Pumping Technology FLOWFLEX COLD WATER BOOSTER SETS INSTALLATION AND OPERATION MANUAL IMPORTANT INFORMATION These instructions must be read and understood before installing, commissioning, operating or maintaining the equipment. SMEDEGAARD PUMPS LTD • 10 Beech Business Park • Bristol Road • Bridgwater • Somerset • TA6 4FF Tel: 01278 458686 • Fax: 01278 452454 Email: info@smedegaard.co.uk • www.Smedegaard.co.uk Contents 1. Warranty................................................................................................6 1.1 TERMS OF WARRANTY 2. Safety and environment........................................................................ 6 2.1 GENERAL 2.2 USERS 2.3 SAFETY PROVISIONS 2.3.1. Labels on the product 2.4 SAFETY PRECAUTIONS 2.4.1. 2.4.2. During normal use During installation, maintenance and repair 2.5 ENVIRONMENTAL ASPECTS 2 2.5.1. 2.5.2. General Dismantling 3. Manual Introduction..............................................................................8 3.1 PREFACE 3.2 ICONS AND SYMBOLS 4. Identification, service and technical support......................................8 4.1 IDENTIFICATION, SERVICE AND TECHNICAL SUPPORT 4.2 SUPPLEMENTARY DOCUMENTATION 5. Introduction...........................................................................................9 5.1 GENERAL 5.2 INTENDED USE 5.3 WORKING RANGE 6. Functioning............................................................................................ 9 6.1 STANDARD OPERATION 6.1.1. 6.1.2. 6.1.3. 6.1.4. 6.1.5. 6.1.6. Settings RS485 Water surge protection - GaardExe SPM WSD-Sensor (option for use with base plate mounted vessels) Temperature-sensor (option) Dry Run Protection Pumping Technology 7. Transport.................................................................................................................................10 7.1 TRANSPORT 7.2 STORAGE 7.2.1. 7.2.2. Preparations for storage Inspection during storage 8. Installation...............................................................................................................................10 8.1 SETTING UP THE INSTALLATION 8.2 PUMP INDICATORS 8.3 ELECTRICAL INSTALLATION 8.4 COMMISSIONING 8.4.1. In an open or closed circuit with sufficient supply pressure 9. Control panel..........................................................................................................................12 9.1 TYPES 9.2 DESCRIPTION - CP 9.3 DESCRIPTION - MH 9.4 SINGLE PHASE CP PANEL WIRING DIAGRAM 9.5 THREE PHASE CP PANEL WIRING DIAGRAM 9.6 SINGLE PHASE MH WIRING DIAGRAM 9.7 THREE PHASE MH WIRING DIAGRAM 9.8 PUMP WIRING 10. FlexDrive Set-Up – Booster Sets...........................................................16 10.1 PARAMETER NAVIGATION. 10.2 SETTINGS.THOSE IN ITALIC MAY NEED TO BE CHECKED/ALTERED ON SITE. 10.3 FACTORY SETTINGS 10.4 ERROR CODES 10.5 THREE PHASE FLEXDRIVE WIRING 10.6 SINGLE PHASE FLEXDRIVE WIRING 10.7 MULTI- DRIVE CONNECTION 3 Pumping Technology 11. Maintenance............................................................................................................................23 11.1 INTRODUCTION 11.2 LUBRICATION 11.3 MAINTAINING THE PUMP FOR AN EXTENDED PERIOD OF NON- OPERATION 11.4 PUMP FAULT TABLE 11.5 RS-485 COMMUNICATION PROTOCOL 11.6 RS485 CONNECTIONS – 3 PHASE FLEXDRIVES ONLY. 11.7 FAILURE TABLE WSD-SENSOR(OPTION) 11.8 GAARDEXE SPM SET UP 11.9 DECLARATION OF CONFORMITY (IIA) 4 Pumping Technology 5 Pumping Technology 1. Warranty 2. Safety and environment 1.1 2.1 TERMS OF WARRANTY The warranty period is as shown in our general terms and conditions of sales. Other terms of warranty have been included in the general terms of delivery, which are available upon request. )) ATTENTION - Modifications or alterations of the product supplied are only permitted after consultation with the manufacturer. Original spare parts and accessories authorised by the manufacturer ensure safety. The use of other parts can invalidate any liability of the manufacturer for consequential damage. )) ATTENTION - The warranty relating to the operating reliability and safety of the product supplied is only valid if the product is used in accordance with its designated use as described in the following sections of this manual. The limits stated in the data sheet must not be exceeded under any circumstances. The warranty becomes invalid if one or more of the points below occur. The buyer makes un-authorised modifications to the equipment. The buyer carries out repairs or has these carried out by a third party during the warranty period and without authorisation from Smedegaard. The product has not been handled or maintained properly. The product has un-authorised non original Smedegaard spare parts fitted. 6 Smedegaard remedies defects under warranty if the points below are observed. Defects are caused by flaws in the design, the materials or the manufacture. The defect has been reported within the warranty period. Pumping Technology GENERAL This Smedegaard product has been developed using state-of-the-art technology; it is manufactured with utmost care and subject to continuous quality control. Smedegaard does not accept any liability for damage and injury caused by not observing the directions and instructions in this manual. This also applies in cases of carelessness during the installation procedure, use and maintenance of the product. Non-compliance with safety instructions can jeopardise the safety of personnel, the environment and the product itself. Non-compliance with these safety instructions will also lead to forfeiture of any and all rights to claims for damages. For example, in particular non-compliance can result in: Failure of important pump/system functions. Failure of prescribed maintenance and servicing practices. Injury to persons by electrical or mechanical causes. Depending on specific activities, extra safety measures may be required. Contact Smedegaard if a potential danger arises during use. )) )) ATTENTION - The owner of the product is responsible for compliance with the local safety regulations and internal company guidelines. ATTENTION - Not only must the general safety instructions laid down in this chapter on "Safety" be complied with, but also the safety instructions outlined under specific headings 2.2 USERS All personnel involved in the operation, maintenance, inspection and installation of the product must be fully qualified to carry out the work involved. Personal responsibilities, competence and supervision must be clearly defined by the operator. If the personnel in question are not already in possession of the required know-how, appropriate training and instruction must be provided. If required, the operator may commission the manufacturer / supplier to take care of such training. In addition, the operator is responsible for ensuring that the contents of the operating instructions are fully understood by the responsible personnel. 2.3 SAFETY PROVISIONS The product has been designed with the greatest possible care. Original parts and accessories meet the safety regulations. Modifications in the construction or the use of non-original parts may lead to a safety risk. )) ATTENTION - Make sure that the product operates within its working range. Only then is the product performance guaranteed. 2.3.1. LABELS ON THE PRODUCT The icons, warnings and instructions applied to the product are part of the safety provisions. The labels may not be removed or covered. Labels must remain legible during the entire life of the product. Replace damaged labels immediately. 2.4 SAFETY PRECAUTIONS 2.4.1. DURING NORMAL USE Contact the local electricity company for questions about the power supply. Shield parts, that can become hot in such a way, that direct contact is impossible. When applicable, always replace deformed coupling protection plates to protect the coupling, before putting the pump into use. Make sure that the coupling protection plates are never in contact with the running coupling. Always close the terminal box. 2.4.2. DURING INSTALLATION, MAINTENANCE AND REPAIR Only authorised personnel may install, maintain and inspect the product and repair electrical components. Observe the local safety regulations. ,, !! !! WARNING - Always disconnect the electrical supply to the product first, before installation, maintenance and repairs. Secure this disconnection. WARNING - Surfaces of a pump can be hot, after continuous operation. WARNING- Make sure that no one can come in contact with rotating components. Pumping Technology !! !! !! 2.5 WARNING - Handle a pump with dangerous liquids with the utmost care. Avoid danger for people or the environment when repairing leakages, draining liquids and venting. It is strongly recommended to place a relief barge under the pump. WARNING - Immediately following completion of the work, all safetyrelevant and protective devices must be re-installed and / or re-activated. WARNING - Please observe the commissioning instructions before returning the product to service. ENVIRONMENTAL ASPECTS 2.5.1. GENERAL The products of Smedegaard are designed to function in an environmentally friendly way during their entire life. Therefore, when applicable, always use biodegradable lubricants for maintenance. !! ENVIRONMENTAL INSTRUCTION - Always act according to the laws, by- laws regulations and instructions with respect to health, safety and the environment. 2.5.2. DISMANTLING Dismantle the product and dispose of it in an environmentally friendly way. The owner is responsible for this. !! ENVIRONMENTAL INSTRUCTION - Ask at the local government about the reuse or the environmentally friendly processing of discarded materials. 7 3. Manual Introduction 3.1 PREFACE This manual contains important information for reliable, proper and efficient operation of the booster set. Compliance with the operating instructions is of vital importance to ensure reliability and a long service life of the product and to avoid any risks. The first chapters contain information about this manual and safety in general. The following chapters provide information about normal use, installation, maintenance and repairs of the product. Read the document. Accurately follow the directions and instructions. Never change the sequence of the operations to be carried out. Keep this manual or a copy of it together with the logbook in a fixed place near the product which can be accessed by all personnel. 3.2 4.1 IDENTIFICATION, SERVICE AND TECHNICAL SUPPORT Please quote this information in all queries, repeat orders and particularly when ordering spare parts. If you need any additional information or instructions exceeding the scope of this manual or in case of damage please contact Smedegaard. 4.2 SUPPLEMENTARY DOCUMENTATION In addition, apart from this manual, we can also supply an O&M for the HIL pumps: ICONS AND SYMBOLS In this document the following icons and symbols are used. )) On some models, the sticker may be found inside the control panel. !! ,, !! Smedegaard Pumps Ltd 10 Beech Business Park Bristol Road Bridgwater Somerset TA6 4FF United Kingdom Is used to indicate SAFETY INSTRUCTIONS. Non-observance may lead to faulty functioning or damage to the product. 8 4. Identification, service and technical support ENVIRONMENTAL INSTRUCTION Remarks with respect to the environment. WARNING - Electrical danger. Safety sign according to IEC 417 - 5036 WARNING - Operations or procedures, if carried out without caution, may cause personal injury or damage to the product. General hazard sign according to ISO 7000 0434 Pumping Technology The following address data are available for service and technical support: t +44-1278-458686 f +44-1278-452454 www.smedegaard.com info@smedegaard.com 5. Introduction 5.1 GENERAL As well as the booster set O&M a detailed manual the FlexDrive is also available on request. 5.2 Any other use of the booster set is not in conformity with its intended use. Smedegaard does not accept any liability for any damage or injury resulting from this. The equipment has been produced in accordance with the current standards and guidelines. Use the equipment should only be used while in a good state of repair and exclusively for its deigned use. See below. The intended use as laid down in EN 12100-1 is the use for which the product is intended according to the specifications of the manufacturer. The use of the product has been described in the available documentation and information. Always observe the instructions as given in the installation and operating instructions. When in doubt the product must be used as becomes evident from its construction, version and function. WORKING RANGE Working conditions for the FlowFlex range of booster sets: Table 1. Specification of the working range Type Maximum ambient temperature [˚C] Liquid temperature [˚C] Maximum working pressure [Bar] Minimum suction pressure Type FlowFlex Application (Drinking water) supply systems. 6. Functioning INTENDED USE The FlowFlex range of booster sets is designed for boosting the pressure of cold potable water within the working range of the set. 5.3 Table 2. Specific application FlowFlex 40 -15 to 40 10 Unless indicated otherwise Not cavitating, suction pressure plus pump pressure, must never be higher than the maximum working pressure. 6.1 STANDARD OPERATION The FlexDrive is a wall or pump mounted inverter that, if it is to be pump mounted should only be done so with purpose made parts. The inverter is self cooling either by natural convection/radiation or via the built in fan(s). Each inverter utilizes the signal from a ‘master’ pressure transducer installed on the pump outlet (or from another source) to vary the speed of the pump motor. Should the master transducer fail electrically then (if fitted) another transducer will take over. The FlexDrive inverters can be interconnected with each other, up to 6 pumps can be controlled in this way. On multiple pump booster sets the lead pump is alternated based on the run time of each pump. If a single pump is not capable of meeting the duty then further pumps, as available, will be bought into operation. Whether sized for duty/assist or duty/standby, the sets are always configured to run duty/assist. 6.1.1. SETTINGS The inverters are programmed and tested prior to dispatch. It should only be necessary to check/alter the set pressure. The alteration to the set pressure in one drive will be transmitted to any other interconnected drives. 6.1.2. RS485 When fitted, RS485 communication is available (3 phase drives only). The communication protocol is listed on page 25 of this document. 6.1.3. WATER SURGE PROTECTION An optional water surge protection module (SPM) is available. This module protects the system, on initial start-up and in the event of a power failure, from the effects of water hammer caused by the pumps operating at full speed due to the low pressure caused by the system not being full. The full set-up is described on page 27 of this document. For booster sets fitted with the GaardExe module, for the warranty to be validated, the set must be commissioned by Smedegaard. Pumping Technology 9 6.1.4. WSD-SENSOR This device can be fitted to monitor the flow of water in and out of the pressure vessel. The WSD control module can be used to send an alarm signal based on: Insufficient water refreshment in the vessel. Damaged diaphragm. Loss of vessel air charge. 6.1.5. TEMPERATURE-SENSOR (OPTION) This is an option for use with the WSD device and is used to monitor the temperature of the vessel. This is especially important in areas with a high ambient temperature. Further information can be found on page 26. 6.1.6. DRY RUN PROTECTION The FlexDrives incorporate electronic dry run protection based on the system pressure. However, the booster set control panels are fitted with terminals to allow for the fitting of a low water level sensor in the suction manifold or break tank. As electronic dry run protection is not suitable for all systems then float switch protection is the advised option. 7.2 STORAGE 7.2.1. PREPARATIONS FOR STORAGE Drain the set if there is a danger of frost. Store the installation in a frost-free environment. Protect from the weather. Protect from dust and other debris Protect from physical damage. 7.2.2. INSPECTION DURING STORAGE Turn the motor shaft(s) every three months. This protects the seals from seizure. After a storage period of six months or longer, inspect the installation before using it again. 8. Installation 8.1 SETTING UP THE INSTALLATION 7. Transport 7.1 TRANSPORT !! !! 10 WARNING Only lift using suitable equipment such as a fork lift truck and taking care to protect the base of the booster set. WARNING - Only qualified people should be involved with the lifting/ transportation of this equipment. DO NOT USE THE MANIFOLDS TO LIFT BOOSTER SET. Transport the booster set on a pallet. Make sure that the booster set is stable. Protect from the weather. Room – Should be clean, dry, dust free, frost free and properly lit. The FlowFlexx range of cold water booster sets is designed for installation into a suitable plant room, outbuilding or similar. The set should be so positioned as to enable maintenance access from all sides and from overhead. There should be proper provision for drainage in the event of spillage during maintenance or in case of a leak. Foundation – Should be smooth, level and large enough to entirely support the base of the booster set. Pumping Technology Connect the water supply to the booster set suction (indicated with sticker). The suction head should be sufficient to enable the priming of the pump and to prevent the ingress of air due to vortexing during normal operation. It should be ensured that the supply is capable of meeting the demands of the system. Connect the booster set discharge (indicated with a sticker) to the cold water demand pipe work In order to reduce the sound level to a minimum, proceed as follows: Position the booster set on anti-vibration (AV) mounts. Make sure the supply and discharge lines are correctly installed and bracketted. Fit flexible pipe connectors to the booster set inlet and discharge manifolds (option). Insert a filter in the water supply line in case of pollution/debrie. Manifolds must be connected free of tension. Diameter of the supply lines of sufficient size. )) ATTENTION Use dry run protection. Fit an isolating valve on the suction and discharge. 8.2 PUMP ROTATION AND FLOW INDICATORS See diagram below: Vent Plug Direction of Rotation Drain Plug 8.3 ELECTRICAL INSTALLATION !! WARNING Only a qualified person should be allowed to make the electrical connections. Pumping Technology Electrical connections Ensure the electrical supply is suitable for the motor rating. Check the electrical diagrams to confirm the wiring of the motors. Connect the set using an interruptible supply. After completion of the wiring, close the control panel. 8.4 COMMISSIONING !! WARNING - The pumps should never be run dry. Before commissioning the system: Rinse the booster set and the rest of the pipework thoroughly prior to use. 8.4.1. IN AN OPEN OR CLOSED CIRCUIT WITH SUFFICIENT SUPPLY PRESSURE 1. Close the suction shut-off valve and the outlet shut-off valve. 2. Remove the vent plug. 3. Gradually open the suction shut-off valve until the liquid flows from the fill plug opening. 4. Close the plug opening. 5. Fully open the suction shut-off valve. 6. Check the rotational direction of the pump. 7. Slowly open the outlet valve to allow the system to stabilise. )) ATTENTION - Seen from the suction end, the pump should rotate anti-clockwise. In case of a 3-phase motor the rotation direction can be changed by exchanging two of the three supply cables. !! WARNING - Always check the direction of rotation. This can be checked by watching the fan. 11 8.4.2. VESSEL PRESSURE For a correct functioning of the installation the supply pressure in the pressure vessel should be 20-50 kPa lower than the pump cut-in pressure. Proceed as follows to determine the supply pressure: 9. Control panel 9.1 The control panel is either an IP66 enclosure (suffix CP) or an IP55 MCB housing (suffix MH) 9.2 A 1. Measure the pressure (A) in the vessel when there is no pressure on the waterside (B). 2. Fill the vessel with nitrogen or air. Use preferably nitrogen. WARNING - Before using the installation, first put the pressure vessel under pressure. ON COMPLETE PACKAGED BOOSTER SETS THE PRESSURE WILL NORMALLY BE FACTORY SET IN ACCORD WITH THE INFORMATION PROVIDED AT ORDER STAGE. THE PRESSURE SHOULD ONLY REQUIRE CHANGING IF THE SITE REQUIRED BOOSTER SET OPERATING PRESSURE IS DIFFERENT FROM FACTORY SETTING. THE VESSEL PRESSURE SHOULD BE REGULARLY CHECKED. 12 Pumping Technology DESCRIPTION - CP RANGE The panels fitted to the FlowFlex range of booster sets contain a panel MCB, pump MCB’s, low water terminals, power in – power out terminals and either common fault terminals or, if fitted, RS485 connections. Common fault terminals and RS485 are only available on 3 Phase sets.The panel door is fitted with a door interlocked isolator and power on/low water lamps. B !! TYPES The inverter/booster set status displays are on each inverter and the setting up of the booster set is carried out via the inverters. 9.3 DESCRIPTION - MH The MCB housing fitted to the FlowFlex Range of Booster Sets contains the pump MCB's Power Isolating MCB, Power In - Power Out Terminals, Low Water Contacts. The inverter/booster set status displays are on each inverter and the setting up of the booster set is carried out via the inverters. 9.4 SINGLE PHASE CP PANEL WIRING DIAGRAM 9.5 THREE PHASE CP PANEL WIRING DIAGRAM NOTE: THE ABOVE WIRING DIAGRAM IS FOR A TWIN PUMP BOOSTER SET, FOR EACH ADDITIONAL PUMP THE TERMINALS 4/5/6 WILL BE DUPLICATED AND NUMBERED 7/8/9 FOR A TRIPLE PUMP SET. TERMINALS 10 TO 20 THEN BEING NUMBERED 13 TO 23. 13 Pumping Technology 9.6 SINGLE PHASE MH WIRING DIAGRAM 14 Pumping Technology 9.7 THREE PHASE MH WIRING DIAGRAM 15 Pumping Technology 9.8 PUMP WIRING Each drive is connected to the pump terminals U, V and W. The direction of rotation should be checked, if it is not correct then either, switch any two of the wires to the pump terminals U V W or, reverse the direction of rotation using menu option Dr-20 in the FlexDrive. 10. FlexDrive Set-Up Booster Sets If fitted, an SPM Module may slow the setting of the drives. To prevent this it should be disabled during the set-up then re-enabled for normal use. Refer to page 27. If the drives have been supplied as part of a booster set then they will have been configured for that use. In which case it may only be necessary to refer to section 8.3 and to check the pressure setting, refer to section 10.3. The Factory set-up instructions are provided for information only but, may be required in the event of the replacement of a drive. 10.1 PARAMETER NAVIGATION. When the power is first applied, the drive will normally be in the ‘St’ menu. To change the menu, press and hold the up/down keys, together, for approx. 3 seconds. The menu will change to ‘Pr’, release the buttons. Repeat to get to ‘Dr’ and repeat to get back to ‘St’. Use either the up or down key to navigate to the required parameter. Press the set/reset key to select the parameter, this will cause the parameter to flash. Use the up or down key to alter the parameter then press set/reset to save the change. 16 When the settings have been altered, navigate to and leave in ‘St’. ‘Dr’ – Drive related settings. ‘St’ – Status display. ‘Pr’ – Pump related settings. Pumping Technology 10.2 SETTINGS.THOSE IN ITALIC MAY NEED TO BE CHECKED/ALTERED ON SITE. ENSURE THE SET HAS BEEN CORRECTLY INSTALLED AND THAT THE NECESSARY WATER CONNECTIONS HAVE BEEN COMPLETED BEFORE TURNING ON THE INVERTERS. ALSO ENSURE THE SET HAS BEEN VENTED AND PRIMED. Settings can only be altered with the FlexDrives in ‘STOP’ mode, see section 10.1. Only the pressure setting will be communicated to other attached drives. All other settings need to be programmed into each drive. If multiple drives are provided then select a ‘Master’ drive. Under the cover of each drive (ensure the power is off before removing the cover) there are 2 switches.’ PNP/NPN’, leave on NPN. ‘Open-Short’, for the master (or only) drive, set this to ‘Short’. For the other ‘slave’ drives, set this to ‘Open’. Replace the covers and switch on the set. Ensure there is power to the drive(s). It/they should be in St mode, if not then navigate it/ them to St mode. LONG PERIODS WITHOUT POWER, SUCH AS STORAGE, MAY LEAD TO A LOSS OF THE SETTINGS 10.3 FACTORY SETTINGS When in St mode the system pressure P will be displayed on all the drives and will show the static pressure. On the master drive hold set/reset for approx. 2 seconds, display will change to d and the parameter will flash. Use the up/down keys to alter the setting to the required pressure (in Bar). Set/reset to save. This setting should be transmitted to any slave drives. The following settings are required to be checked/ altered on both master and slave drives. Pr-50 Single drive (default) 0. Multiple drives set to 1. Pr-51 In each drive set a different ’address’. 1,2 etc. Pr-01 Set the motor kW as found on the motor label. Pr-02 Default 1. label. (Repeat of Pr-01) Dr-11 2 pole (2900rpm) motor set to 1, 4 pole (1450rpm) motor set to 2. Dr-12 From the motor label, set the 3phase amps. 1 phase supply – use 3x230V amps, 3 phase supply – use 3x400V amps. Dr-13 From the motor label, set the speed. ie 2850rpm. Pr-03 Transducer range, default 16 bar, Smedegaard normal setting 10 bar. Dr-14 Motor voltage. For 3 phase drives then will typically be 400 volts and for 1 phase drives will typically be 230V (230 3 phase). Pr-04 Used to cailibrate the transducers against (ie) a pressure gauge. Set +/- tenths of a bar. Dr-17 Motor supply Hz, default 1 (60Hz), change to 0 for 50Hz. Pr-12 Default 0.3. Allowed pressure drop (bar) before the pump starts. Can effect the vessel charge pressure. Dr-20 To reverse motor direction of rotation. 1 or 0. Pr-54 Default 12, set to 1. Dr-23 Default 6 seconds. Pr-70 Default setting 2 bar (above the set pressure). High pressure alarm. Dr-30 Default 1. Pr-71 Assuming the use of a float switch in the break tank, set to 0. 1 if a float switch is not being used. Dr-43 Default 60, normally set to 50Hz. Pr-74 Time for low water level to react, factory set to 30 seconds. Pr-75 Low pressure trip setting. Factory set to 0.3 bar. Pr-76 Default 0 for low pressure sensing, set to 1 for level switch low water sensing. Pr-77 Default 2 seconds. Pr-81/85 Last 5 error codes, most recent in 81. Pr-86 Default 0, set to 1 to clear error log. Automatically resets to 0. Pr-90 Factory reset of Pr memory. Dr-01 Default 0 for operation control from the drive, 1 for remote operation command. Dr-02 Default 0 Dr-10 Set the motor kW as found on the motor Pumping Technology Dr-22 Default 3 seconds. Dr-32 Overload trip time set to 5 Dr-90 Factory reset of Dr menu. Navigate back to St mode. ENSURE THE SET HAS BEEN CORRECTLY INSTALLED AND THAT THE NECESSARY WATER CONNECTIONS HAVE BEEN COMPLETED BEFORE TURNING ON THE INVERTERS. ALSO ENSURE THE SET HAS BEEN VENTED AND PRIMED. The system pressure P will be displayed on all the drives and will show the static pressure. On the master drive hold set/reset for approx. 2 seconds, display will change to d and the parameter will flash. Use the up/down keys to alter the setting to the required pressure (in Bar). Set/reset to save. This setting should be transmitted to any slave drives. 17 10.4 ERROR CODES Display Content Er-01 Er-02 Er-03 Er-04 Er-05 Er-06 tSF tOP tLP tUL tASH tOC Er-07 Er-08 Er-09 Er-10 Er-11 Er-12 Er-13 Er-14 Er-15 SOC tMOH tOH tLv tOv tOL tdOL tGF tldE Er-16 Er-17 Er-18 Er-20 Er-21 tCE tIO tOO tES tLt Description Pressure sensor error High pressure alarm Low pressure alarm Low level alarm Drive arm short trip Drive H/W over current trip Drive H/W over current restriction trip Motor overheat (TMOH) Drive overheat trip DC-Link low voltage trip DC-Link high voltage trip Overload operation trip Drive overload operation trip Ground trip Communication IC duplication trip Communication error Input error Output error External fault input Allowable time elapsed Restarting O O O O X O O O O O O O O X X X X X X X Remarks 7-2 7-3 7-4 7-5 7-5/6 7-6/7 7-8 7-7 7-8 O - Auto Reset X - Does not Auto Reset 7-2 7-3 7-4 18 7-5 7-5/6 7-6/7 7-8 To reset Manually, if in PR press Set/Reset twice or once if in ST. If fault still exists the alarm will again trigger. Er-01 is a sensor error indication but may also be caused by a faulty drive. Er-05 can be caused by entering a too short acceleration/deceleration time into Dr-22 but, can also be caused by damage to the motor windings. Er-06 is similar but usually occurs during the free running of the motor. Er-07 may be caused by Er-05 Er-08 may be caused by an under-rated drive or motor. Er-09, problem with the motor cooling fan or high ambient temperatures. Er-10 is an indication of a low supply voltage. Er-11 is an indication of a high supply voltage or, the motor deceleration time (Dr-23) is to short for the pump/motor rating. Er-12 trips when the motor over-load is exceeded for more than a pre-set time. Check motor plate for current rating, check Dr-10 for current setting, Dr-12 for motor rating, Dr-30 for trip time Dr31 for trip level, Dr-32 for trip time. Er-13. Load is greater than the drive capacity. Er-14 Drive out-put cable or motor winding short circuit. Pumping Technology 7-7 7-8 Er-15. See Pr-51, occurs when multiple drives have the same ID. Er-16. Fault CAN communication. May be faulty connection or faulty drive. Er-17. Output wiring fault, usually terminals Er-18. Output wiring fault, usually terminals. Er-20. External signal error. Er-21. Time elapsed contact Smedegaard. 19 Pumping Technology 10.5 THREE PHASE FLEXDRIVE WIRING MCCB R U S V T W MOTOR FG Control Circuit 24V S1P P1 S1N CG PNP NPN S2P ESTOP NPN CONNECTION Input frequency S2N CG LV1 V1 LV2 0-10V VGND 4-20mA CANH I1 OPEN SHORT CG CAN Communication Terminal CANL Run condition Output Output AT CT RUN BT RS 485 (Optional) 485_TX AT CT BT 20 Pumping Technology CG FAULT 485_RX RS 485 Communication Terminal (Optional) 10.6 SINGLE PHASE FLEXDRIVE WIRING 21 Pumping Technology 10.7 MULTI- DRIVE CONNECTION 22 Pumping Technology 11. Maintenance 11.1 INTRODUCTION ,, WARNING: Observe the general safety precautions for installation, maintenance and repair. Regular maintenance is necessary for the correct operation of the installation. For maintenance of the installation, please contact your supplier. A draft maintenance contract is available upon request. 11.2 LUBRICATION Sealed for life bearings, no lubrication required. 11.3 MAINTAINING THE PUMP FOR AN EXTENDED PERIOD OF NON-OPERATION Turn the shaft every three months. This protects the seals from seizure. To protect the pump if there is a risk of frost. Proceed as follows: 1. Close all pump valves. 2. Drain each pump and/or the system. 3. Remove all plugs from the pump. 4. Open the shut-off and fill/air vent plug, if present. 23 Pumping Technology 11.4 PUMP FAULT TABLE ,, WARNING - Observe the general safety precautions for installation, maintenance and repair. Problem Leakage along the shaft. Pump is vibrating and makes a lot of noise. Possible cause Shaft seal worn. Pump has been operated without water. There is no water in the pump. No water supply. Bearings of pump and/or motor defective. Installation / pump does not start. Hydraulic assembly defective. Pump rotates in the wrong direction. No voltage on the connecting clamps. Thermal motor safety switch triggered. Run-dry protection triggered. Pressure set point incorrect. Drive error. 24 Installation / pump sup- There is air in the pump. plies insufficient capacity Pump rotates in the and/or pressure. wrong direction. Capacity of water meter in the supply line is too small. System filter. Pumps continuously start and stop. Pumping Technology Outlet and/or inlet shutoff valve is closed. Membrane switch vessel(s) leaky or incorrect pressure. Possible solution Replace the shaft seal. Replace the shaft seal. Checkpoints Check the pump for dirt. Fill and de-aerate the pump. Restore the water supply. Check if the supply pipes are not clogged. Have the bearings replaced by a certified company. Replace the hydraulic assembly. Switch two phase wires. Check the power supply. Check there is water in the supply tank and the supply to the booster set is not blocked. Reset the thermal motor safety. Contact the supplier, if this problem occurs more often. Restore the water supply. Reset the installation. Adjust the pressure setpoint. Reset drive and note the error code. Vent the pump. Change two phase wires on the main switch. Increase the capacity of the water meter. Clean filter or check filter flow capability and change if necessary. Open both shut-off valves. Have your supplier check the installation. 11.5 RS-485 COMMUNICATION PROTOCOL Address (Decimal) 4096 Addrress 4097 0x1001 The State of Sytem Operation 4098 4099 0x1002 0x1003 4100 0x1004 Setting Pressure Discharge Pressure (Differential Pressure) Stop state Inverter 4101 0x1005 Ready state Inverter R 4102 0x1006 Run State Inverter R 4103 0x1007 System Fault Content 4104 0x1008 Inverter Fault 4111 4112 4113 4114 4115 4116 0x100F 0x1010 0x1011 0x1012 0x1013 0x1014 Inverter Inverter Inverter Inverter Inverter Inverter 0x1000 Parameter program version 1 Output 2 Output 3 Output 4 Output 5 Output 6 Output Scale 0.01 Unit R 0.01 0.01 bar bar R/W R R R 0.1 0.1 0.1 0.1 0.1 0.1 % % % % % % 11.6 RS485 CONNECTIONS – 3 PHASE FLEXDRIVES ONLY. The RS485 connections are via: AUX1 (TX) AUX2 (RX) CG - Common Connections should be made using 3 core screened cable. Pumping Technology R/W R R R R R R R Content 0~65535 0 : STOP, 1 : READY(inverter EN and output zero), 2 : RUN(inverter EN and output non-zero), 3 : Fault(system fault) 0~10000 0~10000 Content for each bit(1:stop / 0: none) Bit 0: INV 1 Bit 1: Inv 2 Bit 2: Inv 3 Bit 3: Inv 4 Bit 4: Inv 5 Bit 5: Inv 6 Content for each bit(1:ready / 0: none) Bit 0: INV 1 Bit 1: Inv 2 Bit 2: Inv 3 Bit 3: Inv 4 Bit 4: Inv 5 Bit 5: Inv 6 Content for each bit(1:Run / 0: none) Bit 0: INV 1 Bit 1: Inv 2 Bit 2: Inv 3 Bit 3: Inv 4 Bit 4: Inv 5 Bit 5: Inv 6 Content for each bit Trip content Bit 0: Sensor Fault Bit 1: High Pressure Fault Bit 2: Low Pressure Fault Content for each bit Bit 0: Inv 1 Bit 1: Inv 2 Bit 2: Inv 3 Bit 3: Inv 4 Bit 4: Inv 5 Bit 5: Inv 6 0~1000 0~1000 0~1000 0~1000 0~1000 0~1000 25 11.7 FAILURE TABLE WSD-SENSOR(OPTION) ,, WARNING - Observe the general safety precautions for installation, maintenance and repair. Problem There is no input signal when a pump is started. Input signal remains active. Nothing responds 26 Pumping Technology Possible cause Shut-off valve to the WSD Sensor is closed. Pump is operating against the maximum pressure of the unit and does not deliver. Possible solution Open the shut-off valve. Adjust the switch-on pressure of the pump to at least 80 kPa below the maximum pressure of the unit. Pressure in the membrane Adjust the air pressure switch vessel(s) is too in the membrane switch high. vessel to the correct values. Pressure in the membrane Adjust the air pressure switch vessel(s) is in the membrane switch too low, or there is no vessel to the correct pressure at all. values. Reed contact on the WSD Replace the reed contact. Sensor defective. Magnet in the WS Replace / clean the Sensor is stuck. interior of the WSD-Sensor. Magnet in the WSD Replace / clean the Sensor is stuck. interior of the WSD-Sensor. Short circuit on the input signal. Reed contact defective. Replace the reed contact. There is no voltage on the Fuse defective. booster set. Checkpoints Shut-off valve should always be opened. Adjust the pressure set point. Make sure maintenance is performed regularly. Check if the membrane switch vessel is not leaking, if so, replace the membrane switch vessel. Adjust the reed contact. Deposits / dirt. Deposits / dirt. Check the wiring. Check the correct voltage. 11.8 SMEDEGAARD - GAARDEXE -SURGE PROTECTION MODULE. NORMAL Operation Control Buttons When operating normally, if you press and hold any of the Buttons, the Controller will respond as follows… DOWN Button. Pressing the left most (DOWN) Button will cause the Controller to jump into its HISTORY LOG. The last 32 ERROR EVENTS are stored here along with a TIME and DATE STAMP. If multiple errors occurred simultaneously (eng WATER LOW and PRESSURE LOW, then they will scroll in sequence so you can see what the state of the Controller was at any point in time. Using the UP and DOWN Buttons, you can scroll through the logged 32 events. The latest event is numbered 1 and the oldest is number 32. Pressing the SET Button will exit the HISTORY LOG back into normal operation (as will no activity from the operator whilst continuously displaying the log for about 50 Seconds). UP Button. Pressing the centre (UP) Button will cause the Controller to MUTE the ALARM audible BEEPER. If the Alarm BEEPER is running continuously and giving folks a headache, press this Button to toggle the BEEPER ON or OFF. SET Button The SET Button has a dual function. Press and release within a Second or so will cause the Controller to prompt ‘ENTER PIN:’ in order to access the SETUPs. Press and hold this Button for FIVE SECONDS or so, and the Controller will switch OFF and display ‘STANDBY MODE’ (see ‘Initial POWER-ON section). For booster sets fitted with the GaardExe module, for the warranty to be validated, the set must be commissioned by Smedegaard. 27 Pumping Technology SETUP Options - USER SETUP (Entered through pressing the Return Key) Standby Mode : If set to NO (Factory Default) will allow the Controller to start operating as soon as Power is applied. If set to YES, will cause a ‘STANDBY MODE’ message to appear on the LCD and the unit will remain in this mode until manually switched ON by a User (think of it as an ON/ OFF Button on your VCR). Press and hold the SET Button for at least FIVE SECONDS to switch ON. Similarly, to switch INTO Standby Mode, press and hold the SET Button for at least FIVE SECONDS (pressing for less than this time will cause the ‘Enter PIN’ message - for entry into the SET-UP Menu to appear). Caution: In STANDBY MODE the equipment remains LIVE - Don’t try to change the Control Panel or any Pumps without completely isolating the equipment at the wall. Set Pressure : This is the Operational Pressure the equipment is intended to run at. Integral Pressure : This is the Pressure setting (in Bar) up to which the ACTUAL Pressure needs to rise before direct control is transferred to the Pumps. (Factory Default is 0.2 Bar below the Set Pressure). Integral Time : This is a slope pre-set by the Commissioning Engineer to allow the system to drop from the Operational Pressure (Set Pressure) to Zero. It is adjustable in MINUTES from 0 to 240 (Factory Default is 30) Integral Sequence : The time interval to elapse before a further Pump would be sequenced in. (Factory Default = 0 - All Pumps Enabled). Number of Pumps : The Number of Pumps in the installation. Cross-Over Action : The action to be taken once the Actual Pressure and the Integral Pressure is equal. If TRANSFER is the selected option, the actual Transducer is connected to the lead (Master) Pump. Only WATER-LOW continues to be monitored. If SIMULATE is the selected transfer option, then the unit will continue to provide a Simulated Pressure Signal reflecting the ACTUAL Transducer Input, and PRESSURE-LOW, PRESSURE-HIGH and WATER-LOW will continue to be monitored 28 Pressure-Low Alarm ON : The value at which the Pressure LOW Alarm activates. Zero is Disabled. (Factory Default = 0) Pressure-Low Alarm OFF : The value at which the Pressure LOW Alarm deactivates. (Factory Default = 0) Pressure-High Alarm ON : The value at which the Pressure HIGH Alarm activates. (Factory Default = 2 Bar above the Set Pressure) Pressure-High Alarm OFF : The value at which the Pressure HIGH Alarm deactivates. (Factory Default = 1 Bar above the Set Pressure) Pumping Technology Stop on Pressure High : A YES/NO option that will shut-down the Pumps if a Pressure High Alarm is activated. (Factory Default = YES) Water Low Mode : Enables setting of Alarm on Make or Alarm on Break type connections. These should be volt free type. If no Switch/Sensor is to be fitted, then select Alarm on Make and leave the Water Low terminals unconnected or set to Disabled. (Factory Default – Alarm on Break). Water Low Reset : Starts a Timer (0-60 minutes) to prevent Pumps from immediately restarting following reset from a Water-Low Alarm. Allows the Water Tank time to refill in order to prevent continually switching the Pumps whilst emptying small amounts of water from the bottom of a tank. (Factory Default - 0). Leak Alarm : Flags an Alarm if pumps have run for equal to or more than the total cumulative preset time (in MINUTES) during the initial GAARD INTEGRAL MODE. (Factory Default - 0/ Disabled). Stop on LEAK : A YES/NO option that will shut-down the Pumps if a Leak Alarm is activated. (Factory Default - No) VOLT-FREE Relay : Sets all the conditions that will enable the VOLT-FREE Relay. By default the User will ‘Skip Sub-Menu’ if SET is simply pressed, however by using the UP and DOWN Buttons to change this to ‘Configure’ and then pressing SET, the User can then enable or disable all the multiple options that will trip this Relay. The FAILSAFE option reverses the operation of the STOP Relay (ie so it is normally ON and drops out on Alarm, rather than normally OFF and switching ON for Alarm ). Failsafe allows for the provision of signaling an Alarm on PowerFailure. Naturally the NC/NO contacts as marked on the PCB operate in reverse if the Failsafe setting option is used. Factory Defaults : Pressure Low - ON Pressure High - ON Water Low - ON Water Leak - OFF Service Due - OFF System Fault - ON Failsafe - OFF 29 Pumping Technology BEEPER : This option sets all the conditions that will enable the BEEPER. Factory Defaults : Pressure Low - ON Pressure High - ON Water Low - ON Water Leak - ON Service Due - ON System Fault - ON Key Press - ON ALARM LED : This option sets all the conditions that will cause the Status LED to blink RED. Factory Defaults : Pressure Low - ON Pressure High - ON Water Low - ON Water Leak - ON Service Due - ON System Fault - ON Key Press - ON Erase History : Allows the History/Event Log to be Erased. Set Contrast : Changes the LCD (Display) Contrast Ratio for User comfort. Set Date & Time : Allows setting of the System Date and Time which is only used for History/ Event Logging. User PIN : Allows entry/setting of the User PIN code. *Please note that any or all settings may be changed from Default at Commissioning. 30 Pumping Technology 11.9 DECLARATION OF CONFORMITY (IIA) Factory declaration (2.1) according to EN 10204 Undersigned: Smedegaard Pumps Ltd 10 Beech Business Park Bristol Road Bridgwater Somerset UK Tel. +44 (0)1278 458 686 Fax +44 (0)1278 452 454 Declares as manufacturer entirely on his own responsibility, that the products: Product: Flex Booster Sets Type: ExeFlex/FlowFlex/FalFlex to which this declaration refers, is in accordance with the following standard: EN-809, EN-ISO-12100-1 EN-IEC-61000-6-1/3, EN-IEC-61000-3-2 EN 1010, EN-IEC-60204-1 according to the provisions of (when applicable): Machine directive 98/37/EC EMC directive 89/336/EEC Low voltage directive 73/23/EEC If the installation is used as a stand-alone product, it is subject to this declaration of conformity. If the installation is built in an appliance or is assembled together with other equipment in certain installations, then it should not be put into operation until a declaration has been given with respect to the appliance concerned that it complies with the directives listed above. Bridgwater Somerset, 18-01-2011 55 Responsible person: C.K.Barrett, UK Director It is Smedegaard’s policy to continually improve and develop its product range. We reserve the right to change specifications without prior notice. Whilst every care has been taken to ensure the data is correct, no responsibility can be taken for inaccuracies or misprints. Pumping Technology Smedegaard Pumps Ltd United Kingdom Tel. +44 (0)1278 458 686 Fax +44 (0)1278 452 454 info@smedegaard.co.uk www.smedegaard.co.uk T. Smedegaard A/S Denmark Tel. +45 43 96 10 28 Fax +45 43 63 17 66 info@smedegaard.dk www.smedegaard.dk FR 18/01/2011