. Inside measurements shall be not less than Four feet beLween the side walls thereof, or i f circular in shape not less than four feet in diameter inside measurement and not less than f i v e feet at all points between the f l o o r and the top or ceiling. 2. Any access opening to outer air shall be not less than 24 X 26 inches clear measurement i f rectangular in shape. 3. Floors shall be of concrete, stone brick or similar material not subject to decomposition. 4. Manholes shall be installed only in permanently accessible locations. 5. Conduits entering the enclosure shall be terminated not less than two (2) inches from the bottom or one foot from the top. 6. Direct burial conductors shall enter the enclosure by means of conduit sleeve or bushing which shall be suitably sealed. 7. Means for draining the enclosure shall be provided where practical. 8. Suitable wall support or racks attached to the wall(s) shall be provided to secure open conductors in a fixed position two (2) inches or more above the floor. 9. Different systems including high and low voltage systems shall be physically separated. 225 XXXX Handholes and Underground Pull Boxes i . Walls and floors of handholes and pull boxes shall be of concrete or other suitable material, with covers that are designed for the purpose. 2. Covers for handholes and pull boxes shall be f u l l opening, and shall be of the t r a f f i c type when exposed to vehicular t r a f f i c . 3. Handholes shall be installed only in permanently accessible locations. 4. Conductors shall be arranged or secured so they maintain a position two (2) inches or more above the bott~n of tile handhole. 225XXXXX Grounding in Manholes, Handholes and Pull Boxes Exposed noncurrent-carrying metal parts of equipment, conductor supports or racks, conduits and other metal appurtenances including any metal cover and its supporting ring shall be bonded together and connected to a common ground. Tile size of the grounding means shall be as prescribed in Section 260-96 except that where run exposed, the grounding conductor shall be not smaller than No. 8 cubic. SU_BSTANTIATION: Although i t is a cow,non trade practice to install concrete manholes, handholes and underground pull boxes in outdoor underground conduit systems, i t is not specifically recognized by the NATIONAL ELECTRICAL CODE. Properly designed manholes and handholes are safe and meet tile intent and purposes of the NATIONAL ELECTRICAL CODE. However, boxes wi~ich are improperly designed may o f f e r an unsafe and hazardous work condition and greatly increases the chance for electrical f a i l u r e . The proposed requirements for manholes and handholes are practical and reasonable and provide for reasonable safety. PANEL ACTION: Reject. ~CTTO-M]~rEq~T: See Panel Comment for Proposal 4-1. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 1632 4- 3 - (Articles 225, 230, 240): Reject SUBMITTER: Allen KnicKrehm, Los Angeles, CA RECOMMENDATION: Delete the word "approved" when used to mean the use of alternate method(s) or materials. SUBSTANTIATION: The NEC is incorporated in most construction contract documents by reference. Therefore, the authority having j u r i s d i c t i o n - the owner or the owner's representative, will not be the third party qualified person contemplated by the Code-Making Panel. Section 90-4 covers the case for governmental bodies exercising legal j u r i s d i c t i o n . PANEL ACTION: Reject. PANEL COMMENT: The Panel believes that the term "approved" as used in these articles is proper and necessary in many instances. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 2055 4- 4 - (Articles 225, 230, 240): Reject Secretary's Note: The Correlating Committee feels that this proposal is editorial in nature and that i t is unnecessary to repeat information already in the Code. I t was the action of the Correlating Committee that this proposal be reported as "Reject" as i t is not within the scope of CMP 4. SUBMITTER: Ivan P. Nordstrand, Consumers Power Company RECOMMENDATION: Propose each a r t i c l e have the Panel designation A r t i c l e 90 - Introduction (Panel No. 1) A r t i c l e 100 - Definitions (Panel No. 1) A r t i c l e 110 - Requirements f o r Electric Installations (Panel No. i) A r t i c l e 200 - Use and I d e n t i f i c a t i o n of Grounded Conductors (Panel No. 5) Article 210 - Branch Circuits (Panel No. 2) Etc. SUBSTANTIATION: The present format of the published Code book makes i t d i f f i c u l t and time consuming to determine the appropriate Panel responsible for the article in which a problem is developing. The addition of one line in parentheses under the a r t i c l e number giving the Panel designation will quickly provide the proper source. PANEL ACTION: Accept. VOTE ON PANEL ACTION: AFFIRMATIVE: 14 NEGATIVE: Kassebaum. EXPLANATION OF VOTE: ~ A - L I i ~ E - - I - t ' 5 " f 6 k this proposal is the editorial responsibility of the Correlating Committee. Log # 1686 4- 6 - (225-6(b)): Reject SUBMITTER: Charles "Mike" Holt, Concepts in E l e c t r i c i t y Inc. RECOMMENDATION: Removefine print definition for Festoon lighting ~ g - ' 6 " ( ~ ) ' - a n d replace i t in A r t i c l e 100. SUBSTANTIATION: The fine print notes definitions are being used r--h-ro-u-ghout t the Code as in Section 430-71. There are definitions in front of the chapters as in Section 680-4, as well as those included in Article 100. For those not fmniliar with the Code, i t is confusing to determine where a definition may be found. Definitions should either be placed in A r t i c l e 100, or i f they cause a c o n f l i c t with other sections, should be included in the front of the section where they would be applicable. PANEL ACTION: Reject. I~N]~'-C--COM}4E'NT: The Panel feels that the definition is sLill required in Article 225. See Panel Proposal 4-7. VOTE ON PANEL ACTION: Unanimously Affirmative. 54 a. accept the o r i g i n a l proposal and add the f i r s t paragraph of Section 230-24 which gives the basis f o r these clearances or, b. rewrite Section 225-18 as follows: Clearance from Ground. Conductors of not over 600 volts, nominal shall have the minimum clearances f o r service conductors as given in Section 230-24. 4- 7 - (225-6(b), FPN): Accept SUBMITTER: Cf~) 4 RECOMMENDATION: Change the f i n e p r i n t note of d e f i n i t i o n to f u l l text. SUBSTANTIATION: I t is the Panel's intent to make the d e f i n i t i o n a part of the Code, rather than a recommendation. PANEL ACTION: Accept. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . Log # 55 4- 8 - (225-6(b), FPN): Accept SUBMII-FER: Dan Leaf, Westlake V i l l a g e , CA ~R~ATION: Revise f i n e p r i n t note as follows: See Section 225-24 f o r outdoor lampholders. SUBSTANTIATION: E d i t o r i a l . Fine P r i n t Note appears to refer to {ncorrect section. Section 225-25 refers to location of outdoor lamps, Section 225-24 refers to outdoor l ampholders. PANEL ACTION: Accept. I/'O=FE'-qJN-TANCL ACTION: Unanimously A f f i r m a t i v e . Log # 582 4- 9 - (225-14(d)): Reject Secretary's Note: The Correlating Committee directs C ~ ' s 4 and 16 to achieve c o r r e l a t i o n . SUBMITTER: Ralph H. Lee, Lee E l e c t r i c a l Engineering, Inc. ]TE'-C-O-~E'-NDATION: Delete the following: "Power Conductors below Communications Conductors - 30 inches." SUBSTANTIATION: For coordination with proposal to change Section ~ r , ( - a ' ) - ~ t - o - - e l i m i n a t e power conductor placement below communications conductors. PANEL ACTION: Reject. PANEL COMMENT: We feel that climbing space requirements are necessary. I t is not always possible to eliminate power conductors under communication conductors at a pole. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . Log # 1769 4- 12 - (225-19(a), T i t l e ) : Accept SUBMIIq-ER: Louis M i r a g l i a , Paul Revere Chapter IAEI RECOMMENDATION: Change t i t l e from "Over Roofs" to "Above Roofs." ~NTI-ATI~: The term "Above Roofs" is consistent with requirements in Exceptions to Section 225-19 and also would be consistent with Section 230-24. PANEL ACTION: Accept. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . Log # 806 4- 13 - (225-19(a), Exception No. 5): Accept in Principle SUBMII-TER: Robert A. Jutstrom, Westborough, MA ITE'~TION: Change Exception No. 5 to be the same as Section 2J6%26(a-~, Exception No. 2. SUBSTANTIATION: Correlation required. PANEL ACTION: Accept in P r i n c i p l e . 1 Delete "service-drop" and replace with the word " t h e . " PANEL COMMENT: Section 225-19(a) is limited to outside branch cir--~uq-ts" and" feeders. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . Log # 1176 4- 14 - (225-19(d), 225-19(d), Exception-(New)): Accept SUBMI~ER: M. F. 8 o r l e i s , EEl RECOMMENDATION: Delete second paragraph and substitute the ~i'ng-E'x-ception: Exception: Conductors run above the top level of a window shall be permitted to be less than the three (3) feet (914 mm) requirement above. SU3STANTIATION: This change is f o r clariFicati~)n and ta be ~{stent with the s t y l e manu~l gf the NEC. The basic rule in three (3) Feet (g14 mm) so as to be out of reach fro.n windows, doors, porches, f i r e escapes, etc. The Exception is f o r any conductors run above window openings which are considered out of reach. A corresponding proposal has been submitted for Section 230-24(c). PANEL ACTION: Accept. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . Log # 380 4- I0 - (225-18): Reject SUBMII-FER: Gary Lensch, Sheldon, IA RECOF~IENDATION: 20 feet (6.10 m) on land traversed by machinery used f o r c u l t i v a t i n g , ~razing, f o r e s t , and orchard, or where subject to truck t r a f f l c . SUBSTANTIATION: Due to the use of larger machinery I believe that ~wires are needed to prevent e l e c t r i c a l shocks. PANEL ACTION: Reject. COMMENT: The requirements in t h i s section are minimum clearances. Special circumstances require special design considerations. The 20 f e e t would c o n f l i c t with the National E l e c t r i c a l Safety Code. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . L~-O-C-K: I think (914 mm) should be (9.14 m). STANBACK: For e d i t o r i a l improvement, exception should read "Conductors run above the top level of a window." Log # 1196 4- 15 - (225-20): Reject SUBMII-FER: Olaf G. Ferm, Ferm's Fast Finder Index RECOMMENDATION: Change the wording to read: Mechanical protection of conductors on buildings, structures, or poles shall be provided where exposed to physical damage. Where underground conductors emerge Fro,1 the earth they shall be protected against physical damage in accordance with Section 300-5. Conductors specified in Table 310-13 shall only be permitted to be i n s t a l l e d where part of a recognized wiring method of Chapter 3. SUBSTAN~F[ATIO____.~N: In i t s present wording Section 225-20 only refers to Section 230-50. When one reads Section 230-50(b) i t is worded in a manner that r e s t r i c t s many acceptable wiring'methods f o r branch c i r c u i t s and feeders unless i n s t a l l e d 10 feet or more above grade. PANEL ACTION: Reject. F A ~ T : Already covered in Sections 225-20, 225-23 and 225-28. VOTE ON PANEL ACTION: AFFIRMATIVE: 14 NEGATIVE: Muska. COM~4ENT ON VOTE: STANBACK: Panel Comment reference to Section 225-28 should be Section 225-18. EXPLANATION OF VOTE:' MUSKA: Underground outdoor feeder and branch-circuit wiring should be in ~onformity ~ith Section 300-5 which covers underground i n s t a l l a t i o n s . I t should not be in conformity to the more r e s t r i c t i v e requirements of A r t i c l e 230 on services. Log # 804 4- 11 - (225-18): Accept in P r i n c i p l e SUBMII-FER: Robert A. Jutstrom, Westborough, MA RECOMMENDATION: Change wording to be the same as Section 230-24~for v e r t i c a l clearance to ground. SUBSTANTIATION: Correlation of the two Sections is required. PANEL ACTION: Accept i n P r i n c i p l e . Revise the 3rd, 4th and 5th paragraphs to read as follows: 12 f e e t (3.66 m) -- f o r those areas l i s t e d in the 15-foot (4.57 m) c l a s s i f i c a t i o n when the voltage is limited to 300 v o l t s to ground. 15 feet (4.57 m) -- over r e s i d e n t i a l property and driveways, and those commercial areas not subject to truck t r a f f i c . 18 feet (5.49 m) -- over public streets, a l l e y s , roads, parking areas subject to truck t r a f f i c , driveways on other than r e s i d e n t i a l property, and other land traversed by vehicles such as c u l t i v a t e d , grazing, f o r e s t , and orchard. PANEL COMMENT: The lO-foot clearance requirements in Section 230-24(b) s p e c i f i c a l l y refers to service entrances and service-drop cables. VOTE ON PANEL ACTION: AFFIRMATIVEi 14 NEGATIVE: Bowles. EXPLANATION OF VOTE: BOWLES: Although I agree with Robert Jutstrom that correlation is needed, I disagree with the Panel Action and Comment. CMP 4, in i t s Panel Comment, indicates that i t did not include the lO-foot category from Section 230-24(b) because i t refers s p e c i f i c a l l y to service entrances and service-drop cables. There are other sections in A r t i c l e 225 {Sections 225-11, 225-15, 225-16, 225-17) that refer to sections in A r t i c l e 230 which s p e c i f i c a l l y mention sedvices, service drops, or service entrances. Triplex cable should be permitted f o r outside branch c i r c u i t s and feeders with the same clearance provision as when the t r i p l e x is used as service drop conductor. I recommend that CMP 4 either: 55 ARTICLE 230 -- SERVICES 4- 19 - (230-2): Reject Log # 1618 SUBMITTER: Richard B. Boyd, Jr., E l l i s Cannady Chapter, IAEI RECON~MENDATION: Delete words "by only one service" and add "from only one serv-Tce point" in the f i r s t sentence. SUBSTANTIATION: To c l a r i f y what we understand to be the CMP's intent. Other related changes may be desirable. PANEL ACTION: Reject. PANEL COMMENT: The intent of the Panel is to allow only one service. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 643 4- 16 - (230-XX-(New)): Reject SUBMITTER: Robert C. Mierendorf, Square D Company RECOMMENDATION: Add a new Section 230-XX as follows: Surge Arresters (Lightning Arresters) f@r Services of less than 1000 volts. Surge arresters connected and installed in accordance with the requirements of A r t i c l e 280 shall be placed on'each ungrounded conductor on the load side of the service equipment. Exception: Where surge arresters are connected and installed on the secondary side of the distribution transformer which supplies the service and located within 300 feet of the building or structure served. SUBSTANTIATION: At the present time insulation coordination ~outdoor e l e c t r i c a l systems exists as f a r as electrical u t i l i t y practice is concerned. I t does not exist, however, f o r e l e c t r i c a l systems within buildings except by chance, depending upon the impedance of the c i r c u i t s and the connected or disconnected loads. As a result, transient overvoltages caused by lightning strokes in the v i c i n i t y of power lines or switching surges orginiating from u t i l i t y or other sources are l i k e l y to impinge onto the service conductors to buildings and propagate throughout the building e l e c t r i c a l system. Insulation coordination within a building or structure can only be achieved i f transient overvoltages are controlled to specified levels. The essential starting point f o r a controlled overvoltage "situation is at the service entrance, and this can be accomplished by i n s t a l l a t i o n of secondary surge arresters at this location. Surge arresters installed on the secondary side of a distribution transformer and located within 300 feet of the building or structure served are considered to provide similar transient overvoltage protection. Secondary surge arresters are readily available having ratings suitable for 120/240, 600 and 1000 v o l t services. The cost of i n s t a l l a t i o n is offset by the reduction of probability of undesired incidents of loss of equipment such as e l e c t r i c motors, television sets, smoke detectors, home computer terminals and the like due to overvoltage stresses. In addition, safety of persons and property is enhanced since the risk of overvoltage causing flashover with the p o s s i b i l i t y of power follow-current is substantially reduced. PANEL ACTION: Reject. PANEL COMMENT: Insufficient data to make this a mandatory requirement. VOTE ON PANEL ACTION: AFFIRMATIVE: 14 NECV~TIVE: Edwards. EXPLANATION OF VOTE: EDWARDS: With the increased use of consumer electronics, i t is believed that further study of this proposal is j u s t i f i e d . Log # 1455 4- 20 - (230-2): Reject SUBMITTER: Leo Witz, Continental Electric Co. B i l l Hogan, Chicago, IL Fred Smith, Elgin, IL Jim Meehan, New Haven, CT B i l l Conrardy, The Conrardy Co. Robert P. Brooks, Chicago, IL Paul Moore, Paducah, KY Les Rinder, Chicago, IL John W. Erickson, Boltswitch, Inc. Homer M. Lefler, Chicago, IL RECOMMENDATION:. Amend Section 230-2 so as to read as follows: "230-2. Number of Services. Two or more services shall be permitted to serve one building or structure under any of the following conditions: (a) Where one of the services supplies a f i r e pump. (b) Where a separate service is required to supply an emergency system. (c) By special permission, in multiple-occupancy buildings where there is no readily accessible location or space for the service equipment necessary f o r all the occupants of the building. (d) Where the required service capacity is in excess of 3000 amperes at 600 volts or less. (e) Where the service capacity is greater than that which can be served by the serving agency. (Proposers' co~nent: "serving agency" could just as well be "the u t i l i t y supply company"). ( f ) By special permission, in buildings of large area, either vertical or horizontal. (g) Where the d i f f e r e n t services have different electrical characteristics such as voltage, phases or frequency. (h) Where the services supply different types of loads or uses that require a d i f f e r e n t rate structure from the serving u t i l i t y . In each such i n s t a l l a t i o n a permanent plaque or directory, of such size and c l a r i t y so as to be readily and immediately obvious to all persons to whom such knowledge is of some importance, shall be located on or immediately adjacent to each service disconnect that w i l l identify the portion of the building served by the service. In all other instances there shall be but one service to a building or a structure. SUBSTANTIATION: I t is obvious that most e l e c t r i c a l services that are installed today are installed under the provision of one of the "EXCEPTIONS" to Section 230-2. This makes the basic rule, "one service to one building" rather inane. I f the "EXCEPTIONS'~ have proven themselves t o be e l e c t r i c a l l y safe and sound engineering practice (and they certainly have or there would be a clamor to have them removed from the Code) they should have become the law, rat~er than the "EXCEPTIONS" to the law. Through the years we have constantly been adding "EXCEPTIONS" which r e a l l y are not "EXCEPTIONS" at a l l , but are acceptable methods of installing services. We are sure that someone w i l l point out that we have omitted some of the present "EXCEPTIONS." Those that do not appear in our proposed wording as individual sections are included in some other section that has been proposed or are not necessary under this proposed approach. The present Code calls f o r a "plaque or directory" to be installed at each service drop or lateral or service equipment which w i l l denote a l l OTHERservices on or in that.building and the area being served by each such service. When you are standing in front of a piece of service equipment on the f i r s t f l o o r , you want to know what THAT service supplies. You don't want to have to read through a five-page directory to determine what service supplies the 2Bth f l o o r of the building. High-rise buildings, and we know that this is a r e l a t i v e term depending completely on where you are geographically located, are taking the place of buildings thaty once were spread out on a horizontal plane. The very simple fact is that land is too expensive to continue to build in that fashion and serving an 800 foot high building is completely different than serving one 800 feet long. The information that is necessary is "What does this serve?" We know that there are additional services and when we get to them, w e ' l l know what each serves in turn. In our travels around the country, we have found few individual inspectors who have indicated that they were demanding and getting the required directories or plaques. PANEL ACTION: Reject. PANEL COMMENT: The Panel's intent is to require only one service. The Panel disagrees with the f i r s t sentence of the substantiation. Exception No. 7 is omitted. VOTE ON PANEL ACTION: Unanimously Affirmative. COMMENT ON VOTE: ~ D { R ~ ¢ ~ # C - - S e e my comment on Proposal 4-24. Log # 1619 4- 17 - (230-1): Reject Secretary's Note: The Correlating Committee advises CMP 4 that a r t i c l e scope statements are the responsibility of the Correlating Committee and that the Correlating Committee accepts the Panel Action. SUBMITTER: Richard B. Boyd, J r . , E l l i s Cannady Chapter, IAEI RECO~ENDATION: Relocate definition of "Service-point" from Section 230-200 to the end of Section 230-1. SUBSTANTIATION: To c l a r i f y what we understand to be the CMP's intent. PANEL ACTION: Reject. PANEL COMMENT: The definition is used primarily f o r high voltage and the present location is proper. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 368 4- 18 - (230-2): Reject SUBMITTER: DaveKamies, Sheldon, IA ~ATION: Where more than one service is permitted by any of the following exceptions, a removable plaque or directory shall be installed at each entry of the service conductors inside the build by the incoming wires. SUBSTANTIATION: The reason I w~uld like this Code changed is because this would be over s u f f i c i e n t to put a plaque or directory at every service, maybe you have a number of services why not put only one removable plaque or directory at the main entry of the conductors, at that nearest service. Telling the personnel that where each service is located. PANEL ACTION: Reject. PANEL COMMENT: The Panel's intent is to require a permanent plaque or directory at each service. VOTE ON PANEL ACTION: Unanimously' A f f i r m a t i v e . 56 Log # 781 4- 23 - (230-2, Exception NO. 3b.): Reject SUBMITTER: Thomas E. Trainor, City of San Diego RECOMMENDATION: 230-2 Number of Services. Revise E'~-c-eption No. 3 b. to read: b. "By special permission," buildings of multiple occupancy "may" be permitted to have two or more separate sets of service-entrance conductors which are tapped from one service drop or l a t e r a l . SUBSTANTIATION: There has been continuing c o n f l i c t regarding this particular i n s t a l l a t i o n of multiple service entrance conductors. Such an i n s t a l l a t i o n is unacceptable in the southwestern United States. Permitting multiple "services" in this manner leads to unmanageable numbers of "service" disconnects on a building, excessive lengths of unfused "service" conductors on a building and the loss of any control over service disconnects being grouped and/or accessible to f i r e safety personnel in an emergency. Making this exception subject to special permission w i l l allow the jurisdictions enforcing this Code to establish conditions where deemed necessary to address these safety issues. PANEL ACTION: Reject. PANEL COMMENT: See Panel Proposal 4-24. OTOTE-ON PANEL ACTION: Unanimously Affirmative. COMMENT ON VOTE: NIEDERMEYER: See my comment on Proposal 4-24. Log # 909 4- 21 - (230-2, Exception No. 2):' Accept SUBMITTER: Ad Hoc Subcommittee on Cogeneration of Power ~ATION: Revise Exception No. 2. Added wording in quotations. Exception No. 2: For emergency, legally required stand-by, optional stand-by~ or "parallel power production" systems where a separate service IS required. SUBSTANTIATION: The addition to Exception No. 2 is necessary to permit a solar photovoltaic, wind or other e l e c t r i c power production source to be installed in addition to a ( u t i l i t y ) service in a building or other structure. PANEL ACTION: Accept. ~-F#R~L ACTION: Unanimously Affirmative. Log # 1890 4- 22 - (230-2, Exception No. 3): Reject SUBMITTER: Peter Van Putten, Holland, MI ~ATION: Delete part b. of Exception No. 3 and delete designation a. Also, delete reference in Section 230-71(a) to Exception No. 3b. SUBSTANTIATION: Exception No. 3b grants blanket approval to multiple occupancy buildings and in effect negates the provisions of and need f o r Exception a. Few sections of the NATIONAL ELECTRICAL CODE have e l i c i t e d as many f i e l d problems, proposals, comments and arguments as the matter of service entrance disconnects -- one, two to six, or any number with as many as six disconnects on each set or subset of service entrance conductors. In the preceding four Code changes there Has been no less than 32 proposals dealing d i r e c t l y with the matter of one - - two to six -- or more. In addition another dozen or so proposals have been submitted which dealt with periphery issues - - f i r e pumps, height, covering, etc. The proposals represent a variety of interests, inspectors, manufacturers, u t i l i t i e s , code consultants, contractors, insurance underwriters. The proposers were from the east, the west, the north, the south and the heartland of America. The concern therefore is not indigenous to any regional, cultural or climatic circumstance. I t is emanating from a desire to express in a concise manner what a service should consist of. Even Code-Making Panel 3 in Proposal 34a to the 1981 Code attempted to set the record straight. The principal divergence of opinion appears to be with the articulate voice of the e l e c t r i c light and power group, Mr. William Bitterman. His substantiation reference to 1933 is probably accurate. I do not have that issue but the 1937 Code does say exactly the same in A r t i c l e 230 Section 2302 b. "Buildings of multiple occupancy may have two or more separate sets of service entrance conductors." The foregoing is one exception of three to the general rule which calls f o r one set. A r t i c l e 230 of the 1937 Code states in Section 2351 b. disconnecting means), "In a multiple occupancy building supplied y a service in conformity with 2302 b. and having a common readily accessible space available, the service shall be controlled by a single means where there are more than six separate subdivisions of the service." Further, Section 2371 a. 5 requires the overcurrent protection to be a single set of devices where there are more than six separate subdivisions of the service equipment. As Code enforcement people i t is imperative that we look at all of the components of the i n s t a l l a t i o n and therefore all of the applicable Code a r t i c l e s . We w i l l not then be entrapped by the p i t f a l l s of taking things out of context. I find Mr. Bitterman's further substantiation comments t h a t , "There has been no adverse safety record since that time" to be a very bland statement coming from a u t i l i t y person who is not customarily involved with the condition prevalent beyond the service point or interface of provider and customer. My personal experiences can attest to many service-entrance conductors consumed by lack of appropriate (not more than six) disconnects and overcurrent devices on the service conductors. 4- 24 - (230-2, Exception Nos. 3b and 7, 230-3-(New)): Accept Secretary's Note: I t was the action of the Correlating Committee that further consideration be given to the comments expressed in the negative voting dealing with c o n f l i c t . SUBMITTER: CMP 4 ~ATION: Delete Exception No. 3b. Insert a new Section 230-3 t i t l e d : "230-3. Number of Service-Entrance Conductor Sets. Each service drop or lateral shall supply only one set of service-entrance conductors. Exception: Buildings of multiple occupancies shall be permitted to have one set of service-entrance conductors run to each occupancy or to a group of occupancies." Add the word "latera.l" at end of the sentence in Exception No. 7. Renumber the existing Sections 230-3 to 230-4, 230-4 to 230-5, and 230-5 to 230-6. SUBSTANTIATION: To c l a r i f y the Panel's intent on the number of service-entrance conductor sets permitted. PANEL ACTION: Accept. VOT~ ON PANEL ACTION: AFFIRMATIVE: 12 NEGATIVE: Cock, Izydorek, Niedermeyer. COMMENT ON VOTE: - - I ~ O ~ : - - - I - a g r e e with the concept but feel some r e s t r i c t i o n of service-entrance conductors is required on buildings over two stories. I suggest buildings over two stories be limited to not more than six (6) sets of service-entrance conductors per drop or lateral. STANBACK: Word "occupancies" in exception f i r s t line should be "occupancy." EXPLANATION OF VOTE: COCK: I am voting against this proposal because i t would be in c o n f l i c t with Section 230-45 which permits two to six sets of service-entrance conductors to be run to separate enclosures. Exception No. 3b should be removed from Section 230-2 and placed in Part E, Service-Entrance Conductors. Section 230-2 should be rewritten to permit two or more services under the conditions listed in the present exceptions and using the format of Proposal 4-20 but retaining the present wording of all the seven exceptions pertaining to services. The number of disconnecting means For each service or for each sol of service-enLrance conductors can be limited to not more than six grouped in any one location in Section 230-71(a). IZYDOREK: Proposal 4-24 (Log CMP) appears to be in c o n f l i c t with Section 230-45. The new Section 230-3 limits multiple sets of service-entrance conductors to multiple occupancy buildings. Section 230-45 does not l i m i t the i n s t a l l a t i o n described therein to multiple occupancy buildings. I, therefore, am changing my vote to negative. This c o n f l i c t can be eliminated be deleting Section 230-45. Section 230-45 should then be reworded and added as Exception No. 2 to Section 230-3 as follows: Exception No. 2: Two or more sets of service-entrance conductors shall be permitted to be run to the service disconnecting means that are located in separate enclosures and supply separate loads. NIEDERMEYER: We r e a l l y didn't reduce the footage of service-entrance conductors on, or in buildings when we made this change. My' vote changes to affirmative i f we change Lhe exception to read: "except by special permission, multiple occupancies shall be permitted to have up to six sets of service entrance conductors o r i g i n a t i n g from a service p o i n t . * For a low building (two stories or l e s s ) , and fed underground, the l i m i t of six sets of service-entrance conductors shall not apply." I We must define the service: a. the drop or l a t e r a l , b. the service point or interface, c. the service-entrance conductors, d. the main switch or switches, e. the branch c i r c u i t devices or feeder(s) to remote panelboards. We can then say with authority there shall be not more than one service of a class to a building or f i r e wall division and the service equipment shall be comprised of not more than six disconnect switches. The multiple occupancy building can have as many subfeeders as is necessary and consistent with the a b i l i t y of the service to supply i t . PANEL ACTION: Reject. PANEL COMMENT: The Panel feels that i t is necessary to d i f f e r e n t i a t e between Section 230-2, Exception 3(a) and Section 230-2, Exception 3(b) which provides f o r service-entrance conductors. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . • I ~ O I ~ - O N ~ ( T r c T. . . . NIEDERMEYER: See my comment on Proposal 4-24. 57 "Except by special permission, for a multiple occupancy building exceeding two stories in height, the limit of sets of service-entrance conductors shall not exceed six. Such multiple sets of service-entrance conductors shall be permitted to terminate in a common location which is readily accessible to the occupants." The exception, along with another proposal to limit the length inside a building, should give some positive limitations on the amount of unfused conductors on and in a building. Presently, these figures are without any limit. *See Section 230-200 definition. Log ~ 918 4- 28 - (230-2, Exception No. 8-(New)): Reject SUBMITTER: Ad Hoc Subcommittee on Solar Photovoltaics RECOMMENDATION: Add Exception No. 8 to Section 230-2, as follows: ExcepT~-6fi No. 8: For Solar Photovoltaic Systems. SUBSTANTIATION: To permit use of a solar photovoltaic system in conjunction with another service such as the normal u t i l i t y service. PANEL ACTION: Reject. g ~ T : See Panel Comment f o r Proposal 4-21. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . Log # 432 4- 25 - (230-2, Exception No. 3b.): Reject SUBMITTER: Southwestern Section IAEI ~ATION: 230-2 Number of Services Exception No. 3: Multiple Occupancy Buildings a. No change b. "By special permission," buildings of multiple occupancy "may" be permitted to have two or more separate sets of service entrance conductors which are tapped from one service drop or lateral. .SUBSTANTIATION: There has been continuing c o n f l i c t regarding t h i s p a r t i c u l a r i n s t a l l a t i o n of multiple service entrance conductors. Such an i n s t a l l a t i o n is unacceptable in the southwestern United, States. Permitting multiple "services" in t h i s manner leads to unmanageable numbers of "service" disconnects on a building, excessive lengths of unfused "service" conductors on a building, and the loss of any control over service disconnects being grouped and/or accessible to f i r e safety personnel in an emergency. Making t h i s Exception subject to special permission w i l l allow the j u r i s d i c t i o n s enforcing this Code to establish conditions where deemed necessary to address these safety issues. PANEL ACTION: Reject. PANEL COMMENT: See Panel Proposal 4-24. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . COMMENT ON VOTE: NIEDERMEYER: See my comment on Proposal 4-24. Log ~ 670 4- 29 - (230-24(a)): Reject SUBMITTER: Warren H. Cook, IEEE RECOMMENDATION: Conductors shall have a v e r t i c a l clearance of not less than "i0 f e e t " from all points of roofs above which they pass. SUBSTANTIATION: This brings Section 230-24 into conformance with Section~ and the National E l e c t r i c a l Safety Code. PANEL ACTION: Reject. F A I ~ E ' L ~ T : The National Electrical Safety Code and -S-~-tl~9 of the NEC contain other conditions not mentioned in the proposal. VOTE ON PANELACTION: UnanimouslyAffirmative. Log ~ 808 4- 30 - (230-24(a)): Reject SUBMITTER: Robert A. Jutstrom, Westborough, MA RECOMMENDATION: Change to read as follows: Ta~ Above'roofs: Conductors shall have a v e r t i c a l clearance of not less than 10 f e e t from all roof space that is accessible to pedestrians. SUBSTANTIATION: Roofs that can be r e a d i l y walked upon by pedestrians should have the same service clearance as required in 225-1g(a) f o r outdoor feeders. PANEL ACTION: Reject. ~E'L~T: Section 225-19 contains other conditions not m~tfone-e-d-Tn-the proposal. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 433 4- 26 - (230-2, Exception No. 5): Reject SUBMITTER: Southwestern Section IAEI RECO~ENDATION: 230-2 Number of Services. Exception No. 5: Buildings of Large Area, By special permission, f o r a single building or other structure s u f f i c i e n t l y large to make two or more services necessary. "All c i r c u i t s from such separate services shall be r e s t r i c t e d so that no building area shall contain c i r c u i t s from more than one service disconnect." SUBSTANTIATION: A building of large area granted two services is e f f e c t i v e l y tile same as two buildings with single services. The Code should provide equivalent safety f o r occupants, f i r e service and maintenance personnel in each case. I t can be extremely dangerous to have two separate services supplying e l e c t r i c a l equipment in the same area of a building. This proposal establishes a minimum standard to eliminate such hazard and, hopefully, c l a r i f i e s the intent of the Code related to such i n s t a l l a t i o n s . PANEL ACTION: Reject. I~I~dTE'[--~M]~E~N-T: Would negate some of the benefits of the second service. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . Log # 381 4- 31 - (230-24(b)): Reject SUBMITTER: Gary Lensch, Sheldon, IA RECOMMENDATION: 18 feet (5.49 m)-Over public streets, alleys, roads, parkTng areas subject to truck t r a f f i c , driveways on other than residential property. 20 feet (6.10 m)-On land traversed by machinery used f o r c u l t i v a t i n g , grazing, f o r e s t , and orchard, or where subject to truck t r a f f i c . SUBSTANTIATIOIN: Dae to the use of larger machinery I believe that higher wires are needed to prevent e l e c t r i c a l shocks. PANEL ACTION: Reject. PANEL COMMENT: See Panel Comment f o r Proposal 4-10. VOTE ~ ACTIDN: Unanimously A f f i r m a t i v e . Log # 1177 4- 32 - (230-24(c), 230-24(c), Exception-(New)): Accept SUBMITTER: M.F. Borelis, EEl RECOMMENDATION: Delete second paragraph and substitute the following Exception: Exception. Conductors run above the top level of a window shall be permitted to be less than the three (3) feet (914 mm) requirement above. SUBSTANTIATION: This change is f o r c l a r i f i c a t i o n and to be consistent with the s t y l e manual of the NEC. The basic rule is three (3) feet (914 mm) so as to be out of reach from windows, doors, porches, f i r e escapes, etc. The Exception is f o r any conductors run above window openings which are considered out of reach. A corresponding proposal has been submitted f o r Section 225-19(d). PANEL ACTION: Accept. ~OTE-~L ACTION: Unanimously A f f i r m a t i v e . COMMENT ON VOTE: - ~ C ) ( ~ (914 mm) should be (.914 m). STANBACK: For e d i t o r i a l improvement, exception should read "Conductors run above the top level of a window." Log # 782 4- 27 - (230-2, Exception No. 5): Reject SUBMITTER: Thomas E. Trainer, City of San Diego 3TEILTOI~ETTDATION: Revise Exception No. 5 to read: Exception No. 5: Buildings of Large Area. By special permission, f o r a single bullding or other structure s u f f i c i e n t l y large to make two or more services necessary. "All c i r c u i t s from such separate services shall be r e s t r i c t e d so that no building area shall contain c i r c u i t s from more than one service disconnect." SUBSTANTIATION: A building of large area granted two services is e f f e c t i v e l y the same as two buildings with single services. The Code should provide equivalent safety f o r occupants, f i r e service and maintenance personnel in each case. I t can be extremely dangerous to have two separate services supplying e l e c t r i c a l equipment in the same area o f a boilding. This proposal establishes a minimum standard to eliminate such hazard and, hopefully, c l a r i f i e s the intent of the Code related to such i n s t a l l a t i o n s . PANEL ACTION: Reject. PANEL COMMENT: See Panel Comnent f o r Proposal 4 - 2 6 . ~ N - - P A N ~ C ACTION: Unanimously A f f i r m a t i v e . Log # 88 4- 33 - (230-40, Exception a . ) : Reject SUBMIFER: Rusty Burnham, Fickett E l e c t r i c Co. ~DATION: Revise Exception a. to read as follows: a. Bare copper, aluminum, or copper-clad aluminum used in a raceway or part of a service cable assembly. 58 VOTE ON PANEL ACTION: ~ ' F f V ~ ~ "-i"4""" NEGATIVE: Bowles. COCk'lENT ON VOTE: -~"F~N~B-A-CITT~'I~6uld correct typographical e r r o r in Panel Action to change "grounded conductors" to "grounded conductor." EXPLANATION OF VOTE: BOWLES: While some c l a r i f i c a t i o n is needed in Section 230-41, I think that CMP 4's modification of the proposal confuses more than i t helps. I suggest that (1) and (2) be reworded as f o l l o w s : "i00 ampere f o r a 3-wire service to a one f a m i l y . . . " Also, (b) should be r e w r i t t e n as "Ungrounded Conductor. Ungrounded conductors shall have an ampacity of not less than:" since (1) and (2) are r e f e r r i n g to ampacity and not AWG size. SUBSTANTIATION: As presently written in the 1981 NEC, the miles of SE cabte containing aluminum conductors would be in violation. Exception d. appears to apply to underground installations only. Note: Underground installations should be covered in Part D, not Part E. PANEL ACTION: Reject. PANEL COMMENT: Section 230-40 applies to service-entrance c ~ s on e i t h e r overhead or underground services. See Panel Action f o r Proposal 4-34. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . Log # 15 4- 34 - (230-40, Exception d . ) : Accept SUBMITTER: William O. Andersen, J r . , The Aluminum Association RECOMMENDATION: Add the word "or" a f t e r "cable assembly" in Exception d. This section would then read: Exception: A grounded conductor shall be permitted to be uninsulated as f o l l o w s : d. Aluminum or copper-clad aluminum without individual insulation or covering when part of a cable assembly or i d e n t i f i e d f o r underground use in a raceway or f o r d i r e c t b u r i a l . SUBSTANTIATION: The present wording o f Exception d. has been interpreted to prohibit the use of aluminum SE-U cable. The phrase "when part of a cable assembly identified for underground use" requires all aluminum "Service Entrance conductors entering or on the exterior of buildings or other structures" to be identified for underground use. SE-U cable is not used underground. The addition of "or" after "cable assembly". separates and identifies the SE-U cable construction, eliminates the current misinterpretation and more clearly demonstrates the Panel's intent. PANEL ACTION: Accept. VOTE ON PANEL ACTION: UnanimouslyAffirmative. COMMENT ON VOTE: STANBACK: For c l a r i f i c a t i o n d. should read "Aluminum or copper-clad aluminum without individual insulation or covering when part of a cable assembly used above ground, or identified for underground use when used in a raceway underground or for direct burial." Log # 68 4- 37 - (230-41(b)(2)): Reject SUBMITTER: Dan Leaf, Westlake V i l l a g e , CA ~DATION: Insert the word "net" before the word "computed." SUBSTANTIATION: Text is unclear whether "computed" load is connected load or load with allowable demand f a c t o r s . Chapter 9 Example i indicates loads before application of demand factors as "computed" loads, and a f t e r application of demand factors as "net computed" loads, with a statement re: conductors required to have an ampacity of i00 amperes. This proposal would provide f o r consistancy between the example and the t e x t . PANEL ACTION: Reject. PANEL COMMENT: The Panel f e e l s that the terminology presently used is proper and in accordance with Section 230-41(a). VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . Log ~ 212 4- 38 - (230-41(b)(3)): Reject SUBMI~ER: Charles F. Kramer, Edison Bros. Stores, Inc. RECOMMENDATION: Proposed Wording: 30 amperes f o r other 277/480 v o l t , 3-phase, 4-wire loads, and 60 amperes f o r other 120/208 v o l t , 3-phase, 4-wire loads, or other loads. SUBSTANTIATION: Currently the use of 277/480 v o l t service is commonplace in most large shopping centers serving hundreds of small tenant spaces. These small spaces often have t o t a l design loads (which include 25% f o r long continued load) of 15 to 25 amperes. While the service conductors serving power from the u t i l i t y company or landlord d i s t r i b u t i o n center is a c t u a l l y branch c i r c u i t r y and this a r t i c l e should not apply, many times the local e l e c t r i c a l inspection a u t h o r i t i e s apply i t anyway due to the branch c i r c u i t being metered. The resulting problem is that a small space with the aforementioned 15 to 25 ampere design load is compelled to provide a disconnect switch and conduit and conductors some 3 to 4 times larger than said design load and 2 times larger than the very ample 30 ampere size. This is a punitive unnecessary expense to the. small shop owner and i t appears to date back to the era when small shops such as described automatically received 120/208 v o l t service. PANEL ACTION: Reject. PAN'EI_--~: The Panel f e e l s that the requirements and the Exceptions adequately cover services. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . Log # 1587 4- 35 - (230-40, Exception e.-(New)): Reject SUBMITTER: Peter Pollak, The Aluminum Association, Inc. RECOMMENDATION: e. Aluminum or copper-clad,aluminum without individual i n s u l a t i o n when part of cable assembly with an outer overall covering. SUBSTANTIATION: In a r r i v i n g at the present wording of Section Z30-4U, the ~de-Making Panel revised Section 230-40 to preclude a potential shock hazard by eliminating the word "covered." We do not believe the existing wording properly reflects the intent of the Code-Making Panel with regard to the use of SER and SEU constructions and propose that this be c l a r i f i e d as indicated. PANEL ACTION: Reject. PANEL COMMENT: See Panel Action for Proposal 4-34. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 306 4- 36 - (230-41(b)(1) and ( 2 ) ) : Accept in P r i n c i p l e Secretary's Note: I t was the action of the Correlating Committee to d i r e c t the Panel to c l a r i f y the Panel Action on this proposal. SUBMITTER: H. C. Taylor, Rio Rancho, NM RECOMMENDATION: Delete 3-wire connotation. To read: T ~) Ungrounded Conductors. Ungrounded conductors shall not be smaller than: (1) lO0-amperefor a one-family dwelling unit with six or more 2-wire branch circuits. (2) lO0-amperefor a one-family dwelling unit with an i n i t i a l computed load of lOkW or more. (3) 60 amperes for other loads. SUBSTANTIATION: 1. As written inference is made that all wires are ungrounded. 2. As written i t implies that all conductors are to be of 100 ampere rating without regard to the derating of the third conductor (neutral) allowed by Section 220-22. 3. Makes item (b)(1) and item (b)(2) compati.ble with item (b)(3) which does not mention wire numbers. 4. Compatibility is maintained with Example 1, Table 9 i f in that example the word "ungrounded" is inserted between the word so and service conductors. . . . . . . "To read:" so ungrounded service conductors shall be 100 amperes (see Section 230-41(b)(2)). (9th sentence from bottom of page 70-644 NEC) PANEL ACTION: Accept in Principle. Add "Two" before "lO0-ampere" in the second and third sentences. Add the phrase "with grounded conductors" between "ampere" and "for" in the second and third sentences. PANEL COMMENT: Submitter's proposal would permit 2-wire, TO-O----ampere services which is not the intent of the Panel. Log ~ 728 4- 39 - (230-43): Reject SUBMITTER: Donald L. Gregersen, City of Spokane, WA RECOMMENDATION: Add to Section 230-43, wiring methods f o r i n s t a l l i n g service conductors - (13) F l e x i b l e Steel Conduit. SUBSFANTIATION: There are many places where steel f l e x i b l e ~t'c6Jld'be used without creating a hazard - but where aluminum conduit could not be used without creating a hazardous condition, such as at motors, and where, due to locations of service equipment to i n s t a l l r i g i d conduit is a real problem. We seldom had any problem with f l e x i b l e conduit t i l l contractors started using aluminum f l e x i b l e conduit. The difference between aluminum and steel deserves special consideration the same as given to the difference between r i g i d conduit and r i g i d non-metallic conduit. PANEL ACTION: Reject. P-ANEL COMMENT: The Panel does not agree with the submitter's substantiation. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . Log ~ 1456 4- 40 - (230-43): Reject SUBMITTERS: Leo Witz, Continental E l e c t r i c Co. B i l l Hogan, Chicago, IL Fred Smith, Elgin, IL Jim Meehan, New Haven, CT Kenny Gebert, Minneapolis, MN B i l l Conrardy, The Conrardy Co Robert P. Brooks, Chicago, IL Les Rinder, Chicago, IL 59 RECOMMENDATION: AmendSection 230-43 so that i t reads as follows: "230-43. Wiring Methods For 600 Volts, Nominal or Less. Service-entrance conductors shall be installed in conformance with all applicable requirements of this Code for the wiring method being used and shall be limited as follows: ( i ) rigid metal conduit, (2) intermediate metal conduit, (3) electrical metallic tubing, (4) busways, I~I type MC cable, (6) mineral-insulated, metal-sheathed cable, open wiring on insulators, (8) service-entrance cable, (9) wireways, (10) auxiliary gutters (11) rigid nonmetallic conduit, or (12) cablebus. No e l e c t r i c i t y unprotected service-entrance conductor shall extend inside of a building or an enclosed structure more than five (5) feet. No service-entrance conductor or raceway that encloses service-entrance conductors, which when exposed to temperature above their rating or flame emits toxic gases or harmful chemicals shall be installed inside of a building or structure unless i t is enclosed in a metal raceway or embedded in concrete. SUBSTANTIATION: The changes that have been made and will be made in Article 230 regarding the number of services permitted on or in one building are just beginning to catch up with the real world. Most services and therefore, service-entrance conductors have for years been installed under one of the Exceptions to Section 230-2 rather than the basic rule; i.e. one service per building. At the present time, there is nothing f i n i t e in the Code that limits the length of e l e c t r i c i t y unprotected service-entrance conductors inslde of buildings. This in spite of the fact that Article 240 goes to great length to assure that all conductors are provided with some form of overcurrent protection. With the proliferation of services on and in buildings, we will be faced with the possibiity and probability of longer and longer runs of e l e c t r i c i t y unprotected conductors. There can be no doubt that such a condition is hazardous and can and will lead to more fires and injuries i f not regulated. We have chosen the figure, five (5) feet, simply because that same figure has been the rule in several major cities for more than fifteen (15) years and has created a minimum number of problems. I t is our opinion that the distance must be as short as IS possible and practical. I f that number becomes a major stumbling block in the Panel discussion, we would suggest that a simple answer to such a problem could be the insertion of the words, "Except by special permission, no electrically unprotected service-entrance conductor . . . etc." This would provide all the f l e x i b i l i t y needed by inspectors, contractors, engineers, etc. to accomplish the solution of any problem. All that would be necessary is that the problem be presented in writing with good and sufficient reason for departing from the basic rule and permission would be granted by the inspector in charge. Meanwhile, the basic rule prevails and all unprotected service-entrance conductors must terminate no more than five (5) feet inside of the building or enclosure. As a further point for such a discussion, Sections 90-2(c), 90-4 and the definition of "Special Permission" give the inspector all the tools, he needs to accomplish any safe electrical installation. The introduction of this limitation would certainly allay the concerns that have been expressed by many electrical inspectors concerning the proliferation of services and unprotected service-entrance conductors. For those inspectors to whom this has been no problem, the inclusion of the regulation will create no new d i f f i c u l t y since they can give permission for anything that can be j u s t i f i e d . Additional substantiation for proposals made by William P. Hogan et. al. on sections: 110-3(a)(8), 230-43, 300-22(b), 300-22(c), 338-2, 338-3, 340-5, 344-2, 347-2, 351-2, 352-21 and 370-23. I t should be obvious that the thrust of all these proposals is the limitation or actual elimination of the use of those MATERIALS, which when exposed either to the enviroement, temperatures in excess of their ratings, whether from normal or abnormal causes, or flame emit toxic gases, fumes or harmful chemicals. For years the electrical industry has not only permitted but also has encouraged the use of materials that f a l l into this category. These materials do emit toxic gases and do result in harmful chemicals when exposed to the varying atmospheres experienced in everyday living. For instance, i t is not an uncommon phenomenon to observe hydrochloric acid dripping out of a rigid steel conduit in which PVC conductors have been exposed to temperatures higher than their ratings or flame and water has been used to control the source of that heat or flame. There are documented experiences of this reaction where the acid was eating through the switch enclosure. When the inspector attempted to catch the acid in a t i n can so that he could have i t analyzed, i t ate right thru the can. What is startling about this phenomenon is the fact that we are told that the plastic people have known about i t for years and have never f e l t that this information should be publicized because the incidence would be so rare that i t was not worth alerting the electrical industry. In spite of their lack of concern many people in the industry and out of i t are aware of this possibility and the other ramifications of the decomposition of PVC and 'are deeply concerned. We are told over and over again that the amount of plastics and polyvinyl chlorides that are introduced in any building by the electrical installation is infinitesimal when compared with the total of all the other furnishings and building finishes. There are two errors in such statements. The f i r s t is corrected by the reports printed in Modern Plastics based upon the monthly Sales/Production report issued by SPI's Committee on Resin Statistics. According to' their figures, published in January of 1981 there were 3,581,000 tons of resins converLed into building materials in 1979. Of that 1,114,000 tons were PVC Conduit. Is that to be considered infinitesimal? The figures for 1980 are just as revealing; 3,078,000 tons total, 938,000 tons in PVC Conduit. In addition to that there were 841,000 tons of resins converted into electrical/electronic plastics in 1979 of which 195,000 tons were PVC. Likewise, in 1980 out of a total of 736,000 tons, there were 177,000 tons of PVC. These are NOT infinitesimal fractions! The second error is the attempt by the people, who spew forth this falacious claptrap, to hide the fact that we, who are responsible for formulating the National Electrical Code, have one prime responsibility, the safety of the people. We are completely and solely responsible for the electrical installation. We and only we must bear the responsibility For what is in the NEC. We are not in any, shape or form responsible for the furnishings nor the building finishes. Regardless of what others may introduce into the building, we are s t i l l responsible for those things that we permit or require in the electrical installation. We can never loose sight of the prime purpose of the NEC, " . . . t h e practical safeguarding of persons and property from the hazards arising from the use of e l e c t r i c i t y . " For many years a great number of knowledgeable and highly respected people in the scientific world have been aware of the fact that the use of certain materials and wiring methods, which by the very nature of their chemical composition, are certain to add significantly to the toxic gases and harmful chemicals in any f i r e situation. I t has been and s t i l l is their contention that the use of these materials should be curtailed or prohibited. We can no longer afford the luxury of sitting back waiting for someone else to take the f i r s t step. We cannot hide behind a disclaimer saying we know nothing about'toxicity. I f we don't know, i t is because we haven't taken the time to read what is available on the subject or listen to what is being said from every'direction. The numbers of people being killed in recent fires is staggering. The ratio of f i r e deaths to f i r e damage is astounding. I t is completely out of line with historical f i r e data. The number of people died 20 stories away from the'closest flame in the MGM is unforgiveable. The number of people who died in that building after the f i r e was out, but while the hallways and stairwells were f u l l of toxic gases and smoke will never be known, but the fact that many did is additional reason for us to act. We cannot wait until other standards-writing bodies take the lead. We cannot wait until slow moving committees bring in the BODY COUNTS! We can no longer ignore the warnings that havebeen made public in the form of test results from widely divergent groups, government, industry, scholastic and testing f a c i l i t i e s . Here is what just a few highly regarded scientists have to say about this matter: A report compiled by the Uniformed Firefighters Association in 1980 five years after the telephone company f i r e shows that of the 194 firefighters who received medical treatment at the time of the f i r e 71 reported permanent respiratory ailments. The unprotected cables that burned in that f i r e produced "billowing clouds of hydrogen chloride smoke." (American Lung Association Bulletin, (81)). "Large amounts of hydrogen chloride gas (HCL) are released by either HEATING or BURNINGPVC" * "In the case of a rapid electrical overload in PVC insulated wire, smoke which is usually the First indication of f i r e , is only noticeable AFTER significant quantities of HCL have been released." * "Calculations show that for 100 pounds of PVC pyrolyzed (chemically decomposed by heat) in an apartment 8 feet X 25 feet X 50 feet (10,000 cubic feet) a concentration of HCL as high as 57,385 ppm could be reached, about 57 times the concentration that will cause lung edema on very short exposure." * Referring to the M~ f i r e deaths the Clark County Coroner-Medical Examiner reports, "The fact that the concentration of carboxyhemoglobin in most of the victims was not high enough to have caused death indicates that other toxic gases or smoke particles MUST also have been involved." * (Carboxyhemoglobin is the result of carbon monoxide in the blood). • A Literature Study of the C~nbustion Hazards of PVC and ABS. Judith E. Hall and Eric L. Tolefson, University of Calgary. In a discussion concerning the Beverly Hills Supper Club Fire, Deborah Wallace, who is a Toxicologist and the President of Public Interest Scientific Consulting Service states the following about the causes of death at that f i r e , " - - - , the carboxyhemoglobin levels found during the autopsies showed that all assayed victims but one had concentrations well below lethal levels. Manywere as low as 10%." Yet they all died of something that they inhaled. There was a tremendous amount of PVC in that building! 60 Log # 1117 4- 41 - (230-43): Reject SUBMITTER: J.H. Richards, Maryland Electrical Inspectors Association RECOMMENDATION: Add: "Flexible metal conduit in limited lengths s~u-ggest six foot maximum) as acceptable wiring method for services." Rules for proper bonding is covered in Article 350. SUBSTANTIATION: This method was permitted in former codes but was B'ET~-E-d~--.-C~6fd experience has shown that there are times when deflections are required that are not feasible using other listed wiring methods. Further when properly sized grounding and bonding conductors are run in the limited lengths and properly terminated, no greater l i f e or f i r e hazard would exist than with use of the listed accepted methods. PANEL ACTION: Reject. PANEL COMWENT: See Panel Co(mnent f o r Proposal 4-39. VOTE ON_PANEL. A C ~ Z Unanimously Affirmative. Jay A. Young, Ph.D., a Chemical Consultant has this to say, "Structural disintegration of PVC Conduit in a f i r e situation. Such disintegration allows the release of hydrogen chloride or phosgene, or both, formed from the decomposition of PVC insulation on the wiring inside, the conduit and confined inside the conduit until the conduit disintegrates." "The thermal decomposition of PVC has been observed at temperatures below 100 degrees C, although most studies show that the evolution of HCL in significant amounts requires temperatures of about 200-300 degrees C. That is, long before the PVC has reached the temperature at which i t will burn, well in advance of the time when any combustible structural components near PVC conduit would be likely to be burning in a f i r e situation." Dr. Young further states, "Hydrogen Chloride is an i r r i t a t i n g ~as At concentrations in air as low as 5ppm, i t causes choking in most people." Dr. Young continues, "Concentrations of lOOppm are rated as, "Immediately dangerous to l i f e and health" by OSHA and the National Institute for Occupational Safety and Health. Unless removed immediately from an atmosphere containing a concentration of lOOppm death by suffocation will follow." There are no less than 132 books, papers and articles available to you on this subject. You can rest assured that each will point out the t o x i c i t y of the products of combustion of PVC and of the t o x i c i t y of HCL which is produced simply by heating PVC Conduit or insulation. You may be able to ignore this information, but we can not. As far as we are concerned, the facts are in front of you and you must act. We have, - with these proposals. The problem is not going to go away by i t s e l f . Nor is i t going to lessen in intensity. You can be absolutely sure that i t and you will be in the public eye and in every form of mass news media as long as people are killed in fires. I t will make headlines and bring more and more court cases, which will further highlight the shortcomings of the Code. I t seems to be a foolish course of action, or is i t INACTION, to wait until public furor forces us to change. I f we in NFPA through the NEC i n i t i t a t e the act, we at least retain the respect and confidence of the people we serve. I f we do not, you can be assured that those same people will have no respect for this organization or us. I t is f u t i l e to deny~ or attempt to minimize, the presence of the harmful chemicals in the materials used to manufacture insulations and raceways that not only can, but do, emit toxic gases in amounts sufficient to cause instantaneous paralysis when exposed to temperatures in excess of their ratings, or f i r e . The peaceful attitudes of so many of their victims is grim testimony to the speed of these killers and the fact that the victims were t o t a l l y unaware of their impending Fate. Our proposals are intended to minimize or eliminate the exposure of human beings to this peril. Note: I t is most important to understand that this proposal is not intended to do away with a l l , nor any, nonmetallic wiring method. This proposal and all others like i t that we have submitted for the 1984 edition of the NEC are intended to eliminate the MATERIALSwhich emit toxic fumes or gases under various conditions of use. I t is our opinion that the manufacturers of this equipinent or these MATERIALSmust prove that their products do NOT emit toxic gases or harmful chemicals under the conditions specified. I t should not be the responsibility of the NFPA nor any Code-Making Panel to perform the tests or make the investigations that are needed to prove the presence of the toxic gases, fumes or harmful chemicals. PANEL ACTION: Reject. ~-~--E-L COMMENT: The Panel feels that the 5 feet is arbitrary. Furthermore, the submitter has not presented conclusive evidence that the t o x i c i t y hazard would be eliminated by the use of metal raceways. VOTE ON PANELACTION: Log # 1178 4- 42 - (230-43(13)-(New)): Reject SUBMII-FER: M. F. Borleis, EEl ~ATION: Add an item to the f i r s t paragraph as follows: C13) flexible metal conduit not more than 6 feet long between "raceways, or between raceway and serviceequipment, with equipment bonding jumper installed around the flexible metal conduit according to provisions of Section 250-79(a), (b), (c), and (e). Also see Section 350-2. Second paragraph to remain. SUBSTANTIATION: Flexible metal conduit had been used safely as a portion of service-entrance raceway from 1937 until the 1975 edition of the NATIONAL ELECTRICAL CODE. Former subsection 230-63(c) had been eliminated from the 1975 NEC because the wiring method was not listed in Section 230-44 (1971). Recent inquiries at Section meetings of the IAEI indicate flexible metal conduit continues to be used in short lengths to avoid structural protrusions. Flexible metal conduit is particularly useful when making changes or adding to existing service-entrance f a c i l i t i e s . The bonding requirement assures low impedance along the path of a possible fault current. Reference to Section 350-2 effectively limits locations for this use of f l e x i b l e metal conduit. PANEL ACTION: Reject. PANEL COMMENT: See Panel Comment for Proposal 4-39. V O ~ f E - O N ~ ACTION: AFFIRMATIVE: 14 NEGATIVE: Cock. EXPLANATION OF VOTE: ~ - r - a m ~ negative on this proposal because I feel the Code Panel has not f u l l y considered the substantiation for the proposal and I feel i t is accurate. In 1979 the Panel rejected a similar proposal with a statement that "Bonding accomplishes nothing where a fault occurs within the flexible conduit." In r e a l i t y , the bonding accomplishes the purpose exactlyas conduit couplings (threaded or unthreaded) accomplish bonding integrity in a system of rigid metal conduit or metallic tubing. I t is also questionable that the impedance of an arcing fault in 6 feet of metal conduit is substantially different from a similar fault in a 10-foot length of any of the nonflexible metal conduits. I feel that flexible metal conduit should be allowed and that the limitation of 6 feet in this proposal makes i t the most desirable proposal from those for this section. Log # 1230 4- 43 - (230-43, Exception No. 1-(New)): Reject SUBMITTER: Tom Morosco, Independent Electrical Inspection Agency, I-~. NEGATIVE: Niedermeyer. EXPLANATION OF VOTE: NIEDERMEYER: In keeping with the Panel intent as stated in our e f f o r t to l i m i t the number and length o f services in multiple occupancy buildings, I propose we accept this proposal in p r i n c i p l e in that i t places numbers on the footage inside of a building. Instead of 5 feet as stated by the submitter, I propose 15 f e e t , this w i l l allow f o r a flush service and flush meter. I also propose to delete the l a s t sentence of the submitter as not being workable with the present knowledge at hand. Exception: The 15-foot length l i m i t may be waived by special permission. The above accomplishes our e f f o r t to both l i m i t the numbers of services and also the length inside of a.building. The p r o l i f e r a t i o n of unfused conductors must be limited as to number o f services and distance inside a building in order to a t t a i n some degree of safety - at present an unlimited length of total unfused conductors is acceptable under present wording when on or in a building. RECOMMENDATION: Exception No. i : Flexible metal conduit in lengths not exceeding 6 feet, may be used in dry locations (for exposed work) following the requirements of Section 250-79 and Article 350. SUBSTANTIATION: Service raceways entering structures are many t~mes confronted with permanent obstructions. These conditions create serious installation problems. The problem of making jogs, offsets and excessive use of conduit f i t t i n g s will be eliminated. Through experience we are not aware of any problems or conditions involving the use of flexible metal conduit and liquidtight f l e x i b l e conduit. Presently in their use with ac equipnent, etc. and proper bonding they have proven to perform safely as raceways. With this fact and the requirements for their proper installation they should be considered suitable for service raceways on the load side of meter equipments to overcome obstructions. PANEL ACTION: Reject. ~NE~I-~T: See Panel Comment for Proposal 4-39. VOTE ON PANEL ACTION: Unanimously Affirmative. 61 Log # 514 4- 48 - (230-53): "Reject SUBMITTER: J. K. Daugherty, Flint, MI RECOMMENDATION: Delete Section 230-53. ~[AT[dN: T h i s requirement dates back to 1937 or earlier which was prior to moisture-resistant service-entrance conductors and as such was needed. Today, service-entrance conductors are moisture-resistant and there is no need for this requirement. Furthermore, the requirement has been misapplied to the undernro,,n ~ wiring of gasoline dispensing service stations. PANEL ACTION: Reject. TFAITEI---L~ ' }T~QIEI~T: Section 230-53 covers a broader spectrum than the submitter's proposal. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 1369 4- 44 - (230-43, Exception No. 1-(New)): Reject SUBMITTER: M. H. Lounsbury, Eastern Section IAEI ITE"C:~-M-M-EN ' FOATION: Exception 1: Flexible metal conduit may be used ~n dry locations (for exposed work) following the requirements of Section 250-79 and Article 350. SUBSTANTIATION: Service raceways entering structures are many ~n~ronted with permanent obstructions. Theseconditions create serious installation problems. The problem of making jogs, offsets and excessive use of conduit f i t t i n g s w i l l be eliminated. Through experience we are not aware of any problems or conditions involving the use of f l e x i b l e metal conduit and liquidtight flexible conduit. Presently in their use with ac equipment, etc. and proper bonding they haven proven to perform safely as raceways. With this fact and the requirements for their proper installation they should be considered suitable for service raceways on the load side of meter equipments to overcome obstructions. PANEL ACTION: Reject. PANEL COMMENT: See Panel Comment for Proposal 4-39. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 2021 4- 49 - (230-54(c), Exception): Reject SUBMITTER: Idaho Chapter IAEI RECOMMENDATION: RemoveException to Section 230-54(c). SUBSTANTIATION: The Exception is not clear and there is no reason the connection cannot be made below the ~eaLherhead ~here the weatherhead is properly i n s t a l l e d to comply with the basicCode rules addressing service drop clearances to f i n i s h grade and other access points. PANEL ACTION: Reject. #f@[~T: The exception was introduced to provide r e l i e f for upgrading e x i s t i n g services. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . Log # 2060 4- 45 - (230-43, Exception No. 2-(New)): Reject SUBMITTER: Tom Morosco, Independent E l e c t r i c a l Inspection Agency, Inc. RECOMMENDATION: Exception No. 2: L i q u i d t i g h t f l e x i b l e conduit in lengths not exceeding 6 f e e t , may be used in dry or wet locations ( f o r exposed work) following the requirements of Section 250-79 and A~ticle 351. SUBSTANTIATION: Service raceways entering structures are many times confronted with permanent obstructions. These conditions create serious i n s t a l l a t i o n problems. The problem of making jogs, offsets and excessive use of conduit f i t t i n g s w i l ] be eliminated. Through experience we are not aware of any problems or conditions involving the use of f l e x i b l e metal conduit and l i q u i d t i g h t f l e x i b l e conduit. Presently in t h e i r use with ac equipment, etc. and proper bonding they have proven to perform safely as raceways. With t h i s f a c t and the requirements f o r t h e i r proper installation they should be considered suitable for service raceways on the load side of meter equipments to overcome obstructions. PANEL ACTION: Reject. PANEL COMMENT: See Panel Comment for Proposal 4-39. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 1775 4- 50 - (230-56, FPN-(New)): Reject SUBMITTER: Tom Tombarello, Paul Revere Chapter IAEI RECOMMENDATION: Add a new fine print note as follows: FPN: See "Section 384-3(e) and ( f ) for phase arrangement. SUBSTANTIATION: Correlation is necessary among Sections 215-8, ~ , and "384-3(e) and ( f ) and any exceptions or modifications to these requirements. PANEL ACTION: Reject. PAI~EI_-~~ ' I~FME ' -'NT: The Panel feels that a cross reference is not needed. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log e 1200 4- 51 - (230-70): Reject SUBMITTER: Olaf G. Ferm, Ferm's Fast Finder Index RECOMMENDATION: Changethe wording of the f i r s t sentence to read: Means shall be provided to disconnect all conductors in a building or other structure from the service-entrance conductors and the secondary conductors of a separately derived system as described in Section 250-5(d) i f the separately derived system is 5 kVA or larger and with 120 volts or more to ground. SUBSTANTIATION: Conductors on the load side of a separately ~-sy{tem are t r u l y service conductors and should terminate in service disconnecting means. By l i f n i t i n g this requirement to 5 kVA and larger separately derived systems with 120 v o l t s or larger to ground we would be excusing the smaller separately derlved systems such as control c i r c u i t s , etc. from this service disconnect rule and be catching the separately derived systems used for premises wiring. PANEL ACTION: Reject. ~NEL COMMENT: The Panel does not agree that these are service conductors. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 2063 4- 46 - (230-43, Exception No. 2-(New)): Reject SUBMITTER: M. H. Lounsbury, Eastern Section IAEI ~DATION: Exception No. 2: Liquidtight flexible conduit may be used in dry or wet locations (for exposed work) following the requirements of Section 250-79 and Article 351. SUBSTANTIATION: Service raceways entering structures are many ~ 6 - 6 ~ n - ~ C e d with permanent obstructions. Theseconditions create serious installation problems. The problmn of making jogs, offsets and excessive use of conduit f i t t i n g s w i l l be eliminated. Through experience we are not aware of any problems or conditions involving the use of f l e x i b l e metal conduit and liquidtight flexible conduit. Presently in their use with ac equipment, etc. and proper bonding they have proven to perform safely as raceways. With this fact and the requirements for their proper installation they should be considered suitable for service raceways on the load side of meter equipments to overcome obstructions. PANEL ACTION: Reject. PANEL -#(]F~WC~NT: See Panel Comment for Proposal 4-39. V-Ol'~-~ ACTION: UnanimouslyAffirmative. 4- 52 - (230-71(a)): Accept Secretary's Note: I t was the acLion of the Correlating Committee that further consideration be given Lo Lhe comments expressed in the voting. SUBMITTER: CMP 4 RECOMMENDATION: Revise to read as follows: --~a) General. The service-disconnecting means for each service permitted by Section 230-2, for each set of service-entrance conductors permitted by the Exception Lo Section 230-3, shall consist of not more than six switches or six c i r c u i t breakers mounted in a single enclosure, in a group of separate enclosures, or in or on a switchboard. SUBSTANTIATION: To correlate with the changes made by Panel Proposal 4-24. PANEL ACTION: Accept. VOTE ON PANEL ACTION: - -ATFTR~A-Fr ~ E ~ : T NEGATIVE: Cock, [zydorek. COMMENT ON VOTE: STANBACK: The word "or" was in the Panel proposal after "Section 230-2," in the second line. The typographical error of omission should be corrected. Log # 1131 4- 47 - (230-47, Exception No. 2): Reject SUBMITTER: D. J. Christofersen, United Power Association RECOMMENDATION: Revise Exception No. 2 as follows: Exception No. 2: Load management conductors having overcurrent protection. Load management conductors are control circuit or switch leg conductors for use with special rate meters, such as water heater circuits and home heating or air conditioning systems. SUBSTANTIATION: Present NATIONAL ELECTRICAL CODEconsiders time switch conductors only. PANEL ACTION: Reject. PANEL COMMENT: The Panel feels that there is a significant ~ n ~ between class and number of conductors for the present Exception. Service conductors do not have overcurrent protection and could subject the smaller conductors to excessive currents in the event of a fault. VOTE ON PANEL ACTION: UnanimouslyAffirmative. 62 EXPLANATION OF VOTE: COCK: I am voting negative on this proposal to correlate with my comments on P~posal 4-24. I feel that Section 230-71(a) should be reworded to read as follows: Ca) General. The service disconnecting means, grouped in any one location, for each service or for each set of service-entrance conductors permitted, shall consist of not more than six switches or six circuit breakers mounted in a single enclosure, in a group of separate enclosures, or in or on a swltchboard. I feel that this will solve the basic problem that was intended to be solved by Proposal 4-24. IZYDOREK: To correlate with my negative vote of Proposal 4-24, i t will be necessary that Proposal 4-52 be revised to add "No. I : " after exception. 3. The proposed change specifies a multisection service switchboard construction which will enhance safety and r e l i a b i l i t y by: a. Reducing to a minimum the buswork unprotected by the service disconnect. b. Bringing more service-entrance boards under the provisions of Section 230-95, providing ground-fault protection. c. Making i t possible to deenergize more of the bus for safe maintenance. d. Limiting the locations of the service disconnects within a switchboard and making i t easier for the user, u t i l i t y and f i r e department personnel to locate the service disconnect under emergency conditions. e. The single main minimizes the number of load terminals exposed to unprotected line bus. PANEL ACTION: Reject. P-AITE'~--i~-#M~E-N~T: Panel feels this is a design problem and should not be made mandatory. VOTE ON PANEL ACTION: Log # 202 Reject SUBMITTER: Dan Leaf, Westlake Village, CA RECOMMENDATION: Revise the phrase "service-entrance conductors" to "service conductors." SUBSTANTIATION: The fine print note after the definition of "Service-Entrance Conductors, Underground System" in Article 100 indicate there are installations where there are no service-entrance conductors, per se. The definition of "Service Conductors" indicate the proposed wording would be more suitable to apply the requirements of this section. PANEL ACTION: Reject. PANEL COMMENT: Submitter is confusing service-entrance conductors with service conductors. VOTE ON PANELACTION: UnanimouslyAffirmative. 4- 53 - (230-71(a)): NEGATIVE: Stanback. EXPLANATION OF VOTE: ~{~CKS--f~F~6 with the proposer's substantiation. 4- 57 - (230-72(a)): Accept SUBMITTER: CMP 4 RECOMMENDATION: Delete: "for each service." --~~eption No. 1. Reidentify Exception No. 2 to be "Exception." SUBSTANTIATION: To correlate with the changes made by Panel oF rT~-~6~-~l ~ 2 4 . PANEL ACTION: Accept. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 717 4- 54 - (230-71(a)): Reject SUBMITTER: Wallace E. Palmer, Johnstown, OH RECOMMENDATION: Words "or for each set of service entrance conductors permitted by Section 230-2, Exception No. 3(b)" should be separated by parentheses or worded similar to 1978 Code. SUBSTANTIATION: Section 230-71(a) as worded in 1981 Code can ~-~TTy be misinterpreted to mean that the "only" condition that permits the use of six service disconnects is that which is stipulated in Section 230-2, Exception No. 3(b). PANEL ACTION: Reject. PANEL COMMENT: See Panel Action For Panel Proposal 4-52. Panel attempted to achieve the s~me purpose as the proposal. VOTE ON. P A N E L _ ~ L Unanimously Affirmative. Log ~ 1458 4- 58 - (230-72(a)): Reject SUBMITTERS: Leo Witz, Continental Electric Co. --B-TTI--~6~an, Chicago, IL Fred Smith, Elgin, IL Jim Meehan, New Haven, CT Anton Ganje, North Dakota State Electrical Bd. Kenny Gebert, Minneapolis, MN Bill Conrardy, Tile Conrardy Co. Robert P. Brooks, Chicago, IL Paul Moore, Paducah, KY Les Rinder, Chicago, IL Homer M. Lefler, Chicago, IL RECOMMENDATION: Amend Section 230-72(a) so as to read as follows: General. The service disconnects as defined and required in Section 230-71 for each service as permitted in Section 230-2 shall be grouped. Each disconnect shall be marked to indicate the load that i t serves. SUBSTANTIATION: I f our proposal for Section 230-2 is accepted t~re'w{l~F-~-e-no need For the exceptiols. Even i f our proposal is not accepted, there is no need for the exceptions since Section 230-72(b) takes care of the material covered in the two exceptions. PANEL ACTION: Reject. COMMENT: See Panel Action on Proposal 4-57. V d f ~ ACTIqN£ Unanimously Affirmative. Log # 1457 4- 55 - (230-71(a)): Reject SUBMITTERS: Leo Witz, Continental Electric Co. B i l l Hogan, Chicago, IL Fred Smith, Elgin, IL Jim Meehan, New Haven, CT Anton Ganje, North Dakota State Electrical Bd. Kenny Gebert, Minneapolis, MN Bill Conrardy, The Conrardy Co. Robert P. Brooks, Chicago, IL Paul Moore, Paducah, KY Les Rinder, Chicago, IL Homer M. Lefler, Chicago, IL RECOMMENDATION: AmendSection 230-71(a) by deleting therefrom the words, ~xception No. 3b." SUBSTANTIATION: I f our proposal for Section 230-2 is accepted te-F~-e-re-~Tl'T-Be-no Exception No. 3b. PANEL ACTION: Reject. PANEL COMMENT: See Panel Proposal 4-52. ~/'O'InL'-ON--P-~f{L ACTION: Unanimously Affirmative. Log # 401 4- 59 - (230-72(a), Exception No. 2): Reject SUBMITTER: Ronald S. Ludekens, Visalia, CA RECOMMENDATION: Revise Exception No. 2 to read as follows: ~R-~dRE-of the two to six service disconnecting means permitted in Section 230-71, when used FOR FIRE PUMPS, OR FOR EMERGENCY OR LEGALLY REQUIREDSTANDBYSERVICES shall be located sufficiently remote from the other disconnecting means for normal service to minimize the possibility of simultaneous interruption of supply. See Sections 700-12(e) and 701-10(e). SUBSTANTIATION: Two of the six possible sources of power for emergency ~dd-legally required standby services mentioned in Sections 700-12 and 701-10 are separate services or connections ahead of the service disconnecting means. Separate services per 700-12(d) and 701-10(d) are covered by the paragraph Following this one (230-72(b)). This proposed revision is attempting to c l a r i f y present field confusion and be in harmony with 700-12(e) and 701-i0(e). The word "permitted" has been revised to "shall/be" to be in harmony also. I have not included optional standby systems as defined in Article 702 because 702 does not require separation. IF the optional standby system is not a separate service allowed by 230-2, Exception No. 2, brat is frown the same service as the normal, then i t should be treated as one of the one to six service disconnects per 230-71(a). PANEL ACTION: Reject. . PANEL COMMENT: I t is the Panel's intent that only one disconnect be remotely located and intended only for f i r e pumps. VOTE_O_NPANEL ACTION: Unanimously Affirmative. Log # 1801 4- 56 - (230-71): Reject SUBMITTER: F. K. Kitzantides, NEMA ~NOATION: Revise as follows: roposed new text is in quotations) a) General. The service disconnecting means for each service or for each set of service-entrance conductors permitted by Section 230-2 Exception No. 3(b) shall consist of not more than six switches or six circuit breakers mounted in a single enclosure, in a group of separate enclosures or in or on a "single-section" switchboard. "The service disconnecting means for a multisection switchboard shall consist of not more than two (2) switches or circuit breakers." SUBSTANTIATION: 1. The use of multiple service disconnects often avoids the requirement for equipment protection by ground-fault protective equipment thru the use of service disconnects rated less than 1000 amperes each. 2. The service bus joints for multisection switchboards presently cannot be readily maintained because i t is generally not possible for the user to deenergize this bus as i t is not controlled by the switchboard's service disconnects. IR 63 until the stools gets so hot until no one can s i t on i t . Whenmy l i t t l e niece was being trained i t burned her bottom and she was afraid to go near the stool and is s t i l l afraid to use the t o i l e t . One of the inspectors told me not to ever leave the heat on in the bathroom not even for one hour and he is right, but I have been told by several people and the inspectors that i t is in the building code the heater can be installed that close to the stool. I hope you w i l l send someone to see this. We realize i t is cheaper and easy to i n s t a l l these very needed f i x t u r e s on the outside. We think of our health and safety. We do hope this code w i l l be changed although i t w i l l not help us. Please consider our health and safety. Last sunwller someone turned all the current o f f in one of our neighbor's home. The police were call and turned i t back on we Feel that i f the Fuse box and switch box were inside this would not have happened. The locks can easily be torn o f f the fuse boxes. I hope to hear from you soon. PANEL ACTION: Reject. PANEL COMMENT: The Panel feels that this is not a proposal and is design problem. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 402 4- 60 - (230-72(b)): Reject SUBMITTER: Ronaid S. Ludeken, Westinghouse Electric Corporation ~ATION: Revise as follows: Additional Service Disconnecting Means. THE ADDITIONAL SERVICES WITH THE CORRESPONDINGONE TO SIX DISCONNECTINGMEANS for f i r e pumps or f o r emergency, legally required standby, or optional standby services permitted by Section 230-2 shall be installed s u f f i c i e n t l y remote from the one to six service disconnecting means f o r normal service to minimize the p o s s i b i l i t y of simultaneous interruption of supply. See Section 700-12(d) AND SECTION 701-10(d). SUBSTANTIATION: Section 230-2 discusses more than one service as ~f6~s-~GO-12(d) and 701-i0(d) but 700-12(e) and 701-10(e) discuss connections made ahead of the service disconnecting means. The present wording allows f o r confusion. I see continued requests f o r 6 service disconnects f o r one service plus one or more additional service disconnecting means For emergency from this same service, There should be a maxim~n of 6 disconnects per service and no more. My proposed changes to 230-72(a),. Exception No. 2 should also assist in c l a r i f y i n g the ~nergency disconnects from the same service. PANEL ACTION: Reject. COMMENT: The Panel does not intend to l i m i t the number of disconnects as proposed. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 708 4- 64 - (230-72(c)): Reject SUBMITTER: Robert L. Rodecker, Protective Inspectors RECOMMENDATION: The service disconnecting means "of 200 amperes ~-shal'l" be installed either (inside) or outside of a building or structures at a readily accessible location nearest the point of entry of the service-entrance conductors. Material to be added in quotations. Material to be deleted in parentheses. S_U~STANTIATIQN: I would like to suggest NEC Section 230-72(c)be changed to require a main disconnect on all service installations 200 amperes or less at the meter or point of attachment to the structure. This would eliminate the hassle for the electrical inspector, as well as the contractors, on location of a main of an remodel or new single-family dwelling. I t would simplify this section of the Code and provide safety in many instances of~an old structure where a main was not required or is in an impossible location to change. PANEL ACTION: Reject. PANEL COMMENT: Panel feels that 200 amperes is an arbitrary break point ~ y do not agree with the substantiation. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 479 4- 61 - (230-72(b)): Reject SUBMITTER: George W. Flach, New Orleans, LA ~ATION: I d e n t i f i c a t i o n of wording to be deleted: ", or optional standby s e r v i c e s . . . " SUBSTANTIATION: An optional standby system does not share the same status as emergency, and l e g a l l y required standby systems. Optional standby systems are s t r i c t l y f o r the convenience of the user and are limited to on-site generation. The recognition of an optional standby service is being used to negate the six disconnect r u l e . PANEL ACTION: Reject. PANEL COMMENT: I t is the Panel's intent to include optional standby systems. See Section 230-2, Exception No. 2. VOTE ON PANEL_ACTION." Unanimously Affirmative. Log # 203 4- 62 - (230-72(c)): Reject Secretary's Note: I t was the action of the Correlating Committee that further consideration be given to the co~nents expressed in the negative voting. SUBMITTER: Dan Leaf, Westlake Village, CA RECOM~NOATION: Revise the phrase "service-entrance conductors" t o "service conductors." SUBSTANTIATION: The fine print note after the d e f i n i t i o n of Tr~-ervice-Entrance Conductors, Underground System" in A r t i c l e 100 indicates there are installations where there are no service-entrance conductors, per so. The definition of "Service Conductors" indicate the proposed wording would be more suitable to apply the requirements of this section. PANEL ACTION: Reject. PANEL COMMENT: The Panel's intent is to be service-entrance conductors. VOTE ON PANEL ACTION: AFFIRMA'TfVC[ ' - f J - - NEGATIVE: Izydorek, Stanback. EXPLANATION OF VOTE: IZYDOREK: I agree that Proposal 4-62 should be accepted on the basis of the Panel's Action of Proposal 4-57. STANBACK: Acceptance of the proposal would be consistent with the Panel Action on Proposal 4-57 and I agree with the proposer's substantiation. Log ~ 974 4- 65 - (230-72(c)): Accept SUBMITTER: R. L. Hartloff , Southwest Division Ohio Chapter IAEI RECOMMENDATION: Delete sub paragraph (c) from Section 230-72, ~-(~-~o-~'#i-6~of'-Disconnects" and reinsert under Section 230-70, "General," after the f i r s t sentence. SUBSTANTIATION: The present location of this requirement under "Gro~isconnects" implies that this subparagraph applies to multiple (two to six) service disconnecting means only and not to a single (one) main service disconnect. PANEL ACTION: Accept. ~-~N--I~-A-N'-E'L ACTION: Unanimously Affirmative. Log # 1617 4- 66 - (230-72(c), Exception-(New)): Reject SUBMITTER: Richard B. Boyd, Jr., E l l i s Cannady Chapter IAEI RECOMMENL~TION: Add the following as an Exception to Section Exception: Where service-entrance conductors are run to each occupancy of multiple-occupancy buildings, the service disconnecting means permitted by Section 230-71 shall be located at or within the occupancy service. SUBSTANTIATION: To provide c l a r i f i c a t i o n and consistency in the p ~ C 6 d nd6~er and location of the service disconnecting means. PANEL ACTION: Reject. COMME'NT: See Panel Proposals 4-24 and 4-52. VOTE ON PANEL ACT[ON~ Unanifnously Affirmative. Log # 169 4- 63 - (230-72(c)): Reject SUBMITTER: Mildred Carlton, Durham, NC ~ATION: "None" uBS ' "O-B-STA-NTIATION: I am writing in regards of the Fuse boxes and on and o f f switches f o r lights and heat in our cofmnunlty. We have lots of problems with our lights and heat going o f f anytime of the night and day. We have disabled people in our con~nunity. I have been in for more than two years and I have been advised by several doctors not to l i f t more than ten pounds, when my lights and heat goes o f f I w i l l have to go outside my home and unlock the fuse box on the outside of my home and unlock my. storage room door in or to t r i p the on and o f f switch. I can not see with no l i g h t s . I f the fuse box and on and o f f was inside maybe [ oDuld feel iny way and I wouldn't have to unlock my Fuse box and my storage room ~oor. Last year when the snow was up to our door k~)bs, I had to stay in my home f o r hours u n t i l one o f my neighbors was kind enough to send her son to dig the snow f o r me. The snow had to be removed f o r more than t h i r t y feet and i t took more than t h i r t y minutes to do so. The heater in my bathroom is so close to the t o i l e t stool Log # 647 4- 67 - (230-72(d)): Accept SUBMITTER: J. H. Kassebaum, Eli L i l l y and Company RECOMM~NDI~T.ION: Add the word "service" between the words "his" and "disconnecting" so the text would read: In a multiple-occupancy building, each occupant shall have access to his service disconnecting means. SUBSTANTIATION: This change improves c l a r i t y and continuity within this section. PANEL ACTION: Accept. VOTE ON PANEL ACTION: Unanimously Affirmative. 64 SUBSTANTIATION: (Wording taken from NEMAStandard K.S. i-4.62.) --I~66ff~nlca-FcaT-'Tnterlocking systems have been in use f o r many years on all types of disconnect switches. Even the 115 volt, 30 ampere, two-fuse disconnect associated with the turn of the century knob and tube system had an interlock which precluded opening the fuse plug access door while the current was on. A present day manufacturer insists that interlocking is not required even though the equipnent is subject to ready access by the public and of a moderate ampacity (600 amperes) and f a u l t current potential (15000+). PANEL ACTION: Reject. g ~ T : See Panel Comment for Proposal 4-71. VOTE ON PANEL ACTION: --AFTTITMATIVI~.'T NEGATIVE: Niedermeyer. EXPLANATION OF VOTE: ---I~TE'~RMEYER: See comment on Proposal 4-71. Log # 648 4- 68 - (230-74): Accept SUBMIl-[ER: J. H. Kassebaum, Eli L i l l y and Company RECOMMENDATION: Add the word "service" between the words "Each" an--6-d-m~Tsc6n6ecting '' and between the words "ungrounded" and "conductors" and add the words "from the premises wiring system" so the text would read: Each service disconnecting means shall simultaneously disconnect all ungrounded service conductors from the premises wiring system. SUBSTANTIATION: This change improves c l a r i t y and continuity with ~ct~6ns within this Article. PANEL ACTION: Accept. PANEL ACTION: Unanimously Affirmative. Log # 649 4- 69 - (230-76): Accept SUBMITTER: J. H. Kassebaum, Eli L i l l y and Company ~-Eq~b~-'N-DATION: Add the word "service" between the words "The" and "disconnecting" and between "ungrounded" and "conductors" so the text would read: The service disconnecting means for ungrounded service conductors shall consist of . . . (remainder of text remains unchanged) SUBSTANTIATION: This change improves c l a r i t y and continuity with other T6ctFon's with this Article. PANEL ACTION: Accept. VOTE--OIT~L ACTION: UnanimouslyAffirmative. Log # 161 4- 73 - (230-79(c)(i)): Reject SUBMII-FER: Dan Leaf, Westlake Village, CA RECOMMENDATION: Insert the word "net" before the word "computed." SUBSTANTIATION: Chapter 9, Example 1 indicates loads before application of dBnand factors as "computed" loads, and after application of demand factors as "net computed" loads. This proposal would provide for consistency between the exanple and the text. PANEL ACTION: Reject. ~ f ~ T E I _ ~ T : See Panel Co~nent for Proposal 4-37. CO~-~ACTION: Unanimously Affirmative. Log # 650 4- 70 - (230-77): Accept SUBMI1-FER: J. H. Kassebaum, Eli L i l l y and Company RECOM~ZNDATION: Add the word "service" between the words "The" and "disconnecting" so the text would read: The service disconnecting means shall plainly indicate whether i t is in the open or closed position. SUBSTANTIATION: This change improves c l a r i t y and continuity with other " ~ of this Article. PANEL ACTION: Accept. VOTE ON PANELACTIqN~ Unanimously AFfirmative. Log # 1459 4- 74 - (230-82): Reject SUBMITTERS: Leo Witz, Continental Electric Co. Bill Hogan, Chicago, IL Fred Smith, Elgin, IL Jim Meehan, New Haven, CT Robert P. Brooks, Chicago, IL Paul Moore, Paducah, KY Les Rinder, Chicago, IL John W. Ericksnn, Boltswitch, Inc. Homer M. Lefler, Chicago, IL REC~),~MENOATION: Amend Section 230-82 so as to read as Follows: 230-82. Equipment Connected to Service-Entrance Conductors on the Supply Side of the Service Disconnect. Equipment shall be permitted to be connected to the supply side of the service disconnecting means only under the following conditions: (a) as cable limiters or other similar current-limiting devices; (b) meters rated no more than 600 volts nominal wheo all p~etal housings and service equipment are bonded together and grounded as is required in Article 250; (c) equipment identified for connection ahead of the service disconnecting means such as instrument transformers, high impedence shunts, surge protection devices, time switches and surge arresters; (d) as taps supplying time switches as provided for in Section 230-94; and (e) f i r e and sprinkler alarm systems i f provided with service equipment and installed in confon~lance with the requirBnents for service-entrance conductors." SUBSTANTIATION: This section is another example of one in which the "Exceptions" continue to grow like "weeds" and we begin to lose sight of the original rule. Conductors ahead of the service disconnecting means are generally electrically unprotected. The available fault current at that particular point can be anything from a few amperes all the way up to 200,000 amperes. Doing away with the "Exceptions" will make i t necessary for any additional provisions For installation ahead of the service disconnection means to be substantiated by convincing evidence that i t has be~ tested and is identified as suitgble for installation ahead of the disconnecting means. We did not mention what is presently "Exception No. 2" since the material and equipment described and located in that Exception is really service equipment. As such i t stands on its own merits. We also did not mention emergency systems, standby power syst~ns or f i r e pumps since they are more than adequately covered in other sections of the Code. We s~uld suggest that as long as Code-Making Panel 3 is considering this proposal and since i t may get some support that they also consider doing the s~ne thing in Section 230-94. PANEL ACTION: Reject. g~E'L--~OI~T~']~T: The intent of the Panel is to state the basic rule and to permit the Exceptions. See Panel Comment for Proposal 4-20. VOTE ON PANELACTION: Unanimously Affirmative. Log # 394 4- 7"1 - (230-78): Reject SUBMITTER: Kenneth L. Gebert, City of Minneapolis, MN ~ATION: Amend Section 230-78 by adding a second sentence as follows: ' I f the disconnecting means does not include a dead front device, the box cover and switch operating mechanism shall be mechanically interlocked so that the main cover of the cabinet (i) is normally prevented from being opened when the switch contacts are in a closed position, and (2) the switch contacts are normally prevented from being closed when the cover of the switch cabinet is open. (wording taken from NEMAStandard K.S. 1-4.62) SUBSTANTIATION: Mechanical interlocking systems have been in use f o r many years on all types of disconnect switches. Even the 115 volt, 30 ampere, two fuse disconnect associated with the turn of the century knob ahd tube system had an interlock which precluded opening the fuse plug access door while the current was on. A present day manufacturer insists that interlocking is not required even though the equipment is subject to ready access by the public and of a moderate ampacity (600 ampere) and fault current potential (15000+). PANEL ACTION: Reject. PANEL COMMENT: Proposal adds nothing. All externally operable switches are of the dead front type by definition. VOTE ON PANEL ACTION: AFFIRMATIVE: 14 NEGATIVE: Niedermeyer. EXPLANATION OF VOTE: ~ R N I E ' Y ~ R ~ - - [ - d d n ' t agree that the proposal adds nothing - the proposal requires an interlock when fuses are not dead when the door is opened. This proposal requires either dead fronting the fuse while door is open or provide a mechanical interlock. This will assure that untrained persons will have to pull the switch handle before access to the fuses are possible. The existing "dead front" requirements s t i l l allow'access to live fuses. Log # 1895, 1277 4- 72 - (230-78): Reject SUBMI1-FERS: B. Auger/H.B. Love, Michigan Chapter IAE'I (1895) ----~-AL~-I--~77) RECOMMENDATION~ Amend Section 230-78 by adding a second sentence as follows: I f the disconnecting means does not include a dead-front device, the box cover and switch operating mechanism shall be mechanically interlocked so that the main cover of the cabinet (1) is normally prevented from being opened when the switch contacts are in a closed position,.and (2) the switch contacts are normally prevented from being closed when the cover of the switch cabinet is open. 65 Log # 1460 4- 79 - (Section 230-83): Accept in Principle Secretary's Note: I t was the action of the Correlating Committee that further consideration be given to the comments expressed in the negative voting. SUBMITTER: Leo Witz, Continental Electric Co. ~ 1 " ' H ' o g a n , Chicagu, IL Fred Smith, Elgin, IL Jim Meehan, New Haven, CT Anton Ganje, North Dakota Kenny Gebert, Minneapolis, MN Robert P. Brooks, Chicago, IL Paul Moore, Paducah, KY Les Rinder, Chicago, IL John W. Erickson, Boltswitch, Inc. Homer M. Lefler, Chicago, I~ RECOMMENDATION: AmendSection 230-83 to read as follows: ~30-83. Transfer Switches. Transfer switches shall operate such that all ungrounded conductors of one source of supply are disconnected before any ungrounded conductors of the second source is connected. Where manual equipment identified for the purpose or suitable automation equipment is utilized two or more sources shall be permitted to be connected in parallel through transfer s~itches. SUdSTANTIATION: I t seems that we ought to set up a POSITIVE ~ n T as a rule and not start with a hypothetical set of circumstances. In the "Exception" we permit what is one of the most common electrical practices in major electrical installations yet we tell the local inspector that he has to make the judgement concerning the most d i f f i c u l t type of parallel operation; that instance where you must use manual control. Why not make the ;nanufacturer responsible f~r having his ~qJipmeflt listed for such use? ~'ANEL ,~CTION: Accept in Principle. In t--h-e-second paragraph, f i r s t sentence, Insert a comma after "purpose" and before "or." In the second paragraph, f i r s t sentence, replace the word "automation" with "automatic." PANEL COMMENT: Editorial clarification. VO--TE ON PKNECACTION: ~4ATI3/C~'I~-'" NEGATIVE: Izydorek, Stanback. EXPLANATION OF VOTE: --I'~YU~ITEl~:-Tam-~-n-c-~anging my vote to negative For Proposal 4-79 since the second paragraph is in conflict with the First paragraph. Closed transition switching would be needed. STANBACK: Intent of proposal may be proper; but as written, the First and second paragraphs conflict with each other. Closed transition switching may be necessary. Log # 515 4- 75 - (230-82, Exception No. 4): Reject SUBMITTER: J. K. Daugherty, Flint, MI RECOMMENDATION: Add to the end of the sentence: "rated ikV and over.~ . . . . . . . SUBSTANTIATION: The present Exception will permit surge arresters rat-'at-e-d-Fe-s~'t~an 1000 volts to be located on the supply side of tile service disconnect. This is in direct opposition to Section 281)-22. PANEL ACTION: Reject. !~-A]TE'L---CT6~IE~T: Section 280-21 permits connection on the supply side. VOTE ON PANELACTION: UnanimouslyAffirmative. Log # 403 4- 76 - (230-82, Exception No. 5): Reject SUBMITTER: Ronald S. Ludekens, Westinghouse Electric Corporation ITE"C'[]]~@L'~OATION: Delete "time switches," Add at end of sentence "and in accordance with 700-12(e) or 701-i0(e)." SUBSTANTIATION: "Time Switches": is the only item listed of a nonemergency nature. This is inconsistant. The 1981 NEC Handbook notation on this paragraph tries to ignore the time switch and then refers the reader to Section 700-12. This is appropos. Section 700-12(e) and Section 701-10(e) should be o f f i c i a l l y referenced to provide continuity with requirements For sufficiently separated connections to prevent simultaneous interruption of supply. Section 700-12(e) and Section 701-I0(e) already appropriately refer back to Section 230-82. I f the need is there for time switches, then i t should be ,~ne of the regular one to six service disconnects allowed by Section 230-71(a). A similar change ~ill be required for Section 230-94, Exceptions Nos. 3 and 4. PANEL ACTION: Reject. P~-N~NT: The Panel feels time switches were intended. ~/'OI~--OI~-F#/~EC ACTION: UnanimouslyAffirmative. Log # 917 4- 77 - (230-82, Exception No. 6-(New)): Reject SUBMII-FER: Ad Hoc Subcommittee on Solar Photovoltaics ~DATION: Add Exception No. 6 to Section 230-82, as follows: ~xception No. 6: Solar photovoltaic systems in accordance with Section 690-14, Exception No. 2 and Section 690-64." SUBSTANTIATION: See substantiation for proposed Section 690-14, ~66N'o[-2 and Section 690-64. PANEL ACTION: Reject. PANEL COMMENT: See Panel Action on Proposal 4-78. ~OfE'-~-N--F~NI~-C ACTION: Unanimously Affirmative. Log # 86 4- 80 - (230-83): Reject SUBMI~ER: Victor S. Whitcemb, Brooks, ME . RECOMMENDATION: Add a new paragraph to Follow the Exception as Log # 908 4- 78 - (230-82, Exception No. 6-(New)): Accept Secretary's Note: I t was the action of the Correlating Committee that further consideration be given to the comments expressed in the voting. SUBMITTER: Ad Hoc Subcommittee on Cogeneration of Power (TE-'C~}I~n~EITDATION: Add Exception No. 6 to Section 230-82. Exception No. 6: Interconnected electric power production sources. See Article 705. SUBSTANTIATION: For correlation with proposed Section 705-6. To permit another electric power production source to be connected to the supply side of the premises service disconnect as required by Section 705-6. Additional Ad Hoc Subcommittee discussions related to not offering an Exception No. 6, but instead expanding Exception No. 5 as indicated: "Taps used only to supply timo switches, circuits For emergency systems, stand-by power systems INTERCONNECTED ELECTRIC POWER PRODUCTION SOURCES, f i r e pump equipment, and f i r e and sprinkler alarms i f provided with service equipment and installed in accordance with the requirements for service-entrance conductors." Such an Exception, whether within Exception No. 5 or a new No. 6, is needed to accommodate Section 705-6. Other cross references presupposed that such an Exception would be No. 6 since the existing Exception No. 5 seems to relate ~nore to occasional usage. PANEL ACTION: Accept. ON PANELACTION: Unanimously Affirmative. COMMENT ON VOTE: ~ D E ' R ~ f ~ R { - - I am voting affirmative i f the words "See Articles 690 and 705" are included. We rejected Proposal 4-77 by referring i t to this proposal, but we did not include solar photovoltaics in the reference. Means shall be provided to co~npletely isolate the transfer switch equipment. The use of isolating switches shall not be required where there are other ways of de-energizing the equipment for repairs or replacement without loss of power to the building or structure. SUBSTANTIATION: Manytimes, specifically hospitals where total s~uEcf6~ is 1:npossible, ,neans should be. provided to de-energize transfer switch equipment for maintenance or replacement. In health care f a c i l i t i e s , by-pass conductors are installed, and transfer switches are removed and replaced under live and dangerous conditions. See co~npanion proposal for Section 700-6. PANEL ACTION: Reject. COMME'r~T: The Panel feels that this is an installation specification problem. VOTE ON PANELACTION: UnanimouslyAffirmative. Log # 1679 4- 81 - (230-84(a)): Reject SUBMITTER: Charles "Mike" Holt, Concepts in Electricity Inc. RECOM__~NDATIQN: 230-84(a) Where More than o,le building or other structure is on the same property and under single management, each building or other structure served, shall be provided with means for disconnecting all ungrounded conductors, "installed either inside or outside of the remote buildings." (Location shall be in accordance with Section 230-72(e) and (d).) Material in quotations added and material in parentheses deleted. SUBSTANTIATION: Disconnect must be on re[note building, however, by the reference to Sections 230-72(c) and (d)many persons interpret this to mean the disconnect can be located at original building with other service equipment. PANEL ACTION: Reject. g/II~L--C'[FR-r;L[q~T: The Panel feels that i t is clear. VOTE ON PANEL ACTION: Unanimously Affirmative. 66 Log # 1658 Reject SUBMITTER: Charles "Mike" Holt, Concepts in Electricity Inc. RECOMMENDATION: Add (new) paragraph to 230-84(a): ~ o - ~ i x disconnecting means are used for this purpose, all shall be grouped and each disconnect shall be marked to indicate the Ioad served." SUBSTANTIATION: This section gives the impression that only one disconnect c~6 be used. At remote buildings by identifying that two to six disconnecting means can be used, this will provide a clearer understanding for disconnecting on separate buildings. PANEL ACTION: R e j e c t . IIA-NEL COMMENT: See Panel Proposal 4-57. Already covered in Section 110-22. VOTE ON PANEL ACTION: UnanimouslyAffirmative. 4- 82 - (230-84(a)): • Log # 1342 4- 86 (230-90(a)): Reject SUBMITTER: Steve Schaffer, Bussmann Division, McGraw Edison Company RECOIv~IENDATION: Add the following sentence to the end of paragraph 230-90(a) Ungrounded Conductors: Service-entrance conductors that penetrate cembustible walls, floors, or ceilings shall have overcurrent protection ahead of the point of penetration. SUBSTANTIATION: Fires have occurred when unprotected service conductors penetrate combustible materials. See attached substantiating data. (Note: A copy of substantiating data available from NFPA on request.) PANEL ACTION: Reject. PANEL COMMENT: Insufficient substantiation to support proposal. .VOTE ON PANEL ACTION: AFFIRMATIVE: 14 NEGATIVE: Edwards. EXPLANATION OF VOTE: --~DWARDS: Believe this subject deserves additional study. Perhaps formation of a TSC would be in order. 4- 83 - (230-84(a)): Accept Secretary's Note: I t was the action of the Correlating Committee that further consideration be given to the co~nents expressed in the negative voting. SUBMITTER: CMP 4 ~DATION: Change last sentence to read as follows: Location shall be in accordance with Sections 230-70 and 230-72(c). SUBSTANTIATION: To c o r r e l a t e with Panel Action on Proposal 4-65. !rA-RI[[-~CFI-O~ Accept. ~N~-~L ACTION: AFFIRMATIVE: 14 NEGATIVE: Bowles. EXPLANATION OF VOTE: BOWLES: Reference to Section 230-72(c)should be deleted since the wording in t h i s section was moved to Section 230-70 by CMP 4's acceptance of Proposal 4-65. Log # 651 4- 84 - (230-84(a), Exception-(New)): Accept in Principle SUBMI1-FER: J. H. Kassebaum, Eli L i l l y and Company RECOF~IENDATION: Add an Exception after the last sentence to read: Exception: The provisions of this section shall not apply to buildings or other structures containing integrated electrical systems. SUBSTANTIATION: To correlate with Article 685, allowing for a safe and orderly shutdown. PANEL ACTION: Accept in Principle. Revise to read: "Building or other structures qualifying under the provisions of Article 685." PANEL COMMENT: Editorial Clarification. VOTE ON PANEL ACTION: Unanimously Affirmative. ~'~-~dfE~ MUSKA: This proposal is needed, i f Proposal 4-99 (where primary is to be considered as the Service rather than the Secondary) is accepted. In large capacity buildings containing several transformer vaults, this would require a service disconnect at outdoor structure, service disconnect at building entrance plus a service disconnect at high voltage cubicle adjacent to transformers. This unneeded duplication of service disconnects was avoided in the past where only the secondary conductors were considered as the service conductors. This duplication would also arise on multi-building installations under single management. However, the original proposal should be preceded with the following words: "large capacity multi-building installations under single management, and." Log # 311 4- 87 - (230-90, Exception No. 5): Reject Secretary's Note: The Correlating Cemnittee refers this proposal t6 the NFPA Committee ~n Centrifugal Fice Pumps For information. SUBMITTER: Samuel S. Levinrad, Veterans Administration RECOMMENDATION: Correlate the referenced paragraph with NFPA 20 entitled "Centrifugal Fire Pumps." Specifically Paragraph 6-3.3.2. Proposed wording: Exception No. 5 Fire Pumps. Where service to a f i r e pump is provided, no overcurrent protection shall be provided i f conductors are sized For the locked rotor current of the main pump, the jockey pump plus auxilaries. SUBSTANTIATION: The referenced paragraph indicates that when ~s'areoutside buildings the rating or setting of overcurrenL devices shall be based on the locked rotor currents of the f i r e pump, jockey pump and accessories. The wording suggests that under cerltain circumstances, f i r e i)u,np feeders ,nay be routed through buildings without tile protection specified in 230-44 whereas NFPA 20 paragraph 6-3.3.2 requires this. Consequently, i t is not clear whether the setting should be based on a,npacity (125% of f u l l load) or locked rotor currents. Increasing the mnpacity to 600% and eliminating overcurrent protection will acknowledge the critical nature of the f i r e pump and c l a r i f y the requirements. PANEL ACTION: Reject. F~-Cl)l~lqEl]T: The Panel feels that the proposal is contrary to reco~mnended standards such as NFPA 20. VOTE ONPA~!KL~GT[qNE Unanimously Affirmative. ..... STANBACK: First word of Panel text revision should be "Buildings." Log # 1797 4- 85 - (230-84(a), Exception-(New)): Reject SUBMITTER: G. V. Cox, Chemical Manufacturers Association ITE'CDI~v[E'N~ATION: Add an Exception after the last sentence to read: "Exception: Where i t is assured that the disconnectin~ can be accomplished by establishing and maintaining safe switchlng procedures, the disconnecting means shall be permitted to be located elsewhere on the premises." SUBSTANTIATION: In many large f a c i l i t i e s such as medical, industrial, educational, and research of other cmnpus-type f a c i l i t i e s , secondary switches or breakers located at a transformer substation supply power to several buildings. Opening one of the switches or breakers deenergizes the feeder to one of the buildings. To require a second disconnecting means at each building is redundant, and may cause security or safety problems. This Exception recognizes large capacity, multi-building installations on premises under single management which have been operating safely in this manner for many years. PANEL ACTION: Reject. ~OM~'NT: The Panel feels the Exception is too broad. VOTE ON PANEL ACTION: Log # 232 4- 88 - (230490, Exception No. 5): Reject Secretary's Note: The Correlating Committee refers this proposal to the NFPA Committee on Centrifugal Fire Pumps for information. SUBMITTER: H. K. Glenn, Pacific Coast Electrical Association, Inc. REC__OMMENDATION: Second sentence: Overcurrent protection for f i r e pump services shall be selected or set to carry locked-rotor current of the motor(s) "for a period of not less than 20 seconds and not more than 30 seconds." SUBSTANTIATION: Manystates have "hi-rise" safety regulations which require a f i r e pump to be connected to a standby or emergency syStern as well as all the other l i f e safety equipnent. A normally sized generator could not stay on the line witb a f i r e pump on locked rotor current indefinitely and the result would be loss of power to all other l i f e safety equipment. I t would not be feasible to provide a generator large enough to carry locked rotor current of a f i r e pump motor. The 20 second minimum time on locked rotor, as recommended, is longer than normal and will provide time for the motor to overcome a problem with the pump i f i t is possible to do so. The 30 second maximum time reco}~nended will remove a stalled pump before the generator has stalled and will preserve the electrical integrity of the pump motor. ~ ~ T - - ~ - - - NEGATIVE: Kassebaum, Muska. EXPLANATION OF VOTE: KASSEBAUM: I feel the present wording requiring that a building disconnect for multi-building occupancies be installed either inside or outside a building NEARESTTHE POINT OF ENTRANCE of the conductor is not realistic for tile conditions described in the substantiation. B7 The 20 second minimum time is consistent with the requirements of NFPA 20, Section 7-4.2.7. See following proposal to NFPA 20: i . Section/Paragraph: 6-3.4.2 (NFPA 20, Centrifugal Fire Pumps) 2. Proposal (include proposed wording, or i d e n t i f i c a t i o n of wording to be deleted): Add to the sentence, before the bracket note, as follows: ---accessory current "in less than 30 seconds." 3. Statement of Problem and Substantiation f o r Proposal: This is consistent with Section 7-4.2.7 and will provide a measure of protection for a generator when a standby generation system is used for Life Safety Systems. PANEL ACTION: Reject. ~"A'NI~[--(~I~M~EFT: See Panel Comment for Proposal 4-87. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 798 4- 89 - (230-95(a), Exception No. 3-(New)): Reject SUBMITTER: Hy A. Bershad, The Staten Island Hospital ~NI)ATION: "Add" (New): # x c e ~ 3 : The provisions of this section shall not apply to a service disconnecting means f o r a Health Care F a c i l i t y where a non orderly shutdown w i l l introduce additional or increased hazards to patients or s t a f f . SUBSTANTIATION: Sudden interruptions of e l e c t r i c service to ITeal~-h-Care-Facility areas such as Operating and Delivery Suites, Coronary and Intensive Care Units, Cardiac Catheterization Labs, Clinical Laboratories, e t c . , may cause extraordinary hazards to patients and s t a f f . Since these f a c i l i t i e s are generally staffed 24-hrs/day, 7 days per week a more appropriate safeguard f o r the equipment would be a ground-fault indicating device permitting planned and rational shut-downs. PANEL ACTION: Reject. COMMENT: The Panel feels i t introduces more of a hazard by removing the requirement than does the nuisance t r i p p i n g . VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . COMMENT ON VOTE: BEARD: Alt~ugh I am voting to accept the Panel's action to reject this proposal, I do not agree with the Panel's comment. The Panel's comment that the proposal introduces more of a hazard by removing the requirement than does the nuisance tripping is t o t a l l y subjective. The Panel should address the concern of Health Care F a c i l i t y people by commenting that ti~e proposal is lacking in substantiation, i . e . , lack of specific case histories. SUBSTANTIATION: Sudden interruptions of electric service to Ee'aTZ~Icare'F~acility areas such as operating and delivery suites, coronary and intensive care units, cardiac catheterization labs, clinical laboratories, etc, may cause extraordinary hazards to patients and s t a f f . Since these Facilities are generally staffed 24-hrs/day, 7 days per week a more appropriate safeguard for the equipment would be a ground-fault indicating device permitting planned and rational shut-downs. PANEL ACTION: Reject. COM~ME'NT: See Panel Action For Proposal 4-89. "~df~-~.ACTI.ON:. Unanimously Affirmative. Log # 1337 4- 93 - (230-95(b)): Reject SUBMITTER: Paul Friemel, Maryland Heights, MD RECOMMENDATION: Delete the First Fine Print Note, paragraph immediately after 230-95(b) Fuses. SUBSTANTIATION: 230-95 d i s t i n c t l y states "service disconnecting neans r a ~ IO00A or more." The rating of the service disconnecting means is the key since a 1200A c i r c u i t breaker or switch can have lower ~pere rated overcurrent devices such as fuses or t r i p units which could be changed to a maximum ampere rating that the service disconnecting means can accommodate. This will remove the confusion existing in the f i e l d since 230-95 f i r s t paragraph, and the Fine Print Note tu 230-95(b) are in c o n f l i c t . PANEL ACTION: "Reject. F~E'-C-C"O-M--M~'-NT: The fine print note adds c l a r i f i c a t i o n . VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 1077 4- 94 - (230-95(c)): Accept SUBMITTER: Frank K. Kitzantides, NEMA RECOMMENDATION: Add the words "on site" to the end of the f i r s t sentence. Delete the word "approved" from tne second sentence to read: The ground-fault protection system shall be performance tested when f i r s t installed on site. The test shall be conducted in accordance with instructions which shall be provided with the equipment. A written record of this test shall be made and shall be available to the authority having j u r i s d i c t i o n . SUBSTANTIAFION: I t has been contended by some that testing by U1e m a 6 u ~ c C u ~ of ground-Fault pr,)~ectiun eq,Jlpnent prior to shippin3 satlsFieJ this "performance testing." Proposal number 45 to CMP-3 for the 1978 N.E.C. clearly identified the problem as a f i e l d problem. The addition of the ~.mrds "on site" is proposed in the hope tht the text will more clearly indicate this. By d e f i n i t i o n "approved" is "acceptable to the authority having jurisdiction." More clearly, these instructions,should be a part of listed or labeled ~luipnent and ~.).Jld F~ll within the sc,~;e of Section llO-3(b). By elimination of the word "approved," the r e s p o n s i b i l i t y f o r evaluation and l i s t i n g of the instructions would f a l l to those q u a l i f i e d to make such judgements, the "Qualified Testing Laboratory." PANEL ACTION: Accept. ON"PANE'L ACTION: Unanimously A f f i r m a t i v e . Log # 1109 4- 90 - (230-95(a), Exception No. 1, Note-(New)): Reject SUBMITTER: Mary Ann Kelly, American Hospital Association ~r~-c'O-~NDATION: Add Note after Exception No. 1: Note: Health Care F a c i l i t i e s may u t i l i z e this Exception i f a nonorderly shutdown will introduce increased hazards to patients. SUBSTANTIATION: To c l a r i f y my submission made to Panel 17 ~TI?'ZT4"CaT;~hfEh will allow health care Facilities to be exempted similarly to other industries. PANEL ACTION: Reject. PANEL COMMENT: See Panel Comment for Proposal 4-89. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 1517 4- 91 - (230-95(a), Exception No. 3-(New)): Reject SUBMITTER: George N. Webb, Johns Hopkins Hospital, Baltimore, MD R~ATION: Add a new Exception: Exception No. 3: The provisions of this section shall not apply to health care f a c i l i t i e s where such shut down will present a hazard to patients. SUBSTANTIATION: There has been sufficient experience with false ~-o-f-G'Fl equipment in health care f a c i l i t i e s by t r i v i a l Faults that this requirement should not apply to health care f a c i l i t i e s where loss of power may produce a l i f e threatening situati,)n. PANEL ACTION: Reject. PANEL COMMENT: See Panel Comment for Proposal 4-89. E ~ C ACTION: Unanimously Affirmative. Log # 1461 4- 95 - (730-95(c)): Reject SUBMITTER: William P. Hogan, Chicago, IL RECOMMENDATION: Amend Section 230-95(c) by the insertion of the ~fn'g" "s'en't'ence as the third sentence of the section: "Such test shall include the actual application of a Fault current on the sensing devi~es and shall not be merely the actuati,Jn of a test button which operates the nechalical Features of the disc,Jnnect." The re:nainder of the sectiun shall remain the s~ne as i t is. SUBSTANTIATION: I t should be obvious that there are manufacturers who are attempting to use the test button as an indication that the ground-fault protection system is in working order. I t is also well known that such is not the case. Unless the system is actually tested in such a way as to duplicate Fault conditions there is no way to know i f i t will actually work when called upon to do so. By actual test i t can be determined whether or not the device will operate within the time or current limits required. I t seems that everyone is sayin~ that this is the way to test, but i t is my opinion that safety will best be served i f i t is written into the Code. PANEL ACTION: Reject. P ~ : Panel feels i t would be impractical. See Panel Action on Proposal 4-94. VOTE ON P.AN.E.L..A.CTIOI~- Unanimously A f f i m a t i v e . Log # 996 4- 92 - (230-95(a), Exception No. 3-(New)): Reject SUBMITTER: Hy A. Bershad, The Staten Island Hospital ~ATION: "Add" new Exception No. 3 to (a) Setting as Exception No. 3: The provisions of this section shall not apply to a service disconnecting means for a health care f a c i l i t y where a nonorderly shutdown will introduce additional or increased hazards to patients or staff. 68 EXPLANATION OF VOTE: ~:'"r'dd6"t'bel'ieve the Panel intended to delete the requirement of ground-fault protection on services rated 277/480 volt, 1000 amperes or more; however, with' the new proposed wording, the secondary conductors of a 13 kV to 277/480-volt transformer would no longer be classified as service conductors i f the service point was on the supply side of the 13 kV disconnect. In such an installation as described, the primary conductors w,~ulJ be classified as the service conductors and the secondary conductors would become Feeder conductors, requiring no ground fault protection as specified in Section 230-95. MUSKA: The concept is good, but more work is necessary before this proposal can be practicable. Because of the requirement in Section 230-84, that each building must have service disconnect, multibuilding complexes, such as industrial plants, hospitals and campuses, would have to qualify both their indoor and outdoor installations under the rigid requirenents of Article 230. This ~ u l d considerably increase the installation cost and Further widen the cost differential between an owner owned installation and a u t i l i t y owned installation. Log # 1255 4- 96 - (230-95(c)-(New)): Reject SUBMII-FER: IAEI ~ATION: Change (c) to (d) and add a new (c) to read: --CE~--A~Ie and audible means shall be provided to detect any connection or e l e c t r i c a l contact between the grounding and rounded c i r c u i t on the secondary side of the ground-fault sensor. UBSTANTIATION: Ground-fault protection is required by Code and serves as a very necessary device to protect equi~nent from damage or burn-down only when one is assured that other ground-fault return paths have not been established either accidentally or unintentionally. Just because a service has been tested according to Section 230-95(c) does not assure that the GFP equipment cannot be rendered ineffective at a later date by additional wiring or maintenance. In field testing i t has been found when the grounded conductor makes grounding contact on the secondary side of the ground-fault sensor the ground-fault protection equipment will not properly operate. PANEL ACTION: Reject. PANEL COMMENT: The Panel feels that i t is inappropriate and could ~d--~--a-t"aTse sense of security. VOTE ON PANEL ACTION: AFFIRMATIVE: 14 NEGATIVE: Niedermeyer. EXPLANATION OF VOTE: ~t=-~R~--rt-fs not a false sense of security to have audible visual i n d i c a t i o n that a ground f a u l t ( i n s u f f i c i e n t to actuate t r i p p i n g ) has occurred since the o r i g i n a l t e s t . Clearing the problem, at the time, could r e s u l t in preventing d e s t r u c t i v e • damage and costly shutdowns at a l a t e r date. ~ Log # 292 4- 100 - (230-201(a)): Reject SUBMII-FER: J. H. (Jim) Richards, Maryland E l e c t r i c a l Inspectors X-~s-r6 R_ECOM~ENDATION: Add. Subparagraph "Where the secondary conductors are considered as the service conductors under parts ( i ) through (5) of Section 230-201(a) disconnecting means shall not exceed six in number (except as permitted For f i r e pump or emergency service disconnects.) Each disconnecting means shall have an i n t e r r u p t i n g rating equal to or greater than the available f a u l t current. On wye-connected systems having more than 150 v o l t s to ground and not over 600 volts phase-to-phase, disconnecting means of 1000 amperes or more rating shall be provided with ground f a u l t protection as required by Section 230-95. SUBSTANTIATION: With e l e c t r i c u t i l i t i e s raising transmission and d i s t r i b u t i o n voltages an~ the present practice of bringing median voltages to step-down transformers of very low impedances within the b u i l d i n g , in metal clad gear, i t is extremely important that we provide protection from arcing f a u l t burndowns. This should be true f o r all sub-station remotely located separately derived systems. PANEL ACTION: Reject. PN--A'NTL-COMMZNT: Already covered in Section 230-200. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . Log # 233, 1076 4- 97 - (230-96): Accept SUBMITTER: H.K. Glenn, Pacific Coast Electrical Association, Inc. C~) Frank Kitzantides, NEMA(1076) RECOF~IENDATION: Delete Section 230-96. SUBSTANTIATION: The present text infers that service equipment Tovercurrent "Jevices) might deserve special consideration beyond that required in Section 110-16 without being specific. Section 110-16 does provide for working space and clearances For electrical equipment including service equipment. Section 384-2 also provides for "equipment space" when service equipment is of the configuration recognized as within the scope of Article 384. Where language can be eliminated from the Code without diminished effectiveness, i t should be. PANEL ACTION: Accept. V~OT~L ACTION: Unanimously A f f i r m a t i v e . Log # 646 4- I01 - (230-201(ai): Reject SUBMII-FER: J. H. Kassebaum, Eli L i l l y and Company RECOMME_NDATION: Add "for the building proper" so that the revised ~ e ' a ~ s " a s Yollows: (a) SecondaryConductors. The secondary conductors shall constitute the service conductors for the building proper where the step-down transformers are located as follows: . . .(rBnainder of text remains unchanged) SUBSTANTIATION: This clarifies the conditions which differentiate a building supply from a large capacity outdoor industrial substation. PANEL ACTION: Reject. F ~ : See Panel Action for Proposal 4-99. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 1353 4- 98 - (230-98, FPN-(New)): Reject SUBMII-FER: Melvin K. Sanders, Ankeny, IA RECOMMENDATION: Add Fine Print Note: See Section 110-9 for other than service requirements. SUBSTANTIATION: Manytimes service equipment is selected for the short-circuit current available at its supply terminals, and then all other downstream equipment is ignored in terms of selecting components to withstand short-circuit currents available at their respective installed locations. This would insure coordination of all components. PANEL ACTION: Reject. PANEL COMMENT: Reference to other than service equipment should be covered in the appropriate article. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 1798 4- 102 - (230-201(a), Exception-(New)): Reject SUBMII-[ER: G. V. Cox, Chemical Manufacturers Association RECOMMENDATION: Add the following Exception: ~e#t'iodC" The primary conductors shall be permitted to c o n s t i t u t e the service conductors in any of the above cases i f the primary load i n t e r r u p t e r switch or c i r c u i t breaker is capable of being opened or closed from a point either inside or outside of a building or other structure at a r e a d i l y accessible l o c a t i o n . " SUBSTANTIATION: This Exception recognizes large-capacity s~ngle-building i n s t a l l a t i o n s which have been operating safely according to this Exception f o r many years. The Exception a c t u a l l y provides greater safety f o r the person operating the switch. PANEL ACTION: Reject: PANEL COMMENT: See Panel Action f o r Proposals 4-99 and 4-107. ~ ~ ACTION: Unanimously A f f i r m a t i v e . 4- 99 - (230-201): Accept Secretary's Note: I t was the action of the Correlating Committee that further consideration be given to the co~mnents expressed in the negative voting and that the Panel be directed to c l a r i f y the Panel Action on this proposal. SUBMITTER: CMP 4 RECOMMENDATION: Delete the existing Section 230-201 and replace 1-Tt-h--C~ w -F6TI-6wi ng : 230-201. Classification of Service Conductors. All conductors on the load side of the service point which supply power to the service disconnecting means shall be classified as service conductors, regardless of whether they are on the primary or secondary side of a step-down transformer, SUBSTANTIATION: Clarifies the intent. PANEL ACTION: Accept. ON PANEL ACTION: NEGATIVE: Cock, Muska. 6g Log # 415 4- 103 - (230-201(b), Exception No. 2-(New)): Reject SUBMITTER: Donald H. Mclntosh, E.I. du Pont de Nemours and Co. RECOMMENDATION: Exception No. 2: The primary conductors shall be ~6~'to'constitute the service conductors in any of the conditions of Section 230-201(a) i f the primary load interrupter switch or circuit breaker is capable of being opened or closed from a readily accessible location either inside or outside of the building or other structure served nearest the point of entrance of the service-entrance conductor, and meeting the other requirements of Part H. SUBSTANTIATION: Part K is worded in such a way as to cause widely ~ng'~nterpretations by the various inspection authorities. I t must be clarified so the Code can be equitably applied in all jurisdictions. The intent of Section 230-72(a) is to limit the number of service disconnect devices that must be operated, to six, in case of an emergency. This can be accomplished by any of the following: (a) Not more than six switches or circuit breakers mounted in a single enclosure, in a group of separate enclosures, or in or on a switchboard. (b) A single main switch or circuit breaker having adequate continuous current rating, interrupting rating, and capable of being closed on a fault equal to or greater than the maximum available short circuit current in the circuit at its supply terminals. (c) A single main switch or circuit breaker on the primary of the main transformer provided this device has adequate continuous current rating, capable of interrupting transformer f u l l load current, and capable of being closed on a Fault equal to or greater than the maximum available short circuit current in the circuit at its supply terminals. These disconnecting devices can be manually operated when they are in the same building as the transformer and secondary disconnect devices and qualified personnel are available to operate these devices. Where the primary disconnecting devices are remote from the secondary disconnects or where there are no qualified persons available to operate them, the primary disconnect device shall be of the stored energy type and capable of being tripped electrically from a reliable energy source such as a shunt t r i p supplied from a readily accessible pushbutton location. PANEL ACTION: Reject. FAITE~---(TOMNIE'NT: See Panel Action on Proposals 4-99 and 4-107. VOTE ON PANEL ACTION: Unanimously Affirmative. PANEL ACTION: Reject. P ~ : See Panel Action for Proposal 4-99. VOTE ON PANEL ACTION: - "~'FIR-M~TfI V ' E ' : T NEGATIVE: Cock. EXPLANATION OF VOTE: COCK: This proposal should be accepted to c l a r i f y the existing wording of Section 230-201 because i t clearly identifies the service conductors of high voltage installations. In a high-voltage installation where the service point is upstream from the transformer which steps down the voltage to an excess of 600 volts, i t is clear that the primary conductors, on the load side of the service point, are the service conductors and all other Code sections apply as to disconnect and overcurrent devices. The secondary conductors then become feeder conductors requiring all the rules of overcurrent protection until they reach another transformation to utilization voltage less than GO0 volts. Part (b) of this proposal then specifies that the secondary conductors then become service conductors too and require disconnecting means, overcurrent devices, and ground-fault protection providing the service :Beets the requirements of Section 230-95. This proposal keeps all present Code requirements plus the additional coverage for all conductors and equipment on the load side of the service point. The proposal accepted by the Panel (new Proposal 4-99) would change the requirement For ground-fault protection, Section 230-95 (see negative comment on Proposal 4-99.) Log # 1019 4- 105 - (230-202(b)): Accept SUBMITTER: H. F. Van der Voort, Carlon An Indian Head Company RECOMMENDATIONi ChangeSection 230-202(b) by eliminating "where encased in not less than 2 inches (50.8 mm) of concrete" following "(3) in rigid nomnetallic conduit" in the third line of this paragraph. SUBSTANTIATION: Other sections of the National Electrical Code were changed in the 1981 edition to permit rigid nonmetallic conduit to be used in over 600 volt applications without encasement in 2 inches of concrete. The elimination of this requirement was based on a number of tests that prove Schedule 40 rigid PVC conduit is suitable in applications where the potential exceeds 600 volts. High voltage, high current short-circuit tests were conducted on 4 inch Schedule 40 Rigid PVC Conduit under a wide range of conditions. The results prove that the conduit exhibits l i t t l e or no signs of deterioration or physical damage due to the explosions and high temperatures. The report of the results of this work at General Electric Company's Short-Circuit Laboratory at P i t t s f i e l d , Mass. is attached. Additional supporting data is included in the report "Normal and Short Circuit Operating Characteristics of Metallic Shielded Solid Dielectric Power Cable" on page 5 of which paragraph 7 states that: "The Carlo'n PVC Conduit (6 in O.D. (15.2 c,n) .165 inches (3.94 cm (thick)) exhibited l i t t l e or no signs of deterioriation or i)hy~ical d~nage d~Je to explosh~ns or high temperatures resulting from high voltage arcing faults." A number of these tests were performed in open trenches. A copy of the complete paper is attached. Test work done by the Dept. of Water and Power, City of Los Angeles in October 1966, further supports this proposed amendment. A copy of this report is attached. (Note: A copy of attached material available from NFPAon request.) PANEL ACTION: Accept. VOTE ON PANELACTION: --AFFrgMATFV~-T NEGATIVE: Bowles. EXPLANATION qEZQIEE BOWLES: The old CMP 3 resisted efforts in the past to eliminate the concrete encasement requirement for nonmetallic conduit. CIvP 4 should continue to resist these efforts. The data submitted by Allen Hubble in the Technical Committee Documentation for the 1981 NEC gives valid reasons for rejecting this proposal. Log # 1179 4- 104 - (230-201): Reject Secretary's Note: The Correlating Committee directs the Panel to reconsider this proposal in view of further consideration of Proposal 4-99. SUBMITTER: M. F. Borleis, EEl RECOMMENDATION: Delete existing 230-201 and replace with the TCFFd~T6~ .... 230-201. Classification of Service Conductors (a) Primary Conductors. In all cases, the conductors connected to the load side of the service point shall be classified as service conductors. (b) Secondary Conductors. Where a transformer steps down the voltage from above 600 volts to 600 volts or less, the secondary conductors of such a transformer shall also be classified as service conductors. SUBSTANTIATION: Part K of Article 230 should apply to high voltage serwce f a c i l i t i e s on the load side of the service point. We believe that this was the original intent of the high voltage code as o r i g i - a l l y proposed for the NEC 1975. However, the present wording of Section 230-201(a) excludes v i r t u a l l y all high voltage service f a c i l i t i e s on the load side of the service point from compliance with Article 230. The only instances when Article 230 would apply to these f a c i l i t i e s is: 1. When there are no stepdown transformers. 2. When, as stated in the Exception following Section 230-201(b), the installation involves an intermediate voltage above 600 volts and i t is elected to call the primary conductors the service conductors. The provisions of Part K of Article 230 provide the minimum safety requirements fo~ high voltage services and should be applied to all such installations. Also, since installations above 600 volts are, as required by Part B of Article 110, accessible only to qualified persons, we concur with the present intent of Section 230-201(a) that low voltage systems derived from these high voltage installations to be classified as services. However~the present wording of the Exception following Section 230-201(b) allows confusion as to how secondary conductors below 600 volts would be classified where derived from a system with an intermediate voltage above 600 volts. This lack of c l a r i t y has allowed interpretations that the ground-fault provisions of Section 230-95 do not apply to the low voltage f a c i l i t i e s i f i t is elected to have the primary conductors considered the service conductors. The proposed wording would apply Article 230 to the high voltage service f a c i l i t i e s and also to any low voltage service f a c i l i t i e s supplied from such an installation. This revision would remove the confusion and misinterpretation that has been occurring since this section was revised in the 1975 NEC. Log # 1067, 1388 4- 106 - (230-203): Reject SUBMITTERS: Frank K. Kitzantides. NEMA(1067) ~. N~le, Baltimore, MD (13881 RECOMMENDATION: Revise to read as follows: "Precautionary signs shall be posted where unauthorized persons might come in contact with live parts." Add a fine print note: FPN: See Section 110-23. SUBSTANTIATION: See Section 110-23(New). I~(N-E'[--KC'FI-()N:'" Reject. FA]~ET~NT: Present wording is more appropriate in high voltage areas. VOTE ON PANEL ACTION: AFFIRMATIVE: 14 NEGATIVE: Stanback. EXPLANATION OF VOTE: "S~A~CK: A new ANSI Z635 standard for the use of precautionary signs ,nay be available before the next Panel 4 meeting, and correlation may be desirable. 70 ARTICLE 240 -- OVERCURRENT PROTECTION 4- 107 - (230-205): Accept SUBMITTER: C~ 4 RECOMMENDATION: Revise and renumber Section 230-205(b) as follows: 230-205. Disconnecting Means. (a) Location. The service disconnecting means shall be located in accordance with Section 230-72(c) or Section 230-208(b). Exception: Where under single management, the service disconnecting means shall be permitted to be located in a separate building or structure on the same premises. In such case the service disconnecting means shall be capable of being e l e c t r i c a l l y opened by a readily accessible control device located as near as practicable to where the service conductors enter the building served. The control device shall be permanently marked to identify its function and shall provide visual indication of the On or Off status of the remote service disconnect. FPN for (a). See Sections 230-3, 230-44, 230-70, 230-71(a) and 230-200. Renumber existing Section 230-205(a) to read Section "230-205(b)." SUBSTANTIATION: To correlate with Sections 230-72(c) and 230-208(b), and to provide an Exception. PANEL ACTION: Accept. VOTE ON PANELACTION: AFFIRMATIVE: 13 NEGATIVE: Bowles, Muska. COMMENT ON VOTE: COCK: Change "230-72(c)" to "230-70" i f Proposal 4-65 is accepted. EXPLANATION OF VOTE: BOWLES: The text should refer to Section 230-70 instead of 230-72(c) since the text of Section 230-72(c) was moved to Section 230-70 by Proposal 4-65. MUSK/~: Samereason as for Proposal 4-99. Log # 1975 4- 110 - (Article 240): Reject SUBMITTER: Richard Reddy, Rochester, NY RECOMMENDATION: Circuit breaker protection b u i l t into the cord cap of all lamps and small appliances that have'a wire size with less capacity than the circuit into which i t will be connected. SUBSTANTIATION: This will in all probability be a 20 ampere circuit. I have been a volunteer fireman for 40 years and chief for 3 years and have seen many fires that have been started by small wires shorting and burning and not being capable of tripping a 20 ampere circuit breaker because of the small wire size not drawing enough current to open the c i r c u i t . PANEL ACTION: Reject. Ffu~'L--C~-MMTNT: See Substantiation for Proposal 4-116. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 916 4- 111 - (240-2): Accept in Principle Secretary's Note: I t was the action of the Correlating Committee to direct the Panel to c l a r i f y the Panel Action on this proposal with respect to reference to Article 690. SUBMITTER: Ad Hoc Subcommittee on Solar Photovoltaics RECOMMENDATION: In tabulation, after "Over 600 Volts, Nominal General...710," add: "Solar Photovoltaic Systems...690." SUBSTANTIATION: For correlation with proposed Article 690. PANEL ACTION: Accept in Principle. I n s e r t "Solar Photovoltaics Systems" after "Services" in article tabulation. PANEL COMMENT: To correlate with the alphabetical l i s t i n g . VOTE ON ~ ACTION: Unanimously Affirmative. Log # 1180 4- 108 - (230-205(b)): Accept SUBMII-FER: M. F. Borleis, EEl RECOMMENDATION: Delete Section 230-205(b). SUBSTANTIATION: Section 230-200 presently states that service conductors and equipment over 600 volts shall also comply with all applicable provisions of the preceding sections of Article 230. The location of the service disconnecting means is adequately covered by 230-72(c). Section 230-205(b) in conjunction with 230-72(c) could be construed to require two separate service disconnecting means on essentially the same set of service entrance conductors. In addition, the present wording of Section 230-205(b) provides an ambiguous situation in that the service disconnecting means may be located ahead of the service point. Section 230-205(a) describes the type of service disconnecting means that is required. However, Section 230-205(a) would not apply to a service disconnect ahead of the service point because Section 230-200 clearly states that in no case shall the provisions of this article apply to equipment on the supply side of the service point. PANEL ACTION: Accept. VOTE ON PANELACTION: Unanimously Affirmative. Log # 1133 4- 112 - (240-3, Exception No. 1): Accept SUBMIl~FER: H.-I. Stanback, Lexington, Ky. ~ T I O N : Add at the end of the present text: " . . . . and the conductor is not part of a multioutlet branch circuit supplying readily accessible receptacles." SUBSTANTIATION: A conflict has existed in 1981 and previous Codes between Sections 210-19(a) and 240-3 Exception No. 1: Section 240-3 Exception 1: allows the next highest ampere rating of fuse or circuit breaker when conductor ampacity does not correspond with a standard rating. Section 210-19(a) now requires conductor ampacity not less than the rating of the branch circuit (which Section 210-3 indicates is the ampere rating or setting of the fuses or circuit breaker). Taken l i t e r a l l y , Section 210-19(a) would prevent using Section 240-3 Exception No. 1: for any branch circuit. The more restrictive requirement of Section 210-19(a) is only needed for multioutlet branch circuits supplying readily accessible receptacles. The loading of such branch circuits supplying readily accessible receptacles. The loading of such branch circuits is unpredictable and, therefore, the branch circuit overcurrent protection should be selected or set no higher than the ampacity of the conductors. Correlating changes are proposed for Sections 210-19(aI and 240-3 txceptlon No. I to eiimnate the conflict and retaln the more restrictive requirement for multioutlet branch circuits supplying readily accessible receptacles. PANEL ACTION: Accept. VOTE ON PANELACTION: ---AFF'i-R-F~'Tg~ ~- - 1 1 ~ NEGATIVE: Muska. EXPLANATION OF VOTE: MUSKA: This proposal, when piggy-backed on to Proposal 4-116 regarding fusing of extension cords, will require that No. 14 AWG extension cords have internal overcurrent protection in order to be used on a 20-ampere multioutlet branch circuit. Number 14 AWG cord has an ampacity of 17 amperes which, when used with present Section 240-3, Exception No. 1, would allow its use on a 20-ampere c i r c u i t . Proposed change would require a 15-ampere overcurrent. Present wording has withstood the test of time and any conflict should be resolved in Section 210-19(a). Log # 234 4- 109 - (230-212-(New)): Reject SUBMII-FER: H.K. Glenn, Pacific Coast Electrical Association, Inc. RECOMMENDATION: Switches and Circuit Breakers in Parallel (Multiple): When the load of an existing service entrance switching device increases beyond its continuous current rating, a second service entrance device of identical rating may be connected in parallel with i t , provided: (a) Each device has interrupting capacity equal to or greater than the maximum f a u l t current that can occur at its location. (b) Each device has its own overcurrent protection arranged to t r i p both devices automatically. (c) Both devices have a common electrical or mechanical tripping arrangement. (d) Both switches can be locked in the open position. SUBSTANTIATION: There is nothing in the NATIONAL ELECTRICAL CODE today coverln~ this type of installation above 600 volts. This method is a practice in large high-voltage installations and should be covered in the NATIONAL ELECTRICAL CODE. PANEL ACTION: Reject. ~ : Panel feels that this is a design problem. VOTE ON PANELACTION: Unanimously Affirmative. 4- 113 - (240-3, Exception No. 2): Accept SUBMITTER: CMP 4 RECOMMENDATION: Delete "and" between 5 and 8. Add "9 and 10u after 8. SUBSTANTIATION: Correlation with Section 240-21. Changesmade in the 1981 edition of the NEC. PANEL ACTION: Accept. VO'F~-~PANEL ACTION: Unanimously Affirmative. 71 ARTICLE 240 -- OVERCURRENT PROTECTION 4- 107 - (230-205): Accept SUBMITTER: C~ 4 RECOMMENDATION: Revise and renumber Section 230-205(b) as follows: 230-205. Disconnecting Means. (a) Location. The service disconnecting means shall be located in accordance with Section 230-72(c) or Section 230-208(b). Exception: Where under single management, the service disconnecting means shall be permitted to be located in a separate building or structure on the same premises. In such case the service disconnecting means shall be capable of being e l e c t r i c a l l y opened by a readily accessible control device located as near as practicable to where the service conductors enter the building served. The control device shall be permanently marked to identify its function and shall provide visual indication of the On or Off status of the remote service disconnect. FPN for (a). See Sections 230-3, 230-44, 230-70, 230-71(a) and 230-200. Renumber existing Section 230-205(a) to read Section "230-205(b)." SUBSTANTIATION: To correlate with Sections 230-72(c) and 230-208(b), and to provide an Exception. PANEL ACTION: Accept. VOTE ON PANELACTION: AFFIRMATIVE: 13 NEGATIVE: Bowles, Muska. COMMENT ON VOTE: COCK: Change "230-72(c)" to "230-70" i f Proposal 4-65 is accepted. EXPLANATION OF VOTE: BOWLES: The text should refer to Section 230-70 instead of 230-72(c) since the text of Section 230-72(c) was moved to Section 230-70 by Proposal 4-65. MUSK/~: Samereason as for Proposal 4-99. Log # 1975 4- 110 - (Article 240): Reject SUBMITTER: Richard Reddy, Rochester, NY RECOMMENDATION: Circuit breaker protection b u i l t into the cord cap of all lamps and small appliances that have'a wire size with less capacity than the circuit into which i t will be connected. SUBSTANTIATION: This will in all probability be a 20 ampere circuit. I have been a volunteer fireman for 40 years and chief for 3 years and have seen many fires that have been started by small wires shorting and burning and not being capable of tripping a 20 ampere circuit breaker because of the small wire size not drawing enough current to open the c i r c u i t . PANEL ACTION: Reject. Ffu~'L--C~-MMTNT: See Substantiation for Proposal 4-116. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 916 4- 111 - (240-2): Accept in Principle Secretary's Note: I t was the action of the Correlating Committee to direct the Panel to c l a r i f y the Panel Action on this proposal with respect to reference to Article 690. SUBMITTER: Ad Hoc Subcommittee on Solar Photovoltaics RECOMMENDATION: In tabulation, after "Over 600 Volts, Nominal General...710," add: "Solar Photovoltaic Systems...690." SUBSTANTIATION: For correlation with proposed Article 690. PANEL ACTION: Accept in Principle. I n s e r t "Solar Photovoltaics Systems" after "Services" in article tabulation. PANEL COMMENT: To correlate with the alphabetical l i s t i n g . VOTE ON ~ ACTION: Unanimously Affirmative. Log # 1180 4- 108 - (230-205(b)): Accept SUBMII-FER: M. F. Borleis, EEl RECOMMENDATION: Delete Section 230-205(b). SUBSTANTIATION: Section 230-200 presently states that service conductors and equipment over 600 volts shall also comply with all applicable provisions of the preceding sections of Article 230. The location of the service disconnecting means is adequately covered by 230-72(c). Section 230-205(b) in conjunction with 230-72(c) could be construed to require two separate service disconnecting means on essentially the same set of service entrance conductors. In addition, the present wording of Section 230-205(b) provides an ambiguous situation in that the service disconnecting means may be located ahead of the service point. Section 230-205(a) describes the type of service disconnecting means that is required. However, Section 230-205(a) would not apply to a service disconnect ahead of the service point because Section 230-200 clearly states that in no case shall the provisions of this article apply to equipment on the supply side of the service point. PANEL ACTION: Accept. VOTE ON PANELACTION: Unanimously Affirmative. Log # 1133 4- 112 - (240-3, Exception No. 1): Accept SUBMIl~FER: H.-I. Stanback, Lexington, Ky. ~ T I O N : Add at the end of the present text: " . . . . and the conductor is not part of a multioutlet branch circuit supplying readily accessible receptacles." SUBSTANTIATION: A conflict has existed in 1981 and previous Codes between Sections 210-19(a) and 240-3 Exception No. 1: Section 240-3 Exception 1: allows the next highest ampere rating of fuse or circuit breaker when conductor ampacity does not correspond with a standard rating. Section 210-19(a) now requires conductor ampacity not less than the rating of the branch circuit (which Section 210-3 indicates is the ampere rating or setting of the fuses or circuit breaker). Taken l i t e r a l l y , Section 210-19(a) would prevent using Section 240-3 Exception No. 1: for any branch circuit. The more restrictive requirement of Section 210-19(a) is only needed for multioutlet branch circuits supplying readily accessible receptacles. The loading of such branch circuits supplying readily accessible receptacles. The loading of such branch circuits is unpredictable and, therefore, the branch circuit overcurrent protection should be selected or set no higher than the ampacity of the conductors. Correlating changes are proposed for Sections 210-19(aI and 240-3 txceptlon No. I to eiimnate the conflict and retaln the more restrictive requirement for multioutlet branch circuits supplying readily accessible receptacles. PANEL ACTION: Accept. VOTE ON PANELACTION: ---AFF'i-R-F~'Tg~ ~- - 1 1 ~ NEGATIVE: Muska. EXPLANATION OF VOTE: MUSKA: This proposal, when piggy-backed on to Proposal 4-116 regarding fusing of extension cords, will require that No. 14 AWG extension cords have internal overcurrent protection in order to be used on a 20-ampere multioutlet branch circuit. Number 14 AWG cord has an ampacity of 17 amperes which, when used with present Section 240-3, Exception No. 1, would allow its use on a 20-ampere c i r c u i t . Proposed change would require a 15-ampere overcurrent. Present wording has withstood the test of time and any conflict should be resolved in Section 210-19(a). Log # 234 4- 109 - (230-212-(New)): Reject SUBMII-FER: H.K. Glenn, Pacific Coast Electrical Association, Inc. RECOMMENDATION: Switches and Circuit Breakers in Parallel (Multiple): When the load of an existing service entrance switching device increases beyond its continuous current rating, a second service entrance device of identical rating may be connected in parallel with i t , provided: (a) Each device has interrupting capacity equal to or greater than the maximum f a u l t current that can occur at its location. (b) Each device has its own overcurrent protection arranged to t r i p both devices automatically. (c) Both devices have a common electrical or mechanical tripping arrangement. (d) Both switches can be locked in the open position. SUBSTANTIATION: There is nothing in the NATIONAL ELECTRICAL CODE today coverln~ this type of installation above 600 volts. This method is a practice in large high-voltage installations and should be covered in the NATIONAL ELECTRICAL CODE. PANEL ACTION: Reject. ~ : Panel feels that this is a design problem. VOTE ON PANELACTION: Unanimously Affirmative. 4- 113 - (240-3, Exception No. 2): Accept SUBMITTER: CMP 4 RECOMMENDATION: Delete "and" between 5 and 8. Add "9 and 10u after 8. SUBSTANTIATION: Correlation with Section 240-21. Changesmade in the 1981 edition of the NEC. PANEL ACTION: Accept. VO'F~-~PANEL ACTION: Unanimously Affirmative. 71 In the 4-year period from 1976 to 1979, 5,803 incidents of f i r e involving electric products in homes were reported to UL via a newspaper clipping service. Of these f i r e incidents, 5.7 percent involved flexible cord. 51 percent of the incidents involving flexible cords, involved extension cords. This supports the indication given by the IAEI data. The UL newspaper clipping data were analyzed to determine the percentage of incidents that could have been averted i f the flexible cord(s) involved in each incident were protected against overcurrent in accordance with the cord ampacity. Judgment was used to categorize the incidents in those situations where the reported details were either sparse or incomplete. The results of the analysis were as follows: 75 percent of the incidents involving appliance cords (without extension cords) could have been averted; 93 percent of the incidents involving extension cords could have been averted. Among those f i r e incidents that were considered unable to be averted by protecting against overcurrent in accordance with the cord mnpacity were incidents in which no undersized extension cords were reported to be used, and in which appliances that draw high current (e.g., heaters and air conditioners) were involved. In this case, any new overcurrent protection would, by necessity, be of about the same size as the branch-circuit protection. PANEL ACTION: Accept. ~ L ACTION: Log # 126 4- 114 - (240-3, Exception No. 5): Reject Secretary's Note: This Comment (No. 70-5, CMP 4) on Proposal 4 was for the 1981 Code and was held for further study. See NEC-TCD-1980 Annual Meeting. The following was the Secretary's Note with this comment. "The Correlatlng Committee will set up an ad hoc committee to consider protection of conductors and transformers for boost and buck applications. SUBMITTER: Ray L. Olson, Boise, ID ~ATION: Recommendthe panel reconsider Proposal 4 as written with~he addition of Paragraph (d) from the panel's revised recommendation. SUBSTANTIATION: As revised: (a) Is covered by original proposal and is also required for three phase. (b) Is impossible because the excitation windings are not heavy enough to carry a phase to neutral load. Covered by original proposal To be included with original proposal above. This recommendation is with respect to included proposal to Panel 13, Section 450-3(b), Exception-(New). PANEL ACTION: Reject. P~NEL COMMENT: Based on insufficient technical information ~ c o n s i d e r this proposal. VOTE ON PANELACTION: UnanimouslyAffirmative. COMMENTON VOTE: STANBACK: Panel 4 should repeat the request for technical information from an Ad Hoc Committee in order to properly consider this proposal. NEGATIVE: Beard, Cock, Kassebaum, Stanback. EXPLANATION OF VOTE: BEARD: My reason for casting a negative vote on the Panel's action on this proposal is as follows: The data presented, by the NEC Correlating Committee Ad Hoc Subcommittee on Control Circuit Protection, Ampacities and Use of No. 16 and No. 18 Conductors, in substantiation of the proposal i s , at best, marginal. Even i f the data could be accepted as being reasonably valid, the numbers quoted (less than three percent of all electrical fires reported were attributable to extension cords) can in no measure j u s t i f y the added cost that would be imposed on the public as a result of this proposal. Aside from the lack of solid substantiation, the proposal f a i l s to recognize that safety could be compromised rather than enhanced. Consider that because of economic necessity the average family is attempting to do more things for themselves. Once a protected cord becomes inoperable, the handyman/handywoman around the house may attempt to convert i t to the conventional unprotected type. Only now the converted cord may have serious flaws, depending on the s k i l l of the f i x e r . This proposal borders on subscribing to the unrealistic notion that any problem can be mandated out of existence. I urge the Panel to reconsider its action on the proposal. COCK: I do not agree that the substantiation j u s t i f i e s the fusing of every No. 16 and No. 18 extention cord. Newspaper clippings of "incidents" are of l i t t l e value when a profile of "the damage caused by the "incidents" is not made. KASSEBAUM: I disagree that the substantiation j u s t i f i e s fusing of every No. 16 and No. 18 extension cord. I have d i f f i c u l t y believin9 "data" that is based on newspaper clippings, judgement and opinlon. STANBACK: While NEMAagrees that the subject merits further consideration, i t is f e l t that the proposal as worded could lead to abuses which could create more serious safety hazards than i t would solve. NEMA feels that the proposed requirements are too broad. The substantiation with the proposal addresses basically extension cords. NEMAis investigating the subject of extension cords within its related product sections and in a Joint Sections Committee. Also, i t was not the intent of the Ad Hoc Subcommittee to require this protection for lamp cords. The approval process for i n i t i a t i n g any product changes which might be indicated already exists. - Log # 1827 4- 115 - (240-3, Exception No. 5): Reject SUBMITTER: Paul E. Phelan, Trade Education Inc. and New Hampshire ~ l Contractors Inc. RECOMMENDATION: Changethe f i r s t sentence to read: "Conductors supplied by the secondary side of a single phase transformer having, a.27wire (single-voltage~ secondary shall be considered as protecteo Dy overcurrent protection on the primary (supply) side of the transformer provided "primary" protection is in accordance with Section 450-3 and "secondary conductor ampacity is determined by secondary kva rating at transformer full-rated secondary voltage." Transformer secondary conductors (other than 2-wire) are not considered to be protected by the primary overcurrent protection." SUBSTANTIATION: The present wording requires ~hat secondary conductors ampacity be based on the rating of the primary overcurrent protection which is at least 125 percent of the transformer primary current ratin~. This results in oversizing secondary conductors. PANEL ACTION: Reject. PANEL COMMENT: The secondary conductors would not be protected at ~ e i r rated ampacity unless they are oversized. VOTE ON PANELACTION: Unanimously Affirmative. Log # 891 4- 116 - (240-4): Accept SUBMITTER: Ad Hoc Subcommittee on Control Circuit Protection ~ATION: 240-4. Protection of Fixture Wires and Cords. Flexible cord, including tinsel cord and extension cords, shall be protected against overcurrent in accordance with their ampacities as specified in Table 400-5. Fixture wire shall be protected against overcurrent in accordance with its ampacity as specified in Table 402-5. Exception No. 1: When a flexible cord or a tinsel cord approved for and used with a specific listed appliance is connected to a branch circuit of Article 210 in accordance with the following: 20-ampere circuits, tinsel cord or No. 18 cord and larger. 30-ampere circuits, No. 16 cord and larger. 40-ampere circuits, cord of 20-ampere capacity and over. 50-ampere circuits, cord of 20-ampere capacity and over. Exception No. 2: When fixture wire is connected to 120-volt or higher branch circuit of Article 210 in accordance with the following: 20-ampere circuits No, 18 up to 50 feet of run length. 20-ampere circuits No. 16 up to 100 feet of run length. 20-ampere circuits. No. 14 and larger. 30-ampere circuits No. 14 and larger. 40-ampere c i r c u i t s No. 12 and larger. 50-ampere circuits No. 12 and larger. SUBSTANTIATION: In the 10-year period including 1970 to 1979, ~ t s of electrical f i r e were reported to IAEI and were included in the IAEI annually published tabulation. Of these f i r e incidents, 7.8 percent involved flexibIe cords. 38 percent of the incidents involving flexible cords, involved extension cords. ' Since almost every use of an extension cord is in conjunction with the use of an appliance cord, and since there are probably far more appliance cords in use without extension cords, the 38 percent figure mentioned above seems to indicate a disproportionately high frequency of f i r e incidents among extension cords, relative to other applications of flexible cord. Log # 312 4- 117 - (240-7-(New)): Reject SUBMITTER: R. A. Niedermeyer, City of Portland, OR RECOMMENDATION: Add new Section 240-7 to read: with'{enewable links. Fuses using renewable links shall not be installed. SUBSTANTIATION: Class H fuses s t i l l are being made using : renewable links. Experience has shown this type of device to be misused in that two or three links are often found inside of the fuses. These fuses are dangerously overlinked, overheated, and also the IC rating is only 10,000 amperes. The majority of use of this type of fuse is in industrial and conlnercial application. The fault currents available in such locations most generally are much higher than the rating of the renewable fuse. Also, this type of fuse is very d i f f i c u l t to check for proper linking after they are installed, as the fuse must be pulled and taken apart to de~ermine its actual rated current links. Proper fuses, of class and rating, are available on the market to f i l l any specific need. PANEL ACTION: Reject. I}'AITE'[--C~N'T: Proposal lacks sufficient documentation to substantiate the need for exclusion. VOTE ON PANELACTION: NEGATIVE: Beard, Cock, Herbert, Kassebaum, Niedermeyer, VanTassel. 72 Log # 263 4- 121 - (240-20(b)): Reject SUBMITTER: C. E. Muhleman, Marion, IN ~ME'N[}ATION: C i r c u i t breakers shall open all ungrounded conductors of a c i r c u i t except f o r l i g h t i n g c i r c u i t s . For l i g h t i n g c i r c u i t s only, single-pole c i r c u i t breakers shall be used. (Exception wording to remain as w r i t t e n . ) SUBSTANTIATION: The wording in the 1931 NATIONAL ELECTRICAL CODE permits the use of multipole breakers on l i g h t i n g c i r c u i t s which w i l l shut o f f all normal l i g h t s whenever a f a u l t occurs in one phase. The proposed would keep on 2/3 or even 1/3 of the normal l i g h t s should a f a u l t occur in a three phase c i r c u i t . This would c e r t a i n l y be more desirable than resorting to emergency l i g h t i n g as is required due to the wording in the 1975 NATIONAL ELECTRICAL CODE. PANEL ACTION: Reject. PANEL COMMENT: The Exception permits the use of single-pole breakers in l i g h t i n g c i r c u i t s . The Panel feels that i t is unnecessary to make t h i s mandatory. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . EXPLANATION OF VOTE: BLARD: I agree w-Tth the submitter's proposal and substantiation. COCK: I agree with the submitter. HERBERT: I agree with the submitter's comments. I also have noted many instances of severe overheating and damage to the fiber fuse housing. The repeated replacement of blown links combined with the continued use of the same housing creates a structurally unsound interrupting device. The common installation of this link style fuse in circuits over 10,000 AIC combined with the possibility of a p a r t i a l l y damaged housing is dangerous and should be prevented. KASSEBAUM: I agree with the substantiation of the submitter. Renewable link fuses should not be allowed f o r installation below 600 watts. NIEDERMEYER: The substantiation speaks for i t s e l f - the fear that some fuse manufacturer will be put out of business is not a valid argument in defending the continued use of these devices which have a historic background of misuse and damage to equipment. Manymanufacturers will not warrant their equipment i f protected with renewable fuses - must be a reason. VANTASSEL: Regardless of the "documentation" available to substantiate the need for the proposal, one has to question the use of these fuses. The potential for abuse is real, is l i k e l y being practiced, and not l i k e l y to be documented voluntarily. Log # 516 4- 122 - (240-20(b)): Reject SUBMITTER: J. K. Daugherty, Flint, MI ~ATION: Insert "simultaneously" between "shall" and "open" in the ist and 2nd lines. SUBSTANTIATION: To c l a r i f y the intent of this requirement. PANEL ACTION: Reject. PANEL COMMENT: The proposal adds a requirement not intended by the present rule. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 42 4- 118 - (240-10): Reject SUBMITTER: Dan Leaf, Westlake Village, CA RECOMMENDATION: Insert the words "or to comply with equipment labeling or listing" after the word "equipment." SUBSTANTIATION: Unclear whether overcurrent devices required by equipment labeling or listing (therefore required by Code) are considered supplementary. In the absence of a definition, supplementary overcurrent devices could be interpreted as those not required by Code; such device fie]d-installed to comply with equipment labeling or listing could be interpreted as being required by Code (Section 110-3) even when other branch circuit devices are installed. This raises the question of the intent of this section regarding ready access to such field-installed devices. PANEL ACTION: Reject. PANEL COMMENT: The Panel feels that the additional wording is unnecessary. I t is not the intent of the Panel to require supplementary overcurrent devices to be readily accessible regardless of whether factory or f i e l d installed. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 1494 4- 123 - (240-20(b)): Accept in Part SUBMITTER: John A. Pfau, National Conference of States on Bul1~FdT~Codes and Standards RECOMMENDATION: 240-20. Ungrounded Conductors. C i r c u i t breakers as overcurrent device. C i r c u i t breakers shall open all ungrounded conductors of the c i r c u i t . DELETE: The "exception" in i t s e n t i r e t y . SUBSTANTIATION: Failure to have p o s i t i v e opening of both poles of a breaker serving a 220 v o l t o u t l e t and/or load is a f i r e hazard and a danger to personnel through possible shock. This also involves NEC Section 550-4(c). Please see following additional supporting information. THE DANGEROF SUPPLYING 240 VOLT LOADS FROMTIED SINGLE-POLE BREAKERS Log # 1555 4- 119 - (240-11): Reject SUBMITTER: Rich Wideman, Novato, CA RECOMMENDATION: Add another paragraph 240-11 to read: For a device to be applied as a current limiting device, i t shall have industry recognition as being current limiting. SUBSTANTIATION: There is confusion as to whether an overcurrent device is current limiting or not when not marked accordingly, making i t d i f f i c u l t to enforce system integrity. PANEL ACTION: Reject. PANEL COMMENT: The Panel feels that the present definition of current-limiting overcurrent devices is preferable. The Panel feels that the present l i s t i n g , labeling and identification requirements are adequate. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . Log # 1338 4- 120 - (240-13-(New)): Reject SUBMITTER: Martin Smith, Bussman Division, McGraw-Edison Co. RECOMMENDATION: Add the following section/ 240-13. Series listing of combination overcurrent devices for higher interrupting capacity ratings. Only current limiting devices shall be permitted to be used in series to protect loadside overcurrent devices that do not have adequate interrupting capacity ratings for the available fault current at the lineside of their terminals. Other equivalent device(s) capable of limiting the current shall also be permitted. SUBSTANTIATION: There is a misunderstanding and confusion in this area. To assure integrity of the systems, the overcurrent devices must have independent testing laboratory published 12t and Ip values. PANEL ACTION: Reject. PANEL COMMENT: The Panel feels that requirements for listing should not be included in the Code. VOTE ON PANELACTION: AFFIRMATIVE: 11 NEGATIVE: Gubany. EXPLANATION OF VOTE: GUBANY: I am voting negative on Panel Action since I agree with the submitter's substantiation that all overcurrent devices to be used to protect other de~ices should have individual (device) established I peak and I~t published values recognized by industry standards and/or independent laboratories. Someproducts (overcurrent devices) have published values others do not and therein lies the hazard. I 73 1. From the standpoint of possible f i r e and/or personnel safety i t is essential that in the case of a two-pole breaker supplying a 230 volt load, that both poles be certain to open Jnder f a u l t or overload conditions. 2. Two single-pole breakers, externally coupled with a t i e bar and serving a 240 volt load, do not assure positive tripping of both poles under fault or overload conditions. Single-pole tripping is even more l i k e l y when using the compact single-position breakers housing 2 single-pole breakers, externally coupled, and supplying a 240 volt load. 3. For example, consider an energized 2,000 watt, 240 volt baseboard heater which develops a phase-to-ground fault at one end of the heater element. The instanteous magnetic element in the single-pole breaker in that leg will t r i p the breaker. The failure of the other.single-pole breaker to t r i p will result in 120 volts being impressed across the heater element with the resultant current returning through the equipment ground. This could continue indefinitely until detected, during which time i t would present a possible f i r e or shock hazard. 4. A faulty 240 v o l t device or load should be completely protected through the use of a single 2-pole breaker. There are numerous conditions of potential dangers in 240 volt loads that demand proper protection of property and equipment in addition to providing safety from f i r e or shock. I t is significant to note that the exception under Section 240-20(b) Exception permits the use of tied breakers serving 230 volt loads, expressly prohibits the practice when the phase-to-ground voltage exceeds 150. 5. The electrical industry is aware of the inherent danger and hazard of failure to have both circuit breaker poles open on a faulted or overloaded 230 volt load or device. A single 2-pole breaker with a single operating handle should serve to supply 230 v o l t ungrounded loads. Someleading manufacturers have or are taking steps in the design to incorporate - sitive tripping of both poles. This problem should be solved by requiring that circuit breakers serving 230 volt, ungrounded loads or devices, clear both poles on fault or overload conditions. PANEL ACTION: Accept in Part. D e l e t e"each conductor of ungrounded 2-wire circuits," from the Exception. PANEL COMMENT: The Panel f e l t that the supporting data only applied to deleting the Exception for ungrounded 2-wire circuits. SUBSTANTIATION: A~Dacity of feeder conductors do not always match ~--ratlngs"-~gs--ol~ their overcurrent protective devices. Relating the size of tap conductor to feeder overcurrent protection more accurately defines the protection required and brings the logic associated with the protection of Feeder taps in line with Exception No. 10. PANEL ACTION: Reject. ~A]TE'[--Ci~RII~mlSF: The Panel intended Exception No. 10 to be more restrictive. VOTE ON PANEL ACTION: UnanimouslyAffirmative. VOTE ON PANEL ACTION: Unanimously Affirmative. ~OMMENT ON VOTE: NIEDERMEYER: I agree with the requirement that ungrounded 2-wire circuits be required to have a double-pole breaker, however, I'm concerned that the phrasing l e f t , i.e. "each ungrounded conductor of 3-wire direct-current or single-phase circuits" will lead someone to believe that this means 2-wire ungrounded circuits when reading "or single-phase circuits." I'm voting affirmative conditioned that we c l a r i f y by adding "or 3-wire single-phase c i r c u i t s . " This would then remove any confusion as to Panel intent. Log # 1367 4- 124 - (240-21, Exception No. 2b(2a)): Reject SU~MITTER: Paul Hoh, Ralston Purina ITE'-C~Q~E'lq~ATION: Delete Exception No. 2a. SUBSTANTIATION: Sentence 2(a) of Exception No. 2b(1) is in conflict with 240-3, Exception No. 5, last sentence which states that transformer secondary conductors are not considered to be protected by primary overcurrent, other than by 2-wire primary and secondary. PANEL ACTION: Reject. PANEL COMMENT: The Panel believes that there is no conflict. The secondary conductors are not required to be protected by primary overcurrent devices i f they meet the 10 foot tap rule. VOTE ON PANEL ACTION: AFFIRMATIVE: 11 NEGATIVE: Gubany. EXPLANATION OF VOTE: GUBANY: I am voting negative on Panel Action since I agree with this substantiation. 2b(2a) is in conflict with the last sentence of Section 240-3, Exception No. 5. 2b(2a) tap would permit a 400-ampere device (as a motor control center) to be fed by a 10-fo~t, 400-ampere feeder, tapped to the secondary of a transformer without any protection for the tap conductors transformer or the 400-ampere device i t feeds. Primary protection of the transformer which meets Section 450-3 is not recognized as providing protection for secondary conductors when the primary is more than 2-wire and the secondary is more than 2-wire. Log # 1672 4- 128 - (240-21, Exception No. 3 b . ) : Accept in Principle SUBMITTER: Charles "Mike" Holt, Concepts in Electricity Inc. RE~J~-O-B-M~-'N-DATION: 240-21 Exception No. 3b. (The ampacity of the tap conductors is not less than I/3 that of the feeder conductors from which they are supplied.) "The ampacity of the tap conductors have an ampacity of not less than 1/3 that of the conductors or overcurrent protection from which they are tapped." Material to be deleted in parentheses, new material in quotations. SUBSTANTIATION: Provide consistency in sizihg tap conductors to compyly--wiTh Exception No. 8. PANEL ACTION: Accept in Principle. Revise to read as follows: "The ampacity of the tap conductors is not less than i/3 that of the feeder conductors or overcurrent protection from which they are tapped," PANEL COMMENT: Editorial change. V~-ONPANEL ACTION: UnanimouslyAffirmative. Log # 1675 4- 129 - (240-21, Exception No. 8a.): Reject SUBMITTER: Charles "Mike" Holt, Concepts in Electricity Inc. RECOMMENDATION: 240-21, Exception No. 8a. The conductors ~ j i ' 6 ~ h 6 - p r i m a r y of a transformer have an (ampacity) "current-carrying capacity" of at least 1/3 that of the conductors or overcurrent protection from which they are tapped. Material to be deleted in parentheses, new material in quotations. SUBSTANTIATION: This exception makes reference that the conductors have a given ampacity. I t is very possible that the ampacity of the conductor used in Table 310-16 needs to be adjusted by Note 8 correction factors or ambient temperature correction factors, and the current-carrying capacity will not be the same as the ampacity. By replacing these words with current-carrying capacity i t will be clearly understood that i t must have the capacity to carry these loads, not the ampacity, because the ampacities will not change after applying correction factors. PANEL ACTION: Reject, I~-AITEL--i~'OI~IRL'~T: See Panel Comment for Proposal 4-125. VOTE ON PANELACTION: UnanimouslyAffirmative. Log # 1673 4- 125 - (240-21, Exception No. 2b.): Reject SUBMITTER: Charles "Mike" Holt, Concepts in Electricity Inc. ~ATION: 240-21 Exception No. 2b. The (ampacity) "current carrying capacity" of the tap conductor i s . . . Wording to be deleted in parentheses, new material is in uotations. UBSTANTIATION: This exception makes reference that the conductors have a given ampacity. I t is very possible that the ampacity of the conductor used in Table 310-16 needs to be adjusted by Note 8 correction factors or ambient temperature correction factors. AND the current carrying capacity will not the same as the ampacity. By replacing these words with current carrying capacity i t will be clearly understood that i t must have the capacity to carry these loads, not the ampacity, because the ampacities will not change after applying correction factors. PANEL ACTION: Reject. PANEL COMMENT: The Panel feels that i t is not necessary to replace a word by its defined meaning. VOTE ON PANELACTION: UnanimouslyAffirmative. ~ Log # 1676 4- 130 - (240-21, Exception No. 8b.): Reject SUBMIIT[ER: Charles "Mike" Holt, Concepts in Electricity Inc. RECOMMENDATION: 240-21 Exception No. 8b. The conductors supplied ~-y-~-6"sedd6dary of the transformer have an (ampacity) "current-carrying capacity" that, when multiplied by the ratio of the secondary-to-primary voltage, is at least i / 3 the (ampacity) "current-carrying capacity" of the conductors or. overcurrent protection from which the primary conductors are tapped. Material to be deleted in parentheses, new material in quotations. SUBSTANTIATION: This exception makes reference that the ~ t - o - F C ~ g e a given ampacity. I t is very possible that the ampacity of the conductor used in Table 310-16 needs to be adjusted by Note 8 correction factors or ambient temperature correction factors, and the current-carrying capacity will not be the same as the ampacity. By replacing these words with current-carrying capacity i t will be clearly understood that it must have the capaclty to carry these loads, not the ampacity, because the ampacities will not" change after apply correctlon factors. PANEL ACTION: Reject. PANEL COMMENT: See Panel Comment for Proposal 4-125. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 1674 4- 126 - (240-21, Exception 3b.): Reject SUBMITTER: Charles "Mike" Holt, Concepts in Electricity Inc. ~ATION: 240L21, Exception 3b. The (ampacity of) "current carrying capacity of" the tap conductors is not less than i/3 that of the feeder conductors from which they are supplied. Material to be deleted in parentheses, new material in quotations. SUBSTANTIATION: This exception makes reference that the conductors have a given ampacity. I t is very possible that the ampacity of the conductor used in Table 310-16 needs to be adjusted by Note 8 correction factors or ambient temperature correction factors, and the current carrying capacity will not be the same as the ampacity. By replacing these words with current carrying capacity i t will be clearly understood that i t must have the capacity to carry these loads, not the ampacity, because the ampacities will not change after applying correction factors. PANEL ACTION: Reject. PANEL COMMENT: See Panel Comment on Proposal 4-125. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . Log # 498 4- 131 - (240-21, Exception No. 8e.): Reject SUBMITTER: Ernest E. Cannon, Tempe, AZ RECOMMENDATION: Add at the end of present e. Or terminate in a ~ l ~ o - ~ d - - o r panelbeard which serves a computed load not exceeding the transformer secondary FLA and equipped with overcurrent devices with a total value not exceeding 150 percent of the transformer FLA. Each overcurrent device shall be 2-pole for single-phase transformers and 3-pole for 3-phase transformers. The secondary conductors, switchboard, and the panelboard shall be rated not less than 125 percent of the transformer secondary FLA. Log.# 1335 4- 127 - (240-21, Exception No. 3b.): Reject SU~MI~ER: Lawrence R. Walsh, Lizardos Engineering Associates ITE-COI~IEI~ATION: ChangeException No. 3b. to read: The ampacity of the tap conductors is not less than 1/3 that of the overcurrent device from which they are supplied. 74 Log # 1462 4- 136 - (240-21, Exception No. lOg.-(New)): Accept SUBMITTERS: Leo Witz, Continental E l e c t r i c Co. ~-T~i Hogan, Chicago, IL Fred Smith, Elgin, IL Jim Meehan, New Haven, CT Anton Ganje, North Dakota Kenny Gebert, Minneapolis, MN B i l l Conrardy, The Conrardy Co. Robert P. Brooks, Chicago, IL Paul Moore, Chief E l e c t r i c a l Inspector, Paducah, KY Les Rinder, Chicago, IL Leo Nagel, North Dakota John W. Erickson, Boltswitch, Inc. Homer M. L e f l e r , Chicago, IL RECOMMENDATION: Amend Section 240-2], Exception No. 10, by adding thereto a new subsection as follows: "g. The tap shall be made no less than 35 f e e t from the f l o o r . " SUBSTANTIATION: As i t is presently w r i t t e n the tap made under x-l~-x-ception No. i0 can be made anywhere in the building as long as the c e i l i n g is 35 feet high at the walls. There is nothing to prevent you from making the tap two inches o f f the ground or any distance between the f l o o r and the c e i l i n g or f o r t h a t matter in the basement or up on the r o o f . We assume that i t was the i n t e n t i o n of the Code-Making Panel to place some r e s t r i c t i o n upon the location of the permitted tap and since the Panel indicated a 35 foot c e i l i n g , we assume that t h a t ' s where they intended that i t be made. PANEL ACTION: Accept. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . SUBSTANTIATION: NEC does not appear to address this'arrangement. Multi-taps to multi-disconnects with each tap ending in a set of overcurrent devices is addressed. The propose~ arrangement permits a design which is sound and acceptable in our j u r i s d i c t i o n s even though not s p e c i f i c a l l y according to NEC. PANEL ACTION: Reject. PANEL COMMENT: I t is intended that the taps terminate in a single overcurrent device. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . Log # 508 4- 132 - (240-21, Exception No. 9): Reject SUBMITTER: James L o f f l i n , She]don, IA C RO ~ D A T I O N : Conductors from generator terminals to the f i r s t overcurrent device as covered in Section 445-5. When generator is used for normal supply, not emergency supply. SUBSTANTIATION: Clarification. FAN-ET~ Reject. PANEL COMMENT: Section 445-5 is not limited to normal supply generators. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 2015 4- 133 c (240-21, Exception No. 9): Reject SUBMITTER: Idaho Chapter IAEI ITE'-C-O-~-E~-OATION: Change Exception No. 9 to read: Generator feeder taps not over 25 feet long where all the following conditions are met: (a) conductors have an ampacity of at least 115 percent of the generator rating, and (b) the total length of the tap conductor from the generator terminal to the f i r s t overcurrent device sh~ll not be over 10 feet long, and (c) the tap conductor is protected from suitable damage, and (d) the generator tap conductors terminate in a single circuit breaker or set of fuses which will limit the load to that allowed in Tables 310-16 through 310-19. SUBSTANTIATION: Section 240-3 requires an overcurrent device shall be connected at the point where the conductors to be protected receive their supply. Under this present Code wording, an overcurrent device would have to be located at the generator terminal. Tap distances have been provided for transformers, therefore generators should be afforded the same consideration. Inherent generator design is not recognized as overcurrent protection as required by Section 240-21. These generators can be changed in the f i e l d to a larger generator without any knowledge of conductor ampacity of overcurrent requirements thereby causing an overload on the conductors and creating a f i r e hazard. PANEL ACTION: Reject. ~#~MIE:--NT: The proposal would create a conflict with Section 445-5. VOTE ON PANELACTION: UnanimouslyAffirmative. Log #1767 4- 137 - (240-22, Exception No. 2): Accept SUBMITTER: Tom Tombarello, Paul Revere Chapter IAEI RECOMMENDATION: In the second l i n e , delete the word "running." b'-O~-STANf/Af/dN: CMP 11 has deleted the word "running" where i t appeared with "overload p r o t e c t i o n " throughout A r t i c l e 430 and, e d i t o r i a l l y , i t should be deleted in the exception and throughout the NEC where i t appears in t h i s manner. PANEL ACTION: Accept. V ~ L ACTION: Unanimously A f f i r m a t i v e . Log # 1685 4- 138 - (240-23): Reject SUBMITTER: Charles "Mike" Holt, Concepts in E l e c t r i c i t y Inc. RECOMMENDATION: Section 240-3 would best serve i t s purpose i f eliminated e n t i r e l y . Delete Section 240-23. SUBSTANTIATION: I f 240-23 were deleted e n t i r e l y as a Code section and added as a f i n e p r i n t note to Section 240-21 inasmuch as i t is not a requirement but a statement of information. PANEL ACTION: Reject. ~ E L COMMENT: See Panel Action f o r Proposal 4-139. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . Log # 1697 4- 134 - (240-21, Exception lOa.): Reject SUBMITTER: Charles "Mike" Holt, Concepts in Electricity Inc. ITE'C~NXI~ATION: 240-21, Exception 10a. The ampacity of the tap conductors is not less than 1/3 that of the "conductors or" the overcurrent device from which they are supplied. SUBSTANTIATION: Provide consistency in sizing tap conductor to comply with Exception No. 8. Exception No. 3 states size on conductors. Exception No. 8 states size on conductors or device. Exception No. i0 states size on overcurrent device. PANEL ACTION: Reject. PANEL COMMENT: See Panel Comment for Proposal 4-127. VOTE ON PANELACTION: Unanimously Affirmative. Log # 1502 4- 139 - (240-23): Accept SUBMITTER: Melvin K. Sanders, Ankeny, IA ITE~C~FI~;~-(~)ATION: Revise to read as follows: Change in Size of Grounded Conductor. Where a change occurs in the size of the ungrounded conductor, a similar change "shall be permitted to be" made in the size of the ungrounded conductor. SUBSTANTIATION: The word "may" does not lend i t s e l f to positive enforcement, and does not conform to the Sectio# 110-i where shall is the preferred wording. PANEL ACTION: Accept. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . Log # 1677 4- 135 - (240-21, Exception No. iOb.): Reject SUBMITTER: Charles "Mike" Holt, Concepts in E l e c t r i c i t y Inc. RECOMMENDATION: 240-21 Exception No. lOb. The tap conductors terminate with a single c i r c u i t breaker or a single set of fuses t h a t w i l l l i m i t the load to the (ampacity) " c u r r e n t - c a r r y i n g capacity" of the tap conductor...Material to be deleted in arentheses, new material in quotations. UBSTANTIATION: This exception makes reference t h a t the conductors have a given ampacity. I t is very possible that the ampacity of the conductor used in Table 310-16 needs to be adjusted by Note 8 correction factors or ambient temperature correction f a c t o r s , and the c u r r e n t - c a r r y i n g capacity w i l l not be the same as the ampacity. By replacing these words with c u r r e n t - c a r r y i n g capacity i t w i l l be c l e a r l y understood that i t must have the capacity to carry these loads, not the ampacity, because the ampacities w i l l not change a f t e r applying correction factors. PANEL ACTION: Reject. PANEL COMMENT: See Panel Cogent f o r Proposal 4-125. VUlb UIw PANEL ACTION: Unanimously A f f i r m a t i v e . Log # 93 4- 140 - (240-24(a), Exception No. 1): Reject Secretary's Note: I t was the action of the Correlating Committee t h a t f u r t h e r consideration be given to the comments expressed in the negative voting. SUBMITTER: Don L. Gregersen, Spokane, WA ~iV~NDATION: Exception No. i should be deleted. SUBSTANTIATION: Section 240-24, Exception No. 1 is in c o n f l i c t ~Et{6~-230-72(c). PANEL ACTION: Reject. PANEL COMMENT: Not in c o n f l i c t with Section 230-72(c). VOTE ON PANEL ACTION: ~ NEGATIVE: Beard, Niedermeyer. EXPLANATION OF VOTE: I agree with the submitter's proposal and substantiation. NIEDERMEYER: Section 230-72(c) d e f i n i t e l y requires " r e a d i l y accessible l o c a t i o n " and is in c o n f l i c t . No place in either A r t i c l e 240 or 230 allows an overcurrent device to be other than "Readily Accessible." Current l i m i t e r s are not regarded as overcurrent devices in t h i s sense. This Exception No. I should be eliminated as i t has no application. ~RD: 75 Exception: In c i r c u i t s supplied by a system having a grounded neutral and having no conductor at over 300 volts to ground. (c) Fuseholders for c u r r e n t - l i m i t i n g fuses shall not permit insertion of fuses that are not current l i m i t i n g . (d) Marking. Fuses shall be plainly marked, either by printing on the fuse barrel or by a label attached to the barrel, showing the following: (1) Ampere rating, (2) Voltage rating, I~ Interrupting rating where other than I0,000 amperes, "Current l i m i t i n g " where applicable, (5) The name or trademark of the manufacturer. Exception: Interrupting rating markings shall not be required on fuses used for supplementary protection. SUBSTANTIATION: Part "F" as presently written has had the effect ~CgfEtfng development resulting from new technology. This revision would allow the NEC requirements for fuses and fuseholders to be more compatible with the requirements of this "era of space age" technological developments. PANEL ACTION: Reject. ~ANEL COMMENT: The submitted proposal is too broad. See Panel r-~-~Ega-l--4-L-l~ P 6. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 1768 4- 141 - (240-24(a), Exception No. i ) : Reject Secretary's Note: I t was the action of the Correlating Committee that further consideration be given to the comments expressed in the negative voting. SUBMITTER: Tom Tombarello, Paul Revere Chapter IAEI ~ATION: Delete Exception No. 1 - or revise as follows: Exception No. I . For services as provided in Section 230-82. SUBSTANTIATION: Clarification of what appears in the 1981 NEC. PANEL ACTION: Reject. PANEL COMMENT: The Panel does not feel that i t clarifies. VOTE ON PANELACTION: AFFIRMATIVE: 11 NEGATIVE: Niedermeyer. EXPLANATION OF VOTE: ---ITiIL'l}~:R-C-e-S'ee-comment on Proposal 4-140. Log # 1666 4- 142 - (240-24(a), Exception No. 4-(New)): Reject SUBMITTER: Charles "Mike" Holt, Concepts in E l e c t r i c i t y Inc. ~ATION: 240-24(a), Exception No. 4. "Overcurrent devices installed adjacent to motors, appliances, or other equipment which they supply shall be permitted to be located higher than specified in the foregoing and to be accessible by portable means." SUBSTANTIATION: Since Section 380-8(a), Exception No. 2 makes reference to location of switches - i f fusable disconnect or c i r c u i t breaker disconnect is used as a switch, Section 240-24(a) would require i t to be readily accessible, but i f a no fuse switch is used, Section 380-8(a) would not require that i t be readily accessible. PANEL ACTION: Reject. PANEL COMMENT: We disagree with the proposal and feel that in the interest of safety, this exception should not be added. VOTE ON PANEL ACTION: Unanimously Affirmative. 4- 146 - (240-61): Accept SUBMITTER: CMP 4 RECOMMENDATION: Revise Section 240-61 to read as follows: Classification. Cartridge fuses and fuseholders shall be classified according to voltage and amperage ranges. Fuses rated 600 v o l t s , nominal, or less, shall be permitted to be used for voltages at or below t h e i r ratings. Delete: Exception Nos. i and 2. SUBSTANTIATION: Part "F" as presently written has had the e f f e c t of r e s t r i c t i n g development resulting from new technology. This revision would allow the NEC requirements for fuses and fuseholders to be more compatible with the requirements of this "era of space age" technological developments. PANEL ACTION: Accept. VOTE ON PANEL ACTION: Unanimously Affirmative. 4- 143 - (240-33 and Exception-(New)): Accept SUBMITTER: CMP 4 RECO~ATION: Add a period after the word "position" and delete ~t~--t-~e sentence. Add a new exception to read as follows: "Exception: Where this is shown to be impracticable and complies with Section 240-81." SUBSTANTIATION: Editorial change to c l a r i f y that this is an exception. PANEL ACTION: Accept. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 1505 4- 147 - (240-60(b), FPN-(New)): Reject SUBMITTER: Melvin K. Sanders, Ankeny, IA REC M~ATION: Add Fine Print Note: See'SeEtf~-llO-9 f o r interrupting requirements. SUBSTANTIATION: This w i l l make f o r more e f f e c t i v e coordination ~ usageof c u r r e n t - l i m i t i n g fuses and the need to have a large enough interrupting c a p a b i l i t y . Until I read a response to a question covered by an a r t i c l e in the IAEI News magazine, I was not aware of the c o r r e l a t i o n , and have used i t to require contractors and designers to provide properly rated equipment. Many are aware of the need to provide protection at the service, but are not aware of the need to take care of the downstream equipment also. PANEL ACTION: Reject. ~'CO~NIME-NT: Already included as a FPN under Section 240-1, Scope. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 1203 4- 144 - (240-42-(New)): Reject SUBMITTER: Charles J. Hart, NECA RECOMMENDATION: Add the following section: 240-42. Indicating. Disconnects shall clearly indicate whether they are in the open " o f f " or closed "on" position. Where disconnect handles are operated v e r t i c a l l y rather than r o t a t i o n a l l y or horizontally, the up position of the handle shall be the "on" position. SUBSTANTIATION: I t is ingrained in electricians and other operating personnel that l i g h t switches and disconnects in the "up" position are "on" and in the "down" position are " o f f . " During emergencies, people tend to act from habit and do not have time to read which direction is o f f . PANEL ACTION: Reject. ~E-NT: Proposal needs exceptions and additional work f o r acceptance. VOTE ON PANELACTION: AFFIRMATIVE: 10 NEGATIVE: Herbert, Niedermeyer. EXPLANATION OF VOTE: HERBERT: I a g - ~ w i t h the submitter. Vertically mounted disconnects, switches and circuit breakers should follow the up "on" and down "off" convention. I t is now time to standardize on this practice so that i t also becomes a safety feature. NIEDERMEYER: I agree with the supporting comment. Log # 1708 4- 148 - (240-61): Reject SUBMITTER: Charles "Mike" Holt, Concepts in E l e c t r i c i t y Inc. RECOMMENDATION: 240-61. Cartridge fuses and fusehelders not over ~"O-O--#oT-{s"shall be classified as follows: 0-30; 31-60; 61-100; 101-200; 201-400; 401-600; 601-800; 801-1200; 1201-1600; 1601-2000; 2001-2500; 2501-3000; 3001-4000; 4001-5000; 5001-6000. Remove the three columns and provide just one paragraph since they are all the same. SUBSTANTIATION: Since not over 250 volts not over 300 volts and not over 600 volts values are all the same, and since this section applies to under 600 volts only, with a reference to the voltage l i m i t a t i o n , one paragraph would suffice and be clearer than three separate columns which l i s t the same information. PANEL ACTION: Reject~ PANEL COMMENT: See Panel Proposal 4-146. ON PANEL ACTION: Unanimously Affirmative. Log # 1556 4- 145 - (240-60 and 240-61): Reject SUBMITTER: W. A. Mathews, Bussmann Division, McGraw Edison RECOMMENDATION: Revise as follows: 240-60 General, Delete 240-61. 240-60. General. (a) Voltage. Fuses rated 600 v o l t s , nominal, or less, shall be permitted to be used for voltages at or below ~heir voltage ratings. (b) MaximumVoltage. 300-volt type. Cartridge fuses and fuseholders of the 300-volt type shall not be used in c i r c u i t s of over 300 volts between conductors. Log # 434, 1243 4- 149 - (240-81): Accept SUBMITTERS: Southwestern Section IAEI (434) --I-AET-(-I-243) RECOMMENDATION: Amend 2nd paragraph to read: Where c i r c u i t breaker handles on switchboards "or in panelboards" are operated v e r t i c a l l y rather than r o t a t i o n a l l y or horizontally, the "up" position of the handle shall be the "on" position. 7B PANEL ACTION: Reject. F~N-E-C--C~;F#~'-NT: The Panel feels that this proposal would rule out all adjustable breakers. The submitters have not provided adequate substantiating data to warrant such action. VOTE ON PANELACTIqNE AFFIRMATIVE: 11 NEGATIVE: Gubany. EXPLANATION OF VOTE: GUBANY: I am voting negative on Panel Action on this proposal since I support the submitter's substantiating comment, and I disagree that this proposal would rule out all adjustable CB's. "For other than intended adjustments" negates the intent of noninterchangeability. SUBSTANTIATION: Manypanelboards have been installed having main breakers with the up position being " o f f . " Present Code terms are not effective in requiring the change when a panelboard is involved. The majority of disconnecting means installed in this above approved manner. By having panelboards also conform, i t may save an accident. To be indicating is s t i l l a requirement. PANEL ACTION: Accept. ON PANEL ACTION: UnanimouslyAffirmative. Log # 1205 4- 150 - (240-81): Reject SUBMITTER: Charles J. Hart, NECA ~ATION: Delete the two words "on switchboards" from second sentence of Section 240-81. SUBSTANTIATION: I t is ingrained in electricians and other operating personnel that light switches and disconnects in the "up" position are "on" and in the "down" position are " o f f . " During emergencies, people tend to act from habit and do not have time to read which direction is off. Although this safety feature has been recognized for switchboards, the same principle should apply to all vertical mounted breakers. PANEL ACTION: Reject. PANEL COMMENT: See Panel Action for Proposal 4-149. iTO-?-E~-ON--PK ' N-EC ' ACTION: AF RMATI : NEGATIVE: Herbert. EXPLANATION OF VOTE: ~ R ' F T - - % e 6 - C 6 ~ e n t on Proposal 4-144. Log # 1733 4- 153 - (24D-83(a)): Accept in Part SUBMITTER: Charles "Mike" Holt, Concepts in Electricity Inc. ~ATION: 240-83(a). Circuit breakers shall be ma~ked with their "ampere" or "interrupting" rating in a manner that will be durable and visible after installation. SUBSTANTIATION: This section does not c l a r i f y the rating they are talking about; i.e. ampere rating of the circuit breaker, interrupting rating. I am not qualified to make'a proposal as to the specific rating required, but this section needs to be more clearly detailed. PANEL ACTION: Accept in Part. ~{-e-.'~-'~6r interrupting." PANEL COMMENT: Interrupting rating is already covered in Section ~4o --O-:~-c.T:--VOTE ON PANELACTION: UnanimouslyAffirmative. Log # 779 4- 151 - (240-81, Second Paragraph): Reject SUBMITTER: Chester Flanagan, San Diego, CA RECOMMENDATION: Revise to read: ~ I n d i c a t i n g . Circuit breakers shall clearly indicate whether they are in the open "off" or closed "on" position. "Where circuit breaker handles are operated vertically rather than rotationally or horizontally, the up position of the handle shall be the "on" position." SUBSTANTIATION: This proposal would standardize vertically-operated breaker handle operating procedures to promote safety, uniformity and ease of breaker status verification. In some cases, in the local area, vertically operated breaker handles in panelboards have been noted that are "on" while in the down position and " o f f " while in the up position. On the other hand all v e r t i c a l l y operated breaker handles noted in switchboards were " o f f " while in the down position and "on" in the up position. These d i f f e r e n t breaker handle operating methods could lead to confusion and/or error and possible endangerment of l i f e and property. PANEL ACTION: Reject. PANEL COMMENT: See Panel Action f o r Prop6sal 4-149. ~VOTE~ON PANEL - - ACTION: Log # 113 4- 154 - (240-83(d)): Reject SUBMITTER: Michael Tango, Plymouth, MA RECOMMENDATION: SWD should be marked on circuit breakers and visible after installation. SUBSTANTIATION: Section 240-83(d) reads: Circuit Breakers Used as Switches. SWD circuit breakers used For lighting fixture of 120 volt. SWD circuit breakers shall be approved for switching duty. Circuit breaker has to be marked with SWD on i t . I t doesn't say visible after installation. PANEL ACTION: Reject. PANEL COMMENT: The very limited space available on the breaker sh6uT~d for higher p r i o r i t y markings. VOTE ON PANELACTION: UnanimouslyAffirmative. Log # 1256 4- 155 - (240-83(d)): Accept SUBMITTER: IAEI ~ATION: In the second line following 120-volt add, (and 2 7 T ~ l t T . The second line would then read: 120-volt and 277-volt fluorescent lighting circuits, (the rest of the section to remain unchanged.) SUBSTANTIATION: The 277-volt circuit breaker hearing a mark SWD l " - ~ - - 6 ~ - ~ f ~ e t and cannot be installed without violating the Code unless i t is also included in this section. PANEL ACTION: Accept. PANEL COMMENT: The Panel disagrees with the substantiation, but believes that the requirement should be extended to 277-volt flourescent lighting circuits. VOTE ON PANELACTION: UnanimouslyAffirmative. NEGATIVE: Herbert. EXPLANATION OF VOTE: ~-HER~ERT: %ee comment on Proposal 4-144. Log # 1463 4- 152 - (240-82): Reject SUBMITTERS: Leo Witz, Continental Electric Co. Bill Hogan, Chicago, IL Fred Smith, Elgin, IL Jim Meehan, New Haven, CT Anton Ganje, North Dakota Kenny Gebert, Minneapolis, MN B i l l Conrardy, The Conrardy Co. Robert P. Brooks, Chicago, IL Paul Moore, Paducah, KY Les Rinder, Chicago, IL John W. Erickson, Boltswitch, Inc. Homer M. Lefler, Chicago, IL RECOMMENDATION: AmendSection 240-82 by deleting therefrom the TasT-f-f~o-r-ds, i . e . , "for other than intended adjustments." SUBSTANTIATION: I f a circuit breaker is to be NONTAMPERABLE as ~ l n ~ - n d - T c a t e s is the safest condition, then we shouldn't insert the "Mickey Mouse" phrase at the end which will permit the construction of all circuit breakers with provisions for making "intended adjustments." There is no limitation placed upon the manufacturer in this section of the Code. I t means absolutely nothing as presently written. All a manufacturer has to say is that "I am leaving this dial on the side of the circuit breaker so that the intended adjustments may be made without breaking a seal or dismantling the device." I t is obvious that there are some breakers manufactured and used quite widely and quite safely that have provisions for making adjustments in the f i e l d without dismantling the breaker or breaking a seal, when such breakers are installed where there is competent maintenance and where such breakers are under careful and constant supervision. However, there is nothing in Section 240-82 that would indicate that any such supervision or competence of maintenance be present. All breakers are covered by this section of the Code and the intent of the section can be circumvented easier than this proposal has been written. Log # 235 4- 156 - (240-100, Exception-(New)): Accept in Principle SUBMITTER: H. K. Glenn, Pacific Coast Electrical Association, Inc. RECOMMENDATION: Add an exception at end of sections: ~ptio'n:"Taps need not have separate fault protective devices, provided that the conductors are capable of withstanding the maximum short-circuit current that can occur for the time necessary for a fault protective device on the source side of the conductors to operate. SUBST_ANTIATION: I t is common practice in high-voltage systems to protect tapped feeder circuits with one protective device. The feeder protective device tripping time is coordinated with the available system f a u l t current to open the circuit at less than the conductor short-circuit rating. PANEL ACTION: Accept in Principle. Add the words "and their taps" in the f i r s t sentence after "feeder" and before "shall" in Section 240-100. PANEL COMMENT: Taps should have the same protection as the ~ers. VOTE ON PANEL ACTION: Unanimously Affirmative. 77 Log # 236 4- 157 - (240-101, Exception-(New)): Reject SUBMITTER: H. K. Glenn, Pacific Coast Electrical Association, Inc. RECOMMENDATION: Add an exception at end of section: Exception: Taps need not have separate fault protective devices, provided that the conductors are capable of withstanding the maximum short-circuit current that can occur for the time necessary for a fault protective device on the source side of the conductors to operate. SUBSTANTIATION: I t is common practice in high-voltage systems to protect tapped feeder circuits with one protective device. The feeder protective device tripping time is coordinated with the available system fault current to open the circuit at less than the conductor short-circuit rating. PANEL ACTION: Reject. PANEL COMMENT: Branch circuits do not have taps. VOTE ON PANE[ ACTION: Unanimously Affirmative. COMMENTON VOTE: NIEDERMEYER:--I'm voting to reject, but do not agree with t h e Panel Comment. Branch circuits do have taps (fixtures, ranges, motors, etc.). However, those apply only to 600 volt or less. When getting down to the branch-circuit level we s t i l l are getting short-circuit protection only in this section, and i t could result in actual overloading of a "tap." PANEL ACTION: Reject. FANEL COMMENI: The proposal is a contradiction because i t establishes an exception for a system which is not separately derived. VOTE ON PANELACTION: AFFIRMATIVE: 13 NEGATIVE: Mclntosh. EXPLANATION OF VOTE: MCINTOSH: The fundamental problem remains--a misunderstanding of the intent of this confusing section. Present wording provides a defintion of "separately derived systems" in the same sentence with the "rule" for application. Clarity would be enhanced by separating the "definition" from the "rule"--: "250-5(d) Separately Derived Systems. Where required to be grounded as in (a) or (b) above, a separately derived system shall be grounded as specified in Section 250-26." "Defintion of Separately Derived System: A premises wiring system whose power is derived from generator, transformer, or converter windings and has no direct electrical connection, including a solidly connected grounded circuit conductor, to supply conductors originating in another system." Precedent for this writing style has been established in other sections of the NEC, e.g. Sections 430-71 and 430-81. Log # 517 5- 19 - (250-6(b)(2)): Reject SUBMITTER: J . K . Daugherty, F l i n t , Ml ~NDATION: Delete " / o r " and add " f o r use on or o f f the ve-~-TcTe'r-~etween "equipment" and "through" in the 2nd l i n e . SUBSTANTIATION: To c l a r i f y the i n t e n t of t h i s requirement and to avo-'vo-T-d-the use of "and/or" per Section 5-2 of the Manual of Style f o r NFPA Technical Committee Documents 1978. PANEL ACTION: Reject. PANEL COMMENT: I t is the intention that the provisions apply to both items. S t r i c t adherence to the Style Manual by introduction of the term "or both" appears to make the rule unclear. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . ARTICLE 250 -- GROUNDING Log # 915 5- 16 - (250-2): Accept in Principle SUBMITTER: Ad Hoc Subcommittee on Solar Photovoltaics ~ATION: In f i r s t column of tabulation, add: "Solar Photovoltaic Systems." In last column of tabulation add: N690.41,, "690-42" "690-43" "690-44" SUBSTANTIATION: For correlation with proposed Sections 690-41, -42, -43 and -44. See substantiation for these proposed Sections. PANEL ACTION: Accept in Principle. PANEL COMMENT: Same as Proposal 5-2. VOTE ON PANELACTION: UnanimouslyAffirmative. Log # 497 5- 20 - (250-23(a), Exception No. 5): Reject SUBMITTER: Ernest E. Cannon, Tempe, AZ RECOMMENDATION: Delete the words "be permitted to" after "shall" ~ - T a s t - s e n t e n c e so that i t reads "shall be connected.".... SUBSTANTIATION: All ground-fault protection equipment sensors will perform i f the "connection of the grounding electrode conductor is made to the grounding terminal bar." Somesensors, specifically the window-type which enclose all phases and neutral ( i f existing) will not sense properly under ground-fault conditions i f the grounding electrode conductor is connected in a manner which allows the grounding electrode conductor to be included in the window. PANEL ACTION: Reject. ~N~NT: I t is the intent that the provisions be optional. The proposal would exclude, or make ineffective, sensors operating on the main bonding jumper. VOTE ON PANELACTION: UnanimouslyAffirmative. Log # 718 5- 17 - (250-2): Reject SUBMITTER: James F. Jackson, Carlisle, IN ~ATION: Add to l i s t : Agricultural Buildings Article 547 SUBSTANTIATION: Agricultural buildings have some special grounding problems that should be covered in Article 547. PANEL ACTION: Reject. PANEL COMMENT: There are no special requirements in Article 547 and reference is unnecessary. VOTE ON PANELACTION: Unanimously Affirmative. Log # 237 5- 18 - (250-5(d), (250-5(d), Exception-(New)): Reject SUBMITTER: H. K. Glenn, Pacific Coast Electrical Association, Inc. RECOMMENDATION: (d) Separately Derived Systems. A premises wiring system which is required to be grounded as in (a) and (b) above and whose power is derived from generator, transformer or converter windings shall be grounded as specified in Section 250-26. Exception: A separate system grounding electrode per Section 250-26(c) is not required when the grounded circuit conductor of the derived system is solidly connected to a suitably sized rounded circuit conductor of another supply system. UBSTANTIATION: This section was revised in the 1978 Code to " c l a r i f y " its intent and permit separately derived systems, specifically transferrable alternate power sources, to be grounded solidly to the grounded circuit conductor of the normal service or power supply system. This concept was accepted by the Panel (see Proposal 41, Section 250-23(c), page 82 of NFPA70 PR78). Unfortunately, a Technical Subcommittee adopted a "simple" solution which simply aggravated the problem. They doctored up an existing section instead of trying to really make a clear, definitive statement. Section 250-5(d), at best, only says that separately derived systems shall be grouped as specified in Section 250-25 when there is NO electrical connection-it DOES NOT say how to ground the system if there is an electrical connection. In fact the section does not even hint at the possibility that such a connection is permissible. Therein lies the problem. This recommendation to modify the section does not change the intent, i t merely states the facts clearly. The Panel seems to agree that the Code permits a common grounding electrode and grounded circuit conductor for the normal service premises wiring system and the premises wiring system supplied by a separately derived system. We urge the Panel to accept this recommendation and let the Code section say what we all want i t to say. Log # 471 5- 21 - (250-23(a), Exception No. 2): Reject SUBMII-FER: Darrell Hazel wood, J. M. Perry I n s t i t u t e ~ T I O N : Delete 250-23(a), Exception No. 2, SUBSTANTIATION: The problem with Section 250-24(a) is the required association of the AC system grounded conductor with earth ground in too many places. The more times that a system is connected to the earth, the more potential f o r hazard exists, I f three buildings are fed from a single service equipment, there w i l l be f i v e connections made with the earth to the grounded c i r c u i t conductor. I f any one of the grounded c i r c u i t conductor connections from the service equipment to any of the b u i l d i n g ' s disconnecting means f a i l , the neutral current w i l l reenter the system by the grounding electrode connection at the building, through the earth, to the service equipment or the supply transformer. This current flow sets up a voltage gradient from the building to the point of return to the system. This gradient presents a hazard to personnel. The NEC should not require supply system's connections that increase a potential, f o r hazard. Section 250-24(a) is l i k e l y to be used mainly on farm or ranch locations. These types of occupancies commonly have many types of livestock present. There have been cases of c a t t l e being k i l l e d because of current flow from the grounding electrode connections at the various buildings, Each of the above buildings should have a properly sized equipment grounding conductor ran to each building from the service equipment. Any grounded c i r c u i t conductor connection t h a t may f a i l w i l l simply cause the c i r c u i t to open and not operate. No current flow in the earth w i l l be present, no voltage gradient w i l l be present, and there w i l l be no danger to personnel. PANEL ACTION: Reject. PANEL COMMENT: See Proposal 5-24. VI~InE'-ON-P~A-N~C ACTION: UnanimouslyAffirmative. ~ 78 Log # 236 4- 157 - (240-101, Exception-(New)): Reject SUBMITTER: H. K. Glenn, Pacific Coast Electrical Association, Inc. RECOMMENDATION: Add an exception at end of section: Exception: Taps need not have separate fault protective devices, provided that the conductors are capable of withstanding the maximum short-circuit current that can occur for the time necessary for a fault protective device on the source side of the conductors to operate. SUBSTANTIATION: I t is common practice in high-voltage systems to protect tapped feeder circuits with one protective device. The feeder protective device tripping time is coordinated with the available system fault current to open the circuit at less than the conductor short-circuit rating. PANEL ACTION: Reject. PANEL COMMENT: Branch circuits do not have taps. VOTE ON PANE[ ACTION: Unanimously Affirmative. COMMENTON VOTE: NIEDERMEYER:--I'm voting to reject, but do not agree with t h e Panel Comment. Branch circuits do have taps (fixtures, ranges, motors, etc.). However, those apply only to 600 volt or less. When getting down to the branch-circuit level we s t i l l are getting short-circuit protection only in this section, and i t could result in actual overloading of a "tap." PANEL ACTION: Reject. FANEL COMMENI: The proposal is a contradiction because i t establishes an exception for a system which is not separately derived. VOTE ON PANELACTION: AFFIRMATIVE: 13 NEGATIVE: Mclntosh. EXPLANATION OF VOTE: MCINTOSH: The fundamental problem remains--a misunderstanding of the intent of this confusing section. Present wording provides a defintion of "separately derived systems" in the same sentence with the "rule" for application. Clarity would be enhanced by separating the "definition" from the "rule"--: "250-5(d) Separately Derived Systems. Where required to be grounded as in (a) or (b) above, a separately derived system shall be grounded as specified in Section 250-26." "Defintion of Separately Derived System: A premises wiring system whose power is derived from generator, transformer, or converter windings and has no direct electrical connection, including a solidly connected grounded circuit conductor, to supply conductors originating in another system." Precedent for this writing style has been established in other sections of the NEC, e.g. Sections 430-71 and 430-81. Log # 517 5- 19 - (250-6(b)(2)): Reject SUBMITTER: J . K . Daugherty, F l i n t , Ml ~NDATION: Delete " / o r " and add " f o r use on or o f f the ve-~-TcTe'r-~etween "equipment" and "through" in the 2nd l i n e . SUBSTANTIATION: To c l a r i f y the i n t e n t of t h i s requirement and to avo-'vo-T-d-the use of "and/or" per Section 5-2 of the Manual of Style f o r NFPA Technical Committee Documents 1978. PANEL ACTION: Reject. PANEL COMMENT: I t is the intention that the provisions apply to both items. S t r i c t adherence to the Style Manual by introduction of the term "or both" appears to make the rule unclear. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . ARTICLE 250 -- GROUNDING Log # 915 5- 16 - (250-2): Accept in Principle SUBMITTER: Ad Hoc Subcommittee on Solar Photovoltaics ~ATION: In f i r s t column of tabulation, add: "Solar Photovoltaic Systems." In last column of tabulation add: N690.41,, "690-42" "690-43" "690-44" SUBSTANTIATION: For correlation with proposed Sections 690-41, -42, -43 and -44. See substantiation for these proposed Sections. PANEL ACTION: Accept in Principle. PANEL COMMENT: Same as Proposal 5-2. VOTE ON PANELACTION: UnanimouslyAffirmative. Log # 497 5- 20 - (250-23(a), Exception No. 5): Reject SUBMITTER: Ernest E. Cannon, Tempe, AZ RECOMMENDATION: Delete the words "be permitted to" after "shall" ~ - T a s t - s e n t e n c e so that i t reads "shall be connected.".... SUBSTANTIATION: All ground-fault protection equipment sensors will perform i f the "connection of the grounding electrode conductor is made to the grounding terminal bar." Somesensors, specifically the window-type which enclose all phases and neutral ( i f existing) will not sense properly under ground-fault conditions i f the grounding electrode conductor is connected in a manner which allows the grounding electrode conductor to be included in the window. PANEL ACTION: Reject. ~N~NT: I t is the intent that the provisions be optional. The proposal would exclude, or make ineffective, sensors operating on the main bonding jumper. VOTE ON PANELACTION: UnanimouslyAffirmative. Log # 718 5- 17 - (250-2): Reject SUBMITTER: James F. Jackson, Carlisle, IN ~ATION: Add to l i s t : Agricultural Buildings Article 547 SUBSTANTIATION: Agricultural buildings have some special grounding problems that should be covered in Article 547. PANEL ACTION: Reject. PANEL COMMENT: There are no special requirements in Article 547 and reference is unnecessary. VOTE ON PANELACTION: Unanimously Affirmative. Log # 237 5- 18 - (250-5(d), (250-5(d), Exception-(New)): Reject SUBMITTER: H. K. Glenn, Pacific Coast Electrical Association, Inc. RECOMMENDATION: (d) Separately Derived Systems. A premises wiring system which is required to be grounded as in (a) and (b) above and whose power is derived from generator, transformer or converter windings shall be grounded as specified in Section 250-26. Exception: A separate system grounding electrode per Section 250-26(c) is not required when the grounded circuit conductor of the derived system is solidly connected to a suitably sized rounded circuit conductor of another supply system. UBSTANTIATION: This section was revised in the 1978 Code to " c l a r i f y " its intent and permit separately derived systems, specifically transferrable alternate power sources, to be grounded solidly to the grounded circuit conductor of the normal service or power supply system. This concept was accepted by the Panel (see Proposal 41, Section 250-23(c), page 82 of NFPA70 PR78). Unfortunately, a Technical Subcommittee adopted a "simple" solution which simply aggravated the problem. They doctored up an existing section instead of trying to really make a clear, definitive statement. Section 250-5(d), at best, only says that separately derived systems shall be grouped as specified in Section 250-25 when there is NO electrical connection-it DOES NOT say how to ground the system if there is an electrical connection. In fact the section does not even hint at the possibility that such a connection is permissible. Therein lies the problem. This recommendation to modify the section does not change the intent, i t merely states the facts clearly. The Panel seems to agree that the Code permits a common grounding electrode and grounded circuit conductor for the normal service premises wiring system and the premises wiring system supplied by a separately derived system. We urge the Panel to accept this recommendation and let the Code section say what we all want i t to say. Log # 471 5- 21 - (250-23(a), Exception No. 2): Reject SUBMII-FER: Darrell Hazel wood, J. M. Perry I n s t i t u t e ~ T I O N : Delete 250-23(a), Exception No. 2, SUBSTANTIATION: The problem with Section 250-24(a) is the required association of the AC system grounded conductor with earth ground in too many places. The more times that a system is connected to the earth, the more potential f o r hazard exists, I f three buildings are fed from a single service equipment, there w i l l be f i v e connections made with the earth to the grounded c i r c u i t conductor. I f any one of the grounded c i r c u i t conductor connections from the service equipment to any of the b u i l d i n g ' s disconnecting means f a i l , the neutral current w i l l reenter the system by the grounding electrode connection at the building, through the earth, to the service equipment or the supply transformer. This current flow sets up a voltage gradient from the building to the point of return to the system. This gradient presents a hazard to personnel. The NEC should not require supply system's connections that increase a potential, f o r hazard. Section 250-24(a) is l i k e l y to be used mainly on farm or ranch locations. These types of occupancies commonly have many types of livestock present. There have been cases of c a t t l e being k i l l e d because of current flow from the grounding electrode connections at the various buildings, Each of the above buildings should have a properly sized equipment grounding conductor ran to each building from the service equipment. Any grounded c i r c u i t conductor connection t h a t may f a i l w i l l simply cause the c i r c u i t to open and not operate. No current flow in the earth w i l l be present, no voltage gradient w i l l be present, and there w i l l be no danger to personnel. PANEL ACTION: Reject. PANEL COMMENT: See Proposal 5-24. VI~InE'-ON-P~A-N~C ACTION: UnanimouslyAffirmative. ~ 78 Log # 158 5- 22 - (250-23(a), Exception No. 5): Reject SUBMITTER: Hal Knight, San Jose, CA ~ATION: "Where a ground-return type sensor is used for ground-fault protection of service equipment" the main bonding jumper specified in Sections 250-53(b) and 250-79 is a wire or busbar, and is installed from the neutral bar or bus to the equipment grounding terminal bar or bus in the service equipment, the grounding electrode conductor shall be permitted to be connected to the equipment grounding terminal bar or bus to which the main bonding jumper is connected. SUBSTANTIATION: Article 250-23(a), Exception No. 5, as currently written, can lead to confusion and misapplication of Exception No. 5 in the f i e l d . Manyelectricians and other users of the NATIONAL ELECTRICAL CODEare t o t a l l y unaware of the intent expressed in the 1980 Preprint of the Proposed Amendments for the 1981 NEC concerning the reason for the introduction of Exception No. 5. To minimize confusion or misunderstanding in the f i e l d I believe the NEC should be as " e x p l i c i t , " or implicit, as is possible, in showing the intent of any given Exception that is established to a basic rule. PANEL ACTION: Reject. PANEL COMMENT: Panel feels that the proposal is unduly restrictive and that. the connection permitted in Exception No. 5 is acceptable irrespective of the use of ground sensors. VOTE ON PANELACTION: Unanimously Affirmative. 5- 24 - (250-24): Accept SUBMITTER: CMP 5 RECOMMENDATION: (1) Revise as follows: 250-24. Two or More Bu~T~tructures Supplied from a Common Service. (a) Grounded Systems. Where two or more buildings or structures are supplied from a common service, the grounded system in each building or structure shall have a grounding electrode as described in Part H connected to the ac system grounded c i r c u i t conductor on the supply side of the building disconnecting means. (b) Ungrounded Systems. Where two or more buildings or structures are supplied by a common service from an ungrounded system, each building or s t r u c t u r e shall have a grounding electrode as described in Part H connected to the metal enclosure of the building disconnecting means." (2) Add the following as Exception No. 1 to (a) and Exception to (b): "A grounding electrode at separate buildings or structures shall not be required where only one branch c i r c u i t is supplied and there is no equipment in the building or structure that requires grounding." (3) Add Exception No. 2 to (a) as follows: "Exception No. 2: A grounded circuit conductor connection to the grounding electrode shall not be required i f an equipment grounding conductor is run with the circuit conductors for grounding any noncurrent-carrying equipment, interior metal piping systems or building or structure metal frames and the equipment rounding conductor is bonded to a grounding electrode described n Part H." (4) Delete Exception for (a) and (b). SUBSTANTIATION: (1) Added "or structures" in order to accommodate electrical equipment not housed in buildings. Replaced "single service equipment" with "common service" in order to accommodate Proposal 5-26. (2) Repeated Exception No. I to prevent misinterpretation and to accommodate Proposal 5-27. (3) Corrected Exception No. 2 (formerly Exception (b)) to apply only to Section 250-24(a), to delete "No livestock is housed in the building," and to require that the equipment grounding conductor be bonded to a grounding electrode described in Part H in order to accommodate Proposal 5-28. (4) Delete present Exceptions (a) and (b) in accordance with the above. PANEL ACTION: Accept. VOTE ON PANEL ACTION: ~IIT~A~T --17--NEGATIVE: Cohen, Mclntosh. COMMENT ON VOTE: SESSLER: The-wording in "(a) Grounded Systems" does not make i t clear that the grounding electrode is connected to BOTH the grounded c i r c u i t conductor and the metal enclosure of the disconnecting means. I t is suggested the f i r s t sentence be worded as follows: "Where t w o . . . Part H connected to the metal enclosure of the building disconnecting means and to the ac system..." In Exception No. 2, a more r e l i a b l e equipment grounding conductor such as is required in A r t i c l e s 555 and 680, should be considered f o r livestock buildings instead o f , f o r example, a m e t a l l i c conduit buried under a barnyard. SKUGGEVIG: In order to improve the c l a r i t y of Exception No. 2 to (a), the words "at the second building" should be inserted before the words " i f an equipment grounding conductor is r u n . . . " A comma should f o l l o w the word "systems." In addition, the word "and" should be preceded by a comma, and followed by the word "if." The wording of the exception would then read as follows: Exception No. 2: A grounded c i r c u i t conductor connection to the grounding electrode shall not be required at the second building i f an equipment grounding conductor is run with the c i r c u i t conductors f o r grounding any noncurrent-carrying equipment, interior metal piping systems, or building or structural metal frames, and if the equipment grounding conductor is bonded to a grounding electrode described in Part H. EXPLANATION OF VOTE: COHEN: I t is unclear i f proposed Exception No. 2 to Ca) was intended to require the equipment grounding conductor to be bonded to a grounding electrode at the second building as is required by the present part Ca) to the exception, or just back at the f i r s t building. I f the intent is to require this connection at the second building, I suggest that "which exists at the building" be added to the end of Exception No. 2 to Ca). This wording is the same as at the end of the present exception except that the verb is change from plural to singular. MCINTOSH: The words "or structure" need to be inserted between the word "building" and "disconnecting means" at the end of Section 250-24(a), and at the end of Section 250-24(b), for consistency with the SUBSTANTIATION. My "negative" vote will automatically become "affirmative" if the above change is accepted. ~ Log # 1003 5- 23 - C250-23(b), Exception Nos. i and 2-(New)): Reject SUBMITTER: J. S. Dudor, Fluor Engineers and Constructors, Inc. RECOMMENDATION: Renumber existing exception as Exception No. 1 and add: Exception No. 2: In industrial establishments, when (i) the grounded conductor is not used as a circuit conductor, (27 the equipment ground bus in the service equipment is connected to a grounding electrode by a grounding electrode conductor that complies with parts H and J of Article 250; (3) this grounding electrode is connected to the additional grounding connection required by Section 250-23(a) by a grounding electrode conductor that complies with Part J of Article 250: then the grounded conductor shall not be required to be run with the phase conductors from the source of supply to the service equipment. SUBSTANTIATION: In industrial establishments a 480 volt solidly grounded wye-connected system is the most prevalent electrical system. A common source of supply in a large plant which has its own high voltage distribution system is to have outdoor o i l - f i l l e d transformers feeding 480 v o l t switchgear in an electrical switchgear building or room. Many times the incoming conductors consist of busduct or busway, but could be multiple runs of cable in conduit. The system generally feeds a large group of motors and the neutral or grounded conductor is "not" a circuit conductor. The transformer neutral is grounded properly to a grounding electrode outside the building, the switchgear equipment ground bus is grounded to a grounding electrode inside the building and the separate grounding electrodes are connected by grounding electrode conductors sized per Section 250-94. In the above installation we are treating the 480 volt switchgear as service equipment because of Section 230-201(a) which defines the secondary conductors of this transformer as service conductors. I f Section 250-23(b) is now applied the neutral (grounded) conductor must be brought to the switchgear. This requires four-wire busduct, or i f wire in conduit is used, requires an insulated or bare neutral conductor be run to the switchgear. As the grounded conductor is not used in any c i r c u i t , its only function is to act as a grounding electrode conductor. I f all of the conditions described in the proposed exception are f u l f i l l e d , there is no reason to require the grounded conductor to be run with the phase conductors. For large installations that are typical with 500-3000 KVA transformers, the busduct is generally 50 feet or less in length and the slight increase in impedence caused by not routing the ground conductor near the phase conductors does not effect the performance of the overcurrent protection in the service switchgear. In fact, i f 4-wire busduct is not deliberately specified in equipment procurement documents, equipment vendors will not specify or supply 4-wire busduct for the above installation as there is no neutral bus to connect to in the switchgear equipment. I f this exception is not believed necessary due to the fact the Panel does not believe a service is involved in the problem statement, I would request the Panel or Correlating Committee consider redefining or rewriting Section 230-201 to state that only one service can exist on a large complex system consisting of high and low voltages and that the low voltages should be classified as feeders. PANEL ACTION: Reject. PANEL COMMENT: Proposal could add a substantial inductive reactance to the ground-fault return path which could inhibit operation of ground-fault devices. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 605 5- 25 - (250-24(a)): Reject SUBMIII"ER: Darrell Hazel wood, J. M. Perry I n s t i t u t e ~DATION: 250-24(a). Delete the requirement of having separate buildings connect t h e i r ac system grounded c i r c u i t conductor to a grounding electrode on the supply side of the building disconnecting means when the buildings are fed by a grounded system and a single service equipment. 79 SUBSTANTIATION: The problem with Section 250-24(a) is the required association of the ac system grounded conductor with earth ground in too many places. The more times that a system is connected to the earth, the more potential for hazard exists. I f three buildings are fed from a single service equipment, there will be five connections made with the earth to the grounded circuit conductor. I f any one of the grounded circuit conductor connections from the service equipment to any of the building's disconnecting means f a i l , the neutral current will reenter the system by the grounding electrode connection at the building, through the earth, to the service equipment or the supply transformer. This current flow sets up a voltage gradient from the building to the point of return to the system. This gradient presents a hazard to personnel. The NEC should not require supply system's connections that increase a potential for hazard. Section 250-24(a) is l i k e l y to be used mainly on farm or ranch locations. These types of occupancies commonly have many types of livestock present. There have been cases of cattle being killed because of current flow from the grounding electrode connections at the various buildings. Each of the above buildings should have a properly sized equipment grounding conductor run to each building from the service equipment. Any grounded circuit conductor connection that may f a i l will simply cause the circuit to open and not operate. No current flow in the earth will be present, no voltage gradient will be present, and there will be no danger to personnel. PANEL ACTION: Reject. PANEL COMMENT: See Proposal 5-24. VOTE ON PANELACTION: Unanimously Affirmative. PANEL ACTION: Accept in Principle. IFAITE'IZ-COMME'N'F: Same as Proposal 5-24. V--OT~ ACTION: AFFIRMATIVE: 13 NEGATIVE: Cohen. EXPLANATION Of VOTE: -7~-FTC-N~.'~W-F/ITe-we agree in p r i n c i p l e , we are voting negative because we disagree with the wording in Proposal 5-24. Log # 2010 5- 28 - (250-24, Exception No. 1-(New)): Accept in Principle SUBMITTER: Alvin C. Bierbaum, Iowa Association of Electric Cooperatives RECOMMENDATION: Add Exception No. 1 preceding the Exception for (a) and (b). Changethe wording "Exception for (a) and (b) above" to Exception No. 2. Proposed Exception No. 1. When livestock are housed in Building No. 2, and when a separate equipment grounding conductor is run from Building No. 1 to Building No. 2 for the purpose of grounding all metal equipment and parts, i t shall be permissible to isolate the grounding conductor from the neutral in Building No. 2 i f neutral-to-earth voltages cause distress to the confined livestock. SUBSTANTIATION: Neutral-to-earth voltages (stray voltages) are caused by many factors. One of the primary causes is voltage drop on secondary circuits due to circuit imbalance and long circuits. Secondly, voltage drops are imposed on neutral busbars in a building service entrance which is in turn transmitted to metal grounding conductors, oonduit or panel grounding to a metallic water system. Livestock, particularly dairy and swine, are very sensitive to ac voltages that can occur when part of their body makes contact with the described metal equipment and part of their body is in contact with true earth, ac voltages over one volt are known to cause dairy animals to go out of milk production and to inhibit the growth rate of swine. (Note attached paper on stray voltage problems, page 11, item 7.) You will note that an alternate solution to resolving stray voltage problems is to isolate the neutral from the grounding conductors in the barn panel and run a separate fourth wire either back to the transformer or metering location (main farm service entrance). By adding the proposed exception to NEC Section 250-24, i t would make i t legal or permissible to run the fourth wire and isolate the neutral and grounding wires at to farm service entrance panel (Building No. 2) which is assumed to be a grounded system having a grounding electrode connected to the neutral. (Note: A copy of attached paper available from NFPAon request.) PANEL ACTION: Accept in Principle. PANEL COMMENT: Same as Proposal 5-24. ON PA~L ACTION: --A~'FrRMATIVE: 13 NEGATIVE: Cohen. EXPLANATION OF VOTE: COHEN: While we agree in principle, we are voting negative because we disagree with the wording in Proposal 5-24. Log # 226 5- 26 - (250-24(a) and (b)): Accept in Principle Secretary's Note: The Correlating Committee directs that the Panel Action on this proposal be changed to "Accept in Principle." SUBMITTER: Dan Leaf, Westlake Village, CA ~ E N D A T I O N : Revise as follows: Two or More Buildings Supplied From a Common Service. (a) Grounded Systems. Where two or more buildings are supplied from a common service, the grounded system in each building shall have a grounding electrode connected to the ac system grounded circuit conductor on the supply side of the building disconnecting means. (b) Ungrounded Systems. Where two or more buildings are supplied from a common service, each building shall have a grounding electrode connected to the metal enclosure of the building disconnecting means. SUBSTANTIATION: Buildings may have more than one service, per Section 230-2. I f the separate buildings are served from more than one service, they are not l i t e r a l l y supplied from one (single) service equipment. I f a building contains service equipment but does not supply a system within that building (serving only systems in other separate buildings) i t appears the rounding requirements of (a) and (b) do not apply, i f interpreted iterally. An ungrounded system for a separate building, derived from a transformer adjacent to, and supplied from a grounded system service equipment in another building does not appear to be e x p l i c i t l y covered in the present wording. (And also, a grounded system derived from an ungrounded system service equipment.) PANEL ACTION: Accept. PANEL COMMENT: Proposal is incorporated in Proposal 5-24. VOTE ON PANEL ACTION: AFFIRMATIVE: 13 NEGATIVE: Cohen. EXPLANATION OF VOTE: COHEN: The Panel Action should have been Accept in Principle. While we agree in principle, we are voting negative because we disagree with the wording in Proposal 5-24. I Log # 108 5- 29 - (250-24(c), (d), and (e) (New)): Reject SUBMITTER: Dan Leaf, Westlake Village, CA ~DATION: Add the following paragraphs: Grounding Electrode. The grounding electrode shall be in accordance with Section 250-81, Section 250-83, Section 250-84, and Section 250-86. (d) Grounding Conductor. A grounding conductor sized in accordance with Section 250-94 and installed in accordance with Section 250-92(a) and (b) shall be used to connect the grounded conductor or the metal enclosure of the building disconnecting means to the grounding electrode, as specified in (a) and (b) above. (e) Bonding Jumper. A bonding jumper, installed in accordance with Section 250-53(b) and Section 250-79(a) through (c) shall be used to connect the equipment grounding conductor to the grounded conductor. SUBSTANTIATION: Does not specify grounding electrode conductor size, or type of grounding electrode, and does not require a grounded conductor bonding jumpeC. Bonding jumpers, grounding conductors, and grounding electrodes are clearly specified for services and separately derived systems, but are not clearly specified in this section. Systems and disconnecting meant in remote (separate) buildings are in some instances larger than many services or separately derived systems. I t is possible to ground the grounded conductor without providing a low impedence fault current return path or an equal potential condition between metallic equipment and the grounded conductor. For example: an unenclosed (open) insulated grounding electrode conductor entering an enclosure through a cable connector, with no metallic connection to the enclosure, or a grounding conductor installed in non-metallic conduit. I f the only grounding electrode is a driven pipe or rod the impedence of the ground fault current return path could be quite high. Since a grounded conductor bonding jumper may be the most critical single component in the fault current return path and for equipment grounding, this should be a clear requirement. I t would bring this section into conformance with similar requirements such as Section 250-6, 250-26, and 250-53. Log # 1713 5- 27 - (250-24(a) and (b), Exception-(New)): Accept in Principle SUBMITTER: Charles "Mike" Holt, Concepts in Electricity Inc. ~DATION: Exception: A grounding electrode at a separate building shall not be required where the conditions of either (a) or (b) below are met: (a) Only one branch circuit is supplied and there is no equipment in the building that requires grounding. (b) No livestock is housed in the building, an equipment grounding conductor is run with the circuit conductors for grounding any noncurrent-carrying equipment, interior metal piping systems or building metal frames and the equipment grounding conductor is bonded to grounding electrodes described in Sections 250-81 and 250-83 which exist at the building. SUBSTANTIATION: Repeating the Exception in f u l l will prevent misinterpretation. Manypeople reading this article assume the exception to apply to paragraph (b) only even though the Code clearly states i t s intent. But this is the only article that lists an exception in two preceding paragraphs. Although i t would add bulk, i t would eliminate confusion. 80 PANEL ACTION: Reject. ~ : The supply to the second building is a feeder and not a service as confirmed by a Formal Interpretation 70-78-7, therefore, the sizing for the grounding conductor and bonding jumper is inappropriate. Selection of the grounding electrode is addressed in Proposal 5-24. VOTE ON PANELACTION: UnanimouslyAffirmative. Log # 351 5- 34 - (250-42(a)): Reject SUBMITTER: John Breuklander, Schaller, IA ~NDATION: Delete 5 feet horizontally. Section 250-42(a) where within 8 feet (2.44 m) v e r t i c a l l y or horizontally of ground or grounded metal objects and subject to contact by persons. SUBSTANTIATION: 5 feet horizontally is well within reach of persons who may be using wrenches or other current-carrying objects. A distance of 8 feet would be more acceptable. PANEL ACTION: Reject. PANEL COMME-NT: The Panel recognizes that the adult fingertip-to-fingertip span is in excess of five feet, but the Five-foot dimension is a reasonable working space to avoid inadvertant contact. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 1661 5- 30 - (250-26(a)): Reject SUBMITTER: Charles "Mike" Holt, Concepts in Electricity Inc. ~DATION: 250-26(a). " Except as permitted by Exception No. 4 of Section 250-23(a), this connection shall be made "only once" on the separately derived system from the source to the f i r s t system disconnecting means or overcurrent device; or i t shall be made at the source of a separately derived system which has no disconnecting means or overcurrent devices." SUBSTANTIATION: The intent of 250-26(a) is to permit this connection at either the transformer or disconnect but not at both. As now worded, nothing prevents such a connection at both locations simultaneously. PANEL ACTION: Reject. PANEL COMMENT: The intention is that multiple connections be ~ w e e n the equipment grounding conductor and the grounded circuit conductor for these locations. VOTE ON PANEL ACTION: UnanimouslyAffirmative. , Log # 1444 5- 35 - (250-45(d), Exception No. 1): Accept SUBMITTER: William R. Drake, Daniel Woodhead Company RECOMMENDATION: Add "and portable handlamps" between "tool" and ~TT~i~.7 ..... SUBSTANTIATION: Portable handlamps, like most tools, are low-power devices that can be conveniently used on isolated circuits. When used on an isolated circuit and at 50 volts or less, grounding the handlamp serves no purpose. PANEL ACTION: Accept. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 46 5- 31 - (250-26(a), Exception and (b), Exception}: Reject SUBMITTER: Dan Leaf, Westlake Village, CA RECOMMENDATION: Omit from both Exceptions the words "remote control or signaling." SUBSTANTIATION: Exceptions do not include Class 1 Power Limited ~~My--original proposal in the Preprint of the 1981 NEC was revised by the CMP by adding the words "remote control or signaling c i r c u i t s . " The same transformer could be used for either of these types of circuits or a power-limited c i r c u i t . When used to provide power for damper motors in air-conditioning systems the Exceptions would not apply. There does not appear to be a valid reason for excluding this particular Class 1 system transformer from the Exceptions. PANEL ACTION: Reject. PANEL COMMENT: Power-limited circuits have rated currents of up to thirty-three amperes and should not be grounded with No. 14 AWG copper conductors or'No. 12 AWG aluminum conductors. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 340 5- 36 - (250-45, FPN): Accept in Principle SUBMITTER: John L. Bennett, Towson, MD RECOMMENDATION: Revise the fine print note which is at the end of ~-to"read: "With reference to (c) and (d), portable tools are not intended to be used in damp, wet or conductive locations unless they are properly grounded, double insulated or supplied through an isolating transformer." SUBSTANTIATION: The term "special insulating" in the current wording has been misinterpreted. The proposal wording will c l a r i f y the intent. PANEL ACTION: Accept in Principle. e~-evise by adding the words: "or appliances" after "portable tools" in (d) and delete the word "properly." PANEL COMMENT: The Panel feels appliances should be included as they are in the present FPN and to delete the vague term "properly." VOTE ON PANELACTION: UnanimouslyAffirmative. Log # 1680 5- 32 - (250-26(b)): Reject SUBMITTER: Charles "Mike" Holt, Concepts in Electricity Inc. RECOMMENDATION: 250-26(b}. Grounding Electrode Conductor. A grounding electrode conductor, sized in accordance with Section 250-94 for the derived phase conductors, shall be used to connect the grounded conductor of the derived system to the grounding electrode as specified in (c) below. Except as permitted by Exception 4 of Section 250-23(a), this connection shall be made (any point on the separately derived system) at the same location as the bonding jumper required in 250-24(a) from the source to the f i r s t system . . . " . SUBSTANTIATION: Sections 250-26(a) and (b) as worded would permit the bonding jumper in the transformer and the grounding electrode conductor in the disconnect. By adding the words "at the same location as the bonding jumper required in Section 250-24(a)" i t would give the direction that both connections shall be together at either of the selected locations. PANEL ACTION: Reject. ~ R T : I t is the intention that the bonding jumper and rounding electrode conductor are permitted to be connected at ifferen{ locations. VOTE ON PANELACTION~ Unanimously Affirmative. Log # 518 5- 37 - (250-46, FPN): Accept SUBMII-TER: J. K. Daugherty, Flint, MI RECOMMENDATION: Revise 2nd line "NFPA 78-1977" to "NFPA78-1980." ~NTIATI'dN: In order to reference current Lightning Protection Code date. PANEL ACTION: Accept. VOTE ON PANEL ACTION: UnanimouslyAffirmative~ Log # 317 5- 38 - (250-50 Exceptions for (a) and (b)): Reject SUBMITTER: Chester Flanagan, San Diego, CA RECOMMENDATION: Exception for (a) and (b) above: For ~ { r ~ F t extensions only in existing installations that do not have an equipment grounding conductor in the branch circuit, the grounding conductor of a grounding-type receptacle outlet shall be permitted to be grounded to a grounded cold water pipe near the equipment "provided that the pipe is of continuous metal that extends a minimum of 10 feet into the soil." SUBSTANTIATION: This proposal is for the safety of life/property. Accordingly, the intent here is to ensure that the grounding c i r c u i t r y will have the capacity to safely conduct fault current as required since, in many cases, water pipes are replaced with plastictubing (pipes); visible metal pipe does not necessarily mean that i t is continuous as required for safety. PANEL ACTION: Reject. g/~CEl_-~Ol~I~"~T: The effective grounding of the water pipe requires that i t be bonded to the service and is not related to its length in soil. The Panel does recognize that the grounding requirement of the water pipe needs to be strengthened. See Proposal 5-40. VOTE ON PANEL ACTION: UnanimouslyAffirmative. ~ Log # 1681 5- 33 - (250-26(c)): Reject SUBMITTER: Charles "Mike" Holt, Concepts in E l e c t r i c i t y Inc. ~C)ATION: 250-26(c). Grounding Electrode. Delete: "The grounding electrode shall be as near as practicable to and preferably in the same area as the grounding conductor connection to the system." Add: "The grounding electrode shall be as short as practicable and in the same area as the bonding jumper connection required in Section 250-24(a)." The grounding electrode shall be: (1) the nearest available effectively grounded . . . " . SUBSTANTIATION: Existing wording is confusing as to intent. What is grounding conductor connection to system? This section is to indicate that the electrode should be as close as possible to reduce the length of the conductor and shall be at the same location as the bonding jumper that is required. PANEL ACTION: Reject. PANEL COFV4ENT: The intent of the submitter's recommendation is not clear. VOTE ON PANEL ACTION: UnanimouslyAffirmative. 81 Log # 470 5- 39 - (250-50, Exceptions for (a) and (b)): Accept in Principle SUBMITTER: Darrell HazeIv~od, J. M. Perry Institute RECOMMENDATION: Include the phrase: "The replacement of a nongrounding-type receptacle with a grounding type receptacles before the existing phrase" "For branch circuit extensions only in ...,, SUBSTANTIATION: The intent of the exception seems to be plain: to allow the electrician an easy means to pick up a grounded point to provide an equipment grounding conductor connection for a grounding-type receptacle being supplied by a circuit that does not have an existin 9 equipment grounding conductor. The Exception, though, limits the connection of the receptacle's grounding terminal to a grounded cold water pipe for the extension of an existing circuit. The exception needs to beexpanded to include the situation where a grounding-type receptacle is used to ~eplace a receptacle of the nongrounding-type on a nongrounding circuit. PANEL ACTION: Accept in Principle. PANEL COP~4ENT: Sameas Proposal 5-40. VOTE ON PANELACTION: UnanimouslyAffirmative. Remove this definition from Article 250-53(b) and use i t to replace the less complete definition for Main Bonding Jumper found in Article 100. SUBSTANTIATION: This section provides a more accurate definition of the Main Bonding Jumper than the one found in Article 100. Since two definitions are unnecessary, 250-53(b) should be moved to Article 100 to replace the definition that is listed there. PANEL ACTION: Reject. PANEL COMME~N~F: Section 250-53(b) is a rule and not a definition. ~OTEON_PANEL.ACTION£ Unanimously Affirmative. Log # 1888 5- 44 - (250-53(b)): Reject SUBMITTER: Earl W. Roberts, General Electric Company RECOMMENDATION: Add a new sentence as follows: ~oni-c coupling devices in combination with a bonding Jumper shall be permitted when listed for the application. SUBSTANTIATION: The coupling devices will make i t possible to extend ground fault protection to other portions of the electrical system without jeopardizing the integrity of the bonding jumper. PANEL ACTION: Reject. COMMENT: A current transformer on the main bonding jumper is not prohibited and connection of the grounding electrode conductor to the service ground bus is permitted, therefore, this proposal is not necessary to accomplish the stated purpose. VOTE ON PANELACTION: UnanimouslyAffirmative. Lo~ # 1229 5- 40 - (250-50, Exception for (a) and (b)): Accept in Principle Secretary's Note: I t was the action of the Correlating Committee that this proposal be correlated with Proposal 2-18. SUBMITTER: R. A. Niedermeyer, City of Portland, OR RECOI~MENDATION: For replacement of nongrounding-type receptacles with grounding-type receptacles and for branch-circuit extensions only in existing installations that do not have an equipment grounding conductor in the branch c i r c u i t , the grounding conductor of a grounding-type receptacle outlet shall be permitted to be rounded to a grounded cold water pipe near the equipment. UBSTANTIATION: The Code now provides that i f you extend a circuit (maybe only a few inches) you can, by exception, run a wire to a cold water pipe, but i f you wish to install a grounding-type receptacle to replace a nongrounded receptacle at an existing outlet you can not do i t . Examples of where we continuously require grounding of the outlet is at refrigerator plugs and washing machine outlets. I t is inconceivable that because the outlet is existing, i t is not safe to ground in the fashion provided by the exception, but i f you extend the outlet, i t is okay. In order to make refrigerators, washing machines, etc. safe, the exception needs to provide for existing outlets. PANEL ACTION: Accept in Principle. Revise the proposal to read after "outlet": "shall be permitted to be grounded to a water pipe which is bonded in accordance with Section 250-80(a)." PANEL COMMENT: To strengthen the grounding requirements of the water piping system and to include both hot and cold water pipes. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 310 5- 45 - (250-57): Accept SUBMITTER: Dwight Durham, Southwire Co. RECOMMENDATION: Delete reference to paragraph (c) in Section ~ SUBSTANTIATION: Section 250-57 makes reference to paragraph (c) and there is no paragraph (c). CMP 5 accepted a proposal to delete Section 250-57(c) which was implemented in the 1981 Code. Apparently they forgot to delete the reference contained in Section 250-57. PANEL ACTION: Accept. VOT~-~IT-!~-AITEL ACTION: UnanimouslyAffirmative. Log # 1836 5- 46 - (250-57): Accept SUBMITTER: Paul E. Phelan, Trade Education Inc. and New Hampshire E ~ l Contractors Inc. RECOMMENDATION: In the opening sentence, delete reference to "(c)." SUBSTANTIATION: There is no subparagraph (c). ~C-~CT." Accept. ~TOTC-ON PANEL ACTION: UnanimouslyAffirmative. Log # 519 5- 41 - (250-51(3)): Reject SUBMITTER: J. K. Daugherty, Flint, MI RECOMMENDATION: Delete " s u f f i c i e n t l y . " SUBSTANTIATION: The NEC should avoid vague and indefinite terms per Section 4-7 of the Manual of Style for NFPATechnical Committee Documents 1978. PANEL ACTION: Reject. PANEL COMMENT: Deletion of the word does not c l a r i f y the meaning. VOTE ON PANELACTION: UnanimouslyAffirmative. Log # 520 5- 47 - (250-57, Exceptions Nos. 2 and 3): Reject SUBMII-FER: J. K. Daugherty, Flint, MI RE-'C~O-#{I~-~-DATION: Relocate Exception No. 2 as No. 3 and Exception No. 3 as No. 2. SUBSTANTIATION: For improved continuity. Both Exception Nos. 1 and 3 are referring to ac circuits while Exception No. 2 refers to dc circuits. PANEL ACTION: Reject. PANEL COMMENT: No useful purpose is served by such a rearrangement. VOTE ON PANELACTION: UnanimouslyAffirmative. Log # 1693 5- 42 - (250-53(a)): Reject SUBMII-FER: Charles "Mike" Holt, Concepts in Electricity Inc. RECOMMENDATION: 250-53(a). Grounding Electrode Conductor. A grounding electrode conductor shall be used to connect the equipment grounding conductors, the service-equipment enclosures and, where the system is grounded, the grounded service conductor to the grounding electrode. Re~ve definition from Section 250-53(a) since ~t is duplicated in Article 100. SUBSTANTIATION: This is a repetition of the definition of Grounding Electrode Conductor found in Article 100 ~herefore i t is unnecessary. PANEL ACTION: Reject. PANEL COMMENT: Section 250-53(a) is a rule and not a definition. VOTE ON PANELACTION: UnanimouslyAffirmative. Log # 521 5- 48 - (250-57{b)): Reject SUBMII-rER: J. K. Daugherty, Flint, MI RECOMMENDATION: Revise the 6th line from "green, or green with one or more yellow stripes" to "green, or yellow with green." SUBSTANTIATION: The Verband Deutscher Elektrotechniker (VDE) ~ s do not state stripes because they could be convolutions and the yellow could be more predominate than the green in order to provide f l e x i b i l i t y . PANEL ACTION: Reject. PANEL COMMENT: A convoluted stripe is s t i l l a stripe. ~ ~ ACTION: Unanimously Affirmative. Log # 1204 5- 49 - (250-57(b)): Reject SUBMITTER: Charles J. Hart, NECA R_ECOMMENDA!IQN: Revise Section 250-57(b) to read: (b) With Circuit Conductors. By an equipment grounding conductor run with circuit conductors. In busways and factory-assembled cords or cables the equipment grounding conductor shall be permitted to be bare. In all other cases the equipment grounding conductor shall be provided with an individual covering or insulation with an outer finish that is either green or green with one or more yellow stripes. Log # 1694 5- 43 - (250-53(b)): Reject SUBMII-TER: Charles "Mike" Holt, Concepts in Electricity Inc. ~DATION: 250-53(b). Main Bonding Jumper. For a grounded system, an unspliced main bonding jumper shall be used to connect the equipment grounding conductor and the service-equipment enclosure to the grounded conductor of the system within the service equipment or within the service conductor enclosures. A main bonding Jumper shall be a wire, bus, screw, or similar suitable conductor. 82 Log # 89 5- 53 - (250-60): Accept SUBMITTER: Joseph F. Pinachio, Revere, MA ITE-'C~O-M-ME-NDATION: Retain Section 250-60 as i t is in the 1981 NEC. SUBSTANTIATION: Thousands of ranges and clothes dryers have been grounded to the neutral. Despite all the theorizing about the dire consequences of an open neutral, there appears to be a complete lack of evidence to support the concern that has been expressed. I t is extremely naive to believe that the buyer of a replacement range or dryer will have his circuit to the appliance changed to provide a fourth wire for grounding. PANEL ACTION: Accept. VOT-E~--O-N--F-A-N~L ACTION: AFFIRMATIVE: 11 NEGATIVE: Brown, Nagel, Neiswender. EXPLANATION OF VOTE: --B'~O~N-~." These proposals deal with grounding the Frames of ranges and dryers to the neutral. Proponents, including NEMA, of grounding equipment by means of an equipment grounding conductor base their position on these arguments: (1) From a system standpoint the proper method of grounding equipment is by use of an equipment grounding conductor. (2) The "neutral" is only neutral at the transformer. Any current flow in this conductor raises its voltage above ground. (3) The increasingly common practice of providing for alternate energy sources gives rise to dryers "grounded" to the neutral and pushed back against a GROUNDEDgas pipe. (4) Dryers and washers mounted side by side can have a voltage between them i f one is bonded to the neutral. As microelectronic controls become increasingly important, these voltages will invite control failures, some of which will be safety related. (5) Basing opposition to grounding by means of an equipment grounding conductor on fear of misinstallation by electrical contractors and suspicion of inadequate attention by the inspectors is unwarranted. (6) This exception in the Code invites petitions from others who would misground to the neutral. NAGEL: Same as Proposal 5-58. NEISWENDER: The presently permitted practice of allowing the noncurrent-carrying metal frames and enclosures of ranges, range-top cooking units, wall-mounted ovens and clothes dryers to be grounded by using the grounded circuit conductor (neutral) should be discontinued. Known electrical hazards can result from this practice and the fact that numerous documented cases do not apparently exist due mainly to the variety of different state reporting systems, does not condone further use of this grounding method. The Code has been in the forefront of the establishment of the third wire as a grounding conductor for equipment grounding for many years. This one major area of exception, regardless of whatever reasons are used to j u s t i f y i t , should be deleted from this Code and all future Codes. Retain Exception Nos. 1, 2, and 3 and the two Fine Print Notes. SUBSTANTIATION: The grounding conductor is an essential safety element of a circuit under ground-fault conditions. A wide variety of raceways and f i t t i n g s now in use have no specified r e s i s t i v i t y , ampacity, or I CT performance, and therefore raceways cannot be relied upon to provide the effective grounding path required by Section 250-51. Bare conductors may damage insulated conductors where both are installed together in conduit. For marinas and boatyards (Section 555-7) and swimming pools (Section 680-25), NEC requires an insulated equipment grounding conductor run with the circuit conductors, recognizing that a raceway system is not inherently a reliable electrical conductor. Also, many electrical designers recognize the inadequacy of the raceway system as a suitable grounding conductor for modern wiring systems and specify the installation of an insulated grounding conductor in raceways. At intervals of 10 feet and less throughout its length, a raceway system has joints or terminations, often not accessible f o r inspection, that may and on occasion do become loose, rusted, or corroded so as to impair electrical conductivity. The intent of this proposal is to provide the same level of equipment-grounding r e l i a b i l i t y for all installations as is now required for marinas and swimming pools. PANEL ACTION: Reject. PANEL COMMENT: Proposal would eliminate all raceways as a grounding conductor. Submitter has not supplied adequate support for such a proposal as requested when previous similar proposals were made. VOTE ON PANELACTION: Unanimously Affirmative. Log # 287 5- 50 - (250-57(b), Exception No. 1): Accept Secretary's Note: The Correlating Committee directs that t h i s proposal be referred to CMP 6 f o r information. SUBMITTER: Dan Leaf, Westlake V i l l a g e , CA ~ATION: Add the words "or covered" a f t e r the word "insulated" in the f i r s t sentence; and add the words "or covering" a f t e r the word " i n s u l a t i o n " in a, b, and c. SUBSTANTIATION: Paragraph (b) permits "covered" grounding conductors but Exception No. i addresses only "insulated" conductors.. PANEL ACTION: Accept. PANEL COMMENT: Accept and refer to CMP 6 for correlation. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 659 5- 51 - (250-58(a)): Reject SUBMITTER: George C. Gingher, Association of Iron and Steel ]~-6-glneers RECOMMENDATION: Change the last sentence of paragraph (a) to read: "The structural metal frame of a building shall not be used as the required equipment grounding conductor for ac equipment "except" in high-bay manufacturing buildings equipped with embedded ground loop structural bonding." SUBSTANTIATION: The disallowance of structural metal building frames for grounding was placed in the 1977 Code on the basis that steel members "may" have too high an impedance to operate overcurrent devices. However, more than a century of experience with high-bay industrial buildings, such as those used in the steel industry, has shown that such f a c i l i t i e s "do," in fact, have a s u f f i c i e n t l y low impedance path to operate protective devices. The restriction has a substantial economic impact on installation costs because of the additional conductors required under the present language for large electrical systems. There is no j u s t i f i c a t i o n to have an exclusive disallowance of using structural building frames for grounding; the Code should disallow only those systems that f a i l to provide the required protection, such as prefabricated metal buildings, light structural construction, etc. PANEL ACTION: Reject. PANEL COMMENT: The suhmitter does not provide enough technical information to contradict previous studies which have shown that structural building steel is not adequate as an equipment grounding conductor. VOTE ON PANELACTION: UnanimouslyAffirmative. Log # 284 5- 54 - (250-60): Reject SUBMITTER: Maurice C. Wagner, Contra Costa Electrical Code Research and Development Committee RECOMMENDATION: Delete: Entire Section 250-60 SUBSTANTIATION: Refer to 250-61(b), Exception No. 1 proposal. recent f i r e investigation in the c i t y of Martinez, California, revealed that a NEMA, 3-pole, 3-wire, 10-30R dryer receptacle grounded (neutral) conductor was connected to the ungrounded terminal by mistake. The ungrounded (black) conductor was mistakenly connected to the ("L" slot) grounded (neutral) terminal. The Appliance Mechanic then installed an equipment grounding jumper in the dryer from the case to the grounded (neutral) terminal that was mistakenly connected to the ungrounded conductor. The result was that the dryer case was energized to a potential of 115 to 120 volts above ground condition. The owner complained two or three times that the dryer Look such a long time to dry a load of clothes. The Appliance Mechanic did not determine that the machine was connected incorrectly and was operating i n e f f i c i e n t l y in a low 115 volt condition instead of 230 volts. A fault path through the f l e x i b l e plastic exhaust duct, steel spiral wire, caused the plastic to burst into flames behind the dryer located in the garage area resulting in a f i r e loss. I f a four-wire receptacle had been installed, the clothes dryer supplied with a four-wire cord set and the dryer case grounded to the equipment grounding conductor instead of to the grounded (neutral) conductor, this Fire loss would have no doubt been averted. The practice of permitting by Code the grounding of noncurrent-carrying metal frames, enclosures and cases of ranges, clothes dryers, range top cookin9 units and wall-mounted ovens, with the grounded (neutral/white) current-carrying conductor of a branch circuit should be abolished and discontinued. This wnuld afford a higher standard of electrical safety and allow the electrical industry to have a uniform, standard, straight-forward procedure of grounding noncurrent-carrying metal parts of " a l l " equipment without exception and comply.with the provisions of the Code as already outlined in Sections 250-57-59-61(b) (excluding Exception No. 1) and 91(b). Log # 522 5- 52 - (250-59(b)): Reject SUBMITTER: J. K. Daugherty, F l i n t , MI ~ T I O N : Revise the 6th line from "green or green with one or more yellow stripes" to "green, or yellow with green." SUBSTANTIATION: The Verband Deutscher Elektrotechniker (VDE) Standards do not state stripes because they could be convolutions and the yellow could be more predominate than the green in order to provide f l e x i b i l i t y . PANEL ACTION: Reject. PANEL COMMENT: Sameas Proposal 5-48. VOTE ON PANEL ACTION: UnanimouslyAffirmative. 83 The provisions of Section 250-60 to ground noncurrent-carrying metal frames and enclosures, as listed, with the grounded circuit load conductor is not limited to dwelling unit occupancies. This system of grounding is not restricted for commercial and industrial occupancy applications. Therefore, the specified equipment frames and noncurrent-carrying metal parts could be grounded to the (neutral) grounded current-carrying conductor of a coin-operated laundry located in a commercial occupancy, adjacent to a high ampacity electrical service where fault and circulating currents are considered objectional and undesirable from the standpoint of electrical safety. The practice of grounding nonelectrical parts of appliances using the branch circuit grounded (neutral) conductor~ has evidently been deemed an unsafe practice for the reason that the 1981 NATIONAL ELECTRICAL CODESection 250-60 excludes this practice of grounding metal frames of equipment installed in mobile homes and recreational vehicles. This maximum safety should be extended to all wiring systems by deleting the provisions of Section 25~)-60, including Section 250-61(b) Exception No. 1. There was a period of time that cable assemblies were not manufactured with an inherent equipment grounding conductor in the cable assembly listed by a recognized testing laboratory. This is not the case today. There are available adequate supplies of listed cable assemblies provided with equipment grounding conductors, such as nonmetallic sheathed cable, service entrance cable Type "R" and armored cable Type AC, to mention a few, that complies with grounding requirements as set forth in Sections 250-57-59-61(b) (excluding Exception No. 1) and 91(b). Field inspections have revealed washing machine cases grounded with an equipment grounding conductor as part of the cable assembly and the clothes dryer case grounded with an aluminum grounded (neutral) current-carrying conductor. High resistance aluminum connections of the grounded circuit conductor of the dryer has caused from 15 to 20 volts potential difference between the dryers and washer cases in a number of instances. Inspections also revealed that NEMAnumber 10-30R regular type receptacles installed in nonmetallic outlet boxes l e f t the device mounting yokes and the metal cover plates not grounded and in an above ground potential. Therefore, Line No. 10 of the NEMA configuration chart should be eliminated. 3 POLE. 3 WIRE Log # 389 5- 55 - (250-60): Reject SUBMITTER: R. G. DeLuca, Maricopa County, AZ RECOMMENDATION: Delete entire section. New wording as follows: 250-60(a) FP4~MESOF RANGESAND C]_OTHES DRYERS. Frames of electric ranges, wall-mounted ovens, counter-mounted cooking units, clothes dryers, and outlet or junction boxes which are part of the circuit for these appliances shall be grounded in the manner specified by Section 250-57 or Section 250-59. , Exception No. 1. Ranges, clothes dryers, etc. may be ground to the f u l l y insulated grounded conductor when the voltage is 115/230 V 3-wire, single-phase or 120/208, 3-wire, single-phase tapped from a 4-wire, 3-phase wye-connected system. The grounded conductor shall be not less than No. 10 CU or No. 8 AL. Exception No. 2. (a) Existing system where grounded to the uninsulated conductor. (b) The circuit originates at the service equipment panelboard that contains the equipment jumper described in 250-79 and is grounded as required by 250-5(b) to the electrode conductor. Exception No. 3. Mobile homes and travel trailers shall be grounded according to Section 550-9 or Section 551-21. Add new paragraph. (c) Panelboards with insulated neutral (sub panels). Grounding of electrical and nonelectrical equipment shall be through connection to a grounding bus in the panelboard. The grounding bus shall be grounded through the grounding c i r c u i t supplying the panelboard. Grounded circuit conductor (neutral) and the neutral bus shall be insulated from equipment enclosures and other grounded parts. Grounding o~ ranges, ovens, cook tops and dryers from sub panels may be grounded according to i or 2 below. 1. 250-60(a), Exception No. 1. 2. As described in (c) above. SUBSTANTIATION: 250-60 as now written in the Code is too complex, covers too much ground, and is easily misunderstood. See Webster's Dictionary, quote: "semicolon, links main clauses not joined by coordinating conjuctions." Not only does one need an understanding of the art, he must also ha~e a degree in English with "great" understanding of punctuation marks. This proposal is intended to prohibit further use of uninsulated grounded conductors, and To preserve the grounding philosophy for equipment grounding. i . This proposal is intended to inform or alert that ranges, dryers, etc. may be grounded as in 1 and 2 above. 2. Will prevent the use of uninsulated grounded conductors. 3. Will s t i l l permit ranges and dryers to be grounded to the grounded conductor from remote panels. 4. Prevent current flowing in grounding conductor. PANEL ACTION: Reject. ~COM~E'N'T: With some editorial corrections as covered in Proposal 5-56, Section 250-60 adequately conveys the intent of the requirements. Field experience has not shown problems with the use of the uninsulated grounded conductor when i t is part of SE cable and originates at the service equipment. VOTE ON PANEL ACTION: 2 POLE. 3 WIRE N ( M A Rqlfetence: 3 pole. 3 wlrll dwwcos Receptacle: 10-30R P1ui: ~,O-30P REGULAR STARREDITEMS ARE "FOR REPLACEMENT USE ONLY" t GROUNO(O Line No. 14 of the NEMAconfiguration chart should be used because separate terminals are provided for each conductor of a 125/250 volt, 3-wire with ground branch circuit cable. NEGATIVE: Brown, Nagel. EXPLANATION OF VOTE: BROWN: See comment on Proposal 5-53. NAGEL: Same as Proposal 5-59. ALL 3 POe( 4 WlR( w w GI ~ GI N(MA reference Log # 400 5- 56 - (250-60): Accept SUBMITTER: Kenneth L. Gebert, City of Minneapolis, MN RECOMMENDATION: Revise line 5 to read, "250-59; or, except for ~------Bi~le-h~nes-and recreational vehicles, shall be permitted, etc." Provide comma after "or." Provide comma after "vehicles." Change "recreation" to "recreational." Change "or" to "and" between homes-recreation. SUBSTANTIATION: The insertion of a comma before "Except" and aTr~Ve~'icl'6s '' sets the two mentioned units off as an exclusion to the rule. Without the comma, specifically the one after vehicle, the rule would permit that which the exception was e x p l i c i t l y inserted for. The lack of punctuation contributes to confusion as to the meaning and the interpretation of .intent. The addition of "al" to recreation is to keep i t in line with the terminology of Article 551. PANEL ACTION: Accept. ~ L ACTION: UnanimouslyAffirmative. Receptacle L4.60R 14-60P ] 0 A I2$J2$OV $OA 1251250V 60a I Z $ / 2 ~ V N(MA ~ l e r e ~ 4 RecepCacJ4 |4-soa ~4.soe Laundry equipment is often located in the garage area and by Code, we find washer outlets grounded to an equipment ground conductor, the dryer grounded to the neutral (white) conductor. Then, adjacent to the dryer we find a receptacle that must be GFCI protected with an equipment grounding conductor. I t is time consuming for the inspector to explain the reasons for all these requirements to an electrical installer or a frustrated homeowner who has decided to be an electrician because of today's economy. For these reasons i t is highly recommended that Section 250-60 be deleted entirely, including Exception No. 1 of Section 250-61(b) and Line No. 10 for 125/250V receptacle devices of the NEMAconfiguration chart. PA/WEL ACTION: Reject. PANEL COMMENT: Same as substantiation in Proposal 5-55. VOTE ON PANEL ACTION: AFFIRMATIVE: 11 NEGATIVE: Brown, Nagel, Neiswender. EXPLANATION OF VOTE: BROWN: See comment on Proposal 5-53. NAGEL: Same as Proposal 5-58. NEISWENDER: Refer to comment for Proposal 5-53. Log # 435 5- 57 - (250-60): Reject SUBMITTER: Southwestern Section IAEI ~OMMENDATION: Delete entire section - new wording as follows: ~-6"6(-a~'Frames of Ranges and Clothes Dryers. Frames of electric ranges, wall-mounted ovens, counter-mounted cooking units, clothes dryers, and outlet or junction boxes which are part of the circuit for these appliances shall be grounded in the manner specified by Sections 250-57 or 250-59. Exception No. 1. Ranges, clothes dryers, etc., may be grounded to the f u l l y insulated grounded conductor when the voltage is 115/230-volt, 3-wire, single-phase or 120/208-volt, 3-wire, single-phase tapped from a 4-wire, 3-phase wye-connected system. 84 Field inspections have revealed washing machine cases grounded with an equipment grounding conductor as part of the cable assembly and the clothes dryer case grounded with an aluminum grounded (neutral) current-carrying conductor. High resistance aluminum connections of the grounded circuit conductor of the dryer has caused from 15 to 20 volts potential difference between the dryers and washer cases in a number of instances. Inspections also revealed that NEMAnumber I0-30R regular type receptacles installed in nonmetallic outlet boxes l e f t the device mounting yokes and the metal cover plates not grounded and in an above ground potential. Therefore, Line No. 10 of the NEMA configuration chart should be eliminated. (Note: See Proposal 5-54 for configuration chart.) Line number 14'of the NEMAconfiguration chart should be used because separate terminals are provided for each conductor of a 125/250-volt, 3-wire-with-ground branch-circuit cable. (Note: See Proposal 5-54 for configuration chart.) Laundry equipment is often located in the garage area, and by Code, we find washer outlets grounded to an equipment ground conductor, the dryer grounded to the neutral white conductor. Then, adjacent to the dryer we find a receptacle that must be GFCI protected with an equipment grounding conductor. I t is time consuming for the inspector to explain the reasons for all these requirements to an electrical installer or a frustrated homeowner who has decided to be an electrician because of today's econO~lY. For these reasons i t is highly recommended that Section 250-60 be deleted entirely, including Exception No. I of Section 250-61(b) and Line No. 10 for 125/250V receptacle devices of the NEMAconfiguration chart. PANEL ACTION: Reject. PANEL COMMENT: Same as Proposal 5-55. ~/'OTI~--~N"P'~NEL" ACTION: --~FF-rR--M~Tf/~C.'---I'i~ NEGATIVE: Brown, Nagel, Neiswender. EXPLANATI ONOF .VOTE BROWN: See comment on Proposal 5-53. NAGEL: Usually the electric clothes dryer is located next to the washer which is grounded to the grounding conductor in the 3-wire cord. The electric dryer is grounded to the branch circuit grounded (neutral) conductor. This could present a real shock hazard i f the neutral conductor becomes disconnected. The question often raised is, i f i t is safe to ground the dryer to the grounded (neutral) conductor, why not the washer? There was some indication in the report by the Ad Hoc "Subcommittee on Grounding of Ranges and Clothes Dryers that these appliances should be grounded by means of an equipment grounding conductor. I f and when these appliances should become co,nputorized, we may find ourselves in a real dilemma because of our present grounding practices. NEISWENDER: Refer to comment for Proposal 5-53. The grounded conductor shall be not less than No. 10 copper or No. 8 aluminum. Exception No. 2: (a) Existing system where grounded to the uninsulated conductor. (b) The circuit originates at the service equipment panelboard that contains the equipment jumper described in Section 250-79 and is grounded as required by Section 250-5(b) to the electrode conductor. Exception No. 3: Mobile homes and travel trailers shall be grounded according to Sections 550-9 or 551-21. SUBSTANTIATION: Section 250-60, as now written in the Code, is too complex, covers too much ground and is easily misunderstood. See Webster's Dictionary, quote: "semicolon, links main clauses not joined by coordinating conjunctions." Not only does one need an understanding of the art, he must also have a degree in English with "great" understanding of punctuation marks. This proposal is intended to prohibit further use of uninsulated grounded conductors and - to preserve the grounding philosophy for equipment grounding. Have supported Section 250-60 to delete grounding to neutral. This is a companion proposal in case the other proposal is not accepted and will help to eliminate part of the hazards that now exist. PANEL ACTION: Reject. hANEL COMMENT: Same as substantiation in Proposal 5-55. VOTE ON PANEL ACTION: AFFIRMATIVE: 12 NEGATIVE: Brown, Nagel. EXPLANATION OF VOTE: BROWN: See comment on Proposal 5-53. NAGEL: Same as Proposal 5-59. Log # 436 S- 58 - (250-60): Reject SUBMITTER: Southwestern Section IAEI ~ATION: Delete: Entire Section 250-60. SUBSTANTIATION: Refer to 250-61(b), Exception No. 1 proposal. recent f i r e investigation in the' City of Martinez, California, revealed that a NEMA3-pole, 3-wire, 10-30R dryer receptacle grounded (neutral) conductor was connected to the ungrounded terminal by mistake. The ungrounded (black) conductor was mistakenly connected to the (L-slot) grounded (neutral) terminal. The appliance mechanic then installed an equipment grounding jumper in the dryer from the case to the grounded (neutral) terminal that was mistakenly connected to the ungrounded conductor. The result was that the dryer case was energized to a potential of 115 to 120 volts above ground condition. The owner complained two or three times that the dryer took such a long time to dry a load of clothes. The appliance mechanic did not" determine that the machine was connected incorreGtly and was operating i n e f f i c i e h t l y in a low 115 volt condition instead of 230 volts. A f a u l t path through the flexible plastic exhaust duct, steel spiral wire, caused the plastic to burst into flames behind the dryer located in the garage areas, resulting in a f i r e loss. I f a 4-wire receptacle had been installed, the clothes dryer supplied with a 4-wire cord set and the dryer case grounded to the equipment grounding conductor'instead of to the grounded (neutral) conductor, this f i r e loss would have no doubt been averted. The practice of permitting by Code the grounding of noncurrent-carrying metal frames, enclosures and cases of ranges, clothes dryers, range-top cooking units and wall-m~unted ovens, with the grounded (neutral/white) current-carrying conductor of a branch c i r c u i t , should be abolished and discontinued. This would afford a higher standard of electrical safety and allow the electrical industry to have a uniform, standard, straight-forward procedure of grounding noncurrent-carrying metal parts of " a l l " equipment, without exception, and comply with the provisions of the Code as already outlined in Sections 250-57-59-61(b) (excluding Exception No. 1) and 91(b). The provisions of Section 250-60 to ground noncurrent-carrying metal frames and enclosures, as listed, with the grounded circuit load conductor is not limited to dwelling unit occupancies. This system of grounding is not restricted for commercial and industrial occupancy applications. Therefore, the specified equipment frames and noncurrent-carrying metal parts could be ~rounded t 9 the (neutral) 9rounded current-carrying conductor of a o~n opera~eo ~aunary ~ocaced in a commercial occupany, adjacent to a high ampacity electrical service where fault and circulating currents are considered objectionable and undesirable from the standpoint of electrical safety. The practice of grounding nonelectrical parts of appliances using the branch-circuit grounded (neutral) conductor, has evidently been deemed an unsafe practice for the reason that the 1981 NEC Section 250-60 excludes this practice of grounding metal frames of equipment installed in mobile homes and recreational vehicles. This maximum safety should be extended to all wiring systems by deleting the provisions of Section 250-60, including Section 250-61(b), Exception No. I . There was a period of time that cable assemblies were not manufactured with an inherent equipment grounding conductor in the cable assembly listed by a recognized testing laboratory. This is not the case today. There are available adequate supplies of listed cable assemblies provided with equipment grounding conductdrs, such as nonmetallic sheathed cable, service entrance cable type "R" and armored cable type AC, to mention a few, that comply with grounding requirements as set forth in Sections 250-57-59-61(b) (excluding Exception No. 1) and 91(b). Log # 1244 5- 59 - (250-60): Reject SUBMITTER: IAEI ~TION: Delete entire section - New wording as follows: 250-60(~T~. Frames of Ranges and Clothes Dryers. Frames of electric ranges, wall-mounted ovens, counter-mounted cooking units, clothes dryers, and outlet or junction boxes which are part of the c i r c u i t for these appliances shall be grounded in a manner specified by Section 250-57 or 250-59. Exception No. 1. Where grounded to the f u l l y insulated grounded conductor when the voltage is 115/230V 3-wire, single-phase or 120/208, 3-wire, single-phase tapped from a 4-wire, 3-phase wye-connected system. The grounded conductor shall be not less than No. 10 CU or No. 8 AL. Exception No. 2. (a) Existing system where grounded to the uninsulated conductor and the circuit originates at the service equipment panelboard that contains the equipment jumper described in Section 250-79 and is ground as required by Section 250-5(b) to the electrode conductor. Exception No. 3. Mobile homes and travel trailers shall be grounded according to Section 550-9 or 551-21. SUBSTANTIATION: Section 250-60, as now written in the Code, is ~ m p l - 6 ~ ' c ' o v e r s too much ground and is easily misunderstood. See Webster's Dictionary, quote: "semicolon, links main clauses not joined by coordinating conjunctions." Not only does one need an understanding of the art, he must also have a degree in English with "great" understanding of punctuation marks. This proposal is intended to prohibit further use of uninsulated grounded conductors and - to preserve the grounding philosophy for equipment grounding. PANEL ACTION: Reject. " # ' A ' N [ C ~ T : Some as Proposal 5-55. VOTE ON PANEL ACTION: --ATFIIT-MA'FII/E~IT~ NEGATIVE: Brown, Nagel. EXPLANATION OF VOTE: ~{-'~-cdn~I~eBt on Proposal 5-53. NAGEL: The Ad Hoc Subcommittee on Grounding of Ranges and Clothes Dryers in its report indicated a strong support to require that the grounded circuit conductor be insulated. I believe this proposal should be accepted because i t would be the f i r s t step towards eliminating the use of the grounded (neutral) conductor to ground ranges and clothes dryers. BS Log # 1938 5- 60 - (250-60): Reject SUBMITTER: Donald W. Zipse, West Chester, PA RECOMMENDATION: Delete entire Section 250-60. ~USS~ANTIATIO-N: SAFETY I t is agreed that due to the inherent electrical leakage of the ranges and ovens and the energizing of frames of ranges, ovens and dryers that this equipment must be grounded. The use of the grounded circuit conductor to provide a safe equipment ground is questionable. Lack of accuracy in reporting f a t a l i t i e s associated with this equipment is a problem. However, we should not have to wait until a f a t a l i t y can be undeniably attributed to this method of wiring before we act to delete this unsafe practice. COST I t was demonstrated that any additional cost, i f actual, would not put any manufacture or method at a disadvantage with respect to other means of accomplishing the desired task. The requirement of mobile homes to u t i l i z e the 4-wire method of g~ounding has resulted in reduced cost because of volume. I t has been established that SE cable may not be readily available in sizes required as is universally thought or that i t is the least costly. The Code is not retroactive. Therefore, massive rewiring costs are not a factor. WIRING METHODS This change in wiring methods would not disrupt or cause drastic wiring practice changes, nor would i t result in confusion. Instructions presently found in ranges and dryers show in detail how to wire the equipment using a separate ground conductor, 4-wire method. Major municipalities have recognized this Code deficiency and require a 4-wire installation without any reports of confusion, problems, or d i f f i c u l t y of installing, or in obtaining the 4-conductor cable or receptacles and plugs. Nor are there reports of problems with relocating or replacement or interchangability. The problem with adaptors previously has produced unfounded fear with respect to future use. One does not have the possibiqity of misuse of an adaptor in this case as the configuration is not symmetrical and an adaptor, should one come on the market, would f i t only one way. I t was determined that an adaptor would cause no more problem than presently'exist. STANDARDIZATION By removing this obsolete exception to what has become the norm, we will have a standard method of grounding electrical equipment. This will reduce the confusion that exists with the public, that grounding of any equipment can be accomplished without a ground conductor by using the "white wire" as is done in ranges and dryers. Consistency would be gained. The public, due to the 3-wire cords and plugs and receptacles, which have become the standard now, are well aware of the need for a separate equipment ground conductor. This was not prevalent prior to the requirement of grounded receptacles. Will the continuance of this exception prohibit or cause problems in the future with electronic devices due to the flow of uncontrolled current over the ground path? Should not all continuous current flow be contained in an insulated conductor and prevented from flowing uncontrolled over surfaces, piping, ground, etc.? The parallel paths that exist due to this exception allows, er Ohm's Law, continuous uncontrolled current flow. ANEL ACTION: Reject. PANEL COMMENT: Sameas Proposal 5-55. VOTE ON PANELACTION: Log # 523 5- 62 - (250-60, Exception-(New)): Reject SUBMITTER: J. K. Daugherty, Flint, MI R~DATION: Make "250-59" in the 5th line the end of the ~---q'uTrement[--The remainder is an Exception to this requirement: Exception: Except for mobile homes and recreation vehicles, the frames of electric ranges, wall-mounted ovens, counter-mounted cooking units, clothes dryers, and outlet or Junction boxes which are part of the circuit for these appliances shall be permitted to be grounded to the circuit conductor. . . . . . . . . . . • Continue as presently stated but in I t a l i c s . SUBSTANTIATION: In order to i l l u s t r a t e that this is clearly an exception and not the requirement. PANEL ACTION: Reject. PA~NEL COM~'NT: See editorial clarification in Proposal 5-56'. VOTE ON..PANEL.~q~L Unanimously Affirmative. NEGATIVE: Brown, Nagel, Neiswender. EXPLANATION OF VOTE: BROWN: ~ee comment on Proposal 5-53. NAGEL: Sameas Proposal 5-58. NEISWENDER: Refer to co~nent for Proposal 5-53. Log # 607 5- 65 - (250-61, Exception No. 2): Reject SUBMITTER: Darrell Hazelwood, J. M. Perry Institute RECOMMENDATION: Delete Section 250-61, Exception No. 2. ~O~-STKNYI'AiI6N: The problem with Section 250-24(a) is the required association of the ac system grounded conductor with earth ground in too many places. The more times that a system is connected to the earth, the more potential for hazard exists. I f three buildings are fed from a single service equipment, there will be five connections made with the earth to the grounded circuit conductor. I f any one of the grounded circuit conductor connections from the service equipment to any of the building's disconnecting means f a i l , the neutral current will reenter the system by the grounding electrode connection at the building, through the earth, to the service equipment or the supply transformer. This current flow sets up a voltage gradient from the building to the point of return to the system. This gradient presents a hazard to personnel. The NEC should not require supply system's connections that increase a potential for hazard. Section 250-24(a) is likely to be used mainly on farm or ranch locations. These types of occupancies commonly have many types of livestock present. There have been cases of cattle being killed because of current flow from the grounding electrode connections at the various buildings. Each of the above buildings should have a properly sized equipment grounding conductor run to each building from the service equipment. Any grounded circuit conductor connection that may f a i l will simply cause the circuit to open and not operate. No current flow in the earth will be present, no voltage gradient will be present, and there will be no danger to personnel. PANEL ACTION: Reject. ~'COMME'NT: Sameas Proposals 5-24 and 5-25. ~O~FC-~NTA-N~'C" ACTION: UnanimouslyAffirmative. Log # 524 5- 53 - (250-60(c)): Reject SUBMITTER: J. K. Daugherty, Flint, MI RECOMMENDATION: Add "Type SE" between "a" and "service-entrance" SUBSTANTIATION: Type SE cable does have a covering over the ~ninsulated neutral therefore i t is important that Type SE be specified in order that Type USE with a bare neutral will not be used. PANEL ACTION: Reject. PANEL COMMENT: Sameas Proposal 5-55. VOTE ON.PANEL.ACTION~ Unanimously Affirmative. Log # 48 5- 64 - (250-60(e) (New)): Reject SUBMITTER: Dan Leaf, Westlake Village, CA RECOMMENDATION: Add paragraph (e) as follows: The circuit wiring method shall be nonmetallic-sheathed cable, type UF cable, type SE cable, or nonmetallic raceway. SUBSTANTIATION: Permits an undesirable and potentially hazardous condition when metallic raceway system is used. This Section and Section 250-61(b), Exception No. 1 permit the grounded circuit conductor to be utilized as an equipment grounding conductor. When installed in this manner and in metallic raceway, the raceway system is effectively a conductor in parallel with the grounded neutral. This could cause heating or arcing at raceway connections or at contact areas between the raceway and other grounded metal. A break in the neutral may not be readily apparent as the raceway would then become the sole grounded circuit conductor, with perhaps a pronounced increase in the potential for heating and/or arcing effects. PANEL ACTION: Reject. PANEL COMMENT: Same as Proposal 5-55. ON-F/~N'EL ACTION: --A~"F[ITF~ATIVE: 13 NEGATIVE: Nagel. EXPLANATION OF VOTE: ~EC:"S~6 "as~F~posal 5-59. ~ Log # 1891 5- 61 - (250-60): Accept SUBMITTER: Peter Van Putten, Michigan Chapter IAEI ~OATION: Revise line 5 to read, "250-59; or, except for mobile homes and recreational vehicles, shall be permitted etc." Provide comma after "or." Provide comma after "vehicles." Change "recreation" to recreational. Change "or" to "and" between homes - recreation. SUBSTANTIATION: The insertion of a comma before "Except" and a--f't-e'r--m~h-Tcl-es '' sets the two mentioned units off as an exclusion to the rule. Without the comma, specifically the one after vehicle, the rule would permit that which the exception was e x p l i c i t l y inserted for. The lack of punctuation contributes to confusion as to the meaning and the interpretation of intent. The additon of "al" to recreation is to keep i t in line with the terminology of Article 551. PANEL ACTION: Accept. PANEL COMMENT: Sameas Proposal 5-56. VOTE ON PANELACTION: Unanimously Affirmative. 8B The provisions of Section 250-60 to ground noncurrent-carrying metal frames and enclosures, as listed, with the grounded circuit load conductor is not limited to dwelling unit occupancies. This system of grounding is not restricted for commercial and industrial occupancy applications. Therefore, the specified equipment frames and noncurrent-carrying metal parts could be grounded to the (neutral) grounded current-carrying conductor of a coin-operated laundry located in a commercial occupancy, adjacent to a high ampacity electrical service where fault and circulating currents are considered objectional and undesirable frSm the standpoint of electrical safety. The practice of grounding nonelectrical parts of appliances using the branch circuit grounded (neutral) conductor, has evidently been deemed an unsafe practice for the reason that the 1981 NATIONAL ELECTRICAL CODESection 250-60 excludes this practice of grounding metal frames of equipment installed in mobile homes and recreational vehicles. This maximum safety should be extended to all wiring systems by deleting the provisions of Section 250-60, including Section 250-61(b) Exception No. i . There was a period of time that cable assemblies were not manufactured with an inherent equipment grounding conductor in the cable assembly listed by a recognized testing laboratory. This is not the case today. There are available adequate supplies of listed cable assemblies provided with equipment grounding conductors, such as nonmetallic sheathed cable, service entrance cable Type "R" and armored cable Type AC, to mention a few, that complies with grounding requirements as set forth in Sections 250-57-59-61(b) (excluding Exception No. i) and 91(b). Field inspections have revealed washing machine cases @rounded with an equipment grounding conductor as part of the cable assembly and the clothes dryer case grounded with an aluminum grounded (neutral) current-carrying conductor. High resistance aluminum connections of the grounded circuit conductor of the dryer has caused from 15 to 20 volts potential difference between the dryers and washer cases in a number of instances. Inspections also revealed that NEMAnumber I0-30R regular type receptacles installed in nonmetallic outlet boxes l e f t the device mounting yokes and the metal cover plates not grounded and in an above ground potential. Therefore, Line No. 10 of the NEMA configuration chart should be eliminated. (Note: See Proposal 5-54 for configuration chart.) Line No. 14 of the NEMAconfiguration chart should be used because separate terminals are provided for each conductor of a 125/250 volt, 3-wire with ground branch circuit cable. (Note: See Proposal 5-54 for configurationchart.) Laundry equipment is often located in the garage area and by Code, we find washer outlets grounded to an equipment ground conductor, the dryer grounded to the neutral (white) conductor. Then, adjacent to the dryer we find a receptacle that must be GFCI protected with an equipment grounding conductor. I t is time consuming for the inspector to explain the reasons for all these requirements to an electrical installer or a frustrated homeowner who has decided to be an electrician because of today's economy. For these reasons i t is highly recommended that Section 250-60 be deleted entirely, including Exception No. 1 of Section 250-61(b) and Line No. 10 for 125/250V receptacle devices of the NEMAconfiguration chart. PANEL ACTION: Reject. PANEL COMMENT: See Proposal 5-55. VOTE ON PANEL ACTION: --AFI~IITFIA'FIITg.T NEGATIVE: Nagel, Neiswender. EXPLANATION OF VOTE: NAGEL: S~e as-P-{oposal 5-58. NEISWENDER: Refer to comment for Proposal 5-53. Log # 606 5- 66 - (250-61(a)): Reject SUBMITTER: Darrell Hazelwood, J. M. Perry Institute ~ T I O N : 250-61(a)~ Delete the last phrase: "and on the supply side of the main disconnecting means for separate buildings as provided in Section 250-24." SUB.STANTIATION: The problem with Section 250-24(a) is the required association of the ac system grounded conductor with earth ground in too many places. The more times that a system is connected to the earth, the more potential for hazard exists. I f three buildings are fed from a single service equipment, there will be five connections made with the earth to the grounded circuit conductor. I f any one of the grounded circuit conductor connections from the service equipment to any of the building's disconnecting means f a i l , the neutral current will reenter the system by the grounding electrode connection at the building, through the earth, to the service equipment or the supply transformer. This current flow sets up a voltage gradient from the building to the point of return to the system. This gradient presents a hazard to personnel. The NEC should not require supply system's connections that increase a potential for hazard. Section 250-24(a) is l i k e l y to be used mainly on farm or ranch locations. These types of occupancies commonly have many types of livestock present. There have been cases of cattle being killed because of current flow from the grounding electrode connections at the various buildings. Each of the above buildings should have a properly sized equipment grounding conductor run to each building from the service equipment. Any grounded circuit conductor connection that may f a i l will simply cause the circuit to open and not operate. No current flow In the earth will be present, no voltage gradient will be present, and there will be no danger to personnel. PANEL ACTION: Reject. ~ : Sameas Proposals 5-24 and 5-25. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 438 5- 67 - (250-61(b)): Reject SUBMITTER: Southwestern Section IAEI RECO~ENDATION: Delete: Exception No. 1 of Section 250-61(b). SUBSTANTIATION: Refer to 250-60 proposal, Log No. 436. ~NO-N~-." Reject. PANEL COMMENT: Same as Proposal 5-53. ~NETACTION: AFFIRMATIVE: 12 NEGATIVE: Nagel, Neiswender. COMMENT ON VOTE: ~ R T - - ~ T - C o m m e n t should read "See Proposal 5-53" rather than "Same as Proposal 5-53" since Proposal 5-53 was accepted while Proposal 5-67 was rejected, and the action on the former was the basis for the action on the l a t t e r . EXPLANATION OF VOTE: NAGEL: Sameas Proposal 5-58. NEISWENDER: Refer to comment for Proposal 5-53. Log # 285 5- 68 - (250-61(b), Exception No. 1): Reject SUBMI1-FER: Maurice C. Wagner, Contra Costa Electrical Code Research and Development Committee RECOMMENDATION: Delete: Exception No. 1 of Section 250-61(b) ~I]B-S"~T~F:/~r~: Refer to 250-60 proposal. A recent f i r e investigation in the city of Martinez, California, revealed that a NEMA, 3-pole, 3-wire, 10-30R dryer receptacle grounded (neutral) conductor was connected to the ungrounded terminal by mistake. The ungrounded (black) conductor was mistakenly connected to the ("L" slot) grounded (neutral) terminal. The Appliance Mechanic then installed an equipment grounding jumper in the dryer from the case to the grounded (neutral) terminal that was mistakenly connected to the ungrounded conductor. The result was that the dryer case was energized to a potential of 115 to 120 volts above ground condition. The owner complained two or three times that the dryer took such a long time to dry a load of clothes. The Appliance Mechanic did not determine that the machine was connected incorrectly and was operating i n e f f i c i e n t l y in a low 115 volt condition instead of 230 volts. A fault path through the f l e x i b l e plastic exhaust duct, steel spiral wire, caused the plastic to burst into flames behind the dryer located in the garage area resulting in a f i r e loss. I f a four-wire receptacle had been installed, the clothes dryer supplied with a four-wire cord set and the dryer case grounded to the equipment grounding conductor instead of to the grounded (neutral)conductor, this f i r e loss would have no doubt been averted. The practice of permitting by Code the grounding of noncurrent-carrying metal frames, enclosures and cases of ranges, clothes dryers, range top cookin 9 units and wall-mounted ovens, with the grounded (neutral/white) current-carrying conductor of a branch c i r c u i t should be abolished and discontinued. This would afford a higher standard of electrical safety and allow the electrical industry to have a uniform, standard, straight-forward procedure of grounding noncurrent-carrying metal parts of " a l l " equipment without exception and comply with the provisions of the Code as already outlined in Sections 250-57-59-61(b) (excluding Exception No. 1) and 91(b). Log # 437 5- 69 - (250-61(c)-(New)): Reject SUBMITTER: Southwestern Section IAEI RECOMMENDATION: Add new paragraph. ---TE~ Pa6ef6o'ards with Insulated Neutral (Subpanels). Grounding of electrical and nonelectrical equipment shall be through connection to a grounding bus in the panelboard. The grounding bus shall be grounded through the grounding circuit supplying the panelboard. Grounded circuit conductor (neutral) and the neutral bus shall be insulated from equipment enclosures and other grounded parts. Grounding of ranges, ovens, cook-tops and dryers from subpanels may be grounded according to 1 or 2 below. 1. Section 250-60(a), Exception No. 1. 2. As described in (c) above. SUBSTANTIATION: (1) This proposal is intended to inform or alert that ranges, dryers, etc., may be grounded as in i and 2 above. l~I Will prevent the use of uninsulated grounded conductors. Will s t i l l permit ranges and dryers to be grounded to the grounded conductor from remote panels. (4) Prevent current flowing in grounding conductor. PANEL ACTION: Reject. ~CO~CNT: See Proposals 5-55 and 5-57. V-O~E~-ON--I~A-N-E--CACTION: AFFIRM;ff/qE~"I"3-"NEGATIVE: Nagel. EXPLANATION OF VOTE: - ' N / ~ G E 1 _ ~ - - ~ r o p o s a l 5-59. 87 Log # 510 5- 70 - (250-71(a)): Reject SUBMITTER: Mark Porsch, Sheldon, IA RECOMMENDATION: The noncurrent-carrying metal parts of equipment indicated in (1), (2) and (3) below shall be effectively bonded together so as to be electrically continuous. SUBSTANTIATION: Added on: So as to be electrically continuous. This is to insure that no one will only bond one end. PANEL ACTION: Reject. PANEL COMMENT: I t is the intent that only a single path to th e grounded circuit conductor is required. VOTE ON PANELACTION: UnanimouslyAffirmative. Log # 44 5- 75 - (250-71(b)(1)): Accept in Part SUBMITTER: Dan Leaf, Westlake Village, CA RECOMMENDATION: Substitute the words "raceways or cables" for the word "conduit." SUBSTANTIATION: Does not specifically permit Electrical Metallic Tubing, or other metallic service raceways or cable to be utilized for intersystem bonding. Other metallic enclosures are permitted for services, including EMT, MI cable, MC cable, busways, wireways, auxiliary gutters, which may be installed exposed. PANEL ACTION: Accept in Part. Change "conduit" to "raceways." PANEL COMMENT: Service cables do not provide an acceptable ~ means for bonding. VOTE ON PANELACTION: UnanimouslyAffirmative. Log # 47 5- 71 - (250-71(a)(3)): Accept in Principle SUBMITTER: Dan Leaf, Westlake Village, CA ~ATION: Substitute the words "metallic raceway" for the word "conduit." SUBSTANTIATION: Does not specifically require bonding of Electrical Metallic Tubing. Section 250-92 requires or permits EMT as an enclosure for a grounding electrode conductor. This Section could be interpreted as not requiring bonding when so used. PANEL ACTION: Accept in Principle. Revise Section 250-71(a)(3) to read: "(3) Any metallic raceway or armor enclosing a grounding electrode conductor as permitted in Section 250-92(a)." PANEL COMMENT: Clarifies the intent of the proposal. VOTE ON PANEL ACTION: UnanimouslyAffirmative.. Log # 1628 5- 76 - (250-71(b)(3)): Reject SUBMITTER: Walter Gwynn, Onondaga Metropolitan Electrical ~ r s Association, Inc. RECOMMENDATION: I t is proposed that the Following be deleted from A~ticle 250-71(b)(3): "Approved means for the external connection of a bonding or grounding conductor to the service raceway or equipment." SUBSTANTIATION: The requirement causes excessive cost to. homeowner. I t is Further feared that the requirement may cause manufacturers to add a bonding wire, thereby increasing product cost. PANEL ACTION: Reject. FAN-~C COMMENT: The ~equirement is necessary for safety. VOTE ON PANELACTION: Unanimously Affirmative. Log # 1700 5- 72 - (250-71(b)): Reject SUBMITTER: Charles "Mike" Holt, Concepts in Electricity Inc. ~ATION: 250-71(b). Bonding to Other Systems. At dwellings, an accessible means external to enclosures for connecting intersystem bonding and grounding conductors shall be provided at the service by at least one of the following means. "Conductor shall be No. 6 CU or No. 4 AL." SUBSTANTIATION: 1981 Code does not require specified sizing of this conductor. I am not qualified to determine method of sizing but some method should be provided. PANEL ACTION: Reject. I~B~TE'L--C-O]~NT: Submitter's concern is adequately covered by fine print note. VOTE ON PANELACTION: UnanimouslyAffi,rmative. Log # 1762 5- 77 - (250-71(b)(3)): Reject SUBMITTER: Tom Tombarello~ Paul Revere Chapter IAEI R~DATION: Revise (b)(3) as follows: ---T-3-)-"A'{iel-d-installed approved means... SUBSTANTIATION: The addition of the word "field-installed" clarifies that a means may be provided where provisions of (b)(1) or (b)(2) are not available. The fine print note suggesting a projection date led many users of the NEC to believe the provisions of (b)(3) was to be a factory-assembled means only. PANEL ACTION: Reject. ~N~CL--L~O-MTQE~ ' T: The FPN will not appear in the 1984 edition of the NATIONAL ELECTRICAL CODE. I t is the Panel's intention that the acceptable means be either factory- or field-installed. VOTE ON PANELACTION: Unanimously Affirmative. Log # 1118 5- 73 - (250-71(b)): Reject SUBMITTER: J. H. (Jim) Richards, Maryland Electrical Inspectors ~ o n RECOMMENDATION: Amend as follows: An accessible means external to enclosures shall be provided for connection of intersystem bonding and grounding "at or near" the service equipment. SUBSTANTIATION: Recessed equipments makes service conduits and grounding eleEtrode conductors at the service equipment inaccessible, however, usually somewhere near this equipment the grounding electrode conductor is exposed. There would seem to be no reason that the telephone u t i l i t y or the CATV installers should not be required to make some reasonable effort to do their own rounding. ANEL ACTION: Reject. PANEL COMMENT: The term "near" is vague. The present requirements convey that the connection may be at any point, for example, on the serviGe raceway or grounding electrode conductor where accessible. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 1290 5- 78 - (250-71(b), Exception-(New)): Reject SUBMITTER: IAEI RECOMMENDATION: Add new Exception: Exception. For flush recessed type enclosures, intersystem bonding shall be permitted distant From the enclosure in an area where the conditions of (b)(1) and (b)(2) are accessible. SUBSTANTIATION: Inclusion of this Section in the 1981 NEC failed to make note of flush recessed type service equipment. This type equipment usually installed in a finished room would prevent or prohibit proper installation of the requirements listed. PANEL ACTION: Reject. PANEL COMMENT: Sameas Proposal 5-73. VOT~-~FA-FFL'~ ACTION: ~FI~MA~IVE ~ "1%NEGATIVE: Nagel. COMMENTON VOTE: --~E~ff:----Y-he-proposer's substantiation fails to recognize that flush-mounted service equipment is one of the reasons that the available bonding means is needed and was specifically addressed in the support of Proposal 69 on Section 250-71 in the 1980 Preprint. EXPLANATION OF VOTE: --lqA-G'l~'l_-~-l-6C~where enclosures are flush recessed, the present wording can be misinterpreted. I am in Favor of this proposal because the exception would address that problem. ~ Log # 1749 5- 74 - (250-71(b)): Reject SUBMITTER: Charles "Mike" Holt, Concepts in Electricity Inc. ITE'C~O'~OATION: 250-71(b). Bondings to Other Systems. Delete: "At dwellings", and add wording in quotations: "A building containing dwelling units shall have" an accessible means external to enclosures for connecting intersystem bonding and groundin9 conductors shall be provided at the service by at least one of the following means. SUBSTANTIATION: This would better identify the Code's intent, PANEL ACTION. 7- Reject. PANEL COMMENT: The term "dwelling" is defined in Article 100 and conveys the intent. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 1370 5- 79 - (250-71(b),Exception-(New)): Reject SUBMITTER: M. H. Lounsbury, Eastern Section IAEI RECOMMENDATION: Exception. For flush recessed type enclosures, ~ystem bonding shall be permitted distant from the enclosure in an area where the conditions of (b)(1) and (b)(2) are accessible. SUBSTANTIATION: Inclusion of this Section in 1981 NEC failed to make note of flush recessed type service equipment. This type equipment usually installed in a finished room would prevent or prohibit proper installation of the requirements listed. 88 Log # 318 5- 84 - (250-72(d)): Accept in Principle SUBMITTER: Chester Flanagan, San Diego, CA RECOMMENDATION: Bonding Jumpers. Bonding jumpers meeting other ~ ~ o f ths article "shall be used to assure electrical continuity." Bonding jumpers shall be used around concentric or eccentric knockout that are punched or otherwise formed so as to impair the electrical connection to ground. SUBSTANTIATION: This proposal is being submitted to amend apparent error(s) in the subject section. PANEL ACTION: Accept in Principle. P-A-~I~I'~--C~MMEN ' TT: See the Panel recommendation For Proposal 5-85. VOTE ON PANEL ACTION: Unanimously Affirmative. PANEL ACTION: Reject. !~TE'L--C~I~E'RT: Same as Proposal 5-73. VOTE ON PANEL ACTION: AFFIRMATIVE: ~3---NEGATIVE: Nagel. COMMENT ON VOTE: SESSLER: See comment on Proposal 5-78. EXPLANATION OF VOTE: NAGEL: Same as Proposal 5 - 7 8 . Log # 1231 5- 80 - (250-71(b), Exception-(New)): Reject SUBMITTER: Tom Morosco, Utica, NY RECOMMENDATION: Amend Section 250-71(b) to read: Exception. For flush recessed type enclosures, intersystem bonding shall be permitted d i s t a n t from the enclosure in an area where the conditions of (b)(1) and (b)(2) are accessible. SUBSTANTIATION: Inclusion of t h i s Section in the 1981 NEC f a i l e d to make note of flush recessed type service equipment. This type equipment usually i n s t a l l e d in a f i n i s h e d room would prevent or p r o h i b i t proper i n s t a l l a t i o n of the requirements l i s t e d . PANEL ACTION: Reject. PANEL COMMENT: Same as Proposal 5-73. VOTE ON PANEL ACTION: AFFIRMATIVE: 13 NEGATIVE: Nagel. COMMENT ON VOTE: SESSLER: See comment on Proposal 5-78. EXPLANATION OF VOTE: NAGEL: Same as Proposal 5-78. Log # 525 5- 81 - (250-72-Title)): Reject SUBMITTER: J. K. Daugherty, F l i n t , MI RECOMMENDATION: Revise t i t l e to: "250-72. Bonding Service Equipment for 250 Volts or Less." SUBSTANTIATION: In order that the t i t l e will more nearly cover the requirement. PANEL ACTION: Reject. PANEL COMMENT: The requirements of Section 250-72 apply to all services. VOTE ON PANELACTION: Unanimously Affirmative. Log # 526 5- 85 - (250-72(d)): Accept SUBMII-TER: J. K. Daugherty, Flint, MI RECOMMENDATION: Combine 1st and 2nd sentence to: "Bonding jumpers meeting the other requirements of this article shall be used around concentric or eccentric knockouts that are punched or otherwise formed so as to impair the electrical connection to ground." SUBSTANTIATION: The former 1st sentence was dangling. F ~ R ~ Accept. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . Log # 527 86 - (250-74, Exception No. 1): Accept in Principle SUBMITTER: J. K. Daugherty, Flint, MI RECOMMENDATION: Add 2nd sentence: "This Exception shall not inc'~d~16~ boxes with raised covers." SUBSTANTIATION: Exception No. I has been misinterpreted to ~3~{16~ boxes with raised covers where there is only one 6-23 screw securing a receptacle yoke. PANEL ACTION: Accept in Principle. J ~ ~ n d sentence in Exception No. 1 to read: "This Exception shall not apply to cover-mounted receptacles." PANEL COMMENT: Expandson the original proposal to include all cove~t66 receptacles. VOTE ON PANEL ACTION: Unanimously Affirmative. • 5- Log # 833 5- 87 - (250-74, Exception No. 4 and FPN-(New)): Accept in Principle SUBMITTER: Warren H. Lewis, Computer Power Systems Corp. RECO_____MM.ME_N~!gN: Add: "This grounding conductor shall not be terminated to a grounding electrode(s) which is isolated from the applicable derived system or service grounding terminal." Note: Where the receptacle box is connected to flexible metal conduit (Article 350) or to a liquidtight flexible metal conduit (Article 351-A) in lengths exceeding six feet a separate insulated equipment bonding jumper shall be required and shall be installed in accordance with Section 250-79." SUBSTANTIATION: Exception No. 4 is often misinterpreted to allow the equipment bonding wires (green wires) to be connected, into some sort of "isolated" ground ( i . e . , "quiet earth ground") which is not metallically bonded to the g~ounding point of the associated service or separately derived system grounding point, nor a water pipe or even building steel. This is done in an attempt to control real or imagined electrical "noise" and the ground fault path is effectively defeated or seriously compromised. This is becoming an almost universal problem with major computer manufacturers demanding large scale use of IC receptacles on "isolated" ground systems. This is an exceptionally serious problem in "old work" where flexible metal conduit is used within the walls and the original grounded receptacle is changed to an IC style using Exception No. 4 as j u s t i f i c a t i o n . PANEL ACTION: Accept in Principle. -~Exception No. 4 as follows: (1) Change the reference to "Section 384-27, Exception No. i . " (2) Revise last sentence of Section 250-74, Exception No. 4 after the word "directly" as follows: "at an equipment grounding conductor terminal of the applicable derived system or service." (3) Add a Fine Print Note as follows: "Use of an isolated equipment grounding conductor does not relieve the requirement for grounding the raceway system and outlet box." PANEL COt~MENT: This incorporates the intent of the proposal. VOTE ON~ANEL.ACT~ONz Unanimously Affirmative. Log # 1900 5- 82 - (250-72, FPN-(New)): Reject SUBMITTERS: B. Auger/H. B. Love, Michigan Chapter IAEI ITE'i~-O]~N~TION: Add a fine print note at the end of the section: For metal raceway to bok connections on services, some form of bonding is always required. A bonding bushing, bonding wedge, bonding lock nut, or other approved device shall always be installed when a metal connector or raceway is brought into a service enclosure; even when connections are with cut holes or the outer periphery of concentric knockouts. SUBSTANTIATION: There is probably more confusion on the bonding of services than any other single item in the Code. The discussion, debates and disagreements seem to go on and on. Even though the rules are simply and f l a t l y stated, the Code-Making Panel must assume some responsibility towards helping to c l a r i f y this basic question. This FPN is offered as an opening in that direction. PANEL ACTION: Reject. ~ E L COMMENT: The proposal is unacceptable as a FPN since i t contains a mandatory requirement. Stating the requirements twice in another format will not add clarity. VOTE ON PANELACTION: UnanimouslyAffirmative. Log # 286 5- 83 - (250-72(c)): Accept in Principle SUBMI~ER: Dan Leaf, Westlake Village, CA RECOMMENDATION: Change the word "couplings" to " f i t t i n g s . " SUBSTANTIATION: The word "coupling" per se, does not include threadless connectors which when screwed into threaded hubs or bosses, or used with grounding or bonding locknuts or bushings appear to be a satisfactory and commbnly accepted method of obtaining electrical continuity at services. PANEL ACTION: Accept in Principle. Revise t i t l e of (c) to read: "Threadless Couplings and Connectors." Revise f i r s t sentence to read: "Threadless couplings and connectors made..." PANEL COMMENT: Panel agrees, but feels "connectors" is the appropriate term. VOTE ON PANELACTION: UnanimouslyAffirmative. Log # 644 5- 88 - (250-74, Exception No. 4): Reject SUBMITTER: Clyde H. Craig, Craig Electric Co. RECOMMENDATION: Revise (added wording in quotations): On the grounding c i r c u i t , a receptacle in which the ground terminal is purposely insulated from the receptacle mounting means "and the threaded 6-32 machine screw hole for attachment of a cover plate," shall be permitted. 89 SUBSTANTIATION: With the exception of hubble and P and S there is a ~ p a - a t - ~ - c r e a t e d when mounting most insulated receptacles on 4-inch square or hand~ boxes and using metal and/or raised cover plates. This obviously violates the insulated grounding terminal by connecting the normal equipment ground to the insulated ground. This causes problems on computer circuits, certain medical equipment, etc. etc. PANEL ACTION: Reject. PANEL COMMENT: This is an equipment installation problem and not a Code related problem. VOTE ON PANEL ACTION: Unanimously Affirmative. SUBSTANTIATION: 1. This will alert the wiremen that an effective #at-t-h-~ is required and necessary, with no impairments such as eccentric or concentric knockouts or reducing washers creating high resistance connections; thus preventing the opening of the protective device. 2. Manypeople are not aware of the magnitude of fault currents that may and can be much greater than load currents. 3. Manyfires and destruction of equipment is directly related to an ineffective ground path. PANEL ACTION: Accept in Principle. --R6~ion 250-76 as follows: 250-76. Bonding f o r Over 250 Volts. "For c i r c u i t s of over 250 v o l t s to ground, the e l e c t r i c a l c o n t i n u i t y of metal raceways and cables with metal sheaths that contain any conductor other than service conductors shall be assured by one or more of the methods specified for services in Section 250-72(b) through (e)." "Exception: Where oversized, concentric, or eccentric knockouts are not encountered, the following methods shall be permitted: (a) Threadless couplings and connectors for cables with metal sheaths. (b) Two 1ocknuts, on rigid metal conduit, or intemediate metal conduit, one inside and one outside of boxes and cabinets. (c) Fittings with shoulders that seat firmly against the box or cabinet, such as electrical metallic tubing connectors, flexible metallic conduit connectors and cable connectors, with one locknut on the inside of boxes and cabinets." PANEL COMMENT: Panel feels this wording accomodates the intent of e~-~-prb'pb-sal'." Also see Proposal 5-83. VOTE ON PANEL ACT~ON~ Unanimously A f f i r m a t i v e . Log # 1656 5- 89 - (250-74, Exception No. 4): Accept in Principle SUBMITTER: Charles "Mike" Holt, Concepts in Electricity, Inc. ~q~'-CR~Q~:-~ATION: 250-74. Exception No. 4. Where required for the reduction of electrical noise on the grounding c i r c u i t , a receptacle in which the grounding terminal is purposely installed from the receptacle mounting means shall be permitted. The receptacle grounding terminal shall be grounded by an insulated equipment grounding conductor run with the circuit conductors. This grounding conductor shall be permitted to pass through one or more panelboards, without connection to the panelboard grounding terminal as permitted in Section 384-27 Exception, so as to terminate directly at the applicable derived system or service grounding "electrode" terminal. SUBSTANTIATION: This is the only instance in the Code where the term "service grounding terminal" is used. I t is not a readily identifiable term and using the new term ~ould provide c l a r i t y . EDITORIAL CHANGE. PANEL ACTION: Accept in Principle. PANEL COMMENT: See Panel recommendation on Proposal 5-87. ON PANELACTION: UnanimouslyAffirmative. Log # 439 5- 94 - (250-76(c)-(New)): Accept in Principle SUBMITTER: Southwestern Section IAEI RECOMMENDATION: Paragraph (c) to Section 250-76. --llTr-eacf~6ss'Yittings or 2 locknuts described in (a) and (b) shall be used only when knockouts are properly sized and cut" for the conduit or cable size required. The use of one of methods described in Section 250-72(b) through (e) becomes necessary to assure an effective grounding path whenever grounding continuity is impaired by reducing washers, improperly cut knockouts or when concentric or eccentric knockouts are encountered. See Section 250-51. SUBSTANTIATION: An effective path to ground is required and necessary, with no impairments such as eccentric or concentric knockouts or reducing washers creating high resistance connections, thus preventing the opening of the protective device. Many poeple are not aware of the magnitude of fault currents that may and can be much greater than load currents. Many fires and destruction of equipment is directly related to an ineffective ground path. PANEL ACTION: Accept in Principle. P-A-N'ET-COMME~T: See Proposal 5-93. VOTE ON PANELACTION~ Unanimously Affirmative. 5- 90 - (250-75): Reject Log # 528 SUBMITTER: J. K. Daugherty, Flint, MI CIT-EC ' O~MMENDATION: Delete "effectively" and "where necessary" from the 4th line. SUBSTANTIATION: The NEC should avoid vague and indefinite terms per Section 4-7 of the Manual of Style f o r NFPATechnical Committee Documents 1978. PANEL ACTION: Reject. PANEL COMMEN~: The Panel feels terms are necessary to allow use of grounding paths in equipment which have been tested to demonstrate their effectiveness. VOTE ON PANELACTION: Unanimously Affirmative. Log # 529 5- 91 - (250-76-Title): Reject SUBMITTER: J. K. Daugherty, Flint, MI ]TE~]~'-~E--N-OATION: Revise t i t l e to: "250-76. I~)nding Service Equipment for Over 250 Volts" and move this section to immediately after Section 250-72. SUBSTANTIATION: In order that the t i t l e will more nearly cover the requirement and so that Sections 250-72 and 250-76 will have continuity. PANEL ACTION: Reject. I~KITE'L--(~C4E-~T: Section 250-76 applies to all circuits operating at over 250 volts to ground and is not limited to services. VOTE ON PANELACTION: UnanimouslyAffirmative. Log # 1245 5- 95 - (250-76(c)-(New)): Accept in Principle SUBMITTER: IAEI ~L~U~'I~DATION: To add new paragraph (c) to 250-76. Threadless f i t t i n g s or 2 locknuts described in (a) and (b) shall be used only when knockouts are properly sized and cut for the conduit or cable size required. The use of one of the methods described in Section 250-72'(b) through (e) becomes necessary to assure an effective grounding path whenever grounding continuity is impaired by reducing washers, improperly cut knockouts or when concentric or eccentric knockouts are encountered. See Section 250-51. SUBSTANTIATION: An effective path to ground is required and necessary, with no impairments such as eccentric or concentric knockouts or reducing washers creating high resistance connections, thus preventing the opening of the protective device. Many people are not aware of the magnitude of fault currents that may and can be much greater.than load currents. Many fires and destruction of equipment is directly related to an ineffective ground path. PANEL ACTION: Accept in Principle. NI~-~N-E'C--CO~ENT: See Proposal 5-93. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e , Log # 43 5- 92 - (250-76(a)): Accept SUBMITTER: Dan Leaf, Westlake Village, CA ITE'CDIq~[EI~ATION: Add the words "electrical metallic tubing" after the word "conduit." SUBSTANTIATION: Clarification: Does not specifically include electrical metallic tubing as a raceway wiring method. EMT is permitted for circuits of over 250 volts to ground; Section 250-72(c) includes EMT threadless couplings as a bonding method for services. This proposal will c l a r i f y use of EMT and associated threadless f i t t i n g s as being suitable for bonding purposes on circuits of over 250 volts to ground. PANEL ACTION: Accept. VOTE ON PANEL ACTION: Unanimously Affirmative. 5- 96 - (250-78): Reject Log # 1946 SUBMII-FER: Richard J. Buschart, Monsanto Company RECOMMENDATION: Delete this section in its entirety. ~TI]I~-~-T'A-NT'IAYfON: The special grounding and bonding requirements in Hazardous ~ s s i f i e d ) locations are in Sections 501-16, 502-16, and 503-16. Section 250-78 is a duplication of part of the requirements. PANEL ACTION: Reject. PAICE!_~: Section 250-78 is needed for the basic bonding requirements. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 392 5- 93 - (250-76(c)-(New)): Accept in Principle SUBMITTER: R. G. DeLuca, Maricopa County, AZ I~E'C~O-#I~'ITDATION: (c) RACEWAYENTRIES Threadless f i t t i n g s or 2 locknuts described in (a) and (b) shall be used only when knockouts are properly sized and cut for the conduit or cable size required. The use of one of the methods described in Section 250-72 (b) thru (e) becomes necessary to assure an effective grounding path whenever grounding continuity is impaired by reducing washers, improperly cut knockouts or when concentric or eccentric knockouts are encountered. See Section 250-51. go Log # 290 5- 97 - (250-79(b)): Reject SUBMITTER: Dan Leaf, Westlake Village, CA RECOMMENDATION: Add the following: Bonding jumper connections shall not be required to be accessible except as required by Section 250-71(b). SUBSTANTIATION: Section 250-112 Exception permits certain connections of a grounding electrode conductor to be non-accessible, but does not address connections of bonding jp'umers. Bonding jumpers are commonly installed around insulating f i t t i n g s or joints in buried metal piping systems, around expansion f i t t i n g s , in swimming pool installations, etc. where the connections are not accessible. Bonding of interior metal piping systems is commonly done within walls or hollow spaces of buildings to lessen the chance of damage or disturbance. Metal ater ~iping and other pipin 9 systems are permitted or required to e oonoed to the groundlng electrode, which may be concrete-encased re-bar of a structure. This proposal will provide specific permission for such practices. PANEL ACTION: Reject. I~IT~'L--~]~b'--NT: Present rules do not require accessibility. VOTE ON PANEL ACTION: Unanimously Affirmative. SUBSTANTIATION: This proposal would establish a reliable'izeds ~F~~uniform method for determining the optimum service supply side equipment bonding/main bonding jumper. The main bonding jumper is actually a conductor/bus extending From the service grounded conductor on the supply side of the service to the equipment bonding jumper on the service supply side to the equipment bonding jumper on the service load side and the purpose of the equipment bonding/main bonding jumper is to conduct fault current, of sufficient magnitude, back to the source via the service grounded conductor/grounding electrode conductor to trip/actuate the service overcurrent device to clear the fault (see attached line diagram). Also, the size of the equipment bonding jumper on the service load side is based on Table 250-95; the size of the equipment bonding/main bonding jumper on the service supply side is based on Table 250-94. However, since the function of the service supply side and the service load side sections of the equipment bonding/main bonding jumper is the same; the total fault current sensed by the equipment bonding jumper on the service load side is also sensed by the equipment bonding/main bonding jumper on the service supply side. Therefore, since i t is common knowledge that an equipment bonding jumper, sized in accordance with Table 250-95, on the service load side does not, in any way, impair/endanger the system; accordingly, the sizing of the service supply side equipment bonding/main bonding jumper w i l l , likewise, cause no impairment/endangerment of the functions of the system. Also, material usage will be reduced i f bonding jumper size is reduced, based on Table 250-95 (see attached supporting data sheet). Item Definition-per Article 100, NEC 1981 ~ Log # 319 5- 98 - (250-79(c)): Reject SUBMII-FER: Chester Flanagan, San Diego, CA ~ATION: Size-Equipment Bonding Jumper on Supply Side of Service and Main Bonding Jumper. The "equipment" bonding/"main bonding" jumper shall be "sized as indicated in Table 250-95 based on the use of the allowable ampacity of the largest service-entrance phase conductor or equivalent area for parallel conductors as the reference. I f the allowable ampacity of the largest service-entrance phase conductor exceeds Table 250-95, the equipment bonding/main bonding jumper size shall be proportionately increased." Where the service-entrance conductors are paralleled in two or more raceways, the size of the bonding jumper for each raceway shal be "as indicated in Table 250-75, based on the use of the service-entrance phase conductor(s) allowable" ampacity in each raceway "as the reference." Service-entrance Overcurrent device conductor size per rating or setting Table 250-94/allowed per Table 250-95 service-entrance conductor size A system or circuit that is intentionally grounded. The connection between the grounded circuit conductor and the equipment grounding conductor at the service. The connection between two or more Equipment Bonding Jumper portions of the equipment grounding conductors. Equipment Grounding Conductors The conductor used to connect the noncurrent carrying metal parts equipment, raceways and other enclosures to the system grounded conductor and/or the grounding electrode conductor at the service equipment or at the source of a separately derived system. Grounding Electrode Conductor The conductor used to connect the grounding electrode to the equipment grounding conductor and/or to the ground conductor of the circuit at the service equipment or at the source of a separately derived system. Ground Conductor Main Bonding Jumper Service supply side Proposedservice equipment bonding supply side and/or main bonding equipment jumper size per Table bonding and/or 250-94/service supply main bonding side equipment bonding jumper size per and/or main bonding Table 250-95 jumper per A r t i c l e 250-79(c) 2CU IOOA 8CU 8CU i or 1/0 150 6 6 2/0 or 3/0 200 4 6 3/0-350 MCM 300 2 4 350-600 400 i/0 3 600-1100 500 2/0 2 over 1100 600 3/0 i "1250 800 **3/0 i 1500 i000 4/0 2/0 1750 1200 250 MCM 3/0 2500 1600 350 4/0 3000 2000 400 250 MCM 3500 2500 500 350 4000 3000 500 400 6000 4000 750 500 7000 5000 900 700 8000 6000 i000 800 *Size 1400 MCM and above are allowed (based on Table 310-16) for the corresponding overcurrent device amperage rating/setting as listed in Table 250-95. **Size 3/0 and above are based on Section 250-79(c). Aluminum wire data was gathered but is not submitted since the results were proportionately equal to that of the copper wire. 91 SUBSTANTIATION: The Code presently appears to have no specific reqJ~for physical protection of bonding jumpers which are not installed within enclosures or raceways. Since in some installations they may serve essentially the same purpose as equipment grounding conductors, similar protection requirements should be specified as those required for equipment grounding conductors or grounding electrode conductors. The installation of an unprotected No. 12 or No. 14 conductor to bond piping systems per Section 250-30(b) does not provide much assurance that such a connection will not be rather easily broken. Similarly, an exposed No. 10 conductor used as a bonding jumper around a 6 foot length of flexible metal conduit or a No. 8 conductor providing bonding around water meters, etc., may not provide sufficient physical strength for all environments. The latter part of the roposed exception would provide for such installations where the ikeliheod of damage is slight. PANEL ACTION: Reject. PANEL COMMENT: Submitter f a i l s to substantiate need for such ~~irements. VOTE ON PANEL ACTION: UnanimouslyAffirmative. PANEL ACTION: Reject. PANEL COMMENT: The Panel does not agree with the proposer's su-'6B-s-Z-an-t~Fat~n in that faults on the supply may be of different magnitude than faults on the load side. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 54 5- 99 - (250-79(c)): Accept in Principle SUBMITTER: Dan Leaf, Westlake Village, CA RECOMMENDATION: Add the words "or cables" after the word "raceway(s)" in the last sentence. SUBSTANTIATION: Does not refer specifically to paralleled conductors installed in other than raceways. Section 250-71(a)(1) requires metallic armor or sheath of service cables to be bonded; Section 330-3 permits MI cable for services, Section 334-3 permits MC cable for services, and i t seems reasonable that this bonding jumper requirement should apply to such metallic enclosures. PANEL ACTION: Accept in Principle. Revise last sentence to read as follows: "Where the service-entrance conductors are paralleled in two or more raceways or cables, the size of the bonding jumper for each raceway or cable shall be based on the size of the service conductors in each raceway or cable." PANEL COMMENT: Panel agrees cables should be included. VOTE ON PANELACTION: Unanimously Affirmative. ~ Log # 308 5- 103 - (250-79(d), Exception-(New)): Accept SUBMITTER: Dan Leaf, Westlake Village, CA RECOMMENDATION: Add the following: "IE'xEep-t~66~"Theequipment bonding jumper shall not be required to be larger than the circuit conductors supplying the equipment. SUBSTANTIATION: In some cases, especially motor circuits, the rating of the circuit overcurrent device would result in a bonding jumper conductor size larger than the circuit conductors. This proposal will provide the same exception permitted for equipment grounding conductors in Section. 250-95. PANEL ACTION: Accept. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . Log # 320 5- 100 - (250-79(d)): Reject SUBM[TTER: Chester Flanagan, San Diego, CA ~DATION: Size-Equipment Bonding Jumper on Load Side of Service. The equipment bonding jumper on the load side of the service overcurrent device shall not be smaller than the sizes listed by Table 250-95 for equipment grounding conductors. "The bonding jumper size shall be as listed in the table based on the use of the overcurrent device rating/setting or the combined rating/setting of the overcurrent device and the overcurrent device(s) downstream as the bonding jumper sizing reference when the overcurrent device(s) is served by a common bonding jumper." SUBSTANTIATION: The purpose of this proposal is to emphasize the pur~/T~ of Section 250-79(d). As an example, when a common equipment bonding jumper is extended to serve additional equipment (load) the magnitude of the potential fault current increases. As current is increased, a larger bonding will/may be required depending on the current level involved. In essence this is what the subject section is about and the aim here is to make this clear. PANEL ACTION: Reject. ~M~IE-NT: The proposal does not c l a r i f y intent. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 531 5- 104 - (250-7g(e)): Reject SUBMITTER: J. K. Daugherty, F l i n t , MI RECOMMENDATION: Revise last sentence to delete the "and" and ~cewfth'a co~na in the 4th line, delete the period in the 5th line and add: "and shall minimize convolutions." SUBSTANTIATION: Manyconvolutions will cause a choke effect. F~NEL ACTION: .Reject. PANEL COF~V~NT: Insufficient substantiation that there is a p'r'66femln---F6-~e f i e l d . VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . Log # 288 5- 105 - (250-79(e)): Reject SUBMITTER: Dan Leaf, Westlake Village, CA RECOMMENDATION: Add the following as sub-paragraph (2); make present paragrapfi (1): The equipment bonding jumper may be bare, covered, or insulated. Individually covered or insulated bonding jumpers shall have a continuous outer finish that is either green, or green with one or more yellow stripes, or shall be identified as permitted in Exceptions No. 1 and No. 3 of Section 250-57(b). SUBSTANTIATION: Section 310-2 requires that conductors be ~te~exce'pt where otherwise specifically permitted. A bonding jumper is, or may become a conductor. Article 680 for example, permits bare, covered, or insulated bonding jumpers. Article 517 requires certain bonding jumpers to be insulated. Article 250 appears to be silent on this point. There is a fine line of distinction between equipment grounding conductors and equipment bonding jumpers, which in some instances is d i f f i c u l t to discern, as the function of each may overlap. For example: two sections of rigid metal conduit joined by a short section of multiconductor cord or flexible metal conduit, to permit movement (seismic j o i n t , floating dock, etc.) The conductor which is used to provide the connection between the two rigid raceways could meet the definition of bonding jumper or bonding jumper, equipment, in Article 100, or this definition could be inferred by Section 250-79(e). By definition and per Sections 250-57(b) and 250-91(b) i t may also be construed as an equipment grounding conductor. An equipment bonding jumper installed as required by Section 250-74 ( i f not permitted to be bare or not required to be green in color) could easily lead to mistakes in connections by a do-it-yourself homeowner or others, with potential hazards. Since splices and terminations may be interposed in some bonding jumper installations, and lengths are not specifically limited, the lack of code requirements for identification can lead to safety hazards. To avoid controversy over definitions and for the same safety reasons the identification requirements for equipment grounding conductors and equipment bonding jumpers should be the same. PANEL ACTION: Reject. PANEL COMMENT: No substantiation that there is a f i e l d problem. The function of the bonding jumper is readily apparent and color identification is not necessary. VOTE____ON_PANEL.~G~Q~L Unanimously Affirmative. Log # 530 5- 101 - (250-79(d)): Accept in Principle SUBMITTER: J . K . Daugherty, Flint, MI ~E~ATION: Add new sentence: "The equipment bonding jumper shall be permitted to run continuously in series from 2 or more conduits." SUBSTANTIATION: To end a controversy on whether this is acceptable.--On the basis that requirements are written based on one fault at a time and does not conceive.a double f a u l t , this construction should be accepted. PANEL ACTION: Accept in Principle. ~ ~ a s t sentence as follows: "A single common continuous equipment bonding jumper shall be permitted to bond two or more raceways or cables where the bonding jumper is sized in accordance with Table 250-95 for the largest overcurrent device supplying circuits therein. PANEL COMMENT: More clearly describes the intent. VUIL ON PANELACTION: UnanimouslyAffirmative. Log # 309 5- 102 - (250-79(d)(2)-(New)): Reject SUBMITTER: Dan Leaf, Westlake Village, CA RECOMMENDATION: Add the following as subparagraph (2) and make ~aph subparagraph (1): A bonding jumper No. 6 or larger may be installed without an enclosure i f installed where free from probable physical damage, otherwise i t shall be in rigid conduit, intermediate metal conduit, electrical metallic tubing, or cable armor. A bonding jumper shall be installed in accordance with Section 250-92 in regard to restrictions for aluminum. Exception. Enclosures, racewa s, or armor shall not be required where a bonding jumper is installed: a. in the hollow spaces of a wall or partition, or b. imbedded in concrete or masonry, or c. under a minimum 2-inch thick concrete pad, or d. underground with a minimum 12-inch cover, or e. otherwise installed so as not to be subject to physical damage. 92 Log # 783 5- 108 - (250-80): Reject SUBMITTER: Thomas E, Trainer, City of San Diego, CA ~DATION: Section 250-80 Bonding of Piping Systems ---~--l~ret-~T -~ater Piping The i n t e r i o r water piping system on a premises shall always be bonded to the grounding electrode system, (2) The underground water piping system on a premises shall always be bonded to the grounding electrode system. (31 Where the underground water piping system is e l e c t r i c a l l y contlnuous to the i n t e r i o r water piping system, a bonding jumper from either to the grounding electrode system is acceptable. (4) Bonding jumpers shall be sized in accordance with Table 250-94 and connected in the manner specified in Section 250-113. (b) Other Metal Piping. I n t e r i o r metal piping which may become energized shall be bonded to the service equipment enclosure, the grounded conductor at the service, the grounding electrode conductor where of s u f f i c i e n t size, or to the one or more grounding electrodes used. The bonding jumper shall be sized in accordance with Table 250-95 using the rating of the c i r c u i t which may energize the piping. The equipment grounding conductor for the c i r c u i t which may energize the piping shall be permitted to serve as the bonding means. Bonding all piping and metal a i r ducts within the premises w i l l provide additional safety. SUBSTANTIATION: The changes in Section 250-81, beginning in 1978, have indicated that metal underground water piping systems can no longer be relied on to provide a permanent and e f f e c t i v e ground because of the expanding use of p l a s t i c water pipe f o r new and repair work. The requirement to supplement a metal underground water pipe with another electrode regardless of i t s length underground c e r t a i n l y implies that metal underground water pipes are not acceptable as grounding electrodes. This proposal deletes metal underground water pipes from Section 250-81 and places such piping in Section 250-80~ Bonding of Piping Systems. Under this section, metal underground water p i p e would always be bonded to the grounding electrode system andwould no longer be confused as a grounding electrode. Based on the e f f e c t of the changes in Section 250-81, this proposal is intended to recognize the actual status of metal underground water pipe and to place i t l o g i c a l l y in a code section to provide for adequate and e f f e c t i v e bonding of such piping. PANEL ACTION: Reject. PANEL COMMENT: Same as Proposal 5-107. 5- 106 - (250-80): Reject Log # 06 SUBMITTER: Jack E. Reinhard, Southern Union Gas Company RECOMMENDATION: Change Section 250-80 "Bonding of Piping Systems" to read: 250-80 Bonding of Piping Systems. All i n t e r i o r metal water and gas piping that may become energized shall be bonded together and made e l e c t r i c a l l y continuous. An equipment bonding jumper sized in accordance with Table 250-95 shall be connected between the bonded piping system(s) and the grounding electrode conductor at the service disconnectlng means. *UNDERNO CIRCUMSTANCES IS THERE TO BE A BONDINGTO GAS LINES UPSTREAMOF THE METER CONNECTION. Bonding to sewer piping and metal a i r ducts within the premises w i l l provide additional safety. *Capitalized to denote changed wording. SUBSTANTIATION: Southern Union Gas Company has recently encountereo s~veral e~ectrical bonds tied upstream of our meter sets. This bond causes our steel lines to be tied to copper water lines with a copper conductor. The bonding causes cathodic rotection problems for our gas lines which~ in time, could create eakage hazards. Individual cities can alter their local codes to prohibit bonds to gas lines, as has Austin, Texas. In small towns, however, there are often no codes other than the adoption of the various national codes. Southern Union Gas serves numerous small towns in Texas, Oklahoma, and Arizona. We therefore feel that in'the interest of safety and convenience of implementation, the proposed change should be made to the 1981 NATIONAL ELECTRICAL CODE. The change should provide safe service to the population without the hazard or expense of gas line deterioration caused by bonding of conductors upstream of meter connects. Please consider this matter as soon as possible. PANEL ACTION: Reject. PANEL COMMENT: There are no mandatory requirements for bonding to "i-fi1~-F~'or gas pipes upstream from the meter unless such piping is subject to becoming energized. In such cases bonding is necessary for safety. • VOTE ON PANEL ACTION: Unanimously Affirmative. ~ Log # 440 5- 107 - (250-80): Reject SUBMITTER: Southwestern Section IAEI ~NDATION: Section 250-80 Bonding of Piping Systems: (a) Metal Water. Piping. ( i ) The i n t e r i o r water piping system on a premises shall always be bonded to the grounding electrode system. (2) The underground water piping system on a premises shall always be bonded to the grounding electrode system. (3) Where the underground water piping system is e l e c t r i c a l l y continuous to the i n t e r i o r water piping system, a bonding jumper from either to the grounding electrode system is acceptable. (4) Bonding jumpers shall be sized in-accordance with Table 250-94 and connected in the manner specified in Section 250-113. (b) Other Metal Piping.• I n t e r i o r metal piping which may become energized shall be bonded to the service equipment enclosure, the grounded conductor at the service, the grounding electrode conductor where of s u f f i c i e n t size, or to the one or more grounding electrodes used. The bonding jumper shall be sized in accordance with Table 250-94, using the rating of the c i r c u i t which may energize the piping. The equipment grounding conductor for the c i r c u i t which may energize the piping shall be permitted to serve as the bonding means. Bonding all piping and metal a i r ducts within the premises w i l l rovide additional safety. UBSTANTIATION: The changes in.Section 250-81, beginning in 1978, have indicated that metal underground water piping systems can no longer be relied on to provide a permanent and e f f e c t i v e ground because of the expanding use of p l a s t i c water pipe for new and repair work. The requirement to supplement a metal underground water pipe with another electrode regardless of i t s length underground c e r t a i n l y implies that metal underground water pipes are not acceptable as grounding electrodes. This proposal deletes metal underground water pipes from Section 250-81 and places such piping in Section 250-80, Bonding of Piping Systems. Under this section, metal underground water pipe would always be bonded to the grounding electrode system and would no longer be confused as a grounding electrode. Based on the e f f e c t of the changes in Section 250-81, this proposal is intended to recognize the actual status of metal underground water pipe and to place i t l o g i c a l l y in a Code section to provide f o r adequate and e f f e c t i v e bonding of such piping. PANEL ACTION: Reject. ~ : Proposal is not meaningful considering Panel recommendation on Proposals 5-123 and 5-124. VOTE ON PANELACTION: AFFIRMATIVE: 14 NEGATIVE: Nagel. EXPLANATION OF VOTE: NAGkL: Same 6s--P-~oposal 5-124. NEGATIVE: Nagel. EXPLANATION O~ VOTE: --fl/~GE1-'f~n~oposal 5-124. Log # 1246 5- 109 - (250-80): Reject SUBMITTER: IAEI ~ATION: Section 250-80 to read as follows: Section 250-80 Bonding of Piping Systems: (a) Metal Water Piping (i) The interior water piping system on a premises shall always be bonded to the grounding electrode system. (2) The underground water piping system on a premises shall always be bonded to the grounding electrode system. (3) Where the underground water piping system is electrically continuous to the interior water piping system, a bonding jumper from either to the grounding electrode system is acceptable. (4) Bonding jumpers shall be sized in accordance with Table 250-94 and connected in the manner specified in Section 250-113. (b) Other Metal Piping. Interior metal piping which may become energized shall be bonded to the service equipment enclosure, the grounded conductor at the service, the grounding electrode conductor where of sufficient size, or to the one or more grounding electrodes used. The bonding jumper shall be sized in accordance with Table 250-94, using the rating of the circuit which may energize the piping. The equipment grounding conductor for the circuit which may energize the piping shall be permitted to serge as the bonding means. Bonding all piping and metal a i r ducts within the premises w i l l provide additional safety. SUBSTANTIATION: The changes in Section 250-81, beginning in 1978, have indicated that metal underground water piping systems can no longer be relied on to provide a permanent and e f f e c t i v e ground because of the expanding use of p l a s t i c water pipe for new and repair work. The requirement to supplement a metal underground water pipe with another electrode regardless of its length underground c e r t a i n l y implies that metal underground water pipes are not acceptable as grounding electrodes. This proposal deletes metal underground water pipes from Section 250-81 and places such piping in Section 250-80, Bonding of Piping Systems. Under this section, metal underground water pipe would always be bonded to the grounding electrode system and would no longer be confused as a grounding electrode. Based on the effect of the changes in Section 250-81, this proposal is intended to recognize the actual status of metal underground water pipe and to place i t logically in a Code section to provide f o r adequate and effective bonding of such piping. ~ g3 PANEL ACTION: Reject. PANEL COMMENT: Sameas Proposal 5-107. VOTE ON PANELACTION: AFFIRMATIVE: i-4 NEGATIVE: Nagel. EXPLANATION OF VOTE: NAGEL: Same as Proposal 5-124. Log # 2019 5- 114 - (250-80(a), 250-80(a), FPN-(New)): Reject SUBMITTER: Idaho Chapter IAEI R--~-~-O--~EN~TION: Add a new sentence to Section 250-80(a) at the ~-6f-te~h-~-~tion: "Bonding jumper terminations shall be accessible." FPN: See definition of Accessible, Article 100. SUBSTANTIATION: Terminations for grounding electrode conductors as required by Section 250-81(a) are required by Section 250-112 to be accessible (not permanently closed in by the structure or finish or the building). Bonding jumper terminations such as used on bonding hot and cold metal water piping systems in a building, are being made and then are being closed in when the building is finished and then are not accessible. In many instances this involves the grounding electrode conductor which is used as the jumper. These terminations also have a need to be accessible to isolate the metal piping system especially in cold weather areas where welders are used for thawing frozen water pipes. Whether or not this is considered a 9ood practice, i t is a commonly used procedure and has caused fires even in other remotely located buildings because the return path or anticipated circuit (the section of frozen section of pipe intended to be thawed) may be interrupted by some unknown means causing the current to flow elsewhere. And i f this path of least resistance happens to be across a conductor too small to carry the applied current creates an eminent fire hazard. PANEL ACTION: Reject. PANEL COMMENT: Accessibility for disconnection will not solve the problem given in the substantiation because of the inevitable m u l t i p l i c i t y of parallel paths such as an equipment grounding conductor at a water heater. See Proposal 5-112. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 103 5- 110 - (250-80, Exception (New)): Reject SUBMITTER: Dan Leaf, Westlake Village, CA ITE-COI~[E'~ATION: Add Exception as follows: Exception: Isolated metal water piping installed in buildings that do not contain service equipment shall be permitted to be bonded to an effectively grounded metal enclosure of the building disconnecting means for the largest ampacity rated supply conductors. The bonding jumper shall be sized in accordance with Table 250-95 using the largest overcurrent device of any supply circuit to the building. The bonding jumper shall not be required to be larger than the largest supply circuit conductor. SUBSTANTIATION: Does not provide for (alternative) bonding in ~eparate buTF~ings without service equipment ~here metallic water piping may be isolated. The present wording of this section appears to prohibit the bonding of an isolated metal water piping system to the building disconnect means required by Section 230-34(a) when i t is grounded by a metallic raceway (equipment grounding conductor) enclosing the supply conductors, as permitted by the Exception to Section 250-24. For example: a remote (separate) building with a disconnecting means rated 30 amperes supplied by an underground 1/2 inch rigid metal conduit originating from service equipment with service entrance conductors of 500 MCMcopper. I f this remote building contains an isolated metal water piping system a l i t e r a l interpretation requires a 1/0 copper or a 3/0 aluminum bonding jumper to be installed to the area of the service equipment. This seems an unreasonable requirement in view of the acceptability of the conduit as a grounding means for the electrical equipment. PANEL ACTION: Reject. PANEL COMMENT: The submitter has not shown a widespread need for t-F~eException. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 496 5- 115 - (250-80(a), Exception No. 1-(New)): Reject SUBMITTER: Ernest E. Cannon, Tempe, AZ RECOMME_NDATION: Add Exception No. 1. When tests for grounding resistance of the interior metal water piping system show that the system is isolated from earth, the bonding jumper size shall be determined by Table 250-95 using the rating of the circuit or feeder which could energize the system. SUBSTANTIATION: Information from installations indicate that in many installations the interior metal water piping system is isolated from earth ground. Under such conditions there is minor difference between the interior metal water piping system and other interior piping systems. PANEL ACTION: Reject. I~N-E~T.C ' OMM ' EN ' ~F: There is no certainty that the isolation will be Log # 532 5- 111 - (250-80(a)): Accept SUBMITTER: J. K. Daugherty, Flint, MI ~ATION: Delete "always" in the 2nd line. SUBSTANTIATION: Unnecessary understood term. ACTION: Accept. V-Olq~'--~t~-F~l~L ACTION: Unanimously Affirmative. VOT_E ON PANELACTION: UnanimouslyAffirmative. Log # 495 5- 116 - (250-80(a), Exception No. 2-(New)): Reject SUBMITTER: Ernest E. Cannon, Tempe, AZ RECOMMENDATION: Add Exception No. 2. In a dwelling unit where the panelboard or load center is remote from the service entrance equipment and the interior metal water piping system is not isolated From earth, the interior metal water piping system shall be permitted to be bonded to the grounding terminal bar of the panel (See Section 384-27). The size of the bonding jumper for the interior metal water piping system and for the panelboard shall be determined according to Table 250-94 using the size of the panelboard feeder conductor. SUBSTANTIATION: This Exception is intended to address the condition presented in multi-family locations such as apartments or condominiums wherein there are often 4 or 6 units in one building, each with separate systems for water, electric, gas and air-conditioning. Under these conditions there is usually no existing metallic connection between the individual interior metal water plping systems, The electrical supply is usually a grouped set of meters and main service switches. A common configuration consists of 6 meters and mains in the 150-ampere size, all supplied by service-entrance conductors and equipment main rating of 600 amperes (because of the load calcs.) Application of the Exception would permit each separate interior metal water piping system to be bonded to the panelboard and the panelboard to the service with No. 4 copper for 2/0 feeder to the panel. For the installation, there would be 6 such bonds. For nonisolated systems, these would provide the equivalent of 240,000 CM nearly double that provided by the No. 2/0 for 600 amperes. In addition, the method is practical from an installation standpoint and i t provides the safety which the NEC intends. PANEL ACTION: Reject. PAIqEL ' --C~O-R[RE~ ' IT: See Panel recoJmnendation on Proposal 5-117. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 962 5- 112 - (250-80(a)): Reject SUBMITTER: Hal Knight, The City of Santa Clara, CA RECOMMENDATION: Add a new final sentence: The metal water piping "bonding jumper" shall be accessible. SUBSTANTIATION: In the f i e ] d , electrlcal inspectors find i t d i f f i c u l t to actually be able to determine whether the underground metallic water pipe system meets all the requirements of Section 250-81(a). Consequently the bonding jumper required by Section 250-80 could be, and is in many cases, a grounding electrode conductor and i t ' s connection point would have to be accessible. Because of the d i f f i c u l t y of knowing whether you are dealing specifically with a "bonding jumper" or a "grounding electrode conductor," i t would make the field inspector's job considerably easier i f this particular bonding jumper (Section 250-80(a)) was required to be accessible under any circumstances. For that matter, why not make all "bonding jumpers" accessible where practicable? PANEL ACTION: Reject. I~NE'[--~F~NT: There is no evidence that there is a problem in the f i e l d . VOTE ON PANELACTION: UnanimouslyAffirmative. Log # 1514 5- 113 - (250-80(a)): Reject SUBMITTER: R. B. Adams, Freeport, TX ITE'-C'O]@~E'I~ATION: The interior metal water piping system "which may become energized" shall be bonded --- (and add at the end of the sentence) "where personnel safety is a problem." SUBSTANTIATION: The requirement to bond all interior water pipe excesslve. In many industrial plants the grounding of water pipes only introduces new and possibly greater problems. Many papers have been written on methods to protect water piping grounding through mandatory requirements in the NEC. I believe that the bonding only in cases where personnel safety is at stake would eliminate many of these problems. PANEL ACTION: Reject. PANEL COMMENT: Personnel safety will always be a problem i f not Bonded. VOTE ON PANELACTION: UnanimouslyAffirmative. 94 section of frozen section of pipe intended to be thawed) may be interrupted by some unknown mean causing the current to flow elsewhere. And i f this path of least resistance happens to be across a conductor too small to carry the applied current creates an eminent f i r e hazard. PANEL ACTION: Reject. PANEL COMMENT: See Panel recommendation on Proposal 5-114. VdfE'-~-N-I~-A3f~[ ACTION: Unanimously Affirmative. , Log # 407 5- 117 - (250-80(a), Exception-(New)): Accept SUBMITTER: R. W. Worthing, Bakersfield, CA RECOMMENDATION: Add Exception -'-I-h--b-'u-~-F~aT6~C of multiple occupancy, where the interior metal water piping system for the individual occupancies is metallically isolated from all other occupancies by use of nonmetallic water piping, the interior metal water piping system for each occupancy shall be permitted to be bonded to the panelboard or switchboard enclosure supplying that occupancy. The bonding jumper shall be sized inaccordance with Table 250-95. SUBSTANTIATION: With the increased use of nonmetallic water iping systems, underground, i t has become necessary for many urisdictions to either amend Section 250-80 by ordinance or provide administrative procedures which will address the problem. As written, Section 250-80 would require a bonding jumper, sized in accordance with Table 250-94 interconnect all isolated metal water piping systems to the service equipment enclosure. Section 250-51 requires "the path to ground...have sufficiently low impedance to ~imit the voltage to ground and to f a c i l i t a t e the operation of the circuit protective devices in the c i r c u i t . " Section 250-80 does not require the bonding jumper be "run with or enclose the circuit conductors" as does Section 250-91(b) relating to equipment grounding conductors. Therefore, i t is conceivable that a bonding jumper, sized in accordance with Table 250-94, may be larger than that required by Table 250-95 for a specific c i r c u i t , but through its routing and intermediate connections may well provide a higher impedance path. At the Southwest Section meeting of the IAEI in Albuquerque in 1981, a sampling of jurisdictions indicated that the following have amended Section 250-80 for the reasons stated: Stockton, California- 16 separate jurisdictions in San Diego County, California including the City of San Diego - State of New Mexico • Oakland, California - Clovis, California - Fresno, California Huntington Beach, California - Long Beach, California - Phoenix, Arizona - Sacramento, California - County of Sacramento, California - Carson City, Nevada. PANEL ACTION: Accept. VOTE ON PANELACTION: Unanimously Affirmative. Log # 1724 5- 121 - (250-80(x)-(New)): Reject SUBMI1-FER: Charles "Mike*' Holt, Concepts in Electricity Inc. RECOMMENDATION: Add a new Section 250-80(x)-(New) between Section ~J'IJ--~-a'T~n~-Section 250-80(b). 250-80(x): Isolated Metal Piping. Isolated metal piping that may become energized shall be grounded to the nearest equipment grounding conductor of sufficient size, that would be required to open the largest overcurrent device by the use of Table 250-95. SUBSTANTIATION: This section would deal with isolated water plplng systems. Sizing of these conductors shall be based upon overcurrent devices that would be required to be interrupted. The Code requires that all water piping systems be bonded to the service grounding conductor. I t doesn't take into consideration the fact of the great usage of plastic plumbing pipe. Therefore smaller and larger systems do not have all the plumbing piping systems connected with a common metal pipe. The Code does not identify how to bond these isolated systems. PANEL ACTION: Reject. PANEL COMMENT: See Proposal 5-117. ~TOF ' E-'-O-~-P-~N~C ACTION: UnanimouslyAffirmative. ~ Log # 442 5- 122 - (250-81): Reject SUBMITTER: Southwestern Section IAEI RECOMMENDATION: Revise f i r s t paragraph of Section 250-81. ~G-~df6~'ET6Ctrode System. I f available on the premises at each building or structure s~rved, each item (a) through (d) below shall be bonded together to form the grounding electrode system. The bonding jumper shall be sized in accordance with Section 250-95 and shall be connected in the manner specified in Section 250-115. The unspliced grounding electrode conductor shall be permitted to run to any convenient grounding electrode available in the grounding electrode system. I t shall be sized for the largest grounding electrode conductor required among all the available electrodes. (See Section 250-23(a), Exception No. 5.) SUBSTANTIATION: Due to almost universal use of plastic water systems a "zero" ohmage would be 1 ohm which is easily carried by conductor sized per Section 250-95. PANEL ACTION: Reject. COMMENT: Table 250-95 cannot be applied to a service with more-tHan on~ main overcurrent device. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 90 5- 118 - (250-80(b)): Reject SUBMI1-FER: Joseph F. Pinachio, Revere, MA ITE-C'OI~ME'N~ATION: In the f i r s t and second lines, delete the words "which may become energized." SUBSTANTIATION:. To assure that all interior metal piping is to be bonded for added safety. PANEL ACTION: Reject. PANEL COMWENT: Proposal would require excessive and needless b-6-~-dTh~-~G-p-fping which will not become energized. Some judgement is needed. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 936 5- 119 - (250-80(b)): Reject SUBMITTER: C. D. Hansell, GTE Service Corporation RECOMMENDATION: At the end of Section 250-80(b), add: The ~ n - ~ - - ~ F ~ n d i n g conductor for the circuit which may energize the piping shall be permitted to serve as the bonding means. Delete this same sentence which follows Section 250-80(b) and which applies to all of Section 250-80. Retain the Fine Print Note that follows and that applies to all of Section 250-80. SUBSTANTIATION: The sentence should apply only to (b), and not to (a). The bonding required by Section 250-80(a) is to the grounding electrode system, not to load equipment. PANEL ACTION: Reject. PANEL COMMENT: The sentence is already in paragraph (b) only. VOTE ON PANELACTION: Unanimously Affirmative. Log # 784 5- 123 - (250-81): Reject SUBMITTER: Thomas E. Trainor, City of San Diego RECOMMENDATION: Section 250-81 Grounding Electrode Systen --(a~--PrimaryGrounding Electrodes. The electrodes (i) through (3) below are defined to be primary grounding electrodes for the purposes of this section. (1) An electrode encased by at least 2 inches of concrete, located within and near the bottom of a concrete foundation or footing that is in direct contact with the earth, consisting of at least 20 feet of one or more steel reinforcing bars or rods of not less than I / 2 inch diameter, or consisting of at least 20 feet of bare solid copper conductor not smaller than No. 4 AWG. ~I The metal frame of the building, where effectively grounded. A ground ring encircling the building or structure, in direct contact with the earth at a depth below earth surface not less than 2-1/2 feet, consisting of at least 20 feet of bare copper conductor not amaller than No. 2 AWG. (b) SecondaryGrounding Electrodes. The grounding electrodes specified in Section 250-83 are defined to be secondary grounding electrodes for the purposes of this section. Log # 2033 5- 120 - (2~-80(b),250-80(b).FPN-(New)): Reject SUBMII-TER: Idaho Chapter IAEI ITE'CR]I~I~EIT[IATION: Add a new sentence to Section 250-80(b) at the end of the section: "Bonding jumper terminations shall be accessible." FPN: See definition of Accessible, Article 100. SUBSTANTIATION: Terminations for grounding electrode conductors as required by Section 250-81(a) are required by Section 250-112 to be accessible (not permanently closed in by the structure or finish or the building). Bonding jumper terminations such as used in bonding hot and cold metal water piping systems in a building, are being made and then are being closed in when the building is finished and then are not accessible. In many instances this involves the grounding electrode conductor which is used as the jumper. These terminations also have a need to be accessible to isolate the metal piping system especially in cold weather areas where welders are used for thawing frozen water pipes. Whether or not this is considered a good practice, i t is a commonly used procedure and has caused fires even in other remotely located buildings because the return path or anticipated circuit (the Required Grounding Electrodes A primary grounding electrode shall be provided for each building constructed under the provisions of this Code. (2) Either a primary or a secondary grounding electrode shall be provided for all other installations served under the provisions of this Code. (d) Grounding Electrode System. All grounding electrodes available on a building or structure shall be bonded together to Form a grounding electrode system. Bonding jumpers shall be sized in accordance with Section 250-79(c) and connected in the manner specified in Section 250-115. (e) Additional Requirements. Whenever i t is deemed necessary by the authority having jurisdiction, additional electrodes may be required to assure a permanent and effective grounding electrode systBn. 95 SUBSTANTIATION: The permissive wording of Section 250-81 (where av-ai-Ta-bTe on the premises) tends to allow inadequate grounding in certain installations. The most typical example is a wood frame, single-family dweIHng constructed on a slab or foundation with no rebar and supplied by a plastic underground water system. Since none of the "primary" electrodes are available on the premises, the Code specifically permits a typical 1/2 inch copper ground rod to serve as the grounding electrode for the service to this dwelling. The effectiveness of a copper ground rod as a grounding electrode is seriously in question for the following reasons: 1. Ground rods generally have a higher resistance to ground than other electrodes and there are no effective provisions to require a low resistance to ground. (Section 250-84.) 2. Ground rods are often shortened or otherwise improperly installed and such abuses are d i f f i c u l t or impossible to detect. 3. Ground rods are generally installed in locations that subject the rod, ground clamp and grounding electrode conductor to physical damage. In general, ground rods do not seem to satisfy the requirements of Section 250-51. In the not unusual case where the neutral bond is removed or the neutral conductor broken, a ground rod does not have sufficiently low impedance to limit the voltage to ground and to f a c i l i t a t e the operation of the circuit protective devices. (Section 250-51(c)). This proposal requires that a permanent and effective grounding electrode be provided for each building constructed under the provisions of this Code. I t is f e l t that such mandatory wording would better serve the purpose of this Code to provide practical safeguarding of persons and property from hazards arising from the use of e l e c t r i c i t y . (Section 90-1(a).) PANEL ACTION: Reject. ~M~Z~'NT: No evidence that present requirements do not produce an adequate grounding electrode. VOTE ON PANELACTION: ~ In general, ground rods do not seem to satisfy the requirements of Section 250-51. In the not unusual case where the neutral bond is removed or the neutral conductor broken, a ground rod does not have sufficiently low impedance to limit the voltage to ground and to f a c i l i t a t e the operation of the circuit protective devices. Section 250-51(c). This proposal requires that a permanent and effective grounding electrode be provided for each building constructed under the provisions of this Code. I t is f e l t that such mandatory wording would better serve the purpose of this Code to provide practical safeguardiDg of persons and property from the hazards arislng from the use of e l e c t r i c i t y . - Section 90-1(a) - The concrete-encased electrode has been used with success as the main grounding electrode on services for several years. A po11 at a meeting showed that twenty (20) cities or counties now require i t as the grounding electrode for services by local amendment to the NATIONAL ELECTRICAL CODE. This type electrode has been in use in Arizona since 1938. PANEL ACTION: Reject. FAN~C'CR~RI;E'I~T: Same as Proposal 5-123. VOTE ON PANELACTION: NEGATIVE: Nagel. EXPLANATION OF VOTE: --NAGEC~'-I--am-i6"{avor of this proposal because the new language would provide a more effective grounding systBn. Log # 1257 5- 125 - (250-81): Reject SUBMITTER: IAEI ~C'~)-#II~E']~[~TION: In the f i r s t sentence, delete the words " i f available" and s t a r t the sentence with the word where, to read: "Where on the premises, e t c . . " SUBSTANTIATION: The increased use of p l a s t i c (CPVC and p o l y 6 ~ as water services and as i n t e r i o r water systems leaves many services of r e l a t i v e l y high ampacity with a "made" or driven electrode as the only on-site grounding system. Section 250-94 (exception) recognizes that a made or driven electrode w i l l not dissipate a ground-fault beyond what can be carried by a No. 6 copper conductor. Whereas the building steel and the foundation steel " i f available" are both required to be bonded f u l l size as l i s t e d in Table 250-94, the Code Panels would appear to recognize them as an e f f e c t i v e grounding system. The foundation steel and building steel are usually not "avail able" simply because no one bothers to bond'them during the phase of construction when they are a v a i l a b l e . Most structural codes now require rebar steel in the footings or foundation in quantities that would exceed that required in Section 250-81(c) as a grounding system. I t is the intent of this change to require that these steel sections (foundation and building steel) be u t i l i z e d when on the premises. PANEL ACTION: Reject. P ~ ~ : No evidence to indicate that present requirements are not s u f f i c i e n t . VOTE ON PANEL ACTION: AFFIRMATIVE: 13 NEGATIVE: Nagel. EXPLANATION OF VOTE: - - ~ - T - - ~ 6 m ~ a Y P ¥ o p o s a l 5-124. fR--~A-?r V-[---~IK-- NEGATIVE: Nagel. EXPLANATION OF VOTE: ~-~-as-F~oposa] 5-124. Log # 1247 5- 124 - ( 2 ~ - 8 1 ) : Reject SUBMII-FER: IAEI ~DATION: (a) Primary Grounding Electrodes. The electrodes ( I ) through (3) below are defined to be primary grounding electrodes f o r the purposes of this section. ( i ) An electrode encased by at least 2 inches of concrete, located within and near the bottom of a concrete foundation or footing that is in d i r e c t contact with the earth, consisting of at least 20 feet of one or more steel r e i n f o r c i n g bars or rods of not less than 1/2 inch diameter, or consisting of at least 20 f e e t of bare copper conductor not smaller than No. 4 AWG. (2) The metal frame of the building, where e f f e c t i v e l y grounded. (3) A ground ring encircling the building or structure, in direct contact with the earth at a depth below earth surface not less than 2 i / 2 feet, consisting of at least 20 feet of bare copper cofiductor not smaller than No. 2 AWG. (b) SecondaryGrounding Electrodes. The grounding electrodes specified in Section 250-83 are defined t o be secondary grounding electrodes for the purposes of this Section. (c) Required Grounding Electrodes. (1) A primary grounding electrode shall be provided for each building constructed under the provisions of this Code. (2) Either a primary or a secondary grounding electrode shall be provided for all other installations served under the provisions of this Code. (d) Grounding Electrode System. All grounding electrodes available on a building or structure shall be bonded together to form a grounding electrode system. Bonding jumpers shall be sized in accordance with Section 250-79(c) and connected in the manner specified in Section 250-115. (e) Additional Requirements. Whenever i t is deemed necessary by the authority having jurisdiction, additional electrodes may be required to assure a permanent and effective grounding electrode system. SUBSTANTIATION: The permissive wording of Section 250-81 (where available on the premises) tends to allow inadequate grounding in certain installations. The most typical example is a wood frame, single-family dwelling constructed on a slab or foundation with no rebar and supplied by a plastic underground water system. Since none of the "primary" electrodes are available on the premises, the Code specifically permits a typical 1/2 inch-copper ground rod to serve as the grounding electrode for the service to this dwelling. The effectiveness of a copper ground rod as a grounding electrode is seriously in question for the following reasons: (1) Ground rods generally have a higher resistance to ground than other electrodes and there are no effective provisions to require a low resistance to ground. - Section 250-51(c). (2) Ground rods are often shortened or otherwise improperly installed and such abuses are d i f f i c u l t or impossible to detect. (3) Ground rods are generally installed in locations that subject the rod~ ground clamp and grounding electrode conductor to physical damage. Log # 1516 5- 126 - (250-81): Reject SUBMII-[ER: R. B. Adams, Freeport, TX RECOMMENDATION: Change the First sentence to read: ~ C ~ i ' l ' ~ 1 - 6 on thepremises at each building or structure served, each item (a) through (d) below "may" be bonded together---(and the remainder of the text unchanged.) SUBSTANTIATION: In industrial plants, the grounding of water pipes poses many problems due to stray currents. The use of driven galvanized steel ground rods connected with copper cables and all copper and connections sealed from contact with the earth has proven a good method For grounding in large industrial complexes. Impedance checks to ground have indicated very good conductivity with resistances of less than one o~n measured by the voltage drop method using currents in the range of 50 amperes. In low resistance areas the grounding to water pipes has proven c o s t l y in t r y i n 9 to overcome e l e c t r o l y t i c corrosion. PANEL ACTION: Reject. PANEL CO'MME'NT: Safety considerations require bonding. V 6 ~ ' ~ ACTION: Unanimously A f f i r m a t i v e . Log # 1192 5- 127 - (250-81, 250-81(e)-(New)): Accept Secretary's Note: The Correlating Committee directs that this proposal be referred to CMP 20 for c o r r e l a t i o n . SUBMITTER: Olaf G. Ferm, Ferm's Fast Finder Index RECOMMENDATION: Change the wording of the F i r s t sentence to read: ~avai'Ta~1"e on the premises at each building or structure served, each item (a) through (e) below shall be bonded together to Form the grounding electrode system. 9B PANEL ACTION: Reject. I~N-E'I--COMM~NT: See Proposal 5-123. VOTC~ ACTION: AFFIRMATIVE: 13 NEGATIVE: Nagel. EXPLANATION OF VOTE: -NA~C{-~oposal 5-124. Then add subsection (e) to read: (e) The structural reinforcing steel of a concrete swimming pool, or the wall of a bolted or welded metal swimming pool installed below grade, and in direct contact with the earth 2 1/2 feet or more below the earth surface. SUBSTANTIATION: In most cases where there is a below grade swimming pool on the premises, the mass of reinforced concrete or the metal poQl structure in direct contact with the soil will give a resistance to ground reading far less than the items listed in Ca) through (d) and therefore should be listed as one of the items of the grounding electrode system. The bonding together of all the required items in Section 680-22 and then grounding this mass to the electrode system and the main service ground will offer the safest installation possible. (see) Enclosed material from the United States Department of Agriculture. CNote: Copyof enclosed material available from NFPA on request.) PANEL ACTION: Accept. ~ : Refer to CMP 20 for correlation. ~ON PANEL ACTION: UnanimouslyAffirmative. Log # 469 5- 129 - (250-81(a)): Accept in Principle SUBMITTER: Darrell Hazelwood, J. M. Perry Institute RECOMMENDATION: Include in the last sentence of 250-81(a) the ~ng'phrase in quotations: The supplemental electrode shall be pennitted to be bonded to the grounding electrode conductor, the grounded service-entrance conductor, the grounded service raceway, the interior metal water piping at ~ny convenient point, "and any grounded service enclosure.' SUBSTANTIATION: Section 250-81(a) intends to allow the {upp1~rounding electrode conductor to be connected to any service enclosure because of the inclusion of the wording "grounded service raceways." The paragraph, though, needs to specifically include the words "and any grounded service enclosure." Electrically, we are dealing with the smne point in the electrical system when we are on the supply side of the service disconnecting means. To connect our supplemental grounding electrode conductor to any service enclosure on the supply side of the service disconnecting means is in r e a l i t y connecting the grounding electrode conductor to the grounded service-entrance conductor. PANEL ACTION: Accept in Principle. ~G~t-i-F~e-~ast sentence of Section 250-81(a) to read as follows: "The supplemental electrode shall be permitted to be bonded to the grounding electrode conductor, the grounded service-entrance conductor, the grounded service raceway, any grounded service enclosure, or the interior metal water piping at any convenient oint." ANEL COMMENT: Editorial. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 441 5- 128 - (250-81): Reject SUBMITTER: Southwestern Section IAEI ~ATION: Ca) Primary Grounding Electrodes. The electrodes ( i i through (3) below are defined to be primary grounding electrodes for the purposes of this section. (1) An electrode encased by at least 2 inches of concrete, located within and near the bottom of a concrete foundation or footing that is in direct contact with the earth, consisting of at least 20 feet of one or more steel reinforcing bars or rods of not less than 1/2-inch diameter, or consisting of at least 20 feet of bare copper conductor not smaller than No. 4 AWG. (2) The metal flame of the building, where effectively grounded. (3) A ground ring encircling the building or structure, in direct contact with the earth at a depth below earth surface not less than 2 1/2 feet, consisting of at least 20 feet of bare copper conductor not smaller than No. 2 AWG. (b) Secondary Grounding Electrodes. The grounding electrodes specified in Section 250-83 are defined to be secondary grounding electrodes for the purposes of this section. (c) Required Grounding Electrodes. (1) A primary grounding electrode shall be provided for each building constructed under the provisions of this Code. (2) Either a primary or a secondary grounding electrode shall be provided for all other installations served under the provisions of this Code. (d) Grounding Electrode System. All grounding electrodes available on a building or structure shall be bonded together to form a grounding electrode system. Bonding jumpers shall be sized in accordance with Section 250-79(c) and connected in the manner specified in Section 250-115. (e) Additional Requirements. Whenever i t is deemed necessary by the authority ilaving jurisdiction, additional electrodes may be required to assure a permanent and effective grounding electrode system. SUBSTANTIATION: The permissive wording of Section 250-81 (where ~-o-6-6he premises) tends to allow inadequate grounding in certain installations. The most typical example is a wood-frame, single-family dwelling constructed on a slab or foundation with no rebar and supplied by a plastic underground water system. Since none of the "primary" electrodes are available on the premises, the Code specifically permits a typical, 1/2-inch copper ground rod to serve as the grounding electrode for the service to this dwelling. The effectiveness of a copper ground rod as a grounding electrode is seriously in question for the following reasons: (1) Ground rods generally have a higher resistance to ground than other electrodes and there are no effective provisions to require a low resistance to ground. - Section 250-51(c) (2) Ground rods are often shortened or otherwise improperly installed and such abuses are d i f f i c u l t or impossible to detect. (3) Ground rods are generally installed in locations that subject the rod, ground clamp and grounding electrode conductor to physical damage. In general, ground rods do not seem to satisfy the requirements of Section 250-51. In the not unusual case where the neutral bond is removed or the neutral conductor broken, a ground rod does not have sufficiently low impedance to limit the voltage to ground and to f a c i l i t a t e the operation of the circuit protective devices. Section 250-51(c) This proposal requires that a permanent and effective grounding electrode be provided for each building constructed under the provisions of this Code. I t is f e l t that such mandatory wording would better serve the purpose of thisCode to provide practical safeguarding of persons and property from the hazards arising from the use of e l e c t r i c i t y . - Section 90-1(a) - The concrete-encased electrode has been used with success as the main grounding electrode on services for several years. A poll at the meeting showed that twenty (20) cities or counties now require i t as the grounding electrode for services by local amendment to the NATIONAL ELECTRICAL CODE. This type electrode has been in use in Arizona since 1938. ~ Log # 789 5- 130 - (250-81(a)): Reject SUBMITTER: Gordon M. Johnson, City of Sioux City, IA ~E-C-O-M-#E-'N-~ATION: Add (New) paragraph: Where the supplemental electrode is a made electrode as in Section 250-83(c) or (d), that portion of the bonding jumper which is the sole connection to the supplemental grounding electrode shall not be required to be larger than No. 6 copper wire or No. 4 aluminum wire. SUBSTANTIATION: I t is necessary to c l a r i f y that exceptions number one and two of Section 250-94 also apply when sizing bonding jumpers required by Section 250-81. Without this clarification, there are many times when the bonding jumper to a supplemental ground rod is required to be larger than i f the ground rod were the only ground electrode. PANEL ACTION: Reject. F~-EL~'COMME-NT: Already covered in Section 250-94, Exception No. 1. V~fE ON.PANEL.ACTION~ Unanimously Affirmative. Log # 1258 5- 131 - (250-81(a)): Accept in Principle SUBMITTER: IAEI ~EC ' -O-RFF~E~NI~ATION: Include in the last sentence of Section 250-81(a) the following quoted phrase: . . . . the supplemental electrode shall be permitted to be bonded to the grounding electrode conductor, the grounded service-entrance conductor, the grounded service raceway, the interior metal water piping at any convenient point, "and the grounded service enclosure." SUBS___.TANTIATION: Section 250-81(a) intends to allow the supplemental grounding electrode conductor to be connected to any service enclosure because of the inclusion of the wording "grounded service raceway." The paragraph, though, needs to specifically include the words "and the grounded service enclosure." Electrically, we are dealing with the sm,e point in the electrical system when we are on the supply side of the service disconnecting means. To connect our supplemental grounding d electrode conductor to any service enclosure on the supply s i e of the service disconnecting means is in r e a l i t y connecting the grounding electrode conductor to the grounded service entrance conductor, PANEL ACTION: Accept in Principle. PANEL COMMENT: See Panel recommendation on Proposal 5-129. VOTE~T-FA]~____AC!IQN£ Unanimously Affirmative. g7 Log # 2022 5- 132 - (250-81(a)): Reject SUBMITTER: Idaho Chapter IAEI RECOMMENDATION: In the last line of Section 250-81(a) between the ~'CC~Tent" and "point" add the word "accessible:" The last part of the sentence would then read, " . . . a t any convenlent "accessible" point." SUBSTANTIATION: To emphasize the "accessible" requirement as in ~2~dZ23(a) and 250-112. As presently written i t leads one to believe that the supplementary electrode grounding connections are not required to be accessible. PANEL ACTION: Reject. IIT~-fE~C-Cx)--~ICT: See Proposals 5-112 and 5-114. VOTE ON PANELACTION: UnanimouslyAffirmative. "(c) Concrete-Encased Electrode. A steel or copper electrode with an aggregate length of not less than 20 feet (6.1 m) encased by at least 2 inches (50.8 mm) of concrete, located within and near the bott~n of one or more underground concrete foundations or footings in direct contact with the earth, consisting of: (a) one or more connected reinforcing bars or rods of not less than i / 2 inch (12.7 mm) diameter, or (b) bare copper conductor not smaller than No. 4 AWG." "FPN. An aggregate length of underground concrete-encased electrode is formed by one, or a collection of more than one electrically connected, length(s) of metal electrode(s). The steel framing of a building (Section 250-81(b)), or the metal shell of a flammable liquid storage tank, for examples, may serve as the means for electrically connecting several underground foundations or footings forming one large grounding electrode for that building or storage tank. Where only one single concrete-encased electrode is used i t is required by Section 250-81(c) to have at least 20 linear feet of underground concrete encasement in the foundation or footing." Log # 1699 5- 133 - (250-81(a)): Reject SUBMITTER: Charles "Mike" Holt, Concepts in Electricity Inc. ~I~ATION: 250-81(a). The supplemental electrode shall be permitted to be bonded to the grounding elecLrode conductor, the grounded service-entrance conductor, the grounded service raceway or the interior metal water piping at any convenient point. "Supplementary electrode conductor shall be sized according to 250-94." SUBSTANTIATION: 250-81(a) requires a supplementary electrode. The 1981 NEC added this requirement without indicating the sizing of the conductor to the electrode. In making the supplementary electrode conductor sized consistent with 250-94, this sentence should be added. PANEL ACTION: Reject. PANEL COMMENT: Already covered in the f i r s t paragraph of Section 250-81. VOTE ON PANELACTION: UnanimouslyAffirmative. Log # 443 5- 136 - (250-82-(New)): Reject SUBMITTER: Southwestern Section IAEI RE-C~DATION: Add a Section 250-82 (which was vacated) Required Grounding Electrodes. A grounding electrode in accordance with 250-81(c) shall be installed as follows: (a) For services on new buildings and structures. (b) For relocated, enlarge, or replaced services when additional footings are constructed for additions to existing buildings. Exception: An existing grounding electrode in accordance with Section 250-81(c) shall be permitted to be reused. A grounding electrode in accordance with Sections 250-83(c) or (d) shall be permitted to be used for relocated, enlarged, or replaced services when no additional footings are constructed. SUBSTANTIATION: I t is the intent of this proposal to require a concrete-encased electrode in all new or remodeled f a c i l i t i e s which provide additional footings which can be used. Even though additional footings are added, i f they are not in proper location for a concrete-encased electrode to be used for an existing one may be used. Further, i f no footings are added, then Section 250-83(c) and (d) are recognized. In the Phoenix area this amendment has served adequately for the past Code period and is recommended for general use. PANEL ACTION: Reject. PANEL COMMENT: Sameas Proposal 5-123. VOTE ON_PANEL.ACTION£ Unanimously Affirmative. Log # 1789 5- 134 - (250-81(a), Exception-(New)): Reject SUBMII-FER: Leo F. Martin, Paul Revere Chapter IAEI ~ N - - D A T I O N : Add the following exception: Exception: The electrical system shall be pennitted to be instal led without a supplemental grounding electrode where the existing underground water pipe is in direct contact with the earth for 10 feet (3.05 m) or more and either of the following conditions exist. (a) The water pipe is of copper or brass alloy. (b) The water pipe is 3 inch minimum diameter cast iron. SUBSTANTIATION: A buried copper or brass piping system will provide an adequate low resistance ground for the electrical service which wlll not deteriorate or be removed. I t is not common practice to replace cast iron piping systems with PVC and thus remove the existing grounding system. PANEL ACTION: Reject. PANEL COMMENT: The substantiation is not adequately documented. ~ N - P - A N E C ACTION: UnanimouslyAffirmative. Log # 494 5- 137 - (250-82-(New)): Reject SUBMITTER: Ernest E. Cannon, Tempe, AZ RECOMME_N_DA_TION: Add a Section 250-82 (which was vacated). Required Grounding Electrodes. A grounding electrode in accordance with Section 250-81(c) shall be installed as follows: Ca) For services on new buildings and structures. (b) For relocated, enlarged, or replaced services when additional footings are constructed For additions to existing buildings. Exception: An existing grounding electrode in accordance with Section 250-81(c) shall be permitted to be reused. A grounding electrode in accordance with Sections 250-83(c) or (d) shall be permitted Lo be used for relocated, enlarged, or replaced services when no additional Footings are constructed. SUBSTANTIATION: I t is the intent of this proposal to require a conErete-enca-~sed electrode in all new or remodeled f a c i l i t i e s which provide additional footings which can be used. Even though additional Footings are added, i f they are not in proper location for a concrete-encased electrode to be useful, an existing one may be used. Further, i f no footings are added, then Section 250-83(c) and (d) are recognized. In the Phoenix area thls amendment has served adequately for the past Code period and is recommended for general use. PANEL ACTION: Reject. PANEL COMMENT: Sameas Proposal 5-123. voT__._E_EONPANELACTION~ Unanimously A f f i r m a t i v e . Log # 1747 5- 135 - (250-81(c)): Accept in Principle SUBMITTER: Charles "Mike" Holt, Concepts in Electricity Inc. ~NDATION: 250-81(c). Concrete Encased Electrode. An electrode encased by at least 2 inches (50.8 mm) of concrete, located within and near the bottom of a concrete foundation or footing that is in direct contact with the earth, consisting of at least 20 feet (6.1 m) of one (or more) steel reinforcing bars or rods of not less that 1/2 inch (12.7 mm) diameter, or consisting of at least 20 feet (6.1 m) of bare copper conductor not smaller than No. 4 AWG. Eliminate "or more." SUBSTANTIATION: Section 250-81(c) as written gives the impression the 20 foot length can be achieved by multiple bars each less than 20 feet but totaling 20 feet or more. New wording will clearly indicate that one bar 20 feet of not less than 1/2 inch diameter is required as a minimum. PANEL ACTION: Accept in Principle. Revise ~ o read as follows: "An electrode encased by at least 2 inches (50.8 mm) of concrete, located within and near the bottom of a concrete foundation or footing that is in direct contact with the earth, consisting of at least 20 net linear feet of concrete encasement containing one or more steel reinforcing bars or rods of not less than 1/2 inch (12.7 mm) diameter or bare copper conductor not smaller than No. 4 AWG." PANEL COMMENT: To c l a r i f y intent. VOTE ON PANELACTION: Log # 1515 5- 138 - (250-83): Reject SUBMITTER: R. B. Adams, Freeport, TX ~ T I O N : Change the f i r s t sentence to read: Where none of the electrodes specified in 250-81 is used, one or more -- (and the remainder of the t e x t unchanged.) SUBSTANTIATION: In industrial plants, the grounding of water pipes poses many problems due to stray currents. The use of driven galvanized steel ground rods connected with copper cables and all copper and connections sealed from contact with the earth has proven a good method f o r grounding in large i n d u s t r i a l complexes. Impedance checks to ground have indicated very good conductivity with resistances of less than one ohm measured by the voltage drop method using currents in the range of 50 amperes. In low resistance areas the grounding to water pipes has proven costly in t r y i n g to overcome e l e c t r o l y t i c corrosion, NEGATIVE: Mclntosh. EXPLANATION OF VOTE: ~ O ~ ' - F [ C " l ' ~ - ~ C ~ m i t t e r of Proposal 5-135 and the Panel have attempted to c l a r i f y this section of Code with results less than clear. I suggest the following replacement for Section 250-81(c). 98 COMMENTON VOTE: - ~ ' F F E - ~ : - ~ g h no depth requirement for plate electrodes is included in Section 250-83(d), the main paragraph of Section 250-83 states that "where practicable, made electrodes shall be embedded below permanent moisture level." While this does not specify a depth, i t does give a guideline to follow. PANEL ACTION: Reject. I~KITE'[--CO-~FIE-NT: I t is the intent that the electrodes specified be used for safety. There are alternate methods available to mitigate corrosion which do not compromise safety. VOTE ON PANEL ACTION: ~Fi-R--M~f~v-CT. ~4 NEGATIVE: Mclntosh. EXPLANATION OF VOTE: MCINTOSH: My "negative" vote will be changed to "affirmative" with acceptance of the following additional comments (or their equivalent) to the PANEL COMMENT. "The driven rod electrodes of Section 250-83(c), as discussed by the SUBMII-FER, are permitted i f • NONEof the electrodes in Section 250-81 is available at each building or structure served such as the interior metal water pipe serving the building, and tapped from the underground water main. An insulting Joint in the metal water pipe tap at the transition from underground water main to the interior metal water piping, or a nonmetallic underground water main should be effective against stray currents." Log # 656 5- 143 - (250-83(d)): Reject SUBMII-FER: Edward C. Levan Jr., Tonawanda, NY RECOMMENDATION: Plate electrode shall be buried in a trench that is~--at--~'east--2-1/2 feet (762 ram) deep. Plate Electrodes. Each plate electrode shall expose not less than 2 square feet (0.186 sq m) of surface to exterior soil. Electrodes of iron or steel plates shall be at least i / 4 inch (6.35 mm) in thickness. Electrodes of nonferrous metal shall be at least 0.06 inch (1.52 mm) in thickness. Plate electrode shall be buried in a trench that is at least 2 1/2 feet (762 mm) deep. SUBSTANTIATION: Purpose is to provide conformity with depths r ~ ~her electrodes as in Section 250-81(d) Ground Ring, Section 250-83(c) Rod and Pipe Electrodes and as implied in Section 250-81(c) Concrete-Encased Electrode. PANEL ACTION: Reject. P~NaL~C--C]}-~RE'I~[: The proposal lacks substantiation for the specific installation requirements of this seldom used electrode. VOTE ON PANEL ACTION: Unanimously Affirmative. CO~VIENT ON VOTE: C O H C N { ~ g h no depth requirement for plate electrodes is included in Section 250-83(d), the main paragraph of Section 250-83 states that "where practicable, made electrodes shall be embedded below permanent moisture level." While this does not specify a depth, i t does give a guideline to follow. Log # 580 5- 139 - (250-83(b)): Reject SUBMII-FER: Thomas D'Ambola, Nutley, NJ ~NDATION: (b) Other Local Metal Underground Systems or Structures. Other local metal underground systems or structures, such as piping systems and underground tanks. ADD: or underground electric service raceway not smaller than l-inch trade size, minimum of 30 inches below ground made of iron or steel with outer galvanized coating or otherwise metal coated for corrosion protection, not less than 10 feet long. SUBSTANTIATION: Where a metal lateral service is installed 30 or more below grade not less than 10 feet long, use the metal conduit as a made electrode and eliminate the requirement for an additional made electrode such as a ground rod or other electrodes as described in Section 250-83. PANEL ACTION: Reject. PANEL COMMENT: I t is not the intent of paragraph (b) to include this electrode. VOTE ON PANEL ACTION: Unanimously Affirmative. . . Log # 238 5- 144 - (250-83(e)-(New)): Reject SUBMITTER: H. K. Glenn, Pacific Coast Electrical Association, Inc. RECOMMENDATION: Add a new Section 250-83(e) to read: "---('e-~-~b'6drete-Encased Electrode: An electrode encased by at least 2 inches of concrete, with a minimum cross-sectional area of 4 square inches, buried a minimom of 12 inches below grade, that is in direct contact with the earth, consisting of at least 20 feet of one or more steel reinforcing bars or rods of not less than i/2-inch diameter, or consisting of at least 20 feet of bare copper conductor not smaller than No. 4 AWG. SUBSTANTIATION: There are many existing buildings where an e ~ ' i ' d a l ~ g r d u n d must be established as part of a modification or reconstruction program where no new foundations are required. Also there are buildings being constructed that do not use a concrete foundation. This proposal was presented to the Panel In 1978, because this installation is being used in lieu of driven grounds and has proven to be more effective than driven ground rods. We have discussed the question raised in 1978, on frost line condition with Mr. Max McComb, Electrical Engineer, Reno, Nevada, who designed several ski l i f t s in the High Sierras and we are sure you have read the results of his tests on this method of rounding. Mr. McComb states he has made tests on the l i f t s under rozen ground conditions and the reading showed less resistance in the frozen earth than readings taken in other seasons. These l i f t s were subjected to numerous lightning strikes and caused many equipment failures before this method of grounding was installed. There have been no failures since this method was installed. This method should be adopted. PANEL ACTION: Reject. PANEL COMMENT: Panel is concerned with the structural integrity and possible resultant corrosion at cracks. Panel has not seen the referenced supporting data. VOTE ON PANEL ACTION: Unanimously Affirmative. . Log # 339 5- 140 - (250-83(c)(1)): Reject SUBMII'TER: Michael P. O'Quinn, IBEW Local 59 RECOMMENDATION: Add the word "Metal" between the words "or" and "conduit," so as to read: "Electrodes of pipe or "metal" conduit shall not be smaller than 3/4-inch trade size and, where of iron or steel, shall have the outer surface galvanized or otherwise metal-coated for corrosion protection." SUBSTANTIATION: This would be to c l a r i f y that only rigid metal conduit or intermediate metal conduit (or nonelectrical pipe) may be used as an electrode. As the wording stands now, rigid nonmetallic conduit could be misinterpreted as an electrode. PANEL ACTION: Reject. I~-Eq_--I~MME-NT: The Panel feels that i t is understood that electrodes are metallic. VOTE ON PANEL ACTION: UnanimouslyAffirmative. ~ Log # 533 5- 141 - (250-83(c)(3)): Reject SUBMII-FER: J . K . Daugherty, F l i n t , MI RECOF~MENDATION: Revise the 5th line from "or shall be buried in a trench ~ at least 2 1/2 feet (762 mm) deep" to "or at least 20 feet (6.1 m) of one or more electrodes bonded in series shall be buried in a trench that is at least 2 1/2 feet (762 mm) deep." SUBSTANTIATION: The present wording allows the least effective location of a minimal 8 foot electrode. The above wording will improve this requirement to equate withSection 250-81(c). PANEL ACTION: Reject. !~-A-N~C--CX~M~NT: I f the single 8 foot rod is not 25 ohms or less, Section 250-84 requires two rods not less than 6 feet apart. This appears to achieve the objective. VOTE ON PANELACTION: UnanimouslyAffirmative. Log # 03 5- 145 - (250-84): Reject Secretary's Note: This proposal is for a revision of the 1978 edition but was received after the deadline for proposals. SUBMII-FER: Edward J. McNealon, Tampa, FL R~ATION: Add to the existing requirements of 250-84 the following "or augmented by a ground resistance lowering device." SUBSTANTIATION: The criterion of "25 ohms or less" is not possible even with multiple electrodes. This proposal was rejected in 1978 by the Code Panel to wit: "Code Panel feels there is no reason for mandatory requirement that single electrodes be less than 25 ohms." Obviously, the 1978 Code Panel concluded that the "single driven electrode" was my objective rather than a solution to meet the 25 ohm criterion. I have invented a device, "patent pending" that will lower the resistance of a ground rod, new, or existing, to 10 ohms or less. PANEL ACTION: Reject. PANEL COMMENT: There is no c r i t e r i a that grounding electrodes have a resistance of 25 ohms or less, only that where a single electrode is greater than 25 ohms i t be supplemented by a second electrode. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 332 5- 142 - (250-83(d)): Reject SUBMITTER: Michael J. Ciauro, East/West Electrical Contractors, n~. RECOMMENDATION: The 1981 Code does not specify burial depth of ~Ero-6~es. SUBSTANTIATION: I f the burial depth is the sa~e as a h o r i z o n t a l l y b--u-r'~--e~--rod'e'lectrode, 2 1/2 feet (762 m), I think i t should be so stated. PANEL ACTION: Reject. PANEL~M-~--M-~--NT: See Proposal 5-143. ~FANEC ACTION: UnanimouslyAffirmative. 99 Log # 1704 5- 151 - (250-91(a), FPN-(New)): Reject SUBMITTER: Charles "Mike" Holt, Concepts in Electricity Inc. RECOMMENDATION: 250-g1(a). Add fine print note - "There is no ~ o ~ i ~ g ' ~ e q u i r e d of the insulated grounding electrode conductor." SUBSTANTIATION: Some inspectors interpret that this section r6qufrest-s-t-~at-250-57(b) would apply where insulated and the conductor shall be green-tagged. PANEL ACTION: Reject. ]~N~'C--CG~ENT: The Panel agrees that the statement is correct but does not feel i t needs to be incorporated into the Code. VOTE ON PANELACTION: --A~'FIRMA'F~ NEGATIVE: Nagel. EXPLANATION OF VOTE: ~-T~f6gCH6~ the Panel agrees that the statement is correct, I feel the proposal should be accepted. Log # 534 5- 146 - (250-84): Reject SUBMII-TER: J . K . Daugherty, Flint, MI ~DATION: Add "primary" between "single" and "electrode" in the 1st line. SUBSTANTIATION: By adding the word "primary" i t will help c l a r i f y that supplemental electrodes required by Section 250-81(a) will not require the treatment of Section 250-84. PANEL ACTION: Reject. I~B~TE~C--~O--~NT: Requirements of Section 250-84 make i t clear that the supplementary electrode need not be supplemented again. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 535 5- 147 - (250-84 and FPN): Reject SUBMITTER: J . K . Daugherty, Flint, MI ~NDATION: Revise "6 feet (1.83 m)" to "10 feet (3.05 m)" in t--he-~and the FPN. SUBSTANTIATION: To improve the paralleling efficiency of made electrodes and to correlate with the requirements of Sections 3-21.1 and 3-21.2 of the Lightning Protection Code, NFPA78-1980. PANEL ACTION: Reject. ~rAITEqZ-CCI~IE~N~T: No technical justification for the minimal improvement which would be achieved. Increasing the spacing o f 8 foot ground rods from six feet to ten feet improves the net resistance by only eight percent. VOTE ON PANELACTION: UnaninmuslyAffirmative. Log # 1206 5- 152 - (250-91(b)): Reject SUBMI1-FER: Charles J. Hart, NECA R~TION: Revise Section 250-91(b) to read: --~-6-)---fj#6g'6f Equipment andClosure Grounding Conductors. The grounding conductor for equipment and for conduit and other metal raceways or enclosures for conductors shall be one of the following: (1) A conductor of copper or other corrosion-resistant material, stranded or solid, Insulated or bare. I f run in conduit or raceway with current-carrying conductors, i t shall be insulated and identified by a green color or green with one or more yellow stripes. (2) A busbar. (3) The armor of Type AC. (4) The sheath of Type MI cable. (5) The metallic sheath or the combined metallic sheath and grounding conductors of Type MC cable. All bolted or threaded connections at joints and f i t t i n g s shall be made tight by the use of suitable tools. Delete Exceptions. SUBSTANTIATION: The grounding conductor is an essential safety element oT-~--~ircuit under ground-fault conditions. A wide variety of raceways and f i t t i n g s now in use have no specified r e s i s t i v i t y , ampacity, or I CT performance, and therefore raceways cannot be relied upon Lo provide the effective grounding path required by Section 250-51. Bare conductors may damage insulated conductors where both are installed together in conduit. For marinas and boatyards (Section 555-7) and swin~ning pools (Section 680-25), NEC requires an insulated equipment grounding conductor run with the circuit conductors, recognizing that a raceway system is not inherently a reliable electric~ conductor. Also, many electrical designers recognize the inadequacy of the raceway system as a suitable grounding conductor for modern wiring systems and specify Lhe installation of an insulated grounding conductor in raceways. At intervals of 10 feet or less throughout its length, a raceway system has joints or terminations, often not accessible for inspection, that may and on occasion do become loose, rusted, or corroded so as to impair electrical conductivity. The intent of this proposal is to provide the same level of equipment-grounding r e l i a b i l i t y For all installations as is now required for marinas and swimming pools. PANEL ACTION: Reject. ~AI~E-[-~: Proposal would eliminate all raceways as grounding conductors. Submitter has not supplied adequate support for such a change as requested when previous similar proposals were made. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 536 5- 148 - (250-86): Reject SUBMII-FER: J. K. Daugherty, Flint, MI ~NDATION: Revise last sentence from "This provision shall not prohibit the required bonding to~ether of grounding electrodes of different systems" to "All groundlng electrodes of different systems shall be bonded together." SUBSTANTIATION: Former wording has lead to misinterpretation. PANEL ACTION: Reject. I~)~E'L---C~F~'7~F: There is no technical justification for the substantiative change requested. VOTE ON PANELACTION: UnanimouslyAffirmative. Log # 1965 5- 149 - (250-90-(New)): Reject SUBMITTER: Richard W. Osborn, St. Louis, MO RECOMMENDATION: Each branch circuit or feeder derived from a ~rounded alternating current system shall include a corresponding insulated grounding conductor, sized in accordance with Table 250-95. The integrity of the grounding conductor shall be maintained by appropriate wiring methods. Exception No. 1: Service Conductors. Exception No. 2: Covered cable assemblies shall not require insulation on the grounding conductor. Exception No. 3: Section 250-60. SUBSTANTIATION: The increased use of nonmetallic raceway systems, ~ a t { o n - o { electrical equipment requiring dependable grounding sources and the intermingling of various types of wiring systems now require a bold approach to meeting the need for dependable low-resistance grounding sources. PANEL ACTION: Reject. PANEL COMMENT: Submitter has not shown evidence of the inadequacy of present grounding requirements. VOTE ON PANELACTION: Unanimously Affirmative. Log # 53 5- 153 - (250-g1(b), Exception No. i a., Exception No. 2): Reject SUBMITTER: Dan Leaf, Westlake Village, CA RECOMMENDATION: Revise Exception No. 1 a. as follows: a. The total length in any ground return path without an equipment bonding jumper or equipment grounding conductor Is six feet or less. Revise Exception No. 2 as follows: Exception No. 2: Liquidtight f l e x i b l e metal conduit shall be permitted for grounding in the I-1/4 inch and smaller trade sizes i f the total length in any ground return path, without an equipment bonding jumper or equipment grounding conductor is 6 feet or less and the conduit is terminated in f i t t i n g s approved for grounding. Log # 207 5- 150 - (250-91(a), Exception No. 3-(New)): Reject SUBMITTER: Dan Leaf, Westlake Village, CA ~OATION: Add Exception No. 3 as. follows: Connections between an approved grounding plate used as the terminating point for the grounding electrode conductor, and one of the electrodes described in Section 250-81(c) shall be permitted. The conductor from the grounding plate to the electrode shall be copper and not smaller than No. 4 AWG. SUBSTANTIATION: Present wording, in effecL, requires a rebar or No. 4 copper conductor electrode to be stubbed out of the footing or foundation for later connection to the grounding electrode conductor, or a direct imbedded connection to a rebar electrode, with the required length of grounding electrode conductor connected or installed at that time. The stub-out procedure is objectionable in many cases due to esthetics, corrosion, etc. The connection of the grounding electrode conductor in one continuous length at the time of connection to the electrode will generally be at an early stage of construction which promotes the possibility of damage or theft. PANEL ACTION: Reject. 15-~N-I~=C ' ~CO-MMEfT[T: Recommendation and substantiation are not clear. VO~I'E'--OI~-F~TE'I~ ACTION: Unanimously Affirmative. 100 PANEL ACTION: Accept in Principle. FAIfEt--CR]I~E~T: See Proposal 5-154. VOTE ON PANEL ACTION: Unanimously Affirmative. SUBSTANTIATION: Literal interpretation would limit length of any run to six feet whether or not a separate equipment grounding conductor is installed. A l i t e r a l .interpretation of the Exceptions would require all portions of a flexible metal conduit or liquidtight flexible metal conduit run, including that portion with an equipment bonding jumper, to be counted as part of the ground return path, as such conduit is in parallel with the bonding (or grounding) conductor and thus is part of the ground return path. PANEL ACTION: Reject. F]IJTE'C-ObNt~RT: The Panel disagrees that a l i t e r a l interpretation would limit the length when a grounding conductor or bond is run since the conduit is not being used as the equipment grounding conductor. VOTE ON PANELACTION: UnanimouslyAffirmative. Log # 406 5- 156 - (250-91(b), Exception No. 2): Accept Secretary's Note: The Correlating Committee directs that the proposal be referred to CMP 8 for information. SUBMITTER: Frederick 'A. Reker, O-Z/Gedney Company RECOMMENDATION: Add the following to the end of the Section: . ~ . . a n d " t h d ' c i r c u i t conductors contained therein are protected by overcurrent devices rated at 20 amperes or less for 3/8-inch and 1/2-inch trade sizes and 60 amperes or less for 3/4-inch through 1 1/4-inch trade sizes. The exception will then read as follows: Liquidtight Flexible metal conduit shall be permitted as a grounding means in the 1 I / 4 inch and smaller trade sizes i f the total length of any ground return path is 6 feet (1.83 m) or less, the conduit is terminated in f i t t i n g s approved for grounding, and the circuit conductors contained therein are protected by overcurrent devices rated at 20 amperes or less for 3/8-inch and 1/2-inch trade sizes and 60 amperes or less for 3/4-inch through 11/4-inch trade sizes. SUBSTANTIATION: Recent field experience has indicated that i t is poss~le to'overload the armor of liquidtight flexible metal conduit under certain ground-fault conditions. Overloading the armor causes the jacket material to melt, smoke, and possibly flame. This led to a study by UL and industry to determine the practical limit of use for this conduit under ground-fault conditions. Ground-fault current tests were conducted and i t was determined that an overcurrent protective device limitation similar to the limit in Section 350-5 would protect the continuity of the ground system. Recent tests by UL and industry based on the grounding conductor size specified in Table 250-95 of the NATIONAL ELECTRICAL CODE have confirmed the fact that overcurrent protection device limitations proposed will provide a grounding and bonding system that meets nationally accepted standards. See attached bulletin Subject 360 of Sept. 4, 1981 from Underwriters Laboratories Inc. (Note: A copy of this bulletin in available from NFPA upon request.) This will also provide guidance to discourage the possible misuse of this conduit by clearly defining its worst case limitation right in the Code. By limiting the circuits to 20 amperes for 1/2 inch and smaller trade size and 60 amperes for 3/4-inch through 1 1/4-inch trade size, there will be acceptable protection against a ground-fault destroying the conduit. This submittal is supported by the manufacturers of liquidtight flexible metal conduit. Exception No. 2 to Section 250-91(b) uses the words "shall be permitted for grounding" whereas "shall be permitted as a grounding means" is used in Section 351-9, Exception. These should be e d i t o r i a l l y changed to agree with each other preferably using "shall be permitted as a grounding means" in both sections. A companion proposal has been submitted for Section 351-9, Exception. PANEL ACTION: Accept. gO~E:-'O-N-'FAN~L ACTION: AFFIRMATIVE: 13 NEGATIVE: Mclntosh. EXPLANATION OF VOTE: MCINTOSH: The submitter and the UL bulletin 360 of Sept. 4, 1981 are to be complicated on recognizing a problem that has been around f o r many years. However I believe the results desired by the submitter and many users in the trade will not be achieved in the manner proposed. First of all not all liquidtight flexible metal conduit in the market place is approved as a raceway. Some is sunlight resistant-some is not. Secondly, eccentricity of the plastic jacket on the f l e x i b l e conduit, where permitted to exceed to normal manufacturing tolerances, creates a problem associated with proper seating of the ferrule in the end of the flexible conduit. Thirdly, connectors come in many shapes and configurations, some good, some not so good. Fourthly, the liquidtight flexible conduit and the connectors are usually not made by the same manufacturer, which can affect the f i t . Fifthly, liquidtight flexible metal conduit, sizes 3/4 inch and larger, is predominantly used for motor connections in lengths of only 18 to 24 inches in length. This practice is not so much for f l e x i b i l i t y as i t is for simplification of the conduit alignment with the motor and the resulting labor savings resulting compared to use of rigid conduit at the motor. Over half of the total liquidtight flexible metal conduit footage used is 1/2-inch trade size, primarily for instrumentation and control circuit terminations, in typical lengths of 30 to 48 inches. The connector problem also seems to be related: (1) a need for more DEPTH OF PENETRATION of the ferrule into the end of the f l e x i b l e conduit; (2) the LACK OF VISIBILITY on some connector ferrules for the installer to see i f the ferrule is properly seated to f u l l penetration depth; (3) the pull-out problem is worse with combinations of some connectors and conduit from different manufacturers. • I recommend changing Exception No. 2 to read: "Liquidtight flexible metal conduit without an internal or external equipment bonding conductor shall be permitted for grounding i f all the following conditions are met: Log # 2083 5- 154 - (250-91(b), Exception No. i ) : Accept in Principle SUBMITTER: 8. Auger/H.B. Love, Michigan Chapter IAEI ~N~TION: Add to end of present Exception: "; and the conduit is not installed in accordance with Section 350-4, Exception No. 2." SUBSTANTIATION: This is to assure that an effective and ~ous grounding path is maintained. Our field experience shows a consistent problem with loose connections and lost grounding paths where f l e x i b l e metal conduit is used to wire equipment that is not fixed in one place or position. A recent experience involving electrical inspections of dozens of restaurants across d i f f e r e n t parts of the State showed this problem in each and every restaurant. This amendment would serve a dual function. First, i t would assure that, in these instances, the equipment would remain grounded. 'Second, i t would point out that, in lengths over 3 feet, flexible metal conduit must be secured. PANEL ACTION: Accept in Principle. ~xception No. 1 to Section 250-91(b) to read as follows: "Exception No. I : When not used to connect equipment where f l e x i b i l i t y is required, flexible metal conduit and flexible metallic tubing shall be permitted for grounding i f all the following conditions are met." PANEL COMMENT: To meet intent of proposal and to correlate with ~ a ~ T ' 8 - 2 7 6 for a new Exception No. 2 i n Section 350-5. VOTE ON PANEL ACTION: 'agglR~TrV~---f~-- NEGATIVE: Mclntosh. EXPLANATION OF VOTE: MCINTOSH: The submitter is endeavoring to solve a very real flexible conduit (or tubing) and connector loosening and/or pullout problem but I believe the desired results will not be achieved in the manner proposed. First of a l l , not all flexible conduit in the market place is approved as a raceway. Secondly, connectors come in many shapes and configurations, some good, some not so good. The connector problem seems to be related to: ( i ) a need for more DEPTH OF PENETRATION OF THE FERRULE INTO THE FLEXIBLE CONDUIT; (2) the lack of v i s i b i l i t y on some connector ferrules f o r the installer to see i f the ferrule is actually seated at f u l l penetration depth; (3) the pull-out problem is worse with some connectors than with others due in part to f i t - u p tolerances. Remember the flexible conduit and the connectors are usually not made by the same manufacturer. I recommend changing Exception No. 1 to read: "Flexible metal conduit and f l e x i b l e metal tubing without an internal or external equipment bonding conductor shall be permitted for grounding i f all the following conditions are met: a. Circuit voltage is 120 volts, nominal to ground, or less. b. Circuit protective device is 20 amperes, or less. c. Conduit size does not exceed 3/4-inch trade size; tubing, I/2 inch. d. Conduit or tubing length is 6 feet (1.83 m), or less. e. Equipment is located in a nonhazardous area. f . The conduit or tubing and the conduit or tubing connectors are approved for grounding. " I f any of the above conditions (a) through (f) are not met an equipment bonding conductor shall be installed either inside or outside of the conduit or tubing in accordance with Section 250-79(e)." Log # 1987 5- 155 - (250-91(b), Exception No. 1): Accept in Principle SUBMITTER: IAEI ~ T I O N : Add to end of present exception: "; and the conduit is not installed in accordance with Section 350-4, Exception No. 2." SUBSTANTIATION: This is to assure that an effective and continuous grounding path is maintained. Our f i e l d experience shows a consistent problem with loose connections and lost grounding paths where f l e x i b l e metal conduit is used to wire equipment that is not fixed in one place or position. A recent experience involving electrical inspections of dozens of restaurants across different parts of the State showed this problem in each and every restaurant. This amendment would serve a dual function. First, i t would assure that, in these instances, the equipment would remain grounded. Second, i t would point out that in lengths over 3 feet, flexible metal conduit must be secured. 101 a. Circuit voltage is 120 volts, nominal to ground, or less. b. Circuit protective device is 20 amperes, or less. c. Conduit size does not exceed 3/4-inch trade size. d. Conduit length is 6 feet (1.83 m), or less. e. Equipment is located in a nonhazardous area. f . The liquidtight flexible metal conduit and connectors are approved for grounding. " I f any of the above conditions (a) through (f) are not met an equipment bonding conductor shall be installed either inside or outside of the conduit in accordance with Section 250-79(e)." SUBSTANTIATION: The second sentence of Section 250-92(a) is not consistent with the third sentence of this paragraph since i t does not identify the situation where a No. 6 grounding conductor free from exposure to physical damage shall be permitted to be run along the surface of the building construction without metal covering or protection. In general, i t is confusing. The new wording would make i t simple to understand. PANEL ACTION: Reject. PANEL COF~MENT: Request submitter to c l a r i f y the proposal. VOTE ON PANELACTION: Unanimously Affirmative. Log # 622 5- 157 - (250-91(b)(6)): Reject SUBMITTER: J. K. Daugherty, F l i n t , MI RECOMMENDATION: "(6) the armor and bonding strip of armored cable;" SUBSTANTIATION: I t is both the armor and bonding strip terminated under and in direct contact with an armored cable connector that makes armored cable acceptable ~or grounding. Types ACT and ACL should also be acceptable hence the replacement with the term "armored cable." PANEL ACTION: Reject. PANEL COMMENT: I t is not the intention that the bonding strip be required to be terminated since i t performs its function by direct contact with each convolution. VOTE ON PANELACTION: UnanimouslyAffirmative. Log # 52 5- 158 - (250-92(a)): Reject SUBMITTER: Dan Leaf, Westlake Village, CA RECOMMENDATION: Revise f i r s t paragraph as follows: (a) A grounding electrode conductor or its enclosure shall be securely fastened to the surface on which i t is carried: A No. 6 or larger conductor shall be protected i f exposed to physical damage. Required protection shall be provided by installation in rigid metal conduit, rigid nohmetallic conduit, intermediate metal conduit, electrical metallic tubing, or cable armor. Grounding electrode conductors smaller than No. 6 shall be in rigid metal conduit, rigid nonmetallic conduit, intermediate metal conduit, electrical metallic tubing, or cable armor. A grounding electrode conductor shall be permitted in the same raceway or enclosure with other conductors of the system to which i t is connected. Add the following to the second paragraph: When installed as an unenclosed (open) conductor, or in cable armor, supports shall be provided at intervals not exceeding four and one-half feet and within twelve inches of terminations, except when fished. Unenclosed (open) conductors installed through wood framing members shall comply with the requirements of Section 300~(a). SUBSTANTIATION: Wording is vague; no requirements for support of unenclosed conductors. Is some degree of damage to No. 4 or larger conductor acceptable? Is 50 percent severage of a conductor severe? As presently w~rded this Section does not require protection against less than "severe" damage for No. 4 or larger conductors. Staples may not be suitable for installation on masonry or concrete, but an interpretation of this Section may require them, i f enforced l i t e r a l l y . A conductor may be r i g i d l y stapled to construction (where so fastened) but no required spacing is indicated for unenclosed or enclosed-in-armor conductors. I t seems desirable to specify protection for unenclosed conductors against nails~ screws, etc., when installed in wood framing members. PANEL ACTION: Reject. ~ANEL COMMENT: No evidence this is a field problem and includes unsubstantiated substantiative changes. VOTE ON PANELACTION: Unanimously Affirmative. Log # 1655 5- 159 - (250-92(a)): Reject SUBMITTER: Charles "Mike" Holt, Concepts in Electricity Inc. ~ T I O N : 250-92(a). Grounding Electrode Conductor. Delete the words "A grounding electrode conductor or its enclosure shall be securely fastened to the surface on which i t is carried. A No. 4 copper or aluminum, or larger conductor shall be protected i f exposed to severe physical damage. A No. 6 groundingconductor that is free from exposure to physical damage shall be permitted to be run along the surface of the building construction without metal covering or protection where i t is r i g i d l y stapled to the construction, otherwise," and add "grounding electrode conductors exposed to physical damage shall be provided with a metal covering or protection" or i t shall be in rigid metal conduit, intermediate metal conduit, rigid nonmetallic conduit, electrical metallic tubing, or cable armor. Grounding conductors smaller than No. 6 shall be in rigid metal conduit, intermediate metal conduit, rigid nonmetallic conduit, electrical metallic tubing, or cable armor. • 102 Log # 1730 5- 160 - (250-94): Reject SUBMITTER: Charles "Mike" Holt, Concepts in Electricity Inc. RECOMMENDATION: 250-94. The size of the grounding electrode conductor "and/or supplementary electrode conductor" of a grounded or ungrounded ac system shall not be less than given in Table 250-94. SUBSTANTIATION: Change is requested in order that 250-94 will clearly define that Table 250-94 is to be used for main electrode conductor and supplementary electrode conductor sizing. PANEL ACTION: Reject• PANEL COMMENT: See Proposal 5-133. VOTE ON PANELACTION: Unanimously Affirmative. Log # 537 5- 161 - (250-94, Exception No. 1): Accept SUBMITTER: J. K. Daugherty, Flint, MI ~ T I O N : Add "(a)" after "Grounded Systems" in the 1st line and the following: (b) where connected to concrete-enclosed electrode as in Section 250-81(c), that portion of the grounding electrode conductor which is the sole connection between the grounding electrode and the grounded system conductor shall not be required to be larger than No. 4 copper wire. (c) where connected to a ground ring as in Section 250-81(d), that portion of the grounding electrode conductor which is the sole connection between the grounding electrode and the grounded system conductor shall not be required to be larger than No. 2 copper wire. SUBSTANTIATION: In both the concrete-enclosed electrode and the ground ring, the electrode copper wire size may be less than that required by Section 250-94. There is no electrical reason for requiring the grounding electrode conductor to be larger than the electrode when the electrode is constructed of a conductor. PANEL ACTION: Accept. VOTE ON PANEL ACTION: AFFIRMATIVE: 13 NEGATIVE: Cohen• EXPLANATION OF VOTE: COHEN: Mr. Daugherty states that there is no electrical reason for requiring the grounding electrode conductor to be larger than the electrode when the electrode is constructed of a conductor; however, for a concrete-encased electrode, Section 250-81(c) requires the copper conductor to be not smaller than No. 4 AWG, but the proposal states i t shall not be required to be larger than No. 4. Similarly, Section 250-81(d) requires a ground rinq to be not smaller than No. 2 AWG, and the proposal states i t shall not be required to be larger than No. 2. I suggest that Section 250-94, Exception No. l(b) be reworded as follows: "...shall not be required to be larger than the conductor used for the electrode."; and Section 250-94, Exception No. 1(c) be reworded as follows: "shall not be required to be larger than the conductor used for the ground ring." Log # 1881 5- 162 - (250-94,Exception No. 1): Reject SUBMITTER: J. K. Daugherty, Flint, MI RECOMMENDATION: Delete "sole" in the 3rd line. SUBSTANTIATION: The present requirement implies that i f a made electrode is the only grounding electrode, the electrode conductor may be a No. 6 copper wire or No. 4 aluminum. But i f a made electrode is supplementary per Section 250-81(a), the grounding electrode conductor shall be per Table 250-94. I do not see the j u s t i f i c a t i o n for this requirement since a made electrode is current limiting under either condition. PANEL ACTION: Reject. PANEL COMMENT: Under some conditions this would permit made electrodes to be connected by an undersized conductor. VOTE ON PANEL ACTION: UnanimouslyAffirmative. UF installed in accordance with the appropriate provisions of Article 339. PANEL ACTION: Reject. PANEL COM~NT: Request submitter to c l a r i f y meaning of common enclosure and application of requirement to trenches especially with respect to how the grounding conductor and circuit conductors are coupled. VOTE ON PANELACTION: AFFIRMATIVE: 13 NEGATIVE: Brown. EXPLANATION OF VOTE: BROW~: In order to better c l a r i f y the intent of the proposal, the second paragraph should be revised to read "see Section 300-5(c)." Log # 493 5- 163 - (250-94, Exception Nos. 1 and 2): Reject SUBMITTER: Ernest E. Cannon, Tempe, AZ RECOMMENDATION: Add after "Section 250-83(c) or (d)" "or Section 250-81(c)" SUBSTANTIATION: In the revisions of NEC 1975 f o r NEC 1978, concrete-encased electrodes were relocated from Section 250-83(a) to Section 250-81(c) and the re-bar was added. Section 250-94, Exception Nos. 1 and 2 then changed from Section 250-83 to Section 250-83(c) or (d) in 1981NEC. I t appears that the concrete-encased (or Ufer) electrodewas recognized as meeting the criteria for the Exception during NEC 1975 but lost that recognition in NEC 1978 and remained so in 1981. Data submitted by Proposal 61 for 1974 Preprint indicates that the expected resistance of the Ufer is such that No. 6 copper would be more than adequate as the grounding electrode conductor for the concrete-encased electrode. Perhaps i t was an oversight that the concrete-encased electrode was relocated without being relisted in these Exceptions. There appears to be adequate data to qualify for the Exception. In general data indicates that the resistance of rods and plates may be expected to be less than that of concrete-encased grounding electrode. PANEL ACTION: Reject. PANEL COMMENT: Proposal would permit concrete-encased electrodes to be connected by a No. 6 copper conductor which is considered to be too small. Also see Proposal 5-161. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 1723 5- 167 - (250-95): Reject SUBMITTER: Charles "Mike" Holt, Concepts in Electricity Inc. RECOMMENDATION: Add new paragraph: 250-95 "Equipment grounding conductors on secondary of transformer should be sized based upon an overcurrent device conductor that would be used to protect those secondary conductors." SUBSTANTIATION: Section 250-95 as written does not provide a vehicle to size equipment grounding conductors on secondary of a transformer where feeder taps are used for secondary conductors. A reference should be added to indicate a method for sizing equipment grounding conductors on the secondary of transformer. PANEL ACTION: Reject. PANEL COFCVENT: Request submitter to c l a r i f y proposal with regard to type and application of transformer. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 444 5- 164 - (250-94, Exception Nos. I and i ) : Reject SUBMITTER: Southwestern Section IAEI RECOY~MENDATION: Add after "Section 250-83(c) or (d)" "Or Section 250-81(c)" SUBSTANTIATION: In the revisions of NEC 1975 for NEC 1978, concrete-encased electrodes were relocated from Section 250-83(a) to Section 250-81(c) and the re-bar was added. Section 250-94, Exception Nos. I and 2 then changed from Section 250-83 to Section 250-83(c) or (d) in 1981 NEC. I t appears that the concrete-encased (or Ufer) electrode was recognized as meeting the criteria for the exception during NEC 1975 but lost that recognition in NEC 1978 and remained so in 1981. Data submitted by Proposal 61 for 1974 Preprint indicates that the expected resistance of the Ufer is such that No. 6 copper would be more than adequate as the grounding electrode conductor for the concrete-encased electrode. Perhaps i t was an oversight that the concrete-encased electrode was relocated without being relisted in these Exceptions. There appears to be adequate data to qualify for the Exception. In general data indicates that the resistance of rods and plates may be expected to be less than that of concrete-encased grounding electrode. PANEL ACTION: Reject. PANEL COUNT: Sameas Proposal 5-163. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 239 5- 168 - (250-95, 2nd paragraph): Reject SUBMITTER: H. K. Glenn, Pacific Coast Electrical Association, Inc. ~ T I O N : Amend Section 250-95, second paragraph to read as follows: Where c i r c u i t conductors are run in p a r a l l e l and in m u l t i p l e raceways, as permitted in Section 310-4, the equipment grounding conductor, when used, shall also consist of paralleled conductors, one in each raceway. All of the p a r a l l e l equipment groundingnd conductors shall be of the same length, conductor material, a c i r c u l a r - m i l area and sized so as to provide an aggregate ampacity equivalent to that of a single conductor selected on the basis o f the ampere r a t i n g of the overcurrent device protecting the paralleled c i r c u i t conductors. SUBSTANTIATION: The Code permits p a r a l l e l i n g of the c u r r e n t - c a r r y i n g c i r c u i t conductors under specified conditions. I t is not only inconsistent but i l l o g i c a l to deny t h i s design p r i v i l e g e to passive elements of the wiring system. Further inconsistencies in the Code are apparent. Section 250-71(c), f o r instance, allows the equipment bonding jumper (equipment grounding conductor by another name) in parallel service raceways to be based on the size of the service conductors in each raceway. Furthermore, in their proposed outline for Type TC cable (UL1277), the Underwriters Laboratories recognized the inherent v a l i d i t y of the concept of divided, or sectioned, grounding conductors by recognizing their use with the condition that "the total circular-mil area of a sectioned or distributed grounding conductor shall be equal to or larger than that of the corresponding size of a single conductor." The proposed amendment provides the basis and logic for sizing parallel equipment grounding conductors. This procedure will assure a suitable and adequate ground-fault current path, consistent with the design principles of the circuit wiring, when parallel circuit conductors are permitted and will comply with the requirements of Section 250-51. PANEL ACTION: Reject. PANEL COUNT: The proposer makes an unsubstantiated change in the grounding conductor size. Under internal fault conditions the ground current tends to run as closely as possible to the faulted phase conductor. The bulk of the current flows in this path and only a minor portion flows in the other multiple paths. Thus each ground conductor must be suitable for a large share of the total available f a u l t current. The equipment grounding conductors selected by this proposal are not adequate in many cases, in fact, many of the combinations will melt before the protective device will open the circuit. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 538 5- 165 - (250-95): Accept in Principle SUBMITTER: J. K. Daugherty, F l i n t , MI ~ T I O N : Add [o 1st paragraph: "Where the equipment grounding conductor is run in lengths exceeding 100 feet (30.5 m), the size shall be increased to two sizes larger." SUBSTANTIATION: The present requirements of Section 250-95 and Table 260-95 are based on reasonable lengths of conductors. Theoretically, lengths exceeding 100 feet may not operate the overcurrent protective device without a correlated increase in conductor size. PANEL ACTION: Accept in Principle. Revise the third paragraph to read as follows: "When conductors are adjusted in size to compensate for voltage drop, equipment grounding conductors, where required, shall be adjusted proportionately according to circular mil area." PANEL COMMENT: Intent of proposal is covered in third paragraph which is further c l a r i f i e d . VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 871 5- 166 - (250-g5): Reject SUBMITTER: H. Brooke Staffer, NEMA RECOMaMENDATION: Change the last paragraph to read: Where a s--Ingle equipment grounding conductor is run with multiple circuits in a common enclosure, raceway or trench, i t shall be sized for the largest overcurrent device protecting the corresponding circuit conductors. Where run in an enclosure or trench, the grounding conductor shall be grouped with the circuit conductors. SUBSTANTIATION: The rationale applied to the text in the 1981 NEC should be extended to conductors installed in environments beyond "raceways" such as: USE installed in accordance with the appropriate provisions of Article 338. Log # 276 5- 16g - (250-112, Exception): Accept SUBMITTER: W. Creighton Schwan, Hayward, CA RECOMMENDATION: Revise the Exception as follows, added material shown in quotations. Exception: "An encased or buried" connection to a concrete-encased, driven, or buried grounding electrode shall not be required to be accessible. 103 SUBSTANTIATION: Where connections are made to exposed portions of electrodes which are largely encased, driven, or buried, such connections must be accessible. The present wording of the exception leads to possible misinterpretation that electrodes largely concrete-encased, or buried, need not have the exposed connections to them accessible. The suggested revision will not allow such misinterpretation of the intent of the requirement. PANEL ACTION: Accept. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 539 5- 170 - (250-113): Reject SUBMITTER: J. K. Daugherty, Flint, MI ~ATION: Revise the 2nd sentence to: "Securement mechanically, connection devices, or f i t t i n g s that depend on solder for electrical continuity shall not be used." SUBSTANTIATION: Grounding connections could be subjected to ground faults and should not depend on solder for electrical continuity. PANEL ACTION: Reject. PANEL COMMENT: Present wording is much clearer than the proposal: VOTE ON PANELACTION: UnanimouslyAffirmative. SUBSTANTIATION: 250-117(a) and (b) are t o t a l l y confusing in that 250-117(a) states where physical damage is present, i t can be protected by installations where they are not likely to be damaged. EDITORIALCHANGE. PANEL ACTION: Reject. PANEL COMMENT: Does not allow for use of ground clamps approved for general use without protection. VOTE ON PANELACTION: UnanimouslyAffirmative. ARTICLE 280 -- LIGHTNING ARRESTERS Log # 1930 5- 175 - (280-4(b)): Accept SUBMITTER: Charles M. Lutz, Underwriters Laboratories Inc. I ~ATION: Fine Print note - change "Lightning" to "Surge." "C62.2-1969" to "C62.2-1981," SUBSTANTIATION: Change in t i t l e of ANSI C62.2-1981. PANEL ACTION: Accept. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 1576 5- 176 - (280-4(b),FPN): Accept SUBMI1-TER: David W. Jackson, IEEE, Power Engineering Society, Surge Protective Devices Committee RECOMMENDATION: In the Fine Print Note following Section 280-4(b), correct the reference to ANSI C62.2 to read as follows: "Guide for the Application of Valve-Type Surge Arresters for Alternating-Current Systems (ANSI C62.2-1981)." SUBSTANTIATION: C62.2-1981 is the#pproved national standard guide for application of surge arrdsters. The deprecated term "lightning arrester" in the t i t l e has been replaced by the recommended term "surge arrester." PANEL ACTION: Accept. PANEL COMMENT: See Proposal 5-175. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 835 5- 171 - (250-114): Accept in Principle SUBMITTER: Walter A. Upson, Chocorua, NH RECOMMENDATION: Rewrite a portion of the f i r s t sentence. 250-114. Continuity and Attachment of Branch-Circuit Equipment Grounding Conductors to Boxes. Where more than one equipment grounding conductor of a branch circuit enters a box, all such conductors shall be spliced or joined with splicing devices identified For the use and the arrangement shall be such that the disconnection or removal of a receptacle, f i x t u r e , or other device fed from the box will not interfere with or interrupt the grounding continuity. SUBSTANTIATION: The statement, "spliced or joined with splicing devices identified for the use," is more specific than, "good electrical contact with each other." PANEL ACTION: Accept in Principle. PANEL COMMENT: Same as Proposal 5-172. ~ A C T I O N : UnanimouslyAffirmative. Log # 541 5- 177 - (280-22): Reject SUBMITFER: J. K. Daugherty, Flint, MI RECOMMENDATION: Add a new Ist sentence: "Surge arresters shall be installed on the load side of services." SUBSTANTIATION: Although the t i t l e of Section 280-22 clearly states that surge arresters are to be installed on the load side of services, the requirement does not. This proposal will coordinate the t i t l e with the requirement. PANEL ACTION: Reject. PANEL COMMENT: I t is not the intent to require surge arresters. VOTE ON PANELACTION: Unanimously Affirmative. COMMENTON VOTE: NEISWENDER: Although my vote is affirmative, i t is f e l t that a comment is warranted on the mandatory requirement of surge arresters in residential areas. In residential occupancies surge voltages generally are experienced from two major sources: (I) external surges; and (2) the switching of loads within the residence. The external surges are mainly caused by lightning which is a function of local geographical and meteorlogical conditions. An IEEE Transactions Paper, August 1970, entitled "Surge Voltage in Residential and Industrial Power Circuits" states that a significant number of surges above 2000 volts occur periodically in residential power lines. Solid insulation devices such as motors and transformers usually will withstand such surges. However, devices containing semiconductors may be much more vulnerable and these devices are becoming much more con~non in the average household. The switching of refrigerators, food mixers, oil burners, fluorescent lamps, etc. has been found to produce internal surges within a home which are not transmitted to other homes on the same service. The values of these switching surges has been found to range from 300 to 2500 volts. The installation of a surge arrester on the main panel or service would not protect the internal wiring or ~ndividual branch circuits from the effects of these transient voltages. Since i t has been documented that these types of surge voltages can exist in a residential occupancy, we feel an effort should be made to study this problem in more detail with one possible goal of: (1) providing protection from external surges; and (2) making the user and manufacturer aware of the possible damaging effects to ,solid state technology equipment within the average home. We realize that several steps of protection are required: (1) at the service for external surges; and (2) less expensive and closer matched surge arresters at the individual devices requiring them. Technology is fast placing the microprocessor and like equipment in the home. We need to look closer at the area of providing property protection for the non-technically oriented home user of these new devices. Log # 1606 5- 172 - (250-114): Accept SUBMITTER: Andre R. Cartal, Middle Department Inspection Agency, RECOMMENDATION: Revise to read as follows: Where more than one equipment grounding conductor enters a box all such conductors shall be spliced or joined within the box with splicihg devices suitable for the use. Connections depending on solder shall not be used and the arrangement shall be such that the disconnection or the removal of a receptacle, f i x t u r e , or other device fed from the box will not interfere with or interrupt the grounding continuity. SUBSTANTIATION: Section 250-114 now requires that branch circuit grounding conductors shall be in "good electrical contact" with each other - I know of no definition of "good electrical contact." Is a pigtail splice sufficient? What about aluminum branch circuit grounding conductors? The expanded recognition of NM cable in Section 517-11 Exception No. 2 and Section 680-25(d) mandates more specific wording to insure continuity of all equipment grounding conductors. ~ANEL ACTION: Accept. VOTE ON PANELACTION: UnanimouslyAffirmative. Log # 540 5- 173 - (250-115(d)): Reject SUBMITTER: J. K. Daugherty, Flint, MI ~ATION:' Add: "such as thermite (cad) welding." to the end of the sentence. SUBSTANTIATION: Thermite (cad) welding has generally been accepted as an equally substantial approved means. PANEL ACTION: Reject. PANEL COMMENT: Although Panel agrees that this is one acceptable method, listing i t would only put undue emphasis on that method. VOTE ON PANELACTION: Unanimously Affirmative. Log # 1754 5- 174 - (250-117): Reject SUBMITTER: Charles "Mike" Holt, Concepts in Electricity Inc. RECOMMENDATION: 250-117. Delete 250-117(a) and (b) replace i t with: 250-117. Ground clamps and other f i t t i n g s shall be protected from ordinary physical damage by being enclosed in metal, wood, or equivalent protective covering. 104 SUBSTANTIATION: Where connections are made to exposed portions of electrodes which are largely encased, driven, or buried, such connections must be accessible. The present wording of the exception leads to possible misinterpretation that electrodes largely concrete-encased, or buried, need not have the exposed connections to them accessible. The suggested revision will not allow such misinterpretation of the intent of the requirement. PANEL ACTION: Accept. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 539 5- 170 - (250-113): Reject SUBMITTER: J. K. Daugherty, Flint, MI ~ATION: Revise the 2nd sentence to: "Securement mechanically, connection devices, or f i t t i n g s that depend on solder for electrical continuity shall not be used." SUBSTANTIATION: Grounding connections could be subjected to ground faults and should not depend on solder for electrical continuity. PANEL ACTION: Reject. PANEL COMMENT: Present wording is much clearer than the proposal: VOTE ON PANELACTION: UnanimouslyAffirmative. SUBSTANTIATION: 250-117(a) and (b) are t o t a l l y confusing in that 250-117(a) states where physical damage is present, i t can be protected by installations where they are not likely to be damaged. EDITORIALCHANGE. PANEL ACTION: Reject. PANEL COMMENT: Does not allow for use of ground clamps approved for general use without protection. VOTE ON PANELACTION: UnanimouslyAffirmative. ARTICLE 280 -- LIGHTNING ARRESTERS Log # 1930 5- 175 - (280-4(b)): Accept SUBMITTER: Charles M. Lutz, Underwriters Laboratories Inc. I ~ATION: Fine Print note - change "Lightning" to "Surge." "C62.2-1969" to "C62.2-1981," SUBSTANTIATION: Change in t i t l e of ANSI C62.2-1981. PANEL ACTION: Accept. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 1576 5- 176 - (280-4(b),FPN): Accept SUBMI1-TER: David W. Jackson, IEEE, Power Engineering Society, Surge Protective Devices Committee RECOMMENDATION: In the Fine Print Note following Section 280-4(b), correct the reference to ANSI C62.2 to read as follows: "Guide for the Application of Valve-Type Surge Arresters for Alternating-Current Systems (ANSI C62.2-1981)." SUBSTANTIATION: C62.2-1981 is the#pproved national standard guide for application of surge arrdsters. The deprecated term "lightning arrester" in the t i t l e has been replaced by the recommended term "surge arrester." PANEL ACTION: Accept. PANEL COMMENT: See Proposal 5-175. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 835 5- 171 - (250-114): Accept in Principle SUBMITTER: Walter A. Upson, Chocorua, NH RECOMMENDATION: Rewrite a portion of the f i r s t sentence. 250-114. Continuity and Attachment of Branch-Circuit Equipment Grounding Conductors to Boxes. Where more than one equipment grounding conductor of a branch circuit enters a box, all such conductors shall be spliced or joined with splicing devices identified For the use and the arrangement shall be such that the disconnection or removal of a receptacle, f i x t u r e , or other device fed from the box will not interfere with or interrupt the grounding continuity. SUBSTANTIATION: The statement, "spliced or joined with splicing devices identified for the use," is more specific than, "good electrical contact with each other." PANEL ACTION: Accept in Principle. PANEL COMMENT: Same as Proposal 5-172. ~ A C T I O N : UnanimouslyAffirmative. Log # 541 5- 177 - (280-22): Reject SUBMITFER: J. K. Daugherty, Flint, MI RECOMMENDATION: Add a new Ist sentence: "Surge arresters shall be installed on the load side of services." SUBSTANTIATION: Although the t i t l e of Section 280-22 clearly states that surge arresters are to be installed on the load side of services, the requirement does not. This proposal will coordinate the t i t l e with the requirement. PANEL ACTION: Reject. PANEL COMMENT: I t is not the intent to require surge arresters. VOTE ON PANELACTION: Unanimously Affirmative. COMMENTON VOTE: NEISWENDER: Although my vote is affirmative, i t is f e l t that a comment is warranted on the mandatory requirement of surge arresters in residential areas. In residential occupancies surge voltages generally are experienced from two major sources: (I) external surges; and (2) the switching of loads within the residence. The external surges are mainly caused by lightning which is a function of local geographical and meteorlogical conditions. An IEEE Transactions Paper, August 1970, entitled "Surge Voltage in Residential and Industrial Power Circuits" states that a significant number of surges above 2000 volts occur periodically in residential power lines. Solid insulation devices such as motors and transformers usually will withstand such surges. However, devices containing semiconductors may be much more vulnerable and these devices are becoming much more con~non in the average household. The switching of refrigerators, food mixers, oil burners, fluorescent lamps, etc. has been found to produce internal surges within a home which are not transmitted to other homes on the same service. The values of these switching surges has been found to range from 300 to 2500 volts. The installation of a surge arrester on the main panel or service would not protect the internal wiring or ~ndividual branch circuits from the effects of these transient voltages. Since i t has been documented that these types of surge voltages can exist in a residential occupancy, we feel an effort should be made to study this problem in more detail with one possible goal of: (1) providing protection from external surges; and (2) making the user and manufacturer aware of the possible damaging effects to ,solid state technology equipment within the average home. We realize that several steps of protection are required: (1) at the service for external surges; and (2) less expensive and closer matched surge arresters at the individual devices requiring them. Technology is fast placing the microprocessor and like equipment in the home. We need to look closer at the area of providing property protection for the non-technically oriented home user of these new devices. Log # 1606 5- 172 - (250-114): Accept SUBMITTER: Andre R. Cartal, Middle Department Inspection Agency, RECOMMENDATION: Revise to read as follows: Where more than one equipment grounding conductor enters a box all such conductors shall be spliced or joined within the box with splicihg devices suitable for the use. Connections depending on solder shall not be used and the arrangement shall be such that the disconnection or the removal of a receptacle, f i x t u r e , or other device fed from the box will not interfere with or interrupt the grounding continuity. SUBSTANTIATION: Section 250-114 now requires that branch circuit grounding conductors shall be in "good electrical contact" with each other - I know of no definition of "good electrical contact." Is a pigtail splice sufficient? What about aluminum branch circuit grounding conductors? The expanded recognition of NM cable in Section 517-11 Exception No. 2 and Section 680-25(d) mandates more specific wording to insure continuity of all equipment grounding conductors. ~ANEL ACTION: Accept. VOTE ON PANELACTION: UnanimouslyAffirmative. Log # 540 5- 173 - (250-115(d)): Reject SUBMITTER: J. K. Daugherty, Flint, MI ~ATION:' Add: "such as thermite (cad) welding." to the end of the sentence. SUBSTANTIATION: Thermite (cad) welding has generally been accepted as an equally substantial approved means. PANEL ACTION: Reject. PANEL COMMENT: Although Panel agrees that this is one acceptable method, listing i t would only put undue emphasis on that method. VOTE ON PANELACTION: Unanimously Affirmative. Log # 1754 5- 174 - (250-117): Reject SUBMITTER: Charles "Mike" Holt, Concepts in Electricity Inc. RECOMMENDATION: 250-117. Delete 250-117(a) and (b) replace i t with: 250-117. Ground clamps and other f i t t i n g s shall be protected from ordinary physical damage by being enclosed in metal, wood, or equivalent protective covering. 104 SUBSTANTIATION: This Exception will allow the Code to cover optical fiber cables as provided for in proposed Article 770. PANEL ACTION: Accept in Principle. Change the number "4" to the number "3." PANEL COMMENT: The renumbering is made in order to follow the proper numerical sequence for article numbers. See Action on Proposal 3-3. VOTE ON PANEL ACTION: UnanimouslyAffirmative. ARTICLE 300 -- WIRING METHODS Log # 2056 3- I - (Articles 300, 305): Reject • Secretary's Note: The Correlating Committee feels that this proposal is editorial in nature and that i t is unnecessary to repeat information already in the Code. SUBMITTER: Ivan P. Nordstrand, Consumers Power Company RECOMMENDATION: Propose each article have the Panel designation thus: Article 90 - Introduction (Panel No. i) Article 100 - Definitions (Panel No. 1) Article 110 - Requirements for Electric Installations (Panel No. 1) Article 200 - Use and Identification of Grounded Conductors (Panel No. 5) Article 210 - Branch Circuits (Panel No. 2) Etc... SUBSTANTIATION: The present format of the published Code book makes i t d i f f i c u l t and time consuming to determine the appropriate Panel responsible for the article in which a problem is developing. The addition of one line in parentheses under the article number giving the Panel designation will quickly provide the proper source. PANEL ACTION: Reject. PANEL COMMENT: Previously covered in the Code and i t would be redundant to include in Article 300 and Article 305. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 21 3- 6 - (300-1(c), Exception (New)): Accept in Principle Secretary's Note: The Correlating Committee advises CI~° 3 that article scope statements are the responsibility of the Correlating Committee and that the Correlating Committee accepts the Panel Action. I t was the action of the Correlating Committee that further consideration be given to the comments expressed in the negative voting. SUBMITTER: Dan Leaf, Westlake Village, CA RECOMMENDATION: Add Exception as follows: Exception: Where otherwise permitted by Article 250. SUBSTANTIATION: Appears not to consider single conductors permitted by Article 250 for grounding and bonding conductors. Single conductors of types specified in Table 310-13 are permitted in Article 250 as bonding and grounding conductors, and in some installations are not installed according to Chapter 3 wiring methods, e.g., Sections 250-92 and 250-97. PANEL ACTION: Accept in Principle. Revise to read: "Where otherwise as permitted by Article 250." PANEL COMMENT: Editorial c l a r i f i c a t i o n . VOTE ON PANEL ACTION: AFFIRMATIVE: 6 NEGATIVE: Lawry. EXPLANATION OF VOTE: LAWRY: The revision noted in the Panel Action is not correct and as agreed upon by CMP 3. I t should have been "as permitted in Article 250." Log # 1631 3- 2 - (Articles 300, 305): Reject SUBMII'TER: Allen KnicKrehm, Los Angeles, C/~ ~ATION: Delete the word "approved" when used to mean the use of alternate method(s) or materials. SUBSTANTIATION: The NEC is incorporated in most construction contract documents by reference. Therefore, the authority having jurisdiction - the owner or the owner's representative, will not be the third party qualified person contemplated by the Code-Making Panel. Section 90-4 covers the case for governmental bodies exercising legal jurisdiction. PANEL ACTION: Reject. PANEL COMIVENT: Does not comply with Section i0-10(b) of the NFPA Regulations relative to submittal of proposal and his substantiation is contrary to NFPA definitions. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 1259 3- 7 - (300-I(c), FPN-(New)): Reject Secretary's Note: I t was the action of the Correlating Committee that further consideration be given to the comments expressed in the negative voting. The Correlating Committee advises CMP 3 that article scope statements are the responsibility of the Correlating Committee. SUBMITTER: IAEI ~ T I O N : Add second paragraph to read: All conductors of the same circuit including the grounding conductor where used shall be contained within the same raceway, trench, cable, or cord. Add fine print note to read: See Sections 250-79(e), 300-5(i), 339-3(a)(2), 250-57(b), and 300-20(a). SUBSTANTIATION: This would clearly require all conductors and grounding conductors to be grouped without researching several articles and making the mistake of relying on one section such as where this requirement is specified in Sections 300-5(i), 339-3(a)(2), 250-57(b), 300-20(a) and 250-79(e). I t presently misleads some to believe that this is only required when involved with underground installation. PANEL ACTION: Reject. PANEL COUNT: The uses are already spelled out in other sections of the Code. This would be redundant and unnecessary. VOTE ON PANEL ACTION: AFFIRMATIVE: 5 NEGATIVE: Lawry, Wood. EXPLAN/~TION OF VOTE: LAWRY: The substantiation of the submitter is valid. I t is proper for Article 300 to include general requirements that may be found elsewhere in Code. I would recommend that CMP 3 accept the proposal in principle, but rather than adding a FPN, add an exception stating "Exception: As specifically permitted elsewhere in this Code." WOOD: This change would help to solve a f i e l d Jroblem. I agree with the submitter's substantiation. Log # 1136 3- 3 - (300-I(a), Exception No. 3-(New)): Accept Secretary's Note: The Correlating Committee advises CMP 3 that article scope statements are the responsibility of the Correlating Committee and that the Correlating Committee accepts the Panel Action. SUBMITTER: L. H. Sessler, Telephone Group RECOMMENDATION: Renumber the existing Exception No. 3 (Article UUU~ to ~xception No. 4. Add new Exception No. 3. Only those sections referenced in Article 770 shall apply to optical fiber cables. SUBSTANTIATION: This proposal will allow the Code to cover optical fiber cables as provided for in proposed Article 770. PANEL ACTION: Accept. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 1434 3- 4 - (300-I(a), Exception No. 5-(New)): Accept Secretary's Note: The Correlating Committee advises CMP 3 that article scope statements are the responsibility of the Correlating Committee and that the Correlating Committee accepts the Panel Action. SUBMII-rER: L. H. Sessler, Telephone Group RECOI~WMENDATION: Add new Exception No. 5. Only those sections referenced in Article 820 shall apply to Community Antenna Television and Radio Distribution Systems. SUBSTANTIATION: Corrects an apparent omission by proposing an exception for Article 820. PANEL ACTION: Accept. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 1826 3- 8 - (300-3(a)): Reject SUBMITTER: Paul E. Phelan, Trade Education, Inc. and New Hampshire Electrical Contractors, Inc. RECOMMENDATION: Change last sentence to read: "where all conductors are insulated for the maximum " c i r c u i t " voltage of any conductor." SUBSTANTIATION: Clarification of whether we are dealing with circuit voltage or voltage "rating" of conductor insulation. PANEL ACTION: Reject. PANEL CO~IMENT: The Panel believes that the present wording is adequate. The intent is that this section applies to the insulation rating and not the operating voltage. VOTE ON PANEL ACTION: AFFIRMATIVE: 6 NEGATIVE: Lawry. Log # 899 3- 5 - (300-1(a), Exception No. 4-(New)): Accept in Principle Secretary's Note: The Correlating Committee advises CMP 3 that article scope statements are the responsibility of the Correlating Committee and that the Correlating Committee accepts the Panel Action. SUBMII-FER: Ad Hoc Subcommittee on Fiber Optics RECOMMENDATION: Add Exception No. 4. Only those sections referenced in Article 770 shall apply to optical fiber cables. 105 ¢ ~J. Log # 834 3- 12 - (300-4(a)(1)): Accept in Principle Secretary's Note: I t was the action of the Correlating Committee to direct the Panel to c l a r i f y the Panel Action in regards to changes in Code text. SUBMITTER: Walter A. Upson, Chocorua, NH RECOMMENDATION: Rewrite 300-4(a)(1) {a} Cables Through Wood Members. (1) Bored Holes. In both exposed and concealed locations, where a cable or raceway-type wiring method is installed through bored holes in joists, rafters, or wood members, holes shall be bored so that the edge of the hole is not less than 1 1/4 inches (31.8 mm) from the nearest edge of the wood member. Where this distance cannot be maintained the cable or raceway shall be protected from penetration by screws or nails by a steel plate or bushing, at least 1/16 inch (1.59 mm) thick, and of appropriate length and width installed to cover the area of the wiring. SUBSTANTIATION: The rewording of this paragraph would clarify the application of Section 300L4(a)(1) to apply to all wood members, as in solid wood structures, ndt just to structural members. PANEL ACTION: Accept in Principle. Revise heading to read: "Cables and Raceways Through Wood Members." Add a new exception to Section 300-4(a)(1): "Exception: Racewaysas covered in Articles 345, 346, and 348." PANEL COMMENT: Metal raceways covered by the proposal exception should not be effected. VOTE ON PANEL ACTION: UnanimouslyAffirmative. EXPLANATION OF VOTE: LAWRY: Although I agree with the intent stated in the Panel Comment, I s t i l l believe that the present Code language is not clear. The specific wording in the present Code s t i l l leaves the question of whether we are referring to insulation rating or operating voltage. To c l a r i f y this the last portion of (a) could be revised to read "where all conductors are insulated for the maximum insulation voltage rating of any conductor..." Log # 1799 3- 9 - (300-3(a), Exceptioh-(New)): Reject SUBMITTER: G. V. Cox, Chemical Manufacturers Association ~DATION: Add exception to read: "Exception: Excitation, control, relay, and ammeter conductors, i f insulated for the voltage applied to the conductors and where used in connection with any individual motor or starter, shall be permitted to occupy the same enclosure as the motor circuit conductors." SUBSTANTIATION: Exception No. 3 to Section 300-3(b) allows a 30D-volt or 150-volt insulated wire to be used in a similar application using motors of greater than 600 volts. I f allowable f o r motors over 600 volts, similar allowance should be made for motors of 600 volts or less. PANEL ACTION: Reject. PANEL COMMENT: This proposal would be in conflict with Section 725-15. VOTE ON PANEL ACTION: AFFIRMATIVE: 6 NEGATIVE: Mottern. EXPLANATION OF VOTE: MOTTERN: I t is my understanding that Article 300 establishes the general wiring methods of the Code and Section 725-15 amends these general methods as required by Class 1 circuits. I really cannot see a conflict. Consider the following specific examples: 1. Section 300-3(b), Exception No. 3 permits 120-volt control conductors with insulation rated at 300 volts to be installed in the same motor starter with the associated 13.8 kV power conductors. 2. Section 725-38(a)(2), Exception No. 2 permits Class 2 and 3 120-volt control conductors with insulation rated at 300 volts to be installed in the,same motor starter with the associated 460-volt power conductors. This was affirmed in the July, 1980, Fire News as listed Item 70-78-6. I see no reason that excitation, relay, and ammeter conductors, i f insulated for the voltage applied, could not safely be installed in the same motor starter as the associated 460-volt power-conductors. Log # 51 3- 13 - (300-4(a)(2)): Accept in Principle SUBMITTER: Dan Leaf, Westlake Village, CA ]TE~-~-E'I~-DATION: Insert in paragraph (a)(2) the words "or raceways" after the word "cable," in the f i r s t sentence. SUBSTANTIATION: Does not address installation of raceway type wiring methods installed in notches. Installation of raceways in notches in wood members has been a somewhat common installation for many years and generally permitted by inspection authorities. This proposal would c l a r i f y and specifically permit this type installation. PANEL ACTION: Accept in Principle. Add a new exception to Section 300-4(a)(2) to read: "Exception: Raceways as covered in Articles 345, 346, and 348." PANEL COUNT: The Panel accepts the proposal in its entirety and • in addition the Panel has added the Exception. Metal raceways covered by the Exception should not be effected. VOTE ON PANELACTION: Unanimously Affirmative. Log # 1777 3- 14 - (300-4(b)): Reject SUBMITTER: Louis Miraglia, Paul Revere Chapter IAEI ~DATION: Delete (b) and the exception and replace with: (b) Cables Through Metal Framing Members. In both exposed and concealed locations, only Type MI cable, Type MC cable, and Type AC cable shall be used for wiring in systems installed in factory or f i e l d , punched, cut or drilled slots or holes in metal framing members. Other type cables and conductors shall be installed in raceways. SUBSTANTIATION: Other type cables, such as nonmetallic-sheathed cables, are usually pulled through holes and slots and routed to outlet boxes; then protective bushings are installed, however, too late, as damage to the cables has already taken place. PANEL ACTION: Reject. PANEL COMMENT: The Panel believes that the Code presently. requires protection of cables and that this is an enforcement roblem. OTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 914 3- 10 - (300-3(a), Exception-(New)): Accept SUBMITTER: Ad Hoc Subcommittee on Solar Photovoltaics ~DATION: Add Exception to Section 300-3(a), as follows: "Exception: For solar photovoltaic systems in accordance with Section 6go-4(b)." SUBSTANTIATION: For correlation with proposed Section 690-4(b). See substantiation for proposed Section 690-4(b). PANEL ACTION: Accept. VOTE ON PANELACTION: Unanimously Affirmative. Log # 1944 3- 11 - (300-3(b)): Reject SUBMITTER: C. E. Muhleman, Marion, IN ITE']L'OI~E'IT(~TION: Conductors energized over 600 volts, nominal, shall not occupy the same equipment wiring enclosure, cable tray, raceway or duct with conductors of 600 volts, nominal, or less. SUBSTANTIATION: The present wording without "energized" could be construed to mean that a cable having 35 kV insulation rating could not be used to wire a 480 volt c i r c u i t . Whereas this is improbable, I have used 5 kV nonshielded cable for a 230 volt feeder when the proper size 600 volt cable was not available. PANEL ACTION: Reject. PANEL COMMENT: The Code presently permits the installation cited in the preposer's substantiation. VOTE ON PANEL ACTION: AFFIRMATIVE: 6 NEGATIVE: Lawry. EXPLANATION OF VOTE: LAWRY: Although the use of word "nominal" in Section 300-3(b) suggests operating voltage rather than insulation rating (see definition of voltage, nominal), i t appears that the proposal would c l a r i f y (b). The Panel Comment appears to be in conflict with the Panel Comment for Proposal 3-8. I f the intent of Section 300-3(a) is that i t applies to insulation rating, then a 35 kV insulation rating could not be used for a 480-volt circuit in the same raceway with conductors having 600-volt insulation rating. ~ Log # 1790 3- 15 - (300-4(c)-(New)): Reject SUBMITTER: Leo F. Martin, Paul Revere Chapter IAEI RECOMMENDATION: Add new (c) as follows: ,(c) Cables Through Spaces Behind Panels Designed to Allow Access. Cables, or raceway-type wiring methods, installed behind panels designed to allow access shall be supported according to their applicable articles. SUBSTANTIATION: Manytimes, for a myriad of reasons, cables and other wiring methods are fished across hung-ceilings and lay on these grids with l i t t l e or no support and therefore hinder the accessibility through l i f t - o u t panels. PANEL ACTION: Reject. PANEL COMMENT: The Panel feels that the requirements are already covered in the respective article and the proposal is redundant. VOTE ON PANELACTION: AFFIRMATIVE: 6 NEGATIVE: Lawry. EXPLANATION OF VOTE: LAWRY: The problem stated in the submitter's substantiation is very common in the real world. Including this proposed new section in Article 300 would be of immense help in promoting and enforcing safe wiring methods. This is a general problem deserving Article 300 consideration and we should not hide behind the fact that something may be covered elsewhere. 106 Log # 1261 3- 16 - (300-4(c)-(New)): Reject SUBMITTER: IAEI ~ATION: Add a new subsection 300-4(c) to read as follows: Conductors shall be protected from damage by the design of the cabinet, pull box, junction box, auxiliary gutter, f i t t i n g or enclosure, by a bushing identified for the use. Ungrounded conductors of No. 4 or larger shall be protected by substantial insulated bushing providing a smoothly rounded insulating surface unless the conductors are separated from the raceway f i t t i n g by a substantial insulating material securely fastened in place. Conduit bushings constructed wholly of insulating material shall not be used to secure a raceway. The insulating bushing or insulating material shall have a temperature rating not less than the insulation temperature rating of the installed conductors. SUBSTANTIATION: Protection of conductors from damage and abrasion in the electrical system is of primary concern and as such, the statement should be moved from Section 373-6(c) to Section 300-4(c) in order to apply generally. Since electrical and mechanical continuity of raceways is required by Sections 300-10 and 300-12, and since some raceways or f i t t i n g s can be secured without a Iocknut or with one locknut, that portion of Section 373-6(c) is f e l t unnecessary. PANEL ACTION: Reject. PANEL COMMENT: The f i r s t sentence is unclear as to what the proposer wants to achieve and i t is redundant to the f i r s t sentence of Section 300-4. Prohibiting bushings wholly constructed of insulating material may not be desirable. The Panel feels that the Code adequately covers the protection of conductors in Section Nos. 373-3, 370-7, 370-22, 370-52(b), 374-9(c) and 346-8. Submitter has not identified specific problems in the Substantiation. VOTE ON PANEL ACTION: AFFIRMATIVE: 6 NEGATIVE: Lawry. EXPLANATION OF VOTE: LAWRY: Although there are some problems with the proposal as noted in the f i r s t paragraph of the Panel Comment, I believe that the protection of conductors is a subject that applies generally and should be addressed in Article 300. Surely, i t is not necessary to identify specific problems when considering something as basic as conductor protection. SUBSTANTIATION: By applying Exception Nos. I and 2 to conduits tor underground installation with a 2-inch concrete pad is placed for physical protection the cover depth can be reduced 6 inches, and by Table 300-5 conduits only need to be buried 6 inches. I f a concrete slab is applied the conduit could be placed on top of the surface. PANEL ACTION: Reject. PANEL COMMENT: The submitter's comment is not clear as to what he intends. The Panel feels that the concrete slab is sufficient. VOTE ON PANEL ACTION: UnanimouslyAffirmative. I Log # 1371 3- 19 - (300-5, Exception No. 4): Accept SUBMITTER: M. H. Lounsbury, Eastern Section IAEI RELATION: Delete Exception No. 4 of Section 300-5. SUBSTANTIATION: When this exception was added to the NEC Article 680 did not allow the use of direct burial cables. At the present time we feel that a depth of 24 inches is an important factor to be considered by the NEC. PANEL ACTION: Accept. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . Log # 445 3- 20 - (300-5, Exception No. 4): Accept SUBMITTER: Southwestern Section IAE[ RECOM~NDATION: Delete: Exception No. 4. SUBSTANTIATION: Field experience has proven with only 12 inches of cover, many cables have been dug i n t o . Most a l l of t h i s wiring is in lawn and flower or shrub areas where l a t e r planting occurring requires holes more than 12 inches in depth. Cables have been cut, then improperly spliced, r e s u l t i n g in voltage leaks with current high enough f o r shock or electrocution. Very seldom is inspection requested on these splices and most times they are done by owners with l i t t l e or no knowledge of proper splicing methods. In Section 210-8; f o r ground-fault c i r c u i t protection set at 5 plus or minus one milliampere, a 30 ampere-circuit can d e l i v e r much higher shock current. PANEL ACTION: Accept. VOTE ON PANEL ACTION: Unanimously Affirmative~ Log # 353 3- 17 - (300-5(a), Exception No. 1): Reject SUBMITTER: Paul Schat, Sheldon, IA RECOV~MENDATION: The minimum cover requirements shall be permitted to be reduced by 6 inches (152 mm) f o r installations where a 2-inch (50.8 mm) thick concrete pad or equivalent in physical protection is placed in the trench over the underground installation. This exception shall not apply to rigid metal conduit or intermediate metal conduit. SUBSTANTIATION: I believe these words should be added to Exception No. I because, i f the minimum cover requirements are allowed to be reduced 6 inches with adequate physical protection, rigid metal conduit and intermediate metal conduit could be installed at grade level, and being exposed to physical damage. PANEL ACTION: Reject. PANEL COMMENT: The Panel believes that the conduit is not exposed to physica| damage. The 2-inch thick concrete pad or equivalent is s t i l l required. VOTE ON PANEL ACTION: AFFIRMATIVE: 6 NEGATIVE: Lawry. EXPLANATION OF VOTE: LAWRY: I t is unlikely that Exception No. i would ever be applied to rigid metal or intermediate metal conduit because i f a 2-inch thick concrete pad was applied and the burial depth reduced 6 inches, we would end up with the conduit and 2-inch pad both on top of the ground. Depending upon location and use of the area, I do not believe that 2 inches of concrete necessarily provides sufficient protection. This is supported by Exception No. 2 which requires a 4-inch concrete pad in order to not apply the minimum burial depth. In fact, when considering rigid metal or intermediate conduit, I believe Exception Nos. 1 and 2 are in conflict. I would recommend either accepting this proposal or restricting i t s application to direct burial cables. Log # 1291 3- 21 - (300-5, Exception No. 4): Accept SUBMITTER: IAEI ~ T I O N : Delete Exception No. 4 of Section 300-5. SUBSTANTIATION: When t h i s exception was added to the NEC, A r t i c l e 680 did not allow the use of d i r e c t burial cables. At the present time, we feel that a depth of 24 inches is an important f a c t o r to be considered by the NEC. Field experience has proven with only 12 inches of cover, many cables have been dug i n t o . Most all of t h i s wiring is in lawn and flower or shrub areas where l a t e r planting occurring requires holes more than 12 inches in depth. Cables have been cut, then improperly spliced, r e s u l t i n g in voltage leaks with current high enough f o r shock or e l e c t r o c u t i o n . Very seldom is inspection requested on these splices and most times .they are done by owners with l i t t l e or no knowledge of proper spllclng methods. In 210-8, f o r ground f a u l t c i r c u i t protection set at 5 plus or minus one milliamperes, a 30 ampere c i r c u i t can d e l i v e r much higher shock current. PANEL ACTION: Accept. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . Log # 355 3- 22 - (300-5, Exception No. 4): Reject SUBMITTER: Jon Kulp, Sheldon, IA RECO~ATION: Increase the cover requirements f o r unprotected cable to 18 inches. Conductors run in conduit or other approved means may s t i l l be buried at 12 inches. SUBSTANTIATION: Although the branch c i r c u i t is limited to 300 v o l t s and 30 amperes f o r t h i s a p p l i c a t i o n , I do not feel this provides adequate protection to personnel when the conductors are only 12 inches below grade. By increasing>the cover to 18 inches this w i l l prevent damage to the cable and possible shock hazard by homeowners or contractors not aware of the buried cable and digging in the v i c i n i t y . PANEL ACTION: RejeCt. PANEL COMM~ZNT: See Panel Action on Proposals 3-19, 3-20 and 3-21. VOTE ON PANEL ACTION: Unanimously A f f i r m a t i v e . Log # 350 3- 18 - (300-5(a), Exception No. 2): Reject SUBMI~ER: J e f f Nielsen, Sheldon, IA RECO~ENDATION: The minimum cover requirements in Exception No. I shall not apply to any conduits or other raceways buried underground. Conduits or other raceways located under a b u i l d i n g or extending beyond the building a concrete slab not less than 4 inches (102 mm) in thickness and extending not less than 6 inches (152 mm) beyond the underground i n s t a l l a t i o n . • Log # 1464 3- 23 - (300-5(b)): Accept in P r i n c i p l e SUBMITTER: William P. Hogan, Chicago, IL ~DATION: Amend Section 300-5(b) so as to read as follows: "(b) Grounding. All underground i n s t a l l a t i o n s shall be grounded and bonded as is required and prescribed in A r t i c l e 250 of t h i s Code." 107 SUBSTANTIATION: Section 250-51, which is presently referenced in ~ectlon ~ - b ( b ) , contains no specific requirements for underground metal-encased wiring systems. Article 250 contains all the requirements for grounding and bonding wiring systems of all types under all circumstances. The proposed wording would direct the users of the Code to the place where they can find the information that they require. PANEL ACTION: Accept in Principle. Change "as is required and prescribed in" to "in accordance with." PANEL COMMENT: Pane] feels the revised wording is better Code language. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 1195 3- 26 - (300-5(d)): Reject SUBMITTER: Olaf G. Ferm, Ferm's Fast Finder Index RECOMMENI)ATION: Changethe f i r s t sentence to read: Conductors emerging from the ground shall be protected by enclosures or raceways extending from a minimum of 18 inches below grade to a point 8 feet or more above finished grade. SUBSTANTIATION: The present wording does not give a below-grade measurement and appears to lock you in at exactly 8 feet above grade. By not protecting direct burial conductors at least 18 inches below grade where they emerge from the earth, offers a potential hazard in many cases. The Code does make reference to 18 inches below finished grade for mechanical protection of, conductors in Section 551-51(b). This same concept should apply to all underground installations, and be covered in wiring methods and materials Section 300-5(d) underground installations. PANEL ACTION: Reject. PANEL COF%MENT: Table 300-5 already requires mechanical ~rotection to a level of 24 inches when below grade. VOTE ON PANEL ACTION: AFFIRMATIVE: 6 NEGATIVE: Lawry. EXPLANATION OF VOTE: LAWRY: The Panel Comment is questionable. In my opinlon, Table 300-5 does not clearly require mechanicaI protection to a level of 24-inches below grade. The 24-inch burial depth clearly applies to the horizontal portion of the underground run. I t is not clear that i t applies to the vertical portion where the cables leave the ground. Table 300-5 applies to minimum cover requirements. Note that cover is defined as the distance between the top surface of direct buried cables and the finished grade. What is the top surface of a vertically rising cable? I believe that the proposal to extend the mechanical protection down 18 inches is logical and would c l a r i f y the Code. Log # 1885 3- 24 - (300-5(d)): Reject SUBMII-TER: Dave Thrasher, Daverman Associates, Inc. ~ T I O N : Change 8 feet (2.44 m) to 10 feet (3.05 m). SUBSTANTIATION: The above change would then coordinate with Sections 230-49, 230-50(b), and 225-18. There are presently two conflicts: i . Overhead services must be 10 feet in the air Sections 230-24 and 225-18; underground need protection only to 8 feet 300-5(d). 2. Services underground need protection Section 300-5(d) up to 8 feet above grade. All other underground feeders require 10 feet Section 230-50(b). PANEL ACTION: Reject PANEL COMMENT: The rationale for substantiation refers to overhead services and does not appear to be a conflict. Section 225-18 applies to vertical clearances above the ground and not to protection requirements of vertical risers. VOTE ON PANEL ACTION: AFFIRMATIVE: 5 NEGATIVE: Lawry, Wood. EXPLANATION OF VOTE: LAWRY: I agree that Section 225-18 applies to vertical clearances above the ground and presents no conflict with the protection requirements of Section 300-5(d). There does appear to be a conflict, however, with Section 230-50(b) which requires service-entrance conductors consisting of individual open conductors and cables other than S.E. cables to be at least 10 feet above grade. The distance specified in Section 230-50(b) was increased from 8 feet to 10 feet in the 1978 NEC to agree with the National Electrical Safety Code. I t seems logical to also increase the distance specified in Section 300-5(d) to 10 feet. Conflicts in the Code, apparent or real, generate critic!sm of the Code process. Accepting this proposal would eliminate this source of criticism. WOOD: This appears to be a good recommendation and can only add to safety. Log # 1260 3- 27 - (300-5(d)): Accept SUBMITTER: IAEI RIE'COI;~'I~I]ATION: Rewrite last paragraph of Section 300-5(d) to read: Where the enclosure or raceway is subject to physical damage the conductors shall be installed in rigid metal conduit, intermediate metal conduit, Schedule 80 rigid nonmetallic conduit or equivalent, SUBSTANTIATION: As now written, this section is interpreted both ways, such as some require rigid metal conduit, intermediate metal conduit, Schedule 80 rigid nonmetallic conduit, or equivalent in all such installations since all conductors emerging from the ground are subject to physical damage. Others only require these types of raceways where the raceways are subject to physical damage such as in parking lots, etc. This will c l a r i f y that the last paragraph is addressing physical damage to the enclosure and raceway and not the conductors which are presently addressed in the f i r s t two paragraphs. PANEL ACTION: Accept. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 1465 3- 25 - (300-5(d)): Reject SUBMITTER: Lee Witz, Continental Electric Co. ~ g a n , Chicago, IL Fred Smith, Elgin, IL Jim Meehan, New Haven, CT Anton Ganje, North Dakota Kenny Gebert, Minneapolis, MN Bill Conrardy, The Conrardy Co. Robert P. Brooks, Chicago, IL Paul Moore, Paducah, KY Les Rinder, Chicago, IL John W. Erickson, Boltswitch, Inc. Homer M. Lefler, Chicago, IL RECOMMENDATION: AmendSection 300-5(d) by deleting therefrom the words, "8 feet" and further amend i t by inserting in lieu thereof the words, "10 feet." SUBSTANTIATION: There is an obvious contradiction between this section and Section 230-50(b) where they both could be referring to the same conductors. We don't know where the "8 feet" came from, but "10 feet" seems to be more widely accepted by other codes and standards and therefore we suggest that the contradiction be eliminated by the insertion of "10 feet." PANEL ACTION: Reject. PANEL COMMENT: The rationale for substantiation refers to overhead services and does not appear to be a conflict. Section 230-5(b) applies to vertical clearances above the ground and not to protection requirements of vertical risers. VOTE ON PANELACTION: AFFIRMATIVE: 5 NEGATIVE: Lawry, Wood. EXPLANATION OF VOTE: LAWRY: See comment for Proposal 3-24. WOOD: This appears to be a good recommendation and can only add to safety. Log # 277 3- 28 - (300-5(g)): Reject Secretary's Note: I t was the action of the Correlating Committee that this proposal be reported as "Reject" because less than two-thirds of the members eligible to vote have voted in the affirmative. SUBMITTER: W. Creighton Schwan, Hayward, CA ~TION: Replace present text with the following: Raceway Seals. Conduits or raceways shall be sealed or plugged at either or both ends to minimize the entrance of moisture or ases. UBSTANTIATION: The Code concern for underground gas entering a building through conduit goes back at least 60 years, but disappeared (for 600 V or less) in the 1975 Code, as a result of the recommendations of the Technical Subcommittee on Underground Installations. (Gas is s t i l l mentioned in Section 710-3(b)(4) for high-voltage installations). With increasing quantities of waste materials being deposited as land f i l l (due to environmental restrictions on burning) and the scarcity of land leading to increasing use of f i l l e d land as building sites, methane gas produced by decomposing material under buildings isgoing to find its way into these buildings. The NATIONAL ELECTRICAL CODE should require that the entry not be aided by electrical raceways. There are of course other possible sources of gas underground, especially in urban areas, and the long-standing Code concern for sealing conduits against the entrance of such gases should be reinstated. • PANEL ACTION: Accept. VOTE ON PANEL ACTION: AFFIRMATIVE: 4 NEGATIVE: Adelman, Mottern, Whittington. EXPLANATION OF VOTE: ADELMAN: The proposal, as stated, would only minimize the entrance of moisture, or gases, into conduits or raceways. This would not prevent the entrance of gases, or moisture, into the system completely. As proposed, this change would be no improvement over the present text of Section 300-5(g). ~ 108 Log # 1616 3- 31 - (300-11): Reject SUBMITTER: Melvin K. Sanders, Ankeny, IA RECOMMENDATION: Add new second paragraph: No other equipment shall be permitted to be supported by raceways. SUBSTANTIATION: Manytimes telephone and communications cables are secured to electric raceway and are not protected from sharp or raw edges of pipe ends and building steel. Somemajor installations have the raceway completely encircled with telephone cables, reducing the heat dissipation and affecting the load current carrying capability of the electric conductors. In time of f i r e involvement, the extra heat generated from the burning or melting cable jackets intensify the damage to the raceway enclosed conductors. I recently helped investigate a fire in an equipment room of a high rise office buildlng where the f i r e was of non-electrical origin. The 3-1/2 inch rigid aluminum conduits passing through and into this area were exposed to the f i r e heat. One raceway was surrounded by 15 or more large multiconductor telephone cables strapped to i t , with the other raceways clear of cables. The electric conductors within the raceway encircled by the telephone conductors wore checked by a megger and found to have a poor insulation reading. Upon renw)val of these conductors, i t was found the insulation had been overheated and distorted with the conductors showing through the insulation. The other raceway not so encircled by telephone cables were also checked and found to be free from heat degradation. In 1981 NEC Section 384-2 requires space or areas free from foreign systems and i t should be that our electrical raceway also be free from being a support for other systems or objects. PANEL ACTION: Reject. PANEL COMMENT: Other sections of the Code such as Sections 370-13 and 410-16(f) presently permit other equipment to be supported by raceways. VOTE ON PANEL ACTION: AFFIRMATIVE: 5 NEGATIVE: Lawry, Wood. EXPLANATION OF VOTE: LAWRY: I agree with the intent of the submitter to prohibit equipment not related to the raceway from being supported by i t . Both sections referred to in the Panel Comment deal with equipment that is associated with the raceway system. Furthermore, Section 370-13 only permits certain threaded boxes to be supported by the raceway. The equipment specifically permitted to be supported by a raceway is very limited. Possibly the proposal could be reworded as follows: "Raceways shall not be used as a means of support for other equipment or cables. Exception: As specifically permitted elsewhere in this Code." WOOD: The submitter's substantiation is valid. This would prevent the support of other mechanical systems from electrical raceways. MOI-FERN: This proposal requires that essentially ALL underground conduits or raceways be sealed even i f no gas is present or moisture presents no problem. The present requirement of sealing only those which would permit moisture to come into contact with live parts has been greatly expanded to include all installations including those with waterproof cables. The substantiation does not include any j u s t i f i c a t i o n for these expanded sealing requirements against moisture. I t is not necessary to seal underground raceways against moisture when moisture presents no problem. Many underground installations are not made near landfills or other sources of gas. I t is not necessary to seal underground raceways against gas when gas is not present. I suggest that the present Code intent of sealing against moisture be retained and that a similar requirement for sealing against gas be added only for those installations where i t might cause a problem. WHITTINGTON: The present wording of Section 300-5(g) is adequate to cover any sealing or plugging needs for conduits or raceways. Plugging or sealing of a l l raceways or conduits will create unnecessary problems of heat buildup in conductors and rusting of components arising from elimination of circulating air. Log # 1729 3- 29 - (300-5{i), Exception-(New)): Accept SUBMITTER: Charles "Mike" Holt, Concepts in Electricity Inc. ~ATION: Add the following exception: Exception: Conductors in parallel in raceways shall be permitted but each raceway shall contain all conductors of the seme circuit including grounding conductors. SUBSTANTIATION: Provide an exception for parallel conductors since this section implies that all conductors of the same circuit shall be installed in the same raceway, some interpret that where multiple raceways are used, for conductors in parallel, i t would not be permitted because of Section 300-5(i). PANEL ACTION: Accept. VOTE ON PANELACTION: AFFIRMATIVE: 6 NEGATIVE: Lawry. EXPLANATION OF VOTE: LAWRY: In my opinion both problems stated in Proposals 3-29 and 3-30 could be resolved by deleting Section 300-5(i). I t appears to me that the CMP 3 action in accepting these proposals is a "Band-Aid" approach and has cluttered up the Code with additional language which would not be necessary i f Section 300-5(i) was deleted. The argument that the conductors should be in close proximity does have some v a l i d i t y , but I do not believe deleting (i) would result in installation method changes which would cause serious problems. The circuit impedance question is a design consideration anyway. Log # 1181, 1184 3- 30 - (300-5(i), Exception and FPN-(New) : Accept in Principle SUBMITTER: M. F. Borleis, Electric Light & Power Group I~'-~(~U~"ITF)ATION: Add: Exception: Isolated phase installations are permitted in nonmetallic raceways in close proximity where conductors are paralleled as permitted in Section 310-4 and the conditions of Section 300-20 are met. FPN: The effect on voltage drop should be considered. SUBSTANTIATION: Grouped phase conductors are allowed in open wiring (Article 320), in wireways (Article 362) and specifically designed into cable bus (Article 365). In the close quarters of the termination compartments of switchboards, unit substations or transformer enclosures of large power services the maze of crossing conductors can be avoided. I t is true that the spacing of isolated phase conduits can increase the impedance of the circuit and increase the voltage drop. However, this effect can be minimized by keeping the conduits in proximity and by limiting the length of the run. The advantages of straight forward phase connections may be minimal for two conductors per phase but can be quite substantial at 8 to 10 conductors per phase for 3000 or 4000 ampere services. PANEL ACTION: Accept in Principle. Change "are" to "shall be" in the f i r s t sentence between "installations" and "permitted." PANEL COMMENT: The revised wording conforms to the NFPA Manual of Style. VOTE ON PANELACTION: AFFIRMATIVE: 5 NEGATIVE: Lawry, Wood. EXPLANATION OF VOTE: LAWRY: See comment f o r Proposal 3-29. WOOD: Practice in the f i e l d has been and is, that all phases are contained in the same raceway or enclosure. This change would not increase the safety of an installation. No limitations are placed on length of runs. Log # 2023 3- 32 - (300-13{b), Title): Reject SUBMITTER: Idaho Chapter IAEI RECOMMENDATION: Delete "Device Removal" and replace with the following: "Grounded Conductor (Multiwire)." SUBSTANTIATION: This t i t l e would more clearly reflect the condition in mind when searching for this section in the Code. PANEL ACTION: Reject. FANbL CUF~VLEN~: The Panel believes that the term "device removal" is more appropriate. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 365 3- 33 - (300-13(b)): Accept SUBMITTER: Jeremy Waldner, Sheldon, IA RECOM~NDATION: Change "an" to "a," to read as follows. In multiwire circuits the continuity of a grounded conductor. shall not be dependent upon device connections, such as l ampholders, receptacles, etc., where the removal of such devices would interrupt the continuity. SUBSTANTIATION: The use of "an" before "grounded" is not proper grammar. Changing the "an" to "a" l~uld correct the grammar and make this section easier to read, without changing the intent of it. PANEL ACTION: Accept. VUIE ON PANEL ACTION: UnanimouslyAffirmative. Log # 390 3- 34 - (300-13(b)): Reject SUBMII-TER: R. G. DeLuca, Maricopa County, AZ RECOMFENDATION: Device Re~val. In all branch circuits the continuity of all conductors shall not be dependent on device connections such as l ampholders, receptacles, switches, etc. where removal of such a device will Interupt the continuity. SUBSTANTIATION: See Definitions, Branch Circuit. "The circuit conductors between the final overcurrent device protecting the circuit and the outlet(s)." See also definition of Receptacle and Receptacle Outlets. 109 Fixtures, receptacles and switches are by their very nature and use "Replaceable" items not part of the wiring system or circuit. Once the building is occupied, the owner, usually lacking in electrical knowledge, removes, replaces, exchanges, receptacles, fixtures, and switches according to taste and appearance hardly according to use and.conditions, codes, safety and inspectors are now existent. Some consideration should be given to allow easier, safer replacement of devices and fixtures. PANEL ACTION: Reject. PANEL COMMENT: The Panel believe that the existing language is safe and the substantiation does not provide sufficient documentation. VOTE ON PANELACTION: UnanimouslyAffirmative. I Log # 446 3- 35 - (300-13(b)): Reject SUBMITTER: Southwestern Section IAEI ITE'L'~gTE~F~ATION: In all branch circuits, the continuity of all conductors shall not be dependent on device connections such as l ampholders, receptacles, switches etc., where removal of such a device will interrupt the continuity. SUBSTANTIATION: See DEFINITIONS, BPJ~NCHCIRCUIT. "The circuit conductors between the final overcurrent device protecting the circuit and the outlet(s)." See also: DEFINITION OF RECEPTACLEAND RECEPTACLE OUTLETS. Fixtures, receptacles and switches are by their very nature and use "replaceable" items, not part of the wiring system or circuit. Once the building is occupied, in many cases the owner, lacking in electrical knowledge, removes or replaces receptacles, fixtures and switches for ascetic purposes without maintaining proper connections of this equipment. In most cases, permits nor inspections are required by local codes. Not only are improper connections made, but in many instances shocks occur to person making changes, as main circuit is not disconnected and this person gets in series with circuit that is s t i l l in use downstream. Some consideration should be given to allow easier, safer replacement of devices and fixtures. PANEL ACTION: Reject. PANEL COMMENT: See Panel Comment on Proposal 3-34. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 480 3- 36 - (300-13(b), Exception-(New)): Reject SUBMI1-FER: GeorgeW. Flach, New Orleans, LA ~ T I O N : Add the following Exception under Part (b): Exception: Where all ungrounded conductors of a multiwire circuit are disconnected simultaneously, device connections for grounded conductor continuity are acceptable. SUBSTANTIATION: Neutral or grounded conductor continuity is not necessary where all ungrounded conductors of a branch circuit must be disconnected before repairs, replacements, etc. are performed. The last paragraph of Section 210-4 requires simultaneous disconnection of ungrounded conductors of multiwire branch circuits supplying receptacles on the same yoke in dwelling units. To require "pigtailing" of the neutral under these conditions serves no useful purpose. PANEL ACTION: Reject. PANEL COMMENT: This may result in an unsafe condition where the device is removed while energized. VOTE ON PANELACTION: AFFIRMATIVE: 6 NEGATIVE: Cox. EXPLANATION OF VOTE: COX: The concept of simultaneously disconnecting all conductors has been well established with manufactured wiring, office furnishings, bus plugs, etc. Pigtailing does not increase the level of safety under the conditions proposed. SUBSTANTIATION: Too often I see on jobs where you have the do-it-yoursel-i~er, they don't know to ream the ends. When they pull the wires or cables into the ends of these the sheath gets peeled back or nicked. Cables and wires resting on these sharp edges may get cut into after a period of time due to vibrations. PANEL ACTION: Accept in Principle. Delete "In addition." PANEL COMr4ENrF: Panel feels the words "In addition" are not necessary. VOTE ON PANELACTION: UnanimouslyAffirmative. Log # 1466 3- 39 - (300-15(b), Exception No. 5): Accept in Principle SUBMITTER: Leo Witz, Continental Electric Co. ~ g a n , Chicago, IL Fred Smith, Elgin, IL Jim Meehan, New Haven, CT Anton Ganje, North Dakota Kenny Gebert, Minneapolis, MN Robert P. Brooks, Chicago, IL Paul Moore, Paducah, KY Les Rinder, Chicago, IL Leo Nagel, North Dakota John W. Erickson, Boltswitch, Inc. Homer M. Lefler, Chicago, IL RECO~ENDATION: AmendSection 300-15(b), Exception No. 5 by inserting the words, "with integral enclosures and" between the words, "device" and "having." SUBSTANTIATION: I t would seem that in the writing of this most recent edition of this exception the Code-Making Panel inadvertently omitted these very important words. I f i t was their intent to omit the words, such intent was never made public. As the exception presently stands any manufacturer can make any device with brackets that will securely fasten the device to a structural member of a building under construction and he may then proceed to wire the house with nonmetallic-sheathed cable with no boxes at a l l ! ! ! PANEL ACTION: Accept in Principle. See Panel Action on Proposal 3-40. PANEL COMMENT: The proposal di~ not use the phrase "identified for the use." VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 1301 3- 40 - (300-15(b), Exception No. 5): Accept SUBMITTER: W. R. Williford, NEMA C RO - - A T ] O N : Exception No. 5 ~Amend as follows: A "wiring" device with integral enclosure "identified for the use" having brackets that securely fasten the device to a structural member in walls or ceilings of conventional on-site frame construction for use with nonmetallic-sheathed cable shall be permittedwithout a separate box. SUBSTANTIATION: Present language implies that a conventional switch, rece~acle or device can be used i f i t has a bracket(s) attached to i t . PANEL ACTION: Accept. VOTE ON PANELACTION: UnanimouslyAffirmative. Log # 1554 3- 41 - (300-15(b), Exception No. 5): Reject SUBMITTER: Gopal J. Virani, Slater Electric Inc. ~DATION: Exception No. 5 - Amend as follows: A device with an integral enclosure which securely fastens to walls or ceilings and is identified for the use without a separate outlet box shall be permitted without support from a structural member, brace or box. The testing and approval of the device shall include the wall and ceiling construction systems for which i t is intended to be used. SUBSTANTIATION: Millions of these self-contained wiring devices have been installed in mobile homes throughout the country by many builders of mobile homes. Construction of walls and partitions in mobile homes is identical in many respects to on-site construction homes. These wiring devices have been installed without a bracket securing the device to a structural member as permitted under Section 550-8(j). We know of no case of failure in all these installations and thus should be permitted in on-site construction homes also. Presently also accepted by the NEC in manufacturing homes (ref. Section 545-10) and in recreational vehicles (ref. Section 551-14(e) Exception No. 1). PANEL ACTION: Reject. PANEL COMJ~ENT: Manufactured home installations are factory installed under controlled conditions. The Panel does not have sufficient documentation indicating that on-site construction will result in equivalent safety. VOTE ON PANELACTION: AFFIRMATIVE: 6 NEGATIVE: Cox. Log # 38B 3- 37 - (300-14, Exception No. 2-(New)): Reject SUBMITTER: Kris Nicholson, Sheldon, IA ~NDATION: 300-14, Exception No. 2 Rosettes shall have enough conductor length to do the job. SUBSTANTIATION: This article should be added because i t is very hard to get 6 inches of free conductor inside the device. PANEL ACTION: Reject. PANEL COMMENT: This section does not apply to rosettes. VOTE ON PANELACTION: Unanimously Affirmative. Log # 10 3- 38 - (300-15(b), Exception No. 4): Accept in Principle SUBMITTER: B i l l J. Shanks, Bowling Green, OH ~ T I O N : Add a second sentence to read: "In addition, a f i t t i n g shall be provided on the end(s) of the conduit or tubing, to protect the wires or cables from abrasion." 110 Log # 1964 3- 45 - (300-18): Reject SUBMITTER: Richard W. Osbern, St. Louis, MO ~ATION: Omit Section 300-18. SUBSTANTIATION: The usefulness of this section is long past. Improved and more efficient conductor installation methods have lead to prewiring in prefabrication of raceway systems. This is further indicated by the large number of listed prewired flexible raceway systems. Current practices do not support the l i t e r a l text of Section 300-18. This section does not recognize the vastly improved conductor insulations of today. PANEL ACTION: Reject. PANEL COMMENT: Approval of the proposal could result in incompleted installations which would create conditions exposing conductors to physical damage. Listed prewired flexible systems are covered by Article 604. VOTE ON PANELACTION: AFFIRMATIVE: 6 NEGATIVE: Lawry. EXPLANATION OF VOTE: LAWRY: I agree with deleting Sections 300-18(b) and (c). These sections do not appear necessary nor are enforceable from a practical standpoint. There may be v a l i d i t y in retaining Section 300-18(a). CMP 3 did not address (b) or (c) in its Panel Comment. EXPLANATION OF VOTE: COX: Test installations made of boxless devices mounted with special brackets in wallboard were examined in on-site construction. These products were found to provide the same degree of permanence as similar products mounted to structural members. Only extended field experience can indicate i f this construction will result in equivalent safety. Log # 1934 3- 42 - (300-15, Exception No. 5): Reject SUBMITTER: E. L. Eldridge, Thomas & Betts ITE'-~(~-~FE-N~)ATION: AmendException No. 5 to read: A device with an integral enclosure which fastens the device in walls or ceilings of frameconstruction without support from a structural member and for use with nonmetallic-sheathed cable shall be permitted. SUBSTANTIATION: Mobile homes, Section 550-8(j) and manufactured homes, Section 545-10 permits the self-contained device to be used without being connected to a structural member. This has been so since the 1975 NEC. Millions have been installed in this manner. UL fact-finding reports were necessary to obtain listing for this self-contained device. The device installed in this manner does not cause an electrical or mechanical hazard. I t should be permitted in on-site frame construction. PANEL ACTION: Reject. PANEL COMMENT: See Panel Comment for Proposal 3-41. VOTE ON PANEL ACTION: AFFIRMATIVE: 6 NEGATIVE: Cox. EXPLANATION OF VOTE: COX: Test installations made of boxless devices mounted with special brackets in wallboard were examined in on-site construction. These products were found to provide the same degree of permanence as similar products mounted to structural ~embers. Only extended field experience can indicate i f this construction will result in equivalent safety. Log # 155 3- 46 - (300-18(a), Exception No. 2-(New)): Accept in Principle Secretary's Note: I t was the action of the Correlating Committee that this proposal be correlated with Proposal 3-47. SUBMITTER: Albert C. Niewoehner, SACHSElectric Co. RECOMMENDATION: Add Exception No. 2. "Approved, Prewired raceway assemblies (cable assemblies)." SUBSTANTIATION: Please refer to Articles 300, 350, 545, 604. Article 545 and Article 604 recognize manufactured sub-assemblies for branch circuit wiring, and since the Enforcing Authorities of both the City of St. Louis and the County of St. Louis have actually adopted this proposed exception, we as one of the leading national electrical contractors believe that the Enforcing Authority should have the Code backing that this exception would provide. This exception would permit the acceptance o f any manufactured assembly consisting of UL listed components and meeting all National, as well as local NATIONAL ZLECTRICAL CODErequirements. As stated above, this method of wiring has been approved by the Chief Inspectors of the City of St. Louis and the County of St. Louis for installation in commercial buildings, as long as all other requirements of NATIONAL ELECTRICAL CODEare being met during installation of these components. These requirements being; use, size, support, ~rounding, number of bends, fastening, termination etc., of assemblies. The system of wiring presents no known safety hazards of any type presently or in the future. Attached for your information is a copy of the ruling by W. L. Raines, Supervisor, Electrical Inspection Department of Public Works of St. Louis County. A few of the other cities permitting the use of manufactured sub-assemblies in which Sachs Electric Company has made installations are as follows: Houston, Texas Flagstaff, Arizona Phoenix, Arizona Alton, I l l i n o i s Overland Park, Kansas Kansas C~ty, Missouri Independence, Missouri MoberIy, Missouri Please transmit your feelings on this matter at your earliest possible convenience. (Note: Copy of attachment available from NFPA upon request.) PANEL ACTION: Accept in Principle. Delete: "Approved." PANEL COM#4ENT: The Panel believes that manufactured assemblies should be permitted. Use of the word approved is inappropriate. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 168 3- 43 - (300-15(b), Exception No. 7-(New)): Accept in Principle Secretary's Note: I t was the action of the Correlating Committee that the Panel Action using the word "when" is in conflict with the NEC Style Manual, Section C2. SUBMITTER: Dan Leaf, Westlake Village, CA RECOMMENDATION: Add exception as follows: Exception No. 7. A conduit body shall be permitted in lieu of a box where installed to comply with Section 370-6(c) and Section 370-18. SUBSTANTIATION: There appears to be no valid reason to generally restrict Junction points of cable and raceway systems to boxes only. Paragraph (a) permits a f i t t i n g (conduit body) to be used - at a junction point between various raceway systems (e.g., flexible metallic conduit to flexible metallic conduit, flexible conduit to E.M.T., f l e x i b l e conduit to rigid metal conduit, flexible conduit to nonmetallic conduit, etc.). In these cases the conduit body will require support other than the raceway system (straps at hubs, bolts, screws), as Section 370-13 permits "support" only by two or more threaded conduits. Section 370-18(a)(2) exception implies that cables may be used with conduit bodies and this proposal will correlate the wording of these two sections. PANEL ACTION: Accept in Principle. J Changethe word "where" to "when." PANEL CO~ENT: The Panel believes that the term "when" is more technically correct. VOTE O~ PANELACTION: Unanimously Affirmative. COMMENTON VOTE: COX: Support acceptance; however I believe event is place related and not time related. Therefore "where" would be the correct word. Log # 1357 3- 44 - (300-15(b), Exception No. X-(New)): Reject SUBMII-FER: Melvin K. Sanders, Ankeny, IA ~ T I O N : Add new exception: 300-15(b) Exception X. As permitted by Section 336-6(a) and (b) for dwelling unit basements. SUBSTANTIATION: This would recognize a common practice of installing an NM or NMC cable in a short section of raceway down a basement wall to a receptacle as required by Section 210-52(f), or for switch legs for basement lighting circuits. The Code makes mandatory these basement receptacles, then leaves the inspector and installer with an out-of-date requirement for a transition Junction box because you are changing wiring methods. I t is d i f f i c u l t to enforce this requirment and many inspectors ignore the junction box requirement since most NM and NMC cables use a 60°C (TW) type of insulation which is in i t s e l f suitable when installed as a single conductor in a raceway. (This would coordinate with the proposal to permit the installation of NM and NMC cable to be installed in short sections of raceway in dwelling unit basements.) PANEL ACTION: Reject. PANEL COMMENT: The Panel feels that the present wording of the Code permits the practice cited in the substantiation. VOTE ON PANELACTION: Unanimously Affirmative. Log # 182 3- 47 - (300-18(a), Exception No. 2-(New)): Accept Secretary's Note: I t was the action of the Correlating Committee that this proposal be correlated with Proposal 3-46. SUBMITTER: Donald J. Meadows, I.B.E.W. Local One RECOMMENDATION: Add an exception. Numberexisting Exception No. 1. Add an Exception No. 2. Prefabricated flexible raceways shall be permitted to contain conductors prior to installation in place. SUBSTANTIATION: This has been an industry practice for many years and has been amplified by the marketing of listed flexible raceway assemblies. Certain construction procedures lend i t s e l f to prefabricated assemblies being installed in place before structural members are in place. After structural supports are in place, the assemblies are lowered and fastened on the supports. Application of the existing l i t e r a l text causes field problems and unusual hardships. PANEL ACTION: Accept. PANEL COW,lENT: Add as Exception No. 2. VOTE ON PANEL ACTION: Unanimously Affirmative. 111 i I Log # 1302 3- 48 - (300-18(a), Exception No. 2-(New)): Accept SUBMITTER: W. R. Williford, NEMA ECOMMENDATION: Add Exception No. 2 as follows: Exception No. 2: Within 10 feet of a raceway termination. SUBSTANTIATION: At motor and appliance terminal boxes, particularly where raceway connections are made with angle connectors, i t has been common practice to push conductors through the last section of raceway and f i t t i n g s before final assembly. This eliminates the necessity of conductor pulls across tight angles and reduces the potential for insulation damage. This proposal recognizes an installation practice that enhances safety. PANEL ACTION: Accept. PANELCOIV~MENT: Add as Exception No. 3. VOTE ON PANEL ACTION: AFFIRMATIVE: 6 NEGATIVE: Cox. EXPLANATION OF VOTE: COX: Assembling the raceway and f i t t i n g s over the conductors increases the p r o b a b i l i t y of insulation damage. To permit disassembly of raceway systems to i0 f e e t unnecessarily increases the r i s k of damage and is not supported by the substantiation. If the proposal were limited to disassembly of the raceway connection at the terminal box, I could support the proposal. This Committee shall consist of a Correlating Committee and Code-Making Panels. I t shall have primary responsibility for preparing documents on minimizing the risk of e l e c t r i c i t y as a source of electric shock and as a potential ignition source of fires and explosions. I t shall also be responsible for text to minimize the propagation of f i r e and explosions due to electrical installations. -Removal of this phrase from the NEC does not mean that NFPA is ignoring the very important subject of the spread of products of combustion. The NFPACommittee on Air Conditioning has been assigned responsibility for the subject of combustibles in plenums and i t must seek the cooperation of the Committees on Fire Tests, NATIONAL ELECTRICAL CODE, and Safety to Life. The subject of combustibles in concealed spaces has been assigned to the NFPA Building Construction Project. In addition, the NFPA Building Construction Project has been assigned the subject of mechanical smoke control systems. Further, the NFPAStandards Council ha~ appointed a Subcommittee to study the subject of the t o x i c i t y of the products of combustion from combustible materials. Correlating Proposals submitted for Sections 725-2(a), 760-4(a), 800-3(c), and 820-14. PANEL ACTION: Reject. PANEL COMMENT: Since the subject is under study by another NFPA ad hoc committee, the Panel believes that i t is appropriate to leave this term in the section. VOTE ON PANELACTION: Unanimously Affirmative. Log # 272 3- 49 - (300-19(a), FPN-(New)): Reject SUBMITTER: Dan Leaf, Westlake Village, CA ~ T I O N : Add a fine print note as follows: For the purpose of this section a vertical raceway shall be defined as a raceway installed at an angle more than 45 degrees from the horizontal plane. SUBSTANTIATION: Small offsets or bends in vertical runs of raceways are not "vertical" in the strictest sense and can divide the vertical portions into lengths which may not require conductor support, even though such bends would not contribute substantial support or f r i c t i o n conditions to the conductors. On the other hand, raceway bends with a substantial angle from the horizontal can increase f r i c t i o n and provide some conductor support. This proposal attempts to suggest a guide as to how and what degree the conductor support requirements may be modified. PANEL ACTION: Reject. PANEL COMMENT: No documentation in the substantiation to warrant the 45 degree angle, and no specific problems are indicated. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 1182 3- 52 - (300-21): Reject Secretary's Note: I t was the action of the Correlating Committee that this proposal be referred to the NFPA Committee on Air Conditioning for comment. SUBMITTER: M. F. Borleis, Electric Light & Power Group RECOMMENDATION: Delete "Products of Combustion" and revise to read: 300-21. Spread of Fire (or Products of Combustion). Electrical installations in hollow spaces, vertical shafts, and ventilation or air-handling ducts shall be so made that the possible spread oZ f i r e (or products of combustion) will not be substantially increased. Openings around electrical penetrations through f i r e resistance rated walls, partitions, floors, or ceilings shall be firestopped using approved methods. SUBSTANTIATION: In the 1981-82 NFPAYearbook and Committee l i s t (page 101) the Scope of the National Electrical Code Committee states: SCOPE: This Committee shall consist of a Correlating Committee and Code-Making Panels. I t shall have primary responsibility for preparing documents on minimizing the risk of e l e c t r i c i t y as a source of electric shock and as a potential ignition source of fires and explosions. I t shall also be responsible for text to minimize the propagation of f i r e and explosions due to electrical installations. On Page 59 of the same document, the Scope of the Air Conditioning Committee states: SCOPE: The construction, installation, operation and maintenance of systems for air conditioning, warm air heating and ventilating includirl f i l t e r s , ducts and related equipment to protect l i f e and pruperty from f i r e , smoke and gases resulting from f i r e or from conditions having manifestations similar to f i r e . Section 300-21 is and should be primarily concerned with limiting the migration or movement of f i r e through f i r e barriers or in environmental air spaces due to the installation of electrical systems with improper materials or improper methods. However, since the introduction of "products of combustion," the concern has been directed to those possible products of combustion generated by electrical systems subjected to fires "external" to the electrical system. The prime concern, i f we must be concerned about products of combustion, should be those generated by building components and contents subjected to fires possibly caused by overcurrents or short circuits "internal" to the electrical system. Since we have l i t t l e or no control over the building components and contents, our prime concern is that the electrical system not be an ignition source or a means of migration. Of the one million or so building fires estimated to occur annually, approximately 15 percent are attributed to electrical causes. Of the fires of electrical origin, approximately 10 percent are attributed to wires and cables. The data submitted to the Technical Subcommittee on Wiring in Ducts and Plenums reflects an a b i l i t y to control f i r e spread in nonmetallic-sheathed cables. All of the above indicates that wires and cables, that portion of the electrical system that is permitted to be installed in ducts or plenums, is seldom the ignition source for building fires and less frequently are they the fuel for f i r e migration. As stated in the scopes of the technical committees responsible for the National Electrical Code (NFPA 70) and Air Conditioning and Ventilating Systems (NFPA90A) and Residence Type Warm Air Heating and Air Conditionin~ Systems (NFPA 90B), the responsibility to protect l i f e and property from smoke and gases resulting from f i r e lies with the Air Conditioning Committee, not with the NATIONAL ELECTRICAL CODE. PANEL ACTION: Reject. PANEL COPB~ENT: See Panel Comment on Proposal 3-51. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 931 3- 50 - (300-20(b)(FPN)): Reject SUBMITTER: Gerald Pool, William S. Watkins & Associates RECOMMENDATION: Add the following sentence to the fine print note .at the end of Section 300-20(b). When rigid nonmetallic conduit is used the grouping of conductors or special treatment of the conductors or conduit will not be required because neither hysteresis nor induced currents occur. SUBSTANTIATION: This note will clarify the section by explaining why neither aluminum nor rigid nonmetallic conduit require special treatment. PANEL ACTION: Reject. PANEL COMMENT: This is not appropriate to this section since Section 300-20 applies to metal enclosures and metal raceways. VOTE ON PANELACTION: UnanimouslyAffirmative. Log # 1380 3- 51 - (300-21): Reject Secretary's Note: I t was the action of the Correlating Committee that this proposal be referred to the NFPA Committee on Air Conditioning for comment. SUBMITTER: RichardDel.eteBOyd,B. J r . , Raleigh, NC ~MENDATION: "or products of combustion" in heading and f i r s t sentence. SUBSTANTIATION: Spread of products of combustion is outside the Scope of the National Electrical Cbde Committee as established by the NFPAStandards Council. This Scope, approved after the 1981 Code was processed, is as follows: 112 PANEL ACTION: Reject. PANEL COMMENT: The Panel believes that the NEC should not r~en-n~e-a specific laboratory standard. The,section in which the proposal is to be inserted is not indicated. There is no supporting data that the proposal criteria is valid. VOTE ON PANEL ACTION: Unanimously Affirmative. Log # 838 3- 53 - (300-21): Reject Secretary's Note: I t was the action of the Correlating Committee that this proposal be referred to the NFPA Committee on Air Conditioning for comment. SUBMITTER: Robert E. Taylor, Smoke Control Association RECOMMENDATION: Revise Section 300-21 to read: 300-21 Prevention of Spread of Fire or Smoke. Electrical installations shall be made to prevent the spread of f i r e or smoke through fire-rated, fire-resistant, fire-stopped walls, partitions, ceiling and floors; hollow spaces; plenums, vertical shafts and ventilating or air handling ducts and enviromental air handling spaces. SUBSTANTIATION: To make Code interpretation more precise and accurate, an accepted "scientific" definition of smoke should be used in Section 300-21 in place of the nondefinable term "Products of Combustion." The accepted ASTM definition for smoke has been recommended to Panel 1 for inclusion in the definitions. The ASTM definition f o r SMOKE(n) - the airborne solid and liquid particulates and gases evolved when a material undergoes pyrolosis or combustion. The proposed change also eliminates the term "will not be substantially increased" which l i t e r a l l y is a nonenforceable phrase for the authority having jurisdiction. Instead the proposed revision simply says, "made to prevent the spread of f i r e or smoke..." which is a phrase that can be accomplished by the installer and enforced by the authority having jurisdiction. Environmental air spaces has been added since smoke movement through such spaces by fires originating in the environmental space or outside the space may move rapidly through the space to cause serious l i f e safety hazards and make f i r e fighting extremely difficult. A member of the Smoke Control Association will be pleased to appear before the Panel to discuss this proposed change in greater depth at the Panel's request. PANEL ACTION: Reject. PANEL COMMENT: See Panel Comment f o r Proposal 3-51. The Panel supports the concept of the submitter, but believes that the present Code is acceptable with the present technology. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 463 3- 57 - (300-22(a), Exception-(New)): Reject Secretary's Note: I t was the action of the Correlating Committee that this proposal be referred to the NFPA Committee on Air Conditioning for comment. SUBMITTER: Leo F. Hnyda, Eastman Kodak Co. R-'~-(~OMMENDATION: Add Exception: Equipment and associated wiring approved as i n t r i n s i c a l l y safe may be installed in these areas. SUBSTANTIATION: Since i n t r i n s i c a l l y safe equipment and wiring is not capable of releasing sufficient electrical or thermal energy under normal or abnormal conditions to cause ignition of flammable or combustible atmospheric mixtures, i t should be accepted as a means for monitoring or control of these materials within the duct systems. PANEL ACTION: Reject. PANEL COMMENT: The submitter has not provided adequate documentation to support the proposal. Furthermore, sensors would be permitted to be inserted into the duct. VOTE ON PANEL ACTION: UnanimouslyAffirmative. Log # 1298 3- 58 - (300-22(b)): Reject Secretary's Note: I t was the action of the Correlating Committee that this proposal be referred to the NFPA Committee on Air Conditioning for comment. SUBMITTER: Doug Pendergras, NFPA Health Care Section Executive Board RECOMMENDATION: Revise f i r s t sentence to read as follows: "Only wiring methods consisting of low-smoke, flame-resistant plastic sheathed cable specifically listed for use, mineral-insulated, metal-sheathed cable, Type MC..." (rest of sentence to remain the same). SUBSTANTIATION: Widespread abuse of this requirement for metal sheathed or conduit encased wiring for communication systems now exists. The advent of the new product (low-smoke, flame-resistant, plastic-sheathed cable), and indication by communication organizations that they view the use of same with favor, would be a major move towards correcting this troublesome condition in all building categories. PANEL ACTION: Reject. PANEL COMMENT: The Panel feels that the substantiation does not provide documentation to support the proposal. Perhaps the submitter intended this proposal for Section 300-22(c). There is no definition in the present Code to define flame-resistant. VOTE ON PANELACTION: Unanimously Affirmative. Log # 1791 3- 54 - (300-21): Accept in Part SUBMITTER: Leo F. Martin, Paul Revere Chapter IAEI ITE'CI]I~PL'I~DATION: Change the last sentence to read as follows: "shall be firestopped using listed devices or materials, such as concrete, to maintain the fire-resistance rating." SUBSTANTIATION: Poke-through wiring is being installed in a manner that contributes to the spread of f i r e and products of combustion. PANEL ACTION: Accept in Part. Add "to maintain the fire-resistance rating" to the present second sentence. PANEL COMMENT: The Panel believes that there are suitable materials such as concrete and gypsum which are not specifically listed for f i r e stopping. VOTE ON PANELACTION: Unanimously Affirmative. Log # 1400 3- 59 - (300-22(b)): Reject Secretary's Note: I t was the action of the Correlating Committee that this proposal be referred to the NFPACommittee on Air Conditioning for comment. SUBMITTER: C. W. Beile, Allied Tube & Conduit Corporation RECOMMENDATION: Revise the f i r s t sentence as follows: Only noncombustible wiring methods, consisting of mineral-insulated . . . (balance of paragraph remains the same). SUBSTANTIATION: The installation of unprotected combustible materials capable of producing smoke or gases that may spread throughout a structure and inhibit the safe e x i t from burning buildings should be prohibited. I t is recommended that a more inclusive and consistent term be used. Please note definition of "noncombustible" submitted as proposal to 1984 NEC, Article 100. This definition is consistent with NFPA 90-A, which will be correlated with NFPA 70 with regard to Ducts and Plenums as directed by the Standards Council actions. PANEL ACTION: Reject. PANEL COMMENT: No definition of combustible in the present Code. VOTE ON PANEL ACTION: AFFIRMATIVE: 6 NEGATIVE: Lawry. EXPLANATION OF VOTE: LAWRY: Although I have reservations about including the word "noncombustible" in this section at this time, I believe other revisions are clearly in order. I would recommend deleting flexible metal conduit and certainly liquidtight flexible metal conduit, and adding flexible metal tubing as a recognized wiring method. With flexible metal tubing and proper connectors now available, there:appears to be no logical reason to continue recognizing flexible metal conduit or liquidtight in this application. Also, i f the revisions I have suggested were adopted, there should be no reason to add the word "noncombustible." Log # 257 3- 55 - (300-21): Accept in Principle SUBMII-FER: C. E. Muhleman, Marion, IN RECOMMENDATION: Add: Such firestops shall be so designed so as not to decrease the ampacity of the cable or the overcurrent protection must be reduced and the protective device, load panel labeled against oversizing. SUBSTANTIATION: Because the firestops are thermal barriers, a c i r c u i t ' s heat due to cable losses could not be dissipated from within the firestop. PANEL ACTION: Accept in Principle. Add as a Fine Print Note. Revise to read as follows: "Firestops may require decreasing the allowable load on the conductors." PANEL COMMENT: Panel feels that enforcement would be impossible and is a design consideration. VOTE ON PANELACTION: Unanimously Affirmative. Log # 1604 3- 56 - (300-22): Reject Secretary's Note: I t was the action of the Correlating Committee that this proposal be referred to the NFPA Committee on Air Conditioning for comment. SUBMII-TER: William A. Schmidt, Veterans Administration RECOMMENDATION: Cables shall be tested in accordance with UL 910 and shall have an optical density peak of .5 based on a 20 minute f i r e test, and a flame spread rating equivalent of 25 without continuing progressive combustion. SUBSTANTIATION: This is an attempt to c l a r i f y requirements for wiring in ceiling and plenum areas. 113' The second error is the attempt by the people, who spew forth this falacious claptrap, to hide the fact that we, who are responsible for formulating the National Electrical Code, have one prime responsibility, the safety of the people. We are completely and solely responsible for the electrical installation. We and only we must bear the responsibility for what is in the NEC. We are not in any, shape or form responsible for the furnishings nor the buildin~ finishes. Regardless of what others may introduce into the building, we are s t i l l responsible for those things that we permit or require in the electrical installation. We can never loose sight of the prime purpose of the NEC, " . . . t h e practical safeguarding of persons and property from the hazards arising from the use of e l e c t r i c i t y . " For many years a great number of knowledgeable and highly respected people in the scientific world have been aware of the fact that the use of certain materials and wiring methods, which by the very nature of their chemical composition, are certain to add significantly to the toxic gases and harmful chemicals in any f i r e situation. I t has been and s t i l l is their contention that the use of these materials should be curtailed or prohibited. We can no longer afford the luxury of sitting back waiting for someone else to take the f i r s t step. We cannot hide behind a disclaimer saying we know nothing about t o x i c i t y . I f we don't know, i t is because we haven't taken the time to read what is available on the subject or listen to what is being said from every direction. The numbers of people being killed in recent fires is staggering. The ratio of f i r e deaths to f i r e damage is astounding. I t is completely out of line with historical f i r e data. The number of people died 20 stories away from the closest flame in the MGM is unforgiveable. The number of people who died in that building after the f i r e was out, but while the hallways and stairwells were f u l l of toxic gases and smoke will never be known, but the fact that many did is additional reason for us to act. We cannot wait until other standards-writing bodies take the lead. We cannot wait until slow moving committees bring in the BODY COUNTS! We can no longer ignore the warnings that have been made public in the form of test results from widely diwergent groups, government, industry, scholastic and testing f a c i l i t i e s . Here is what just a few highly regarded scientists have to say about this matter: A report compiled by the Uniformed Firefighters Association in 1980 five years after the telephone company f i r e shows that of the 194 firefighters who received medical treatment at the time of the f i r e 71 reported permanent respiratory ailments. The unprotected cables that burned in that f i r e produced "billowing clouds of hydrogen chloride smoke." (American Lung Association Bulletin, Log # 1467 3- 60 - (300-22(b)): Reject Secretary's Note: I t was the action of the Correlating Committee that this proposal be referred to the NFPA Committee on Air Conditioning for comment. SUBMITTERS: Leo Witz, Continental Electric Co. Bill Hogan, Chicago, IL Fred Smith, Elgin, I I Jim Meehan, New Haven, CT Anton Ganje, North Dakota Kenny Gebert, Minneapolis, MN Bill Conrardy, The Conrardy Co. Robert P. Brooks, Chicago, IL Paul Moore, Paducah, KY Les Rinder, Chicago, IL John W. Erickson, Boltswitch Inc. RECOMMENDATION: AmendSection 300-22(b) to read as follows: "(b}. Ducts or Plenums Used for Environmental Air. Only noncombustible wiring methods shall be permitted to be installed in ducts or plenums used for environmental air. Flexible metal conduit shall be permitted in lengths not to exceed (4) four feet to connect physically adjustable equipment and devices permitted to be installed in ducts or plenums. The connectors used with such flexible metal conduit shall effectively close all openings at the connections. Electrical equipment and devices shall be permitted to be installed within such ducts or plenums only i f necessary for their direct action on or sensing of the contained air. When i t is necessary to install illumination inside of such duct or plenums, completely enclosed and gasketed fixtures shall be utilized." SUBSTANTIATION: Electrical equipment or devices have no business being installed in air-handling ducts or plenums unless their presence is absolutely necessary for the proper functioning of the air-handling system: The prime purpose of the NEC is the practical safeguarding of persons and property from any and all electrical hazards. The air that is being moved thru the ducts and plenums referred to in this section of the Code moves from one occupied space to another. Electrical equipment, which when i t f a l l s , emits toxic fumes or gases or products of combustion should not be permitted to be installed in such locations. While this proposal does not itemize the wiring methods contained in the present Section 300-22(b), the only one that has been eliminated is liquidtight flexible nonmetallic conduit. In view of what has been said concerning toxic gases, fumes and products of combustion, you can see why we have deleted that from this proposal. Limiting wiring methods will make i t easier in the future for the Panel to decide upon proposals for other wiring methods in such areas. I f they are combustible, the Panel will have no trouble rejecting them. I t is rather obvious that this was the intention of CF~ 6 in 1953 so this proposal is not as drastic as i t might appear at f i r s t reading. Additional substantiation for proposals made by William P. Hogan et. al. on Sections: 110-3(a)(8), 230-43, 300-22(b), 300-22(c), 338-2, 338-3, 340-5, 344-2, 347-2, 351-2, 352-21 and 370-23. I t should be obvious that the thrust of all these proposals is the limitation or actual elimination of the use of those MATERIALS, which when exposed either to the environment, temperatures in excess of their ratings, whether from normal or abnormal causes, or flame emit toxic gases, fumes or harmful chemicals. For years the electrical industry has not only permitted but also has encouraged the use of materials that f a l l into this category. These materials do emit toxic gases and do result in harmful chemicals when exposed to the varying atmospheres experienced in everyday living. For instance, i t is not an uncommon phenomenon to observe hydrochloric acid dripping out of a rigid steel conduit in which PVC conductors have been exposed to temperatures higher than their ratings or flame and water has been used to control the source of that heat or flame, There are documented experiences of this reaction where the acid was eating through the switch enclosure. When the inspector attempted to catch the acid in a t i n can so that he could have i t analyzed, i t ate right thru the can. What is startling about this phenomenon is the fact that we are told that the plastic people have known about i t for years and have never f e l t that this information should be publicized because the incidence would be so rare that i t was not worth alerting the electrical industry. In spite of their lack of concern many people in the industry and out of i t are aware of this possibility and the other ramifications of the decomposition of PVC and are deeply concerned. We are told over and over again that the amount of plastics and polyvinyl chlorides that are introduced in any building by the electrical installation is infinitesimal when compared with the total of all the other furnishings and building finishes. There are two errors in such statements. The f i r s t is corrected by the reports printed in Modern Plastics based upon the monthly Sales/Production report issued by SPI's Committee on Resin Statistics. According to their figures, published in January of 1981 there were 3,581,000 tons of resins converted into building materials in 1979. Of that 1,114,000 tons were PVC Conduit. Is that to be considered infinitesimal? The figures for 1980 are just as revealing; 3,078,000 tons total, 938,000 tons in PVC Conduit. In addition to that there were 841,000 tons of resins converted into electrical/electronic plastics in 1979 of which 195,000 tons were PVC. Likewise, in 1980 out of a total of 736,000 tons, there were 177,000 tons of PVC. These are NOT infinitesimal fractions! (81)). "Large amounts of hydrogen chloride gas (HCL) are released by either HEATING or BURNINGPVC".* "In the case of a rapid electrical overload in PVC insulated wire, smoke which is usually the f i r s t indication of f i r e , is only noticeable AFTER significant quantities of HCL have been released." * "Calculations show that for 100 pounds of PVC pyrolyzed (chemically decomposed by heat) in an apartment 8 feet X 25 feet X 50 feet (10,000 cubic feet) a concentration of HCL as high as 57,385 ppm could be reached, about 57 times the concentration that will cause lung edema on very short exposure." * Referring to the MGMf i r e deaths the Clark County Coroner-Medical Examiner reports, "The fact that the concentration of carboxyhemoglobin in must of the victims was not high enough to have caused death indicates that other toxic gases or smoke particles MUST also have been involved." * (carboxyhemoglobin is the result of carbon monoxide in the blood). • A Literature Study of the Combustion Hazards of PVC and ABS. Judith E. Hall and Eric L. Tolefson, University of Calgary. In a discussion concerning the Beverly Hills Supper Club Fire, Deborah Wallace, who is a Toxicologist and the President of Public Interest Scientific Consulting Service states the following about the causes of death at that f i r e , " - - - , the carboxyhemoglobin levels found during the autopsies showed that all assayed victims but one had concentrations well below lethal levels. Manywere as low as 10%." Yet they all died of something that they inhaled. There was a tremendous amount of PVC in that building! Jay A. Young, Ph.D., a Chemical Consultant has this to say, "Structural disintegration of PVC Conduit in a f i r e situation. Such disintegration allows the release of hydrogen chloride or phosgene, or both, formed from the decomposition of PVC insulation on the wiring inside, the conduit and confined inside the conduit until the conduit disintegrates, u "The thermal decomposition of PVC has been observed at temperatures below 100 degrees C, although most studies show that the evolution of HCL in significant amounts requires temperatures of about 200-300 degrees C. That is, long before the PVC has reached the temperature at which i t will burn, well in advance of the time when any combustible structural components near PVC conduit would be l i k e l y to be burning in a f i r e situation." Dr. Young further states, "Hydrogen Chloride is an i r r i t a t i n g gas At concentrations in air as low as 5ppm, i t causes choking in most people." 114 EXPLANATION OF VOTE: ADELMAN: Need to receive additional documentation to substantiate the claims of the proposer of early failure of nonferrous materials in the submitter's reference fires. Fire reports received of the Carlyle Apartment f i r e , and the Cedarwood Tower f i r e , make no mention of early failure of nonferrous electrical components. Rel~rts of the Henry Grady Hotel f i r e , and the Occidental Tower f i r e , have not been submitted to the Panel members. COX: I do not believe that the substantiation adequately supports the prohibition of this widely used material. LAWRY: The substantiation does not support the Panel Action. The fact that a zinc alloy f i t t i n g may f a i l prior to a ferrous raceway is not cause to prohibit i t . There is no documentation that failure of zinc alloy f i t t i n g s caused any injuries. Also, other equipment and materials which are permitted within this space have melting temperatures less than zinc alloy f i t t i n g s . MOT-fERN: Apparently, the intent of the original proposal was to require f i t t i n g s in plenums and ducts that would not melt below approximately 1800°F and permit gases and combustibles to be transmitted by conduit to other areas. Prohibiting zinc alloy f i t t i n g s will not prevent this problem because there are items in both the conduit and duct systems that will melt before the zinc alloy f i t t i n g s , which melt at approximately 700°F. The reports that I have read on the Cedarwood Tower Apartment f i r e and the Carlye Apartment f i r e do not mention connections and f i t t i n g s as being a factor in the rapid transmission of gases and combustibles. The subject of failure of devices and materials in ducts and plenums should be studied by a TSC. SCHIER: I voted negatively on Proposal 3-61 after reviewing public comment from L.E. Mason Co., The Halex Company and the Zinc Institute Inc. WHITTINGTON: This proposal is inconsistent with the wording of Section 90-1(a), the substantiation used with respect to noted fires has been found not to contain references supporting the proposal, and other studies have concluded that the prohibiting of zinc alloy f i t t i n g s is not j u s t i f i e d . WOOD: There is no substantiation that the use of zinc alloy f i t t i n g s has added to risk or the transmission of combustibles. Dr. Young continues, "Concentrations of 100ppm are rated as, "Immediately dangerous to l i f e and health" by OSHAand the National Institute for Occupational Safety and Health. Unless removed immediately from an atmosphere containing a concentration o f lOOppm death by suffocation will follow." There are no less than 132 books, papers and articles available to you on this subject. You can rest assured that each will point out the t o x i c i t y of the products of combustion of PVC and of the t o x i c i t y of HCL which is produced simply by heating PVC Conduit or insulation. You may be able to ignore this information, but we can not. As far as we are concerned, the facts are in front of you and you must act. We have, - with these proposals. The problem is not going to go away by i t s e l f . Nor is i t going to lessen in intensity. You can be absolutely sure that i t and you will be in the public eye and in every form of mass news media as long as people are killed in fires. I t will make headlines and bring more and more court cases, which will further highlight the shortcomings of the Code. I t seems to be a foolish course of action, or is i t INACTION, to wait until public furor forces us to change. I f we in NFPA through the NEC i n i t i t a t e the act, we at l e a s t r e t a i n the respect and confidence of the people we serve. I f we do not, you can be assured that those same people will have no respect for this organization or us. I t is f u t i l e to deny, or attempt to minimize, the presence of the harmful chemicals in the materials used to manufacture insulations and raceways that not only can, but do, emit toxic gases in amounts sufficient to cause instantaneous paralysis when exposed to temperatures in excess of their ratings, or f i r e . The peaceful attitudes of so many of their victims is grim testimony to the speed of these killers and the fact that the victims were t o t a l l y unaware of their impending fate. Our proposals are intended to minimize or eliminate the exposure of human beings to this peril. Note: I t is most important to understand that this proposal is not intended to do away with a l l , nor any, nonmetallic wiring method. This proposal and all others like i t that we have submitted for the 1984 edition of the NEC are intended to eliminate the MATERIALSwhich emit toxic fumes or gases under various conditions of use. I t is our opinion that the manufacturers of this equipment or these MATERIALSmust prove that their products do NOT emit toxic gases or harmful chemicals under the conditions specified. I t should not be the responsibility of the NFPA nor any Code-Making Panel to perform the tests or make the investigations that are needed to prove the presence of the toxic gases, fumes or harmful chemicals. PANEL ACTION: Reject. PANEL COMMENT: No definition of combustible in the present Code. VOTE ON PANEL ACTION: AFFIRMATIVE: 6 NEGATIVE: Wood. EXPLANATION OF VOTE: WOOD: I agree with the submitter's substantiation. The terms combustible and noncombustible are used in the NEC. Ex. Articles 410 and 725. Log # 836 3- 62 - (300-22): Reject Secretary's Note: I t was the action of the Correlating Committee that this proposal be referred to the NFPA Committee on Air Conditioning for comment. SUBMITTER: Robert E. Taylor, Republic Steel Corporation E~LMENDATION: Insert the following after the f i r s t sentence in Section 300-22(b) and after the second sentence in Section 300-22(c): "All of the metallic raceway components including the f i t t i n g s and connectors shall be made of ferrous materials." SUBSTANTIATION: Early failures of nonferrous f i t t i n g s and connectors in ferrous raceway systems during fires destroy the integrity of the system and permit more rapid transmission of decomposltion gases and smoke to other areas of the structure through walls, plenums or other spaces used for environmental air. Documentation of actual fires indicates early failures of nonferrous materials and retention of the integrity of ferrous components in at least the following fires: Henry Grady Hotel f i r e tests, Atlanta, Georgia (1972); Carlyle Apartment f i r e , Lakewood, Ohio (1974); Cedarwood Tower Apartment f i r e , Rochester, New York (1976); the Occidental Tower f i r e , Los Angeles (1976); and the Beverly HillsSupper Club (1977). PANEL ACTION: Reject. PANEL COMMENT: The Panel has not had access to referred f i r e reports and we do not know i f they included conduit and fittings made of aluminum. The proposal as written would prohibit the use of aluminum f i t t i n g s with steel raceways which is specifically allowed in other sections of the Code. VOTE ON PANELACTION: Unanimously Affirmative. Log # 1172 3- 61 - (300-22(b)): Reject Secretary's Note: I t was the action of the Correlating Committee that this proposal be reported as "Reject" because less than two-thirds of the members eligible to vote have voted in the affirmative and be referred to the NFPA Committee on Air Conditioning for comment. SUBMITTER: Walter G. Wells, American Iron and Steel Institute RECOM~NDATION: Add following as a new third sentence to Section 300-22(b): "Connections and f i t t i n g s used with electrical metallic tubing, intermediate metal conduit, and rigid metal conduit shall be made of the same base metal as the tubing or conduit." SUBSTANTIATION: There have been numerous instances of early failure, melting and disintegration of raceway components made of material other than ferrous in f i r e situations. Early failure in plenums or other spaces used for environmental air risks more rapid transmission of gases and combustibles. Documentation is available to i l l u s t r a t e early failure of nonferrous materials and retention of the integrity of ferrous components in at least the following fires: Henry Grady Hotel Fire Test, Atlanta, Georgia 1972); Carlyle Apartment Fire, Lakewood, Ohio (1974); Cedarwood ower Apartment Fire, Rochester, New York (1976); and the Occidental Tower Fire, Los Angeles, California (1976). PANEL ACTION: Accept in Principle. Add a new sentence to read: "Zinc alloy f i t t i n g s shall be prohibited." PANEL COM~NT: The Panel feels that this proposal satisfies the intent of the submitter. The proposal as written would prohibit th e use of aluminum f i t t i n g s with steel raceways which is specifically allowed in other sections of the Code. VOTE ON PANELACTION: AFFIRMATIVE: 0 NEGATIVE: Adelman, Cox, Lawry, Mottern, Schier, Whittington, Wood. Log # 1399 3- 63 - (300-22(c)): Reject Secretary's Note: I t was the action of the Correlating Committee that this proposal be referred to the NFPA Committee en Air Conditioning for comment. SUBMITTER: C. W. Beile, Allied Tube & Conduit Corporation RECOM#4ENDATION: Revise the f i r s t sentence as follows: Only noncombustible wiring methods, consisting of mineral-insulated...(balance of paragraph remains t ~ s~i~I ~ SUBSTANTIATION: The installation of unprotected co us materials capable of producing smoke or gases that may spread throughout a structure and inhibit the safe exist from burning buildings should be prohibited. I t is recommended that a more inclusive and consistant term be used. Please note definition of "noncombustible" submitted as proposal to 1984 NEC, Article 100. This definition is consistent with NFPA 90A, which will be correlated with NFPA 70 with regard to Ducts and Plenums as directed by the Standards Council actions. 115 I PANEL ACTION: Reject. PANEL COMt~NT: The current Code does not contain a definition of noncombustible. There is no documentation submitted indlcating the current test standards used for cables identified for use in these areas are inadequate. VOTE ON PANELACTION: AFFIRMATIVE: 6 NEGATIVE: Lawry. EXPLANATION OF VOTE: LAWRY: See comment for Proposal 3-59. I t should be obvious that the thrust of all these proposals is the limitation or actual elimination of the use of those MATERIALS, which when exposed either to the environment, temperatures in excess of their ratings, whether from normal or abnormal causes, or flame emit toxic gases, fumes or harmful chemicals. For years the electrical industry has not only permitted but also has encouraged the use of materials that f a l l into this category. These materials do emit toxic gases and do result in harmful chemicals when exposed to the varying atmospheres experienced in everyday living. For instance, i t is not an uncommon phenomenon to observe hydrochloric aciddripping out of a rigid steel conduit in which PVC conductors have been exposed to temperatures higher than their ratings or flame and water has been used to control the source of that heat or flame. There are documented experiences of this reaction where the acid was eating through the switch enclosure. When the inspector attempted to catch the acid in a t i n can so that he could have i t analyzed, i t ate right thru the can. What is startling about this phenomenon is the fact that we are told that the plastic people have known about i t for years and have never f e l t that this information should be publicized because the incidence would be so rare that i t was not worth alerting the electrical industry. In spite of their lack of concern many people in the industry and out of i t are aware of this possibility and the other ramifications of the decomposition of PVC and are deeply concerned. We are told over and over again that the amount of plastics and polyvinyl chlorides that are introduced in any building by the electrical installation is infinitesimal when compared with the total of all the other furnishings and building finishes. There are two errors in such statements. The f i r s t is corrected by the reports printed in Modern Plastics based upon the monthly Sales/Production report issued by SPI's Committee on Resin Statistics. According to their figures, published in January of 1981 there were 3,581,000 tons of resins converted into building materials in 1979. Of that 1,114,000 tons wore PVC Conduit. Is that to be considered infinitesimal? The figures for 1980 are just as revealing; 3,078,000 tons total, 938,000 tons in PVC Conduit. In addition to that there were 841,000 tons of resins converted into electrical/electronic plastics in 1979 of which 195,000 tons wore PVC. Likewise, in 1980 out of a total of 736,000 tons, there were 177,000 tons of PVC. These are NOT infinitesimal fractions! The second error is the attempt by the people, who spew forth this falacious claptrap, to hide the fact that we, who are responsible for formulating the National Electrical Code, have one prime responsibility, the safety of the people. We are completely and solely responsible for the electrical installation. We and only we must bear the responsibility for what is in the NEC. We are not in any, shape or form responsible for the furnishings nor the building finishes. Regardless of what others may introduce into the building, we are s t i l l responsible for those things that we permit or require in the electrical installation. We can never loose sight of the prime purpose of the NEC, " . . . t h e practical safeguarding of persons and property from the hazards arising from the use of e l e c t r i c i t y . " For many years a great number of knowledgeable and highly respected people in the scientific world have been aware of the fact that the use of certain materials and wiring methods, which by the very nature of their chemical composition, are certain to add significantly to the toxic gases and harmful chemicals in any f i r e situation. I t has been and s t i l l is their contention that the use of these materials should be curtailed or prohibited. We can no longer afford the luxury of sitting back waiting for someone else to take the f i r s t step. We cannot hide behind a disclaimer saying we know nothing about t o x i c i t y . I f we don't know, i t is because we haven't taken the time to read what is available on the subject or listen to what is being said from every direction. The numbers of peeple being killed in recent fires is staggering. The ratio of f i r e deaths to f i r e damage is astounding. I t is completely out of line with historical f l r e data. The number of people died 20 stories away from the closest flame in the MC~Mis unforgiveable. The number of people who died in that building after the f i r e was out, but while the hallways and stairwells were f u l l of toxic gases and smoke will never De known, but the fact that many did is additional reason for us to act. We cannot wait until other standards-writing bodies take the lead. We cannot wait until slow moving committees bring in the BODY COUNTS~ We can no longer ignore the warnings that have been made public in the form of test results from widely divergent groups, government, industry, scholastic and testing f a c i l i t i e s . Here is what just a few highly regarded scientists have to say about this matter: A report compiled by the Uniformed Firefighters Association in 1980 five years after the telephone company f i r e shows that of the 194 firefighters who received medical treatment at the time of the f i r e 71 reported permanent respiratory ailments. The unprotected cables that burned in that f i r e produced "billowing clouds of hydrogen chloride smoke." (American Lung Association Bulletin, (81)). "Large amounts of hydrogen chloride gas (HCL) are released by either HEATING or BURNINGPVC".* Log # 1468 3- 64 - (300-22(c)): Reject Secretary's Note: I t was the action of the Correlating Committee that this proposal be referred to the NFPA Committee on Air Conditioning for comment. SUBMITTERS: Leo Witz, Continental Electric Co. Bl-~BTll--F~-gan, Chicago, IL Fred Smith, Elgin, IL Jim Meehan, New Haven, CT Anton Ganje, North Dakota Kenny Gebert, Minneapolis, MN Bill Conrardy, The Conrardy Co Robert P. Brooks, Chicago, IL Paul Moore, Paducah, KY Les Rinder, Chicago, IL John W. Erickson, Boltswitch Inc. RECOMMENDATION: AmendSection 300-22(c) so as to read as follows: "(c). All other Spaces Used for Environmental Air. Only noncombustible wiring methods shall be utilized in the wiring of systems that are permitted to be installed in all other spaces that are used for the movement of environmental air. Electrical equipment that is normally permitted to be installed in concealed spaces in buildings shall be permitted to be installed in these spaces provided the wiring materials that are utilized are encased in noncombustible enclosures or raceways. The provisions of this sub-section apply, except as listed below and as required in (a) and (b) of this section, to any enclosed space inside of any structure that is used for environmental air-handling purposes. Exception No. I : Integral fan systems specifically identified for the purpose. Exception No. 2: This sub-section is not intended to include any habitable room or space inside of buildings. Exception No. 3: This sub-section is not intended to include the spaces between joists and studs in residential housing where the wiring passes through such spaces perpendicular to the long dimensions of the space. SUBSTANTIATION: At the present time the wording, "and other factory-assembled multiconductor control or power cables cable which is specifically listed for the use shall --- etc.," is the only deviation from the requlrement'that the wiring method be noncombustible. There is nothing in this sub-section that would indicate to the laboratory that would be "specifically listing" these types of cables what the intention of the Code is concerning them. I t is reasonable to assume that such cables, which would be replacing a noncombustible wiring method should also be noncombustible. I f this assumption is not true then why has the Code-Making Panel gone to the trouble of listing only noncombustible wiring methods? There is no mention of any of the combustible wiring methods that are certainly approved for use in other parts of the Code. We have seen some of the products that are "specifically listed" for this purpose and we have seen the results of tests that wore used to ascertain their acceptability by that testing agency. I t is our opinion that the tests are falacious and that the results based upon these unrealistic tests are useless. I t seems to us that we should face the problem head on. What we are, in the 1981 edition of the NEC as well as in the 1962 edition of the NEC when CMP 6 f i r s t made the basic change, really trying to accomplish is the containment of f i r e and smoke that originate in the electrical system to the smallest possible area. When you have a false ceiling space that extends over an entire floor of a building and you permit combustible wiring methods in that false ceiling space, you are not accomplishing the true intent of the Code. The smoke and products of combustion from the combustible wiring method are going to be spread throughout the entire floor and all other floors and spaces served by the same air-handling system. We are either going to shoulder the responsibility placed upon us by Section 90-I(a) of the Code or we are not! We are either going to be liable for the results of our decisions or we are not! I t is not an easy decision, but then neither is the death of the f i r s t person who dies because we have permitted combustible materials to be installed in air-handling spaces. The difference between, "low smoke producing" and "noncombustible" is not all that great in terms of dollars and cents, but there is a world of difference in the end result of the Code rule. We will be able to say that we have taken the steps necessary for the, "practical safeguarding of persons and property from the hazards arising from the use of e l e c t r i c i t y . " Additional substantiation for proposals made by William P. Hogan et. al. on Sections: 110-3(a)(8), 230-43, 300-22(b), 300-22(c), 338-2, 338-3, 340-5, 344-2, 347-2, 351-2, 352-21 and 370-23. 116 "In the case of a rapid electrical overload in PVC insulated wire, smoke which is usually the f i r s t indication of f i r e , is only noticeable AFTER significant quantities of HCL have been rel eased." * "Calculations show that f o r 100 pounds of PVC pyrolyzed (chemically decomposed by heat) in an apari~ent 8 feet X 25 feet X 50 feet (10,000 cubic feet) a concentration of HCL as high as 57,385 ppm could be reached, about 57 times the concentration that will cause lung edema on very short exposure." * Referring to the MQMf i r e deaths the Clark County Coroner-Medical Examiner reports, "The fact that the concentration of carboxyhemoglobin in most of the victims was not high enough to have caused death indicates that other toxic gases or smoke articles MUST also have been involved." * (carboxyhemoglobin is he result of carbon monoxide in the blood). • A Literature Study of the Combustion Hazards of PVC and ABS. Judith E. Hall and Eric L. Tolefson, University of Calgary. In a discussion concerning the Beverly Hills Supper Club Fire, Deborah Wallace, who is a Toxicologist and the President of Public Interest Scientific Consulting Service states the following about the causes of death at that f i r e , " - - - , the carboxyhemoglobin levels found during the autopsies showed that all assayed victims but one had concentrations well below lethal levels. Manywere as low as i0%." Yet they all died of something that they inhaled. There was a tremendous amount of PVC in that building! Jay A. Young, Ph.D., a Chemical Consultant has this to say, "Structural disintegration of PVC Conduit in a f i r e situation. Such disintegration allows the release of hydrogen chloride or phosgene, or both, formed from the decomposition of PVC insulation on the wiring inside, the conduit and confined inside the conduit until the conduit disintegrates." "The thermal decomposition of PVC has been observed at temperatures below 100 degrees C, although most studies show that the evolution of HCL in significant amounts requires temperatures of about 200-300 degrees C. That is, long before the PVC has reached the temperature at which i t will burn, well in advance of the tithe when any combustible structural components near PVC conduit would be l i k e l y to be burning in a f i r e situation." Dr. Young further states, "Hydrogen Chloride is an i r r i t a t i n g ~as At concentrations in air as low as 5ppm, i t causes choking in most people." Dr. Young continues, "Concentrations of lOOppm are rated as, "Immediately dangerous to l i f e and health" by OSHA and the National Institute f o r Occupational Safety and Health. Unless removed immediately from an atmosphere containing a concentration of lOOppm death by suffocation will follow." There are no less than 132 books, papers and articles available to you on this subject. You can rest assured that each will point out the t o x i c i t y of the products of combustion of PVC and of the t o x i c i t y of HCL which is produced simply by heating PVC Conduit or insulation. You may be able to ignore this information, but we can not. As far as we are concerned, the facts are in front of you and you must act. We have, - with these proposals. The problem is not going to go away by i t s e l f . Nor is i t going to lessen in intensity. You can be absolutely sure that i t and you will be in the public eye and in every form of mass news media as long as people are killed in f i r e s . I t will make headlines and bring more and more court cases, which will further highlight the shortcomings of the Code. Itseems to be a foolish course of action, or is i t INACTION, to wait until public furor forces us to change. I f we in NFPA through the NEC i n i t i t a t e the act, we at least retain the respect and confidence of the people we serve. I f we do not, you can be assured that those same people will have no respect f o r this organization or us. I t is f u t i l e to deny, or attempt to minimize, the presence of the harmful chemicals in the materials used to manufacture insulations and raceways that not only can, but do, emit toxic gases in amounts sufficient to cause instantaneous paralysis when exposed to temperatures in excess of their ratings, or f i r e . The peaceful attitudes of so many of their victims is grim testimony to the speed of these killers and the fact that the victims were t o t a l l y unaware of their impending fate. Our proposals are intended to minimize or eliminate the exposure of human beings to this peril. Note: I t is most important to understand that this proposal is not intended to do away with a l l , nor any, nonmetallic wiring method. This proposal and all others like i t that we have submitted f o r the 1984 edition of the NEC are intended to eliminate the MATERIALS which emit toxic fumes or gases under various conditions of use. I t is our opinion that the manufacturers of this equipment or these MATERIALS must prove that their products do NOT emit toxic gases or harmful chemicals under the. conditions specified. I t should not be the responsibility of the NFPA nor any Code-Making Panel to perform the tests or make the investigations that are needed to prove the presence of the toxic ases, fumes or harmful chemicals. PANEL ~OTION: Reject. PANEL COMMENT: See Panel Comment f o r Proposal 3-63. VOTE ON PANELACTION: AFFIRMATIVE: 6 ~EGATIVE: Wood. EXPLANATION OF VOTE: WOOD: I agree with the submitter's substantiation. The term combustible and noncombustible are used in the NEC. EX. Articles 410 and 725. ~ Log # 1173 3- 65 - (300-22(c)): Reject Secretary's Note: I t was the action of the Correlating Committee that this proposal be reported as "Reject" because less than two-thirds of the members eligible to vote have voted in the affirmative and be referred to the NFPACommittee on Air Conditioning for comment. SUBMITTER: Walter G. Wells, American Iron and Steel Institute RECOMI4-NDATION: "Connections and f i t t i n g s used with electrical metallic tubing, intermediate metal conduit, and rigid metal I conduit shall be made of the same base met'al as the tubing or conduit ." SUBSTANT~TION: There have been numerous instances of early f a i l u r e , melting, and disintegration of raceway components made of material other than ferrous, in f i r e situations. Early failure in plenums or other spaces used for environmental air risks more rapid transmission of gases and combustibles. Documentation is available to illustrate early failures of nonferrous materials and retention of the integrity of ferrous components in at least the following f i r e s : Henry Grady Hotel Fire Test, Atlanta, Georgia (1972); Carlyle Apartment Fire, Lakewood, Ohio {1974); Cedarwood Tower Apar~ent Fire, Rochester, New York (1976); and the Occidental Tower Fire, Los Angeles, California (1976). PANEL ACTION: Accept in Principle. Add a new sentence: "Zinc alloy f i t t i n g s shall be prohibited." PANEL COMMENT: See Panel Comment f o r Proposal 3-61. VOTE ON PANELACTION: AFFIRMATIVE: 0 NE~TIVE: Adelman, Cox, Lawry, Mottern, Schier, Whittington, Wood. EXPLANATION OF VOTE: ADELMAN: Need to receive additional documentation to substantiate the claims of the proposer of early failure of nonferrous materials in the submitter's reference fires. Fire reports received of the Carlyle Apartment f i r e , and the Cedarwood Tower f i r e , make no mention of early f a i l u r e of nonferrous electrical components. Reports of the Henry Grady Hotel f i r e , and the Occidental Tower f i r e , have not been submitted to the Panel members. COX: I do not believe t h a t the substantiation adequately supports the p r o h i b i t i o n of t h i s widely used m a t e r i a l . LAL~RY: See comment f o r Proposal 3-61. MOTTERN: Same as that f o r Proposal 3-61. SCHIER: I voted n e g a t i v e l y on Proposal 3-61 a f t e r reviewing public comment from L.E. Mason Co., the Halex Company and the Zinc I n s t i t u t e Inc. WHITTINGTON: This proposal is inconsistent with the wording of Section 90-1(a), the substantiation used with respect to noted f i r e s has been found not to contain references supporting the proposal, and other studies have concluded that the p r o h i b i t i n g of zinc a l l o y f i t t i n g s is not j u s t i f i e d . WOOD: This is no substantiation that the use of zinc alloy fittings has added to r i s k or the transmission of combustibles. Log # 642 3-66 - (300-22(c)): Accept Secretary's Note: I t was the action of the Correlating Committee t